You are on page 1of 8

Industry & Facilities Division

Third Party Inspection Report Page 1 of 8

INSPECTION REPORT No: PU-SEEN-22.119-IR02 Revision No. 0


Initial Interim Final Resident Remote
Inspection requested by: SEEN TECHNOLOGIES CORPORATION
Inspection performed as Recognised Authority: Yes, :(Recognition) No
BV Job No: BUH/IDD/2023/TBD (BV Romania) / PU-SEEN-22.119 (BV Vietnam)

Project: Yen Xa Wastewater Treatment Plant IPO Ref : PU-SEEN-22.119-IPO02


(BV internal P/o)
BV Client: SEEN TECHNOLOGIES CORPORATION P/o no: -
(client to BV)
Manufacturer/Vendor: ELECTROTEL SA (manufacturer) P/o no: -
SOLCON INDUSTRIES LTD (vendor) (client to Manufacturer)
Sub-Vendor (If applicable): N/A
Inspection Location: Electrotel SA, Strada Dunării 279, Alexandria Previous Inspection (If applicable): N/A
140103, jud. Teleorman, ROMANIA (Date)
Inspection Location (GPS Coordinates): Next Inspection (If applicable): N/A
43.95720863193676, 25.34730079999745 (Date)
Inspection performed on: 05.01.2023 Total No. of Inspection Days: 1
( Date(s) )

MATERIAL / SUBJECT OF INSPECTION QTY


QTY
Refer to attachment section J instead ITEM / TAG Nr Offered for
As per P/O
(Indicate if separate material list is provided in attachment) inspection
CAPACITOR PANEL ( AB-MVP-3, AB-MVP-4)
753, 754 4 2

A – INSPECTION RESULT
Satisfactory Satisfactory with comments Not Satisfactory
(Without comments) (Any of trailing Punch or Non Conformity (NCR raised during the
items is still open) inspection)
Inspection Summary: (for details refer to section E)
 Inspection / FAT acc. to “Switchgear Factory Acceptance Test Procedure” issued by SOLCON
 Inspection / FAT acc. to “FACTORY TEST AND INSPECTION PLAN” issued by JFE-TSK
Result: Satisfactory
Open Non Conformities: Yes, details in section G No
Open Punch List Items: Yes, details in section H No
Release Note Issued: Yes, number(s): (Release Note number) No
BV Traceability Stamping: Yes, Yes, No

BV Inspector: George Nitulescu BV Coordinator: Iosif Rebleanu

BV Office: Bucharest, Romania Inspection Report Date: 06.01.2023

Distribution: Attachments Report:


CLIENT BV MANUFACTURER Yes, details in section J No
OTHER: …………………………..

GM-SI-101 INSP002-En Rev. 3.1 Copyright Bureau Veritas 06/2021


Industry & Facilities Division
Third Party Inspection Report
Page 2 of 8

INSPECTION REPORT No: PU-SEEN-22.119-IR02 Revision No: 0

B - REFERENCE DOCUMENTATION: Refer to attachment section J instead


(Indicate if separate document list is provided in attachment)
Approval
Title Reference n° Rev. Approved by Date
status
“Switchgear Factory issued by
- Rev.02 - 08.11.2021
Acceptance Test Procedure” SOLCON
“FACTORY TEST AND
INSPECTION PLAN
issued by JFE-
CAPACITOR PANEL ( AB- - - - -
TSK
MVP-3, AB-MVP-4, AB-MVP-
15, AB-MVP-16)”
issued by
Electrical plan & layout 1225-21-1 Rev.5 - 13.04.2022
SOLCON

C – ATTENDEES
Name Position Representing
Mr. Stefan VATU Project Manager ELECTROTEL
Mr. Crisan MANAFU QC Engineer ELECTROTEL
Mr. George NITULESCU Surveyor BUREAU VERITAS

D - MEASURING & TESTING EQUIPMENT USED Refer to attachment section J instead


(Indicate if separate equipment list is provided in attachment)
Equipment Type Equipment Identity n° Last Calibration Date Expiry Date
HV dielectric testing system HVTS- 07.05.2020
2015 05.2023
70/50 (Metrological cert No. 0653)
30.05.2022
Digital multimeter Fluke 87V 41210153 05.2023
(Metrological cert No. 2248)
06.04.2020
Digital megohmeter METREL MI-2077 16021080/06 04.2023
(Metrological cert No. 0314E/2020)
21.01.2022
Analogic ampermeter UH 28-A 1A 01.2023
(Metrological cert No. ELT-E-003)

E – INSPECTION DETAILS
E – General
E1 – Details of Witness (W) & Hold (H) Inspection Points
The equipment was found completely manufactured and prepared for FAT test.

