(TR-541-2)
Standards Guideline
For
3 Acknowledgement 6
4 Foreword 7
5 Working group 7
6 Purpose 7
7 Scope 7
1|Page
Classification: Restricted - مقيدة
1. Amendment Page
To ensure that each copy of this technical document (Abu Dhabi Guideline) contains a
complete record of amendments, the Amendment Page is updated and issued with each set of
revised/new pages of the document. This ADG/ISGL is a live document which can be amended
when necessary. QCC operates TR-541/1 and 2 Standard Drawings Group which prepared this
document and can review stakeholder comments in order to review and amend this document
and issue an updated version when necessary.
1 Geometric Details
2022
02 Part 1 GM-0 Revised As marked up on the drawing
(January)
Part 1 GM-1 Revised As marked up on the drawing
Part 1 GM-1a New drawing
Part 1 GM-2 Revised As marked up on the drawing
Part 1 GM-3 Revised As marked up on the drawing
Part 1 GM-4 Revised As marked up on the drawing
Part 1 GM-4a Revised As marked up on the drawing
Part 1 GM-5 Revised As marked up on the drawing
Part 1 GM-6 Revised As marked up on the drawing
Part 1 GM-7 Revised As marked up on the drawing
Part 1 GM-7a New drawing
Part 1 GM-8 Revised As marked up on the drawing
Part 1 GM-9 Revised As marked up on the drawing
Part 1 GM-9a New drawing
Part 1 GM-10 Drawing retained, content replaced
Part 1 GM-10a New drawing
Part 1 GM-11 Revised As marked up on the drawing
Part 1 GM-12 Revised As marked up on the drawing
Part 1 GM-12a New drawing
Part 1 GM-12b New drawing
Part 1 GM-12c New drawing
Part 1 GM-12b New drawing
Part 1 GM-13 Revised As marked up on the drawing
Part 1 GM-14 Revised As marked up on the drawing
Part 1 GM-15 Revised As marked up on the drawing
Part 1 GM-16 Revised As marked up on the drawing
Part 1 GM-17 Revised As marked up on the drawing
Part 1 GM-17a New drawing
Part 1 GM-18 Revised As marked up on the drawing
2|Page
Classification: Restricted - مقيدة
Part 1 GM-19 Revised As marked up on the drawing
Part 1 GM-20 Revised As marked up on the drawing
Part 1 GM-21 Removed (transferred to TR-520)
Part 1 GM-22 Revised As marked up on the drawing
Part 1 GM-23 Revised As marked up on the drawing
Part 1 GM-24 Revised As marked up on the drawing
2 Traffic
2022
02 Part 1 TF-1 Revised As marked up on the drawing
(January)
Part 1 TF-1A New drawing
Part 1 TF-2 Revised As marked up on the drawing
Part 1 TF-5 Revised As marked up on the drawing
Part 1 TF-6 Revised As marked up on the drawing
Part 1 TF-7 Revised As marked up on the drawing
Part 1 TF-8 Revised As marked up on the drawing
Part 1 TF-13 Revised As marked up on the drawing
Part 1 TF-14 Revised As marked up on the drawing
Part 1 TF-15 Revised As marked up on the drawing
Part 1 TF-21 Revised As marked up on the drawing
Part 1 TF-22 Revised As marked up on the drawing
Part 1 TF-23 Revised As marked up on the drawing
5 Lighting
2022
02 Part 1 27 drawings Removed (transferred to PR-402)
(January)
6 Civil Works
2022
02 Part 2 C-1 Revised As marked up on the drawing
(January)
Part 2 C-2 Revised As marked up on the drawing
Part 2 C-3 Revised As marked up on the drawing
Part 2 C-4 Revised As marked up on the drawing
Part 2 C-5 Revised As marked up on the drawing
Part 2 C-7 Revised As marked up on the drawing
Part 2 C-8 Revised As marked up on the drawing
Part 2 C-9 Revised As marked up on the drawing
Part 2 C-10 Revised As marked up on the drawing
3|Page
Classification: Restricted - مقيدة
Part 2 C-11 Revised As marked up on the drawing
Part 2 C-12 Revised As marked up on the drawing
Part 2 C-13 Revised As marked up on the drawing
Part 2 C-16 Revised As marked up on the drawing
Part 2 C-21 Revised As marked up on the drawing
Part 2 C-22 Revised As marked up on the drawing
Part 2 C-23 Revised As marked up on the drawing
Part 2 C-24 Revised As marked up on the drawing
Part 2 C-25 Revised As marked up on the drawing
Part 2 C-26 Revised As marked up on the drawing
Part 2 C-27 Revised As marked up on the drawing
Part 2 C-28 Deleted
Part 2 C-29 Deleted
Part 2 C-30 Deleted
Part 2 C-31 Deleted
Part 2 C-32 Deleted
Part 2 C-33 Deleted
Part 2 C-34 Deleted
Part 2 C-35 Deleted
Part 2 C-36 Removed (transferred to TR-520)
Part 2 C-37 Removed (transferred to TR-520)
Part 2 C-38 Removed (transferred to TR-520)
Part 2 C-44 Deleted
7 Structures
2022
02 Part 2 ST-02 Revised As marked up on the drawing
(January)
Part 2 ST-03 Revised As marked up on the drawing
Part 2 ST-06 Revised As marked up on the drawing
Part 2 ST-08 Revised As marked up on the drawing
Part 2 ST-12 Revised As marked up on the drawing
Part 2 ST-16 Revised As marked up on the drawing
Part 2 ST-20 Revised As marked up on the drawing
4|Page
Classification: Restricted - مقيدة
2. About the Abu Dhabi Quality and Conformity Council
Abu Dhabi Quality and Conformity Council (QCC) is an Abu Dhabi
government entity established in accordance with Local Law No. (3) of
2009 to raise the quality of Abu Dhabi’s exports and products traded
locally. QCC consists of a council of regulators and industry with a
mandate to ensure provision of quality infrastructure in line with global
standards.
o QCC’s functions are divided into six key areas:
• Developing standards and specifications
• Capacity building of metrology systems
• Strengthening testing infrastructure
• Launching conformity schemes
• Protecting consumer interests
• Ensuring fair trade
5|Page
Classification: Restricted - مقيدة
3. Acknowledgement
QCC would like to thank the members of the Working Group listed below.
6|Page
Classification: Restricted - مقيدة
4. Foreword
Several technical circulars were issued for cost saving and updating some standards. All issued
technical circulars will be inserted in the amended version of the TR-541/1 and 2 Standard Drawings
manual.
5. Working Group
The Professional Working Group was organized by Abu Dhabi Quality and Conformity Council and
established in April 2021, which was requested by Abu Dhabi Municipality, to prepare the TR-541/1
and 2 Standard Drawings Manual in cooperation with the related stakeholders including
representatives from government and private sectors in order to establish operating procedures
and technical guidelines for the relevant Authorities, Project Developers, Planners, Engineers etc.,
a step-by-step guidance on how to prepare the standard drawings aspect of a planning application
for new development in the Emirate of Abu Dhabi at the Inception, Planning & Design stages of
the Project.
6. Purpose
The purpose of updating this manual is to gather and insert all issued technical circulars into the
amended version and to design as per the international best practices with a unified approach for
all users.
7. Scope
TR-541 is a compiled set of technical drawings that standardize infrastructure design details in the
emirate of Abu Dhabi. The current amendment provides information for the disciplines of Road
Geometric Design, Road and Traffic Safety, Public Realm, Structures, Materials Design, and
selected aspects of Transportation (such as Parking Design Standards and Cycle Tracks). Although
TR-541 was devised in alignment with other QCC-approved standards and manuals, these
drawings should still be read in conjunction with the aforementioned.
The following drawings / drawing sets were removed in the current amendment and transferred
to be included into more relevant documents:
• Drawing Set 3 of Part 1 (Traffic Control Systems), which included drawings TCS-00 to TCS-
52, is now removed from this document. The drawings will be transferred to the latest
version of QCC document TR-529 (Traffic Signals and Electronic Warning Information
Systems Manual).
7|Page
Classification: Restricted - مقيدة
• Drawing Set 4 of Part 1 (Work Zone Traffic Management), which included drawings TM-1
to TM-8, is now removed from this document. The drawings will be transferred to the
latest version of QCC document TR-531 (Work Zone Traffic Management Manual).
• Drawing Set 5 of Part 1 (Lighting), which included drawings L-01 to L-27, is now removed
from this document. The drawings will be transferred to the latest version of QCC
document PR-402 (Lighting Manual).
• The details in GM-21 (Part 1) Traffic Calming Measures for Rural Roads – Sheet 2 of 2 is
being transferred to QCC document TR-528 (Traffic Calming Guidelines).
• The details previously provided in drawings C-36, C-37, C-38 (Part 2) will be updated and
included in the latest version of QCC document TR-520 (Technical Circular – Bus Stop
Design Standard Drawings).
• The bus lay-by details previously provided in drawings GM-11 (Part 1) will be updated and
included in the latest version of QCC document TR-520 (Technical Circular – Bus Stop
Design Standard Drawings).
The following drawings have been identified as outdated and removed from this amendment:
8|Page
Classification: Restricted - مقيدة
New drawings as listed below have been provided in this amendment in order to accommodate
new details, to serve as an extension of an existing drawings, or to re-organize information:
• GM-1a, Part 1 (Typical Roundabout Layout Characteristics – Urban Roads)
• GM-7a, Part 1 (Motorcycle and LEV Parking Design Standards)
• GM-9a, Part 1 (Typical Driveway / Plot Access Interface Details)
• GM-17a, Part 1 (Tactile Specifications)
• GM-10, Part 1 (Basement Parking Design Standards – 1000 sq.m. or more – Sheet 2 of 2)
• GM-10A, Part 1 (Basement Parking Design Standards – 1000 sq.m. or more – Sheet 1 of 2)
• GM-12A, Part 1 (School Bus Drop-Off / Pick-Up and Parking Design Standards - Large
School Buses – Sheet 1 of 2)
• GM-12B, Part 1 (School Bus Drop-Off / Pick-Up and Parking Design Standards - Large
School Buses – Sheet 2 of 2)
• GM-12C, Part 1 (School Bus Drop-Off / Pick-Up and Parking Design Standards - Small
School Buses – Sheet 1 of 2)
• GM-12D, Part 1 (School Bus Drop-Off / Pick-Up and Parking Design Standards - Small
School Buses – Sheet 2 of 2)
• TF-1A, Part 1 (Sign Details – Sheet 2 of 6)
• C1-A, Part 2 (Roadway Details – Kerb and Wheel Stop Details – Sheet 2 of 2)
The remaining drawings have either been amended (as marked) or retained as is. Further
information for revised drawings has been provided in the Amendments page.
9|Page
Classification: Restricted - مقيدة
STANDARD DRAWINGS (TR-541)
Second Edition
January 2022
PO Box 20
© Copyright 2022, by the Department of Municipalities and Transport. All Rights Reserved. This manual, or parts thereof, may not be reproduced in any form without written permission of the publisher
LIST OF DRAWINGS
PART 1 PART 2
TITLE
STANDARD DRAWINGS
DRAWING TITLE
CIVIL WORKS
KERB TYPE F (FLUSH KERB) ROADWAY DETAILS
KERB AND WHEEL STOP DETAILS
Sheet 1 of 2
20000.23
KERB TYPE J (ROLLED KERB) KERB TYPE J1 (ROLLED KERB)
PLAN VIEW
A
Sheet 2 of 2
C C
KERB TYPE D
SECTION A-A AND B-B
TITLE
STANDARD DRAWINGS
DRAWING TITLE
CIVIL WORKS
ROADWAY DETAILS
PEDESTRIAN CROSSWALK, KERB,
TYPE 1 TYPE 2 TYPE 3 AND BOLLARD DETAILS
Sheet 1 of 3
KERB TYPE D WITH TYPE 1 BOLLARD
DRAWN . SCALE NTS
FOR MEDIAN CROSSING CHECKED . DATE .
SECTION C-C BOLLARD TYPES
APPROVED . SIZE A1
PROJECT DWG.
No. . No. C-2
NOTES:
PLAN
PHOTO
Sheet 2 of 3
PHOTO
1
·
14 18
2
3 ·
17
3 4 ·
6
15
5
NEW MAIN ROAD PAVEMENT CROSS SLOPE
13 7 TYPICAL SECTION
26
19 QUARRY TILES
20
CROSS SLOPES ARE TO BE AS FOLLOWS:
21
7
24
8 3 7
PEDESTRIAN PAVERS
9
25
6
OVERLAY PAVEMENT 22
23
24
1
3 2 4
CYCLE TRACK PAVEMENT CONSTRUCTION
6 13
SECTOR ROAD OR 27 11 27 18
PARKING AREA PAVEMENT 28 QUARRY TILE JOINT NOTES
12
15
23
7
11 10 7
1 2021 AMENDMENT - FINAL ISSUE JAN 2022
12
No. REVISIONS APP'D DATE
GRANITE PAVERS ON SAND BED GRANITE PAVERS ON MORTAR BED
CLIENT
13
LEGEND :
21 7
1 15
TITLE
2
3
16
17
STANDARD DRAWINGS
4 18
DETAIL A
TYPICAL LONGITUDINAL AND TRANSVERSE TRANSITION BETWEEN NEW AND EXISTING PAVEMENTS
JAN 2022
TRANSITION CONNECTION BETWEEN ASPHALT PAVEMENT 1 2021 AMENDMENT - FINAL ISSUE
TITLE
STANDARD DRAWINGS
DETAIL B DRAWING TITLE
CIVIL WORKS
TYPICAL LONGITUDINAL TRANSITION BETWEEN DIFFERENT PAVEMENT OPTIONS ROADWAY DETAILS
PAVEMENT SECTIONS
Sheet 2 of 3
LEGEND
TITLE
STANDARD DRAWINGS
DRAWING TITLE
CIVIL WORKS
ROADWAY DETAILS
PAVEMENT SECTIONS
Sheet 3 of 3
VULCAN TO PCMB
TRANSITION ANCHORED
(SEE NOTE 4) SEE SHEETS 2-3 FOR
ADDITIONAL GATE TRAFFIC
ORIENTATIONS (SEE NOTE 5)
PCMB
(SEE NOTE 4) 3 2 1 1 2 3
ELEVATION (CLOSED)
SCALE: NTS
TITLE
STANDARD DRAWINGS
DRAWING TITLE
CIVIL WORKS
CAST IN PLACE
CONCRETE BARRIER TYPE - ll
F-SHAPE PROFILE (TL-2)
CAST IN PLACE
CONCRETE BARRIER TYPE - l TYPICAL SECTION
F-SHAPE PROFILE (TL-4) DOUBLE SIDED MEDIAN BARRIER (CAST IN PLACE)
F-SHAPE PROFILE (TL-4)
TITLE
STANDARD DRAWINGS
DRAWING TITLE
JOINT DETAILS CIVIL WORKS
REFERENCE IMAGE - GOOD PRACTICE ROADWAY DETAILS
TYPICAL SECTION TYPICAL SECTION CONCERTE BARRIER DETAILS
STANDARD PRECAST MEDIAN BARRIER DOUBLE SIDED PRECAST MEDIAN BARRIER
F-SHAPE PROFILE (TL-4) F-SHAPE PROFILE (TL-4)
DRAWN . SCALE NTS
CHECKED . DATE .
