You are on page 1of 28

FILLER BOARD

STRUCTURAL JOINT
SEISMIC
FIRE PROTECTION
PU FOAM VERTICAL
VEDAFEU
CERTIFIED HORIZONTAL
TESTED ROPE
MATTRESS FIRESTOP SYSTEMS
ACOUSTIC UP TO 840 MM

BLANKET
CLASSIFICATION REPORTS
MOVEMENT

PERFORMANCE

ROPE MATTRESS BLANKET FILLER BOARD PU FOAM


GV2 VEDA FRANCE
20, ALLEE DES ERABLES
BATIMENT E
95700 ROISSY CHARLES DE GAULLE
FRANCE

Bureau Veritas Certification France certifiy that the Management System of the above
organization has been audited and found to be in accordance with the requirements of the
management system standard detailed below

Standard

ISO 9001:2015
Scope of certification

DESIGN AND SUPPLY OF EXPANSION JOINT FOR ALL TYPES OF


BUILDING.

DEVELOPPEMENT ET COMMERCIALISATION DE JOINTS DE DILATATION


DESTINES A TOUT TYPE DE BATIMENT.

Certification cycle start date: 09 September 2016


Subject to the continued satisfactory operation of the organization’s Management System,
this certificate expires on : 08 September 2019

Original certification date: 09 September 2013

Certificate No. : FR030385-2 Date: 30 September 2016


Contract No. : 6359821

Jacques Matillon - Managing Director


Local office: Bureau Veritas Certification France
60, avenue du Général de Gaulle – 92046 Paris La Défense

Further clarifications regarding the scope of this certificate the applicability of the
management system requirements may be obtained by consulting the organization.
To check this certificate validity, please call + 33(0) 1 41 97 00 60.

© All rights reserved - Non contractual drawings - 02/2017


3
WHO ARE WE ?

A s a building joints specialist, we have developed a know-how recognized by all professionals: architects, engineers,
consultants, general contractors and subcontractors.
We design, manufacture and market a full range of standard and seismic joints: joint covers, expansion joints, control
joints, firestop systems, stair nosings, etc.

JOINT COVERS AND FIRESTOP SYSTEMS EXPANSION JOINTS


COMPRESSION PROFILES Tested and approved
Official certifications (EN, UL, BS…)

►Clip affixed joint covers are manufactured in ► VEDAFEU C© Rope ►All-metal type or with flexible rubber
aluminium, PVC and brass. They are available For joint widths up to 150 mm. insert, suitable for horizontal and vertical
in any RAL colour and also in wood, gold, silver, applications. We provide a wide range,
bronze and brass aspects. ►VEDAFEU M© Mattress adapted to all types of public or private
For joint widths up to 450 mm. buildings, factories, shops, offices...
►Drilled and countersunk extruded joint
covers are produced for floors, walls and ►VEDAFEU N© Blanket
For joint widths up to 840 mm. ►At the cutting edge of innovation we
facades for gaps up to 320 mm wide.
always develop new products, amongst
►Folded joint covers are available in stainless ►VEDAFEU FB© Filler board which an extra-large seismic joint, for joint
steel, galvanized steel or aluminium (mill finish, For joint widths up to 100 mm. widths up to 280 mm, specifically created for
anodized or powder coated). flexible floors for hospitals, daycare centres
►Compression profiles are designed to close ►VEDAFEU PU© Foam
and schools.
expansion joints up to 100 mm wide. For joint widths up to 40 mm.

w
ww

Applications Guarantees Specification


Schools, hospitals, shopping centres, Regular tests and inspections conducted by A specification tool, available online at
industrial and residential buildings, airports, official laboratories (CSTB, Efectis, TÜV, UL) www.vedafrance.com enables you with just a
railway stations, leisure centres, car parks… enable us to ensure conformity to the highest few clicks, to choose the products
For new buildings or renovation projects. standards (ISO 9001:2015, official classification that fit your needs.
reports, patents and registered models).

