Ref: MDCG/MF/01/7002 02 April 2022

Mr. Chen Yongjian


Authorized Representative CGGC-DESCON JV
Patti Banda, Tehsil Pindiayali,
District Mohmand, Khyber Pakhtunkhwa

Dear Mr. Chen,

MOHMAND DAM HYDROPOWER PROJECT


PROJECT COLONY – SUBMISSION OF SHOP DRAWINGS LT PANEL DESIGN FOR
JUNIOR OFFICERS’ & STAFF HOSTEL BUILDINGS 1 & 2

1. CDJV-MDHP-MDCG-2022-4406 dated: 04 March 2022

We refer to your letter ref. (1).


We have reviewed the Shop Drawings of the Main Panel Boards (MPB) of Junior Officers’ and
Staff Hostel Buildings 1 & 2.
The Engineer has marked-up the submittal with comments in red text.
The submittal is “Approved Except as Noted” (AEN).
The Contractor is required to incorporate the Engineer’s comments and resubmit to the
Engineer for review.

Yours sincerely,

Mark Fox
Project Manager / Construction Manager
Mohmand Dam Consultants Group (MDCG)
IA

Attachments: 1. Marked up Shop Drawings – 7 pages

Copy to: 1. General Manager / PD (MDHP)


2. Mirza Asif Baig, Zafar Ahmad, Sergio Gomes, Dr. Shahzad Rahman, M. Irfan
Akhtar, Saleem Cheema, Khawaja Muhammad, Shiraz Shakeel.

Page 1 of 8
SHT. No. TITLE

PROJECT : MOHMAND DAM HYDROPOWER PROJECT


1 TITLE SHEET

2 FRONT VIEW AND SIDE VIEW PAKISTAN


CLIENT /
3 INTERNAL & DEAD VIEW : WATER AND POWER DEVELOPMENT AUTHORITY
EMPLOYER
(WAPDA)
4 SINGLE LINE DIAGRAM
CONSULTANT /
5 CONTROL DIAGRAM : MDCG (MOHMAND DAM CONSULTANTS GROUP)
ENGINEER
6 MATERIAL SHEET

7 MATERIAL SHEET
MAIN CONTRACTOR : CGGC - DESCON Joint Venture

PANEL BUILDER : ERCON INDUSTRY PVT. LTD.

1) Refer to our comments on the attached drawing


sheets. ERCON JOB No. : PK1561D-01

2) The contractor is required to only use that "Drawing REVISION DATE DESCRIPTION DESIGNED CHECKED APPROVED
Panel" which is approved by WAPDA/MDCG. The
present drawing panel is not acepted. R00-D00 25-02-2022 FIRST ISSUE SHERAZ SHERAZ MURAD

THE EMPLOYER: PAKISTAN


WATER AND POWER DEVELOPMENT AUTHORITY
(WAPDA)

THE ENGINEER:

THE CONTRACTOR:
PANEL NAME MPB-1&2 (JUNIOR OFFICER AND STAFF HOSTEL)
CGGC - DESCON
DESCON
Joint Venture
DESIGNATION TITLE SHEET

SHEET No. 1 PANEL MANUFACTURE :

ERCON
REFERENCE NO PK1561D-01 ERCON
Industry (pvt) Ltd.
SCALE ALL DIMENSIONS ARE IN mm www.erconme.com
1) As per contract document volume, 2A clause no. 2) As per contract document volume 2A, clause no. 3) Regarding the clearance between bare metal bus
14.3.2.1, the switching lever of the Main incoming Air 14.4.2 all openable doors shall be grounded with the bar in the panel, as per NEC(USA), the minimum
LV NETWORK PARAMETERS circuit breaker/Moulded case circuit breaker of LV use of flexible copper Cable/strap of at least 10mm2 distance between live part to ground should be
VOLTAGE SYSTEM (415V) switchboard (which are floor mounted) shall be cross-sectional area. Contractor to indicate it in the 12.7mm. Contractor to confirm it. (Typical)
400 VAC 3Ø, 230VAC 1Ø, 50Hz
accessible from the outside of the panel doors while drawing and confirm it.
these doors are in closed position. In this drawing 4) Indicate the name of the change over panel in which
CONTROL VOLTAGE interlocking has been provided as shown in the Single
such a switching lever is missing and contractor is
230VAC required toFRONT
provide. (Typical)
VIEW line diagram.
2400 SIDE VIEW
SHORT CIRCUIT
700 300 400 300 700 300
5) Provide a drawing wherein MPB- Junior Staff Hostel is
50KA
ERCON ERCON
located on a concrete foundation. It shall be indicated as to
how much are the dimensions i.e. length x breadth x height
Distributing Power Distributing Power

