You are on page 1of 491

Copyright © 2019 NR. All rights reserved.

NR, the NR logo are either registered trademarks or trademarks of NR Electric Co., Ltd. No NR
trademarks may be used without written permission. NR products appearing in this document may
be covered by P.R. China and foreign patents. NR Electric Co., Ltd. reserves all rights and
benefits afforded under P.R. China and international copyright and patent laws in its products,
including but not limited to software, firmware and documentation. NR Engineering Co., Ltd. is
licensed to use this document as well as all intellectual property rights owned or held by NR
Electric Co., Ltd, including but not limited to copyright, rights in inventions, patents, know-how,
trade secrets, trademarks and trade names, service marks, design rights, database rights and
rights in data, utility models, domain names and all similar rights.

The information in this document is provided for informational use only and does not constitute a
legal contract between NR and any person or entity unless otherwise specified. Information in this
document is subject to change without prior notice.

To the extent required the products described herein meet applicable IEC and IEEE standards,
but no such assurance is given with respect to local codes and ordinances because they vary
greatly.

Although every reasonable effort is made to present current and accurate information, this
document does not purport to cover all details or variations in equipment nor provide for every
possible contingency to be met in connection with installation, operation, or maintenance. Should
further information be desired or should particular problems arise which are not covered
sufficiently for your purposes, please do not hesitate to contact us.
Preface

Preface

About This Manual


The technical manual describes the protection, automation, control, and supervision functions of
PCS S series device, and contains operation principle descriptions, and lists function blocks, logic
diagrams, input and output signals, setting parameters and technical data, sorted per function, as
well as the hardware of the device. The manual can be used as a technical reference during the
engineering phase and during normal service. In addition, the manual also includes a glossary
that lists and defines technical terms used throughout the manual.

Safety Information
This manual is not a complete index of all safety measures required for operation of the
equipment (module or device). However, it comprises important information that must be followed
for personal safety, as well as to avoid material damage. Information is highlighted and illustrated
as follows according to the degree of danger:

Indicates an imminently hazardous situation that, if not avoided, will

result in death or serious injury.

Indicates a potentially hazardous situation that, if not avoided, could

result in death or serious injury.

Indicates a potentially hazardous situation that, if not avoided, may result

in minor or moderate injury or equipment damage.

Indicates that property damage can result if the measures specified are

not taken.

Important information about the device, product handling or a certain


section of the documentation which must be given particular attention.

Instructions and Warnings


The following hazard statements apply to this device.

Disconnect or de-energize all external connections BEFORE opening this


device. Contact with hazardous voltages and currents inside this device

PCS-9611S Feeder Relay I


Date: 2019-04-24
Preface

can cause electrical shock resulting in injury or death.

Contact with instrument terminals can cause electrical shock that can
result in injury or death.

Use of this equipment in a manner other than specified in this manual can
impair operator safety safeguards provided by this equipment.

Have only qualified personnel service this equipment. If you are not
qualified to service this equipment, you can injure yourself or others, or
cause equipment damage.

This device is shipped with default passwords. Default passwords should


be changed to private passwords at installation. Failure to change each
default password to a private password may allow unauthorized access.
NR shall not be responsible for any damage resulting from unauthorized
access.

DO NOT look into the fiber (laser) ports/connectors.

DO NOT look into the end of an optical cable connected to an optical


output.

DO NOT perform any procedures or adjustments that this instruction


manual does not describe.

During installation, maintenance, or testing of the optical ports, ONLY use


the test equipment qualified for Class 1 laser products!

II PCS-9611S Feeder Relay


Date: 2019-04-24
Preface

Incorporated components, such as LEDs, transceivers, and laser emitters,


are NOT user serviceable. Return units to NR for repair or replacement.

Equipment components are SENSITIVE to electrostatic discharge (ESD).


Undetectable permanent damage can result if you do not use proper ESD
procedures. Ground yourself, your work surface, and this equipment
BEFORE removing any cover from this equipment. If your facility is not
equipped to work with these components, contact NR about returning this
device and related NR equipment for service.

Insufficiently rated insulation can deteriorate under abnormal operating


conditions and cause equipment damage. For external circuits, use wiring
of SUFFICIENTLY RATED insulation that will not break down under
abnormal operating conditions.

SEVERE power and ground problems can occur on the communications


ports of this equipment as a result of using non-standard cables. Please
use the wiring method recommended in the manual for communication
terminals.

DO NOT connect power to the relay until you have completed these
procedures and receive instruction to apply power. Equipment damage
can result otherwise.

Use of controls or adjustments, or performance of procedures other than


those specified herein, may RESULT IN hazardous radiation exposure.

The firmware may be upgraded to add new features or enhance/modify


existing features, please MAKE SURE that the version of this manual is
compatible with the product in your hand.

PCS-9611S Feeder Relay III


Date: 2019-04-24
Preface

Document Conventions
 The abbreviations and acronyms in this manual are explained in “Appendix A Glossary”. The
Glossary also contains definitions of important terms.

 Menu path is connected with the arrow "→" and bold.

For example: the access path of protection settings is: MainMenu→Settings→Protection


Settings

 Settings not in the table should be placed in brackets.

For example: the system setting [Opt_SysFreq]

 Cross-references are presented in italics.

For example: refer to Figure 1.1-1, refer to Table 1.1-1, reference to Section 1.1

 Binary input signals, binary output signals, analogs, LED lights, buttons, and other fixed
meanings, should be written in double quotes and bold.

For example: press the button "ENT".

Symbols
 AND Gate

& & &

 OR Gate

>=1 >=1 >=1

 Comparator

 Binary signal Input

BI xxx

 Signal input

SIG xxx

IV PCS-9611S Feeder Relay


Date: 2019-04-24
Preface

 Setting input

SET xxx

 Enable input

EN xxx

 Timer

Optional definite-time or inverse-time characteristics

Timer
t
t

 Timer

Fixed delay pickup (10ms), fixed delay dropout (2ms)

10ms 2ms

 Timer

Settable delay pickup, fixed delay dropout

[Tset1] 0ms

 Timer

Fixed delay pickup, settable delay dropout

0ms [Tset2]

 Timer

Settable delay pickup, settable delay dropout

[Tset1] [Tset2]

 Generator

 Transformer

PCS-9611S Feeder Relay V


Date: 2019-04-24
Preface

 Reactor

 Motor

 Capacitor

 Busbar

 Circuit breaker

52

 Current transformer

3CT
*

 Voltage transformer

3VT

 Disconnector

VI PCS-9611S Feeder Relay


Date: 2019-04-24
Preface

 Earth

Three-phase Corresponding Relationship


Basic
A, B, C L1, L2, L3 R, Y, B
AN, BN, CN L1N, L2N, L3N RN,YN, BN
ABC L123 RYB
U (voltage) V U

Example
Ia, Ib, Ic, I0 IL1, IL2, IL3, IN IR, IY, IB, IN
Ua, Ub, Uc VL1, VL2, VL3 UR, UY, UB
Uab, Ubc, Uca VL12, VL23, VL31 URY, UYB, UBR
U0, U1, U2 VN, V1, V2 UN, U1, U2

Warranty
This product is covered by the standard NR 10-year warranty. For warranty details, please consult
the manufacturer or agent for warranty information.

Document Structure
This manual is a comprehensive work covering the theories of protection, control, supervision,
measurement, etc. and the structure & technical data of relevant hardware. Read the sections that
pertain to your application to gain valuable information about using this device. To concentrate on
the target sections of this manual as your job needs and responsibilities dictate. An overview of
each manual section and section topics follows.

1 Introduction
Introduces the features of this device, summarizes functions and applications of the device.

2 Technical Data
Lists device specifications, type tests, and ratings.

3 Protection Functions
Describes the function of various protection elements, gives detailed specifics on protection
scheme logic, and provides the relevant logic diagrams.

4 Control Functions
Describes the logic for the control of disconnectors and circuit breakers.

PCS-9611S Feeder Relay VII


Date: 2019-04-24
Preface

5 Measurement
Provides information on viewing fundamental and metering quantities for voltages and currents,
as well as power and energy metering data.

6 Supervision
Describes self-supervision technique to help diagnose potential difficulties should these occur and
includes the list of status notification messages. Provides a troubleshooting chart for common
device operation problems.

7 System Functions
Describes how to perform fundamental operations such as clock synchronization, communicating
with the device, switching active setting group, checking relay status, reading event reports and
SER (Sequential Events Recorder) records.

8 Hardware
Describes the hardware of the PCS S series device family and provides general information on
the product structure and the modules’ information.

9 Settings
Provides a list of all PCS-9611S settings and their ranges, unit, steps, defaults. The organization
of the settings is similar to the settings organization in the device and in the PCS-Studio
configuration tool.

Appendix A Glossary
Describes the abbreviations adopted in this manual.

Document Revision History


PN: ZL_PCS-9611S_X_Technical Manual_EN_Overseas General_X

Current version: R1.01

Corresponding Version
Date Description of change
Document Software

R1.00 R1.00 2019-01-31  Form the original manual.

 Positive-sequence overvoltage protection is added;


R1.01 R1.00 2019-04-24
 Outmap settings are added.

VIII PCS-9611S Feeder Relay


Date: 2019-04-24
Introduction

1 Introduction
1
Table of Contents

1.1 Application ....................................................................................................... 1-1


1.2 Functions ......................................................................................................... 1-1
1.3 Features ............................................................................................................ 1-6

List of Figures

Figure 1.1-1 Functional diagram of PCS-9611S ....................................................................... 1-1

PCS-9611S Feeder Relay 1-a


Date: 2019-04-24
1 Introduction

1-b PCS-9611S Feeder Relay


Date: 2019-04-24
Introduction

1.1 Application

The PCS-9611S relay is a protection, control and monitoring unit for various primary equipment
1
(such as overhead line, underground cable and transformer etc.) on solidly grounded, impedance
grounded, Peterson coil grounded and ungrounded system. This relay is suitable for wall surface
mounted indoors or outdoors or flush mounted into a control panel.

The function diagram of this relay is shown in Figure 1.1-1.

Busbar
3VTs

52

27P 59P 59Q VTS 59G 81U 81O 81R 25 79


1VT

67P 32R

3CTs
*

50P 51P CTS 50BF 51Q

1CT
*

50G 51G SOTF 67G 37

1CT
*

51SEF 60/59 60/50 67SEF FR


1VT

Load

Figure 1.1-1 Functional diagram of PCS-9611S

1.2 Functions

1 Protection functions

PCS-9611S Feeder Relay 1-1


Date: 2019-04-24
1 Introduction

ANSI Protection Functions Remark


 Up to 6 stages with independent logic

1 

Voltage control element for each stage
Optional direction element for each stage, including
67P forward direction, reverse direction and non-direction
Phase overcurrent protection
50/51P  Optional definite-time characteristic and inverse-time
characteristic for each stage
 Selectable trip purpose or alarm purpose for each stage
 Harmonic control element for each stage
 Up to 6 stages with independent logic
 Optional direction element for each stage, including
forward direction, reverse direction and non-direction
 Optional measured zero-sequence current or calculated
67G
Earth fault protection zero-sequence current
50/51G
 Optional definite-time characteristic and inverse-time
characteristic for each stage
 Selectable trip purpose or alarm purpose for each stage
 Harmonic control element for each stage
 Only measured zero-sequence current is supported
 Up to 6 stages with independent logic
A.67G Another group of earth fault
 Optional definite-time characteristic and inverse-time
A.50/51G overcurrent protection
characteristic for each stage
 Selectable trip purpose or alarm purpose for each stage
 Up to 2 stages with independent logic
 Optional direction element for each stage, including
Negative-sequence overcurrent forward direction, reverse direction and non-direction
50/51Q
protection  Optional definite-time characteristic and inverse-time
characteristic for each stage
 Selectable trip purpose or alarm purpose for each stage
 The measured zero-sequence current from the
high-precision CT is adopted
 Up to 6 stages with independent logic
 Optional direction element for each stage, including
50/51SEF Sensitive earth fault protection
forward direction, reverse direction and non-direction
 Optional definite-time characteristic and inverse-time
characteristic for each stage
 Selectable trip purpose or alarm purpose for each stage
 Up to 2 stages with independent logic
nd th
 Full-current RMS value includes 2 ~11 harmonic
50/51R RMS overcurrent protection
component
 Selectable trip purpose or alarm purpose for each stage
 Optional blocking condition, including circuit breaker
37 Undercurrent protection position and current criterion
 Selectable trip purpose or alarm purpose for each stage

1-2 PCS-9611S Feeder Relay


Date: 2019-04-24
Introduction

 Breaker failure protection and re-trip function


 Optional current criterion (phase overcurrent element,

50BF Breaker failure protection


zero-sequence overcurrent element, negative-sequence
overcurrent element)
1
 It can be initiated by current, circuit breaker position or
external binary input
 Two time delays
 One stage of phase overcurrent SOTF protection
 One stage of earth fault overcurrent SOTF protection
50PSOTF
Switch-on-to-fault protection  Harmonic control element
50GSOTF
 Voltage control element for phase overcurrent SOTF
protection
 Up to 2 stages with independent logic
 Optional definite-time characteristic and inverse-time
characteristic for each stage
59P Overvoltage protection
 Optional phase voltage or phase-to-phase voltage
 Optional “1-out-of-3” logic or “3-out-of-3” logic
 Selectable trip purpose or alarm purpose for each stage
 Up to 2 stages with independent logic
 Optional definite-time characteristic and inverse-time
characteristic for each stage
 Optional phase voltage or phase-to-phase voltage
27P Undervoltage protection  Optional “1-out-of-3” logic or “3-out-of-3” logic
 Check mode using circuit breaker position and current
criterion
 Blocked by instantaneous VT circuit failure
 Selectable trip purpose or alarm purpose for each stage
Negative-sequence overvoltage  Up to 2 stages with independent logic
59Q
protection  Selectable trip purpose or alarm purpose for each stage
Positive-sequence overvoltage  One stage of positive-sequence overvoltage protection
59Pos
protection  Selectable trip purpose or alarm purpose
 Up to 2 stages with independent logic
 Optional measured zero-sequence voltage or calculated
59G Residual overvoltage protection
zero-sequence voltage
 Selectable trip purpose or alarm purpose for each stage
 Up to 6 stages with independent logic
81O Overfrequency protection
 Voltage control element
 Up to 6 stages with independent logic
81U Underfrequency protection
 Voltage control element
Frequency rate-of-change  Up to 6 stages with independent logic
81R
protection  Voltage control element
 Up to 2 stages with independent logic
32R Reverse power protection
 Selectable trip purpose or alarm purpose for each stage

PCS-9611S Feeder Relay 1-3


Date: 2019-04-24
1 Introduction

 Up to 2 stages with independent logic


60/50 Unbalance current protection
 Selectable trip purpose or alarm purpose for each stage

1 60/59 Unbalance voltage protection




Up to 2 stages with independent logic
Selectable trip purpose or alarm purpose for each stage
 It can be triggered by on-load signal or circuit breaker
CLP Cold load pickup position
 Short resetting is supported
25 Synchrocheck  Independent logic for auto-reclosing and manually closing
 One shot or multi-shot
 3-pole AR
79 Auto-reclosing  It can be triggered by protection operation signal or
external binary input signal
 Supports synchronism check or dead charge check
CTS Current transformer supervision
VTS Voltage transformer supervision
TCS Tripping circuit supervision

2 Control functions

 Circuit breaker & disconnector control (Remote/Local)

 Synchronism check for remote and manual closing

3 Measurement functions

 Energy metering (active and reactive energy are calculated in import and export direction
respectively)

 Power (Apparent/Active/Reactive)

 Power factor

 Frequency

 Event recorder including 1024 disturbance items, 1024 binary events, 1024 supervision
events, 256 control logs and 1024 device logs.

 Disturbance recorder including 64 disturbance records with waveforms (The file format of
disturbance recorder is compatible with international COMTRADE file.)

4 Supervision functions

 VT circuit supervision

 CT circuit supervision

 Trip/Close coil supervision

 Self diagnostic

 DC power supply supervision

 System frequency supervision

1-4 PCS-9611S Feeder Relay


Date: 2019-04-24
Introduction

5 Communication functions

 Up to four 10Base-T/100Base-TX copper Ethernet ports using IEC 61850, DNP3.0 or


IEC 60870-5-103 over TCP/IP 1
 Up to four 100Base-FX optical Ethernet ports using IEC 61850, DNP3.0 or IEC
60870-5-103 over TCP/IP

 Two RS-485 serial ports using IEC 60870-5-103

 One RS-485 serial port for clock synchronization

 Support GOOSE communication module using IEC 61850-8-1 GOOSE

 Full compatibility between IEC 61850 Editions 1 and 2

 Redundancy protocols PRP and HSR

 One front RJ45 port for debugging

6 User Interfaces

 Friendly HMI interface with LCD, easy-to-use keypad aids simple navigation and
set-point adjustment

 Push buttons for open/close, switch for selection between local and remote control, and
user's login and logout authority management

 4 Programmable operator pushbuttons with user-configurable labels

 Up to 15/18 (1/3U or 1/2U chassis) programmable target LEDs with user-configurable


labels

 1 RS-232 or RS-485 rear ports for printer

 Language switchover—English+ selected language

 Configuration tool—PCS-Studio

7 Additional functions

 User programmable logic

 Fault location

 Fault phase selection

 System phase sequences rotation function (ABC or ACB)

 Clock synchronization

 IRIG-B: IRIG-B via RS-485 differential level or TTL level

 PPS: Pulse per second (PPS) via RS-485 differential level or binary input

 PPM: Pulse per minute (PPM) via RS-485 differential level or binary input

PCS-9611S Feeder Relay 1-5


Date: 2019-04-24
1 Introduction

 IEEE1588: Clock message based on IEEE1588 via optical fiber interface

 SNTP (PTP): Unicast (point-to-point) SNTP mode via Ethernet network


1  SNTP (BC): Broadcast SNTP mode via Ethernet network

 Message (IEC103/Modbus/DNP3.0): Clock messages through IEC103 protocol,


Modbus protocol and DNP3.0 protocol

 Cyber security

 NERC CIP

 IEC 62351

 IEC 62443

 IEEE 1686

1.3 Features

 Unified software and hardware platform, comprehensive power grid solutions of protection,
control, measurement and monitoring, easy to use and maintain.

 High reliability and redundancy design for drive systems of the sampling circuit and the output
circuit ensure that overall reliability of the device is high. Real-time sampling based on dual AD
can mutually check and detect the potential abnormality in the sampling circuit in time. The
control power supply of the output relay is independent with the control circuit of trigger signals,
which can prevent from undesired operation caused by the abnormality of drive circuit of
output relays.

 Various function modules can satisfy various situations according to the different requirements
of users. Flexible and universal logic programming, user-defined configuration of BI/BOs,
buttons and LEDs and powerful analog programming are supported.

 Modularized hardware design makes the device be easily upgraded or repaired by a qualified
service person. It can be mixed with different I/O modules, with online self-check and
monitoring function, and the device can be restored from abnormal operation only need to
replace a single abnormal module.

 Support memory check and error correction function, ensure high reliability and safety.

 Support the internet communication protocol of native PRP/HSR and RSTP.

 Fully compatible with IEC 61850 edition 1 & edition 2, support MMS service, IEC 62351
communication service, GOOSE communication in station level & process level, SV
communication with multi-sampling rate.

 Full comply with cyber security standards, including IEC62443, IEC62351, IEEE1686,
NERC-CIP, support role based access control (RBAC), security audit, security encryption
communication and security tool, improve the cyber security capability of devices.

1-6 PCS-9611S Feeder Relay


Date: 2019-04-24
Introduction

 Powerful COMTRADE fault and disturbance recording function is supported. The whole
recording time is automatically configurable by the fault duration, which is convenient to fault
analysis and replay. The recording sample rate is up to 9.6kHz.
1
 Settable secondary rated current (1A/5A) and settable voltage threshold of binary input

 Support small size and large size LCD, control and multifunction button

 Support flush mounting, semi-flush mounting, surface mounting, wall mounting and other
mounting methods.

 Cross screw IO, CT/VT terminals can support AWG12 specification connector and 4mm 2 lead

 Multiple variants with case size 1/3 or 1/2 × 19"

 Protection class of front side is up to IP54

 PCS-Studio engineering tool is the application software on the user's PC for the interface with
PCS S series devices providing all the related functionality. It ranges from device configuration
to full substation design of bay integration.

 Support IEEE1588, IRIG-B clock synchronization

 Support actual system phase sequence, either ABC or ACB, incorrect connection of actual
phase sequence can automatically be verified and relevant protection functions can be
blocked.

 Equipped with high-speed large capacity output relay, its operation speed is less than 1ms and
its break capacity is up to 10A. The real-time supervision for output drive circuit can detect the
abnormality in advance.

 Support setup up to 40 users and allow each user to own different password and access
authority.

 Fully integrates multi functions into one device and can realize the protection and monitoring

function of feeder and capacitor etc.

 Comprehensive functionality includes phase overcurrent protection, earth fault overcurrent

protection, negative-sequence overcurrent protection, sensitive earth fault protection,

overvoltage protection, undervoltage protection, frequency protection, reverse power

protection, breaker failure protection, undercurrent protection etc. The breaker failure,

reclosing, measuring, monitoring and control function are supported.

 The overcurrent protection is combined with harmonic blocking and cold load pickup logic,

which can prevent mal-operation affected by inrush current while the transformer is no-load

energized.

 Selectable IEC, ANSI inverse-time characteristic curves, also the curve can be defined by

PCS-9611S Feeder Relay 1-7


Date: 2019-04-24
1 Introduction

users and the inverse-time drop-out curve selection is supported.

 Overvoltage and undervoltage protection support single phase and three phase operation
1
criteria setting, phase voltage and phase-to-phase voltage measurement mode are selectable,

which can be for various applications.

 Complete event recording function is provided: 64 latest protection operation reports, 1024

latest supervision records, 1024 latest control operation records, 1024 latest user operation

records and 1024 latest records of time tagged sequence of event (SOE) can be recorded.

1-8 PCS-9611S Feeder Relay


Date: 2019-04-24
2 Technical Data

2 Technical Data

Table of Contents

2.1 Electrical Specifications ................................................................................. 2-1 2


2.1.1 AC Current Input ................................................................................................................... 2-1

2.1.2 AC Voltage Input ................................................................................................................... 2-2

2.1.3 Power Supply ....................................................................................................................... 2-2

2.1.4 Binary Input .......................................................................................................................... 2-2

2.1.5 Binary Output........................................................................................................................ 2-4

2.2 Mechanical Specifications .............................................................................. 2-5


2.3 Ambient Temperature and Humidity Range .................................................. 2-6
2.4 Communication Port ....................................................................................... 2-6
2.4.1 EIA-485 Port ......................................................................................................................... 2-6

2.4.2 Ethernet Port ........................................................................................................................ 2-6

2.4.3 Optical Fiber Port ................................................................................................................. 2-7

2.4.4 Print Port ............................................................................................................................... 2-7

2.4.5 Clock Synchronization Port .................................................................................................. 2-7

2.5 Type Tests ........................................................................................................ 2-7


2.5.1 Environmental Tests ............................................................................................................. 2-7

2.5.2 Mechanical Tests .................................................................................................................. 2-8

2.5.3 Electrical Tests ...................................................................................................................... 2-8

2.5.4 Electromagnetic Compatibility .............................................................................................. 2-8

2.6 Certifications .................................................................................................. 2-10


2.7 Liquid Crystal Display (LCD) ........................................................................ 2-10
2.8 Terminals ........................................................................................................ 2-10
2.8.1 Ring Ferrule ........................................................................................................................ 2-10

2.8.2 Pin Ferrule .......................................................................................................................... 2-11

2.9 Measurement Scope and Accuracy ..............................................................2-11


2.10 Management Function..................................................................................2-11

PCS-9611S Feeder Relay 2-a


Date: 2019-04-24
2 Technical Data

2.10.1 Control Performance ........................................................................................................ 2-11

2.10.2 Clock Performance ........................................................................................................... 2-12

2.10.3 Fault and Disturbance Recording..................................................................................... 2-12

2.10.4 Binary Input Signal ........................................................................................................... 2-12

2 2.11 Protective Functions ................................................................................... 2-12


2.11.1 Phase Overcurrent Protection (50/51P) ........................................................................... 2-12

2.11.2 Earth Fault Protection (50/51G) ....................................................................................... 2-13

2.11.3 Another Group of Earth Fault Overcurrent Protection ...................................................... 2-14

2.11.4 Negative-sequence Overcurrent Protection (50/51Q)...................................................... 2-14

2.11.5 Sensitive Earth Fault Protection (50/51SEF) ................................................................... 2-15

2.11.6 RMS Overcurrent Protection (50/51R) ............................................................................. 2-16

2.11.7 Phase Overvoltage Protection (59P) ................................................................................ 2-16

2.11.8 Residual Overvoltage Protection (59G) ........................................................................... 2-17

2.11.9 Negative-sequence Overvoltage Protection (59Q) .......................................................... 2-17

2.11.10 Positive-sequence Overvoltage Protection (59Pos) ...................................................... 2-17

2.11.11 Phase Undervoltage Protection (27P) ............................................................................ 2-17

2.11.12 Overfrequency Protection (81O) .................................................................................... 2-18

2.11.13 Underfrequency Protection (81U)................................................................................... 2-18

2.11.14 Frequency Rate-of-change Protection (81R) ................................................................. 2-18

2.11.15 Reverse Power Protection (32R).................................................................................... 2-18

2.11.16 Undercurrent Protection (37) .......................................................................................... 2-19

2.11.17 Breaker Failure Protection (50BF).................................................................................. 2-19

2.11.18 Unbalance Current Protection (60/50) ........................................................................... 2-19

2.11.19 Unbalance Voltage Protection (60/59) ........................................................................... 2-20

2.11.20 Auto-reclosing (79) ......................................................................................................... 2-20

2.11.21 Transient Overreach ....................................................................................................... 2-20

2.11.22 Fault Locator ................................................................................................................... 2-20

2-b PCS-9611S Feeder Relay


Date: 2019-04-24
2 Technical Data

2.1 Electrical Specifications

“System phase sequence”, which can be set by PCS-Studio, this setting


informs the device of the actual system phase sequence, either ABC or 2
ACB. CT and VT inputs on the device, labeled as A, B and C, must be
connected to system phase A, B and C for correct operation.

2.1.1 AC Current Input

 Conventional AC current input

Phase rotation ABC or ACB

Nominal frequency (fn) 50Hz, 60Hz

Rated current (In) 1A/5A (Settable)

Linear to 0.05In~40In

Thermal withstand

-continuously 4In

-for 10s 30In

-for 1s 100In

-for half a cycle 250In

Burden <0.05VA/phase @1A, <0.25VA/phase @5A

Number Up to 5 current inputs according to various applications

 AC current input for sensitive earth fault protection

Rated current (In) 1A

Linear to 0.01A~5A

Thermal withstand

-continuously 20A

-for 10s 100A

-for 1s 300A

-for half a cycle 750A

Burden <0.15VA/phase @1A

PCS-9611S Feeder Relay 2-1


Date: 2019-04-24
2 Technical Data

2.1.2 AC Voltage Input

Phase rotation ABC or ACB

Nominal frequency (fn) 50Hz, 60Hz

Rated voltage (Un) 100V~130V

2 Linear to 1V~300V

Thermal withstand Phase-to-ground Phase-to-phase

-continuously 300V 519V

-10s 600V 1038V

-1s 660V 1141V

Burden at rated <0.10VA/phase @100V

Number Up to 5 voltage inputs according to various applications

2.1.3 Power Supply

Standard IEC 61000-4-29:2000

100Vac/110Vac/115Vac/120Vac

Rated voltage 110Vdc/125Vdc/220Vdc/250Vdc 127Vac/220Vac/230Vac/240Vac

250Vac

Permissible voltage range 88~300Vdc 88~275Vac

Permissible AC ripple voltage ≤15% of the nominal auxiliary voltage

Burden

Quiescent condition <15W

Operating condition <20W

2.1.4 Binary Input

Settable pickup voltage and dropout voltage

Rated voltage 110Vdc 125Vdc 220Vdc 250Vdc

Rated current drain 0.73mA 0.83mA 1.47mA 1.67mA

On value (default set) 69.3~132Vdc 78.75~160Vdc 138.6~264Vdc 157.5~300Vdc

Off value (default set) <55Vdc <62.5Vdc <110Vdc <125Vdc

Maximum permissible voltage 300Vdc

2-2 PCS-9611S Feeder Relay


Date: 2019-04-24
2 Technical Data

Withstand voltage 2000Vac, 2800Vdc (continuously)

Up to 34 (6U, 1/3, ring ferrule), 41 (6U, 1/3, pin ferrule), 84 (6U, 1/2,

Number ring ferrule) or 105 (6U, 1/2, pin ferrule) binary inputs according to

various hardware configurations

2
Settable pickup voltage and dropout voltage

Rated voltage 110Vac 220Vac

Rated current drain 0.73mA 1.47mA

On value (default set) 69.3~132Vac 138.6~264Vac

Off value (default set) <55Vac <110Vac

Maximum permissible voltage 300Vac

Withstand voltage 2000Vac, 2800Vdc (continuously)

Up to 34 (6U, 1/3, ring ferrule), 41 (6U, 1/3, pin ferrule), 84 (6U, 1/2,

Number ring ferrule) or 105 (6U, 1/2, pin ferrule) binary inputs according to

various hardware configurations

Settable pickup voltage and dropout voltage

Rated voltage 24V 48V

Rated current drain 0.16mA 0.32mA

On value (default set) 15.12~28.8Vdc 30.24~57.6Vdc

Off value (default set) <12V <24V

Maximum permissible voltage 300Vdc

Withstand voltage 2000Vac, 2800Vdc (continuously)

Up to 34 (6U, 1/3, ring ferrule), 41 (6U, 1/3, pin ferrule), 84 (6U, 1/2,

Number ring ferrule) or 105 (6U, 1/2, pin ferrule) binary inputs according to

various hardware configurations

PCS-9611S Feeder Relay 2-3


Date: 2019-04-24
2 Technical Data

2.1.5 Binary Output

Tripping/signaling contact

Output mode Potential free contact

Max. system voltage 250Vac, 300Vdc

2 Continuous carry 10A

Pickup time (Typical value) <5ms

Dropout time (Resistive load) <6ms

0.5A@48Vdc

0.35A@110Vdc

Breaking capacity (L/R=40ms) 0.30A@125Vdc

0.20A@220Vdc

0.15A@250Vdc

0.5A@48Vdc

0.35A@110Vdc
Cyclic Capacity (2.5 cycle/second,
0.30A@125Vdc
L/R=40ms)
0.20A@220Vdc

0.15A@250Vdc

30A@3s
Short duration current
50A@1s

Durability (Loaded contact) 10000 operations

Up to 18 (6U, 1/3, ring ferrule), 22 (6U, 1/3, pin ferrule), 44 (6U, 1/2,

Number ring ferrule) or 56 (6U, 1/2, pin ferrule) binary outputs according to

various hardware configurations

Heavy-capacity tripping contact

Output mode Potential free contact

MOV Protection (maximum voltage ) 350Vdc, 275Vac

Continuous carry 10A

Pickup time (Typical value) <1ms

2-4 PCS-9611S Feeder Relay


Date: 2019-04-24
2 Technical Data

Dropout time (Resistive load) <10ms

10A@48V

10A@110V
Breaking capacity (L/R=40ms)
10A@125V

10A@250V 2
10A@48V L/R=40ms
Cyclic Capacity (4cycles in 1 second,
10A@110V L/R=40ms
followed by 2 minutes idle for thermal
10A@125V L/R=40ms
dissipation)
10A@250V L/R=20ms

30A@3s
Short duration current
50A@1s

Durability (Loaded contact) 10000 operations

Up to 4 (6U, 1/3, ring ferrule) or 12 (6U, 1/2, ring ferrule)


Number heavy-capacity binary outputs according to various hardware
configurations

2.2 Mechanical Specifications

Chassis color Silver grey

Approx. 8.66kg (6U, 1/2)


Weight per device
Approx. 6.93kg (6U, 1/3)

Chassis material Aluminum alloy

Location of terminal Rear panel of the device

Device structure Plug-in modular type @ rear side, integrated front plate

Protection Class

Standard IEC 60529-2013

Front side IP52

Other sides IP50

Rear side, connection terminals IP20

PCS-9611S Feeder Relay 2-5


Date: 2019-04-24
2 Technical Data

2.3 Ambient Temperature and Humidity Range

Standard IEC 60255-1:2009

-40°C to +80°C (Readability of display may be impaired below -20°C


Operating temperature

2 and above 70°C)

Transport and storage temperature


-40°C to +80°C
range

Permissible humidity 5%~95%, without condensation

Pollution degree Ⅱ

Altitude <3000m

2.4 Communication Port

2.4.1 EIA-485 Port

Baud rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s

Protocol IEC 60870-5-103:1997 or Modbus

Max. capacity 32

Max. transmission distance 500m

Safety level Isolation to ELV level

Twisted pair Screened twisted pair cable

2.4.2 Ethernet Port

Connector type RJ-45 LC

Transmission rate 100Mbits/s

Transmission standard 100Base-TX 100Base-FX

Max. transmission distance 100m 2km (1310nm)

Protocol IEC 60870-5-103:1997, DNP 3.0 or IEC 61850

Safety level Isolation to ELV level

2-6 PCS-9611S Feeder Relay


Date: 2019-04-24
2 Technical Data

2.4.3 Optical Fiber Port

For Station Level

Characteristic Glass optical fiber

Connector type LC

Fiber type Multi mode 2


Max. transmission distance 2km

Wave length 1310nm

Transmission power 50μm: -24dBm 62.5μm: -20dBm

Minimum receiving power Min -31dBm

Margin 50μm: -7dBm 62.5μm: -9dBm

2.4.4 Print Port

Type RS-232

Baud Rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s

Printer type EPSON® 300K printer

Safety level Isolation to ELV level

2.4.5 Clock Synchronization Port

Type RS-485 serial port

Input Demodulated IRIG-B or PPS

Nominal Voltage 5Vdc+10%

Maximum Voltage 8Vdc

Input Impedance 2.5kΩ

Isolation 500Vdc

2.5 Type Tests

2.5.1 Environmental Tests

Dry cold test IEC60068-2-1:2007

Dry heat test IEC60068-2-2:2007

PCS-9611S Feeder Relay 2-7


Date: 2019-04-24
2 Technical Data

Damp heat test, cyclic IEC60068-2-30:2005

2.5.2 Mechanical Tests

Vibration IEC 60255-21-1:1988 Class Ⅰ

Shock and bump IEC 60255-21-2:1988 Class Ⅰ


2
2.5.3 Electrical Tests

Standard IEC 60255-27:2013

Dielectric tests Test voltage 2kV, 50Hz, 1min

Impulse voltage tests Test voltage 5kV

Overvoltage category Ⅲ

Insulation resistance measurements Isolation resistance >100MΩ@500VDC

2.5.4 Electromagnetic Compatibility

IEC 60255-26:2013

1MHz burst disturbance test Common mode: class Ⅲ 2.5kV

Differential mode: class Ⅲ 1.0kV

IEC 61000-4-2:2008 class Ⅳ

Electrostatic discharge test For contact discharge: 8kV

For air discharge: 15kV

IEC 60255-26:2013 class Ⅲ

Frequency sweep

Radiated amplitude-modulated

Radio frequency interference tests 10V/m (rms), f=80~1000MHz, 14000~2700MHz

Spot frequency

Radiated amplitude-modulated

10V/m (rms), f=80MHz/160MHz/450MHz/900MHz

IEC 60255-26:2013

Fast transient disturbance tests Power supply, I/O, Earth: class Ⅳ, 4kV, 5kHz, 5/50ns

Communication terminals: class Ⅳ, 2kV, 5kHz, 5/50ns

Surge immunity test IEC 60255-26:2013

2-8 PCS-9611S Feeder Relay


Date: 2019-04-24
2 Technical Data

Power supply, AC input, I/O port: class Ⅳ, 1.2/50us

Common mode: 4kV

Differential mode: 2kV

IEC 60255-26:2013

Conducted RF Electromagnetic
Power supply, AC, I/O, Comm. Terminal: Class Ⅲ, 10Vrms, 150 2
kHz~80MHz
Disturbance
Spot frequency

10V/m (rms), f=27MHz/68MHz

Power Frequency Magnetic Field IEC 61000-4-8: 2009

Immunity class Ⅴ, 100A/m for 1min, 1000A/m for 3s

IEC 61000-4-9:2016
Pulse Magnetic Field Immunity
class Ⅴ, 6.4/16μs, 1000A/m for 3s

Damped oscillatory magnetic field IEC 61000-4-10:2016

immunity class Ⅴ, 100kHz & 1MHz–100A/m

IEC 60255-26:2013

Conducted emission 0.15MHz~0.50MHz: 79dB (μV) quasi peak, 66dB (μV) average

0.50MHz~30MHz: 73dB (μV) quasi peak, 60dB (μV) average

IEC 60255-26:2013

30MHz~230MHz: 40dB (μV/m) quasi peak @10m,

50dB (μV/m) quasi peak @3m


Below 1GHz
230MHz~1000MHz: 47dB (μV/m) quasi peak @10m,

Radiated emission 57dB (μV/m) quasi peak @3m

1GHz~3GHz: 56dB (μV/m) average, 76dB (μV/m)

peak @3m
Above 1GHz
3GHz~6GHz: 60dB (μV/m) average, 80dB (μV/m)

peak @3m

Auxiliary power supply performance IEC 60255-26:2013

PCS-9611S Feeder Relay 2-9


Date: 2019-04-24
2 Technical Data

- Voltage dips
Up to 200ms for dips to 40% of rated voltage without reset
-Voltage short interruptions
50ms for interruption without rebooting without energy storage board

(Typical configuration)

500ms for interruption without rebooting with energy storage board

2 (Typical configuration)

2.6 Certifications

 ISO9001:2008

 ISO14001:2004

 OHSAS18001:2007

 ISO10012:2003

 CMMI L5

 EMC: 2014/30/EU, EN60255-26:2013

 Products safety (LVD): 2014/35/EU, EN60255-27:2014

2.7 Liquid Crystal Display (LCD)

Type Resolution

Large size 320x240 pixels

Small size 240x160 pixels

2.8 Terminals

2.8.1 Ring Ferrule

Connection Type Wire Size Screw Type Torque

AC current Screw terminals, 1.5~4mm2 lead M4 1.6~1.8 N⋅m

2
AC voltage Screw terminals, 0.8~4mm lead M4 1.6~1.8 N⋅m

Power supply Screw terminals, 0.8~4mm2 lead M4 0.8~1.4 N⋅m

2
Contact I/O Screw terminals, 0.8~4mm lead M4 0.8~1.4 N⋅m

2
Grounding (Earthing) Connection BVR type, 0.8~4mm lead M3 0.6~0.8 N⋅m

2-10 PCS-9611S Feeder Relay


Date: 2019-04-24
2 Technical Data

2.8.2 Pin Ferrule

Connection Type Wire Size Screw Type Torque

Power supply Screw terminals, 0.3~3.3mm2 lead M2.5 0.4~0.6 N⋅m

2
Contact I/O Screw terminals, 0.3~3.3mm lead M2.5 0.4~0.6 N⋅m

2
2.9 Measurement Scope and Accuracy

Item Range Accuracy

Phase range 0°~ 360° ≤±1°

Frequency fn±3 Hz ≤ 0.01Hz

Currents from protection measurement current transformers

≤ 1.0% of rating (0.05~1.00In)


Current 0.05~4.00In
≤ 0.5% of applied quantities (1.00~4.00In)

≤ 1.0% of rating (0.05~1.00Un)


Voltage 0.05~1.50Un
≤ 0.5% of applied quantities (1.00~1.50Un)

0.05~1.50Un ≤ 2.0% of rating (0.05~1.00In, 0.05~1.00Un)


Active power (W)
0.05~4.00In ≤ 1.0% of applied quantities (1.00~4.00In, 1.00~1.50Un)

0.05~1.50Un ≤ 2.0% of rating (0.05~1.00In, 0.05~1.00Un)


Reactive power (VAr)
0.05~4.00In ≤ 1.0% of applied quantities (1.00~4.00In, 1.00~1.50Un)

0.05~1.50Un ≤ 2.0% of rating (0.05~1.00In, 0.05~1.00Un)


Apparent power (VA)
0.05~4.00In ≤ 1.0% of applied quantities (1.00~4.00In, 1.00~1.50Un)

0.05~1.50Un ≤ 2.0% of rating (0.05~1.00In, 0.05~1.00Un)


Energy (Wh)
0.05~4.00In ≤ 1.0% of applied quantities (1.00~4.00In, 1.00~1.50Un)

0.05~1.50Un ≤ 2.0% of rating (0.05~1.00In, 0.05~1.00Un)


Energy (VAh)
0.05~4.00In ≤ 1.0% of applied quantities (1.00~4.00In, 1.00~1.50Un)

2.10 Management Function

2.10.1 Control Performance

Control mode Local or remote

PCS-9611S Feeder Relay 2-11


Date: 2019-04-24
2 Technical Data

Response time of local control ≤1s

Response time of remote control ≤3s

2.10.2 Clock Performance

Real time clock accuracy ≤1s/day


2 Accuracy of GPS synchronization ≤1ms

External time synchronization IRIG-B (200-98), PPS, IEEE1588 or SNTP protocol

2.10.3 Fault and Disturbance Recording


Settable pre-disturbance, post-disturbance and maximum recorded
Duration & Recording position
duration

Sampling rate Up to 9.6kHz

2.10.4 Binary Input Signal

Resolution of binary input signal ≤1ms

Binary input mode Potential-free contact

2.11 Protective Functions

2.11.1 Phase Overcurrent Protection (50/51P)

Without direction controlled element

Pickup current 1.0×Setting

Current setting accuracy ≤1%×Setting or 0.01In, whichever is greater

Voltage setting accuracy ≤1%×Setting or 0.1V, whichever is greater

Pickup time ≤25ms (at 2 times current setting)

Operating time delay accuracy


≤1%×Setting or 25ms (at 2 times current setting)
(Definite-time characteristics)
Operating time delay accuracy
≤5% of calculated value + 1% current tolerance or 35ms (1.2≤I/Ip≤30)
(Inverse-time characteristics)
Dropout time accuracy (Definite-time
≤1%×Setting or 30ms
characteristics)
Dropout time accuracy (Inverse-time
≤5% of calculated value or 30ms
characteristics)

Dropout ratio 0.95

2-12 PCS-9611S Feeder Relay


Date: 2019-04-24
2 Technical Data

With direction controlled element

Pickup current 1.0×Setting

Current setting accuracy ≤1%×Setting or 0.01In, whichever is greater

Voltage setting accuracy ≤1%×Setting or 0.1V, whichever is greater

Pickup time ≤40ms (at 2 times current setting) 2


Operating time delay accuracy
≤1%×Setting or 40ms (at 2 times current setting)
(Definite-time characteristics)
Operating time delay accuracy
≤5% of calculated value + 1% current tolerance or 35ms (1.2≤I/Ip≤30)
(Inverse-time characteristics)
Dropout time accuracy (Definite-time
≤1%×Setting or 30ms
characteristics)
Dropout time accuracy (Inverse-time
≤5% of calculated value or 30ms
characteristics)

Dropout ratio 0.95

Phase angel accuracy ≤3°

2.11.2 Earth Fault Protection (50/51G)

Without direction controlled element

Pickup current 1.0×Setting

Current setting accuracy ≤1%×Setting or 0.01In, whichever is greater

Pickup time ≤25ms (at 2 times current setting)

Operating time delay accuracy


≤1%×Setting or 25ms (at 2 times current setting)
(Definite-time characteristics)
Operating time delay accuracy
≤5% of calculated value + 1% current tolerance or 35ms (1.2≤I/Ip≤30)
(Inverse-time characteristics)
Dropout time accuracy (Definite-time
≤1%×Setting or 30ms
characteristics)
Dropout time accuracy (Inverse-time
≤5% of calculated value or 30ms
characteristics)

Dropout ratio 0.95

With direction controlled element

Pickup current 1.0×Setting

Current setting accuracy ≤1%×Setting or 0.01In, whichever is greater

Voltage setting accuracy ≤1%×Setting or 0.1V, whichever is greater

PCS-9611S Feeder Relay 2-13


Date: 2019-04-24
2 Technical Data

Pickup time ≤40ms (at 2 times current setting)

Operating time delay accuracy


≤1%×Setting or 40ms (at 2 times current setting)
(Definite-time characteristics)
Operating time delay accuracy
≤5% of calculated value + 1% current tolerance or 35ms (1.2≤I/Ip≤30)
(Inverse-time characteristics)
Dropout time accuracy (Definite-time
2 characteristics)
≤1%×Setting or 30ms

Dropout time accuracy (Inverse-time


≤5% of calculated value or 30ms
characteristics)

Dropout ratio 0.95

Phase angel accuracy ≤3°

2.11.3 Another Group of Earth Fault Overcurrent Protection

Pickup current 1.0×Setting

Current setting accuracy ≤1%×Setting or 0.01In, whichever is greater

Pickup time ≤25ms (at 2 times current setting)

Operating time delay accuracy


≤1%×Setting or 25ms (at 2 times current setting)
(Definite-time characteristics)
Operating time delay accuracy
≤5% of calculated value + 1% current tolerance or 35ms (1.2≤I/Ip≤30)
(Inverse-time characteristics)
Dropout time accuracy (Definite-time
≤1%×Setting or 30ms
characteristics)
Dropout time accuracy (Inverse-time
≤5% of calculated value or 30ms
characteristics)

Dropout ratio 0.95

2.11.4 Negative-sequence Overcurrent Protection (50/51Q)

Without direction controlled element

Pickup current 1.0×Setting

Current setting accuracy ≤1%×Setting or 0.01In, whichever is greater

Pickup time ≤25ms (at 2 times current setting)

Operating time delay accuracy


≤1%×Setting or 25ms (at 2 times current setting)
(Definite-time characteristics)
Operating time delay accuracy
≤5% of calculated value + 1% current tolerance or 35ms (1.2≤I/Ip≤30)
(Inverse-time characteristics)
Dropout time accuracy (Definite-time
≤1%×Setting or 30ms
characteristics)
Dropout time accuracy (Inverse-time ≤5% of calculated value or 30ms

2-14 PCS-9611S Feeder Relay


Date: 2019-04-24
2 Technical Data

characteristics)

Dropout ratio 0.95

With direction controlled element

Pickup current 1.0×Setting

Current setting accuracy ≤1%×Setting or 0.01In, whichever is greater


2
Voltage setting accuracy ≤1%×Setting or 0.1V, whichever is greater

Pickup time ≤40ms (at 2 times current setting)

Operating time delay accuracy


≤1%×Setting or 40ms (at 2 times current setting)
(Definite-time characteristics)
Operating time delay accuracy
≤5% of calculated value + 1% current tolerance or 35ms (1.2≤I/Ip≤30)
(Inverse-time characteristics)
Dropout time accuracy (Definite-time
≤1%×Setting or 30ms
characteristics)
Dropout time accuracy (Inverse-time
≤5% of calculated value or 30ms
characteristics)

Dropout ratio 0.95

Phase angel accuracy ≤3°

2.11.5 Sensitive Earth Fault Protection (50/51SEF)

Without direction controlled element

Pickup current 1.0×Setting

Current setting accuracy ≤0.5%×Setting or 1mA, whichever is greater

Pickup time ≤25ms (at 2 times current setting)

Operating time delay accuracy


≤1%×Setting or 25ms (at 2 times current setting)
(Definite-time characteristics)

Operating time delay accuracy ≤5% of calculated value + 0.5% current tolerance or 35ms

(Inverse-time characteristics) (1.2≤I/Ip≤30)

Dropout time accuracy (Definite-time


≤1%×Setting or 30ms
characteristics)
Dropout time accuracy (Inverse-time
≤5% of calculated value or 30ms
characteristics)

Dropout ratio 0.95

PCS-9611S Feeder Relay 2-15


Date: 2019-04-24
2 Technical Data

With direction controlled element

Pickup current 1.0×Setting

Current setting accuracy ≤0.5%×Setting or 1mA, whichever is greater

Voltage setting accuracy ≤1%×Setting or 0.1V, whichever is greater

2 Pickup time ≤40ms (at 2 times current setting)

Operating time delay accuracy


≤1%×Setting or 40ms (at 2 times current setting)
(Definite-time characteristics)

Operating time delay accuracy ≤5% of calculated value + 0.5% current tolerance or 35ms

(Inverse-time characteristics) (1.2≤I/Ip≤30)

Dropout time accuracy (Definite-time


≤1%×Setting or 30ms
characteristics)
Dropout time accuracy (Inverse-time
≤5% of calculated value or 30ms
characteristics)

Dropout ratio 0.95

Phase angel accuracy ≤3°

2.11.6 RMS Overcurrent Protection (50/51R)

Pickup current 1.0×Setting

Current setting accuracy ≤1%×Setting or 0.01In, whichever is greater

Pickup time ≤25ms (at 2 times current setting)

Operating time delay accuracy ≤1%×Setting or 25ms (at 2 times current setting)

Dropout time accuracy ≤1%×Setting or 30ms

Dropout ratio 0.95

2.11.7 Phase Overvoltage Protection (59P)

Pickup voltage 1.0×Setting

Voltage setting accuracy ≤1%×Setting or 0.1V, whichever is greater

Pickup time ≤35ms (at 1.1 times voltage setting)

Operating time delay accuracy


≤1%×Setting or 35ms (at 1.1 times voltage setting)
(Definite-time characteristics)
Operating time accuracy
≤5% of calculated value + 1% voltage tolerance or 40ms (1.1≤U/Up≤2)
(Inverse-time characteristics)

Dropout time accuracy ≤1%×Setting or 30ms

Dropout ratio Settable 0.93~1.00, default value: 0.98

2-16 PCS-9611S Feeder Relay


Date: 2019-04-24
2 Technical Data

2.11.8 Residual Overvoltage Protection (59G)

Pickup voltage 1.0×Setting

Voltage setting accuracy ≤1%×Setting or 0.1V, whichever is greater

Pickup time ≤35ms (at 1.1 times voltage setting)

Operating time delay accuracy ≤1%×Setting or 40ms (at 1.1 times voltage setting) 2
Dropout time accuracy ≤30ms

Dropout ratio Settable 0.93~1.00, default value: 0.98

2.11.9 Negative-sequence Overvoltage Protection (59Q)

Pickup voltage 1.0×Setting

Voltage setting accuracy ≤1%×Setting or 0.1V, whichever is greater

Pickup time ≤35ms (at 1.1 times voltage setting)

Operating time delay accuracy ≤1%×Setting or 40ms (at 1.1 times voltage setting)

Dropout time accuracy ≤30ms

Dropout ratio Settable 0.93~1.00, default value: 0.98

2.11.10 Positive-sequence Overvoltage Protection (59Pos)

Pickup voltage 1.0×Setting

Voltage setting accuracy ≤1%×Setting or 0.1V, whichever is greater

Pickup time ≤35ms (at 1.1 times voltage setting)

Operating time delay accuracy ≤1%×Setting or 40ms (at 1.1 times voltage setting)

Dropout time accuracy ≤30ms

Dropout ratio Settable 0.93~1.00, default value: 0.98

2.11.11 Phase Undervoltage Protection (27P)

Pickup voltage 1.0×Setting

Voltage setting accuracy ≤1%×Setting or 0.1V, whichever is greater

Pickup time ≤35ms (at 0.9 times voltage setting)

Operating time delay accuracy


≤1%×Setting or 35ms (at 0.9 times voltage setting)
(Definite-time characteristics)
Dropout time accuracy (Inverse-time
≤5% of calculated value + 1% voltage tolerance or 50ms (U/Up≤0.9)
characteristics)

PCS-9611S Feeder Relay 2-17


Date: 2019-04-24
2 Technical Data

Dropout time accuracy ≤1%×Setting or 30ms

Dropout ratio Settable 1.00~1.20, default value: 1.03

2.11.12 Overfrequency Protection (81O)

Pickup frequency 1.0×Setting


2 Frequency setting accuracy ≤ 0.01Hz

Pickup time ≤70ms

Time delay accuracy ≤1%×Setting+70ms

Dropout time accuracy ≤40ms

Dropout frequency 1.0×Setting

2.11.13 Underfrequency Protection (81U)

Pickup frequency 1.0×Setting

Frequency setting accuracy ≤ 0.01Hz

Pickup time ≤70ms

Time delay accuracy ≤1%×Setting+70ms

Dropout time accuracy ≤40ms

Dropout frequency 1.0×Setting

2.11.14 Frequency Rate-of-change Protection (81R)

Pickup frequency 1.0×Setting

Frequency rate-of-change setting


≤ 0.02Hz
accuracy

Pickup time ≤70ms

Time delay accuracy ≤1%×Setting+70ms

Dropout time accuracy ≤40ms

Dropout frequency 1.0×Setting

2.11.15 Reverse Power Protection (32R)

Pickup power 1.0×Setting

Power setting accuracy ≤2%×Setting or 0.01pu, whichever is greater

Current setting accuracy ≤1%×Setting or 0.01pu, whichever is greater

2-18 PCS-9611S Feeder Relay


Date: 2019-04-24
2 Technical Data

Voltage setting accuracy ≤1%×Setting or 0.1V, whichever is greater

Pickup time ≤25ms (at 2 times power setting)

Operating time delay accuracy ≤1%×Setting or 25ms (at 2 times voltage setting)

Dropout time accuracy ≤30ms

Dropout ratio 0.95 2


2.11.16 Undercurrent Protection (37)

Pickup current 1.0×Setting

Current setting Accuracy ≤1%×Setting or 0.01In, whichever is greater

Pickup time ≤25ms (at 0.5 times current setting)

Operating time delay accuracy ≤1%×Setting or 25ms (at 0.5 times current setting)

Drop-out time accuracy ≤30ms

Dropout ratio 1.1

2.11.17 Breaker Failure Protection (50BF)

Pickup current 1.0×Setting

Current setting Accuracy ≤1%×Setting or 0.01In, whichever is greater

Operating time delay accuracy ≤1%×Setting or 10ms (at 2 times current setting)

Pickup time ≤20ms

Dropout time <20ms

Dropout ratio 1

2.11.18 Unbalance Current Protection (60/50)

Pickup current 1.0×Setting

Current setting accuracy ≤1%×Setting or 0.01In, whichever is greater

Pickup time ≤25ms (at 2 times current setting)

Operating time delay accuracy ≤1%×Setting or 25ms (at 2 times current setting)

Dropout time accuracy ≤30ms

Dropout ratio 0.95

PCS-9611S Feeder Relay 2-19


Date: 2019-04-24
2 Technical Data

2.11.19 Unbalance Voltage Protection (60/59)

Pickup current 1.0×Setting

Voltage setting accuracy ≤1%×Setting or 0.1V, whichever is greater

Pickup time ≤35ms (at 1.1 times voltage setting)

2 Operating time delay accuracy ≤1%×Setting or 35ms (at 1.1 times voltage setting)

Dropout time accuracy ≤30ms

Dropout ratio 0.95

2.11.20 Auto-reclosing (79)


Phase angel accuracy (synchronism
≤2°
check)
Voltage setting accuracy
≤1%×Setting or 0.1V, whichever is greater
(synchronism check)
Frequency setting accuracy
0.01Hz
(synchronism check)
Time delay accuracy (synchronism
≤1%×Setting+20ms
check)

Time delay accuracy (Reclaim) ≤1%×Setting+20ms

Time delay accuracy (Reclosing) ≤1%×Setting+20ms

2.11.21 Transient Overreach

Accuracy for all high-speed protection ≤2%

2.11.22 Fault Locator


Accuracy for multi-phase faults with < ±2.5%
single end feed

Tolerance will be higher in case of single-phase fault with high ground resistance.

2-20 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

3 Protection Functions

Table of Contents

3.1 Three-phase Current Element (TCUR3P) ....................................................... 3-1


3.1.1 Function Description............................................................................................................. 3-1

3.1.2 Function Block Diagram ....................................................................................................... 3-2

3.1.3 I/O Signals ............................................................................................................................ 3-2 3


3.1.4 Settings ................................................................................................................................. 3-3

3.2 Three-phase Voltage Element (TVOL3P)........................................................ 3-3


3.2.1 Function Description............................................................................................................. 3-3

3.2.2 Function Block Diagram ....................................................................................................... 3-4

3.2.3 I/O Signals ............................................................................................................................ 3-4

3.2.4 Settings ................................................................................................................................. 3-5

3.3 One-phase Current Element (TCUR1P).......................................................... 3-5


3.3.1 Function Description............................................................................................................. 3-5

3.3.2 Function Block Diagram ....................................................................................................... 3-5

3.3.3 I/O Signals ............................................................................................................................ 3-6

3.3.4 Settings ................................................................................................................................. 3-6

3.4 One-phase Voltage Element (TVOL1P) .......................................................... 3-6


3.4.1 Function Description............................................................................................................. 3-6

3.4.2 Function Block Diagram ....................................................................................................... 3-7

3.4.3 I/O Signals ............................................................................................................................ 3-7

3.4.4 Settings ................................................................................................................................. 3-7

3.5 Phase Overcurrent Protection (50/51P) ......................................................... 3-7


3.5.1 Function Description............................................................................................................. 3-8

3.5.2 Function Block Diagram ..................................................................................................... 3-19

3.5.3 I/O Signal ............................................................................................................................ 3-20

3.5.4 Logic ................................................................................................................................... 3-21

3.5.5 Settings ............................................................................................................................... 3-21

PCS-9611S Feeder Relay 3-a


Date: 2019-04-24
3 Protection Functions

3.6 Earth Fault Overcurrent Protection (50/51G) ............................................... 3-37


3.6.1 Function Description........................................................................................................... 3-37

3.6.2 Function Block Diagram ..................................................................................................... 3-46

3.6.3 I/O Signal ............................................................................................................................ 3-46

3.6.4 Logic ................................................................................................................................... 3-47

3.6.5 Settings ............................................................................................................................... 3-47

3.7 Another Group of Earth Fault Overcurrent Protection ............................... 3-63


3 3.7.1 Function Description........................................................................................................... 3-63

3.7.2 Function Block Diagram ..................................................................................................... 3-69

3.7.3 I/O Signal ............................................................................................................................ 3-69

3.7.4 Logic ................................................................................................................................... 3-70

3.7.5 Settings ............................................................................................................................... 3-70

3.8 Negative-sequence Overcurrent Protection (50/51Q) ................................. 3-82


3.8.1 Function Description........................................................................................................... 3-82

3.8.2 Function Block Diagram ..................................................................................................... 3-91

3.8.3 I/O Signal ............................................................................................................................ 3-91

3.8.4 Logic ................................................................................................................................... 3-92

3.8.5 Settings ............................................................................................................................... 3-92

3.9 Sensitive Earth Fault Protection (50/51SEF) ............................................... 3-97


3.9.1 Function Description........................................................................................................... 3-97

3.9.2 Function Block Diagram ................................................................................................... 3-106

3.9.3 I/O Signal .......................................................................................................................... 3-106

3.9.4 Logic ................................................................................................................................. 3-107

3.9.5 Settings ............................................................................................................................. 3-107

3.10 RMS Overcurrent Protection (50/51R).......................................................3-118


3.10.1 Function Description....................................................................................................... 3-118

3.10.2 Function Block Diagram ................................................................................................. 3-121

3.10.3 I/O Signal ........................................................................................................................ 3-122

3.10.4 Logic ............................................................................................................................... 3-122

3.10.5 Settings ........................................................................................................................... 3-122

3-b PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

3.11 Phase Overvoltage Protection (59P) ........................................................ 3-123


3.11.1 Function Description ....................................................................................................... 3-123

3.11.2 Function Block Diagram ................................................................................................. 3-129

3.11.3 I/O Signal ........................................................................................................................ 3-129

3.11.4 Logic ............................................................................................................................... 3-130

3.11.5 Settings ........................................................................................................................... 3-130

3.12 Residual Overvoltage Protection (59G) ................................................... 3-134


3.12.1 Function Description....................................................................................................... 3-134 3
3.12.2 Function Block Diagram ................................................................................................. 3-136

3.12.3 I/O Signal ........................................................................................................................ 3-137

3.12.4 Logic ............................................................................................................................... 3-137

3.12.5 Settings ........................................................................................................................... 3-137

3.13 Negative-sequence Overvoltage Protection (59Q) .................................. 3-138


3.13.1 Function Description....................................................................................................... 3-139

3.13.2 Function Block Diagram ................................................................................................. 3-141

3.13.3 I/O Signals ...................................................................................................................... 3-141

3.13.4 Logic ............................................................................................................................... 3-142

3.13.5 Settings ........................................................................................................................... 3-142

3.14 Positive-sequence Overvoltage Protection (59Pos) ............................... 3-143


3.14.1 Function Description....................................................................................................... 3-143

3.14.2 Function Block Diagram ................................................................................................. 3-146

3.14.3 I/O Signals ...................................................................................................................... 3-146

3.14.4 Logic ............................................................................................................................... 3-146

3.14.5 Settings ........................................................................................................................... 3-146

3.15 Phase Undervoltage Protection (27P) ...................................................... 3-147


3.15.1 Function Description....................................................................................................... 3-147

3.15.2 Function Block Diagram ................................................................................................. 3-153

3.15.3 I/O Signal ........................................................................................................................ 3-154

3.15.4 Logic ............................................................................................................................... 3-155

3.15.5 Settings ........................................................................................................................... 3-156

PCS-9611S Feeder Relay 3-c


Date: 2019-04-24
3 Protection Functions

3.16 Overfrequency Protection (81O)............................................................... 3-160


3.16.1 Function Description....................................................................................................... 3-160

3.16.2 Function Block Diagram ................................................................................................. 3-162

3.16.3 I/O Signals ...................................................................................................................... 3-162

3.16.4 Logic ............................................................................................................................... 3-163

3.16.5 Settings ........................................................................................................................... 3-163

3.17 Underfrequency Protection (81U)............................................................. 3-164


3 3.17.1 Function Description....................................................................................................... 3-164

3.17.2 Function Block Diagram ................................................................................................. 3-166

3.17.3 I/O Signals ...................................................................................................................... 3-166

3.17.4 Logic ............................................................................................................................... 3-167

3.17.5 Settings ........................................................................................................................... 3-167

3.18 Frequency Rate-of-change Protection (81R) ........................................... 3-168


3.18.1 Function Description....................................................................................................... 3-168

3.18.2 Function Block Diagram ................................................................................................. 3-170

3.18.3 I/O Signals ...................................................................................................................... 3-170

3.18.4 Logic ............................................................................................................................... 3-171

3.18.5 Settings ........................................................................................................................... 3-171

3.19 Reverse Power Protection (32R) .............................................................. 3-172


3.19.1 Function Description....................................................................................................... 3-172

3.19.2 Function Block Diagram ................................................................................................. 3-175

3.19.3 I/O Signals ...................................................................................................................... 3-175

3.19.4 Logic ............................................................................................................................... 3-176

3.19.5 Settings ........................................................................................................................... 3-176

3.20 Cold Load Pickup Logic (CLP) ................................................................. 3-177


3.20.1 Function Description....................................................................................................... 3-177

3.20.2 Function Block Diagram ................................................................................................. 3-177

3.20.3 I/O Signals ...................................................................................................................... 3-177

3.20.4 Logic ............................................................................................................................... 3-178

3.20.5 Settings ........................................................................................................................... 3-178

3-d PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

3.21 Undercurrent Protection (37) .................................................................... 3-181


3.21.1 Function Description....................................................................................................... 3-182

3.21.2 Function Block Diagram ................................................................................................. 3-184

3.21.3 I/O Signals ...................................................................................................................... 3-185

3.21.4 Logic ............................................................................................................................... 3-186

3.21.5 Settings........................................................................................................................... 3-186

3.22 Breaker Failure Protection (50BF) ............................................................ 3-187


3.22.1 Function Description....................................................................................................... 3-187 3
3.22.2 Function Block Diagram ................................................................................................. 3-189

3.22.3 I/O Signals ...................................................................................................................... 3-189

3.22.4 Logic ............................................................................................................................... 3-190

3.22.5 Settings ........................................................................................................................... 3-191

3.23 Switch-on-to-Fault Protection (SOTF) ...................................................... 3-192


3.23.1 Function Description....................................................................................................... 3-192

3.23.2 Function Block Diagram ................................................................................................. 3-193

3.23.3 I/O Signals ...................................................................................................................... 3-193

3.23.4 Logic ............................................................................................................................... 3-194

3.23.5 Settings ........................................................................................................................... 3-196

3.24 Unbalance Current Protection (60/50) ...................................................... 3-197


3.24.1 Function Description....................................................................................................... 3-198

3.24.2 Function Block Diagram ................................................................................................. 3-200

3.24.3 I/O Signals ...................................................................................................................... 3-200

3.24.4 Logic ............................................................................................................................... 3-200

3.24.5 Settings ........................................................................................................................... 3-200

3.25 Unbalance Voltage Protection (60/59) ...................................................... 3-201


3.25.1 Function Description....................................................................................................... 3-202

3.25.2 Function Block Diagram ................................................................................................. 3-204

3.25.3 I/O Signals ...................................................................................................................... 3-204

3.25.4 Logic ............................................................................................................................... 3-204

3.25.5 Settings ........................................................................................................................... 3-204

PCS-9611S Feeder Relay 3-e


Date: 2019-04-24
3 Protection Functions

3.26 Automatic Reclosure (79).......................................................................... 3-205


3.26.1 Function Description....................................................................................................... 3-205

3.26.2 Function Block Diagram ................................................................................................. 3-214

3.26.3 I/O Signals ...................................................................................................................... 3-214

3.26.4 Settings ........................................................................................................................... 3-215

3.27 VT Circuit Supervision (VTS) .................................................................... 3-216


3.27.1 General Application ........................................................................................................ 3-216

3 3.27.2 Function Description....................................................................................................... 3-217

3.27.3 Function Block ................................................................................................................ 3-217

3.27.4 I/O Signals ...................................................................................................................... 3-217

3.27.5 Logic ............................................................................................................................... 3-218

