You are on page 1of 16

YFM High Wall

FAN COIL UNITS

TECHNICAL INFORMATION

COOLING CAPACITIES: 1.6 to 3.6 kW


HEATING CAPACITIES: 2.1 to 5.3 kW

by johnson controls TYFMGB 02/09


by johnson controls

YFM High Wall Fan Coil

The Johnson Controls YFM high wall fan coils harmonoiusly combine the needs of performance, silence, ease
of installation and simple maintenance, through a range of three models available with elegantly designed infra-
red remote controls and wall-mounted controls.

YFMY model without infra-red remote control


The YFMY can be operated using the Johnson Controls wall-mounted controls after having completed the
simple electrical connections.

YFMH model with infra-red remote control


The YFMH are operated using the elegantly designed infra-red remote control, providing complete control over
the functions of the unit.

Johnson Controls take part to the Eurovent program of fan coil performance certification.
The official figures are published in the Eurovent web site (www.eurovent-certification.com).
The tested performances are:

• Cooling total emission at the following conditions: • Heating emission (2 pipe units) at the following conditions:
- Water temperature +7°C E.W.T. +12°C L.W.T. - Entering water temperature +50°C
- Entering air temperature +27°C dry bulb +19°C wet bulb - Entering air temperature +20°C
- Water flow rate as for the cooling conditions

• Fan absorption • Water pressure drop • Sound power

GB 2 02/09
by johnson controls

CONTENTS

Constructional characteristics and main components........................................................................................... 4


Dimensions and weights........................................................................................................................................ 4
Eurovent certification.............................................................................................................................................. 5
Operating limits...................................................................................................................................................... 5
Cooling emission.................................................................................................................................................... 6
Heating emission.................................................................................................................................................... 6
Water side pressure drop....................................................................................................................................... 6
Remote control YFMH............................................................................................................................................ 7
Connection terminal block YFMH.......................................................................................................................... 8
Wiring diagrams YFMY........................................................................................................................................... 9
Accessories.......................................................................................................................................................... 12
3 way valve frame................................................................................................................................................. 12
2 way valve........................................................................................................................................................... 13
Frame................................................................................................................................................................... 14
Change-Over TMM............................................................................................................................................... 14
TME low temperature cut-out thermostat............................................................................................................ 14

02/09 3 GB
by johnson controls

Constructional characteristics and main


components

Versions Heat exchange coil


YFMY three models without valves for wired wall Made from copper tubes and aluminium fins; the coil
controls. has two 12mm diameter copper pipe connections.
YFMH three models without valves with IR infra-red Supplied complete with the connectors to be fitted
remote control. at the end of the water pipes and on the fan coil
YFMH-V two models with 3 way fitted valves and connections.
with IR infra-red remote control.
Condensate collection tray
Cabinet Made from plastic, with 16mm OD fitting.
Made from a strong ABS structure with exceptional
mechanical characteristics and excellent resistance Drilling template
to ageing. Each unit is supplied with a paper template for
mounting the unit on the wall.
Filter
Washable-regenerable synthetic filter, readily
accessible.

Fan assembly and electric motor


Tangential fan with three-speed motor, ensuring high
efficiency and minimal noise levels.

Dimensions and weights

Model YFMY(H) 20 YFMY(H) 30 YFMY(H) 40 YFMH 20 V YFMH 30 V


Weight kg 11 11 14 11 14
W mm 830 907 830 907
H mm 285 290 285 290
D mm 189 195 189 195

GB 4 02/09
by johnson controls

Eurovent certification

The following standard rating conditions are used:

Cooling (summer mode) Heating (winter mode)


Air temperature: +27°C dry bulb +19°C wet bulb Air temperature: +20°C
Water temperature: +7°C E.W.T. +12°C L.W.T. Water temperature: +50°C E.W.T.
water flow rate as for the cooling conditions

Models without valve (accessory on request)


Model YFMY(H) 20 YFMY(H) 30 YFMY(H) 40
Speed 1 2 3 1 2 3 1 2 3
Air flow m3/h 334 376 436 403 522 632 570 691 780
Cooling total emission kW 1.60 1.73 1.91 1.95 2.31 2.60 3.00 3.39 3.60
Cooling sensible emission kW 1.28 1.39 1.70 1.54 1.86 2.30 2.36 2.72 2.80
Heating kW 2.07 2.22 3.05 2.50 3.00 4.15 4.05 4.52 5.30
∆p Cooling kPa 5.0 6.0 7.0 6.0 9.0 11.0 9.0 12.0 14.0
∆p Heating kPa 4.0 6.0 7.0 4.0 6.0 7.0 9.0 11.0 14.0
Fan W 22 24 26 36 38 42 36 38 47
Sound power Lw dBA dB(A) 31 37 46 34 40 48 43 48 55
Sound pressure Lp dBA * dB(A) 27 30 35 30 33 37 39 41 44