PANEL GENERAL PROPERTIES


SUPPLY AVAILABLE SUPPLY AVAILABLE

CABLE ENTERY & EXIT


R-PHASE Y-PHASE B-PHASE R-PHASE Y-PHASE B-PHASE

of the concrete foundation. It shall not be accepted that the


CABLE BOTTOM
A V A V

Main Panel Board is simply put on the Finished Floor


ASS
R Y
VSS
L1N
0
L12
ASS
R Y
VSS
L1N
0
L12 without concrete foundation.
INCOMMING
L2N L23 L2N L23

B L3N L31 B L3N L31

OUTGOING

ENCLOSURE MOUNTING

1150

1150
1200
1200
FLOOR STANDING
KEY LOCK KEY LOCK KEY LOCK

ENCLOSURE SPECIFICATIONS
COLOR ACCESS
RAL 7035 FRONT DB-1 DB-2
IP (INGRESS PROTECTION)
IP44
SHEET THICKNESS

50
50

THE EMPLOYER:
2mm/14SWG PAKISTAN
WATER AND POWER DEVELOPMENT AUTHORITY
ENCLOSURE ACCESSORIES (WAPDA)
BLIND DOOR ( 14 SWG )
TOM VIEW
BLIND PLATE (16 SWG) THE ENGINEER:
700 300 400 300 700
KEY LOCK
METERING
300

96x48
DRAWING PURPOSE
THE CONTRACTOR:
FOR APPROVAL
CGGC - DESCON
QUANTITY DESCON
Joint Venture
01
-------------------
PANEL MANUFACTURE :

NOTES:-
ERCON
Industry (pvt) Ltd.
1- DOOR EARTHING SHALL BE PROVIDED WITH www.erconme.com
BRAIDED COPPER CONDUCTOR
2- COPPER BUSBAR SHALL BE TIN COATED PROJECT:
3- RUBBER GASKET SHALL BE PROVIDED FOR DOOR
MOHMAND DAM HYDROPOWER PROJECT

ALL INTER CONNECTION WITH BUSBAR


* THROUGH COPPER/CABLE REVISION DATE DESCRIPTION DESIGNED CHECKED APPROVED PANEL NAME
MPB-1&2 (JUNIOR
OFFICER AND STAFF HOSTEL)

SHERAZ
FRONT VIEW AND SIDE VIEW
R00-D00 25-02-2022 AS PER COMMENTS SHERAZ MURAD DESIGNATION GENERAL SPECIFICATION

SHEET No. 2

ERCON PK1561D-01
REFERENCE NO

SCALE ALL DIMENSIONS ARE IN mm


1) All relevant comments given on other drawing
sheets are applicable on this drawing sheet as well.

DEAD FRONT VIEW INTERNAL VIEW


2400 2400
700 300 400 300 700 700 300 400 300 700

CONTROL

UVT INTERLOCKING

CABLE CONNECTION

CABLE CONNECTION
160AT

160AT
CT=3 CT=3

Q1.1 Q1.2 Q1.3 Q1.4 Q2.1 Q2.2 Q2.3 Q2.4

400AT/400AF
1150

1150
100A 100A 100A 80A 100A 100A 63A 63A

400AT/400AF
1200

1200
Q01.1
Q02.1

ELECTRICAL ELECTRICAL
INTERLOCK INTERLOCK

Q01 COUPLER BREAKERS Q02

Q1.5 Q1.6 SPACE SPACE


63A 63A
O/G O/G
I/C I/C THE EMPLOYER:
PAKISTAN
N N
WATER AND POWER DEVELOPMENT AUTHORITY
E E (WAPDA)
50

50
THE ENGINEER:

BOTTOM VIEW BOTTOM VIEW


700 300 400 300 700 700 300 400 300 700

THE CONTRACTOR:
300

G.L.P G.L.P G.L.P G.L.P


300

G.L.P G.L.P G.L.P G.L.P


CGGC - DESCON
DESCON
Joint Venture

PANEL MANUFACTURE :