APPROVED . SIZE A1
PROJECT DWG.
No. . No. C-9
NOTES:
1-1
2-2
3-3
SECTION 1-1
SECTION 2-2
3-3
CONCRETE BARRIER TRANSITION FOR BARRIER TYPE II
1 2021 AMENDMENT - FINAL ISSUE JAN 2022
1 2
610
5. EXACT OPENING,LENGTH,ETC...TO BE VERIFIED WITH
CLIENT / AUTHORITY SAFETY/ TRAFFIC CONTROL &
OPERATION BY PROVIDING SHOP DRAWINGS AND TO BE
APPROVED BY THE ENGINEER.
PLAN
SCALE: NTS
7905
PLASTIC
NOSE PIECE
813
457 457 457 457 457 457 457 457 457 457 457 457 457 457 800
REF
A
C-10
ELEVATION
SCALE: NTS
787
610
35 MAXIMUM
30 MINIMUM
WITH SPRING LOCK WASHER,
FLAT WASHER & HEX NUT
SECURING TRACC UNIT TO
CONCRETE PAD.
(32 OFF)
813
JAN 2022
(MINIMUM)
1 2021 AMENDMENT - FINAL ISSUE
150
No. REVISIONS APP'D DATE
CLIENT
TITLE
200
450
B C1773G - THRIE BEAM
C-11 RHS TRANSITION PANEL STANDARD THRIE BEAM POST TRAFFIC
A AND BLOCKING PIECE
C-11
PLAN
SCALE: NTS
ELEVATION
SCALE: NTS
W-BEAM BLOCKOUT
PIECE WIDTH VARIES BACKUP POST
4 @ 215mm PART NO. C1790G TRACC
4 @ 195mm (2 POSITIONS) BACKUP
4 @ 215mm FRAME
M16 x 50 MUSHROOM HS (12 POSITIONS) 1 2021 AMENDMENT - FINAL ISSUE JAN 2022
WITH M16 OVERSIZE NUT
PART NO. C11505 & C1520 No. REVISIONS APP'D DATE
M20 x 75 LONG
(16 POSITIONS) M16 x 30 HEX HD NUT CLIENT
HEX HD BOLT
PART NO. C1525 WITH FLAT WASHER
(32 POSITIONS)
EITHER SIDE & NUT
PART NO. C1593 & C1612
SUPPLIED BY I.C.P.
(4 POSITIONS) TITLE
2100mm POST
STANDARD DRAWINGS
(3 POSITIONS)
DRAWING TITLE
CIVIL WORKS
CRASH CUSHION DETAILS
C 100
GENERAL ARRANGEMENT
C-11
(Transition to Thriebeam Assembly)
Sheet 2 of 9
A SECTION A-A B SECTION B-B C SECTION C-C REFERENCE IMAGE - GOOD PRACTICE DRAWN . SCALE NTS
C-11 SCALE NTS C-11 SCALE NTS C-11 SCALE NTS
CHECKED . DATE .
APPROVED . SIZE A1
PROJECT DWG.
No. . No. C-13
NOTES:
610
450
TRAFFIC
PLAN
SCALE: NTS
3990
B C EXISTING OR NEW
LOWER TRANSITION RAIL
C-12 C-12 GUARDRAIL
100 4m NET LAYING LENGTH.
PART NO. C1780G
ELEVATION
SCALE: NTS
A BACKUP POST
C-12
PART NO. C1790G
VARIES VARIES (2 POSITIONS)
BLOCKOUT PIECE 230 230
(RIGHT HAND) BACKUP
BLOCKOUT PIECE
(6 POSITIONS) FRAME
(LEFT HAND)
(6 POSITIONS) 1 2021 AMENDMENT - FINAL ISSUE JAN 2022
M16 x 30 HEX HD
No. REVISIONS APP'D DATE
WITH M16 NUT
M20 x 75 LONG CLIENT
M16 x 50 MUSHROOM HD PART NO. C1525
HEX HD BOLT
WITH M16 OVERSIZE NUT (44 POSITIONS) 710
795
530
EITHER SIDE & NUT
(24 POSITIONS) PART NO. C1593 & C1612
SUPPLIED BY I.C.P. TITLE
(4 POSITIONS) STANDARD DRAWINGS
DRAWING TITLE
TRANSITION POST
1800mm LONG CIVIL WORKS
PART NO. C1785G CRASH CUSHION DETAILS
(6 POSITIONS) 100
GENERAL ARRANGEMENT
VARIES VARIES
D (Transition to Flexbeam Assembly)
R-12
Sheet 3 of 9
610
FERROUS ARTICLES.
PLAN
SCALE: NTS
PLASTIC
NOSEPIECE 6480
813
457 457 457 457 457 457 457 457 457 457 457 750 REF
A
C-15
787
ELEVATION
SCALE: NTS
610
35 MAXIMUM
30 MINIMUM
FLAT WASHER & HEX NUT
SECURING THE UNIT TO
CONCRETE PAD.
(26 OFF)
813
CLIENT
150
TITLE
200
STANDARD DRAWINGS
DRAWING TITLE
Ø19
495 CIVIL WORKS
1
C-15
CRASH CUSHION DETAILS
1220 (TL3 system)
1 DETAIL 1
C-15 SCALE NTS Sheet 4 of 9
A SECTION A-A
C-15 SCALE NTS DRAWN . SCALE NTS
CHECKED . DATE .
APPROVED . SIZE A1
PROJECT DWG.
No. . No. C-15
NOTES:
1. ALL DIMENSION ARE IN MILLIMETERS UNLESS
OTHERWISE NOTED.
PLAN
SCALE: NTS
REMOVE M16 x 50 SPLICE BOLT UPPER TRANSITION RAIL GALV. M16 x 75mm LONG M24 STUD ANCHORS (CHEMSET CAPSULES)
SUPPLIED WITH UNIT & INSTALL M16 x 3m NET LAYING LENGTH, HEX HD COACH SCREWS, SECURING UPPER & LOWER CONNECTION
65 CONNECTING BOLT (2 PLACES) 26m RADII CONVEX. WITH GALV. FLAT WASHER, BRACKETS TO BARRIER (5 POSITIONS)
(2 POSITIONS) ONCE FASTENED CUT STUD EXCESS BACK
TO 5mm ABOVE NUT.
UPPER CONNECTION
BRACKET
LOWER TRANSITION RAIL SPLICE BOLTS M16 x 32mm LONG WITH M16 LOWER CONNECTION
2m NET LAYING LENGTH. BRACKET
OVERSIZE NUTS CONNECTING UPPER &
TO INSTALL TRANSITION PANELS THE TRANSITION LOWER CONNECTION BRACKETS TO
A PANELS MUST BE PLACED BEHIND THE FENDER TRANSITION RAILS (16 POSITIONS)
C-16 PANELS OF THE SYSTEM TO INSURE PROPER TRUBOLT STUD ANCHORS M16
FUNCTION OF SYSTEM. x 150mm LONG SECURING
BACKUP FRAME TO 'F' TYPE
ELEVATION BARRIER (4 POSITIONS)
SCALE: NTS
CAST INSITU OR EXISTING
CONCRETE BARRIER (BY
OTHERS)
TITLE
STANDARD DRAWINGS
DRAWING TITLE
200
CIVIL WORKS
REFERENCE IMAGE - GOOD PRACTICE
CRASH CUSHION DETAILS
NON-REINFORCED RIGHT SHOULDER TRAFFIC
CONCRETE PAD - 32MPa
(single sided transition to concrete barrier)
(CONSTRUCTED BY OTHERS)
SECTION A-A Sheet 5 of 9
A
C-16 SCALE NTS DRAWN . SCALE NTS
CHECKED . DATE .
APPROVED . SIZE A1
PROJECT DWG.
No. . No. C-16
NOTES:
2240 MIN.
CLIENT / AUTHORITY SAFETY/ TRAFFIC CONTROL &
1334
OPERATION BY PROVIDING SHOP DRAWINGS AND TO BE
APPROVED BY THE ENGINEER.
PLAN
SCALE: NTS
6710
PLASTIC
NOSEPIECE
813
457 457 457 457 457 457 457 457 457 457 457
A ELEVATION B
C-17 SCALE: NTS C-17
610
610
TITLE
STANDARD DRAWINGS
DRAWING TITLE
200
CIVIL WORKS
CRASH CUSHION DETAILS
495 (1330mm wide system)
1220
Sheet 6 of 9
1470
2185
PLAN
SCALE: NTS
6340
813
457 457 457 461.69 452.31 457 457 457 457 457 457
A B
C-18 C-18
787
VARIES PER FRAME EXTENSION
610 ELEVATION
SCALE: NTS 610
TITLE
STANDARD DRAWINGS
DRAWING TITLE
CIVIL WORKS
CRASH CUSHION DETAILS
200
990
OPERATION BY PROVIDING SHOP DRAWINGS AND TO BE
APPROVED BY THE ENGINEER.
PLAN
SCALE: NTS
PLASTIC
NOSEPIECE 6710
813
457 457 457 457 457 457 457 457 457 457 457 686 REF.
A B
C-19 C-19
ELEVATION
SCALE: NTS
787 975
610 610
CLIENT
TITLE
STANDARD DRAWINGS
200
DRAWING TITLE
CIVIL WORKS
495
CRASH CUSHION DETAILS
1220
(990mm wide system)
Sheet 8 of 9
A SECTION A-A B SECTION B-B
C-19 C-19
DRAWN . SCALE NTS
SCALE NTS SCALE NTS
CHECKED . DATE .
APPROVED . SIZE A1
PROJECT DWG.
No. . No. C-19
NOTES:
6328mm ± WIDE DOUBLE FLARE UNIT 7066mm TEN BAY EXTENSION
1. ALL DIMENSION ARE IN MILLIMETERS UNLESS OTHERWISE
6354mm NINE BAY EXTENSION NOTED.
5649mm EIGHT BAY EXTENSION 2. EXACT OPENING, LENGTH, ETC. TO BE VERIFIED WITH
CLIENT / AUTHORITY SAFETY/ TRAFFIC CONTROL &
4943mm SEVEN BAY EXTENSION OPERATION BY PROVIDING SHOP DRAWINGS AND TO BE
APPROVED BY THE ENGINEER.
4238mm SIX BAY EXTENSION
3532mm FIVE BAY EXTENSION
2827mm FOUR BAY EXTENSION
7°
2122mm THREE BAY EXTENSION
1410mm TWO BAY EXTENSION
705mm ONE BAY EXTENSION
1823mm ±
2338mm ±
3037mm ±
2516mm ±
2688mm ±
1474mm ±
1970mm ±
1645mm ±
2167mm ±
2859mm ±
3209mm ±
WIDE
WING POST
712mm TY
P.
1423mm
2135mm
2847mm
3558mm
7°
4270mm
4982mm
5693mm
TYPICAL 6405mm
ASSEMB 7117mm
LED WIN
G EXTEN
SION STR
UCTURE
M16 x 50 BOLT
M16 NUT 203 x 58 x 6mm CHANNEL
816mm
LENGTH VARIES
PER APPLICATION
12
ADHESIVE ANCHORED
M16 x 190mm ANCHOR STUD
M16 FLAT WASHER 413mm 89mm
M16 LOCK WASHER 140mm 1 2021 AMENDMENT - FINAL ISSUE JAN 2022
M16 HEX NUT
THE EXTENSION PANELS MUST BE PLACED BEHIND THE No. REVISIONS APP'D DATE
712mm
FENDER PANELS OF THE WIDE SYSTEM TO INSURE CLIENT
PROPER FUNCTION OF SYSTEM.
A SECTION A-A
C-20 SCALE NTS
TITLE
STANDARD DRAWINGS
813mm
DRAWING TITLE
CIVIL WORKS
CRASH CUSHION DETAILS
WING EXTENSION STRUCTURES
Sheet 9 of 9
15
1 50
1 50
OTHERWISE NOTED.
0
1 1 1
NATURAL ROUNDED STONES 2 ROUNDED STONES 2 ROUNDED STONES 2 2. GUARDRAIL POSTS ARE SET INTO CLASS 25/20 TO THE
ROUND AS DETAILED ON THE DRAWINGS
100
100
100
500 500 500 3. ALL POSTS HAVE A PROTECTIVE COATING OF
GROUND LEVEL GROUND LEVEL GROUND LEVEL BITUMINOUS PAINT OVER THE LENGTH WHICH IS TO
CONCRETE CONCRETE CONCRETE PENETRATE THE GROUND. THE BITUMINOUS PAINT OF
CLASS 20/20 CLASS 20/20 CLASS 20/20
DIA. 10 @ 25
HIGH QUALITY AS PER THE APPROVAL OF THE ENGINEER.
DIA. 10 @ 25 DIA. 10 @ 25
12 DIA. 10 12 DIA. 10 12 DIA. 10 4. LOCATION OF GUARD RAILS AND PRECAST CONCRETE
800
800
800
SINGLE-SIDED BARRIER SHOULD BE SHOWN ON THE
CONCRETE LAYOUT PLANS.
CONCRETE CONCRETE
CLASS 40/20 CLASS 40/20
CLASS 40/20 5. ON CURVES LESS THAN 100M RADIUS PROPRIETARY RED
500 400 400 REFLECTORS ARE AFFIXED TO THE GUARDRAIL AT EACH
POST.
6. AS PER TR-518, RAMPED ENDS MUST NOT BE USED
EMBANKMENT HEIGHT = 6.00 to 8.00m EMBANKMENT HEIGHT = 4.00 to 6.00m EMBANKMENT HEIGHT = <4.00m WHERE THEY COULD BE STRUCK BY ERRANT VEHICLES.
