‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪DKG - 207‬‬
‫ﻛﻨﺘﺮﻟﺮ ﺍﺿﻄﺮﺍﺭﻱ ﻭ ﺍﺳﺘﺎﺭﺕ ﺍﺗﻮﻣﺎﺗﻴﻚ‬

‫ﺍﻣﻜﺎﻧﺎﺕ‬
‫ﭘﺸﺘﻴﺒﺎﻧﻲ ﻣﻮﺗﻮﺭﻫﺎﻱ ﮔﺎﺯﺳﻮﺯ‬ ‫•‬ ‫ﻗﻄﻊ ﺑﺮﻕ ﺍﺗﻮﻣﺎﺗﻴﮏ‬ ‫•‬
‫ﺷﻤﺎﺭﻧﺪﻩ ﻫﺎﯼ ﺁﻣﺎﺭﯼ‬ ‫•‬ ‫ﮐﻨﺘﺮﻝ ﻣﻮﺗﻮﺭ‬ ‫•‬
‫ﭘﺎﺭﺍﻣﺘﺮﻫﺎﯼ ﻗﺎﺑﻞ ﺗﻨﻈﻴﻢ‬ ‫•‬ ‫ﻣﺤﺎﻓﻈﺖ ﮊﻧﺮﺍﺗﻮﺭ‬ ‫•‬
‫ﭘﻮﺭﺕ ﺳﺮﻳﺎﻝ ﺩﻳﺠﻴﺘﺎﻝ‬ ‫•‬ ‫ﺍﺧﻄﺎﺭﻫﺎ ﻭ ﺁﻻﺭﻡ ﻫﺎﯼ ﺩﺍﺧﻠﯽ‬ ‫•‬
‫ﭘﻮﺭﺕ ﺳﺮﻳﺎﻝ ‪RS-232‬‬ ‫•‬ ‫ﻭﺭﻭﺩﯼ ﻫﺎﯼ ﻭﻟﺘﺎﮊ ﺑﺮﻕ ‪ ۳‬ﻓﺎﺯ‬ ‫•‬
‫ﻧﻈﺎﺭﺕ ﺍﺯ ﺭﺍﻩ ﺩﻭﺭ ﺑﻪ ﻃﺮﻳﻖ‪ :‬ﻣﺤﻠﯽ ‪ ،‬ﺷﺒﮑﻪ ‪ ،‬ﺍﻳﻨﺘﺮﻧﺖ ﻭ ﻣﻮﺩﻡ‬ ‫•‬ ‫ﻭﺭﻭﺩﯼ ﻫﺎﯼ ﻭﻟﺘﺎﮊ ﮊﻧﺮﺍﺗﻮﺭ ﺗﻜﻔﺎﺯ‬ ‫•‬
‫ﻧﻈﺎﺭﺕ ‪ ،‬ﻗﺮﺍﺋﺖ ﭘﺎﺭﺍﻣﺘﺮﻫﺎ‬ ‫•‬ ‫ﻭﺭﻭﺩﯼ ﻫﺎﯼ ﺗﺮﺍﻧﺲ ﺟﺮیﺎﻥ)‪ (CT‬ﮊﻧﺮﺍﺗﻮﺭ ﺗﻜﻔﺎﺯ‬ ‫•‬
‫ﻧﻤﺎﻳﺸﮕﺮ ﻫﺎﯼ ‪LED‬‬ ‫•‬ ‫ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﯼ ﻓﺸﺎﺭ ﺭﻭﻏﻦ ﻣﻮﺗﻮﺭ‬ ‫•‬
‫ﻭﺭﻭﺩﯼ ﻫﺎﯼ ﺁﻧﺎﻟﻮﮒ ﻗﺎﺑﻞ ﭘﻴﮑﺮﺑﻨﺪﯼ ‪۲ :‬‬ ‫•‬ ‫ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﯼ ﺩﻣﺎﯼ ﻣﺎیﻊ ﺧﻨﮏ ﮐﻨﻨﺪﻩ ﻣﻮﺗﻮﺭ‬ ‫•‬
‫ﻭﺭﻭﺩﯼ ﻫﺎﯼ ﺩﻳﺠﻴﺘﺎﻝ ﻗﺎﺑﻞ ﭘﻴﮑﺮﺑﻨﺪﯼ ‪۵ :‬‬ ‫•‬ ‫ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﯼ ﺗﻮﺍﻥ ﺍﮐﺘﻴﻮ ﮊﻧﺮﺍﺗﻮﺭ‬ ‫•‬
‫ﺧﺮﻭﺟﯽ ﻫﺎﯼ ﺭﻟﻪ ﺍﯼ ﻗﺎﺑﻞ ﭘﻴﮑﺮﺑﻨﺪﯼ ‪۲ :‬‬ ‫•‬ ‫ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﯼ ﺿﺮیﺐ ﺗﻮﺍﻥ ﻣﻮﺗﻮﺭ‬ ‫•‬
‫ﻗﺎﺑﻠﻴﺖ ﮔﺴﺘﺮﺵ ﻭﺭﻭﺩﯼ ﻭ ﺧﺮﻭﺟﯽ ﻫﺎ‬ ‫•‬ ‫ﻧﺸﺎﻧﮕﺮ ﺩﺭﺧﻮﺍﺳﺖ ﺗﻌﻤﻴﺮ ﺩﻭﺭﻩ ﺍﯼ‬ ‫•‬
‫ﺍﺑﻌﺎﺩ ‪130x100139 mm:‬‬ ‫•‬ ‫ﻣﺠﻤﻮﻉ ﺧﺮﻭﺟﯽ ﻫﺎﯼ ﺭﻟﻪ ﺍﯼ ‪۶ :‬‬ ‫•‬
‫ﻗﻄﻊ ﺍﺳﺘﺎﺭﺕ‬ ‫•‬ ‫ﻗﺎﺑﻠﻴﺖ ﺍﺳﺘﺎﺭﺕ ﺍﺯ ﺭﺍﻩ ﺩﻭﺭ‬ ‫•‬

‫‪1‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫ﻓﻬﺮﺳﺖ‬

‫‪ -۱‬ﻧﺼﺐ‬
‫‪ ۱-۱‬ﻣﻌﺮﻓﻲ ﻛﻨﺘﺮﻟﺮ‬
‫‪ ۱-۲‬ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ‬
‫‪ -۲‬ﻭﺭﻭﺩﻱ ﻫﺎ ﻭ ﺧﺮﻭﺟﻲ ﻫﺎ‬
‫‪ -۳‬ﺻﻔﺤﻪ ﻧﻤﺎﻳﺶ‬
‫‪ LED ۳-۱‬ﻫﺎﻱ ﺻﻔﺤﻪ ﻧﻤﺎﻳﺶ‬
‫‪ ۳-۲‬ﻧﻤﺎﻳﺸﮕﺮ ﺩﻳﺠﻴﺘﺎﻟﻲ‬
‫‪ -۴‬ﺁﻻﺭﻡ ﻫﺎ ﻭ ﻫﺸﺪﺍﺭﻫﺎ‬
‫‪ -۵‬ﺣﺎﻟﺘﻬﺎﻱ ﻋﻤﻠﻴﺎﺗﻲ‬
‫‪ -۶‬ﺩﻳﮕﺮ ﺧﺼﻮﺻﻴﺎﺕ‬
‫‪ ۶-۱‬ﻋﻤﻠﮑﺮﺩ ﺑﻪ ﺻﻮﺭﺕ ‪Remote Start‬‬
‫‪ ۶-۲‬ﺍﻧﺘﺨﺎﺏ ﻧﻮﻉ ﺳﻨﺴﻮﺭ‬
‫‪ ۶-۳‬ﮔﺮﻡ ﮐﺮﺩﻥ ﻣﻮﺗﻮﺭ‬
‫‪ ۶-۴‬ﻧﻤﺎﻳﺸﮕﺮ ﺳﺮﻭﻳﺲ ﺩﻭﺭﻩ ﺍﻱ‬
‫‪ ۶-۵‬ﺳﺎﻋﺖ ﻛﺎﺭﻛﺮﺩ ﻣﻮﺗﻮﺭ‬
‫‪ ۶-۶‬ﺍﺭﺗﺒﺎﻁ ﺑﺎ ﻣﻮﺩﻡ‬
‫‪Remote Monitoring And Programming ۶-۷‬‬
‫‪ ۶-۸‬ﻛﺎﺭﻛﺮﺩ ﻧﻮﺑﺘﻲ‬
‫‪Exerciser ۶-۹‬‬
‫‪ ۶-۱۰‬ﻛﻨﺘﺮﻝ ﺳﻠﻮﻧﻮﺋﻴﺪ ﮔﺎﺯ ﻣﻮﺗﻮﺭﻫﺎﻱ ﮔﺎﺯﺳﻮﺯ‬

‫‪2‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫ﻓﻬﺮﺳﺖ‬

‫‪ -۷‬ﺷﻤﺎﺭﻧﺪﻩ ﻫﺎﯼ ﺁﻣﺎﺭﯼ‬


‫‪ -۸‬ﻧﮕﻬﺪﺍﺭﻱ‬
‫‪ -۹‬ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ ﻛﻨﺘﺮﻟﺮ‬
‫‪ -۱۰‬ﺭﻓﻊ ﻋﻴﺐ‬
‫‪ -۱۱‬ﺍﻋﻼﻡ ﺗﻄﺎﺑﻖ ﻫﺎ‬
‫‪ -۱۲‬ﻣﺸﺨﺼﺎﺕ ﻓﻨﻲ‬
‫‪ -۱۳‬ﺩﻳﺎﮔﺮﺍﻡ ﻧﺼﺐ‬

‫ﺧﻮﺍﻫﺸﻤﻨﺪ ﺍﺳﺖ ﺟﻬﺖ ﺩﺭﻳﺎﻓﺖ ﺍﻃﻼﻋﺎﺕ ﺑﻴﺸﺘﺮ ﺑﺎ ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ ﻧﻤﺎﻳﻨﺪﮔﻲ ﺍﻧﺤﺼﺎﺭﻱ‬
‫ﻣﺤﺼﻮﻻﺕ ‪ DATACOM‬ﺗﺮﻛﻴﻪ ﺩﺭ ﺍﻳﺮﺍﻥ ﻭ ﻣﻨﻄﻘﻪ ﺧﻠﻴﺞ ﻓﺎﺭﺱ ﺗﻤﺎﺱ ﺣﺎﺻﻞ‬
‫ﻓﺮﻣﺎﻳﻴﺪ‪.‬‬
‫ﺗﻠﻔﻦ ‪۰۲۱-۲۲۸۸۳۱۶۹ – ۷۰:‬‬
‫ﭘﺴﺖ ﺍﻟﻜﺘﺮﻭﻧﻴﻜﻲ ‪sales@dornamehr.com :‬‬

‫‪3‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪ ۱-۱‬ﻣﻌﺮﻓﯽ ﻛﻨﺘﺮﻟﺮ‬

‫ﺳﻴﺴﺘﻢ ﺍﺭﺍﺋﻪ ﺷﺪﻩ ﮐﻨﺘﺮﻝ ﻭ ﺣﻔﺎﻇﺖ ﺍﺯ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ ﺭﺍ ﺑﺮ ﻋﻬﺪﻩ ﺩﺍﺭﺩ ‪ .‬ﮐﺎﺭﺑﺮﯼ ﻭ ﻧﺼﺐ ﻳﻮﻧﻴﺖ ﻃﺮﺍﺣﯽ‬
‫ﺷﺪﻩ ﺑﺴﻴﺎﺭ ﺭﺍﺣﺖ ﻣﯽ ﺑﺎﺷﺪ ﻭ ﻣﻌﻤﻮﻻ ﻧﻴﺎﺯﯼ ﺑﻪ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ ﺁﻥ ﻭﺟﻮﺩ ﻧﺪﺍﺭﺩ ﻭ ﻣﻘﺎﺩﻳﺮ ﭘﻴﺶ ﻓﺮﺽ ﺁﻥ‬
‫ﺑﺮﺍﯼ ﺑﻴﺸﺘﺮ ﮐﺎﺭﺑﺮﺩﻫﺎ ﻣﻨﺎﺳﺐ ﻣﯽ ﺑﺎﺷﻨﺪ ‪ .‬ﭘﺎﺭﺍﻣﺘﺮﻫﺎﯼ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ ﺍﻳﻦ ﻛﻨﺘﺮﻟﺮ‪ ،‬ﮐﻨﺘﺮﻝ ﮐﺎﻣﻞ ﺩﻳﺰﻝ‬
‫ﮊﻧﺮﺍﺗﻮﺭ ﺭﺍ ﻣﻤﮑﻦ ﻣﯽ ﺳﺎﺯﺩ ‪ .‬ﭘﺎﺭﺍﻣﺘﺮﻫﺎﯼ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ ﺁﻥ ﺑﺮ ﺭﻭﯼ ﺣﺎﻓﻈﻪ ﻣﻮﻗﺖ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ ﻣﯽ‬
‫ﺷﻮﻧﺪ ‪ ،‬ﭘﺎﺭﺍﻣﺘﺮﻫﺎ ﺑﺮﻧﺎﻣﻪ ﺩﺍﺩﻩ ﺷﺪﻩ ﺩﺭ ﺣﺎﻓﻈﻪ ﻏﻴﺮ ﻓﺮﺍﺭ ﺫﺧﻴﺮﻩ ﺷﺪﻩ ﻭ ﺣﺘﻲ ﺩﺭ ﺻﻮﺭﺕ ﻗﻄﻌﻲ ﻛﺎﻣﻞ ﺑﺮﻕ‬
‫ﺑﺎﻗﻲ ﺧﻮﺍﻫﺪ ﻣﺎﻧﺪ ‪.‬‬

‫ﭘﺎﺭﺍﻣﺘﺮﻫﺎﯼ ﻗﺎﺑﻞ ﺍﻧﺪﺍﺯﯼ ﮔﻴﺮﯼ ﻋﺒﺎﺭﺗﻨﺪ ﺍﺯ ‪:‬‬


‫‪ -‬ﻭﻟﺘﺎﮊﺍﺻﻠﯽ ﻓﺎﺯ ‪R‬‬
‫‪ -‬ﻭﻟﺘﺎﮊﺍﺻﻠﯽ ﻓﺎﺯ ‪S‬‬
‫‪ -‬ﻭﻟﺘﺎﮊﺍﺻﻠﯽ ﻓﺎﺯ ‪T‬‬
‫‪ -‬ﻭﻟﺘﺎﮊ ﺑﻴﻦ ﻓﺎﺯﻫﺎﯼ ‪R-S‬‬
‫‪ -‬ﻭﻟﺘﺎﮊ ﺑﻴﻦ ﻓﺎﺯﻫﺎﯼ ‪S-T‬‬
‫‪ -‬ﻭﻟﺘﺎﮊ ﺑﻴﻦ ﻓﺎﺯﻫﺎﯼ ‪T-R‬‬
‫‪ -‬ﻭﻟﺘﺎﮊﻓﺎﺯ ‪ U‬ﮊﻧﺮﺍﺗﻮﺭ‬
‫‪ -‬ﻓﺮﮐﺎﻧﺲ ﮊﻧﺮﺍﺗﻮﺭ‬
‫‪ -‬ﺟﺮﻳﺎﻥ ﻓﺎﺯ ‪ U‬ﮊﻧﺮﺍﺗﻮﺭ‬
‫‪ KW -‬ﻓﺎﺯ ‪ U‬ﮊﻧﺮﺍﺗﻮﺭ‬
‫‪ Cos ø‬ﻓﺎﺯ ‪ U‬ﮊﻧﺮﺍﺗﻮﺭ‬ ‫‪-‬‬
‫‪ -‬ﻭﻟﺘﺎﮊ ﺑﺎﻃﺮﯼ‬
‫‪ -‬ﺩﻣﺎﯼ ﺳﺮﺩﮐﻨﻨﺪﻩ‬
‫‪ -‬ﻓﺸﺎﺭ ﺭﻭﻏﻦ‬

‫‪4‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪ ۱-۲‬ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪:‬‬


‫ﺍﻳﻦ ﻛﻨﺘﺮﻟﺮ ﺑﺮﺍﻱ ﻧﺼﺐ ﺑﻪ ﺻﻮﺭﺕ ﺗﺎﺑﻠﻮﻳﻲ ﻃﺮﺍﺣﯽ ﺷﺪﻩ ﺍﺳﺖ ﻭ ﮐﺎﺭﺑﺮ ﻧﺒﺎﻳﺪ ﺑﻪ ﺟﺰ ﻗﺴﻤﺖ ﺟﻠﻮﯼ‬
‫ﻛﻨﺘﺮﻟﺮ ﺑﻪ ﺑﻘﻴﻪ ﺍﺟﺰﺍﺀ ﺩﺳﺘﺮﺳﯽ ﺩﺍﺷﺘﻪ ﺑﺎﺷﺪ ‪.‬‬
‫ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ﻣﯽ ﺑﺎﻳﺴﺖ ﺑﻪ ﺻﻮﺭﺕ ﻋﻤﻮﺩﯼ ﺑﺮ ﺭﻭﯼ ﻳﮏ ﺳﻄﺢ ﺗﺨﺖ ﺑﺎﺷﺪ ‪.‬‬
‫ﺍﺑﻌﺎﺩ ﻛﻨﺘﺮﻟﺮ ‪ ۱۱۶×۸۶‬ﻣﻴﻠﻴﻤﺘﺮ ﻣﻲ ﺑﺎﺷﺪ‪ .‬ﻭ ﻻﺯﻡ ﺍﺳﺖ ﮐﻪ ﺍﻳﻦ ﺍﺑﻌﺎﺩ ﺩﺭ ﺍﺑﺘﺪﺍ ﺑﺮ ﺭﻭﯼ ﺗﺎﺑﻠﻮ ﻣﺸﺨﺺ‬
‫ﮔﺮﺩﻳﺪﻩ ﻭ ﺑﻌﺪ ﻛﻨﺘﺮﻟﺮ ﺭﺍ ﺟﺎ ﮔﺬﺍﺭﯼ ﻧﻤﺎﻳﻴﺪ‪.‬‬

‫ﻧﮑﺘﻪ ‪ :‬ﺑﺮﺍﯼ ﻋﻤﻠﮑﺮﺩ ﺻﺤﻴﺢ ﻛﻨﺘﺮﻟﺮ ‪ ،‬ﻣﯽ ﺑﺎﻳﺴﺖ ﺑﺪﻧﻪ ﻣﻮﺗﻮﺭ ﺯﻣﻴﻦ ﺷﻮﺩ ﺩﺭ ﻏﻴﺮ‬
‫ﺍﻳﻦ ﺻﻮﺭﺕ ﻣﻤﻜﻦ ﺍﺳﺖ ﻣﻘﺎﺩﻳﺮ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺷﺪﻩ ﻭﻟﺘﺎﮊ ﻭ ﻓﺮﮐﺎﻧﺲ ﺻﺤﻴﺢ ﻧﺒﺎﺷﻨﺪ ‪.‬‬

‫ﺧﺮﻭﺟﯽ ﺗﺮﺍﻧﺲ ﺟﺮﻳﺎﻥ ﻣﯽ ﺑﺎﻳﺴﺖ ‪ ۵‬ﺁﻣﭙﺮ ﺑﺎﺷﺪ ‪ ،‬ﺑﺎﺯﻩ ﺟﺮﻳﺎﻥ ﺑﺮ ﺣﺴﺐ ﻧﻴﺎﺯ ﻗﺎﺑﻞ ﺗﻨﻈﻴﻢ ﺍﺳﺖ )ﺑﻴﻦ‬
‫‪ ۱۰/۵‬ﻭ ‪ (۹۰۰۰ /۵‬ﺧﺮﻭﺟﯽ ﻫﺮ ﺗﺮﺍﻧﺲ ﺟﺮﻳﺎﻥ ﻣﯽ ﺑﺎﻳﺴﺖ ﺑﻪ ﻭﺳﻴﻠﻪ ﺯﻭﺝ ﮐﺎﺑﻞ ﺟﺪﺍﮔﺎﻧﻪ ﺍﻱ ﺑﻪ‬
‫ﺳﻴﺴﺘﻢ ﻣﺘﺼﻞ ﺷﻮﺩ ﻭ ﺑﺎﺯﻩ ﺗﻐﺬﻳﻪ ﻣﻮﺭﺩ ﻧﻴﺎﺯ ﺑﺮﺍﯼ ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮ ﺣﺪﺍﻗﻞ ‪ 5VA‬ﺑﺎﺷﺪ ﻭ ﺍﺳﺘﻔﺎﺩﻩ ﺍﺯ‬
‫ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮﻫﺎﯼ ﺑﺎ ﺩﻗﺖ ‪ ۱‬ﺩﺭﺻﺪ ﺗﻮﺻﻴﻪ ﻣﯽ ﺷﻮﺩ ‪.‬‬

‫ﺍﮔﺮ ﻫﻤﻪ ﺳﻨﺴﻮﺭﻫﺎﯼ ﺁﻧﺎﻟﻮﮒ ﺑﻪ ﻛﻨﺘﺮﻟﺮ ﺍﺻﻠﯽ ﻭﺻﻞ ﺑﺎﺷﻨﺪ ﺍﺳﺘﻔﺎﺩﻩ ﺍﺯ ﻧﻤﺎﻳﺸﮕﺮ ﮐﻤﮑﯽ ﻣﻘﺪﻭﺭ ﻧﻤﻲ‬
‫ﺑﺎﺷﺪ ‪ ،‬ﺑﻪ ﻋﺒﺎﺭﺕ ﺩﻳﮕﺮ ﻛﻨﺘﺮﻟﺮ ﻣﻤﮑﻦ ﺍﺳﺖ ﺻﺪﻣﻪ ﺑﺒﻴﻨﺪ ‪ .‬ﺍﮔﺮ ﻧﻤﺎﻳﺸﮕﺮ ﻓﺸﺎﺭ ﻭ ﺩﻣﺎ ﺩﺭ ﮐﻨﺘﺮﻝ ﭘﻨﻞ‬
‫ﮊﻧﺮﺍﺗﻮﺭ ﻭﺟﻮﺩ ﺩﺍﺭﻧﺪ ‪ ،‬ﺳﻨﺴﻮﺭﻫﺎ ﺭﺍ ﺑﻪ ﻛﻨﺘﺮﻟﺮ ﻭﺻﻞ ﻧﮑﻨﻴﺪ ‪.‬ﺗﻨﻈﻴﻤﺎﺕ ﮐﺎﺭﺧﺎﻧﻪ ﺟﻬﺖ ﺳﻨﺴﻮﺭﻫﺎﯼ‬
‫ﻛﻨﺘﺮﻟﺮﺍﺯ ﻧﻮﻉ ‪ VDO‬ﻣﯽ ﺑﺎﺷﻨﺪ ‪ .‬ﻟﺬﺍ ﺍﻧﺘﺨﺎﺏ ﺳﻨﺴﻮﺭﻫﺎﻳﻲ ﻣﺘﻔﺎﻭﺕ ﺍﺯ ﻃﺮﻳﻖ ﻣﻨﻮﯼ ﻛﻨﺘﺮﻟﺮ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ‬
‫ﺭﻳﺰﯼ ﻧﻤﻲ ﺑﺎﺷﺪ ‪ ).‬ﻟﻄﻔﺎ ﻗﺴﻤﺖ ‪ Programming‬ﺭﺍ ﺑﺮﺭﺳﯽ ﻓﺮﻣﺎﺋﻴﺪ(‬

‫ﻣﻲ ﺗﻮﺍﻧﺪ‬ ‫ﻭﺭﻭﺩﯼ ﻫﺎﯼ ﺩﻳﺠﻴﺘﺎﻝ ﻗﺎﺑﻠﻴﺖ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺑﻪ ﺻﻮﺭﺕ ﺑﺎﺯ ﻳﺎ ﺑﺴﺘﻪ ﻣﻲ ﺑﺎﺷﻨﺪ ﻭ ﻫﻤﭽﻨﻴﻦ‬
‫ﺑﻪ ﺗﺮﻣﻴﻨﺎﻟﻬﺎﻱ ‪ BAT+‬ﻭ ‪ BAT-‬ﻣﺘﺼﻞ ﮔﺮﺩﺩ‪ .‬ﺗﺮﻣﻴﻨﺎﻝ ﺷﺎﺭﮊ ﺩﻳﻨﺎﻡ ﻋﻤﻞ ﺟﺮﻳﺎﻥ ﺗﺤﺮﻳﻚ ﺭﺍ ﻧﻴﺰ‬
‫ﺍﻧﺠﺎﻡ ﻣﻲ ﺩﻫﺪ ﺑﻨﺎﺑﺮﺍﻳﻦ ﺍﺣﺘﻴﺎﺝ ﺑﻪ ﻻﻣﭗ ﺷﺎﺭﮊ ﺧﺎﺭﺟﻲ ﻧﻴﺴﺖ‪.‬‬

‫‪5‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪ -۲‬ﻭﺭﻭﺩﯼ ﻫﺎ ﻭ ﺧﺮﻭﺟﯽ ﻫﺎ ‪:‬‬


‫‪: Serial Data‬‬
‫ﻣﻲ ﺷﻮﺩ ‪ ،‬ﻣﺎﻧﻨﺪ‬ ‫ﺑﻪ ﻭﺳﻴﻠﻪ ﺍﻳﻦ ﻛﺎﻧﻜﺘﻮﺭ ﺟﻬﺖ ﮔﺮﻓﺘﻦ ﺍﻃﻼﻋﺎﺕ ﺳﺮﻳﺎﻝ ﻭﺭﻭﺩﻱ ﻭ ﺧﺮﻭﺟﻲ ﺍﺳﺘﻔﺎﺩﻩ‬
‫ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﻭ ﻗﺮﺍﺋﺖ ﺍﻃﻼﻋﺎﺕ ﺍﺯ ﺭﺍﻩ ﺩﻭﺭ ﻭ ﺑﺮﺍﻱ ﺍﺗﺼﺎﻝ ﺑﻪ ﻛﺎﻣﭙﻴﻮﺗﺮ ﺑﺎﻳﺴﺘﻲ ﺍﺯ ﻳﻚ ﺍﺩﺍﭘﺘﻮﺭ ‪RS232‬‬
‫ﺍﺳﺘﻔﺎﺩﻩ ﻧﻤﺎﻳﻴﻢ ‪.‬‬

‫‪Term‬‬ ‫‪Function‬‬ ‫‪Technical data‬‬ ‫‪Description‬‬


‫‪Generator‬‬ ‫ﺭﻟﻪ ﺧﺮﻭﺟﯽ ‪16A(AC)-‬‬ ‫ﺍﺯ ﻃﺮﻳﻖ ﺍﻳﻦ ﺧﺮﻭﺟﯽ ﺍﻣﮑﺎﻥ ﻓﻌﺎﻝ ﮐﺮﺩﻥ ﮐﻨﺘﺎﮐﺘﻮﺭ ﮊﻧﺮﺍﺗﻮﺭ ﻭﺟﻮﺩ‬
‫‪Contactor‬‬
‫ﺧﻮﺍﻫﺪ ﺩﺍﺷﺖ ‪ .‬ﺍﮔﺮ ﺩﺭ ﻫﺮﻳﮏ ﺍﺯ ﻓﺎﺯﻫﺎﯼ ﮊﻧﺮﺍﺗﻮﺭ ﻣﻘﺪﺍﺭ ﻭﻟﺘﺎﮊ ﻳﺎ‬
‫ﻓﺮﮐﺎﻧﺲ ﻏﻴﺮ ﻗﺎﺑﻞ ﻗﺒﻮﻝ ﺑﺎﺷﻨﺪ ‪ ،‬ﮐﻨﺘﺎﮐﺘﻮﺭ ﮊﻧﺮﺍﺗﻮﺭ ﻏﻴﺮ ﻓﻌﺎﻝ ﻭ ﺑﯽ‬
‫‪1‬‬ ‫ﺑﺮﻕ ﺧﻮﺍﻫﺪ ﺷﺪ ‪ .‬ﺩﺭ ﺣﺎﻟﺘﯽ ﮐﻪ ﻣﯽ ﺧﻮﺍﻫﻴﻢ ﻳﮏ ﺣﻔﺎﻇﺖ ﻋﺎﻟﯽ‬
‫ﺩﺍﺷﺘﻪ ﺑﺎﺷﻴﻢ ﺑﻬﺘﺮ ﺍﺳﺖ ﮐﻨﺘﺎﮐﺖ ‪ Normally Close‬ﺍﺯ‬
‫ﮐﻨﺘﺎﮐﺘﻮﺭ ﺑﺮﻕ ﺷﻬﺮ ﺭﺍ ﺑﻪ ﺻﻮﺭﺕ ﺳﺮﯼ ﺳﺮ ﺭﺍﻩ ﺗﻐﺬﻳﻪ ﮐﻨﺘﺎﮐﺘﻮﺭ‬
‫ﮊﻧﺮﺍﺗﻮﺭ ﻗﺮﺍﺭ ﺩﻫﻴﻢ ‪.‬‬
‫‪U‬‬ ‫ﻓﺎﺯﻫﺎﯼ ﻭﺭﻭﺩﯼ ﮊﻧﺮﺍﺗﻮﺭ ﺭﺍ ﺑﻪ ﺍﻳﻦ ﻭﺭﻭﺩﯼ ﻫﺎ ﻣﺘﺼﻞ ﻧﻤﺎﺋﻴﺪ ﻭ ﻓﺎﺯﻫﺎﯼ ﻭﺭﻭﺩﯼ ﮊﻧﺮﺍﺗﻮﺭ‪-۰‬‬
‫‪2‬‬ ‫‪ ۳۰۰‬ﻭﻟﺖ ‪AC‬‬ ‫ﻣﻲ ﺑﺎﺷﺪ‪.‬‬ ‫ﻣﺤﺪﻭﺩﻩ ﺑﺎﻻ ﻭ ﭘﺎﻳﻴﻦ ﮊﻧﺮﺍﺗﻮﺭ ﻧﻴﺰ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ‬
‫‪Generator Neutral‬‬ ‫ﻭﺭﻭﺩﯼ ‪ ۰‬ﺗﺎ ‪ ۳۰۰‬ﻭﻟﺖ ‪AC‬‬ ‫ﺗﺮﻣﻴﻨﺎﻝ ﺧﻨﺜﯽ ﺑﺮﺍﯼ ﻓﺎﺯﻫﺎﯼ ﮊﻧﺮﺍﺗﻮﺭ‬
‫‪3‬‬
‫‪Mains Neutral‬‬ ‫ﻭﺭﻭﺩﯼ ‪ ۰‬ﺗﺎ ‪ ۳۰۰‬ﻭﻟﺖ ‪AC‬‬ ‫ﺗﺮﻣﻴﻨﺎﻝ ﺧﻨﺜﯽ ﺑﺮﺍﯼ ﻓﺎﺯﻫﺎﯼ ﺑﺮﻕ ﺷﻬﺮ‬
‫‪4‬‬

‫‪T‬‬ ‫ﻓﺎﺯﻫﺎﯼ ﺑﺮﻕ ﺷﻬﺮ ﺭﺍ ﺑﻪ ﺍﻳﻦ ﻭﺭﻭﺩﯼ ﻫﺎ ﻭﺻﻞ ﻧﻤﺎﺋﻴﺪ ‪ ،‬ﺣﺪ ﺑﺎﻻ ﻭ ﻭﺭﻭﺩﯼ ﻫﺎﯼ ﺍﺻﻠﯽ ﺑﺮﻕ‬
‫‪5‬‬
‫ﺷﻬﺮ‪ ۳۰۰-۰‬ﻭﻟﺖ ‪AC‬‬ ‫ﭘﺎﻳﻴﻦ ﻭﻟﺘﺎﮊﺑﺮﻕ ﺷﻬﺮ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ ﻫﺴﺘﻨﺪ ‪.‬‬
‫‪S‬‬
‫‪6‬‬
‫‪R‬‬
‫‪7‬‬
‫‪Main Contactor‬‬ ‫ﺍﻳﻦ ﺧﺮﻭﺟﯽ ﮐﻨﺘﺎﮐﺘﻮﺭ ﺑﺮﻕ ﺷﻬﺮ ﺭﺍ ﻓﻌﺎﻝ ﻣﯽ ﺳﺎﺯﺩ ‪ .‬ﺍﮔﺮ ﻣﻘﺪﺍﺭ ﺭﻟﻪ ﺧﺮﻭﺟﯽ ‪16A-AC‬‬
‫ﻭﻟﺘﺎﮊ ﻓﺎﺯﻫﺎﯼ ﺑﺮﻕ ﺷﻬﺮ ﻗﺎﺑﻞ ﻗﺒﻮﻝ ﻧﺒﺎﺷﺪ ﺍﻳﻦ ﮐﻨﺘﺎﮐﺘﻮﺭ ﻏﻴﺮﻓﻌﺎﻝ ﻣﯽ‬
‫ﺷﻮﺩ ‪ .‬ﺩﺭ ﺣﺎﻟﺘﯽ ﮐﻪ ﻣﯽ ﺧﻮﺍﻫﻴﻢ ﻳﮏ ﺣﻔﺎﻇﺖ ﻋﺎﻟﯽ ﺩﺍﺷﺘﻪ ﺑﺎﺷﻴﻢ‬
‫‪8‬‬ ‫ﺑﻬﺘﺮ ﺍﺳﺖ ﻳﮏ ﮐﻨﺘﺎﮐﺖ ‪ Normally Close‬ﺍﺯ ﮐﻨﺘﺎﮐﺘﻮﺭ‬
‫ﮊﻧﺮﺍﺗﻮﺭ ﺭﺍ ﺑﻪ ﺻﻮﺭﺕ ﺳﺮﯼ ﺳﺮ ﺭﺍﻩ ﺗﻐﺬﻳﻪ ﮐﻨﺘﺎﮐﺘﻮﺭ ‪) Main‬ﺑﺮﻕ‬
‫ﺷﻬﺮ( ﻗﺮﺍﺭ ﺩﻫﻴﻢ ‪.‬‬

‫‪6‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪Term‬‬ ‫‪Function‬‬ ‫‪Technical data‬‬ ‫‪Description‬‬


‫‪Oil Pressure Sender‬‬ ‫ﻭﺭﻭﺩﯼ ‪ ۰‬ﺗﺎ ‪ ۵۰۰۰‬ﺍﻫﻢ‬ ‫ﺳﻨﺴﻮﺭ ﻓﺸﺎﺭ ﺭﻭﻏﻦ ﺑﻪ ﺍﻳﻦ ﻭﺭﻭﺩﯼ ﻣﺘﺼﻞ ﻣﯽ ﮔﺮﺩﺩ ‪ .‬ﺳﻨﺴﻮﺭ ﺭﺍ‬
‫ﺑﻪ ﻭﺳﻴﻠﻪ ﯼ ﺩﻳﮕﺮﯼ ﻣﺘﺼﻞ ﻧﻨﻤﺎﺋﻴﺪ ‪ .‬ﺍﻳﻦ ﻭﺭﻭﺩﯼ ﻣﺸﺨﺼﻪ ﻗﺎﺑﻞ‬
‫‪9‬‬
‫ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ ﺩﺍﺷﺘﻪ ﻭ ﺍﻧﻮﺍﻉ ﺳﻨﺴﻮﺭﻫﺎ ﻧﻴﺰ ﺑﻪ ﺁﻥ ﻭﺻﻞ ﻣﯽ ﺷﻮﻧﺪ ‪.‬‬

‫‪Coolant Temp‬‬ ‫ﻭﺭﻭﺩﯼ ‪ ۰‬ﺗﺎ ‪ ۵۰۰۰‬ﺍﻫﻢ‬ ‫ﺳﻨﺴﻮﺭ ﺩﻣﺎﯼ ﺁﺏ ﺑﻪ ﺍﻳﻦ ﻭﺭﻭﺩﯼ ﻣﺘﺼﻞ ﻣﯽ ﮔﺮﺩﺩ ‪ .‬ﺳﻨﺴﻮﺭ ﺭﺍ ﺑﻪ‬
‫‪Sender‬‬
‫ﻭﺳﻴﻠﻪ ﺩﻳﮕﺮﯼ ﻣﺘﺼﻞ ﻧﻨﻤﺎﺋﻴﺪ ‪ .‬ﺍﻳﻦ ﻭﺭﻭﺩﯼ ﻣﺸﺨﺼﻪ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ‬
‫‪10‬‬ ‫ﺭﻳﺰﯼ ﺩﺍﺷﺘﻪ ﻭ ﺍﻧﻮﺍﻉ ﺳﻨﺴﻮﺭﻫﺎ ﻧﻴﺰ ﺑﻪ ﺁﻥ ﻣﺘﺼﻞ ﻣﯽ ﮔﺮﺩﺩ ‪.‬‬

‫‪Battery Positive‬‬ ‫‪ ۱۲+‬ﻳﺎ‪ ۲۴‬ﻭﻟﺖ‪DC‬‬ ‫ﺗﺮﻣﻴﻨﺎﻝ ﻣﺜﺒﺖ ﻣﻨﺒﻊ ‪ DC‬ﺑﺎﻳﺪ ﺑﻪ ﺍﻳﻦ ﺗﺮﻣﻴﻨﺎﻝ ﻣﺘﺼﻞ ﮔﺮﺩﺩ ﻭ‬
‫‪11‬‬
‫ﻛﻨﺘﺮﻟﺮ ﺑﺎ ﻫﺮ ﺩﻭ ﺑﺎﻃﺮﯼ ‪ ۱۲‬ﻳﺎ ‪ ۲۴‬ﻭﻟﺖ ﻣﯽ ﺗﻮﺍﻧﺪ ﮐﺎﺭ ﮐﻨﺪ ‪.‬‬
‫‪Ground‬‬ ‫‪ ۰‬ﻭﻟﺖ ‪DC‬‬ ‫ﺍﺗﺼﺎﻝ ﻣﻨﻔﯽ ﻣﻨﺒﻊ ﺗﻐﺬﻳﻪ‬
‫‪12‬‬
‫‪Relay-1‬‬ ‫ﺍﻳﻦ ﺭﻟﻪ ﻓﺎﻧﮑﺸﻦ ﻫﺎﯼ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ ﺩﺍﺷﺘﻪ ﮐﻪ ﺍﺯ ﻟﻴﺴﺖ ﻗﺎﺑﻞ‬
‫‪13‬‬ ‫)‪ (Horn Relay‬ﺭﻟﻪ ﻫﺸﺪﺍﺭ‬ ‫ﺧﺮﻭﺟﯽ‪10A/28VDC‬‬
‫ﺍﻧﺘﺨﺎﺏ ﺧﻮﺍﻫﺪ ﺑﻮﺩ‬