3.27.6 Settings ........................................................................................................................... 3-218

3.28 CT Circuit Supervision (CTS).................................................................... 3-219


3.28.1 Function Description....................................................................................................... 3-219

3.28.2 Function Block Diagram ................................................................................................. 3-219

3.28.3 I/O Signals ...................................................................................................................... 3-219

3.28.4 Logics ............................................................................................................................. 3-220

3.28.5 Settings ........................................................................................................................... 3-220

List of Figures

Figure 3.5-1 The enabling and blocking logic of phase overcurrent protection .................. 3-8

Figure 3.5-2 Logic diagram of the fault detector element of phase overcurrent protection3-8

Figure 3.5-3 Logic diagram of the voltage control element of phase overcurrent protection3-9

Figure 3.5-4 The direction element operation characteristics when phase A voltage is
polarized ..................................................................................................................................... 3-10

Figure 3.5-5 Logic diagram of forward and reverse direction element of phase overcurrent
protection ................................................................................................................................... 3-12

Figure 3.5-6 Logic diagram of harmonic control element of phase overcurrent protection3-13

Figure 3.5-7 Definite-time operation characteristic curve of phase overcurrent protection3-15

Figure 3.5-8 Inverse-time operation characteristic curve of phase overcurrent protection3-16

3-f PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Figure 3.5-9 Definite-time dropout characteristic of phase overcurrent protection .......... 3-17

Figure 3.5-10 Inverse-time dropout characteristic curve of phase overcurrent protection3-18

Figure 3.5-11 Inverse-time dropout characteristic of phase overcurrent protection......... 3-19

Figure 3.5-12 Logic diagram of phase overcurrent protection ............................................ 3-21

Figure 3.6-1 The enabling and blocking logic of earth fault overcurrent protection ......... 3-38

Figure 3.6-2 Logic diagram of the fault detector element of earth fault overcurrent
protection ................................................................................................................................... 3-38

Figure 3.6-3 The direction element operation characteristics when zero-sequence voltage
is polarized ................................................................................................................................. 3-39
3
Figure 3.6-4 Logic diagram of forward and reverse direction element of earth fault
overcurrent protection .............................................................................................................. 3-40

Figure 3.6-5 Logic diagram of harmonic control element of earth fault overcurrent
protection ................................................................................................................................... 3-41

Figure 3.6-6 Definite-time operation characteristic curve of earth fault overcurrent


protection ................................................................................................................................... 3-42

Figure 3.6-7 Inverse-time operation characteristic curve of earth fault overcurrent


protection ................................................................................................................................... 3-43

Figure 3.6-8 Definite-time dropout characteristic of earth fault overcurrent protection ... 3-44

Figure 3.6-9 Inverse-time dropout characteristic curve of earth fault overcurrent protection3-45

Figure 3.6-10 Inverse-time dropout characteristic of earth fault overcurrent protection . 3-46

Figure 3.6-11 Logic diagram of earth fault overcurrent protection...................................... 3-47

Figure 3.7-1 The enabling and blocking logic of another group of earth fault overcurrent
protection ................................................................................................................................... 3-63

Figure 3.7-2 Logic diagram of the fault detector element of another group of earth fault
overcurrent protection .............................................................................................................. 3-64

Figure 3.7-3 Definite-time operation characteristic curve of another group of earth fault
overcurrent protection .............................................................................................................. 3-65

Figure 3.7-4 Inverse-time operation characteristic curve of another group of earth fault
overcurrent protection .............................................................................................................. 3-66

Figure 3.7-5 Definite-time dropout characteristic of another group of earth fault overcurrent
protection ................................................................................................................................... 3-67

Figure 3.7-6 Inverse-time dropout characteristic curve of another group of earth fault
overcurrent protection .............................................................................................................. 3-68

Figure 3.7-7 Inverse-time dropout characteristic of another group of earth fault overcurrent

PCS-9611S Feeder Relay 3-g


Date: 2019-04-24
3 Protection Functions

protection ................................................................................................................................... 3-69

Figure 3.7-8 Logic diagram of another group of earth fault overcurrent protection ......... 3-70

Figure 3.8-1 The enabling and blocking logic of negative-sequence overcurrent protection3-83

Figure 3.8-2 Logic diagram of the fault detector element of negative-sequence overcurrent
protection ................................................................................................................................... 3-83

Figure 3.8-3 The direction element operation characteristics of negative-sequence


overcurrent protection .............................................................................................................. 3-84

Figure 3.8-4 Logic diagram of forward and reverse direction element of negative-sequence
3 overcurrent protection .............................................................................................................. 3-85

Figure 3.8-5 Definite-time operation characteristic curve of negative-sequence overcurrent


protection ................................................................................................................................... 3-86

Figure 3.8-6 Inverse-time operation characteristic curve of negative-sequence overcurrent


protection ................................................................................................................................... 3-87

Figure 3.8-7 Definite-time dropout characteristic of negative-sequence overcurrent


protection ................................................................................................................................... 3-89

Figure 3.8-8 Inverse-time dropout characteristic curve of negative-sequence overcurrent


protection ................................................................................................................................... 3-90

Figure 3.8-9 Inverse-time dropout characteristic of negative-sequence overcurrent


protection ................................................................................................................................... 3-91

Figure 3.8-10 Logic diagram of negative-sequence overcurrent protection ...................... 3-92

Figure 3.9-1 The enabling and blocking logic of sensitive earth fault protection ............. 3-98

Figure 3.9-2 Logic diagram of the fault detector element of sensitive earth fault protection3-98

Figure 3.9-3 The direction element operation characteristics of sensitive earth fault
protection ................................................................................................................................... 3-99

Figure 3.9-4 Logic diagram of forward and reverse direction element of sensitive earth fault
protection ................................................................................................................................. 3-100

Figure 3.9-5 Definite-time operation characteristic curve of sensitive earth fault protection3-102

Figure 3.9-6 Inverse-time operation characteristic curve of sensitive earth fault protection3-103

Figure 3.9-7 Definite-time dropout characteristic of sensitive earth fault protection ..... 3-104

Figure 3.9-8 Inverse-time dropout characteristic curve of sensitive earth fault protection3-105

Figure 3.9-9 Inverse-time dropout characteristic of sensitive earth fault protection ...... 3-106

Figure 3.9-10 Logic diagram of sensitive earth fault protection ........................................ 3-107

Figure 3.10-1 The enabling and blocking logic of RMS overcurrent protection .............. 3-119

3-h PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Figure 3.10-2 Logic diagram of the fault detector element of RMS overcurrent protection3-119

Figure 3.10-3 Definite-time operation characteristic curve of RMS overcurrent protection3-120

Figure 3.10-4 Definite-time dropout characteristic of RMS overcurrent protection ........ 3-121

Figure 3.10-5 Logic diagram of RMS overcurrent protection ............................................. 3-122

Figure 3.11-1 The enabling and blocking logic of phase overvoltage protection ............ 3-124

Figure 3.11-2 Logic diagram of the fault detector element of phase overvoltage protection3-125

Figure 3.11-3 Definite-time operation characteristic curve of phase overvoltage protection3-126

Figure 3.11-4 Inverse-time operation characteristic curve of phase overvoltage protection3-127 3


Figure 3.11-5 Definite-time dropout characteristic of phase overvoltage protection ...... 3-128

Figure 3.11-6 Logic diagram of phase overvoltage protection .......................................... 3-130

Figure 3.12-1 The enabling and blocking logic of residual overvoltage protection ........ 3-134

Figure 3.12-2 Logic diagram of the fault detector element of residual overvoltage
protection ................................................................................................................................. 3-135

Figure 3.12-3 Definite-time operation characteristic curve of residual overvoltage


protection ................................................................................................................................. 3-135

Figure 3.12-4 Definite-time dropout characteristic of residual overvoltage protection .. 3-136

Figure 3.12-5 Logic diagram of residual overvoltage protection ....................................... 3-137

Figure 3.13-1 Logic diagram of enabling/disabling negative-sequence overvoltage


protection ................................................................................................................................. 3-139

Figure 3.13-2 Logic diagram of the fault detector of negative-sequence overvoltage


protection ................................................................................................................................. 3-139

Figure 3.13-3 Operation characteristic curve of negative-sequence overvoltage protection3-140

Figure 3.13-4 Definite-time dropout characteristic of negative-sequence overvoltage


protection ................................................................................................................................. 3-141

Figure 3.13-5 Logic diagram of negative-sequence overvoltage protection .................... 3-142

Figure 3.14-1 Logic diagram of enabling/disabling positive-sequence overvoltage


protection ................................................................................................................................. 3-143

Figure 3.14-2 Logic diagram of the fault detector of positive-sequence overvoltage


protection ................................................................................................................................. 3-144

Figure 3.14-3 Operation characteristic curve of positive-sequence overvoltage protection3-144

Figure 3.14-4 Definite-time dropout characteristic of positive-sequence overvoltage


protection ................................................................................................................................. 3-145

PCS-9611S Feeder Relay 3-i


Date: 2019-04-24
3 Protection Functions

Figure 3.14-5 Logic diagram of positive-sequence overvoltage protection ..................... 3-146

Figure 3.15-1 The enabling and blocking logic of phase undervoltage protection ......... 3-148

Figure 3.15-2 Logic diagram of the fault detector element of phase undervoltage protection
................................................................................................................................................... 3-150

Figure 3.15-3 Definite-time operation characteristic curve of phase undervoltage protection


................................................................................................................................................... 3-151

Figure 3.15-4 Inverse-time operation characteristic curve of phase undervoltage protection


................................................................................................................................................... 3-152

3 Figure 3.15-5 Definite-time dropout characteristic of undervoltage protection ............... 3-153

Figure 3.15-6 Logic diagram of phase undervoltage protection ........................................ 3-155

Figure 3.16-1 Logic diagram of enabling/disabling overfrequency protection ................ 3-161

Figure 3.16-2 Logic diagram of the fault detector of overfrequency protection .............. 3-161

Figure 3.16-3 Operation characteristic curve of overfrequency protection ..................... 3-162

Figure 3.16-4 Function block diagram of overfrequency protection ................................. 3-162

Figure 3.16-5 Logic diagram of overfrequency protection ................................................. 3-163

Figure 3.17-1 Logic diagram of enabling/disabling underfrequency protection .............. 3-165

Figure 3.17-2 Logic diagram of the fault detector of underfrequency protection ............ 3-165

Figure 3.17-3 Operation characteristic curve of underfrequency protection ................... 3-166

Figure 3.17-4 Function block diagram of underfrequency protection............................... 3-166

Figure 3.17-5 Logic diagram of underfrequency protection ............................................... 3-167

Figure 3.18-1 Logic diagram of enabling/disabling frequency rate-of-change protection3-169

Figure 3.18-2 Logic diagram of the fault detector of frequency rate-of-change protection3-169

Figure 3.18-3 Operation characteristic curve of frequency rate-of-change protection ... 3-170

Figure 3.18-4 Function block diagram of frequency rate-of-change protection .............. 3-170

Figure 3.18-5 Logic diagram of frequency rate-of-change protection............................... 3-171

Figure 3.19-1 Logic diagram of enabling/disabling reverse power protection ................ 3-173

Figure 3.19-2 Logic diagram of the fault detector of reverse power protection .............. 3-173

Figure 3.19-3 Operation characteristic curve of reverse power protection ...................... 3-174

Figure 3.19-4 Function block diagram of reverse power protection ................................. 3-175

Figure 3.19-5 Logic diagram of reverse power protection.................................................. 3-176

Figure 3.20-1 Function block diagram of cold load pickup logic....................................... 3-177

3-j PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Figure 3.20-2 Logic diagram of cold load pickup logic ....................................................... 3-178

Figure 3.21-1 Logic diagram of enabling/disabling undercurrent protection................... 3-182

Figure 3.21-2 Logic diagram of the fault detector of undercurrent protection ................ 3-183

Figure 3.21-3 Operation characteristic curve of undercurrent protection ........................ 3-184

Figure 3.21-4 Function block diagram of undercurrent protection ................................... 3-184

Figure 3.21-5 Logic diagram of undercurrent protection.................................................... 3-186

Figure 3.22-1 Logic of enabling breaker failure protection ................................................ 3-190

Figure 3.22-2 Logic of breaker failure initiating signal abnormality .................................. 3-190 3
Figure 3.22-3 Logic of breaker failure protection ................................................................ 3-190

Figure 3.23-1 The enabling and blocking logic of SOTF protection .................................. 3-192

Figure 3.10-3 Logic of auto-reclosing signal........................................................................ 3-194

Figure 3.10-2 Logic of manual closing signal ...................................................................... 3-194

Figure 3.23-2 Logic of phase overcurrent SOTF protection ............................................... 3-195

Figure 3.23-3 Logic of earth fault overcurrent SOTF protection ........................................ 3-196

Figure 3.24-1 Application of the unbalance current protection ......................................... 3-198

Figure 3.24-2 Logic diagram of enabling/disabling unbalance current protection.......... 3-198

Figure 3.24-3 Logic diagram of the fault detector of unbalance current protection........ 3-199

Figure 3.24-4 Operation characteristic curve of unbalance current protection ............... 3-199

Figure 3.24-5 Function block diagram of unbalance current protection .......................... 3-200

Figure 3.24-6 Logic diagram of unbalance current protection........................................... 3-200

Figure 3.25-1 Application of the unbalance voltage protection ......................................... 3-202

Figure 3.25-2 Logic diagram of enabling/disabling unbalance voltage protection ......... 3-202

Figure 3.25-3 Logic diagram of the fault detector of unbalance voltage protection ....... 3-203

Figure 3.25-4 Operation characteristic curve of unbalance voltage protection ............... 3-203

Figure 3.25-5 Function block diagram of unbalance voltage protection .......................... 3-204

Figure 3.25-6 Logic diagram of unbalance voltage protection .......................................... 3-204

Figure 3.26-1 Logic of enabling AR ....................................................................................... 3-206

Figure 3.26-2 Logic of AR block ............................................................................................. 3-207

Figure 3.26-3 Logic of AR ready ............................................................................................ 3-208

Figure 3.26-4 Tripping initiating AR ....................................................................................... 3-208

PCS-9611S Feeder Relay 3-k


Date: 2019-04-24
3 Protection Functions

Figure 3.26-5 CB state initiating AR ...................................................................................... 3-209

Figure 3.26-6 One-shot AR ..................................................................................................... 3-209

Figure 3.26-7 Reclosing output logic .................................................................................... 3-210

Figure 3.26-8 Reclosing failure and success ....................................................................... 3-211

Figure 3.26-9 Transient fault................................................................................................... 3-212

Figure 3.26-10 Permanent fault ([79.Num]=2) ....................................................................... 3-213

Figure 3.27-1 VT circuit supervision logic diagram ............................................................. 3-218

3 Figure 3.28-1 Logic of CT circuit failure................................................................................ 3-220

List of Tables

Table 3.1-1 Input/Output signals of three-phase current element ......................................... 3-2

Table 3.1-2 Settings of three-phase current element............................................................... 3-3

Table 3.2-1 Input/Output signals of three-phase voltage element ......................................... 3-4

Table 3.2-2 Settings of three-phase voltage element .............................................................. 3-5

Table 3.3-1 Input/Output signals of one-phase current element ............................................ 3-6

Table 3.3-2 Settings of one-phase current element ................................................................. 3-6

Table 3.4-1 Input/Output signals of one-phase voltage element ............................................ 3-7

Table 3.4-2 Settings of one-phase voltage element ................................................................. 3-7

Table 3.5-1 Input/output signals of phase overcurrent protection ...................................... 3-20

Table 3.5-2 Settings of phase overcurrent protection ........................................................... 3-21

Table 3.6-1 Input/output signals of earth fault overcurrent protection ............................... 3-46

Table 3.6-2 Settings of earth fault overcurrent protection .................................................... 3-47

Table 3.7-1 Input/output signals of another group of earth fault overcurrent protection . 3-69

Table 3.7-2 Settings of another group of earth fault overcurrent protection ...................... 3-70

Table 3.8-1 Input/output signals of negative-sequence overcurrent protection ................ 3-91

Table 3.8-2 Settings of negative-sequence overcurrent protection..................................... 3-92

Table 3.9-1 Input/output signals of sensitive earth fault protection .................................. 3-106

Table 3.9-2 Settings of sensitive earth fault protection ...................................................... 3-107

Table 3.10-1 Input/output signals of RMS overcurrent protection ..................................... 3-122

Table 3.10-2 Settings of RMS overcurrent protection ......................................................... 3-122

3-l PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Table 3.11-1 Input/output signals of phase overvoltage protection .................................. 3-129

Table 3.11-2 Settings of phase overvoltage protection ....................................................... 3-131

Table 3.12-1 Input/output signals of residual overvoltage protection ............................... 3-137

Table 3.12-2 Settings of residual overvoltage protection ................................................... 3-137

Table 3.13-1 Input/output signals of negative-sequence overvoltage protection ............ 3-141

Table 3.13-2 Settings of negative-sequence overvoltage protection ................................ 3-142

Table 3.14-1 Input/output signals of positive-sequence overvoltage protection ............. 3-146

Table 3.14-2 Settings of positive-sequence overvoltage protection ................................. 3-147 3


Table 3.15-1 Input/output signals of phase undervoltage protection ................................ 3-154

Table 3.15-2 Settings of phase undervoltage protection .................................................... 3-156

Table 3.16-1 Input/output signals of overfrequency protection ......................................... 3-162

Table 3.16-2 Settings of overfrequency protection.............................................................. 3-163

Table 3.17-1 Input/output signals of underfrequency protection ....................................... 3-166

Table 3.17-2 Settings of underfrequency protection ........................................................... 3-167

Table 3.18-1 Input/output signals of frequency rate-of-change protection ...................... 3-170

Table 3.18-2 Settings of frequency rate-of-change protection ........................................... 3-171

Table 3.19-1 Input/output signals of reverse power protection.......................................... 3-175

Table 3.19-2 Settings of reverse power protection .............................................................. 3-176

Table 3.20-1 Input/output signals of cold load pickup logic ............................................... 3-177

Table 3.20-2 Settings of cold load pickup logic ................................................................... 3-179

Table 3.21-1 Input/output signals of undercurrent protection............................................ 3-185

Table 3.21-2 Settings of undercurrent protection ................................................................ 3-186

Table 3.22-1 Input/output signals of breaker failure protection ......................................... 3-189

Table 3.22-2 Settings of breaker failure protection.............................................................. 3-191

Table 3.23-1 Input/output signals of SOTF protection ........................................................ 3-193

Table 3.23-2 Settings of SOTF protection ............................................................................. 3-196

Table 3.24-1 Input/output signals of unbalance current protection................................... 3-200

Table 3.24-2 Settings of unbalance current protection ....................................................... 3-201

Table 3.25-1 Input/output signals of unbalance voltage protection .................................. 3-204

Table 3.25-2 Settings of unbalance voltage protection ....................................................... 3-205

PCS-9611S Feeder Relay 3-m


Date: 2019-04-24
3 Protection Functions

Table 3.26-1 Input/Output signals of AR ............................................................................... 3-214

Table 3.26-2 Settings of AR .................................................................................................... 3-215

Table 3.27-1 Input/output signals of VT circuit supervision ............................................... 3-217

Table 3.27-2 Settings of VT circuit supervision ................................................................... 3-218

Table 3.28-1 Input/output signals of CT circuit supervision ............................................... 3-219

Table 3.28-2 Settings of CT circuit supervision ................................................................... 3-220

3-n PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

3.1 Three-phase Current Element (TCUR3P)

Three-phase current element is responsible for pre-processing three phase currents and
calculating sequence components, amplitudes and phase angles of three phase currents, etc. All
calculated information of three-phase current element is used for protection logic calculation.

Three-phase current element is a basic element, for a specific application,


the displayed signals and settings may have different prefixes in front of
them.
3
3.1.1 Function Description
Three-phase current element has following functions:

1. Pre-process three phase currents

2. Calculate information related to three-phase current

When any phase current is greater than 0.04In, the input current signals are valid and the valid
signal will be outputted for programmable logic application.

CT circuit supervision of three-phase current is carried out by the CTS element, which can refer to
Section 3.28 for details.

PCS-9611S Feeder Relay 3-1


Date: 2019-04-24
3 Protection Functions

3.1.2 Function Block Diagram

TCUR3P

in_ia I3P

in_ib Ia_Sec

in_ic Ib_Sec

Ic_Sec

I1_Sec

3 I2_Sec

3I0_Cal_Sec

Ang(Ia-Ib)

Ang(Ib-Ic)

Ang(Ic-Ia)

Ang(Ia)

Ang(Ib)

Ang(Ic)

Ang(3I0_Cal)

Alm_CTS

Flg_OnLoad

3.1.3 I/O Signals


Table 3.1-1 Input/Output signals of three-phase current element

No. Input Signal Description


1 in_ia Sampled value of phase-A current
2 in_ib Sampled value of phase-B current
3 in_ic Sampled value of phase-C current
No. Output Signal Description
1 I3P A current data set
2 Ia_Sec Amplitude of secondary phase-A current
3 Ib_Sec Amplitude of secondary phase-B current
4 Ic_Sec Amplitude of secondary phase-C current
5 I1_Sec Amplitude of secondary positive-sequence current
6 I2_Sec Amplitude of secondary negative-sequence current
7 3I0_Cal_Sec Amplitude of calculated secondary residual current
8 Ang(Ia-Ib) Phase angle between phase A and phase B currents
9 Ang(Ib-Ic) Phase angle between phase B and phase C currents

3-2 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

10 Ang(Ic-Ia) Phase angle between phase C and phase A currents


11 Ang(Ia) Phase angle of phase-A current
12 Ang(Ib) Phase angle of phase-B current
13 Ang(Ic) Phase angle of phase-C current
14 Ang(3I0_Cal) Phase angle of calculated residual current
15 Alm_CTS CT secondary circuit failure
16 Flg_OnLoad A flag indicating that the load current is detected

3.1.4 Settings
 Access path:

MainMenu  Settings  Global Settings  System Settings


3
Table 3.1-2 Settings of three-phase current element

No. Item Range Step Unit Default Description


1 Prot.I1n 0~9999 1 A 1000 Primary current value of the three-phase CT
2 Prot.I2n 1 or 5 - A 1 Secondary current value of the three-phase CT
Enabled, Logic setting of enabling/disabling the current
3 Prot.En_RevCT - - Disabled
Disabled polarity of the three-phase CT reversed

3.2 Three-phase Voltage Element (TVOL3P)

Three-phase voltage element is responsible for pre-processing three phase voltages and
calculating sequence components, amplitudes and phases of three phase voltages, etc. All
calculated information of three-phase voltage element is used for the protection logic calculation.

3.2.1 Function Description


Three-phase voltage element has following functions:

1. Pre-process three phase voltages

2. Calculate information related to three phase voltages

VT circuit failure supervision of three-phase voltage is carried out by the VTS element, which can
refer to Section 3.27 for details.

PCS-9611S Feeder Relay 3-3


Date: 2019-04-24
3 Protection Functions

3.2.2 Function Block Diagram

TVOL3P

in_ua U3P

in_ub Ua_Sec

in_uc Ub_Sec

BI_En_VT Uc_Sec

U1_Sec

3 U2_Sec

3U0_Cal_Sec

Ang(Ua-Ub)

Ang(Ub-Uc)

Ang(Uc-Ua)

Ang(Ua)

Ang(Ub)

Ang(Uc)

Ang(3U0_Cal)

Alm_VTS

3.2.3 I/O Signals


Table 3.2-1 Input/Output signals of three-phase voltage element

No. Input signal Description


1 in_ua Sampled value of phase-A voltage
2 in_ub Sampled value of phase-B voltage
3 in_uc Sampled value of phase-C voltage
4 BI_En_VT Input signal of indicating VT in service
No. Output signal Description
1 U3P A voltage data set
2 Ua_Sec Amplitude of phase-A secondary voltage
3 Ub_Sec Amplitude of phase-B secondary voltage
4 Uc_Sec Amplitude of phase-C secondary voltage
5 U1_Sec Amplitude of positive-sequence secondary voltage
6 U2_Sec Amplitude of negative-sequence secondary voltage
7 3U0_Cal_Sec Amplitude of calculated residual secondary voltage
8 Ang(Ua-Ub) Phase angle between phase A and phase B voltages
9 Ang(Ub-Uc) Phase angle between phase B and phase C voltages

3-4 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

No. Input signal Description


10 Ang(Uc-Ua) Phase angle between phase C and phase A voltages
11 Ang(Ua) Phase angle of phase-A voltage
12 Ang(Ub) Phase angle of phase-B voltage
13 Ang(Uc) Phase angle of phase-C voltage
14 Ang(3U0_Cal) Phase angle of calculated residual voltage
15 Alm_VTS VT secondary circuit abnormality

3.2.4 Settings
 Access path:

MainMenu  Settings  Global Settings  System Settings


3
Table 3.2-2 Settings of three-phase voltage element

No. Item Range Step Unit Default Description


1 Prot.U1n 1~1100 0.001 kV Rated value of primary voltage of the three-phase VT
2 Prot.U2n 1~120 0.001 V Rated value of secondary voltage of the three-phase VT
Enabled,
3 En_VT Enabled Logic setting to put the three-phase VT into service
Disabled

3.3 One-phase Current Element (TCUR1P)

One-phase current element is responsible for pre-processing measured one-phase current and
calculating the magnitude and the phase angle of the one-phase current, etc. All calculated
information of one-phase current element is used for the protection logic calculation.

3.3.1 Function Description


One-phase current element has following functions:

1. Pre-process measured one-phase current

2. Calculate information related to the one-phase current

3.3.2 Function Block Diagram

TCUR1P

x.in_ip x.I1P

x.3I0_Ext_Sec

x.Ang(3I0_Ext)

x.Flg_OnLoad

PCS-9611S Feeder Relay 3-5


Date: 2019-04-24
3 Protection Functions

3.3.3 I/O Signals


Table 3.3-1 Input/Output signals of one-phase current element

No. Input signal Description


1 x.in_ip Measured one-phase current
No. Output signal Description
1 x.I1P A current data set
2 x.3I0_Ext_Sec Amplitude of external residual secondary current
3 x.Ang(3I0_Ext) Phase angle of external residual current
4 x.Flg_OnLoad A flag indicating there is load current
3 3.3.4 Settings

One-phase current element is a basic element, for a specific application,


the displayed settings may have different prefixes in front of them.

 Access path:

MainMenu  Settings  Global Settings  System Settings

Table 3.3-2 Settings of one-phase current element

No. Item Range Step Unit Default Description


1 x.I1n 0~9999 1 A 1000 Primary rated current of the one-phase CT
Secondary rated current of the one-phase
2 x.I2n 1 or 5 - A 1
CT
Enabled, Logic setting of enabling/disabling the
3 x.En_RevCT - - Disabled
Disabled current polarity of the one-phase CT

3.4 One-phase Voltage Element (TVOL1P)

One-phase voltage element is responsible for pre-processing one-phase voltage and calculating
the magnitude and the phase angle of the one-phase voltage, etc. All calculated information of
one-phase voltage element is used for the protection logic calculation.

3.4.1 Function Description

One-phase voltage element has following functions:

1. Pre-process measured one-phase voltage

2. Calculate information related to one-phase voltage

3-6 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

3.4.2 Function Block Diagram

TVOL1P

in_up U1P

BI_En_VT U_Sec

Ang(U)

3.4.3 I/O Signals


Table 3.4-1 Input/Output signals of one-phase voltage element
3
No. Input signal Description
1 x.iIn_up Measured one-phase voltage
2 BI_En_VT Input signal of indicating VT in service
No. Output signal Description
1 U1P A voltage data set
2 U_Sec Amplitude of the one-phase voltage (secondary value)
3 Ang(U) Phase angle of the one-phase voltage

3.4.4 Settings

One-phase voltage element is a basic element, for a specific application,


the displayed settings may have different prefixes in front of them.

 Access path:

MainMenu  Settings  Global Settings  System Settings

Table 3.4-2 Settings of one-phase voltage element

No. Item Range Step Unit Default Description


1 x.U1n 0~1100 0.001 kV - Primary rated voltage of the one-phase VT
2 x.U2n 1~200 0.001 V - Secondary rated voltage of the one-phase VT

3.5 Phase Overcurrent Protection (50/51P)


Phase overcurrent protection is the most widely used type of protection element in power systems.
It can be used as the main protection of the feeder, and can also be used as the backup protection
for power equipment such as transformers, reactors, and motors. When a fault occurs in the
system, a fault current will be generated and the phase overcurrent protection can reflect the
increase of the fault current.

PCS-9611S Feeder Relay 3-7


Date: 2019-04-24
3 Protection Functions

3.5.1 Function Description


The device can provide six stages of phase overcurrent protection with independent logic. Each
stage can be independently set as definite-time characteristics or inverse-time characteristics.
The dropout characteristics can be set as instantaneous dropout, definite-time dropout or
inverse-time dropout. Users can choose whether it is blocked by the voltage control element,
direction control element, or harmonic control element, users can also choose whether it is
controlled by cold load pickup. The direction control element can be set as no direction, forward
direction and reverse direction. The phase overcurrent protection picks up when the current
exceeds the current threshold value, and operates after a certain time delay, once the fault
disappears, the phase overcurrent protection will dropout.
3 Phase overcurrent protection can be enabled or disabled via the settings or binary input signals,
for some specific applications, overcurrent protection needs to be blocked by the external signal,
so the device provides a function block input signal to be used to block overcurrent protection.
The enabling and blocking logic of phase overcurrent protection is shown in the figure below:

EN 50/51Px.En &
50/51Px.On

SIG 50/51Px.Enable

&
SIG 50/51Px.Block ≥1 50/51Px.Blocked

SIG Fail_Device
&
50/51Px.Valid

Figure 3.5-1 The enabling and blocking logic of phase overcurrent protection

The logic diagram of the fault detector element of phase overcurrent protection is as follows:

SET Ia>0.95×[50/51Px.I_Set]
>=1
SET Ib>0.95×[50/51Px.I_Set] &
0 500ms &
SET Ic>0.95×[50/51Px.I_Set]
50/51Px.Pkp
SIG 50/51Px.On

SIG 50/51Px.Valid
&
FD.Pkp
SET [50/51Px.Opt_Trp/Alm]=Alm

Figure 3.5-2 Logic diagram of the fault detector element of phase overcurrent protection

3.5.1.1 Voltage Control Element

When a fault occurs at the remote end of a feeder, the fault current is relatively small, so the
voltage control element can be adopted to increase the sensitivity for this kind of fault. Users can

3-8 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

enable or disable the voltage control element via the setting [50/51Px.En_Volt_Blk] (x=1~6). If the
VT circuit supervision function is enabled for the device, and the setting [50/51P.En_VTS_Blk] is
set as “1”, when VT circuit failure happens, the device will issue a VT circuit failure alarm signal
[VTS.Alm], and the voltage controlled phase overcurrent protection will be blocked. If the voltage
control element of phase overcurrent protection is not enabled, phase overcurrent protection will
not effected by VT circuit failure. The corresponding relationship between the phase-segregated
overcurrent element and the voltage control element is as follows.

Voltage control
Phase A Phase B Phase C
criterion
Phase-to-phase Uab<[50/51P.VCE.Upp] Uab<[50/51P.VCE.Upp] Ubc<[50/51P.VCE.Upp]
criterion Uca<[50/51P.VCE.Upp] Ubc<[50/51P.VCE.Upp] Uca<[50/51P.VCE.Upp] 3
Negative-sequence
U2>[50/51P.VCE.U2] U2>[50/51P.VCE.U2] U2>[50/51P.VCE.U2]
criterion
Zero-sequence
U0_Cal>[50/51P.VCE.3U0] U0_Cal>[50/51P.VCE.3U0] U0_Cal>[50/51P.VCE.3U0]
criterion

The relationship between the phase-to-phase criterion, the negative-sequence criterion and the
zero-sequence criterion is "or". The logic diagram of the voltage control element action is shown
below:

EN [50/51P.En_VTS_Blk] &

>=1

SIG VTS.Alm
>=1
SIG Uab, Ubc, Uca & 50/51P.VCE.Op
criterion
Voltage

SIG U2, U0_Cal

SIG Prot.BI_En_VT &

EN [En_VT]

Figure 3.5-3 Logic diagram of the voltage control element of phase overcurrent protection

3.5.1.2 Direction Control Element

In order to ensure the selectivity of phase overcurrent protection, direction control element is
introduced. The setting [50/51Px.Opt_Dir] (x=1~6) is used for users to select the directional mode
of each stage of phase overcurrent protection: no direction, forward direction and reverse
direction are selectable.

Takes the phase A fault as an example, the polarization mode is set as “Up”, its operation
characteristics are shown in the figure below. The principle of phase B and phase C is the same. If
the positive-sequence voltage or the phase-to-phase voltage is polarized, the operation

PCS-9611S Feeder Relay 3-9


Date: 2019-04-24
3 Protection Functions

characteristics are the same.

The operation boundary of the forward direction element can be set by [50/51P.DIR.phi_Min_Fwd]
and [50/51P.DIR.phi_Max_Fwd]. The operation boundary of the reverse direction element can be
set by [50/51P.DIR.phi_Min_Rev] and [50/51P.DIR.phi_Max_Rev].

Ua

[50/51P.DIR.phi_Min_Fwd]

3 Non-operating
area
Ia

[50/51P.DIR.phi_Max_Rev] Operating area in


forward direction

[50/51P.DIR.RCA]

Operating area in
reverse direction

[50/51P.DIR.phi_Max_Fwd]

[50/51P.DIR.phi_Min_Rev] Non-operating
area

Figure 3.5-4 The direction element operation characteristics when phase A voltage is polarized

Where:

The sensitivity angle of the direction control element (RCA) can be set by the setting
[50/51P.DIR.RCA].

The selection of the polarization voltage can be set by the setting [50/51P.DIR.Opt_PolarizedVolt].
The following table shows the relationship between the operating current, the polarized voltage
and the polarization mode.

Direction criterion
Polarization Faulty Operating
Polarized voltage Angle difference
mode phase current
Phase-A Positive-sequence
Phase A Angle_A=Angle(U1)-Angle(Ia)-RCA
current Ia voltage
Positive-sequence Phase-B Positive-sequence
Phase B Angle_B=Angle(U1)-Angle(Ib)-RCA-120º
voltage polarized current Ib voltage
Phase-C Positive-sequence
Phase C Angle_C=Angle(U1)-Angle(Ic)-RCA+120º
current Ic voltage
Phase-to-phase Phase-A Phase-to-phase
Phase A Angle_A=Angle(Ubc)-Angle(Ia)-RCA+90º
voltage polarized current Ia voltage Ubc

3-10 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Phase-B Phase-to-phase
Phase B Angle_B=Angle(Uca)-Angle(Ib)-RCA+90º
current Ib voltage Uca
Phase-C Phase-to-phase
Phase C Angle_C=Angle(Uab)-Angle(Ic)-RCA+90º
current Ic voltage Uab
Phase-A Phase-to-ground
Phase A Angle_A=Angle(Ua)-Angle(Ia)-RCA
current Ia voltage Ua
Phase-to-ground Phase-B Phase-to-ground
Phase B Angle_B=Angle(Ub)-Angle(Ib)-RCA
voltage polarized current Ib voltage Ub
Phase-C Phase-to-ground
Phase C Angle_C=Angle(Uc)-Angle(Ic)-RCA
current Ic voltage Uc

In order to improve the reliability of the direction control element, the direction control element with 3
the above three polarization modes must be used in conjunction with the negative-sequence
direction criterion. The negative-sequence direction criterion is shown in the table below.

Negative-sequence direction criterion


Operating current Polarized voltage Angle difference
Negative-sequence current Negative-sequence voltage Angle_I2=Angle(U2)-Angle(I2)-RCA+180º

Therefore, the criterion for the three-phase direction control element is as follows:

Three-phase direction control element


Direction element Operating condition
Angle_A forward direction operates and Angle_I2 reverse direction does not
Phase A forward direction
operate.
Angle_A reverse direction operates and Angle_I2 forward direction does not
Phase A reverse direction
operate.
Angle_B forward direction operates and Angle_I2 reverse direction does not
Phase B forward direction
operate.
Angle_B forward direction operates and Angle_I2 forward direction does not
Phase B reverse direction
operate.
Angle_C forward direction operates and Angle_I2 reverse direction does not
Phase C forward direction
operate.
Angle_C forward direction operates and Angle_I2 forward direction does not
Phase C reverse direction
operate.

The direction element calculation needs to judge the voltage threshold and current threshold. The
direction can be judged only when both of the voltage and current are greater than the threshold,
choose a different polarization mode, the selection of voltage and current, and the threshold are
not the same, the specific principles are:

Polarized voltage Minimum operating current Minimum operating voltage


Phase-to-phase voltage Phase current Phase-to-phase voltage
Phase-to-ground voltage Phase current Phase-to-ground voltage
Positive-sequence voltage Phase current Positive-sequence voltage
Negative-sequence voltage Negative-sequence current Negative-sequence voltage

PCS-9611S Feeder Relay 3-11


Date: 2019-04-24
3 Protection Functions

The direction element has memory function that can eliminate the dead zone of the direction
element when the close up three-phase short circuit fault occurs. When the polarized voltage is
less than the minimum operating voltage setting [50/51P.DIR.U_Min], the positive-sequence
voltage before two cycles is used to judge the direction. The polarized voltage will not be used to
judge the direction until it is greater than [50/51P.DIR.U_Min]. The logic diagram of the forward
direction element and reverse direction element is shown as below.

EN [50/51P.En_VTS_Blk] &

3 >=1

SIG VTS.Alm

SIG Three-phase currents Forward direction & >=1


50/51P.FwdDir.Op
SIG Three-phase voltages
criterion

SIG Memorized U1

SET [50/51P.DIR.Opt_PolarizedVolt]

SIG Prot.BI_En_VT &

EN [En_VT]

EN [50/51P.En_VTS_Blk] &

>=1

SIG VTS.Alm

SIG Three-phase currents & >=1


Reverse direction

50/51P.RevDir.Op
SIG Three-phase voltages
criterion

SIG Memorized U1

SET [50/51P.DIR.Opt_PolarizedVolt]

SIG Prot.BI_En_VT &

EN [En_VT]

Figure 3.5-5 Logic diagram of forward and reverse direction element of phase overcurrent protection

Where:

Memorized U1: the positive-sequence memory voltage, it refers to the positive-sequence voltage
of two cycles before the polarized voltage is less than the minimum operating voltage setting
[50/51P.DIR.U_Min], and it is calculated from the three-phase voltage.

3-12 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

3.5.1.3 Harmonic Control Element

When transformer and other equipment are energized without any load, the inrush current may be
generated, which may cause the mal-operation of the phase overcurrent protection. According to
the characteristics of high secondary harmonic component in the inrush current and low
secondary harmonic component in common fault current, the secondary harmonic control element
is added to prevent the phase overcurrent protection from mal-operation due to inrush current. For
the harmonic control element, the harmonic blocking mode can be selected through the setting
[50/51P.HMB.Opt_Blk], it can support phase locking, cross locking, and maximum phase locking.
The correspondences are shown in the following table:

Setting Value
Phase A
Harmonic blocking criterion
Phase B Phase C
3
1 PhaseBlk Ia2/Ia1>[50/51P.HMB.K_Hm2] Ib2/Ib1>[50/51P.HMB.K_Hm2] Ic2/Ic1>[50/51P.HMB.K_Hm2]
2 CrossBlk (Ia2/Ia1) or (Ib2/Ib1) or (Ic2/Ic1)> [50/51P.HMB.K_Hm2]
Max(Ia2, Ib2, Ic2)/Ia1> Max(Ia2, Ib2, Ic2)/Ib1> Max(Ia2, Ib2, Ic2)/Ic1>
3 MaxPhaseBlk
[50/51P.HMB.K_Hm2] [50/51P.HMB.K_Hm2] [50/51P.HMB.K_Hm2]

Where:

Ia1, Ib1, Ic1: the fundamental current;

Ia2, Ib2, Ic2: the secondary harmonic component of the current.

When the fundamental current is greater than the setting [50/51P.HMB.I_Rls], the harmonic
blocking element of the corresponding phase is released.

The following figure shows the logic diagram of the harmonic control element of phase
overcurrent protection.

SET Imax>[50/51P.HMB.I_Rls]

SIG Ia1, Ib1, Ic1


&
50/51P.HMB.Op
Harmonic
criterion

SIG Ia2, Ib2, Ic2

SET [50/51P.HMB.Opt_Blk]

Figure 3.5-6 Logic diagram of harmonic control element of phase overcurrent protection

Where:

Ia1, Ib1, Ic1: the fundamental current

Ia2, Ib2, Ic2: the 2nd harmonic current

Imax: the maximum phase current

3.5.1.4 Operation Characteristic

Phase overcurrent protection can operate without time delay or operate with a definite-time limit, it
can also operate with an inverse-time limit, the characteristic curve meets the IEC60255-3 and

PCS-9611S Feeder Relay 3-13


Date: 2019-04-24
3 Protection Functions

ANSI C37.112 standards. Phase overcurrent protection can support definite-time limit, IEC &
ANSI standard inverse time limit and user-defined inverse-time limit, users can select the wanted
operating curve by the setting [50/51Px.Opt_Curve] (x=1~6), the relationship between the value of
the setting and the curve is shown in the table below.

50/51Px.Opt_Curve Time Characteristic k α c tr


ANSIE ANSI Extremely Inverse 28.2 2.0 0.1217 29.1
ANSIV ANSI Very inverse 19.61 2.0 0.491 21.6
ANSIN ANSI Normal Inverse 0.0086 0.02 0.0185 0.46
ANSIM ANSI Moderately Inverse 0.0515 0.02 0.114 4.85

3
ANSIDefTime ANSI Definite Time - - - -
ANSILTE ANSI Long Time Extremely Inverse 64.07 2.0 0.25 30
ANSILTV ANSI Long Time Very Inverse 28.55 2.0 0.712 13.46
ANSILT ANSI Long Time Inverse 0.086 0.02 0.185 4.6
IECN IEC Normal Inverse 0.14 0.02 0 -
IECV IEC Very inverse 13.5 1.0 0 -
IEC IEC Inverse 0.14 0.02 0 -
IECE IEC Extremely inverse 80.0 2.0 0 -
IECST IEC Short-time inverse 0.05 0.04 0 -
IECLT IEC Long-time inverse 120.0 1.0 0 -
IECDefTime IEC Definite Time - - - -
UserDefine Programmable

Only when the setting [50/51Px.Opt_Curve] is set as “UserDefine”, i.e. the user-defined
inverse-time characteristic is selected, the settings [50/51Px.K], [50/51Px.C] and [50/51Px.Alpha]
are useful, the inverse-time operating curve is determined by the three settings.

 Without time delay

When I > Ip , phase overcurrent protection operates immediately.

 Definite-time characteristic

When I > Ip , the protection operates with a time delay of top (i.e. the value of the setting
[50/51Px.t_Op]), and the operation characteristic curve is shown in the following figure:

3-14 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

t op

3
IP I

Figure 3.5-7 Definite-time operation characteristic curve of phase overcurrent protection

 Inverse-time characteristic

When I > Ip , the inverse-time accumulator begins to accumulate, and the operating time is
affected by the applied current I . The operating time will decrease with the current increasing,
but the operating time shall not less than tmin , i.e. the setting [50/51Px.tmin] (x=1~6). The
inverse-time operation characteristic equation is:

 k 
t 
 c   TMS
 (I / I P ) 1 

Where:

Ip is the current setting [50/51Px.I_Set];


TMS is the inverse-time time multiplier, i.e. the setting [50/51Px.TMS];

k is the inverse-time coefficient K, i.e. the setting [50/51Px.K];


c is the inverse-time coefficient C, i.e. the setting [50/51Px.C];
 is the inverse-time coefficient Alpha, i.e. the setting [50/51Px.Alpha];

I is the measured current.


The inverse-time operation characteristic curve is shown as below:

PCS-9611S Feeder Relay 3-15


Date: 2019-04-24
3 Protection Functions

3 t min

IP ID I

Figure 3.5-8 Inverse-time operation characteristic curve of phase overcurrent protection

When the applied current is not a fixed value, but changes with time, the operating behavior of the
protection is shown in the following equation:

T0
1
 t ( I )dt
0
1

Where:

T0 is the operating time of the protection element;

t(I) is the theoretical operating time when the current is I.

3.5.1.5 Dropout Characteristic

The supported dropout characteristics of the phase overcurrent protection include instantaneous
dropout, definite-time dropout and ANSI inverse-time dropout.

When the operating curve is selected as definite-time, IEC inverse-time or user-defined


inverse-time characteristic, the dropout characteristic can only be selected as instantaneous
dropout or definite-time dropout, if inverse-time dropout is selected, the alarm signal
"Fail_Settings" will be issued and the device will be blocked.

When the operating curve is selected as ANSI inverse-time characteristic, the dropout
characteristic can be selected as instantaneous dropout, definite-time dropout and ANSI
inverse-time dropout.

 Instantaneous dropout

When I <0.95* Ip , the protection drops out immediately.

 Definite-time dropout

3-16 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

When I <0.95* Ip , the protection drops out with a time delay of tdr (i.e. the value of the setting
[50/51Px.t_DropOut]), and the dropout characteristic curve is shown in the following figure:

Start time

I>Ip

Start
signal

3
Operating
signal

Protection
Operating threshold operate

Operating
counter

t dr t dr t dr
Dropout time setting
Dropout time
Dropout time

Figure 3.5-9 Definite-time dropout characteristic of phase overcurrent protection

 Inverse-time dropout

When I > Ip , the inverse-time operating accumulator begins to accumulate, the accumulated
value after tp (Assuming tp is less than the theoretical operating time) is calculated according
to the following equation:

tp
1
I tp   dt
0
t ( I )

At this time, if I <0.95* Ip , the protection element starts dropout, and the dropout characteristic
meets the following equation:

TR
1
I tp   dt  0
t (I )
0 R

Where:

TR is the dropout time;


tR ( I ) is the dropout characteristic equation

PCS-9611S Feeder Relay 3-17


Date: 2019-04-24
3 Protection Functions

When I <0.95* Ip , the inverse-time dropout characteristic equation is as follows:

 tr 
tR   2
 TMS
1  ( I / I P ) 

Where:

Ip is the current setting [50/51Px.I_Set];


TMS is the inverse-time factor, i.e. the setting [50/51Px.TMS];

tr is the dropout time coefficient, it is the dropout time required for the current to drop to 0 after
3 the protection operates.

I is the measured current.


When 0.95* Ip < I < Ip , the accumulator will neither accumulate nor drop out

The inverse time dropout characteristic curve is shown in the figure below.

tr

IP I

Figure 3.5-10 Inverse-time dropout characteristic curve of phase overcurrent protection

The correspondence between the start signal, operating signal, and operating accumulator in the
inverse-time dropout characteristic is shown in the figure below:

3-18 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Start time

I>Ip

Start
signal

Operating
signal

Operating threshold
Protection
operate
3
Operating
counter

tr Dropout time coefficient


Dropout time
Dropout time

Figure 3.5-11 Inverse-time dropout characteristic of phase overcurrent protection

3.5.2 Function Block Diagram

50/51P

50/51Px.Enable 50/51Px.On

50/51Px.Block 50/51Px.Blocked

50/51Px.Valid

50/51Px.St

50/51Px.StA

50/51Px.StB

50/51Px.StC

50/51Px.Op

50/51Px.Op.PhA

50/51Px.Op.PhB

50/51Px.Op.PhC

50/51P.FwdDir.Op

50/51P.RevDir.Op

50/51Px.Alm

PCS-9611S Feeder Relay 3-19


Date: 2019-04-24
3 Protection Functions

3.5.3 I/O Signal


Table 3.5-1 Input/output signals of phase overcurrent protection

No. Input signal Description


Stage x of phase overcurrent protection enabling input, it is triggered from
1 50/51Px.Enable
binary input or programmable logic etc. (x=1~6)
Stage x of phase overcurrent protection blocking input, it is triggered from
2 50/51Px.Block
binary input or programmable logic etc. (x=1~6)
No. Output signal Description
1 50/51Px.On Stage x of phase overcurrent protection is enabled

3 2 50/51Px.Blocked Stage x of phase overcurrent protection is blocked


3 50/51Px.Valid Stage x of phase overcurrent protection is valid
4 50/51Px.St Stage x of phase overcurrent protection starts
5 50/51Px.StA Stage x of phase overcurrent protection starts (Phase A)
6 50/51Px.StB Stage x of phase overcurrent protection starts (Phase B)
7 50/51Px.StC Stage x of phase overcurrent protection starts (Phase C)
8 50/51Px.Op Stage x of phase overcurrent protection operates
9 50/51Px.Op.PhA Stage x of phase overcurrent protection operates (Phase A)
10 50/51Px.Op.PhB Stage x of phase overcurrent protection operates (Phase B)
11 50/51Px.Op.PhC Stage x of phase overcurrent protection operates (Phase C)
12 50/51Px.Alm Stage x of phase overcurrent protection alarms
13 50/51P.FwdDir.Op The forward direction element of phase overcurrent protection operates
14 50/51P.RevDir.Op The reverse direction element of phase overcurrent protection operates

3-20 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

3.5.4 Logic

SET Ia>[50/51Px.I_Set]

SIG 50/51P.VCE.Op_A >=1 &

EN [50/51Px.En_Volt_Blk]

SIG 50/51P.FwdDir.Op_A

selection
Direction
SIG 50/51P.RevDir.Op_A

SIG [50/51Px.Opt_Dir] 50/51Px.StA


&

3
SIG 50/51P.HMB.Op_A & & Timer
t
&
t
EN [50/51Px.En_Hm_Blk] 50/51Px.Op.PhA

SIG 50/51Px.Pkp

SET [50/51Px.Opt_Trp/Alm]=Trp
&
50/51Px.Alm.PhA
SET [50/51Px.Opt_Trp/Alm]=Alm

SIG 50/51Px.StA
>=1
SIG 50/51Px.StB 50/51Px.St

SIG 50/51Px.StC

SIG 50/51Px.Op.PhA
>=1
SIG 50/51Px.Op.PhB 50/51Px.Op

SIG 50/51Px.Op.PhC

SIG 50/51Px.Alm.PhA
>=1
SIG 50/51Px.Alm.PhB 50/51Px.Alm

SIG 50/51Px.Alm.PhC

Figure 3.5-12 Logic diagram of phase overcurrent protection

3.5.5 Settings
 Access path:

MainMenu  Settings  Protection Settings  OC Settings

Table 3.5-2 Settings of phase overcurrent protection

Default
No. Settings Range Unit Step Description
value
The low voltage blocking setting
1 50/51P.VCE.Upp 10~100 70 V 0.001 of the voltage control element of
phase overcurrent protection

PCS-9611S Feeder Relay 3-21


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The negative-sequence voltage
blocking setting of the voltage
2 50/51P.VCE.U2 2~57 8 V 0.001
control element of phase
overcurrent protection
The residual voltage setting (set
according to 3U0) of voltage
3 50/51P.VCE.3U0 2~57 8 V 0.001
control element of phase
overcurrent protection

3 4 50/51P.DIR.RCA -180~179 45 deg 1


The relay characteristic angle of
the direction control element of
phase overcurrent protection
The relay negative-sequence
50/51P.DIR.RCA_N characteristic angle of the
5 -180~179 45 deg 1
egOC direction control element of
phase overcurrent protection
The minimum boundary of the
50/51P.DIR.phi_Min
6 10~90 90 deg 1 forward direction element of
_Fwd
phase overcurrent protection
The maximum boundary of the
50/51P.DIR.phi_Ma
7 10~90 90 deg 1 forward direction element of
x_Fwd
phase overcurrent protection
The minimum boundary of the
50/51P.DIR.phi_Min
8 10~90 90 deg 1 reverse direction element of
_Rev
phase overcurrent protection
The maximum boundary of the
50/51P.DIR.phi_Ma
9 10~90 90 deg 1 reverse direction element of
x_Rev
phase overcurrent protection
The voltage polarization mode
for direction control element of
phase overcurrent protection
Upp; Upp: phase-to-phase voltage
50/51P.DIR.Opt_Pol
10 Up; Upp - - polarized
arizedVolt
U1 Up: phase-to-ground voltage
polarized
U1: positive-sequence voltage
polarized
The minimum operating current
setting for the direction control
11 50/51P.DIR.I_Min (0.05~1)In 0.05 - 0.001
element of phase overcurrent
protection

3-22 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The minimum operating voltage
setting for the direction control
12 50/51P.DIR.U_Min 1~10 4 V 0.001
element of phase overcurrent
protection
Logic setting to determine the
behavior of phase overcurrent
protection when VT circuit
supervision function is enabled

Disabled;
and VT circuit failure happens.
Disabled: phase overcurrent
3
13 50/51P.En_VTS_Blk Disabled - -
Enabled protection will not effected by VT
circuit failure
Enabled: voltage controlled
phase overcurrent protection will
be blocked by VT circuit failure
signal
The percent setting of the
50/51P.HMB.K_Hm
14 0.1~1 0.2 - 0.001 harmonic control element of
2
phase overcurrent protection
The current setting for releasing
15 50/51P.HMB.I_Rls 2~150 20 A 0.001 the harmonic control element of
phase overcurrent protection
The setting used to select the
harmonic blocking mode of
PhaseBlk phase overcurrent protection
50/51P.HMB.Opt_Bl
16 CrossBlk PhaseBlk - - PhaseBlk: phase blocking
k
MaxPhaseBlk CrossBlk: cross blocking
MaxPhaseBlk: maximum phase
blocking
The current setting of stage 1 of
17 50/51P1.I_Set 0.05~200 15 A 0.001
phase overcurrent protection
The operating time setting of
18 50/51P1.t_Op 0 ~100 0.1 s 0.001 stage 1 of phase overcurrent
protection
The dropout time setting of
19 50/51P1.t_DropOut 0 ~100 0 s 0.001 stage 1 of phase overcurrent
protection

PCS-9611S Feeder Relay 3-23


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The logic setting for
enabling/disabling the voltage
control element of stage 1 of
phase overcurrent protection
Disabled: stage 1 of phase
50/51P1.En_Volt_Bl Disabled; overcurrent protection is not
20 Disabled - -
k Enabled controlled by the voltage control
element

3 Enabled: stage 1 of phase


overcurrent protection is
controlled by the voltage control
element
Non_Directional The setting used to select the
Non_Directio
21 50/51P1.Opt_Dir Forward - - directional mode of stage 1 of
nal
Reverse phase overcurrent protection.
The logic setting for
enabling/disabling the harmonic
control element of stage 1 of
phase overcurrent protection
Disabled: stage 1 of phase
50/51P1.En_Hm_Bl Disabled; overcurrent protection is not
22 Disabled - -
k Enabled controlled by the harmonic
control element
Enabled: stage 1 of phase
overcurrent protection is
controlled by the harmonic
control element
The logic setting for
Disabled;
23 50/51P1.En Enabled - - enabling/disabling the stage 1 of
Enabled
phase overcurrent protection
Enabling stage 1 of phase
overcurrent protection operate
50/51P1.Opt_Trp/Al Trp;
24 Trp - - to trip or alarm.
m Alm
Trp: for tripping purpose
Alm: for alarm purpose

3-24 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
ANSILT; inverse-time operation
25 50/51P1.Opt_Curve IECDefTime - -
IECN;
IECV;
characteristic curve of stage 1 of
phase overcurrent protection.
3
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 1 of
50/51P1.Opt_Curve
26 DefTime; Inst - - phase overcurrent protection
_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
27 50/51P1.TMS 0.04~ 20 1 - 0.001 stage 1 of phase overcurrent
protection
The minimum operating time
28 50/51P1.tmin 0 ~10 0.02 s 0.001 setting of stage 1 of phase
overcurrent protection
The constant “k” of the
customized inverse-time
0.000
29 50/51P1.K 0.001~120 0.14 - operation characteristic of stage
1
1 of phase overcurrent
protection
The constant “α” of the
customized inverse-time
0.000
30 50/51P1.Alpha 0.01 ~3 0.02 - operation characteristic of stage
1
1 of phase overcurrent
protection

PCS-9611S Feeder Relay 3-25


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The constant “C” of the
customized inverse-time
0.000
31 50/51P1.C 0 ~1 0 - operation characteristic of stage
1
1 of phase overcurrent
protection
The current setting of stage 1 of
32 50/51P1.I_Set 0.05~200 15 A 0.001
phase overcurrent protection
The operating time setting of

3 33 50/51P2.t_Op 0 ~100 0.1 s 0.001 stage 2 of phase overcurrent


protection
The dropout time setting of
34 50/51P2.t_DropOut 0 ~100 0 s 0.001 stage 2 of phase overcurrent
protection
The logic setting for
enabling/disabling the voltage
control element of stage 2 of
phase overcurrent protection
Disabled: stage 2 of phase
50/51P2.En_Volt_Bl Disabled; overcurrent protection is not
35 Disabled - -
k Enabled controlled by the voltage control
element
Enabled: stage 2 of phase
overcurrent protection is
controlled by the voltage control
element
Non_Directional The setting used to select the
Non_Directio
36 50/51P2.Opt_Dir Forward - - directional mode of stage 2 of
nal
Reverse phase overcurrent protection.
The logic setting for
enabling/disabling the harmonic
control element of stage 2 of
phase overcurrent protection
Disabled: stage 2 of phase
50/51P2.En_Hm_Bl Disabled; overcurrent protection is not
37 Disabled - -
k Enabled controlled by the harmonic
control element
Enabled: stage 2 of phase
overcurrent protection is
controlled by the harmonic
control element

3-26 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The logic setting for
Disabled;
38 50/51P2.En Enabled - - enabling/disabling the stage 2 of
Enabled
phase overcurrent protection
Enabling stage 2 of phase
overcurrent protection operate
50/51P2.Opt_Trp/Al Trp;
39 Trp - - to trip or alarm.
m Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
3
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
ANSILT; inverse-time operation
40 50/51P2.Opt_Curve IECDefTime - -
IECN; characteristic curve of stage 2 of
IECV; phase overcurrent protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 2 of
50/51P2.Opt_Curve
41 DefTime; Inst - - phase overcurrent protection
_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
42 50/51P2.TMS 0.04~ 20 1 - 0.001 stage 2 of phase overcurrent
protection
The minimum operating time
43 50/51P2.tmin 0 ~10 0.02 s 0.001 setting of stage 2 of phase
overcurrent protection
The constant “k” of the
customized inverse-time
0.000
44 50/51P2.K 0.001~120 0.14 - operation characteristic of stage
1
2 of phase overcurrent
protection

PCS-9611S Feeder Relay 3-27


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The constant “α” of the
customized inverse-time
0.000
45 50/51P2.Alpha 0.01 ~3 0.02 - operation characteristic of stage
1
2 of phase overcurrent
protection
The constant “C” of the
customized inverse-time
0.000
46 50/51P2.C 0 ~1 0 - operation characteristic of stage
1
3 2 of
protection
phase overcurrent

The current setting of stage 3 of


47 50/51P3.I_Set 0.05~200 15 A 0.001
phase overcurrent protection
The operating time setting of
48 50/51P3.t_Op 0 ~100 0.1 s 0.001 stage 3 of phase overcurrent
protection
The dropout time setting of
49 50/51P3.t_DropOut 0 ~100 0 s 0.001 stage 3 of phase overcurrent
protection
The logic setting for
enabling/disabling the voltage
control element of stage 3 of
phase overcurrent protection
Disabled: stage 3 of phase
50/51P3.En_Volt_Bl Disabled; overcurrent protection is not
50 Disabled - -
k Enabled controlled by the voltage control
element
Enabled: stage 3 of phase
overcurrent protection is
controlled by the voltage control
element
Non_Directional The setting used to select the
Non_Directio
51 50/51P3.Opt_Dir Forward - - directional mode of stage 3 of
nal
Reverse phase overcurrent protection.

3-28 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The logic setting for
enabling/disabling the harmonic
control element of stage 3 of
phase overcurrent protection
Disabled: stage 3 of phase
50/51P3.En_Hm_Bl Disabled; overcurrent protection is not
52 Disabled - -
k Enabled controlled by the harmonic
control element
Enabled: stage 3 of phase
overcurrent protection is
3
controlled by the harmonic
control element
The logic setting for
Disabled;
53 50/51P3.En Enabled - - enabling/disabling the stage 3 of
Enabled
phase overcurrent protection
Enabling stage 3 of phase
overcurrent protection operate
50/51P3.Opt_Trp/Al Trp;
54 Trp - - to trip or alarm.
m Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
ANSILT; inverse-time operation
55 50/51P3.Opt_Curve IECDefTime - -
IECN; characteristic curve of stage 3 of
IECV; phase overcurrent protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine

PCS-9611S Feeder Relay 3-29


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 3 of
50/51P3.Opt_Curve
56 DefTime; Inst - - phase overcurrent protection
_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of

3 57 50/51P3.TMS 0.04~ 20 1 - 0.001 stage 3 of phase overcurrent


protection
The minimum operating time
58 50/51P3.tmin 0 ~10 0.02 s 0.001 setting of stage 3 of phase
overcurrent protection
The constant “k” of the
customized inverse-time
0.000
59 50/51P3.K 0.001~120 0.14 - operation characteristic of stage
1
3 of phase overcurrent
protection
The constant “α” of the
customized inverse-time
0.000
60 50/51P3.Alpha 0.01 ~3 0.02 - operation characteristic of stage
1
3 of phase overcurrent
protection
The constant “C” of the
customized inverse-time
0.000
61 50/51P3.C 0 ~1 0 - operation characteristic of stage
1
3 of phase overcurrent
protection
The current setting of stage 4 of
62 50/51P4.I_Set 0.05~200 15 A 0.001
phase overcurrent protection
The operating time setting of
63 50/51P4.t_Op 0 ~100 0.1 s 0.001 stage 4 of phase overcurrent
protection
The dropout time setting of
64 50/51P4.t_DropOut 0 ~100 0 s 0.001 stage 4 of phase overcurrent
protection

3-30 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The logic setting for
enabling/disabling the voltage
control element of stage 4 of
phase overcurrent protection
Disabled: stage 4 of phase
50/51P4.En_Volt_Bl Disabled; overcurrent protection is not
65 Disabled - -
k Enabled controlled by the voltage control
element
Enabled: stage 4 of phase
overcurrent protection is
3
controlled by the voltage control
element
Non_Directional The setting used to select the
Non_Directio
66 50/51P4.Opt_Dir Forward - - directional mode of stage 4 of
nal
Reverse phase overcurrent protection.
The logic setting for
enabling/disabling the harmonic
control element of stage 4 of
phase overcurrent protection
Disabled: stage 4 of phase
50/51P4.En_Hm_Bl Disabled; overcurrent protection is not
67 Disabled - -
k Enabled controlled by the harmonic
control element
Enabled: stage 4 of phase
overcurrent protection is
controlled by the harmonic
control element
The logic setting for
Disabled;
68 50/51P4.En Enabled - - enabling/disabling the stage 4 of
Enabled
phase overcurrent protection
Enabling stage 4 of phase
overcurrent protection operate
50/51P4.Opt_Trp/Al Trp;
69 Trp - - to trip or alarm.
m Alm
Trp: for tripping purpose
Alm: for alarm purpose

PCS-9611S Feeder Relay 3-31


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
ANSILT; inverse-time operation
70 50/51P4.Opt_Curve IECDefTime - -
3 IECN;
IECV;
characteristic curve of stage 4 of
phase overcurrent protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 4 of
50/51P4.Opt_Curve
71 DefTime; Inst - - phase overcurrent protection
_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
72 50/51P4.TMS 0.04~ 20 1 - 0.001 stage 4 of phase overcurrent
protection
The minimum operating time
73 50/51P4.tmin 0 ~10 0.02 s 0.001 setting of stage 4 of phase
overcurrent protection
The constant “k” of the
customized inverse-time
0.000
74 50/51P4.K 0.001~120 0.14 - operation characteristic of stage
1
4 of phase overcurrent
protection
The constant “α” of the
customized inverse-time
0.000
75 50/51P4.Alpha 0.01 ~3 0.02 - operation characteristic of stage
1
4 of phase overcurrent
protection

3-32 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The constant “C” of the
customized inverse-time
0.000
76 50/51P4.C 0 ~1 0 - operation characteristic of stage
1
4 of phase overcurrent
protection
The current setting of stage 5 of
77 50/51P5.I_Set 0.05~200 15 A 0.001
phase overcurrent protection
The operating time setting of
78 50/51P5.t_Op 0 ~100 0.1 s 0.001 stage 5 of phase overcurrent
protection
3
The dropout time setting of
79 50/51P5.t_DropOut 0 ~100 0 s 0.001 stage 5 of phase overcurrent
protection
The logic setting for
enabling/disabling the voltage
control element of stage 5 of
phase overcurrent protection
Disabled: stage 5 of phase
50/51P5.En_Volt_Bl Disabled; overcurrent protection is not
80 Disabled - -
k Enabled controlled by the voltage control
element
Enabled: stage 5 of phase
overcurrent protection is
controlled by the voltage control
element
Non_Directional The setting used to select the
Non_Directio
81 50/51P5.Opt_Dir Forward - - directional mode of stage 5 of
nal
Reverse phase overcurrent protection.
The logic setting for
enabling/disabling the harmonic
control element of stage 5 of
phase overcurrent protection
Disabled: stage 5 of phase
50/51P5.En_Hm_Bl Disabled; overcurrent protection is not
82 Disabled - -
k Enabled controlled by the harmonic
control element
Enabled: stage 5 of phase
overcurrent protection is
controlled by the harmonic
control element

PCS-9611S Feeder Relay 3-33


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The logic setting for
Disabled;
83 50/51P5.En Enabled - - enabling/disabling the stage 5 of
Enabled
phase overcurrent protection
Enabling stage 5 of phase
overcurrent protection operate
50/51P5.Opt_Trp/Al Trp;
84 Trp - - to trip or alarm.
m Alm
Trp: for tripping purpose
Alm: for alarm purpose

3 ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
ANSILT; inverse-time operation
85 50/51P5.Opt_Curve IECDefTime - -
IECN; characteristic curve of stage 5 of
IECV; phase overcurrent protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 5 of
50/51P5.Opt_Curve
86 DefTime; Inst - - phase overcurrent protection
_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
87 50/51P5.TMS 0.04~ 20 1 - 0.001 stage 5 of phase overcurrent
protection
The minimum operating time
88 50/51P5.tmin 0 ~10 0.02 s 0.001 setting of stage 5 of phase
overcurrent protection
The constant “k” of the
customized inverse-time
0.000
89 50/51P5.K 0.001~120 0.14 - operation characteristic of stage
1
5 of phase overcurrent
protection

3-34 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The constant “α” of the
customized inverse-time
0.000
90 50/51P5.Alpha 0.01 ~3 0.02 - operation characteristic of stage
1
5 of phase overcurrent
protection
The constant “C” of the
customized inverse-time
0.000
91 50/51P5.C 0 ~1 0 - operation characteristic of stage
1
5 of
protection
phase overcurrent
3
The current setting of stage 6 of
92 50/51P6.I_Set 0.05~200 15 A 0.001
phase overcurrent protection
The operating time setting of
93 50/51P6.t_Op 0 ~100 0.1 s 0.001 stage 6 of phase overcurrent
protection
The dropout time setting of
94 50/51P6.t_DropOut 0 ~100 0 s 0.001 stage 6 of phase overcurrent
protection
The logic setting for
enabling/disabling the voltage
control element of stage 6 of
phase overcurrent protection
Disabled: stage 6 of phase
50/51P6.En_Volt_Bl Disabled; overcurrent protection is not
95 Disabled - -
k Enabled controlled by the voltage control
element
Enabled: stage 6 of phase
overcurrent protection is
controlled by the voltage control
element
Non_Directional The setting used to select the
Non_Directio
96 50/51P6.Opt_Dir Forward - - directional mode of stage 6 of
nal
Reverse phase overcurrent protection.