C
L POST
DETAIL
REINFORCED CONCRETE TOE BEAM FOR STONE PITCHING
4500 SCALE: NTS
150
C-21
A
CLASS 25/20
785
CONCRETE NOSING
1 150 150
10 RAIL SPLICE
DIRECTION OF TRAFFIC DIRECTION OF TRAFFIC
DIA. 16 CARRIAGE
STEEL BLOCK BOLT W/HEX. NUT
350
300
1045
175
CONCRETE 3200
CLASS 25/20
SURROUND PLAN
GALVANIZED STEEL BLOCK
(EACH BLOCK
435
ATTACHED TO POST
1905 W/TWO 16DIA. HEX. BOLTS)
1830
GALVANIZED
LAP IN THE DIRECTION OF TRAFFIC FLAT PLATE WASHER STEEL POST 150x75x6
TYPICAL DETAIL FOR APPROACH END
SCALE: NTS CLASS 25/20
CONCRETE SURROUND
DIRECTION OF TRAFFIC EDGE OF HARD SHOULDER DIRECTION OF TRAFFIC BURIED PART OF POST
PROTECTED WITH
BITUMINOUS PAINT
1000
300
POST
ANCHOR END RAIL
GUARD RAIL FACE ELEVATION A SECTION A-A
FLARE LENGTH = 5000 NORMAL STRETCH C-21
SPACING = 1905
SCALE NTS
SPACING OF POSTS = 1000
TYPICAL APPROACH END (PLAN) TYPICAL PATTERN FOR STONE PITCHING METAL BEAM GUARD RAIL WITH STEEL POSTS AND BLOCKS
SCALE: NTS SCALE: (PLAN VIEW) NTS SCALE: NTS
150 75
35
83
50
75 150 75 2 81 318
50
27
51 108 108 51
250
10°
175
57 300
250
350
19x64
1830
SLOT
83
R24 23x29
39
14
310
C
L
50
19x64
310
SCALE: NTS
RAIL SPLICE BACK-UP PLATE PLACEMENT OF W-BEAM BARRIERS IN-LINE WITH KERBS CLIENT
10 GAUGE (3.4 PLATE MIN.)
6 SCALE: NTS SCALE: NTS
51 108 108
400 400
ROUNDING
STANDARD DRAWINGS
700 PRECAST FLUSH CURB
DRAWING TITLE
155 155
76
CIVIL WORKS
310
PITCHING
254
RECESS ONE 5 2
OR BOTH SIDES 38 DIA. 18 PAVEMENT
DIA. 33 1
SEMI-RIGID BARRIER AND
86
CONSTRUCTION
22
44
381
WASHER IS USED AT RAIL.
GUARDRAIL EXTRUDER
GUARDRAIL ELEMENT GUARDRAIL ELEMENT GUARDRAIL ANCHOR 5. EXACT OPENING, LENGTH, ETC. TO BE VERIFIED WITH
16Øx30 LG H.G.R. 16Øx30 LG H.G.R. DO NOT ATTACH RAIL TO 16Øx30 LG H.G.R. 10Øx40 HEX HD BOLT OBJECT MARKER
BRACKETS @ RAIL SPLICES W/WASHER, LOCKWASHER (REFER DETAIL BELOW)
SPLICE BOLTS & NUTS SPLICE BOLTS & NUTS SPLICE BOLTS & NUTS &HEX NUT
C-23
A
(AT POSTS 3,5 &7)
711
2
C-23
C-23
B
1
AFTER FINAL ASSEMBLY, RECHECK C-23
CABLE TO BE SURE IT IS TAUT AND
HAS NOT RELAXED.
BRACKETS ELEVATION
SCALE: NTS
300 300
HBA TOP1 IPE 160 BEARING PLATE 203x16x203
76
YELLOW
10Øx50 HEX HD BOLTS W/
WASHER, LOCKWASHER IMPACT ROADSIDE
UNDER HEX NUT
900
TRAFFIC SIDE FLANGE PLATE 70x5x100 BLACK
170
C-23
D
140
2 DETAIL - 2 VIEW - D
45°
C
1 DETAIL - 1 C-23 SCALE NTS C-23 SCALE NTS
70
C-23 (POST #1)
SCALE NTS
(POST #1)
TITLE
1825
CIVIL WORKS
PLAN (TL-3)
ELEVATION A
IMAGE OF CRASHWORTHY END TERMINAL
1 2021 AMENDMENT - FINAL ISSUE JAN 2022
TITLE
A STANDARD DRAWINGS
PLAN ELEVATION B DRAWING TITLE
CIVIL WORKS
MOULDED NOSE PROTECTOR ROADWAY DETAILS
CRASHWORTHY END TERMINALS
REFERENCE IMAGES - GOOD PRACTICE
SOCKET DETAIL FOR POSTS 2 TO 7 DRAWN . SCALE NTS
CHECKED . DATE .
APPROVED . SIZE A1
PROJECT DWG.
No.
. No.
C-23
NOTES:
A A B
A A B
PLAN
A A B
B
A A
SIDE ELEVATION
A
ELEVATION ELEVATION SECTION A-A SECTION B-B
2 NESTED 10-GAUGE THRIE BEAM 10-GAUGE THRIE BEAM
A B B
B B
ELEVATION 1 2021 AMENDMENT - FINAL ISSUE JAN 2022
10-GAUGE W-BEAM No. REVISIONS APP'D DATE
A
CLIENT
ELEVATION
10-GAUGE THRIE BEAM
TITLE
STANDARD DRAWINGS
DRAWING TITLE
ROADWAY DETAILS
SIMPLIFIED STEEL - POST MGS
REFERENCE IMAGES - GOOD PRACTICE
STIFFNESS TRANSITION
580
580
1250
8 DIA AT 200
840
8 DIA AT 200
840
FOR FLARE END TERMINAL 65
SEE DWG. R-27 EDGE OF SHOULDER
SHLDR
180
180
TYPICAL FLARED END TERMINAL STANDARD TYPICAL FIXED OBJECT ATTACHMENT C-25
GR-FDA GR-SF GR-FDA
80
80
100
DIRECTION OF TRAFFIC
100
EDGE OF LANE
300
300
TYPICAL APPROACH END
SCALE: NTS
SECTION A-A
A TYPICAL SINGLE FACE CONCRETE BARRIER B SECTION B-B
C-25 SCALE NTS C-25 SCALE NTS
40
10 DIA AT 200
800
8 DIA AT 200
840
800
840
50
80
100
1000(MIN)
100
ELEVATION
1 DETAIL 1
300
C-25 SCALE NTS
VARIES
750 SECTION D-D
80 D TYPICAL GUARD RAIL (GR-SF) C SECTION C-C
NEUTRAL AXIS C-25 SCALE NTS C-25 SCALE NTS
85
R-5.00
1250 TYPICAL SINGLE FACE
CONCRETE BARRIER
50
75 108 108 101 102 TRANSVERSE JOINT
SEE SD-8
170
No. REVISIONS APP'D DATE
90
CLIENT
50
312
180
90
TWO-WAY TRAFFIC - DIMENSIONS "A", "B","C","D" AND "Z" FOR NEAR-SIDE TRAFFIC
SCALE: NTS
START BARRIER START BARRIER
TERMINAL TERMINAL
LENGTH OF NEED
END ANCHOR
C (SEE NOTE 4) BLOCK PROTECTED
END ANCHOR WIDTH B
BLOCK Z(30M MIN)
(SEE NOTE 3)
(SEE TABLE 1)
OFFSET D
(SEE NOTE 5) A
SHOULDER
DIRECTION OF TRAFFIC
DIRECTION OF TRAFFIC
SHOULDER
HAZARD
ONE-WAY TRAFFIC
END ANCHOR SCALE: NTS
BLOCK
START BARRIER
START BARRIER TERMINAL
TERMINAL
LENGTH OF NEED END ANCHOR
BLOCK
Z(30M MIN)
C (SEE NOTE 4)
PROTECTED (SEE TABLE 1)
WIDTH B
(SEE NOTE 3)
OFFSET D
(SEE NOTE 5)
A SHOULDER
DIRECTION OF TRAFFIC
DIRECTION OF TRAFFIC
SHOULDER
1 2021 AMENDMENT - FINAL ISSUE JAN 2022
TWO-WAY TRAFFIC -DIMENSIONS "A", "B","C","D" AND "Z" FOR FAR-SIDE TRAFFIC No. REVISIONS APP'D DATE
SCALE: NTS CLIENT
TABLE 1 - LENGTH "Z" FOR WIRE ROPE SAFETY BARRIER (METRES) ( SEE NOTE 5 )
TITLE
PROTECTED WIDTH STANDARD DRAWINGS
"B"(m) 9 8 7 6 5 4 3
(SEE NOTE 4)
DRAWING TITLE
SPEED (km/h) 120 110 100 120 110 100 90 120 110 100 90 120 110 100 90 80 120 110 100 90 80 70 120 110 100 90 80 70 60 120 110 100 90 80 70 60 50 CIVIL WORKS
1 110 100 90 105 100 90 80 105 100 90 80 100 90 85 75 70 95 90 80 75 65 60 90 85 75 70 60 55 50 80 75 70 65 55 50 45 35
2 100 90 80 90 85 75 70 90 80 75 70 85 75 70 60 55 70 65 60 55 50 45 60 55 50 45 40 35 30 0 0 0 0 0 0 0 0 WIRE ROPE SAFETY BARRIER (WRSB)
WRSB
OFFSET FROM 3 90 75 70 75 70 65 60 70 65 60 55 65 60 55 50 45 50 45 40 40 35 30 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
TRAFFIC LANE 4 70 65 60 60 55 50 45 55 50 45 40 45 40 40 35 30 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Sheet 1 of 2
"A" (m) 5 55 50 45 50 45 40 35 40 35 30 30 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 DRAWN . SCALE NTS
6 45 40 35 40 35 30 30 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
CHECKED . DATE .
7 35 30 30 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
APPROVED . SIZE A1
PROJECT DWG.
No. . No. C-26
NOTES:
6000
AL
TERMIN
6. WHERE SITE CONSTRAINTS PREVENT THE ADOPTION OF A
CURVE
200M RADIUS DESIRABLE TREATMENT, CONSIDERATION SHOULD BE
A GIVEN TO INCLUDING ANY ELEMENTS FORM A HIGHER
VERGE STANDARD TREATMENT THAT CAN BE ADOPTED AT THE
WRSB LINE OF STRAIGHT WRSB SITE.
120
9. REFER TO TR-518 FOR MORE INFORMATION ON RUNOUT
AREA DETAILS.
120
OPTION APPROACH AREA RUNOUT AREA POSSIBLE S0-6
TERMINAL OFFSET 200M RADIUS CURVE
LENGTH 'Z'
A LENGTH A WIRE ROPE
DESIRABLE 10:1 10:1 MAX REDUCTION
(m) (m)
(m)
770
MAXIMUM 10:1 6:1 MAX
1.0 20.0 10
ABSOLUTE MAXIMUM 6:1 4:1 MAX
1.5 24.5 15
TABLE 1 - GRADING OF FLARED TERMINAL APPROACH & RUNOUT AREAS 2.0 28.3 20
50
A BARRIER LENGTH 'Z' FROM TABLE 1 OF SD-6 MAY ONLY BE REDUCED AS SHOWN
IN TABLE 2 WHEN POINT & PRECEDES ANY HAZARDS BEING PROTECTED BY THE WRSB
BY AT LEAST 10m.
CLASS 25/20
CONCRETE SURROUND
BURIED PART OF POST
PROTECTED WITH
BITUMINOUS PAINT
30000 5000 10000
FLEXIBLE BARRIERS
SCALE: NTS
6000
1500
VERGE
WRSB
TERMINAL
SHOULDER 1 2021 AMENDMENT - FINAL ISSUE JAN 2022
STRAIGHT TERMINAL
SCALE: NTS
RUNOUT AREA A TITLE
STANDARD DRAWINGS
RUNOUT AREA B
OPTION RUNOUT AREA A RUNOUT AREA B DRAWING TITLE
DESIRABLE MATCH VERGE SLOP 10:1 MAX CIVIL WORKS
FLEXIBLE BARRIER & WIRE ROPE
MAXIMUM MATCH VERGE SLOP 6:1 MAX SAFETY BARRIER TERMINAL
RUNOUT AREA DETAILS
ABSOLUTE MAXIMUM MATCH VERGE SLOP NO WORSE THAN ROADSIDE
PRECEDING TERMINAL DRAWN . SCALE NTS
CHECKED . DATE .
TABLE 3 - GRADING OF STRAIGHT TERMINAL RUNOUT AREA A & B APPROVED . SIZE A1
PROJECT DWG.
No. . No. C-27
NOTES:
TITLE
STANDARD DRAWINGS
DRAWING TITLE
CIVIL WORKS
TYPICAL CURBSIDE BUS STOP
ARTICULATED BUS
TITLE
STANDARD DRAWINGS
DRAWING TITLE
CIVIL WORKS
BUS STOP WITH LAYBY
ONE STANDARD BUS FOR POSTED
SPEED UPTO 60km/h
TITLE
STANDARD DRAWINGS
DRAWING TITLE
CIVIL WORKS
500
2000
2000
TRUSS ROD
STRETCHER BAR
10 GAUGE GALVANIZED
TENSION CABLE
100
TRUSS ROD
100
200
EXISTING GROUND
800
16 DIA MIN
900
900
COPPER CLAD
800
800
900
EXISTING GROUND
* STEEL ROD
(TYPICAL)
* * * * *
100
100
100
100
100
100
300Ø
(MIN) 350Ø 300Ø 300Ø 300Ø
(MIN) (MIN) (MIN) (MIN) 300Ø
(MIN)
(MIN)
600
HINGE 90° SWING HINGE (180° SWING)
TENSIONER
800
800
TENSIONER
800
800
900
TITLE
900
*
900
900
*
EXISTING
* * * * * STANDARD DRAWINGS
100
GROUND
* * 250
100
100
100
100
(MIN)
100
100
100
3000 MAX. 1500 3000 MAX. 3000 MAX. 4500 3000 MAX. TYPICAL FENCING DETAILS
GATE OPENING GATE OPENING
Sheet 1 of 3
50
EXISTING GROUND
EACH TELEPHONE WIRE OR CABLE CROSSING, IT
SHOULD BE ALSO APPROVED FROM CLIENT / AUTHORITY
AND ALL RELATED AUTHORITIES.
TERMINAL POST
STRETCHER BAR GALVANIZED (END,CORNER OR PULL)
15°
FLAT STEEL BAR MIN 7.5mmx20mm
FABRIC
6 GAUGE STEEL
GALVANIZED WIRE
WIND ON FULL TURN
STRETCHER BAR
50
AROUND CABLE
10 GAUGE GALVANIZED
CONNECTION TO POST TENSION CABLE
SCALE: NTS FABRIC TIES AT
500 CENTERS POST
10 GAUGE GALVANIZED
TENSION CABLE
ELEVATION PLAN
32 14 GAGE
42
CULVERT
FENCE
89
PLAN PLAN
10 GAGE
SCALE: NTS SCALE: NTS 1 2021 AMENDMENT - FINAL ISSUE JAN 2022
89
No. REVISIONS APP'D DATE
CLIENT
86.3
LOCK LOOPS
TITLE
STANDARD DRAWINGS
1330
CONCRETE 500 x 500 x 500mm FOOTING EQUIVALENT TO THE WIDTHS OF THE SQUARE
END STRAINING POST LINE POST INTERMEDIATE POST DIMENSIONS.
