TECHNICAL INFORMATION
The Johnson Controls YFM high wall fan coils harmonoiusly combine the needs of performance, silence, ease
of installation and simple maintenance, through a range of three models available with elegantly designed infra-
red remote controls and wall-mounted controls.
Johnson Controls take part to the Eurovent program of fan coil performance certification.
The official figures are published in the Eurovent web site (www.eurovent-certification.com).
The tested performances are:
• Cooling total emission at the following conditions: • Heating emission (2 pipe units) at the following conditions:
- Water temperature +7°C E.W.T. +12°C L.W.T. - Entering water temperature +50°C
- Entering air temperature +27°C dry bulb +19°C wet bulb - Entering air temperature +20°C
- Water flow rate as for the cooling conditions
GB 2 02/09
by johnson controls
CONTENTS
02/09 3 GB
by johnson controls
GB 4 02/09
by johnson controls
Eurovent certification
Operating limits
02/09 5 GB
by johnson controls
Cooling emission
Entering air temperature: +27°C dry bulb +19°C wet bulb Relative humidity 47%
Water temperature Water temperature Water temperature Water temperature
Air EWT 5 - LWT 10 EWT 7 - LWT 12 EWT 9 - LWT 14 EWT 12 - LWT 17
Model Speed
flow Water Total Sensible Water Total Sensible Water Total Sensible Water Total Sensible
flow emission emission flow emission emission flow emission emission flow emission emission
m3/h l/h kW kW l/h kW kW l/h kW kW l/h kW kW
High 436 406 2.36 1.74 329 1.91 1.70 244 1.42 1.36 186 1.08 1.08
YFMY(H) 20 Med 376 368 2.14 15.70 298 1.73 1.39 222 1.29 1.22 169 0.98 0.98
Low 334 339 1.97 1.44 275 1.60 1.28 205 1.19 1.12 153 0.89 0.89
High 632 556 3.23 2.37 447 2.60 2.30 335 1.95 1.86 256 1.49 1.49
YFMY(H) 30 Med 522 490 2.85 2.08 397 2.31 1.86 298 1.73 1.63 225 1.31 1.31
Low 403 413 2.40 1.73 335 1.95 1.54 253 1.47 1.35 186 1.08 1.08
High 780 772 4.49 3.32 619 3.60 2.80 476 2.77 2.63 375 2.18 2.18
YFMY(H) 40 Med 691 714 4.15 3.04 583 3.39 2.72 444 2.58 2.40 344 2.00 2.00
Low 570 630 3.66 2.64 516 3.00 2.36 394 2.29 2.08 299 1.74 1.74
High 540 420 2.45 2.00 334 1.95 1.75 284 1.65 1.65 225 1.30 1.30
YFMH 20 V Med 478 387 2.25 1.90 299 1.75 1.60 267 1.55 1.55 212 1.20 1.20
Low 439 361 2.10 1.80 277 1.60 1.45 245 1.45 1.45 203 1.10 1.10
High 600 533 3.10 2.30 430 2.50 2.10 319 1.85 1.85 253 1.50 1.50
YFMH 30 V Med 527 498 2.90 2.20 404 2.35 1.90 298 1.75 1.75 238 1.40 1.40
Low 507 464 2.70 2.05 378 2.20 1.75 283 1.65 1.65 225 1.30 1.30
Heating emission
Entering air temperature: +20°C
Water temperature Water temperature Water temperature
Air EWT 60 - LWT 50 EWT 50 - LWT 40 EWT 45 - LWT 40
Model Speed
flow
Water flow Total emission Water flow Total emission Water flow Total emission
m3/h l/h kW l/h kW l/h kW
High 436 292 3.60 202 2.70 383 2.33
YFMY(H) 20 Med 376 267 3.06 181 2.08 343 1.98
Low 334 244 2.80 166 1.92 314 1.82
High 632 451 4.90 276 3.70 522 3.18
YFMY(H) 30 Med 522 354 4.07 241 2.79 452 2.64
Low 403 293 3.37 200 2.31 377 2.18
High 780 630 6.90 404 4.67 744 4.60
YFMY(H) 40 Med 691 534 6.14 371 4.28 680 3.93
Low 570 462 5.32 322 3.72 588 3.40
High 540 300 3.50 210 2.45 404 2.35
YFMH 20 V Med 478 275 3.20 189 2.20 361 2.10
Low 439 253 2.95 176 2.05 344 2.00
High 600 386 4.40 275 3.20 533 3.10
YFMH 30 V Med 527 357 4.15 245 2.85 490 2.85
Low 507 331 3.85 227 2.65 446 2.60
ºC K
20 0,94
30 0,90
40 0,86
50 0,82
60 0,78
70 0,74
80 0,70 Water
flow l/h
GB 6 02/09
by johnson controls
The YFMH are very high quality units designed for residential application.