Our premises are ideally located


only minutes from
Paris
Roissy Charles de Gaulle airport hub,
25kms north of Paris.
VEDA FRANCE BUILDING JOINTS

j Clip affixed joints covers j Floor joints covers j Compression profiles

j Vertical expansion joints j Mechanical floor joints j Carpark expansion joints

Surface mounted all metal Heavy duty


j Embedded all metal
expansion joints j expansion joints j expansion joints

Wide movement Special resilient flooring


j expansion joints j expansion joints j Control joints

j Roof expansion joints j Stair nosings j Waterstops

© All rights reserved - Non contractual drawings - 02/2017


5
INDEX
06 WHAT IS AN
EXPANSION JOINT ?

EXPANSION JOINTS AND


FIRESTOP LOCATION 07
08 VEDAFEU RANGE

VEDAFEU STRENGTHS 09
10 EUROPEAN REGULATIONS

INTERNATIONAL APPROVALS 11
12 HOW TO READ A
CLASSIFICATION REPORT ?

VEDAFEU C© ROPE 14
18 NAPPES VEDAFEU
VEDAFEU N
M© MATTRESS

VEDAFEU N© BLANKET 20
22 VEDAFEU FB© FILLER BOARD

VEDAFEU PU© EXPANDING FOAM 26


WHAT IS AN EXPANSION JOINT ?
An expansion joint is an empty space, free of any material
between two parts of a structure designed to safely absorb
thermal expansion and contraction of building structures,
to absorb vibration or to allow horizontal, vertical or shear
movement due to soil settlement or seismic activity.

CAUSES OF MOVEMENT

Concrete shrinkage Expansion and contraction Settlement


of the structure of the structure

Environment
(wind, train vibration...)
© All rights reserved - Non contractual drawings - 02/2017
Earthquakes
7
EXPANSION JOINTS AND
FIRESTOP LOCATIONS

1
3
2

7
6

‘‘
1 – Joint de passerelle
u - Linking bridge
2 – Joint entre plancher et mur rideau
v - Curtain wall
3 – Joint de façade extérieure
wtoiture
4 – Joint de - Facade
5 – Joint étanche circulable
x - Roof
6 – Joint en tête de maçonnerie
y - Driveway
7 – Joint pour charges lourdes
z - Head of wall
 - Loading bay

‘‘
A solution to any configuration
VEDAFEU RANGE

VEDAFEU C© firestop rope VEDAFEU M© firestop mattress VEDAFEU N© firestop blanket

VEDAFEU FB© firestop filler board VEDAFEU PU© firestop foam

10 120 144
RESULTS
©
VEDAFEU C Rope
Joint width (mm)
40 100 300 450 Movement (mm)
©
VEDAFEU M Mattress

40 150 560 840


©
VEDAFEU N Blanket

0 10 40 100 120 144 150 300 450 560 840


Joint width (mm)

RECOMMENDATIONS

0 10
‘‘
VEDAFEU C Rope
©

120
©
VEDAFEU M Mattress

450
©
VEDAFEU N Blanket

840 Joint width (mm)

‘‘
VEDAFEU FB© filler board and VEDAFEU PU© foam are not shown in this chart due to their specific use

VEDAFEU the best firestop


solutions
© All rights reserved - Non contractual drawings - 02/2017
9
VEDAFEU STRENGTHS
FOR GAPS FROM 10 TO 840 MM

FIRESTOP up to 240 MINUTES (EI 240)

EXPANSION MOVEMENT up to + 275%

COMPRESSIBILITY up to 95%

NOT EXPOSED or EXPOSED to FIRE

HORIZONTAL or VERTICAL POSITION

WITHOUT or WITH JUNCTION

ALL KINDS of BUILDINGS

SAFE FOR THE HEALTH


EASY TO INSTALL AND FOR THE ENVIRONMENT
EUROPEAN REGULATIONS
Definitions

Reaction to fire Resistance to fire


Product’s tendency to produce smoke, Duration for which a fire protection
flames or burning droplets. It is defined by system helps to limit fire spread.
the Euroclass sytem classification.

European Classification Standard EN 13501-2 (May 2004)

Fire resistance classification for special building components and systems. This standard details the test
procedures : position of the samples, movement capacity, junction types, joint width, etc.

European Test Method Standard EN 1366-4 (Novembre 2006) + A1 extension (June 2010)

Fire resistance testing of construction systems, part 4 : Expansion joint fillers. This standard details a test
method for fire-resistant joint filler according to their final use, with or without movement during the
tests. This standard was approved by the CEN (European Committee for Standardization) in April 2006.