L= 2700 L= 2500 L= 2700
CONCRETE 500 x 500 x 950mm FOOTING CONCRETE 300 x 300 x 750mm FOOTING CONCRETE 500 x 500 x 950mm
FOOTING
19mm Ø HOLES 100 x 50 x 6mm 1 2021 AMENDMENT - FINAL ISSUE JAN 2022
42
MS PLATE
NOTE:
27
DRAWING TITLE
CIVIL WORKS
Sheet 3 of 3
DROPPER BAR INTERMEDIATE STRAINING POSTS STRUT CONNECTION AND RATCHET WINDER DRAWN . SCALE NTS
SCALE: NTS SCALE: NTS CHECKED . DATE .
APPROVED . SIZE A1
PROJECT DWG.
No. . No. C-41
NOTES:
PLAN
TITLE
PANEL DETAIL
BASE PLATE DETAIL FIXING DETAIL TO CONCRETE WALL POST WITH WELDED BASE PLATE DETAIL C DETAIL D
(INTERMEDIATE POSTS)
FOUNDATION DETAILS
TITLE
STANDARD DRAWINGS
DRAWING TITLE
CIVIL WORKS
ROADWAY DETAILS
REFERENCE IMAGE: VISIRAIL FENCE OPTION
MEDIAN FENCE TYPE - 2
AS AN ALTERNATIVE, HIGH VISIBILITY RAILING DESIGNS MAY BE USED, ESPECIALLY IN AREAS CLOSE TO JUNCTIONS AND CROSSINGS
L.O.W L.O.W
Petrol Petrol
Station Station
EXISTING
TASJEEL
New Car Showrooms
L.O.W
M
O
24.0m ROW
SQ
24.0m ROW
UE
P12
Existing
Existing Structure
BH02 15.00 45.00
24.0m ROW
S/S
PROPOSED
L.O.W
TEMPORARY STP
WASH
IRRIGATION
PS
BH03
32.96
TANK &
PUMP STATION
36.6m ROW
67.0m ROW
EXISTING GAS PIPELINE
36.6m ROW
36.6m ROW
36.6m ROW
BH04
P13
P10
P7
P9
P8 L.O.W
P11
RD 29
RD 2
RD 2
RD 7
TEMPORARY ARRANGEMENT
(TO BE MODIFIED UNDER STAGE 2 316
ةايم خض ةطحم
67.0m ROW TEMPORARY ARRANGEMENT 54.0m ROW TEMPORARY ARRANGEMENT 54.0m ROW TEMPORARY ARRANGEMENT
(TO BE MODIFIED UNDER STAGE 2 (TO BE MODIFIED UNDER STAGE 2 (TO BE MODIFIED UNDER STAGE 2
L.O.W
RD 1 RD 1
RD 1
Bus Bay No. 1 Bus Bay No. 2 Bus Bay No. 3
RD 1 RD 1
BH01 RD 1
RD 13
RD 14
PS
36.6m ROW
36.6m ROW
TEMPORARY ARRANGEMENT
(TO BE MODIFIED UNDER STAGE 2
Mosque
RD 11
P3 P5
L.O.W
36.6m ROW
RD 8
24.0m ROW
TP04
RD 29
RD 10
L.O.W
RD 8 RD 8
Taxi Stop No. 2 (40m Long)
L.O.W
RD 8
Retail
RD 8
L.O.W
Car
24.0m ROW
36.6m ROW
24.0m ROW
Auction
10m utility corridor
RD 12
24.0m ROW
24.0m ROW
36.6m ROW
24.0m ROW
24.0m ROW
24.0m ROW
P2
BH05 P6 33/11 KV SS
RD 11
Reserved for
132/33/11 KV SS
P4
36.6m ROW
24.0m ROW
RD 11 TP02
P1
36.6m ROW
36.6m ROW
Administration
67.0m ROW
96
0
0+
60
3+
1. BORE HOLE LOCATIONS ARE INDICATIVE. CONSULTANT
SHALL SUBMIT BORE HOLE LOCATION PLAN BASED ON
PROJECT SPECIFIC REQUIREMENTS.
00
0+9
0
50
0
3+
00
0+
0+
000
RD 01
0+300
0+ 14
CD 0+302.252
0+800
100
RAMP 02
LHS P
40
2 + 10 0
0 M 10
3+
0+
UN
RA DE
23
2+0 PA
27 28 RP
00
22 0+
200 AS
01
20
0 0+200 S0
0+ 0+300 3
S
04 30
PAS
1+9 0+400
13 29
GE
00 0 +6 0+700 0 0
97.5 0+800
+3
P 03
82
0+3 ID 3 22 0+
RAM 0+500
R
000 0+60 300
BR
0 0
+00 0+90 SD RAMP 01
DE
0
00
1+8 5 21
RD
05
0
0 +7
0 0+600 12
UN
CD
E
RHS 0+4
000
G
0 0 21 0+5
1+ 00
ID
1+7 4 0+
400
BR
0 0
0
00
UND
0+10
0
10
0 +5 3 +2
0+ 00 00 1
01
0+
1+6 0
ER P
0 0 11 00 31
3 E 0+
0+
0+
DG
40 500
00 0
RI PA
0 +6 1
LOO
00 1+
ASS
B 20 RA
32
0
1+5 MP
60
00
00 SD 03
0+
P 01
10 1
3+ RA
04
0+7 0+0 0+
2 00 00 6
02
00
0+2 M
0
97.9 1+4 P0
0+20
GE
74 00 19
1
0+
D
00
RI
01
30
0+8
20
0
0+2
00
0
B
20
P
0+
9
1+
M
0 1+3
00 00
RA
03 0+3
RAMP 04
1 3+ 1 4.47
GE
18 9
0
0
0+9
SD
00
50
0 0
LOOP
0+300
0+
0+
8
B RI 1+2
00
88 0+10+000
0+
00
7.8
02
0 17
90 39
20
2+ 1+1
0
0+
0
0
00
30
0+30
7
1+
1+1
10
0 00
00 RD
0+
0+
16 1+0
00
0
40 CD
0+100
6 0 0+
80 1+2 LH
2+
RAMP 05
00
S
0+100
0+9 0+
00 10
15 0
0
0+30
1+3
0
00
40
0
+70
1+
0
2
40
0+8
00
0+
23 1+4 0+0
00 00
LOOP 03 0+800
00 0+700
UN
2+6 0+200
0
825.544 0+8
20
00 1+ 24
0+
0+5 0+500 1 00
5.985
RAMP 01 0+400 RAMP 01
9
0+53
RP
6.280 0
1+56 2 +5 0 0+300 0+700
0+200 1+6
AS
00
25 0+100 0+600
S0
0
2+40 0+500 5
RAMP 0
00
0+0 RD
2
0+3
26 00
0+400
CD
2+300 RHS
BORE HOLES LOCATION AT BRIDGES BORE HOLES LOCATION AT UNDERPASSES
EXISTING FINISHED EXISTING FINISHED
POINT NO. EASTING NORTHING BORE HOLE POINT NO. EASTING NORTHING BORE HOLE GROUND LEVEL ROAD LEVEL
DEPTH GROUND LEVEL ROAD LEVEL
LEGEND: (METERS) (METERS) DEPTH (METERS) (METERS)
1 21
##
BORE HOLE AT BRIDGES & APPROACHES 2 22
## 3 23
BORE HOLE AT UNDER PASSES 4 24
5 25
6 26 1 2021 AMENDMENT - FINAL ISSUE JAN 2022
7 27
No. REVISIONS APP'D DATE
8 28
CLIENT
9 29
10 30
11 31
12 32
13 TITLE
14 STANDARD DRAWINGS
15
16
DRAWING TITLE
17
18 CIVIL WORKS
19 SAMPLE BORE HOLE LOCATIONS
20 FOR BRIDGES
21
22
23
DRAWN . SCALE 1:400
CHECKED . DATE .
APPROVED . SIZE A1
PROJECT DWG.
No. . No. C-46
NOTES:
POINT C
1. ALL DIMENSIONS ARE IN METERS UNLESS OTHERWISE
EXPANSION JOINT 3.00 5.00 NOTED.
8.0 MAX
2. STONES MAY PROTRUDE ABOVE THE WORK LINE TO MAKE
A RANDOM PATTERN SURFACE.
POINT C POINT D
3. THE NUMBER OF TERRACES MIGHT VARY TO MATCH WITH
THE HEIGHT OF THE EMBANKMENT.
POINT D
4. ALL WORK LINES ARE A CONSTANT DISTANCE BELOW
STRUT LINE OF UPPER WORK POINT (A) EXCEPT THE BOTTOM WORK POINT
END WALL TYPE A PLANTED AREA 6:1 OR FLATTER
WORK POINT (WORK POINT (F) IN THE CASE SHOWN) WHICH WILL VARY
BEGIN PRECAST CONC. SLOPE VARIES
EXCEPT THE BOTTOM WORK POINT WITH THE EXISTING
PLANTERS BASE ON SOIL STABILIZATION
1.6
POINT F
POINT B&C
POINT D&E
6:1 OR FLATTER
B SECTION B-B
C-40 SCALE NTS
GROUND LINE AT TDE OF SLOPE
ELEVATION POINT C
SCALE: NTS
STEPS
3.00 5.00 3.00
0.30 TYP.
POINT D POINT E
60mm/m BATTER
PERMITTED
E C-40 UPPER WORK POINT
FINISHED
PAVEMENT LEVEL FINISHED
GROUND
ROADWAY PAVEMENT
EXPANSION
POINT F
JOINT
CONCRETE FOUNDATION 1.00
LOWER WORK
0.60
1.5
0.10
PRECAST CONC
PLANTER DRAWN . SCALE NTS
TYPICAL CROSS SECTION WALL TYPE A CHECKED . DATE .
SCALE: NTS LOWER WORK
POINT F (NO STRUTS AND NO STEEL APPROVED . SIZE A1
(SEE NOTE 3) REINFORCING REQUIRED)
PROJECT DWG.
No. . No. C-47
NOTES:
300
5. STEEL REINFORCEMENT SHALL BE DEFORMED
UNCOATED BARS TO ASTM A615 GRADE 60, OR BS4449
660 300 2080 300 660 2.5m GRADE 460.
2.5 0m
A 2.5
m m 3.4
C-41 6. ALL EXPOSED CONCRETE EDGES WHICH HAVE AN ANGLE
THAN 120° SHALL HAVE 20mm CHAMFERS OR FILLETS,
UNLESS OTHERWISE NOTED.
WALL TYPE B
4000
3400
B
300
C-41
PLAN D
10Ø
10Ø
300
6-20Ø (TYP)
C
1000
10Ø C-41
600
10Ø
100
A SECTION A-A
C-41 SCALE NTS
C SECTION C-C
C-41 SCALE NTS
10 Ø STIRRUPS
20Ø CLIENT
20Ø
10Ø 10Ø
300 300
4-20Ø EACH FACE TITLE
3-20Ø EACH FACE
STANDARD DRAWINGS
200
100
200
PREFORMED JOINT FILTER
DEPTH AS REQUIRED
DEPTH AS REQUIRED
SEE FRAME&GRATE 200 200
100Ø PERFORATED PVC
DETAIL. THIS SHEET PIPE WRAPPED WITH 100
PRE CAST CONC. PLANTER FILTER FABRIC
100Ø PERFORATED
PVC PIPE
200Ø PVC PIPE UNDER DRAIN DETAIL
WATER PROOFING
PROTECTION (TYP.) B SECTION B-B
C-42 SCALE NTS
150
600
150
200Ø PVC PIPE
WATER PROOFING
PROTECTION (TYP.) UNDER DRAIN CONNECTION
SPECIAL INLET
SCALE: NTS
1050
100m (TYP)
80
500 35 35
WALL 'B' SPECIAL INLET CONNECT TO INLET
WALL 'A' (TYP)
PLANTED AREA
SECTION
680
WALL 'A'
GENERAL PLAN
1120
SCALE: NTS
PLAN
WALL 'B' WALL 'A'
680
PLANTED AREA
88.9
PRE CAST CONC. PLANTER CLIENT
SECTION
MORTAR BEDDING (TYP)
ACUTE
FACE OF ABUTMENT
1. LOCATE POINT 1 AT OUTSIDE CORNER OF ABUTMENT WING
WALL.
END OF WING WALL
2. ESTABLISH LINE 1-30 AT 90° FROM SHOULDER LINE 30-31
CURVE CENTRES 22, 15, 8 AND 1 ARE ON LINE 27-1
22 EXTENDED.
15
8 4 3. RADIUS OF ARC 2-3=1.60m WITH CENTRE AT 1.
1 3.0 7 11 14 18 21 25 28 29
A 3 4. LOCATE 27 ON LINE 1-30 AND 0.50m BACK OF FACE OF
IES
2 31 ABUTMENT.
6
1
3.0
3.0
AR
1. 5: 1
VE
5:
10 5. E 3-6, 10-13, 17-20, AND 24-27 WILL EACH BE 3.0m FOR A
EV
1.
LE
B 13
5 3.0 TOTAL OF (4X3.0) =12.0m
OP
17
5.0
SL
LEVEL 20 6. HORIZONTAL DISTANCE 6-10, 13-17, AND 20-24 WILL EACH
3.0
EQUAL HORIZONTAL DISTANCES (3-27 MINUS 12.0)/3.
24
C 27
9 7. SET 27 AND 29 AT SAME ELEVATIONS AS 30 AND 31.
3.0
1. 5: 1 30
D 8. SET 3 AND 4 AT SAME ELEVATIONS AS 2.
12 SET 6 AND 7 AT SAME ELEVATIONS AS 5.
SET 10 AND 11 AT SAME ELEVATIONS AS 9.
5.0
LEVEL SET 13 AND 14 AT SAME ELEVATIONS AS 12.
SHOULDER BREAK LINE SET 17 AND 18 AT SAME ELEVATIONS AS 16.
E EDGE OF PAVED SHOULDER SET 20 AND 21 AT SAME ELEVATIONS AS 19.
16 SET 24 AND 25 AT SAME ELEVATIONS AS 23.
3.0
1. 5: 1 EDGE OF PAVEMENT
F
19
5.0
LEVEL
G
23
3.0
1. 5: 1
H CAST - IN - PLACE
26
CONCRETE PLANTERS
CONC. PLANTERS TO BE PRECAST SEE DWG SPD-2
AS SHOWN ON DWG.NO. SPD-2
WING WALL
A
C-43
1.5
:1
(T
YP.
)
3 5 3 5 3 5 3
A
2. ESTABLISH LINE 1-30 AT 90° FROM SHOULDER LINE 30-31
-
CURVE CENTRES 22, 15, 8 AND 1 ARE ON LINE 27-1
EXTENDED.