PCS-9611S Feeder Relay 3-35


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The logic setting for
enabling/disabling the harmonic
control element of stage 6 of
phase overcurrent protection
Disabled: stage 6 of phase
50/51P6.En_Hm_Bl Disabled; overcurrent protection is not
97 Disabled - -
k Enabled controlled by the harmonic
control element

3 Enabled: stage 6 of phase


overcurrent protection is
controlled by the harmonic
control element
The logic setting for
Disabled;
98 50/51P6.En Enabled - - enabling/disabling the stage 6 of
Enabled
phase overcurrent protection
Enabling stage 6 of phase
overcurrent protection operate
50/51P6.Opt_Trp/Al Trp;
99 Trp - - to trip or alarm.
m Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
ANSILT; inverse-time operation
100 50/51P6.Opt_Curve IECDefTime - -
IECN; characteristic curve of stage 6 of
IECV; phase overcurrent protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine

3-36 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 6 of
50/51P6.Opt_Curve
101 DefTime; Inst - - phase overcurrent protection
_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
102 50/51P6.TMS 0.04~ 20 1 - 0.001 stage 6 of phase overcurrent
protection
3
The minimum operating time
103 50/51P6.tmin 0 ~10 0.02 s 0.001 setting of stage 6 of phase
overcurrent protection
The constant “k” of the
customized inverse-time
0.000
104 50/51P6.K 0.001~120 0.14 - operation characteristic of stage
1
6 of phase overcurrent
protection
The constant “α” of the
customized inverse-time
0.000
105 50/51P6.Alpha 0.01 ~3 0.02 - operation characteristic of stage
1
6 of phase overcurrent
protection
The constant “C” of the
customized inverse-time
0.000
106 50/51P6.C 0 ~1 0 - operation characteristic of stage
1
6 of phase overcurrent
protection

3.6 Earth Fault Overcurrent Protection (50/51G)


The normal operating power system is three-phase symmetrical, its zero-sequence current and
voltage are theoretically zero. Most of the faults are three-phase asymmetrical, according to the
asymmetry of the fault, various protections reflect sequence component principle can be
constituted. Earth fault overcurrent protection has been widely used in power systems, it can be
used for the fault conditions that zero-sequence fault current flows into the earth, including
single-phase earth fault and phase-to-phase short-circuit earth fault etc..

3.6.1 Function Description

The device can provide six stages of earth fault overcurrent protection with independent logic.
Each stage can be independently set as definite-time characteristics or inverse-time
characteristics. The dropout characteristics can be set as instantaneous dropout, definite-time

PCS-9611S Feeder Relay 3-37


Date: 2019-04-24
3 Protection Functions

dropout or inverse-time dropout. Users can choose whether it is blocked by the direction control
element or the harmonic control element, users can also choose whether it is controlled by cold
load pickup. The direction control element can be set as no direction, forward direction and
reverse direction. The zero-sequence current used by earth fault overcurrent protection can be
calculated zero-sequence current or the measured zero-sequence current, it can operate to trip or
alarm, it can be enabled or blocked by the external binary input.

Earth fault overcurrent protection can be enabled or disabled via the settings or binary input
signals, for some specific applications, the protection needs to be blocked by the external signal,
so the device provides a function block input signal to be used to block earth fault overcurrent
protection. The enabling and blocking logic of earth fault overcurrent protection is shown in the
3 figure below:

EN 50/51Gx.En &
50/51Gx.On

SIG 50/51Gx.Enable

&
SIG 50/51Gx.Block ≥1 50/51Gx.Blocked

SIG Fail_Device
&
50/51Gx.Valid

Figure 3.6-1 The enabling and blocking logic of earth fault overcurrent protection

The logic diagram of the fault detector element of earth fault overcurrent protection is as follows:

SET 3I0>0.95*[50/51Gx.3I0_Set] & 50/51Gx.Pkp


0 500ms
&
SIG 50/51Gx.On &
FD.Pkp
SIG 50/51Gx.Valid

EN [50/51Gx.Opt_Trp/Alm]=Alm

Figure 3.6-2 Logic diagram of the fault detector element of earth fault overcurrent protection

3.6.1.1 Direction Control Element

In order to ensure the selectivity of earth fault overcurrent protection, direction control element is
introduced. The setting [50/51Gx.Opt_Dir] (x=1~6) is used for users to select the directional mode
of each stage of earth fault overcurrent protection: no direction, forward direction and reverse
direction are selectable.

The operation boundary of the forward direction element can be set by [50/51G.DIR.phi_Min_Fwd]
and [50/51G.DIR.phi_Max_Fwd]. The operation boundary of the reverse direction element can be
set by [50/51G.DIR.phi_Min_Rev] and [50/51G.DIR.phi_Max_Rev].

3-38 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

-U0

[50/51G.DIR.phi_Min_Fwd]

Non-operating I0
area

Operating area in
[50/51G.DIR.phi_Max_Rev] forward direction

[50/51G.DIR.RCA]

Operating area in
reverse direction
3

[50/51G.DIR.phi_Max_Fwd]
Non-operating
area
[50/51G.DIR.phi_Min_Rev]

Figure 3.6-3 The direction element operation characteristics when zero-sequence voltage is polarized

Where:

The sensitivity angle of the direction control element (RCA) can be set by the setting
[50/51G.DIR.RCA].

The forward direction characteristic is:

-[50/51G.DIR.phi_Min_Fwd]<angle<[50/51G.DIR.phi_Max_Fwd]

The reverse direction characteristic is:

180-[50/51G.DIR.phi_Min_Rev]<angle<180+[50/51G.DIR.phi_Max_Rev]

The following table shows the relationship between the operating current, the polarized voltage
and the polarization mode.

Polarized
Polarization mode Operating current Angle difference
voltage
Zero-sequence Calculated residual current 3I0_Cal -3U0 angle=angle(-3U0)-angle(3I0_Cal)-RCA
voltage polarized Measured residual current 3I0_Ext -3U0 angle=angle(-3U0)-angle(3I0_Ext)-RCA

The logic diagram of the forward direction element and reverse direction element is as follows.

PCS-9611S Feeder Relay 3-39


Date: 2019-04-24
3 Protection Functions

EN [50/51G.En_VTS_Blk] &

>=1

SIG VTS.Alm

SIG 3I0_Ext, 3I0_Cal


& >=1

direction
Forward
criterion
50/51G.FwdDir.Op

SIG 3U0_Cal

3 EN [En_VT] &

SIG Prot.BI_En_VT

EN [50/51G.En_VTS_Blk] &

>=1

SIG VTS.Alm
& >=1
SIG 3I0_Ext, 3I0_Cal 50/51G.RevDir.Op
direction
Reverse
criterion

SIG 3U0_Cal

EN [En_VT] &

SIG Prot.BI_En_VT

Figure 3.6-4 Logic diagram of forward and reverse direction element of earth fault overcurrent protection

Where:

3I0_Ext is the measured residual current.

3I0_Cal is the calculated residual current.

3U0_Cal: the calculated residual voltage

3.6.1.2 Harmonic Control Element

Zero-sequence harmonic control element can be used together with earth fault overcurrent
protection when harmonic blocking is required, the zero-sequence current can be the calculated
zero-sequence current or the measured zero-sequence current.

When the percentage of second harmonic component to fundamental component of residual


current is greater than the setting [50/51G.HMB.K_Hm2], harmonic blocking element operates to
block stage x of earth fault protection if corresponding logic setting [50/51Gx.En_Hm_Blk] is
enabled.

3-40 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

When the fundamental zero-sequence current is greater than the setting [50/51G.HMB.I_Rls], the
harmonic blocking element is released.

The following figure shows the logic diagram of the harmonic control element of earth fault
overcurrent protection.

SET 3I0>[50/51G.HMB.I_Rls]

&
SIG 3I0_Ext or 3I0_Cal
50/51G.Hm_Op
Harmonic
blocking
logi c

3
SET 3I02/3I0>[50/51G.HMB.K_Hm2]

Figure 3.6-5 Logic diagram of harmonic control element of earth fault overcurrent protection

Where:

3I0_Ext, 3I0_Cal: the measured residual current and the calculated residual current

3I02: the 2nd harmonic residual current

3.6.1.3 Operation Characteristic

Earth fault overcurrent protection can operate without time delay or operate with a definite-time
limit, it can also operate with an inverse-time limit, the characteristic curve meets the IEC60255-3
and ANSI C37.112 standards. Earth fault overcurrent protection can support definite-time limit,
IEC & ANSI standard inverse time limit and user-defined inverse-time limit, users can select the
wanted operating curve by the setting [50/51Gx.Opt_Curve], the relationship between the value of
the setting and the curve is shown in the table below.

50/51Gx.Opt_Curve Time Characteristic k α c tr


ANSIE ANSI Extremely Inverse 28.2 2.0 0.1217 29.1
ANSIV ANSI Very inverse 19.61 2.0 0.491 21.6
ANSIN ANSI Normal Inverse 0.0086 0.02 0.0185 0.46
ANSIM ANSI Moderately Inverse 0.0515 0.02 0.114 4.85
ANSIDefTime ANSI Definite Time - - - -
ANSILTE ANSI Long Time Extremely Inverse 64.07 2.0 0.25 30
ANSILTV ANSI Long Time Very Inverse 28.55 2.0 0.712 13.46
ANSILT ANSI Long Time Inverse 0.086 0.02 0.185 4.6
IECN IEC Normal Inverse 0.14 0.02 0 -
IECV IEC Very inverse 13.5 1.0 0 -
IEC IEC Inverse 0.14 0.02 0 -
IECE IEC Extremely inverse 80.0 2.0 0 -
IECST IEC Short-time inverse 0.05 0.04 0 -
IECLT IEC Long-time inverse 120.0 1.0 0 -
IECDefTime IEC Definite Time - - - -
UserDefine Programmable

PCS-9611S Feeder Relay 3-41


Date: 2019-04-24
3 Protection Functions

Only when the setting [50/51Gx.Opt_Curve] is set as “UserDefine”, i.e. the user-defined
inverse-time characteristic is selected, the settings [50/51Gx.K], [50/51Gx.C] and [50/51Gx.Alpha]
are useful, the inverse-time operating curve is determined by the three settings.

 Without time delay

When I 0 > I 0 p , the protection operates immediately.

 Definite-time characteristic

When I 0 > I 0 p , the protection operates with a time delay of top (i.e. the value of the setting
[50/51Gx.t_Op]), and the operation characteristic curve is shown in the following figure:

3 t

t op

I0p I0

Figure 3.6-6 Definite-time operation characteristic curve of earth fault overcurrent protection

 Inverse-time characteristic

When I 0 > I 0 p , the inverse-time accumulator begins to accumulate, and the operating time is
affected by the applied current I 0 . The larger current is, the smaller the operating time is, but not
unlimited. When the current is large enough to a certain threshold ( I 0 p ), the inverse-time
operating time will not continue to decrease, then the operation characteristic becomes the
definite-time characteristic, and the operating time is tmin , i.e. the setting [50/51Gx.tmin]. The
inverse-time operation characteristic equation is:

 k 
t   
 c   TMS
(I 0 / I 0P )  1 

Where:

I 0 p is the current setting [50/51Gx.3I0_Set];


TMS is the inverse-time time multiplier, i.e. the setting [50/51Gx.TMS];

k is the inverse-time coefficient K, i.e. the setting [50/51Gx.K];


c is the inverse-time coefficient C, i.e. the setting [50/51Gx.C];

3-42 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

 is the inverse-time coefficient Alpha, i.e. the setting [50/51Gx.Alpha];

I is the measured zero-sequence current.

The inverse-time operation characteristic curve is shown as below:

t min

I0P ID I0

Figure 3.6-7 Inverse-time operation characteristic curve of earth fault overcurrent protection

When the applied zero-sequence current I 0 is not a fixed value, but changes with time, the
operating behavior of the protection is shown in the following equation:

T0
1
 t ( I )dt
0 0
1

Where:

T0 is the operating time of the protection element;

t(I0) is the theoretical operating time when the current is I 0 .

3.6.1.4 Dropout Characteristic

The supported dropout characteristics of the earth fault overcurrent protection include
instantaneous dropout, definite-time dropout and ANSI inverse-time dropout.

When the operating curve is selected as definite-time, IEC inverse-time or user-defined


inverse-time characteristic, the dropout characteristic can only be selected as instantaneous
dropout or definite-time dropout, if inverse-time dropout is selected, the alarm signal
"Fail_Settings" will be issued and the device will be blocked.

When the operating curve is selected as ANSI inverse-time characteristic, the dropout
characteristic can be selected as instantaneous dropout, definite-time dropout and ANSI
inverse-time dropout.

 Instantaneous dropout

PCS-9611S Feeder Relay 3-43


Date: 2019-04-24
3 Protection Functions

When I 0 <0.95* I 0 p , the protection drops out immediately.

 Definite-time dropout

When I 0 <0.95* I 0 p , the protection drops out with a time delay of tdr (i.e. the value of the
setting [50/51Gx.t_DropOut]), the dropout characteristic curve is shown in the following figure:

Start time

I0>I0p

3
Start
signal

Operating
signal

Protection
Operating threshold operate

Operating
counter

t dr t dr t dr
Dropout time setting
Dropout time
Dropout time

Figure 3.6-8 Definite-time dropout characteristic of earth fault overcurrent protection

 Inverse-time dropout

When I 0 > I 0 p , the inverse-time operating accumulator begins to accumulate, the accumulated
value after tp (Assuming tp is less than the theoretical operating time) is calculated according
to the following equation:

tp
1
Itp   t(I
0
0
dt
)

At this time, if I 0 <0.95* I 0 p , the protection element starts dropout, and the dropout characteristic
meets the following equation:

TR
1
I tp   dt  0
0
t R ( I )

Where:

3-44 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

TR is the dropout time;

tR( I ) is the dropout characteristic equation

When I 0 <0.95* I 0 p , the inverse-time dropout characteristic equation is as follows:

 tr 
tR   2
 TMS
1  ( I / I P ) 

Where:

IP is the current setting [50/51Gx.3I0_Set]; 3


TMS is the inverse-time factor, i.e. the setting [50/51Gx.TMS];

tr is the dropout time coefficient, it is the dropout time required for the current to drop to 0 after
the protection operates.

I 0 is the measured current.


When 0.95* I 0 p < I 0 < I 0 p , the accumulator will neither accumulate nor drop out

The inverse time dropout characteristic curve is shown in the figure below.

tr

I0 P I0

Figure 3.6-9 Inverse-time dropout characteristic curve of earth fault overcurrent protection

The correspondence between the start signal, operating signal, and operating accumulator in the
inverse-time dropout characteristic is shown in the figure below:

PCS-9611S Feeder Relay 3-45


Date: 2019-04-24
3 Protection Functions

Start time

I0>I0p

Start
signal

Operating
signal

3 Operating threshold
Protection
operate

Operating
counter

tr Dropout time coefficient


Dropout time
Dropout time

Figure 3.6-10 Inverse-time dropout characteristic of earth fault overcurrent protection

3.6.2 Function Block Diagram

50/51G

50/51Gx.Enable 50/51Gx.On

50/51Gx.Block 50/51Gx.Blocked

50/51Gx.Valid

50/51Gx.St

50/51Gx.Op

50/51Gx.Alm

50/51Gx.FwdDir.Op

50/51Gx.RevDir.Op

3.6.3 I/O Signal


Table 3.6-1 Input/output signals of earth fault overcurrent protection

No. Input signal Description


Stage x of earth fault overcurrent protection enabling input, it is triggered from
1 50/51Gx.Enable
binary input or programmable logic etc. (x=1~6)
Stage x of earth fault overcurrent protection blocking input, it is triggered from
2 50/51Gx.Block
binary input or programmable logic etc. (x=1~6)

3-46 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

No. Output signal Description


1 50/51Gx.On Stage x of earth fault overcurrent protection is enabled
2 50/51Gx.Blocked Stage x of earth fault overcurrent protection is blocked
3 50/51Gx.Valid Stage x of earth fault overcurrent protection is valid
4 50/51Gx.St Stage x of earth fault overcurrent protection starts
5 50/51Gx.Op Stage x of earth fault overcurrent protection operates
6 50/51Gx.Alm Stage x of earth fault overcurrent protection alarms
7 50/51G.FwdDir.Op The forward direction element of earth fault overcurrent protection operates
8 50/51G.RevDir.Op The reverse direction element of earth fault overcurrent protection operates

3.6.4 Logic
3
SET 3I0>[50/51Gx.3I0_Set]

SIG 50/51G.FwdDir.Op 50/51Gx.St


&
selection
Direction

SIG 50/51G.RevDir.Op & Timer


t
SET [50/51Gx.Opt_Dir] t

SIG 50/51G.HMB.Op &

EN [50/51Gx.En_Hm_Blk]

SIG 50/51Gx.Pkp
&
50/51Gx.Op
SET [50/51Gx.Opt_Trp/Alm]=Trp

&
50/51Gx.Alm
SET [50/51Gx.Opt_Trp/Alm]=Alm

Figure 3.6-11 Logic diagram of earth fault overcurrent protection

3.6.5 Settings
 Access path:

MainMenu  Settings  Protection Settings  ROC Settings

Table 3.6-2 Settings of earth fault overcurrent protection

Default Uni
No. Settings Range Step Description
value t
The relay characteristic angle
of the direction control
1 50/51G.DIR.RCA -180~179 45 deg 1
element of earth fault
overcurrent protection

PCS-9611S Feeder Relay 3-47


Date: 2019-04-24
3 Protection Functions

Default Uni
No. Settings Range Step Description
value t
The minimum boundary of the
50/51G.DIR.phi_Min_ forward direction element of
2 10~90 90 deg 1
Fwd earth fault overcurrent
protection
The maximum boundary of the
50/51G.DIR.phi_Max_ forward direction element of
3 10~90 90 deg 1
Fwd earth fault overcurrent
protection

3 50/51G.DIR.phi_Min_
The minimum boundary of the
reverse direction element of
4 10~90 90 deg 1
Rev earth fault overcurrent
protection
The maximum boundary of the
50/51G.DIR.phi_Max_ reverse direction element of
5 10~90 90 deg 1
Rev earth fault overcurrent
protection
The minimum operating
current setting for the direction
6 50/51G.DIR.I_Min (0.05~1)In 0.05 - 0.001
control element of earth fault
overcurrent protection
The minimum operating
voltage setting for the direction
7 50/51G.DIR.U_Min 1~10 4 V 0.001
control element of earth fault
overcurrent protection
Logic setting to determine the
behavior of earth fault
overcurrent protection when
VT circuit supervision function
is enabled and VT circuit
failure happens.
Disabled;
8 50/51G.En_VTS_Blk Disabled - - Disabled: earth fault
Enabled
overcurrent protection will not
effected by VT circuit failure
Enabled: voltage controlled
earth fault overcurrent
protection will be blocked by
VT circuit failure signal
The percent setting of the
harmonic control element of
9 50/51G.HMB.K_Hm2 0.1~1 0.2 - 0.001
earth fault overcurrent
protection

3-48 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default Uni
No. Settings Range Step Description
value t
The current setting for
releasing the harmonic control
10 50/51G.HMB.I_Rls 2~150 20 A 0.001
element of earth fault
overcurrent protection
The setting used to select the
residual current that used for
stage 1 of earth fault
Ext; overcurrent protection
11 50/51G1.Opt_3I0 Ext - -
Cal Ext: the measured residual
current
3
Cal: the calculated residual
current
The current setting of stage 1
12 50/51G1.3I0_Set 0.05~200 15 A 0.001 of earth fault overcurrent
protection
The operating time setting of
13 50/51G1.t_Op 0 ~100 0.1 s 0.001 stage 1 of earth fault
overcurrent protection
The dropout time setting of
14 50/51G1.t_DropOut 0 ~100 0 s 0.001 stage 1 of earth fault
overcurrent protection
The setting used to select the
directional mode of stage 1 of
Non_Direction
earth fault overcurrent
al; Non_Directio
15 50/51G1.Opt_Dir - - protection.
Forward; nal
1: no direction;
Reverse
2: forward direction;
3: reverse direction.
The logic setting for
enabling/disabling the
harmonic control element of
the stage 1 of earth fault
overcurrent protection
Disabled: stage 1 of earth fault
Disabled;
16 50/51G1.En_Hm_Blk Disabled - - overcurrent protection is not
Enabled
controlled by the harmonic
control element
Enabled: stage 1 of earth fault
overcurrent protection is
controlled by the harmonic
control element

PCS-9611S Feeder Relay 3-49


Date: 2019-04-24
3 Protection Functions

Default Uni
No. Settings Range Step Description
value t
The logic setting for
Disabled; enabling/disabling the stage 1
17 50/51G1.En Enabled - -
Enabled of earth fault overcurrent
protection
Enabling stage 1 earth fault
overcurrent protection operate
Trp;
18 50/51G1.Opt_Trp/Alm Trp - - to trip or alarm.
Alm
Trp: for tripping purpose

3 ANSIE;
Alm: for alarm purpose

ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
The setting for selecting the
ANSILTV;
inverse-time operation
ANSILT;
19 50/51G1.Opt_Curve IECDefTime - - characteristic curve of stage 1
IECN;
of earth fault overcurrent
IECV;
protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
characteristic curve of stage 1
Inst;
50/51G1.Opt_Curve_ of earth fault overcurrent
20 DefTime; Inst - -
DropOut protection
IDMT
Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
21 50/51G1.TMS 0.04~ 20 1 - 0.001 stage 1 of earth fault
overcurrent protection
The minimum operating time
22 50/51G1.tmin 0 ~10 0.02 s 0.001 setting of stage 1 of earth fault
overcurrent protection

3-50 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default Uni
No. Settings Range Step Description
value t
The constant “k” of the
customized inverse-time
23 50/51G1.K 0.001~120 0.14 - 0.0001 operation characteristic of
stage 1 of earth fault
overcurrent protection
The constant “α” of the
customized inverse-time
24 50/51G1.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of
stage 1 of
overcurrent protection
earth fault
3
The constant “C” of the
customized inverse-time
25 50/51G1.C 0 ~1 0 - 0.0001 operation characteristic of
stage 1 of earth fault
overcurrent protection
The setting used to select the
residual current that used for
stage 2 of earth fault
Ext; overcurrent protection
26 50/51G2.Opt_3I0 Ext - -
Cal Ext: the measured residual
current
Cal: the calculated residual
current
The current setting of stage 2
27 50/51G2.3I0_Set 0.05~200 15 A 0.001 of earth fault overcurrent
protection
The operating time setting of
28 50/51G2.t_Op 0 ~100 0.1 s 0.001 stage 2 of earth fault
overcurrent protection
The dropout time setting of
29 50/51G2.t_DropOut 0 ~100 0 s 0.001 stage 2 of earth fault
overcurrent protection
The setting used to select the
directional mode of stage 2 of
Non_Direction
earth fault overcurrent
al; Non_Directio
30 50/51G2.Opt_Dir - - protection.
Forward; nal
1: no direction;
Reverse
2: forward direction;
3: reverse direction.

PCS-9611S Feeder Relay 3-51


Date: 2019-04-24
3 Protection Functions

Default Uni
No. Settings Range Step Description
value t
The logic setting for
enabling/disabling the
harmonic control element of
the stage 2 of earth fault
overcurrent protection
Disabled: stage 2 of earth fault
Disabled;
31 50/51G2.En_Hm_Blk Disabled - - overcurrent protection is not
Enabled
controlled by the harmonic

3 control element
Enabled: stage 2 of earth fault
overcurrent protection is
controlled by the harmonic
control element
The logic setting for
Disabled; enabling/disabling the stage 2
32 50/51G2.En Enabled - -
Enabled of earth fault overcurrent
protection
Enabling stage 2 earth fault
overcurrent protection operate
Trp;
33 50/51G2.Opt_Trp/Alm Trp - - to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
The setting for selecting the
ANSILTV;
inverse-time operation
ANSILT;
34 50/51G2.Opt_Curve IECDefTime - - characteristic curve of stage 2
IECN;
of earth fault overcurrent
IECV;
protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine

3-52 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default Uni
No. Settings Range Step Description
value t
The setting for selecting the
inverse-time dropout
characteristic curve of stage 2
Inst;
50/51G2.Opt_Curve_ of earth fault overcurrent
35 DefTime; Inst - -
DropOut protection
IDMT
Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout

36 50/51G2.TMS 0.04~ 20 1 - 0.001


The time multiplier setting of
stage 2 of earth fault
3
overcurrent protection
The minimum operating time
37 50/51G2.tmin 0 ~10 0.02 s 0.001 setting of stage 2 of earth fault
overcurrent protection
The constant “k” of the
customized inverse-time
38 50/51G2.K 0.001~120 0.14 - 0.0001 operation characteristic of
stage 2 of earth fault
overcurrent protection
The constant “α” of the
customized inverse-time
39 50/51G2.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of
stage 2 of earth fault
overcurrent protection
The constant “C” of the
customized inverse-time
40 50/51G2.C 0 ~1 0 - 0.0001 operation characteristic of
stage 2 of earth fault
overcurrent protection
The setting used to select the
residual current that used for
stage 3 of earth fault
Ext; overcurrent protection
41 50/51G3.Opt_3I0 Ext - -
Cal Ext: the measured residual
current
Cal: the calculated residual
current
The current setting of stage 3
42 50/51G3.3I0_Set 0.05~200 15 A 0.001 of earth fault overcurrent
protection

PCS-9611S Feeder Relay 3-53


Date: 2019-04-24
3 Protection Functions

Default Uni
No. Settings Range Step Description
value t
The operating time setting of
43 50/51G3.t_Op 0 ~100 0.1 s 0.001 stage 3 of earth fault
overcurrent protection
The dropout time setting of
44 50/51G3.t_DropOut 0 ~100 0 s 0.001 stage 3 of earth fault
overcurrent protection
The setting used to select the
directional mode of stage 3 of
Non_Direction
3 45 50/51G3.Opt_Dir
al; Non_Directio
- -
earth
protection.
fault overcurrent

Forward; nal
1: no direction;
Reverse
2: forward direction;
3: reverse direction.
The logic setting for
enabling/disabling the
harmonic control element of
the stage 3 of earth fault
overcurrent protection
Disabled: stage 3 of earth fault
Disabled;
46 50/51G3.En_Hm_Blk Disabled - - overcurrent protection is not
Enabled
controlled by the harmonic
control element
Enabled: stage 3 of earth fault
overcurrent protection is
controlled by the harmonic
control element
The logic setting for
Disabled; enabling/disabling the stage 3
47 50/51G3.En Enabled - -
Enabled of earth fault overcurrent
protection
Enabling stage 3 earth fault
overcurrent protection operate
Trp;
48 50/51G3.Opt_Trp/Alm Trp - - to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose

3-54 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default Uni
No. Settings Range Step Description
value t
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
The setting for selecting the
ANSILTV;
inverse-time operation
ANSILT;
49 50/51G3.Opt_Curve IECDefTime - - characteristic curve of stage 3
IECN;
IECV;
of earth fault overcurrent 3
protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
characteristic curve of stage 3
Inst;
50/51G3.Opt_Curve_ of earth fault overcurrent
50 DefTime; Inst - -
DropOut protection
IDMT
Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
51 50/51G3.TMS 0.04~ 20 1 - 0.001 stage 3 of earth fault
overcurrent protection
The minimum operating time
52 50/51G3.tmin 0 ~10 0.02 s 0.001 setting of stage 3 of earth fault
overcurrent protection
The constant “k” of the
customized inverse-time
53 50/51G3.K 0.001~120 0.14 - 0.0001 operation characteristic of
stage 3 of earth fault
overcurrent protection
The constant “α” of the
customized inverse-time
54 50/51G3.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of
stage 3 of earth fault
overcurrent protection

PCS-9611S Feeder Relay 3-55


Date: 2019-04-24
3 Protection Functions

Default Uni
No. Settings Range Step Description
value t
The constant “C” of the
customized inverse-time
55 50/51G3.C 0 ~1 0 - 0.0001 operation characteristic of
stage 3 of earth fault
overcurrent protection
The setting used to select the
residual current that used for
stage 4 of earth fault

3 56 50/51G4.Opt_3I0
Ext;
Cal
Ext - -
overcurrent protection
Ext: the measured residual
current
Cal: the calculated residual
current
The current setting of stage 4
57 50/51G4.3I0_Set 0.05~200 15 A 0.001 of earth fault overcurrent
protection
The operating time setting of
58 50/51G4.t_Op 0 ~100 0.1 s 0.001 stage 4 of earth fault
overcurrent protection
The dropout time setting of
59 50/51G4.t_DropOut 0 ~100 0 s 0.001 stage 4 of earth fault
overcurrent protection
The setting used to select the
directional mode of stage 4 of
Non_Direction
earth fault overcurrent
al; Non_Directio
60 50/51G4.Opt_Dir - - protection.
Forward; nal
1: no direction;
Reverse
2: forward direction;
3: reverse direction.
The logic setting for
enabling/disabling the
harmonic control element of
the stage 4 of earth fault
overcurrent protection
Disabled: stage 4 of earth fault
Disabled;
61 50/51G4.En_Hm_Blk Disabled - - overcurrent protection is not
Enabled
controlled by the harmonic
control element
Enabled: stage 4 of earth fault
overcurrent protection is
controlled by the harmonic
control element

3-56 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default Uni
No. Settings Range Step Description
value t
The logic setting for
Disabled; enabling/disabling the stage 4
62 50/51G4.En Enabled - -
Enabled of earth fault overcurrent
protection
Enabling stage 4 earth fault
overcurrent protection operate
Trp;
63 50/51G4.Opt_Trp/Alm Trp - - to trip or alarm.
Alm
Trp: for tripping purpose

ANSIE;
Alm: for alarm purpose
3
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
The setting for selecting the
ANSILTV;
inverse-time operation
ANSILT;
64 50/51G4.Opt_Curve IECDefTime - - characteristic curve of stage 4
IECN;
of earth fault overcurrent
IECV;
protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
characteristic curve of stage 4
Inst;
50/51G4.Opt_Curve_ of earth fault overcurrent
65 DefTime; Inst - -
DropOut protection
IDMT
Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
66 50/51G4.TMS 0.04~ 20 1 - 0.001 stage 4 of earth fault
overcurrent protection
The minimum operating time
67 50/51G4.tmin 0 ~10 0.02 s 0.001 setting of stage 4 of earth fault
overcurrent protection

PCS-9611S Feeder Relay 3-57


Date: 2019-04-24
3 Protection Functions

Default Uni
No. Settings Range Step Description
value t
The constant “k” of the
customized inverse-time
68 50/51G4.K 0.001~120 0.14 - 0.0001 operation characteristic of
stage 4 of earth fault
overcurrent protection
The constant “α” of the
customized inverse-time
69 50/51G4.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of

3 stage 4 of
overcurrent protection
earth fault

The constant “C” of the


customized inverse-time
70 50/51G4.C 0 ~1 0 - 0.0001 operation characteristic of
stage 4 of earth fault
overcurrent protection
The setting used to select the
residual current that used for
stage 5 of earth fault
Ext; overcurrent protection
71 50/51G5.Opt_3I0 Ext - -
Cal Ext: the measured residual
current
Cal: the calculated residual
current
The current setting of stage 5
72 50/51G5.3I0_Set 0.05~200 15 A 0.001 of earth fault overcurrent
protection
The operating time setting of
73 50/51G5.t_Op 0 ~100 0.1 s 0.001 stage 5 of earth fault
overcurrent protection
The dropout time setting of
74 50/51G5.t_DropOut 0 ~100 0 s 0.001 stage 5 of earth fault
overcurrent protection
The setting used to select the
directional mode of stage 5 of
Non_Direction
earth fault overcurrent
al; Non_Directio
75 50/51G5.Opt_Dir - - protection.
Forward; nal
1: no direction;
Reverse
2: forward direction;
3: reverse direction.

3-58 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default Uni
No. Settings Range Step Description
value t
The logic setting for
enabling/disabling the
harmonic control element of
the stage 5 of earth fault
overcurrent protection
Disabled: stage 5 of earth fault
Disabled;
76 50/51G5.En_Hm_Blk Disabled - - overcurrent protection is not
Enabled
controlled by the harmonic
control element
Enabled: stage 5 of earth fault
3
overcurrent protection is
controlled by the harmonic
control element
The logic setting for
Disabled; enabling/disabling the stage 5
77 50/51G5.En Enabled - -
Enabled of earth fault overcurrent
protection
Enabling stage 5 earth fault
overcurrent protection operate
Trp;
78 50/51G5.Opt_Trp/Alm Trp - - to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
The setting for selecting the
ANSILTV;
inverse-time operation
ANSILT;
79 50/51G5.Opt_Curve IECDefTime - - characteristic curve of stage 5
IECN;
of earth fault overcurrent
IECV;
protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine

PCS-9611S Feeder Relay 3-59


Date: 2019-04-24
3 Protection Functions

Default Uni
No. Settings Range Step Description
value t
The setting for selecting the
inverse-time dropout
characteristic curve of stage 5
Inst;
50/51G5.Opt_Curve_ of earth fault overcurrent
80 DefTime; Inst - -
DropOut protection
IDMT
Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout

3 81 50/51G5.TMS 0.04~ 20 1 - 0.001


The time multiplier setting of
stage 5 of earth fault
overcurrent protection
The minimum operating time
82 50/51G5.tmin 0 ~10 0.02 s 0.001 setting of stage 5 of earth fault
overcurrent protection
The constant “k” of the
customized inverse-time
83 50/51G5.K 0.001~120 0.14 - 0.0001 operation characteristic of
stage 5 of earth fault
overcurrent protection
The constant “α” of the
customized inverse-time
84 50/51G5.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of
stage 5 of earth fault
overcurrent protection
The constant “C” of the
customized inverse-time
85 50/51G5.C 0 ~1 0 - 0.0001 operation characteristic of
stage 5 of earth fault
overcurrent protection
The setting used to select the
residual current that used for
stage 6 of earth fault
Ext; overcurrent protection
86 50/51G6.Opt_3I0 Ext - -
Cal Ext: the measured residual
current
Cal: the calculated residual
current
The current setting of stage 6
87 50/51G6.3I0_Set 0.05~200 15 A 0.001 of earth fault overcurrent
protection

3-60 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default Uni
No. Settings Range Step Description
value t
The operating time setting of
88 50/51G6.t_Op 0 ~100 0.1 s 0.001 stage 6 of earth fault
overcurrent protection
The dropout time setting of
89 50/51G6.t_DropOut 0 ~100 0 s 0.001 stage 6 of earth fault
overcurrent protection
The setting used to select the
directional mode of stage 6 of
Non_Direction

90 50/51G6.Opt_Dir
al; Non_Directio
- -
earth
protection.
fault overcurrent
3
Forward; nal
1: no direction;
Reverse
2: forward direction;
3: reverse direction.
The logic setting for
enabling/disabling the
harmonic control element of
the stage 6 of earth fault
overcurrent protection
Disabled: stage 6 of earth fault
Disabled;
91 50/51G6.En_Hm_Blk Disabled - - overcurrent protection is not
Enabled
controlled by the harmonic
control element
Enabled: stage 6 of earth fault
overcurrent protection is
controlled by the harmonic
control element
The logic setting for
Disabled; enabling/disabling the stage 6
92 50/51G6.En Enabled - -
Enabled of earth fault overcurrent
protection
Enabling stage 6 earth fault
overcurrent protection operate
Trp;
93 50/51G6.Opt_Trp/Alm Trp - - to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose

PCS-9611S Feeder Relay 3-61


Date: 2019-04-24
3 Protection Functions

Default Uni
No. Settings Range Step Description
value t
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
The setting for selecting the
ANSILTV;
inverse-time operation
ANSILT;
94 50/51G6.Opt_Curve IECDefTime - - characteristic curve of stage 6
3 IECN;
IECV;
of earth fault overcurrent
protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
characteristic curve of stage 6
Inst;
50/51G6.Opt_Curve_ of earth fault overcurrent
95 DefTime; Inst - -
DropOut protection
IDMT
Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
96 50/51G6.TMS 0.04~ 20 1 - 0.001 stage 6 of earth fault
overcurrent protection
The minimum operating time
97 50/51G6.tmin 0 ~10 0.02 s 0.001 setting of stage 6 of earth fault
overcurrent protection
The constant “k” of the
customized inverse-time
98 50/51G6.K 0.001~120 0.14 - 0.0001 operation characteristic of
stage 6 of earth fault
overcurrent protection
The constant “α” of the
customized inverse-time
99 50/51G6.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of
stage 6 of earth fault
overcurrent protection

3-62 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default Uni
No. Settings Range Step Description
value t
The constant “C” of the
customized inverse-time
100 50/51G6.C 0 ~1 0 - 0.0001 operation characteristic of
stage 6 of earth fault
overcurrent protection

3.7 Another Group of Earth Fault Overcurrent Protection


For the applications of some grounding transformers and station transformers that two sets of
residual currents are required, the device provides another group of earth fault overcurrent 3
protection.

3.7.1 Function Description


The device can provide six stages of another group of earth fault overcurrent protection with
independent logic. Each stage can be independently set as definite-time characteristics or
inverse-time characteristics. The dropout characteristics can be set as instantaneous dropout,
definite-time dropout or inverse-time dropout. The protection fixedly adopts the measured residual
current, the calculated residual current is not supported. It can operate to trip or alarm, it can be
enabled or blocked by the external binary input.

Another group of earth fault overcurrent protection can be enabled or disabled via the settings or
binary input signals, for some specific applications, the protection needs to be blocked by the
external signal, so the device provides a function block input signal to be used to block another
group of earth fault overcurrent protection. The enabling and blocking logic of another group of
earth fault overcurrent protection is shown in the figure below:

EN A.50/51Gx.En &
A.50/51Gx.On

SIG A.50/51Gx.Enable

&
SIG A.50/51Gx.Block ≥1 A.50/51Gx.Blocked

SIG Fail_Device
&
A.50/51Gx.Valid

Figure 3.7-1 The enabling and blocking logic of another group of earth fault overcurrent protection

The logic diagram of the fault detector element of another group of earth fault overcurrent
protection is as follows:

PCS-9611S Feeder Relay 3-63


Date: 2019-04-24
3 Protection Functions

SET 3I0>0.95*[A.50/51Gx.3I0_Set] & A.50/51Gx.Pkp


0 500ms
&
SIG A.50/51Gx.On &
FD.Pkp
SIG A.50/51Gx.Valid

EN [A.50/51Gx.Opt_Trp/Alm]=Alm

Figure 3.7-2 Logic diagram of the fault detector element of another group of earth fault overcurrent
protection

3.7.1.1 Operation Characteristic


3 Another group of earth fault overcurrent protection can operate without time delay or operate with
a definite-time limit, it can also operate with an inverse-time limit, the characteristic curve meets
the IEC60255-3 and ANSI C37.112 standards. Another group of earth fault overcurrent protection
can support definite-time limit, IEC & ANSI standard inverse time limit and user-defined
inverse-time limit, users can select the wanted operating curve by the setting
[A.50/51Gx.Opt_Curve], the relationship between the value of the setting and the curve is shown
in the table below.

A.50/51Gx.Opt_Curve Time Characteristic k α c tr


ANSIE ANSI Extremely Inverse 28.2 2.0 0.1217 29.1
ANSIV ANSI Very inverse 19.61 2.0 0.491 21.6
ANSIN ANSI Normal Inverse 0.0086 0.02 0.0185 0.46
ANSIM ANSI Moderately Inverse 0.0515 0.02 0.114 4.85
ANSIDefTime ANSI Definite Time - - - -
ANSILTE ANSI Long Time Extremely Inverse 64.07 2.0 0.25 30
ANSILTV ANSI Long Time Very Inverse 28.55 2.0 0.712 13.46
ANSILT ANSI Long Time Inverse 0.086 0.02 0.185 4.6
IECN IEC Normal Inverse 0.14 0.02 0 -
IECV IEC Very inverse 13.5 1.0 0 -
IEC IEC Inverse 0.14 0.02 0 -
IECE IEC Extremely inverse 80.0 2.0 0 -
IECST IEC Short-time inverse 0.05 0.04 0 -
IECLT IEC Long-time inverse 120.0 1.0 0 -
IECDefTime IEC Definite Time - - - -
UserDefine Programmable

Only when the setting [A.50/51Gx.Opt_Curve] is set as “UserDefine”, i.e. the user-defined
inverse-time characteristic is selected, the settings [A.50/51Gx.K], [A.50/51Gx.C] and
[A.50/51Gx.Alpha] are useful, the inverse-time operating curve is determined by the three
settings.

 Without time delay

When I 0 > I 0 p , the protection operates immediately.

3-64 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

 Definite-time characteristic

When I 0 > I 0 p , the protection operates with a time delay of top (i.e. the value of the setting
[A.50/51Gx.t_Op]), and the operation characteristic curve is shown in the following figure:

3
t op

I0p I0

Figure 3.7-3 Definite-time operation characteristic curve of another group of earth fault overcurrent
protection

 Inverse-time characteristic

When I 0 > I 0 p , the inverse-time accumulator begins to accumulate, and the operating time is
affected by the applied current I 0 . The operating time will decrease with the current increasing,
but the operating time shall not less than tmin , i.e. the setting [A.50/51Gx.tmin]. The inverse-time
operation characteristic equation is:

 k 
t   
 c   TMS
(I 0 / I 0P )  1 

Where:

I 0 p is the current setting [A.50/51Gx.3I0_Set];


TMS is the inverse-time time multiplier, i.e. the setting [A.50/51Gx.TMS];

k is the inverse-time coefficient K, i.e. the setting [A.50/51Gx.K];


c is the inverse-time coefficient C, i.e. the setting [A.50/51Gx.C];
 is the inverse-time coefficient Alpha, i.e. the setting [A.50/51Gx.Alpha];

I 0 is the measured zero-sequence current.


The inverse-time operation characteristic curve is shown as below:

PCS-9611S Feeder Relay 3-65


Date: 2019-04-24
3 Protection Functions

3 t min

I0P ID I0

Figure 3.7-4 Inverse-time operation characteristic curve of another group of earth fault overcurrent
protection

When the applied zero-sequence current I 0 is not a fixed value, but changes with time, the
operating behavior of the protection is shown in the following equation:

T0
1
 t ( I )dt
0 0
1

Where:

T0 is the operating time of the protection element;

t(I0) is the theoretical operating time when the current is I 0 .

3.7.1.2 Dropout Characteristic

The supported dropout characteristics of another group of earth fault overcurrent protection
include instantaneous dropout, definite-time dropout and ANSI inverse-time dropout.

When the operating curve is selected as definite-time, IEC inverse-time or user-defined


inverse-time characteristic, the dropout characteristic can only be selected as instantaneous
dropout or definite-time dropout, if inverse-time dropout is selected, the alarm signal
"Fail_Settings" will be issued and the device will be blocked.

When the operating curve is selected as ANSI inverse-time characteristic, the dropout
characteristic can be selected as instantaneous dropout, definite-time dropout and ANSI
inverse-time dropout.

 Instantaneous dropout

When I 0 <0.95* I 0 p , the protection drops out immediately.

3-66 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

 Definite-time dropout

When I 0 <0.95* I 0 p , the protection drops out with a time delay of tdr (i.e. the value of the
setting [A.50/51Gx.t_DropOut]), and the dropout characteristic curve is shown in the following
figure:

Start time

I0>I0p

Start
signal
3

Operating
signal

Protection
Operating threshold operate

Operating
counter

t dr t dr t dr
Dropout time setting
Dropout time
Dropout time

Figure 3.7-5 Definite-time dropout characteristic of another group of earth fault overcurrent protection

 Inverse-time dropout

When I 0 > I 0 p , the inverse-time operating accumulator begins to accumulate, the accumulated
value after tp (Assuming tp is less than the theoretical operating time) is calculated according
to the following equation:

tp
1
Itp   t(I
0
0
dt
)

At this time, if I 0 <0.95* I 0 p , the protection element starts dropout, and the dropout characteristic
meets the following equation:

TR
1
I tp   dt  0
0
t R ( I )

Where:

PCS-9611S Feeder Relay 3-67


Date: 2019-04-24
3 Protection Functions

TR is the dropout time;

tR( I ) is the dropout characteristic equation

When I 0 <0.95* I 0 p , the inverse-time dropout characteristic equation is as follows:

 tr 
tR   2
 TMS
1  ( I / I P ) 

Where:

3 IP is the current setting [A.50/51Gx.3I0_Set];

TMS is the inverse-time factor, i.e. the setting [A.50/51Gx.TMS];

tr is the dropout time coefficient, it is the dropout time required for the current to drop to 0 after
the protection operates.

I 0 is the measured current.


When 0.95* I 0 p < I 0 < I 0 p , the accumulator will neither accumulate nor drop out

The inverse time dropout characteristic curve is shown in the figure below.

tr

I0 P I0

Figure 3.7-6 Inverse-time dropout characteristic curve of another group of earth fault overcurrent
protection

The correspondence between the start signal, operating signal, and operating accumulator in the
inverse-time dropout characteristic is shown in the figure below:

3-68 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Start time

I0>I0p

Start
signal

Operating
signal

Operating threshold
Protection
operate
3
Operating
counter

tr Dropout time coefficient


Dropout time
Dropout time

Figure 3.7-7 Inverse-time dropout characteristic of another group of earth fault overcurrent protection

3.7.2 Function Block Diagram

A.50/51G

A.50/51Gx.On

A.50/51Gx.Enable A.50/51Gx.Blocked

A.50/51Gx.Block A.50/51Gx.Valid
A.50/51Gx.St

A.50/51Gx.Op

A.50/51Gx.Alm

3.7.3 I/O Signal


Table 3.7-1 Input/output signals of another group of earth fault overcurrent protection

No. Input signal Description


Stage x of another group of earth fault overcurrent protection enabling input, it
1 A.50/51Gx.Enable
is triggered from binary input or programmable logic etc. (x=1~6)
Stage x of another group of earth fault overcurrent protection blocking input, it
2 A.50/51Gx.Block
is triggered from binary input or programmable logic etc. (x=1~6)
No. Output signal Description
1 A.50/51Gx.On Stage x of another group of earth fault overcurrent protection is enabled
2 A.50/51Gx.Blocked Stage x of another group of earth fault overcurrent protection is blocked
3 A.50/51Gx.Valid Stage x of another group of earth fault overcurrent protection is valid

PCS-9611S Feeder Relay 3-69


Date: 2019-04-24
3 Protection Functions

No. Input signal Description


4 A.50/51Gx.St Stage x of another group of earth fault overcurrent protection starts
5 A.50/51Gx.Op Stage x of another group of earth fault overcurrent protection operates
6 A.50/51Gx.Alm Stage x of another group of earth fault overcurrent protection alarms

3.7.4 Logic

A.50/51Gx.St

Timer &
SET 3I0>[A.50/51Gx.3I0_Set] & A.50/51Gx.Op
t

3 SIG A.50/51Gx.Pkp
t

SET [A.50/51Gx.Opt_Trp/Alm] = Trp &


A.50/51Gx.Alm
SET [A.50/51Gx.Opt_Trp/Alm] = Alm

Figure 3.7-8 Logic diagram of another group of earth fault overcurrent protection

3.7.5 Settings
 Access path:

MainMenu  Settings  Protection Settings  ROC2 Settings

Table 3.7-2 Settings of another group of earth fault overcurrent protection

Default
No. Settings Range Unit Step Description
value
The current setting of
stage 1 of another group of
1 A.50/51G1.3I0_Set 0.05~200 15 A 0.001
earth fault overcurrent
protection
The operating time setting
of stage 1 of another group
2 A.50/51G1.t_Op 0 ~100 0.1 s 0.001
of earth fault overcurrent
protection
The dropout time setting of
stage 1 of another group of
3 A.50/51G1.t_DropOut 0 ~100 0 s 0.001
earth fault overcurrent
protection
The logic setting for
enabling/disabling the
Disabled;
4 A.50/51G1.En Enabled - - stage 1 of another group of
Enabled
earth fault overcurrent
protection

3-70 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
Enabling stage 1 of
another group of earth fault
Trp; overcurrent protection
5 A.50/51G1.Opt_Trp/Alm Trp - -
Alm operate to trip or alarm.
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
3
ANSIDefTime;
ANSILTE; The setting for selecting
ANSILTV; the inverse-time operation
ANSILT; characteristic curve of
6 A.50/51G1.Opt_Curve IECDefTime - -
IECN; stage 1 of another group of
IECV; earth fault overcurrent
IEC; protection.
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting
the inverse-time dropout
characteristic curve of
stage 1 of another group of
Inst; earth fault overcurrent
A.50/51G1.Opt_Curve_D
7 DefTime; Inst - - protection
ropOut
IDMT Inst: instantaneous
dropout
DefTime: definite-time
dropout
IDMT: inverse-time dropout
The time multiplier setting
of stage 1 of another group
8 A.50/51G1.TMS 0.04~ 20 1 - 0.001
of earth fault overcurrent
protection
The minimum operating
time setting of stage 1 of
9 A.50/51G1.tmin 0 ~10 0.02 s 0.001
another group of earth fault
overcurrent protection

PCS-9611S Feeder Relay 3-71


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The constant “k” of the
customized inverse-time
operation characteristic of
10 A.50/51G1.K 0.001~120 0.14 - 0.0001
stage 1 of another group of
earth fault overcurrent
protection
The constant “α” of the
customized inverse-time

3 11 A.50/51G1.Alpha 0.01 ~3 0.02 - 0.0001


operation characteristic of
stage 1 of another group of
earth fault overcurrent
protection
The constant “C” of the
customized inverse-time
operation characteristic of
12 A.50/51G1.C 0 ~1 0 - 0.0001
stage 1 of another group of
earth fault overcurrent
protection
The current setting of
stage 2 of another group of
13 A.50/51G2.3I0_Set 0.05~200 15 A 0.001
earth fault overcurrent
protection
The operating time setting
of stage 2 of another group
14 A.50/51G2.t_Op 0 ~100 0.1 s 0.001
of earth fault overcurrent
protection
The dropout time setting of
stage 2 of another group of
15 A.50/51G2.t_DropOut 0 ~100 0 s 0.001
earth fault overcurrent
protection
The logic setting for
enabling/disabling the
Disabled;
16 A.50/51G2.En Enabled - - stage 2 of another group of
Enabled
earth fault overcurrent
protection
Enabling stage 2 of
another group of earth fault
Trp; overcurrent protection
17 A.50/51G2.Opt_Trp/Alm Trp - -
Alm operate to trip or alarm.
Trp: for tripping purpose
Alm: for alarm purpose

3-72 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE; The setting for selecting
ANSILTV; the inverse-time operation
ANSILT; characteristic curve of
18 A.50/51G2.Opt_Curve IECDefTime - -
IECN;
IECV;
stage 2 of another group of
earth fault overcurrent
3
IEC; protection.
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting
the inverse-time dropout
characteristic curve of
stage 2 of another group of
Inst; earth fault overcurrent
A.50/51G2.Opt_Curve_D
19 DefTime; Inst - - protection
ropOut
IDMT Inst: instantaneous
dropout
DefTime: definite-time
dropout
IDMT: inverse-time dropout
The time multiplier setting
of stage 2 of another group
20 A.50/51G2.TMS 0.04~ 20 1 - 0.001
of earth fault overcurrent
protection
The minimum operating
time setting of stage 2 of
21 A.50/51G2.tmin 0 ~10 0.02 s 0.001
another group of earth fault
overcurrent protection
The constant “k” of the
customized inverse-time
operation characteristic of
22 A.50/51G2.K 0.001~120 0.14 - 0.0001
stage 2 of another group of
earth fault overcurrent
protection

PCS-9611S Feeder Relay 3-73


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The constant “α” of the
customized inverse-time
operation characteristic of
23 A.50/51G2.Alpha 0.01 ~3 0.02 - 0.0001
stage 2 of another group of
earth fault overcurrent
protection
The constant “C” of the
customized inverse-time

3 24 A.50/51G2.C 0 ~1 0 - 0.0001
operation characteristic of
stage 2 of another group of
earth fault overcurrent
protection
The current setting of
stage 3 of another group of
25 A.50/51G3.3I0_Set 0.05~200 15 A 0.001
earth fault overcurrent
protection
The operating time setting
of stage 3 of another group
26 A.50/51G3.t_Op 0 ~100 0.1 s 0.001
of earth fault overcurrent
protection
The dropout time setting of
stage 3 of another group of
27 A.50/51G3.t_DropOut 0 ~100 0 s 0.001
earth fault overcurrent
protection
The logic setting for
enabling/disabling the
Disabled;
28 A.50/51G3.En Enabled - - stage 3 of another group of
Enabled
earth fault overcurrent
protection
Enabling stage 3 of
another group of earth fault
Trp; overcurrent protection
29 A.50/51G3.Opt_Trp/Alm Trp - -
Alm operate to trip or alarm.
Trp: for tripping purpose
Alm: for alarm purpose

3-74 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE; The setting for selecting
ANSILTV; the inverse-time operation
ANSILT; characteristic curve of
30 A.50/51G3.Opt_Curve IECDefTime - -
IECN;
IECV;
stage 3 of another group of
earth fault overcurrent
3
IEC; protection.
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting
the inverse-time dropout
characteristic curve of
stage 3 of another group of
Inst; earth fault overcurrent
A.50/51G3.Opt_Curve_D
31 DefTime; Inst - - protection
ropOut
IDMT Inst: instantaneous
dropout
DefTime: definite-time
dropout
IDMT: inverse-time dropout
The time multiplier setting
of stage 3 of another group
32 A.50/51G3.TMS 0.04~ 20 1 - 0.001
of earth fault overcurrent
protection
The minimum operating
time setting of stage 3 of
33 A.50/51G3.tmin 0 ~10 0.02 s 0.001
another group of earth fault
overcurrent protection
The constant “k” of the
customized inverse-time
operation characteristic of
34 A.50/51G3.K 0.001~120 0.14 - 0.0001
stage 3 of another group of
earth fault overcurrent
protection

PCS-9611S Feeder Relay 3-75


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The constant “α” of the
customized inverse-time
operation characteristic of
35 A.50/51G3.Alpha 0.01 ~3 0.02 - 0.0001
stage 3 of another group of
earth fault overcurrent
protection
The constant “C” of the
customized inverse-time

3 36 A.50/51G3.C 0 ~1 0 - 0.0001
operation characteristic of
stage 3 of another group of
earth fault overcurrent
protection
The current setting of
stage 4 of another group of
37 A.50/51G4.3I0_Set 0.05~200 15 A 0.001
earth fault overcurrent
protection
The operating time setting
of stage 4 of another group
38 A.50/51G4.t_Op 0 ~100 0.1 s 0.001
of earth fault overcurrent
protection
The dropout time setting of
stage 4 of another group of
39 A.50/51G4.t_DropOut 0 ~100 0 s 0.001
earth fault overcurrent
protection
The logic setting for
enabling/disabling the
Disabled;
40 A.50/51G4.En Enabled - - stage 4 of another group of
Enabled
earth fault overcurrent
protection
Enabling stage 4 of
another group of earth fault
Trp; overcurrent protection
41 A.50/51G4.Opt_Trp/Alm Trp - -
Alm operate to trip or alarm.
Trp: for tripping purpose
Alm: for alarm purpose

3-76 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE; The setting for selecting
ANSILTV; the inverse-time operation
ANSILT; characteristic curve of
42 A.50/51G4.Opt_Curve IECDefTime - -
IECN;
IECV;
stage 4 of another group of
earth fault overcurrent
3
IEC; protection.
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting
the inverse-time dropout
characteristic curve of
stage 4 of another group of
Inst; earth fault overcurrent
A.50/51G4.Opt_Curve_D
43 DefTime; Inst - - protection
ropOut
IDMT Inst: instantaneous
dropout
DefTime: definite-time
dropout
IDMT: inverse-time dropout
The time multiplier setting
of stage 4 of another group
44 A.50/51G4.TMS 0.04~ 20 1 - 0.001
of earth fault overcurrent
protection
The minimum operating
time setting of stage 4 of
45 A.50/51G4.tmin 0 ~10 0.02 s 0.001
another group of earth fault
overcurrent protection
The constant “k” of the
customized inverse-time
operation characteristic of
46 A.50/51G4.K 0.001~120 0.14 - 0.0001
stage 4 of another group of
earth fault overcurrent
protection

PCS-9611S Feeder Relay 3-77


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The constant “α” of the
customized inverse-time
operation characteristic of
47 A.50/51G4.Alpha 0.01 ~3 0.02 - 0.0001
stage 4 of another group of
earth fault overcurrent
protection
The constant “C” of the
customized inverse-time

3 48 A.50/51G4.C 0 ~1 0 - 0.0001
operation characteristic of
stage 4 of another group of
earth fault overcurrent
protection
The current setting of
stage 5 of another group of
49 A.50/51G5.3I0_Set 0.05~200 15 A 0.001
earth fault overcurrent
protection
The operating time setting
of stage 5 of another group
50 A.50/51G5.t_Op 0 ~100 0.1 s 0.001
of earth fault overcurrent
protection
The dropout time setting of
stage 5 of another group of
51 A.50/51G5.t_DropOut 0 ~100 0 s 0.001
earth fault overcurrent
protection
The logic setting for
enabling/disabling the
Disabled;
52 A.50/51G5.En Enabled - - stage 5 of another group of
Enabled
earth fault overcurrent
protection
Enabling stage 5 of
another group of earth fault
Trp; overcurrent protection
53 A.50/51G5.Opt_Trp/Alm Trp - -
Alm operate to trip or alarm.
Trp: for tripping purpose
Alm: for alarm purpose

3-78 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE; The setting for selecting
ANSILTV; the inverse-time operation
ANSILT; characteristic curve of
54 A.50/51G5.Opt_Curve IECDefTime - -
IECN;
IECV;
stage 5 of another group of
earth fault overcurrent
3
IEC; protection.
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting
the inverse-time dropout
characteristic curve of
stage 5 of another group of
Inst; earth fault overcurrent
A.50/51G5.Opt_Curve_D
55 DefTime; Inst - - protection
ropOut
IDMT Inst: instantaneous
dropout
DefTime: definite-time
dropout
IDMT: inverse-time dropout
The time multiplier setting
of stage 5 of another group
56 A.50/51G5.TMS 0.04~ 20 1 - 0.001
of earth fault overcurrent
protection
The minimum operating
time setting of stage 5 of
57 A.50/51G5.tmin 0 ~10 0.02 s 0.001
another group of earth fault
overcurrent protection
The constant “k” of the
customized inverse-time
operation characteristic of
58 A.50/51G5.K 0.001~120 0.14 - 0.0001
stage 5 of another group of
earth fault overcurrent
protection

PCS-9611S Feeder Relay 3-79


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The constant “α” of the
customized inverse-time
operation characteristic of
59 A.50/51G5.Alpha 0.01 ~3 0.02 - 0.0001
stage 5 of another group of
earth fault overcurrent
protection
The constant “C” of the
customized inverse-time

3 60 A.50/51G5.C 0 ~1 0 - 0.0001
operation characteristic of
stage 5 of another group of
earth fault overcurrent
protection
The current setting of
stage 6 of another group of
61 A.50/51G6.3I0_Set 0.05~200 15 A 0.001
earth fault overcurrent
protection
The operating time setting
of stage 6 of another group
62 A.50/51G6.t_Op 0 ~100 0.1 s 0.001
of earth fault overcurrent
protection
The dropout time setting of
stage 6 of another group of
63 A.50/51G6.t_DropOut 0 ~100 0 s 0.001
earth fault overcurrent
protection
The logic setting for
enabling/disabling the
Disabled;
64 A.50/51G6.En Enabled - - stage 6 of another group of
Enabled
earth fault overcurrent
protection
Enabling stage 6 of
another group of earth fault
Trp; overcurrent protection
65 A.50/51G6.Opt_Trp/Alm Trp - -
Alm operate to trip or alarm.
Trp: for tripping purpose
Alm: for alarm purpose

3-80 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE; The setting for selecting
ANSILTV; the inverse-time operation
ANSILT; characteristic curve of
66 A.50/51G6.Opt_Curve IECDefTime - -
IECN;
IECV;
stage 6 of another group of
earth fault overcurrent
3
IEC; protection.
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting
the inverse-time dropout
characteristic curve of
stage 6 of another group of
Inst; earth fault overcurrent
A.50/51G6.Opt_Curve_D
67 DefTime; Inst - - protection
ropOut
IDMT Inst: instantaneous
dropout
DefTime: definite-time
dropout
IDMT: inverse-time dropout
The time multiplier setting
of stage 6 of another group
68 A.50/51G6.TMS 0.04~ 20 1 - 0.001
of earth fault overcurrent
protection
The minimum operating
time setting of stage 6 of
69 A.50/51G6.tmin 0 ~10 0.02 s 0.001
another group of earth fault
overcurrent protection
The constant “k” of the
customized inverse-time
operation characteristic of
70 A.50/51G6.K 0.001~120 0.14 - 0.0001
stage 6 of another group of
earth fault overcurrent
protection

PCS-9611S Feeder Relay 3-81


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The constant “α” of the
customized inverse-time
operation characteristic of
71 A.50/51G6.Alpha 0.01 ~3 0.02 - 0.0001
stage 6 of another group of
earth fault overcurrent
protection
The constant “C” of the
customized inverse-time

3 72 A.50/51G6.C 0 ~1 0 - 0.0001
operation characteristic of
stage 6 of another group of
earth fault overcurrent
protection

3.8 Negative-sequence Overcurrent Protection (50/51Q)


When a phase-to-phase phase fault occurs in the system, the fault current is small, and the phase
current criterion may not be able to detect the fault. At this time, the negative-sequence
overcurrent protection with higher sensitivity can be used. Negative-sequence overcurrent
protection can also be used to detect the broken phase operation or load unbalance.

3.8.1 Function Description


The device can provide two stages of negative-sequence overcurrent protection with independent
logic. Each stage can be independently set as definite-time characteristics or inverse-time
characteristics. The dropout characteristics can be set as instantaneous dropout, definite-time
dropout or inverse-time dropout. For a double-circuit or a ring network line, the negative-sequence
fault current may have different flow direction. Considering the protection selectivity, the
negative-sequence overcurrent protection can be blocked by the direction control element.
Negative-sequence overcurrent protection can operate to trip or alarm, it can be enabled or
blocked by the external binary input.

Negative-sequence overcurrent protection can be enabled or disabled via the settings or binary
input signals, for some specific applications, the protection needs to be blocked by the external
signal, so the device provides a function block input signal to be used to block negative-sequence
overcurrent protection. The enabling and blocking logic of negative-sequence overcurrent
protection is shown in the figure below:

3-82 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

EN [50/51Qx.En] &
50/51Qx.On

SIG 50/51Qx.Enable

&
SIG 50/51Qx.Block ≥1 50/51Qx.Blocked

SIG Fail_Device
&
50/51Qx.Valid

Figure 3.8-1 The enabling and blocking logic of negative-sequence overcurrent protection
3
The logic diagram of the fault detector element of negative-sequence overcurrent protection is as
follows:

SET I2>0.95×[50/51Qx.I2_Set] & 50/51Qx.Pkp


0 500ms &
SIG 50/51Qx.On &
FD.Pkp
SIG 50/51Qx.Valid

SET [50/51Qx.Opt_Trp/Alm]=Alm

Figure 3.8-2 Logic diagram of the fault detector element of negative-sequence overcurrent protection

3.8.1.1 Direction Control Element

In order to ensure the selectivity of negative-sequence overcurrent protection, direction control


element is introduced. The setting [50/51Qx.Opt_Dir] (x=1 and 2) is used for users to select the
directional mode of each stage of negative-sequence overcurrent protection: no direction, forward
direction and reverse direction are selectable.

The operation boundary of the forward direction element can be set by [50/51Q.DIR.phi_Min_Fwd]
and [50/51Q.DIR.phi_Max_Fwd]. The operation boundary of the reverse direction element can be
set by [50/51Q.DIR.phi_Min_Rev] and [50/51Q.DIR.phi_Max_Rev].

For the direction control element of negative-sequence overcurrent protection, the


negative-sequence voltage is polarized, the operation characteristic is shown as below.