The elegance of the aesthetics, the electronic management and the top quality components ensure
perfect integration into the environment and a high level of comfort.
A. MODE
Used to select the mode of operation (cooling, heating,
dehumidifying/dry, fan).
B. ROOM TEMPERATURE SET
Used to set the room temperature or program the timer.
C. FAN ( )
Used to set the fan speed in sequence to automatic, high,
medium, low.
D. SWING
Used to start or stop vertical swing of the louvers or flaps and to
set the required airflow direction upwards or downwards.
E. TIMER
Used to set or cancel timer operation.
F. SLEEP ( )
Used to set or cancel the SLEEP function.
G. SMART ( )
Upon pressing this button the appliance automatically
establishes the most suitable mode of operation to ensure
maximum comfort.
H. SUPER ( )
Used to start or stop fast cooling (fast cooling works with the
fan at high speed and the temperature automatically set at
18°C).
I. ON/OFF
Used to switch the appliance on and off.
Note: the settings continue to appear on the display even with
the fan coil switched off.
02/09 7 GB
by johnson controls
Power supply
(220-240)V ~
Receiver and led display board
50/60Hz
Brown
Fuse I Blue
Yellow/Green
Blue
Red Winter
relay
Brown
Summer
Black relay
AP2 Valve
Printed circuit board relay
Heat
exchanger
Yellow/
Green
Fan motor Transformer
YFMH 40 / YFMH 30 V
sensor sensor
50/60Hz
Switch board
Brown
Blue
Yellow/Green
Blue
Red Winter
relay
Brown
Summer
Black relay
Valve
relay
Heat
exchanger
Yellow/
Green
Fan motor Transformer
GB 8 02/09
by johnson controls
Low speed
Med. speed
High speed
TR TR
LEGEND
02/09 9 GB
by johnson controls
Note: with 4 pipe installations and continuous chilled and hot water supply, it allows the automatic summer/winter
change-over in accordance to the room temperature (-1°C = Winter, +1°C = Summer, Dead Zone 2°C).
ATR ATR
LEGEND
GB 10 02/09
by johnson controls
A maximum of 4 units can be connected together; the units must be of the same size.
TR 9060161
TR
by johnson controls
20° °C
TR
ATR 9060164
ATR
by johnson controls
20° °C
ATR
WARNING: a maximum of 4 units can be connected together; the units must be of the same size.
02/09 11 GB
by johnson controls
Accessories
3 way valve frame
Water flow control kit with 3 way ON-OFF valves with thermoelectric actuator. The kit includes the connection
pipes and the valves. This kit allows the water flow to be diverted from the coil in order to cut out operation.
Description Q.ty
GB 12 02/09
by johnson controls
Accessories
2 way valve
2 way valve ON-OFF
with thermoelectric actuator.
Suitable for the connection with Ø 12mm pipes.
Actuator characteristics:
02/09 13 GB
by johnson controls
Accessories
Frame
Frame for installation of valves (non included).
Change-Over TMM
To be used with the following controls: TR & ATR.
Automatic summer/winter switch to be installed in
contact with the water circuit.
RED
BLACK
The descriptions and illustrations provided in this without the requirement to promptly update this piece
publication are not binding: Johnson Controls reserves of literature, any changes that it considers useful for the
the right, whilst maintaining the essential characteristics of purpose of improvement or for any other manufacturing or
the types described and illustrated, to make, at any time, commercial requirements.
GB 14 02/09