ERCON
Industry (pvt) Ltd.
www.erconme.com

PROJECT:
MOHMAND DAM HYDROPOWER PROJECT

REVISION DATE DESCRIPTION DESIGNED CHECKED APPROVED


MPB-1&2 (JUNIOR
PANEL NAME
OFFICER AND STAFF HOSTEL)

SHERAZ
INTERNAL & DEAD VIEW
R00-D00 25-02-2022 AS PER COMMENTS SHERAZ MURAD DESIGNATION GENERAL SPECIFICATION

SHEET No. 3

ERCON PK1561D-01
REFERENCE NO

SCALE ALL DIMENSIONS ARE IN mm


1) Refer to our issued IFC drawings
wherein these CBs are shown enclosed
in a change over panel (Steel Box). So
Contractor shall also indicate the 3) Indicate the size of incoming cable from
change over panel in single line 200kVA distribution transformer up to MPB.
diagram accrodingly. Presently, such a
box is missing.
T1 200 KVA T2 200 KVA
4) On sheet no 2, the short circuit is indicated
2) Indicate the symbols of transformer T1 & as 50kA. So make it 50kA in lieu of 36kA
T2 in black color. which you have indicated. (Typical)

ELECTRICAL
400V, 3ph + N+ P.E, 50Hz, 50kA FOR 1sec. INTERLOCKING 3.5 CORE 70mm² Cu/PVC CABLE 400V, 3ph + N+ P.E, 50Hz, 50kA FOR 1sec.

Q01.1
R Y B MCB 25KA R Y B MCB 5) Indicate the ampere rating
160AT/160AF
of this busbar as well.
6A 6A
V VSS
MCCB V VSS
MCCB
350AT/400AF 350AT/400AF
RC:50KA Q02.1 RC:50KA
25KA
160AT/160AF
800A MAIN BUSBAR A ASS CTs 400/5 A A ASS CTs 400/5 A
CLASS - 0.5 CLASS - 0.5
400V, 3ph + N+ P.E, 50Hz, 36kA FOR 1sec.
TP MCCB

TP MCCB

TP MCCB

TP MCCB

TP MCCB

TP MCCB

TP MCCB

TP MCCB

TP MCCB

TP MCCB

TP MCCB

TP MCCB
THE EMPLOYER:
100A 100A 100A 80A 63A 63A 100A 100A 63A 63A PAKISTAN
36KA 36KA 36KA 36KA 36KA 36KA 36KA 36KA 36KA 36KA WATER AND POWER DEVELOPMENT AUTHORITY
Q1.1 Q1.2 Q1.3 Q1.4 Q1.5 Q1.6 Q2.1 Q2.2 Q2.3 Q2.4 (WAPDA)
3.5C 35mm²

3.5C 35mm²

3.5C 35mm²

3.5C 25mm²

3.5C 25mm²

3.5C 25mm²

3.5C 35mm²

3.5C 35mm²

3.5C 25mm²

3.5C 25mm²
+1C 16mm²

+1C 16mm²

+1C 16mm²

+1C 16mm²

+1C 16mm²

+1C 16mm²

+1C 16mm²

+1C 16mm²

+1C 16mm²

+1C 16mm²
THE ENGINEER:

OUTGOING OUTGOING OUTGOING OUTGOING OUTGOING OUTGOING SPACE OUTGOING OUTGOING OUTGOING OUTGOING SPACE THE CONTRACTOR:
CGGC - DESCON
DESCON
Joint Venture
MAIN PANEL BOAR DB-1 MAIN PANEL BOAR DB-2

PANEL MANUFACTURE :
8) Contractor shall follow all the ampere ratings and
3.5C, 35mm2 Cu/PVC/PVC+
1C, 16mm2 CU/PVC (CPC) interrupting ratings of all MCCBs and MCBs as well ERCON
as cable sizes of incoming and outgoing circuits as Industry (pvt) Ltd.
www.erconme.com
per the issued IFC drawing, (Engineer's letter no;
6292). Contractor to confirm it. (Typical). In case PROJECT:
6) Each Main Panel Board is feeding Sub some change from IFC drawing is necessary, then MOHMAND DAM HYDROPOWER PROJECT
DB's. The contractor shall Indicate the names the contractor shall clarify it in detail. (Typical).
of outgoing circuits as mentioned in the
MPB-1&2 (JUNIOR
issued IFC drawing. Further, indicate spare REVISION DATE DESCRIPTION DESIGNED CHECKED APPROVED PANEL NAME
OFFICER AND STAFF HOSTEL)
circuit breakers in the single line diagram.
R00-D00 25-02-2022 AS PER COMMENTS SHERAZ SHERAZ MURAD DESIGNATION SINGLE LINE DIAGRAM
7) Contractor shall provide 20% spare MCBs.
SHEET No. 4
As per practice being followed in MDHP
regarding indoor DBs etc, it shall be 20% ERCON PK1561D-01
(refer to VOL-2C, Clause 12.4.1). (Typical) REFERENCE NO