‫‪14‬‬ ‫‪Start Relay‬‬ ‫ﺧﺮﻭﺟﯽ ‪10A/28VDC‬‬ ‫ﺍﻳﻦ ﺭﻟﻪ ﻋﻤﻞ ﺍﺳﺘﺎﺭﺕ ﻣﻮﺗﻮﺭ ﺭﺍ ﺍﻧﺠﺎﻡ ﻣﻲ ﺩﻫﺪ‪.‬‬

‫ﺍﻳﻦ ﺭﻟﻪ ﺑﺮﺍﯼ ﮐﻨﺘﺮﻝ ﺳﻮﻟﻮﻧﻮﺋﻴﺪ ﺳﻮﺧﺖ ﺍﺳﺘﻔﺎﺩﻩ ﻣﯽ ﮔﺮﺩﺩ ﮐﻪ ﺑﻪ‬


‫‪Fuel Relay‬‬ ‫ﺧﺮﻭﺟﯽ ‪10A/28VDC‬‬
‫ﺻﻮﺭﺕ ﺩﺍﺧﻠﯽ ﺑﻪ ﺗﺮﻣﻴﻨﺎﻝ ‪ ۱۶‬ﺟﻬﺖ ﺗﻐﺬﻳﻪ ﺟﺮﻳﺎﻥ ﺷﺎﺭﮊ ﺩﻳﻨﺎﻡ‬
‫‪15‬‬
‫ﻣﺘﺼﻞ ﻣﯽ ﺑﺎﺷﺪ ‪.‬‬
‫ﺗﺮﻣﻴﻨﺎﻝ ‪ D+‬ﺍﺯ ﺷﺎﺭﮊﺭ ﺭﺍ ﺑﻪ ﺍﻳﻦ ﻭﺭﻭﺩﯼ ﻧﺼﺐ ﻧﻤﺎﺋﻴﺪ ﺍﻳﻦ ﺗﺮﻣﻴﻨﺎﻝ‬
‫‪16‬‬ ‫‪Charge‬‬ ‫ﻭﺭﻭﺩﯼ ﻭ ﺧﺮﻭﺟﯽ‬
‫ﻋﻤﻞ ﺗﻐﺬﻳﻪ ﺟﺮﻳﺎﻥ ﺗﺤﺮﻳﻚ ﺭﺍ ﺍﻧﺠﺎﻡ ﺩﺍﺩﻩ ﻭ ﻭﻟﺘﺎﮊ ﺷﺎﺭﮊ ﺩﻳﻨﺎﻡ ﺭﺍ‬
‫ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﻣﻲ ﻛﻨﺪ ‪.‬‬
‫‪Relay-2‬‬ ‫ﺍﻳﻦ ﺭﻟﻪ ﻓﺎﻧﮑﺸﻦ ﻫﺎﯼ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ ﺩﺍﺷﺘﻪ ﮐﻪ ﺍﺯ ﻟﻴﺴﺖ ﻗﺎﺑﻞ‬
‫‪17‬‬ ‫)‪ (Stop relay‬ﺭﻟﻪ ﺗﻮﻗﻒ‬ ‫ﺧﺮﻭﺟﯽ ‪10A/28VDC‬‬
‫ﺍﻧﺘﺨﺎﺏ ﺧﻮﺍﻫﺪ ﺑﻮﺩ ‪.‬‬
‫‪Low Oil Pressure‬‬ ‫ﺍﻳﻦ ﻭﺭﻭﺩﯼ ﻫﺎ ﺧﺼﻮﺻﻴﺖ ﺑﺮﻧﺎﻣﻪ ﭘﺬﻳﺮﯼ ﺭﺍ ﺗﻮﺳﻂ ﻣﻨﻮﯼ‬
‫‪18‬‬
‫‪ Program‬ﺩﺍﺭﺍ ﻣﯽ ﺑﺎﺷﻨﺪ ‪ .‬ﻫﺮ ﻭﺭﻭﺩﯼ ﻣﻲ ﺗﻮﺍﻧﺪ ﺑﻪ ﺻﻮﺭﺕ‬
‫‪High Temp‬‬ ‫ﮐﻨﺘﺎﮐﺖ ‪ Normally Close‬ﻳﺎ‪ Normally Open‬ﻓﻌﺎﻝ‬
‫‪19‬‬
‫‪Rectifier Fail‬‬ ‫ﺷﻮﺩ ﻭ ﺑﻪ ﻫﺮ ﻳﮏ ﺍﺯﺗﺮﻣﻴﻨﺎﻟﻬﺎﻱ ) ‪ Battery+‬ﻳﺎ ‪(Battery-‬‬
‫‪20‬‬ ‫ﻭﺭﻭﺩﯼ ﻫﺎﯼ ﺩﻳﺠﻴﺘﺎﻝ‬
‫ﻣﺘﺼﻞ ﮔﺮﺩﺩ ﻭ ﻧﺤﻮﻩ ﺍﺗﺼﺎﻝ ﺍﺯ ﻟﻴﺴﺖ ﻗﺎﺑﻞ ﺍﻧﺘﺨﺎﺏ ﺍﺳﺖ ‪ .‬ﺑﺮﺍﯼ‬
‫‪Emergency Stop‬‬
‫‪21‬‬ ‫ﺟﺰﺋﻴﺎﺕ ﺑﻴﺸﺘﺮ ﮐﺎﻓﯽ ﺍﺳﺖ ﺑﻪ ﻗﺴﻤﺖ ‪ Programming‬ﻣﺮﺍﺟﻌﻪ‬
‫‪22‬‬ ‫‪Spare/Remote Start‬‬
‫ﻧﻤﺎﻳﻴﺪ ‪.‬‬
‫‪23‬‬ ‫‪Program Lock‬‬

‫‪7‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪Term‬‬ ‫‪Function‬‬ ‫‪Technical data‬‬ ‫‪Description‬‬


‫ﺗﺮﻣﻴﻨﺎﻟﻬﺎﯼ ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮ ﺟﺮﻳﺎﻥ ﮊﻧﺮﺍﺗﻮﺭ ﺭﺍ ﺑﻪ ﺍﻳﻦ ﻭﺭﻭﺩﯼ ﻫﺎ ﻣﺘﺼﻞ ﻭﺭﻭﺩﯼ ﻫﺎﯼ ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮ‬
‫ﻣﯽ ﻧﻤﺎﻳﻴﻢ ‪ .‬ﻳﮏ ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮ ﺟﺮﻳﺎﻥ ﺭﺍ ﺑﻪ ﺩﻳﮕﺮ ﻭﺳﺎﻳﻞ ﻣﺘﺼﻞ ﺟﺮﻳﺎﻥ ‪5A-AC‬‬
‫ﻧﻨﻤﺎﺋﻴﺪ ‪ .‬ﺑﻪ ﻋﺒﺎﺭﺕ ﺩﻳﮕﺮ ﺑﺮﺍﯼ ﻛﻨﺘﺮﻟﺮ ﺧﻄﺎ )‪ (Fail‬ﺍﺗﻔﺎﻕ‬
‫‪24‬‬ ‫‪CURR U+‬‬ ‫ﻣﯽ ﺍﻓﺘﺪ ‪ .‬ﺗﺮﻣﻴﻨﺎﻝ ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮ ﺟﺮﻳﺎﻥ ﺭﺍ ﺑﻪ ﺗﺮﻣﻴﻨﺎﻝ ﻣﺘﻨﺎﺳﺐ ﺑﻪ ﺁﻥ‬
‫ﻭﺻﻞ ﻧﻤﺎﻳﻴﺪ ﻭﺍﺯ ﺯﻣﻴﻦ ﻛﺮﺩﻥ) ‪ (Grounding‬ﻭ ﺗﺮﻣﻴﻨﺎﻝ‬
‫ﻣﺸﺘﺮﮎ ﺍﺳﺘﻔﺎﺩﻩ ﻧﻨﻤﺎﻳﻴﺪ‬
‫ﺑﮑﺎﺭ ﺑﺮﺩﻥ ﺍﺗﺼﺎﻻﺕ ﺩﺭﺳﺖ ﺣﻴﺎﺗﻲ ﺍﺳﺖ ‪ ،‬ﺍﮔﺮ ﺗﻮﺍﻥ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﯼ‬
‫ﺷﺪﻩ ﻣﻨﻔﯽ ﺑﻮﺩ ﺟﻬﺖ ﻫﺮ ﺳﻪ ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮ ﺟﺮﻳﺎﻥ ) ‪Current‬‬
‫‪ (Transformer‬ﺭﺍ ﺗﻐﻴﻴﺮﺩﻫﻴﺪ ‪ .‬ﻣﻘﺪﺍﺭﻫﻤﻪ ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮ ﻫﺎ‬
‫‪25‬‬ ‫‪CURR U-‬‬
‫ﻣﯽ ﺑﺎﻳﺴﺖ ﺑﺮﺍﯼ ﻫﺮ ﺳﻪ ﻓﺎﺯ ﻳﮑﯽ ﺑﺎﺷﺪ‪ .‬ﺳﻴﻢ ﭘﻴﭻ ﺛﺎﻧﻮﻳﻪ‬
‫ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮ ﺟﺮﻳﺎﻥ ﻣﻲ ﺑﺎﻳﺴﺖ ‪ 5A‬ﺁﻣﭙﺮﺑﺎﺷﺪ‪ .‬ﺑﻪ ﻃﻮﺭ ﻣﺜﺎﻝ‬
‫) ‪( 200/5‬‬

‫‪ LED ۳-۱‬ﻫﺎﯼ ﺻﻔﺤﻪ ﻧﻤﺎﻳﺶ ‪:‬‬

‫ﻛﻨﺘﺮﻟﺮ ﺩﺍﺭﺍﯼ ‪ ۱۸‬ﻋﺪﺩ ‪ LED‬ﺍﺳﺖ ﮐﻪ ﺩﺭ ‪ ۴‬ﮔﺮﻭﻩ ﺗﻘﺴﻴﻢ ﺑﻨﺪﯼ ﺷﺪﻩ ﺍﻧﺪ ‪.‬‬

‫‪ : Group 1‬ﺣﺎﻟﺖ ﻋﻤﻠﻴﺎﺗﻲ ‪ :‬ﺍﻳﻦ ﮔﺮﻭﻩ ﻧﺸﺎﻧﮕﺮ ﻋﻤﻠﻜﺮﺩ ﺗﻮﺍﺑﻊ ﺳﻴﺴﺘﻢ ﺭﺍ ﻣﻲ ﺑﺎﺷﺪ ‪.‬‬

‫‪ : Group 2‬ﺣﺎﻟﺖ ﺩﻳﺎﮔﺮﺍﻡ ﮐﻠﯽ ﺳﻴﺴﺘﻢ ‪ ،‬ﮐﻪ ﺍﻳﻦ ﮔﺮﻭﻩ ﻧﻤﺎﻳﺸﮕﺮ ﻭﺿﻌﻴﺖ ﺟﺎﺭﻱ ﻭﻟﺘﺎﮊﻫﺎ ﻭ‬
‫ﮐﻨﺘﺎﮐﺘﻮﺭﻫﺎﯼ ﺑﺮﻕ ﺷﻬﺮ ﻭ ﮊﻧﺮﺍﺗﻮﺭ ﻣﻲ ﺑﺎﺷﺪ‪.‬‬

‫‪ Warning & Alarms : Group 3‬ﺍﻋﻼﻡ ﻭﺿﻌﻴﺖ ﻫﺸﺪﺍﺭ‪ :‬ﺍﻳﻦ ﮔﺮﻭﻩ ﻭﺟﻮﺩ ﻭﺿﻌﻴﺖ ﻏﻴﺮ ﻋﺎﺩﯼ ﺭﺍ‬
‫ﺩﺭ ﻃﻮﻝ ﻋﻤﻠﮑﺮﺩ ﺭﺍ ﻧﺸﺎﻥ ﻣﯽ ﺩﻫﺪ ‪.‬‬

‫‪ : Group 4‬ﺍﻳﻦ ﮔﺮﻭﻩ ﻣﻘﺎﺩﻳﺮ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﯼ ﺷﺪﻩ ﺫﻳﻞ ﺭﺍ ﻧﻤﺎﻳﺶ ﻣﯽ ﺩﻫﺪ‪.‬‬

‫‪8‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪Function‬‬ ‫‪Color‬‬ ‫‪Description‬‬


‫ﺍﻳﻦ ‪ LED‬ﺯﻣﺎﻧﻲ ﻛﻪ ﻭﻟﺘﺎﮊ ﻓﺎﺯ ﮊﻧﺮﺍﺗﻮﺭ ﺩﺭ ﻣﺤﺪﻭﺩﻩ ﻫﺎﻱ‬
‫‪Generator‬‬ ‫‪ )Yellow‬ﺭﻧﮓ ﺯﺭﺩ (‬ ‫ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺷﺪﻩ ﺑﺎﺷﺪ ﭼﺸﻤﻚ ﻣﻲ ﺯﻧﺪ ﻭ ﻭﻗﺘﻲ ﻛﻨﺘﺎﻛﺘﻮﺭ‬
‫ﮊﻧﺮﺍﺗﻮﺭ ﻓﻌﺎﻝ ﻣﻲ ﺷﻮﺩ ﺭﻭﺷﻦ ﻣﻲ ﺷﻮﺩ ‪.‬‬
‫ﺍﻳﻦ ‪ LED‬ﺯﻣﺎﻧﻲ ﻛﻪ ﻭﻟﺘﺎﮊ ﻫﺮ ﺳﻪ ﻓﺎﺯ ﺑﺮﻕ ﺷﻬﺮ ﺩﺭ‬

‫‪Mains‬‬ ‫‪) Green‬ﺭﻧﮓ ﺳﺒﺰ(‬ ‫ﻣﺤﺪﻭﺩﻩ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺑﺎﺷﺪ ﭼﺸﻤﻚ ﻣﻲ ﺯﻧﺪ ﻭ ﻭﻗﺘﻲ‬
‫ﻛﻨﺘﺎﻛﺘﻮﺭ ﺑﺮﻕ ﺷﻬﺮ ﻓﻌﺎﻝ ﺍﺳﺖ ﺭﻭﺷﻦ ﻣﻲ ﺷﻮﺩ‪.‬‬
‫ﺍﻳﻦ ‪ LED‬ﻫﺎ ﻭﻗﺘﯽ ﺭﻭﺷﻦ ﻣﯽ ﺷﻮﻧﺪ ﮐﻪ ﺳﻴﺴﺘﻢ ﺩﺭ‬
‫‪Test‬‬ ‫‪ )Yellow‬ﺭﻧﮓ ﺯﺭﺩ (‬
‫ﺣﺎﻟﺖ ﻛﺎﺭﻱ ﻣﺮﺑﻮﻃﻪ ﺍﻧﺘﺨﺎﺏ ﺷﻮﺩ‪ .‬ﺍﻳﻦ ‪ LED‬ﻫﺎ ﻧﺸﺎﻧﮕﺮ‬
‫ﺣﺎﻟﺖ ﻛﺎﺭﻱ ﻣﺮﺑﻮﻃﻪ ﻣﻲ ﺑﺎﺷﺪ ‪.‬ﻭ ﻫﺮ ﺩﻭ ‪ LED‬ﺩﺭ‬
‫‪Auto‬‬ ‫‪) Green‬ﺭﻧﮓ ﺳﺒﺰ(‬ ‫ﺣﺎﻟﺖ ‪ OFF‬ﺧﺎﻣﻮﺵ ﻣﻲ ﺑﺎﺷﺪ‪.‬‬

‫ﺗﻌﻤﻴﺮﺍﺕ ﺩﻭﺭﻩ ﺍﯼ ﻣﻮﺗﻮﺭ ﺭﺍ ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﻭ ‪ LED‬ﭘﺲ ﺍﺯ‬


‫‪Service Request‬‬ ‫‪ )Red‬ﺭﻧﮓ ﻗﺮﻣﺰ (‬ ‫ﺳﭙﺮﻱ ﺷﺪﻥ ﺯﻣﺎﻥ ﻛﺎﺭﻱ ﻳﺎ ﺑﻌﺪ ﺍﺯ ﺗﻤﺎﻡ ﺷﺪﻥ ﺯﻣﺎﻥ‬
‫ﺳﺮﻭﻳﺲ ﻗﺒﻠﻲ ﺭﻭﺷﻦ ﻣﯽ ﺷﻮﺩ ‪.‬‬
‫ﭼﻨﺎﻧﭽﻪ ﺧﻄﺎ ﺑﺎﻋﺚ ﺧﺎﻣﻮﺵ ﺷﺪﻥ ﻣﻮﺗﻮﺭ ﮔﺮﺩﺩ ‪LED‬‬
‫ﻣﺘﻨﺎﺳﺐ ﺑﺎ ﺧﻄﺎ ﺑﻪ ﻃﻮﺭ ﺩﺍﺋﻢ ﺭﻭﺷﻦ ﻣﻲ ﻣﺎﻧﺪ ﻭ ﺍﮔﺮ ﺣﺎﻟﺖ‬
‫ﻫﺸﺪﺍﺭ ﺑﻮﺟﻮﺩ ﺁﻣﺪﻩ ﺑﺎﺷﺪ ‪ LED‬ﺁﻻﺭﻡ ﻣﺮﺑﻮﻃﻪ ﺷﺮﻭﻉ ﺑﻪ‬
‫ﭼﺸﻤﮏ ﺯﺩﻥ ﺧﻮﺍﻫﺪ ﻧﻤﻮﺩ ‪ .‬ﺁﻻﺭﻡ ﻫﺎ ﺑﺮ ﭘﺎﻳﻪ ﺍﻭﻟﻮﻳﺖ‬
‫‪Alarm Group‬‬ ‫‪ )Red‬ﺭﻧﮓ ﻗﺮﻣﺰ (‬
‫ﺑﻨﺪﻱ ﻋﻤﻞ ﺧﻮﺍﻫﻨﺪ ﻧﻤﻮﺩ ﺑﺎ ﺑﻮﺟﻮﺩ ﺁﻣﺪﻥ ﻳﮏ ﺧﻄﺎ ‪،‬‬
‫ﺧﻄﺎﻫﺎﯼ ﺑﺎ ﺍﻭﻟﻮﻳﺖ ﺑﺮﺍﺑﺮ ﻳﺎ ﭘﺎﻳﻴﻦ ﺗﺮ ﻏﻴﺮ ﻓﻌﺎﻝ ﺧﻮﺍﻫﻨﺪ ﺷﺪ‪.‬‬

‫ﺍﻳﻦ ﮔﺮﻭﻩ ﻧﻤﺎﻳﺸﮕﺮﻭﺍﺣﺪﻫﺎﻱ ﻣﻘﺎﺩﻳﺮ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﯼ ﺷﺪﻩ ﺑﺮ‬


‫ﺭﻭﻱ ﻧﻤﺎﻳﺸﮕﺮ ﻣﻲ ﺑﺎﺷﺪ‪ .‬ﻫﻨﮕﺎﻣﻴﮑﻪ ﻣﻮﺗﻮﺭ ﺩﺭ ﺣﺎﻟﺖ‬
‫ﻛﺎﺭﺍﺳﺖ ﺍﻳﻦ ﻭﺍﺣﺪ ﻓﺮﮐﺎﻧﺲ ﮊﻧﺮﺍﺗﻮﺭﺭﺍ ﻧﺸﺎﻥ ﻣﻲ ﺩﻫﺪ ‪ ،‬ﺩﺭ‬
‫‪Unit Group‬‬ ‫‪ )Red‬ﺭﻧﮓ ﻗﺮﻣﺰ (‬ ‫ﻏﻴﺮ ﺍﻳﻦ ﺻﻮﺭﺕ ﻭﻟﺘﺎﮊ ﺑﺎﻃﺮﯼ ﺭﺍ ﻧﻤﺎﻳﺶ ﺧﻮﺍﻫﺪ ﺩﺍﺩ ﻭ‬
‫ﻣﻘﺎﺩﻳﺮ ﻣﺨﺘﻠﻒ ﺑﺎ ﻓﺸﺎﺭ ﺩﺍﺩﻥ ﺩﮐﻤﻪ ‪ Menu‬ﻗﺎﺑﻞ ﻧﻤﺎﻳﺶ‬
‫ﻣﻲ ﺑﺎﺷﻨﺪ ‪.‬‬

‫‪9‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪ ۳-۲‬ﻧﻤﺎﻳﺸﮕﺮﻫﺎﯼ ﺩﻳﺠﻴﺘﺎﻝ‬
‫ﻛﻨﺘﺮﻟﺮ ﺩﺍﺭﺍﯼ ‪ ۱‬ﻋﺪﺩ ﻧﻤﺎﻳﺸﮕﺮ ‪ Seven Segment‬ﺍﺳﺖ ‪ ،‬ﺍﻳﻦ ﻧﻤﺎﻳﺸﮕﺮ ﻧﺸﺎﻥ ﺩﻫﻨﺪﻩ ‪:‬‬
‫‪ -‬ﭘﺎﺭﺍﻣﺘﺮﻫﺎﯼ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﯼ ﺷﺪﻩ‬
‫‪ -‬ﻧﺎﻡ ﭘﺎﺭﺍﻣﺘﺮ‬
‫‪ -‬ﺷﻤﺎﺭﻧﺪﻩ ﻫﺎﻱ ﺳﺮﻭﻳﺲ‬
‫‪ -‬ﭘﺎﺭﺍﻣﺘﺮﻫﺎﯼ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ‬
‫ﺑﺎ ﺩﮐﻤﻪ ‪ Menu‬ﻣﯽ ﺗﻮﺍﻥ ﺻﻔﺤﺎﺕ ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﺷﺪﻩ ﺩﺭ ﻫﺮ ﮔﺮﻭﻩ ﺭﺍ ﻋﻮﺽ ﻧﻤﻮﺩ ‪.‬‬
‫ﺑﺎ ﻓﺸﺎﺭ ﺩﺍﺩﻥ ﺩﮐﻤﻪ ‪ Menu‬ﻧﺎﻡ ﭘﺎﺭﺍﻣﺘﺮ ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﻣﻲ ﺷﻮﺩ ﻭ ﻣﻘﺎﺩﻳﺮ ﺯﻳﺮ ﺑﻪ ﻧﻤﺎﻳﺶ ﮔﺬﺍﺷﺘﻪ ﻣﻲ ﺷﻮﺩ‪.‬‬

‫‪ -‬ﻧﻤﺎﻳﺶ ﻭﻟﺘﺎﮊﻫﺎﻱ ‪ R,S,T‬ﺷﺒﻜﻪ ﻧﺴﺒﺖ ﺑﻪ ﻧﻮﻝ‬


‫‪ -‬ﻧﻤﺎﻳﺶ ﻭﻟﺘﺎﮊ ‪ U‬ﮊﻧﺮﺍﺗﻮﺭ ﻧﺴﺒﺖ ﺑﻪ ﻧﻮﻝ‬
‫‪ -‬ﻧﻤﺎﻳﺶ ﺟﺮﻳﺎﻥ ﻓﺎﺯ ‪ U‬ﮊﻧﺮﺍﺗﻮﺭ‬
‫‪ -‬ﻧﻤﺎﻳﺶ ﻓﺮﻛﺎﻧﺲ ﮊﻧﺮﺍﺗﻮﺭ‬
‫‪ -‬ﻧﻤﺎﻳﺶ ‪ CosΦ‬ﻓﺎز ‪ U‬ﮊﻧﺮﺍﺗﻮﺭ‬
‫‪ -‬ﻧﻤﺎﻳﺶ ﺗﻮﺍﻥ ﺍﻛﺘﻴﻮ ﮊﻧﺮﺍﺗﻮﺭ)‪(KW‬‬
‫‪ -‬ﻧﻤﺎﻳﺶ ﻓﺸﺎﺭ ﺭﻭﻏﻦ )‪(bar‬‬
‫‪ -‬ﻧﻤﺎﻳﺶ ﺣﺮﺍﺭﺕ ﺁﺏ )‪(ºC‬‬
‫‪ -‬ﻧﻤﺎﻳﺶ ﻭﻟﺘﺎﮊ ﺑﺎﻃﺮﻱ )‪(V-DC‬‬
‫ﺑﺎ ﻓﺸﺎﺭ ﺩﺍﺩﻥ ﺩﻛﻤﻪ ‪ Menu‬ﺑﻪ ﻣﺪﺕ ‪ ۱‬ﺛﺎﻧﻴﻪ ﺩﺳﺘﮕﺎﻩ ﺷﻤﺎﺭﻧﺪﻩ ﻫﺎﻱ ﺳﺮﻭﻳﺲ ﺭﺍ ﻧﺸﺎﻥ ﻣﻲ ﺩﻫﺪ ‪.‬‬
‫‪ -‬ﺳﺎﻋﺖ ﻛﺎﺭﻛﺮﺩ ﻛﻞ ﻣﻮﺗﻮﺭ‬
‫‪ -‬ﺳﺎﻋﺖ ﻫﺎﻱ ﺳﺮﻭﻳﺲ ﻣﻮﺗﻮﺭ‬
‫‪ -‬ﺳﺎﻋﺖ ﺑﺎﻗﻴﻤﺎﻧﺪﻩ ﺗﺎ ﺳﺮﻭﻳﺲ‬

‫‪10‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪Alarm & Warning -۴‬‬


‫ﺁﻻﺭﻡ ﻫﺎ ﻭﺿﻌﻴﺖ ﻏﻴﺮﻋﺎﺩﯼ ﺭﺍ ﺩﺭﮊﻧﺮﺍﺗﻮﺭ ﺑﻪ ﻧﻤﺎﻳﺶ ﺩﺭﻣﯽ ﺁﻭﺭﻧﺪ ﮐﻪ ﺍﺯﻧﻈﺮﺍﻭﻟﻮﻳﺖ ﺑﻨﺪﻱ ﺑﻪ ‪ ۲‬ﻗﺴﻤﺖ‬
‫ﺗﻘﺴﻴﻢ ﺷﺪﻩ ﺍﺳﺖ ‪:‬‬

‫‪ Alarms -۱‬ﺁﻻﺭﻣﻬﺎ ‪ :‬ﺣﺎﻟﺘﻬﺎﻱ ﺯﻳﺮ ﺍﺯ ﻣﻬﻤﺘﺮﻳﻦ ﺩﻻﻳﻞ ﻭ ﻭﺿﻌﻴﺖ ﺧﻄﺎﻫﺎ ﻣﻲ ﺑﺎﺷﻨﺪ‪.‬‬


‫‪ -‬ﺭﻭﺷﻦ ﺑﻮﺩﻥ ﺩﺍﺋﻢ ‪ LED‬ﻣﺮﺑﻮﻃﻪ ﻭﺿﻌﻴﺖ ﺁﻻﺭﻡ ﺭﺍ ﮔﺰﺍﺭﺵ ﻣﯽ ﺩﻫﻨﺪ‬
‫‪ -‬ﻗﻄﻊ ﺷﺪﻥ ﻓﻮﺭﻱ ﮐﻨﺘﺎﮐﺘﻮﺭ ﮊﻧﺮﺍﺗﻮﺭ‬
‫‪ -‬ﺗﻮﻗﻒ ﻓﻮﺭﻱ ﻣﻮﺗﻮﺭ‬
‫‪ -‬ﻋﻤﻠﻜﺮﺩ ﺭﻟﻪ ﻫﺎﯼ ﺧﺮﻭﺟﯽ ﺁﮊﻳﺮ ‪ ،‬ﻫﺸﺪﺍﺭ ﻭ ﺧﻄﺎ ﻋﻤﻞ ﮐﻨﻨﺪ ‪) .‬ﺍﮔﺮ ﺍﻳﻦ ﺭﻟﻪ ﻫﺎ ﺩﺭ ﻫﻨﮕﺎﻡ ﺑﺮﻧﺎﻣﻪ‬
‫ﺭﻳﺰﻱ ﺍﻧﺘﺨﺎﺏ ﺷﺪﻩ ﺑﺎﺷﻨﺪ(‬

‫‪ Warning -۲‬ﻫﺸﺪﺍﺭﻫﺎ ‪:‬ﭼﻨﻴﻦ ﺣﺎﻟﺘﻲ ﺳﺒﺐ‪:‬‬


‫‪ LED -‬ﻣﺮﺑﻮﻃﻪ ﭼﺸﻤﮏ ﺑﺰﻧﻨﺪ ﻋﻤﻠﻜﺮﺩ ﺭﻟﻪ ﻫﺎﯼ ﺧﺮﻭﺟﯽ ﻫﺸﺪﺍﺭ ﻭ ﺧﻄﺎ ﻋﻤﻞ ﮐﻨﻨﺪ ‪) .‬ﺍﮔﺮ ﺍﻳﻦ‬
‫ﺭﻟﻪ ﻫﺎ ﺩﺭ ﻫﻨﮕﺎﻡ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺍﻧﺘﺨﺎﺏ ﺷﺪﻩ ﺑﺎﺷﻨﺪ(‪.‬‬
‫‪ -‬ﺭﻟﻪ ﻫﺎﯼ ﺧﺮﻭﺟﯽ ﺁﮊﻳﺮ ‪ ،‬ﺧﻄﺎ ﻭ ﻫﺸﺪﺍﺭﻓﻌﺎﻝ ﺷﻮﻧﺪ ‪.‬‬

‫ﺍﮔﺮ ﺩﮐﻤﻪ ‪ Alarm Mute‬ﻓﺸﺎﺭ ﺩﺍﺩﻩ ﺷﻮﺩ ‪ ،‬ﺧﺮﻭﺟﯽ ﺭﻟﻪ ﺁﮊﻳﺮﻏﻴﺮ ﻓﻌﺎﻝ ﺧﻮﺍﻫﺪ ﺷﺪ ‪ .‬ﻫﺮ ﭼﻨﺪ ﺧﻄﺎﻱ‬
‫ﻣﺮﺑﻮﻃﻪ ﻭﺟﻮﺩ ﺩﺍﺷﺘﻪ ﻭ ﺑﺎﻋﺚ ﻏﻴﺮ ﻓﻌﺎﻝ ﺷﺪﻥ ﻋﻤﻠﻜﺮﺩ ﺳﻴﺴﺘﻢ ﺷﻮﺩ‪.‬‬

‫ﺁﻻﺭﻡ ﻫﺎ ﺑﺮ ﺍﺳﺎﺱ ﺍﻭﻟﻮﻳﺖ ﻭﻗﻮﻉ ﭘﺎﺳﺦ ﺩﺍﺩﻩ ﻣﯽ ﺷﻮﻧﺪ ‪:‬‬


‫‪ -‬ﺍﮔﺮ ﺧﻄﺎ ﻭﺟﻮﺩ ﺩﺍﺷﺘﻪ ﺑﺎﺷﺪ ‪ ،‬ﺧﻄﺎ ﻫﺎ ﻭ ﻫﺸﺪﺍﺭﻫﺎﯼ ﺯﻳﺮ ﻗﺎﺑﻞ ﻗﺒﻮﻝ ﻧﺨﻮﺍﻫﻨﺪ ﺷﺪ ‪.‬‬
‫‪ -‬ﺍﮔﺮ ﻫﺸﺪﺍﺭ ﻭﻗﻮﻉ ﻳﺎﻓﺘﻪ ﺑﺎﺷﺪ ‪ ،‬ﻫﺸﺪﺍﺭﻫﺎﯼ ﺯﻳﺮ ﻗﺎﺑﻞ ﻗﺒﻮﻝ ﻧﺨﻮﺍﻫﻨﺪ ﺷﺪ‪.‬‬
‫ﺁﻻﺭﻡ ﻫﺎ ﻣﻤﮑﻦ ﺍﺳﺖ ﺍﺯ ﻧﻮﻉ ﻗﻔﻞ ﺷﻮﻧﺪﻩ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ ﮔﺮﺩﻧﺪ ﻭ ﺩﺭ ﺍﻳﻦ ﺣﺎﻟﺖ ﺩﺭ ﺻﻮﺭﺕ ﺍﺯ ﺑﻴﻦ ﺭﻓﺘﻦ‬
‫ﺁﻻﺭﻡ ‪ ،‬ﺁﻻﺭﻡ ﻫﺎ ﻓﻌﺎﻝ ﺑﺎﻗﯽ ﻣﯽ ﻣﺎﻧﻨﺪ ﻭ ﺟﻠﻮﯼ ﮐﺎﺭﮐﺮﺩ ﺳﻴﺴﺘﻢ ﺭﺍ ﺧﻮﺍﻫﻨﺪ ﮔﺮﻓﺖ ‪.‬‬
‫ﺁﻻﺭﻡ ﻫﺎﯼ ﻣﻮﺟﻮﺩ ﻣﻤﮑﻦ ﺍﺳﺖ ﺑﻪ ﻭﺳﻴﻠﻪ ﻓﺸﺎﺭ ﺩﺍﺩﻥ ﻳﮑﯽ ﺍﺯ ﺩﮐﻤﻪ ﻫﺎﯼ ﺣﺎﻟﺘﻬﺎﻱ ﻋﻤﻠﮑﺮﺩﻱ ﺳﻴﺴﺘﻢ ﺍﺯ‬
‫ﺑﻴﻦ ﺑﺮﻭﻧﺪ )‪( Load Test-Test-OFF-Auto‬‬
‫ﺑﻴﺸﺘﺮ ﺁﻻﺭﻡ ﻫﺎ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ ﻫﺴﺘﻨﺪ ﺑﻪ ﻗﺴﻤﺖ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ ﺑﺮﺍﯼ ﺗﻨﻈﻴﻤﺎﺕ ﺁﻻﺭﻡ ﻣﺮﺍﺟﻌﻪ ﻧﻤﺎﻳﻴﺪ ‪.‬‬
‫‪11‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪ : Pressure Low Oil‬ﺍﻳﻦ ﺁﻻﺭﻡ ﺩﺭ ﺻﻮﺭﺗﯽ ﻓﻌﺎﻝ ﻣﯽ ﺷﻮﺩ ﮐﻪ ﺍﺯ ﻭﺭﻭﺩﻱ ﺩﻳﺠﻴﺘﺎﻝ‬


‫‪ Low Oil Pressure‬ﺳﻴﮕﻨﺎﻟﯽ ﺩﺭﻳﺎﻓﺖ ﺷﻮﺩ ﻭ ﻳﺎ ﻣﻘﺪﺍﺭ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﯼ ﺷﺪﻩ ﻓﺸﺎﺭﺭﻭﻏﻦ ﺳﻴﺴﺘﻢ ﮐﻪ ﺍﺯ‬
‫ﺳﻨﺴﻮﺭ ﻓﺸﺎﺭ ﺳﻨﺠﻴﺪﻩ ﻣﯽ ﺷﻮﺩ ‪ ،‬ﺯﻳﺮ ﺣﺪ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﺑﺮﻧﺎﻣﻪ ﺑﺎﺷﺪ ‪.‬‬
‫ﻣﺤﺪﻭﺩﻩ ‪ (P-016) Warning‬ﻭ ‪ (P-015) Alarm‬ﻫﺮ ﻳﻚ ﺑﺮﺍﯼ ﺳﻨﺴﻮﺭ ﻓﺸﺎﺭ ﺭﻭﻏﻦ ﺑﻪ ﺻﻮﺭﺕ‬
‫ﺟﺪﺍ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ ﻫﺴﺘﻨﺪ‪ .‬ﺍﻳﻦ ﺧﻄﺎ ﺑﻌﺪ ﺍﺯﺍﺳﺘﺎﺭﺕ ﻣﻮﺗﻮﺭ ﻭ ﺑﻌﺪ ﺍﺯ ﺳﭙﺮﯼ ﺷﺪﻥ ﺯﻣﺎﻥ ﺗﺎﺧﻴﺮ ‪Hold‬‬
‫‪ OFF‬ﮐﻪ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ) ‪ ( P-023‬ﻗﺎﺑﻞ ﺗﻨﻈﻴﻢ ﺍﺳﺖ ‪ ،‬ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﺧﻮﺍﻫﺪ ﺷﺪ ‪.‬‬
‫ﻫﻤﭽﻨﻴﻦ ﺍﮔﺮ ﺩﺭ ﻟﺤﻈﻪ ﻭﻗﻮﻉ ﺍﺳﺘﺎﺭﺕ ﺳﻮﺋﻴﭻ ﻓﺸﺎﺭ ﺭﻭﻏﻦ ‪ ،‬ﺑﺎﺯ ﺷﻮﺩ ﻣﻮﺗﻮﺭ ﺍﺳﺘﺎﺭﺕ ﻧﺨﻮﺍﻫﺪ ﺷﺪ ﻭ ‪LED‬‬
‫ﻣﺮﺑﻮﻁ ﺑﻪ ‪ Oil Pressure‬ﺷﺮﻭﻉ ﺑﻪ ﭼﺸﻤﮏ ﺯﺩﻥ ﺧﻮﺍﻫﺪ ﻧﻤﻮﺩ ‪ .‬ﻫﻨﮕﺎﻣﻴﮑﻪ ﺳﻮﺋﻴﭻ ﻓﺸﺎﺭ ﺭﻭﻏﻦ ﺩﻭﺑﺎﺭﻩ‬
‫ﺑﺴﺘﻪ ﺷﻮﺩ ‪ ،‬ﺳﻴﺴﺘﻢ ﺑﻪ ﺻﻮﺭﺕ ﻋﺎﺩﯼ ﺑﻪ ﮐﺎﺭ ﻧﺨﻮﺍﻫﺪ ﻛﺮﺩ‪.‬‬

