Title: Air -Conditioning Finding Report Doc no.

KVC/BDN/R/A – 000123
Date: 31/12/2022 Service Report No.
Location: RTG 150 Work Area: Sinamic Room (A/C 2)
Time Start: 09:00 HRS Time Finish: 12:00 HRS Work Order: WO22066566

No. Crew Attending Service Code Total hours


1. Supervisor - -
2. Technician - -

Work Description
Problem:
During PM on 31 December 2022, A/C 2 at Sinamic Room found out that the outdoor unit was corroded severely
that may lead pipe to leakage. Plus, the unit PCB was faulty and high ampere. The Brand: York, Manufacture year:
2013, Model: YSL15C3-AMPOL, S/N: 20564402-43076. The A/C has reached it life-cycled indicating the unit in poor
performance that may cause in breakdown cases. To prevent from further breakdown, it’s recommended changing
new unit for both A/C model for 1.5 HP.

Rectify & Action:


A/C is running normally so crane can continue operate until failure. Request to change the new unit 1.5 HP split unit
in Electrical Room for both A/C 2.

A/C 2

Recommendation:
Propose to perform and replace new unit 1.5 HP air-conditioning Unit: -:

Description Service Code Quantity


Daikin 1.5HP Split Unit Air-condition
ENGACM-18-0042 x1
R410A or R32 (Indoor & Outdoor)
Installation Charge 1.5HP ENGACM-18-0013 x1
Refill Gas R410 or R32 ENGACM-18-0045 x1
Copper pipe - 1 Length ENGACM-18-0055 x1

Report Prepared By:


Signature:
Name: Syazwan Bin Shamsuddin
Designation: Assistant Service Engineer
Date: 03/01/2023