‘‘ All our fire resistance tests were made at CSTB and Efectis France,
two of the leading official Laboratories in Europe.

‘‘
Complying with the latest standards is
making sure everyone stays safe

© All rights reserved - Non contractual drawings - 02/2017


11
INTERNATIONAL APPROVALS
DATE : 2015-11-10
‫ﺑﺴﻢ ﺍﻟﻠﻪ ﺍﻟﺮﺣﻤﻦ ﺍﻟﺮﺣﻴﻢ‬
: ‫ﺍﻟﺘﺎﺭﻳـــــــﺦ‬
PERMIT # PAC150032
36 : ‫ﺭﻗﻢ ﺍﻟﻄﻠﺐ‬ ‫ﻭﺯﺍﺭﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
‫ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‬

‫ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬
TECHNICAL REPO
RT
PRODUCT :
Gap Seals, Penet
ration seals, Smoke ‫ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻲ‬
PRODUCT APPL Putty, Wraps, sealan seals, Fire pillows,
ICATION : ts etc.
Fire Rated and Retard : ‫ﺍﻟﻤﻨﺘﺞ‬
APPLICANT / P.O ant materials
.Box : ‫ﺗﺼﻨﻴﻒ ﺍﻟﻤﻌﺪﺓ‬
MANUFACTURER ‫ﺍﻟﻤﻨﺎﺯﻝ ﺍﻟﻘﻄﺮﻳﺔ ﻟﻠﺘﻄﻮﻳﺮ‬
/
LOCATION : GV2 INTERNATIO : ‫ﻣﻘﺪﻡ ﺍﻟﻄﻠﺐ‬
NAL VEDA FRAN
CE / FRANCE
PRODUCT / MOD :‫ ﺑﻠﺪ ﺍﻟﺼﻨﻊ‬/ ‫ﺍﻟﺸﺮﻛﺔ ﺍﻟﻤﺼﻨﻌﺔ‬
EL :
‫ﺍﻟﻮﺻﻒ‬
Fire Barrier Backe ‫ﺍﻟﻤﻮﺩﻳﻞ‬ : ‫ﻗﺎﺋﻤﺔ ﺍﻟﻤﻨﺘﺠﺎﺕ‬
r Rods
System consists
of
and rotproof minera a core of fireproof VEDAFEU C
l an outer braidin
fiberglass thread g of
.
3RD PARTY
CERTIFICATE /
APPROVAL : EFR-15-003538
- EFR-1501-0008
- EFECTIS ‫ﺷﻬﺎﺩﺓ ﺍﻟﻤﺨﺘﺒﺮﺍﺕ ﺍﻟﻤﺴﺎﻧﺪﺓ‬
RECOMMENDAT : ( ‫)ﻣﻦ ﻫﻴﺌﺎﺕ ﻣﻌﺘﻤﺪﺓ‬
IONS

NOTES / STANDARD ‫ﺍﻟﺘﻮﺻﻴﺎﺕ‬


S
Tested to Standard
EN 1366-4

/‫ﻉ‬

‫ﻣﺪﻳﺮ ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬


‫ﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‬
‫ﺍ‬

Page 2 of 2

itters
Underwtrories Civil Defense Civil Defense
Labora United Arab Emirates Qatar

BS 476
Part 20

ile) TÜV (Singapore) Bomba (M Tecnalia (Spain)


h alaysia)
Idiem (C
HOW TO READ A CLASSIFICATION REPORT ?
Fire resistance according to standard EN 13501-2.
EI : E = firestop integrity I = thermal insulation. EI expressed in minutes.
H or V : H = horizontal construction support. V = vertical construction support.
M or X : M = movement. X = no movement. M and X expressed in percentage.
B or F : junction type. B = factory and on-site manufactured. F = on-site manufactured.
W = tested joint width. Expressed in millimeters.