‫‪ : High Temperature‬ﺍﻳﻦ ﺁﻻﺭﻡ ﺩﺭ ﺻﻮﺭﺗﯽ ﻓﻌﺎﻝ ﻣﯽ ﺷﻮﺩ ﮐﻪ ﺍﺯﺳﻮﺋﻴﭻ ﺩﻣﺎﻱ ﺑﺎﻻ ‪(High‬‬
‫)‪ Temp‬ﺳﻴﮕﻨﺎﻟﯽ ﺩﺭﻳﺎﻓﺖ ﺷﻮﺩ ﻭ ﻳﺎ ﻣﻘﺪﺍﺭ ﺩﻣﺎﯼ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﯼ ﺷﺪﻩ ﺳﻴﺴﺘﻢ ﮐﻪ ﺗﻮﺳﻂ ﺳﻨﺴﻮﺭ ﺩﻣﺎ‬
‫ﺳﻨﺠﻴﺪﻩ ﻣﯽ ﺷﻮﺩ ‪ ،‬ﺑﺎﻻﯼ ﺣﺪ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﺑﺮﻧﺎﻣﻪ ﺑﺎﺷﺪ ‪.‬‬
‫ﻣﺤﺪﻭﺩﻩ ‪ (P-017) Warning‬ﻭ ‪ (P-018) Alarm‬ﻫﺮﻳﻚ ﺑﺮﺍﯼ ﺳﻨﺴﻮﺭ ﺩﻣﺎ ﺑﻪ ﺻﻮﺭﺕ ﺟﺪﺍ ﻗﺎﺑﻞ‬
‫ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ ﻫﺴﺘﻨﺪ ‪.‬‬

‫‪ : Speed‬ﺍﻳﻦ ﺁﻻﺭﻡ ﺩﺭ ﺻﻮﺭﺗﯽ ﻓﻌﺎﻝ ﻣﯽ ﮔﺮﺩﺩ ﮐﻪ ﻓﺮﮐﺎﻧﺲ ﮊﻧﺮﺍﺗﻮﺭ ﺧﺎﺭﺝ ﺍﺯﻣﺤﺪﻭﺩﻩ ﺗﻌﺮﻳﻒ ﺷﺪﻩ‬
‫ﺩﺭ ﺑﺮﻧﺎﻣﻪ ﺑﺎﺷﺪ ‪ .‬ﺍﻳﻦ ﺧﻄﺎ ﭘﺲ ﺍﺯﺍﺳﺘﺎﺭﺕ ﻣﻮﺗﻮﺭ ﻭ ﺑﻌﺪ ﺍﺯ ﺳﭙﺮﯼ ﺷﺪﻥ ﺯﻣﺎﻥ ﺗﺎﺧﻴﺮ ‪ Hold OFF‬ﮐﻪ ﺩﺭ‬
‫ﭘﺎﺭﺍﻣﺘﺮ ) ‪ ( P-023‬ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺍﺳﺖ ‪ ،‬ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﺧﻮﺍﻫﺪ ﺷﺪ ‪.‬‬
‫ﺣﺪﻫﺎﯼ ﺑﺎﻻ ﻭ ﭘﺎﻳﻴﻦ ﺑﺮﺍﯼ ‪ Warning‬ﻭ ‪ Alarm‬ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮﻫﺎﯼ )‪ P-008‬ﻭ ‪ P-009‬ﻭ ‪ P-010‬ﻭ‬
‫‪ ( P-011‬ﺑﻪ ﺻﻮﺭﺕ ﺟﺪﺍ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ ﻣﯽ ﺑﺎﺷﻨﺪ ‪.‬‬

‫‪ : Start Fail‬ﺍﻳﻦ ﺁﻻﺭﻡ ﺩﺭ ﺻﻮﺭﺗﯽ ﻓﻌﺎﻝ ﻣﯽ ﮔﺮﺩﺩ ﮐﻪ ﻣﻮﺗﻮﺭ ﺑﻌﺪ ﺍﺯ ﺗﻌﺪﺍﺩ ﺩﻓﻌﺎﺕ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺷﺪﻩ‬
‫)‪ (P-035‬ﺟﻬﺖ ﺍﺳﺘﺎﺭﺕ ﺭﻭﺷﻦ ﻧﺸﻮﺩ‪.‬‬

‫‪ : Over Load‬ﺍﻳﻦ ﺁﻻﺭﻡ ﺩﺭ ﺻﻮﺭﺗﯽ ﻓﻌﺎﻝ ﻣﯽ ﺷﻮﺩ ﮐﻪ ﺣﺪﺍﻗﻞ ﻳﮑﯽ ﺍﺯ ﺟﺮﻳﺎﻧﻬﺎﯼ ﻓﺎﺯﻫﺎﯼ ﮊﻧﺮﺍﺗﻮﺭ‬
‫ﺑﺎﻻﺗﺮ ﺍﺯ ﭘﺎﺭﺍﻣﺘﺮ ﺗﻨﻈﻴﻢ ﺷﺪﻩ ‪ (P-002) Over Current Limit‬ﺑﺎﺷﺪ ﻭ ﻳﺎ ﺗﻮﺍﻧﯽ ﮐﻪ ﮊﻧﺮﺍﺗﻮﺭ ﺑﻪ ﺑﺎﺭ‬
‫‪12‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫ﻣﯽ ﺩﻫﺪ ﺑﻴﺸﺘﺮﺍﺯ ﺣﺪ ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ )‪ Excess Power(P-003‬ﺑﺎﺷﺪ ﻭ ﺯﻣﺎﻥ ﺍﺭﺍﺋﻪ ﺍﻳﻦ ﺗﻮﺍﻥ‬
‫ﺑﻴﺶ ﺍﺯ ﺯﻣﺎﻧﯽ ﺑﺎﺷﺪ ﮐﻪ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ )‪ Over Current/Excess Power Timer(P-511‬ﺗﻨﻈﻴﻢ‬
‫ﺷﺪﻩ ﺍﺳﺖ ‪ .‬ﺍﮔﺮ ﺟﺮﻳﺎﻥ ﻭﺗﻮﺍﻥ ﺑﻪ ﭘﺎﻳﻴﻦ ﺗﺮ ﺍﺯ ﻣﻘﺪﺍﺭ ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﻗﺒﻞ ﺍﺯ ﺳﭙﺮﻱ ﺷﺪﻥ ﺗﺎﻳﻤﺮ ﺑﺮﺳﺪ ﻫﻴﭻ ﮔﻮﻧﻪ‬
‫ﺧﻄﺎﻳﻲ ﺍﻋﻼﻡ ﻧﺨﻮﺍﻫﺪ ﺷﺪ‪.‬‬

‫‪ : Voltage‬ﺍﻳﻦ ﺁﻻﺭﻡ ﺯﻣﺎﻧﯽ ﻓﻌﺎﻝ ﻣﯽ ﮔﺮﺩﺩ ﮐﻪ ﻭﻟﺘﺎﮊ ﻳﮑﯽ ﺍﺯ ﻓﺎﺯﻫﺎﯼ ﮊﻧﺮﺍﺗﻮﺭﺍﺯ ﺣﺪﻫﺎﯼ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ‬
‫ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮﻫﺎﯼ )‪ ( P-006/P007‬ﺧﺎﺭﺝ ﮔﺮﺩﺩ ‪ .‬ﺍﻳﻦ ﺧﻄﺎ ﺑﻌﺪ ﺍﺯﺭﻭﺷﻦ ﺷﺪﻥ ﻣﻮﺗﻮﺭ ﻭ ﭘﺲ ﺍﺯ‬
‫ﺳﭙﺮﯼ ﺷﺪﻥ ﺯﻣﺎﻥ ﺗﺎﺧﻴﺮ ‪ Hold OFF‬ﮐﻪ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ) ‪ ( P-023‬ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺍﺳﺖ ‪ ،‬ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ‬
‫ﺧﻮﺍﻫﺪ ﺷﺪ ‪.‬‬

‫‪ : Cool Level‬ﺍﻳﻦ ﺁﻻﺭﻡ ﺯﻣﺎﻧﯽ ﻓﻌﺎﻝ ﻣﯽ ﮔﺮﺩﺩ ﮐﻪ ﺍﺯ ﻭﺭﻭﺩﯼ ﺳﻮﺋﻴﭻ ‪ Coolant Level‬ﻳﮏ‬
‫ﺳﻴﮕﻨﺎﻝ ﺑﺮﺍﯼ ﻛﻨﺘﺮﻟﺮ ﺍﺭﺳﺎﻝ ﮔﺮﺩﺩ ‪.‬‬

‫‪ : Battery‬ﺍﻳﻦ ﺁﻻﺭﻡ ﺯﻣﺎﻧﯽ ﻓﻌﺎﻝ ﻣﯽ ﮔﺮﺩﺩ ﮐﻪ ﻭﻟﺘﺎﮊ ﺑﺎﻃﺮﯼ ﺧﺎﺭﺝ ﺍﺯ ﻣﺤﺪﻭﺩﻩ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﺑﺮﻧﺎﻣﻪ‬
‫ﺑﺎﺷﺪ ‪ .‬ﺩﺭ ﻃﻮﻝ ﺍﺳﺘﺎﺭﺕ ﻣﻮﺗﻮﺭ ﺍﻳﻦ ﺧﻄﺎ ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﻧﻤﯽ ﺷﻮﺩ ‪.‬‬
‫ﺍﺧﻄﺎﺭ ﺑﺮﺍﯼ ﭘﺎﻳﻴﻦ ﺑﻮﺩﻥ ﺳﻄﺢ ﻭﻟﺘﺎﮊ ﺑﺎﻃﺮﯼ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ )‪ ( P-012‬ﻭ ﺑﺮﺍﯼ ﺑﺎﻻ ﺑﻮﺩﻥ ﺳﻄﺢ ﻭﻟﺘﺎﮊ‬
‫ﻣﻲ‬ ‫ﺍﺧﻄﺎﺭﻫﺎﻱ )‪ Warning (P-013‬ﻭ )‪ Alarm (P-014‬ﺩﺭ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ ﻗﺎﺑﻞ ﺗﻌﺮﻳﻒ‬
‫ﺑﺎﺷﻨﺪ ‪.‬‬
‫‪ : Charge‬ﺍﻳﻦ ﺁﻻﺭﻡ ﺯﻣﺎﻧﯽ ﻓﻌﺎﻝ ﻣﯽ ﺷﻮﺩ ﮐﻪ ﺩﻳﻨﺎﻡ ﺩﭼﺎﺭ ﺍﺷﻜﺎﻝ ﺷﻮﺩ )ﻳﺎ ﺗﺴﻤﻪ ﭘﺎﺭﻩ ﺷﻮﺩ( ﻭﺿﻌﻴﺖ‬
‫ﺍﻳﻦ ﺍﻳﺮﺍﺩ ﻣﻨﺠﺮ ﺑﻪ ﺧﻄﺎ ﻭ ﻳﺎ ﻫﺸﺪﺍﺭ ﻫﺎﻱ ﺯﻳﺮ ﻣﻲ ﮔﺮﺩﺩ ‪ .‬ﺑﺮﻧﺎﻣﻪ )‪(P-038‬‬

‫‪ : Rectifier Fail‬ﺍﻳﻦ ﺁﻻﺭﻡ ﺯﻣﺎﻧﯽ ﻓﻌﺎﻝ ﻣﯽ ﺷﻮﺩ ﮐﻪ ﺍﺯ ﻭﺭﻭﺩﯼ ‪ Rectifier Fail‬ﺳﻴﮕﻨﺎﻟﯽ‬


‫ﺩﺭﻳﺎﻓﺖ ﺷﻮﺩ ‪ .‬ﺍﻳﻦ ﻭﺭﻭﺩﯼ ﻓﻘﻂ ﺯﻣﺎﻧﯽ ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﻣﯽ ﺷﻮﺩ ﮐﻪ ﻭﻟﺘﺎﮊ ﺑﺮﻕ ﺷﻬﺮ ﻭﺟﻮﺩ ﺩﺍﺷﺘﻪ ﺑﺎﺷﺪ‪.‬‬
‫‪ : Emergency Stop‬ﺍﻳﻦ ﺁﻻﺭﻡ ﺯﻣﺎﻧﯽ ﻓﻌﺎﻝ ﻣﯽ ﺷﻮﺩ ﮐﻪ ﺍﺯ ﻭﺭﻭﺩﯼ ﻣﺮﺑﻮﻁ ﺑﻪ ‪Emergency‬‬
‫‪ Stop‬ﺳﻴﮕﻨﺎﻝ ﺩﺭﻳﺎﻓﺖ ﺷﻮﺩ ‪.‬‬
‫‪ : Spare‬ﺍﻳﻦ ﺁﻻﺭﻡ ﺯﻣﺎﻧﯽ ﻓﻌﺎﻝ ﻣﯽ ﺷﻮﺩ ﮐﻪ ﺍﺯ ﻳﮑﯽ ﺍﺯ ﻭﺭﻭﺩﯼ ﻫﺎﯼ ‪ Spare‬ﺳﻴﮕﻨﺎﻟﯽ ﺩﺭﻳﺎﻓﺖ‬
‫ﺷﻮﺩ ‪.‬‬

‫‪13‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪ -۵‬ﺣﺎﻟﺘﻬﺎﻱ ﻋﻤﻠﻴﺎﺗﻲ‬

‫ﻣﯽ ﺑﺎﺷﺪ ‪.‬‬ ‫ﺣﺎﻟﺘﻬﺎﻱ ﻋﻤﻠﻴﺎﺗﻲ ﺩﺭﺍﻳﻦ ﺳﻴﺴﺘﻢ ﺑﻪ ﻭﺳﻴﻠﻪ ﻓﺸﺎﺭ ﺩﺍﺩﻥ ﮐﻠﻴﺪﻫﺎﯼ ﺟﻠﻮﯼ ﻛﻨﺘﺮﻟﺮﺍﻣﮑﺎﻥ ﭘﺬﻳﺮ‬
‫ﺗﻐﻴﻴﺮ ﺣﺎﻟﺖ ﻛﺎﺭﻛﺮﺩ ﺩﺭ ﺯﻣﺎﻧﻲ ﻛﻪ ﺳﻴﺴﺘﻢ ﺩﺭ ﺣﺎﻟﺖ ﻛﺎﺭ ﺑﺎﺷﺪ ﻣﻨﺠﺮ ﺑﻪ ﻋﻤﻠﻜﺮﺩ ﺳﻴﺴﺘﻢ ﺑﻪ ﺣﺎﻟﺖ ﻛﺎﺭﻱ‬
‫ﺟﺪﻳﺪ ﻣﻲ ﺷﻮﺩ‪ .‬ﺑﺮﺍﯼ ﻣﺜﺎﻝ ﺯﻣﺎﻧﻲ ﮐﻪ ﮊﻧﺮﺍﺗﻮﺭ ﺩﺭﺣﺎﻝ ﮐﺎﺭ ﺩﺭ ﺣﺎﻟﺖ ‪ Test Mode‬ﻣﻲ ﺑﺎﺷﺪ ﻭ ﻛﻠﻴﺪ ﺩﺭ‬
‫ﺣﺎﻟﺖ ‪ Auto Mode‬ﺍﻧﺘﺨﺎﺏ ﮔﺮﺩﺩ ‪ ،‬ﺩﺭ ﺍﻳﻦ ﺣﺎﻟﺖ ﮊﻧﺮﺍﺗﻮﺭ ﺧﺎﻣﻮﺵ ﺷﺪﻩ ﻭ ﺣﺎﻟﺖ ﻭﺟﻮﺩ ﺑﺮﻕ ﺷﻬﺮ‬
‫ﺑﺮﺍﻱ ﻛﻨﺘﺮﻟﺮ ﺍﻳﺠﺎﺩ ﻣﻲ ﮔﺮﺩﺩ ‪.‬‬

‫‪ : OFF‬ﺩﺭ ﺍﻳﻦ ﺣﺎﻟﺖ‪ ،‬ﺍﮔﺮ ﻭﻟﺘﺎﮊﻓﺎﺯﻫﺎﯼ ﺑﺮﻕ ﺷﻬﺮ ﺩﺭ ﺩﺍﺧﻞ ﻣﺤﺪﻭﺩﻩ ﻫﺎﯼ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺷﺪﻩ ﺩﺭ‬
‫ﺳﻴﺴﺘﻢ ﺑﺎﺷﻨﺪ ‪ ،‬ﮐﻨﺘﺎﮐﻮﺭ ﺑﺮﻕ ﺷﻬﺮ ﻓﻌﺎﻝ ﺷﺪﻩ ﻭ ﻣﻮﺗﻮﺭ ﻣﺘﻮﻗﻒ ﺧﻮﺍﻫﺪ ﺷﺪ ‪.‬‬

‫‪ : Auto‬ﺩﺭ ﺍﻳﻦ ﺣﺎﻟﺖ ‪ ،‬ﺑﺮﻕ ﺷﻬﺮ ﻭ ﺳﻴﺴﺘﻢ ﮊﻧﺮﺍﺗﻮﺭ ﺑﻪ ﺻﻮﺭﺕ ﺧﻮﺩﮐﺎﺭ ﻋﻤﻞ ﻣﯽ ﻧﻤﺎﻳﻨﺪ ﻭ ﺍﮔﺮ ﻭﻟﺘﺎﮊ‬
‫ﻳﮑﯽ ﺍﺯ ﻓﺎﺯﻫﺎ ﺧﺎﺭﺝ ﺍﺯ ﻣﺤﺪﻭﺩﻩ ﺑﺎﺷﺪ )‪ P-004‬ﻭ ‪ ( P-005‬ﮐﻨﺘﺎﮐﺘﻮﺭ ﺑﺮﻕ ﺷﻬﺮ ﻏﻴﺮ ﻓﻌﺎﻝ ﺧﻮﺍﻫﺪ ﺷﺪ ‪.‬‬
‫ﺩﻳﺰﻝ ﺑﺎ ﺯﻣﺎﻥ ﺗﻌﺮﻳﻒ ﺷﺪﻩ )‪ (P-035‬ﻭ ﺑﻌﺪ ﺍﺯ ﺯﻣﺎﻥ ﺗﺎﺧﻴﺮ ﭘﺮﻳﻮﺩﻳﮏ )‪ (P-026‬ﺍﺳﺘﺎﺭﺕ ﺧﻮﺍﻫﺪ ﺷﺪ ‪ .‬ﺑﻪ‬
‫ﻣﺤﺾ ﺍﻳﻨﮑﻪ ﻣﻮﺗﻮﺭ ﺑﻪ ﺭﺍﻩ ﺍﻓﺘﺎﺩ ‪ ،‬ﺭﻟﻪ ﺍﺳﺘﺎﺭﺕ ﺑﻼﻓﺎﺻﻠﻪ ﻏﻴﺮ ﻓﻌﺎﻝ ﺧﻮﺍﻫﺪ ﺷﺪ ‪ .‬ﻣﻮﺗﻮﺭ ﺑﺪﻭﻥ ﺑﺎﺭ ﺗﺎ ﭘﺎﻳﺎﻥ‬
‫ﺯﻣﺎﻥ ‪ (P-029) Heating‬ﮐﺎﺭ ﺧﻮﺍﻫﺪ ﮐﺮﺩ ﻭ ﺑﻌﺪ ﺍﺯ ﺁﻥ ﺍﮔﺮ ﻧﻮﺳﺎﻥ ﻭﻟﺘﺎﮊ ﻭ ﻓﺮﮐﺎﻧﺲ ﻫﺮ ﻳﮏ ﺍﺯ ﻓﺎﺯﻫﺎ‬
‫ﺩﺭ ﺩﺍﺧﻞ ﻣﺤﺪﻭﺩﻩ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺑﺎﺷﺪ ‪ ،‬ﮐﻨﺘﺮﻟﺮ ﺻﺒﺮ ﻣﯽ ﮐﻨﺪ ﺗﺎ ﺯﻣﺎﻥ ﮊﻧﺮﺍﺗﻮﺭ‪Contactor Period‬‬
‫)‪ (P-032‬ﺳﭙﺮﯼ ﺷﻮﺩ ﻭ ﺳﭙﺲ ﮐﻨﺘﺎﮐﺘﻮﺭ ﺍﺻﻠﯽ ﮊﻧﺮﺍﺗﻮﺭ ﺭﺍ ﺑﺮﻗﺪﺍﺭ ﺧﻮﺍﻫﺪ ﮐﺮﺩ ‪.‬‬
‫ﻫﻨﮕﺎﻣﯽ ﮐﻪ ﻭﻟﺘﺎﮊ ﻫﻤﻪ ﻓﺎﺯﻫﺎﯼ ﺑﺮﻕ ﺷﻬﺮ ﺩﺭ ﺩﺍﺧﻞ ﻣﺤﺪﻭﺩﻩ ﻫﺎﯼ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﻗﺮﺍﺭ ﮔﺮﻓﺖ ‪ ،‬ﮊﻧﺮﺍﺗﻮﺭ‬
‫ﻫﻤﭽﻨﺎﻥ ﺑﻪ ﮐﺎﺭ ﺧﻮﺩ ﺍﺩﺍﻣﻪ ﺧﻮﺍﻫﺪ ﺩﺍﺩ ﺗﺎ ﺯﻣﺎﻥ ‪ ( P-030) Main Wait Period‬ﺳﭙﺮﯼ ﺷﻮﺩ ‪ .‬ﺩﺭ‬
‫ﺍﻧﺘﻬﺎﯼ ﭘﺮﻳﻮﺩ ﮐﻨﺘﺎﮐﺘﻮﺭ ﮊﻧﺮﺍﺗﻮﺭ ﺑﯽ ﺑﺮﻕ ﻣﯽ ﺷﻮﺩ ﻭ ﮐﻨﺘﺎﮐﺘﻮﺭ ﺑﺮﻕ ﺷﻬﺮ ﺑﺮﻗﺪﺍﺭ ﺧﻮﺍﻫﺪ ﺷﺪ ‪ .‬ﺍﮔﺮ ﺯﻣﺎﻥ‬
‫ﺧﻨﻚ ﺷﺪﻥ ﺩﻳﺰﻝ) ‪ (P-031) (Cooling Period‬ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺑﺎﺷﺪ‪ ،‬ﺩﻳﺰﻝ ﺗﺎ ﭘﺎ ﻳﺎﻥ ﺯﻣﺎﻥ ﺧﻨﻚ‬
‫ﺷﺪﻥ ﺑﻪ ﮐﺎﺭ ﺧﻮﺩ ﺍﺩﺍﻣﻪ ﻣﯽ ﺩﻫﺪ )ﺍﻟﺒﺘﻪ ﺩﺭ ﺣﺎﻟﺖ ﺑﯽ ﺑﺎﺭ( ﺩﺭ ﺍﻧﺘﻬﺎﯼ ﺍﻳﻦ ﺯﻣﺎﻥ ‪ Fuel Solenoid‬ﻏﻴﺮ‬
‫ﻓﻌﺎﻝ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﺩﻳﺰﻝ ﻣﺘﻮﻗﻒ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﺩﺭ ﻧﻬﺎﻳﺖ ﮐﻨﺘﺮﻟﺮﺑﺮﺍﯼ ﻗﻄﻊ ﺑﻌﺪﯼ ﺑﺮﻕ ﺷﻬﺮ ﺁﻣﺎﺩﻩ‬
‫ﻣﯽ ﺑﺎﺷﺪ ‪.‬‬

‫‪14‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫ﺍﮔﺮ ﻋﻤﻠﮑﺮﺩ ﺩﻳﺰﻝ ﺑﺎ ﺗﻮﺟﻪ ﺑﻪ ﺟﺪﻭﻝ ﺯﻣﺎﻧﺒﻨﺪﯼ ﻫﻔﺘﮕﯽ ﻏﻴﺮ ﻓﻌﺎﻝ ﺷﻮﺩ ‪ LED ،‬ﻣﺮﺑﻮﻁ ﺑﻪ ‪Auto‬‬
‫ﭼﺸﻤﮏ ﺧﻮﺍﻫﺪ ﺯﺩ ﻭ ﺩﺭ ﻧﻬﺎﻳﺖ ﻋﻤﻠﮑﺮﺩ ﻛﻨﺘﺮﻟﺮ ﺩﺭ ﺣﺎﻟﺖ ‪ OFF‬ﻗﺮﺍﺭ ﺧﻮﺍﻫﺪ ﮔﺮﻓﺖ ‪.‬‬

‫‪ : TEST‬ﺍﻳﻦ ﺣﺎﻟﺖ ﺑﺮﺍﯼ ﺗﺴﺖ ﮊﻧﺮﺍﺗﻮﺭ ﺩﺭ ﺯﻣﺎﻧﯽ ﮐﻪ ﺑﺮﻕ ﺷﻬﺮ ﺑﺮﻗﺮﺍﺭ ﺍﺳﺖ ﻭ ﻳﺎ ﻧﮕﻪ ﺩﺍﺷﺘﻦ ﮊﻧﺮﺍﺗﻮﺭ‬
‫ﺩﺭ ﺣﺎﻟﺖ ﻛﺎﺭ ﺩﺭ ﺣﺎﻟﺖ ‪ ، (P-041) Emergency Backup‬ﻣﻮﺭﺩ ﺍﺳﺘﻔﺎﺩﻩ ﻗﺮﺍﺭ ﻣﯽ ﮔﻴﺮﺩ ‪.‬‬
‫ﻋﻤﻠﮑﺮﺩ ﮊﻧﺮﺍﺗﻮﺭ ﺩﺭ ﺍﻳﻦ ﺣﺎﻟﺖ ﺷﺒﻴﻪ ﺣﺎﻟﺖ ﺍﺗﻮﻣﺎﺗﻴﮏ ﺧﻮﺍﻫﺪ ﺑﻮﺩ ﺍﻣﺎ ﮐﻨﺘﺎﮐﺘﻮﺭ ﺑﺮﻕ ﺷﻬﺮ ﻗﻄﻊ ﻧﺒﺎﺷﺪ ‪،‬‬
‫ﺩﺭ ﺍﻳﻦ ﺣﺎﻟﺖ ﭼﻨﺎﻧﭽﻪ ﮐﻨﺘﺎﮐﺘﻮﺭ ﺑﺮﻕ ﺷﻬﺮ ﻗﻄﻊ ﺷﻮﺩ ‪ ،‬ﮐﻨﺘﺎﮐﺘﻮﺭ ﮊﻧﺮﺍﺗﻮﺭ ﺑﺮﻗﺪﺍﺭ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﻫﻨﮕﺎﻣﯽ‬
‫ﮐﻪ ﺑﺮﻕ ﺷﻬﺮ ﺑﺎﺯﮔﺮﺩﺩ ‪ ،‬ﺳﻴﺴﺘﻢ ﺑﺮ ﺭﻭﯼ ﺑﺮﻕ ﺷﻬﺮ ﺗﻐﻴﻴﺮ ﻭﺿﻌﻴﺖ ﺧﻮﺍﻫﺪ ﺩﺍﺩ ‪ ،‬ﺍﻣﺎ ﻣﻮﺗﻮﺭﺑﺪﻭﻥ ﺗﻐﻴﻴﺮ ﺩﺭ‬
‫ﺣﺎﻟﺖ ﺭﻭﺷﻦ ﺑﺎﻗﻲ ﺧﻮﺍﻫﺪ ﻣﺎﻧﺪ ﻣﮕﺮ ﺍﻳﻨﻜﻪ ﺣﺎﻟﺖ ﺩﻳﮕﺮﻱ ﺍﻧﺘﺨﺎﺏ ﮔﺮﺩﺩ ‪ .‬ﺟﻬﺖ ﺧﺎﻣﻮﺵ ﻛﺮﺩﻥ ﻣﻮﺗﻮﺭ‬
‫ﻣﻲ ﺗﻮﺍﻥ ﺍﺯ ﻳﻜﻲ ﺍﺯ ﺣﺎﻟﺘﻬﺎﻱ‪ Auto‬ﻳﺎ ‪ OFF‬ﺭﺍ ﺍﻧﺘﺨﺎﺏ ﻛﺮﺩ‪.‬‬

‫‪-۶‬ﺩﻳﮕﺮ ﺧﺼﻮﺻﻴﺎﺕ ‪:‬‬


‫‪ : ۶-۱‬ﻋﻤﻠﮑﺮﺩ ﺑﻪ ﺻﻮﺭﺕ ‪Remote Start‬‬

‫)‪(P-042‬‬ ‫ﺩﺭ ﺍﻳﻦ ﻛﻨﺘﺮﻟﺮ ﺍﻣﮑﺎﻥ ﺍﺳﺘﺎﺭﺕ ﺑﻪ ﺻﻮﺭﺕ ‪ Remote‬ﭘﻴﺶ ﺑﻴﻨﯽ ﺷﺪﻩ ﺍﺳﺖ ‪ .‬ﺍﮔﺮ ﭘﺎﺭﺍﻣﺘﺮ‬
‫ﺑﺮﺍﺑﺮ ‪ ۱‬ﺩﺭ ﻧﻈﺮ ﮔﺮﻓﺘﻪ ﺷﻮﺩ ‪ ،‬ﻛﻨﺘﺮﻟﺮ ﺩﺭ ﺣﺎﻟﺖ ‪ Remote Start‬ﻗﺮﺍﺭ ﺧﻮﺍﻫﺪ ﮔﺮﻓﺖ ‪ .‬ﺳﻴﮕﻨﺎﻝ‬
‫‪ Remote Start‬ﺑﺎﻳﺪ ﺑﻪ ﻭﺭﻭﺩﯼ )‪ Spare (22‬ﻣﺘﺼﻞ ﺷﻮﺩ ‪.‬‬
‫ﻓﺮﻣﺎﻥ ‪ Remote Signal‬ﻣﻲ ﺗﻮﺍﻧﺪ ﺑﻪ ﺻﻮﺭﺕ ﻛﻨﺘﺎﻛﺖ ‪ NC‬ﻳﺎ ‪ NO‬ﺍﺭﺳﺎﻝ ﺷﻮﺩ‪ .‬ﻭ ﺑﻪ ﻫﺮ ﻳﮏ‬
‫ﺍﺯﻗﻄﺐ ﻫﺎﯼ ﺑﺎﻃﺮﯼ )‪ +‬ﻳﺎ ‪ ( -‬ﺍﺗﺼﺎﻝ ﺩﺍﺩﻩ ﺷﻮﺩ ﻭ ﺍﻧﺘﺨﺎﺏ ﻧﻮﻉ ﻛﻨﺘﺎﻛﺖ ‪ NC‬ﻳﺎ‪ NO‬ﺍﺯ ﻃﺮﻳﻖ ﻣﻨﻮﻱ‬
‫ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﻗﺎﺑﻞ ﺍﺟﺮﺍ ﻣﻲ ﺑﺎﺷﺪ‪.‬‬
‫ﻫﻤﭽﻨﻴﻦ ﺿﺮﻭﺭﻱ ﺍﺳﺖ ﻣﻘﺪﺍﺭ ﭘﺎﺭﺍﻣﺘﺮ ‪ P-077‬ﺭﻭﻱ ﻋﺪﺩ ‪ 3‬ﺗﻨﻈﻴﻢ ﮔﺮﺩﺩ ﺗﺎ ﺍﺯ ﺁﻻﺭﻡ ﻫﺎﻱ ﺗﻮﻟﻴﺪ ﺷﺪﻩ‬
‫ﺗﻮﺳﻂ ﺍﻳﻦ ﻭﺭﻭﺩﻱ ﺟﻠﻮﮔﻴﺮﻱ ﺷﻮﺩ‪.‬‬
‫ﺩﺭ ﺍﻳﻦ ﺣﺎﻟﺖ ﻓﺎﺯﻫﺎﯼ ﺑﺮﻕ ﺷﻬﺮ ﻣﻮﻧﻴﺘﻮﺭ ﻧﺨﻮﺍﻫﻨﺪ ﺷﺪ ‪ .‬ﺍﮔﺮ ﺳﻴﮕﻨﺎﻝ ‪ Remote Start‬ﻣﻮﺟﻮﺩ ﺑﺎﺷﺪ ‪،‬‬
‫ﺗﺼﻮﺭ ﺳﻴﺴﺘﻢ ﺍﻳﻦ ﺍﺳﺖ ﮐﻪ ﺑﺮﻕ ﺷﻬﺮ ﻗﻄﻊ ﺷﺪﻩ ﺍﺳﺖ ﻭ ﺑﺮﻋﮑﺲ ﺍﮔﺮ ﺳﻴﮕﻨﺎﻝ ‪Remote Start‬‬
‫ﻣﻮﺟﻮﺩ ﻧﺒﺎﺷﺪ ‪ ،‬ﺗﺼﻮﺭ ﺳﻴﺴﺘﻢ ﺍﻳﻦ ﺍﺳﺖ ﮐﻪ ﺑﺮﻕ ﺷﻬﺮ ﺑﺮﻗﺮﺍﺭ ﺍﺳﺖ ﻭ ﺩﺭ ‪ Mimic Diagram‬ﺩﺭ ﭘﻨﻞ‬
‫ﺟﻠﻮﻳﯽ ‪ LED ،‬ﺑﺮﻕ ﺷﻬﺮ ﺑﺮ ﺍﺳﺎﺱ ﻭﺭﻭﺩﻱ ‪ Remote Start‬ﻋﻤﻞ ﺧﻮﺍﻫﺪ ﮐﺮﺩ ‪.‬‬
‫‪15‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪ : ۶-۲‬ﺍﻧﺘﺨﺎﺏ ﻧﻮﻉ ﺳﻨﺴﻮﺭ‬

‫ﺳﻴﺴﺘﻢ ﻗﺎﺑﻠﻴﺖ ﺗﻄﺒﻴﻖ ﺑﺎ ﻫﺮ ﻧﻮﻉ ﺳﻨﺴﻮﺭ ﻓﺸﺎﺭ ﻳﺎ ﺩﻣﺎ ﺭﺍ ﺩﺍﺭﺍﺳﺖ ‪ .‬ﺑﻪ ﻃﻮﺭ ﻛﻠﻲ ﻣﺸﺨﺼﻪ ﺳﻨﺴﻮﺭﻫﺎﯼ‬
‫ﺍﺳﺘﺎﻧﺪﺍﺭﺩ ﺩﺭ ﺩﺍﺧﻞ ﺣﺎﻓﻈﻪ ﻛﻨﺘﺮﻟﺮ ﺛﺒﺖ ﺷﺪﻩ ﺍﺳﺖ ﻭ ﺍﺯ ﺭﻭﯼ ﻟﻴﺴﺖ ﻗﺎﺑﻞ ﺍﻧﺘﺨﺎﺏ ﺍﺳﺖ ‪ .‬ﺳﻨﺴﻮﺭﻫﺎﯼ ﻏﻴﺮ‬
‫ﺍﺳﺘﺎﻧﺪﺍﺭﺩ ﻧﻴﺰ ﻣﻤﮑﻦ ﺍﺳﺖ ﺑﺎ ﻭﺍﺭﺩ ﻛﺮﺩﻥ ﻣﺸﺨﺼﺎﺕ ﺁﻧﻬﺎ ﺩﺭ ﺟﺪﻭﻝ ﻗﺎﺑﻞ ﺍﻧﺘﺨﺎﺏ ﺑﺎﺷﻨﺪ ‪.‬‬
‫ﺍﻧﺘﺨﺎﺏ ﻧﻮﻉ ﺳﻨﺴﻮﺭ ﻓﺸﺎﺭ ‪:‬‬
‫ﻧﻮﻉ ﺳﻨﺴﻮﺭ ﻓﺸﺎﺭ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ )‪ (P-019‬ﻗﺎﺑﻞ ﺍﻧﺘﺨﺎﺏ ﺍﺳﺖ ‪ .‬ﻧﻮﻉ ﺳﻨﺴﻮﺭﻫﺎﯼ ﻗﺎﺑﻞ ﺍﻧﺘﺨﺎﺏ ﻋﺒﺎﺭﺗﻨﺪ ﺍﺯ ‪:‬‬
‫‪. ( P-142‬‬ ‫‪ : ۰‬ﻣﺸﺨﺼﺎﺕ ﺳﻨﺴﻮﺭﺩﺭ ﺟﺪﻭﻝ ﭘﺎﺭﺍﻣﺘﺮﻫﺎ ﺗﻌﻴﻴﻦ ﻣﯽ ﮔﺮﺩﺩ‪ ،‬ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ )‪ P-131‬ﺗﺎ‬
‫‪VDO 0-7bars (10-180 ohms) : ۱‬‬
‫‪VDO 0-10bars (10-180 ohms) : ۲‬‬
‫‪DATCON 0-7bars (240-33 ohms) : ۳‬‬
‫‪DATCON 0-10bars (240-33 ohms) : ۴‬‬
‫‪DATCON 0-7bars (0-90 ohms) : ۵‬‬
‫‪DATCON 0-10bars (0-90 ohms) : ۶‬‬
‫‪DATCON 0-7bars (75-10 ohms) : ۷‬‬