V
WEEPHOLE 75 DIA STAGGERED
3. RADIUS OF ARC 2-3=1.60m WITH CENTRE AT 1.
1000 VERTICAL AND 3000 HORIZONTAL H
V
4. LOCATE 27 ON LINE 1-30 AND 0.50m BACK OF FACE OF
1000
VARIES
H
ABUTMENT.
A
300 GROUTED RIPRAP
-
10
5. E 3-6, 10-13, 17-20, AND 24-27 WILL EACH BE 3.0m FOR A
00
300
30
TOTAL OF (4X3.0) =12.0m
GROUND LEVEL 0 300 GRAVEL FILTER TRAPEZOIDAL DITCH - B > 3000 6. HORIZONTAL DISTANCE 6-10, 13-17, AND 20-24 WILL EACH
EQUAL HORIZONTAL DISTANCES (3-27 MINUS 12.0)/3.
1500 MINIMUM OR AS DIRECTED
7. SET 27 AND 29 AT SAME ELEVATIONS AS 30 AND 31.
BY THE ENGINEER.
STUBS AT 10000 INTERVALS AND
AT THE ENDS OF PROTECTION SHOULDER VERGE 1000 8. SET 3 AND 4 AT SAME ELEVATIONS AS 2.
BACKFILL TO BE
ROUNDING SET 6 AND 7 AT SAME ELEVATIONS AS 5.
COMPACTED PLACE RIPRAP AGAINST SET 10 AND 11 AT SAME ELEVATIONS AS 9.
UNDISTURBED MATERIAL 500 500 B < 3000 SET 13 AND 14 AT SAME ELEVATIONS AS 12.
SET 17 AND 18 AT SAME ELEVATIONS AS 16.
SET 20 AND 21 AT SAME ELEVATIONS AS 19.
750 SET 24 AND 25 AT SAME ELEVATIONS AS 23.
500 500
V
VARIES
H H
30
10
00
TRIANGULAR DITCH
A
-
GROUND LEVEL
750
TITLE
30
SEE NOTE 1
STANDARD DRAWINGS
300
VARIES
1000
GROUND LEVEL
VARIES
3. SURFACE WATER DRAINAGE INLET UNITS NOT SHOWN FOR CLARITY.
1
WATERPROOFING SYSTEM -
TYPE A
NOTE: NOTE:
VARIES
1
WATERPROOFING TO WATERSTOPER LIMIT TO BE -
APPROACH SLAB TERMINATE 100mm ABOVE 300mm BELOW LEVEL OF TOP APPROVED
WATERSTOP TOP LEVEL OF SOIL TWO PART
POLYSULPHIDE
JOINT SEALANT
WATERSTOP
100
BLINDING CONCRETE
WATERPROOFING SYSTEM
TYPE A
A A
WATERPROOFING SYSTEM
TYPE A - -
200 APPROVED FILTER FABRIC
TYPICAL WATERPROOFING
APPROVED FILTER FABRIC DETAIL OF WATERPROOFING LIMITS
200 DIAMETER PERFORATED
PVC DRAIN PIPE (TYP) WRAPPED IN PVC
AT JOINT IN WALLS
WATER STOPPER FILTER MATERIAL AND LAID WATER STOPPER SCALE 1:5
(TYP.) TO 1:200 MINIMUM FALL (TYP.)
200 DIAMETER PERFORATED FGL
800 DRAIN PIPE (TYP) WRAPPED IN 50mm SINGLE SIZED FGL
150
150
FILTER MATERIAL AND LAID GRAVEL FILL
(NOMINAL)
(NOMINAL)
1000
1000
50mm SINGLE SIZED
WATERPROOFING SYSTEM
GRAVEL FILL
TYPE A
CONCRETE BASE
200
800
2 25 x 25 APPROVED
- BITUMEN FILLET
2
- B 300 WIDE STRIP OF
WATERPROOFING DETAIL AT WATER STOPPER IN RETAINING APPROVED COLD APPLIED
- BITUMINOUS WATER
DETAIL AT UNDERPASS RETAINING WALL SECTION @ JOINTS WALL @ JOINTS PROOFING MEMBRANE
SCALE 1:25 SCALE 1:25 SCALE 1:25
BLINDING CONCRETE
WATERPROOFING
SYSTEM TYPE A
50 THICK SAND CEMENT
PROTECTIVE SCREED
DETAIL 2
TYPICAL WATERPROOFING DETAIL
DETAIL AT BASE
5
APPROVED SCALE 1:5
TWO PART
10
POLYSULPHIDE
JOINT SEALANT
5
ROOF WATER STOPPER
15 WATERPROOFING SYSTEM
TYPE A
DETAIL 1
SCALE 1:1
WATERPROOFING SYSTEM
TYPE A
WALL WATER WALL WATER STOPPER 1 2021 AMENDMENT - FINAL ISSUE JAN 2022
STOPPER
1000 1000 No. REVISIONS APP'D DATE
WATERPROOFING SYSTEM CLIENT
TYPE A
WATER STOPPER
TITLE
STANDARD DRAWINGS
GAP
GAP DRAWING TITLE
FLOOR WATER STOPPER STRUCTURES
SECTION B-B SECTION A-A
WALL WATER STOPPER WATERPROOFING DETAILS
WATER PROOFING DETAIL AT JOINT
CHANGE OF RETAINING WALL THICKNESS Sheet 1 of 2
SCALE 1:20
DRAWN . SCALE AS SHOWN
WATERSTOP TYPES @ MOVEMENT JOINT CHECKED . DATE .
SCALE = NTS
APPROVED . SIZE A1
PROJECT DWG.
No. . No. ST-01
NOTES:
BLINDING CONCRETE
WATERPROOFING SYSTEM
TYPE A WATERPROOFING SYSTEM
TYPE A
50 SINGLE SIZED
GRAVEL FILL DETAIL 2
DETAIL 1 (TYPICAL INTERNAL CORNER)
3 (TYPICAL EXTERNAL CORNER) SCALE 1:5
- SCALE 1:5
PILE CAP
3 WATERPROOFING SYSTEM
FGL - TYPE A
5
APPROVED 25 x 25 APPROVED
(NOMINAL)
- POLYSULPHIDE
5 JIONT SEALANT
WATERPROOFING SYSTEM
TYPE A
50 THICK SAND CEMENT
PROTECTIVE SCREED
4
- DETAIL 3 DETAIL 4
SCALE 1:1 SCALE 1:5
PROOFING MEMBRANE
(STAR CUT & SPLAY CUT)
REPROFILE IRREGULAR
15mm THICK APPROVED 1 2021 AMENDMENT - FINAL ISSUE JAN 2022
FROM THIS POINT
TITLE
BLINDING CONCRETE STANDARD DRAWINGS
WATERPROOFING SYSTEM
TYPE A
DRAWING TITLE
20 x 20 APPROVED
BITUMEN FILLET STRUCTURES
PILE
Sheet 2 of 2
TYPICAL PILEHEAD PROTECTION DETAIL
SCALE 1:5 DRAWN . SCALE AS SHOWN
CHECKED . DATE .
APPROVED . SIZE A1
PROJECT DWG.
No. . No. ST-02
NOTES:
1. REINFORCEMENT SHALL NOT EXTEND THROUGH EXPANSION JOINTS.
2. CONTRACTOR TO SUBMIT DETAILS OF EXPANSION JOINTS, INCLUDING
ARCHITECTURAL TERMINATION DETAILS.
ARCHITECTURAL 3. ALL CONST. JOINT BELOW GROUND LEVEL SHALL HAVE INJECTABLE
TREATMENT TREATMENT
HOSES.
4. ALL EXP JOINTS BELOW GROUND LEVEL SHALL HAVE INJECTABLE HOSES,
ARCHITECTURAL WATERPROOFING SYSTEM AS PER SPECIFICATIONS.
WATERPROOFING SYSTEM TREATMENT 5. ELASTOMERIC CONCRETE IS SUBSIDIARY OBLIGATION OF THE EXPANSION
ARCHITECTURAL JOINT SYSTEM. NO SEPARATE PAYMENT WILL BE MADE FOR THIS ITEM.
TREATMENT 6. CONTRACTOR TO SUBMIT DETAILS OF WATER STOPPER AS PER
MANUFACTURER REQUIREMENTS FOR ENGINEER'S APPROVAL.
T (VARIES)
T (VARIES)
C D
T (VARIES) T (VARIES)
- -
MIN.100mm
MIN.100mm
T/10 OR
T/10 OR
INJECTABLE HOSE (AS
WATER STOPPER PER SPEC). NOTE A:
MIN.100mm
WATER STOPPER WATER STOPPER WATER STOPPER
T/10 OR
EXPANSION JOINT FOR BASE SLAB SHALL BE AS PER OWNER'S
PREFORMED REQUIREMENTS AND SPECIFICATIONS.
JOINT FILLER
NOTE B:
PREFORMED
JOINT SEALER SHALL BE IN COMPLIANCE WITH THE OWNER'S AND
JOINT FILLER
APPROVED MANUFACTURER'S SPECIFICATIONS. THE COLOR OF THE
SEALING COMPOUND SHALL MATCH THE FINISHED COLOR OF THE
T/3 T/3 T/3 REINJECTABLE EXPOSED CONCRETE SURFACES.
HOSE (AS PER
MIN.100mm
T/3 T/3 T/3 T/4
T/10 OR
SPEC). NOTE C:
ALL ARCHITECTURAL TREATMENT SHALL BE AS PER PROJECT
T/3 T/3 T/3 REQUIREMENTS.
T/3 T/3 T/3
TYPICAL WALL SECTION (ABOVE FINISHED ELEVATION) TYPICAL WALL SECTION (BELOW FINISHED GROUND ELEVATION)
SCALE 1:10
SCALE 1:10
CONC. PROTECTION
C/L EXP. JOINT
A
- C/L EXP. JOINT
T/3
PREFORMED
JOINT FILLER
ABOVE REINFORCEMENT
WATER STOPPER
WATER STOPPER
100
B 10
SCALE 1:7.5
-
C/L EXP. JOINT JOINT SEALER PREFORMED
INTERNAL EXPANSION JOINT
10
200
JOINT FILLER
T/4
(TYP)
WATER STOPPER
T/3
10
10 1 2021 AMENDMENT - FINAL ISSUE JAN 2022
T/2
T
SCALE 1:2
WATER STOPPER FOR
WATER STOPPER FOR CONSTRUCTION JOINT
PREFORMED CONSTRUCTION JOINT
JOINT FILLER TITLE
RE-INJECTABLE HOSE
WATER STOP LOCATION
(AS PER SPEC). INJECTABLE HOSE (AS
PER SPEC).
SCALE N.T.S.
10
STANDARD DRAWINGS
25
TOP SLAB 25mm BITUMINOUS CORK FILLER 25x15 DEEP SEALANT
BOARD OR SIMILAR DRAWING TITLE
T/3
10 10
400 400 30 END CAP STRUCTURES
WATER STOPPER
10
DETAILS OF JOINTS
TOP SLAB TYPICAL EXPANSION JOINT FOR TOP SLAB 25mmØ PLAIN STEEL
FILLER 28mmØ SLEEVE 430mm LONG
(TUNNEL, UNDERPASS & CULVERT)
SCALE 1:20 BAR c/c= 300mm
CONSTRUCTION JOINT
50
SCALE 1:10
SCREED DRAWN . SCALE AS SHOWN
DETAIL D
100
SCALE 1:2
CHECKED . DATE .
TANKING BASE SLAB (FOR CONCRETE PAVEMENT) APPROVED . SIZE A1
SCALE N.T.S. BLINDING
(DETAILS OF MOVEMENT JOINT) PROJECT DWG.
No. . No. ST-03
NOTES:
CAST-IN-PLACE CONCRETE DECK PC GIRDER 1. MINIMUM 28 DAY COMPRESSIVE STRENGTH OF EPOXY MORTAR AND CEMENT
END MORTAR MUST BE 40 MPa.
B
END 2. THE MIX RATIO OF EPOXY AND SAND FOR THE EPOXY MORTAR BLOCK MUST
A BE IN ACCORDANCE WITH THE EPOXY MANUFACTURER'S SPECIFICATION.
A
3. THE TYPE OF SAND USED IN THE MIX MUST BE IN ACCORDANCE WITH THE
MANUFACTURER'S SPECIFICATION.
1
-
.)
YP 4. BLOCKS TO BE TAGGED APPROPRIATELY. MINIMUM THICKNESS OF EPOXY
°(T
GRADE 36 OR HIGHER.
HORIZONTAL ON COMPLETION OF BRIDGE
COMPLETION OF BRIDGE CONSTRUCTION
GIRDER PROFILE 5. EXPOSED EDGES OF STEEL PLATES MUST BE ROUNDED TO A RADIUS OF
CONSTRUCTION A 1.5mm PRIOR TO GALVANIZING.
CL OF BEARING
DENOTES VALUES MUST BE DETERMINED BY DESIGNER USING CALCULATED
EPOXY MORTAR BLOCK
TOP OF BEARING RL 'X' PRE-MOULDED EPOXY NET HOG.
USED TO ADJUST LEVELING
CL OF BEARING
20
20
PRE-MOULDED EPOXY
MORTAR BLOCK 1 THOSE WITH LINK SLABS.
- ELEVATION OF GIRDER AFTER DECK CONSTRUCTION VIEW - A
LAMINATED
50 50 FOR VALUES OF a1, a2, a3, a4, b1, b2, b3 AND b4 SEE TABLE 1
ELASTOMERIC
(MIN.) (MIN.) BEARING, SEE DETAIL
(TYP.) (TYP.)
20
20
HORIZONTAL
.)
YP
(CROSS SECTION OF BEARING WITH MASONRY PLATE)
°(T
90
CL OF GIRDER AND BEARING
S
STEEL PLATE OR EPOXY BEARING SCHEDULE
50 = = 50 TOP OF BEARING RL 'X'
GROUTING PLINTH (TO BE Bearing Identification Mark
(MIN.) (MIN.)
GROUTED DURING THE
25 ERECTING OF THE PRE-CAST Number of Bearings
-
(MIN.) GIRDER ABOVE THE BEARING) LAMINATED Upper Surface
ELASTOMERIC BEARING, Seating Material
Lower Surface
(MIN.)
SEE DETAIL
50
HORIZONTAL Serviceability -
Upper Face
CL OF BEARING
Serviceability -
Lower Face
- - 50
Ultimate -
R
FINISH Vertical -
permanent
Serviceability Limit State minimum -
(MIN.)
(MIN.)
