You are on page 1of 3

BELL MAKE

TECHNICAL DATA SHEET OF COOLING TOWER (CTI APPROVED)

Country of Origin : India


Manufacturer : Bell Cooling Towers Pvt. Ltd., New Delhi
Type of duty operation : Continuous (24 x7)
Project : Gwalior Airport

Designed Duty Conditions:

Hot Water Temperature : 97.65°F

Cold Water Temperature : 88.00°F

Wet Bulb Temperature : 83.00°F (Design)

Water flow rate : 1250.00 USGPM – Based on the Approved


Daikin Chiller Patrameter

Heat Rejection Capacity : 15,21,200 Kcal/hr

1. Components classification no. : BCTI-090XEC2 (# In Twin Cells)

2. Type : Induced Draught Counter flow

3. Distribution : Gravity flow (static)/Main header and branch arm


system

4. Design wet bulb approach : 5°F

5. Dimensions (mm) # LWH : 5550 x 4635 x 3760

6. Operating wt. (kg) : 8945

7. Fill wetted area (sq.m) : 3716

8. Evaporation loss : 0.91%

9. Drift loss : 0.005%

10. Total water loss : 0.915% (without bleed off)

11. Fan casing dia. (mm) : 2200

12. No. of fans : 2 (One Per Cell)

13. Air flow (CFM) : 80500 CFM per fan x 2

14. Tip velocity (m/min) : 3868


15. Fan material & Type : Cast al. Alloy with MSHDG Hub, Axial flow

16. VFD Operated Motor

HP : 15 HP x 02 Nos. (One Per Cell)


RPM : 570
Type : Squirrel Cage (IP55), TEAO, IE3

17. Motor make : New India (NIEC) / Hindustan

18. Tower structure - Casing : FRP


Basin : FRP

19. Fills : High efficiency PVC 'Film Pack

20. Drift Eliminators : High efficiency PVC 'Drifts Pack

21. Fill support : HOT DIPPED GALVANIZED FRAME

22. Distribution supports : HOT DIPPED GALVANIZED FRAME

23. Bird screen : HOT DIPPED GALVANIZED FRAME

24. Hardware : Stainless Steel

25. Baseframe : M.S.H.D.G.

26. Noise level @ 3 mtr : 75 dBA

*****

You might also like