‫ﺍﻧﺘﺨﺎﺏ ﻧﻮﻉ ﺳﻨﺴﻮﺭ ﺩﻣﺎ ‪:‬‬

‫ﻧﻮﻉ ﺳﻨﺴﻮﺭ ﺩﻣﺎ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ‪ P-020‬ﻗﺎﺑﻞ ﺍﻧﺘﺨﺎﺏ ﺍﺳﺖ ‪ .‬ﺍﻧﻮﺍﻉ ﺳﻨﺴﻮﺭﻫﺎﯼ ﻗﺎﺑﻞ ﺍﻧﺘﺨﺎﺏ ﻋﺒﺎﺭﺗﻨﺪ ﺍﺯ ‪:‬‬
‫‪ : ۰‬ﻣﺸﺨﺼﺎﺕ ﺳﻨﺴﻮﺭ ﺩﺭ ﺟﺪﻭﻝ ﭘﺎﺭﺍﻣﺘﺮﻫﺎ ﻭ ﺩﺭﭘﺎﺭﺍﻣﺘﺮﻫﺎﯼ ‪ P-143‬ﺗﺎ ‪ P-154‬ﻗﺎﺑﻞ ﺍﻧﺘﺨﺎﺏ ﺍﺳﺖ‪.‬‬
‫‪VDO : ۱‬‬
‫‪DATCON DAH Type : ۲‬‬
‫‪DATCON DAL Type : ۳‬‬

‫‪16‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪ : ۶-۳‬ﮔﺮﻡ ﮐﺮﺩﻥ ﻣﻮﺗﻮﺭ ‪:‬‬


‫ﺑﻪ ﺻﻮﺭﺕ ﻭﻳﮋﻩ ﺩﺭ ﻣﻮﺗﻮﺭﻫﺎﻳﯽ ﺑﺪﻭﻥ ﮔﺮﻡ ﻛﻦ ﻳﺎ ﮔﺮﻡ ﻛﻦ ﻣﻌﻴﻮﺏ ‪ ،‬ﺑﻬﺘﺮ ﺍﺳﺖ ﻣﻮﺗﻮﺭ ﺗﺎ ﺭﺳﻴﺪﻥ ﺑﻪ ﺩﻣﺎﯼ‬
‫ﻣﻨﺎﺳﺐ ﺗﺤﺖ ﺑﺎﺭ ﻗﺮﺍﺭ ﻧﮕﻴﺮﺩ ‪ .‬ﺍﻳﻦ ﻛﻨﺘﺮﻟﺮ ﺩﻭ ﺭﺍﻩ ﺑﺮﺍﯼ ﺍﻳﻨﮑﺎﺭ ﭘﻴﺸﻨﻬﺎﺩ ﻣﯽ ﮐﻨﺪ ‪:‬‬

‫‪ -۱‬ﺗﺎﻳﻤﺮ ﺟﻬﺖ ﮔﺮﻡ ﺷﺪﻥ ﻣﻮﺗﻮﺭ ‪:‬‬


‫ﺍﻳﻦ ﺣﺎﻟﺖ ﺩﺭ ﺻﻮﺭﺗﯽ ﻗﺎﺑﻞ ﺍﻧﺘﺨﺎﺏ ﺍﺳﺖ ﮐﻪ ﭘﺎﺭﺍﻣﺘﺮ ‪ P-037‬ﺑﺮﺍﺑﺮ‪ 0‬ﻗﺮﺍﺭ ﮔﻴﺮﺩ ‪ .‬ﺩﺭ ﺍﻳﻦ ﺣﺎﻟﺖ‬
‫ﻣﻮﺗﻮﺭ ﺩﺭ ﻃﻮﻝ ﺯﻣﺎﻧﯽ ﮐﻪ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ‪ P-029‬ﺗﻨﻈﻴﻢ ﻣﯽ ﺷﻮﺩ ‪ ،‬ﺭﻭﺷﻦ ﺑﻮﺩﻩ ﻭ ﭘﺲ ﺍﺯ ﺳﭙﺮﻱ ﺷﺪﻥ‬
‫ﺯﻣﺎﻥ ﺗﺎﻳﻤﺮ ﺗﺤﺖ ﺑﺎﺭ ﻗﺮﺍﺭ ﻣﯽ ﮔﻴﺮﺩ ‪.‬‬

‫‪ -۲‬ﺗﺎﻳﻤﺮ ﺟﻬﺖ ﮔﺮﻡ ﺷﺪﻥ ﻣﻮﺗﻮﺭ ﻭ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺣﺮﺍﺭﺕ ﺁﺏ ﻣﻮﺗﻮﺭ ‪:‬‬
‫ﺍﻳﻦ ﺣﺎﻟﺖ ﺩﺭ ﺻﻮﺭﺗﯽ ﻗﺎﺑﻞ ﺍﻧﺘﺨﺎﺏ ﺍﺳﺖ ﮐﻪ ﭘﺎﺭﺍﻣﺘﺮ ‪ P-037‬ﺑﺮﺍﺑﺮ‪ ۱‬ﻗﺮﺍﺭ ﮔﻴﺮﺩ ‪ .‬ﺩﺭ ﺍﻳﻦ ﺣﺎﻟﺖ‬
‫ﻣﻮﺗﻮﺭ ﺩﺭ ﻃﻮﻝ ﺯﻣﺎﻧﯽ ﮐﻪ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ‪ P-029‬ﺗﻨﻈﻴﻢ ﻣﯽ ﺷﻮﺩ ‪ ،‬ﺭﻭﺷﻦ ﺑﻮﺩﻩ ﻭ ﺳﭙﺲ ﺭﻭﺷﻦ ﺑﺎﻗﯽ ﻣﯽ‬
‫ﻣﺎﻧﺪ ﺗﺎ ﻭﻗﺘﯽ ﮐﻪ ﺩﻣﺎﯼ ﻣﻮﺗﻮﺭ ﺑﻪ ﺣﺪ ﺗﻌﻴﻴﻦ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ‪ P-022‬ﺑﺮﺳﺪ‪ .‬ﻫﻨﮕﺎﻣﻲ ﮐﻪ ﺩﻣﺎ ﺑﻪ ﺣﺪ‬
‫ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺭﺳﻴﺪ ‪ ،‬ﺑﺎﺭ ﺑﺮ ﺭﻭﯼ ﮊﻧﺮﺍﺗﻮﺭ ﻗﺮﺍﺭ ﻣﻲ ﮔﻴﺮﺩ ‪ .‬ﺍﺯ ﺍﻳﻦ ﺣﺎﻟﺖ ﺑﻪ ﻋﻨﻮﺍﻥ ﭘﺸﺘﻮﺍﻧﻪ ﺳﻴﺴﺘﻢ ﮔﺮﻡ‬
‫ﻛﻦ ﻣﻮﺗﻮﺭ ﻧﻴﺰ ﺍﺳﺘﻔﺎﺩﻩ ﻣﻲ ﺷﻮﺩ ﻭ ﭼﻨﺎﻧﭽﻪ ﺩﻣﺎﻱ ﺑﺪﻧﻪ ﻣﻮﺗﻮﺭ ﺑﻪ ﺍﻧﺪﺍﺯﻩ ﻛﺎﻓﻲ ﮔﺮﻡ ﺑﺎﺷﺪ ﺳﻴﺴﺘﻢ ﺍﺯ ﮔﺮﻡ‬
‫ﮔﺮﺩﻥ ﻣﻮﺗﻮﺭ ﺑﻪ ﺍﻳﻦ ﺭﻭﺵ ﺻﺮﻑ ﻧﻈﺮ ﺧﻮﺍﻫﺪ ﻛﺮﺩ ‪.‬‬

‫‪ : ۶-۴‬ﻧﻤﺎﻳﺸﮕﺮ ﺳﺮﻭﻳﺲ ﺩﻭﺭﻩ ﺍﻱ‬


‫ﺍﻳﻦ ‪ LED‬ﺟﻬﺖ ﺗﻌﻤﻴﺮﺍﺕ ﻭ ﻧﮕﻬﺪﺍﺭﯼ ﺩﻭﺭﻩ ﺍﯼ ﺳﺎﺯﮔﺎﺭ ﺑﺎ ﮐﺎﺭﮐﺮﺩ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭﻃﺮﺍﺣﯽ ﺷﺪﻩ ﺍﺳﺖ ‪.‬‬
‫ﺗﻌﻤﻴﺮﺍﺕ ﻭ ﻧﮕﻬﺪﺍﺭﯼ ﺩﻭﺭﻩ ﺍﯼ ﺑﺮﺍﺳﺎﺱ ﺭﺳﻴﺪﻥ ﺑﻪ ﺯﻣﺎﻥ ﺧﺎﺻﯽ ﺑﺮﺍﯼ ﮐﺎﺭﮐﺮﺩ ﻣﻮﺗﻮﺭ ﻃﺮﺍﺣﯽ ﺷﺪﻩ ﺍﺳﺖ‬
‫)ﺑﻪ ﻋﻨﻮﺍﻥ ﻣﺜﺎﻝ ‪ ۲۰۰‬ﺳﺎﻋﺖ ( ‪.‬‬
‫ﺍﻣﺎ ﺍﮔﺮ ﻣﻴﺰﺍﻥ ﺳﺎﻋﺖ ﮐﺎﺭﮐﺮﺩ ﻛﺎﻣﻞ ﻧﺸﺪﻩ ﺑﺎﺷﺪ ‪ ،‬ﻛﻨﺘﺮﻟﺮ ﺑﺎ ﺭﺳﻴﺪﻥ ﺑﻪ ﺣﺪ ﺯﻣﺎﻧﯽ ﻋﻤﻞ ﺧﻮﺍﻫﺪ ﮐﺮﺩ )ﻣﺜﻼ‬
‫‪ ۱۲‬ﻣﺎﻩ ( ‪.‬‬

‫ﺗﻮﺟﻪ ‪ LED :‬ﻣﺮﺑﻮﻁ ﺑﻪ ﺳﺮﻭﻳﺲ ﺩﻭﺭﻩ ﺍﻱ ﺗﺎﺛﻴﺮﯼ ﺩﺭ ﻋﻤﻠﮑﺮﺩ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ ﻧﺨﻮﺍﻫﺪ ﺩﺍﺷﺖ ‪.‬‬

‫‪17‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫ﺍﻳﻦ ﻛﻨﺘﺮﻟﺮ ﻗﺎﺑﻠﻴﺖ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ ﺑﻪ ﺩﻭ ﺻﻮﺭﺕ ‪ ،‬ﺳﺎﻋﺖ ﮐﺎﺭﮐﺮﺩ ﻣﻮﺗﻮﺭ ﻭ ﻣﺤﺪﻭﺩﻩ ﺯﻣﺎﻧﯽ ﺗﻌﻤﻴﺮﺍﺕ ﻭ‬
‫ﻧﮕﻬﺪﺍﺭﯼ ﺭﺍ ﺩﺍﺭﺍ ﻣﻲ ﺑﺎﺷﺪ ‪ .‬ﺳﺎﻋﺖ ﮐﺎﺭﮐﺮﺩ ﻣﻮﺗﻮﺭ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ )‪ (P-044‬ﺑﺎ ﻣﺮﺣﻠﻪ‬
‫ﻫﺎﻱ ‪ ۵۰‬ﺳﺎﻋﺘﻪ ﺍﺳﺖ ﻭ ﻣﺤﺪﻭﺩﻩ ﺯﻣﺎﻧﯽ ﺗﻌﻤﻴﺮﺍﺕ ﻭ ﻧﮕﻬﺪﺍﺭﯼ ﻧﻴﺰ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ )‪ (P-045‬ﺑﺎ ﻣﺮﺣﻠﻪ ﻫﺎﻱ ‪۱‬‬
‫ﻣﺎﻫﻪ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺍﺳﺖ ‪ .‬ﺍﮔﺮ ﻫﺮ ﻳﮏ ﺍﺯ ﭘﺎﺭﺍﻣﺘﺮﻫﺎﯼ ﮔﻔﺘﻪ ﺷﺪﻩ ﺑﺎ ﻋﺪﺩ ﺻﻔﺮ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ ﺷﻮﻧﺪ ﺍﻳﻦ ﺑﻪ‬
‫ﺁﻥ ﻣﻌﻨﯽ ﺧﻮﺍﻫﺪ ﺑﻮﺩ ﮐﻪ ﺍﺯ ﺁﻥ ﭘﺎﺭﺍﻣﺘﺮﺍﺳﺘﻔﺎﺩﻩ ﻧﻤﯽ ﺷﻮﺩ ‪ .‬ﺑﻪ ﻋﻨﻮﺍﻥ ﻣﺜﺎﻝ ﺍﮔﺮ ﻣﺤﺪﻭﺩﻩ ﺯﻣﺎﻧﯽ ﺗﻌﻤﻴﺮﺍﺕ ﻭ‬
‫ﻧﮕﻪ ﺩﺍﺭﯼ ﺑﺮﺍﺑﺮ ﺻﻔﺮ ﺩﺭ ﻧﻈﺮ ﮔﺮﻓﺘﻪ ﺷﻮﺩ ‪ ،‬ﺑﻪ ﺍﻳﻦ ﻣﻌﻨﯽ ﺍﺳﺖ ﮐﻪ ﺳﻴﺴﺘﻢ ﻓﻘﻂ ﺑﺮ ﺍﺳﺎﺱ ﺳﺎﻋﺖ ﮐﺎﺭﮐﺮﺩ‬
‫ﻣﻮﺗﻮﺭ ﭘﺎﺳﺦ ﺧﻮﺍﻫﺪ ﺩﺍﺩ ﻭ ﻫﻤﭽﻨﻴﻦ ﺍﮔﺮ ﺳﺎﻋﺖ ﮐﺎﺭﮐﺮﺩ ﻧﻴﺰ ﺻﻔﺮ ﺷﻮﺩ ﺍﻳﻦ ﺑﻪ ﻣﻌﻨﯽ ﺍﺳﺖ ﮐﻪ ﻧﻤﺎﻳﺸﮕﺮ‬
‫‪ Service Request‬ﻏﻴﺮ ﻓﻌﺎﻝ ﻣﯽ ﺷﻮﺩ ‪.‬‬

‫ﻫﻨﮕﺎﻣﯽ ﮐﻪ ﺣﺪ ﺯﻣﺎﻧﯽ ﻳﺎ ﺳﺎﻋﺖ ﮐﺎﺭﮐﺮﺩ ﻣﻮﺗﻮﺭ ﺑﻪ ﭘﺎﻳﺎﻥ ﺑﺮﺳﺪ ‪ LED‬ﻣﺮﺑﻮﻁ ﺑﻪ ‪Service‬‬


‫‪ Request‬ﺷﺮﻭﻉ ﺑﻪ ﭼﺸﻤﮏ ﺯﺩﻥ ﺧﻮﺍﻫﺪ ﻧﻤﻮﺩ ‪.‬‬
‫ﺑﺮﺍﯼ ﺧﺎﻣﻮﺵ ﺷﺪﻥ ﺍﻳﻦ ‪ LED‬ﻭ ‪ Reset‬ﺗﻌﻤﻴﺮﺍﺕ ﺩﻭﺭﻩ ﺍﯼ ﮐﺎﻓﯽ ﺍﺳﺖ ﮐﻪ ﺩﻭ ﺩﮐﻤﻪ ‪Lamp Test‬‬
‫ﻭ ‪ Alarm Mute‬ﺭﺍ ﺑﺮﺍﯼ ﻣﺪﺕ ‪ ۵‬ﺛﺎﻧﻴﻪ ﺑﻪ ﺻﻮﺭﺕ ﻫﻤﺰﻣﺎﻥ ﻧﮕﻪ ﺩﺍﺭﻳﺪ ‪ .‬ﻧﻤﺎﻳﺸﮕﺮ ﺑﺎﻻﻳﻲ ﻋﺒﺎﺭﺕ "‬
‫‪ " SER‬ﺭﺍ ﻧﻤﺎﻳﺶ ﺧﻮﺍﻫﺪ ﺩﺍﺩ ‪.‬‬
‫ﺑﺎﻗﻴﻤﺎﻧﺪﻩ ﺯﻣﺎﻥ ﻛﺎﺭﻛﺮﺩ ﻣﻮﺗﻮﺭ ﻭ ﺑﺎﻗﻴﻤﺎﻧﺪﻩ ﻣﺤﺪﻭﺩﻩ ﺯﻣﺎﻧﻲ ﺩﺭ ﺣﺎﻓﻈﻪ ﻏﻴﺮ ﻓﺮﺍﺭ ﺫﺧﻴﺮﻩ ﻣﯽ ﺷﻮﻧﺪ ﻭ ﺑﺎ ﻗﻄﻊ‬
‫ﺑﺮﻕ ﺳﻴﺴﺘﻢ ﭘﺎﮎ ﻧﺨﻮﺍﻫﻨﺪ ﺷﺪ ‪.‬‬
‫ﺯﻣﺎﻥ ﺑﺎﻗﯽ ﻣﺎﻧﺪﻩ ﺑﺮﺍﯼ ﺗﻌﻤﻴﺮﺍﺕ ﻭ ﻧﮕﻬﺪﺍﺭﯼ ﻭﺳﺎﻋﺖ ﮐﺎﺭﮐﺮﺩ ﻣﻮﺗﻮﺭ ﺩﺭ ﻣﻨﻮﯼ ﺁﻣﺎﺭﯼ ‪ ،‬ﺑﺎ ﻧﮕﻪ ﺩﺍﺷﺘﻦ‬
‫ﺩﮐﻤﻪ ‪ Menu‬ﺑﻪ ﻣﺪﺕ ‪ ۱‬ﺛﺎﻧﻴﻪ ‪ ،‬ﻗﺎﺑﻞ ﻣﺸﺎﻫﺪﻩ ﺧﻮﺍﻫﺪ ﺑﻮﺩ ‪.‬‬
‫ﻭﻗﺘﻲ ﻛﻠﻴﺪ ‪ Menu‬ﻓﺸﺎﺭ ﺩﺍﺩﻩ ﻣﻲ ﺷﻮﺩ ﻧﻤﺎﻳﺸﮕﺮ ﻛﻠﻤﻪ " ‪ " Hts‬ﺳﺎﻋﺖ ﻛﺎﺭ ﺳﺮﻭﻳﺲ ﻣﻮﺗﻮﺭ )ﺑﺮ ﺣﺴﺐ‬
‫ﺳﺎﻋﺖ( ﺭﺍ ﻧﻤﺎﻳﺶ ﻣﻲ ﺩﻫﺪ ‪.‬‬
‫ﻭﻗﺘﻲ ﻛﻠﻴﺪ ‪ Menu‬ﺭﻫﺎ ﻣﻲ ﮔﺮﺩﺩ ﻧﻤﺎﻳﺸﮕﺮ ‪ ۳‬ﺭﻗﻢ ﺍﻭﻝ ﺳﺎﻋﺖ ﻛﺎﺭ ﺳﺮﻭﻳﺲ ﻣﻮﺗﻮﺭ ﺭﺍ ﻧﻤﺎﻳﺶ ﺧﻮﺍﻫﺪ‬
‫ﺩﺍﺩ ‪ .‬ﻭ ﻭﻗﺘﻲ ﺩﻭﺑﺎﺭﻩ ﻛﻠﻴﺪ ‪ Menu‬ﻓﺸﺎﺭ ﺩﺍﺩﻩ ﺷﻮﺩ ﻧﻤﺎﻳﺸﮕﺮ ﻛﻠﻤﻪ ”‪ “Hts‬ﺭﺍ ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﻭ ﭘﺲ ﺍﺯ ﺭﻫﺎ‬
‫ﻛﺮﺩﻥ ﻛﻠﻴﺪ ‪ Menu‬ﻧﻤﺎﻳﺸﮕﺮ ‪ ۳‬ﺭﻗﻢ ﺁﺧﺮ ﺳﺎﻋﺖ ﻛﺎﺭ ﺳﺮﻭﻳﺲ ﻣﻮﺗﻮﺭ ﺭﺍ ﻧﻤﺎﻳﺶ ﻣﻲ ﺩﻫﺪ ‪.‬‬
‫ﻭﻗﺘﻲ ﻛﻠﻴﺪ ‪ Menu‬ﻓﺸﺎﺭ ﺩﺍﺩﻩ ﻣﻲ ﺷﻮﺩ ﻧﻤﺎﻳﺸﮕﺮ ﻛﻠﻤﻪ " ‪ " tts‬ﺯﻣﺎﻥ ﺑﺎﻗﻴﻤﺎﻧﺪﻩ ﺑﻪ ﺳﺮﻭﻳﺲ )ﺑﺮ ﺣﺴﺐ‬
‫ﺳﺎﻋﺖ( ﺭﺍ ﻧﻤﺎﻳﺶ ﻣﻲ ﺩﻫﺪ ‪.‬‬

‫‪18‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫ﻭﻗﺘﻲ ﻛﻠﻴﺪ ‪ Menu‬ﺭﻫﺎ ﻣﻲ ﮔﺮﺩﺩ ﻧﻤﺎﻳﺸﮕﺮ ‪ ۳‬ﺭﻗﻢ ﺍﻭﻝ ﺯﻣﺎﻥ ﺑﺎﻗﻴﻤﺎﻧﺪﻩ ﺳﺮﻭﻳﺲ ﺭﺍ ﻧﻤﺎﻳﺶ ﺧﻮﺍﻫﺪ ﺩﺍﺩ ‪ .‬ﻭ‬
‫ﻭﻗﺘﻲ ﺩﻭﺑﺎﺭﻩ ﻛﻠﻴﺪ ‪ Menu‬ﻓﺸﺎﺭ ﺩﺍﺩﻩ ﺷﻮﺩ ﻧﻤﺎﻳﺸﮕﺮ ﻛﻠﻤﻪ ”‪ “tts‬ﺭﺍ ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﻭ ﭘﺲ ﺍﺯ ﺭﻫﺎ ﻛﺮﺩﻥ‬
‫ﻛﻠﻴﺪ ‪ Menu‬ﻧﻤﺎﻳﺸﮕﺮ ‪ ۳‬ﺭﻗﻢ ﺁﺧﺮ ﺯﻣﺎﻥ ﺑﺎﻗﻴﻤﺎﻧﺪﻩ ﺳﺮﻭﻳﺲ ﺭﺍ ﻧﻤﺎﻳﺶ ﻣﻲ ﺩﻫﺪ ‪.‬‬

‫‪ : -۶-۵‬ﺳﺎﻋﺖ ﻛﺎﺭﻛﺮﺩ ﻣﻮﺗﻮﺭ‬


‫ﺍﻳﻦ ﻛﻨﺘﺮﻟﺮﺩﺍﺭﺍﻱ ﺳﺎﻋﺖ ﻛﺎﺭ ﻣﻮﺗﻮﺭ ﺑﻮﺩﻩ ﮐﻪ ﻏﻴﺮ ﻗﺎﺑﻞ ﭘﺎﮎ ﮐﺮﺩﻥ ﺍﺳﺖ ﺳﺎﻋﺖ ﮐﺎﺭ ﻣﻮﺗﻮﺭ ﺩﺭ ﺣﺎﻓﻈﻪ‬
‫ﻏﻴﺮ ﻓﺮﺍﺭ ﺳﻴﺴﺘﻢ ﻧﮕﻪ ﺩﺍﺭﯼ ﻣﯽ ﺷﻮﺩ ﻭ ﺑﺎ ﻗﻄﻊ ﺑﺮﻕ ﻧﻴﺰ ﭘﺎﮎ ﻧﺨﻮﺍﻫﺪ ﺷﺪ ‪.‬‬
‫ﺳﺎﻋﺖ ﮐﺎﺭ ﻣﻮﺗﻮﺭ ﺩﺭ ﻣﻨﻮﯼ ﺁﻣﺎﺭﯼ ﺗﻮﺳﻂ ﻓﺸﺎﺭ ﺩﺍﺩﻥ ﺩﮐﻤﻪ ‪ Menu‬ﺑﻪ ﻣﺪﺕ ‪ ۱‬ﺛﺎﻧﻴﻪ‪ ،‬ﻗﺎﺑﻞ ﻣﺸﺎﻫﺪﻩ‬
‫ﺍﺳﺖ ‪.‬‬
‫ﻭﻗﺘﻲ ﻛﻠﻴﺪ ‪ Menu‬ﻓﺸﺎﺭ ﺩﺍﺩﻩ ﻣﻲ ﺷﻮﺩ ﻧﻤﺎﻳﺸﮕﺮ ﻛﻠﻤﻪ " ‪ " EnH‬ﺳﺎﻋﺖ ﻛﺎﺭﻛﺮﺩ ﻣﻮﺗﻮﺭ )ﺑﺮ ﺣﺴﺐ‬
‫ﺳﺎﻋﺖ( ﺭﺍ ﻧﻤﺎﻳﺶ ﻣﻲ ﺩﻫﺪ ‪.‬‬
‫ﻭﻗﺘﻲ ﻛﻠﻴﺪ ‪ Menu‬ﺭﻫﺎ ﻣﻲ ﮔﺮﺩﺩ ﻧﻤﺎﻳﺸﮕﺮ ‪ ۳‬ﺭﻗﻢ ﺍﻭﻝ ﺳﺎﻋﺖ ﻛﺎﺭﻛﺮﺩ ﻣﻮﺗﻮﺭ ﺭﺍ ﻧﻤﺎﻳﺶ ﺧﻮﺍﻫﺪ ﺩﺍﺩ ‪ .‬ﻭ‬
‫ﻭﻗﺘﻲ ﺩﻭﺑﺎﺭﻩ ﻛﻠﻴﺪ ‪ Menu‬ﻓﺸﺎﺭ ﺩﺍﺩﻩ ﺷﻮﺩ ﻧﻤﺎﻳﺸﮕﺮ ﻛﻠﻤﻪ ”‪ “EnH‬ﺭﺍ ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﻭ ﭘﺲ ﺍﺯ ﺭﻫﺎ‬
‫ﻛﺮﺩﻥ ﻛﻠﻴﺪ ‪ Menu‬ﻧﻤﺎﻳﺸﮕﺮ ‪ ۳‬ﺭﻗﻢ ﺁﺧﺮ ﺳﺎﻋﺖ ﻛﺎﺭﻛﺮﺩ ﻣﻮﺗﻮﺭ ﺭﺍ ﻧﻤﺎﻳﺶ ﻣﻲ ﺩﻫﺪ ‪.‬‬

‫‪ : ۶-۶‬ﺍﺭﺗﺒﺎﻁ ﺑﺎ ﻣﻮﺩﻡ‬
‫ﺩﺭ ﺑﺮﻧﺎﻣﻪ‬ ‫ﻛﻨﺘﺮﻟﺮ ﺍﻣﻜﺎﻥ ‪ Programming‬ﻭ ‪ Monitoring‬ﺭﺍ ﺍﺯ ﺍﺭﺗﺒﺎﻁ ﺑﺎ ﻣﻮﺩﻡ ﺍﻳﺠﺎﺩ ﻣﻲ ﻛﻨﺪ‪.‬‬
‫ﺑﺮﺍﯼ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ ﮐﺮﺩﻥ ﻭ ﻣﻮﻧﻴﺘﻮﺭﻳﻨﮓ ﺍﺯ ﻣﻮﺩﻡ ﺍﺳﺘﻔﺎﺩﻩ ﻣﯽ ﺷﻮﺩ ‪.‬‬
‫ﺍﮔﺮ ﺍﺯ ﻣﻮﺩﻡ ﺍﺳﺘﻔﺎﺩﻩ ﺷﻮﺩ ‪ ،‬ﭘﺎﺭﺍﻣﺘﺮ )‪ ( P-043‬ﺑﺎﻳﺪ ﺑﺮﺍﺑﺮ ﺑﺎ ‪ ۱‬ﺩﺭ ﻧﻈﺮ ﮔﺮﻓﺘﻪ ﺷﻮﺩ ‪ ،‬ﺩﺭ ﻏﻴﺮ ﺍﻳﻦ ﺻﻮﺭﺕ‬
‫ﻣﻤﮑﻦ ﺍﺳﺖ ﺧﻄﺎ ﺍﺗﻔﺎﻕ ﺑﻴﺎﻓﺘﺪ ‪.‬‬

‫‪19‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪Remote Monitoring And Programming : ۶-۷‬‬

‫ﺟﻬﺖ ‪ Down Load‬ﺑﺮﻧﺎﻣﻪ ‪ Monitoring‬ﻭ ‪ Programming‬ﺑﻪ ﺳﺎﻳﺖ ﺷﺮﮐﺖ ﻣﺮﺍﺟﻌﻪ ﻧﻤﺎﻳﻴﺪ ‪:‬‬
‫‪WWW.DATAKOM.COM.tr‬‬
‫ﺍﻳﻦ ﻧﺮﻡ ﺍﻓﺰﺍﺭ ﺍﻣﻜﺎﻥ ﺩﻳﺪﻥ ﻭ ﺛﺒﺖ ﺗﻤﺎﻣﯽ ﻣﻘﺎﺩﻳﺮ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﯼ ﺷﺪﻩ ﺭﺍ ﺑﻪ ﻛﺎﺭﺑﺮ ﻣﻲ ﺩﻫﺪ ‪ .‬ﭘﺎﺭﺍﻣﺘﺮﻫﺎﯼ‬
‫ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﯼ ﺷﺪﻩ ﺭﺍ ﻣﻲ ﺗﻮﺍﻥ ﺑﻪ ﺻﻮﺭﺕ ﮔﺮﺍﻓﻴﻜﻲ ﻣﻮﺭﺩ ﺗﺠﺰﻳﻪ ﻭ ﺗﺤﻠﻴﻞ ﻗﺮﺍﺭ ﺩﺍﺩﻩ ﻭ ﻫﻤﭽﻨﻴﻦ ﻗﺎﺑﻠﻴﺖ‬
‫ﺁﻧﻬﺎ ﻧﻴﺰ ﻭﺟﻮﺩ ﺩﺍﺭﺩ‪.‬‬
‫ﺍﻳﻦ ﻧﺮﻡ ﺍﻓﺰﺍﺭ ﻫﻤﭽﻨﻴﻦ ﺍﻣﮑﺎﻥ ﺗﻨﻈﻴﻢ ﻭ ﺫﺧﻴﺮﻩ ﺗﻤﺎﻡ ﭘﺎﺭﺍﻣﺘﺮﻫﺎ ﺭﺍ ﺍﺯ ﻃﺮﻳﻖ ‪ PC‬ﺑﻪ ﺩﺍﺧﻞ ﻛﻨﺘﺮﻟﺮ ﻭ ﺑﺎﻟﻌﻜﺲ‬
‫ﺭﺍ ﺩﺍﺭﺍ ﻣﻲ ﺑﺎﺷﺪ‪.‬‬

‫‪ : ۶-۸‬ﻛﺎﺭﻛﺮﺩ ﻧﻮﺑﺘﻲ ﺩﺭ ﺣﺎﻟﺖ ‪Auto‬‬


‫ﭼﻨﺎﻧﭽﻪ ﺑﺎﺭ ﺑﻪ ﺻﻮﺭﺕ ﻳﻚ ﺳﻴﺴﺘﻢ ﻛﻪ ﺑﺎ ﺑﺎﻃﺮﻱ ﻋﻤﻞ ﻣﻲ ﻛﻨﺪ ﻣﺎﻧﻨﺪ ﺍﻳﺴﺘﮕﺎﻫﻬﺎﻱ ‪ GSM‬ﺑﺎﺷﺪ ‪ ،‬ﺍﺣﺘﻴﺎﺝ‬
‫ﺑﻪ ﺭﻭﺷﻦ ﻛﺮﺩﻥ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ ﺑﻪ ﺻﻮﺭﺕ ﻓﻮﺭﻱ ﺑﻌﺪ ﺍﺯ ﻗﻄﻊ ﺑﺮﻕ ﻧﻤﻲ ﺑﺎﺷﺪ ‪.‬‬
‫ﭘﺎﺭﺍﻣﺘﺮ ‪ P-025‬ﺗﻌﺮﻳﻒ ﻛﻨﻨﺪﻩ ﺗﺎﺧﻴﺮ ﺩﺭ ﺣﺎﻟﺖ ﻛﺎﺭﻛﺮﺩ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ ﺑﻌﺪ ﺍﺯ ﻗﻄﻊ ﺑﺮﻕ ﺑﺮ ﺣﺴﺐ ﺩﻗﻴﻘﻪ‬
‫ﻣﻲ ﺑﺎﺷﺪ ﻭ ﻣﺤﺪﻭﺩﻩ ﺍﻳﻦ ﺗﻐﻴﻴﺮ ﺍﺯ ‪ 0-4‬ﺳﺎﻋﺖ ﻣﻲ ﺑﺎﺷﺪ‪ .‬ﻫﻤﭽﻨﻴﻦ ﺍﺣﺘﻴﺎﺝ ﺑﻪ ﺭﻭﺷﻦ ﺑﻮﺩﻥ ﮊﻧﺮﺍﺗﻮﺭ ﺑﻪ‬
‫ﺻﻮﺭﺕ ﻧﺎﻣﺤﺪﻭﺩ ﻧﻤﻲ ﺑﺎﺷﺪ ﺯﻳﺮﺍ ﺑﺎﺭ ﺑﺎﻃﺮﻱ ﻫﺎﻱ ﺧﻮﺩ ﺭﺍ ﭘﺲ ﺍﺯ ﺭﻭﺷﻦ ﺷﺪﻥ ﮊﻧﺮﺍﺗﻮﺭ ﺷﺎﺭﮊ ﺧﻮﺍﻫﺪ‬
‫ﻛﺮﺩ ‪ .‬ﺑﻨﺎﺑﺮﺍﻳﻦ ﺑﻌﺪ ﺍﺯ ﻣﺪﺕ ﺯﻣﺎﻧﻲ ﻛﻪ ﺑﺎﻃﺮﻱ ﻫﺎ ﺑﻪ ﺷﺎﺭﮊ ﻣﻨﺎﺳﺐ ﺭﺳﻴﺪ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ ﺧﺎﻣﻮﺵ ﺧﻮﺍﻫﺪ‬
‫ﺷﺪ ‪.‬‬
‫ﭘﺎﺭﺍﻣﺘﺮ ﺷﻤﺎﺭﻩ ‪ P-047‬ﺗﻌﺮﻳﻒ ﻛﻨﻨﺪﻩ ﻣﺎﻛﺰﻳﻤﻢ ﺯﻣﺎﻥ ﺗﺎﺧﻴﺮ ﺭﻭﺷﻦ ﺷﺪﻥ ﮊﻧﺮﺍﺗﻮﺭ ﺑﻮﺩﻩ ﻭ ﻣﺤﺪﻭﺩﻩ ﺁﻥ ﺍﺯ‬
‫‪ ۶‬ﺩﻗﻴﻘﻪ ﺗﺎ ‪ ۱۴‬ﺳﺎﻋﺖ ﻣﻲ ﺑﺎﺷﺪ‪ .‬ﭼﻨﺎﻧﭽﻪ ﺍﻳﻦ ﺯﻣﺎﻥ ﺗﺎﺧﻴﺮ ﺑﻪ ﻣﻘﺪﺍﺭ ﺻﻔﺮ ﺗﻨﻈﻴﻢ ﮔﺮﺩﺩ ‪ ،‬ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ ﺑﻪ‬
‫ﻣﻘﺪﺍﺭ ﻧﺎﻣﺤﺪﻭﺩ ﻛﺎﺭ ﺧﻮﺍﻫﺪ ﻛﺮﺩ ‪.‬‬
‫ﺑﺎ ﺍﺳﺘﻔﺎﺩﻩ ﻫﻤﺰﻣﺎﻥ ﺍﺯ ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ‪ P-025‬ﻭ ‪ P-047‬ﺣﺎﻟﺖ ﻛﺎﺭﻱ ﻧﻮﺑﺘﻲ ﺑﺮﺍﻱ ﮊﻧﺮﺍﺗﻮﺭ ﺩﺭ ﺍﻳﺴﺘﮕﺎﻫﻬﺎﻱ‬
‫‪ GSM‬ﺍﺳﺘﻔﺎﺩﻩ ﻣﻲ ﺷﻮﺩ ‪.‬‬

‫‪20‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪Exerciser : ۶-۹‬‬
‫ﺍﻳﻦ ﻛﻨﺘﺮﻟﺮ ﺍﻣﮑﺎﻥ ﺍﻧﺠﺎﻡ ﺁﺯﻣﺎﻳﺶ ﺍﺗﻮﻣﺎﺗﻴﻚ ﺳﻴﺴﺘﻢ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ ﺭﺍ ﺩﺍﺭﺍ ﺍﺳﺖ ‪ .‬ﻋﻤﻠﻴﺎﺕ ﺁﺯﻣﺎﻳﺶ‬
‫ﺍﺗﻮﻣﺎﺗﻴﻚ ﺭﺍ ﻣﻲ ﺗﻮﺍﻥ ﺑﻪ ﺻﻮﺭﺕ ﺭﻭﺯﺍﻧﻪ ‪ ،‬ﻫﻔﺘﮕﯽ ﻭ ﻣﺎﻫﺎﻧﻪ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ ﻛﺮﺩ ‪.‬‬
‫ﺭﻭﺯ ﻭ ﺯﻣﺎﻥ ﻭﻣﺪﺕ ﺯﻣﺎﻥ ﻛﺎﺭﻛﺮﺩ ﺍﺗﻮﻣﺎﺗﻴﻚ ﻧﻴﺰ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﻣﻲ ﺑﺎﺷﺪ‪.‬‬
‫ﺁﺯﻣﺎﻳﺶ ﺍﺗﻮﻣﺎﺗﻴﻚ ﻣﻲ ﺗﻮﺍﻧﺪ ﺑﻪ ﺻﻮﺭﺕ ﺑﺪﻭﻥ ﺑﺎﺭ ﻳﺎ ﺑﺎ ﺑﺎﺭ ﺍﻧﺠﺎﻡ ﮔﺮﺩﺩ ‪.‬‬