PCS-9611S Feeder Relay 3-83


Date: 2019-04-24
3 Protection Functions

-U2

[50/51Q.DIR.phi_Min_Fwd]

Non-operating I2
area
[50/51Q.DIR.phi_Max_Rev]
Operating area in
forward direction

[50/51Q.DIR.RCA]

3 Operating area in
reverse direction

[50/51Q.DIR.phi_Max_Fwd]
Non-operating
area

[50/51Q.DIR.phi_Min_Rev]

Figure 3.8-3 The direction element operation characteristics of negative-sequence overcurrent protection

Where:

The sensitivity angle of the direction control element (RCA) can be set by the setting
[50/51Q.DIR.RCA].

The forward direction characteristic is:


-[50/51Q.DIR.phi_Min_Fwd]<angle<[50/51Q.DIR.phi_Max_Fwd]

The reverse direction characteristic is:


180-[50/51Q.DIR.phi_Min_Rev]<angle<180+[50/51Q.DIR.phi_Max_Rev]

The following table shows the relationship between the operating current, the polarized voltage
and the polarization mode.

Polarized
Polarization mode Operating current Angle difference
voltage
Negative-sequence
Negative-sequence current I2 -U2 Angle=Angle(-U2)-Angle(I2)-RCA
voltage polarized

The logic diagram of the forward direction element and reverse direction element is as follows.

3-84 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

EN [50/51Q.En_VTS_Blk] &

>=1

SIG VTS.Alm
& >=1
SIG I2 50/51Q.FwdDir.Op

direction
Forward
criterion
SIG U2

EN [En_VT] & 3
SIG Prot.BI_En_VT

EN [50/51Q.En_VTS_Blk] &

>=1

SIG VTS.Alm
& >=1
SIG I2 50/51Q.RevDir.Op
direction
Reverse
criterion

SIG U2

EN [En_VT] &

SIG Prot.BI_En_VT

Figure 3.8-4 Logic diagram of forward and reverse direction element of negative-sequence overcurrent
protection

3.8.1.2 Operation Characteristic

Negative-sequence overcurrent protection can operate instantaneously or operate with a


definite-time limit, it can also operate with an inverse-time limit, the characteristic curve meets the
IEC60255-3 and ANSI C37.112 standards. Negative-sequence overcurrent protection can support
definite-time limit, IEC & ANSI standard inverse time limit and user-defined inverse-time limit,
users can select the wanted operating curve by the setting [50/51Qx.Opt_Curve] (x=1 or 2), the
relationship between the value of the setting and the curve is shown in the table below.

50/51Qx.Opt_Curve Time Characteristic k α c tr


ANSIE ANSI Extremely Inverse 28.2 2.0 0.1217 29.1
ANSIV ANSI Very inverse 19.61 2.0 0.491 21.6
ANSIN ANSI Normal Inverse 0.0086 0.02 0.0185 0.46
ANSIM ANSI Moderately Inverse 0.0515 0.02 0.114 4.85
ANSIDefTime ANSI Definite Time - - - -

PCS-9611S Feeder Relay 3-85


Date: 2019-04-24
3 Protection Functions

50/51Qx.Opt_Curve Time Characteristic k α c tr


ANSILTE ANSI Long Time Extremely Inverse 64.07 2.0 0.25 30
ANSILTV ANSI Long Time Very Inverse 28.55 2.0 0.712 13.46
ANSILT ANSI Long Time Inverse 0.086 0.02 0.185 4.6
IECN IEC Normal Inverse 0.14 0.02 0 -
IECV IEC Very inverse 13.5 1.0 0 -
IEC IEC Inverse 0.14 0.02 0 -
IECE IEC Extremely inverse 80.0 2.0 0 -
IECST IEC Short-time inverse 0.05 0.04 0 -
IECLT IEC Long-time inverse 120.0 1.0 0 -
3 IECDefTime IEC Definite Time - - - -
UserDefine Programmable

Only when the setting [50/51Qx.Opt_Curve] is set as “UserDefine”, i.e. the user-defined
inverse-time characteristic is selected, the settings [50/51Qx.K], [50/51Qx.C] and [50/51Qx.Alpha]
are useful, the inverse-time operating curve is determined by the three settings.

 Without time delay (Instantaneously)

When I 2 > I 2 p , the protection operates immediately.

 Definite-time characteristic

When I 2 > I 2 p , the protection operates with a time delay of top (i.e. the value of the setting
[50/51Qx.t_Op]), and the operation characteristic curve is shown in the following figure:

t op

I2p I2

Figure 3.8-5 Definite-time operation characteristic curve of negative-sequence overcurrent protection

 Inverse-time characteristic

3-86 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

When I 2 > I 2 p , the inverse-time accumulator begins to accumulate, and the operating time is
affected by the applied current I 2 . The operating time will decrease with the current increasing,
but the operating time shall not less than tmin , i.e. the setting [50/51Qx.tmin]. The inverse-time
operation characteristic equation is:

Where:

I 2 p is the current setting [50/51Qx.I2_Set]; 3


TMS is the inverse-time time multiplier, i.e. the setting [50/51Qx.TMS];

k is the inverse-time coefficient K, i.e. the setting [50/51Qx.K];


c is the inverse-time coefficient C, i.e. the setting [50/51Qx.C];
 is the inverse-time coefficient Alpha, i.e. the setting [50/51Qx.Alpha];

I 2 is the measured negative-sequence overcurrent current.


The inverse-time operation characteristic curve is shown as below:

t min

I2P ID I2

Figure 3.8-6 Inverse-time operation characteristic curve of negative-sequence overcurrent protection

When the applied negative-sequence overcurrent current I 2 is not a fixed value, but changes
with time, the operating behavior of the protection is shown in the following equation:

PCS-9611S Feeder Relay 3-87


Date: 2019-04-24
3 Protection Functions

Where:

T0 is the operating time of the protection element;

t(I2) is the theoretical operating time when the current is I2 .


3.8.1.3 Dropout Characteristic

The supported dropout characteristics of the negative-sequence overcurrent protection include


instantaneous dropout, definite-time dropout and ANSI inverse-time dropout.

When the operating curve is selected as definite-time, IEC inverse-time or user-defined


inverse-time characteristic, the dropout characteristic can only be selected as instantaneous
3 dropout or definite-time dropout, if inverse-time dropout is selected, the alarm signal
"Fail_Settings" will be issued and the device will be blocked.

When the operating curve is selected as ANSI inverse-time characteristic, the dropout
characteristic can be selected as instantaneous dropout, definite-time dropout and ANSI
inverse-time dropout.

 Instantaneous dropout

When I 2 <0.95* I 2 p , the protection drops out immediately.

 Definite-time dropout

When I 2 <0.95* I 2 p , the protection drops out with a time delay of tdr (i.e. the value of the
setting [50/51Qx.t_DropOut]), and the dropout characteristic curve is shown in the following
figure:

3-88 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Start time

I2>I2p

Start
signal

Operating
signal
3
Protection
Operating threshold operate

Operating
counter

t dr t dr t dr
Dropout time setting
Dropout time
Dropout time

Figure 3.8-7 Definite-time dropout characteristic of negative-sequence overcurrent protection

 Inverse-time dropout

When I 2 > I 2 p , the inverse-time operating accumulator begins to accumulate, the accumulated
value after tp (Assuming tp is less than the theoretical operating time) is calculated according
to the following equation:

tp
1
I tp   dt
0
t ( I 2 )

At this time, if I 2 <0.95* I 2 p , the protection element starts dropout, and the dropout characteristic
meets the following equation:

TR
1
I tp   dt  0
0
tR ( I 2 )

Where:

TR is the dropout time;

tR( I 2 ) is the dropout characteristic equation

PCS-9611S Feeder Relay 3-89


Date: 2019-04-24
3 Protection Functions

When I 2 <0.95* I 2 p , the inverse-time dropout characteristic equation is as follows:

Where:

I 2 p is the current setting [50/51Qx.I2_Set];

3 TMS is the inverse-time factor, i.e. the setting [50/51Qx.TMS];

tr is the dropout time coefficient, it is the dropout time required for the current to drop to 0 after
the protection operates.

I 2 is the measured current.

When 0.95* I 2 p < I 2 < I 2 p , the accumulator will neither accumulate nor drop out

The inverse time dropout characteristic curve is shown in the figure below.

tr

Figure 3.8-8 Inverse-time dropout characteristic curve of negative-sequence overcurrent protection

The correspondence between the start signal, operating signal, and operating accumulator in the
inverse-time dropout characteristic is shown in the figure below:

3-90 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Start time

I2>I2p

Start
signal

Operating
signal

Operating threshold
Protection
operate
3
Operating
counter

tr Dropout time coefficient


Dropout time
Dropout time

Figure 3.8-9 Inverse-time dropout characteristic of negative-sequence overcurrent protection

3.8.2 Function Block Diagram

50/51Q

50/51Qx.On
50/51Qx.Enable
50/51Qx.Blocked
50/51Qx.Block
50/51Qx.Valid

50/51Qx.St
50/51Qx.Op

50/51Qx.Alm

50/51Q.FwdDir.Op

50/51Q.RevDir.Op

3.8.3 I/O Signal


Table 3.8-1 Input/output signals of negative-sequence overcurrent protection

No. Input signal Description


Stage x of negative-sequence overcurrent protection enabling input, it is
1 50/51Qx.Enable
triggered from binary input or programmable logic etc. (x=1~2)
Stage x of negative-sequence overcurrent protection blocking input, it is
2 50/51Qx.Block
triggered from binary input or programmable logic etc. (x=1~2)
No. Output signal Description
1 50/51Qx.On Stage x of negative-sequence overcurrent protection is enabled

PCS-9611S Feeder Relay 3-91


Date: 2019-04-24
3 Protection Functions

No. Input signal Description


2 50/51Qx.Blocked Stage x of negative-sequence overcurrent protection is blocked
3 50/51Qx.Valid Stage x of negative-sequence overcurrent protection is valid
4 50/51Qx.St Stage x of negative-sequence overcurrent protection starts
5 50/51Qx.Op Stage x of negative-sequence overcurrent protection operates
6 50/51Qx.Alm Stage x of negative-sequence overcurrent protection alarms
The forward direction element of negative-sequence overcurrent protection
7 50/51Q.FwdDir.Op
operates
The reverse direction element of negative-sequence overcurrent protection
8 50/51Q.RevDir.Op
operates

3 3.8.4 Logic

SET I2>[50/51Qx.I2_Set]
50/51Qx.St
SIG 50/51Q.FwdDir.Op
&
& Timer
selection
Direction

t
SIG 50/51Q.RevDir.Op
t
SET [50/51Qx.Opt_Dir]

SIG 50/51Qx.Pkp
&
50/51Qx.Op
SET [50/51Qx.Opt_Trp/Alm]=Trp

&
50/51Qx.Alm
SET [50/51Qx.Opt_Trp/Alm]=Alm

Figure 3.8-10 Logic diagram of negative-sequence overcurrent protection

3.8.5 Settings
 Access path:

MainMenu  Settings  Protection Settings  NegOC Settings

Table 3.8-2 Settings of negative-sequence overcurrent protection

Default
No. Settings Range Unit Step Description
value
The relay characteristic angle
of the direction control
1 50/51Q.DIR.RCA -180~179 45 deg 1
element of negative-sequence
overcurrent protection
The minimum boundary of the
50/51Q.DIR.phi_Min_ forward direction element of
2 10~90 90 deg 1
Fwd negative-sequence
overcurrent protection

3-92 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The maximum boundary of the
50/51Q.DIR.phi_Max forward direction element of
3 10~90 90 deg 1
_Fwd negative-sequence
overcurrent protection
The minimum boundary of the
50/51Q.DIR.phi_Min_ reverse direction element of
4 10~90 90 deg 1
Rev negative-sequence
overcurrent protection

50/51Q.DIR.phi_Max
The maximum boundary of the
reverse direction element of
3
5 10~90 90 deg 1
_Rev negative-sequence
overcurrent protection
The minimum operating
current setting for the direction
6 50/51Q.DIR.I_Min (0.05~1)In 0.05 - 0.001 control element of
negative-sequence
overcurrent protection
The minimum operating
voltage setting for the direction
7 50/51Q.DIR.U_Min 1.0~10.0 4 V 0.001 control element of
negative-sequence
overcurrent protection
Logic setting to determine the
behavior of
negative-sequence
overcurrent protection when
VT circuit supervision function
is enabled and VT circuit
failure happens.
Disabled;
8 50/51Q.En_VTS_Blk Disabled - - Disabled: negative-sequence
Enabled
overcurrent protection will not
effected by VT circuit failure
Enabled: voltage controlled
negative-sequence
overcurrent protection will be
blocked by VT circuit failure
signal
The current setting of stage 1
9 50/51Q1.I2_Set 0.05~200 15 A 0.001 of negative-sequence
overcurrent protection

PCS-9611S Feeder Relay 3-93


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The operating time setting of
10 50/51Q1.t_Op 0.03 ~100 0.1 s 0.001 stage 1 of negative-sequence
overcurrent protection
The dropout time setting of
11 50/51Q1.t_DropOut 0 ~100 0 s 0.001 stage 1 of negative-sequence
overcurrent protection
The setting used to select the
directional mode of stage 1 of
Non_Direction
3 12 50/51Q1.Opt_Dir
al Non_Directio
- -
negative-sequence
overcurrent protection.
Forward nal
1: no direction;
Reverse
2: forward direction;
3: reverse direction.
The logic setting for
Disabled; enabling/disabling the stage 1
13 50/51Q1.En Enabled - -
Enabled of negative-sequence
overcurrent protection
Enabling stage 1 of
negative-sequence
Trp; overcurrent protection operate
14 50/51Q1.Opt_Trp/Alm Trp - -
Alm to trip or alarm.
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
The setting for selecting the
ANSILTV;
inverse-time operation
ANSILT;
15 50/51Q1.Opt_Curve IECDefTime - - characteristic curve of stage 1
IECN;
of negative-sequence
IECV;
overcurrent protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine

3-94 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The setting for selecting the
inverse-time dropout
characteristic curve of stage 1
Inst;
50/51Q1.Opt_Curve_ of negative-sequence
16 DefTime; Inst - -
DropOut overcurrent protection
IDMT
Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout

17 50/51Q1.TMS 0.04~ 20 1 - 0.001


The time multiplier setting of
stage 1 of negative-sequence
3
overcurrent protection
The minimum operating time
setting of stage 1 of
18 50/51Q1.tmin 0 ~10 0.02 s 0.001
negative-sequence
overcurrent protection
The constant “k” of the
customized inverse-time
19 50/51Q1.K 0.001~120 0.14 - 0.0001 operation characteristic of
stage 1 of negative-sequence
overcurrent protection
The constant “α” of the
customized inverse-time
20 50/51Q1.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of
stage 1 of negative-sequence
overcurrent protection
The constant “C” of the
customized inverse-time
21 50/51Q1.C 0 ~1 0 - 0.0001 operation characteristic of
stage 1 of negative-sequence
overcurrent protection
The current setting of stage 2
22 50/51Q2.I2_Set 0.05~200 15 A 0.001 of negative-sequence
overcurrent protection
The operating time setting of
23 50/51Q2.t_Op 0.03 ~100 0.1 s 0.001 stage 2 of negative-sequence
overcurrent protection
The dropout time setting of
24 50/51Q2.t_DropOut 0 ~100 0 s 0.001 stage 2 of negative-sequence
overcurrent protection

PCS-9611S Feeder Relay 3-95


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The setting used to select the
directional mode of stage 2 of
Non_Direction
negative-sequence
al Non_Directio
25 50/51Q2.Opt_Dir - - overcurrent protection.
Forward nal
1: no direction;
Reverse
2: forward direction;
3: reverse direction.
The logic setting for

3 26 50/51Q2.En
Disabled;
Enabled
Enabled - -
enabling/disabling the stage 2
of negative-sequence
overcurrent protection
Enabling stage 2 of
negative-sequence
Trp; overcurrent protection operate
27 50/51Q2.Opt_Trp/Alm Trp - -
Alm to trip or alarm.
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
The setting for selecting the
ANSILTV;
inverse-time operation
ANSILT;
28 50/51Q2.Opt_Curve IECDefTime - - characteristic curve of stage 2
IECN;
of negative-sequence
IECV;
overcurrent protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
characteristic curve of stage 2
Inst;
50/51Q2.Opt_Curve_ of negative-sequence
29 DefTime; Inst - -
DropOut overcurrent protection
IDMT
Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout

3-96 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The time multiplier setting of
30 50/51Q2.TMS 0.04~ 20 1 - 0.001 stage 2 of negative-sequence
overcurrent protection
The minimum operating time
setting of stage 2 of
31 50/51Q2.tmin 0 ~10 0.02 s 0.001
negative-sequence
overcurrent protection
The constant “k” of the

32 50/51Q2.K 0.001~120 0.14 - 0.0001


customized
operation
inverse-time
characteristic of
3
stage 2 of negative-sequence
overcurrent protection
The constant “α” of the
customized inverse-time
33 50/51Q2.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of
stage 2 of negative-sequence
overcurrent protection
The constant “C” of the
customized inverse-time
34 50/51Q2.C 0 ~1 0 - 0.0001 operation characteristic of
stage 2 of negative-sequence
overcurrent protection

3.9 Sensitive Earth Fault Protection (50/51SEF)


If a single-phase earth fault occurs in some non-effectively grounded systems, the amplitude of
the earth current is small due to the large ground resistance, so it is difficult to detect by the
ordinary CTs. Sensitive earth fault protection using high-precision CT can effectively detect the
earth current.

3.9.1 Function Description

The device can provide six stages of sensitive earth fault protection with independent logic. Each
stage can be independently set as definite-time characteristics or inverse-time characteristics.
The dropout characteristics can be set as instantaneous dropout, definite-time dropout or
inverse-time dropout. Users can choose whether it is blocked by the direction control element.
The direction control element can be set as no direction, forward direction and reverse direction.
The zero-sequence current used by sensitive earth fault protection is the measured
zero-sequence current from the high-precision CT. Sensitive earth fault protection can operate to
trip or alarm, it can be enabled or blocked by the external binary input.

Sensitive earth fault protection can be enabled or disabled via the settings or binary input signals,
for some specific applications, the protection needs to be blocked by the external signal, so the
device provides a function block input signal to be used to block sensitive earth fault protection.

PCS-9611S Feeder Relay 3-97


Date: 2019-04-24
3 Protection Functions

The enabling and blocking logic of sensitive earth fault protection is shown in the figure below:

EN 50/51SEFx.En &
50/51SEFx.On

SIG 50/51SEFx.Enable

&
SIG 50/51SEFx.Block ≥1 50/51SEFx.Blocked

SIG Fail_Device
&
50/51SEFx.Valid

3
Figure 3.9-1 The enabling and blocking logic of sensitive earth fault protection

The logic diagram of the fault detector element of sensitive earth fault protection is as follows:

SET Isef>0.95*[50/51SEFx.3I0_Set] & 50/51SEFx.Pkp


0 500ms
&
SIG 50/51SEFx.On &
FD.Pkp
SIG 50/51SEFx.Valid

EN [50/51SEFx.Opt_Trp/Alm]=Alm

Figure 3.9-2 Logic diagram of the fault detector element of sensitive earth fault protection

3.9.1.1 Direction Control Element

In order to ensure the selectivity of sensitive earth fault protection, direction control element is
introduced. The setting [50/51SEFx.Opt_Dir] (x: 1~6) is used for users to select the directional
mode of each stage of sensitive earth fault protection: no direction, forward direction and reverse
direction are selectable.

3-98 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

-U0

[50/51SEF.DIR.phi_Min_Fwd]

Non-operating Isef
area

Operating area in
[50/51SEF.DIR.phi_Max_Rev] forward direction

[50/51SEF.DIR.RCA] 3
Operating area in
reverse direction

[50/51SEF.DIR.phi_Max_Fwd]

Non-operating
area
[50/51SEF.DIR.phi_Min_Rev]

Figure 3.9-3 The direction element operation characteristics of sensitive earth fault protection

Where:

The sensitivity angle of the direction control element (RCA) can be set by the setting
[50/51SEF.DIR.RCA].

The operation boundary of the forward direction element can be set by


[50/51SEF.DIR.phi_Min_Fwd] and [50/51SEF.DIR.phi_Max_Fwd].

The operation boundary of the reverse direction element can be set as


[50/51SEF.DIR.phi_Min_Rev] and [50/51SEF.DIR.phi_Max_Rev].

The forward direction characteristic is:

-[50/51SEF.DIR.phi_Min_Fwd]<angle<[50/51SEF.DIR.phi_Max_Fwd]

The reverse direction characteristic is:

180-[50/51SEF.DIR.phi_Min_Rev]<angle<180+[50/51SEF.DIR.phi_Max_Rev]

The following table shows the relationship between the operating current, the polarized voltage
and the polarization mode.

Polarized
Polarization mode Operating current Angle difference
voltage
Zero-sequence The sensitive earth fault current
-3U0 Angle=Angle(-3U0)-Angle(Isef)-RCA
voltage polarized Isef

PCS-9611S Feeder Relay 3-99


Date: 2019-04-24
3 Protection Functions

The logic diagram of the forward direction element and reverse direction element is as follows.

EN [50/51SEF.En_VTS_Blk] &

>=1

SIG VTS.Alm

SIG Isef
& >=1

Forward direction
50/51SEF.Fwd Dir.Op

3
criterion
SIG 3U0_Cal

SIG Prot.BI_En_VT &

EN [En_VT]

EN [50/51SEF.En_VTS_Blk] &

>=1

SIG VTS.Alm

SIG Isef
& >=1
Reverse direction

50/51SEF.RevDir.Op
criterion

SIG 3U0_Cal

SIG Prot.BI_En_VT &

EN [En_VT]

Figure 3.9-4 Logic diagram of forward and reverse direction element of sensitive earth fault protection

3.9.1.2 Operation Characteristic

Sensitive earth fault protection can operate without time delay or operate with a definite-time limit,
it can also operate with an inverse-time limit, the characteristic curve meets the IEC60255-3 and
ANSI C37.112 standards. Sensitive earth fault protection can support definite-time limit, IEC &
ANSI standard inverse time limit and user-defined inverse-time limit, users can select the wanted
operating curve by the setting [50/51SEFx.Opt_Curve] (x=1~6), the relationship between the
value of the setting and the curve is shown in the table below.

3-100 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

50/51SEFx.Opt_Curve Time Characteristic k α c tr


ANSIE ANSI Extremely Inverse 28.2 2.0 0.1217 29.1
ANSIV ANSI Very inverse 19.61 2.0 0.491 21.6
ANSIN ANSI Normal Inverse 0.0086 0.02 0.0185 0.46
ANSIM ANSI Moderately Inverse 0.0515 0.02 0.114 4.85
ANSIDefTime ANSI Definite Time - - - -
ANSILTE ANSI Long Time Extremely Inverse 64.07 2.0 0.25 30
ANSILTV ANSI Long Time Very Inverse 28.55 2.0 0.712 13.46
ANSILT ANSI Long Time Inverse 0.086 0.02 0.185 4.6
IECN IEC Normal Inverse 0.14 0.02 0 -
IECV IEC Very inverse 13.5 1.0 0 - 3
IEC IEC Inverse 0.14 0.02 0 -
IECE IEC Extremely inverse 80.0 2.0 0 -
IECST IEC Short-time inverse 0.05 0.04 0 -
IECLT IEC Long-time inverse 120.0 1.0 0 -
IECDefTime IEC Definite Time - - - -
UserDefine Programmable

Only when the setting [50/51SEFx.Opt_Curve] is set as “UserDefine”, i.e. the user-defined
inverse-time characteristic is selected, the settings [50/51SEFx.K], [50/51SEFx.C] and
[50/51SEFx.Alpha] are useful, the inverse-time operating curve is determined by the three
settings.

 Without time delay

When Isef > Isef _ set , the protection operates immediately.

 Definite-time characteristic

When Isef > Isef _ set , the protection operates with a time delay of top (i.e. the value of the setting
[50/51SEFx.t_Op]), and the operation characteristic curve is shown in the following figure:

PCS-9611S Feeder Relay 3-101


Date: 2019-04-24
3 Protection Functions

t op

I sef_set Isef

Figure 3.9-5 Definite-time operation characteristic curve of sensitive earth fault protection

 Inverse-time characteristic

When Isef > Isef _ set , the inverse-time accumulator begins to accumulate, and the operating time
is affected by the applied current Isef . The operating time will decrease with the current
increasing, but the operating time shall not less than tmin , i.e. the setting [50/51SEFx.tmin]. The
inverse-time operation characteristic equation is:

Where:

Isef _ set is the current setting [50/51SEFx.3I0_Set];

TMS is the inverse-time time multiplier, i.e. the setting [50/51SEFx.TMS];

k is the inverse-time coefficient K, i.e. the setting [50/51SEFx.K];


c is the inverse-time coefficient C, i.e. the setting [50/51SEFx.C];
 is the inverse-time coefficient Alpha, i.e. the setting [50/51SEFx.Alpha];

Isef is the measured zero-sequence current.


The inverse-time operation characteristic curve is shown as below:

3-102 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

t min 3

I Sef_set ID Isef

Figure 3.9-6 Inverse-time operation characteristic curve of sensitive earth fault protection

When the applied zero-sequence current Isef is not a fixed value, but changes with time, the
operating behavior of the protection is shown in the following equation:

T0
1
 t(I
0 sef )
dt  1

Where:

T0 is the operating time of the protection element;

t ( I sef ) is the theoretical operating time when the current is Isef .

3.9.1.3 Dropout Characteristic

The supported dropout characteristics of the sensitive earth fault protection include instantaneous
dropout, definite-time dropout and ANSI inverse-time dropout.

When the operating curve is selected as definite-time, IEC inverse-time or user-defined


inverse-time characteristic, the dropout characteristic can only be selected as instantaneous
dropout or definite-time dropout, if inverse-time dropout is selected, the alarm signal
"Fail_Settings" will be issued and the device will be blocked.

When the operating curve is selected as ANSI inverse-time characteristic, the dropout
characteristic can be selected as instantaneous dropout, definite-time dropout and ANSI
inverse-time dropout.

 Instantaneous dropout

When Isef <0.95* Isef _ set , the protection drops out immediately.

PCS-9611S Feeder Relay 3-103


Date: 2019-04-24
3 Protection Functions

 Definite-time dropout

When Isef <0.95* Isef _ set , the protection drops out with a time delay of tdr (i.e. the value of the
setting [50/51SEFx.t_DropOut]), and the dropout characteristic curve is shown in the following
figure:

Start time

Isef>Isef_set

3 Start
signal

Operating
signal

Protection
Operating threshold operate

Operating
counter

t dr t dr t dr
Dropout time setting
Dropout time
Dropout time

Figure 3.9-7 Definite-time dropout characteristic of sensitive earth fault protection

 Inverse-time dropout

When Isef > Isef _ set , the inverse-time operating accumulator begins to accumulate, the
accumulated value after tp (Assuming tp is less than the theoretical operating time) is
calculated according to the following equation:

tp
1
I tp   dt
0
t ( I sef )

At this time, if Isef <0.95* Isef _ set , the protection element starts dropout, and the dropout
characteristic meets the following equation:

TR
1
I tp   dt  0
0
t R ( I sef )

Where:

TR is the dropout time;

3-104 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

tR( I sef ) is the dropout characteristic equation

When Isef <0.95* Isef _ set , the inverse-time dropout characteristic equation is as follows:

Where:

Isef _ set is the current setting [50/51SEFx.3I0_Set];


3
TMS is the inverse-time factor, i.e. the setting [50/51SEFx.TMS];

tr is the dropout time coefficient, it is the dropout time required for the current to drop to 0 after
the protection operates.

Isef is the measured current.


When 0.95* Isef I
_ set < sef < Isef _ set , the accumulator will neither accumulate nor drop out

The inverse time dropout characteristic curve is shown in the figure below.

tr

Isef_set Isef

Figure 3.9-8 Inverse-time dropout characteristic curve of sensitive earth fault protection

The correspondence between the start signal, operating signal, and operating accumulator in the
inverse-time dropout characteristic is shown in the figure below:

PCS-9611S Feeder Relay 3-105


Date: 2019-04-24
3 Protection Functions

Start time

Isef>Isef_set

Start
signal

Operating
signal

3 Operating threshold
Protection
operate

Operating
counter

tr Dropout time coefficient


Dropout time
Dropout time

Figure 3.9-9 Inverse-time dropout characteristic of sensitive earth fault protection

3.9.2 Function Block Diagram

50/51SEF

50/51SEFx.Enable 50/51SEFx.On

50/51SEFx.Block 50/51SEFx.Blocked

50/51SEFx.Valid

50/51SEFx.St

50/51SEFx.Op

50/51SEFx.Alm

50/51SEF.FwdDir.Op

50/51SEF.RevDir.Op

3.9.3 I/O Signal


Table 3.9-1 Input/output signals of sensitive earth fault protection

No. Input signal Description


Stage x of sensitive earth fault protection enabling input, it is triggered from
1 50/51SEFx.Enable
binary input or programmable logic etc. (x=1~6)
Stage x of sensitive earth fault protection blocking input, it is triggered from
2 50/51SEFx.Block
binary input or programmable logic etc. (x=1~6)

3-106 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

No. Output signal Description


1 50/51SEFx.On Stage x of sensitive earth fault protection is enabled
2 50/51SEFx.Blocked Stage x of sensitive earth fault protection is blocked
3 50/51SEFx.Valid Stage x of sensitive earth fault protection is valid
4 50/51SEFx.St Stage x of sensitive earth fault protection starts
5 50/51SEFx.Op Stage x of sensitive earth fault protection operates
6 50/51SEFx.Alm Stage x of sensitive earth fault protection alarms
7 50/51SEF.FwdDir.Op The forward direction element of sensitive earth fault protection operates
8 50/51SEF.RevDir.Op The reverse direction element of sensitive earth fault protection operates

3.9.4 Logic
3
SET Isef>[50/51SEFX.3I0_Set]
50/51SEFx.St
SIG 50/51SEF.FwdDir.Op
&
& Timer
selection
Direction

t
SIG 50/51SEF.RevDir.Op
t
SET [50/51SEFx.Opt_Dir]

SIG 50/51SEFx.Pkp
&
50/51SEFx.Op
SET [50/51SEFx.Opt_Trp/Alm]=Trp

&
50/51SEFx.Alm
SET [50/51SEFx.Opt_Trp/Alm]=Alm

Figure 3.9-10 Logic diagram of sensitive earth fault protection

3.9.5 Settings
 Access path:

MainMenu  Settings  Protection Settings  SEF Settings

Table 3.9-2 Settings of sensitive earth fault protection

Default
No. Settings Range Unit Step Description
value
The relay characteristic angle of
1 50/51SEF.DIR.RCA -180~179 45 deg 1 the direction control element of
sensitive earth fault protection
The minimum boundary of the
50/51SEF.DIR.phi_Mi
2 10~90 90 deg 1 forward direction element of
n_Fwd
sensitive earth fault protection
The maximum boundary of the
50/51SEF.DIR.phi_M
3 10~90 90 deg 1 forward direction element of
ax_Fwd
sensitive earth fault protection

PCS-9611S Feeder Relay 3-107


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The minimum boundary of the
50/51SEF.DIR.phi_Mi
4 10~90 90 deg 1 reverse direction element of
n_Rev
sensitive earth fault protection
The maximum boundary of the
50/51SEF.DIR.phi_M
5 10~90 90 deg 1 reverse direction element of
ax_Rev
sensitive earth fault protection
The minimum operating current
setting for the direction control
6 50/51SEF.DIR.I_Min (0.05~1)In 0.05 - 0.001
3 element of sensitive earth fault
protection
The minimum operating voltage
setting for the direction control
7 50/51SEF.DIR.U_Min 1.0~10.0 4 V 0.001
element of sensitive earth fault
protection
Logic setting to determine the
behavior of sensitive earth fault
protection when VT circuit
supervision function is enabled
and VT circuit failure happens.
50/51SEF.En_VTS_Bl Disabled; Disabled: sensitive earth fault
8 Disabled - -
k Enabled protection will not effected by VT
circuit failure
Enabled: voltage controlled
sensitive earth fault protection
will be blocked by VT circuit
failure signal
The current setting of stage 1 of
9 50/51SEF1.3I0_Set 0.005~2 1 A 0.001
sensitive earth fault protection
The operating time setting of
10 50/51SEF1.t_Op 0 ~100 0.1 s 0.001 stage 1 of sensitive earth fault
protection
The dropout time setting of
50/51SEF1.t_DropOu
11 0 ~100 0 s 0.001 stage 1 of sensitive earth fault
t
protection
Non_Directional The setting used to select the
Non_Dire
12 50/51SEF1.Opt_Dir Forward - - directional mode of stage 1 of
ctional
Reverse sensitive earth fault protection.
The logic setting for
Disabled;
13 50/51SEF1.En Enabled - - enabling/disabling the stage 1 of
Enabled
sensitive earth fault protection

3-108 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
Enabling stage 1 of sensitive
earth fault protection operate to
50/51SEF1.Opt_Trp/ Trp;
14 Trp - - trip or alarm.
Alm Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
3
ANSILTE;
ANSILTV; The setting for selecting the
50/51SEF1.Opt_Curv ANSILT; IECDefTi inverse-time operation
15 - -
e IECN; me characteristic curve of stage 1 of
IECV; sensitive earth fault protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 1 of
50/51SEF1.Opt_Curv
16 DefTime; Inst - - sensitive earth fault protection
e_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
17 50/51SEF1.TMS 0.04~ 20 1 - 0.001 stage 1 of sensitive earth fault
protection
The minimum operating time
18 50/51SEF1.tmin 0 ~10 0.02 s 0.001 setting of stage 1 of sensitive
earth fault protection
The constant “k” of the
customized inverse-time
19 50/51SEF1.K 0.001~120 0.14 - 0.0001 operation characteristic of stage
1 of sensitive earth fault
protection

PCS-9611S Feeder Relay 3-109


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The constant “α” of the
customized inverse-time
20 50/51SEF1.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of stage
1 of sensitive earth fault
protection
The constant “C” of the
customized inverse-time
21 50/51SEF1.C 0 ~1 0 - 0.0001 operation characteristic of stage

3 1 of
protection
sensitive earth fault

The current setting of stage 2 of


22 50/51SEF2.3I0_Set 0.005~2 1 A 0.001
sensitive earth fault protection
The operating time setting of
23 50/51SEF2.t_Op 0 ~100 0.1 s 0.001 stage 2 of sensitive earth fault
protection
The dropout time setting of
50/51SEF2.t_DropOu
24 0 ~100 0 s 0.001 stage 2 of sensitive earth fault
t
protection
Non_Directional The setting used to select the
Non_Dire
25 50/51SEF2.Opt_Dir Forward - - directional mode of stage 2 of
ctional
Reverse sensitive earth fault protection.
The logic setting for
Disabled;
26 50/51SEF2.En Enabled - - enabling/disabling the stage 2 of
Enabled
sensitive earth fault protection
Enabling stage 2 of sensitive
earth fault protection operate to
50/51SEF2.Opt_Trp/ Trp;
27 Trp - - trip or alarm.
Alm Alm
Trp: for tripping purpose
Alm: for alarm purpose

3-110 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
50/51SEF2.Opt_Curv ANSILT; IECDefTi inverse-time operation
28 - -
e IECN;
IECV;
me characteristic curve of stage 2 of
sensitive earth fault protection.
3
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 2 of
50/51SEF2.Opt_Curv
29 DefTime; Inst - - sensitive earth fault protection
e_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
30 50/51SEF2.TMS 0.04~ 20 1 - 0.001 stage 2 of sensitive earth fault
protection
The minimum operating time
31 50/51SEF2.tmin 0 ~10 0.02 s 0.001 setting of stage 2 of sensitive
earth fault protection
The constant “k” of the
customized inverse-time
32 50/51SEF2.K 0.001~120 0.14 - 0.0001 operation characteristic of stage
2 of sensitive earth fault
protection
The constant “α” of the
customized inverse-time
33 50/51SEF2.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of stage
2 of sensitive earth fault
protection

PCS-9611S Feeder Relay 3-111


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The constant “C” of the
customized inverse-time
34 50/51SEF2.C 0 ~1 0 - 0.0001 operation characteristic of stage
2 of sensitive earth fault
protection
The current setting of stage 3 of
35 50/51SEF3.3I0_Set 0.005~2 1 A 0.001
sensitive earth fault protection
The operating time setting of

3 36 50/51SEF3.t_Op 0 ~100 0.1 s 0.001 stage 3 of sensitive earth fault


protection
The dropout time setting of
50/51SEF3.t_DropOu
37 0 ~100 0 s 0.001 stage 3 of sensitive earth fault
t
protection
Non_Directional The setting used to select the
Non_Dire
38 50/51SEF3.Opt_Dir Forward - - directional mode of stage 3 of
ctional
Reverse sensitive earth fault protection.
The logic setting for
Disabled;
39 50/51SEF3.En Enabled - - enabling/disabling the stage 3 of
Enabled
sensitive earth fault protection
Enabling stage 3 of sensitive
earth fault protection operate to
50/51SEF3.Opt_Trp/ Trp;
40 Trp - - trip or alarm.
Alm Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
50/51SEF3.Opt_Curv ANSILT; IECDefTi inverse-time operation
41 - -
e IECN; me characteristic curve of stage 3 of
IECV; sensitive earth fault protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine

3-112 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 3 of
50/51SEF3.Opt_Curv
42 DefTime; Inst - - sensitive earth fault protection
e_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
43 50/51SEF3.TMS 0.04~ 20 1 - 0.001 stage 3 of sensitive earth fault
protection
3
The minimum operating time
44 50/51SEF3.tmin 0 ~10 0.02 s 0.001 setting of stage 3 of sensitive
earth fault protection
The constant “k” of the
customized inverse-time
45 50/51SEF3.K 0.001~120 0.14 - 0.0001 operation characteristic of stage
3 of sensitive earth fault
protection
The constant “α” of the
customized inverse-time
46 50/51SEF3.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of stage
3 of sensitive earth fault
protection
The constant “C” of the
customized inverse-time
47 50/51SEF3.C 0 ~1 0 - 0.0001 operation characteristic of stage
3 of sensitive earth fault
protection
The current setting of stage 4 of
48 50/51SEF4.3I0_Set 0.005~2 1 A 0.001
sensitive earth fault protection
The operating time setting of
49 50/51SEF4.t_Op 0 ~100 0.1 s 0.001 stage 4 of sensitive earth fault
protection
The dropout time setting of
50/51SEF4.t_DropOu
50 0 ~100 0 s 0.001 stage 4 of sensitive earth fault
t
protection
Non_Directional The setting used to select the
Non_Dire
51 50/51SEF4.Opt_Dir Forward - - directional mode of stage 4 of
ctional
Reverse sensitive earth fault protection.
The logic setting for
Disabled;
52 50/51SEF4.En Enabled - - enabling/disabling the stage 4 of
Enabled
sensitive earth fault protection

PCS-9611S Feeder Relay 3-113


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
Enabling stage 4 of sensitive
earth fault protection operate to
50/51SEF4.Opt_Trp/ Trp;
53 Trp - - trip or alarm.
Alm Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;

3 ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
50/51SEF4.Opt_Curv ANSILT; IECDefTi inverse-time operation
54 - -
e IECN; me characteristic curve of stage 4 of
IECV; sensitive earth fault protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 4 of
50/51SEF4.Opt_Curv
55 DefTime; Inst - - sensitive earth fault protection
e_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
56 50/51SEF4.TMS 0.04~ 20 1 - 0.001 stage 4 of sensitive earth fault
protection
The minimum operating time
57 50/51SEF4.tmin 0 ~10 0.02 s 0.001 setting of stage 4 of sensitive
earth fault protection
The constant “k” of the
customized inverse-time
58 50/51SEF4.K 0.001~120 0.14 - 0.0001 operation characteristic of stage
4 of sensitive earth fault
protection

3-114 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The constant “α” of the
customized inverse-time
59 50/51SEF4.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of stage
4 of sensitive earth fault
protection
The constant “C” of the
customized inverse-time
60 50/51SEF4.C 0 ~1 0 - 0.0001 operation characteristic of stage
4 of
protection
sensitive earth fault
3
The current setting of stage 5 of
61 50/51SEF5.3I0_Set 0.005~2 1 A 0.001
sensitive earth fault protection
The operating time setting of
62 50/51SEF5.t_Op 0 ~100 0.1 s 0.001 stage 5 of sensitive earth fault
protection
The dropout time setting of
50/51SEF5.t_DropOu
63 0 ~100 0 s 0.001 stage 5 of sensitive earth fault
t
protection
Non_Directional The setting used to select the
Non_Dire
64 50/51SEF5.Opt_Dir Forward - - directional mode of stage 5 of
ctional
Reverse sensitive earth fault protection.
The logic setting for
Disabled;
65 50/51SEF5.En Enabled - - enabling/disabling the stage 5 of
Enabled
sensitive earth fault protection
Enabling stage 5 of sensitive
earth fault protection operate to
50/51SEF5.Opt_Trp/ Trp;
66 Trp - - trip or alarm.
Alm Alm
Trp: for tripping purpose
Alm: for alarm purpose

PCS-9611S Feeder Relay 3-115


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
50/51SEF5.Opt_Curv ANSILT; IECDefTi inverse-time operation
67 - -
3 e IECN;
IECV;
me characteristic curve of stage 5 of
sensitive earth fault protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 5 of
50/51SEF5.Opt_Curv
68 DefTime; Inst - - sensitive earth fault protection
e_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
69 50/51SEF5.TMS 0.04~ 20 1 - 0.001 stage 5 of sensitive earth fault
protection
The minimum operating time
70 50/51SEF5.tmin 0 ~10 0.02 s 0.001 setting of stage 5 of sensitive
earth fault protection
The constant “k” of the
customized inverse-time
71 50/51SEF5.K 0.001~120 0.14 - 0.0001 operation characteristic of stage
5 of sensitive earth fault
protection
The constant “α” of the
customized inverse-time
72 50/51SEF5.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of stage
5 of sensitive earth fault
protection

3-116 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The constant “C” of the
customized inverse-time
73 50/51SEF5.C 0 ~1 0 - 0.0001 operation characteristic of stage
5 of sensitive earth fault
protection
The current setting of stage 6 of
74 50/51SEF6.3I0_Set 0.005~2 1 A 0.001
sensitive earth fault protection
The operating time setting of
75 50/51SEF6.t_Op 0 ~100 0.1 s 0.001 stage 6 of sensitive earth fault
protection
3
The dropout time setting of
50/51SEF6.t_DropOu
76 0 ~100 0 s 0.001 stage 6 of sensitive earth fault
t
protection
Non_Directional The setting used to select the
Non_Dire
77 50/51SEF6.Opt_Dir Forward - - directional mode of stage 6 of
ctional
Reverse sensitive earth fault protection.
The logic setting for
Disabled;
78 50/51SEF6.En Enabled - - enabling/disabling the stage 6 of
Enabled
sensitive earth fault protection
Enabling stage 6 of sensitive
earth fault protection operate to
50/51SEF6.Opt_Trp/ Trp;
79 Trp - - trip or alarm.
Alm Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
50/51SEF6.Opt_Curv ANSILT; IECDefTi inverse-time operation
80 - -
e IECN; me characteristic curve of stage 6 of
IECV; sensitive earth fault protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine

PCS-9611S Feeder Relay 3-117


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 6 of
50/51SEF6.Opt_Curv
81 DefTime; Inst - - sensitive earth fault protection
e_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of

3 82 50/51SEF6.TMS 0.04~ 20 1 - 0.001 stage 6 of sensitive earth fault


protection
The minimum operating time
83 50/51SEF6.tmin 0 ~10 0.02 s 0.001 setting of stage 6 of sensitive
earth fault protection
The constant “k” of the
customized inverse-time
84 50/51SEF6.K 0.001~120 0.14 - 0.0001 operation characteristic of stage
6 of sensitive earth fault
protection
The constant “α” of the
customized inverse-time
85 50/51SEF6.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of stage
6 of sensitive earth fault
protection
The constant “C” of the
customized inverse-time
86 50/51SEF6.C 0 ~1 0 - 0.0001 operation characteristic of stage
6 of sensitive earth fault
protection

3.10 RMS Overcurrent Protection (50/51R)


When the capacitive equipment such as a capacitor bank or the inductive equipment such as a
rotating electrical machine in the system has a serious fault, the fundamental component in the
fault current will be relatively low, and the higher harmonic component will be higher. The
conventional phase overcurrent protection uses filtering algorithms to filter out higher harmonics
and perform calculation based on the fundamental component, resulting in failure to truly reflect
the fault condition and the protection sensitivity is affected. The RMS overcurrent protection
calculates the full-current RMS value includes 2nd~11th harmonic component, which can
sensitively reflect the actual fault current, so the fault can be removed quickly and accurately.

3.10.1 Function Description


The device can provide two stages of RMS overcurrent protection with independent logic. When

3-118 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

the fault current with more harmonic component is generated in the system, the amplitude is
larger than the current threshold of RMS overcurrent protection, the RMS overcurrent protection
will operate.

The operation characteristics of RMS overcurrent protection is definite-time characteristics. The


dropout characteristics can be set as instantaneous dropout or definite-time dropout. RMS
overcurrent protection can operate to trip or alarm, it can be enabled or blocked by the external
binary input.

RMS overcurrent protection can be enabled or disabled via the settings or binary input signals, for
some specific applications, the protection needs to be blocked by the external signal, so the
device provides a function block input signal to be used to block RMS overcurrent protection. The
enabling and blocking logic of RMS overcurrent protection is shown in the figure below:
3
EN 50/51Rx.En &
50/51Rx.On

SIG 50/51Rx.Enable

&
SIG 50/51Rx.Block ≥1 50/51Rx.Blocked

SIG Fail_Device
&
50/51Rx.Valid

Figure 3.10-1 The enabling and blocking logic of RMS overcurrent protection

The logic diagram of the fault detector element of RMS overcurrent protection is as follows:

SET IRMS >0.95*[50/51Rx.I_Set] & 50/51Rx.Pkp


0 500ms
&
SIG 50/51Rx.On &
FD.Pkp
SIG 50/51Rx.Valid

EN [50/51Rx.Opt_Trp/Alm]=Alm

Figure 3.10-2 Logic diagram of the fault detector element of RMS overcurrent protection

3.10.1.1 Operation Characteristic

RMS overcurrent protection can operate without time delay or operate with a definite-time limit,
the characteristic curve meets the IEC60255-3 and ANSI C37.112 standards.

When IRMS is larger than the current setting, the protection operates with a time delay of top (i.e.
the value of the setting [50/51Rx.t_Op]), and the operation characteristic curve is shown in the
following figure:

PCS-9611S Feeder Relay 3-119


Date: 2019-04-24
3 Protection Functions

t 0p

3
IRMSp IRMS

Figure 3.10-3 Definite-time operation characteristic curve of RMS overcurrent protection

3.10.1.2 Dropout Characteristic

The supported dropout characteristics of the phase overvoltage protection include instantaneous
dropout and definite-time dropout.

 Instantaneous dropout

When I RMS <0.95* I RMSP , the protection drops out immediately.

 Definite-time dropout

When I RMS <0.95* I RMSP , the protection drops out with a time delay of tdr (i.e. the value of the

setting [50/51Rx.t_DropOut]), and the dropout characteristic curve is shown in the following figure:

3-120 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Start time

IRMS >Iset

Start
signal

Operating
signal
3
Protection
Operating threshold operate

Operating
counter

t dr t dr t dr
Dropout time setting
Dropout time
Dropout time

Figure 3.10-4 Definite-time dropout characteristic of RMS overcurrent protection

3.10.2 Function Block Diagram

50/51R

50/51Rx.Enable 50/51Rx.On

50/51Rx.Blocked
50/51Rx.Block
50/51Rx.Valid

50/51Rx.St

50/51Rx.StA
50/51Rx.StB
50/51Rx.StC

50/51Rx.Op
50/51Rx.Op.PhA

50/51Rx.Op.PhB

50/51Rx.Op.PhC
50/51Rx.Alm

PCS-9611S Feeder Relay 3-121


Date: 2019-04-24
3 Protection Functions

3.10.3 I/O Signal


Table 3.10-1 Input/output signals of RMS overcurrent protection

No. Input signal Description


Stage x of RMS overcurrent protection enabling input, it is triggered from binary
1 50/51Rx.Enable
input or programmable logic etc. (x=1~2)
Stage x of RMS overcurrent protection blocking input, it is triggered from binary
2 50/51Rx.Block
input or programmable logic etc. (x=1~2)
No. Output signal Description
1 50/51Rx.On Stage x of RMS overcurrent protection is enabled

3 2 50/51Rx.Blocked Stage x of RMS overcurrent protection is blocked


3 50/51Rx.Valid Stage x of RMS overcurrent protection is valid
4 50/51Rx.St Stage x of RMS overcurrent protection starts
5 50/51Rx.StA Stage x of RMS overcurrent protection starts (Phase A)
6 50/51Rx.StB Stage x of RMS overcurrent protection starts (Phase B)
7 50/51Rx.StC Stage x of RMS overcurrent protection starts (Phase C)
8 50/51Rx.Op Stage x of RMS overcurrent protection operates
9 50/51Rx.Op.PhA Stage x of RMS overcurrent protection operates (Phase A)
10 50/51Rx.Op.PhB Stage x of RMS overcurrent protection operates (Phase B)
11 50/51Rx.Op.PhC Stage x of RMS overcurrent protection operates (Phase C)
12 50/51Rx.Alm Stage x of RMS overcurrent protection alarms

3.10.4 Logic

50/51Rx.St

Timer &
SET IRMS>[50/51Rx.I_Set] & 50/51Rx.Op
t
t
SIG 50/51Rx.Pkp

SET [50/51Rx.Opt_Trp/Alm] = Trp &


50/51Rx.Alm
SET [50/51Rx.Opt_Trp/Alm] = Alm

Figure 3.10-5 Logic diagram of RMS overcurrent protection

3.10.5 Settings
 Access path:

MainMenu  Settings  Protection Settings  RMS OC Settings

Table 3.10-2 Settings of RMS overcurrent protection

Default
No. Settings Range Unit Step Description
value
The current setting of stage 1 of RMS
1 50/51R1.I_Set 0.05~200 15 A 0.001
overcurrent protection

3-122 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The operating time setting of stage 1 of
2 50/51R1.t_Op 0 ~100 0.1 s 0.001
RMS overcurrent protection
The dropout time setting of stage 1 of
3 50/51R1.t_DropOut 0 ~100 0 s 0.001
RMS overcurrent protection
Disabled; The logic setting for enabling/disabling the
4 50/51R1.En Enabled - -
Enabled stage 1 of RMS overcurrent protection
Enabling stage 1 of RMS overcurrent
Trp; protection operate to trip or alarm.
5 50/51R1.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose 3
Alm: for alarm purpose
The current setting of stage 2 of RMS
6 50/51R2.I_Set 0.05~200 15 A 0.001
overcurrent protection
The operating time setting of stage 2 of
7 50/51R2.t_Op 0 ~100 0.1 s 0.001
RMS overcurrent protection
The dropout time setting of stage 2 of
8 50/51R2.t_DropOut 0 ~100 0 s 0.001
RMS overcurrent protection
Disabled; The logic setting for enabling/disabling the
9 50/51R2.En Enabled - -
Enabled stage 2 of RMS overcurrent protection
Enabling stage 2 of RMS overcurrent
Trp; protection operate to trip or alarm.
10 50/51R2.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose
Alm: for alarm purpose

3.11 Phase Overvoltage Protection (59P)


Some abnormal conditions in the power system will generate high voltage, which may damage
the insulation performance of transformers, capacitors, motors and transmission lines, resulting in
equipment damage. Phase overvoltage protection can effectively detect the overvoltage that may
be generated in the system.

3.11.1 Function Description


The device can provide two stages of phase overvoltage protection with independent logic. When
a high voltage occurs in the system, it is greater than the voltage threshold, phase overvoltage
protection will operate to remove the device from the system after a time delay. In addition, the
overvoltage protection also provides the alarm function, prompting the overvoltage of the system,
it allows users to find the cause timely, and preventing further deterioration of the fault. Each stage
of phase overvoltage protection can be independently set as definite-time characteristics or
inverse-time characteristics. The dropout characteristics can be set as instantaneous dropout and
definite-time dropout.

Users can select phase voltage or phase-to-phase voltage for the protection calculation via the
setting [59P.Opt_Up/Upp]. If it is set as “Up”, phase voltage criterion is selected, and if it is set to
“Upp”, phase-to-phase voltage criterion is selected.

PCS-9611S Feeder Relay 3-123


Date: 2019-04-24
3 Protection Functions

Users can select “1-out-of-3” or “3-out-of-3” logic for the protection criterion via the setting
[59P.Opt_1P/3P]. If it is set as “1P”, phase overvoltage protection can operate if any
phase/phase-to-phase voltage is greater than the voltage setting. If it is set as “3P”, phase
overvoltage protection cannot operate unless three phase/phase-to-phase voltages are greater
than the voltage setting.

Phase overvoltage protection can be enabled or disabled via the settings or binary input signals,
for some specific applications, overvoltage protection needs to be blocked by the external signal,
so the device provides a function block input signal to be used to block overvoltage protection.
The enabling and blocking logic of phase overvoltage protection is shown in the figure below:

3 EN 59Px.En &
59Px.On

SIG 59Px.Enable

&
SIG 59Px.Block ≥1 59Px.Blocked

SIG Fail_Device
&
59Px.Valid

Figure 3.11-1 The enabling and blocking logic of phase overvoltage protection

The logic diagram of the fault detector element of phase overvoltage protection is as follows:

3-124 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

SET [59P.Opt_Up/Upp]=Upp

SET Uab>[U_DropOut]
>=1
SET Ubc>[U_DropOut] &
SET Uca>[U_DropOut]

SET [59P.Opt_1P/3P]=1P
&
SET [59P.Opt_1P/3P]=3P >=1
SET Uab>[U_DropOut]
&
&
SET Ubc>[U_DropOut]

SET Uca>[U_DropOut]
3
SET Ua>[U_DropOut]
>=1
SET Ub>[U_DropOut] &
SET Uc>[U_DropOut]

SET [59P.Opt_1P/3P]=1P

SET [59P.Opt_1P/3P]=3P >=1


SET Ua>[U_DropOut]
&
&
SET Ub>[U_DropOut]

SET Uc>[U_DropOut]
& &
0 500ms &
SET [59P.Opt_Up/Upp]=Up x.59Px.Pkp

SIG 59Px.On

SIG 59Px.Valid
&
FD.Pkp
SET [59Px.Opt_Trp/Alm]=Alm

Figure 3.11-2 Logic diagram of the fault detector element of phase overvoltage protection

Where:

U_DropOut: the dropout voltage value, i.e. [59Px.K_DropOut]*[59Px.U_Set]

3.11.1.1 Operation Characteristic

Phase overvoltage protection can operate with a definite-time limit, it can also operate with an
inverse-time limit, the characteristic curve meets the IEC60255-3 and ANSI C37.112 standards.
Phase overvoltage protection can support definite-time limit, IEC & ANSI standard inverse time
limit and user-defined inverse-time limit, users can select the wanted operating curve by the
setting [59Px.Opt_Curve] (x=1, 2), the relationship between the value of the setting and the curve
is shown in the table below.

59Px.Opt_Curve Time Characteristic k α c


ANSIDefTime ANSI Definite Time - - -
IECDefTime IEC Definite Time - - -
UserDefine UserDefine
InvTime_U InvCrv_U 1 1 0

PCS-9611S Feeder Relay 3-125


Date: 2019-04-24
3 Protection Functions

When the setting [59Px.Opt_Curve] is set as “InvTime_U”, the operation characteristic is the
corresponding selected operating curve type, and the settings [59Px.K], [59Px.C] and
[59Px.Alpha] are useless.

When the setting [59Px.Opt_Curve] is set as “UserDefine”, i.e. the user-defined inverse-time
characteristic is selected, the inverse-time operating curve is determined by the settings [59Px.K],
[59Px.C] and [59Px.Alpha].

When the setting [59Px.Opt_Curve] is set as “ANSIDefTime” or “IECDefTime”, it is definite-time


overvoltage protection.

 Definite-time characteristic
3 When U > Up , the protection operates with a time delay of top (i.e. the value of the setting
[59Px.t_Op]), and the operation characteristic curve is shown in the following figure:

t op

Up U

Figure 3.11-3 Definite-time operation characteristic curve of phase overvoltage protection

 Inverse-time characteristic

When U > Up , the inverse-time accumulator begins to accumulate, and the operating time is
affected by the applied voltage U . The larger voltage is, the smaller the operating time is, but not
unlimited. When the voltage is large enough to a certain threshold ( Up ), the inverse-time
operating time will not continue to decrease, then the operation characteristic becomes the
definite-time characteristic, and the operating time is tmin , i.e. the setting [59Px.tmin]. The
inverse-time operation characteristic equation is:

 k 
t 
 c   TMS
 (U / U P )  1 

Where:

Up is the voltage setting [59Px.U_Set];

TMS is the inverse-time time multiplier, i.e. the setting [59Px.TMS];

3-126 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

k is the inverse-time coefficient K, i.e. the setting [59Px.K];


c is the inverse-time coefficient C, i.e. the setting [59Px.C];
 is the inverse-time coefficient Alpha, i.e. the setting [59Px.Alpha];

U is the measured voltage.


The inverse-time operation characteristic curve is shown as below:

t min

UP UD U

Figure 3.11-4 Inverse-time operation characteristic curve of phase overvoltage protection

When the applied voltage is not a fixed value, but changes with time, the operating behavior of the
protection is shown in the following equation:

T0
1
 t (U )dt
0
1

Where:

T0 is the operating time of the protection element;

t (U ) is the theoretical operating time when the voltage is U .

3.11.1.2 Dropout Characteristic

The supported dropout characteristics of the phase overvoltage protection include instantaneous
dropout and definite-time dropout.

 Instantaneous dropout

When U <[ 59Px.K_DropOut]* Up , the protection drops out immediately.

 Definite-time dropout

When U <[59Px.K_DropOut]* Up , the protection drops out with a time delay of tdr (i.e. the value

PCS-9611S Feeder Relay 3-127


Date: 2019-04-24
3 Protection Functions

of the setting [59Px.t_DropOut]), and the dropout characteristic curve is shown in the following
figure:

Start time

U>Up

Start
signal

3
Operating
signal

Protection
Operating threshold operate

Operating
counter

t dr t dr t dr
Dropout time setting
Dropout time
Dropout time

Figure 3.11-5 Definite-time dropout characteristic of phase overvoltage protection

3-128 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

3.11.2 Function Block Diagram

59P

59Px.Enable 59Px.On

59Px.Block 59Px.Blocked

59Px.Valid

59Px.St

59Px.StA

59Px.StB 3
59Px.StC

59Px.Op

59Px.Op.PhA

59Px.Op.PhB

59Px.Op.PhC

59Px.Alm

3.11.3 I/O Signal


Table 3.11-1 Input/output signals of phase overvoltage protection

No. Input signal Description


Stage x of phase overvoltage protection enabling input, it is triggered from
1 59Px.Enable
binary input or programmable logic etc. (x=1~2)
Stage x of phase overvoltage protection blocking input, it is triggered from
2 59Px.Block
binary input or programmable logic etc. (x=1~2)
No. Output signal Description
1 59Px.On Stage x of phase overvoltage protection is enabled
2 59Px.Blocked Stage x of phase overvoltage protection is blocked
3 59Px.Valid Stage x of phase overvoltage protection is valid
4 59Px.St Stage x of phase overvoltage protection starts
5 59Px.StA Stage x of phase overvoltage protection starts (Phase A)
6 59Px.StB Stage x of phase overvoltage protection starts (Phase B)
7 59Px.StC Stage x of phase overvoltage protection starts (Phase C)
8 59Px.Op Stage x of phase overvoltage protection operates
9 59Px.Op.PhA Stage x of phase overvoltage protection operates (Phase A)
10 59Px.Op.PhB Stage x of phase overvoltage protection operates (Phase B)
11 59Px.Op.PhC Stage x of phase overvoltage protection operates (Phase C)
12 59Px.Alm Stage x of phase overvoltage protection alarms

PCS-9611S Feeder Relay 3-129


Date: 2019-04-24
3 Protection Functions

3.11.4 Logic

SET [59P.Opt_Up/Upp]=Upp

SET Uab>[59Px.U_Set]
>=1
SET Ubc>[59Px.U_Set] &
SET Uca>[59Px.U_Set]

SET [59P.Opt_1P/3P]=1P
&
SET [59P.Opt_1P/3P]=3P >=1 >=1
SET Uab>[59Px.U_Set]
&

3 SET Ubc>[59Px.U_Set]
&

SET Uca>[59Px.U_Set]

SET [59P.Opt_Up/Upp]=Up

SET Ua>[59Px.U_Set]
>=1
SET Ub>[59Px.U_Set] &
SET Uc>[59Px.U_Set]

SET [59P.Opt_1P/3P]=1P
&
SET [59P.Opt_1P/3P]=3P >=1
SET Ua>[59Px.U_Set]
&
& 59Px.St
SET Ub>[59Px.U_Set]
& Timer
SET Uc>[59Px.U_Set] t
&
t
SIG 59Px.Pkp 59Px.Op

SET [59Px.Opt_Trp/Alm]=Trp
&
59Px.Alm
SET [59Px.Opt_Trp/Alm]=Alm

Figure 3.11-6 Logic diagram of phase overvoltage protection

3.11.5 Settings
 Access path:

MainMenu  Settings  Protection Settings  OV Settings

3-130 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Table 3.11-2 Settings of phase overvoltage protection

Default
No. Settings Range Unit Step Description
value
Option of phase-to-phase
voltage or phase voltage for
Up; overvoltage protection
1 59P.Opt_Up/Upp Upp - -
Upp Up: phase voltage
Upp: phase-to-phase
voltage
Option of 1-out-of-3 mode or

3P;
3-out-of-3 mode for 3
2 59P.Opt_1P/3P 3P - - overvoltage protection
1P
3P: 3-out-of-3 mode
1P: 1-out-of-3 mode
The voltage setting of stage
3 59P1.U_Set 57.7~200 115 V 0.001 1 of phase overvoltage
protection
The dropout coefficient of
4 59P1.K_DropOut 0.93 ~1.00 0.98 - 0.001 stage 1 of phase
overvoltage protection
The operating time setting of
5 59P1.t_Op 0.1 ~100 1 s 0.001 stage 1 of phase
overvoltage protection
The dropout time setting of
6 59P1.t_DropOut 0 ~100 0 s 0.001 stage 1 of phase
overvoltage protection
The logic setting for
Disabled; enabling/disabling the stage
7 59P1.En Enabled - -
Enabled 1 of phase overvoltage
protection
Enabling stage 1 of phase
overvoltage protection
Trp;
8 59P1.Opt_Trp/Alm Trp - - operate to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose
The setting for selecting the
ANSIDefTime;
inverse-time operation
IECDefTime;
9 59P1.Opt_Curve IECDefTime - - characteristic curve of stage
UserDefine;
1 of phase overvoltage
InvTime_U
protection.

PCS-9611S Feeder Relay 3-131


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The setting for selecting the
inverse-time dropout
characteristic curve of stage
Inst; 1 of phase overvoltage
10 59P1.Opt_Curve_DropOut Inst - -
DefTime protection
Inst: instantaneous dropout
DefTime: definite-time
dropout

3 11 59P1.TMS 0.04~ 20 1 - 0.001


The time multiplier setting of
stage 1 of phase
overvoltage protection
The minimum operating time
12 59P1.tmin 0 ~10 0.02 s 0.001 setting of stage 1 of phase
overvoltage protection
The constant “k” of the
customized inverse-time
13 59P1.K 0.001~120 1 - 0.0001 operation characteristic of
stage 1 of phase
overvoltage protection
The constant “α” of the
customized inverse-time
14 59P1.Alpha 0.01 ~3 1 - 0.0001 operation characteristic of
stage 1 of phase
overvoltage protection
The constant “C” of the
customized inverse-time
15 59P1.C 0 ~1 0 - 0.0001 operation characteristic of
stage 1 of phase
overvoltage protection
The voltage setting of stage
16 59P2.U_Set 57.7~200 115 V 0.001 2 of phase overvoltage
protection
The dropout coefficient of
17 59P2.K_DropOut 0.93 ~1.00 0.98 - 0.001 stage 2 of phase
overvoltage protection
The operating time setting of
18 59P2.t_Op 0.1 ~100 1 s 0.001 stage 2 of phase
overvoltage protection
The dropout time setting of
19 59P2.t_DropOut 0 ~100 0 s 0.001 stage 2 of phase
overvoltage protection

3-132 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The logic setting for
Disabled; enabling/disabling the stage
20 59P2.En Enabled - -
Enabled 2 of phase overvoltage
protection
Enabling stage 2 of phase
overvoltage protection
Trp;
21 59P2.Opt_Trp/Alm Trp - - operate to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose
The setting for selecting the
3
ANSIDefTime;
inverse-time operation
IECDefTime;
22 59P2.Opt_Curve IECDefTime - - characteristic curve of stage
UserDefine;
2 of phase overvoltage
InvTime_U
protection.
The setting for selecting the
inverse-time dropout
characteristic curve of stage
Inst; 2 of phase overvoltage
23 59P2.Opt_Curve_DropOut Inst - -
DefTime protection
Inst: instantaneous dropout
DefTime: definite-time
dropout
The time multiplier setting of
24 59P2.TMS 0.04~ 20 1 - 0.001 stage 2 of phase
overvoltage protection
The minimum operating time
25 59P2.tmin 0 ~10 0.02 s 0.001 setting of stage 2 of phase
overvoltage protection
The constant “k” of the
customized inverse-time
26 59P2.K 0.001~120 1 - 0.0001 operation characteristic of
stage 2 of phase
overvoltage protection
The constant “α” of the
customized inverse-time
27 59P2.Alpha 0.01 ~3 1 - 0.0001 operation characteristic of
stage 2 of phase
overvoltage protection

PCS-9611S Feeder Relay 3-133


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The constant “C” of the
customized inverse-time
28 59P2.C 0 ~1 0 - 0.0001 operation characteristic of
stage 2 of phase
overvoltage protection

3.12 Residual Overvoltage Protection (59G)


If an earth fault occurs in the feeder of a high-resistance grounding system, the residual current
3 changes little and is difficult to detect. However, the amplitude of the residual voltage changes
significantly and can be used as a criterion for earth fault. In addition, the neutral point gap of the
transformer is grounded, once a fault occurs, the residual voltage increases, and the residual
overvoltage protection can also be used as the backup protection of the transformer. The residual
voltage can be measured from the open-triangle side of the voltage transformer, and it can also be
calculated internally by the protection device using three-phase voltage.

