Calculation
FOUR STOREY W/ ROOFDECK RESIDENTIAL BUILDING
Beam Design
Beam Mark Label B -1
Design Parameters
F'c = 20 MPa
Fy = 414 MPa
Fy (secondary) = 227 MPa
Rebar Diameter (Main) = 16 mm
Rebar Diameter (Stirrups) = 10 mm
Concrete Density = 24 kN/m3
Wu 28.38 kN/m
Max. Moment 58.1878688 kN-m
Beam Type
T-Beams
L-Beams
= 9.14 kN/m
= 3.8 kN/m
2 layers brad
1 layer' 0.058
2 layer d' 0.0785
- - assumption is correct
Engineering Report Structural
PROPOSED
Calculation
FOUR STOREY W/ ROOFDECK RESIDENTIAL BUILDING
- - - - - Stirrups is Needed
- - - - - Vs Limits is Okay
= 148.25
74.125
157.0796327 Av
227 fy
e at Balance Condition) 296.5 d
26.90143835 Vs
Beam Pass For Ductillity Requirement 393.002154 spacing
Engineering Report Structural
PROPOSED
Calculation
FOUR STOREY W/ ROOFDECK RESIDENTIAL BUILDING
201.0619
Engineering Report Structural
PROPOSED
Calculation
FOUR STOREY W/ ROOFDECK RESIDENTIAL BUILDING
Beam Design
Beam Mark Label B -2
Design Parameters
F'c = 20 MPa
Fy = 414 MPa
Fy (secondary) = 227 MPa
Rebar Diameter (Main) = 16 mm
Rebar Diameter (Stirrups) = 10 mm
Concrete Density = 24 kN/m3
Wu 31.579 kN/m
Max. Moment 64.7468 kN-m
Beam Type
T-Beams
L-Beams
11.425 kN/m
4.75 kN/m
2 layers brad
1 layer' 0.058
2 layer d' 0.0785
1.418604651
mption is correct
Engineering Report Structural
PROPOSED
Calculation
FOUR STOREY W/ ROOFDECK RESIDENTIAL BUILDING
- Stirrups is Needed
- Vs Limits is Okay
135.75
67.875
157.0796327 Av
227 fy
ance Condition) 271.5 d
39.73136581 Vs
ass For Ductillity Requirement 243.6587846 spacing