FIRE PROTECTION

DESIGN COURSE

AYMAN QURANY
MECHANICAL ENGINEER
aymmhas@yahoo.com
01004334635
FOURTH LECTURE CONTENTS

 Revision on Hydraulic Calculation Method.

1. Fire Elite Hydraulic Calculation program & Example.

2. Calculation of Fire Water Tank Capacity.

3. Introduction to Fire Alarm System.

27-Jul-15 2
1. FIRE ELITE SOFTWARE
HYDRAULIC CALCULATION

27-Jul-15 3
1. INSIDE& OUTSIDE
HOSE STREAM ALLOWANCE

27-Jul-15 4
(2&4)DEFAULT K-FACTOR&
SPRINKLER SIZE

27-Jul-15 5
3. TEMPERATURE RATING

27-Jul-15 6
(5&7)MINIMUM DESIRED DENSIT Y&
AREA OF SPRINKLER OPERATION

27-Jul-15 7
(8)MAXIMUM AREA PER SPRINKLER

27-Jul-15 8
MINIMUM OPERATING PRESSURE
FOR SPRINKLER

27-Jul-15 9
WATER VELOCIT Y THROUGH PIPES

 FOR PUMP SUCTION& DISCHARGE LINE:


 V Suction = 10ft/sec = 3 m/s
 V Discharge = 13.33ft/sec = 4 m/s

 FOR NET WORK VELOCIT Y NOT TO EXCEED 2.5m/s(8.2ft/sec)

27-Jul-15 10
HYDRAULIC JUNCTION POINT
(NODE PRESSURE)

27-Jul-15 11
DAMPING FACTOR

27-Jul-15 12
2. CALCULATION OF FIRE
WATER TANK CAPACIT Y
 After determination of pump capacity, according to occupancy
hazard type the amount of firefighting water tank shall be
calculated.

 The fire pumps should operate for a specific minimum


duration according to the type and hazard of the occupancy.

 Fire water tank should be calculated according to the highest


hazard at the project being designed.

27-Jul-15 13
EXAMPLE

 Calculated pump capacity=750 gpm.


 Hazard Type= Ordinary Hazard. (60-90 minutes).
Or 30 Minutes(NFPA -14)
 Fire Water Tank Capacity=750*30=22,500 gallons= 85m 3

Fire water tank should consist of ( 2 compartments) of 85m 3


water reserve for firefighting purposes.

27-Jul-15 14
MINIMUM WATER SUPPLY TIME

27-Jul-15 15
WATER TANK

27-Jul-15 16
27-Jul-15 17