3.12.1 Function Description


The device can provide two stages of residual overvoltage protection with independent logic.
When the residual voltage is greater than the voltage threshold, the residual overvoltage
protection will operate to remove the device from the system after a time delay. In addition, the
residual overvoltage protection also provides the alarm function, it prompt that there is an earth
fault leading to residual voltage generation, it allows users to find the cause timely, and preventing
further deterioration of the fault. The dropout characteristics of residual overvoltage protection can
be set as instantaneous dropout and definite-time dropout.

Residual overvoltage protection can be enabled or disabled via the settings or binary input signals,
for some specific applications, residual overvoltage protection needs to be blocked by the external
signal, so the device provides a function block input signal to be used to block residual
overvoltage protection. The enabling and blocking logic of residual overvoltage protection is
shown in the figure below:

EN 59Gx.En &
59Gx.On

SIG 59Gx.Enable

&
SIG 59Gx.Block ≥1 59Gx.Blocked

SIG Fail_Device
&
59Gx.Valid

Figure 3.12-1 The enabling and blocking logic of residual overvoltage protection

3-134 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

The logic diagram of the fault detector element of residual overvoltage protection is as follows:

SET 3U0_Cal> U_DropOut &

SET [59G.Opt_3U0]=Cal
≥1
SET 3U0_Ext> U_DropOut &
& 59Gx.Pkp
SET [59Gx.Opt_3U0]=Ext 0 500ms
&
SIG 59Gx.On &
FD.Pkp
SIG

EN
59Gx.Valid

[59Gx.Opt_Trp/Alm]=Alm
3

Figure 3.12-2 Logic diagram of the fault detector element of residual overvoltage protection

Where:

U_DropOut: the dropout voltage value, i.e. [59Gx.K_DropOut]*[59Gx.3U0_Set]

3.12.1.1 Operation Characteristic

Residual overvoltage protection can operate with a settable time delay. When U 0 > U 0 p , the
protection operates with a time delay of top (i.e. the value of the setting [59Gx.t_Op]), and the
operation characteristic curve is shown in the following figure:

t op

U0p U0

Figure 3.12-3 Definite-time operation characteristic curve of residual overvoltage protection

3.12.1.2 Dropout Characteristic

The supported dropout characteristics of the residual overvoltage protection include

PCS-9611S Feeder Relay 3-135


Date: 2019-04-24
3 Protection Functions

instantaneous dropout and definite-time dropout.

 Instantaneous dropout

When U 0 <[59Gx.K_DropOut]* U 0 p , the protection drops out immediately.

 Definite-time dropout

When U 0 <[59Gx.K_DropOut]* U 0 p , the protection drops out with a time delay of tdr (i.e. the
value of the setting [59Gx.t_DropOut]), and the dropout characteristic curve is shown in the
following figure:

3 Start time

U0>U0p

Start
signal

Operating
signal

Protection
Operating threshold operate

Operating
counter

t dr t dr t dr
Dropout time setting
Dropout time
Dropout time

Figure 3.12-4 Definite-time dropout characteristic of residual overvoltage protection

3.12.2 Function Block Diagram

59G

59Gx.Enable 59Gx.On
59Gx.Block 59Gx.Blocked
59Gx.Valid
59Gx.St
59Gx.Op
59Gx.Alm

3-136 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

3.12.3 I/O Signal


Table 3.12-1 Input/output signals of residual overvoltage protection

No. Input signal Description


Stage x of residual overvoltage protection enabling input, it is triggered from
1 59Gx.Enable
binary input or programmable logic etc. (x=1~2)
Stage x of residual overvoltage protection blocking input, it is triggered from
2 59Gx.Block
binary input or programmable logic etc. (x=1~2)
No. Output signal Description
1 59Gx.On Stage x of residual overvoltage protection is enabled
2 59Gx.Blocked Stage x of residual overvoltage protection is blocked 3
3 59Gx.Valid Stage x of residual overvoltage protection is valid
4 59Gx.St Stage x of residual overvoltage protection starts
5 59Gx.Op Stage x of residual overvoltage protection operates
6 59Gx.Alm Stage x of residual overvoltage protection alarms

3.12.4 Logic

SET 3U0_Cal> [59Gx.3U0_Set] & 59Gx.St

SET [59G.Opt_3U0]=Cal
≥1 &
[59Gx.t_Op] [59Gx.t_DropOut]
SET 3U0_Ext> [59Gx.3U0_Set] & &
59Gx.Op

SET [59Gx.Opt_3U0]=Ext

SIG 59Gx.Pkp

SET [59Gx.Opt_Trp/Alm] = Trp


&
59Gx.Alm
SET [59Gx.Opt_Trp/Alm] = Alm

Figure 3.12-5 Logic diagram of residual overvoltage protection

3.12.5 Settings
 Access path:

MainMenu  Settings  Protection Settings  ROV Settings

Table 3.12-2 Settings of residual overvoltage protection

Default
No. Settings Range Unit Step Description
value
Option of measured residual voltage or
calculated residual voltage for residual
Ext;
1 59G.Opt_3U0 Cal - - overvoltage protection
Cal
Ext: the measured residual voltage
Cal: the calculated residual voltage

PCS-9611S Feeder Relay 3-137


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The voltage setting of stage 1 of residual
2 59G1.3U0_Set 1~200 50 V 0.001
overvoltage protection
The dropout coefficient of stage 1 of residual
3 59G1.K_DropOut 0.93 ~1 0.98 - 0.001
overvoltage protection
The operating time setting of stage 1 of
4 59G1.t_Op 0.1 ~100 1 s 0.001
residual overvoltage protection
The dropout time setting of stage 1 of
5 59G1.t_DropOut 0 ~100 0 s 0.001
residual overvoltage protection

3 The logic setting for enabling/disabling the


Disabled; stage 1 of residual overvoltage protection
6 59G1.En Enabled - -
Enabled 0: disabling
1: enabling
Enabling stage 1 of residual overvoltage
Trp; protection operate to trip or alarm.
7 59G1.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose
Alm: for alarm purpose
The voltage setting of stage 2 of residual
8 59G2.3U0_Set 1~200 50 V 0.001
overvoltage protection
The dropout coefficient of stage 2 of residual
9 59G2.K_DropOut 0.93 ~1 0.98 - 0.001
overvoltage protection
The operating time setting of stage 2 of
10 59G2.t_Op 0.1 ~100 1 s 0.001
residual overvoltage protection
The dropout time setting of stage 2 of
11 59G2.t_DropOut 0 ~100 0 s 0.001
residual overvoltage protection
The logic setting for enabling/disabling the
Disabled; stage 2 of residual overvoltage protection
12 59G2.En Enabled - -
Enabled 0: disabling
1: enabling
Enabling stage 2 of residual overvoltage
Trp; protection operate to trip or alarm.
13 59G2.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose
Alm: for alarm purpose

3.13 Negative-sequence Overvoltage Protection (59Q)

When the system has a broken-conductor, reverse phase sequence or inter-phase voltage
imbalance, the negative-sequence voltage increases, and the negative-sequence overvoltage
protection can reflect the system imbalance fault. It is used to protect the equipment from
insulation breakdown or premature aging due to overvoltage. The negative-sequence overvoltage
protection can also be used to alarm for prompting users the system voltage state is abnormal at
this moment.

3-138 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

3.13.1 Function Description


This device provides two stages of negative-sequence overvoltage protection. If the
negative-sequence voltage is larger than the predefined setting, this protection will operate. The
negative-sequence overvoltage protection can operate with a definite-time limit, and the
supported dropout characteristics include instantaneous dropout and definite-time dropout.

Negative-sequence overvoltage protection can be enabled or disabled via the settings or binary
input signals, for some specific applications, overvoltage protection needs to be blocked by the
external signal, so the device provides a function block input signal to be used to block
overvoltage protection. The enabling and blocking logic of negative-sequence overvoltage
protection is shown in the figure below: 3
The logic diagram of enabling/disabling negative-sequence overvoltage protection is shown as
below.

EN 59Qx.En & 59Qx.On

SIG 59Qx.Enable

& 59Qx.Blocked
SIG 59Qx.Block ≥1

SIG Fail_Device
& 59Qx.Valid

Figure 3.13-1 Logic diagram of enabling/disabling negative-sequence overvoltage protection

When the negative-sequence overvoltage protection is enabled and no external blocking signal is
input, if the negative-sequence voltage is larger than the voltage setting multiplied by the dropout
coefficient setting of the negative-sequence overvoltage protection, the negative-sequence
overvoltage protection will pick up.

The logic diagram of the fault detector of the negative-sequence overvoltage protection is shown
as below.

SET U2 >U2_DropOut & 59Qx.Pkp


0ms 500ms
&
SIG 59Qx.On & FD.Pkp

SIG 59Qx.Valid

EN [59Qx.Opt_Trp/Alm]=Alm

Figure 3.13-2 Logic diagram of the fault detector of negative-sequence overvoltage protection

Where:

PCS-9611S Feeder Relay 3-139


Date: 2019-04-24
3 Protection Functions

U2_DropOut: the dropout voltage value, i.e. [59Qx.K_DropOut]*[59Qx.U2_Set]

3.13.1.1 Operation Characteristic

Negative-sequence overvoltage protection can operate with a definite-time limit, the characteristic
curve meets the IEC60255-3 and ANSI C37.112 standards.

When the negative-sequence voltage is larger than the voltage setting, the protection operates
with a time delay of top (i.e. the value of the setting [59Qx.t_Op]), and the operation
characteristic curve is shown in the following figure:

t
3

t op

U2p U2

Figure 3.13-3 Operation characteristic curve of negative-sequence overvoltage protection

3.13.1.2 Dropout Characteristic

The supported dropout characteristics of the negative-sequence overvoltage protection include


instantaneous dropout and definite-time dropout.

 Instantaneous dropout

When U2 <[ 59Qx.K_DropOut]*[59Qx.U2_Set] (x: 1~2), the protection drops out immediately.

 Definite-time dropout

When U2 <[59Qx.K_DropOut]*[59Qx.U2_Set] (x: 1~2), the protection drops out with a time delay
of tdr (i.e. the value of the setting [59Qx.t_DropOut]), and the dropout characteristic curve is
shown in the following figure:

3-140 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Start time

U 2> U2p

Start signal

Operating
signal
3
Protection
Operating threshold operate

Operating
counter

t dr t dr t dr
Dropout time setting
Dropout time
Dropout time

Figure 3.13-4 Definite-time dropout characteristic of negative-sequence overvoltage protection

3.13.2 Function Block Diagram

59Q

59Qx.Enable 59Qx.On
59Qx.Block 59Qx.Blocked
59Qx.Valid
59Qx.St
59Qx.Op
59Qx.Alm

3.13.3 I/O Signals


Table 3.13-1 Input/output signals of negative-sequence overvoltage protection

No. Input Signal Description


Stage x of negative-sequence overvoltage protection enabling input, it is
1 59Qx.Enable
triggered from binary input or programmable logic etc. (x=1~2)
Stage x of negative-sequence overvoltage protection blocking input, it is
2 59Qx.Block
triggered from binary input or programmable logic etc. (x=1~2)
No. Output Signal Description
1 59Qx.On Stage x of negative-sequence overvoltage protection is enabled

PCS-9611S Feeder Relay 3-141


Date: 2019-04-24
3 Protection Functions

2 59Qx.Blocked Stage x of negative-sequence overvoltage protection is blocked


3 59Qx.Valid Stage x of negative-sequence overvoltage protection is valid
4 59Qx.St Stage x of negative-sequence overvoltage protection starts
5 59Qx.Op Stage x of negative-sequence overvoltage protection operates
6 59Qx.Alm Stage x of negative-sequence overvoltage protection alarms

3.13.4 Logic

59Qx.St

SET U2 > [59Qx.U2_Set] &


3 SIG 59Qx.Pkp
[59Qx.t_Op] [59Qx.t_DropOut]
& 59Qx.Op

SET [59Qx.Opt_Trp/Alm] = Trp


& 59Qx.Alm

SET [59Qx.Opt_Trp/Alm] = Alm

Figure 3.13-5 Logic diagram of negative-sequence overvoltage protection

3.13.5 Settings
 Access path:

MainMenu  Settings  Protection Settings  NegOV Settings

Table 3.13-2 Settings of negative-sequence overvoltage protection

No. Setting Range Default Unit Step Description


The voltage setting of the stage 1 of
1 59Q1.U2_Set 2~100 15 V 0.001
negative-sequence overvoltage protection
The dropout coefficient setting of the stage
2 59Q1.K_DropOut 0.93~1 0.98 - 0.001 1 of negative-sequence overvoltage
protection
The time setting of the stage 1 of
3 59Q1.t_Op 0.1~100 1 s 0.001
negative-sequence overvoltage protection
The dropout time setting of the stage 1 of
4 59Q1.t_DropOut 0~100 0 s 0.001
negative-sequence overvoltage protection
Disabled; The logic setting of the stage 1 of
5 59Q1.En Enabled - -
Enabled negative-sequence overvoltage protection
Enabling stage 1 of negative-sequence
Trp; overvoltage operate to trip or alarm.
6 59Q1.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose
Alm: for alarm purpose
The voltage setting of the stage 2 of
7 59Q2.U2_Set 2~100 15 V 0.001
negative-sequence overvoltage protection

3-142 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

The dropout coefficient setting of the stage


8 59Q2.K_DropOut 0.93~1 0.98 - 0.001 2 of negative-sequence overvoltage
protection
The time setting of the stage 2 of
9 59Q2.t_Op 0.1~100 1 s 0.001
negative-sequence overvoltage protection
The dropout time setting of the stage 2 of
10 59Q2.t_DropOut 0~100 0 s 0.001
negative-sequence overvoltage protection
Disabled; The logic setting of the stage 2 of
11 59Q2.En Enabled - -
Enabled negative-sequence overvoltage protection
Enabling stage 2 of negative-sequence

12 59Q2.Opt_Trp/Alm
Trp;
Trp - -
overvoltage operate to trip or alarm. 3
Alm Trp: for tripping purpose
Alm: for alarm purpose

3.14 Positive-sequence Overvoltage Protection (59Pos)

3.14.1 Function Description

This device provides one stage of positive-sequence overvoltage protection. If the


positive-sequence voltage is larger than the pre-defined setting, this protection will operate. The
positive-sequence overvoltage protection can operate with a definite-time limit, and the supported
dropout characteristics include instantaneous dropout and definite-time dropout.

Positive-sequence overvoltage protection can be enabled or disabled via the settings or binary
input signals, for some specific applications, overvoltage protection needs to be blocked by the
external signal, so the device provides a function block input signal to be used to block
overvoltage protection. The enabling and blocking logic of positive-sequence overvoltage
protection is shown in the figure below:

The logic diagram of enabling/disabling positive-sequence overvoltage protection is shown as


below

EN 59Pos.En & 59Pos.On

SIG 59Pos.Enable

& 59Pos.Blocked
SIG 59Pos.Block ≥1

SIG Fail_Device
& 59Pos.Valid

Figure 3.14-1 Logic diagram of enabling/disabling positive-sequence overvoltage protection

When the positive-sequence overvoltage protection is enabled and no external blocking signal is

PCS-9611S Feeder Relay 3-143


Date: 2019-04-24
3 Protection Functions

input, if the positive-sequence voltage is larger than the voltage setting multiplied by the dropout
coefficient setting of the positive-sequence overvoltage protection, the positive-sequence
overvoltage protection will pick up.

The logic diagram of the fault detector of the positive-sequence overvoltage protection is shown
as below.

SET U1 >U1_DropOut & 59Pos.Pkp


0ms 500ms
&
SIG 59Pos.On & FD.Pkp

3 SIG 59Pos.Valid

EN [59Pos.Opt_Trp/Alm]=Alm

Figure 3.14-2 Logic diagram of the fault detector of positive-sequence overvoltage protection

Where:

U1: the positive-sequence voltage;

U1_DropOut: the dropout voltage value, i.e. [59Pos.K_DropOut]*[59Pos.U1_Set].

3.14.1.1 Operation Characteristic

Positive-sequence overvoltage protection can operate with a definite-time limit, the characteristic
curve meets the IEC60255-3 and ANSI C37.112 standards.

When the positive-sequence voltage is larger than the voltage setting, the protection operates
with a time delay of top (i.e. the value of the setting [59Pos.t_Op]), and the operation
characteristic curve is shown in the following figure:

t op

U 1p U1

Figure 3.14-3 Operation characteristic curve of positive-sequence overvoltage protection

3-144 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

3.14.1.2 Dropout Characteristic

The supported dropout characteristics of the positive-sequence overvoltage protection include


instantaneous dropout and definite-time dropout.

 Instantaneous dropout

When U <[ 59Pos.K_DropOut]*[59Pos.U1_Set] (x: 1~2), the protection drops out immediately.
1

 Definite-time dropout

When U <[59Pos.K_DropOut]*[59Pos.U1_Set] (x: 1~2), the protection drops out with a time delay
1

of tdr (i.e. the value of the setting [59Pos.t_DropOut]), and the dropout characteristic curve is
shown in the following figure: 3
Start time

U 1> U1p

Start signal

Operating
signal

Protection
Operating threshold operate

Operating
counter

t dr t dr t dr
Dropout time setting
Dropout time
Dropout time

Figure 3.14-4 Definite-time dropout characteristic of positive-sequence overvoltage protection

PCS-9611S Feeder Relay 3-145


Date: 2019-04-24
3 Protection Functions

3.14.2 Function Block Diagram

59Pos

59Pos.Enable 59Pos.On
59Pos.Block 59Pos.Blocked
59Pos.Valid
59Pos.St
59Pos.Op
59Pos.Alm

3 3.14.3 I/O Signals


Table 3.14-1 Input/output signals of positive-sequence overvoltage protection

No. Input Signal Description


Positive-sequence overvoltage protection enabling input, it is triggered from
1 59Pos.Enable
binary input or programmable logic etc.
Positive-sequence overvoltage protection blocking input, it is triggered from
2 59Pos.Block
binary input or programmable logic etc.
No. Output Signal Description
1 59Pos.On Positive-sequence overvoltage protection is enabled
2 59Pos.Blocked Positive-sequence overvoltage protection is blocked
3 59Pos.Valid Positive-sequence overvoltage protection is valid
4 59Pos.St Positive-sequence overvoltage protection starts
5 59Pos.Op Positive-sequence overvoltage protection operates
6 59Pos.Alm Positive-sequence overvoltage protection alarms

3.14.4 Logic

59Pos.St

SET U1 > [59Pos.U1_Set] &


[59Pos.t_Op] [59Pos.t_DropOut]
& 59Pos.Op
SIG 59Pos.Pkp

SET [59Pos.Opt_Trp/Alm] = Trp


& 59Pos.Alm

SET [59Pos.Opt_Trp/Alm] = Alm

Figure 3.14-5 Logic diagram of positive-sequence overvoltage protection

3.14.5 Settings
 Access path:

MainMenu  Settings  Protection Settings  PosOV Settings

3-146 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Table 3.14-2 Settings of positive-sequence overvoltage protection

No. Setting Range Default Unit Step Description


The voltage setting of the
1 59Pos.U1_Set 2~100 60 V 0.001
positive-sequence overvoltage protection
The dropout coefficient setting of the
2 59Pos.K_DropOut 0.93~1 0.98 - 0.001
positive-sequence overvoltage protection
The time setting of the positive-sequence
3 59Pos.t_Op 0.1~100 1 s 0.001
overvoltage protection
The dropout time setting of the
4 59Pos.t_DropOut 0~100 0 s 0.001
positive-sequence overvoltage protection
Disabled; The logic setting of the positive-sequence 3
5 59Pos.En Enabled - -
Enabled overvoltage protection
Enabling the positive-sequence
Trp; overvoltage operate to trip or alarm.
6 59Pos.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose
Alm: for alarm purpose

3.15 Phase Undervoltage Protection (27P)


Some abnormal conditions in the power system will lead to low voltage. Electric equipment such
as motors cannot operate for a long time under the rated voltage and need to be removed from
the system in time. In addition, the voltage reduction may also be related to the shortage of
system reactive power. Reducing part of the reactive power load through the undervoltage
protection can help increase the voltage level of the system.

3.15.1 Function Description


The device can provide two stages of phase undervoltage protection with independent logic.
When the voltage drops in the system and it is lower than the voltage threshold, phase
undervoltage protection will operate.

Taking into account that the role of undervoltage protection is to remove the running device from
the system, but in order to prevent that undervoltage protection is always operating when it is not
charged, the breaker closed position check criterion is added, users can choose to detect the
breaker position, current or no-check as the releasing condition for the protection.

In addition, the undervoltage protection also provides the alarm function, prompting the voltage
drop of the system, it allows users to find the cause timely, and preventing further deterioration of
the fault. Each stage of phase undervoltage protection can be independently set as definite-time
characteristics or inverse-time characteristics. The dropout characteristics can be set as
instantaneous dropout and definite-time dropout.

Users can select phase voltage or phase-to-phase voltage for the protection calculation via the
setting [27P.Opt_Up/Upp]. If it is set as “0”, phase voltage criterion is selected, and if it is set to “1”,
phase-to-phase voltage criterion is selected.

Users can select “1-out-of-3” or “3-out-of-3” logic for the protection criterion via the setting

PCS-9611S Feeder Relay 3-147


Date: 2019-04-24
3 Protection Functions

[27P.Opt_1P/3P]. If it is set as “1P”, phase undervoltage protection can operate if any


phase/phase-to-phase voltage is smaller than the voltage setting. If it is set as “3P”, phase
undervoltage protection cannot operate unless three phase/phase-to-phase voltages are smaller
than the voltage setting.

The breaker closed position check mode is configured via the setting [27P.Opt_LogicMode], it
includes:

[27P.Opt_LogicMode]=None: no-check;

[27P.Opt_LogicMode]=Curr: check the current;

3 [27P.Opt_LogicMode]=CBPos: check the breaker position;

[27P.Opt_LogicMode]=CurrAndCBPos: check the current and the breaker position;

[27P.Opt_LogicMode]=CurrOrCBPos: check the current or the breaker position.

Undervoltage protection can be enabled or disabled via the settings or binary input signals, for
some specific applications, undervoltage protection needs to be blocked by the external signal, so
the device provides a function block input signal to be used to block undervoltage protection. The
enabling and blocking logic of undervoltage protection is shown in the figure below:

EN 27Px.En &
27Px.On

SIG 27Px.Enable

&
SIG 27Px.Block ≥1 27Px.Blocked

SIG Fail_Device
&
27Px.Valid

Figure 3.15-1 The enabling and blocking logic of phase undervoltage protection

The logic diagram of the fault detector element of phase undervoltage protection is as follows:

3-148 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

SET [27P.Opt_1P/3P]=3P
&
SET [27P.Opt_Up/Upp]=Upp

SET Uab<[U_DropOut]
&
SET Ubc<[U_DropOut]

SET Uca<[U_DropOut]
>=1
&
SET [27P.Opt_1P/3P]=1P

SET Uab<[U_DropOut]
>=1
SET Ubc<[U_DropOut] 3
SET Uca<[U_DropOut]

SET [27P.Opt_1P/3P]=3P
&
SET [27P.Opt_Up/Upp]=Up

SET Ua<[U_DropOut]
&
SET Ub<[U_DropOut] >=1
SET Uc<[U_DropOut]
>=1 Pickup voltage criterion
&
SET [27P.Opt_1P/3P]=1P

SET Ua<[U_DropOut]
>=1
SET Ub<[U_DropOut]

SET Uc<[U_DropOut]

SET [27P.Opt_LogicMode]=None

SET [27P.Opt_LogicMode]=Curr & >=1


>=1
SIG Ia, Ib and Ic > 0.04In Auxiliary criterion

SET [27P.Opt_LogicMode]=CBPos &

SIG CB closed position

>=1
&
>=1
SET [27P.Opt_LogicMode]=CurrOrCBPos

&
&

SET [27P.Opt_LogicMode]=CurrAndCBPos

PCS-9611S Feeder Relay 3-149


Date: 2019-04-24
3 Protection Functions

SIG Pickup voltage criterion


& 27Px.Pkp
SIG Auxiliary criterion 0 500ms &
&
SIG VTS.Alm & FD.Pkp

&
EN [27Px.En_VTS_Blk]

SIG 27Px.On

SIG 27Px.Valid

3
SET [27Px.Opt_Trp/Alm]=Alm

Figure 3.15-2 Logic diagram of the fault detector element of phase undervoltage protection

Where:

U_DropOut: the dropout voltage value, i.e. [27Px.K_DropOut]*[27Px.U_Set]

3.15.1.1 Operation Characteristic

Undervoltage protection can operate with a definite-time limit, it can also operate with an
inverse-time limit, the characteristic curve meets the IEC60255-3 and ANSI C37.112 standards.
Undervoltage protection can support definite-time limit, IEC & ANSI standard inverse time limit
and user-defined inverse-time limit, users can select the wanted operating curve by the setting
[27Px.Opt_Curve] (x=1 or 2), the relationship between the value of the setting and the curve is
shown in the table below.

27Px.Opt_Curve Time Characteristic k α c


ANSIDefTime ANSI Definite Time - - -
IECDefTime IEC Definite Time - - -
UserDefine UserDefine
InvTime_U InvCrv_U 1 1 0

When the setting [27Px.Opt_Curve] is set as “InvTime_U”, the operation characteristic is the
corresponding selected operating curve type, and the settings [27Px.K], [27Px.C] and
[27Px.Alpha] are useless.

When the setting [27Px.Opt_Curve] is set as “UserDefine”, i.e. the user-defined inverse-time
characteristic is selected, the inverse-time operating curve is determined by the settings [27Px.K],
[27Px.C] and [27Px.Alpha].

When the setting [27Px.Opt_Curve] is set as “ANSIDefTime” or “IECDefTime”, it is definite-time


undervoltage protection.

 Definite-time characteristic

When U < Up , the protection operates with a time delay of top (i.e. the value of the setting
[27Px.t_Op]), and the operation characteristic curve is shown in the following figure:

3-150 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

t op

3
Up U

Figure 3.15-3 Definite-time operation characteristic curve of phase undervoltage protection

 Inverse-time characteristic

When U < Up , the inverse-time accumulator begins to accumulate, and the operating time is
affected by the applied voltage U . The lower voltage is, the smaller the operating time is, but not
unlimited. When the voltage is low enough to a certain threshold ( Up ), the inverse-time operating
time will not continue to decrease, then the operation characteristic becomes the definite-time
characteristic, and the operating time is tmin , i.e. the setting [27Px.tmin]. The inverse-time
operation characteristic equation is:

 k 
t 
 c   TMS
1  (U / U P ) 

Where:

Up is the voltage setting [27Px.U_Set];

TMS is the inverse-time time multiplier, i.e. the setting [27Px.TMS];

k is the inverse-time coefficient K, i.e. the setting [27Px.K];


c is the inverse-time coefficient C, i.e. the setting [27Px.C];
 is the inverse-time coefficient Alpha, i.e. the setting [27Px.Alpha];

U is the measured voltage.


The inverse-time operation characteristic curve is shown as below:

PCS-9611S Feeder Relay 3-151


Date: 2019-04-24
3 Protection Functions

3 t min

UD UP U

Figure 3.15-4 Inverse-time operation characteristic curve of phase undervoltage protection

When the applied voltage is not a fixed value, but changes with time, the operating behavior of the
protection is shown in the following equation:

T0
1
 t (U )dt
0
1

Where:

T0 is the operating time of the protection element;

t (U ) is the theoretical operating time when the voltage is U .

3.15.1.2 Dropout Characteristic

The supported dropout characteristics of the undervoltage protection include instantaneous


dropout and definite-time dropout.

 Instantaneous dropout

When U >[27Px.K_DropOut]* Up , the protection drops out immediately.

 Definite-time dropout

When U >[27Px.K_DropOut]* Up , the protection drops out with a time delay of tdr (i.e. the value
of the setting [27Px.t_DropOut]), and the dropout characteristic curve is shown in the following
figure:

3-152 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Start time

U<Up

Start
signal

Operating
signal
3
Protection
Operating threshold operate

Operating
counter

t dr t dr t dr
Dropout time setting
Dropout time
Dropout time

Figure 3.15-5 Definite-time dropout characteristic of undervoltage protection

3.15.2 Function Block Diagram

27P

27Px.Enable 27Px.On

27Px.Block 27Px.Blocked

27Px.Valid

27Px.St

27Px.StA

27Px.StB

27Px.StC

27Px.Op

27Px.Op.PhA

27Px.Op.PhB

27Px.Op.PhC

27Px.Alm

PCS-9611S Feeder Relay 3-153


Date: 2019-04-24
3 Protection Functions

3.15.3 I/O Signal


Table 3.15-1 Input/output signals of phase undervoltage protection

No. Input signal Description


Stage x of phase undervoltage protection enabling input, it is triggered from binary
1 27Px.Enable
input or programmable logic etc. (x=1~2)
Stage x of phase undervoltage protection blocking input, it is triggered from binary
2 27Px.Block
input or programmable logic etc. (x=1~2)
No. Output signal Description
1 27Px.On Stage x of phase undervoltage protection is enabled

3 2 27Px.Blocked Stage x of phase undervoltage protection is blocked


3 27Px.Valid Stage x of phase undervoltage protection is valid
4 27Px.St Stage x of phase undervoltage protection starts
5 27Px.StA Stage x of phase undervoltage protection starts (Phase A)
6 27Px.StB Stage x of phase undervoltage protection starts (Phase B)
7 27Px.StC Stage x of phase undervoltage protection starts (Phase C)
8 27Px.Op Stage x of phase undervoltage protection operates
9 27Px.Op.PhA Stage x of phase undervoltage protection operates (Phase A)
10 27Px.Op.PhB Stage x of phase undervoltage protection operates (Phase B)
11 27Px.Op.PhC Stage x of phase undervoltage protection operates (Phase C)
12 27Px.Alm Stage x of undervoltage protection alarms

3-154 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

3.15.4 Logic

SET [27P.Opt_1P/3P]=3P
&
SET [27P.Opt_Up/Upp]=Upp

SET Uab<[27Px.U_Set]
&
SET Ubc<[27Px.U_Set]

SET Uca<[27Px.U_Set]
>=1
&
SET [27P.Opt_1P/3P]=1P

SET Uab<[27Px.U_Set]
>=1
3
SET Ubc<[27Px.U_Set]

SET Uca<[27Px.U_Set]

SET [27P.Opt_1P/3P]=3P
&
SET [27P.Opt_Up/Upp]=Up

SET Ua<[27Px.U_Set]
&
SET Ub<[27Px.U_Set] >=1
SET Uc<[27Px.U_Set]
>=1 Voltage criterion
&
SET [27P.Opt_1P/3P]=1P

SET Ua<[27Px.U_Set]
>=1
SET Ub<[27Px.U_Set]

SET Uc<[27Px.U_Set]

SIG Voltage criterion 27Px.St


&
SIG Auxiliary criterion & Timer
t
t
SIG VTS.Alm &
&
EN [27Px.En_VTS_Blk]

SIG 27Px.On

SIG 27Px.Pkp
&
27Px.Op
SET [27Px.Opt_Trp/Alm]=Trp

&
27Px.Alm

SET [27Px.Opt_Trp/Alm]=Alm

Figure 3.15-6 Logic diagram of phase undervoltage protection

PCS-9611S Feeder Relay 3-155


Date: 2019-04-24
3 Protection Functions

Where:

Auxiliary criterion: please refer to Figure 3.15-2.

3.15.5 Settings
 Access path:

MainMenu  Settings  Protection Settings  UV Settings

Table 3.15-2 Settings of phase undervoltage protection

Default

3
No. Settings Range Unit Step Description
value
Option of phase-to-phase
voltage or phase voltage
for stage x of
Up;
1 27P.Opt_Up/Upp Upp - - undervoltage protection
Upp
Up: phase voltage
Upp: phase-to-phase
voltage
Option of 1-out-of-3 mode
or 3-out-of-3 mode for
3P; stage x of undervoltage
2 27P.Opt_1P/3P 3P - -
1P protection
3P: 3-out-of-3 mode
1P: 1-out-of-3 mode
Breaker closed position
check mode
None: no check
Curr: check the current
None; CBPos: check the
Curr; normally open auxiliary
3 27P.Opt_LogicMode CBPos; Curr - - contact
CurrOrCBPos; CurrOrCBPos: check the
CurrAndCBPos current and normally open
auxiliary contact
CurrAndCBPos: check the
current or normally open
auxiliary contact
The voltage setting of
4 27P1.U_Set 5~120 80 V 0.001 stage 1 of phase
undervoltage protection
The dropout coefficient of
5 27P1.K_DropOut 1~1.2 1.03 - 0.001 stage 1 of phase
undervoltage protection

3-156 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The operating time setting
6 27P1.t_Op 0.1 ~100 1 s 0.001 of stage 1 of phase
undervoltage protection
The dropout time setting
7 27P1.t_DropOut 0 ~100 0 s 0.001 of stage 1 of phase
undervoltage protection
Logic setting to determine
the behavior of stage 1 of
phase undervoltage
protection when VT circuit
3
supervision function is
Disabled;
8 27P1.En_VTS_Blk Disabled - - enabled and VT circuit
Enabled
failure happens.
0: it is not effected by VT
circuit failure
1: it will be blocked by VT
circuit failure signal
The logic setting for
enabling/disabling the
Disabled; stage 1 of phase
9 27P1.En Enabled - -
Enabled undervoltage protection
0: disabling
1: enabling
Enabling stage 1 of phase
undervoltage protection
Trp;
10 27P1.Opt_Trp/Alm Trp - - operate to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose
The setting for selecting
ANSIDefTime;
the inverse-time operation
IECDefTime;
11 27P1.Opt_Curve IECDefTime - - characteristic curve of
UserDefine;
stage 1 of phase
InvTime_U
undervoltage protection.
The setting for selecting
the inverse-time dropout
characteristic curve of
stage 1 of phase
Inst;
12 27P1.Opt_Curve_DropOut Inst - - undervoltage protection
DefTime
Inst: instantaneous
dropout
DefTime: definite-time
dropout

PCS-9611S Feeder Relay 3-157


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The time multiplier setting
13 27P1.TMS 0.04~ 20 1 - 0.001 of stage 1 of phase
undervoltage protection
The minimum operating
time setting of stage 1 of
14 27P1.tmin 0.03 ~10 0.03 s 0.001
phase undervoltage
protection
The constant “k” of the

3 15 27P1.K 0.001~120 0.14 - 0.0001


customized inverse-time
operation characteristic of
stage 1 of phase
undervoltage protection
The constant “α” of the
customized inverse-time
16 27P1.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of
stage 1 of phase
undervoltage protection
The constant “C” of the
customized inverse-time
17 27P1.C 0 ~1 0 - 0.0001 operation characteristic of
stage 1 of phase
undervoltage protection
The voltage setting of
18 27P2.U_Set 5~120 80 V 0.001 stage 2 of phase
undervoltage protection
The dropout coefficient of
19 27P2.K_DropOut 1~1.2 1.03 - 0.001 stage 2 of phase
undervoltage protection
The operating time setting
20 27P2.t_Op 0.1 ~100 1 s 0.001 of stage 2 of phase
undervoltage protection
The dropout time setting
21 27P2.t_DropOut 0 ~100 0 s 0.001 of stage 2 of phase
undervoltage protection

3-158 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
Logic setting to determine
the behavior of stage 2 of
phase undervoltage
protection when VT circuit
supervision function is
Disabled;
22 27P2.En_VTS_Blk Disabled - - enabled and VT circuit
Enabled
failure happens.
0: it is not effected by VT
circuit failure
1: it will be blocked by VT
3
circuit failure signal
The logic setting for
enabling/disabling the
Disabled; stage 2 of phase
23 27P2.En Enabled - -
Enabled undervoltage protection
0: disabling
1: enabling
Enabling stage 2 of phase
undervoltage protection
Trp;
24 27P2.Opt_Trp/Alm Trp - operate to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose
The setting for selecting
ANSIDefTime;
the inverse-time operation
IECDefTime;
25 27P2.Opt_Curve IECDefTime - - characteristic curve of
UserDefine;
stage 2 of phase
InvTime_U
undervoltage protection.
The setting for selecting
the inverse-time dropout
characteristic curve of
stage 2 of phase
Inst;
26 27P2.Opt_Curve_DropOut Inst - - undervoltage protection
DefTime
Inst: instantaneous
dropout
DefTime: definite-time
dropout
The time multiplier setting
27 27P2.TMS 0.04~ 20 1 0.001 of stage 2 of phase
undervoltage protection

PCS-9611S Feeder Relay 3-159


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
The minimum operating
time setting of stage 2 of
28 27P2.tmin 0.03 ~10 0.03 s 0.001
phase undervoltage
protection
The constant “k” of the
customized inverse-time
29 27P2.K 0.001~120 0.14 - 0.0001 operation characteristic of
stage 2 of phase

3 undervoltage protection
The constant “α” of the
customized inverse-time
30 27P2.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of
stage 2 of phase
undervoltage protection
The constant “C” of the
customized inverse-time
31 27P2.C 0 ~1 0 - 0.0001 operation characteristic of
stage 2 of phase
undervoltage protection

3.16 Overfrequency Protection (81O)

Frequency is an important index of the power quality, which can reflect the balance of the output
power of the generator and the active power of the load. The increase of frequency indicates that
the output power of the system is much larger than that of the load. When the system frequency is
greater than the predefined setting, the overfrequency protection will operate for removing some
part of active power supplies from the system.

3.16.1 Function Description


The device can provide six stages of overfrequency protection. If the system frequency is greater
than the setting, overfrequency protection will operate to remove some part of active power
supplies from the system. Overfrequency protection is with independent definite-time
characteristics and with instantaneous dropout characteristics.

Overfrequency protection protection can be enabled or disabled via the settings or binary input
signals, for some specific applications, overfrequency protection needs to be blocked by the
external signal, so the device provides a function block input signal to be used to block
overfrequency protection. The enabling and blocking logic of overfrequency protection is shown in
the figure below:

3-160 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

EN 81Ox.En & 81Ox.On

SIG 81Ox.Enable

& 81Ox.Blocked
SIG 81Ox.Block ≥1

SIG Fail_Device
& 81Ox.Valid

Figure 3.16-1 Logic diagram of enabling/disabling overfrequency protection


3
When the overfrequency protection is enabled and no external blocking signal is input, if the
system frequency is greater than the frequency setting of the overfrequency protection and all the
phase-to-phase voltages are greater than the setting of the voltage blocking element of the
overfrequency protection, the overfrequency protection will pick up.

The logic diagram of the fault detector of the overfrequency protection is shown in Figure 3.16-2.

SET f > [81Ox.f_Set] &

SET Upp_min > [81.Upp_Blk]

& 81Ox.Pkp
0ms 500ms
&
SIG 81Ox.On
FD.Pkp

SIG 81Ox.Valid

Figure 3.16-2 Logic diagram of the fault detector of overfrequency protection

3.16.1.1 Operation Characteristic

The overfrequency protection has definite-time delay characteristic complied with IEC 60255-3
and ANSI C37.112. If the system frequency is greater than the frequency setting [81Ox.f_Set] (x:
1~6), the overfrequency protection will operate after the time setting [81Ox.t_Op] (x: 1~6).

The operation characteristic curve of overfrequency protection is shown in Figure 3.16-3.

PCS-9611S Feeder Relay 3-161


Date: 2019-04-24
3 Protection Functions

t op

fp f

Figure 3.16-3 Operation characteristic curve of overfrequency protection

3.16.1.2 Dropout Characteristic

The overfrequency protection is with instantaneous dropout characteristic. If the system frequency
is less than the setting [81Ox.f_Set] (x: 1~6), the overfrequency protection will drop out at once.

3.16.2 Function Block Diagram

81O

81Ox.Enable 81Ox.On
81Ox.Blocked
81Ox.Block
81Ox.Valid
81Ox.St
81Ox.Op

Figure 3.16-4 Function block diagram of overfrequency protection

3.16.3 I/O Signals


Table 3.16-1 Input/output signals of overfrequency protection

No. Input Signal Description


Stage x of overfrequency protection enabling input, it is triggered from binary
1 81Ox.Enable
input or programmable logic etc. (x=1~6)
Stage x of overfrequency protection blocking input, it is triggered from binary
2 81Ox.Block
input or programmable logic etc. (x=1~6)
No. Output Signal Description
1 81Ox.On Stage x of overfrequency protection is enabled.
2 81Ox.Blocked Stage x of overfrequency protection is blocked.

3-162 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

3 81Ox.Valid Stage x of overfrequency protection is valid.


4 81Ox.St Stage x of overfrequency protection starts.
5 81Ox.Op Stage x of overfrequency protection operates.

3.16.4 Logic

SET f>[81Ox.f_Set] & 81Ox.St

&
SET Upp_min>[81.Upp_Blk] [81Ox.t_Op] 0 81Ox.Op

SIG 81Ox.Pkp

3
Figure 3.16-5 Logic diagram of overfrequency protection

3.16.5 Settings
 Access path:

MainMenu  Settings  Protection Settings  FreqProt Settings

Table 3.16-2 Settings of overfrequency protection

No. Setting Range Default Unit Step Description


The setting of the low voltage blocking
1 81.Upp_Blk 10~150 70 V 0.001 element of the frequency protection
(phase-to-phase voltage)
The frequency setting of the stage 1 of
2 81O1.f_Set 50~65 52 Hz 0.001
overfrequency protection
The time setting of the stage 1 of
3 81O1.t_Op 0.1~100 0.3 s 0.001
overfrequency protection
Disabled; The logic setting of the stage 1 of
4 81O1.En Enabled - -
Enabled overfrequency protection
The frequency setting of the stage 2 of
5 81O2.f_Set 50~65 52 Hz 0.001
overfrequency protection
The time setting of the stage 2 of
6 81O2.t_Op 0.1~100 0.3 s 0.001
overfrequency protection
Disabled; The logic setting of the stage 2 of
7 81O2.En Enabled - -
Enabled overfrequency protection
The frequency setting of the stage 3 of
8 81O3.f_Set 50~65 52 Hz 0.001
overfrequency protection
The time setting of the stage 3 of
9 81O3.t_Op 0.1~100 0.3 s 0.001
overfrequency protection
Disabled; The logic setting of the stage 3 of
10 81O3.En Enabled - -
Enabled overfrequency protection
The frequency setting of the stage 4 of
11 81O4.f_Set 50~65 52 Hz 0.001
overfrequency protection

PCS-9611S Feeder Relay 3-163


Date: 2019-04-24
3 Protection Functions

The time setting of the stage 4 of


12 81O4.t_Op 0.1~100 0.3 s 0.001
overfrequency protection
Disabled; The logic setting of the stage 4 of
13 81O4.En Enabled - -
Enabled overfrequency protection
The frequency setting of the stage 5 of
14 81O5.f_Set 50~65 52 Hz 0.001
overfrequency protection
The time setting of the stage 5 of
15 81O5.t_Op 0.1~100 0.3 s 0.001
overfrequency protection
Disabled; The logic setting of the stage 5 of
16 81O5.En Enabled - -
Enabled overfrequency protection

3 17 81O6.f_Set 50~65 52 Hz 0.001


The frequency setting of the stage 6 of
overfrequency protection
The time setting of the stage 6 of
18 81O6.t_Op 0.1~100 0.3 s 0.001
overfrequency protection
Disabled; The logic setting of the stage 6 of
19 81O6.En Enabled - -
Enabled overfrequency protection

3.17 Underfrequency Protection (81U)

Frequency is an important index of the power quality, which can reflect the balance of the output
power of the generator and the active power of the load. The decrease of frequency indicates that
the output power of the system is much less than that of the load. When the system frequency is
less than the predefined setting, the underfrequency protection will operate for shedding some
part of loads from the system.

3.17.1 Function Description

This device provides six stages of underfrequency protection. If the system frequency is less than
the predefined setting, this protection will operate for shedding some part of loads from the system.
The underfrequency protection is with independent definite-time delay characteristic and with
instantaneous dropout characteristic.

3.17.1.1 Underfrequency Protection

The underfrequency protection can be enabled or disabled by the settings. If the setting [81Ux.En]
(x: 1~6) is set as “1”, and the signal [81Ux.Enable] (x: 1~6) is “1” and the signal [81Ux.Block] (x:
1~6) is “0”. For some special application, the underfrequency protection needs to be blocked by
external signal, the input signal [81Ux.Block] (x: 1~6) is provided for this purpose.

The logic diagram of enabling/disabling underfrequency protection is shown in Figure 3.17-1.

3-164 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

EN 81Ux.En & 81Ux.On

SIG 81Ux.Enable

& 81Ux.Blocked
SIG 81Ux.Block ≥1

SIG Fail_Device
& 81Ux.Valid

Figure 3.17-1 Logic diagram of enabling/disabling underfrequency protection


3
When the underfrequency protection is enabled and no external blocking signal is input, if the
system frequency is less than the setting of the underfrequency protection and all the
phase-to-phase voltages are greater than the setting of the voltage blocking element of the
underfrequency protection, the underfrequency protection will pick up.

The logic diagram of the fault detector of the underfrequency protection is shown in Figure 3.17-2.

SET f < [81Ux.f_Set] &

SET Upp_min > [81.Upp_Blk]

& 81Ux.Pkp
0ms 500ms
&
SIG 81Ux.On
FD.Pkp

SIG 81Ux.Valid

Figure 3.17-2 Logic diagram of the fault detector of underfrequency protection

3.17.1.2 Operation Characteristic

The underfrequency protection has definite-time delay characteristic complied with IEC 60255-3
and ANSI C37.112. If the system frequency is less than the frequency setting [81Ux.f_Set] (x:
1~6), the underfrequency protection will operate after the time setting [81Ux.t_Op] (x: 1~6).

The operation characteristic curve of underfrequency protection is shown in Figure 3.17-3.

PCS-9611S Feeder Relay 3-165


Date: 2019-04-24
3 Protection Functions

t op

3
fp f

Figure 3.17-3 Operation characteristic curve of underfrequency protection

3.17.1.3 Dropout Characteristic

The underfrequency protection is with instantaneous dropout characteristic. If the system


frequency is greater than the setting [81Ux.f_Set] (x: 1~6), the underfrequency protection will drop
out at once.

3.17.2 Function Block Diagram

81U

81Ux.Enable 81Ux.On

81Ux.Block 81Ux.Blocked
81Ux.Valid
81Ux.St
81Ux.Op

Figure 3.17-4 Function block diagram of underfrequency protection

3.17.3 I/O Signals


Table 3.17-1 Input/output signals of underfrequency protection

No. Input Signal Description


Stage x of underfrequency protection enabling input, it is triggered from binary
1 81Ux.Enable
input or programmable logic etc. (x=1~6)
Stage x of underfrequency protection blocking input, it is triggered from binary
2 81Ux.Block
input or programmable logic etc. (x=1~6)
No. Output Signal Description
1 81Ux.On Stage x of underfrequency protection is enabled.
2 81Ux.Blocked Stage x of underfrequency protection is blocked.

3-166 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

3 81Ux.Valid Stage x of underfrequency protection is valid.


4 81Ux.St Stage x of underfrequency protection starts.
5 81Ux.Op Stage x of underfrequency protection operates.

3.17.4 Logic

SET f<[81Ux.f_Set] & 81Ux.St

&
SET Upp_min>[81.Upp_Blk] [81Ux.t_Op] 0 81Ux.Op

SIG 81Ux.Pkp

3
Figure 3.17-5 Logic diagram of underfrequency protection

3.17.5 Settings
 Access path:

MainMenu  Settings  Protection Settings  FreqProt Settings

Table 3.17-2 Settings of underfrequency protection

No. Setting Range Default Unit Step Description


The setting of the low voltage blocking
1 81.Upp_Blk 10~150 70 V 0.001 element of the frequency protection
(phase-to-phase voltage)
The frequency setting of the stage 1 of
2 81U1.f_Set 45~60 48 Hz 0.001
underfrequency protection
The time setting of the stage 1 of
3 81U1.t_Op 0.1~100 0.3 s 0.001
underfrequency protection
Disabled; The logic setting of the stage 1 of
4 81U1.En Enabled - -
Enabled underfrequency protection
The frequency setting of the stage 2 of
5 81U2.f_Set 45~60 48 Hz 0.001
underfrequency protection
The time setting of the stage 2 of
6 81U2.t_Op 0.1~100 0.3 s 0.001
underfrequency protection
Disabled; The logic setting of the stage 2 of
7 81U2.En Enabled - -
Enabled underfrequency protection
The frequency setting of the stage 3 of
8 81U3.f_Set 45~60 48 Hz 0.001
underfrequency protection
The time setting of the stage 3 of
9 81U3.t_Op 0.1~100 0.3 s 0.001
underfrequency protection
Disabled; The logic setting of the stage 3 of
10 81U3.En Enabled - -
Enabled underfrequency protection
The frequency setting of the stage 4 of
11 81U4.f_Set 45~60 48 Hz 0.001
underfrequency protection

PCS-9611S Feeder Relay 3-167


Date: 2019-04-24
3 Protection Functions

The time setting of the stage 4 of


12 81U4.t_Op 0.1~100 0.3 s 0.001
underfrequency protection
Disabled; The logic setting of the stage 4 of
13 81U4.En Enabled - -
Enabled underfrequency protection
The frequency setting of the stage 5 of
14 81U5.f_Set 45~60 48 Hz 0.001
underfrequency protection
The time setting of the stage 5 of
15 81U5.t_Op 0.1~100 0.3 s 0.001
underfrequency protection
Disabled; The logic setting of the stage 5 of
16 81U5.En Enabled - -
Enabled underfrequency protection

3 17 81U6.f_Set 45~60 48 Hz 0.001


The frequency setting of the stage 6 of
underfrequency protection
The time setting of the stage 6 of
18 81U6.t_Op 0.1~100 0.3 s 0.001
underfrequency protection
Disabled; The logic setting of the stage 6 of
19 81U6.En Enabled - -
Enabled underfrequency protection

3.18 Frequency Rate-of-change Protection (81R)

Frequency rate-of-change reflects the balance of the output power of the generator and the active
power of the load. It can reflect the increase of active load power and the decrease of frequency.
When the frequency changes too fast, it is generally considered that the system has a fault, and
the frequency rate-of-change protection can operate in such a situation.

3.18.1 Function Description

This device provides six stages of frequency rate-of-change protection. If the system frequency
rate-of-change is greater than the predefined setting, this protection will operate. The frequency
rate-of-change protection is with independent definite-time delay characteristic and with
instantaneous dropout characteristic.

3.18.1.1 Frequency Rate-of-change Protection

The frequency rate-of-change protection can be enabled or disabled by the settings. If the setting
[81Rx.En] (x: 1~6) is set as “1”, and the signal [81Rx.Enable] (x: 1~6) is “1” and the signal
[81Rx.Block] (x: 1~6) is “0”. For some special application, the frequency rate-of-change protection
needs to be blocked by external signal, the input signal [81Rx.Block] (x: 1~6) is provided for this
purpose.

The logic diagram of enabling/disabling the frequency rate-of-change protection is shown in


Figure 3.18-1.

3-168 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

EN 81Rx.En & 81Rx.On

SIG 81Rx.Enable

& 81Rx.Blocked
SIG 81Rx.Block ≥1

SIG Fail_Device
& 81Rx.Valid

Figure 3.18-1 Logic diagram of enabling/disabling frequency rate-of-change protection


3
When the frequency rate-of-change protection is enabled and no external blocking signal is input,
if the absolute value of the system frequency rate-of-change is greater than the absolute value of
setting of the frequency rate-of-change protection, the frequency rate-of-change protection will
pick up.

The logic diagram of the fault detector of the frequency rate-of-change protection is shown in
Figure 3.18-2.

df/dt > 0 &


SET
df/dt > [81Rx.df/dt_Set] &

SET Upp_min > [81.Upp_Blk] ≥1

df/dt < 0 &


SET
df/dt < [81Rx.df/dt_Set] &

SET Upp_min > [81.Upp_Blk] & 81Rx.Pkp


0ms 500ms
& FD.Pkp
SIG 81Rx.On

SIG 81Rx.Valid

Figure 3.18-2 Logic diagram of the fault detector of frequency rate-of-change protection

3.18.1.2 Operation Characteristic

The frequency rate-of-change protection has definite-time delay characteristic complied with IEC
60255-3 and ANSI C37.112. If the absolute value of the system frequency rate-of-change is
greater than the absolute value of setting [81Rx.df/dt_Set] (x: 1~6), the frequency rate-of-change
protection will operate after the time setting [81Rx.t_Op] (x: 1~6).

The operation characteristic curve of the frequency rate-of-change protection is shown in Figure
3.18-3.

PCS-9611S Feeder Relay 3-169


Date: 2019-04-24
3 Protection Functions

top

3
-df/dtset df/dtset
-df/dt df/dt

Figure 3.18-3 Operation characteristic curve of frequency rate-of-change protection

3.18.1.3 Dropout Characteristic

The frequency rate-of-change protection is with instantaneous dropout characteristic. If the


absolute value of the system frequency rate-of-change is less than the absolute value of setting
[81Rx.df/dt_Set] (x: 1~6), the frequency rate-of-change protection will drop out at once.

3.18.2 Function Block Diagram

81R

81Rx.Enable 81Rx.On

81Rx.Blocked
81Rx.Block
81Rx.Valid

81Rx.St
81Rx.Op

Figure 3.18-4 Function block diagram of frequency rate-of-change protection

3.18.3 I/O Signals


Table 3.18-1 Input/output signals of frequency rate-of-change protection

No. Input Signal Description


Stage x of frequency rate-of-change protection enabling input, it is triggered from
1 81Rx.Enable
binary input or programmable logic etc. (x=1~6)
Stage x of frequency rate-of-change protection blocking input, it is triggered from
2 81Rx.Block
binary input or programmable logic etc. (x=1~6)
No. Output Signal Description
1 81Rx.On Stage x of frequency rate-of-change protection is enabled.
2 81Rx.Blocked Stage x of frequency rate-of-change protection is blocked.
3 81Rx.Valid Stage x of frequency rate-of-change protection is valid.

3-170 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

4 81Rx.St Stage x of frequency rate-of-change protection starts.


5 81Rx.Op Stage x of frequency rate-of-change protection operates.

3.18.4 Logic

df/dt > 0 &


SET
df/dt > [81Rx.df/dt_Set]
&
SET f > [81Rx.f_Pkp]

81Rx.St
SET Upp_min > [81.Upp_VCE]
≥1
df/dt < 0 & &
3
SET
df/dt < [81Rx.df/dt_Set] [81Rx.t_Op] 0 81Rx.Op
&
SET f < [81Rx.f_Pkp]

SET Upp_min > [81.Upp_VCE]

SIG 81Rx.Pkp

Figure 3.18-5 Logic diagram of frequency rate-of-change protection

3.18.5 Settings
 Access path:

MainMenu  Settings  Protection Settings  FreqProt Settings

Table 3.18-2 Settings of frequency rate-of-change protection

No. Setting Range Default Unit Step Description


The setting of the low voltage blocking
1 81.Upp_Blk 10~150 70 V 0.001 element of the frequency protection
(phase-to-phase voltage)
The rate-of-change setting of the stage x of
2 81R1.df/dt_Set -5~5 0.5 Hz/s 0.001
frequency rate-of-change protection
The time setting of the stage x of frequency
3 81R1.t_Op 0.1~100 0.1 s 0.001
rate-of-change protection
The pickup frequency setting of the stage x
4 81R1.f_Pkp 45~65 50 Hz 0.001
of frequency rate-of-change protection
Disabled; The logic setting of the stage x of frequency
5 81R1.En Enabled - -
Enabled rate-of-change protection
The rate-of-change setting of the stage 1 of
6 81R2.df/dt_Set -5~5 0.5 Hz/s 0.001
frequency rate-of-change protection
The time setting of the stage 1 of frequency
7 81R2.t_Op 0.1~100 0.1 s 0.001
rate-of-change protection
The pickup frequency setting of the stage 1
8 81R2.f_Pkp 45~65 50 Hz 0.001
of frequency rate-of-change protection
Disabled; The logic setting of the stage 1 of frequency
9 81R2.En Enabled - -
Enabled rate-of-change protection

PCS-9611S Feeder Relay 3-171


Date: 2019-04-24
3 Protection Functions

The rate-of-change setting of the stage 2 of


10 81R3.df/dt_Set -5~5 0.5 Hz/s 0.001
frequency rate-of-change protection
The time setting of the stage 2 of frequency
11 81R3.t_Op 0.1~100 0.1 s 0.001
rate-of-change protection
The pickup frequency setting of the stage 2
12 81R3.f_Pkp 45~65 50 Hz 0.001
of frequency rate-of-change protection
Disabled; The logic setting of the stage 2 of frequency
13 81R3.En Enabled - -
Enabled rate-of-change protection
The rate-of-change setting of the stage 3 of
14 81R4.df/dt_Set -5~5 0.5 Hz/s 0.001
frequency rate-of-change protection

3 15 81R4.t_Op 0.1~100 0.1 s 0.001


The time setting of the stage 3 of frequency
rate-of-change protection
The pickup frequency setting of the stage 3
16 81R4.f_Pkp 45~65 50 Hz 0.001
of frequency rate-of-change protection
Disabled; The logic setting of the stage 3 of frequency
17 81R4.En Enabled - -
Enabled rate-of-change protection
The rate-of-change setting of the stage 4 of
18 81R5.df/dt_Set -5~5 0.5 Hz/s 0.001
frequency rate-of-change protection
The time setting of the stage 4 of frequency
19 81R5.t_Op 0.1~100 0.1 s 0.001
rate-of-change protection
The pickup frequency setting of the stage 4
20 81R5.f_Pkp 45~65 50 Hz 0.001
of frequency rate-of-change protection
Disabled; The logic setting of the stage 4 of frequency
21 81R5.En Enabled - -
Enabled rate-of-change protection
The rate-of-change setting of the stage 5 of
22 81R6.df/dt_Set -5~5 0.5 Hz/s 0.001
frequency rate-of-change protection
The time setting of the stage 5 of frequency
23 81R6.t_Op 0.1~100 0.1 s 0.001
rate-of-change protection
The pickup frequency setting of the stage 5
24 81R6.f_Pkp 45~65 50 Hz 0.001
of frequency rate-of-change protection
Disabled; The logic setting of the stage 5 of frequency
25 81R6.En Enabled - -
Enabled rate-of-change protection

3.19 Reverse Power Protection (32R)

If a power supply failure occurs on the feeder, the synchronous motors become generators due to
the inertia of their load and the induction motors become generators. The aim of the reverse
power protection is to detect the inverse flow of energy and to ensure that the motor does not feed
the fault which has appeared on the network.

3.19.1 Function Description


This device provides two stages of reverse power protection. If the reverse power is detected and
it is greater than the predefined setting, the reverse power protection will operate. The reverse

3-172 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

power protection is with independent definite-time delay characteristic and with instantaneous
dropout characteristic.

3.19.1.1 Reverse Power Protection

The reverse power protection can be enabled or disabled by the settings. If the setting [32Rx.En]
(x: 1~2) is set as “1”, and the signal [32Rx.Enable] (x: 1~2) is “1” and the signal [32Rx.Block] (x:
1~2) is “0”. For some special application, the reverse power protection needs to be blocked by
external signal, the input signal [32Rx.Block] (x: 1~2) is provided for this purpose.

The logic diagram of enabling/disabling reverse power protection is shown in Figure 3.19-1.

EN 32Rx.En & 32Rx.On


3
SIG 32Rx.Enable

& 32Rx.Blocked
SIG 32Rx.Block ≥1

SIG Fail_Device
& 32Rx.Valid

Figure 3.19-1 Logic diagram of enabling/disabling reverse power protection

When the reverse power protection is enabled and no external blocking signal is input, if the
reverse power is greater than the power setting of the reverse power protection, the reverse
power protection will pick up.

The logic diagram of the fault detector of the reverse power protection is shown in Figure 3.19-2.

SET |P| > 0.95*[32Rx.P_Set] &

SIG P<0
32Rx.Pkp

SET U1 < [32R.U1_VCE] & & 0ms 500ms


&
≥1 & FD.Pkp
SET I1 < [32R.I1_CCE]

SET U2 > [32R.U2_VCE]

SIG 32Rx.On

SIG 32Rx.Valid

EN [32Rx.Opt_Trp/Alm]=Alm

Figure 3.19-2 Logic diagram of the fault detector of reverse power protection

Where:

PCS-9611S Feeder Relay 3-173


Date: 2019-04-24
3 Protection Functions

The power value is positive-sequence power, P1 = 3×U1×I1×cosθ (θ is the phase angle


between positive-sequence voltage and positive-sequence current).

[32Rx.P_Set] (x: 1~2) is the power setting of the stage x reverse power protection.

[32R.U1_VCE] is the setting of the positive-sequence voltage control element of the reverse
power protection.

[32R.I1_CCE] is the positive-sequence current setting of the current control element of the
reverse power protection.

[32R.U2_VCE] is the setting of the negative-sequence voltage control element of the reverse

3 power protection.

“I1” is the positive-sequence current.

“U1” is the positive-sequence voltage.

“U2” is the negative-sequence voltage.

3.19.1.2 Operation Characteristic

The reverse power protection has definite-time delay characteristic complied with IEC 60255-3
and ANSI C37.112. If the power value is less than “0”, and the absolute power value is greater
than the power setting of the reverse power protection [32Rx.P_Set] (x: 1~2), the reverse power
protection will operate after the time setting [32Rx.t_Op] (x: 1~2).

The operation characteristic curve of reverse power protection is shown in Figure 3.19-3.

top

P1 P1set

Figure 3.19-3 Operation characteristic curve of reverse power protection

3.19.1.3 Dropout Characteristic

The reverse power protection is with instantaneous dropout characteristic. If the power is greater
than “0” or the power is less than the power setting [32Rx.P_Set] (x: 1~2) multiplied by 0.95, the
reverse power protection will drop out at once.

3-174 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

3.19.2 Function Block Diagram

32R

32Rx.Enable 32Rx.On

32Rx.Block 32Rx.Blocked
32Rx.Valid

32Rx.St

32Rx.Op
32Rx.Alm

3
Figure 3.19-4 Function block diagram of reverse power protection

3.19.3 I/O Signals


Table 3.19-1 Input/output signals of reverse power protection

No. Input Signal Description


Stage x of reverse power protection enabling input, it is triggered from binary
1 32Rx.Enable
input or programmable logic etc. (x=1~2)
Stage x of reverse power protection blocking input, it is triggered from binary
2 32Rx.Block
input or programmable logic etc. (x=1~2)
No. Output Signal Description
1 32Rx.On Stage x of reverse power protection is enabled.
2 32Rx.Blocked Stage x of reverse power protection is blocked.
3 32Rx.Valid Stage x of reverse power protection is valid.
4 32Rx.St Stage x of reverse power protection picks up.
5 32Rx.Op Stage x of reverse power protection operates.
6 32Rx.Alm Stage x of reverse power protection alarms.

PCS-9611S Feeder Relay 3-175


Date: 2019-04-24
3 Protection Functions

3.19.4 Logic

SET |P| > [32Rx.P_Set] &

SIG P<0

SET U1 < [32R.U1_VCE] & 32Rx.St

≥1
SET I1 < [32R.I1_CCE]

SET U2 > [32R.U2_VCE] &


[32Rx.t_Op] 0
& 32Rx.Op

3 SIG 32Rx.Pkp

SET [32Rx.Opt_Trp/Alm] = Trp


& 32Rx.Alm

SET [32Rx.Opt_Trp/Alm] = Alm

Figure 3.19-5 Logic diagram of reverse power protection

3.19.5 Settings
 Access path:

MainMenu  Settings  Protection Settings  RevPower Settings

Table 3.19-2 Settings of reverse power protection

No. Setting Range Default Unit Step Description


The voltage setting of the
1 32R.U1_VCE 5~60 5 V 0.001 positive-sequence voltage control element
of the reverse power protection
The positive-sequence current setting of
2 32R.I1_CCE 0.01~1 0.1 p.u. 0.001 the current control element of the reverse
power protection
The voltage setting of the
3 32R.U2_VCE 8~60 8 V 0.001 negative-sequence voltage control element
of the reverse power protection
The power setting of the stage 1 of reverse
4 32R1.P_Set 0.1~10 0.15 p.u. 0.001
power protection
The time setting of the stage 1 of reverse
5 32R1.t_Op 0.01~100 0.1 s 0.001
power protection
Disabled; The logic setting of the stage 1 of reverse
6 32R1.En Enabled - -
Enabled power protection
Enabling stage 1 of reverse power
Trp; protection operate to trip or alarm.
7 32R1.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose
Alm: for alarm purpose

3-176 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

The power setting of the stage 2 of reverse


8 32R2.P_Set 0.1~10 0.15 p.u. 0.001
power protection
The time setting of the stage 2 of reverse
9 32R2.t_Op 0.01~100 0.1 s 0.001
power protection
Disabled; The logic setting of the stage 2 of reverse
10 32R2.En Enabled - -
Enabled power protection
Enabling stage 2 of reverse power
Trp; protection operate to trip or alarm.
11 32R2.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose
Alm: for alarm purpose

3
3.20 Cold Load Pickup Logic (CLP)

3.20.1 Function Description

The cold load pickup (CLP) logic which is included within this relay serves to either inhibit the
selected protective elements for an appointed duration, or to raise the settings of the selected
protective elements. Therefore, it allows the protection settings to be set closer to the load profile
by automatically increasing them following circuit energization. The CLP logic thus provides
stability, whilst maintaining protection during starting.