Fireproofing Horizontal Movement Initial approved


& Thermal
insulation support of joint
in minutes H +50 % 560 mm

EI 240 - H - M50 - B - W 560


EI 240 - V - M20 - B - W 20 to 120 mm

Vertical Movement VALID for width


240 Junction
support of from
minutes type
V +20 % 20 to 120 mm

Understanding a classification
EXAMPLE
Failed after Tested
60 minutes WITHOUT
ONLY MOVEMENT

E 60 - H - X - F - W 60

VALID for a
NO «I» HORIZONTAL gap of 60 mm
NO THERMAL SUPPORT ONLY.
INSULATION ONLY Not valid for
a range

© All rights reserved - Non contractual drawings - 02/2017


13
HOW TO READ A CLASSIFICATION REPORT ? (CONTINUED)
E or EI classification
An E classification
does not validate
+ an EI classification.
Joint fillers
must have an

+ = EI
E = Smoke, gas and I = thermal EI classification.
firestop insulation

Position : horizontal or vertical


A test carried out in
horizontal position
does not
validate a
vertical configuration.
Horizontal position Vertical position

Without movement or with movement


A test carried out
without
movement does not
validate a
configuration
Without movement With movement with movement.

Without junction or with junction


A test carried out
without
junction does not
validate a
configuration with
junction.
Without junction With junction

Exposure to fire
A test carried out from
Firestop not Fire the non exposed
exposed to fire exposed to fire
side to fire
does not validate
a configuration
exposed to fire.
‘‘
VEDAFEU C ROPE ©

‘‘
The most
extensive range in
firestop systems

firestop 4 HrS MOVEMENT JOINT WIDTH


EI 240 + 20 % 10 to 120 mm
TESTed d VEDAFEU C© ROPE STRENGTHS
e
certifi

POSITIONS
Tested and certified for
horizontal and vertical applications. Horizontal position

Vertical position

EXPOSURE
Tested and certified
not exposed or exposed to fire.
Not exposed to fire Exposed to fire

COMPRESSIBILITY
Tested and certified up to - 80% compression.
Initial joint With compression

EXPANSION MOVEMENT
Tested and certified up to + 20% expansion.
Initial joint With movement

APPLICATIONS
Hospitals, industrial buildings, offices, housing, hotels,
malls, carparks, schools, train stations, airports, stadiums, etc.

© All rights reserved - Non contractual drawings - 02/2017


15
OFFICIAL CLASSIFICATION
Classification report n° RS14-077 dated 17/03/2015

EI 240 – H – M20 – B – W 10 to 120


EI 240 – V – M20 – B – W 10 to 120

Rope diameter according to initial joint width


with movement (M) + 20% according to mentioned above report.

Initial joint width


10 20 40 60 80 100 120
[mm]

ø rope 12 30 60 90 120 150 180


VEDAFEU C© [mm]

Other VEDAFEU C ropes ø : 20, 40, 50, 70, 80, 100 and 170 mm.
©

A colour system has been thought to easily identify different diameters and prevent misuse.
©
VEDAFEU C has also been tested and approved with movement of +7,5% with lower compression rate.

CERTIFIED CONFIGURATIONS
ED ED
CERTIFI CERTIFI

NO WITH
sealant joint
NO cover
joint NO
cover sealant

ED ED
CERTIFI CERTIFI

WITH WITH
waterproofing
sealant
NO membrane
joint NO
cover joint cover
©
VEDAFEU C PROPERTIES
VEDAFEU C© firestop rope COMPRESSIBILITY tests
Immediate After 2 hours After 72 hours
Load F (kN) and
Ref. Test Compressibility form form form
VEDAFEU C©
recovery recovery recovery
1 F = 4 kN 69 % 83 % 88 % 90 %
VEDAFEU C©
2 F = 50 kN 83% 78 % 84 % 86 %
Ø 60
3 F = 5 kN 70% 76 % 87 % 91 %
AVERAGE 74% 79 % 86 % 89 %
1 F = 30 kN 81% 55 % 69 % 74 %
VEDAFEU C©
2 F = 30 kN 80% 62 % 69 % 71 %
Ø 100
3 F = 30 kN 85 % 57 % 62 % 63 %
AVERAGE 82 % 58 % 67 % 69 %
1 F = 100 kN 86 % 54 % 55 % 72 %
VEDAFEU C©
2 F = 100 kN 88 % 56 % 57 % 67 %
Ø 150
3 F = 100 kN 88 % 68 % 71 % 81 %
AVERAGE 87 % 59 % 61 % 73 %

VEDAFEU C© AIR and SMOKE tightness


Nominal pressure (Pa) 50 100 150 200 250
Permeability (m /h) 3
0.0 0.0 0.0 0.0 0.0
Results of test report n° 16-26061937 dated 22/03/2016.