50
Design Load
SCALE 1:5 Effects (KN) Longitudinal -
Vertical -
RECTANGULAR ELASTOMERIC BEARING Ultimate Limit State Transverse -
SCALE 1:5 Longitudinal -
Transverse -
Irreversible
Translation Serviceability Longitudinal -
CL OF GIRDER AND BEARING (mm) Limit State
Transverse -
Reversible
S
Longitudinal -
= = Transverse -
Irreversible
Rotations Serviceability Longitudinal -
(radians) Limit State Transverse -
Reversible
CL OF BEARING
Longitudinal -
B B 2 2 Maximum rate (radians /100 kN)
Transverse -
=
Longitudinal -
- - - - Transverse -
R
Upper Surface
Longitudinal -
Maximum
Transverse -
=
SLOT ( TYP)
STEEL PLATES
DRAWING TITLE
STRUCTURES
STEEL PLATES
SECTION-2
SAMPLE DETAILS OF ELASTOMERIC BEARINGS
T
SCALE 1:5
6. THE BEARINGS AND THE CONNECTION SHALL ALLOW FOR SIMPLE EXCHANGE
OF BEARINGS WITHIN 3 HOURS WITHOUT THE NEED FOR CLOSURE OF THE
SECTION A-A SECTION B-B SECTION C-C BRIDGE.
A A B B C C
- - - - - -
TEFLON TEFLON
SHEAR CONNECTOR
SHEAR CONNECTOR SHEAR CONNECTOR
SLIDING PLATE SLIDING PLATE
PISTON PISTON
SOLE PLATE SOLE PLATE
SOLE PLATE PISTON
POT POT
POT
MASONRY PLATE
BASE PLATE FIXING MASONRY PLATE BASE PLATE FIXING MASONRY PLATE BASE PLATE FIXING
D D E E F F
- - - - - - TITLE
STANDARD DRAWINGS
DRAWING TITLE
STRUCTURES
Sheet 1 of 2
PLAN PLAN PLAN
DRAWN . SCALE AS SHOWN
FREE SLIDING POT BEARING GUIDED SLIDING POT BEARING FIXED POT BEARING
NTS NTS NTS CHECKED . DATE .
APPROVED . SIZE A1
PROJECT DWG.
No. . No. ST-05
NOTES:
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE NOTED.
Serviceability
Lower Face
Ultimate
Design Load maximum
Effects (KN)
BRIDGE DECK Vertical permanent
Serviceability Limit State minimum
Transverse
Vertical
Strength Limit State Transverse
Longitudinal
Vertical
Transverse
PIER Irreversible
Ultimate Limit Longitudinal
State
Transverse
Reversible
Longitudinal
DETAIL 1 Rotations
Irreversible
Transverse
SCALE 1:10 (radians)
Serviceability Longitudinal
Limit State
Transverse
Reversible
Longitudinal
Transverse
Maximum rate (radians /100 kN)
CL BEARING Longitudinal
Maximum Transverse
50 BOTTOM 50 Bearing Upper Surface 1 2021 AMENDMENT - FINAL ISSUE JAN 2022
OF DECK Dimensions Longitudinal
MIN.
Transverse
1
Lower Surface CLIENT
1 Longitudinal
Overall Height
50
25*
Vertical
TOP OF PIER/ABUTMENT Tolerable movement of bearing under
transient loads Transverse TITLE
- - EXPANSION JOINT
5. THE CONTRACTOR SHALL CALCULATE THE EXPANSION JOINT GAP IN
6mm GAP BETWEEN
B B PLATE AND SERVIFLEX 230 ACCORDANCE WITH THE MOVEMENTS GIVEN IN THE TABLE, TEMPERATURE
AT THE TIME OF INSTALLATION AND PRESET REQUIRED.
- - 6mm THICK COVER PLATE
6. THE CONTRACTOR SHALL SUBMIT THE CALCULATIONS ALONG WTH THE
METHOD STATEMENT FOR THE APPROVAL OF ENGINEER IN CHARGE.
MOVEMENT Y
2% FALL
CJ
G M
A RIN
F BE DECK
NO DECK
TIO
CL BRIDGE
EC DECK
DIR
APPROACH SLAB 11mm THICK BEDDING
MORTAR
MOVEMENT X EXPANSION GAP
CL DECK
CL DECK
SECTION B-B SECTIONAL ELEVATION C-C
SCALE 1:25 SCALE 1:25
STAINLESS STEEL
PLAN FOR SKEWED ABUTMENTS COVER PLATE
MOVEMENT X : EJ MOVEMENT CL EXPANSION JOINT
BARRIER
PLAN AT DECK LEVEL PLAN AT DECK LEVEL IN LONGITUDINAL DIRECTION
TABLE 1 J
MOVEMENT Y : EJ MOVEMENT
(AT PIER) (AT ABUTMENT) IN TRANSVERSE DIRECTION
TEMPERATURE GAP AT INTALLATION MAX. GAP MIN.GAP
SCALE 1:100 SCALE 1:100
STEEL PLATE REINFORCEMENT 20°C -
DECK
DECK PARAPET PARAPET
BRIDGE DECK ABUTMENT
ELEVATION OF BARRIER
STEEL ANGLE ELASTOMERIC SCALE 1:25
COMPRESSION SEAL
POURED-IN-PLACE SILICONE
SEALANT
POLYMER CONCRETE HEADER (TYP.)
BACKER ROD
BLOCK OUT
PRIMER
J
J
WELDED STEEL STUDS STRIP SEAL JOINT
SPACED ALTERNATELY SCALE NTS
℄ EXPANSION JOINT
WELDED STEEL STUDS
SPACED ALTERNATELY BOX-TYPE SEALS SHOWN GLAND-TYPE SEALS SHOWN
COMPRESSION SEAL JOINT RAPID CURE SILICONE SEALANTS JOINT SECTION BETWEEN SUPPORT BOXES SHWON SECTION THROUGH SUPPORT BOX SHWON
SCALE NTS SCALE NTS 1 2021 AMENDMENT - FINAL ISSUE JAN 2022
CENTER BEAM TO SUPPORT BAR
ELASTOMERIC STRIP SEAL
WELDED CONNECTION (MULTIPLE No. REVISIONS APP'D DATE
GLAND (TYP.)
SUPPORT BAR SYSTEM SHOWN)
SHOWN WITH ASPHALT OVERLAY SHOWN WITHOUT ASPHALT OVERLAY CENTER BEAM (TYP.) CLIENT
ELASTOMERIC BOX-TYPE
SLIDING STEEL PLATE
SEAL (TYP.) COMPRESSION SPRING WITH
POLYMER MODIFIED ASPHALT STEEL ANGLE (TYP.) STEEL ANGLE BONDED PTFE SURFACE
A ANCHORAGE (TYP.) BLOCKOUT EDGE BEAM (TYP.)
LIMITS (TYP.) STAINLESS STEEL
ASPHALT OVERLAY STEEL PLATE (A < J) SLIDING SURFACE
LOCATING SPIKE
BACKER ROD TITLE
STANDARD DRAWINGS
DRAWING TITLE
STRUCTURES
BRIDGE DECK ABUTMENT
BRIDGE DECK ABUTMENT BRIDGE DECK ABUTMENT
J
EXPANSION JOINT DETAILS
J
SUPPORT BAR (3 TOTAL, SUPPORT BOX (TYP.)
J WELDED STEEL STUDS
FOR ANCHORAGE (TYP.) CENTER ONE SHOWN)"
SUPPORT BEARING
WITH PTFE SURFACE
CONTROL SPRINGS BETWEEN DRAWN . SCALE AS SHOWN
ANCHOR BOLT (TYP.) ADJACENT SUPPORT BARS END CONTROL SPRING
CHECKED . DATE .
ASPHALTIC PLUG JOINT STEEL SLIDING PLATE JOINT MODULAR EXPANTION JOINT APPROVED . SIZE A1
SCALE NTS SCALE NTS SCALE NTS PROJECT DWG.
No. . No. ST-07
NOTES:
1. ALL DIMENSIONS EXCEPT LEVEL & CHAINAGES, ARE IN MILLIMETERS. UNLESS
NOTED OTHERWISE.
500
C BY THE SUPPLIER.
L DOWEL HOLE
WALL PANEL * * 100 500
150 200 150
COPING BEAM
200
WALL PANEL
(MIN.)
(MIN.)
150
150
ABUTMENT
200x200x400
500
BUILDING BLOCK
30
350
200x200x400
BUILDING BLOCK
800*
800*
(MIN.)
(MIN.)
150
150
APPROVED COMPRESSIBLE MATERIAL
45°
45°
55 WALL PANEL
145
150 150
(MIN.) (MIN.)
CHAINAGE LINE
CHAINAGE LINE
CL ABUTMENT
ABUTMENT WALL
WING WALL
30 x 30
APPROVED
SEALANT
200
WALL PANEL
300
30 x 30
APPROVED 300 WIDE GRANULAR
SEALANT FILL FOR DRAINAGE
APPROVED
COMPRESSIBLE
MATERIAL
TYPICAL CORNER DETAIL FOR CLOSED ABUTMENT
SCALE 1:25 HEIGHT OF WALL
A
ABUTMENT -
MIN. LENGTH OF BACKFILLING = 0.80 x HEIGHT OF WALL TITLE
A
-
STANDARD DRAWINGS
30
30 x 30
APPROVED COPPING
DRAWING TITLE
SEALANT FGL
BEAM
FGL
STRUCTURES
REINFORCED SOIL WALL DETAILS
(MIN.)
30
250
200
WALL PANEL
300
30 x 30 TYPICAL M.S.E. WALL SECTION
APPROVED
SEALANT CORNER UNIT
SCALE N.T.S. DRAWN . SCALE AS SHOWN
DETAIL PROVIDED BY
APPROVED DESIGNER. CHECKED . DATE .
COMPRESSIBLE
MATERIAL TYPICAL CORNER DETAIL FOR OPEN ABUTMENT APPROVED . SIZE A1
SCALE 1:25 PROJECT DWG.
No. . No. ST-08
NOTES:
3000 1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS STATED OTHERWISE.
1 2. THIS DRAWING IS TO BE READ IN CONJUNCTION WITH ALL RELEVANT
- DRAWINGS ISSUED BY THE ENGINEER.
500
T16-150 T16-150
300
1T16
ASPHALTIC PLUG JOINT ASPHALT SURFACING 90mm
SAND ASPHALT 20mm
100mm THICK BLINDING T20-150 250 WATERPROOFING 3mm
ASPHALT SURFACING
CONCRETE
SECTION A-A
SCALE 1:25
BAKER ROD
CAULK
6000
1 COMPACTED FILL
-
500
500
T16-150 T16-150
500
20 x 20 APPROVED
SEALANT
1T16
ABUTMENT
T25-150 100mm THICK BLINDING
T20-150 CONCRETE APPROACH SLAB
SECTION B-B
SCALE 1:25 DETAIL 2
SCALE = 1:5
20 x 20 APPROVED 2
SEALANT -
CL EXPANSION JOINT CL EXPANSION JOINT
3000 CL ABUTMENT 6000 CL ABUTMENT
1T16
1T16 L BAR
L BAR (FACE BAR)
(FACE BAR)
T20-150 B2
T16-150 B2
L BAR
L BAR
500
T16-150 T2 T16-150 T2
L BAR L BAR
℄ EXPANSION
JOINT
℄ BEARING
T16-150 B2 T20-150 B2
T20-150 B1
DEPTH OF
300/500
DECK
1T16 1T16 40 200
(FACE BAR) (FACE BAR)
CL DECK CL DECK 1 2021 AMENDMENT - FINAL ISSUE JAN 2022
CLIENT
- - - - T25-300
BLINDING SS DOWEL
CONCRETE
COMPRESSIBLE
FILLER
T16-150 T2 T16-150 T2 APPROVED TITLE
L BAR L BAR NEOPRENE
STANDARD DRAWINGS
T16-150 T1
FGL
DRAWING TITLE
/2
+Ø
45°
T16-150 B2
L BAR
T20-150 B2
L BAR
STRUCTURES
PLAN FOR 3M APPROACH SLAB PLAN FOR 6M APPROACH SLAB DETAIL 1 DETAIL AT ABUTMENT CHECKED . DATE .
SCALE 1:10 APPROVED SIZE
SCALE 1:100 SCALE 1:100 SCALE 1:50 . A1
PROJECT DWG.
No. . No. ST-09
CL PIER 2 NOTES:
CL ABUTMENT-A CL PIER 1 CL PIER n CL ABUTMENT-B
1. ALL DIMENSION ARE IN MILLIMETER UNLESS STATED OTHERWISE.
SPAN 1 SPAN 2 SPAN n 2. FOR LOCAL ZONE REINFORCEMENT, THE CONTRACTOR MUST PROVIDE THE
DETAILS OF REINFORCEMENT REQUIRED FOR THE APPROVED POST
TENSIONING SYSTEM.
(Y)
5. DIMENSION SHOWN IN THE TENDONS ARRANGEMENT ARE MINIMUM GUIDELINE
& SHALL BE MODIFIED ACCORDING TO THE ACTUAL BRIDGE LAYOUT & TO BE
CONFIRMED WITH THE SUPPLIER.
0.1L
0.2L
0.3L
0.4L
0.5L
0.6L
0.7L
0.8L
0.9L
0.1L
0.2L
0.3L
0.4L
0.5L
0.6L
0.7L
0.8L
0.9L
0.1L
0.2L
0.3L
0.4L
0.5L
0.6L
0.7L
0.8L
0.9L
0.1L
0.2L
0.3L
0.4L
0.5L
0.6L
0.7L
0.8L
0.9L
7. DETAILS OF PS COUPLERS (FOR STAGE CONSTRUCTION , IF REQUIRED )SHALL
L
DISTANCE ALONG C/L
BE ADDED IN THE CONTRACT DRAWINGS.
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
(Y)
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
(Y)
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
(Y)
Pj = - - - kN
- = Denotes the jacking end
WEB POST TENSIONING CABLE PROFILE
SCALE: HORIZONTAL = 1:300
VERTICAL = 1:150
R
R
TENDON
B
WE
C\L
C\L WEB
TENDON
(REFER TABLE)
R
R
SPACING AS PER
(Y)
(REFER TABLE)
SCALE 1:25
SEE NOTE 6.
P/T DUCT (TYP.)
P/T DUCT (TYP.)
(Y)
STRUCTURES
(Y)
JACK RECESS
PRE-STRESSING DETAILS
B
WE
C\L WEB
PORTION TO BE CAST
C\
2.3 ± CL.
SPLICE TUBE INSERTED IN HSS TUBE POST FLANGE TO BE CUT PARALLEL TO
RAILING ELEVATION KSI MINIMUM. THE MINIMUM HORIZONTAL BENDING RADII OF THE HSS TUBING
HSS TUBE SPLICE TUBE ROADWAY PROFILE GRADE WHEN OVER 50
SHALL BE 2.4M. PICKET CARRIER ANGLES, ANCHOR PLATES, AND SPLICE TUBE
1.5%.
PLATES SHALL CONFORM TO THE REQUIREMENTS OF AASHTO M 270 GRADE
CL TUBE (TYP.)
20
36. PICKET TUBING SHALL CONFORM TO ASTM A 513 WITH FY = 250 MPA MIN.
OR A 500 GRADE B.
