You are on page 1of 3

NUCLEAR POWER CORPORATION OF INDIA LTD.

DESIGN OF BI-AXIAL ISOLATED RCC FOOTING (IS 456, 2000)


Building Name tv < tc hence O.K.
Footing Number: F1 tv < tc hence O.K.
Node number tv < allowable hence O.K.
Hence footing is safe against max gross bearing pr.
COLUMN C5 max pressure
Length (l, dim. || Z axis ) = 750 mm
global
Breadth (b, dim. || X axis) = 375 mm
X
Breadth 2.85 m
FOOTING
Foot length (L, dim. || Z axis) = 2.85 m
global global
Foot Breadth (B, dim. || X axis) = 2.85 m Z
Thickness of footing (t) = 750 mm Z
Clear cover of footing = 50 mm
global
Main bar dia of footing = 20 mm
X
Depth of the footing 1500 mm
Effective depth of footing = 690 mm Length 2.85 m
Selfweight of the footing = 152.30 KN Footing Dimensions
Area of Footing(A) = 8.12 m2
Sect mod of foot about Z axis (Zz) = 3.86 m3
Sec mod of foot about X axis (Zx) = 3.86 m3

MATERIALS OF CONSTRUCTION
2
Grade of concrete fck = 30 N/mm
2
Grade of steel fy = 550 N/mm

CHECK FOR GROSS BEARING PRESSURE


Safe NET bearing pressure = 325 KN/m2
Safe gross bearing pr. = 406.25 KN/m3 (net pr. + depth of foot * soil unit wt)
Unfactored load case number = 1
Axial load from output (P1) = 1988.67 KN 2983 LOAD factored
Moment about Z axis (Mz) = 103.33 KN-m 155 MZ
Moment about X axis (Mx) = 176.00 KN-m 264 MX
Depth of top of foot. from ground = 0.75 m
3
Unit wt of soil = 18 KN/m
Weight of soil retained above foot = 105.86 KN
P = (P1+soil+foot self wt) = 1988.67 KN
2 P My Mx
Maximum bearing pressure = 317.23 KN/m  
Minimum bearing pressure = 172.43 KN/m
2 A Zy Zx
Hence footing is safe against max gross bearing pr.

DESIGN FORCES
Factored load comb. no. 2
Axial load:(Pu) = 2983.00 KN
Moment about Z axis (Muz) = 155 KN-m
Moment about X axis (Mux) = 264 KN-m
Maximum effective soil pressure pe max
2
( Pu/Area+ Muz/Zz + Mux/Zx) = 475.85 KN/m
Minimum effective soil pressure pe min
2
( Pu/Area - Muz/Zz - Mux/Zx) = 258.65 KN/m
Design of footing is done using above maximum effective soil pressure

FOOTING F1
NUCLEAR POWER CORPORATION OF INDIA LTD.

CALCULATION FOR BOTTOM STEEL


Mu about X1 X1 = ( pe max x length2/2)= 262.31 KN-m per meter
Mulimit = 1859.56 KN-m per meter
0.5 f ck  4.6 M u 
Ast  1  1   bd The section is singly reinforced
f y  f ck bd 2 
2
Hence, Ast = 812.426 mm
2
Min Ast = 2070.000 mm (0.12 % for slab, cl 26.5.2.1)
Spacing = 151.77 mm (considering max of above two calculated values of Ast)
pt provided = 0.30 %
Hence provide 20 mm dia bar @ 151 mm c/c parellel to length of footing ( || to Z)

Mu about N1 N1 = ( pe max x length2/2)= 364.36 KN-m per meter


2
Calc. Ast = 1138.568 mm The section is singly reinforced
2
Min Ast = 2070 mm (0.12 % for slab, cl 26.5.2.1)
Spacing = 151.77 mm (considering max of above two calculated values of Ast)
pt provided = 0.3 %
Hence provide 20 mm dia bar @ 151 mm c/c parellel to breadth of footing ( || to X)
Arrangement of bottom reinforcement as per above design is shown below

20 mm dia bar @ 151 mm c/c

20 mm dia bar @ 151 mm c/c

1 1

Footing Length 2850 mm Breadth 2850 mm

Sec 1-1

1440 375
1065
L1 X1 X

a a

Z Z
N1 N1
a a

L2 L2

360 X1 X
L1 Breadth 2850 mm
750
Footing Length 2850 mm 547.5
PLAN

FOOTING F1
NUCLEAR POWER CORPORATION OF INDIA LTD.

CHECK FOR ONE WAY SHEAR :


One way shear at critical section L1- L1
Distance of critical sec. from edge of footing = 0.36 m
Shear force Vs =pe max x 0.36 x 1m width of footing = 171.307 KN
2
Shear stress tv = Vs/bd = 0.248 N/mm
2
tc = 0.40 N/mm
tv < tc hence O.K.

One way shear at critical section L2- L2


Distance of critical sec. from edge of footing = 0.5475 m
Shear force Vs =pe max x 0.5475 x 1m width of footing = 260.529 KN
2
Shear stress tv = Vs/bd = 0.378 N/mm
2
tc = 0.40 N/mm
tv < tc hence O.K.

CHECK FOR TWO WAY SHEAR


Ref. cl 34.2.4 and cl.31.6.3 of IS 456 : 2000
Allowable shear stress tv allowable = kstc
ks = ( 0.5 + bc) = 1.5 >1
Hence, ks= 1
2
tc = 0.25 (fck)0.5 = 1.36931 N/mm
2
tv allowable = ks x tc = 1.36931 N/mm
Shear force Vs = 475.851 ( 2.85 x 2.85 - 1.44 x 1.065) = 3135.34 KN
Length of critical section = 2 x ( 1440 + 1065) = 5010 mm
2
Area of the critical section (length of critical sec x eff. d ) = 3456900 mm
2
Hence shear stress tv = 0.907 N/mm
tv < allowable hence O.K.

FOOTING F1

You might also like