If the CLP logic is operated, the CLP settings are enabled for the overcurrent protection and the
zero-sequence overcurrent protection respectively. After the dropout time delay of the CLP logic
has elapsed, the normal protection settings are applied. And if a fast resetting signal is received,
the normal protection settings are applied after the pre-define short resetting time delay.

3.20.2 Function Block Diagram

CLP

CLP.in_init CLP.On

CLP.in_shortRst CLP.Blocked

CLP.Valid

Figure 3.20-1 Function block diagram of cold load pickup logic

3.20.3 I/O Signals


Table 3.20-1 Input/output signals of cold load pickup logic

No. Input Signal Description


1 CLP.in_init The input of the CLP initiation signal
2 CLP.in_ShortRst The input of the short resetting signal
No. Output Signal Description
1 CLP.On The cold load pickup logic is enabled.

PCS-9611S Feeder Relay 3-177


Date: 2019-04-24
3 Protection Functions

2 CLP.Blocked The cold load pickup logic is blocked.


3 CLP.Valid The cold load pickup logic is valid.

3.20.4 Logic

SIG CLP.Onload &

SET [CLP.Opt_LogicMode] = 0

≥1
SE T
EN CLP.On tCold 0ms
S Q
&

SIG CLP.BI_52b R
CLR
Q
SET [CLP.Opt_LogicMode] = 1 tRst 0ms

3
≥1

& &
tS hort Rst 0ms

SIG CLP.In_ShortRst

SIG CLP.St_50/51

≥1

SIG CLP.in_Init

&
CLP.Op

EN CLP.On

Figure 3.20-2 Logic diagram of cold load pickup logic

Where:

CLP.Onload is the signal denotes anyone of the phase currents is greater than 0.04In.

CLP.BI_52b is the binary input for inputting the normally closed contact of the circuit breaker.

CLP.St_50/51 is the binary signal which denotes anyone of the selected protective elements
picked up.

“CLP.On” is the signal for denoting the cold load pickup logic function is enabled.

“tCold” is the setting [CLP.t_Cold], the time setting for ensuring the cold load condition is met.

“tRst” is the setting [CLP.t_Rst], the time setting for resetting the cold load pickup logic function.

“tShortRst” is the setting [CLP.t_ShortRst], the time setting for fast resetting the cold load pickup logic
function.

3.20.5 Settings
 Access path:

MainMenu  Settings  Protection Settings  CLP Settings

3-178 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Table 3.20-2 Settings of cold load pickup logic

No. Setting Range Default Unit Step Description


The setting for selecting the cold load
Curr;
1 CLP.Opt_LogicMode CBPos - - initiation condition.
CBPos
Curr: current; CBPos: CB position.
The time setting for ensuring the cold
2 CLP.t_Cold 0~4000 3 s 0.001
load condition is met
The time setting for resetting the cold
3 CLP.t_Rst 0~4000 3 s 0.001
load pickup logic
The time setting for fast resetting the cold
4 CLP.t_ShortRst 0~600 1 s 0.001
load pickup logic 3
Disabled; The logic setting of the cold load pickup
5 CLP.En Enabled - -
Enabled logic function
The multiple setting of the stage 1 of
6 50/51P1.CLP.IMult 1~10 1 - 0.001 overcurrent protection when CLP is
active
The time setting of the stage 1 of
7 50/51P1.CLP.t_Op 0~100 0.1 s 0.001 overcurrent protection when CLP is
active
The time multiplier setting of the stage 1
8 50/51P1.CLP.TMS 0.05~100 1 s 0.001 of IDMT overcurrent protection when CLP
is active
The multiple setting of the stage 1 of
9 50/51G1.CLP.IMult 1~10 1 - 0.001 zero-sequence overcurrent protection
when CLP is active
The time setting of the stage 1 of
10 50/51G1.CLP.t_Op 0~100 0.1 s 0.001 zero-sequence overcurrent protection
when CLP is active
The time multiplier setting of the stage 1
11 50/51G1.CLP.TMS 0.05~100 1 s 0.001 of zero-sequence IDMT overcurrent
protection when CLP is active
The multiple setting of the stage 2 of
12 50/51P2.CLP.IMult 1~10 1 - 0.001 overcurrent protection when CLP is
active
The time setting of the stage 2 of
13 50/51P2.CLP.t_Op 0~100 0.1 s 0.001 overcurrent protection when CLP is
active
The time multiplier setting of the stage 2
14 50/51P2.CLP.TMS 0.05~100 1 s 0.001 of IDMT overcurrent protection when CLP
is active
The multiple setting of the stage 2 of
15 50/51G2.CLP.IMult 1~10 1 - 0.001 zero-sequence overcurrent protection
when CLP is active

PCS-9611S Feeder Relay 3-179


Date: 2019-04-24
3 Protection Functions

The time setting of the stage 2 of


16 50/51G2.CLP.t_Op 0~100 0.1 s 0.001 zero-sequence overcurrent protection
when CLP is active
The time multiplier setting of the stage 2
17 50/51G2.CLP.TMS 0.05~100 1 s 0.001 of zero-sequence IDMT overcurrent
protection when CLP is active
The multiple setting of the stage 3 of
18 50/51P3.CLP.IMult 1~10 1 - 0.001 overcurrent protection when CLP is
active
The time setting of the stage 3 of

3 19 50/51P3.CLP.t_Op 0~100 0.1 s 0.001 overcurrent protection when CLP is


active
The time multiplier setting of the stage 3
20 50/51P3.CLP.TMS 0.05~100 1 s 0.001 of IDMT overcurrent protection when CLP
is active
The multiple setting of the stage 3 of
21 50/51G3.CLP.IMult 1~10 1 - 0.001 zero-sequence overcurrent protection
when CLP is active
The time setting of the stage 3 of
22 50/51G3.CLP.t_Op 0~100 0.1 s 0.001 zero-sequence overcurrent protection
when CLP is active
The time multiplier setting of the stage 3
23 50/51G3.CLP.TMS 0.05~100 1 s 0.001 of zero-sequence IDMT overcurrent
protection when CLP is active
The multiple setting of the stage 4 of
24 50/51P4.CLP.IMult 1~10 1 - 0.001 overcurrent protection when CLP is
active
The time setting of the stage 4 of
25 50/51P4.CLP.t_Op 0~100 0.1 s 0.001 overcurrent protection when CLP is
active
The time multiplier setting of the stage 4
26 50/51P4.CLP.TMS 0.05~100 1 s 0.001 of IDMT overcurrent protection when CLP
is active
The multiple setting of the stage 4 of
27 50/51G4.CLP.IMult 1~10 1 - 0.001 zero-sequence overcurrent protection
when CLP is active
The time setting of the stage 4 of
28 50/51G4.CLP.t_Op 0~100 0.1 s 0.001 zero-sequence overcurrent protection
when CLP is active
The time multiplier setting of the stage 4
29 50/51G4.CLP.TMS 0.05~100 1 s 0.001 of zero-sequence IDMT overcurrent
protection when CLP is active

3-180 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

The multiple setting of the stage 5 of


30 50/51P5.CLP.IMult 1~10 1 - 0.001 overcurrent protection when CLP is
active
The time setting of the stage 5 of
31 50/51P5.CLP.t_Op 0~100 0.1 s 0.001 overcurrent protection when CLP is
active
The time multiplier setting of the stage 5
32 50/51P5.CLP.TMS 0.05~100 1 s 0.001 of IDMT overcurrent protection when CLP
is active
The multiple setting of the stage 5 of
33 50/51G5.CLP.IMult 1~10 1 - 0.001 zero-sequence overcurrent
when CLP is active
protection
3
The time setting of the stage 5 of
34 50/51G5.CLP.t_Op 0~100 0.1 s 0.001 zero-sequence overcurrent protection
when CLP is active
The time multiplier setting of the stage 5
35 50/51G5.CLP.TMS 0.05~100 1 s 0.001 of zero-sequence IDMT overcurrent
protection when CLP is active
The multiple setting of the stage 6 of
36 50/51P6.CLP.IMult 1~10 1 - 0.001 overcurrent protection when CLP is
active
The time setting of the stage 6 of
37 50/51P6.CLP.t_Op 0~100 0.1 s 0.001 overcurrent protection when CLP is
active
The time multiplier setting of the stage 6
38 50/51P6.CLP.TMS 0.05~100 1 s 0.001 of IDMT overcurrent protection when CLP
is active
The multiple setting of the stage 6 of
39 50/51G6.CLP.IMult 1~10 1 - 0.001 zero-sequence overcurrent protection
when CLP is active
The time setting of the stage 6 of
40 50/51G6.CLP.t_Op 0~100 0.1 s 0.001 zero-sequence overcurrent protection
when CLP is active
The time multiplier setting of the stage 6
41 50/51G6.CLP.TMS 0.05~100 1 s 0.001 of zero-sequence IDMT overcurrent
protection when CLP is active

3.21 Undercurrent Protection (37)

The undercurrent protection can remove the device from the system by detecting the smaller load
current when the load is lost, the capacitor is lost of voltage and the motor is running without any
load.

PCS-9611S Feeder Relay 3-181


Date: 2019-04-24
3 Protection Functions

3.21.1 Function Description


The device can provide one stage of undercurrent protection. For different protected equipment,
the single-phase criterion or three-phase criterion can be selected. The position of circuit breaker,
the load current also can be taken as the enabling conditions for the undercurrent protection. The
undercurrent protection is with definite-time operation characteristic and instantaneous dropout
characteristic. Undercurrent protection can operate to trip or alarm, it can be enabled or blocked
by the external binary input.

Undercurrent protection can be enabled or disabled via the settings or binary input signals, for
some specific applications, undercurrent protection needs to be blocked by the external signal, so
3 the device provides a function block input signal to be used to block undercurrent protection. The
enabling and blocking logic of undercurrent protection is shown in the figure below:

EN 37.En & 37.On

SIG 37.Enable

& 37.Blocked
SIG 37.Block ≥1

SIG Fail_Device
& 37.Valid

Figure 3.21-1 Logic diagram of enabling/disabling undercurrent protection

When the undercurrent protection is enabled and no external blocking signal is input, if the
detected current is less than the current setting multiplied by 1.10 of the undercurrent protection,
the undercurrent protection will pick up.

Users can select “1-out-of-3” or “3-out-of-3” logic for the protection criterion via the setting
[37.Opt_1P/3P]. If it is set as “1P”, undercurrent protection can operate if any phase current is
smaller than the current setting. If it is set as “3P”, undercurrent protection cannot operate unless
three phase currents are smaller than the current setting.

The circuit breaker position with/without the current condition can be used as an auxiliary criterion
for undercurrent protection, which can be configured via the setting [37.Opt_LogicMode].

The logic diagram of the fault detector of the undercurrent protection is shown as below.

3-182 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

SIG Ia<1.10×[37.I_Set]
>=1
SIG Ib<1.10×[37.I_Set] &
SIG Ic<1.10×[37.I_Set]
>=1
Pickup current criterion
SET [37.Opt_1P/3P]=1P

SIG Ia<1.10×[37.I_Set]
&
SIG Ib<1.10×[37.I_Set] &
SIG Ic<1.10×[37.I_Set]

SET [37.Opt_1P/3P]=3P
3
SET [37.Opt_LogicMode]=None

SET [37.Opt_LogicMode]=Curr & >=1


>=1
SIG Ip>0.04In Auxiliary criterion

SET [37.Opt_LogicMode]=CBPos &

SIG CB closed position

>=1
&
>=1
SET [37.Opt_LogicMode]=CurrOrCBPos

&
&

SET [37.Opt_LogicMode]=CurrAndCBPos

SIG Pickup current criterion


& 37.Pkp
SIG Auxiliary criterion 0 500ms &
SIG 37.On
&
FD.Pkp
SIG 37.Valid

SET [37.Opt_Trp/Alm]=Alm

Figure 3.21-2 Logic diagram of the fault detector of undercurrent protection

3.21.1.1 Operation Characteristic

The undercurrent protection has definite-time operation characteristic complied with IEC 60255-3
and ANSI C37.112. If the load current is less than the current setting of the undercurrent
protection [37.I_Set], the undercurrent protection will operate after the time setting [37.t_Op].

The operation characteristic curve of undercurrent protection is shown as below.

PCS-9611S Feeder Relay 3-183


Date: 2019-04-24
3 Protection Functions

t op

Ip I

Figure 3.21-3 Operation characteristic curve of undercurrent protection

3.21.1.2 Dropout Characteristic

The undercurrent protection is with instantaneous dropout characteristic. If the load current is
larger than the current setting [37.I_Set] multiplied by 1.10, the undercurrent protection will drop
out immediately.

3.21.2 Function Block Diagram

37

37.Enable 37.On

37.Block 37.Blocked

37.Valid

37.St

37.StA

37.StB

37.StC

37.Op

37.Op.PhA

37.Op.PhB

37.Op.PhC

37.Alm

Figure 3.21-4 Function block diagram of undercurrent protection

3-184 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

3.21.3 I/O Signals


Table 3.21-1 Input/output signals of undercurrent protection

No. Input Signal Description


Undercurrent protection enabling input, it is triggered from binary input or
1 37.Enable
programmable logic etc.
Undercurrent protection blocking input, it is triggered from binary input or
2 37.Block
programmable logic etc.
No. Output Signal Description
1 37.On Undercurrent protection is enabled.
2 37.Blocked Undercurrent protection is blocked. 3
3 37.Valid Undercurrent protection is valid.
4 37.St Undercurrent protection starts.
5 37.StA Undercurrent protection starts (Phase A)
6 37.StB Undercurrent protection starts (Phase B)
7 37.StC Undercurrent protection starts (Phase C)
8 37.Op Undercurrent protection operates.
9 37.Op.PhA Undercurrent protection operates (Phase A)
10 37.Op.PhB Undercurrent protection operates (Phase B)
11 37.Op.PhC Undercurrent protection operates (Phase C)
12 37.Alm Undercurrent protection alarms.

PCS-9611S Feeder Relay 3-185


Date: 2019-04-24
3 Protection Functions

3.21.4 Logic

SIG Ia<[37.I_Set]
>=1
SIG Ib<[37.I_Set] &
SIG Ic<[37.I_Set]
>=1
Current criterion
SET [37.Opt_1P/3P]=1P

SIG Ia<[37.I_Set]
&
SIG Ib<[37.I_Set] &
3 SIG Ic<[37.I_Set]

SET [37.Opt_1P/3P]=3P

SIG Current criterion


& 37.St
SIG Auxiliary criterion &
[37.t_Op] 0
SIG 37.On

SIG 37.Pkp
&
37.Op
SET [37.Opt_Trp/Alm]=Trp

&
37.Alm

SET [37.Opt_Trp/Alm]=Alm

Figure 3.21-5 Logic diagram of undercurrent protection

Where:

Auxiliary criterion: please refer to Figure 3.21-2.

3.21.5 Settings
 Access path:

MainMenu  Settings  Protection Settings  UC Settings

Table 3.21-2 Settings of undercurrent protection

No. Setting Range Default Unit Step Description


The current setting of the
1 37.I_Set 0.1~5 0.5 A 0.001
undercurrent protection
The time setting of the undercurrent
2 37.t_Op 0.1~100 0.1 s 0.001
protection
The setting for selecting the
1P;
3 37.Opt_1P/3P 3P - - three-phase criterion (3P) or
3P
single-phase criterion (1P)

3-186 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

None;
Curr;
CurrAnd The setting of the CB position check
4 37.Opt_LogicMode CBPos; - -
CBPos mode.
CurrAndCBPos;
CurrOrCBPos
Disabled; The logic setting of the undercurrent
5 37.En Enabled - -
Enabled protection
Enabling undercurrent protection
Trp; operate to trip or alarm.
6 37.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose
Alm: for alarm purpose
3
3.22 Breaker Failure Protection (50BF)
When a fault happens to the power system, the device will operate to trip the circuit breaker, and
the fault will be isolated by opening the circuit breaker. If the circuit breaker fails to open within the
certain time due to some abnormalities (for example, low tripping pressure), the fault may cause
system stability being destroyed or electrical equipment being damaged. Breaker failure
protection is adopted to issue a backup tripping command to trip adjacent circuit breakers, and
isolate the fault as requested by the device.

According to the tripping information from the device and the auxiliary information (the current and
the position) of target circuit breaker, breaker failure protection constitutes the criterion to
discriminate whether the target circuit fails to open. If the criterion is confirmed, breaker failure
protection will operate to trip the target circuit breaker with the time delay [50BF.t_ReTrp], trip it
again with the time delay [50BF.t1_Op] and trip the adjacent circuit breakers with the time delay
[50BF.t2_Op]. As a special backup protection, breaker failure protection can quickly isolate the
fault, reduce the affected range by the fault, keep system stability and prevent generators,
transformers and other primary equipments from seriously damaged.

3.22.1 Function Description

For breaker failure protection, re-trip and two time delays are available.

3.22.1.1 Re-trip

When breaker failure protection receives initiating signal of tripping and phase overcurrent
element of any phase operates, the device will issue tripping command to re-trip the target circuit
breaker with the time delay [50BF.t_ReTrp]. In order to improve the sensitivity, both
zero-sequence overcurrent element and negative-sequence overcurrent element are added,
which can be enabled or disabled by the settings [50BF.En_3I0_3P] and [50BF.En_I2_3P].

3.22.1.2 First Time Delay

As similar as re-trip, the device will operate to re-trip the target circuit breaker again with the time
delay [50BF.t1_Op] when the relevant operating criterion is satisfied.

PCS-9611S Feeder Relay 3-187


Date: 2019-04-24
3 Protection Functions

3.22.1.3 Second Time delay

As similar as re-trip, the device will operate to trip the adjacent circuit breakers with the time delay
[50BF.t2_Op] when the relevant operating criterion is satisfied.

3.22.1.4 Current Criterion

1. Phase overcurrent element

Where:

3 = A, B or C

2. Zero-sequence overcurrent element

Where:

is calculated residual current

3. Negative-sequence overcurrent element

Where:

is negative-sequence current

For some special fault (for example, mechanical protection or overvoltage protection operating),
maybe faulty current is very small and current criterion of breaker failure protection is not met, in
order to make breaker failure protection can also operate under the above situation, an input
signal "50BF.ExTrp_WOI" is equipped to initiate breaker failure protection, once the input signal is
energized, normally closed auxiliary contact of circuit breaker is chosen in addition to breaker
failure current check to trigger breaker failure timer. The device takes current as priority with CB
auxiliary contact "50BF.52b" as an option criterion for breaker failure check.

When the initiating signal of breaker failure protection is energized for longer than 10s, an alarm
signal "50BF.Alm_Init" will be issued, and will drop out with a time delay of 10s.

3-188 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

3.22.2 Function Block Diagram

50BF

50BF.Enable 50BF.On

50BF.Block 50BF.Blocked

50BF.ExTrp3P 50BF.Valid

50BF.ExTrp_WOI 50BF.St

50BF.Op_ReTrp3P

50BF.Op_t1 3
50BF.Op_t2

50BF.Alm_Init

3.22.3 I/O Signals


Table 3.22-1 Input/output signals of breaker failure protection

No. Input Signal Description


Breaker failure protection enabling input, it is triggered from binary input or
1 50BF.Enable
programmable logic etc.
Breaker failure protection blocking input, it is triggered from binary input or
2 50BF.Block
programmable logic etc.
3 50BF.ExtTrp3P Input signal of initiating breaker failure protection (three-phases)
Input signal of initiating breaker failure protection with the position check of
4 50BF.ExtTrp_WOI
the circuit breaker
No. Output Signal Description
1 50BF.On Breaker failure protection is enabled.
2 50BF.Blocked Breaker failure protection is blocked.
3 50BF.Valid Breaker failure protection is valid.
4 50BF.St Breaker failure protection starts
5 50BF.Op_ReTrp3P Breaker failure protection operates to re-trip three-phases circuit breaker.
6 50BF.Op_t1 Breaker failure protection operates with the time delay [50BF.t1_Op].
7 50BF.Op_t2 Breaker failure protection operates with the time delay [50BF.t2_Op].
8 50BF.Alm_Init The initiating signal of breaker failure protection is energized consistently.

PCS-9611S Feeder Relay 3-189


Date: 2019-04-24
3 Protection Functions

3.22.4 Logic

EN [50BF.En] &
50BF.On
SIG 50BF.Enable
&
SIG 50BF.Block >=1 50BF.Blocked

SIG Fail_Device
&
50BF.Valid

3
Figure 3.22-1 Logic of enabling breaker failure protection

SIG 50BF.ExtTrp3P 10s 10s >=1

SIG 50BF.ExtTrp_WOI 10s 10s

&
EN [50BF.En_Alm_Init] 50BF.Alm_Init

SIG 50BF.Valid

Figure 3.22-2 Logic of breaker failure initiating signal abnormality

SIG 50BF.Valid &

SIG 50BF.Alm_Init

EN [50BF.En_ReTrp]

EN [50BF.En_Ip]

SET IA>[50BF.I_Set] &


>=1 [50BF.t_ReTrp] 0 50BF.Op_ReTrp3P
SET IB>[50BF.I_Set]

SET IC>[50BF.I_Set]
&

SIG 50BF.ExtTrp3P

&
EN [50BF.En_3I0_3P] &

SET 3I0>[50BF.3I0_Set]
>=1 &
& >=1 [50BF.t1_Op] 0 50BF.Op_t1
EN [50BF.En_I2_3P] &

SET I2>[50BF.I2_Set]

SIG 50BF.ExtTrp_WOI
>=1
& 50BF.St
EN [50BF.En_CB_Ctrl]

SIG 50BF.52b

EN [50BF.En_t1]
&
[50BF.t2_Op] 0 50BF.Op_t2
EN [50BF.En_t2]

Figure 3.22-3 Logic of breaker failure protection

3-190 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Where:

50BF.52b: Input signal of three-phase open position of circuit breaker.

3.22.5 Settings
 Access path:

MainMenu  Settings  Protection Settings  BFP Settings

Table 3.22-2 Settings of breaker failure protection

No. Setting Range Default Unit Step Description

1 50BF.I_Set 0.05~200 1.000 A 0.001


The phase current setting of breaker 3
failure protection
The zero-sequence current setting of
2 50BF.3I0_Set 0.05~200 1.000 A 0.001
breaker failure protection
The negative-sequence current setting of
3 50BF.I2_Set 0.05~200 1.000 A 0.001
breaker failure protection
The re-trip time delay of breaker failure
4 50BF.t_ReTrp 0~20 0.050 s 0.001
protection
The first time delay of breaker failure
5 50BF.t1_Op 0~20 0.100 s 0.001
protection
The second time delay of breaker failure
6 50BF.t2_Op 0~20 0.200 s 0.001
protection
Disabled Enabling/disabling breaker failure
7 50BF.En Enabled - -
Enabled protection
Disabled Enabling/disabling re-trip function of
8 50BF.En_ReTrp Enabled - -
Enabled breaker failure protection
Disabled Enabling/disabling first time delay of
9 50BF.En_t1 Disabled - -
Enabled breaker failure protection
Disabled Enabling/disabling second time delay of
10 50BF.En_t2 Disabled - -
Enabled breaker failure protection
Enabling/disabling phase overcurrent
Disabled
11 50BF.En_Ip Disabled - - element of breaker failure protection via
Enabled
three-phases initiating signal
Enabling/disabling zero-sequence
Disabled overcurrent element of breaker failure
12 50BF.En_3I0_3P Disabled - -
Enabled protection via three-phases initiating
signal
Enabling/disabling negative-sequence
Disabled overcurrent element of breaker failure
13 50BF.En_I2_3P Disabled - -
Enabled protection via three-phases initiating
signal
Enabling/disabling breaker failure
Disabled
14 50BF.En_CB_Ctrl Disabled - - protection be initiated by normally closed
Enabled
contact of circuit breaker

PCS-9611S Feeder Relay 3-191


Date: 2019-04-24
3 Protection Functions

Disabled Enabling/disabling abnormality check of


15 50BF.En_Alm_Init Disabled - -
Enabled breaker failure initiating signal

3.23 Switch-on-to-Fault Protection (SOTF)


When the line is put into operation or the power is restored, the circuit breaker is necessary to be
closed automatically, it is possible to switch on to a permanent fault. The conventional phase
overcurrent protection or earth fault overcurrent protection requires a time delay to operate and
isolate the fault, which will affect the power system seriously. Switch-on-to-fault (SOTF) protection
can quickly operate to remove the fault and reduce the impact of the fault on the system.

3 3.23.1 Function Description


The device can provide one stage of phase overcurrent SOTF protection and one stage of earth
fault overcurrent SOTF protection. The SOTF protection is with definite-time delay characteristic
and instantaneous dropout characteristic, it can be enabled or blocked by the external binary
input.

The SOTF protection can be enabled or disabled via the settings or binary input signals, for some
specific applications, the protection needs to be blocked by the external signal, so the device
provides a function block input signal to be used to block RMS overcurrent protection. The
enabling and blocking logic of the SOTF protection is shown in the figure below:

EN 50PSOTF.En &
50PSOTF.On

SIG 50PSOTF.Enable

&
SIG 50PSOTF.Block ≥1 50PSOTF.Blocked

SIG Fail_Device
&
50PSOTF.Valid

EN 50GSOTF.En &
50GSOTF.On

SIG 50GSOTF.Enable

&
SIG 50GSOTF.Block ≥1 50GSOTF.Blocked

SIG Fail_Device
&
50GSOTF.Valid

Figure 3.23-1 The enabling and blocking logic of SOTF protection

The SOTF protection must be initiated by auto-reclosing signal or manual closing signal, the

3-192 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

initiating time can be set by the setting [STOF.t_En]. After the acceleration condition is satisfied,
the SOTF protection will operate with a time delay of [50PSOTF.t_Op]/ [50GSOTF.t_Op].

The device provides a variety of accelerated tripping modes by manual closing signal, which can
choose circuit breaker position, external binary signal of manual closing.

1. Circuit breaker position (The setting [SOTF.Opt_Mode_ManCls] shall be set as "CBPos" or


"ManClsBI/CBPos")

When the circuit breaker is in open position while the device does not pick up, then manual
closing signal will be kept for a certain time which is determined by the setting [SOTF.t_En], and
SOTF protection will be enabled.

2. External binary signal of manual closing (The setting [SOTF.Opt_Mode_ManCls] shall be set
3
as "ManClsBI"or "ManClsBI/CBPos")

When external binary input of manual closing is energized, then manual closing signal will be kept
for a certain time which is determined by the setting [SOTF.t_En], and SOTF protection will be
enabled.

When the SOTF protection is used for the transformer bay, large inrush current generated during
manual closing and auto-reclosing maybe lead to an undesired operation of SOTF protection.
Second harmonic blocking can be selected by the setting
[50PSOTF.En_Hm2_Blk]/[50GSOTF.En_Hm2_Blk] to prevent the mal-operation due to inrush
current. The harmonic blocking characteristic of the phase overcurrent SOTF protection is
consistent with that of phase overcurrent protection. The harmonic blocking characteristic of the
earth fault overcurrent SOTF protection is consistent with that of earth fault overcurrent protection.

In order to improve the reliability, phase overcurrent SOTF protection can select phase voltage
element, phase-to-phase voltage element, zero-sequence voltage element and
negative-sequence voltage element as auxiliary criterion.

3.23.2 Function Block Diagram

50PSOTF 50GSOTF

50PSOTF.Enable 50PSOTF.On 50GSOTF.Enable 50GSOTF.On

50PSOTF.Block 50PSOTF.Blocked 50GSOTF.Block 50GSOTF.Blocked

50PSOTF.Valid 50GSOTF.Valid

50PSOTF.Op
50GSOTF.Op

50PSOTF.St
50GSOTF.St

3.23.3 I/O Signals


Table 3.23-1 Input/output signals of SOTF protection

No. Input Signal Description


1 50PSOTF.Enable Phase overcurrent SOTF protection enabling input, it is triggered from binary

PCS-9611S Feeder Relay 3-193


Date: 2019-04-24
3 Protection Functions

input or programmable logic etc.


Phase overcurrent SOTF protection blocking input, it is triggered from binary
2 50PSOTF.Block
input or programmable logic etc.
Earth fault overcurrent SOTF protection enabling input, it is triggered from
3 50GSOTF.Enable
binary input or programmable logic etc.
Earth fault overcurrent SOTF protection blocking input, it is triggered from
4 50GSOTF.Block
binary input or programmable logic etc.
No. Output Signal Description
1 50PSOTF.On Phase overcurrent SOTF protection is enabled.
2 50PSOTF.Blocked Phase overcurrent SOTF protection is blocked

3 3 50PSOTF.Valid Phase overcurrent SOTF protection is valid


4 50PSOTF.Op Phase overcurrent SOTF protection operates.
5 50PSOTF.St Phase overcurrent SOTF protection starts.
6 50GSOTF.On Earth fault overcurrent SOTF protection is enabled.
7 50GSOTF.Op Earth fault overcurrent SOTF protection operates.
8 50GSOTF.Blocked Earth fault overcurrent SOTF protection is blocked
9 50GSOTF.Valid Earth fault overcurrent SOTF protection is valid
10 50GSOTF.St Earth fault overcurrent SOTF protection starts.

3.23.4 Logic

SIG 79.Close 0 [SOTF.t_En] AR signal

Figure 3.23-2 Logic of auto-reclosing signal

SIG 52b_PhA
>=1
SIG 52b_PhB

SIG 52b_PhC
&
SIG FD.Pkp

SET [SOTF.Opt_Mode_ManCls]=CBPos >=1

SET [SOTF.Opt_Mode_ManCls]=ManClsBI/CBPos >=1


0 [SOTF.t_En] Manual closing signal

SET [SOTF.Opt_Mode_ManCls]=ManClsBI >=1

SET [SOTF.Opt_Mode_ManCls]=ManClsBI/CBPos
&
SIG FD.Pkp

SIG ManCls

Figure 3.23-3 Logic of manual closing signal

3-194 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

SIG AR signal >=1

SIG Manual closing signal

SET Ia>[50PSOTF.I_Set]
>=1
SET Ib>[50PSOTF.I_Set]

SET Ic>[50PSOTF.I_Set]

SIG I3P 2nd Hm Detect & &

EN [50PSOTF.En_Hm2_Blk]

SET Ua<[50PSOTF.Up_Set]
>=1
SET Ub<[50PSOTF.Up_Set]

SET Uc<[50PSOTF.Up_Set]
&
3
EN [50PSOTF.En_Up_UV]

SET Uab<[50PSOTF.Upp_Set]
>=1 >=1
SET Ubc<[50PSOTF.Upp_Set] &
SET Uca<[50PSOTF.Upp_Set]

EN [50PSOTF.En_Upp_UV]

SET U2>[50PSOTF.U2_Set] & >=1


>=1
EN [50PSOTF.En_U2_OV]

SET U2>[50PSOTF.3U0_Set] &

EN [50PSOTF.En_3U0_OV]

EN [50PSOTF.En_Up_UV]
>=1
EN [50PSOTF.En_Upp_UV]

EN [50PSOTF.En_U2_OV]

EN [50PSOTF.En_3U0_OV]
&
SIG FD.Pkp & [50PSOTF.t_Op] 0 50PSOTF.Op

SIG 50PSOTF.Enable & 50PSOTF.St

&
SIG 50PSOTF.Block 50PSOTF.On

EN [50PSOTF.En]

Figure 3.23-4 Logic of phase overcurrent SOTF protection

PCS-9611S Feeder Relay 3-195


Date: 2019-04-24
3 Protection Functions

SIG I3P 2nd Hm Detect &

SET [50/51G1.En_Hm2_Blk]

SIG AR signal >=1

SIG Manual closing signal


50GSOTF.St
SET 3I0>[50GSOTF.3I0_Set] & &
[50GSOTF.t_Op] 0 50GSOTF.Op

SIG FD.Pkp

SIG 50GSOTF.Enable &


3 SIG 50GSOTF.Block
&
50GSOTF.On

EN [50GSOTF.En]

Figure 3.23-5 Logic of earth fault overcurrent SOTF protection

3.23.5 Settings
 Access path:

MainMenu  Settings  Protection Settings  SOTF Settings

Table 3.23-2 Settings of SOTF protection

No. Setting Range Default Unit Step Description


The initiating time for the SOTF
1 SOTF.t_En 0.2~100 3 s 0.001
protection
Option of manual SOTF mode
ManClsBI:initiated by input signal of
ManClsBI
manual config
SOTF.Opt_Mode_Man CBPos
2 CBPos - - CBPos:initiaed by CB position
Cls ManClsBI/
ManClsBI/CBPos:initiated by either
CBPos
input signal of manual closing or CB
postition
Current setting of phase overcurrent
3 50PSOTF.I_Set 0.05~200 1 A 0.001
SOTF protection
Voltage setting for phase
4 50PSOTF.Up_Set 0~200 1 V 0.001
undervoltage supervision logic
Voltage setting for phase-to-phase
5 50PSOTF.Upp_Set 0~200 1 V 0.001
undervoltage supervision logic
Voltage setting for negative-sequence
6 50PSOTF.U2_Set 0~200 1 V 0.001
overvoltage supervision logic
Voltage setting for zero-sequence
7 50PSOTF.3U0_Set 0~200 1 V 0.001
overvoltage supervision logic
Time delay for phase overcurrent
8 50PSOTF.t_Op 0~100 0.1 s 0.001
SOTF protection

3-196 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Disabled Enabling/disabling phase overcurrent


9 50PSOTF.En Enabled - -
Enabled SOTF protection
Enabling/disabling second harmonic
Disabled
10 50PSOTF.En_Hm2_Blk Enabled - - blocking for phase overcurrent SOTF
Enabled
protection
Enabling/disabling phase
Disabled
11 50PSOTF.En_Up_UV Enabled - - undervoltage supervision logic for
Enabled
phase overcurrent SOTF protection
Enabling/disabling phase-to-phase
Disabled
12 50PSOTF.En_Upp_UV Enabled - - undervoltage supervision logic for
Enabled
phase overcurrent SOTF protection
3
Enabling/disabling
Disabled negative-sequence overvoltage
13 50PSOTF.En_U2_OV Enabled - -
Enabled supervision logic for phase
overcurrent SOTF protection
Enabling/disabling zero-sequence
Disabled
14 50PSOTF.En_3U0_OV Enabled - - overvoltage supervision logic for
Enabled
phase overcurrent SOTF protection
The option of the residual current
used by earth fault overcurrent SOTF
Ext
15 50GSOTF.Opt_3I0 Cal - - protection
Cal
Ext: the measured residual current
Cal: the calculated residual current
Current setting of earth fault
16 50GSOTF.3I0_Set 0.05~200 1 A 0.001
overcurrent SOTF protection
Time delay for earth fault overcurrent
17 50GSOTF.t_Op_3P 0~100 0.1 s 0.001
SOTF protection
Disabled Enabling/disabling earth fault
18 50GSOTF.En Enabled - -
Enabled overcurrent SOTF protection
Enabling/disabling earth fault
Disabled
19 50GSOTF.En_Hm2_Blk Disabled - - overcurrent SOTF protection blocked
Enabled
by harmonic

3.24 Unbalance Current Protection (60/50)

The unbalance current protection is adopted for the internal fault of capacitor bank with
double-star connection. The fault causes the capacitance reactance of a phase branch to be
changed, makes three phase reactance unequal and the unbalance current will be generated at
neutral point.

The application of the unbalance current protection in the capacitor bank with double-star
connection is shown in following figure.

PCS-9611S Feeder Relay 3-197


Date: 2019-04-24
3 Protection Functions

60/50N

Figure 3.24-1 Application of the unbalance current protection

3.24.1 Function Description

This device provides two stages of unbalance current protection. If the unbalance current is
greater than the predefined setting, this protection will operate. The unbalance current protection
is with independent definite-time delay characteristic and with instantaneous dropout
characteristic.

3.24.1.1 Unbalance Current Protection

The unbalance current protection can be enabled or disabled by the settings. If the setting
[60/50-x.En] (x: 1~2) is set as “1”, and the signal [60/50-x.Enable] (x: 1~2) is “1” and the signal
[60/50-x.Block] (x: 1~2) is “0”. For some special application, the unbalance current protection
needs to be blocked by external signal, the input signal [60/50-x.Block] (x: 1~2) is provided for this
purpose.

The logic diagram of enabling/disabling unbalance current protection is shown in Figure 3.24-2.

EN 60/50-x.En & 60/50-x.On

SIG 60/50-x.Enable

& 60/50-x.Blocked
SIG 60/50-x.Block ≥1

SIG Fail_Device
& 60/50-x.Valid

Figure 3.24-2 Logic diagram of enabling/disabling unbalance current protection

When the unbalance current protection is enabled and no external blocking signal is input, if the

3-198 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

unbalance current is greater than the current setting multiplied by 0.95 of the unbalance current
protection, the unbalance current protection will pick up.

The logic diagram of the fault detector of unbalance current protection is shown in Figure 3.24-3.

SET Iu > [60/50-x.I_Set] × 0.95 & 60/50-x.Pkp


0ms 500ms
&
SIG 60/50-x.On & FD.Pkp

SIG 60/50-x.Valid

EN [60/50-x.Opt_Trp/Alm]=Alm

3
Figure 3.24-3 Logic diagram of the fault detector of unbalance current protection

3.24.1.2 Operation Characteristic

The unbalance current protection has definite-time delay characteristic complied with IEC
60255-3 and ANSI C37.112. If the unbalance current is greater than the voltage setting of the
unbalance current protection [60/50-x.I_Set] (x: 1~2), the unbalance current protection will
operate after the time setting [60/50-x.t_Op] (x: 1~2).

The operation characteristic curve of unbalance current protection is shown in Figure 3.24-4.

t op

I u_set Iu

Figure 3.24-4 Operation characteristic curve of unbalance current protection

3.24.1.3 Dropout Characteristic

The unbalance current protection is with instantaneous dropout characteristic. If the unbalance
current is less than the current setting [60/50-x.I_Set] (x: 1~2) multiplied by 0.95, the unbalance
current protection will drop out at once.

PCS-9611S Feeder Relay 3-199


Date: 2019-04-24
3 Protection Functions

3.24.2 Function Block Diagram

60/50

60/50-x.Enable 60/50-x.On
60/50-x.Block 60/50-x.Blocked
60/50-x.Valid
60/50-x.St
60/50-x.Op
60/50-x.Alm

3 Figure 3.24-5 Function block diagram of unbalance current protection

3.24.3 I/O Signals


Table 3.24-1 Input/output signals of unbalance current protection

No. Input Signal Description


Stage x of unbalance current protection enabling input, it is triggered from binary
1 60/50-x.Enable
input or programmable logic etc. (x=1~2)
Stage x of unbalance current protection blocking input, it is triggered from binary
2 60/50-x.Block
input or programmable logic etc. (x=1~2)
No. Output Signal Description
1 60/50-x.On Stage x of unbalance current protection is enabled.
2 60/50-x.Blocked Stage x of unbalance current protection is blocked.
3 60/50-x.Valid Stage x of unbalance current protection is valid.
4 60/50-x.St Stage x of unbalance current protection picks up.
5 60/50-x.Op Stage x of unbalance current protection operates.
6 60/50-x.Alm Stage x of unbalance current protection alarms.

3.24.4 Logic

60/50-x.St

SET Iu > [60/50-x.I_Set] &


[60/50-x.t_Op] 0 & 60/50-x.Op
SIG 60/50-x.Pkp

SET [60/50-x.Opt_Trp/Alm] = Trp


& 60/50-x.Alm

SET [60/50-x.Opt_Trp/Alm] = Alm

Figure 3.24-6 Logic diagram of unbalance current protection

3.24.5 Settings
 Access path:

MainMenu  Settings  Protection Settings  UnbalCurr Settings

3-200 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Table 3.24-2 Settings of unbalance current protection

No. Setting Range Default Unit Step Description


The current setting of stage 1 of
1 60/50-1.I_Set 0.02~200 1 A 0.001
unbalance current protection
The operating time setting of stage 1 of
2 60/50-1.t_Op 0.05~100 0.1 s 0.001
unbalance current protection
Disabled; The logic setting for enabling/disabling
3 60/50-1.En Enabled - -
Enabled stage 1 of unbalance current protection
Enabling stage 1 of unbalance current
Trp; protection operate to trip or alarm.
4 60/50-1.Opt_Trp/Alm
Alm
Trp - -
Trp: for tripping purpose 3
Alm: for alarm purpose
The current setting of stage 2 of
5 60/50-2.I_Set 0.02~200 1 A 0.001
unbalance current protection
The operating time setting of stage 2 of
6 60/50-2.t_Op 0.05~100 0.1 s 0.001
unbalance current protection
Disabled; The logic setting for enabling/disabling
7 60/50-2.En Enabled - -
Enabled stage 2 of unbalance current protection
Enabling stage 2 of unbalance current
Trp; protection operate to trip or alarm.
8 60/50-2.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose
Alm: for alarm purpose

3.25 Unbalance Voltage Protection (60/59)

The unbalance voltage protection is adopted for the internal fault of capacitor bank with
double-star connection. The fault causes the capacitance reactance of a phase branch to be
changed, makes three phase reactance unequal and the unbalance voltage will be generated at
neutral point.

The application of the unbalance voltage protection for a capacitor bank with double-star
connection is shown in following figure.

PCS-9611S Feeder Relay 3-201


Date: 2019-04-24
3 Protection Functions

60/59N

Figure 3.25-1 Application of the unbalance voltage protection

3.25.1 Function Description

This device supports two stages of unbalance voltage protection. If the unbalance voltage is
greater than the predefined setting, this protection will operate. The unbalance voltage protection
is with independent definite-time delay characteristic and with instantaneous dropout
characteristic. In order to adapt to different applications, unbalance voltage protection can operate
to trip or alarm, it can be enabled or blocked by the external binary input.

3.25.1.1 Unbalance voltage Protection

Unbalance voltage protection can be enabled or disabled via the settings or binary input signals,
for some specific applications, unbalance voltage protection needs to be blocked by the external
signal, so the device provides a function block input signal to be used to block unbalance voltage
protection. The enabling and blocking logic of unbalance voltage protection is shown in the figure
below:

EN 60/59-x.En & 60/59-x.On

SIG 60/59-x.Enable

& 60/59-x.Blocked
SIG 60/59-x.Block ≥1

SIG Fail_Device
& 60/59-x.Valid

Figure 3.25-2 Logic diagram of enabling/disabling unbalance voltage protection

When the unbalance voltage protection is enabled and no external blocking signal is input, if the

3-202 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

unbalance voltage is greater than the voltage setting multiplied by 0.95, the unbalance voltage
protection will pick up.

The logic diagram of the fault detector of unbalance voltage protection is shown as below.

SET Uu > [60/59-x.U_Set]×0.95 & 60/59-x.Pkp


0ms 500ms
&
SIG 60/59-x.On & FD.Pkp

SIG 60/59-x.Valid

EN [60/59-x.Opt_Trp/Alm]=Alm

3
Figure 3.25-3 Logic diagram of the fault detector of unbalance voltage protection

3.25.1.2 Operation Characteristic

The unbalance voltage protection can operate with a definite-time limit, the characteristic curve
meets the IEC60255-3 and ANSI C37.112 standards.

When the unbalance voltage (Uub) is larger than the voltage setting, the protection operates with a
time delay of top (i.e. the value of the setting [60/59-x.U_Set] (x=1~2)), and the operation
characteristic curve is shown in the following figure:

t op

Uu_set Uu

Figure 3.25-4 Operation characteristic curve of unbalance voltage protection

3.25.1.3 Dropout Characteristic

The unbalance voltage protection is with instantaneous dropout characteristic. If the unbalance
voltage is less than the voltage setting multiplied by 0.95, the unbalance voltage protection will
drop out immediately.

PCS-9611S Feeder Relay 3-203


Date: 2019-04-24
3 Protection Functions

3.25.2 Function Block Diagram

60/59

60/59-x.Enable 60/59-x.On
60/59-x.Block 60/59-x.Blocked
60/59-x.Valid
60/59-x.St
60/59-x.Op
60/59-x.Alm

3 Figure 3.25-5 Function block diagram of unbalance voltage protection

3.25.3 I/O Signals


Table 3.25-1 Input/output signals of unbalance voltage protection

No. Input Signal Description


Stage x of unbalance voltage protection enabling input, it is triggered from
1 60/59-x.Enable
binary input or programmable logic etc. (x=1~2)
Stage x of unbalance voltage protection blocking input, it is triggered from binary
2 60/59-x.Block
input or programmable logic etc. (x=1~2)
No. Output Signal Description
1 60/59-x.On Stage x of unbalance voltage protection is enabled.
2 60/59-x.Blocked Stage x of unbalance voltage protection is blocked.
3 60/59-x.Valid Stage x of unbalance voltage protection is valid.
4 60/59-x.St Stage x of unbalance voltage protection starts
5 60/59-x.Op Stage x of unbalance voltage protection operates.
6 60/59-x.Alm Stage x of unbalance voltage protection alarms.

3.25.4 Logic

60/59-x.St

SET Uu > [60/59-x.U_Set] &


[60/59-x.t_Op] 0 & 60/59-x.Op
SIG 60/59-x.Pkp

SET [60/59-x.Opt_Trp/Alm] = Trp


& 60/59-x.Alm

SET [60/59-x.Opt_Trp/Alm] = Alm

Figure 3.25-6 Logic diagram of unbalance voltage protection

3.25.5 Settings
 Access path:

3-204 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

MainMenu  Settings  Protection Settings  UnbalVolt Settings

Table 3.25-2 Settings of unbalance voltage protection

No. Setting Range Default Unit Step Description


The voltage setting of the stage 1 of
1 60/59-1.U_Set 1~63.5 50 V 0.001
unbalance voltage protection
The time setting of the stage 1 of
2 60/59-1.t_Op 0.1~100 1 s 0.001
unbalance voltage protection
Disabled; The logic setting for enabling/disabling
3 60/59-1.En Enabled - -
Enabled stage 1 of unbalance voltage protection
Enabling stage 1 of unbalance voltage 3
Trp; protection operate to trip or alarm.
4 60/59-1.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose
Alm: for alarm purpose
The voltage setting of the stage 2 of
5 60/59-2.U_Set 1~63.5 50 V 0.001
unbalance voltage protection
The time setting of the stage 2 of
6 60/59-2.t_Op 0.1~100 1 s 0.001
unbalance voltage protection
Disabled; The logic setting for enabling/disabling
7 60/59-2.En Enabled - -
Enabled stage 2 of unbalance voltage protection
Enabling stage 2 of unbalance voltage
Trp; protection operate to trip or alarm.
8 60/59-2.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose
Alm: for alarm purpose

3.26 Automatic Reclosure (79)


To maintain the integrity of the overall electrical transmission system, the device is installed on the
transmission system to isolate faulted segments during system disturbances. Faults caused by
lightning, wind, or tree branches could be transient in nature and may disappear once the circuit is
de-energized. According to statistics, for overhead transmission line, 80%~90% of the faults on
overhead lines are the transient faults. AR are installed to restore the faulted section of the
transmission system once the fault is extinguished (providing it is a transient fault). For certain
transmission systems, AR is used to improve system stability by restoring critical transmission
paths as soon as possible.

Besides overhead lines, other equipment failure, such as cables, busbar, transformer fault and so
on, are generally permanent fault, and AR is not initiated after faulty feeder is tripped. For some
mixed circuits, such as overhead line with a transformer unit, hybrid transmission lines, etc., it is
required to ensure that AR is only initiated for faults overhead line section, or make a choice
according to the situation.

3.26.1 Function Description


AR can be used with either integrated device or external device. When AR is used with integrated
device, the internal protection logic can initiate AR, moreover, a tripping contact from external

PCS-9611S Feeder Relay 3-205


Date: 2019-04-24
3 Protection Functions

device can be connected to the device via input signal to initiate integrated AR.

When AR is used as an independent device, it can be initiated by operating signal of protections.


The device can output some configurable output signals (such as, contact signals or digital signal,
for example, GOOSE signal) to initiate external AR or block external AR. The contact signals
includes tripping signal, blocking AR signal and protection operating signal, etc,. According to
requirement, these contacts can be selectively connected to external AR and the device can be
set as one-shot or multi-shot AR.

3.26.1.1 Enable AR

When the setting [79.Opt_Enable] is set as "Setting&Config", AR is determined whether it is


3 enabled or disabled by the external input signal and the internal setting. Otherwise, it is only
determined by the internal setting. When AR is enabled, the device outputs the signal "79.On",
otherwise the device outputs the signal "79.Off".

The logic of enabling AR is:

EN [79.En] &
>=1
SET [79.Opt_Enable]=Setting &
79.On
SET [79.Opt_Enable]=Setting&Config &
79.Off
SIG 79.Enable

SIG 79.Block

Figure 3.26-1 Logic of enabling AR

3.26.1.2 AR Ready

AR must be ready to operate before performing reclosing. The output signal [79.Ready] means
that the auto-reclosure can perform at least one time of reclosing function, i.e., breaker
open-close-open.

When the device is energized or after the settings are modified, AR cannot be ready unless the
following conditions are met:

1. AR is enabled.

2. The circuit breaker is ready, such as, normal storage energy and no low pressure signal.

3. The duration of the circuit breaker in closed position pre-fault is greater than the setting
[79.t_CBClsd].

4. There is no the signal of blocking AR.

After AR operates, it must reset, i.e. [79.Active]=0, in addition to the above conditions for reclosing
again.

When there is a fault on an overhead line, the concerned circuit breakers will be tripped normally.
After the fault is cleared, the tripping signal will drop out immediately. In case the circuit breaker is

3-206 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

in failure, etc., and the tripping signal of the circuit breaker maintains and in excess of the time
delay [79.t_PersistTrp], AR will be blocked, as shown in following figure

The input signal [79.CB_Healthy] must be energized before AR gets ready. Because most circuit
breakers can finish one complete process: open-closed-open, it is necessary that circuit breaker
has enough energy before reclosing. When the time delay of AR is exhausted, AR will be blocked
if the input signal [79.CB_Healthy] is still not energized within time delay [79.t_CBReady]. If this
function is not required, the input signal [79.CB_Healthy] can be not to configure, and its state will
be thought as “1” by default.

In order to block AR reliably even if the signal of manually open circuit breaker not connected to
the input signal of blocking AR, when the circuit breaker is open by manually and there is CB
position input under normal conditions, AR will be blocked with the time delay of 100ms if AR is
3
not initiated and no any trip signal.

SIG Any tripping signal [79.t_PersistTrp] 0 >=1


0 [79.t_DDO_BlkAR] 79.AR_Blocked
SIG 79.LockOut

Figure 3.26-2 Logic of AR block

When AR is disabled, AR fails, synchronism check fails or last shot is reached, or when the
internal blocking condition of AR is met. AR will be discharged immediately and next AR will be
disabled. When the input signal [79.LockOut] is energized, AR will be blocked immediately. The
blocking flag of AR will be also controlled by the internal blocking condition of AR. When the
blocking flag of AR is valid, AR will be blocked immediately. The logic of AR ready is shown as
below

AR will be blocked immediately once the blocking condition of AR appears, but the blocking
condition of AR will drop out with a time delay [79.t_DDO_BlkAR] after blocking signal disappears.

PCS-9611S Feeder Relay 3-207


Date: 2019-04-24
3 Protection Functions

>=1
SIG CB closed position [79.t_CBClsd] 100ms &
SIG 79.Active >=1

SIG Any tripping signal


& &
2s 0 79.Ready
SIG 79.Inprog

BI [79.CB_Healthy] 0 [79.t_CBReady] &

3 SIG 79.AR_Blkd >=1


>=1
SIG 79.Lockout &
SIG 79.Failed
>=1
SIG 79.Fail_Chk

SIG Last shot is made

SIG 79.On

Figure 3.26-3 Logic of AR ready

When any protection element operates to trip, the device will output a signal [79.Active] until AR
drop out (Reset Command). Any tripping signal can be from external protection device or internal
protection element.

3.26.1.3 AR Initiation

AR can be initiated by the tripping signal of line protection or CB state.

1. AR initiated by tripping signal of line protection

AR can be initiated by tripping signal of line protection, and the tripping signal may be from
internal trip signal or external trip signal.

When AR is ready to reclosing (“79.Ready”=1) and the tripping signal is received, this tripping
signal will be kept in the device, and AR will be initiated after the tripping signal drops out. The
tripping signal kept in the device will be cleared after the completion of AR sequence (Reset
Command). Its logic is shown as below.

SIG Reset Command &


>=1

SIG Trip Signal

& AR Initiation

SIG 79.Ready

Figure 3.26-4 Tripping initiating AR

3-208 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

2. AR initiated by CB state

AR can be initiated by CB state by setting the setting [79.En_CBInit]. Under normal conditions,
when AR is ready to reclose (“79.Ready”=1), AR will be initiated if circuit breaker is open and
corresponding phase current is nil. AR initiated by CB state logic is shown as below. Usually
normally closed contact of circuit breaker is used to reflect CB state.

SIG CB open

&
EN [79.En_CBInit] & AR Initiation

SIG 79.Ready
3
Figure 3.26-5 CB state initiating AR

3.26.1.4 AR Reclosing

When the dead time delay of AR expires after AR is initiated, if the synchronism check is enabled,
the release of reclosing signal shall be subject to the result of synchronism check.

After the dead time delay of AR expires, if the synchronism check is still unsuccessful within the
time delay [79.t_wait_Chk], the signal of synchronism check failure ("79.Fail_Chk") will be output
and the AR will be blocked. If 3-pole AR with no-check is enabled, the condition of synchronism
check success ("25.RSYN_OK") will always be established. And the signal of synchronism check
success ("25.RSYN_OK") from the synchronism check logic can be applied by AR inside the
device or outside the device.

[79.t_Dd_3PS1] 0 & AR Pulse


If 79.Inhibit_AR operates,
SIG 79.Inhibit_AR then circuit of time delay
will be interrupted. >=1
& [79.t_Wait_Chk] 0 79.Fail_Chk
SIG 3-pole AR Initiation

SIG 79.Ok_Chk

Figure 3.26-6 One-shot AR

Reclosing pulse length may be set through the setting [79.t_PW_AR]. For the circuit breaker
without anti-pump interlock, the setting [79.En_CutPulse] is available to control the reclosing
pulse. When this function is enabled, if the device operates to trip during reclosing, the reclosing
pulse will drop out immediately, so as to prevent multi-shot reclosing onto fault. After the reclosing
signal is issued, AR will drop out with time delay [79.t_Reclaim], and can carry out next reclosing.

The reclaim timer is started when the CB closing signal is given. The reclaim timer defines a time
from the issue of the reclosing command, after which the reclosing function resets. Should a new
trip occur during this time, it is treated as a continuation of the first fault.

PCS-9611S Feeder Relay 3-209


Date: 2019-04-24
3 Protection Functions

SIG AR Pulse 0ms [79.t_PW_AR]

&
SIG Three- phase Trip 79.AR_Out
&
EN [ 79.En _ CutPulse]

>=1
&
79.AR_Out [79.t_ Reclaim] 0ms Reset Command
3
SIG

Figure 3.26-7 Reclosing output logic

3.26.1.5 Reclosing Failure and Success

For line fault, the fault will be cleared after the device operates to trip. When the following cases
appear, the reclosing is unsuccessful.

1. If any protection element operates to trip when AR is enabled ("79.On"=1) and AR is not
ready ("79.Ready"=0), the device will output the signal "79.Failed".

2. For one-shot AR, if the tripping signal is received again within reclaim time after the reclosing
pulse is issued, the reclosing shall be considered as unsuccessful.

3. For multi-shot AR, if the reclosing times are equal to the setting value of AR number and the
tripping signal is received again after the last reclosing pulse is issued, the reclosing shall be
considered as unsuccessful.

4. The setting [79.En_FailCheck] is available to judge whether the reclosing is successful by CB


state, when it is set as “Enabled”. If CB is still in open position with a time delay [79.t_Fail]
after the reclosing pulse is issued, the reclosing shall be considered as unsuccessful. For this
case, the device will issue a signal "79.Failed" to indicate that the reclosing is unsuccessful,
and this signal will drop out after (Reset Command). AR will be blocked if the reclosing shall
be considered as unsuccessful.

After unsuccessful AR is confirmed, AR will be blocked.

3-210 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

SIG 79.On
&
SIG 79.Ready

SIG Any tripping command


& >=1
0 100ms
>=1
SIG Last shot is made 79.Failed

79.Inprog
SIG
&

SIG 79.AR_Blkd

>=1 3
SIG AR Pulse &
[79.t_Fail ] 0
&
SIG CB closed

EN [79.En_ FailCheck ]
&
79.Succeeded
&

0 [79.t_Fail ]
0s 2s 79.Completed

Figure 3.26-8 Reclosing failure and success

3.26.1.6 Reclosing Numbers Control

The device may be set up into one-shot or multi-shot AR. Through the setting [79.Num], the
maximum number of reclosing attempts may be set up to 4 times. Generally, only one-shot AR is
selected. Some corresponding settings may be hidden if one-shot AR is selected.

 [79.Num]=1

It means one-shot reclosing. Line protection device will operate to trip when a transient fault
occurs on the line and AR will be initiated. After the dead time delay for AR is expired, the device
will send reclosing pulse, and then AR will drop out after the time delay [79.t_Reclaim] to ready for
the next reclosing. For permanent fault, the device will operate to trip again after the reclosing is
performed, and the device will output the signal of reclosing failure "79.Failed".

 [79.Num]>1

It means multi-shot reclosing. For multi-shot reclosing, line protection device will operate to trip
when a transient fault occurs on the line and AR will be initiated. After the dead time delay of the
first reclosing is expired, the device will send reclosing pulse, and then AR will drop out after the
time delay [79.t_Reclaim] to ready for the next reclosing. For permanent fault, the device will
operate to trip again after the reclosing is performed, and then AR is initiated after the tripping
contact drops off. After the time delay for AR is expired, the device will send reclosing pulse. The
sequence is repeated until the reclosing is successful or the maximum permit reclosing number
[79.Num] is reached.

3.26.1.7 AR Time Sequence Diagram

The following two examples indicate typical time sequence of AR process for transient fault and

PCS-9611S Feeder Relay 3-211


Date: 2019-04-24
3 Protection Functions

permanent fault respectively.

Signal

Fault

Trip

CB 52b

3 79.t_Reclaim
Open [79.t_Reclaim]

79.Active

79.Inprog [79.t_Dd_3PS1]

79.Inprog_3P [79.t_Dd_3PS1]

79.Ok_Chk

AR Out [79.t_PW_AR]

79.Perm_Trp3P

79.Failed

Time

Figure 3.26-9 Transient fault

3-212 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

Signal

Fault

Trip

Open Open
52b
[79.t_Reclaim]
79.t_Reclaim

79.Active

79.Inprog 3
79.Inprog_3P1 [79.t_Dd_3PS1]

79.Inprog_3PS2 [79.t_Dd_3PS2]

79.Ok_Chk

AR Out [79.t_PW_AR] [79.t_PW_AR]

79.Perm_Trp3P

79.Failed 200ms

Time

Figure 3.26-10 Permanent fault ([79.Num]=2)

PCS-9611S Feeder Relay 3-213


Date: 2019-04-24
3 Protection Functions

3.26.2 Function Block Diagram

79

79. Enable 79.On

79.Block 79.Off

79.Trp3P 79. Close

79. Lockout 79. Ready

79.CB_ Healthy 79.AR_Blkd

3 79.Clr_ Counter 79. Active

79. Inprog

79. Inprog_3P

79.Inprog _ 3PS1

79.Inprog _ 3PS2

79.Inprog _ 3PS3

79.Inprog _ 3PS4

79. Rcls_ Status

79.Failed

79.Succeeded

79.Completed

79.Fail_Chk

3.26.3 I/O Signals


Table 3.26-1 Input/Output signals of AR

No. Input Signal Description


Input signal of enabling AR, it is triggered from binary input or programmable logic
1 79.Enable
etc.
Input signal of blocking AR, it is triggered from binary input or programmable logic
2 79.Block
etc.
3 79.Trp3P Input signal of three-phase tripping from line protection to initiate AR
Input signal of blocking reclosing, usually it is connected with the operating
4 79.Lockout signals of definite-time protection, transformer protection and busbar differential
protection, etc.
The input for indicating whether circuit breaker has enough energy to perform the
5 79.CB_Healthy
close function
6 79.Clr_Counter Clear the reclosing counter
No. Output Signal Description

3-214 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

1 79.On AR is enabled.
2 79.Off AR is disabled.
3 79.Close AR operates.
4 79.Ready AR have been ready for reclosing cycle.
5 79.AR_Blkd AR is blocked.
6 79.Active AR logic is active.
7 79.Inprog AR cycle is in progress
8 79.Inprog_3P 3-pole AR cycle is in progress
9 79.Inprog_3PS1 First 3-pole AR cycle is in progress
10 79.Inprog_3PS2 Second 3-pole AR cycle is in progress
11 79.Inprog_3PS3 Third 3-pole AR cycle is in progress 3
12 79.Inprog_3PS4 Fourth 3-pole AR cycle is in progress
AR status
0: AR is preprocessed
13 79.Status 1: AR is ready.
2: AR is in progress.
3: AR is successful.
14 79.Failed Auto-reclosing fails
15 79.Succeeded Auto-reclosing is successful
16 79.Fail_Chk Synchrocheck for AR fails
17 79.Completed AR is completed.

3.26.4 Settings
 Access path:

MainMenu  Settings  Protection Settings  AR Settings

Table 3.26-2 Settings of AR

Default
No. Settings Range Unit Step Description
value
Maximum number of reclosing
1 79.Num 1~4 1 - 1
attempts
Dead time of first shot 3-pole
2 79.t_Dd_3PS1 0~600 0.600 s 0.001
reclosing
Dead time of second shot 3-pole
3 79.t_Dd_3PS2 0~600 0.600 s 0.001
reclosing
Dead time of third shot 3-pole
4 79.t_Dd_3PS3 0~600 0.600 s 0.001
reclosing
Dead time of fourth shot 3-pole
5 79.t_Dd_3PS4 0~600 0.600 s 0.001
reclosing
Time delay of circuit breaker in
6 79.t_CBClsd 0~600 5.000 s 0.001
closed position before reclosing

PCS-9611S Feeder Relay 3-215


Date: 2019-04-24
3 Protection Functions

Default
No. Settings Range Unit Step Description
value
Time delay to wait for CB healthy,
and begin to timing when the input
signal [79.CB_Healthy] is
7 79.t_CBReady 0~600 5.000 s 0.001
de-energized and if it is not
energized within this time delay, AR
will be blocked.
Maximum wait time for synchronism
8 79.t_Wait_Chk 0~600 10.000 s 0.001
check

3 9 79.t_Reclaim 0~600 15.000 s 0.001 Reclaim time of AR

Dropout time delay of blocking AR,


when blocking signal for AR
10 79.t_DDO_BlkAR 0~600 5.000 s 0.001
disappears, AR blocking condition
drops out after this time delay
Time delay of excessive trip signal
11 79.t_PersistTrp 0~600 0.200 s 0.001
to block AR
Time delay allow for CB status
12 79.t_Fail 0~600 0.200 s 0.001 change to conform reclosing
successful

13 79.t_PW_AR 0~600 0.120 s 0.001 Pulse width of AR closing signal

Enabling/disabling confirm whether


Disabled
14 79.En_FailCheck Disabled - - AR is successful by checking CB
Enabled
state
Disabled Enabling/disabling adjust the length
15 79.En_CutPulse Disabled - -
Enabled of reclosing pulse
Disabled
16 79.En Enabled - - Enabling/disabling auto-reclosing
Enabled
Enabling/disabling AR by external
input signal besides logic setting
Setting [79.En]
17 79.Opt_Enable Setting - -
Setting&Config Setting: only the setting
Setting&Config: the setting and
configuration signal
Disabled Enabling/disabling AR be initiated
18 79.En_CBInit Disabled - -
Enabled by open state of circuit breaker

3.27 VT Circuit Supervision (VTS)


3.27.1 General Application

The purpose of VT circuit supervision is to detect whether VT circuit is normal. Some protection
functions should be disabled when VT circuit fails.

VT circuit failure can be caused by many reasons, such as fuse blown due to short-circuit fault,

3-216 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

poor contact of VT circuit, VT maintenance and so on. The device can detect them and issue an
alarm signal to block relevant protection functions. However, the alarm of VT circuit failure should
not be issued when the following cases happen.

1. Line VT is used as protection VT and the protected line is out of service.

2. Only current protection functions are enabled and VT is not connected to the device.

3.27.2 Function Description

VT circuit supervision can detect failure of single-phase, two-phase and three-phase on protection
VT. Under normal condition, the device continuously supervises input voltage from VT, VT circuit
failure signal will be activated if residual voltage exceeds the threshold value or positive-sequence 3
voltage is lower than the threshold value. If the device is under pickup state due to system fault or
other abnormality, VT circuit supervision will be disabled.

Under normal conditions, the device detects residual voltage greater than the setting
[VTS.3U0_Set] to determine single-phase or two-phase VT circuit failure, and detect three times
positive-sequence voltage less than the setting [VTS.U1_Set] to determine three-phase VT circuit
failure. Upon detecting abnormality on VT circuit, an alarm will comes up after a time delay of
[VTS.t_DPU] and drop off with a time delay of [VTS.t_DDO] after VT circuit restored to normal.

VT (secondary circuit) MCB auxiliary contact as a binary input can be connected to the binary
input circuit of the device. If MCB is open (i.e. [VTS.MCB_VT] is energized), the device will
consider the VT circuit is not in a good condition and issues an alarm without a time delay. If the
auxiliary contact is not connected to the device, VT circuit supervision will be issued with time
delay as mentioned in previous paragraph.

When VT is not connected into the device, the alarm will be not issued if the system setting
[En_VT] is set as "Disabled". However, the alarm is still issued if the binary input [VTS.MCB_VT]
is energized, no matter that the logic setting [En_VT] is set as “Enabled” or “Disabled”.

3.27.3 Function Block

VTS

VTS.Enable VTS.Alm

VTS.Block VTS.InstAlm

VTS.MCB_VT

3.27.4 I/O Signals


Table 3.27-1 Input/output signals of VT circuit supervision

No. Input Signal Description


VT circuit supervision enabling input, it is triggered from binary input or programmable
1 VTS.Enable
logic etc.