190
GALVANIZED AND PAINTED DARK BRONZE. ANCHOR PLATE SHALL BE
350 GALVANIZED ONLY. HEADS OF 22Ø ROUND HEAD BOLTS SHALL BE PAINTED TO
290
HSS125x100x6 MATCH RAIL.
700
3. ANCHOR BOLTS SHALL BE SET WITH TEMPLATES. THE NUT SECURING THE
TYPICAL SPLICE SPLICE DETAIL POST BASE PLATE TO THE CONCRETE SHALL BE TIGHTENED TO A SNUG FIT
325
1055
HSS125x125x6 SPLICES WHERE POSSIBLE. RAILS SHALL BE SPLICED IN THE PANELS OVER
EXPANSION JOINT.
W150X625 POST (SET PLUMB) W150X625
5. ENDS OF TUBE SECTIONS SHALL BE SAWED. GRIND SMOOTH EXPOSED
A CL POST 700 ± CL SPLICE AND SPLICE TUBE EDGES. ALL CUT ENDS SHALL BE TRUE AND SMOOTH.
- 6. ALL POSTS TO BE PLUMB WHEN PROFILE GRADE EXCEEDS 1.5%. FOR PROFILE
(175 AT SAFETY
700 (SPLICE TUBE) CAST CONCRETE PAD 25 ALL AROUND
BOTTOM OF GRADES LESS THAN 1.5%, POSTS SHALL BE SET PERPENDICULAR TO GRADE.
MONOLITHICALLY WITH BASE PLATE
375
38 x 38 x 1.5 (16 GA.) THICK PICKETS 32mm BASE PLATE BASE PLATE
775 LONG AT SAFETY CURB 975 LONG 1 25 MIN. (TYP.) THERMAL EXPANSION AT BRIDGE SIDEWALK AND SAFETY CURB 7. POST FLANGE WELD DOES NOT REQUIRE MAGNETIC PARTICLE TESTING. WELD
CURB)
JOINT +12mm 75 (CRITICAL) SHALL BE BACK-GOUGED ON BACK SIDE EXCEPT AT WEB. WELD IS THE SAME
AT SIDEWALK - L75x50x6 (TYP.) ON BOTH FLANGES.
S)
8. 22Ø ROUND HEAD BOLTS SHALL CONFORM TO THE CHEMICAL AND PHYSICAL
IDE
LEVEL BEARING AREA
REQUIREMENTS OF AASHTO M164.
(3 S
ACCURATELY FINISHED DIMENSIONS TOP OF CONCRETE
45°
INCLUDE PAD 9. FOR OTHER TEST LEVEL RAILINGS, AS APPLICABLE, SHALL BE DETAILED IN
3mm MOLDED FABRIC CONTRACT DOCUMENTS.
CONSTRUCTION
EXPANSION OR
ANCHOR PLATE
SETTING OF POSTS (PROFILE GRADE OVER 1.5%) SECTION 1
SCALE 1:10 SCALE 1:10
SECTION AT SIDEWALK SHOWN. SECTION
AT SAFETY CURB SIMILAR, EXCEPT AS
NOTED.
50 CL.
22
CL HSS
SCALE 1:20
SECTION AT SIDEWALK SHOWN. SECTION
AT SAFETY CURB SIMILAR, EXCEPT AS
NOTED.
22 Ø
3 SLOT 3
44 44
HSS125x125x6
SCALE 1:5
HSS125x100X6 16Ø A325 BOLT AND SECTION THRU POST WEB
63
WASHER
24 x 55 VERT. SLOT IN
100 HSS125x100x6 (TOP RAIL)
POST
38
50
125
SECTION 2 SECTION 4
SCALE 1:5
L75x50x6
PICKET ℄ 8 HARDENED COUNTER-SUNK MACHINE LONG LEG UP
SCREW WITH NUT AND LOCK WASHER 30 Ø HOLES FOR 1 2021 AMENDMENT - FINAL ISSUE JAN 2022
28 Ø ANCHOR BOLTS (TYP.)
No. REVISIONS APP'D DATE
SECTION 3 SECTION 5 75 Ø HOLE CENTERED CLIENT
ON PLATE
- - - CONCRETE TITLE
50
20x50 HORIZONTAL
SLOT HARDENED 25 STANDARD DRAWINGS
100
WASHER
100
300
300
W150X625
DRAWING TITLE
300
STRUCTURES
100
100
ANCHOR ⅊
45
(TL4)
50
2 3 4 5
- - - - 175
TACK WELD
28 Ø ASTM A 449
ANCHOR BOLT 75 175 50
250
8 DRAWN . SCALE AS SHOWN
DETAIL A 20x50 HORIZONTAL
SLOT
DETAIL B 300
CHECKED . DATE .
TYPICAL PICKET TO RAIL DETAILS ANCHOR PLATE ANCHOR BOLT BASE PLATE APPROVED . SIZE A1
SCALE 1:5 SCALE 1:5 SCALE 1:5 SCALE 1:5
PROJECT DWG.
No. . No. ST-11
NOTES:
1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS STATED OTHERWISE.
2. ALL RAILING IS TO BE FABRICATED AND ERECTED SO THAT THE RAILS ARE
PARALLEL TO EACH OTHER AND TO THE GRADE. THE POSTS ARE TO BE
SEAL WELD AND GRIND TRULY VERTICAL. IF GRADE OF BRIDGE EXCEEDS 8%, THE DESIGNER MAY
SMOOTH (TYP.) ELECT TO DESIGNATE ON THE PLANS THAT POSTS ARE TO BE SET
A PERPENDICULAR TO THE GRADE.
℄ OF 16 mm DIA. HOLE FOR 12.7 mm 3. WHEN THE RAILING IS TO BE PLACED ON A PREFORMED SURFACE, THE BASE
SEE CAP ⅊ DETAIL 267 SEE "RAIL SPLICE DETAIL" CL OF RAILING EXPANSION JOINT - DIA. GALV. ROUND HEAD SQUARE NECK BOLTS PLATE MAY BE PARALLEL TO THE GRADE OR MAY BE PERPENDICULAR TO
(TYP. ALL POSTS) (CARRIAGE BOLTS)
102 x 102 x 4.8 RAIL TUBE THE POST AND MADE LEVEL BY THE USE OF (1:1 RATIO CEMENT TO SAND)
(TYP.) ℄ OF POST & BOLTS (TYP.) 1.5 MIN. 4 m MAXIMUM POST SPACING MORTAR.
4. TUBULAR STEEL RAILS, RAIL POSTS, NUTS AND WASHERS, CARRIAGE BOLTS,
FACE OF RAIL BASE PLATE ASSEMBLIES, ANCHOR STUDS, ANCHOR PLATES, ANY
12.7 mm DIA. GALV. ROUND HEAD
NECESSARY SHIMS AND MORTAR PADS TO BE PAID FOR UNDER THE RAILING
SQUARE NECK BOLT (CARRIAGE
102
ITEM.
BOLT) HEX NUT AND SPRING
5. AFTER THE ANCHOR STUD NUTS HAVE BEEN PLACED AND TIGHTENED TO
LOCK WASHER (TYP.)
THE SATISFACTION OF THE ENGINEER, THE STUDS SHALL BE CUT OFF 25 mm
102 x 102 x 4.8 RAILING POST ABOVE THE NUT AND THE THREADS SHALL BE DAMAGED SO THE NUT SHALL
202
(TYP.) NOT BACK OFF.
6. RAIL SHALL SPAN A MINIMUM OF 3 POSTS, EXCEPT AT THE END OF THE
BRIDGE RAILING WHERE THE RAIL MAY SPAN A MINIMUM OF 2 POSTS.
102 x 102 x 4.8 RAILING POST
51
7. RAILING COMPONENTS ARE TO BE GALVANIZED IN ACCORDANCE WITH
102
MATERIAL SPECIFICATION.
102 x 102 x 4.8 RAIL 8. PRIOR TO GALVANIZING, GRIND ALL SHARP EDGES TO A MINIMUM RADIUS OF
2MM.
150
TUBES
9. CEMENT MORTAR PADS SHALL BE PAID FOR UNDER THE RAILING ITEM.
1060
CUT EXCESS & PEEN (TYP.)
10. REPAIR TO ALL DAMAGED GALVANIZED SURFACES INCLUDING ANCHOR
STUDS SHALL BE MADE IN ACCORDANCE WITH MATERIAL SPECIFICATION.
102
11. ARCHITECTURAL RAILING PROPOSALS AS PER PROJECT SPECIFIC
REQUIREMENTS SHALL BE PROPOSED FOR ACCEPTANCE PRIOR DETAILING
FOR STRUCTURAL SOLUTIONS.
150
12. FOR BRIDGES THAT ARE USED FOR CYCLISTS' MOVEMENT, THE HEIGHT OF
102 RAILING SHALL BE A MINIMUM OF 1400 MM.
50
B 27 B TOP OF SIDEWALK
150
25
(TYP.)
180
180
ANCHOR STUDS
C C
- - 190 x 230 x 13 RAILING POST ANCHOR
PLATE
200
M16 GALV. ROUND HEAD SQUARE NECK BOLT 19 mm DIA. HEAVY HEX NUT & FACE OF RAIL
(CARRIAGE BOLT), USE 1 BOLT AT EXPANSION JOINTS WASHER (2 OF EACH REQUIRED 102 122
AND TWO BOLTS ON ALL OTHER SPLICES. WITH MORTAR PADS) TYPICAL
190 FACE OF RAIL
190
190 x 230 x 19 ⅊ SEE CAP PL DETAIL
102 x 102 x 4.8 RAIL TUBE 75 30 130 30
102 x 102 x 4.8 RAIL POST 30 30 190 x 230 x 13 ⅊ ASTM HEX NUT FOR 19 mm DIA.
A36M ANCHOR STUD (TYPICAL)
30
89 x 89 x 6.4 SPLICE TUBE ASTM A500M, ℄ OF RAILING ANCHORAGE
30
AND ℄ OF RAILING POST
64
GRADE B
115
℄ OF RAILING ANCHORAGE
5 mm END CAP ⅊ (TYPICAL
51
AND ℄ OF RAILING POST
230
230
102
12 DIA. WEEP HOLE ALL RAIL ENDS)
115
BOLTS TO BE TIGHT AND THE THREADS BELOW THE NUT
64
30
8
ALL SHARP EDGES SHALL BE TO BE DAMAGED A.O.B.E. 30
GROUND SMOOTH AFTER CUTTING TACK WELD (TYP.) 65 65
℄ OF 25 mm DIA. HOLE FOR 19 mm
DIA. ANCHOR STUD ASTM F568 (TYP.) 30 65 65 30 ℄ OF 25 mm DIA. HOLE FOR 19 mm
SECTION D-D ℄ OF RAILING ANCHORAGE DIA. ANCHOR STUD ASTM F568
SCALE 1:5 145 122 (TYP.)
℄ OF 90 mm DIA. HOLE
FASCIA ℄ OF RAILING ANCHORAGE
RAIL TERMINATION DETAIL
SECTION B-B SECTION C-C SCALE 1:10
150
DRAWING TITLE
102
51
FOR SLAB:
1. MAX SIZE OF OPENING = 600mm OR SPAN/4.
PLACE 50% OF INTERCEPTED PLACE 50% OF INTERCEPTED
2. IF SIZE OF OPENING IS LESS THAN 200mm, DISPLACE BARS TO SIDES OF
REINFORCING BARS OF THIS REINFORCING BARS OF THIS
OPENING, NO EXTRA TRIMMING BARS REQUIRED.
AREA ON EACH SIDE AREA ON EACH SIDE
SLAB/WALL 3. FOR LARGE SIZE OF OPENING, DETAILS OF STEEL ARRANGEMENT SHALL BE
SLAB/WALL
REINFORCING OPENING OPENING SPECIFIED BY THE ENGINEER.
REINFORCING
4. NOT APPLICABLE TO OPENINGS IN CANTILEVER SLAB
h
h
NOTE:-
EMBEDDED STEEL ITEMS OR SLEEVES
IF ANY, ARE NOT SHOWN FOR CLARITY
COVER COVER
CL OPENING
TENSION DEVELOPMENT
A
12 DIA
LENGTH TYPICAL
00 GO
SLAB/WALL SLAB/WALL
B
2 MU BAR
M NA
-
xB M
REINFORCING REINFORCING
IN L
I
-
FO S
R
PI AR
DIAGONAL BAR
L
CA
TY LE
ADDITIONAL EACH FACE
C
75
.)
YP
(T
0
75
DIMENSION
OPENING
OPENING
LEAST
"B"
CL OPENING
D
A B
- -
1 2021 AMENDMENT - FINAL ISSUE JAN 2022
TITLE
STANDARD DRAWINGS
DRAWING TITLE
STRUCTURES
B
-
960
960 65 860 35
PLATE 35 x 8 THICK
5 475 475 5
5
5
5
35
40
40
180
110
50
140
225
80
WIRE MESH
400
WIRE MESH
PLATE 35 x 8 THICK
800
PLATE 65 x 8 THICK 5
50 65 67 5 35
800
600
960
500
500
960
850
800
800
5
50
A A
- 35 - 80 20
27 30
PLATE 30 x 200 x 6 (TYP) 800 STAINLESS STEEL
20 33 TAP BOLTS WITH
400
WASHERS (TYP)
20
80
20
225
140
50
110
180
40
40
35
5
5
5
(TYP AT EACH CORNER)
6
CHANNEL 200 x 75 x 23
B (TYP) STAINLESS STEEL TAP
BOLTS WITH
- WASHERS (TYP) PLATE 35 x 8 THICK
4
(TYP) CHANNEL 200 x 75 x 23
CHANNEL 200 x 75 x 23
1 2021 AMENDMENT - FINAL ISSUE JAN 2022
SLAB THICKNESS
CLIENT
4 4 4 4
TITLE
HINGE 50 40 40
STANDARD DRAWINGS
CHAIN WITH DOOR
PLATE 8mm THICK PLATE 8mm THICK LOCK OUTSIDE
DRAWING TITLE
HINGE
STAINLESS STEEL
TAP BOLTS WITH
STRUCTURES
PLATE 8mm THICK SECTION A-A WASHERS (TYP) SECTION B-B
SCALE 1:5 SCALE 1:5
ACCESS DOOR DETAILS
min.
5d
BETWEEN THE SPECIFIED OVERALL DIMENSION AND THE TRUE LENGTH
r
MEASURED ALONG THE CENTRAL AXIS OF THE BAR OR WIRE. WHEN THE
A
A BENDING ANGLES APPROACH 90°, IT IS PREFERABLE TO SPECIFY SHAPE
00 A 44 (E) A + B + C + D + (E) - 2r - 4d CODE 99 WITH A FULLY DIMENSIONED SKETCH.
A
(B) 4. FOR SHAPES WITH STRAIGHT AND SEMICIRCULAR LENGTH (e.g. SHAPE
CODES 13 AND 33) THE LARGEST PRACTICAL RADIUS FOR THE PRODUCTION
D
OF A CONTINUOUS CURVE IS 200mm, AND FOR LARGER RADII THE CURVE
MAY BE PRODUCED BY SERIES OF STRAIGHT SECTIONS.