Inspection / FAT was performed according the procedure mentioned in “Switchgear Factory Acceptance Test
Procedure” issued by SOLCON and “FACTORY TEST AND INSPECTION PLAN” issued by JFE-TSK.
It included:
- Checking of the items, according to the applicable documentation, before FAT;
- Cubicle over-all dimensions check Height x Width x Depth – as per drawings
- That construction bolts are properly fastened
- Panel name plates , low voltage component indexes and terminals, control module – as per drawings
- Markings of all control and power wires in the cabinet.
- Main ground (GND) Copper conductor cross section: 60 x 5 mm .GND Bus Bar clearly marked.
- Grounding of doors and L.V control plates: copper wire 6 mm2 / braid 16 mm2. Grounding screws are clearly marked
on doors
- Minimum air distance between exposed phases and phase to metal part
- H.V Insulator screws tightening Torque
- Functional and simulation Test
- Verify correct functioning of indication lights.

GM-SI-101 INSP002-En Rev. 3.1 Copyright Bureau Veritas 06/2021


Industry & Facilities Division
Third Party Inspection Report
Page 3 of 8

INSPECTION REPORT No: PU-SEEN-22.119-IR02 Revision No: 0

- Draw-out devices e.g: Contactor, Circuit Breaker will remain in insert position
- M.V Circuit Dielectric test (power frequency test)
- Aux. L.V Circuit Dielectric test
- Functional and simulation tests
- Insulation resistance test / Megger test

Result: Satisfactory, the equipment passed the FAT tests

E2 – Details of Monitoring and Surveillance Patrols Tick if conducted during the visit
NA
E3 – Details of Certificates Review Tick if conducted during the visit
NA

F – HEALTH, SAFETY & ENVIRONMENT COMMENTS


(Comment on Observations and Actions Taken During the Inspection)
During the inspection the required PPE was worn in the workshop according to the manufacturer’s procedure.

G- NON CONFORMITIES
Refer to attachment section J instead
(Indicate if separate punch list is provided in attachment)
Report Report
Item Description Status Raised on Closed on Comments
No. No.
N.A.
-
H – PUNCH LIST ITEMS
Refer to attachment section J instead
(Indicate if separate punch list is provided in attachment)
Report Report
Item Description Status Raised on Closed on Comments
No. No.
N.A. -

I – DIGITAL PICTURES

Description: Manufacturer plate for sn 753 Description: Manufacturer plate for sn 754

GM-SI-101 INSP002-En Rev. 3.1 Copyright Bureau Veritas 06/2021


Industry & Facilities Division
Third Party Inspection Report
Page 4 of 8

INSPECTION REPORT No: PU-SEEN-22.119-IR02 Revision No: 0

Description: Rear-right view Description: Rear-left view

Description: Front-left view Description: Electrical cabinet door

GM-SI-101 INSP002-En Rev. 3.1 Copyright Bureau Veritas 06/2021


Industry & Facilities Division
Third Party Inspection Report
Page 5 of 8

INSPECTION REPORT No: PU-SEEN-22.119-IR02 Revision No: 0

Description: AB-MVP-4 tag Description: AB-MVP-3 tag

Description: Parameter plate Description: Indicator during tests

Description: HV dielectric test value Description: Megger test value

GM-SI-101 INSP002-En Rev. 3.1 Copyright Bureau Veritas 06/2021


Industry & Facilities Division
Third Party Inspection Report
Page 6 of 8

INSPECTION REPORT No: PU-SEEN-22.119-IR02 Revision No: 0

Description: Circuit breaker indicator during test Description: Busbars

Description: HV dielectric tester Description: Insulation tests

GM-SI-101 INSP002-En Rev. 3.1 Copyright Bureau Veritas 06/2021


Industry & Facilities Division
Third Party Inspection Report
Page 7 of 8

INSPECTION REPORT No: PU-SEEN-22.119-IR02 Revision No: 0

Description: Separator test Description: LV dielectric test voltage

Description: LV dielectric test value. Description: Screw torque verification

GM-SI-101 INSP002-En Rev. 3.1 Copyright Bureau Veritas 06/2021


Industry & Facilities Division
Third Party Inspection Report
Page 8 of 8

INSPECTION REPORT No: PU-SEEN-22.119-IR02 Revision No: 0

Description: Screw torque verification Description: LV dielectric test

J – ATTACHMENTS
Item Attachment Name Total Pages Description

1 CE HVTS 70 50 2 pages Calibration certificate no. 0653


CE_2248_FLUKE 87V
2 5 pages Calibration certificate no. 2248
serie 41210153
SIMAR Megohmetru MI
3 5 pages Calibration certificate no. 0314E/2020
2077
Stand incercare tensiune
4 2 pages Calibration certificate no. ELT-E-003
marita UH 28A
ELECTROTEL Quality
docs - CI 7170802-
5 4 pages Declaration of Conformity no. 2173
Solcon - 1225-21 Hai
Anh Capacitor
SOLCON FAT Test
6 4 pages FAT test report for sn. 753 and 754
Report 7170802
VCS Test Report
7 2 pages VCS test report for sn V522-01345 and V522-01346
7170802 sr 753 754

END OF REPORT