‫ﭘﺎﺭﺍﻣﺘﺮﻫﺎﯼ ﻣﺮﺑﻮﻁ ﺑﻪ ﺗﻨﻈﻴﻢ ﺁﺯﻣﺎﻳﺶ ﺍﺗﻮﻣﺎﺗﻴﻚ ﺷﺎﻣﻞ ‪:‬‬


‫‪ : P-113‬ﻣﺮﺑﻮﻁ ﺑﻪ ﺭﻭﺯ ﻭ ﺳﺎﻋﺖ ﺭﺍﻩ ﺍﻧﺪﺍﺯﯼ ﺍﺗﻮﻣﺎﺗﻴﻚ‬
‫‪ : P-114‬ﻣﺪﺕ ﺯﻣﺎﻥ ﺭﺍﻩ ﺍﻧﺪﺍﺯﯼ ﺍﺗﻮﻣﺎﺗﻴﻚ‬
‫‪ : P-116‬ﺭﺍﻩ ﺍﻧﺪﺍﺯﯼ ﺭﻭﺯﺍﻧﻪ‪ /‬ﻫﻔﺘﮕﻲ ‪ /‬ﻣﺎﻫﺎﻧﻪ‬

‫ﻟﻄﻔﺎ" ﺑﺮﺍﯼ ﺍﻃﻼﻋﺎﺕ ﺑﻴﺸﺘﺮ ﺑﻪ ﻗﺴﻤﺖ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ ﻣﺮﺍﺟﻌﻪ ﻧﻤﺎﻳﻴﺪ ‪.‬‬

‫ﺩﺭ ﺯﻣﺎﻥ ﻓﺮﺍ ﺭﺳﻴﺪﻥ ﺭﻭﺯ ﻭ ﺳﺎﻋﺖ ﺍﺳﺘﺎﺭﺕ ﺍﺗﻮﻣﺎﺗﻴﻚ ‪ ،‬ﻛﻨﺘﺮﻟﺮ ﺑﻪ ﺻﻮﺭﺕ ﺍﺗﻮﻣﺎﺗﻴﻚ ﺑﺮ ﺭﻭﯼ ﺣﺎﻟﺖ‬
‫‪ Test‬ﻗﺮﺍﺭ ﺧﻮﺍﻫﺪ ﮔﺮﻓﺖ‪ .‬ﻣﻮﺗﻮﺭ ﺑﻪ ﺻﻮﺭﺕ ﺧﻮﺩﮐﺎﺭ ﺭﻭﺷﻦ ﺧﻮﺍﻫﺪ ﺷﺪ ‪.‬‬
‫ﺍﮔﺮ ﻗﻄﻊ ﺑﺮﻕ ﺷﻬﺮ ﺩﺭ ﻃﻮﻝ ﺭﺍﻩ ﺍﻧﺪﺍﺯﯼ ﺍﺗﻮﻣﺎﺗﻴﻚ ﺩﺭ ﺣﺎﻟﺖ ﺑﻲ ﺑﺎﺭ ﺍﺗﻔﺎﻕ ﺑﻴﺎﻓﺘﺪ ‪ ،‬ﻛﻨﺘﺮﻟﺮ ﺍﺟﺎﺯﻩ ﺍﻧﺘﻘﺎﻝ ﺑﺎﺭ‬
‫ﺑﺮ ﺭﻭﯼ ﮊﻧﺮﺍﺗﻮﺭ ﺭﺍ ﺑﺪﻭﻥ ﺍﻳﻨﮑﻪ ‪ P-041‬ﺑﺮ ﺭﻭﯼ ‪ ۱‬ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺑﺎﺷﺪ ﺭﺍ ﻧﻤﯽ ﺩﻫﺪ ) ‪Emergency‬‬
‫‪ (backup Operation‬ﺍﺯ ﺍﻳﻨﺮﻭ ﺗﻮﺻﻴﻪ ﻣﯽ ﺷﻮﺩ ﮐﻪ ﺣﺎﻟﺖ ‪Emergency backup‬‬
‫‪ Operation‬ﺩﺭ ﺣﺎﻟﺖ ﻛﺎﺭﻱ ‪ Exerciser‬ﻓﻌﺎﻝ ﺷﻮﺩ ‪.‬‬
‫ﺑﺎ ﭘﺎﻳﺎﻥ ﺯﻣﺎﻥ ﺭﺍﻩ ﺍﻧﺪﺍﺯﯼ‪ ، Exerciser‬ﻛﻨﺘﺮﻟﺮ ﺑﻪ ﺣﺎﻟﺖ ﻛﺎﺭﻛﺮﺩ ﺍﻭﻟﻴﻪ ﺑﺎﺯ ﻣﯽ ﮔﺮﺩﺩ ‪.‬‬
‫ﺍﮔﺮ ﻳﮑﯽ ﺍﺯ ﮐﻠﻴﺪﻫﺎﯼ ﺍﻧﺘﺨﺎﺏ ﺣﺎﻟﺖ ﺩﺭ ﻃﻮﻝ ﺭﺍﻩ ﺍﻧﺪﺍﺯﯼ‪ Exerciser‬ﺍﻧﺘﺨﺎﺏ ﺷﻮﺩ ‪ ،‬ﺭﺍﻩ ﺍﻧﺪﺍﺯﯼ‬
‫‪ Exerciser‬ﻣﺘﻮﻗﻒ ﺧﻮﺍﻫﺪ ﺷﺪ ‪.‬‬

‫‪21‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪ : ۶-۱۰‬ﻛﻨﺘﺮﻝ ﺳﻠﻮﻧﻮﺋﻴﺪ ﺳﻮﺧﺖ ﻣﻮﺗﻮﺭﻫﺎﻱ ﮔﺎﺯﺳﻮﺯ‬

‫ﺩﺳﺘﮕﺎﻩ ﺩﺍﺭﺍﻱ ﻳﻚ ﺣﺎﻟﺖ ﻣﺨﺼﻮﺹ ﺟﻬﺖ ﻛﻨﺘﺮﻝ ﺳﻠﻮﻧﻮﺋﻴﺪ ﻣﻮﺗﻮﺭﻫﺎﻱ ﮔﺎﺯﺳﻮﺯ ﻣﻲ ﺑﺎﺷﺪ ‪ .‬ﺳﻠﻮﻧﻮﺋﻴﺪ‬
‫ﺳﻮﺧﺖ ﻣﻮﺗﻮﺭﻫﺎﻱ ﮔﺎﺯﺳﻮﺯ ﻣﺘﻔﺎﻭﺕ ﺍﺯ ﺳﻠﻮﻧﻮﺋﻴﺪ ﻣﻮﺗﻮﺭﻫﺎﻱ ﺩﻳﺰﻝ ﻣﻲ ﺑﺎﺷﺪ ﻭ ﻣﻲ ﺑﺎﻳﺴﺘﻲ ﺑﻌﺪ ﺍﺯ‬
‫ﺍﺳﺘﺎﺭﺕ ﺷﺪﻥ ﻣﻮﺗﻮﺭ ﺑﺎﺯ ﺷﺪﻩ ﻭ ﺩﺭ ﻫﻨﮕﺎﻡ ﻣﺪﺕ ﺍﺳﺘﺎﺭﺕ ﺑﺴﺘﻪ ﺷﻮﺩ ‪ .‬ﺗﺎﺧﻴﺮ ﺑﻴﻦ ﺯﻣﺎﻥ ﺍﺳﺘﺎﺭﺕ ﻭ ﺑﺎﺯ ﺷﺪﻥ‬
‫ﺳﻠﻮﻧﻮﺋﻴﺪ ﺳﻮﺧﺖ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ‪ p-50‬ﻗﺎﺑﻞ ﺗﻨﻈﻴﻢ ﻣﻲ ﺑﺎﺷﺪ ‪.‬‬
‫ﺣﺎﻟﺖ ﻛﺎﺭﻱ ﺳﻠﻮﻧﻮﺋﻴﺪ ﺳﻮﺧﺖ ﻣﻲ ﺗﻮﺍﻥ ﺑﻪ ﺭﻟﻪ ﻫﺎﻱ ﻛﻤﻜﻲ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ‪ P-051‬ﻭ ‪ P-052‬ﻭ‬
‫ﻫﻤﭽﻨﻴﻦ ﺑﺮﺩﻫﺎﻱ ﮔﺴﺘﺮﺵ ﺗﺨﺼﻴﺺ ﺩﺍﺩ‪.‬‬

‫‪ -۷‬ﺷﻤﺎﺭﻧﺪﻩ ﻫﺎﯼ ﺁﻣﺎﺭﯼ‬

‫ﻛﻨﺘﺮﻟﺮ ﻳﮏ ﺳﺮﯼ ﺍﺯ ﺷﻤﺎﺭﻧﺪﻩ ﻫﺎﯼ ﺍﻓﺰﺍﻳﺸﯽ ﻏﻴﺮ ﻗﺎﺑﻞ ﺭﻳﺴﺖ ﺭﺍ ﺑﺮﺍﻱ ﺛﺒﺖ ﺑﺮﺧﻲ ﺍﺯ ﻭﻗﺎﻳﻊ ﻓﺮﺍﻫﻢ ﻣﯽ‬
‫ﺁﻭﺭﺩ ﻛﻪ ﻋﺒﺎﺭﺗﻨﺪ ﺍﺯ ‪:‬‬
‫‪ -‬ﺗﻌﺪﺍﺩ ﺩﻓﻌﺎﺕ ﺍﺳﺘﺎﺭﺕ ﻣﻮﺗﻮﺭ‬
‫‪ -‬ﺗﻌﺪﺍﺩ ﺩﻓﻌﺎﺕ ﺭﻭﺷﻦ ﺷﺪﻥ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ‬
‫‪ -‬ﺗﻌﺪﺍﺩ ﺩﻓﻌﺎﺕ ﺯﻳﺮ ﺑﺎﺭ ﺭﻓﺘﻦ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ‬

‫ﺍﻳﻦ ﺷﻤﺎﺭﻧﺪﻩ ﻫﺎ ﺩﺭ ﺣﺎﻓﻈﻪ ﻏﻴﺮ ﻓﺮﺍﺭ ﺳﻴﺴﺘﻢ ﺫﺧﻴﺮﻩ ﻣﯽ ﺷﻮﻧﺪ ﻭ ﺩﺭ ﺻﻮﺭﺕ ﻗﻄﻊ ﺑﺮﻕ ﺍﺯ ﺑﻴﻦ ﻧﻤﯽ ﺭﻭﻧﺪ ‪.‬‬
‫ﺷﻤﺎﺭﻧﺪﻩ ﻫﺎ ﻱ ﺁﻣﺎﺭﻱ ﺗﻨﻬﺎ ﺍﺯ ﻃﺮﻳﻖ ‪ PC‬ﻗﺎﺑﻞ ﻧﻤﺎﻳﺶ ﻫﺴﺘﻨﺪ ﻭ ﺩﺳﺘﺮﺳﯽ ﺑﻪ ﺍﻳﻦ ﺷﻤﺎﺭﻧﺪﻩ ﻫﺎ ﻓﻘﻂ ﺩﺭ‬
‫ﺻﻮﺭﺕ ﮐﺎﺭ ﺑﺎ ﻧﺮﻡ ﺍﻓﺰﺍﺭ ﺍﻣﮑﺎﻥ ﭘﺬﻳﺮ ﺍﺳﺖ ﻭ ﻣﺸﺎﻫﺪﻩ ﺍﻳﻦ ﺷﻤﺎﺭﻧﺪﻩ ﻫﺎ ﺩﺭ ﻛﻨﺘﺮﻟﺮ ﺍﻣﮑﺎﻥ ﭘﺬﻳﺮ ﻧﻤﯽ ﺑﺎﺷﺪ ‪.‬‬

‫‪ -۸‬ﻧﮕﻬﺪﺍﺭﻱ‬

‫ﻛﻨﺘﺮﻟﺮ ﺭﺍ ﺑﺎﺯ ﻧﮑﻨﻴﺪ‬


‫ﻗﺴﻤﺖ ﻗﺎﺑﻞ ﺗﻌﻤﻴﺮﯼ ﺩﺭ ﺩﺍﺧﻞ ﺁﻥ ﻭﺟﻮﺩ ﻧﺪﺍﺭﺩ ‪.‬‬

‫ﺩﺭ ﺻﻮﺭﺕ ﻧﻴﺎﺯ ﺑﺮﺍﯼ ﺗﻤﻴﺰ ﮐﺮﺩﻥ ﺁﻥ ﺍﺯ ﭘﺎﺭﭼﻪ ﻧﻤﺪﺍﺭ ﺍﺳﺘﻔﺎﺩﻩ ﮐﻨﻴﺪ ﻭ ﺍﺯ ﻣﻮﺍﺩ ﺷﻴﻤﻴﺎﻳﻲ ﺍﺳﺘﻔﺎﺩﻩ‬
‫ﻧﮑﻨﻴﺪ ‪.‬‬
‫‪22‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪ – ۹‬ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ ﻛﻨﺘﺮﻟﺮ‬

‫ﺍﺯ ﺣﺎﻟﺖ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ ﺩﺭ ﺗﻨﻈﻴﻢ ﺗﺎﻳﻤﺮﻫﺎ ‪ ،‬ﺗﻌﺮﻳﻒ ﺣﺪﻭﺩ ﮐﺎﺭ ﺳﻴﺴﺘﻢ ﻭ ﭘﻴﮑﺮﺑﻨﺪﯼ ﺳﻴﺴﺘﻢ ﺍﺳﺘﻔﺎﺩﻩ ﻣﯽ‬
‫ﺷﻮﺩ ‪.‬‬
‫ﺑﺮﺍﯼ ﻭﺍﺭﺩ ﺷﺪﻥ ﺑﻪ ﺍﻳﻦ ﺣﺎﻟﺖ ﮐﺎﻓﯽ ﺍﺳﺖ ﮐﻪ ﺩﮐﻤﻪ ‪ Menu‬ﺭﺍ ﺑﺮﺍﯼ ﻣﺪﺕ ‪ ۵‬ﺛﺎﻧﻴﻪ ﻧﮕﻪ ﺩﺍﺭﻳﺪ ‪ ،‬ﺑﺮﺍﯼ ﺍﻳﻦ‬
‫ﻛﺎﺭ ﻻﺯﻡ ﺍﺳﺖ ﮐﻪ ﻭﺭﻭﺩﯼ ‪) Program Lock‬ﺗﺮﻣﻴﻨﺎﻝ ‪ (۲۳‬ﺑﺎﺯ ﺑﺎﺷﺪ ‪ .‬ﺍﮔﺮ ﻭﺭﻭﺩﯼ ﻣﺮﺑﻮﻃﻪ ﺯﻣﻴﻦ‬
‫ﺷﻮﺩ ﺍﺟﺎﺯﻩ ﺗﻐﻴﻴﺮﺍﺕ ﻏﻴﺮ ﻣﺠﺎﺯ ﺩﺭ ﻣﻘﺎﺩﻳﺮ ﭘﺎﺭﺍﻣﺘﺮﻫﺎﯼ ﺑﺮﻧﺎﻣﻪ ﺩﺍﺩﻩ ﻧﺨﻮﺍﻫﺪ ﺷﺪ ﺍﺯ ﺍﻳﻨﺮﻭ ﺗﻮﺻﻴﻪ ﻣﯽ ﺷﻮﺩ‬
‫ﮐﻪ ﺍﻳﻦ ﻭﺭﻭﺩﯼ ﺭﺍ ﺣﺘﻤﺎ ﺑﻪ ﺯﻣﻴﻦ ﻭﺻﻞ ﻧﻤﺎﻳﻴﺪ ‪.‬‬

‫ﺣﺎﻟﺖ ‪ Program‬ﺗﺎﺛﻴﺮﯼ ﺩﺭ ﻋﻤﻠﮑﺮﺩ ﻛﻨﺘﺮﻟﺮ ﻧﺪﺍﺭﺩ ﺍﺯ ﺍﻳﻨﺮﻭﻣﯽ ﺗﻮﺍﻥ ﺩﺭ ﻣﻮﺍﻗﻌﯽ ﮐﻪ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ‬
‫ﺩﺭﺣﺎﻝ ﮐﺎﺭ ﺍﺳﺖ ﻭﺍﺭﺩ ﺍﻳﻦ ﺣﺎﻟﺖ ﺷﺪ ﻭ ﻣﻘﺎﺩﻳﺮ ﺭﺍ ﺗﻐﻴﻴﺮ ﺩﺍﺩ ‪.‬‬

‫ﻫﻨﮕﺎﻣﯽ ﮐﻪ ﻛﻨﺘﺮﻟﺮ ﻭﺍﺭﺩ ﺣﺎﻟﺖ ‪ Program‬ﻣﯽ ﺷﻮﺩ ﺩﺭ ﻧﻤﺎﻳﺸﮕﺮ ﺑﺎﻻﯼ ﺻﻔﺤﻪ " ‪ " PGM‬ﻧﻤﺎﻳﺶ‬
‫ﺩﺍﺩﻩ ﻣﯽ ﺷﻮﺩ ﺩﺭ ﻧﻤﺎﻳﺸﮕﺮ ﻣﻴﺎﻧﯽ ﺻﻔﺤﻪ ﺷﻤﺎﺭﻩ ﭘﺎﺭﺍﻣﺘﺮ ﻭ ﻧﻤﺎﻳﺸﮕﺮ ﭘﺎﻳﻴﻨﻲ ﺻﻔﺤﻪ ﻣﻘﺪﺍﺭ ﺗﻨﻈﻴﻤﻲ ﭘﺎﺭﺍﻣﺘﺮ‬
‫ﺭﺍ ﻧﻤﺎﻳﺶ ﻣﻲ ﺩﻫﺪ‪.‬‬
‫ﻫﺮ ﺑﺎﺭ ﻓﺸﺎﺭ ﺩﺍﺩﻥ ﺩﮐﻤﻪ ‪ Menu‬ﺳﺒﺐ ﺭﻓﺘﻦ ﺑﻪ ﭘﺎﺭﺍﻣﺘﺮ ﺷﻤﺎﺭﻩ ﺑﻌﺪ ﻣﯽ ﺷﻮﺩ ‪ .‬ﺑﺎ ﻓﺸﺎﺭ ﺩﺍﺩﻥ ﻭ ﻧﮕﻪ ﺩﺍﺷﺘﻦ‬
‫ﺩﮐﻤﻪ ‪ Menu‬ﺑﺎﻋﺚ ﺍﻓﺰﺍﻳﺶ ﺑﺎ ﮔﺎﻡ ‪ ۱۰‬ﺗﺎﻳﻲ ﺩﺭ ﺷﻤﺎﺭﻩ ﭘﺎﺭﺍﻣﺘﺮ ﻣﯽ ﺷﻮﺩ ‪ .‬ﺑﻌﺪ ﺍﺯ ﺭﺳﻴﺪﻥ ﺑﻪ ﺁﺧﺮﻳﻦ‬
‫ﭘﺎﺭﺍﻣﺘﺮ ﺩﻭﺑﺎﺭﻩ ﺍﻭﻟﻴﻦ ﭘﺎﺭﺍﻣﺘﺮ ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﺧﻮﺍﻫﺪ ﺷﺪ ‪.‬‬
‫ﺑﺮﺍﯼ ﺍﻓﺰﺍﻳﺶ ﻭ ﻛﺎﻫﺶ ﻣﻘﺪﺍﺭ ﻳﮏ ﭘﺎﺭﺍﻣﺘﺮ ﺍﺯ ﺩﮐﻤﻪ ﻫﺎﯼ ‪ ‬ﻭ ‪ ‬ﺍﺳﺘﻔﺎﺩﻩ ﻧﻤﺎﻳﻴﺪ ‪ .‬ﺑﺮﺍﯼ ﺍﻓﺰﺍﻳﺶ ‪/‬‬
‫ﻛﺎﻫﺶ ﻣﻘﺪﺍﺭ ﻳﮏ ﭘﺎﺭﺍﻣﺘﺮ ﺑﺎ ﮔﺎﻡ ‪ ۱۰‬ﮐﺎﻓﯽ ﺍﺳﺖ ﮐﻪ ﺩﮐﻤﻪ ﻫﺎﯼ ‪ ‬ﻭ ‪ ‬ﺭﺍ ﻓﺸﺎﺭ ﺩﺍﺩﻩ ﻭ ﻧﮕﻪ ﺩﺍﺭﻳﺪ ‪.‬‬
‫ﭘﺎﺭﺍﻣﺘﺮﻫﺎﯼ ﺑﺮﻧﺎﻣﻪ ﺩﺭ ﺣﺎﻓﻈﻪ ﻏﻴﺮﻓﺮﺍﺭ ﺳﻴﺴﺘﻢ ﻧﮕﻬﺪﺍﺭﯼ ﻣﯽ ﺷﻮﻧﺪ ﺍﺯ ﺍﻳﻨﺮﻭ ﺑﺎ ﻗﻄﻊ ﺑﺮﻕ ﺍﻳﻦ ﻣﻘﺎﺩﻳﺮ ﺣﻔﻆ‬
‫ﺧﻮﺍﻫﻨﺪ ﺷﺪ ‪.‬‬
‫ﺑﺮﺍﯼ ﺧﺮﻭﺝ ﺍﺯ ﺣﺎﻟﺖ ‪ Progarm‬ﮐﺎﻓﯽ ﺍﺳﺖ ﮐﻪ ﻳﮑﯽ ﺍﺯ ﺩﮐﻤﻪ ﻫﺎﯼ ﺗﻐﻴﻴﺮﺣﺎﻟﺖ ﺭﺍ ﻓﺸﺎﺭ ﺩﻫﻴﺪ ﻭ ﻳﺎ‬
‫ﻛﻠﻴﺪﻫﺎﻱ ﻛﻨﺘﺮﻟﺮ ﺭﺍ ﺑﻪ ﻣﺪﺕ‪ ۱‬ﺩﻗﻴﻘﻪ ﺩﺳﺖ ﻧﺰﻧﻴﺪ ‪.‬‬

‫‪23‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫ﺟﺪﻭﻝ ﭘﺎﺭﺍﻣﺘﺮﻫﺎ‬
‫‪Pgm‬‬ ‫‪Definition‬‬ ‫‪Unit‬‬ ‫‪Std.val‬‬ ‫‪Description‬‬
‫ﻧﺎﻡ ﭘﺎﺭﺍﻣﺘﺮ‬ ‫ﺗﻨﻈﻴﻢ ﻛﺎﺭﺧﺎﻧﻪ ﻭﺍﺣﺪ‬ ‫ﺷﺮﺡ‬
‫ﻧﺴﺒﺖ ﺗﺒﺪﻳﻞ ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮ ﺟﺮﻳﺎﻥ ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﻗﺮﺍﺭ ﺩﺍﺩﻩ ﻣﯽ‬
‫‪0‬‬ ‫ﺟﺮﻳﺎﻥ ﺍﻭﻟﻴﻪ ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮ‬ ‫‪A‬‬ ‫‪500‬‬
‫ﺷﻮﺩ ‪ .‬ﻫﻤﻪ ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮ ﻫﺎﯼ ﺟﺮﻳﺎﻥ ﻣﯽ ﺑﺎﻳﺴﺖ ﺩﺍﺭﺍﻱ ﻧﺴﺒﺖ‬
‫ﺗﺒﺪﻳﻞ ﻳﻜﺴﺎﻥ ﺑﺎﺷﻨﺪ‪ .‬ﺛﺎﻧﻮﻳﻪ ﺗﺮﺍﻧﺲ ﺟﺮﻳﺎﻥ ﺑﺎﻳﺪ ‪ ۵‬ﺁﻣﭙﺮ ﺑﺎﺷﺪ ‪ .‬ﺑﺮﺍﻱ‬
‫ﻣﻘﺎﺩﻳﺮ ﺑﺎﻻﻱ ‪ ۹۹۰‬ﺁﻣﭙﺮ ‪ %۱۰‬ﻣﻘﺪﺍﺭ ﺣﻘﻴﻘﻲ ﺭﺍ ﺍﺳﺘﻔﺎﺩﻩ ﻧﻤﺎﻳﻴﺪ ‪ ،‬ﺍﻳﻦ‬
‫ﻣﻘﺎﺩﻳﺮ ﺑﻪ ﺻﻮﺭﺕ ﻛﻴﻠﻮ ﺁﻣﭙﺮ ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﺧﻮﺍﻫﺪ ﺷﺪ‪.‬‬

‫ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺭﻧﺞ ﻧﻤﺎﻳﺶ ﻣﻘﺎﺩﻳﺮ ﺟﺮﻳﺎﻥ ﻭ ﺗﻮﺍﻥ ﺍﮐﺘﻴﻮ ﺭﺍ ﻣﺸﺨﺺ‬


‫ﻣﯽ ﮐﻨﺪ‬
‫‪1‬‬ ‫ﻣﻤﻴﺰ ﺍﻋﺸﺎﺭﯼ ﺑﺮﺍﯼ ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮ‬
‫‪0‬‬
‫‪000-999 : ۰‬‬
‫ﺟﺮﻳﺎﻥ‬
‫‪0.00-9.99 : ۱‬‬
‫‪00.0-99.9 : 2‬‬
‫ﺍﮔﺮ ﻣﻘﺪﺍﺭ ﺟﺮﻳﺎﻥ ﺍﺯ ﺍﻳﻦ ﺣﺪ ﺩﺭ ﺯﻣﺎﻥ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ‪P-‬‬
‫‪ 024‬ﺑﺎﻻﺗﺮ ﺭﻭﺩ ﭘﻴﻐﺎﻡ ‪ OverLoad‬ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﺧﻮﺍﻫﺪ ﺷﺪ ‪.‬‬
‫ﻣﺤﺪﻭﺩﻳﺖ ﺍﺿﺎﻓﻪ ﺟﺮﻳﺎﻥ‬ ‫‪A‬‬ ‫‪500‬‬
‫‪2‬‬ ‫ﻣﻘﺪﺍﺭ ﺗﻨﻈﻴﻤﻲ ﺑﺎﻳﺪ ﻣﻄﺎﺑﻖ ﺑﺎ ﻣﻘﺪﺍﺭ ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ‪P-000‬‬
‫)‪( Over Current‬‬
‫ﺑﺎﺷﺪ‪.‬‬

‫ﺍﮔﺮ ﻣﻘﺪﺍﺭ ﺗﻮﺍﻥ ﺍﺯ ﺍﻳﻦ ﺣﺪ ﺩﺭ ﺯﻣﺎﻥ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ‪P-‬‬


‫‪ 024‬ﺑﺎﻻﺗﺮ ﺭﻭﺩ ﭘﻴﻐﺎﻡ ‪ OverLoad‬ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﺧﻮﺍﻫﺪ ﺷﺪ ‪.‬‬
‫‪3‬‬ ‫ﻣﺤﺪﻭﺩﻳﺖ ﺍﺿﺎﻓﻪ ﺗﻮﺍﻥ‬ ‫‪KW‬‬ ‫‪350‬‬
‫ﻣﻘﺪﺍﺭ ﺗﻨﻈﻴﻤﻲ ﺑﺎﻳﺪ ﻣﻄﺎﺑﻖ ﺑﺎ ﻣﻘﺪﺍﺭ ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ‪P-000‬‬
‫ﺑﺎﺷﺪ‪.‬‬
‫ﺍﮔﺮ ﻭﻟﺘﺎﮊ ﻳﮑﯽ ﺍﺯ ﻓﺎﺯﻫﺎﻱ ﺑﺮﻕ ﺷﻬﺮ ﺑﻪ ﺯﻳﺮ ﺣﺪ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ‬
‫ﺣﺪ ﭘﺎﻳﻴﻦ ﻭﻟﺘﺎﮊ ﺑﺮﻕ ﺷﻬﺮ‬ ‫‪V‬‬ ‫‪170‬‬
‫‪4‬‬ ‫ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺑﺮﺳﺪ ‪ ،‬ﺍﻳﻦ ﺑﻪ ﻣﻌﻨﯽ ﻗﻄﻊ ﺑﺮﻕ ﺷﻬﺮ ﺧﻮﺍﻫﺪ ﺑﻮﺩ ﻭ ﺩﻳﺰﻝ‬
‫ﮊﻧﺮﺍﺗﻮﺭ ﺩﺭ ﺣﺎﻟﺖ ‪ Test‬ﻭ ‪ Auto‬ﺍﺳﺘﺎﺭﺕ ﺧﻮﺍﻫﺪ ﺷﺪ ‪.‬‬

‫ﺍﮔﺮ ﻭﻟﺘﺎﮊ ﻳﮑﯽ ﺍﺯ ﻓﺎﺯﻫﺎﻱ ﺑﺮﻕ ﺷﻬﺮ ﺑﻪ ﺑﺎﻻﯼ ﺣﺪ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ‬
‫‪5‬‬ ‫ﺣﺪ ﺑﺎﻻﯼ ﻭﻟﺘﺎﮊﺑﺮﻕ ﺷﻬﺮ‬ ‫ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺑﺮﺳﺪ ‪ ،‬ﺍﻳﻦ ﺑﻪ ﻣﻌﻨﯽ ﻗﻄﻊ ﺑﺮﻕ ﺷﻬﺮ ﺧﻮﺍﻫﺪ ﺑﻮﺩ ﻭ ﺩﻳﺰﻝ‬
‫‪V‬‬ ‫‪270‬‬
‫ﮊﻧﺮﺍﺗﻮﺭ ﺩﺭﺣﺎﻟﺖ ‪ Test‬ﻭ ‪ Auto‬ﺍﺳﺘﺎﺭﺕ ﺧﻮﺍﻫﺪ ﺷﺪ‬

‫ﺍﮔﺮ ﻭﻟﺘﺎﮊ ﻳﮑﯽ ﺍﺯ ﻓﺎﺯﻫﺎﯼ ﮊﻧﺮﺍﺗﻮﺭ ﺑﻪ ﺯﻳﺮ ﺣﺪ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﺍﻳﻦ‬


‫ﭘﺎﺭﺍﻣﺘﺮ ﺑﺮﺳﺪ )ﺩﺭ ﺷﺮﺍﻳﻄﯽ ﮐﻪ ﺯﻳﺮ ﺑﺎﺭ ﺍﺳﺖ( ‪ ،‬ﺁﻻﺭﻡ ﻭﻟﺘﺎﮊ ﻧﻤﺎﻳﺶ‬
‫‪6‬‬ ‫ﺣﺪ ﭘﺎﻳﻴﻦ ﻭﻟﺘﺎﮊ ﮊﻧﺮﺍﺗﻮﺭ‬ ‫‪V‬‬ ‫‪180‬‬
‫ﺩﺍﺩﻩ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﻣﻮﺗﻮﺭ ﻣﺘﻮﻗﻒ ﺧﻮﺍﻫﺪ ﺷﺪ ‪.‬‬

‫‪24‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪Pgm‬‬ ‫‪Definition‬‬ ‫‪Unit‬‬ ‫‪Std.val‬‬ ‫‪Description‬‬


‫ﻧﺎﻡ ﭘﺎﺭﺍﻣﺘﺮ‬ ‫ﺗﻨﻈﻴﻢ ﻛﺎﺭﺧﺎﻧﻪ ﻭﺍﺣﺪ‬ ‫ﺷﺮﺡ‬
‫ﺍﮔﺮ ﻭﻟﺘﺎﮊ ﻳﮑﯽ ﺍﺯ ﻓﺎﺯﻫﺎﯼ ﮊﻧﺮﺍﺗﻮﺭ ﺑﻪ ﺑﺎﻻﯼ ﺣﺪ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ‬
‫ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺑﺮﺳﺪ ) ﺩﺭ ﺷﺮﺍﻳﻄﯽ ﮐﻪ ﺯﻳﺮ ﺑﺎﺭ ﺍﺳﺖ ( ‪ ،‬ﺁﻻﺭﻡ ﻭﻟﺘﺎﮊ‬
‫‪7‬‬ ‫ﺣﺪ ﺑﺎﻻﻱ ﻭﻟﺘﺎﮊ ﮊﻧﺮﺍﺗﻮﺭ‬ ‫‪V‬‬ ‫‪270‬‬
‫ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﺧﻮﺍﻫﺪ ﺷﺪ‪ ،‬ﻭ ﻣﻮﺗﻮﺭ ﻣﺘﻮﻗﻒ ﺧﻮﺍﻫﺪ ﺷﺪ ‪.‬‬

‫ﺍﮔﺮ ﻓﺮﮐﺎﻧﺲ ﮊﻧﺮﺍﺗﻮﺭ ﺑﻪ ﺯﻳﺮ ﺣﺪ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺑﺮﺳﺪ‬


‫‪ ،‬ﺁﻻﺭﻡ ‪ Speed‬ﻇﺎﻫﺮ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﻣﻮﺗﻮﺭ ﺭﺍ ﻣﺘﻮﻗﻒ ﺧﻮﺍﻫﺪ‬
‫‪8‬‬ ‫ﺁﻻﺭﻡ ﺣﺪ ﭘﺎﻳﻴﻦ ﻓﺮﮐﺎﻧﺲ ﮊﻧﺮﺍﺗﻮﺭ‬ ‫‪Hz‬‬ ‫‪30‬‬
‫ﮐﺮﺩ ‪ .‬ﺍﻳﻦ ﺁﻻﺭﻡ ﺗﻨﻬﺎ ﺩﺭ ﺯﻣﺎﻧﯽ ﮐﻪ ﻣﻮﺗﻮﺭ ‪ Run‬ﺍﺳﺖ ﻭ ﺑﻌﺪ ﺍﺯ‬
‫‪ Delay Time‬ﮐﻪ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ‪ P-023‬ﺗﻌﻴﻴﻦ ﻣﯽ ﮔﺮﺩﺩ ﻇﺎﻫﺮ‬
‫ﺧﻮﺍﻫﺪ ﺷﺪ ‪.‬‬

‫ﺍﮔﺮ ﻓﺮﮐﺎﻧﺲ ﮊﻧﺮﺍﺗﻮﺭ ﺑﻪ ﺯﻳﺮ ﺣﺪ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺑﺮﺳﺪ‬


‫‪ ،‬ﻫﺸﺪﺍﺭ ﻣﺮﺑﻮﻁ ﺑﻪ ‪ Speed‬ﻇﺎﻫﺮ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﺍﻳﻦ ﺍﺧﻄﺎﺭ ﺑﻌﺪ ﺍﺯ‬
‫‪9‬‬ ‫ﻫﺸﺪﺍﺭ ﭘﺎﻳﻴﻦ ﺭﻓﺘﻦ ﻓﺮﮐﺎﻧﺲ‬
‫‪Hz‬‬ ‫‪40‬‬ ‫ﺗﺎﺧﻴﺮﻱ ﮐﻪ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ‪ P-023‬ﺗﻌﻴﻴﻦ ﻣﯽ ﮔﺮﺩﺩ ﻋﻤﻞ ﺧﻮﺍﻫﺪ‬
‫ﮊﻧﺮﺍﺗﻮﺭ ﺍﺯ ﻣﻘﺪﺍﺭ ﺗﻌﻴﻴﻦ ﺷﺪﻩ‬
‫ﮐﺮﺩ ‪.‬‬
‫ﺍﮔﺮ ﻓﺮﮐﺎﻧﺲ ﮊﻧﺮﺍﺗﻮﺭ ﺑﻪ ﺑﺎﻻﯼ ﺣﺪ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ‬
‫ﺑﺮﺳﺪ ‪ ،‬ﻫﺸﺪﺍﺭ ﻣﺮﺑﻮﻁ ﺑﻪ ‪ Speed‬ﻇﺎﻫﺮ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﺍﻳﻦ ﺍﺧﻄﺎﺭ‬
‫‪Hz‬‬ ‫‪54‬‬
‫‪10‬‬ ‫ﻫﺸﺪﺍﺭ ﺑﺎﻻﺭﻓﺘﻦ ﻓﺮﮐﺎﻧﺲ ﮊﻧﺮﺍﺗﻮﺭ‬
‫ﺑﻌﺪ ﺍﺯ ﺗﺎﺧﻴﺮﻱ ﮐﻪ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ‪ P-023‬ﺗﻌﻴﻴﻦ ﻣﯽ ﮔﺮﺩﺩ ﻇﺎﻫﺮ‬
‫ﺍﺯ ﻣﻘﺪﺍﺭ ﺗﻌﻴﻴﻦ ﺷﺪﻩ‬
‫ﺧﻮﺍﻫﺪ ﺷﺪ ‪.‬‬

‫ﺍﮔﺮ ﻓﺮﮐﺎﻧﺲ ﮊﻧﺮﺍﺗﻮﺭ ﺑﻪ ﺑﺎﻻﯼ ﺣﺪ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ‬


‫ﺑﺮﺳﺪ ‪ ،‬ﺁﻻﺭﻡ ‪ Speed‬ﻇﺎﻫﺮ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﻣﻮﺗﻮﺭ ﺭﺍ ﻣﺘﻮﻗﻒ‬
‫‪11‬‬ ‫ﺁﻻﺭﻡ ﺑﺎﻻﺭﻓﺘﻦ ﻓﺮﮐﺎﻧﺲ ﮊﻧﺮﺍﺗﻮﺭ‬ ‫‪Hz‬‬ ‫‪57‬‬ ‫ﺧﻮﺍﻫﺪ ﮐﺮﺩ ‪ .‬ﺍﻳﻦ ﺁﻻﺭﻡ ﺗﻨﻬﺎ ﺩﺭ ﺯﻣﺎﻧﯽ ﮐﻪ ﻣﻮﺗﻮﺭ ‪ Run‬ﺍﺳﺖ ﻭ‬
‫ﺍﺯ ﻣﻘﺪﺍﺭ ﺗﻌﻴﻴﻦ ﺷﺪﻩ‬ ‫ﺑﻌﺪ ﺍﺯ ﺗﺎﺧﻴﺮﻱ ﮐﻪ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ‪ P-023‬ﺗﻌﻴﻴﻦ ﻣﯽ ﮔﺮﺩﺩ ﻇﺎﻫﺮ‬
‫ﺧﻮﺍﻫﺪ ﺷﺪ‬