VEDAFEU C© THERMAL Properties


In accordance with the Thermal Regulation RT 2012
Thermal resistance at 30 50 60 70 90 120 180 mm ASTM
average temperature 0,70 1,23 1,84 1,77 2,47 3,46 5,55 m2.K/W D5930

The thermal value (Lambda) of VEDAFEU C© firestop rope is about 0.040 W/mK at 20°C.
Results of test report n° RA.15.36.EB-V2 dated 25/10/2015 (available upon request).

VEDAFEU C© ACOUSTICAL Properties


In accordance with the NRA (New Acoustical Regulation 2012)
30 60 90 120 150 180 mm
Sound attenuation (dB) depending EN ISO
on diameter of rope (mm) 34 36 40 40 40 40 dB 717 - 1

Results of test report n° BEB2.F.6023 dated 09/07/2015 (available upon request).

© All rights reserved - Non contractual drawings - 02/2017


17
©
VEDAFEU C ROPE
Installation instructions for
joint width from 10 to 120 mm
If necessary, remove formwork material such as polystyrene, honeycomb cardboard, etc.
The contact surfaces must be clean, dry and free from contamination. Remove dust, using a brush or a broom.

*
Apply a layer of VEDACOLLE While the adhesive is still wet, Linking of 2 lengths VEDAFEU C © with junction.
adhesive with a brush on both sides insert VEDAFEU C © by hands into (patented).
of the joint. the joint.

For installation accessories, please refer to the concerned classification report.

EXAMPLES OF APPLICATION
j Expansion joint
k Head of wall

Application on floor, wall, ceiling with junctions. A single rope Double rope

l Curtain wall
m Other possible
applications

Windows and doors frames,


bearing protection ...

Application on curtain wall.


‘‘
VEDAFEU M© MATTRESS 100%
PATENTED

‘‘
Solutions for standard
or seismic joints

firestop 2 HrS MOVEMENT JOINT WIDTH


EI 120 SEISMIC up to + 275% 40 to 450 mm

TESTed d
certifi
e VEDAFEU M© MATTRESS STRENGTHS
POSITIONS
Tested and certified for
horizontal and vertical applications. Horizontal position Vertical position

COMPRESSIBILITY
Tested and certified up to - 95%.
Initial joint With compression

EXPANSION MOVEMENT
Tested and certified up to + 50%.
Initial joint With movement

EASY to handle and to install.

SAFE HANDLING for the health and the environment.

APPLICATIONS
Hospitals, industrial buildings, offices, housing, hotels,
malls, carparks, schools, train stations, airports, stadiums, etc.

© All rights reserved - Non contractual drawings - 02/2017


19
OFFICIAL CLASSIFICATION
Classification report n° EFR-15-000543 dated 01/03/2016

EI 120 – H – M40 – B – W 40 to 300


EI 120 – V – M50 – B – W 40 to 300

Installation instructions for


joint width from 150 to 300 mm
If necessary, remove formwork material such as polystyrene, honeycomb cardboard, etc.
The contact surfaces must be clean, dry and free from contamination. Remove dust, using a brush or a broom.

Apply the glue on both sides of the joint Apply the glue on the underside of the wings Insert the mattress into the joint.
and on a width of 5 cm on the upper side and on the vertical side of the mattress
of the concrete slab. on a width of 6 cm.

Fix the wings of the mattress to the slab Mattress after installation. Application on floor and wall with junctions.
every 20 cm using a pneumatic nailer.

For installation accessories, please refer to the concerned classification report.


‘‘ VEDAFEU N BLANKET ©

100%
PATENTED

‘‘
Veda France, always
ahead in terms of fire
protection

firestop UP TO MOVEMENT JOINT WIDTH


4 HrS EI 240 SEISMIC + 50% 150 to 840 mm

TESTed d
certifi
e VEDAFEU N© BLANKET STRENGTHS
COMPRESSIBILITY
Tested and certified up to - 75% compression.
Initial joint With compression

EXPANSION MOVEMENT
Tested and certified up to + 50% expansion.
Initial joint With movement

EASY to handle and to install.