PCS-9611S Feeder Relay 3-217


Date: 2019-04-24
3 Protection Functions

VT circuit supervision blocking input, it is triggered from binary input or programmable


2 VTS.Block
logic etc.
3 VTS.MCB_VT Binary input for VT MCB auxiliary contact
No. Output Signal Description
1 VTS.Alm Alarm signal to indicate VT circuit fails
2 VTS.InstAlm VT circuit failure instantaneous alarm signal

3.27.5 Logic

&

3 SIG FD.Pkp

SET 3U0>[VTS.3U0_Set]
>=1
SET U1<[VTS.U1_Set] &
>=1 If "FD.Pkp" operates, the circuit of time
SET [VTS.Opt_VT]=Bay & delay will be interrupted.

[VTS.t_DPU] [VTS.t_DDO]
SIG 52b (Three phases) >=1
&
SIG Ip > 0.04In
>=1
BI Prot.BI_En_VT >=1
VTS.Alm
EN [En_VT]

SIG VTS.MCB_VT &

EN [VTS.En]
&
SIG VTS.Enable

SIG VTS.Block

Figure 3.27-1 VT circuit supervision logic diagram

If fault detector element operates or automatic reclosing cycle is in progress, and VT circuit failure
signal have been detected, then the VT circuit failure signal will be maintained, only when the fault
detector element and automatic reclosing element are all drop-off, VT circuit supervision will
return to normal operation.

3.27.6 Settings
 Access path:

MainMenu  Settings  Global Settings  Superv Settings

Table 3.27-2 Settings of VT circuit supervision

No. Setting Default Range Step Unit Description


Disabled or Logic setting for alarm function of
1 VTS.En Enabled
Enabled VT circuit supervision
Delay pickup setting for the alarm of
2 VTS.t_DPU 1.500 0.000~30.000 0.001 s
VT circuit supervision
Delay drop off setting for the alarm
3 VTS.t_DDO 10.000 0.000~30.000 0.001 s
of VT circuit supervision
Positive-sequence voltage
4 VTS.U1_Set 30.00 0~100 0.01 V
threshold for VT circuit supervision
5 VTS.3U0_Set 8.00 0~100 0.01 V Zero-sequence voltage (calculated)

3-218 PCS-9611S Feeder Relay


Date: 2019-04-24
3 Protection Functions

No. Setting Default Range Step Unit Description


threshold for VT circuit supervision
Negative-sequence voltage setting
6 VTS.U2_Set 8.00 0~100 0.01 V
of VT circuit supervision function.

3.28 CT Circuit Supervision (CTS)


The purpose of the CT circuit supervision is to detect any abnormality on CT secondary circuit.
When CT secondary circuit is abnormal, the current acquired by the device is not accurate, which
will affect protection functions related to the current. Therefore, it is necessary to monitor the CT
abnormal condition. When CT abnormality is detected, the device shall issue an alarm signal and
block the relevant protection functions. 3
3.28.1 Function Description
Under normal conditions, CT secondary signal is continuously supervised by detecting the
residual current and voltage. If residual current is larger than [CTS.3I0_Set] whereas residual
voltage is less than [CTS.3U0_Set], and any phase current is less than 0.06In, CT circuit failure is
considered. The concerned protection functions are blocked and an alarm is issued with a time
delay of [CTS.t_DPU] and drop off with a time delay of [CTS.t_DDO] after CT circuit is restored to
normal condition.

3.28.2 Function Block Diagram

CTS

CTS.Enable CTS.On

CTS.Block CTS.Blocked

CTS.Valid

CTS.Alm

3.28.3 I/O Signals


Table 3.28-1 Input/output signals of CT circuit supervision

No. Input Signal Description


CT circuit supervision enabling input, it is triggered from binary input or
1 CTS.Enable
programmable logic etc.
CT circuit supervision blocking input, it is triggered from binary input or
2 CTS.Block
programmable logic etc.
No. Output Signal Description
1 CTS.Alm Alarm signal to indicate CT circuit fails
2 CTS.On CT circuit supervision is enabled.
3 CTS.Blocked CT circuit supervision is blocked.
4 CTS.Valid CT circuit supervision is valid.

PCS-9611S Feeder Relay 3-219


Date: 2019-04-24
3 Protection Functions

3.28.4 Logics

EN [CTS.En] &
CTS.On
SIG CTS.Enable
&
SIG CTS.Block >=1 CTS.Blocked

SIG Fail_Device
&
CTS.Valid

3 SIG CTS.Valid &


[CTS.t_DPU] [CTS.t_DDO] CTS.Alm
SET 3I0>[CTS.3I0_Set]
&
SET 3U0<[CTS.3U0_Set]

SIG IA<0.06In
>=1
SIG IB<0.06In

SIG IC<0.06In

Figure 3.28-1 Logic of CT circuit failure

3.28.5 Settings
 Access path:

MainMenu  Settings  Global Settings  Superv Settings

Table 3.28-2 Settings of CT circuit supervision

Default
No. Settings Range Unit Step Remark
value
The calculated residual
1 CTS.3I0_Set 0.00~200.00 0.1 A 0.001 current setting of CT circuit
supervision function.
The calculated residual
2 CTS.3U0_Set 0.00~200.00 30 V 0.001 voltage setting of CT circuit
supervision function.
Delay pick-up time setting
3 CTS.t_DPU 0.000~100.000 1.25 s 0.001
for CT circuit failure
Delay drop-off time setting
4 CTS.t_DPO 0.000~100.000 10 s 0.001
for CT circuit failure
Disabled Enabling/disabling CT circuit
5 CTS.En Disabled - -
Enabled supervision function.

3-220 PCS-9611S Feeder Relay


Date: 2019-04-24
4 Control Functions

4 Control Functions

Table of Contents

4.1 Switchgear Control .......................................................................................... 4-1


4.1.1 Functional Description .......................................................................................................... 4-1

4.1.2 Operation Theory.................................................................................................................. 4-2

4.1.3 Function Block Diagram ....................................................................................................... 4-4

4.1.4 I/O Signals ............................................................................................................................ 4-5

4.1.5 Logics ................................................................................................................................... 4-6


4
4.1.6 Settings ................................................................................................................................. 4-7

4.2 Manual Closing Synchronism Check ............................................................. 4-8


4.2.1 Operation Theory.................................................................................................................. 4-8

4.2.2 Function Block Diagram ..................................................................................................... 4-10

4.2.3 I/O Signals .......................................................................................................................... 4-10

4.2.4 Logics ................................................................................................................................. 4-12

4.2.5 Settings ............................................................................................................................... 4-13

4.3 Voltage Selection ........................................................................................... 4-14


4.3.1 Functional Description ........................................................................................................ 4-15

4.3.2 Function Block Diagram ..................................................................................................... 4-18

4.3.3 I/O Signals .......................................................................................................................... 4-18

4.3.4 Logics ................................................................................................................................. 4-19

4.3.5 Settings ............................................................................................................................... 4-21

List of Figures
Figure 4.1-1 Logic diagram of switchgear control ................................................................... 4-2

Figure 4.1-2 DPS synthesis logic ............................................................................................... 4-6

Figure 4.1-3 DPS alarm logic ...................................................................................................... 4-6

Figure 4.1-4 Interlocking logic ................................................................................................... 4-6

Figure 4.1-5 Manual control logic .............................................................................................. 4-7

Figure 4.2-1 Relationship between reference and synchronous voltages ........................... 4-9

PCS-9611S Feeder Relay 4-a


Date: 2019-04-24
4 Control Functions

Figure 4.2-2 Synchro-check logic ............................................................................................ 4-12

Figure 4.2-3 Dead charge check logic ..................................................................................... 4-12

Figure 4.3-1 Voltage connection for double busbars 1 ......................................................... 4-15

Figure 4.3-2 Voltage connection for double busbars 2 ......................................................... 4-16

Figure 4.3-2 Voltage connection for one-and-half breakers arrangement .......................... 4-17

Figure 4.3-3 Voltage selection for double busbar arrangement ........................................... 4-19

Figure 4.3-4 Voltage selection for 3/2 breakers arrangement (closing a bus CB) ............. 4-20

Figure 4.3-5 Voltage selection for 3/2 breakers arrangement (closing the tie CB) ............ 4-21

List of Tables
4
Table 4.1-1 Remote/Local control mode switch logic.............................................................. 4-3

Table 4.1-2 Input/Output signals of control function ............................................................... 4-5

Table 4.1-3 Settings of control function .................................................................................... 4-7

Table 4.2-1 Input signals of manual closing synchronism check ........................................ 4-10

Table 4.2-2 Output signals of manual closing synchronism check ..................................... 4-11

Table 4.2-3 Settings of synchronism check ........................................................................... 4-13

Table 4.3-1 Input signals of voltage selection ........................................................................ 4-18

Table 4.3-2 Output signals of voltage selection ..................................................................... 4-19

Table 4.3-3 Settings of voltage selection ................................................................................ 4-21

4-b PCS-9611S Feeder Relay


Date: 2019-04-24
4 Control Functions

4.1 Switchgear Control


The switchgear control function is mainly used to realize operation of primary equipment such as
circuit breaker (CB), disconnect switch (DS) and earthing switch (ES). This function can be
divided into remote control and local control according to the control source location. A remote
control mainly refers to remote control commands from substation automation system (SAS) or
network control center (NCC). However, a control triggered manually from the device LCD, by a
terminal contact or by a panel handle is a local control. The switchgear control function is closely
related to interlocking, double point status (DPS), remote/local control mode switching and
tripping statistics.

4.1.1 Functional Description

A control command can realize various control signals such as the CB/DS/ES opening/closing. In
order to ensure the reliability of the control output, a locking circuit is added to each control object.
The operation is strictly in accordance with the selection, check and execution steps, to ensure 4
that the control operation can be safely and reliably implemented. In addition, the device has a
hardware self-checking and blocking function to prevent hardware damage from mal-operation
output.

When the device is in the remote-control mode, the control command may be sent via the IEC
60870-5-103 or IEC 61850 protocol; when it is in the local control mode, the local operation may
be performed on the device LCD or panel handle.

A complete control process is:

1. Protocol module sends a selection command;

2. Control module responds the success or failure result of selection;

3. If the selection is successful, the protocol module sends an execution command, otherwise it
sends a cancel command;

4. Control module responds the success or failure result of execution;

5. The control operation may be open/close or up/down/stop.

When the device is in the maintenance status, it can still respond to local control commands.

The switchgear control function can cooperate with functions such as synchronism check and
interlocking criteria calculation to complete the output of the corresponding operation command. It
can realize the normal control output in one bay and the interlocking and programmable logic
configuration between bays.

This device supports the following functional control module:

Module Description
CSWI Control of circuit breaker (CB), disconnector switch (DS) or earthing switch (ES)
RMTLOC Remote or local control mode
XCBR Synthesis of CB position, three-phase or phase separated

PCS-9611S Feeder Relay 4-1


Date: 2019-04-24
4 Control Functions

Module Description
XSWI Synthesis of DS/ES position
SXCBR/SCSWI Trip statistics of CB/DS/ES
RSYN Synchronism check for CB closing
CILO Interlocking logic for CB/DS/ES control
MCSWI Manual control of CB/DS/ES

4.1.2 Operation Theory

The initiation of a control command may be sent to the device by the SCADA or the NCC through
protocol IEC 60870-5-103 or IEC 61850. It may also be the operation of the device LCD or the
manual triggering through configured signal. The command is sent by the CPU to the control
module for processing, and a control record is made on the CPU module according to the control
result.

4
SCADA/NCC IEC 60870-5-103

CPU

CSWI BO
IEC 61850

Control
Record
Local LCD

BI contact

Figure 4.1-1 Logic diagram of switchgear control

4.1.2.1 Remote/Local Control Mode Switch

Since the source of a control command may be SAS or NCC, or may be triggered by the device
LCD or terminal contact, it is necessary to provide a remote/local control mode switch function.

The remote/local control mode switch function determines whether the device is in the remote or
the local control permission state through the configuration of terminal contact, function key, or
binary signal. Each control object provides a remote/local input, and the control module
determines the current control authority to be remote or local according to the input value. By
default, if the input is not configured, any control operation is blocked.

4-2 PCS-9611S Feeder Relay


Date: 2019-04-24
4 Control Functions

Table 4.1-1 Remote/Local control mode switch logic

in_Remote in_Local Remote Control Local Control


NULL NULL Disable Disable
0 NULL Disable Enable
1 NULL Enable Disable
NULL 0 Enable Disable
NULL 1 Disable Enable
0 0 Disable Disable
0 1 Disable Enable
1 0 Enable Disable
1 1 Enable Enable

4.1.2.2 Double Point Status

A double point status (DPS), which usually indicates switchgear status, can be derived from 2
ordinary binary inputs. The signification of a DPS is shown in the following table. For switchgear
4
status, only the 2 statuses "01" and "10" indicating respectively the positions opening and closing
are valid. The other 2 statuses "00" and "11", i.e. intermediate or bad status, will cause the alarm
"DPS.Alm".

DPS Bit0 = 0 Bit0 = 1


Bit1 = 0 DPS_INT DPS_OFF
Bit1 = 1 DPS_ON DPS_BAD

The unit also supports the DPS synthesis through switchgear opening and closing positions after
jittering processing. The synthetic DPS contains original SOE timestamp. The CB control function
supports phase-segregated position inputs and can synthesize these inputs into general position.

In accordance with the control object, the DPS synthesis function is divided into 2 modules: XCBR
and XSWI. The XCBR is mainly used for CB position synthesis, including phase-segregated
positions, while the XSWI is used DS or ES position synthesis.

4.1.2.3 Trip Statistics

The trip statistics function takes the opening position as input count the trip times. For CB, this
device supports general trip statistics. The tripping statistics function is triggered by DPS change.
The statistics result is stored in non-volatile memory for power-off holding.

Use the clear command from the menu in local LCD or customized binary signal to reset the trip
statistics.

4.1.2.4 Interlocking

The interlocking function will influence the control operation output. When the function is enabled,
the device determines whether the control operation is permitted based on the interlocking logic
result. Each control object is equipped with an independent interlocking logic which supports
unlocking operation through a binary signal.

The interlocking function is very important for the control operation of switchgears. During the

PCS-9611S Feeder Relay 4-3


Date: 2019-04-24
4 Control Functions

operation of primary equipment, the positions of the relevant equipment must be correct for
operation permission. For remote control, i.e. command from SAS or NCC, this device could
judge the interlocking logic depending on the message within the command; for local control
through device LCD or terminal contact, please use the corresponding logic setting to
enable/disable the interlocking function.

4.1.2.5 Manual Control

The switchgear control function supports manual control function that can be configured with a
terminal contact or binary signal to trigger the control operation.

The manual control function supports the control input configuration of selection and open/close.
When the control object selection input is configured, the signal "1" indicates that the current
control object has to be selected before a control operation; if the control object selection input is
not configured, the control command can be directly issued without judgment of selection.

4 4.1.2.6 Direct Control

For applications such as signal reset and function enable/disable, the control mode is generally
direct control, i.e. execution without selection before, direct control with normal security in IEC
61850.

The direct control function provides remote/local switch and interlocking configurations. The
control command is usually issued directly by the SAS. It also supports the command triggered by
binary signal.

4.1.3 Function Block Diagram

CSWI:XCBR CSWI:XSWI

in_Remote in_Remote

in_Local in_Local
in_Pos_NO
in_Pos_NO
in_Pos_NC
in_Pos_NC
in_N_Trp
in_N_Trp
in_Rsyn

in_EnaOpn in_EnaOpn

in_EnaCls in_EnaCls

in_CILO_Bypass in_CILO_Bypass

in_Manual_Sel in_Manual_Sel
in_Manual_Opn
in_Manual_Opn
in_Manual_Cls
in_Manual_Cls

4-4 PCS-9611S Feeder Relay


Date: 2019-04-24
4 Control Functions

4.1.4 I/O Signals


Table 4.1-2 Input/Output signals of control function

No. Input Signal Description


1 CSWI**.in_Remote Remote control mode
2 CSWI**.in_Local Local control mode
3 CSWI**.in_Pos_NO Normally opened contact input for DPS opening position
4 CSWI**.in_Pos_NC Normally closed contact input for DPS closing position
5 CSWI**.in_N_Trp Opening command for trip counter
6 CSWI**.in_Rsyn Pointer of synchronism check element (only valid in CB control)
7 CSWI**.in_EnaOpn Opening permission for interlocking
8 CSWI**.in_EnaCls Closing permission for interlocking
9 CSWI**.in_CILO_Bypass Bypass for interlocking
10 CSWI**.in_Manual_Sel Selection for manual control
11 CSWI**.in_Manual_Opn Opening for manual control 4
12 CSWI**.in_Manual_Cls Closing for manual control
No. Output Signal Description
1 CSWI**.Opn_Sel Opening selection
2 CSWI**.Cls_Sel Closing selection
3 CSWI**.Opn_Exec Opening operation
4 CSWI**.Cls_Exec Closing operation
5 CSWI**.Opn_Enabled Permission of opening operation
6 CSWI**.Cls_Enabled Permission of closing operation
7 CSWI**.Opn/Cls_Enabled Permission of operation (Opn_Enabled OR Cls_Enabled)
8 CSWI**.DPS Synthetic DPS for switchgear position
9 CSWI**.N_Trp Tripping statistics
10 CSWI**.DPS.Alm Alarm signal when DPS status is BAD or INT
11 CSWI**.Cmd_ManSel Selection command for manual control
12 CSWI**.Cmd_ManOpn Opening command for manual control
13 CSWI**.Cmd_ManCls Closing command for manual control

In above table, CSWI** can be “Breaker” or “Switch 01”~“Switch 09”.

PCS-9611S Feeder Relay 4-5


Date: 2019-04-24
4 Control Functions

4.1.5 Logics

SIG DPS_A = OFF


≥1
DPS = OFF
SIG DPS_B = OFF

SIG DPS_C = OFF

SIG DPS_A = ON
&
DPS = ON
SIG DPS_B = ON

SIG DPS_C = ON

SIG DPS_A = INT


≥1
DPS = INT
SIG DPS_B = INT

SIG DPS_C = INT

SIG DPS_A = BAD


≥1

4 SIG DPS_B = BAD


DPS = BAD

SIG DPS_C = BAD

Figure 4.1-2 DPS synthesis logic

SIG CSWI**.DPS = BAD >=1

SIG CSWI**.DPS = INT & CSWI**.Alm_DPS


[CSWI**.DPS.t_Alm] 0ms

SET [CSWI**.DPS.En_Alm]

Figure 4.1-3 DPS alarm logic

Remote command from


SIG
SAS/NCC with "Interlocking" flag

≥1 CSWI** interlocking
Local command from device function activated
SIG
LCD with "InterlockChk"

≥1
&
Contact triggered manual
SIG
opening/closing operation

EN [CSWI**.En_Opn_Blk] ≥1

EN [CSWI**.En_Cls_Blk]

Figure 4.1-4 Interlocking logic

4-6 PCS-9611S Feeder Relay


Date: 2019-04-24
4 Control Functions

SIG in_Manual_Sel not configurated &

SIG in_Manual_Opn=1
≥1

SIG in_Manual_Sel =1 &

SIG in_Manual_Opn=1

& Opn_Exec_Man
SIG Opn_Enabled =1

SIG Control mode is Local

SIG in_Manual_Sel not configurated &

SIG in_Manual_Cls=1
≥1

&
4
SIG in_Manual_Sel =1

SIG in_Manual_Cls=1

& Cls_Exec_Man
SIG Cls_Enabled =1

SIG Control mode is Local

Figure 4.1-5 Manual control logic

In above figures, CSWI** can be “Breaker” or “Switch 01”~“Switch 09”.

4.1.6 Settings
Table 4.1-3 Settings of control function

No. Setting Default Range Step Unit Description


Delay Pick Up (DPU) time, i.e.
1 Breaker.DPS.t_DPU 500 0~60000 1 ms debounce time, for DPS of the circuit
breaker
Disabled or Logic setting for DPS alarm of the
2 Breaker.DPS.En_Alm Disabled
Enabled circuit breaker
Operation time delay of DPS alarm of
3 Breaker.DPS.t_Alm 500 0~60000 1 ms
the circuit breaker
Delay Pick Up (DPU) time, i.e.
4 Switch**.DPS.t_DPU 500 0~60000 1 ms debounce time, for DPS of switch**
(**=01~09)
Disabled or Logic setting for DPS alarm of the
5 Switch**.DPS.En_Alm Disabled
Enabled circuit breaker of switch** (**=01~09)
Operation time delay of DPS alarm of
6 Switch**.DPS.t_Alm 500 0~60000 1 ms the circuit breaker of switch**
(**=01~09)

PCS-9611S Feeder Relay 4-7


Date: 2019-04-24
4 Control Functions

No. Setting Default Range Step Unit Description


Pulse Width (PW), i.e. holding time,
7 Breaker.t_PW_Opn 500 0~60000 1 ms for opening output of the circuit
breaker
Pulse Width (PW), i.e. holding time,
8 Breaker.t_PW_Cls 500 0~60000 1 ms for closing output of the circuit
breaker
Pulse Width (PW), i.e. holding time,
9 Switch**.t_PW_Opn 500 0~60000 1 ms for direct opening output of switch**
(**=01~09)
Pulse Width (PW), i.e. holding time,
10 Switch**.t_PW_Cls 500 0~60000 1 ms for direct closing output of switch**
(**=01~09)
Logic setting for interlocking logic
4 11 Breaker.En_CILO_Opn Disabled
Disabled
Enabled
or
control of closing output of the circuit
breaker
Logic setting for interlocking logic
Disabled or
12 Breaker.En_CILO_Cls Disabled control of opening output of the circuit
Enabled
breaker
Logic setting for interlocking logic
Disabled or
13 Switch**.En_CILO_Opn Disabled control of direct closing output of
Enabled
switch** (**=01~09)
Logic setting for interlocking logic
Disabled or
14 Switch**.En_CILO_Cls Disabled control of direct opening output of
Enabled
switch** (**=01~09)

4.2 Manual Closing Synchronism Check


The purpose of synchronism check is to ensure two systems are synchronous before they are
going to be connected.

When two asynchronous systems are connected together, due to phase difference between the
two systems, larger impact will be led to the system during closing. Thus, closing operation is
applied with the synchronism check to avoid this situation and maintain the system stability. The
synchronism check includes synchro-check and dead charge check.

4.2.1 Operation Theory


4.2.1.1 Synchro-check

The comparative relationship between the reference voltage and the synchronization voltage for
synchro-check is as follow. Furthermore, the measured three-phase voltages for synchro-check
should not exceed the overvoltage threshold [25.U_OV] or lag the undervoltage threshold
[25.U_UV].

4-8 PCS-9611S Feeder Relay


Date: 2019-04-24
4 Control Functions

U_Ref
U_Syn

Figure 4.2-1 Relationship between reference and synchronous voltages

This figure shows the characteristics of synchro-check element used for CB closing if both
reference and synchronous sides are live. The element operates if the voltage difference,
frequency difference, slip frequency difference and phase angle difference are all within their 4
setting ranges.

 The difference between the reference voltage and the synchronization voltage is checked by
the following equation

|U_Ref- U_Syn| ≥ [25.U_Diff]

 The frequency difference between the reference side and the synchronization side is
checked by the following equation

|f(U_Ref)-f(U_Syn)| ≤ [25.f_Diff]

 The slip frequency difference is checked by the following equation

df/dt ≤ [25.df/dt]

 The phase difference between the reference voltage and the synchronization voltage is
checked by the following equation

∆δ ≤ [25.phi_Diff]

4.2.1.2 Dead Charge Check

The dead charge check mode checks only the synchro-check voltage. Several dead charge check
modes are supported in using the setting [25.Opt_Mode_DdChk]. The device compares the
reference side and the synchronous side voltages at both sides of circuit breaker with the settings
[25.U_LvChk] and [25.U_DdChk]. When the voltage is higher than [25.U_LvChk], the
corresponding side is regarded as live. When the voltage is lower than [25.U_DdChk], the
corresponding side is regarded as dead.

4.2.1.3 Voltage Input Channel

The synchronism check function is suitable for several applications. According to different
applications, user needs to configure different voltage input channel. For both the reference side
and the synchronous side, the voltage input channel may be single phase or three-phase.

PCS-9611S Feeder Relay 4-9


Date: 2019-04-24
4 Control Functions

While configuring through the PCS-Studio software, user can configure three phase or single
phase voltage channel for reference and synchronization inputs.

In the meantime, the voltage selection logic can be adopted for the synchronism check input
channel, please refer to the following section.

For synchronism check voltage input channel configuration, please MAKE


SURE that the voltage source to connect to the inputs "in_ref" and
"in_syn" should be the same with that used in measurement function,
such as BayMMXU and UMMXN. Otherwise, the alarm "25.Alm_Cfg_Ch"
will be issued.

4.2.2 Function Block Diagram


4
RSYN

in_ref_A
in_ref_B
in_ref_C
in_syn_A
in_syn_B
in_syn_C
in_25_Blk
in_Dd_Blk
in_Lv_Blk
in_SYN_Blk
in_25_Bypass
in_vol_chk
in_syn_chk

4.2.3 I/O Signals


Table 4.2-1 Input signals of manual closing synchronism check

No. Input Signal Description


1 in_ref_A Reference voltage channel (phase A or single phase)
2 in_ref_B Reference voltage channel (phase B)
3 in_ref_C Reference voltage channel (phase C)
4 in_syn_A Synchronization voltage channel (phase A or single phase)
5 in_syn_B Synchronization voltage channel (phase B)
6 in_syn_C Synchronization voltage channel (phase C)
7 in_25_Blk Signal to block synchronism check logic
8 in_Dd_Blk Signal to block dead charge logic
9 in_Lv_Blk Signal to block live check logic
10 in_SYN_Blk Signal to block synchro-check logic

4-10 PCS-9611S Feeder Relay


Date: 2019-04-24
4 Control Functions

No. Input Signal Description


11 in_25_Bypass Signal to temporarily bypass synchronism check logic
12 in_syn_chk Activate synchro-check (valid only if the setting [25.Opt_ValidMode] = Config)
13 in_Vol_chk Activate dead charge check (valid only if the setting [25.Opt_ValidMode] = Config)

Table 4.2-2 Output signals of manual closing synchronism check

No. Output Signal Description


1 U_Diff Voltage difference
2 phi_DIff Phase angle difference
3 f_diff Frequency difference
4 df/dt Frequency rate-of-change
5 25.SynChk_OK Satisfaction of synchro-check logic
6 25.DdChk_OK Satisfaction of dead charge check logic
7 25.RSYN_OK Satisfaction of synchronism check logic, i.e. SynChk_OK or DdChk_OK
8 25.U_Diff_OK Voltage difference within setting range 4
9 25.f_Diff_OK Frequency difference within setting range
10 25.df/dt_OK Frequency variation difference within setting range
11 25.phi_Diff_OK Phase difference within setting range
12 25.RefDd The reference side is dead.
13 25.RefLv The reference side is live.
14 25.SynDd The synchronous side is dead.
15 25.SynLv The synchronous side is live.

PCS-9611S Feeder Relay 4-11


Date: 2019-04-24
4 Control Functions

4.2.4 Logics

SIG in_2 5_Blk


SIG in_S YN_Blk
SET df/d t ≤ [25.df/d t]
≥1
SET [25.En_df/dtChk] = Disabled
SET ΔU ≤ [25.U_ Diff]
SET Δf ≤ [25.f_Di ff]
≥1
SET [25.En_fDiffChk] = Disabl ed
SET Δδ ≤ [25.phi_Diff] & 25.SynChk_OK
SET U_Ref ≤ [25.U_UV]
SET U_Ref ≥ [25.U_OV]
≥1
SET U_Syn ≤ [25.U_UV]
SET U_Syn ≥ [25.U_OV]

SET f_Ref ≤ [25.f_UV]


SET f_Ref ≥ [25.f_OV]
≥1

4 SET

SET
f_Syn ≤ [25.f_UV]
f_Syn ≥ [25.f_OV]

SIG 25.SynChk_OK
SIG Cmd with synchro-check
SET [25.Opt_Valid Mo de] = Se tting & SynChk Success
&
EN [25.En_ Syn Ch k] ≥1
≥1
SET [25.Opt_Valid Mo de] = Config
&
SIG in_S yn _Ch k
&
SIG Cmd without synchro-check

Figure 4.2-2 Synchro-check logic

SIG in_2 5_Blk


SIG in_Dd_ Blk
SIG in_L v_ Blk

SET Valu e.[25.Opt_Mode _Dd Ch k] & 25.DdChk_OK

SET U_Ref ≤ [25.U_DdChk] Dead


check
SET U_Syn ≤ [25.U_DdChk] crite ria
selectio n
SET U_Ref ≥ [25.U_LvChk]

SET U_Syn ≥ [25.U_LvChk]

SIG Cmd with d ead charge check

SIG Cmd with d ead charge check DdChk Success


&
SET [25.Opt_Valid Mo de] = Se tting
& ≥1
EN [25.En_DdChk]
≥1
SET [25.Opt_Valid Mo de] = Config
&
SIG in_Dd_ Ch k
&
SIG Cmd without d ead ch arge check

Figure 4.2-3 Dead charge check logic

4-12 PCS-9611S Feeder Relay


Date: 2019-04-24
4 Control Functions

4.2.5 Settings
Table 4.2-3 Settings of synchronism check

No. Setting Default Range Step Unit Description


Selection of decision
1 25.Opt_ValidMode Setting Setting or Config - - mode for synchronism
check
Logic setting for
synchro-check (valid
2 25.En_SynChk Enabled Disabled or Enabled - - only if the setting
[25.Opt_ValidMode] =
Setting)
Logic setting for dead
charge check (valid
3 25.En_DdChk Enabled Disabled or Enabled - - only if the setting 4
[25.Opt_ValidMode] =
Setting)
Percentage threshold
4 25.U_UV 80.00 0~100 0.01 % of under voltage for
CB closing blocking
Percentage threshold
5 25.U_OV 170.00 100~170 0.01 % of over voltage for CB
closing blocking
Percentage threshold
6 25.f_UF 45.000 45~65 0.001 Hz of under frequency for
CB closing blocking
Percentage threshold
7 25.f_OF 65.000 45~65 0.001 Hz of over frequency for
CB closing blocking
Selection of voltage
8 25.Opt_U_SynChk Ua Ua, Ub, Uc, Uab, Ubc, Uca - -
for synchronism check
Threshold of voltage
9 25.U_Diff_Set 10.00 0~100 0.01 V difference for
synchronism check
Logic setting for
10 25.En_f_Diff_Chk Enabled Disabled or Enabled - - frequency difference
check
Threshold of
11 25.f_Diff_Set 0.50 0~2 0.01 Hz frequency difference
for synchronism check
Logic setting for
12 25.En_df/dt_Chk Enabled Disabled or Enabled - - frequency variation
difference check
13 25.df/dt_Set 1.00 0~2 0.01 Hz/s Threshold of

PCS-9611S Feeder Relay 4-13


Date: 2019-04-24
4 Control Functions

No. Setting Default Range Step Unit Description


frequency variation for
synchronism check.
Threshold of phase
14 25.phi_Diff_Set 15.00 0~180 0.01 ° difference for
synchronism check
Compensation angle
15 25.phi_Comp 0.00 0~360 0.01 ° of phase difference for
synchronism check
SynDdRefDd
SynLvRefDd
SynDdRefLv
Selection of dead
16 25.Opt_Mode_DdChk AnySideDd RefDd - -
charge check mode
SynDd

4 SynLvRefDd/SynDdRefLv
AnySideDd
Threshold for voltage
17 25.U_DdChk 17.32 0~100 0.01 V
dead check
Threshold for voltage
18 25.U_LvChk 34.64 0~100 0.01 V
live check
Threshold of duration
19 25.t_Reset 5 0~60 1 s
for synchro-check
Circuit breaker closing
time. It is the time
from receiving closing
20 25.t_Close_CB 20 0~2000 1 ms
command pulse till the
CB is completely
closed.

 25.Opt_Mode_DdChk

No. Setting Value Dead charge check mode

1 SynDdRefDd Dead check for both the reference and the synchronization sides

2 SynLvRefDd Live check for synchronization side and dead check for reference side

3 SynDdRefLv Dead check for synchronization side and live check for reference side

4 RefDd Dead check for reference side

5 SynDd Dead check for synchronization side

6 SynLvRefDd/SynDdRefLv Option 2 or 3

7 AnySideDd Option 1, 2 or 3

4.3 Voltage Selection


The voltage selection function can be used to switch the reference and synchronization voltages
for the synchronism check function in double busbars and one-and-half circuit breakers scenarios,

4-14 PCS-9611S Feeder Relay


Date: 2019-04-24
4 Control Functions

or to switch three-phase voltages among double busbars used by protection calculations or


measurements. The "Near priority" principle is adopted by default, and the user interface for
programmable switching logic is also reserved.

4.3.1 Functional Description

The voltage selection module is used in the following scenarios:

 For double busbars, selection of appropriate voltage signals from Bus1 and Bus2 for
synchronizing are required. Line VT signal is taken as reference to check synchronizing with
the voltage after voltage selection function. Selection approach is as follows.

Bus2

Bus1

DS1 DS2
4
UB1

UB2

DS1.DPS

CB

DS2.DPS

 Ua

UL1 Ub
Line
Uc

Figure 4.3-1 Voltage connection for double busbars 1

 For double busbars, three-phases voltages from Bus1 VT and Bus2 VT via switching is used
for protection calculations or measurements and meanwhile used as reference side of
synchronism check. Single-phase voltage from line VT is used as synchronizing side of
synchronism check. Selection approach is as follows.

PCS-9611S Feeder Relay 4-15


Date: 2019-04-24
4 Control Functions

Bus2

Bus1

DS1 DS2
Ua

UB1 Ub
Uc
Ua

UB2 Ub
Uc
CB
DS1.DPS

DS2.DPS

4
UL1
Line

Figure 4.3-2 Voltage connection for double busbars 2

 For one-and-half breakers arrangement, selection of appropriate voltage signals among


Line1 VT, Line2 VT and Bus 2 VT as reference voltage to check synchronizing with Bus 1
voltage signal for closing breaker at Bus 1 side.

4-16 PCS-9611S Feeder Relay


Date: 2019-04-24
4 Control Functions

Bus1

UB1

Bus1_CB.DPS Bus1_CB
Line 1

 Ua
UL1 Ub
Uc DS1

DS1.DPS

Tie_CB.DPS Tie_CB
Line 2

UL2 4

DS2.DPS

DS2

Bus2_CB.DPS Bus2_CB

UB2

Bus2

Figure 4.3-3 Voltage connection for one-and-half breakers arrangement

PCS-9611S Feeder Relay 4-17


Date: 2019-04-24
4 Control Functions

4.3.2 Function Block Diagram

VolSwitch

in_UB1_A_Chn Ref_Chn_A
in_UB1_B_Chn Ref_Chn_B
in_UB1_C_Chn Ref_Chn_C

in_UB2_A_Chn Syn_Chn_A
Syn_Chn_B
in_UB2_B_Chn
Syn_Chn_C
in_UB2_C_Chn
in_UL1_A_Chn
in_UL1_B_Chn
in_UL1_C_Chn
in_UL2_A_Chn

4 in_UL2_B_Chn
in_UL2_C_Chn
in_Bus1_CB
in_Tie_CB
in_Bus2_CB
in_DS1
in_DS2

4.3.3 I/O Signals


Table 4.3-1 Input signals of voltage selection

No. Input Signal Description


1 in_UB1_A_Chn Voltage input for Bus1 (phase A)
2 in_UB1_B_Chn Voltage input for Bus1 (phase B)
3 in_UB1_C_Chn Voltage input for Bus1 (phase C)
4 in_UB2_A_Chn Voltage input for Bus2 (phase A)
5 in_UB2_B_Chn Voltage input for Bus2 (phase B)
6 in_UB2_C_Chn Voltage input for Bus2 (phase C)
7 in_UL1_A_Chn Voltage input for Line1 (phase A)
8 in_UL1_B_Chn Voltage input for Line1 (phase B)
9 in_UL1_C_Chn Voltage input for Line1 (phase C)
10 in_UL2_A_Chn Voltage input for Line2 (phase A)
11 in_UL2_B_Chn Voltage input for Line2 (phase B)
12 in_UL2_C_Chn Voltage input for Line2 (phase C)
13 in_Bus1_CB DPS position for the Bus 1 side CB in 3/2 arrangement
14 in_Tie_CB DPS position for the tie CB in 3/2 arrangement
15 in_Bus2_CB DPS position for the Bus 2 side CB in 3/2 arrangement
16 in_DS1 DPS position for the Bus 1 side DS in 3/2 or double busbars arrangement
17 in_DS2 DPS position for the Bus 2 side DS in 3/2 or double busbars arrangement

4-18 PCS-9611S Feeder Relay


Date: 2019-04-24
4 Control Functions

No. Input Signal Description


18 in_bus1_sel Bus1-selected input for customized programmable voltage selection logic
19 in_bus2_sel Bus2-selected input for customized programmable voltage selection logic
20 in_line1_sel Line1-selected input for customized programmable voltage selection logic
21 in_line2_sel Line2-selected input for customized programmable voltage selection logic

Table 4.3-2 Output signals of voltage selection

No. Output Signal Description


1 Ref_Chn_A Reference voltage channel (Phase A)
2 Ref_Chn_B Reference voltage channel (Phase B)
3 Ref_Chn_C Reference voltage channel (Phase C)
4 Syn_Chn_A Synchronization voltage channel (Phase A)
5 Syn_Chn_B Synchronization voltage channel (Phase B)
6 Syn_Chn_C Synchronization voltage channel (Phase C)
4
4.3.4 Logics

SIG DS1.DPS=ON &


UB1_Sel
SIG DS2.DPS=OFF

SIG DS1.DPS=OFF &


UB2_Sel
SIG DS2.DPS=ON

&
Alm_Invalid_Sel

UB1 U_Syn

UB2

Figure 4.3-4 Voltage selection for double busbar arrangement

PCS-9611S Feeder Relay 4-19


Date: 2019-04-24
4 Control Functions

SIG DS1.DPS=ON

SIG DS1.DPS=OFF

SIG Bus1_CB.DPS=ON

SIG DS2.DPS=ON

SIG DS2.DPS=OFF

SIG Bus2_CB.DPS=ON

UL1_Sel

&
UL2_Sel

&
UB2_Sel

4 &
Alm_Invalid_Sel

UL1 U_Ref

UL2

UB2

UB1 U_Syn

Figure 4.3-5 Voltage selection for 3/2 breakers arrangement (closing a bus CB)

4-20 PCS-9611S Feeder Relay


Date: 2019-04-24
4 Control Functions

SIG DS1.DPS=ON UL1_Sel

SIG DS1.DPS=OFF &


UB1_Sel
SIG Bus1_CB.DPS=ON

UL1 Uref

UB1

SIG DS2.DPS=ON UL2_Sel

SIG DS2.DPS=OFF &


UB2_Sel
SIG Bus2_CB.DPS=ON

UL2 Usyn
4
UB2

&

>=1
& Alm_Invalid_Sel

Figure 4.3-6 Voltage selection for 3/2 breakers arrangement (closing the tie CB)

4.3.5 Settings
Table 4.3-3 Settings of voltage selection

No. Setting Default Range Step Unit Description


Selection of circuit breaker
NoVolSel, DblBusOneCB,
1 Opt_CBConfig NoVolSel - - arrangement for voltage
3/2BusCB, 3/2TieCB
selection

PCS-9611S Feeder Relay 4-21


Date: 2019-04-24
4 Control Functions

4-22 PCS-9611S Feeder Relay


Date: 2019-04-24
5 Measurement

5 Measurement

Table of Contents

5.1 Primary Values ................................................................................................. 5-1


5.1.1 General Values ..................................................................................................................... 5-1

5.1.2 Angle Values ......................................................................................................................... 5-1

5.1.3 Sequence Components Values ............................................................................................ 5-2

5.1.4 Power Values ........................................................................................................................ 5-2

5.1.5 Harmonics ............................................................................................................................ 5-3

5.2 Secondary Values ............................................................................................ 5-3


5.2.1 General Values ..................................................................................................................... 5-3

5.2.2 Angle Values ......................................................................................................................... 5-4 5


5.2.3 Sequence Components Values ............................................................................................ 5-5

5.2.4 Power Values ........................................................................................................................ 5-5

5.2.5 Harmonics ............................................................................................................................ 5-6

5.3 Calculation Values ........................................................................................... 5-6


5.3.1 Synchrocheck ....................................................................................................................... 5-6

5.4 Energy Metering............................................................................................... 5-7


5.5 Power Quality ................................................................................................... 5-7

PCS-9611S Feeder Relay 5-a


Date: 2019-04-24
5 Measurement

5-b PCS-9611S Feeder Relay


Date: 2019-04-24
5 Measurement

5.1 Primary Values


Access path: MainMenu  “Measurements”  “Primary Values”

5.1.1 General Values

No. Symbol Definition Unit

1 Ia_Pri Phase-A current A

2 Ib_Pri Phase-B current A

3 Ic_Pri Phase-C current A

4 Ua_Pri Phase-A protection voltage kV

5 Ub_Pri Phase-B protection voltage kV

6 Uc_Pri Phase-C protection voltage kV

7 Uab_Pri Phase-AB protection voltage kV

8 Ubc_Pri Phase-BC protection voltage kV

9 Uca_Pri Phase-CA protection voltage kV

10

11
f

Neu.I_Pri
Frequency of protection voltage

External measured residual current


Hz

A
5
12 SEF.I_Pri The sensitive residual current measured from the high-precision CT A

13 Neu2.I_Pri Another group of residual current A

14 60/50.I_Pri Unbalance current A

15 Delt.U_Pri External measured residual voltage kV

16 Syn.U_Pri Voltage for synchronism check kV

17 60/59.U_Pri Unbalance voltage kV

5.1.2 Angle Values

No. Symbol Definition Unit

1 Ang (Ua-Ia) Phase angle between phase-A voltage and phase-A current °

2 Ang (Ub-Ib) Phase angle between phase-B voltage and phase-B current °

3 Ang (Uc-Ic) Phase angle between phase-C voltage and phase-C current °

4 Ang (Ua-Ub) Phase angle between phase-A voltage and phase-B voltage °

5 Ang (Ub-Uc) Phase angle between phase-B voltage and phase-C voltage °

6 Ang (Uc-Ua) Phase angle between phase-C voltage and phase-A voltage °

7 Ang (Ia-Ib) Phase angle between phase-A current and phase-B current °

8 Ang (Ib-Ic) Phase angle between phase-B current and phase-C current °

9 Ang (Ic-Ia) Phase angle between phase-C current and phase-A current °

Phase angle between phase-A voltage and the referenced angle,


10 Ang (Ua) °
currently, the angle of phase-A voltage is used as the referenced angle.

PCS-9611S Feeder Relay 5-1


Date: 2019-04-24
5 Measurement

No. Symbol Definition Unit

11 Ang (Ub) Phase angle between phase-B voltage and the referenced angle °

12 Ang (Uc) Phase angle between phase-C voltage and the referenced angle °

13 Ang (Ia) Phase angle between phase-A current and the referenced angle °

14 Ang (Ib) Phase angle between phase-B current and the referenced angle °

15 Ang (Ic) Phase angle between phase-C current and the referenced angle °

Phase angle between the external measured residual current and the
16 Neu.Ang (I) °
referenced angle

Phase angle between the external measured residual current and the
17 SEF.Ang (I) °
referenced angle

Phase angle between another group of external measured residual


18 Neu2.Ang (I) °
current and the referenced angle

19 60/50.Ang (I) Phase angle between the unbalance current and the referenced angle °

Phase angle between the external measured residual voltage and the
20 Delt.Ang (U) °
referenced angle

5 21 Syn.Ang (U)
Phase angle between the synchronism check used voltage and the
referenced angle
°

22 60/59.Ang (U) Phase angle between the unbalance voltage and the referenced angle °

5.1.3 Sequence Components Values

No. Symbol Definition Unit

1 I1_Pri The positive-sequence current A

2 I2_Pri The negative-sequence current A

3 3I0_Pri Residual current A

4 U1_Pri The positive-sequence voltage kV

5 U2_Pri The negative-sequence voltage kV

6 3U0_Pri The calculated residual voltage kV

5.1.4 Power Values

No. Sign Description Unit

1 Pa_Pri

2 Pb_Pri The primary values of three-phases active powers. MW

3 Pc_Pri

4 Qa_Pri

5 Qb_Pri The primary values of three-phases reactive powers. MVAr

6 Qc_Pri

7 Sa_Pri The primary values of three-phases apparent powers. MVA

5-2 PCS-9611S Feeder Relay


Date: 2019-04-24
5 Measurement

No. Sign Description Unit

8 Sb_Pri

9 Sc_Pri

10 P_Pri The primary value of active power. MW

11 Q_Pri The primary value of reactive power. MVAr

12 S_Pri The primary value of apparent power. MVA

13 Cosa

14 Cosb Three-phases power factors.

15 Cosc

16 Cos Power factor

5.1.5 Harmonics

No. Sign Description Unit

1 U_Hm01_Pri kV

2 U_Hm02_Pri kV

3 U_Hm03_Pri kV 5
4 U_Hm04_Pri kV

5 U_Hm05_Pri kV

6 U_Hm06_Pri kV

7 U_Hm07_Pri kV

8 U_Hm08_Pri The primary value of the 1st~15th voltage harmonic kV

9 U_Hm09_Pri kV

10 U_Hm10_Pri kV

11 U_Hm11_Pri kV

12 U_Hm12_Pri kV

13 U_Hm13_Pri kV

14 U_Hm14_Pri kV

15 U_Hm15_Pri kV

5.2 Secondary Values


Access path: MainMenu  “Measurements”  “Secondary Values”

5.2.1 General Values

No. Symbol Definition Unit

1 Ia_Sec Phase-A current (summation current for double circuit breakers mode) A

2 Ib_Sec Phase-B current (summation current for double circuit breakers mode) A

3 Ic_Sec Phase-C current (summation current for double circuit breakers mode) A

PCS-9611S Feeder Relay 5-3


Date: 2019-04-24
5 Measurement

No. Symbol Definition Unit

4 Ua_Sec Phase-A protection voltage V

5 Ub_Sec Phase-B protection voltage V

6 Uc_Sec Phase-C protection voltage V

7 Uab_Sec Phase-AB protection voltage V

8 Ubc_Sec Phase-BC protection voltage V

9 Uca_Sec Phase-CA protection voltage V

10 f Frequency of protection voltage Hz

11 Neu.I_Sec External measured residual current A

12 SEF.I_Sec The sensitive residual current measured from the high-precision CT A

13 Neu2.I_Sec Another group of residual current A

14 60/50.I_Sec Unbalance current A

15 Delt.U_Sec External measured residual voltage V

16 Syn.U_Sec Voltage for synchronism check V

17 60/59.U_Sec Unbalance voltage V


5
5.2.2 Angle Values

No. Symbol Definition Unit

1 Ang (Ua-Ia) Phase angle between phase-A voltage and phase-A current °

2 Ang (Ub-Ib) Phase angle between phase-B voltage and phase-B current °

3 Ang (Uc-Ic) Phase angle between phase-C voltage and phase-C current °

4 Ang (Ua-Ub) Phase angle between phase-A voltage and phase-B voltage °

5 Ang (Ub-Uc) Phase angle between phase-B voltage and phase-C voltage °

6 Ang (Uc-Ua) Phase angle between phase-C voltage and phase-A voltage °

7 Ang (Ia-Ib) Phase angle between phase-A current and phase-B current °

8 Ang (Ib-Ic) Phase angle between phase-B current and phase-C current °

9 Ang (Ic-Ia) Phase angle between phase-C current and phase-A current °

Phase angle between phase-A voltage and the referenced angle,


10 Ang (Ua) °
currently, the angle of phase-A voltage is used as the referenced angle.

11 Ang (Ub) Phase angle between phase-B voltage and the referenced angle °

12 Ang (Uc) Phase angle between phase-C voltage and the referenced angle °

13 Ang (Ia) Phase angle between phase-A current and the referenced angle °

14 Ang (Ib) Phase angle between phase-B current and the referenced angle °

15 Ang (Ic) Phase angle between phase-C current and the referenced angle °

Phase angle between the external measured residual current and the
16 Neu.Ang (I) °
referenced angle

17 SEF.Ang (I) Phase angle between the external measured residual current and the °

5-4 PCS-9611S Feeder Relay


Date: 2019-04-24
5 Measurement

No. Symbol Definition Unit

referenced angle

Phase angle between another group of external measured residual


18 Neu2.Ang (I) °
current and the referenced angle

19 60/50.Ang (I) Phase angle between the unbalance current and the referenced angle °

Phase angle between the external measured residual voltage and the
20 Delt.Ang (U) °
referenced angle

Phase angle between the synchronism check used voltage and the
21 Syn.Ang (U) °
referenced angle

22 60/59.Ang (U) Phase angle between the unbalance voltage and the referenced angle °

5.2.3 Sequence Components Values

No. Symbol Definition Unit

1 I1_Sec The positive-sequence current A

2 I2_Sec The negative-sequence current A

4
3I0_Sec

U1_Sec
Residual current

The positive-sequence voltage


A

V
5
5 U2_Sec The negative-sequence voltage V

6 3U0_Sec The calculated residual voltage V

5.2.4 Power Values

No. Sign Description Unit

1 Pa_Sec

2 Pb_Sec The secondary values of three-phases active powers. W

3 Pc_Sec

4 Qa_Sec

5 Qb_Sec The secondary values of three-phases reactive powers. Var

6 Qc_Sec

7 Sa_Sec

8 Sb_Sec The secondary values of three-phases apparent powers. VA

9 Sc_Sec

10 P_Sec The primary value of active power. W

11 Q_Sec The primary value of reactive power. Var

12 S_Sec The primary value of apparent power. VA

13 Cosa

14 Cosb Three-phases power factors.

15 Cosc

PCS-9611S Feeder Relay 5-5


Date: 2019-04-24
5 Measurement

No. Sign Description Unit

16 Cos Power factor

5.2.5 Harmonics

No. Sign Description Unit

1 U_Hm01_Sec V

2 U_Hm02_Sec V

3 U_Hm03_Sec V

4 U_Hm04_Sec V

5 U_Hm05_Sec V

6 U_Hm06_Sec V

7 U_Hm07_Sec V

8 U_Hm08_Sec The secondary value of the 1st~15th voltage harmonic V

9 U_Hm09_Sec V

10 U_Hm10_Sec V

5 11 U_Hm11_Sec V

12 U_Hm12_Sec V

13 U_Hm13_Sec V

14 U_Hm14_Sec V

15 U_Hm15_Sec V

5.3 Calculation Values


Access path: MainMenu  “Measurements”  “Function Values”

5.3.1 Synchrocheck

No. Sign Description Unit

1 25.U_Ref_Sec Secondary voltage of reference side V

2 25.U_Ref_Pri Primary voltage of reference side kV

3 25.f_Ref Frequency of reference side Hz

4 25.U_Syn_Sec Secondary voltage of synchronization side V

5 25.U_Syn_Pri Primary voltage of synchronization side kV

6 25.f_Syn Synchronization side frequency Hz

7 25.U_Diff_Sec Secondary voltage difference for CB synchronism check V

8 25.U_Diff_Pri Primary voltage difference for CB synchronism check kV

9 25.phi_Diff Phase angle difference for CB synchronism check Deg

10 25.f_Diff Frequency difference for CB synchronism check Hz

11 25.df/dt Frequency variation difference for CB synchronism check Hz/s

5-6 PCS-9611S Feeder Relay


Date: 2019-04-24
5 Measurement

No. Sign Description Unit

12 25.RSYN_OK Synchronism check is passed.

13 25.SynChk_OK Synchro-check is passed.

14 25.DdChk_OK Dead charge check is passed.

15 25.U_Diff_OK Voltage difference criteria is satisfied.

16 25.f_Diff_OK Frequency difference criteria is satisfied.

17 25.dfdt_OK Voltage variation difference criteria is satisfied.

18 25.phi_Diff_OK Phase difference criteria is satisfied.

19 25.RefDd Dead check of reference side is passed.

20 25.RefLv Live check of reference side is passed.

21 25.SynDd Dead check of synchronization side is passed.

22 25.SynLv Live check of synchronization side is passed.

5.4 Energy Metering


Access path: MainMenu  “Measurements”  “Energy Metering”

No. Symbol Definition Unit


5
1 EA_Accu_Fwd Positive active energy kWh

2 EA_Accu_Rev Negative active energy kWh

3 ER_Accu_Fwd Positive reactive energy kVarh

4 ER_Accu_Rev Negative reactive energy kVarh

5.5 Power Quality


Access path: MainMenu  “Measurements”  “Power Quality”

No. Symbol Definition Unit

1 PwrQual.UnbalRate_U Voltage unbalance rate %

2 PwrQual.UnbalRate_I Current unbalance rate %

3 PwrQual.THD Total harmonic distortion %

U a  3  U nn
4 Ua_Devn Deviation of phase A voltage  %
U nn

U b  3  U nn
5 Ub_Devn Deviation of phase B voltage  %
U nn

U c  3  U nn
6 Uc_Devn Deviation of phase C voltage  %
U nn

7 f_Devn Deviation of frequency = f_meas - fn Hz

PCS-9611S Feeder Relay 5-7


Date: 2019-04-24
5 Measurement

No. Symbol Definition Unit

8 UnbalRate_U2 Unbalance rate of negative-sequence voltage = U2/U1 %

Unbalance rate of zero-sequence voltage (calculated) =


9 UnbalRate_3U0 %
3U0/U1

Total Harmonic Distortion (THD) of phase A voltage

15
10 THD_Ua U
i 2
2
Hm _ i %
THD 
U Hm _1

11 UnbalRate_I2 Unbalance rate of negative-sequence current = I2/I1 %

12 UnbalRate_3I0 Unbalance rate of zero-sequence current (calculated) = 3I0/I1 %

5-8 PCS-9611S Feeder Relay


Date: 2019-04-24
6 Supervision

6 Supervision

Table of Contents

6.1 Overview ........................................................................................................... 6-1


6.2 Device Hardware Supervision ........................................................................ 6-1
6.2.1 Hardware Resource Consumption Supervision ................................................................... 6-2

6.2.2 Hardware Status Supervision ............................................................................................... 6-2

6.2.3 Hardware Configuration Supervision ................................................................................... 6-3

6.2.4 Device Firmware Supervision .............................................................................................. 6-3

6.2.5 CPU Process and Module Supervision ................................................................................ 6-3

6.3 Analog Input Supervision ............................................................................... 6-3


6.4 Secondary Circuit Supervision....................................................................... 6-4
6.5 Binary Input Supervision ................................................................................ 6-5
6.5.1 Debounce Time .................................................................................................................... 6-5

6.5.2 Jitter Processing ................................................................................................................... 6-7


6
6.6 Circuit Breaker Supervision ........................................................................... 6-9
6.6.1 Tripped Position Contact Supervision .................................................................................. 6-9

6.7 Tripping Counter Statistics ............................................................................. 6-9


6.8 Supervision Alarms and Handling Suggestion ............................................. 6-9

List of Figures

Figure 6.4-1 Principle of the TCS function with two binary inputs ........................................ 6-4

Figure 6.5-1 Sequence chart of debounce technique ............................................................. 6-5

Figure 6.5-2 Debounce time configuration page...................................................................... 6-6

Figure 6.5-3 Sequence chart of jitter processing..................................................................... 6-8

List of Tables

Table 6.8-1 Alarm description..................................................................................................... 6-10

PCS-9611S Feeder Relay 6-a


Date: 2019-04-24
6 Supervision

6-b PCS-9611S Feeder Relay


Date: 2019-04-24
6 Supervision

6.1 Overview

Protection system is in quiescent state under normal conditions, and it is required to respond
promptly for faults occurred on power system. When the device is in energizing process before
the LED “HEALTHY” is on, the device need to be checked to ensure no abnormality. Therefore,
the automatic supervision function, which checks the health of the protection system when startup
and during normal operation, plays an important role.

The numerical relay based on the microprocessor operations is suitable for implementing this
automatic supervision function of the protection system.

In case a defect is detected during initialization when DC power supply is provided to the device,
the device will be blocked with indication and alarm of relay out of service. It is suggested a trial
recovery of the device by re-energization. Please contact supplier if the device is still failure.

When a failure is detected by the automatic supervision, it is followed by a LCD message, LED
indication and alarm contact outputs. The failure alarm is also recorded in event recording report
and can be printed if required.

6.2 Device Hardware Supervision

All hardware has real-time monitoring functions, such as CPU module monitoring, communication
interface status monitoring, power supply status monitoring. 6
The monitoring function of CPU module also includes processor self-check, memory self-check
and so on. The processor self-check is checked by designing execution instructions and data
operations. Check whether the processor can execute all instructions correctly, and whether it can
correctly calculate complex data operations to determine whether it works normally. For
peripherals, it can monitor the status of the interface module, check the input and output data,
send the communication interface and receive self-loop detection. Memory self-check is used to
detect unexpected memory errors in the running process. It can effectively prevent program logic
abnormality caused by memory errors.

The status monitoring of communication interface also includes Ethernet communication interface
monitoring and differential channel communication interface monitoring. By accessing the status
register of the communication interface, the state of the corresponding interface is obtained, such
as the state of connection, the number of sending frames, the number of frames received, and the
number of wrong frames. According to the statistics of the acquired interface state, it is judged
whether the interface work is abnormal.

The hardware supervision also includes the power supply status monitoring. The voltage
monitoring chip is used by all the power supplies. The reset voltage threshold is preset to the reset
monitoring circuit. When the power supply is abnormal, the voltage monitoring chip will output the
reset signal to control CPU to be in the reset state and avoid the wrong operation.

PCS-9611S Feeder Relay 6-1


Date: 2019-04-24
6 Supervision

6.2.1 Hardware Resource Consumption Supervision


1. Logic component total execution time monitoring

In the process of operation, the safety allowance should always be kept and no overload
phenomenon is allowed. When the user configures logic components with PCS-Studio, the
PCS-Studio automatically calculates the time required for the theoretical execution of the
configured components. When the security limit is exceeded, the PCS-Studio will indicate that the
configuration error is not allowed to download the current configuration to the device.

2. Module data exchange monitoring

During the operation of the device, there is a lot of data exchange between modules. The number
of data exchanges is related to the number of logical components configured by the user. When
the configuration is too large to cause the number of data exchange to exceed the upper limit
supported by the device, the PCS-Studio prompts the configuration error.

3. Configuration file size monitoring

The initialization of the device depends on the configuration files of each module. The user
configured logical components will eventually be embodied in the configuration file, limited to the
hardware memory space. When the configuration file size is more than the upper limit, the
PCS-Studio prompts the configuration error.

6.2.2 Hardware Status Supervision


6 1. Memory ECC and parity functions.

The DDR3 memory chip has the function of ECC (Error Checking and Correcting) to eliminate
unexpected changes in memory caused by electromagnetic interference. The chip memory has
parity function. When an error occurs, the system can detect anomalies immediately, and
eliminate the logic abnormity caused by memory errors.

2. Memory error monitoring in code area and constant data area

In addition to the above hardware memory reliability measures, the device software is also
constantly checking the memory during operation, including code, constant data, and so on. Once
the error detection, the system will automatically restart the restore operation. If they detect the
error immediately after the restart, it may be the result of a permanent fault locking device
hardware, only at the moment and not restart.

3. Binary output relay drive monitoring

The reliability of the device is largely determined by the reliability of the export drive. By reading
the driving state of the binary output relay, the alarm signal will be generated and the device is
immediately blocked to prevent the relay from mal-operation when the device is not given a
tripping order and the binary output relay driver is detected in the effective state.

4. CPU temperature monitoring

The CPU chip needs to be able to ensure long-term stability under the permissible working
temperature of the specification. Therefore, it is necessary to monitor the working temperature

6-2 PCS-9611S Feeder Relay


Date: 2019-04-24
6 Supervision

monitored by CPU.

6.2.3 Hardware Configuration Supervision

The device is blocked when the actual hardware configuration is not consistent with the hardware
configuration file. Compared with pre configured modules, this device will be blocked if more
module is inserted, fewer module is inserted, and wrong modules is inserted.

6.2.4 Device Firmware Supervision

1. Each hardware module configuration check code needs to be consistent with CPU module.

The device CPU module stores the configuration check codes of other modules. In initialization
procedure, it checks whether the configuration check code of each module is consistent with the
stored code in CPU module, and if it is not consistent, this device is blocked.

2. The hardware modules and process interface versions need to be consistent with the CPU
module.

If the system is incompatible with the upgrade, it will upgrade the internal interface version. At this
moment, each hardware module and process will be upgraded synchronously, otherwise the
version of the interface will be inconsistent.

3. Configuration text is correct.

The configuration text formed by the device calibration visualization project includes checking
whether the check code is wrong or not. 6
4. Whether any setting is over the range, whether it needs to confirm the settings.

If the setting exceeds the configuration range, the device is blocked; if some settings are added, it
is necessary to confirm the new values through the LCD.

6.2.5 CPU Process and Module Supervision


1. Monitor the heartbeat of the module.

In the operation procedure, the CPU module sends a time synchronization command to other
module, each module repeats heartbeat message to the CPU module, if it does not respond or the
heartbeat is abnormal, then this device is blocked.

2. Check whether the settings of other modules are consistent with the CPU module.

The actual values of all the settings in the CPU module are initialized to send to the corresponding
slave modules. In the process of operation, the setting values stored in the CPU module and the
setting values of other modules will be checked one by one. If they are not consistent, this device
will issue the alarm signal "Fail_Settings".

6.3 Analog Input Supervision

The sampling circuit of this device is designed as dual-design scheme. Each analog sampling

PCS-9611S Feeder Relay 6-3


Date: 2019-04-24
6 Supervision

channel is sampled by two groups of ADC. The sampling data is self checking and inter checking
in real time. If any sampling circuit is abnormal, the device reports the alarm signal [Alm_Sample],
and the protection function related to the sampling channel is disabled at the same time. When
the sampling circuit returns to normal state, the related protection is not blocked after 10s.

6.4 Secondary Circuit Supervision

The secondary circuit supervision function includes current transformer supervision (CTS),
voltage transformer supervision (VTS) and tripping/closing circuit supervision.

 CTS function

The purpose of the CTS function is to detect whether the current transformer circuit is failed. In
some cases, if the CT is failed (broken-conductor, short-circuit), related protective element should
be blocked for preventing this device from mal-operation.

See further details about the CTS function, please refer Chapter 3.

 VTS function

The purpose of the VTS function is to detect whether the VT analog input is normal. Because
some function, such as synchronism check, will be influenced by a voltage input failure.

The VT circuit failure can be caused by many reasons, such as fuse blown due to short-circuit

6 fault, poor contact of VT circuit, VT maintenance and so on. The device can detect the failure, and
then issue an alarm signal and block relevant function.

See further details about the VTS function, please refer Chapter 3.

 Tripping circuit function

The tripping circuit supervision function can be realized by program the logic function of this
device through the PCS-Studio according to the practical application experience of the user. In
this manual, a scheme which uses two independent binary inputs to supervise the tripping circuit
is recommended.

The following figure show the recommended scheme for tripping circuit supervision and the logic
diagram of the TCS function.

DC+ DC-
52a TC
BTJ

52b

Protection Device Circuit Breaker


[BI_01]
& 600ms [Alm_TCS]
[BI_02]

Figure 6.4-1 Principle of the TCS function with two binary inputs

6-4 PCS-9611S Feeder Relay


Date: 2019-04-24
6 Supervision

Where:

“BTJ” is the protection tripping output contact;

“TC” is the tripping coil of the circuit breaker;

[BI_01] is the binary input which is parallel connected with “BTJ”;

[BI_02] is the binary input which is serial connected with the “52b” contact.

6.5 Binary Input Supervision

6.5.1 Debounce Time

The well-designed debounce technique is adopted in this device, and the state change of binary
input within “Debounce time” will be ignored. As shown in Figure 6.5-1.

Binary input
state

SOE report SOE report


timestamps timestamps
Validated binary input Validated binary input
state changes state changes
1

0
6
Debounce time of Debounce time of
delayed pickup delayed dropout
Time

Figure 6.5-1 Sequence chart of debounce technique

All binary inputs should setup necessary debounce time to prevent the device from undesired
operation due to transient interference or mixed connection of AC system and DC system. When
the duration of binary input is less than the debounce time, the state of the binary input will be
ignored. When the duration of binary input is greater than the debounce time, the state of the
binary input will be validated and wrote into SOE.

In order to meet flexible configurable requirement for different project field, all binary inputs
provided by the device are configurable. Through the configuration tool, this device provides two
parameters to setup debounce time of delayed pickup and dropout based on specific binary
signal.

PCS-9611S Feeder Relay 6-5


Date: 2019-04-24
6 Supervision

Figure 6.5-2 Debounce time configuration page

The configurable binary signals can be classified as follows:

1. Type 1

This type of binary inputs includes enable/disable of protection functions, AR mode selection,
“BI_RstTarg”, “BI_Maintenance”, disconnector position, settings group switch, open and
close command of circuit breaker and disconnector, enable/disable of auxiliary functions (for
example, manually trigger recording). They are on the premise of reliability, and the
debounce time of delayed pickup and delayed dropout is recommended to set as 100ms at
least.

6 2. Type 2

This type of binary inputs include breaker failure initiating binary inputs,
“CSWIxx.Cmd_LocCtrl”, “CSWIxx.Cmd_RmtCtrl” and so on.

Debounce time

BI Input Signal.X1 t1 t2 &


Time delay Output
SIG Operation condition

 Time delay is equal to 0

The debounce time of delayed pickup and delayed dropout is recommended to set as
15ms, in order to prevent binary signals from mal-operation due to mixed connection of
AC system and DC system.

 Time delay is not equal to 0

The debounce time of delayed pickup and delayed dropout is recommended to set as
(-t1+ t2+Time delay)≥15ms, in order to prevent binary signals from mal-operation due to
mixed connection of AC system and DC system. Where, “t1” is the debounce time of
delayed pickup, and “t2” is the debounce time of delayed dropout.