Models with fitted valve


Model YFMH 20 V YFMH 30 V
Speed 1 2 3 1 2 3
Air flow m /h
3
439 478 540 507 527 600
Cooling total emission kW 1.60 1.75 1.95 2.20 2.35 2.50
Cooling sensible emission kW 1.45 1.60 1.75 1.75 1.90 2.10
Heating kW 2.95 3.20 3.50 3.85 4.15 4.50
∆p Cooling kPa 13.0 15.0 18.0 18.0 22.0 25.0
∆p Heating kPa 9.0 14.0 17.0 14.0 16.0 19.0
Fan W 40 42 46 48 50 60
Sound power Lw dBA dB(A) 47 51 55 53 56 60
Sound pressure Lp dBA * dB(A) 38 42 44 45 47 49

* Sound pressure in open field conditions at 1 metre from front of unit

Operating limits

MIN. entering water temperature: +5°C


Water flow MAX. working pressure: 8 bar
MAX. entering water temperature: +60°C
MIN. entering air temperature: +6°C
Air flow Suitable relative humidity 25-85%
MAX. entering air temperature: +40°C
Supply Single phase 220-240V / 1 / 50Hz
MIN. height: 2,3 m
Installation
MAX. height: 3,2 m

02/09 5 GB
by johnson controls

Cooling emission
Entering air temperature: +27°C dry bulb +19°C wet bulb Relative humidity 47%
Water temperature Water temperature Water temperature Water temperature
Air EWT 5 - LWT 10 EWT 7 - LWT 12 EWT 9 - LWT 14 EWT 12 - LWT 17
Model Speed
flow Water Total Sensible Water Total Sensible Water Total Sensible Water Total Sensible
flow emission emission flow emission emission flow emission emission flow emission emission
m3/h l/h kW kW l/h kW kW l/h kW kW l/h kW kW
High 436 406 2.36 1.74 329 1.91 1.70 244 1.42 1.36 186 1.08 1.08
YFMY(H) 20 Med 376 368 2.14 15.70 298 1.73 1.39 222 1.29 1.22 169 0.98 0.98
Low 334 339 1.97 1.44 275 1.60 1.28 205 1.19 1.12 153 0.89 0.89
High 632 556 3.23 2.37 447 2.60 2.30 335 1.95 1.86 256 1.49 1.49
YFMY(H) 30 Med 522 490 2.85 2.08 397 2.31 1.86 298 1.73 1.63 225 1.31 1.31
Low 403 413 2.40 1.73 335 1.95 1.54 253 1.47 1.35 186 1.08 1.08
High 780 772 4.49 3.32 619 3.60 2.80 476 2.77 2.63 375 2.18 2.18
YFMY(H) 40 Med 691 714 4.15 3.04 583 3.39 2.72 444 2.58 2.40 344 2.00 2.00
Low 570 630 3.66 2.64 516 3.00 2.36 394 2.29 2.08 299 1.74 1.74
High 540 420 2.45 2.00 334 1.95 1.75 284 1.65 1.65 225 1.30 1.30
YFMH 20 V Med 478 387 2.25 1.90 299 1.75 1.60 267 1.55 1.55 212 1.20 1.20
Low 439 361 2.10 1.80 277 1.60 1.45 245 1.45 1.45 203 1.10 1.10
High 600 533 3.10 2.30 430 2.50 2.10 319 1.85 1.85 253 1.50 1.50
YFMH 30 V Med 527 498 2.90 2.20 404 2.35 1.90 298 1.75 1.75 238 1.40 1.40
Low 507 464 2.70 2.05 378 2.20 1.75 283 1.65 1.65 225 1.30 1.30