SAFE HANDLING for the health and the environment.

APPLICATIONS
Hospitals, industrial buildings, offices, housing, hotels,
malls, carparks, schools, train stations, airports, stadiums, etc.

© All rights reserved - Non contractual drawings - 02/2017


21
OFFICIAL CLASSIFICATION
Initial Maximum
Ref. Official classification Joint cover
gap [mm] gap [mm]
N 150 EI 180 150 225 EI 180 - H - M50 - B - W 150 compulsory
N 150 EI 240 150 225 EI 240 - V - M50 - B - W 150 compulsory
N 200 EI 180 200 300 EI 180 - H - M50 - B - W 200 compulsory
N 400 EI 60 400 600 EI 60 - H - M50 - B - W 400 optional
N 400 EI 120 400 600 EI 120 - H - M50 - B - W 400 compulsory
N 560 EI 240 560 840 EI 240 - H - M50 - B - W 560 compulsory

©
VEDAFEU N BLANKET
Installation instructions for
joint width from 150 to 560 mm

If necessary, remove formwork material such as polystyrene, honeycomb cardboard, etc.

Make sure that the joint edges Flatten the blanket against the Keep the pressure on the flange
©
VEDAFEU N blanket after
are straight and clean concrete with the flange. while fixing with pneumatic nailer. installation.
to get a good contact
between the blanket and
its supports.

Joint cover affixed with Detail. Application on floor and wall


Section.
VEDAFLEX SIL sealant or screws
with junctions.
and plugs.
For installation accessories, please refer to the concerned classification report.
‘‘VEDAFEU FB FILLER BOARD ©

‘‘
All-in-one PRODUCT :
formwork, fire barrier, acoustic
and thermal insulation 100%
PATENTED

firestop 4 HrS MOVEMENT JOINT WIDTH


EI 240 UP TO + 20 % 20 to 60 mm
TESTed d
CERTIFI
e VEDAFEU FB© FILLER BOARD STRENGTHS
EXPOSURE
Tested and certified
not exposed or exposed to fire.
Not exposed to fire Exposed to fire

COMPRESSIBILITY
Tested and certified up to - 60%.
initial joint With compression

EXPANSION MOVEMENT
Tested and certified up to + 20%.
initial joint With movement

EASY to handle and to install. It is a substitute to materials


(honeycomb cardboard, polystyrene ...) used to realize
the expansion joint while pouring the concrete.

APPLICATIONS
Hospitals, industrial buildings, offices, housing, hotels,
malls, carparks, schools, train stations, airports, stadiums...

© All rights reserved - Non contractual drawings - 02/2017


23
OFFICIAL CLASSIFICATION
HORIZONTAL
Classification Report n° 12-F-148 dated 01/03/2012
EI 240 – H – M20 – B – W 20 to 40 EI 240 – H – M15 – B – W 20 to 60

VERTICAL
Classification Report n° 13-F-131441 dated 16/04/2014
EI 240 – V – M20 – B – W 20 EI 240 – V – M7,5 – B – W 20 to 60

‘‘
‘‘
Firestop up to 4 hours from
a height of 140 mm
VEDAFEU FB© PROPERTIES
VEDAFEU FB© filler board COMPRESSIBILITY tests
Load F (kN) and Immediate After 2 hours
Ref. Test VEDAFEU FB© Compressibility form form
thickness Ec to F (mm) recovery recovery
1 F = 7.4 kN - Ec = 7 mm 64 % 88 % 96 %
2 F = 5.7 kN - Ec = 7 mm 67 % 82 % 91 %
VEDAFEU FB©
20 3 F = 8,4 kN - Ec = 6 mm 70 % 81 % 93 %
4 F = 9,0 kN - Ec = 8 mm 63 % 85 % 98 %
5 F = 8,8 kN - Ec = 7 mm 65 % 81 % 95 %
AVERAGE 66% 83 % 95 %
1 F = 11,1 kN - Ec = 17 mm 58 % 91 % 94 %
2 F = 11.4 kN - Ec = 18 mm 55 % 93 % 97 %
VEDAFEU FB©
3 F = 12.9 kN - Ec = 19 mm 54 % 92 % 95 %
40
4 F = 11,1 kN - Ec = 15 mm 60 % 92 % 98 %
5 F = 11,3 kN - Ec = 18 mm 55 % 91 % 94 %
AVERAGE 56 % 92 % 96 %
1 F = 8,0 kN - Ec = 25 mm 59 % 93 % 96 %
2 F = 6,7 kN - Ec = 22 mm 63 % 89 % 97 %
VEDAFEU FB©
3 F = 9,2 kN - Ec = 27 mm 55 % 93 % 97 %
60
4 F = 7.3 kN - Ec = 23 mm 62 % 89 % 98 %
5 F = 6,1 kN - Ec = 19 mm 68 % 88 % 97 %
AVERAGE 62 % 90 % 97 %
Results of test report n° EEM 13 26043939/A dated 25/02/2013 (available upon request).