SCALE ALL DIMENSIONS ARE IN mm


1) All relevant comments given on other drawing
sheets are applicable on this drawing sheet as well.
CONTROL DIAGRAM
2) Provide a list of legends.
(Typical).

THE EMPLOYER:
PAKISTAN
WATER AND POWER DEVELOPMENT AUTHORITY
(WAPDA)

YU YU YU YU
THE ENGINEER:
VOLTAGE COIL

VOLTAGE COIL

VOLTAGE COIL

VOLTAGE COIL
UNDER

UNDER

UNDER

UNDER
THE CONTRACTOR:
CGGC - DESCON
INCOMING SUPPLY 01 INCOMING SUPPLY 02 DESCON
Joint Venture

PANEL MANUFACTURE :

ERCON
Industry (pvt) Ltd.
www.erconme.com

PROJECT:
MOHMAND DAM HYDROPOWER PROJECT

REVISION DATE DESCRIPTION DESIGNED CHECKED APPROVED


MPB-1&2 (JUNIOR
PANEL NAME
OFFICER AND STAFF HOSTEL)

SHERAZ
FRONT VIEW AND
R00-D00 25-02-2022 AS PER COMMENTS SHERAZ MURAD DESIGNATION GENERAL SPECIFICATION

SHEET No. 5

ERCON PK1561D-01
REFERENCE NO

SCALE ALL DIMENSIONS ARE IN mm


1) 6A MCB is not acceptable.
2) Regarding C.Ts, submit calclation to 3) Provide catalog cuts of all equipment
Provide minimum rating of 10A.
(Typical).
MATERIAL SHEET prove that 5VA is adequate. Also which is indicated on this sheet.
indicate kA rating of the C.Ts. (Typical). (Typical).

4) For any equipment or device etc.


where kA matters (e.g. CTs, MCCB,
MCBs, voltmeter, ammeter etc.) then its
rated kA shall be indicated here in this
table. (Typical).

THE EMPLOYER:
PAKISTAN
WATER AND POWER DEVELOPMENT AUTHORITY
(WAPDA)

THE ENGINEER:

THE CONTRACTOR:
CGGC - DESCON
DESCON
Joint Venture

PANEL MANUFACTURE :

ERCON
Industry (pvt) Ltd.
www.erconme.com

PROJECT:
MOHMAND DAM HYDROPOWER PROJECT

REVISION DATE DESCRIPTION DESIGNED CHECKED APPROVED


MPB-1&2 (JUNIOR
PANEL NAME
OFFICER AND STAFF HOSTEL)

R00-D00 25-02-2022 AS PER COMMENTS SHERAZ SHERAZ MURAD DESIGNATION MATERIAL SHEET

SHEET No. 6

ERCON
REFERENCE NO PK1561D-01

SCALE ALL DIMENSIONS ARE IN mm


1) 6A MCB is not acceptable.
MATERIAL SHEET Provide minimum rating of 10A.
2) All relevant comments given on other drawing
sheets are applicable on this drawing sheet as well.
(Typical).

THE EMPLOYER:
PAKISTAN
WATER AND POWER DEVELOPMENT AUTHORITY
(WAPDA)

THE ENGINEER:

THE CONTRACTOR:
CGGC - DESCON
DESCON
Joint Venture

PANEL MANUFACTURE :

ERCON
Industry (pvt) Ltd.
www.erconme.com

PROJECT:
MOHMAND DAM HYDROPOWER PROJECT

REVISION DATE DESCRIPTION DESIGNED CHECKED APPROVED


MPB-1&2 (JUNIOR
PANEL NAME
OFFICER AND STAFF HOSTEL)

R00-D00 25-02-2022 AS PER COMMENTS SHERAZ SHERAZ MURAD DESIGNATION MATERIAL SHEET

SHEET No. 7

ERCON
REFERENCE NO PK1561D-01

SCALE ALL DIMENSIONS ARE IN mm