‫ﺍﮔﺮ ﻭﻟﺘﺎﺯ ﺑﺎﻃﺮﯼ ﺑﻪ ﺯﻳﺮ ﻣﻘﺪﺍﺭ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺑﺮﺳﺪ ‪،‬‬
‫ﻫﺸﺪﺍﺭ ﭘﺎﻳﻴﻦ ﺁﻣﺪﻥ ﻭﻟﺘﺎﮊ ﺑﺎﻃﺮﯼ‬
‫‪12‬‬ ‫ﻫﺸﺪﺍﺭ ﻣﺮﺑﻮﻁ ﺑﻪ‪ Battery‬ﻇﺎﻫﺮ ﺧﻮﺍﻫﺪ ﺷﺪ ‪.‬‬
‫‪V‬‬ ‫‪9.0‬‬
‫ﺍﺯ ﻣﻘﺪﺍﺭ ﺗﻌﻴﻴﻦ ﺷﺪﻩ‬

‫ﺍﮔﺮ ﻭﻟﺘﺎﮊ ﺑﺎﻃﺮﯼ ﺑﻪ ﺑﺎﻻﯼ ﻣﻘﺪﺍﺭ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺑﺮﺳﺪ‬
‫ﻫﺸﺪﺍﺭ ﺑﺎﻻﺭﻓﺘﻦ ﻭﻟﺘﺎﮊ ﺑﺎﻃﺮﯼ ﺍﺯ‬ ‫‪V‬‬ ‫‪31.0‬‬
‫‪13‬‬ ‫‪ ،‬ﻫﺸﺪﺍﺭ ﻣﺮﺑﻮﻁ ﺑﻪ ‪ Battery‬ﻇﺎﻫﺮ ﺧﻮﺍﻫﺪ ﺷﺪ ‪.‬‬
‫ﻣﻘﺪﺍﺭ ﺗﻌﻴﻴﻦ ﺷﺪﻩ‬

‫‪25‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪Pgm‬‬ ‫‪Definition‬‬ ‫‪Unit‬‬ ‫‪Std.val‬‬ ‫‪Description‬‬


‫ﻧﺎﻡ ﭘﺎﺭﺍﻣﺘﺮ‬ ‫ﺗﻨﻈﻴﻢ ﻛﺎﺭﺧﺎﻧﻪ ﻭﺍﺣﺪ‬ ‫ﺷﺮﺡ‬
‫ﺍﮔﺮ ﻭﻟﺘﺎﮊ ﺑﺎﻃﺮﯼ ﺑﻪ ﺑﺎﻻﯼ ﻣﻘﺪﺍﺭ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺑﺮﺳﺪ‬
‫ﺁﻻﺭﻡ ﺑﺎﻻﺭﻓﺘﻦ ﻭﻟﺘﺎﮊ ﺑﺎﻃﺮﯼ ﺍﺯ‬
‫‪14‬‬ ‫‪ ،‬ﺁﻻﺭﻡ ‪ Battery‬ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﻣﻮﺗﻮﺭ ﺭﺍ ﻣﺘﻮﻗﻒ‬
‫‪V‬‬ ‫‪33.0‬‬
‫ﻣﻘﺪﺍﺭ ﺗﻌﻴﻴﻦ ﺷﺪﻩ‬
‫ﻣﯽ ﮐﻨﺪ ‪.‬‬

‫ﺍﮔﺮ ﻓﺸﺎﺭ ﺭﻭﻏﻦ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﯼ ﺷﺪﻩ ﺩﺭ ﺁﻧﺎﻟﻮﮒ ﻭﺭﻭﺩﯼ ﺑﻪ ﺯﻳﺮ ﺍﻳﻦ‬
‫‪15‬‬ ‫ﺣﺪ ﺑﺮﺳﺪ ‪ ،‬ﻫﺸﺪﺍﺭ ﻣﺮﺑﻮﻁ ﺑﻪ ‪ Oil Pressure‬ﻇﺎﻫﺮ ﺧﻮﺍﻫﺪ‬
‫ﻫﺸﺪﺍﺭﭘﺎﻳﻴﻦ ﺑﻮﺩﻥ ﻓﺸﺎﺭ ﺭﻭﻏﻦ‬ ‫‪Bar‬‬ ‫‪1.5‬‬
‫ﺷﺪ ﺍﻳﻦ ﻭﺭﻭﺩﯼ ﻓﻘﻂ ﻭﻗﺘﯽ ﻓﻌﺎﻝ ﺧﻮﺍﻫﺪ ﺷﺪ ﮐﻪ ﻣﻮﺗﻮﺭ ‪ Run‬ﺑﺎﺷﺪ‬
‫ﻭ ﺯﻣﺎﻥ ﺗﻌﻴﻴﻦ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ‪ P-023‬ﺳﭙﺮﯼ ﺷﺪﻩ ﺑﺎﺷﺪ‪.‬‬

‫ﺍﮔﺮ ﻓﺸﺎﺭ ﺭﻭﻏﻦ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﯼ ﺷﺪﻩ ﺩﺭ ﺁﻧﺎﻟﻮﮒ ﻭﺭﻭﺩﯼ ﺑﻪ ﺯﻳﺮ ﺍﻳﻦ‬
‫ﺣﺪ ﺑﺮﺳﺪ ‪ ،‬ﺁﻻﺭﻡ ﻣﺮﺑﻮﻁ ﺑﻪ ‪ Oil Pressure‬ﻇﺎﻫﺮ ﺧﻮﺍﻫﺪ ﺷﺪ‬
‫‪16‬‬ ‫ﺁﻻﺭﻡ ﭘﺎﻳﻴﻦ ﺑﻮﺩﻥ ﻓﺸﺎﺭ ﺭﻭﻏﻦ‬ ‫ﺍﻳﻦ ﻭﺭﻭﺩﯼ ﻓﻘﻂ ﻭﻗﺘﯽ ﻓﻌﺎﻝ ﺧﻮﺍﻫﺪ ﺷﺪ ﮐﻪ ﻣﻮﺗﻮﺭ ‪ Run‬ﺑﺎﺷﺪ ﻭ‬
‫‪Bar‬‬ ‫‪1.0‬‬
‫ﺯﻣﺎﻥ ﺗﻌﻴﻴﻦ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ‪ P-023‬ﺳﭙﺮﯼ ﺷﺪﻩ ﺑﺎﺷﺪ ‪.‬‬

‫ﺍﮔﺮ ﺩﻣﺎﯼ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﯼ ﺷﺪﻩ ﺗﻮﺳﻂ ﻭﺭﻭﺩﯼ ﻫﺎﯼ ﺁﻧﺎﻟﻮﮒ ﺍﺯ‬
‫‪C‬‬ ‫‪90‬‬ ‫ﺩﻣﺎﯼ ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺑﻴﺸﺘﺮ ﺍﺯ ﻣﻘﺪﺍﺭ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺷﻮﺩ‬
‫‪17‬‬ ‫ﻫﺸﺪﺍﺭ ﺑﺎﻻ ﺑﻮﺩﻥ ﺩﻣﺎﻱ ﺁﺏ‬
‫‪ ،‬ﻫﺸﺪﺍﺭ ﻣﺮﺑﻮﻁ ﺑﻪ ‪ High Temp‬ﻇﺎﻫﺮ ﺧﻮﺍﻫﺪ ﺷﺪ ‪.‬‬
‫ﺍﮔﺮ ﺩﻣﺎﯼ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﯼ ﺷﺪﻩ ﺗﻮﺳﻂ ﻭﺭﻭﺩﯼ ﺁﻧﺎﻟﻮﮒ ﺍﺯ ﺩﻣﺎﯼ‬
‫ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺑﻴﺸﺘﺮ ﺷﻮﺩ ‪ ،‬ﺁﻻﺭﻡ ﻣﺮﺑﻮﻁ ﺑﻪ ‪High‬‬
‫ﺁﻻﺭﻡ ﺑﺎﻻ ﺑﻮﺩﻥ ﺩﻣﺎﻱ ﺁﺏ‬ ‫‪C‬‬ ‫‪98‬‬
‫‪18‬‬ ‫‪ Temp‬ﻇﺎﻫﺮ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﻣﻮﺗﻮﺭ ﺭﺍ ﻣﺘﻮﻗﻒ ﺧﻮﺍﻫﺪ ﮐﺮﺩ ‪.‬‬
‫ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﻧﻮﻉ ﺳﻨﺴﻮﺭ ﻓﺸﺎﺭ ﺭﻭﻏﻦ ﺭﺍ ﺗﻌﻴﻴﻦ ﻣﯽ ﮐﻨﺪ‬
‫‪ : ۰‬ﺳﻨﺴﻮﺭ ﺍﺳﺘﺎﻧﺪﺍﺭﺩ ﻧﻴﺴﺖ ﻭ ﻣﺸﺨﺼﺎﺕ ﺳﻨﺴﻮﺭ ﺩﺭ ﺟﺪﻭﻝ‬
‫ﻣﯽ‬ ‫ﭘﺎﺭﺍﻣﺘﺮﻫﺎ ﻭ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮﻫﺎﯼ ‪ P-131‬ﺗﺎ ‪ P-142‬ﺗﻌﻴﻴﻦ‬
‫ﮔﺮﺩﺩ ‪.‬‬
‫‪19‬‬ ‫ﺍﻧﺘﺨﺎﺏ ﻧﻮﻉ ﺳﻨﺴﻮﺭ ﻓﺸﺎﺭ ﺭﻭﻏﻦ‬
‫‪-‬‬ ‫‪1‬‬
‫‪VDO 0-7bars (10-180 ohms) : ۱‬‬
‫‪VDO 0-10bars (10-180 ohms) : ۲‬‬
‫‪DATCON 0-7bars (240-33 ohms) : ۳‬‬
‫‪DATCON0-10bars (240-33 ohms) : ۴‬‬
‫‪DATCON 0-7bars (0-90 ohms) : ۵‬‬
‫‪DATCON 0-10bars (0-90 ohms) : ۶‬‬
‫‪DATCON 0-7bars (75-10 ohms) : ۷‬‬

‫‪26‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪Pgm‬‬ ‫‪Definition‬‬ ‫‪Unit‬‬ ‫‪Std.val‬‬ ‫‪Description‬‬


‫ﻧﺎﻡ ﭘﺎﺭﺍﻣﺘﺮ‬ ‫ﺗﻨﻈﻴﻢ ﻛﺎﺭﺧﺎﻧﻪ ﻭﺍﺣﺪ‬ ‫ﺷﺮﺡ‬
‫ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﻧﻮﻉ ﺳﻨﺴﻮﺭ ﺩﻣﺎﻱ ﺁﺏ ﺭﺍ ﺗﻌﻴﻴﻦ ﻣﯽ ﮐﻨﺪ‬
‫‪ : ۰‬ﺳﻨﺴﻮﺭ ﺍﺳﺘﺎﻧﺪﺍﺭﺩ ﻧﻴﺴﺖ ﻭ ﻣﺸﺨﺼﺎﺕ ﺳﻨﺴﻮﺭ ﺩﺭ ﺟﺪﻭﻝ‬
‫ﭘﺎﺭﺍﻣﺘﺮﻫﺎ ﻭ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮﻫﺎﯼ ‪ P-143‬ﻭ ‪ P-154‬ﺗﻌﻴﻴﻦ ﻣﯽ ﮔﺮﺩﺩ ‪.‬‬
‫‪20‬‬ ‫ﺍﻧﺘﺨﺎﺏ ﻧﻮﻉ ﺳﻨﺴﻮﺭ ﺩﻣﺎﻱ ﺁﺏ‬ ‫‪-‬‬ ‫‪1‬‬
‫‪VDO : ۱‬‬
‫‪DATCON DAH type : ۲‬‬
‫‪DATCON DAL type : ۳‬‬

‫ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺑﺎﻋﺚ ﻣﺤﺪﻭﺩ ﻛﺮﺩﻥ ﻭﻟﺘﺎﮊ ﮊﻧﺮﺍﺗﻮﺭ ﻭ ﺑﺮﻕ ﺷﻬﺮﺑﻪ‬


‫ﻛﻤﻚ ﻳﻚ ﺑﺎﺯﻩ ﻛﻨﺘﺮﻟﻲ ﺟﻬﺖ ﺟﻠﻮﮔﻴﺮﯼ ﺍﺯ ﺧﻄﺎﯼ ﺍﺣﺘﻤﺎﻟﯽ ﻣﻲ‬
‫ﮔﺮﺩﺩ‪.‬‬
‫‪21‬‬ ‫ﻭﻟﺘﺎﮊ ﻫﻴﺴﺘﺮﻳﺰﻳﺲ‬ ‫‪V‬‬ ‫‪8‬‬ ‫ﺑﺮﺍﻱ ﻣﺜﺎﻝ ﻫﻨﮕﺎﻣﻲ ﻛﻪ ﺑﺮﻕ ﺷﻬﺮ ﻭﺟﻮﺩ ﺩﺍﺭﺩ ﭘﺎﺭﺍﻣﺘﺮ‪ P_004‬ﺑﻪ‬
‫ﻋﻨﻮﺍﻥ ﺣﺪ ﭘﺎﻳﻴﻦ ﻭﻟﺘﺎﮊ ﺩﺭ ﻧﻈﺮ ﮔﺮﻓﺘﻪ ﻣﻲ ﺷﻮﺩ ﻭ ﺩﺭ ﻫﻨﮕﺎﻡ ﻗﻄﻊ‬
‫ﺑﺮﻕ ﺷﻬﺮ ﺟﻤﻊ ﺩﻭ ﭘﺎﺭﺍﻣﺘﺮ ‪ P_004+P_021‬ﺑﻪ ﻋﻨﻮﺍﻥ ﺣﺪ ﭘﺎﻳﻴﻦ‬
‫ﻭﻟﺘﺎﮊ ﺩﺭ ﻧﻈﺮ ﮔﺮﻓﺘﻪ ﻣﻲ ﺷﻮﺩ ‪ .‬ﺗﻮﺻﻴﻪ ﻣﯽ ﺷﻮﺩ ﻣﻘﺪﺍﺭ ‪ ۸‬ﺑﺮﺍﻱ ﺍﻳﻦ‬
‫ﭘﺎﺭﺍﻣﺘﺮ ﺩﺭﻧﻈﺮ ﮔﺮﻓﺘﻪ ﺷﻮﺩ‬

‫ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﻧﺸﺎﻥ ﺩﻫﻨﺪﻩ ﺩﻣﺎﻳﻲ ﺍﺳﺖ ﻛﻪ ﻛﻨﺘﺮﻟﺮ ﺗﺎ ﺭﺳﻴﺪﻥ ﺩﻣﺎﻱ‬


‫ﻣﻮﺗﻮﺭ ﺑﻪ ﺍﻳﻦ ﻣﻘﺪﺍﺭ ﺍﺟﺎﺯﻩ ﺑﺎﺭ ﺩﺍﺭ ﺷﺪﻥ ﮊﻧﺮﺍﺗﻮﺭ ﺭﺍ ﻧﻤﻲ ﺩﻫﺪ ‪.‬‬
‫‪22‬‬ ‫ﺩﻣﺎﯼ ﻣﻮﺗﻮﺭ‬ ‫‪C‬‬ ‫‪50‬‬

‫ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺯﻣﺎﻥ ﺗﺎﺧﻴﺮﯼ ﺭﺍ ﺗﻌﺮﻳﻒ ﻣﯽ ﮐﻨﺪ ﮐﻪ ﺑﻌﺪ ﺍﺯ ‪Run‬‬


‫‪23‬‬ ‫ﺗﺎﻳﻤﺮ ﺗﺎﺧﻴﺮ‬ ‫‪Sec‬‬ ‫‪8‬‬
‫ﺷﺪﻥ ﻣﻮﺗﻮﺭ‪،‬ﺩﺭ ﺁﻥ ﺯﻣﺎﻥ ‪ Fault‬ﻫﺎ ﻓﻌﺎﻝ ﻧﻤﻲ ﺷﻮﻧﺪ ‪.‬‬

‫ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺯﻣﺎﻥ ﺗﺎﺧﻴﺮﻱ ﺍﺳﺖ ﮐﻪ ﺩﺭ ﺻﻮﺭﺕ ﺗﺠﺎﻭﺯ ﮐﺮﺩﻥ‬


‫ﺗﺎﻳﻤﺮﺗﺎﺧﻴﺮﺍﺿﺎﻓﻪ ﺟﺮﻳﺎﻥ) ‪Over‬‬ ‫ﺟﺮﻳﺎﻥ ﻭ ﺗﻮﺍﻥ ﺍﮐﺘﻴﻮ ﺍﺯ ﺣﺪﻭﺩ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ) ‪ P-002‬ﻭ ‪P-‬‬
‫‪24‬‬ ‫‪ ، (Current‬ﺍﺿﺎﻓﻪ ﺗﻮﺍﻥ ﻭ‬ ‫‪ (003‬ﻻﺯﻡ ﺍﺳﺖ ﺳﭙﺮﯼ ﺷﻮﺩ ﺗﺎ ﺁﻻﺭﻡ ﻇﺎﻫﺮ ﮔﺮﺩﺩ ‪.‬‬
‫ﻓﺮﮐﺎﻧﺲ‬ ‫‪Sec‬‬ ‫‪3‬‬ ‫ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺑﺮﺍﯼ ﺣﺪﻭﺩ ﻓﺮﮐﺎﻧﺲ )‪ P-008‬ﻭ ‪ (P-011‬ﻭ ﻇﺎﻫﺮ‬
‫ﺷﺪﻥ ﺁﻻﺭﻡ ‪ Speed Fault‬ﻧﻴﺰ ﺻﺎﺩﻕ ﺍﺳﺖ‪.‬‬

‫ﺗﺎﻳﻤﺮﺗﺎﺧﻴﺮﻓﻌﺎﻝ ﺷﺪﻥ ﺷﻴﺮ ﺳﻮﺧﺖ ﭘﺲ ﺍﺯ ﻗﻄﻊ ﺑﺮﻕ ﺷﻬﺮ ﻭ ﻗﺒﻞ ﺍﺯ‬


‫ﺗﺎﻳﻤﺮﺗﺎﺧﻴﺮ ﻓﻌﺎﻝ ﺷﺪﻥ ﺷﻴﺮ‬ ‫‪Min‬‬ ‫‪0‬‬
‫‪25‬‬ ‫ﺍﺳﺘﺎﺭﺕ ﻣﻮﺗﻮﺭ ﻛﻪ ﺍﺯ ﺍﺳﺘﺎﺭﺕ ﻧﺎﺧﻮﺍﺳﺘﻪ ﻣﻮﺗﻮﺭ ﺟﻠﻮﮔﻴﺮﻱ ﻣﻲ‬
‫ﺳﻮﺧﺖ‬
‫ﻧﻤﺎﻳﺪ‪.‬‬

‫‪27‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪Pgm‬‬ ‫‪Definition‬‬ ‫‪Unit‬‬ ‫‪Std.val‬‬ ‫‪Description‬‬


‫ﻧﺎﻡ ﭘﺎﺭﺍﻣﺘﺮ‬ ‫ﺗﻨﻈﻴﻢ ﻛﺎﺭﺧﺎﻧﻪ ﻭﺍﺣﺪ‬ ‫ﺷﺮﺡ‬
‫ﺯﻣﺎﻥ ﺑﻴﻦ ﻓﻌﺎﻝ ﺷﺪﻥ ﺷﻴﺮ ﺳﻮﺧﺖ ﻭ ﺍﺳﺘﺎﺭﺕ ﻣﻮﺗﻮﺭ ‪ ،‬ﺩﺭ ﺍﻳﻦ ﺑﺎﺯﻩ‬
‫‪26‬‬ ‫ﺯﻣﺎﻥ ﭘﻴﺶ ﮔﺮﻡ ﻛﻦ‬ ‫‪Sec‬‬ ‫‪1‬‬
‫ﺯﻣﺎﻧﻲ ﺭﻟﻪ ﻣﺮﺑﻮﻁ ﺑﻪ ﭘﻴﺶ ﮔﺮﻡ ﻛﻦ ﺩﺭ ﺻﻮﺭﺕ ﻓﻌﺎﻝ ﺑﻮﺩﻥ‬
‫ﭘﺎﺭﺍﻣﺘﺮ ﻣﺮﺑﻮﻃﻪ ﻓﻌﺎﻝ ﻣﻲ ﮔﺮﺩﺩ‪.‬‬

‫ﻣﺪﺕ ﺯﻣﺎﻥ ﺍﺳﺘﺎﺭﺕ ﺭﺍ ﻣﺸﺨﺺ ﻣﯽ ﮐﻨﺪ ‪ .‬ﺩﺭ ﺻﻮﺭﺕ ﺭﻭﺷﻦ ﺷﺪﻥ‬


‫ﮊﻧﺮﺍﺗﻮﺭ ‪ ،‬ﺍﺳﺘﺎﺭﺕ ﺑﻪ ﺻﻮﺭﺕ ﺍﺗﻮﻣﺎﺗﻴﮏ ﻗﺒﻞ ﺍﺯ ﺑﻪ ﭘﺎﻳﺎﻥ ﺭﺳﻴﺪﻥ ﺍﻳﻦ‬
‫ﺯﻣﺎﻥ ﺍﺳﺘﺎﺭﺕ‬ ‫‪Sec‬‬ ‫‪6‬‬
‫‪27‬‬ ‫ﺯﻣﺎﻥ ﻗﻄﻊ ﻣﯽ ﺷﻮﺩ‬

‫ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﻓﺎﺻﻠﻪ ﺯﻣﺎﻧﯽ ﺑﻴﻦ ﺩﻭ ﺍﺳﺘﺎﺭﺕ ﺭﺍ ﻣﺸﺨﺺ ﻣﯽ ﮐﻨﺪ ‪.‬‬


‫‪28‬‬ ‫ﺯﻣﺎﻥ ﺑﻴﻦ ﺍﺳﺘﺎﺭﺕ ﻫﺎ‬ ‫‪Sec‬‬ ‫‪10‬‬

‫ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺑﺮﺍﯼ ﮔﺮﻡ ﮐﺮﺩﻥ ﻣﻮﺗﻮﺭ ﺍﺳﺘﻔﺎﺩﻩ ﻣﯽ ﺷﻮﺩﺑﺮﺍﺳﺎﺱ‬


‫‪29‬‬ ‫ﺯﻣﺎﻥ ﮔﺮﻡ ﮐﺮﺩﻥ ﻣﻮﺗﻮﺭ‬ ‫‪Sec‬‬ ‫‪3‬‬
‫ﻣﻘﺪﺍﺭﺗﻨﻈﻴﻤﻲ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ‪P-037‬‬
‫ﺯﻣﺎﻥ ﺗﺎﺧﻴﺮ ﭘﺲ ﺍﺯ ﺑﺮﮔﺸﺖ ﺑﺮﻕ ﺷﻬﺮ ﺩﺭ ﻣﺤﺪﻭﺩﻩ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ‪،‬‬
‫‪30‬‬ ‫ﺯﻣﺎﻥ ﺍﻧﺘﻈﺎﺭﭘﺲ ﺍﺯ ﺑﺮﮔﺸﺖ ﺑﺮﻕ‬ ‫‪Min‬‬ ‫‪0.5‬‬
‫ﻭ ﻗﻄﻊ ﺷﺪﻥ ﮐﻨﺘﺎﮐﺘﻮﺭ ﮊﻧﺮﺍﺗﻮﺭ ‪.‬‬
‫ﺷﻬﺮ‬
‫ﺑﺎﺯﻩ ﺯﻣﺎﻧﯽ ﻛﺎﺭﻛﺮﺩ ﺑﺪﻭﻥ ﺑﺎﺭ ﮊﻧﺮﺍﺗﻮﺭ ﺑﻪ ﻣﻨﻈﻮﺭﺧﻨﮏ ﺷﺪﻥ ﻣﻮﺗﻮﺭ‬
‫ﺯﻣﺎﻥ ﺧﻨﻚ ﺷﺪﻥ‬ ‫‪Min‬‬ ‫‪1.0‬‬
‫‪31‬‬ ‫‪ ،‬ﺑﻌﺪ ﺍﺯ ﺑﺮﮔﺸﺖ ﺑﺮﻕ ﺷﻬﺮ ﻭ ﺍﻧﺘﻘﺎﻝ ﺑﺎﺭ ﺑﻪ ﺑﺮﻕ ﺷﻬﺮ ‪.‬‬

‫ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﻣﺪﺕ ﺯﻣﺎﻧﯽ ﺍﺳﺖ ﮐﻪ ﺑﻌﺪ ﺍﺯ ﻏﻴﺮ ﻓﻌﺎﻝ ﺷﺪﻥ ﮐﻨﺘﺎﮐﺘﻮﺭ‬
‫‪32‬‬ ‫ﺗﺎﻳﻤﺮ ﺗﺎﺧﻴﺮ ﻭﺻﻞ ﮐﻨﺘﺎﮐﺘﻮﺭ‬ ‫‪Sec‬‬ ‫‪1‬‬
‫ﺑﺮﻕ ﺷﻬﺮ ﻻﺯﻡ ﺍﺳﺖ ﺳﭙﺮﯼ ﺷﻮﺩ ﻭ ﺑﻌﺪ ﺍﺯ ﺁﻥ ﮐﻨﺘﺎﮐﺘﻮﺭ ﮊﻧﺮﺍﺗﻮﺭ‬
‫ﮊﻧﺮﺍﺗﻮﺭ‬
‫ﻭﺻﻞ ﮔﺮﺩﺩ ‪.‬‬
‫ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﻣﺪﺕ ﺯﻣﺎﻧﯽ ﺍﺳﺖ ﮐﻪ ﺑﻌﺪ ﺍﺯ ﻏﻴﺮ ﻓﻌﺎﻝ ﺷﺪﻥ ﮐﻨﺘﺎﮐﺘﻮﺭ‬
‫‪33‬‬ ‫ﺗﺎﻳﻤﺮ ﺗﺎﺧﻴﺮ ﻭﺻﻞ ﮐﻨﺘﺎﮐﺘﻮﺭ ﺑﺮﻕ‬ ‫‪Sec‬‬ ‫‪1‬‬
‫ﮊﻧﺮﺍﺗﻮﺭ‪ ،‬ﻻﺯﻡ ﺍﺳﺖ ﮐﻪ ﺳﭙﺮﯼ ﺷﻮﺩ ﻭ ﺑﻌﺪ ﺍﺯ ﺁﻥ ﮐﻨﺘﺎﮐﺘﻮﺭ ﺑﺮﻕ‬
‫ﺷﻬﺮ‬
‫ﺷﻬﺮ ﻭﺻﻞ ﺷﻮﺩ ‪.‬‬
‫ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺑﻴﺸﺘﺮﻳﻦ ﺣﺪ ﺯﻣﺎﻥ ﺭﺍ ﺑﺮﺍﯼ ﺗﻮﻗﻒ ﻣﻮﺗﻮﺭ ﺗﻌﻴﻴﻦ ﻣﯽ‬
‫ﮐﻨﺪ ‪ .‬ﺩﺭ ﻃﻮﻝ ﺍﻳﻦ ﺯﻣﺎﻥ ﺭﻟﻪ ﺧﺮﻭﺟﯽ ‪ Stop‬ﻓﻌﺎﻝ ﺧﻮﺍﻫﺪ ﺷﺪ ‪.‬‬
‫ﺗﺎﻳﻤﺮ ﺧﺎﻣﻮﺵ ﺷﺪﻥ‬ ‫‪Sec‬‬ ‫‪10‬‬ ‫)ﺍﻟﺒﺘﻪ ﺍﮔﺮ ﺑﻪ ﻭﺳﻴﻠﻪ ﺑﺮﻧﺎﻣﻪ ﺗﻌﺮﻳﻒ ﺷﻮﺩ( ﺍﮔﺮ ﻣﻮﺗﻮﺭ ﺑﻌﺪ ﺍﺯ ﻣﺪﺕ‬
‫‪34‬‬ ‫ﺯﻣﺎﻥ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﻣﺘﻮﻗﻒ ﻧﺸﻮﺩ ‪ ،‬ﺁﻻﺭﻡ ‪ Stop Fail‬ﻇﺎﻫﺮ‬
‫ﺧﻮﺍﻫﺪ ﺷﺪ ‪.‬‬
‫ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺑﻴﺸﺘﺮﻳﻦ ﺗﻌﺪﺍﺩ ﺩﻓﻌﺎﺕ ﺍﺳﺘﺎﺭﺕ ﺭﺍ ﻣﺸﺨﺺ ﻣﯽ ﮐﻨﺪ ‪.‬‬
‫‪35‬‬ ‫ﺗﻌﺪﺍﺩ ﺩﻓﻌﺎﺕ ﺍﺳﺘﺎﺭﺕ‬ ‫‪-‬‬ ‫‪3‬‬

‫‪28‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪Pgm‬‬ ‫‪Definition‬‬ ‫‪Unit‬‬ ‫‪Std.val‬‬ ‫‪Description‬‬


‫ﻧﺎﻡ ﭘﺎﺭﺍﻣﺘﺮ‬ ‫ﺗﻨﻈﻴﻢ ﻛﺎﺭﺧﺎﻧﻪ ﻭﺍﺣﺪ‬ ‫ﺷﺮﺡ‬
‫ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﻣﺪﺕ ﺯﻣﺎﻧﯽ ﺭﺍ ﺗﻌﻴﻴﻦ ﻣﯽ ﮐﻨﺪ ﮐﻪ ﺧﺮﻭﺟﯽ ‪ Horn‬ﺩﺭ‬
‫ﻃﻮﻝ ﺁﻥ ﻓﻌﺎﻝ ﺧﻮﺍﻫﺪ ﺑﻮﺩ ‪.‬‬
‫‪36‬‬ ‫ﺗﺎﻳﻤﺮ ﺁﮊﻳﺮ‬ ‫‪Sec‬‬ ‫‪10‬‬
‫ﺍﮔﺮ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ‪ 0‬ﺑﺎﺷﺪ ﺑﻪ ﻣﻌﻨﯽ ﻧﺎﻣﺤﺪﻭﺩ ﺑﻮﺩﻥ ﻣﺪﺕ ﺯﻣﺎﻥ ﺁﮊﻳﺮ‬
‫ﻣﻲ ﺑﺎﺷﺪ‪.‬‬

‫ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﻧﺤﻮﻩ ﮔﺮﻡ ﮐﺮﺩﻥ ﻣﻮﺗﻮﺭ ﺭﺍ ﺗﻌﻴﻴﻦ ﻣﻴﮑﻨﺪ ‪ .‬ﮊﻧﺮﺍﺗﻮﺭ ﻗﺒﻞ‬
‫ﺍﺯ ﺍﺗﻤﺎﻡ ﻋﻤﻠﻴﺎﺕ ﮔﺮﻡ ﺷﺪﻥ ﺯﻳﺮ ﺑﺎﺭ ﻧﻤﯽ ﺭﻭﺩ ‪.‬‬
‫‪P-‬‬ ‫‪ : 0‬ﻣﻮﺗﻮﺭ ﺩﺭ ﻃﻮﻝ ﻣﺪﺕ ﺯﻣﺎﻥ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ‬
‫‪37‬‬ ‫ﺗﻌﻴﻴﻦ ﻧﺤﻮﻩ ﮔﺮﻡ ﮐﺮﺩﻥ ﻣﻮﺗﻮﺭ‬ ‫‪-‬‬ ‫‪0‬‬ ‫‪ 029‬ﺩﺭ ﺣﺎﻝ ﮔﺮﻡ ﺷﺪﻥ ﻣﯽ ﺑﺎﺷﺪ ‪.‬‬
‫‪ : ۱‬ﻣﻮﺗﻮﺭ ﻭﻗﺘﯽ ﮔﺮﻡ ﺷﺪﻩ ﺗﻠﻘﯽ ﻣﯽ ﺷﻮﺩ ﮐﻪ ﺩﻣﺎﯼ ﺁﻥ ﺑﻪ ﺩﻣﺎﯼ‬
‫ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ‪ P-022‬ﺑﺮﺳﺪ ﻭ ﺣﺪﺍﻗﻞ ‪ ،‬ﻣﺪﺕ ﺯﻣﺎﻥ‬
‫ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ‪ P-029‬ﺳﭙﺮﻱ ﺷﺪﻩ ﺑﺎﺷﺪ‪.‬‬

‫‪ : 0‬ﻭﺭﻭﺩﯼ ﺷﺎﺭﮊ ﻫﺸﺪﺍﺭ ﺩﻫﺪ ﻭ ﻣﻮﺗﻮﺭ ﺭﺍ ﻣﺘﻮﻗﻒ ﻧﺴﺎﺯﺩ‬


‫‪38‬‬ ‫ﻭﺭﻭﺩﯼ ‪ Charge‬ﺁﻻﺭﻡ‬ ‫‪-‬‬ ‫‪0‬‬
‫‪ : ۱‬ﻭﺭﻭﺩﯼ ﺷﺎﺭﮊ ‪ Alarm‬ﺩﻫﺪ ﻭ ﻣﻮﺗﻮﺭ ﺭﺍ ﻣﺘﻮﻗﻒ ﺳﺎﺯﺩ ‪.‬‬
‫‪39‬‬ ‫‪Not Used‬‬
‫‪40‬‬ ‫‪Not Used‬‬
‫‪ : ۰‬ﺩﺭ ﺣﺎﻟﺖ ﺗﺴﺖ ﻫﺮﮔﺎﻩ ﺑﺮﻕ ﺷﻬﺮ ﻗﻄﻊ ﮔﺮﺩﺩ ﺑﺎﺭ ﺑﺮ ﺭﻭﯼ‬
‫ﮊﻧﺮﺍﺗﻮﺭ ﻗﺮﺍﺭ ﻧﻤﻲ ﮔﻴﺮﺩ‪.‬‬
‫‪41‬‬ ‫‪-‬‬ ‫‪0‬‬
‫ﻋﻤﻠﮑﺮﺩ ﺩﺭ ﺣﺎﻟﺖ ﺍﺿﻄﺮﺍﺭﯼ‬ ‫‪ :۱‬ﺩﺭ ﺣﺎﻟﺖ ﺗﺴﺖ ﻫﺮﮔﺎﻩ ﺑﺮﻕ ﺷﻬﺮ ﻗﻄﻊ ﮔﺮﺩﺩ ﺑﺎﺭ ﺑﺮ ﺭﻭﯼ ﮊﻧﺮﺍﺗﻮﺭ‬
‫ﻗﺮﺍﺭ ﻣﻲ ﮔﻴﺮﺩ ‪.‬‬
‫‪ : ۰‬ﺣﺎﻟﺖ ‪ Remote Start‬ﻓﻌﺎﻝ ﻧﺒﺎﺷﺪ ‪ .‬ﻣﻮﺗﻮﺭ ﺩﺭ ﺻﻮﺭﺗﯽ ﮐﻪ‬
‫ﺑﺮﻕ ﺷﻬﺮ ﻗﻄﻊ ﺷﻮﺩ ﺭﻭﺷﻦ ﻣﻲ ﺷﻮﺩ ‪.‬‬
‫ﻋﻤﻠﮑﺮﺩ ‪RemoteStart‬‬ ‫‪-‬‬ ‫‪0‬‬
‫‪42‬‬ ‫‪ : ۱‬ﺣﺎﻟﺖ ‪ Remote Start‬ﻓﻌﺎﻝ ﺑﺎﺷﺪ ‪ .‬ﻛﻨﺘﺮﻟﺮ ﻭﻟﺘﺎﮊ ﺑﺮﻕ ﺷﻬﺮ‬
‫ﺭﺍ ﺩﺭ ﻧﻈﺮ ﻧﻤﻲ ﮔﻴﺮﺩ ﻭ ﻣﻮﺗﻮﺭ ﻓﻘﻂ ﺩﺭ ﺻﻮﺭﺗﯽ ﺭﻭﺷﻦ ﻣﻲ ﺷﻮﺩ‬
‫ﮐﻪ ﻭﺭﻭﺩﯼ )‪ Remote Start (22‬ﻭﺻﻞ ﺑﺎﺷﺪ ‪.‬‬
‫‪ : 0‬ﻣﻮﺩﻡ ﻣﺘﺼﻞ ﻧﻴﺴﺖ ‪ .‬ﺍﺯ ﭘﻮﺭﺕ ﺳﺮﻳﺎﻝ ﺑﺮﺍﯼ ﺍﺗﺼﺎﻝ ﺑﻪ ‪PC‬‬
‫ﺍﺗﺼﺎﻝ ﻣﻮﺩﻡ‬ ‫‪-‬‬ ‫‪0‬‬
‫‪43‬‬ ‫ﺍﺳﺘﻔﺎﺩﻩ ﻣﯽ ﺷﻮﺩ ‪.‬‬
‫‪ : ۱‬ﻣﻮﺩﻡ ﻣﺘﺼﻞ ﺍﺳﺖ ‪.‬‬

‫‪29‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪Pgm‬‬ ‫‪Definition‬‬ ‫‪Unit‬‬ ‫‪Std.val‬‬ ‫‪Description‬‬