VEDAFEU FB© THERMAL Properties


In accordance with the Thermal Regulation RT 2012
Thickness 20 40 60 100 140 200 mm
ISO 8301
Thermal resistance Thermal
0.51 1.02 1.53 2.56 3.59 5.12 m2.K/W EN 12667
resistance
The thermal resistance R (m² K/W) is calculated by the ratio of the thickness of insulation on Lambda (0.039).
Results of test report n° RA.15.36.EB-V2 dated 25/10/2015 (available upon request).

VEDAFEU FB© ACOUSTICAL Properties


In accordance with the NRA (New Acoustical Regulation 2012)
Sound attenuation (dB) 20x140 20x200 40x140 40x200 60x140 60x200 mm
EN ISO
depending on dimension of
37 43 36 40 35 38 dB 717-1
fillerboard (mm)
Results of test report n° BEB2.F.6023 dated 09/07/2015 (available upon request).

© All rights reserved - Non contractual drawings - 02/2017


25
©
VEDAFEU FB FILLER BOARD
Installation instructions for
joint width from 20 to 60 mm

v v

Side
A u
eA
Sid u

1. Attach the anchoring springs to the upper 2. Install the VEDAFEU FB© filler board along 3. Concrete slab sideupoured.
part of the VEDAFEU FB© filler board on the wooden formwork.
Side A according to the fig. 1.

100%
u PATENTED
Side B

v
v
4. Attach the anchoring springs to the lower 5. Concrete slab sidevpoured.
part of the VEDAFEU FB© filler boards on
Side B according to the fig. 2.

75

Fig. 1
300

‘‘ 300

Side
FaceA

1200
A
300 205

20
30

205
Fig. 2
300
1200

Side B
Face B

300 300 75
20

30

‘‘
Patented junction system.
No risk of gas or fire leak
‘‘ VEDAFEU PU EXPANDING FOAM ©

‘‘
The quickest and easiest
firestop solution

firestop FROM HANDLING JOINT WIDTH


EI 120 TO EI 240 EASY 10 to 40 mm
OFFICIAL CLASSIFICATION
Classification report n° EFR-14-F-003505 dated 21/05/2015

EI 240 – V – X – W 10 to 20
EI 180 – V – X – W 10 to 30
EI 120 – V – X – W 10 to 40

TECHNICAL DATA
Volume Approx 30 L (free foamed), can of 750 ml
Density 24 kg/m3
Tack free time 10 - 15 min 18°C/60% RH
Cutting time 1 hour ø=3 cm, 18°C/60% RH
Hardening time 24 hours
Thermal conductivity 0,029 W/(m K) at 20°C DIN 52612
Fire reaction B s1 d0 EN 13501-1

© All rights reserved - Non contractual drawings - 02/2017


27
GV2 - VEDA FRANCE
A specification tool

u r w e b s i t e
Vi s i t o e . c o m
v e d a f r a n c
www.

GV2 - VEDA FRANCE - CS 63052 - 95972 Roissy CDG Cedex - France


Tél : + 33 (0)1 48 61 70 80 - Fax : + 33 (0)1 48 61 70 81
Web : www.vedafrance.com - E-mail : export@vedafrance.com
GV2 - VEDA FRANCE - CS 63052 - 95972 Roissy CDG Cedex - France
Tél : + 33 (0)1 48 61 70 80 - Fax : + 33 (0)1 48 61 70 81 - Web : www.vedafrance.com - E-mail : export@vedafrance.com

You might also like