Please Fill Following Details

Ceylon Electricity Board Area Office = HORANA


CSC = HORANA
Area Engineer = Eng. P.V.N Shashimal
Electrical Superintendent = Mr.G.D THUSHARA

Proposed Solar installation transformer (SIN) = HR256


Transformer Capacity (KVA) = 160
Number of LT feeders = 3
Installed Solar Capacity (kW) = 34.00
Type A
Feeder 1 = ABC 17.36
Feeder 2 = ABC 18.66
Average Daytime Loading of the proposed Feeder 3 = ABC 15.6
solar connecting LT feeder (A) without solar Feeder 4 = FLY
Feeder 5 = FLY
Feeder 6 = FLY
Transformer Tapping Voltage (V) = 394

Customer Name = S.DC.D.Subasinghe


Customer Address 268/2B, D.L.Gunasekara Mw,
= Munagama,Horana.
Customer Company (If not a domestic Consumer) = 3122050803
Proposed Solar PV Capacity (kW) = 5
Distance to the installation location from Transformer = 230
Proposed connection LT feeder = 3

Proposed Solar Capacity Can be accomadated

Phase Voltage within Limit


Line Voltage within Limit

Phase Voltage within Limit


Line Voltage within Limit

Phase Voltage within Limit


Line Voltage within Limit

Phase Voltage within Limit


Line Voltage within Limit

Phase Voltage within Limit


Line Voltage within Limit

Phase Voltage within Limit


Line Voltage within Limit
Feeder 1 Feeder 2 Feeder 3 Feeder 4
(kWp) (kWp) (kWp) (kWp)
Pole Distance
B C A B C A B C A B C
ORANA No (m) A
ORANA Pole 0 0
N Shashimal Pole 1 30 0 0 0
THUSHARA Pole 2 60 0 0 0
Pole 3 90
R256 Pole 4 120 5
160 Pole 5 150 0 0 0
3 Pole 6 180
34.00 Pole 7 210 2
PF Pole 8 240 4 4 4 5 0 0
0.9 Pole 9 270 0 0 0
0.9 Pole 10 300 5
0.9 Pole 11 330
0.9 Pole 12 360
0.9 Pole 13 390
0.9 Pole 14 420 0 0 0
394 Pole 15 450 5
Pole 16 480
e Pole 17 510
sekara Mw,
na. Pole 18 540
Pole 19 570 0 0 0 0 0
5 Pole 20 600 0
230 Pole 21 630
3 Pole 22 660
Pole 23 690
Pole 24 720 0
accomadated Pole 25 750 0
Pole 26 780
imit Pole 27 810
mit Pole 28 840
Pole 29 870
mit Pole 30 900
mit Pole 31 930
Pole 32 960
mit Pole 33 990
mit Pole 34 1020 0 0 0 0 0 0 0 0 0
Pole 35 1050
mit Pole 36 1080
mit Pole 37 1110
Pole 38 1140
mit Pole 39 1170 0 0
mit Pole 40 1200
Pole 41 1230
mit Pole 42 1260 0
mit Pole 43 1290 0
Pole 44 1320 0 0 0 0 0 0 0 0
Pole 45 1350 0 0 0 0
Pole 46 1380 0 0 0 0
Pole 47 1410 0 0 0 0
Pole 48 1440 0 0 0 0
Pole 49 1470 0 0 0 0 0 0 0 0 0 0 0
Pole 50 1500 0 0 0 0 0 0 0 0 0 0 0 0
Max Phase Voltage (V) 232.00 237.05 235.04 227.48
Max Line Voltage (V) 393.98 396.59 394.84 394.00
Total PV (kWp) 7.00 17.00 10.00 0.00
Voltage Unbalance(%) 2.41 4.12 3.62 0.00

Voltage Unbalance(%) High High High within Limit


Feeder 5 Feeder 6
(kWp) (kWp)
Max. F1 Phase Voltage (V)
A B C A B C 245

240

0 0 235

230

0 225

220

0 0 215
0 0

Max. F2 Phase Voltage (V)


0 0 245

240

235

0 0 230

225

220

Max. F3 Phase Voltage (V)


245

240

235

0 0 0 0 0 0 230

225

0 0 0
220

0 0
Max. F4 Phase Voltage (V)
250

0 0 245
0 0
240
0 0 0
0 0 235
0 0 230
0 0 0 0 0 0
225
0 0 0 0 0 0
227.48 227.48 220
394.00 394.00 215
0.00 0.00
0.00 0.00

within Limit within Limit Max. F5 Phase Voltage (V)


250

245

240

235

230

225

220

215

Max. F6 Phase Voltage (V)


250

245

240

235

230

225

220

215
tage (V)

)
tage (V)

tage (V)