‫ﻧﺎﻡ ﭘﺎﺭﺍﻣﺘﺮ‬ ‫ﺗﻨﻈﻴﻢ ﻛﺎﺭﺧﺎﻧﻪ ﻭﺍﺣﺪ‬ ‫ﺷﺮﺡ‬
‫‪ LED‬ﻣﺮﺑﻮﻁ ﺑﻪ ‪ Service Request‬ﺑﻌﺪ ﺍﺯ ﺳﭙﺮﯼ ﺷﺪﻥ ﺍﻳﻦ‬
‫ﺯﻣﺎﻥ ﺍﺯ ﺁﺧﺮﻳﻦ ﺗﻌﻤﻴﺮﺍﺕ ﻭ ﻧﮕﻬﺪﺍﺭﯼ ﺭﻭﺷﻦ ﺧﻮﺍﻫﺪ ﺷﺪ ‪.‬‬
‫‪44‬‬ ‫ﻣﺪﺕ ﺯﻣﺎﻥ ﺗﻌﻤﻴﺮﺍﺕ ﻭ ﻧﮕﻬﺪﺍﺭﯼ‬ ‫ﺳﺎﻋﺖ‬ ‫‪200‬‬
‫ﺩﺭ ﺻﻮﺭﺕ ﺍﻧﺘﺨﺎﺏ ﻋﺪﺩ ‪ 0‬ﻧﻴﺎﺯ ﺑﻪ ﺗﻌﻤﻴﺮﺍﺕ ﻭ ﻧﮕﻬﺪﺍﺭﯼ ﺑﺮﺍﯼ‬
‫)ﺳﺎﻋﺖ ﮐﺎﺭﮐﺮﺩ ﻣﻮﺗﻮﺭ(‬
‫ﮊﻧﺮﺍﺗﻮﺭ ﻧﺨﻮﺍﻫﺪ ﺑﻮﺩ ‪.‬‬
‫‪ LED‬ﻣﺮﺑﻮﻁ ﺑﻪ ‪ Service Request‬ﺑﻌﺪ ﺍﺯ ﺳﭙﺮﯼ ﺷﺪﻥ ﺍﻳﻦ‬
‫ﺯﻣﺎﻥ ﺍﺯ ﺁﺧﺮﻳﻦ ﺗﻌﻤﻴﺮﺍﺕ ﻭ ﻧﮕﻬﺪﺍﺭﯼ ﺭﻭﺷﻦ ﺧﻮﺍﻫﺪ ﺷﺪ‬
‫ﻣﺪﺕ ﺯﻣﺎﻥ ﺗﻌﻤﻴﺮﺍﺕ ﻭ ﻧﮕﻬﺪﺍﺭﯼ‬
‫‪45‬‬ ‫ﻣﺎﻩ‬ ‫‪6‬‬ ‫ﺩﺭ ﺻﻮﺭﺕ ﺍﻧﺘﺨﺎﺏ ﻋﺪﺩ ‪ 0‬ﻧﻴﺎﺯ ﺑﻪ ﺗﻌﻤﻴﺮﺍﺕ ﻭ ﻧﮕﻬﺪﺍﺭﯼ ﺑﺮﺍﯼ‬
‫)ﻣﺎﻫﺎﻧﻪ(‬
‫ﮊﻧﺮﺍﺗﻮﺭ ﻧﺨﻮﺍﻫﺪ ﺑﻮﺩ‬
‫‪46‬‬ ‫‪Not Used‬‬
‫‪47‬‬ ‫ﻣﺎﻛﺰﻳﻤﻢ ﺯﻣﺎﻥ ﻛﺎﺭﻛﺮﺩ ﻣﻮﺗﻮﺭ‬ ‫ﺳﺎﻋﺖ‬ ‫‪0‬‬ ‫ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﻣﺎﻛﺰﻳﻤﻢ ﺯﻣﺎﻥ ﻛﺎﺭﻛﺮﺩ ﻣﻮﺗﻮﺭ ﺗﻌﻴﻴﻦ ﻣﻲ ﮔﺮﺩﺩ ﻭ‬
‫ﭼﻨﺎﻧﭽﻪ ﺍﻳﻦ ﺯﻣﺎﻥ ﺑﻪ ﻣﻘﺪﺍﺭ ‪ 0‬ﺗﻨﻈﻴﻢ ﮔﺮﺩﺩ ﻣﻮﺗﻮﺭ ﺑﻪ ﻃﻮﺭ ﻧﺎﻣﺤﺪﻭﺩ‬
‫ﻛﺎﺭ ﺧﻮﺍﻫﺪ ﻛﺮﺩ ‪ .‬ﺩﺭ ﺳﻴﺴﺘﻢ ﻫﺎﻳﻲ ﻛﻪ ﺑﺎ ﺑﺎﻃﺮﻱ ﻛﺎﺭ ﻣﻲ ﻛﻨﻨﺪ ﻧﻴﺎﺯ‬
‫ﺑﻪ ﻛﺎﺭﻛﺮﺩ ﻣﻮﺗﻮﺭ ﺑﻪ ﺻﻮﺭﺕ ﻧﺎﻣﺤﺪﻭﺩ ﻧﻤﻲ ﺑﺎﺷﺪ‪ .‬ﺑﺎ ﺗﻮﺟﻪ ﺑﻪ‬
‫ﻗﺎﺑﻠﻴﺖ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﻣﻮﺗﻮﺭ ﭘﺲ ﺍﺯ ﺷﺎﺭﮊ ﻛﺎﻓﻲ ﺑﺎﻃﺮﻱ ﺧﺎﻣﻮﺵ‬
‫ﺧﻮﺍﻫﺪ ﺷﺪ‪.‬‬
‫‪48‬‬ ‫‪Not Used‬‬
‫‪49‬‬ ‫‪Not Used‬‬
‫ﺳﻠﻮﻧﻮﺋﻴﺪ ﺳﻮﺧﺖ ﻣﻮﺗﻮﺭ ﮔﺎﺯﺳﻮﺯ ﭘﺲ ﺍﺯ ﺳﭙﺮﻱ ﺷﺪﻥ ﺯﻣﺎﻥ ﺗﺎﺧﻴﺮ‬
‫ﺗﺎﺧﻴﺮ ﺯﻣﺎﻥ ﺳﻠﻮﻧﻮﺋﻴﺪ ﺳﻮﺧﺖ‬
‫ﺩﺭ ﻫﻨﮕﺎﻡ ﺍﺳﺘﺎﺭﺕ ﻣﻮﺗﻮﺭ ﺑﺎﺯ ﺧﻮﺍﻫﺪ ﺷﺪ‬
‫‪50‬‬
‫ﻣﻮﺗﻮﺭ ﮔﺎﺯﺳﻮﺯ‬ ‫‪5‬‬
‫ﺛﺎﻧﻴﻪ‬

‫ﭘﺎﺭﺍﻣﺘﺮ ‪ P-051‬ﺗﺎ ‪ P-052‬ﻋﻤﻠﻴﺎﺕ ﻣﺨﺘﻠﻒ ﺭﺍ ﺑﺮﺍﯼ ﺭﻟﻪ ﻫﺎﯼ ﺧﺮﻭﺟﯽ ﺗﻌﺮﻳﻒ ﻣﻴﻨﻤﺎﻳﻨﺪ ‪ .‬ﺍﻳﻦ ﻛﻨﺘﺮﻟﺮ ‪۶‬‬
‫ﺭﻟﻪ ﺧﺮﻭﺟﯽ ﺩﺍﺭﺩ ﻭ ‪ ۲‬ﻋﺪﺩ ﺍﺯ ﺁﻧﻬﺎ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ ﻫﺴﺘﻨﺪ ‪ .‬ﺭﻟﻪ ﻫﺎﻳﻲ ﮐﻪ ﻋﻤﻠﻴﺎﺕ ﺛﺎﺑﺖ ﺩﺍﺭﻧﺪ ﻋﺒﺎﺭﺗﻨﺪ‬
‫ﺍﺯ ‪ ، Start ، Fuel‬ﮐﻨﺘﺎﮐﺘﻮﺭ ﮊﻧﺮﺍﺗﻮﺭ ﻭ ﮐﻨﺘﺎﮐﺘﻮﺭ ﺑﺮﻕ ﺷﻬﺮ ‪.‬‬
‫ﻓﺎﻧﮑﺸﻦ ﻫﺎﯼ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ ﺑﺮﺍﯼ ﺭﻟﻪ ﻫﺎﯼ ﺧﺮﻭﺟﯽ ﺩﺭ ﺷﮑﻞ ﺯﻳﺮ ﻧﺸﺎﻥ ﺩﺍﺩﻩ ﺷﺪﻩ ﺍﺳﺖ ‪.‬‬

‫‪30‬‬
DKG207 ‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫ﻟﻴﺴﺖ ﻓﺎﻧﻜﺸﻦ ﻫﺎ ﻱ ﺭﻟﻪ ﺍﻱ‬


Program Description Std 00 Fuel 24 Oil Sender Alarm
51 ۱ ‫ﻋﻤﻠﮑﺮﺩ ﺭﻟﻪ‬ 03 01 Horn 25 Temp Sender Alarm
52 ۲ ‫ﻋﻤﻠﮑﺮﺩ ﺭﻟﻪ‬ 01 02 Start 26 Speed Alarm
03 Stop 27 Start Fail Alarm
04 Gen.Contactor 28 Change Alarm
05 Mains Contactor 29 OverLoad Alarm
06 Choke 30 Voltage Alarm
07 Preheat 31 Battery High Alarm
08 Alarm 32 Oil Switch Warning
09 Warnning 33 Temp Switch Warn.
10 Alarm+Warnning 34 Level Switch Warn.
11 Automatic Ready 35 Rectifier Warning
12 Week. On Time 36 Emerg Stop Warn.
13 Exerciser 37 Spare-1 Warning
14 - 38 Spare-2 Warning
15 Gas Engine Fuel 39 -
Solnoid Relay
16 Oil Switch Alarm 40 Oil Sender Warning
17 Temp Switch Alarm 41 Temp Sender Warn.
18 Level Switch Alarm 42 Speed Warning
19 Rectifier Alarm 43 Stop Fail Warning
20 Emerg.Stop alarm 44 Change Warning
21 Spare-1 alarm 45 Battery Low
Warning
22 Spare-2 alarm 46 -
23 - 47 Battery High Warn.

‫ ﺍﻣﻜﺎﻧﺎﺕ‬. ‫ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ ﻭﺭﻭﺩﯼ ﻫﺎﯼ ﺩﻳﺠﻴﺘﺎﻝ ﺭﺍ ﺑﺮ ﻋﻬﺪﻩ ﺩﺍﺭﻧﺪ‬P-088 ‫ ﺗﺎ‬P-053 ‫ﭘﺎﺭﺍﻣﺘﺮﻫﺎﯼ ﺷﻤﺎﺭﻩ‬
: ‫ﻭﺭﻭﺩﯼ ﻫﺎﯼ ﺩﻳﺠﻴﺘﺎﻝ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ ﻋﺒﺎﺭﺗﻨﺪ ﺍﺯ‬
Operation -(‫ ﻫﺸﺪﺍﺭ ﻭ ﻏﻴﺮﻩ‬، ‫ ﻋﻤﻠﻴﺎﺕ ﺑﺮ ﺭﻭﯼ ﻭﺭﻭﺩ ﺳﻴﮕﻨﺎﻝ ﺑﻪ ﺳﻴﺴﺘﻢ )ﺁﻻﺭﻡ‬-
Fault Monitoring – ‫ ﺩﺭﻧﻈﺮ ﮔﺮﻓﺘﻦ ﺳﻴﮕﻨﺎﻟﻬﺎﻱ ﺧﻄﺎ‬-
Latching – ‫ ﻗﻔﻞ ﺷﺪﻥ ﺑﺮ ﺭﻭﻱ ﺳﻴﮕﻨﺎﻝ ﺧﻄﺎ‬-
Switching – (Bat- ‫ ﻭ‬Bat+) ‫ ﭘﻼﺭﻳﺘﻪ‬-
(Close ‫ ﻳﺎ ﻧﺮﻣﺎﻟﯽ‬Open ‫ ﻧﻮﻉ ﮐﻨﺘﺎﮐﺖ )ﻧﺮﻣﺎﻟﯽ‬-
Response Delay – ‫ ﺗﺎﺧﻴﺮ ﺩﺭ ﭘﺎﺳﺨﮕﻮﻳﯽ‬-

31
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫ﻭﺭﻭﺩﯼ )‪ (Switch‬ﮐﻢ ﺑﻮﺩﻥ ﻓﺸﺎﺭ ﺭﻭﻏﻦ )‪(Low Oil Pressure Switch‬‬

‫‪Prog‬‬ ‫‪Description‬‬ ‫‪Std‬‬


‫‪ : ۰‬ﺁﻻﺭﻡ )ﻣﻮﺗﻮﺭ ﻣﺘﻮﻗﻒ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﺭﻟﻪ ‪ Horn‬ﻋﻤﻞ ﺧﻮﺍﻫﺪ ﮐﺮﺩ(‬
‫‪53‬‬ ‫ﻋﻤﻠﮑﺮﺩ‬ ‫‪0‬‬
‫‪) Warning : ۲‬ﺭﻟﻪ ‪ Horn‬ﻋﻤﻞ ﺧﻮﺍﻫﺪ ﮐﺮﺩ(‬
‫‪ : ۳‬ﻋﻤﻞ ﻧﺨﻮﺍﻫﺪ ﮐﺮﺩ‬
‫‪ : ۰‬ﻫﻤﻴﺸﻪ‬
‫‪54‬‬ ‫ﻧﻤﺎﻳﺶ ‪Fault‬‬ ‫‪1‬‬
‫‪ : ۱‬ﺑﻌﺪ ﺍﺯ ﺯﻣﺎﻥ ‪Hold Off‬‬
‫‪ : ۲‬ﻫﻨﮕﺎﻣﯽ ﮐﻪ ﺑﺮﻕ ﺷﻬﺮ ﻭﺟﻮﺩ ﺩﺍﺷﺖ‬
‫‪ : ۰‬ﻗﻔﻞ ﻧﺸﻮﺩ‬
‫‪55‬‬ ‫ﻗﻔﻞ ﺷﺪﻥ‬ ‫‪1‬‬
‫‪ : ۱‬ﻗﻔﻞ ﺷﻮﺩ‬

‫‪ : ۰‬ﻧﺮﻣﺎﻟﯽ ‪Open‬‬
‫‪56‬‬ ‫ﻧﻮﻉ ﮐﻨﺘﺎﮐﺖ‬ ‫‪0‬‬
‫‪ : ۱‬ﻧﺮﻣﺎﻟﯽ ‪Close‬‬
‫‪ : ۰‬ﻣﻨﻔﯽ ﺑﺎﻃﺮﯼ‬
‫‪57‬‬ ‫ﺳﻮﺋﻴﭽﻴﻨﮓ‬ ‫‪0‬‬
‫‪ : ۱‬ﻣﺜﺒﺖ ﺑﺎﻃﺮﯼ‬

‫‪ : ۰‬ﺗﺎﺧﻴﺮ ﻧﺪﺍﺭﺩ‬
‫‪58‬‬ ‫ﺗﺎﺧﻴﺮ ﭘﺎﺳﺨﮕﻮﻳﻲ‬ ‫‪0‬‬
‫‪ : ۱‬ﺗﺎﺧﻴﺮ ﺩﺍﺭﺩ )‪ ۴‬ﺛﺎﻧﻴﻪ(‬

‫‪32‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫ﻭﺭﻭﺩﯼ )ﺳﻮﺋﻴﭻ( ﺩﻣﺎﯼ ﺑﺎﻻﻱ ﺁﺏ )‪(High Temprature Switch‬‬


‫‪Prog‬‬ ‫‪Description‬‬ ‫‪Std‬‬
‫‪ : ۰‬ﺁﻻﺭﻡ )ﻣﻮﺗﻮﺭ ﻣﺘﻮﻗﻒ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﺭﻟﻪ ‪ Horn‬ﻋﻤﻞ ﺧﻮﺍﻫﺪ ﮐﺮﺩ(‬
‫‪59‬‬ ‫ﻋﻤﻠﮑﺮﺩ‬ ‫‪0‬‬
‫‪) Warning : ۲‬ﺭﻟﻪ ‪ Horn‬ﻋﻤﻞ ﺧﻮﺍﻫﺪ ﮐﺮﺩ(‬
‫‪ : ۳‬ﻋﻤﻞ ﻧﺨﻮﺍﻫﺪ ﮐﺮﺩ‬
‫‪ : ۰‬ﻫﻤﻴﺸﻪ‬
‫‪60‬‬ ‫ﻧﻤﺎﻳﺶ ‪Fault‬‬ ‫‪0‬‬
‫‪ : ۱‬ﺑﻌﺪ ﺍﺯ ﺯﻣﺎﻥ ‪Hold Off‬‬
‫‪ : ۲‬ﻫﻨﮕﺎﻣﯽ ﮐﻪ ﺑﺮﻕ ﺷﻬﺮ ﻭﺟﻮﺩ ﺩﺍﺷﺖ‬
‫‪ : ۰‬ﻗﻔﻞ ﻧﺸﻮﺩ‬
‫‪61‬‬ ‫ﻗﻔﻞ ﺷﺪﻥ‬ ‫‪1‬‬
‫‪ : ۱‬ﻗﻔﻞ ﺷﻮﺩ‬
‫‪ : ۰‬ﻧﺮﻣﺎﻟﯽ ‪Open‬‬
‫‪62‬‬ ‫ﻧﻮﻉ ﮐﻨﺘﺎﮐﺖ‬ ‫‪0‬‬
‫‪ : ۱‬ﻧﺮﻣﺎﻟﯽ ‪Close‬‬
‫‪ : ۰‬ﻣﻨﻔﯽ ﺑﺎﻃﺮﯼ‬
‫‪63‬‬ ‫ﺳﻮﺋﻴﭽﻴﻨﮓ‬ ‫‪0‬‬
‫‪ : ۱‬ﻣﺜﺒﺖ ﺑﺎﻃﺮﯼ‬
‫‪ : ۰‬ﺗﺎﺧﻴﺮ ﻧﺪﺍﺭﺩ‬
‫‪64‬‬ ‫ﺗﺎﺧﻴﺮ ﭘﺎﺳﺨﮕﻮﻳﻲ‬ ‫‪0‬‬
‫‪ : ۱‬ﺗﺎﺧﻴﺮ ﺩﺍﺭﺩ )‪ ۴‬ﺛﺎﻧﻴﻪ(‬

‫ﻭﺭﻭﺩﯼ ﻳﻜﺴﻮ ﺳﺎﺯ )‪(Fail Rectifier‬‬


‫‪Prog‬‬ ‫‪Description‬‬ ‫‪Std‬‬
‫‪ : ۰‬ﺁﻻﺭﻡ )ﻣﻮﺗﻮﺭ ﻣﺘﻮﻗﻒ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﺭﻟﻪ ‪ Horn‬ﻋﻤﻞ ﺧﻮﺍﻫﺪ ﮐﺮﺩ(‬
‫‪65‬‬ ‫ﻋﻤﻠﮑﺮﺩ‬ ‫‪2‬‬
‫‪) Warning : ۲‬ﺭﻟﻪ ‪ Horn‬ﻋﻤﻞ ﺧﻮﺍﻫﺪ ﮐﺮﺩ(‬
‫‪ : ۳‬ﻋﻤﻞ ﻧﺨﻮﺍﻫﺪ ﮐﺮﺩ‬
‫‪ : ۰‬ﻫﻤﻴﺸﻪ‬
‫‪66‬‬ ‫ﻧﻤﺎﻳﺶ ‪Fault‬‬ ‫‪2‬‬
‫‪ : ۱‬ﺑﻌﺪ ﺍﺯ ﺯﻣﺎﻥ ‪Hold Off‬‬
‫‪ : ۲‬ﻫﻨﮕﺎﻣﯽ ﮐﻪ ﺑﺮﻕ ﺷﻬﺮ ﻭﺟﻮﺩ ﺩﺍﺷﺖ‬
‫‪ : ۰‬ﻗﻔﻞ ﻧﺸﻮﺩ‬
‫‪67‬‬ ‫ﻗﻔﻞ ﺷﺪﻥ‬ ‫‪1‬‬
‫‪ : ۱‬ﻗﻔﻞ ﺷﻮﺩ‬
‫‪ : ۰‬ﻧﺮﻣﺎﻟﯽ ‪Open‬‬
‫‪68‬‬ ‫ﻧﻮﻉ ﮐﻨﺘﺎﮐﺖ‬ ‫‪0‬‬
‫‪ : ۱‬ﻧﺮﻣﺎﻟﯽ ‪Close‬‬
‫‪ : ۰‬ﻣﻨﻔﯽ ﺑﺎﻃﺮﯼ‬
‫‪69‬‬ ‫ﺳﻮﺋﻴﭽﻴﻨﮓ‬ ‫‪0‬‬
‫‪ : ۱‬ﻣﺜﺒﺖ ﺑﺎﻃﺮﯼ‬
‫‪70‬‬ ‫ﺗﺎﺧﻴﺮ ﭘﺎﺳﺨﮕﻮﻳﻲ‬ ‫‪1‬‬ ‫‪ : ۰‬ﺗﺎﺧﻴﺮ ﻧﺪﺍﺭﺩ‬
‫‪ : ۱‬ﺗﺎﺧﻴﺮ ﺩﺍﺭﺩ )‪ ۴‬ﺛﺎﻧﻴﻪ(‬
‫‪33‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫ﻭﺭﻭﺩﯼ ‪Emergency Stop‬‬


‫‪Prog‬‬ ‫‪Description‬‬ ‫‪Std‬‬
‫‪ : ۰‬ﺁﻻﺭﻡ )ﻣﻮﺗﻮﺭ ﻣﺘﻮﻗﻒ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﺭﻟﻪ ‪ Horn‬ﻋﻤﻞ ﺧﻮﺍﻫﺪ ﮐﺮﺩ(‬
‫‪71‬‬ ‫ﻋﻤﻠﮑﺮﺩ‬ ‫‪0‬‬
‫‪) Warning : ۲‬ﺭﻟﻪ ‪ Horn‬ﻋﻤﻞ ﺧﻮﺍﻫﺪ ﮐﺮﺩ(‬
‫‪ : ۳‬ﻋﻤﻞ ﻧﺨﻮﺍﻫﺪ ﮐﺮﺩ‬
‫‪ : ۰‬ﻫﻤﻴﺸﻪ‬
‫‪72‬‬ ‫ﻧﻤﺎﻳﺶ ‪Fault‬‬ ‫‪0‬‬
‫‪ : ۱‬ﺑﻌﺪ ﺍﺯ ﺯﻣﺎﻥ ‪Hold Off‬‬
‫‪ : ۲‬ﻫﻨﮕﺎﻣﯽ ﮐﻪ ﺑﺮﻕ ﺷﻬﺮ ﻭﺟﻮﺩ ﺩﺍﺷﺖ‬
‫‪ : ۰‬ﻗﻔﻞ ﻧﺸﻮﺩ‬
‫‪73‬‬ ‫ﻗﻔﻞ ﺷﺪﻥ‬ ‫‪0‬‬
‫‪ : ۱‬ﻗﻔﻞ ﺷﻮﺩ‬
‫‪ : ۰‬ﻧﺮﻣﺎﻟﯽ ‪Open‬‬
‫‪74‬‬ ‫ﻧﻮﻉ ﮐﻨﺘﺎﮐﺖ‬ ‫‪0‬‬
‫‪ : ۱‬ﻧﺮﻣﺎﻟﯽ ‪Close‬‬
‫‪ : ۰‬ﻣﻨﻔﯽ ﺑﺎﻃﺮﯼ‬
‫‪75‬‬ ‫‪Switching‬‬ ‫‪0‬‬
‫‪ : ۱‬ﻣﺜﺒﺖ ﺑﺎﻃﺮﯼ‬
‫‪ : ۰‬ﺗﺎﺧﻴﺮ ﻧﺪﺍﺭﺩ‬
‫‪76‬‬ ‫ﺗﺎﺧﻴﺮ ﭘﺎﺳﺨﮕﻮﻳﻲ‬ ‫‪0‬‬
‫‪ : ۱‬ﺗﺎﺧﻴﺮ ﺩﺍﺭﺩ )‪ ۴‬ﺛﺎﻧﻴﻪ(‬

‫ﻭﺭﻭﺩﯼ ﺫﺧﻴﺮﻩ ﺧﻄﺎ ) ‪(Spare Fault‬‬


‫‪Prog‬‬ ‫‪Description‬‬ ‫‪Std‬‬
‫‪ : ۰‬ﺁﻻﺭﻡ )ﻣﻮﺗﻮﺭ ﻣﺘﻮﻗﻒ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﺭﻟﻪ ‪ Horn‬ﻋﻤﻞ ﺧﻮﺍﻫﺪ ﮐﺮﺩ(‬
‫‪77‬‬ ‫ﻋﻤﻠﮑﺮﺩ‬ ‫‪0‬‬
‫‪) Warning : ۲‬ﺭﻟﻪ ‪ Horn‬ﻋﻤﻞ ﺧﻮﺍﻫﺪ ﮐﺮﺩ(‬
‫‪ : ۳‬ﻋﻤﻞ ﻧﺨﻮﺍﻫﺪ ﮐﺮﺩ‬
‫‪ : ۰‬ﻫﻤﻴﺸﻪ‬
‫‪78‬‬ ‫ﻧﻤﺎﻳﺶ ‪Fault‬‬ ‫‪0‬‬
‫‪ : ۱‬ﺑﻌﺪ ﺍﺯ ﺯﻣﺎﻥ ‪Hold Off‬‬
‫‪ : ۲‬ﻫﻨﮕﺎﻣﯽ ﮐﻪ ﺑﺮﻕ ﺷﻬﺮ ﻭﺟﻮﺩ ﺩﺍﺷﺖ‬
‫‪ : ۰‬ﻗﻔﻞ ﻧﺸﻮﺩ‬
‫‪79‬‬ ‫ﻗﻔﻞ ﺷﺪﻥ‬ ‫‪0‬‬
‫‪ : ۱‬ﻗﻔﻞ ﺷﻮﺩ‬
‫‪ : ۰‬ﻧﺮﻣﺎﻟﯽ ‪Open‬‬
‫‪80‬‬ ‫ﻧﻮﻉ ﮐﻨﺘﺎﮐﺖ‬ ‫‪0‬‬
‫‪ : ۱‬ﻧﺮﻣﺎﻟﯽ ‪Close‬‬
‫‪ : ۰‬ﻣﻨﻔﯽ ﺑﺎﻃﺮﯼ‬
‫‪81‬‬ ‫‪Switching‬‬ ‫‪0‬‬
‫‪ : ۱‬ﻣﺜﺒﺖ ﺑﺎﻃﺮﯼ‬
‫‪82‬‬ ‫ﺗﺎﺧﻴﺮ ﭘﺎﺳﺨﮕﻮﻳﻲ‬ ‫‪0‬‬ ‫‪ : ۰‬ﺗﺎﺧﻴﺮ ﻧﺪﺍﺭﺩ‬
‫‪ : ۱‬ﺗﺎﺧﻴﺮ ﺩﺍﺭﺩ )‪ ۴‬ﺛﺎﻧﻴﻪ(‬
‫‪34‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫ﻭﺭﻭﺩﯼ ﻗﻔﻞ ﺑﺮﻧﺎﻣﻪ‬


‫‪Prog‬‬ ‫‪Description‬‬ ‫‪Std‬‬

‫‪ : ۰‬ﺁﻻﺭﻡ )ﻣﻮﺗﻮﺭ ﻣﺘﻮﻗﻒ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﺭﻟﻪ ‪ Horn‬ﻋﻤﻞ ﺧﻮﺍﻫﺪ ﮐﺮﺩ(‬


‫‪83‬‬ ‫ﻋﻤﻠﮑﺮﺩ‬ ‫‪3‬‬
‫‪) Warning : ۲‬ﺭﻟﻪ ‪ Horn‬ﻋﻤﻞ ﺧﻮﺍﻫﺪ ﮐﺮﺩ(‬
‫‪ : ۳‬ﻋﻤﻞ ﻧﺨﻮﺍﻫﺪ ﮐﺮﺩ‬
‫‪ : ۰‬ﻫﻤﻴﺸﻪ‬
‫‪84‬‬ ‫ﻧﻤﺎﻳﺶ ‪Fault‬‬ ‫‪0‬‬
‫‪ : ۱‬ﺑﻌﺪ ﺍﺯ ﺯﻣﺎﻥ ‪Hold Off‬‬
‫‪ : ۲‬ﻫﻨﮕﺎﻣﯽ ﮐﻪ ﺑﺮﻕ ﺷﻬﺮ ﻭﺟﻮﺩ ﺩﺍﺷﺖ‬
‫‪ : ۰‬ﻗﻔﻞ ﻧﺸﻮﺩ‬
‫‪85‬‬ ‫ﻗﻔﻞ ﺷﺪﻥ‬ ‫‪0‬‬
‫‪ : ۱‬ﻗﻔﻞ ﺷﻮﺩ‬
‫‪ : ۰‬ﻧﺮﻣﺎﻟﯽ ‪Open‬‬
‫‪86‬‬ ‫ﻧﻮﻉ ﮐﻨﺘﺎﮐﺖ‬ ‫‪0‬‬
‫‪ : ۱‬ﻧﺮﻣﺎﻟﯽ ‪Close‬‬
‫‪ : ۰‬ﻣﻨﻔﯽ ﺑﺎﻃﺮﯼ‬
‫‪87‬‬ ‫‪Switching‬‬ ‫‪0‬‬
‫‪ : ۱‬ﻣﺜﺒﺖ ﺑﺎﻃﺮﯼ‬
‫‪ : ۰‬ﺗﺎﺧﻴﺮ ﻧﺪﺍﺭﺩ‬
‫‪88‬‬ ‫ﺗﺎﺧﻴﺮ ﭘﺎﺳﺨﮕﻮﻳﻲ‬ ‫‪0‬‬
‫‪ : ۱‬ﺗﺎﺧﻴﺮ ﺩﺍﺭﺩ )‪ ۴‬ﺛﺎﻧﻴﻪ(‬

‫ﺍﻳﻦ‬ ‫ﭘﺎﺭﺍﻣﺘﺮ ‪ P-089‬ﺗﺎ ‪ P-100‬ﻣﺸﺨﺼﺎﺕ ﺍﻫﻢ‪ -‬ﺑﺎﺭ ﺳﻨﺴﻮﺭ ﻓﺸﺎﺭ ﺭﻭﻏﻦ ﺭﺍ ﺗﻌﻴﻴﻦ ﻣﯽ ﮐﻨﺪ ‪.‬‬
‫ﻣﺸﺨﺼﺎﺕ ﺣﺪﺍﮐﺜﺮ ﺩﺭ ‪ ۶‬ﻧﻘﻄﻪ ﺗﻌﻴﻴﻦ ﻣﯽ ﮔﺮﺩﺩ ‪ .‬ﺍﻳﻦ ﻣﺸﺨﺼﺎﺕ ﻣﯽ ﺑﺎﻳﺴﺖ ﺑﻪ ﺻﻮﺭﺕ ﺍﻓﺰﺍﻳﺶ ﺍﻫﻢ ﺍﺯ‬
‫ﭘﺎﻳﻴﻦ ﺑﻪ ﺑﺎﻻ ﻭﺍﺭﺩ ﺷﻮﻧﺪ ‪ .‬ﺑﺮﺍﯼ ﻧﻘﺎﻃﯽ ﮐﻪ ﺍﺳﺘﻔﺎﺩﻩ ﻧﻤﯽ ﺷﻮﻧﺪ ﺑﺎﻳﺪ ﻣﻘﺪﺍﺭ ﺻﻔﺮ ﻗﺮﺍﺭ ﺩﺍﺩﻩ ﺷﻮﺩ ‪ .‬ﻣﺸﺨﺼﺎﺕ‬
‫ﺯﻳﺮ ﻣﺸﺨﺼﺎﺕ ﻳﮏ ﺳﻨﺴﻮﺭ ﺍﺳﺖ ﮐﻪ ﺑﻪ ﺻﻮﺭﺕ ﻧﻤﻮﻧﻪ ﻭ ﻣﺜﺎﻝ ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮﻫﺎ ﻗﺮﺍﺭ ﺩﺍﺩﻩ ﻣﯽ ﺷﻮﺩ ‪.‬‬
‫‪0.0 bar…..240 ohms‬‬
‫‪1.0 bar ….. 218 ohms‬‬
‫‪5.0 bar ….. 183 ohms‬‬
‫‪10.0 bar ….. 103 ohms‬‬

‫‪35‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪Prog‬‬ ‫‪Description‬‬ ‫‪Unit‬‬ ‫‪Value‬‬

‫‪89‬‬ ‫ﻣﻘﺎﻭﻣﺖ ﻧﻘﻄﻪ ‪۱‬‬ ‫‪ohms‬‬ ‫‪103‬‬


‫‪90‬‬ ‫ﻓﺸﺎﺭ ﻧﻘﻄﻪ ‪۱‬‬ ‫‪bar‬‬ ‫‪10.0‬‬
‫‪91‬‬ ‫ﻣﻘﺎﻭﻣﺖ ﻧﻘﻄﻪ ‪۲‬‬ ‫‪ohms‬‬ ‫‪153‬‬
‫‪92‬‬ ‫ﻓﺸﺎﺭ ﻧﻘﻄﻪ ‪۲‬‬ ‫‪bar‬‬ ‫‪5.0‬‬
‫‪93‬‬ ‫ﻣﻘﺎﻭﻣﺖ ﻧﻘﻄﻪ ‪۳‬‬ ‫‪ohms‬‬ ‫‪218‬‬
‫‪94‬‬ ‫ﻓﺸﺎﺭ ﻧﻘﻄﻪ ‪۳‬‬ ‫‪bar‬‬ ‫‪1.0‬‬
‫‪95‬‬ ‫ﻣﻘﺎﻭﻣﺖ ﻧﻘﻄﻪ ‪۴‬‬ ‫‪ohms‬‬ ‫‪240‬‬
‫‪96‬‬ ‫ﻓﺸﺎﺭ ﻧﻘﻄﻪ ‪۴‬‬ ‫‪bar‬‬ ‫‪0.0‬‬
‫‪97‬‬ ‫ﻣﻘﺎﻭﻣﺖ ﻧﻘﻄﻪ ‪۵‬‬ ‫‪ohms‬‬ ‫‪0‬‬
‫‪98‬‬ ‫ﻓﺸﺎﺭ ﻧﻘﻄﻪ ‪۵‬‬ ‫‪bar‬‬ ‫‪0.0‬‬
‫‪99‬‬ ‫ﻣﻘﺎﻭﻣﺖ ﻧﻘﻄﻪ ‪۶‬‬ ‫‪ohms‬‬ ‫‪0‬‬
‫‪100‬‬ ‫ﻓﺸﺎﺭ ﻧﻘﻄﻪ ‪۶‬‬ ‫‪bar‬‬ ‫‪0.0‬‬

‫ﭘﺎﺭﺍﻣﺘﺮ ‪ P-101‬ﺗﺎ ‪ P-116‬ﻣﺸﺨﺼﺎﺕ ﺍﻫﻢ‪ -‬ﺩﺭﺟﻪ ﺳﻨﺴﻮﺭ ﺩﻣﺎ ﺭﺍ ﺗﻌﻴﻴﻦ ﻣﯽ ﮐﻨﺪ ‪ .‬ﺍﻳﻦ ﻣﺸﺨﺼﺎﺕ‬
‫ﺣﺪﺍﮐﺜﺮ ﺩﺭ ‪ ۶‬ﻧﻘﻄﻪ ﺗﻌﻴﻴﻦ ﻣﯽ ﮔﺮﺩﺩ ‪ .‬ﺍﻳﻦ ﻣﺸﺨﺼﺎﺕ ﻣﯽ ﺑﺎﻳﺴﺖ ﺑﻪ ﺻﻮﺭﺕ ﺍﻓﺰﺍﻳﺶ ﺍﻫﻢ ﺍﺯ ﭘﺎﻳﻴﻦ ﺑﻪ ﺑﺎﻻ‬
‫ﻭﺍﺭﺩ ﺷﻮﻧﺪ ‪ .‬ﺑﺮﺍﯼ ﻧﻘﺎﻃﯽ ﮐﻪ ﺍﺳﺘﻔﺎﺩﻩ ﻧﻤﯽ ﺷﻮﻧﺪ ﺑﺎﻳﺪ ﻣﻘﺪﺍﺭ ﺻﻔﺮ ﻗﺮﺍﺭ ﺩﺍﺩﻩ ﺷﻮﺩ ‪ .‬ﻣﺸﺨﺼﺎﺕ ﺯﻳﺮ‬
‫ﻣﺸﺨﺼﺎﺕ ﻳﮏ ﺳﻨﺴﻮﺭ ﺍﺳﺖ ﮐﻪ ﺑﻪ ﺻﻮﺭﺕ ﻧﻤﻮﻧﻪ ﻭ ﻣﺜﺎﻝ ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮﻫﺎ ﻗﺮﺍﺭ ﺩﺍﺩﻩ ﻣﯽ ﺷﻮﺩ ‪.‬‬

‫‪38 C ….. 342 ohm‬‬


‫‪82 C ….. 71 ohm‬‬
‫‪104 C ….. 40 ohm‬‬
‫‪121 C ….. 30 ohm‬‬

‫‪36‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪Prog‬‬ ‫‪Description‬‬ ‫‪Unit‬‬ ‫‪Value‬‬

‫‪101‬‬ ‫ﻣﻘﺎﻭﻣﺖ ﻧﻘﻄﻪ ‪۱‬‬ ‫‪ohms‬‬ ‫‪30‬‬


‫‪102‬‬ ‫ﺩﻣﺎﯼ ﻧﻘﻄﻪ ‪۱‬‬ ‫‪C‬‬ ‫‪121‬‬
‫‪103‬‬ ‫ﻣﻘﺎﻭﻣﺖ ﻧﻘﻄﻪ ‪۲‬‬ ‫‪ohms‬‬ ‫‪40‬‬
‫‪104‬‬ ‫ﺩﻣﺎﯼ ﻧﻘﻄﻪ ‪۲‬‬ ‫‪C‬‬ ‫‪104‬‬
‫‪105‬‬ ‫ﻣﻘﺎﻭﻣﺖ ﻧﻘﻄﻪ ‪۳‬‬ ‫‪ohms‬‬ ‫‪71‬‬
‫‪106‬‬ ‫ﺩﻣﺎﯼ ﻧﻘﻄﻪ ‪۳‬‬ ‫‪C‬‬ ‫‪82‬‬
‫‪107‬‬ ‫ﻣﻘﺎﻭﻣﺖ ﻧﻘﻄﻪ ‪۴‬‬ ‫‪ohms‬‬ ‫‪342‬‬
‫‪108‬‬ ‫ﺩﻣﺎﯼ ﻧﻘﻄﻪ ‪۴‬‬ ‫‪C‬‬ ‫‪38‬‬
‫‪109‬‬ ‫ﻣﻘﺎﻭﻣﺖ ﻧﻘﻄﻪ ‪۵‬‬ ‫‪ohms‬‬ ‫‪0‬‬
‫‪110‬‬ ‫ﺩﻣﺎﯼ ﻧﻘﻄﻪ ‪۵‬‬ ‫‪C‬‬ ‫‪0‬‬
‫‪111‬‬ ‫ﻣﻘﺎﻭﻣﺖ ﻧﻘﻄﻪ ‪۶‬‬ ‫‪ohms‬‬ ‫‪0‬‬
‫‪112‬‬ ‫ﺩﻣﺎﯼ ﻧﻘﻄﻪ ‪۶‬‬ ‫‪C‬‬ ‫‪0‬‬