Heating emission
Entering air temperature: +20°C
Water temperature Water temperature Water temperature
Air EWT 60 - LWT 50 EWT 50 - LWT 40 EWT 45 - LWT 40
Model Speed
flow
Water flow Total emission Water flow Total emission Water flow Total emission
m3/h l/h kW l/h kW l/h kW
High 436 292 3.60 202 2.70 383 2.33
YFMY(H) 20 Med 376 267 3.06 181 2.08 343 1.98
Low 334 244 2.80 166 1.92 314 1.82
High 632 451 4.90 276 3.70 522 3.18
YFMY(H) 30 Med 522 354 4.07 241 2.79 452 2.64
Low 403 293 3.37 200 2.31 377 2.18
High 780 630 6.90 404 4.67 744 4.60
YFMY(H) 40 Med 691 534 6.14 371 4.28 680 3.93
Low 570 462 5.32 322 3.72 588 3.40
High 540 300 3.50 210 2.45 404 2.35
YFMH 20 V Med 478 275 3.20 189 2.20 361 2.10
Low 439 253 2.95 176 2.05 344 2.00
High 600 386 4.40 275 3.20 533 3.10
YFMH 30 V Med 527 357 4.15 245 2.85 490 2.85
Low 507 331 3.85 227 2.65 446 2.60

Water side pressure drop


Pressure drop for mean water temperature of 10°C; ∆p - kPa
for different temperatures multiply the pressure drop
figure by the K correction factors in the table.

ºC K
20 0,94
30 0,90
40 0,86
50 0,82
60 0,78
70 0,74
80 0,70 Water
flow l/h

GB 6 02/09
by johnson controls

YFMH Infra-red remote control

The YFMH are very high quality units designed for residential application.
The elegance of the aesthetics, the electronic management and the top quality components ensure
perfect integration into the environment and a high level of comfort.

A. MODE
Used to select the mode of operation (cooling, heating,
dehumidifying/dry, fan).
B. ROOM TEMPERATURE SET
Used to set the room temperature or program the timer.
C. FAN ( )
Used to set the fan speed in sequence to automatic, high,
medium, low.
D. SWING
Used to start or stop vertical swing of the louvers or flaps and to
set the required airflow direction upwards or downwards.
E. TIMER
Used to set or cancel timer operation.
F. SLEEP ( )
Used to set or cancel the SLEEP function.
G. SMART ( )
Upon pressing this button the appliance automatically
establishes the most suitable mode of operation to ensure
maximum comfort.
H. SUPER ( )
Used to start or stop fast cooling (fast cooling works with the
fan at high speed and the temperature automatically set at
18°C).
I. ON/OFF
Used to switch the appliance on and off.
Note: the settings continue to appear on the display even with
the fan coil switched off.

Indicator symbols on the liquid crystal display:


Signal transmission Automatic fan speed
Cooling High speed
Dry/dehumidifying Medium speed
Fan Low speed
Heating
SUPER cooling Used to adjust the temperature
SMART in the SMART mode
SLEEP or the Dry/dehumidifying level

02/09 7 GB
by johnson controls

Connection terminal block


YFMH 20/30 / YFMH 20 V

Battery temperature sensor


Room temperature sensor Yellow/Green

Power supply
(220-240)V ~
Receiver and led display board

50/60Hz
Brown
Fuse I Blue

Yellow/Green
Blue
Red Winter
relay
Brown
Summer
Black relay

AP2 Valve
Printed circuit board relay

Heat
exchanger

Yellow/
Green
Fan motor Transformer

Swing motor YFM

YFMH 40 / YFMH 30 V

Battery Room Receiver


temperature temperature and led display board Yellow/Green
Power supply
(220-240)V ~

sensor sensor
50/60Hz

Switch board
Brown
Blue

Yellow/Green
Blue
Red Winter
relay
Brown
Summer
Black relay
Valve
relay

Heat
exchanger

Yellow/
Green
Fan motor Transformer

Swing motor YFM

GB 8 02/09
by johnson controls

YFMY Model - Electrical connections


Wiring diagram
YFMY

Low speed
Med. speed
High speed

Electrical connections with Johnson Controls electronic controls Identification Code


TR 9060161

- Manual speed switch.


- Manual Summer/Winter switch.
by johnson controls
- Electronic thermostat for fan control (ON-OFF).
- Electronic thermostat for valve(s) control (ON-OFF) (the fan keeps
20° °C working).
- It allows to control the low temperature cut-out thermostat (TME).
- It allows to install the Summer/Winter switch centralized and remote,
or to control it with an automatic change-over fitted on the water pipe
(for 2 pipe installations only). The latter case needs the adjustment of
the jumper on the control board (see the instruction leaflet supplied
with the control).

