CHAPTER IV – DESIGN CRITERIA AND PARAMETERS || 2
DEAD LOAD
All data presented here are taken from NSCP 2001 & 2010 Code and ASCE 7-98 specifications.
USE - refers to the values used by the designer in the calculation of dead loads.
LIVE LOAD
CHAPTER IV – DESIGN CRITERIA AND PARAMETERS || 4
The data presented here are taken from NSCP 2010 and ASCE 7-98 specifications:
MINIMUM USE
Use or occupancy DESCRIPTION UNIFORM CONCENTRATED UNIFORM CONCENTRATED
(kPA) (kN) (kPA) (kN)
SPECIAL LOADS
CHAPTER IV – DESIGN CRITERIA AND PARAMETERS || 5
Note 10: The mounting of handrails shall be such that the completed handrail and supporting
structure are capable of withstanding a load of at least 890 N applied in any direction at any point
on the rail.
CHAPTER IV – DESIGN CRITERIA AND PARAMETERS || 7
WIND LOAD
All data presented here are parameters used for the calculation of windload.
Occupancy category: special occupancy structure. III
Basic Wind Speed: V=290 kph Reference:
From Table 207-1, wind zone for the different provinces of the Philippines of the NSCP
2010, Surigao del Sur is located at zone 2 having V=290 kph.
Reference:
Table 207.4 of 2010 NSCP Code
Topographic Factor, Kzt = (1+𝐾1𝐾2𝐾3)2
Gust Effect Factor: G = 0.85
Reference:
For rigid structure, from Structural Theory by Aslam Kassimali
CHAPTER IV – DESIGN CRITERIA AND PARAMETERS || 8
SEISMIC LOAD
PROPERTIES OF MATERIALS
Concrete: fc’ = 21 MPa based on 28 days curing strength (for beams and footing) fc’
= 27.6 MPa based on 28 days curing strength (for column)
PRELIMINARY DESIGN
CHAPTER IV – DESIGN CRITERIA AND PARAMETERS || 10
The design of structural element such as footing, column, beam and slab shown in this
sheet are only preliminary dimension assumed by the designer for the purpose of determination
of preliminary dead load carried by the beam for framework analysis. In addition, it also used for
the computation for structural details. The dimension shown can be change once there is failure,
to carry the desired loading occurs or even for economic reasons.
Slab Dimension:
Roof Deck
Concrete slab thickness = 150mm
Bituminous surface (Asphalt) = 10mm
Note: Asphalt is used as coating for concrete only as adsorbent to water.
Beam Dimension:
Column Dimension:
Footing Dimension:
Iw
= 2.01 ( 𝑍
𝑍𝑔
) 2/ᾳ
where: Z𝑔 = 365cm
m
Kz6.1 = 2.01 (
6.1
365)
2/7
= 0.624
Kz3.1 = 2.01 (
3.1
365)
2/7
= 0.515
qz6.1 = 47.3x10-6
(0.624)(1.0)(0.85)(2002
CHAPTER IV – DESIGN CRITERIA AND PARAMETERS || 15
)(1.0) = 1.004
qz3.1 = 47.3x10-6
(0.515)(1.0)(0.85)(2002
)(1.0) = 0.828
P = qGCp – qh (GCpi)
P = qGCp – qh (GCpi)
q = qh
P = qGCp – qh (GCpi)