U [W/m2 K] U [W/m K] Remarks
BKD
Ext. wall type I 0.56
ENGG CERT

HAL

Ext. wall type II -


Int. wall type I 0.8
HAL

Int. wall type II -


Roof type I 0.46
Roof type II -
Floor type I
Floor type II -
Windows type I -
Windows type II
DESCRIPTION

Windows type III


AS BUILT

Ext. door type I


Ext. door type II -
Int. doors type I
Int. doors type II -
REQUIRED CAPACITIES (According to thermal load calculation executed by Vendor)
Item COOLING LOAD HEATING LOAD Remarks
Calculation month / hour JULY 17:00 For:
Total Floor Area [FT2 ] 400 400 -Lunch and Locker area
Total Cooling Load [BTU/h] 23343 11338 -S.O. Office
JO/EWO

31471

Total Sensible Load [BTU/h] 21818


Total latent Load [BTU/h] 2525
HAL Total Air Flow [cfm] 998
02/05/02
DATE

02/05/02 Outdoor Ventilation Airflow [cfm] 160


Total System Pressure Drop [Pa]
NO.
REV

Coil Entering Temp. (Db/Wb) [oF] 77.7 / 64.8


01

HAL
02/05/02
DISCIPLINE Coil Leaving Temp. (Db/Wb) [oF] 57.3 / 56.7
ENGINEER Coil ADP [oF] 56.2
HAL Bypass Factor 0.050
DATE:
02/05/02 AIR CONDITIONING UNITS
PROJECT
ENGINEER Equipment type: ROOF TOP SINGLE PACKAGE COOLING/HEATING UNIT WITH AIR DISTR. DUCTS & ACC.

SAG Mfr. / Model: CARRIER / 50 SS-042-3


DATE:
02/05/02 Equipment capacity: Cooling 3.5 Tr / Heating 5 kW
CERTIFIED
Cooling Heating
AKM Total Cooling Capacity [KBTU/h ]: 35.50 Total Heating Capacity [kW ]: 5.0 K W
DATE:
02/05/02
CONSTRUCTION Nominal Sensible Capacity [KBTU/h ]: 26.21 Nominal Sensible Capacity [BTU/h ]:
AGENCY
Corrected Sensible Capacity [KBTU/h ]: 4.4 Corrected Sensible Capacity [BTU/h ]:
6/25/2023

(for the current air conditions) (for the current air conditions)
02060228

DATE:
JDS

Latent capacity [KBTU/h ]: 9.29 Latent capacity [BTU/h ]:


OPERATIONS
Nominal air flow [ CFM ]: 1225 Nominal air flow [CFM]:
COILS (Note 1)
DATE: Evaporator Condenser Remarks
CONTROL NUMBER

Nominal Capacity [KBTU/h ]: 35.5 35.5


VERIFICATION
01

728200-jo-1998-31471-030

Operating Temperature [oF]: 109.8 109.8


EDSD

Working Pressure [kPa]: 0.25 0.25


DATE:

Tube / Fine Material: Cu / Al Cu / Al BLY-GOLD COATING


BY:
REVISIONCERTIFICATION

DATA SHEET FOR HVAC SYSTEM DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE

DAT
OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE

BLDG. No 430 OPERATOR SHELTER OFFICE


H46 K BE- 338846
(DCC) NO. _____________________

INLET AREA FACILITIES 002 01


SAUDI ARABIA JO / EWO:
HAWIYAH
EDSD/2616-0399.doc