Without valves YFMY With 1 valve YFMY

TR TR

LEGEND

YFMY = YFMY electrical board


TR = TR electrical board
ATR = ATR electrical board
CH = Remote Summer/Winter switch
E= Valve set (2 pipe installation)

02/09 9 GB
by johnson controls

YFMY Model - Electrical connections

Electrical connections with Johnson Controls electronic controls Identification Code


ATR 9060164

Same characteristics as TR, adding:


- Manual or automatic speed switch.
by johnson controls
- Electronic thermostat for fan control (ON-OFF).
- Electronic thermostat for valve(s) control (ON-OFF).
20° °C - Simultaneus thermostatic control of the valves and fan (ON-OFF).
- It allows to install the Summer/Winter switch centralized and remote,
or to control it with an automatic change-over fitted on the water pipe
(for 2 pipe installations only). The latter case needs the adjustment of
the jumper on the control board (see the instruction leaflet supplied
with the control).

Note: with 4 pipe installations and continuous chilled and hot water supply, it allows the automatic summer/winter
change-over in accordance to the room temperature (-1°C = Winter, +1°C = Summer, Dead Zone 2°C).

Without valves YFMY With 1 valve YFMY

ATR ATR

LEGEND

YFMY = YFMY electrical board


TR = TR electrical board
ATR = ATR electrical board
CH = Remote Summer/Winter switch
E= Valve set (2 pipe installation)

GB 10 02/09
by johnson controls

YFMY Model - Electrical connections


Electrical connections of more units with Johnson Controls electronic controls

A maximum of 4 units can be connected together; the units must be of the same size.

Identification Code YFMY YFMY YFMY YFMY

TR 9060161

TR

by johnson controls

20° °C

YFMY YFMY YFMY YFMY

TR

Identification Code YFMY YFMY YFMY YFMY

ATR 9060164

ATR

by johnson controls

20° °C

YFMY YFMY YFMY YFMY

ATR

WARNING: a maximum of 4 units can be connected together; the units must be of the same size.

02/09 11 GB
by johnson controls

Accessories
3 way valve frame
Water flow control kit with 3 way ON-OFF valves with thermoelectric actuator. The kit includes the connection
pipes and the valves. This kit allows the water flow to be diverted from the coil in order to cut out operation.

Description Q.ty

A. 3 way valve kit with support 1


B. Paper installation template 1
C. Spacer 1
D. Adhesive insulation for fan coil base 1
E. Condensate drain pipe 1
F. Insulation for condensate drain pipe 1
G. Expansion plugs with screws 4
H. Plastic strap 1
I. Screws M5 x 6,5 2
L. Supporting bracket (mod. 20 and 30) 1
M. Screws 3,5 x 6,5 1
N. Screw M5 x 10 (mod. 40) 1
∆p - kPa O. Supporting bracket (mod. 40) 1
P. Supporting bracket (mod. 40) 1
Instructions 1

3 way valve technical data

MAX. operating temperature 100ºC


Actuator movement 2,5 mm
Power supply 230 V
Power supply cable 0,6 mt
Input 5W
Regulation signal ON-OFF
Ambient operating temperature 0 ÷ 50°C
Thrust 180 N (40 lbs)
Max. differential pressure:
- Maximum aperture flow coefficient 1,7 Kvs
- By-pass flow coefficient 1,5 Kvs
Reaction time (in operation) 2 - 4 min.
Protection IP 42
Heating element PTC
Water flow l/h Weight 0,13 kg

GB 12 02/09
by johnson controls

Accessories
2 way valve
2 way valve ON-OFF
with thermoelectric actuator.
Suitable for the connection with Ø 12mm pipes.

Actuator characteristics:

- Max. ambient temperature: 50°C


- Supply: 230 V - 50/60 Hz
- Power: 5W
- Protection: IP 44
- Reaction time: approx. 4 min.
- Max. glycol content of water: 50%

Valves characteristics: ∆p - kPa

- Max. rated pressure: 16 bar


- Kvs: 1,7
- Maximum pressure difference
for valve to close (∆pmax): 80 kPa
- Valve connection (external thread): 1/2”

Water flow l/h

02/09 13 GB
by johnson controls

Accessories
Frame
Frame for installation of valves (non included).

Change-Over TMM
To be used with the following controls: TR & ATR.
Automatic summer/winter switch to be installed in
contact with the water circuit.

RED

BLACK

TME low temperature cut-out thermostat


To be used with the following controls: TR & ATR.
To be fitted between the coil fins.
It stops the fan when the water temperature is lower
than 38°C and it starts the fan when is higher than
42°C.

The descriptions and illustrations provided in this without the requirement to promptly update this piece
publication are not binding: Johnson Controls reserves of literature, any changes that it considers useful for the
the right, whilst maintaining the essential characteristics of purpose of improvement or for any other manufacturing or
the types described and illustrated, to make, at any time, commercial requirements.

GB 14 02/09
by johnson controls

NOTES

02/09 15 GB
www.johnsoncontrols.com TYFMGB 02/09