NEITHER "A" NOR E SHALL BE LESS MINIMUM MINIMUM
C NOMINAL MINIMUM
THAN "A" IN TABLE SIZE OF BAR RADIUS FOR DIAMETER OF END
SCHEDULING BENDING
FORMER DIMENSION
A + (B) - 1 / 2 r - d A (E) A + 2B + C + (E)
11 46
d r M A
B
- - - -
D
NEITHER "A" NOR E SHALL BE LESS 6 12 24 110
(B) NEITHER "A" NOR "B" SHALL BE LESS THAN "A" IN TABLE. SEE NOTE 3
C - - - -
10 20 40 120
NEITHER "A" NOR "B" SHALL BE LESS 12 24 48 125
(D)
(B) THAN A IN TABLE NOR LESS THAN (R +
6d) 16 32 64 130
B
20 40 80 160
13 (C) A + 0.57B + (C) - 1.57d
25 50 100 200
NEITHER "A" NOR "C" SHALL BE LESS
THAN "A" IN TABLE NOR LESS THAN (21"B" 32 64 128 260
SEMI CIRCULAR "C" AND "D" SHALL BE EQUAL AND
B
+ 5"d"). "B" SHALL NOT BE LESS THAN 2(r NOT MORE THAN "A" OR "B" NOR 40 80 160 320
+"d"). SEE NOTE 4 A LESS THAN "A" IN TABLE.
A
- - - -
8 16 32 115
NEITHER "A" NOR "C" SHALL BE LESS
THAN "A" IN TABLE. R - - - -
(C)
SEE NOTE 3 10 20 40 120
21 A + B + (C) - r - 2d 77 C p (A - d) 12 24 48 125
16 32 64 130
A
(C)
20 70 140 190
A
B
25 A + B + (E) 40 140 280 380
A NEITHER "A" NOR "B" SHALL BE LESS
B
10 20 40 120
EXCEPTION OF RECTANGULAR LINKS, 5 BENDS OR MORE ARE
NEITHER "A" NOR "C" SHALL BE LESS UNDESIRABLE AND MAY BE IMPRACTICAL WITHIN PERMITTED 12 24 48 125
A THAN "A" IN TABLE. SEE NOTE 3 TOLERANCES BUT THEY SHALL BE DRAWN OUT IN FULL AND
CODED 99. - - - -
A DIMENSIONED SKETCH SHALL BE DRAWN OVER THE - - - -
A
31 A + B + C + (D) - 1½r - 3d DIMENSION COLUMNS A TO E. EVERY DIMENSION SHALL BE
SPECIFIED AND THE DIMENSION THAT IS TO ALLOW FOR - - - -
PERMISSIBLE DEVIATIONS SHALL BE INDICATED IN - - - -
(D)
JAN 2022
B
C
NEITHER "A" NOR "E" SHALL BE LESS
THAN "A" IN TABLE
SHAPE CODES, BENDING RADII, BAR SIZES AND LENGTHS OF REINFORCING STEEL STANDARD BAR SHAPES
REINFORCEMENT BARS ARE ACCORDING TO BS 8666:2000
500
FOOTPATH / 270 50 180
FOOTPATH / 450 PEDESTRIAN PUBLIC REALM* 20x20
400 PEDESTRIAN PUBLIC REALM* 220 50 180 CHAMFER
17050 180 20x20
20x20 CHAMFER
450
CHAMFER
740
485
1070*
360
50 50 50
R2 R2 R2
815*
690*
80 250
80 250
80 250
SIDEWALK
FRL FRL FRL
CJ CJ CJ
630
180 5017050 180
630
630 20x20
180 5017050 180
CHAMFER
180 5017050 180
20x20
20x20 CHAMFER
CHAMFER
500
740
485
1070
360
815
690
500
FRL FRL FRL
80 250
80 250
80 250
CJ CJ CJ
REINFORCEMENT DETAIL AT LIGHT POLE SUPPORT
SCALE 1:20
(SEE NOTE 1)
MEDIAN BARRIER AT DECK (TL3) MEDIAN BARRIER AT DECK (TL4) MEDIAN BARRIER AT DECK (TL5)
SCALE 1:25 SCALE 1:25 SCALE 1:25
400
180 50 170
400
20x20 CHAMFER
180 50 170
20x20 CHAMFER
1040
740
R25 R25
0 0
CLIENT
80 250
80 250
FINISHED FINISHED
GROUND GROUND
500
500
TITLE
CONCRETE CONCRETE STANDARD DRAWINGS
FOUNDATION FOUNDATION
D
DRAWING TITLE
FOR BARRIER LOCATED
WITHIN 3.0m FROM FACE
FOR BARRIER LOCATED AT
MORE THAN 3.0m FROM FACE
(SEE NOTE 1) (SEE NOTE 1) STRUCTURES
OF PIERS/ABUTMENTS. OF PIERS/ABUTMENTS.
(SEE NOTE 1) (SEE NOTE 1)
CONCRETE BARRIER AND
PROTECTION BARRIER DETAILS MEDIAN BARRIER REINFORCEMENT EDGE BARRIER REINFORCEMENT MISC. BRIDGE DECK DETAILS
SCALE 1:25 SCALE 1:25 SCALE 1:25
1200*(PER.)
PIPES FROM
ABUTMENT SHELF
DRAINAGE CHANNEL
INSIDE 150
℄ EXPANSION
L100x100x10
JOINT
5 Ø12-300 ℄ BEARING
150
ALUMINUM COVER PLATE FOR OVER
PARAPET BEAM GAP BOLTED THE
8 ABUTMENT SIDE ONLY.
6
PLATE 80x6
6
300
50 LEDGE WITH
CHANNEL
100
OUTSIDE RECESS TO CONTAIN
STAINING FROM
PIPE
1000*
1200* 1200x1000 GRP LOCKABLE
ACCESS PANEL PAINTED TO
MATCH ABUTMENT COLOR (TO
SECTION 1-1 CONTRACTOR'S DETAIL AND
SCALE 1:10 ENGINEER'S APPROVAL)
300
50 200 50 WING WALL
50
30
225
325
GALVANIZED STEEL FRAME TYP.
RIVET TO FIX GRP 50 5mm TH. RECESSED
INTO WALL
100
PLATE (TYP)
95 5 45 5
50
GROUND LEVEL
100
PLATE 80x6
5
50
100
100
150
30
FGL
WING WALL DRAINAGE DETAIL
C/L M/O STAINLESS SCALE 1:10
HINGE
STEEL TAP BOLTS
100 WITH WASHERS ( TYP.)
80 80
1000
700
700
30 30
1 1
- -
CONCRETE OPENING
OUT LINE
TWO DIAGONAL
REINFORCEMENT RIBS
JAN 2022
30
150
CLIENT
50
EXTERNAL
5
℄ ABUTMENT A ℄ PIER 1 ℄ PIER 2 ℄ PIER n ℄ ABUTMENT B 3. ALL THE DIMENSIONS SHOWN ARE FOR GUIDANCE ONLY.
TOTAL LENGTH OF BRIDGE
4. CONSIDERATION FOR ANCHORING FUTURE CABLES SHALL BE TAKEN INTO
SPAN 1 SPAN 2 END SPAN ACCOUNT IN THE DETAILING OF DECK REINFORCEMENT.
℄ BRIDGE
(TYP.)
100
100
100
200 300
(TYP.)
300
REFER TO NOTE 4
℄ BRIDGE
450
TITLE
(MIN.)
STANDARD DRAWINGS
R10250
DRAWING TITLE
STRUCTURES
DETAIL 1 DETAIL 2
DRAWN . SCALE AS SHOWN
CHECKED . DATE .
APPROVED . SIZE A1
PROJECT DWG.
No. . No. ST-18
NOTES:
C
A B -
- -
CL BEARING/ABUTMENT-A CL BEARING/ABUTMENT-B
1 SPAN
-
CL INTERMEDIATE DIAPHRAGM
DEPTH
TENDON 1
TENDON 2 B
A TENDON 3
- C
- -
TYPICAL ELEVATION OF GIRDER
SCALE 1:75
0.15L
0.20L
0.25L
0.30L
0.35L
0.40L
0.45L
0.50L
0.55L
0.60L
0.65L
0.70L
0.75L
0.80L
0.85L
0.90L
0.95L
0.05L
ALONG GIRDER
0.00
L
TENDON
*
*
Y DISTANCE No. 1
FROM BOTTOM OF
GIRDER TO CG OF TENDON
*
*
TENDON No. 2
(IN METERS)
TENDON
*
*
No. 3
TENDON PROFILE
SCALE 1:75
18.00
16.00
14.00
12.00
10.00
8.00
6.00
4.00
2.00
0.00
0.25L
0.50L
0.75L
X DISTANCE
0.00
L
ALONG GIRDER
SHORT TERM
DEFLECTION DUE TO
0.00
0.00
**
**
**
SELFWEIGHT OF
GIRDER AND
PRESTRESSING (mm)
DEPTH
THK
TENDON 2
Y
TENDON 3
Y
Y
Y
Y
Y
LIVE END
DEAD END
Y
DRAWING TITLE
Y
Y
THK THK THK
X
STRUCTURES
300
POST-TENSIONED PRECAST
SECTION A-A SECTION B-B SECTION C-C DETAIL 1 GIRDER DETAILS
SCALE 1:25 SCALE 1:25 SCALE 1:25 SCALE 1:25
3. ALL THE DIMENSIONS SHOWN ARE MINIMUM, DESIGNER SHALL PROVIDE ALL
THE DIMENSIONS AS PER DESIGN.
FOOTPATH /
PRECAST PC CB* PEDESTRIAN PUBLIC REALM*
GIRDER
1:40
SPLAY
100 x 100 SURFACING IN TWO
GR. LVL LAYERS AS PER
SPECIFICATION
CJ
DEPTH
FALL
(FOUNDATION TYPE AS
300 (MIN)
SECTION AT ABUTMENT PER DESIGN) SUB-BASE FILL
SCALE 1:75
25 THICK
SAND/CEMENT TEMPORARY SUPPORT PRECAST
100mm THICK 3:1 MORTAR BED DURING INSTALLATION
25 RADIUS PC GIRDER
BRIDGE WIDTH PRECAST CONCRETE HAUNCH
HALF ROUND CONCRETE PANEL 200 x 300
DRIP GROOVE SUB STRUCTURE
(TYP)
BEARING
CB FP SH CARRIAGEWAY SH FP CB
PRECAST
DETAIL 1 PC GIRDER SECTION AT PIER
SCALE 1:25 SCALE 1:50
1 (WITHOUT EXPANSION JOINT)
- *NOTES:
(FOR PRE-TENSIONING GIRDER)
1. IN URBAN AREAS, PEDESTRIAN THROUGH ZONES AND CYCLE TRACKS SHALL BE
FALL PROVIDED IN ALIGNMENT WITH THE USDM AND WCMP.
FALL SURFACING 2. DESIGN OF BARRIERS AND KERBS SHALL MEET ALL ROAD DESIGN AND SAFETY
FALL DESIGN REQUIREMENTS FOR THE DESIGN SPEED OF THE ROAD. CONSULTANTS TO
PROVIDE DETAILS OF ALL NECESSARY REQUIREMENTS.
3. FOR BRIDGES THAT ARE USED FOR CYCLISTS' MOVEMENT, CONSULTANT TO
PROVIDE ADDITIONAL DETAILS ABOVE THE BRIDGE BARRIER IN ORDER TO MEET THE
MINIMUM RAILING HEIGHT REQUIREMENT OF 1400 MM.
PRECAST PC
GIRDER
FOOTPATH /
CB* PEDESTRIAN PUBLIC REALM*
BRIDGE WIDTH
CL EXPANSION
SURFACING IN TWO JOINT
CB FOOTPATH SH CARRIAGEWAY SH VERGE CB LAYERS AS PER CL BEARING CL BEARING
SPLAY SPECIFICATION
100 x 100 SURFACING IN TWO
LAYERS AS PER
SPECIFICATION
CJ
SURFACING FALL
FALL FALL
DEPTH
FALL
PRECAST PC
GIRDER
PRECAST
* NOTE 4 25 THICK PC GIRDER
SUB-BASE FILL SAND/CEMENT SUB STRUCTURE
PVC-U DRAIN 3:1 MORTAR BED
OUT PIPE BEARING BEARING
3
-
CONCRETE HAUNCH
200 x 300
(TYP)
SECTION AT PIER
SCALE 1:50
(WITH EXPANSION JOINT) 1 2021 AMENDMENT - FINAL ISSUE JAN 2022
GR. LVL
(FOR PRE-TENSIONING AND POST-TENSIONING)
No. REVISIONS APP'D DATE
CLIENT
DETAIL 2 DECK SURFACING
SCALE 1:25 FALL
(FOUNDATION TYPE
AS PER DESIGN) *NOTES: CAST IN SITU DECK SLAB
SECTION AT ABUTMENT 1. IN URBAN AREAS, PEDESTRIAN THROUGH ZONES AND CYCLE TRACKS SHALL BE
SCALE 1:75 PROVIDED IN ALIGNMENT WITH THE USDM AND WCMP.
BRIDGE WIDTH
2. DESIGN OF BARRIERS AND KERBS SHALL MEET ALL ROAD DESIGN AND SAFETY
DESIGN REQUIREMENTS FOR THE DESIGN SPEED OF THE ROAD. CONSULTANTS TO
PERMANENT TIMBER STRIPS TITLE
PROVIDE DETAILS OF ALL NECESSARY REQUIREMENTS.
3. FOR BRIDGES THAT ARE USED FOR CYCLISTS' MOVEMENT, CONSULTANT TO
PROVIDE ADDITIONAL DETAILS ABOVE THE BRIDGE BARRIER IN ORDER TO MEET THE
STANDARD DRAWINGS
CB FOOTPATH SH CARRIAGEWAY SH FOOTPATH CB MINIMUM RAILING HEIGHT REQUIREMENT OF 1400 MM.
PRECAST GIRDER
2
- DRAWING TITLE
SURFACING STRUCTURES
FALL
FALL 15 GAP
FALL
DETAIL 3
SAMPLE PRE-CAST
SCALE 1:10 GIRDER BRIDGE DECK DETAILS
PRECAST PC
GIRDER
LEGEND DRAWN . SCALE AS SHOWN
SH : SHOULDER
FP : FOOTPATH CHECKED . DATE .
CB : CONE BARRIER
SECTION AT MID SPAN GR. LVL : GROUND LEVEL APPROVED . SIZE A1
SCALE 1:75
PROJECT DWG.
No. . No. ST-20