‫ﭘﺎﺭﺍﻣﺘﺮ ‪ P-113‬ﺗﺎ ‪ ، P-116‬ﻣﺮﺑﻮﻁ ﺑﻪ ﺭﺍﻩ ﺍﻧﺪﺍﺯﻱ ﺩﻭﺭﻩ ﺍﻱ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ ﻣﻲ ﺑﺎﺷﺪ‪.‬‬


‫‪Prog‬‬ ‫‪Difinition‬‬ ‫‪Unit‬‬ ‫‪Std.val‬‬ ‫‪Description‬‬
‫ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺭﻭﺯ ﻭ ﺳﺎﻋﺖ ﺍﺳﺘﺎﺭﺕ ﮊﻧﺮﺍﺗﻮﺭ ﺭﺍ ﺗﻌﻴﻴﻦ‬
‫ﻣﯽ ﮐﻨﺪ ‪ .‬ﻣﻘﺎﺩﻳﺮ ﻣﺴﺎﻭﯼ ﻳﺎ ﺑﻴﺸﺘﺮ ﺍﺯ ‪ ۱۶۸‬ﺑﻪ ﻣﻌﻨﯽ ﻋﺪﻡ‬
‫ﺍﺳﺘﻔﺎﺩﻩ ﺍﺯ ﺍﻳﻦ ﻋﻤﻠﻜﺮﺩ ﺧﻮﺍﻫﺪ ﺑﻮﺩ ‪.‬‬
‫ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺑﺮ ﺍﺳﺎﺱ ﺳﺎﻋﺖ ﺷﻤﺮﺩﻩ ﺷﺪﻩ ﺍﺯ ﺍﻭﻟﻴﻦ ﺭﻭﺯ‬
‫ﻫﻔﺘﻪ )ﺩﻭﺷﻨﺒﻪ( ﻣﺤﺎﺳﺒﻪ ﻣﯽ ﺷﻮﺩ ‪ .‬ﻣﺜﺎﻝ ‪:‬‬
‫‪ = ۰‬ﺍﺳﺘﺎﺭﺕ ﺩﺭ ﺳﺎﻋﺖ ‪ ۰۰ :۰۰‬ﺩﻭ ﺷﻨﺒﻪ‬
‫‪113‬‬ ‫ﺳﺎﻋﺖ ﻭ ﺭﻭﺯ ﺍﺳﺘﺎﺭﺕ‬ ‫‪-‬‬ ‫‪168‬‬ ‫‪ = ۱‬ﺍﺳﺘﺎﺭﺕ ﺩﺭ ﺳﺎﻋﺖ ‪ ۰۱ :۰۰‬ﺩﻭﺷﻨﺒﻪ‬
‫‪ = ۸‬ﺍﺳﺘﺎﺭﺕ ﺩﺭ ﺳﺎﻋﺖ ‪ ۰۸ :۰۰‬ﺩﻭﺷﻨﺒﻪ‬
‫‪ =۲۴‬ﺍﺳﺘﺎﺭﺕ ﺩﺭﺳﺎﻋﺖ ‪ ۰۰ :۰۰‬ﺳﻪ ﺷﻨﺒﻪ‬
‫‪ =۱۶۷‬ﺍﺳﺘﺎﺭﺕ ﺩﺭ ﺳﺎﻋﺖ ‪ ۲۳ :۰۰‬ﻳﮑﺸﻨﺒﻪ‬
‫‪ =۱۶۸‬ﻏﻴﺮ ﻓﻌﺎﻝ‬
‫ﺍﮔﺮ ﭘﺎﺭﺍﻣﺘﺮ )‪ (P-158=0‬ﺍﻧﺘﺨﺎﺏ ﺷﺪﻩ ﺑﺎﺷﺪ‪ ،‬ﺍﺳﺘﺎﺭﺕ‬
‫ﺩﻭﺭﻩ ﺍﻱ ﺑﻪ ﺻﻮﺭﺕ ﺭﻭﺯﺍﻧﻪ ﺑﺪﻭﻥ ﺩﺭ ﻧﻈﺮ ﮔﺮﻓﺘﻦ‬
‫ﺭﻭﺯﻫﺎﻱ ﻫﻔﺘﻪ ﺍﻧﺠﺎﻡ ﻣﻲ ﮔﻴﺮﺩ ‪.‬ﺍﮔﺮ ﭘﺎﺭﺍﻣﺘﺮ‬
‫)‪ (P-158=2‬ﺍﻧﺘﺨﺎﺏ ﺷﺪﻩ ﺑﺎﺷﺪ ‪ ،‬ﺍﺳﺘﺎﺭﺕ ﺩﻭﺭﻩ ﺍﻱ‬
‫ﺑﻪ ﺻﻮﺭﺕ ﻫﻔﺘﻪ ﺍﻭﻝ ﻫﺮ ﻣﺎﻩ ﺍﺟﺮﺍ ﺧﻮﺍﻫﺪ ﺷﺪ‪.‬‬
‫‪37‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﻣﺪﺕ ﺯﻣﺎﻥ ﺍﺳﺘﺎﺭﺕ ﺩﻭﺭﻩ ﺍﻱ ﺭﺍ ﻣﺸﺨﺺ‬


‫‪114‬‬ ‫ﻣﺪﺕ ﺯﻣﺎﻥ ﺍﺳﺘﺎﺭﺕ ﺩﻭﺭﻩ ﺍﻱ‬ ‫‪Min‬‬ ‫‪10‬‬
‫ﻣﯽ ﮐﻨﺪ ﻭ ﺩﺭ ﮔﺎﻡ ﻫﺎﯼ ‪ ۱۰‬ﺩﻗﻴﻘﻪ ﺍﯼ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ‬
‫ﺍﺳﺖ‬
‫‪ : 0‬ﺍﺳﺘﺎﺭﺕ ﺩﻭﺭﻩ ﺍﻱ ﻫﺮ ﺭﻭﺯ ﺍﻧﺠﺎﻡ ﻣﯽ ﺷﻮﺩ ‪.‬‬
‫)ﺍﺳﺘﺎﺭﺕ ﺩﻭﺭﻩ ﺍﻱ ﻫﺮ ﺭﻭﺯ ﺻﺮﻓﻨﻈﺮ ﺍﺯ ﺍﻳﻨﮑﻪ ﭼﻪ ﺭﻭﺯﯼ‬
‫ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ‪ P-155‬ﺍﻧﺘﺨﺎﺏ ﺷﺪﻩ ﺍﺳﺖ (‬
‫‪116‬‬ ‫ﺍﺳﺘﺎﺭﺕ ﺩﻭﺭﻩ ﺍﻱ ﺭﻭﺯﺍﻧﻪ ‪ ،‬ﻫﻔﺘﮕﯽ ‪،‬‬ ‫‪-‬‬ ‫‪1‬‬ ‫‪ : ۱‬ﺍﺳﺘﺎﺭﺕ ﺩﻭﺭﻩ ﺍﻱ ﻫﻔﺘﻪ ﺍﯼ ﻳﮑﺒﺎﺭ ﺍﻧﺠﺎﻡ ﻣﯽ ﮔﺮﺩﺩ‬
‫ﻣﺎﻫﺎﻧﻪ‬ ‫‪ : ۲‬ﺍﺳﺘﺎﺭﺕ ﺩﻭﺭﻩ ﺍﻱ ﻣﺎﻫﯽ ﻳﮏ ﺑﺎﺭ ﺍﻧﺠﺎﻡ ﻣﯽ ﮔﺮﺩﺩ‬
‫)ﺍﺳﺘﺎﺭﺕ ﺩﻭﺭﻩ ﺍﻱ ﮊﻧﺮﺍﺗﻮﺭ ﺩﺭ ﺍﻭﻟﻴﻦ ﻫﻔﺖ ﺭﻭﺯ ﻣﺎﻩ ﻭ ﺑﺎ‬
‫ﻣﻘﺎﺩﻳﺮ ﭘﺎﺭﺍﻣﺘﺮ ‪ P-155‬ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ ﻣﻴﮕﺮﺩﺩ (‬

‫ﭘﺎﺭﺍﻣﺘﺮﻫﺎﯼ ‪ P-117‬ﺗﺎ ‪ P-122‬ﺯﻣﺎﻥ ﻭ ﺗﺎﺭﻳﺦ ﺭﺍ ﺗﻨﻈﻴﻢ ﻣﯽ ﻧﻤﺎﻳﻨﺪ ‪.‬‬

‫‪117‬‬ ‫ﺳﺎﻝ‬ ‫‪-‬‬ ‫‪0-99‬‬ ‫ﺩﻭ ﺭﻗﻢ ﺁﺧﺮ ﺳﺎﻝ ﺟﺎﺭﯼ‬


‫‪118‬‬ ‫ﻣﺎﻩ‬ ‫‪-‬‬ ‫‪01-12‬‬ ‫ﻣﺎﻩ ﺟﺎﺭﯼ‬
‫‪119‬‬ ‫ﺭﻭﺯ‬ ‫‪-‬‬ ‫‪01-31‬‬ ‫ﺭﻭﺯ ﺟﺎﺭﯼ ﺍﺯ ﻣﺎﻩ‬
‫‪120‬‬ ‫ﺍﻳﺎﻡ ﻫﻔﺘﻪ‬ ‫‪-‬‬ ‫‪0-6‬‬ ‫ﺭﻭﺯ ﺟﺎﺭﯼ ﺍﺯﻫﻔﺘﻪ‬
‫‪121‬‬ ‫ﺳﺎﻋﺖ‬ ‫‪-‬‬ ‫‪00-23‬‬ ‫ﺳﺎﻋﺖ‬
‫‪122‬‬ ‫ﺩﻗﻴﻘﻪ‬ ‫‪-‬‬ ‫‪00-59‬‬ ‫ﺩﻗﻴﻘﻪ‬

‫‪ -۱۲‬ﺭﻓﻊ ﻋﻴﺐ‬

‫ﮐﻨﺘﺮﻟﺮ ﻣﺎﺩﺍﻣﻴﻜﻪ ﺑﺮﻕ ﺷﻬﺮ ﻭﺻﻞ ﺍﺳﺖ ﻳﺎ ﺑﻌﺪ ﺍﺯ ﺁﻣﺪﻥ ﺑﺮﻕ ﺷﻬﺮ ﻫﻤﭽﻨﺎﻥ ﺑﺎﺭ ﺭﺍ ﺑﺮ ﺭﻭﻱ ﮊﻧﺮﺍﺗﻮﺭ‬ ‫‪‬‬
‫ﻧﮕﻪ ﺩﺍﺷﺘﻪ ﺍﺳﺖ ‪:‬‬
‫‪ -‬ﺍﺗﺼﺎﻝ ﺑﺪﻧﻪ ﻣﻮﺗﻮﺭ ﺭﺍ ﭼﮏ ﮐﻨﻴﺪ ‪.‬‬
‫‪ -‬ﻭﻟﺘﺎﮊ ﻓﺎﺯﻫﺎﯼ ﺑﺮﻕ ﺷﻬﺮ ﻣﻤﮑﻦ ﺍﺳﺖ ﺧﺎﺭﺝ ﺍﺯ ﺣﺪﻭﺩ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺑﺎﺷﺪ ﻭﻟﺘﺎﮊ ﻓﺎﺯﻫﺎ ﺭﺍ ﺍﻧﺪﺍﺯﻩ‬
‫ﮔﻴﺮﯼ ﻧﻤﺎﻳﻴﺪ ‪.‬‬
‫‪ -‬ﻭﻟﺘﺎﮊ ‪ AC‬ﺧﻮﺍﻧﺪﻩ ﺷﺪﻩ ﺭﺍ ﺑﻪ ﻭﺳﻴﻠﻪ ﻓﺸﺎﺭ ﺩﺍﺩﻥ ﺩﮐﻤﻪ ‪ Menu‬ﭼﮏ ﮐﻨﻴﺪ ‪.‬‬
‫‪ -‬ﻣﺤﺪﻭﺩﻩ ﻭﻟﺘﺎﮊ ﺑﺮﻕ ﺷﻬﺮ ﻣﻤﮑﻦ ﺍﺳﺖ ﺧﻴﻠﻲ ﻧﺰﺩﻳﻚ ﺑﻪ ﻫﻢ ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺑﺎﺷﺪ ‪ .‬ﭘﺎﺭﺍﻣﺘﺮﻫﺎﯼ ‪P-‬‬
‫‪ 004‬ﻭ ‪ P-005‬ﺭﺍ ﭼﮏ ﮐﻨﻴﺪ ‪.‬‬
‫‪38‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪ -‬ﻣﻴﺰﺍﻥ ﻭﻟﺘﺎﮊ ﻫﻴﺴﺘﺮﻳﺰﻳﺲ ﻣﻤﮑﻦ ﺍﺳﺖ ﺯﻳﺎﺩ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺑﺎﺷﺪ ‪ .‬ﭘﺎﺭﺍﻣﺘﺮ ‪ P-021‬ﺭﺍ ﭼﮏ ﮐﻨﻴﺪ ﻭ‬
‫ﺗﻮﺟﻪ ﮐﻨﻴﺪ ﮐﻪ ﻣﻘﺪﺍﺭ ﭘﻴﺸﻨﻬﺎﺩﯼ ‪ ۸‬ﻭﻟﺖ ﺍﺳﺖ ‪.‬‬

‫ﻣﻘﺪﺍﺭ ﻭﻟﺘﺎﮊ ‪ AC‬ﻳﺎ ﻓﺮﮐﺎﻧﺲ ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﺷﺪﻩ ﺩﺭﺳﺖ ﻧﻴﺴﺖ ‪:‬‬ ‫‪‬‬
‫‪ -‬ﺍﺗﺼﺎﻝ ﺑﺪﻧﻪ ﻣﻮﺗﻮﺭ ﺑﻪ ﺯﻣﻴﻦ ﺭﺍ ﭼﮏ ﮐﻨﻴﺪ ‪) .‬ﺍﻳﻦ ﺁﻳﺘﻢ ﺿﺮﻭﺭﯼ ﺍﺳﺖ(‬
‫‪ -‬ﻣﻴﺰﺍﻥ ﺧﻄﺎ ﺩﺭ ﺧﻮﺍﻧﺪﻥ ﻣﻘﺎﺩﻳﺮ ﺑﺮﺍﯼ ﮐﻨﺘﺮﻟﺮ ﺑﺮﺍﺑﺮ ‪ -/+ ۳‬ﺍﺳﺖ ‪.‬‬
‫‪ -‬ﺍﮔﺮ ﻭﻗﺘﯽ ﮊﻧﺮﺍﺗﻮﺭ ﺭﻭﺷﻦ ﺍﺳﺖ ‪ ،‬ﺧﻄﺎ ﺩﺭ ﺧﻮﺍﻧﺪﻥ ﻣﻘﺎﺩﻳﺮ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﯼ ﺷﺪﻩ ﻣﺸﺎﻫﺪﻩ ﺷﻮﺩ ‪ ،‬ﺍﻳﻦ‬
‫ﺧﻄﺎ ﻣﻤﮑﻦ ﺍﺳﺖ ﻣﺮﺑﻮﻁ ﺑﻪ ﺷﺎﺭﮊﺭ)ﺩﻳﻨﺎﻡ( ﻳﺎ ﺭﮔﻮﻻﺗﻮﺭ ﻭﻟﺘﺎﮊ ﺑﺎﺷﺪ ‪ .‬ﺍﺗﺼﺎﻝ ﺷﺎﺭﮊﺭ ﺭﺍ ﺍﺯ ﻣﻮﺗﻮﺭ‬
‫ﺟﺪﺍ ﮐﻨﻴﺪ ﻭ ﭼﮏ ﮐﻨﻴﺪ ﮐﻪ ﺁﻳﺎ ﺧﻄﺎ ﺑﺮﻃﺮﻑ ﺷﺪﻩ ﻳﺎ ﺧﻴﺮ ‪.‬‬
‫‪ -‬ﺍﮔﺮ ﻫﻨﮕﺎﻣﯽ ﮐﻪ ﺑﺮﻕ ﺷﻬﺮ ﻭﺟﻮﺩ ﺩ ﺍﺭﺩ ﺧﻄﺎ ﺩﺭ ﻣﻘﺎﺩﻳﺮ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﯼ ﺷﺪﻩ ﻭﺟﻮﺩ ﺩﺍﺷﺖ ‪ ،‬ﺷﺎﺭﮊﺭ‬
‫)ﺩﻳﻨﺎﻡ( ﻣﻤﮑﻦ ﺍﺳﺖ ﺩﭼﺎﺭ ﻣﺸﮑﻞ ﺷﺪﻩ ﺑﺎﺷﺪ ‪.‬‬

‫ﻣﻘﺎﺩﻳﺮ ﻭﻟﺘﺎﮊﻫﺎﻱ ﻓﺎﺯ ﺑﻪ ﻓﺎﺯ ﺻﺤﻴﺢ ﻧﺒﻮﺩﻩ ﺑﺎ ﻭﺟﻮﺩ ﺍﻳﻨﻜﻪ ﻣﻘﺎﺩﻳﺮ ﻭﻟﺘﺎﮊ ﻓﺎﺯ ﺑﻪ ﻧﻮﻝ ﺻﺤﻴﺢ ﺍﺳﺖ ‪.‬‬ ‫‪‬‬
‫‪ -‬ﺗﺮﺗﻴﺐ ﻓﺎﺯﻫﺎ ﺻﺤﻴﺢ ﻧﻤﻲ ﺑﺎﺷﺪ ‪ ،‬ﻟﻄﻔﺎ" ﺗﺮﺗﻴﺐ ﻓﺎﺯﻫﺎ ﺭﺍ ﺗﺼﺤﻴﺢ ﻧﻤﺎﻳﻴﺪ‪.‬‬

‫ﻣﻘﺪﺍﺭ ﻗﺮﺍﺋﺖ ‪ Cosφ‬ﻭ ‪ KW‬ﻣﻨﻔﻲ ﻫﺴﺘﻨﺪ ﺑﺎ ﻭﺟﻮﺩ ﺍﻳﻨﻜﻪ ﻣﻘﺪﺍﺭ ﻗﺮﺍﺋﺖ ﺟﺮﻳﺎﻥ ﺻﺤﻴﺢ ﻣﻲ ﺑﺎﺷﺪ‪.‬‬ ‫‪‬‬
‫‪ -‬ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮ ﺩﺭ ﺟﻬﺖ ﻣﻌﻜﻮﺱ ﻣﺘﺼﻞ ﺷﺪﻩ ﺍﺳﺖ ﺟﻬﺖ ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮ ﺭﺍ ﺗﺼﺤﻴﺢ ﻧﻤﺎﻳﻴﺪ‪.‬‬
‫‪ ‬ﺧﺮﻭﺟﯽ ﻫﺎﯼ ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮﻫﺎﯼ ﺟﺮﻳﺎﻥ ﺭﺍ ﺩﺭ ﺻﻮﺭﺗﯽ ﮐﻪ ﺍﺯ ﺁﻧﻬﺎ ﺍﺳﺘﻔﺎﺩﻩ ﻧﻤﯽ ﮐﻨﻴﺪ ‪ ،‬ﺍﺗﺼﺎﻝ ﮐﻮﺗﺎﻩ‬
‫ﻧﻤﺎﻳﻴﺪ ‪.‬‬

‫ﺑﺮﻕ ﺷﻬﺮ ﻗﻄﻊ ﺷﺪﻩ ﻭ ﺧﺮﻭﺟﯽ ﺷﻴﺮﺳﻮﺧﺖ ﻓﻌﺎﻝ ﺷﺪﻩ ‪ ،‬ﻭﻟﻲ ﻣﻮﺗﻮﺭ ﺍﺳﺘﺎﺭﺕ ﻧﻤﻲ ﮔﺮﺩﺩ ﻭ‬ ‫‪‬‬
‫‪ LED‬ﻣﺮﺑﻮﻁ ﺑﻪ ‪ Oil Pressuer‬ﺷﺮﻭﻉ ﺑﻪ ﭼﺸﻤﮏ ﺯﺩﻥ ﻛﺮﺩﻩ ﺍﺳﺖ ‪:‬‬
‫‪ -‬ﻭﺭﻭﺩﯼ ‪ Oil Pressure‬ﻛﻨﺘﺮﻟﺮ ﺑﺎ ﻭﻟﺘﺎﮊ ﻣﻨﻔﯽ ﺑﺎﻃﺮﯼ ﺗﻐﺬﻳﻪ ﻧﮕﺮﺩﻳﺪﻩ‪.‬‬
‫‪ Oil Pressure Switch -‬ﻭﺻﻞ ﻧﻴﺴﺖ ‪.‬‬
‫‪ -‬ﺳﻴﻢ ‪ Oil Pressure Switch‬ﻗﻄﻊ ﺷﺪﻩ ﺍﺳﺖ ‪.‬‬
‫‪ Oil Pressure Switch -‬ﺩﺍﺭﺍﯼ ﺧﻄﺎ ﻣﯽ ﺑﺎﺷﺪ ‪.‬‬

‫‪39‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪ -‬ﻛﻨﺘﺎﻛﺖ ‪ Oil Pressure Switch‬ﺑﺎ ﺗﺎﺧﻴﺮ ﺑﺴﺘﻪ ﻣﻲ ﺷﻮﺩ ‪ .‬ﺩﺭ ﺻﻮﺭﺕ ﺑﺴﺘﻪ ﺑﻮﺩﻥ ﺍﻳﻦ‬
‫ﻛﻨﺘﺎﻛﺖ ﻛﻨﺘﺮﻟﺮ ﺍﺳﺘﺎﺭﺕ ﻣﯽ ﺷﻮﺩ ‪ Oil Pressure Switch .‬ﺑﺎﻳﺪ ﺗﻌﻮﻳﺾ ﮔﺮﺩﺩ ‪.‬‬

‫ﻣﻮﺗﻮﺭ ﺑﻌﺪ ﺍﺯ ﻭﻗﻮﻉ ﺍﻭﻟﻴﻦ ﺍﺳﺘﺎﺭﺕ ﺭﻭﺷﻦ ﻧﻤﻲ ﺷﻮﺩ ‪ ،‬ﻛﻨﺘﺮﻟﺮ ﺩﻭﺑﺎﺭﻩ ﺍﺳﺘﺎﺭﺕ ﻧﻤﻲ ﺯﻧﺪ ﻭ ‪LED‬‬ ‫‪‬‬
‫ﻣﺮﺑﻮﻁ ﺑﻪ ‪ Oil Pressure‬ﺷﺮﻭﻉ ﺑﻪ ﭼﺸﻤﮏ ﺯﺩﻥ ﻛﺮﺩﻩ ﺍﺳﺖ‪:‬‬
‫‪ -‬ﻛﻨﺘﺎﻛﺖ ‪ Oil Pressure Switch‬ﺑﺎ ﺗﺎﺧﻴﺮ ﺑﺴﺘﻪ ﻣﻲ ﺷﻮﺩ ‪ .‬ﻣﺎﺩﺍﻣﻴﻜﻪ ﻛﻨﺘﺮﻟﺮ ﻭﺟﻮﺩ ﻛﻨﺘﺎﻛﺖ‬
‫ﻓﺸﺎﺭ ﺭﻭﻏﻦ ﺭﺍ ﺩﺭ ﻭﺭﻭﺩﻱ ﺗﺸﺨﻴﺺ ﺩﺍﺩﻩ ﺍﺳﺖ ﻓﺮﻣﺎﻥ ﺍﺳﺘﺎﺭﺕ ﺩﺍﺩﻩ ﻧﻤﻲ ﺷﻮﺩ‪ .‬ﺩﺭﺻﻮﺭﺗﻲ ﮐﻪ‬
‫‪ Oil Pressure Switch‬ﺑﺴﺘﻪ ﺷﻮﺩ ‪،‬ﻛﻨﺘﺮﻟﺮ ﺍﺳﺘﺎﺭﺕ ﺧﻮﺍﻫﺪ ﺷﺪ ‪ .‬ﭘﺲ ‪Oil Pressure‬‬
‫‪ Switch‬ﺑﺎﻳﺪ ﺗﻌﻮﻳﺾ ﮔﺮﺩﺩ ‪.‬‬

‫‪ ‬ﻭﻟﺘﺎﮊ ﺑﺮﻕ ﺷﻬﺮ ﻗﻄﻊ ﺷﺪﻩ ﻭ ﻣﻮﺗﻮﺭ ﺍﺳﺘﺎﺭﺕ ﻭ ﺭﻭﺷﻦ ﺷﺪﻩ ﻭﻟﯽ ﺁﻻﺭﻡ ‪ Start Fail‬ﻣﻲ ﺩﻫﺪ ﻭ ﻣﻮﺗﻮﺭ‬
‫ﺧﺎﻣﻮﺵ ﻣﻲ ﺷﻮﺩ ‪:‬‬
‫‪ -‬ﻭﻟﺘﺎﮊ ﻓﺎﺯﻫﺎﯼ ﮊﻧﺮﺍﺗﻮﺭ ﺑﻪ ﺻﻮﺭﺕ ﺻﺤﻴﺢ ﺑﻪ ﻛﻨﺘﺮﻟﺮ ﻭﺻﻞ ﻧﻴﺴﺘﻨﺪ ‪ .‬ﻭﻟﺘﺎﮊ ﻓﺎﺯﻫﺎﯼ ‪ U,V,W‬ﻭ‬
‫ﺧﻨﺜﯽ ﮊﻧﺮﺍﺗﻮﺭ ﺍﺯ ﭘﺸﺖ ﻛﻨﺘﺮﻟﺮ ﺩﺭ ﻫﻨﮕﺎﻣﯽ ﮐﻪ ﻣﻮﺗﻮﺭ ﺭﻭﺷﻦ ﺍﺳﺖ ‪ ،‬ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﯼ ﮐﻨﻴﺪ ‪ .‬ﻓﻴﻮﺯ‬
‫ﺣﻔﺎﻇﺖ ﻓﺎﺯﻫﺎﯼ ﮊﻧﺮﺍﺗﻮﺭ ﻣﻤﮑﻦ ﺍﺳﺖ ﺳﻮﺧﺘﻪ ﺑﺎﺷﺪ ‪ .‬ﻣﻤﮑﻦ ﺍﺳﺖ ﺍﺗﺼﺎﻻﺕ ﺑﻪ ﺻﻮﺭﺕ ﺻﺤﻴﺢ‬
‫ﺍﻧﺠﺎﻡ ﻧﺸﺪﻩ ﺑﺎﺷﺪ ‪ .‬ﺍﮔﺮ ﻫﻤﻪ ﭼﻴﺰ ﺩﺭﺳﺖ ﺍﺳﺖ ﻫﻤﻪ ﻓﻴﻮﺯﻫﺎ ﺭﺍ ﻗﻄﻊ ﮐﻨﻴﺪ ﺳﭙﺲ ﻫﻤﻪ ﻓﻴﻮﺯﻫﺎ ﺭﺍ‬
‫ﻭﺻﻞ ﻧﻤﺎﻳﻴﺪ )ﺍﺯ ﻓﻴﻮﺯ ﻣﻨﺒﻊ ﺗﻐﺬﻳﻪ ‪ DC‬ﺷﺮﻭﻉ ﻧﻤﺎﻳﻴﺪ( ‪ .‬ﺳﭙﺲ ﻛﻨﺘﺮﻟﺮ ﺭﺍ ﺩﻭﺑﺎﺭﻩ ﺗﺴﺖ ﮐﻨﻴﺪ ‪.‬‬

‫‪ ‬ﻛﻨﺘﺮﻟﺮ ﺑﻪ ﮐﻨﺪﯼ )ﺩﻳﺮ( ﺍﺳﺘﺎﺭﺕ ﺭﺍ ﻗﻄﻊ ﻣﻲ ﮐﻨﺪ ‪:‬‬


‫‪ -‬ﻭﻟﺘﺎﮊ ﮊﻧﺮﺍﺗﻮﺭ ﺑﻪ ﮐﻨﺪﯼ ﺍﻓﺰﺍﻳﺶ ﭘﻴﺪﺍ ﻣﯽ ﮐﻨﺪ ‪ ،‬ﻫﻤﭽﻨﻴﻦ ﺟﻤﻊ ﻭﻟﺘﺎﮊﻫﺎﻱ ﮊﻧﺮﺍﺗﻮﺭ ﺯﻳﺮ ‪ ۲۰‬ﻭﻟﺖ‬
‫ﺍﺳﺖ ‪ .‬ﻛﻨﺘﺮﻟﺮﺍﺣﺘﻴﺎﺝ ﺑﻪ ﺣﺪﺍﻗﻞ ‪ ۲۰‬ﻭﻟﺖ ﺑﺮﺍﯼ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﯼ ﻓﺮﮐﺎﻧﺲ ﺩﺍﺭﺩ ﻭ ﺍﺳﺘﺎﺭﺕ ﮊﻧﺮﺍﺗﻮﺭ ﺑﺎ‬
‫ﺗﻮﺟﻪ ﺑﻪ ﻋﺪﻡ ﺷﻨﺎﺳﺎﻳﻲ ﻓﺮﮐﺎﻧﺲ ﻗﻄﻊ ﻧﺨﻮﺍﻫﺪ ﺷﺪ ‪ .‬ﺑﺮﺍﯼ ﺍﺟﺘﻨﺎﺏ ﺍﺯ ﺍﻳﻦ ﻭﺿﻌﻴﺖ ﺗﻨﻬﺎ ﺭﺍﻩ ﺍﺳﺘﻔﺎﺩﻩ‬
‫ﺍﺯ ﻳﮏ ﺭﻟﻪ ﮐﻤﮑﯽ ﺍﺳﺖ ‪ .‬ﺑﻮﺑﻴﻦ ﺍﻳﻦ ﺭﻟﻪ ﺑﺎﻳﺪ ﺑﻴﻦ )‪ Battery(-‬ﻭ ﺗﺮﻣﻴﻨﺎﻝ ‪ D+‬ﻣﺮﺑﻮﻁ ﺑﻪ‬
‫ﺷﺎﺭﮊﺭ ﻣﺘﻨﺎﻭﺏ ﻗﺮﺍﺭ ﮔﻴﺮﺩ ‪ .‬ﮐﻨﺘﺎﮐﺖ ‪ Normaly Close‬ﺍﻳﻦ ﺭﻟﻪ ﺑﺎﻳﺪ ﺑﻪ ﺻﻮﺭﺕ ﺳﺮﯼ ﺑﻪ‬
‫ﺧﺮﻭﺟﯽ ﺍﺳﺘﺎﺭﺕ ﻛﻨﺘﺮﻟﺮ ﻣﺘﺼﻞ ﮔﺮﺩﺩ ‪.‬‬

‫‪40‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪ ‬ﻛﻨﺘﺮﻟﺮ ﻛﺎﺭ ﻧﻤﻲ ﻛﻨﺪ ‪:‬‬


‫‪ -‬ﻭﻟﺘﺎﮊ ‪ DC‬ﻣﺮﺑﻮﻁ ﺑﻪ ﺗﻐﺬﻳﻪ ﻛﻨﺘﺮﻟﺮ )ﺗﺮﻣﻴﻨﺎﻝ ﻫﺎﯼ ‪ ۱۱‬ﻭ ‪ (۱۲‬ﺭﺍ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﯼ ﻧﻤﺎﻳﻴﺪ ‪ .‬ﻫﻤﻪ ﻓﻴﻮﺯﻫﺎ‬
‫ﺭﺍ ‪ OFF‬ﮐﻨﻴﺪ ﺳﭙﺲ ﻫﻤﻪ ﻓﻴﻮﺯﻫﺎ ﺭﺍ ‪ ON‬ﮐﻨﻴﺪ ‪ .‬ﺍﺯ ﻣﻨﺒﻊ ﺗﻐﺬﻳﻪ ‪ DC‬ﺷﺮﻭﻉ ﮐﻨﻴﺪ ﻭ ﺩﻭﺑﺎﺭﻩ‬
‫ﻛﻨﺘﺮﻟﺮ ﺭﺍ ﺗﺴﺖ ﮐﻨﻴﺪ ‪.‬‬

‫‪ ‬ﻛﻨﺘﺮﻟﺮ ﻭﺍﺭﺩ ﺣﺎﻟﺖ ‪ Programming‬ﻧﻤﻲ ﺷﻮﺩ ‪:‬‬


‫‪ -‬ﻭﺭﻭﺩﯼ ﻗﻔﻞ ‪ Programming‬ﻣﺎﻧﻊ ﺍﺯ ﻭﺭﻭﺩ ﮐﻨﺘﺮﻟﺮ ﺑﻪ ﺍﻳﻦ ﺣﺎﻟﺖ ﻣﯽ ﺷﻮﺩ ‪ .‬ﻗﺒﻞ ﺍﺯ ﺗﻐﻴﻴﺮﺍﺕ ‪،‬‬
‫ﻭﺭﻭﺩﯼ ﻗﻔﻞ ﺑﺮﻧﺎﻣﻪ ﺭﺍ ﺍﺯ ﻣﻨﻔﯽ ﺑﺎﻃﺮﯼ ﺟﺪﺍ ﻧﻤﺎﻳﻴﺪ ‪ .‬ﻓﺮﺍﻣﻮﺵ ﻧﮑﻨﻴﺪ ﮐﻪ ﺍﻳﻦ ﺍﺗﺼﺎﻝ ﺭﺍ ﺑﺮﺍﯼ‬
‫ﺟﻠﻮﮔﻴﺮﯼ ﺍﺯ ﻭﺍﺭﺩ ﺷﺪﻥ ﺑﻪ ﺣﺎﻟﺖ ‪ ، Program‬ﺩﻭﺑﺎﺭﻩ ﻭﺻﻞ ﻧﻤﺎﻳﻴﺪ ‪.‬‬

‫‪ -۱۳‬ﺍﻋﻼﻡ ﺗﻄﺎﺑﻖ ﻫﺎ‬


‫ﺍﻳﻦ ﻛﻨﺘﺮﻟﺮ ﺍﺯ ﺩﺳﺘﻮﺭﺍﻟﻌﻤﻞ ‪ EU‬ﭘﻴﺮﻭﯼ ﻣﯽ ﮐﻨﺪ‬
‫‪ 73/23/EEC -‬ﻭ ‪(Low Voltage) 93/68/EEC‬‬
‫‪ 89/336/EEC -‬ﻭ ‪ 92/31/EEC‬ﻭ ‪93/68/EEC‬‬

‫ﻣﺂﺧﺬ ﻗﺎﻧﻮﻧﯽ ﻣﺮﺑﻮﻁ ﺑﻪ ‪: Refrence‬‬


‫‪EN 61010 -‬‬
‫‪EN50081-2 -‬‬
‫‪EN50082-2 -‬‬
‫ﻧﺸﺎﻥ ‪ ، CE‬ﻧﺸﺎﻥ ﻣﯽ ﺩﻫﺪ ﮐﻪ ﺍﻳﻦ ﺗﻮﻟﻴﺪ ‪ Safty‬ﻫﺎ ‪ ،‬ﺳﻼﻣﺖ ﻣﺤﻴﻂ ﻭ ﺣﻔﺎﻇﺖ ﻣﺸﺘﺮﯼ‬
‫ﻣﻮﺭﺩ ﻧﻴﺎﺯ ﺍﺭﻭﭘﺎ ﺭﺍ ﺗﺎﻣﻴﻦ ﻣﻴﮑﻨﺪ ‪.‬‬

‫‪41‬‬
DKG207 ‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫ ﻣﺸﺨﺼﺎﺕ ﻓﻨﻲ‬-۱۴
Alternator voltage : 0 to 300V-AC (Ph-N)
Alternator frequency : 0-100 HZ.
Maun voltage : 0 to 300 V- AC (Ph-N)
Current input: from current transformer,…/5A. Max load 0.7VA per phase
Digital inpusts : input voltage 0-30V-DC. Internally connected to battery positive via 4700
ohm resistor
Analog inputs:Resistor input 0 to 5000 ohms connected to the battery negative. Sources 10 ma
when closedto battery negative.
Measurment category: CAT II
Air category: Pollution degree II
DC Supply range: 9.0 V – DC to 30.0 V-DC
Cranking dropout: survive 0V for 100 ms
Typical current consumption: 100 ma - DC
Maximum current consumption: 350 ma – DC ( Relay outputs open)
Generator/mains contactor outputs: 16A / 250 V.
DC relay outputs: 10 A / 28 V .
Max.current for each terminal: 10A-RMS.
Charge alternator excitation current: 54 ma -DC @ 12V - DC
Communication port: RS-232.2400 bauds, no parity, 1 stop bit.
Operating temprerature range: -20C to +70C (-4F to +158F)
Storage temperature range: -40C to +80C (-40F to +176F)
Maximum humidity: 95% , non-condensing
IP protection: IP65 from front panel , IP30 from the rear
Dimensions: 130 x 100 x 39 mm (W x H x D)
Mounting opening dimensions: 116 x 86 mm minimum
Mounting: Front panel mounted, retaning steel spring at the rear
Weight: 250 g (approx)
Case material : High temperature , self extinguishing ABS (UL94-V0,110C)

42
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG207‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪ -۱۵‬ﺩﻳﺎﮔﺮﺍﻡ ﻧﺼﺐ‬

‫‪43‬‬