3. Type 3

6-6 PCS-9611S Feeder Relay


Date: 2019-04-24
6 Supervision

This type of binary inputs is usually used as auxiliary input condition, and the debounce time
of delayed pickup and delayed dropout is recommended to set as 5ms.

When users have their own reasonable setting principles, they can set the
debounce time related settings according to their own setting principles.

6.5.2 Jitter Processing

This device can handle repetitive signal or so-called jitter via binary input module with the following
settings:

[Mon_Window_Jitter] T, monitoring window of binary input jitter processing

[Num_Blk_Jitter] N, times threshold to block binary input status change due to jitter

[Blk_Window_Jitter] T', blocking window of binary input status change due to jitter

[Num_Reblk_Jitter] N', times threshold to initiate immediately another blocking


window of binary input status change due to continuous jitter

For a binary input voltage variation, if the jitter processing function is enabled, its handling
principle is:

1. During the T,

 If the actual jitter times < N, the block will not be initiated and the status change of this
6
binary input will be considered.

 If the actual jitter times ≥ N, the T' is initiated, and the status change of binary input will
be ignored during the T'.

2. During the T',

 If the actual jitter times < N', the block window will expire. The final status of this binary
input will be compared to the original one before T', so as to determine whether there is a
change or not.

 If the actual jitter times ≥ N', the T' will be initiated again immediately (i.e. restart the
timer), and the status change of binary input will be ignored during the next T'.

An example of jitter processing is shown in the following sequence chart:

PCS-9611S Feeder Relay 6-7


Date: 2019-04-24
6 Supervision

Debounce time Input voltage level


(falling edge)

Debounce time
(rising edge)

Jitter blocking flag

n=N
initiate jitter block
Signal after
debounce & jitter
n=N processing
n=5<N=7 Prolong blocking
window

T
T t7 t8
t11
t5 t6

T T T

t1 t2 t3 t4 t9 t10 t

Figure 6.5-3 Sequence chart of jitter processing

①Red line Voltage variation of binary input

6 ②Green line Blocking signal of binary input status change due to jitter

③Blue line Binary input status after debounce and jitter processing

n Actual jitter times

We take N = 7 and N' = 5 in this example.

3. T = t2 - t1

 n=5<N

 No blocking, ② stays at 0 and ③ is tracing the voltage variation to create SOE events.

4. T = t4 - t3, at t5

 n=7=N

 The processing initiates the blocking immediately due to jitter

 Jitter blocking, no more SOE event, ② changes its status to 1 and ③ stops the tracing.

5. T' = t6 - t5

 At t7, n = 5 =N', the processing prolongs the blocking immediately due to jitter

6-8 PCS-9611S Feeder Relay


Date: 2019-04-24
6 Supervision

 Jitter blocking continues, no SOE event, ② stays at 1 and ③ keeps its status.

6. T'= t8 - t7

 At t9, n = 5 =N', the processing prolongs the blocking immediately due to jitter.

 Jitter blocking continues, no SOE event, ② stays at 1 and ③ keeps its status.

7. T'= t10 - t9

 n = 2 < N'

 At t10, jitter unblocking, ② changes its status to 0 and ③ keeps its status.

8. At t11

 Debounce time = t11 - t10

 ③ restarts to trace the voltage variation to create SOE events.

6.6 Circuit Breaker Supervision

6.6.1 Tripped Position Contact Supervision 6


If the relay detects that the tripped auxiliary contact position is on (i.e., the value of [BI_52b] is “1”.),
meanwhile any phase current is greater than 0.04In, and such a condition keeps for longer than
10 seconds, the alarm signals [Alm_Device] and [Alm_52b] will be issued, and the LED indicator
“ALARM” will be on at the same time.

6.7 Tripping Counter Statistics

The tripping counter statistics function supports statistics of the tripping operation, such as circuit
breakers, disconnectors and so on. For phase separation circuit breaker, when the position of
phase A, B, and C is detected from close state to open state, the total position tripping counter is
added, and the tripping counter is added once when the position of the disconnector is detected
from close state to open state.

In addition, the statistics of the number of state change of circuit breakers and disconnectors are
also provided. The state change counter will add one when the position is detected from close
state to open state or from open state to close state.

6.8 Supervision Alarms and Handling Suggestion

Hardware circuit and operation status of this device are self-supervised continuously. If any

PCS-9611S Feeder Relay 6-9


Date: 2019-04-24
6 Supervision

abnormal condition is detected, information or report will be displayed and a corresponding alarm
will be issued.

A minor abnormality may block a certain number of protections functions while the other functions
can still work. However, if severe hardware failure or abnormality, such as PWR module failure,
DC converter failure and so on, are detected, all protection functions will be blocked and the LED
“HEALTHY” will be extinguished and blocking output contacts “BO_Fail” will be given. The
protective device then cannot work normally and maintenance is required to eliminate the failure.
All the alarm signals and the corresponding handling suggestions are listed below.

If the device is blocked or alarm signal is sent during operation, please do find out its reason with
the help of self-diagnostic record. If the reason cannot be found at site, please notify the factory
NR. Please do not simply press button “TARGET RESET” on the protection panel or re-energize
on the device.

Table 6.8-1 Alarm description

No
Item Description Handling suggestion
.
Fail Signals (Device will be blocked)
The signal is issued with other
This signal will be issued if any fail
specific fail signals, and please
1 Fail_Device signal picks up and it will drop off when
refer to the handling suggestion
all fail signals drop off.
other specific alarm signals.
6 This signal will be issued if any
Please inform the manufacture
2 Fail_DeviceInit hardware or software failure is detected
or the agent for repair.
in the device initialization process.
1. Go to the menu
“Information→Borad Info”,
check the abnormality
This signal will be issued due to information.
mismatch between the configuration of 2. For the abnormality board, if
3 Fail_BoardConfig
plug-in modules and the designing the board is not used, then
drawing of an applied-specific project. remove, and if the board is
used, then check whether the
board is installed properly and
work normally.
Check whether the CCD
process level configuration file
This signal will be issued if the CCD
of this device is exist and
process level configure file is parsed
4 Fail_ProcLevelConfig whether the file content is
wrongly or the type in the file is
correct. May need to download
inconsistent with the actual device.
and update the correct CCD
process level configuration file.
After configuration file is updated, Please check the settings
5 Fail_SettingItem_Chgd
settings of the file and settings saved mentioned in the prompt

6-10 PCS-9611S Feeder Relay


Date: 2019-04-24
6 Supervision

No
Item Description Handling suggestion
.
on the device are not matched. This message on the LCD, and go to
signal will be issued instantaneously the menu “Settings” and select
and will be latched unless the “Confirm_Settings” item to
recommended handling suggestion is confirm settings. Then, the
adopted. device will restore to normal
operation stage.
Please reset setting values
The value of any setting is out of scope. according to the range
This signal will be issued described in the instruction
6 Fail_Setting_OvRange instantaneously and will be latched manual, then re-power or reboot
unless the recommended handling the device and the device will
suggestion is adopted. restore to normal operation
state.
The alarm signal will be issued
instantaneously when an error is found
7 Fail_Memory
during checking memory data, and
usually, it will automatically drop out. Please inform the manufacture
The board fails to register the variable, or the agent for repair.
because of abnormal board, insufficient
8 Fail_BoardRegister
memory space, or incorrect
configuration. 6
The configuration process does not run
9 Fail_ProcessConfig
properly. View the menu "Initialization
The board fails to be initialized, Error" to check the detailed
because of abnormal board, insufficient reason, and send the reason to
10 Fail_BoardInit
memory space, or incorrect the manufacture or the agent.
configuration.
Error is found during checking settings.
It means inappropriate or incorrect
settings for some application scenarios
are checked.
11 Fail_Settings Please check the settings
This signal will be issued
instantaneously and will be latched
unless the recommended handling
suggestion is adopted.
Sampling error, it means that the DC 1. Please make the device out
component contained in the sample is of service.
too large or there is some problem 2. Then check if the analog input
12 Fail_Sample during the mutual-check of double AD modules and wiring connectors
sample value. connected to those modules are
This signal will be issued installed at the position.
instantaneously and will be latched 3. Re-power the device, if it is

PCS-9611S Feeder Relay 6-11


Date: 2019-04-24
6 Supervision

No
Item Description Handling suggestion
.
unless the recommended handling still invalid, please replace the
suggestion is adopted. CPU module.
Alarm Signals (Device will not be blocked)
The signal is issued with other
The device is abnormal. This signal will
specific alarm signals, and
be issued if any alarm signal picks up
13 Alm_Device please refer to the handling
and it will drop off when all alarm
suggestion other specific alarm
signals drop off.
signals.
This signal will be issued if any
hardware or software configuration Please inform the manufacture
14 Alm_DeviceInit
wrong is detected in the device or the agent to deal with it.
initialization process.
Users may pay no attention to
the alarm signal in the project
commissioning stage, but it is
needed to download the latest
package file (including correct
The error is found during checking the version checksum file) provided
version of software downloaded to the by R&D engineer to make the
15 Alm_Version device. This signal will be issued alarm signal disappear. Then
6 instantaneously and will drop off users get the correct software
instantaneously. version. It is not allowed that the
alarm signal is issued on the
device already has been put into
service. The devices having
being put into service so that
the alarm signal disappears.
Alarm signal indicating that the
equipment is in maintenance state (the Check the binary input
16 Alm_Maintenance
binary input [BI_Maintenance] is [BI_Maintenance].
energized.
The device is in the communication test No special treatment is needed,
mode. This signal will be issued and disable the communication
17 Alm_CommTest
instantaneously and will drop off test function after the completion
instantaneously. of the test.
Management procedure will upload and
check the parameters and settings of
Put the protective device out of
each protection plug-in module
18 Alm_Settings_MON service at once. Inform the
regularly, if the parameters and settings
factory or agency to maintain it.
are inconsistent, the alarm signal will be
issued.
19 Alm_BI_SettingGrp The active group set by settings in Please check the value of

6-12 PCS-9611S Feeder Relay


Date: 2019-04-24
6 Supervision

No
Item Description Handling suggestion
.
device and that set by binary input are setting [Active_Grp] and binary
not matched. This signal will issued input of indicating active group,
instantaneously and will drop off and make them matched. Then
instantaneously. the “ALARM” LED will be
extinguished and the
corresponding alarm message
will disappear and the device
will restore to normal operation
state.
1. Check whether the selected
clock synchronization mode
matches the clock
synchronization source;
2. Check whether the wiring
connection between the device
and the clock synchronization
source is correct
3. Check whether the setting for
selecting clock synchronization
The time synchronization abnormality (i.e. [Opt_TimeSyn]) is set
20 Alm_TimeSyn
alarm. correctly. If there is no clock 6
synchronization, please set the
setting [Opt_TimeSyn] as ”No
TimeSyn”.
After the abnormality is
removed, the “ALARM” LED will
be extinguished and the
corresponding alarm message
will disappear and the device
will restore to normal operation
state.
The memory of CPU plug-in module is Please inform the manufacture
21 Alm_Insuf_Memory
insufficient. or the agent to deal with it.
The configuration file of IEC103 is
detected to be not correct when this file Please inform the manufacture
22 Alm_CfgFile_IEC103
is parsed in the device initialization or the agent to deal with it.
process.
CPU module detects that some module
23 Alm_Board is reset due to the abnormality during
Please inform the manufacture
the device operating.
or the agent to deal with it.
An abnormality is detected during the
24 Bx.Alm_Board
module self-check.

PCS-9611S Feeder Relay 6-13


Date: 2019-04-24
6 Supervision

No
Item Description Handling suggestion
.
No sufficient NOR flash space used to
25 Alm_Insuf_NORflash
store the program in CPU module
The settings which are stored in CPU
26 Alm_Settings module are different with the settings
which are used by other modules.
Please refer to the fault
Disturbance fault recording settings are
27 Alm_Settings_DFR recording configuration related
set wrongly
contents, i.e. Section 7.4.
Check the setting of network
The network mode is inconsistent, such
mode, or upload the device log
as the setting is set as HSR mode, but
28 Alm_NetMode_Unmatched and confirm with the
the actual operation mode is PRP
manufacturer or agent whether
mode.
the network mode is supported.
The device's master process is
Please check the load of the
29 Alm_master abnormal and it is blocked for more
device.
than 1 minute.
The configuration file of DNP client 1 is
30 Alm_CfgFile_TCP1_DNP
incorrect.
The configuration file of DNP client 2 is Please contact the configuration
31 Alm_CfgFile_TCP2_DNP
incorrect. engineer to check and confirm
6 32 Alm_CfgFile_TCP3_DNP
The configuration file of DNP client 3 is the contents of DNP
incorrect. configuration file.
The configuration file of DNP client 4 is
33 Alm_CfgFile_TCP4_DNP
incorrect.
No special treatment is needed,
The device is in the binary output test and disable the binary output
34 Alm_BOTest
mode. test function after the completion
of the test.
Sampling abnormality alarm, indicating
Please check the data sampling
35 Alm_Sample that the data sampling quality is sent
quality
abnormally.
DPS abnormality signal, if the circuit
breaker position is intermediate or bad,
this alarm will be issued.
36 Breaker.DPS.Alm
This signal will pick up and drop off with
a time delay defined by
Check the corresponding DPS
[CSWI**.DPS.t_Alm].
signal
DPS abnormality signal, if the switch 0x
position is intermediate or bad, this
Switch0x.DPS.Alm
37 alarm will be issued.
(x=1~9)
This signal will pick up and drop off with
a time delay defined by

6-14 PCS-9611S Feeder Relay


Date: 2019-04-24
6 Supervision

No
Item Description Handling suggestion
.
[CSWI**.DPS.t_Alm].
The initiating signal of breaker failure Check the initiating contact of
38 50BF.Alm_Init
protection is energized consistently. breaker failure protection
Please check the corresponding
CT circuit fails.
CT secondary circuit. After the
This signal will pick up with a time delay
39 CTS.Alm abnormality is eliminated, the
[CTS.t_DPU] and will drop off with a
device returns to normal
time delay [CTS.t_DDO].
operation state.
Please check the corresponding
VT circuit fails.
VT secondary circuit. After the
This signal will pick up with a time delay
40 VTS.Alm abnormality is eliminated, the
[VTS.t_DPU] and will drop off with a
device returns to normal
time delay [VTS.t_DDO].
operation state.
GOOSE alarm signals
It is an overall alarm signal and will be
issued if any of the following alarm Please check Ethernet switch of
signals is generated: GOOSE network, GOOSE
41 GAlm_Overall
“GAlm_AStorm”, “GAlm_BStorm”, configuration file and GOOSE
“GAlm_CfgFile”, “XX.GAlm_ADisc”, network.
“XX.GAlm_BDisc”, “XX.GAlm_Cfg”

GOOSE alarm signal indicating that


Inform commissioning personnel 6
42 GAlm_CfgFile to check the GOOSE
GOOSE configuration file is incorrect.
configuration file.
@Bx.Name_n_GCommLink. Network A of corresponding GOOSE
43
GAlm_ADisc link is disconnected
@Bx.Name_n_GCommLink. Network B of corresponding GOOSE
44 Please check the GOOSE
GAlm_BDisc link is disconnected
network and GOOSE
The GOOSE control blocks received on
configuration file.
@Bx.Name_n_GCommLink. network and GOOSE control blocks
45
GAlm_Cfg defined in GOOSE configuration file are
unmatched.

Where:

@Bx.Name_n_GCommLink is the set value of the label setting of [Bx.Name_n_GCommLink]


(n=000~127)

PCS-9611S Feeder Relay 6-15


Date: 2019-04-24
6 Supervision

6-16 PCS-9611S Feeder Relay


Date: 2019-04-24
7 System Functions

7 System Functions

Table of Contents

7.1 Clock Synchronization .................................................................................... 7-1


7.1.1 Clock Synchronization Mode ................................................................................................ 7-1

7.1.2 Clock Synchronization Abnormality ...................................................................................... 7-1

7.1.3 Clock Synchronization Priority ............................................................................................. 7-1

7.1.4 SNTP Setup .......................................................................................................................... 7-2

7.2 State Information ............................................................................................. 7-3


7.2.1 Overview ............................................................................................................................... 7-3

7.2.2 Access Method ..................................................................................................................... 7-3

7.3 Event Recording .............................................................................................. 7-4


7.3.1 Overview ............................................................................................................................... 7-4

7.3.2 Disturbance Records ............................................................................................................ 7-4

7.3.3 Supervision Events ............................................................................................................... 7-4

7.3.4 Binary Events ....................................................................................................................... 7-4

7.3.5 Device Logs .......................................................................................................................... 7-4 7


7.3.6 Control Logs ......................................................................................................................... 7-5

7.3.7 Access Method ..................................................................................................................... 7-5

7.4 Fault Recording ............................................................................................... 7-5


7.4.1 Overview ............................................................................................................................... 7-5

7.4.2 Fault Report .......................................................................................................................... 7-6

7.4.3 Fault Waveform .................................................................................................................... 7-6

7.4.4 Access Method ..................................................................................................................... 7-7

7.5 Maintenance State ........................................................................................... 7-7


7.6 Communication Test ....................................................................................... 7-8
7.7 Output Test ....................................................................................................... 7-8
7.8 Target Reset ..................................................................................................... 7-9
7.9 Switch Setting Groups .................................................................................... 7-9

PCS-9611S Feeder Relay 7-a


Date: 2019-04-24
7 System Functions

7-b PCS-9611S Feeder Relay


Date: 2019-04-24
7 System Functions

7.1 Clock Synchronization

7.1.1 Clock Synchronization Mode

The device supports various kinds of clock synchronization methods, including hardware clock
synchronization and software clock synchronization.

1. Hardware clock synchronization ([Opt_TimeSyn]=Conventional)

 IRIG-B: IRIG-B via RS-485 differential level, TTL level or optical fiber interface

 PPS: Pulse per second (PPS) via RS-485 differential level or binary input

 PPM: Pulse per minute (PPM) via RS-485 differential level or binary input

 IEEE1588: Clock message based on IEEE1588 via optical fiber interface

2. Software clock synchronization ([Opt_TimeSyn]=SAS)

 SNTP (PTP): Unicast (point-to-point) SNTP mode via Ethernet network

 SNTP (BC): Broadcast SNTP mode via Ethernet network

 Message (IEC103/Modbus/DNP3.0): Clock messages through IEC103 protocol, Modbus


protocol and DNP3.0 protocol

7.1.2 Clock Synchronization Abnormality


The device provide an alarm signal "Alm_TimeSyn", which indicates the signal of clock
synchronization is abnormal or is lost. The setting [Opt_TimeSyn] should be set reasonably
according to actual clock synchronization source.
7
If the setting [Opt_TimeSyn] is set as "Conventional" and no hardware clock synchronization
signal is connected, the device will automatically switch into software clock synchronization and
issue the alarm signal. If the setting [Opt_TimeSyn] is set as "SAS" and neither hardware clock
synchronization signal nor software clock synchronization signal is connected, the device will
issue the alarm signal. If the setting [Opt_TimeSyn] is set as "NoTImeSyn" and no clock
synchronization signal is connected, the device will not issue the alarm signal. The clock
synchronization is still fulfilled when valid clock synchronization signal is received.

7.1.3 Clock Synchronization Priority

The device provides a priority-based adaptive clock synchronization scheme, which means that
the device can automatically identify multiple clock synchronization sources in the same clock
synchronization mode and choose the highest priority of lock synchronization sources.

When the setting [Opt_TimeSyn] is set as "Conventional", the device can automatically identify
clock synchronization signal among IRIG-B, PPS, PPM and IEC1588. If IRIG-B, PPS, PPM and
IEC1588 exist at the same time, the device selects IRIG-B in priority. If PPS, PPM and IEC1588
exist at the same time, the device selects IEEE1588 in priority.

PCS-9611S Feeder Relay 7-1


Date: 2019-04-24
7 System Functions

When the setting [Opt_TimeSyn] is set as "SAS", the device can automatically identify whether
there is valid hardware clock synchronization signal. The device selects hardware clock
synchronization signal or the combination of hardware clock synchronization signal plus software
clock synchronization signal in priority.

Clock synchronization mode Clock synchronization signal Priority selection


IRIG-B + IEEE1588 + PPS/PPM IRIG-B
IRIG-B + IEEE1588 IRIG-B
Hardware clock synchronization
IRIG-B + PPS/PPM IRIG-B
IEEE1588 + PPS/PPM IEEE1588
Priority 1: IRIG-B
Priority 2: SNTP
Priority 3: Message
IRIG-B + SNTP + Message
Only one kind of clock
synchronization signal is valid
according to the priority
Priority 1: IEEE1588
Priority 2: SNTP
Priority 3: Message
IEEE1588 + SNTP + Message
Only one kind of clock
Software clock synchronization
synchronization signal is valid
according to the priority
Priority 1: PPS/PPM + SNTP
Priority 2: PPS/PPM + Message
Priority 3: PPS/PPM
Priority 4: SNTP
PPS/PPM + SNTP + Message
7 Priority 5: Message
Select clock synchronization signal
(including combination mode)
according to the priority

7.1.4 SNTP Setup

When the device adopts SNTP to realize clock synchronization, [IP_Server_SNTP] and
[IP_StandbyServer_SNTP] shall be set correctly.

[IP_Server_SNTP] is the address of SNTP clock synchronization server which sends SNTP timing
messages to the relay or BCU. [IP_StandbyServer_SNTP] is the address of standby SNTP clock
synchronization server.

Both [IP_Server_SNTP] and [IP_StandbyServer_SNTP] are ineffective unless SNTP clock


synchronization is valid.

When both [IP_Server_SNTP] and [IP_StandbyServer_SNTP] are set as "000.000.000.000", the


device receives broadcast SNTP synchronization message.

When either [IP_Server_SNTP] or [IP_StandbyServer_SNTP] is set as "000.000.000.000", the

7-2 PCS-9611S Feeder Relay


Date: 2019-04-24
7 System Functions

device adopts the setting whose value is not equal to "000.000.000.000" as SNTP server address
and receives unicast SNTP synchronization message.

If neither [IP_Server_SNTP] nor [IP_StandbyServer_SNTP] is set as "000.000.000.000", the


device adopts the setting [IP_Server_SNTP] as SNTP server address to receive unicast SNTP
synchronization message. If the device does not receive any server response after 30s, it adopts
the setting [IP_StandbyServer_SNTP] as SNTP server address to receive unicast SNTP
synchronization message.

The device will switch between [IP_Server_SNTP] and [IP_StandbyServer_SNTP] repeatedly if it


does not receive any server response in 30s.

7.2 State Information

7.2.1 Overview
The device can provide real-time state information, including analog quantities (such primary
measurement value, secondary measurement value, metering value and so on) and status
quantities (supervision status, input status, output status and so on). By check these state
information, operators can know operation state of the protected equipment and whether the
device is healthy.

7.2.2 Access Method


7.2.2.1 Access by Local HMI (Human Machine Interface)

These state information can be gained via local HMI. The menu path is:

1. Analog quantities
7
 MainMenu  "Measurements"  "Primary Values"

 MainMenu  "Measurements"  "Secondary Values"

 MainMenu  "Measurements"  "Function Values"

 MainMenu  "Measurements"  "Synchrocheck"

 MainMenu  "Measurements"  "Energy Metering"

 MainMenu  "Measurements"  "Power Quality"

 MainMenu  "Measurements"  "UserDef Values"

2. Status quantities

 MainMenu  "Status"  "Inputs"

 MainMenu  "Status"  "Outputs"

 MainMenu  "Status"  "Superv Status"

 MainMenu  "Status"  "Running Status"

PCS-9611S Feeder Relay 7-3


Date: 2019-04-24
7 System Functions

 MainMenu  "Status"  "UserDef Status"

7.2.2.2 Access by Virtual HMI

Using the virtual LCD tool, the corresponding content can be viewed through the same menu path
as local LCD.

7.2.2.3 Access by Communication Client

Device's state information can be uploaded into clients through message communication. For
differential protocols, the state information can be gained through corresponding communication
service.

7.2.2.4 Access by Printer

The device can print the current state information, so that the operator can observe and save the
current operation condition. The access path is:

MainMenu  "Print"  "Device Status"

7.3 Event Recording

7.3.1 Overview

The device can store the latest 1024 time-stamped disturbance records, 1024 time-stamped
binary events, 1024 time-stamped supervision events, 256 time-stamped control logs and 1024
time-stamped device logs. All the records are stored in non-volatile memory, and when the
available space is exhausted, the oldest record is automatically overwritten by the latest one.

7.3.2 Disturbance Records


7
When any protection element operates or drops out, such as fault detector, distance protection
etc., they will be logged in event records. Disturbance records include signal name, its value
before and after changing, and the time precision is up to 1ms.

7.3.3 Supervision Events

The device is under automatic supervision all the time. If there are any failure or abnormal
condition detected, such as, chip damaged, VT circuit failure and so on, it will be logged in event
records. Supervision events include signal name, its value before and after changing, and the
time precision is up to 1ms.

7.3.4 Binary Events

When there is a binary input is energized or de-energized, i.e., its state has changed from “0” to “1”
or from “1” to “0”, it will be logged in event records. Binary events include signal name, its value
before and after changing, and the time precision is up to 1ms.

7.3.5 Device Logs


If an operator executes some operations on the device, such as reboot protective device, modify

7-4 PCS-9611S Feeder Relay


Date: 2019-04-24
7 System Functions

setting, etc., they will be logged in event records. Device logs include signal name, its value
before and after changing, and the time precision is up to 1ms.

7.3.6 Control Logs

When an operator executes a control command via local LCD, PCS-Studio or communication
client, it will be logged in control logs. Control logs include time stamp, controlled object, control
origination, control position, operation condition ,interlocking condition, control command and
operation result.

7.3.7 Access Method


7.3.7.1 Access by Local HMI

The device provides corresponding menus to view event recorders. The menu path is:

MainMenu  "Test"  "Disturb Item"

MainMenu  "Records"  "Superv Events"

MainMenu  "Records"  "IO Events"

MainMenu  "Records"  "Device Logs"

MainMenu  "Records"  "Control Logs"

7.3.7.2 Access by Virtual HMI

Using the virtual LCD tool, the corresponding content can be viewed through the same menu path
as local LCD.

7.3.7.3 Access by Communication Client

Event recorders can be uploaded into clients through corresponding communication service of the 7
protocol (including IEC60870-5-103, IEC61850, DNP3.0).

7.3.7.4 Access by Printer

The device can print event recorders, so that the operator can observe and save the current
operation condition. The access path is:

MainMenu  "Print"  "Superv Events"

MainMenu  "Print"  "IO Events"

7.4 Fault Recording

7.4.1 Overview
Fault recorder can be used to have a better understanding of the behavior of the power network
and related primary and secondary equipment during and after a disturbance. Analysis of the
recorded data provides valuable information that can be used to improve existing equipment. This
information can also be used when planning for and designing new installations.

PCS-9611S Feeder Relay 7-5


Date: 2019-04-24
7 System Functions

The fault recorder is comprised of the report and the waveform, which can be triggered by pickup
signals, trip signals and configurable binary signal [BI_TrigDFR].

The fault memory of the device is automatically updated with every recording. When the fault
memory is filled completely, the oldest records are overwritten automatically. Thus, the most
recent recordings are always stored safely. The maximum number of recordings is 32.

7.4.2 Fault Report


For each fault report, the following items are included:

1. Sequence number

Each operation will be recorded with a sequence number in the record and displayed on LCD
screen.

2. Date and time of fault occurrence

The date and time is recorded when a system fault is detected. The time resolution is 1ms.

3. Relative operating time

An operating time (not including the operating time of output relays) is recorded in the record. The
time resolution is 1ms.

4. Fault information

Including faulty phase, fault location and protection elements

7.4.3 Fault Waveform


A fault waveform contains all analog and digital quantities related to protection such as currents,
7 voltages, differential current, alarm elements, and binary inputs and etc.

The overall duration of a single fault recording comprises the total duration of the configurable
recording criterion, the pre-trigger time and the post-trigger time. With the fault recording
parameter, these components can be individually set. The pre-trigger waveform recorded duration
is configured via the setting [RecDur_PreTrigDFR]. The waveform recorded duration after the fault
disappears is configured via the setting [RecDur_PostFault]. The maximum post-trigger waveform
recorded duration is configured via the setting [MaxRecDur_PostTrigDFR].

4. [MaxRecDur_PostTrigDFR]

1. [RecDur_PreTrigDFR] 2.Pickup 3. [RecDur_PostFault]

Trigger point

Total recording time

1. Pre-trigger recording time

Use the setting [RecDur_PreTrigDFR] to set this time.

7-6 PCS-9611S Feeder Relay


Date: 2019-04-24
7 System Functions

2. Pickup recording time

The pickup recording time cannot be set. It continues as long as any valid trigger condition, binary
or analog, persists (unless limited by the limit time, which is determined by the setting
[MaxRecDur_PostTrigDFR]).

3. Post-fault recording time

The recording time begins after all activated triggers are reset. Use the setting [RecDur_PostFault]
to set this time.

4. Maximal post-trigger recording time

Use the setting [MaxRecDur_PostTrigDFR] to set this time. If the summation of pickup recording
time and post-fault recording time is larger than maximal post-trigger recording time, the
post-trigger recording time shall be equal to the setting [MaxRecDur_PostTrigDFR].

7.4.4 Access Method


7.4.4.1 Access by Local HMI

The device provides corresponding menus to check fault recording. The menu path is:

MainMenu  "Records"  "Disturb Records"

7.4.4.2 Access by Virtual HMI

Using the virtual LCD tool, the corresponding content can be viewed through the same menu path
as local LCD.

7.4.4.3 Access by Communication Client

Fault recording can be uploaded into clients through corresponding communication service of the
protocol (including IEC60870-5-103, IEC61850, DNP3.0).
7
7.4.4.4 Access by Printer

The device can print fault recording, so that the operator can observe and save the current
operation condition. The access path is:

MainMenu  "Print"  "Disturb Records"

7.5 Maintenance State

The device provides maintenance state, i.e., the binary input [BI_Maintenance] is energized,
which is convenient for maintenance work. For adopting conventional CT/VT, binary inputs and
binary outputs, maintenance state has no influence on protection logics. For binary inputs and
binary outputs by GOOSE connections. During device maintenance, the object will send GOOSE
message with Test quality attribute. The Test quality attribute indicates to the receiver device that
the object received via a GOOSE message was created under test conditions and not operating
conditions. If the Test quality attribute received is different with the object's Test quality attribute,
binary inputs and binary outputs by GOOSE connections will be affected based on different types

PCS-9611S Feeder Relay 7-7


Date: 2019-04-24
7 System Functions

of binary inputs and binary outputs. For SV (Sampling Value) message, if the Test quality attribute
received is different with the object's Test quality attribute, the relevant protection functions will be
blocked.

For IEC60870-5-103 protocol, only the messages in link layer maintained, service messages in
the application layer which is uploaded automatically are blocked, and service messages in the
application layer which is issued by the client are rejected. For IEC61850 protocol, all Test quality
attribute set as "1". For DNP3.0 and ModBus protocol, they are not affected.

7.6 Communication Test

The device provides Test Mode to allow all protection elements, supervision events and binary
events to fulfill communication test, but to avoid the output contacts to close. During
communication test, protection functions are not affected, the signals generated by
communication test are recorded in relevant reports, and event recording and fault recording will
not stop recording disturbance information. The alarm signal "Alm_CommTest" will be issued to
indicate the operator when activating Test Mode and exiting Test Mode.

Communication test can be gained via local HMI and the virtual HMI, the corresponding content
can be viewed through the following menu paths:

 Events Simulation

Main Menu  "Test"  "Device Test"  "Disturb Events"

Main Menu  "Test"  "Device Test"  "Superv Events"

Main Menu  "Test"  "Device Test"  "IO Events"

7  Forced Measurements

Main Menu  "Test"  "Device Test"  "Measurements"

Forced measurement ONLY affects the values modified and transmitted to


station control or control center. Primary circuit, secondary circuit and
device local logic will not be influenced. Forced value will remain during the
test until the exit of this menu.

If no input operation is carried out within 60s, this test will exit and return to
the previous menu automatically.

7.7 Output Test


The device provides Output Test Mode to test all outputs. Through this mode, there will be real
operations, such as contact closing and GOOSE output value change, triggered by the device to
test output circuits and links. So, protection functions outputs and the connecting primary
equipments are affected. The output signals generated by output test are not recorded, while the

7-8 PCS-9611S Feeder Relay


Date: 2019-04-24
7 System Functions

entering and exiting of output test mode will be recorded in Superv Events. During the output test,
the protection functions will not stop, nor will the all recording functions.

Output test can be gained via the local LCD or virtual HMI of a debugging PC, the corresponding
content can be viewed through the following menu paths:

 Contacts Outputs

Main Menu  "Test"  "Device Test"  "Contact Outputs"

 GOOSE Outputs

Main Menu  "Test"  "Device Test"  "GOOSE Outputs"

7.8 Target Reset

The device provides target reset which can be used to reset local signals (including magnetic
latching output relays), latched LEDs, and confirm pop-up windows of reports. The function does
not affect the protection logic and communication function. There are several ways to reset.

1. Reset via local HMI

 Access menu path: MainMenu  "Local Cmd"  "Reset Target"

 Press the command pushbutton “ESC”+“ENT” on operation panel of the device under
main interface

 Press the command pushbutton " TARGET RESET" on operation panel of the device

2. Reset via virtual HMI

Access menu path: MainMenu  "Local Cmd"  "Reset Target" 7


3. Reset via binary input

Energize the binary input "BI_RstTarg"

4. Reset via IEC61870-5-103

Use ASDU20, INF19 of IEC61870-5-103 protocol

5. Reset via remote control

Use standard remote service of corresponding protocol

7.9 Switch Setting Groups

For different applications users can save the respective function settings in so-called settings
groups, and if necessary enable them quickly. Up to 10 different settings groups can be saved in
the device. In the process, only one settings group is active at any given time. During operation,
the operator can switch between setting groups.

PCS-9611S Feeder Relay 7-9


Date: 2019-04-24
7 System Functions

The device will be temporarily blocked during switching setting groups. During temporary device
blocking, the device will loss protection functions and communication functions. Alarm signals
"Fail_Device" and "Alm_Device" will be issued. There are several ways to switch setting groups.

1. Switch via local HMI

 Access menu path: MainMenu  "Setting"  "Global Settings"  "System Settings",


change the value of the setting [Active_Grp]

 Press the command pushbutton “MENU” under main interface (password is required)

2. Switch via virtual HMI

Access menu path: MainMenu  "Setting"  "Global Settings"  "System Settings",


modify the setting [Active_Grp]

3. Switch via binary inputs

There are 2 appropriate input signals available for switching setting group via binary inputs.
These input signals allow selection of the settings group via a binary code. If one of two
signals changes, the signal image present will result in switching over to the appropriate
settings group. If only 2 settings groups must be switched over, only 1 binary input is required.
The following table shows the possible binary codes and applicable setting groups.

External input signals can be connected with "setting_grp_bit0" and "setting_grp_bit1"


respectively by PCS-Studio.

Binary codes Group 1 Group 2 Group 3 Group 4


setting_grp_bit1 0 0 1 1
setting_grp_bit0 0 1 0 1

7 4. Switch via communication client

The communication protocols IEC 60870-5-103 or IEC 61850 can be used for switching the
setting groups via a communication connection.

 Use "General Service" of IEC61870-5-103 protocol to modify the setting [Active_Grp]

 Use "SelectActiveSG" of IEC61850 protocol to switch setting groups.

7-10 PCS-9611S Feeder Relay


Date: 2019-04-24
8 Hardware

8 Hardware

Table of Contents

8.1 Overview ........................................................................................................... 8-1


8.2 Typical Wiring .................................................................................................. 8-4
8.3 CT Requirement ............................................................................................... 8-7
8.3.1 CT Types .............................................................................................................................. 8-7

8.3.2 CT Requirement ................................................................................................................... 8-8

8.4 Plug-in Module Description ............................................................................ 8-9


8.4.1 Human-machine Interface Module (NR6855/NR6856) ........................................................ 8-9

8.4.2 Power Supply Module (NR6305/NR6310) ........................................................................... 8-9

8.4.3 CPU Module (NR6106) ...................................................................................................... 8-12

8.4.4 Analog Input Module (NR6641) .......................................................................................... 8-16

8.4.5 Binary Input Module (NR6601/NR6610) ............................................................................ 8-19

8.4.6 Binary Output Module (NR6651/NR6652/NR6660) ........................................................... 8-23

List of Figures

Figure 8.1-1 Hardware diagram .................................................................................................. 8-1

Figure 8.1-2 Front view of this device.......................................................................................... 8-3

Figure 8.1-3 Typical rear view of this device (pin-ferrule-terminal modules) ............................ 8-3 8
Figure 8.1-4 Typical rear view of this device (ring-ferrule-terminal modules) ........................... 8-4

Figure 8.2-1 Typical hardware configuration 1 (pin-ferrule-terminal modules) ......................... 8-4

Figure 8.2-2 Typical wiring 1 (pin-ferrule-terminal modules) ...................................................... 8-5

Figure 8.2-3 Typical hardware configuration 2 (ring-ferrule-terminal modules) ........................ 8-6

Figure 8.2-4 Typical wiring 2 (ring-ferrule-terminal modules) .................................................... 8-7

Figure 8.4-1 View of power supply module ............................................................................... 8-10

Figure 8.4-2 View of CPU module .............................................................................................. 8-14

Figure 8.4-3 Connection of communication terminal ............................................................ 8-15

Figure 8.4-4 Jumpers of printer/RS-485 port .......................................................................... 8-15

PCS-9611S Feeder Relay 8-a


Date: 2019-04-24
8 Hardware

Figure 8.4-5 Schematic diagram of CT circuit automatically closed ................................... 8-16

Figure 8.4-6 Terminal definition of analog input module ...................................................... 8-17

Figure 8.4-7 Current connection examples ............................................................................ 8-18

Figure 8.4-8 Voltage connection examples............................................................................. 8-19

Figure 8.4-9 Voltage dependence for binary inputs............................................................... 8-20

Figure 8.4-10 View of binary input module (NR6601A) ......................................................... 8-21

Figure 8.4-11 View of binary input module (NR6610A/B) ...................................................... 8-22

Figure 8.4-12 View of binary output module NR6651A ......................................................... 8-24

Figure 8.4-13 View of binary output module NR6651B ......................................................... 8-25

Figure 8.4-14 View of binary output module NR6652A ......................................................... 8-26

Figure 8.4-15 View of binary output module (NR6660A) ....................................................... 8-27

List of Tables

Table 8.4-1 Terminal definition and description of power supply module ............................... 8-11

Table 8.4-2 Terminal definition and description of power supply module ............................... 8-11

Table 8.4-3 Configuration and terminal definition of CPU module........................................... 8-14

Table 8.4-4 Terminal definition and description of binary input module (NR6601A) ............... 8-21

Table 8.4-5 Terminal definition and description of binary input module (NR6610A/B) .......... 8-23

8-b PCS-9611S Feeder Relay


Date: 2019-04-24
8 Hardware

8.1 Overview

The modular design of this device allows this device to be easily upgraded or repaired by a
qualified service person. The faceplate is hinged to allow easy access to the configurable
modules, and back-plugging structure design makes it easy to repair or replace any module.

This device adopts one 32-bit ARM core in the CPU chip as control core for management and
monitoring function, and adopts another 32-bit ARM core in the CPU chip for all the protection
calculation. The parallel processing of sampled data can be realized in each sampling interval to
ensure ultrahigh reliability and safety of the device.

This device is developed on the basis of our latest software and hardware platform, and the new
platform major characteristics are of high reliability, networking and great capability in
anti-interference. See Figure 8.1-1 for the hardware diagram.

External
Binary Input

Conventional CT/VT A/D


Output
ARM1
Relay
A/D

Pickup
ECVT Relay

ETHERNET

+E
LCD
Clock SYN
Power
Uaux LED ARM2
Supply
RJ45

Keypad
PRINT

Figure 8.1-1 Hardware diagram 8


The working process of the device is shown in above figure: the currents and voltages from
conventional CT/VT are converted into small voltage signal and sent to ARM1 core after filtered
and A/D conversion for protection calculation and fault detector respectively (ECVT signals are
sent to the device without small signal and A/D conversion). The ARM1 core carries out fault
detector, protection logic calculation, tripping output, and the ARM2 core performs SOE
(sequence of event) record, waveform recording, printing, communication between the device and
SAS and communication between HMI and CPU. When the fault detector detects a fault and picks
up, the positive power supply for output relay is provided.

The items can be flexibly configured depending on the situations like sampling method of the
device (conventional CT/VT or ECT/EVT), and the mode of binary output (conventional binary
output or GOOSE binary output). The configurations for PCS S series based on microcomputer
are classified into standard and optional modules.

PCS-9611S Feeder Relay 8-1


Date: 2019-04-24
8 Hardware

Table 8.1-1 Module configuration of this device

Module ID Module description Remark


NR6855/NR6856 Human machine interface module (HMI module) Mandatory
NR6305/6310 Power supply module (PWR module) Mandatory
NR6106 Main CPU module (CPU module) Mandatory
NR6641 Analog input module (AI module) Mandatory
NR6601/NR6610 Binary input module (BI module) Mandatory
NR6651/NR6652/NR6660 Binary output module (BO module) Mandatory

 HMI module is comprised of LCD, keypad, LED indicators and multiplex RJ45 ports for user
as human-machine interface.

 PWR module converts DC 250/220/125/110V into various DC voltage levels for modules of
the device.

 CPU module provides functions like communication with SAS, event record, setting
management etc., and performs filtering, sampling, protection calculation and fault detector
calculation.

 AI module converts AC current and voltage from current transformers and voltage
transformers respectively to small voltage signal.

 BI module provides binary inputs via opto-couplers with rating voltage among AC110V/220V
or DC24V/48V/110V/125V/220V/250V (configurable).

 BO module provides output contacts for tripping, and signal output contact for annunciation
signal, remote signal, fault and disturbance signal, operation abnormal signal etc.

Following figures show front and rear views of this device respectively.

8-2 PCS-9611S Feeder Relay


Date: 2019-04-24
8 Hardware

Figure 8.1-2 Front view of this device

Figure 8.1-3 Typical rear view of this device (pin-ferrule-terminal modules)

PCS-9611S Feeder Relay 8-3


Date: 2019-04-24
8 Hardware

Figure 8.1-4 Typical rear view of this device (ring-ferrule-terminal modules)

8.2 Typical Wiring

B01 B02 & B03 B04 B05 B06 P1 B01 B02 & B03 B04 P1

NR6106AA NR6641-6I5U Option Option Option NR6310A NR6106AA NR6641-6I5U Option NR6310A

BI_01+ 01 BI_01+ 01
01 I1 I1n 02 01 I1 I1n 02
BI_01- 02 BI_01- 02
03 I2 I2n 04 BI_02+ 03 03 I2 I2n 04 BI_02+ 03
BI_02- 04 BI_02- 04
NET 05 I3 I3n 06 BI_COM 05 NET 05 I3 I3n 06 BI_COM 05
BI_03 06 BI_03 06
LC 07 I4 I4n 08 LC 07 I4 I4n 08
BI_04 07 BI_04 07
LC BI_05 08 LC BI_05 08
09 I5 I5n 10 09 I5 I5n 10
BI_06 09 BI_06 09
11 I6 I6n 12 BI_07 10 11 I6 I6n 12 BI_07 10
BI_08 11 BI_08 11
13 14 BI_09 12 13 14 BI_09 12
13 13

8
15 U1 U1n 16 BO_01 15 U1 U1n 16 BO_01
14 14
17 U2 U2n 18 15 17 U2 U2n 18 15
BO_02 BO_02
16 16
01 1A 19 U3 U3n 20 17 01 1A 19 U3 U3n 20 17
BO_03 BO_03
02 1B 18 02 1B 18
03 SGND 21 U4 U4n 22 19 03 SGND 21 U4 U4n 22 19
BO_04 BO_04
04 2A 20 04 2A 20
23 U5 U5n 24 23 U5 U5n 24
05 2B 21 05 2B 21
06 SGND BO_05 06 SGND
BO_05
22 22
07 SYN+ 07 SYN+
23 23
08 SYN- BO_Fail 08 SYN- BO_Fail
24 24
09 SGND 09 SGND
PWR+ 25 PWR+ 25
10 SYN-TTL 10 SYN-TTL
PWR- 26 PWR- 26

CONSOLE Ground CONSOLE Ground

Figure 8.2-1 Typical hardware configuration 1 (pin-ferrule-terminal modules)

The following wiring is given based on above hardware configuration

8-4 PCS-9611S Feeder Relay


Date: 2019-04-24
8 Hardware

Optional optical or electrical Ethernet to SCADA


485-1A 0101 0201

COM
485-1B 0102 Ia
0202
SGND 0103
0203
485-2A 0104 Ib
0204

COM
485-2B 0105
0205
SGND 0106
Ic
SYN+ 0107 0206

Clock SYN
SYN- 0108 0207
SGND 0109 I0
0208
TTL 0110
0209
I0
Multiplex RJ45 0210
0211

AI plug-in module
Isef
P101 + BI_01 0212
0213
P102 -
0214
- P103 + BI_02
0215
P104 - U0
0216
P106 + BI_03 0217
Ux
0218
P107 + BI_04 0219
Ua
0220
PWR plug-in module

0221
P112 + BI_09 Ub
0222
P105 0223
P113 Uc
BO_01 0224
P114
P115
P116 BO_02

P121
P122 BO_05

P123
P124 BO_Fail

PWR+ P125
External DC power Power
supply
PWR- P126 Supply
8
Grounding Bus

Figure 8.2-2 Typical wiring 1 (pin-ferrule-terminal modules)

PCS-9611S Feeder Relay 8-5


Date: 2019-04-24
8 Hardware

B01 B02 & B03 B04 B05 B06 P1 B01 B02 & B03 B04 P1

NR6106AA NR6641-6I5U Option Option Option NR6305A NR6106AA NR6641-6I5U Option NR6305A

01 I1 I1n 02 01 BI_01+ BI_01- 02 01 I1 I1n 02 01 BI_01+ BI_01- 02

03 I2 I2n 04 03 BI_02+ BI_02- 04 03 I2 I2n 04 03 BI_02+ BI_02- 04

NET 05 I3 I3n 06 05 BI_COM BI_03 06 NET 05 I3 I3n 06 05 BI_COM BI_03 06

LC 07 I4 I4n 08 07 BI_04 BI_05 08 LC 07 I4 I4n 08 07 BI_04 BI_05 08

LC 09 BI_06 BI_07 10 LC 09 BI_06 BI_07 10


09 I5 I5n 10 09 I5 I5n 10

11 I6 I6n 12 11 BI_08 BI_09 12 11 I6 I6n 12 11 BI_08 BI_09 12

13 14 13 BO_01 14 13 14 13 BO_01 14

15 U1 U1n 16 15 BO_02 16 15 U1 U1n 16 15 BO_02 16

17 U2 U2n 18 17 BO_03 18 17 U2 U2n 18 17 BO_03 18

01 1A 19 U3 U3n 20 19 BO_04 20 01 1A 19 U3 U3n 20 19 BO_04 20


02 1B 02 1B
03 SGND 21 U4 U4n 22 21 BO_05 22 03 SGND 21 U4 U4n 22 21 BO_05 22
04 2A 04 2A
23 U5 U5n 24 23 BO_Fail 24 23 U5 U5n 24 23 BO_Fail 24
05 2B 05 2B
06 SGND 06 SGND
25 PWR+ PWR- 26 25 PWR+ PWR- 26
07 SYN+ 07 SYN+
08 SYN- 08 SYN-
09 SGND 09 SGND
10 SYN-TTL 10 SYN-TTL

CONSOLE CONSOLE
Ground Ground

Figure 8.2-3 Typical hardware configuration 2 (ring-ferrule-terminal modules)

The following wiring is given based on above hardware configuration

8-6 PCS-9611S Feeder Relay


Date: 2019-04-24
8 Hardware

Optional optical or electrical Ethernet to SCADA


485-1A 0101 0201

COM
485-1B 0102 Ia
0202
SGND 0103
0203
485-2A 0104 Ib
0204

COM
485-2B 0105
0205
SGND 0106
Ic
SYN+ 0107 0206

Clock SYN
SYN- 0108 0207
SGND 0109 I0
0208
TTL 0110
0209
I0
Multiplex RJ45 0210
0211

AI plug-in module
Isef
P101 + BI_01 0212
0213
P102 -
0214
- P103 + BI_02
0215
P104 - U0
0216
P106 + BI_03 0217
Ux
0218
P107 + BI_04 0219
Ua
0220
PWR plug-in module

0221
P112 + BI_09 Ub
0222
P105 0223
P113 Uc
BO_01 0224
P114
P115
P116 BO_02

P121
P122 BO_05

P123
P124 BO_Fail

PWR+ P125
External DC power Power
supply
PWR- P126 Supply
8
Grounding Bus

Figure 8.2-4 Typical wiring 2 (ring-ferrule-terminal modules)

8.3 CT Requirement

8.3.1 CT Types
Generally there are three types of CT: high remanence, low remanence and no
remanence.

 High remanence: TPX, TPS, P, PX.

 Low remanence: TPY, PR, and the residual magnetism does not exceed 10% of the
saturation flux.

PCS-9611S Feeder Relay 8-7


Date: 2019-04-24
8 Hardware

 No remanence: TPZ level, residual magnetism can actually be ignored.

The high residual magnetism CT may have large residual magnetism. When the fault
non-periodic component and residual magnetism are in the same direction, the CT
saturation degree will be more serious. The following CT type checking calculation takes
into account the maximum residual magnetism of CT and the maximum non periodic
component on the site.

8.3.2 CT Requirement
Rated secondary limit e.m.f (volts) formula:

Esl = Kalf × Isn × (Rct + Rbn)

Kalf Accuracy limit factor: Kalf = Ipal / Ipn

Isn Rated secondary current (amps)

Rct Current transformer secondary winding resistance (ohms)

Sbn Rated burden (VAs)


Rbn Rated resistance burden (ohms): Rbn = Sbn / Isn2

Actual secondary limit e.m.f (volts) under different fault conditions:

Esl1′ = k1×Ipcf1 ×Isn×(Rct+Rb)/Ipn

Esl2′ = k2×Ipcf2 ×Isn×(Rct+Rb)/Ipn

Esl3′ = k3×Ipnt×Isn×(Rct+Rb)/Ipn

Esl4′ = k4×Ipcf4×Isn×(Rct+Rb)/Ipn

k1, k2, k3, k4 are transient factors.

Ipcf1 Maximum through fault current when out-zone fault (amps)

Maximum fault current through two bridge CB but not transformer when
Ipcf2
8 out-zone fault (amps)

Ipcf4 Maximum fault current when in-zone fault (amps)

Ipnt Transformer rated primary current (amps)

Ipn CT rated primary current (amps)

Isn CT rated secondary current (amps)

Rct Current transformer secondary winding resistance (ohms)

Rb Real resistance burden (ohms): Rb = Rr + 2RL

RL Resistance of a single lead from relay to the CT (ohms)

Rr Impedance of relay phase current input (ohms)

1. K Value Requirement

1) Single CB connection, the following condition should be fulfilled

Esl > Esl1′

8-8 PCS-9611S Feeder Relay


Date: 2019-04-24
8 Hardware

Esl > min (Esl3′, Esl4′)

While: k1=2,k3=30,k4=1.

2) Double CB connection, the following condition should be fulfilled:

Esl > Esl1′

Esl > Esl2′

Esl > min (Esl3′, Esl4′)

If both CTs of double CB are low remanence type, and with the same model, then k1=2,
k2=1.5, k3=30, k4=1.

Otherwise: k1=2,k2=2,k3=30,k4=1.

2. Example

Kalf=30, Isn=5A, Rct=1Ω, Sbn=60VA

Ipcf1=40000A, RL=0.5Ω, Rr=0.1Ω, Rc=0.1Ω, Ipn=2000A, Ipnt=1500A

Esl = kalf×Isn×(Rct+Rbn) = kalf×Isn×(Rct+ Sbn/Isn2)

= 30×5×(1+60/25)=510V

Esl1′ = k1×Ipcf1×Isn×(Rct+Rb)/Ipn

= 2×Ipcf1 ×Isn×(Rct+(Rr+2×RL))/Ipn

= 2×40000×5×(1+(0.1+2×0.5))/2000=420V

Esl3′ = k3×Ipnt×Isn×(Rct+Rb)/Ipn

=30×1500*5*(1+(0.1+2×0.5)) /2000=236.25V

Thus, Esl > Esl1′ and Esl > Esl3′

8.4 Plug-in Module Description 8


The device consists of power supply module (PWR), main CPU module (CPU), AI module, BI
module, BO plug-in module, CH plug-in module and NET-DSP plug-in module. Terminal
definitions and application of each plug-in module are introduced as follows.

8.4.1 Human-machine Interface Module (NR6855/NR6856)


The human machine interface (HMI) module is installed on the front panel of this device. It is used
to observe the running status and event information on the LCD, and configure the protection
settings and device operation mode. It can help the user to know the status of this device and
detailed event information easily, and provide convenient and friendly access interface for the
user.

8.4.2 Power Supply Module (NR6305/NR6310)


The power supply module is a DC/DC converter with electrical insulation between input and

PCS-9611S Feeder Relay 8-9


Date: 2019-04-24
8 Hardware

output. It has an input voltage range as described in Chapter 2 Technical Data. The standardized
output voltages are +5Vdc and +12Vdc. The tolerances of the output voltages are continuously
monitored.

The +5Vdc output provides power supply for all the electrical elements that need +5Vdc power
supply in this device.

The use of an external miniature circuit breaker is recommended. The miniature circuit breaker
must be in the on position when the device is in operation and in the off position when the device
is in cold reserve.

8
Figure 8.4-1 View of power supply module

Three types of power supply modules are provided: NR6305A, NR6305B and NR6310A. The
NR6305B is same as the NR6305A except that the NR6105B can support at least 500ms power
supply interruption.

 NR6305A & NR6305B

The power supply module also provides 9 binary inputs, 5 binary outputs and a device failure
binary output. A 26-pin connector is fixed on the power supply module. The terminal definition of
the connector is described as below.

8-10 PCS-9611S Feeder Relay


Date: 2019-04-24
8 Hardware

Table 8.4-1 Terminal definition and description of power supply module

Pin No. Symbol Description


01 BI_01+
The No.1 programmable binary input
02 BI_01-
03 BI_02+
The No.2 programmable binary input
04 BI_02-
05 BI_COM The common negative connection of the BI_01 to BI_09
06 BI_03 The No.3 programmable binary input
07 BI_04 The No.4 programmable binary input
08 BI_05 The No.5 programmable binary input
09 BI_06 The No.6 programmable binary input
10 BI_07 The No.7 programmable binary input
11 BI_08 The No.8 programmable binary input
12 BI_09 The No.9 programmable binary input
13
BO_01 The No.1 programmable binary output
14
15
BO_02 The No.2 programmable binary output
16
17
BO_03 The No.3 programmable binary output
18
19
BO_04 The No.4 programmable binary output
20
21
BO_05 The No.5 programmable binary output
22
23
BO_Fail The device failure signal output
24
25 PWR+ DC power supply positive input
26 PWR- DC power supply negative input

Grounded connection of the power supply 8


 NR6310A

The power supply module also provides 9 binary inputs, 5 binary outputs and a device failure
binary output. A 22-pin connector and a 4-pin connector are fixed on the power supply module.
The terminal definition of the connector is described as below.

Table 8.4-2 Terminal definition and description of power supply module

Pin No. Symbol Description


01 BI_01+
The No.1 programmable binary input
02 BI_01-
22-pin 03 BI_02+
The No.2 programmable binary input
04 BI_02-
05 BI_COM The common negative connection of the BI_01 to BI_09

PCS-9611S Feeder Relay 8-11


Date: 2019-04-24
8 Hardware

06 BI_03 The No.3 programmable binary input


07 BI_04 The No.4 programmable binary input
08 BI_05 The No.5 programmable binary input
09 BI_06 The No.6 programmable binary input
10 BI_07 The No.7 programmable binary input
11 BI_08 The No.8 programmable binary input
12 BI_09 The No.9 programmable binary input
13
BO_01 The No.1 programmable binary output
14
15
BO_02 The No.2 programmable binary output
16
17
BO_03 The No.3 programmable binary output
18
19
BO_04 The No.4 programmable binary output
20
21
BO_05 The No.5 programmable binary output
22
23
BO_Fail The device failure signal output
24
4-pin
25 PWR+ DC power supply positive input
26 PWR- DC power supply negative input

Grounded connection of the power supply

The standard rated voltage of the PWR module is self-adaptive to


88~300Vdc or 88~275Vac. For a non-standard rated voltage power supply
module please specify when place order, and check if the rated voltage of
8 power supply module is the same as the voltage of power source before
the device being put into service.

The PWR module a grounding screw for device grounding. The grounding
screw shall be connected to grounding screw and then connected to the
earth copper bar of panel via dedicated grounding wire.

Effective grounding is the most important measure for a device to prevent


EMI, so effective grounding must be ensured before the device is put into
service.

8.4.3 CPU Module (NR6106)


The CPU module is the central part of this device, and contains a multi-core 32-bit powerful
processor and some necessary electronic elements. This powerful processor performs all of the
functions for this device: protection function, communication function, human-machine interface
function and so on. There are several A/D conversion circuits on this module, which are used to

8-12 PCS-9611S Feeder Relay


Date: 2019-04-24
8 Hardware

convert the AC analog signals to corresponding DC signals for fulfilling the demand of the
electrical level standard. A high-accuracy clock chip is contained in this module, it provide
accurate current time for this device.

The main functional details of the CPU module are listed as below:

 Protection calculation and logical judgment function

The CPU module can calculate protective elements (such as overcurrent element) on the
basis of the analog sampled values (voltages and currents) and binary inputs, then it does
logical judgment function and decides whether the device needs to trip or close.

 Communication function

The CPU module can effectively manage all communication procedures, and reliably send
out some useful information through its various communication interfaces. These interfaces
are used to communicate with a SAS or a RTU. It also can communicate with the human
machine interface module. If an event occurs (such as SOE, protective tripping event etc.),
this module will send out the relevant event information through these interfaces, and make it
be easily observed by the user.

 Auxiliary calculation

Based on the voltage and current inputs, the CPU module also can calculate out the metering
values, such as active power, reactive power and power factor etc. All these values can be
sent to a SAS or a RTU through the communication interfaces.

 Human-machine interface function

This module can respond the commands from the keypad of this device and show the results
on the LCD and LED indicators of this device. It also can show the operation situation and
event information for the users through the LCD and LED indicators.

 Time synchronization

This module has a local clock chip and an interface to receive time synchronized signals from
external clock source. These signals include PPS (pulse per second) signal and IRIG-B
8
signal. Basing on the timing message (from SAS or RTU) and the PPS signal, or basing on
the IRIG-B signal, this module can synchronize local clock with the standard clock.

PCS-9611S Feeder Relay 8-13


Date: 2019-04-24
8 Hardware

Figure 8.4-2 View of CPU module

Do NOT look into the end of an optical fiber connected to an optical port.

Do NOT look into an optical port/connector.

A direct sight to laser light may cause temporary or permanent blindness.


8 The configuration and terminal definition of the CPU modules are listed in following table.

Table 8.4-3 Configuration and terminal definition of CPU module

Module ID Memory Interface Terminal No. Usage Physical Layer


2 RJ45 Ethernet Ethernet
Twisted pair wire
2 SFP Ethernet communication
01 A
RS-485 02 B To SCADA Twisted pair wire
03 SGND
NR6106AA 1G DDR
04 A
RS-485 05 B To SCADA Twisted pair wire
06 SGND
07 SYN+ To clock
RS-485 Cable
08 SYN- synchronization

8-14 PCS-9611S Feeder Relay


Date: 2019-04-24
8 Hardware

09 SGND
TTL 10 SYN-TTL Cable

The correct connection is shown in Figure 8.4-3. Generally, the shielded cable with two pairs of
twisted pairs inside shall be applied. One pair of the twisted pairs are respectively used to connect
the “+” and “–” terminals of difference signal. The other pair of twisted pairs are used to connect
the signal ground of the communication interface. The module reserves a free terminal for all the
communication ports. The free terminal has no connection with any signal of the device, and it is
used to connect the external shields of the cable when connecting multiple devices in series. The
external shield of the cable shall be grounded at one of the ends only.

Twisted pair wire


A 01

B 02

COM
SGND 03
cable with single point earthing

04
To the screen of other coaxial

Twisted pair wire


SYN+ 01

Clock SYN
SYN- 02

SGND 03

04

Cable
RTS 05

PRINT
TXD 06

SGND 07

Figure 8.4-3 Connection of communication terminal

Figure 8.4-4 Jumpers of printer/RS-485 port

The 2nd RS-485 port also can be configured as a printer port through the

PCS-9611S Feeder Relay 8-15


Date: 2019-04-24
8 Hardware

jumpers “J10” and “J11”.

Jumper RS-485 Printer


J10 Pin-1 and Pin-2 are connected Pin-2 and Pin-3 are connected
J11 Pin-1 and Pin-2 are connected Pin-2 and Pin-3 are connected

8.4.4 Analog Input Module (NR6641)


The analog input module is applicable for power plant or substation with conventional VT and CT,
and it can transform high AC input values to relevant low AC output value, which are suited to the
analog inputs of the CPU module. The transformers are used both to step-down the currents and
voltages to levels appropriate to the device’s electronic circuitry and to provide effective isolation
between this device and the power system. A low pass filter circuit is connected to each
transformer (CT or VT) secondary circuit for reducing the noise of each analog AC input signal.

For the analog input module, if the plug is not put in the socket, external CT circuit is closed itself.
Just shown as below.

Plug
Socket

In

Out

plug is not put in the socket

8 In

Out

Put the plug in the socket

Figure 8.4-5 Schematic diagram of CT circuit automatically closed

There are several types of analog input modules. The rated current is adaptive (1A/5A). Please
declare which kind of AI module is needed before ordering. Maximum linear range of the current
converter is 40In.

 NR6641-6I5U: 6CT+5VT

8-16 PCS-9611S Feeder Relay


Date: 2019-04-24
8 Hardware

 NR6641-4I4U: 4CT+4VT

 NR6641-4I7U: 4CT+7VT

The terminal definition of the analog input module is shown as below.

NR6641-6I5U NR6641-4I4U NR6641-4I7U


01 I1 I1n 02 01 I1 I1n 02 01 I1 I1n 02
03 I2 I2n 04 03 I2 I2n 04 03 I2 I2n 04
05 I3 I3n 06 05 I3 I3n 06 05 I3 I3n 06
07 I4 I4n 08 07 I4 I4n 08 07 I4 I4n 08
09 I5 I5n 10 09 10 09 10
11 I6 I6n 12 11 12 11 U1 U1n 12
13 14 13 14 13 U2 U2n 14
15 U1 U1n 16 15 16 15 U3 U3n 16
17 U2 U2n 18 17 U1 U1n 18 17 U4 U4n 18
19 U3 U3n 20 19 U2 U2n 20 19 U5 U5n 20
21 U4 U4n 22 21 U3 U3n 22 21 U6 U6n 22
23 U5 U5n 24 23 U4 U4n 24 23 U7 U7n 24

Figure 8.4-6 Terminal definition of analog input module

NEVER allow the current transformer (CT) secondary circuit connected to 8


this device to be opened while the primary system is energized. The
opened CT secondary circuit will produce a dangerously high voltage. If
this safety precaution is disregarded, personal death, severe personal
injury or considerable equipment damage will occur.

Each analog input channel can be configured according to practical


application through PCS-Studio.

Some connection examples of the current transformers and voltage transformers which are
supported by this relay are shown in this section. If one of the analog inputs has no input in a
practical engineering, the relevant input terminals should be disconnected.

PCS-9611S Feeder Relay 8-17


Date: 2019-04-24
8 Hardware

1. Current connections examples

A B C A B C
Ia Ia
Ian Ian
Ib Ib
Ibn Ibn
Ic Ic
Icn Icn
I01
I01n I01

(1) I01n

A B C (3)
Ia
Ian
Ib I0s

Ibn I0sn

Ic
(4)
Icn

I01 I02
I01n I02n

(2) (5)

Figure 8.4-7 Current connection examples

Where:

(1) Current connections to three current transformers with a star-point connection for ground
current (zero-sequence current or residual current).

(2) Current connections to three current transformers with a separate ground current
8 transformer (summation current transformer or core balance current transformer).

(3) Current connections to two current transformers with a separate ground current
transformer (summation current transformer or core balance current transformer), only
for ungrounded or compensated networks.

(4) Current connection to a core balance neutral current transformer for sensitive ground
fault detection, only for ungrounded or compensated networks.

(5) Current connection to a separate ground current transformer (summation current


transformer or core balance current transformer) for the No.2 zero-sequence current
input of this relay.

2. Voltage connections examples

8-18 PCS-9611S Feeder Relay


Date: 2019-04-24
8 Hardware

A B C A B C

Ux
52 52 52 Ux 52 52 52
Uxn
Uxn

Ua Ua
Ub Ub
Uc Uc
Un Un

U0 U0
U0n U0n
(1) (2)

Figure 8.4-8 Voltage connection examples

Where:

(1) Voltage connections to three star-connected voltage transformers with open-delta


windings and additionally to any phase voltage (for synchronism check).

(2) Voltage connections to three star-connected voltage transformers with open-delta


windings and additionally to any phase-to-phase voltage (for synchronism check).

8.4.5 Binary Input Module (NR6601/NR6610)


The binary input module contains some optical isolated binary inputs which are used to monitor
the contact positions of the corresponding bay, and all the binary inputs are configurable through
PCS-Studio according to practical application.

There are three kinds of BI modules available, NR6601A, NR6610A and NR6610B. The binary
input module can respectively provide 25 or 32 binary inputs.

8
The rated voltage of binary input is optional: 24Vdc, 30Vdc, 48Vdc, 110Vdc,
125V, 220V, 110Vac or 220Vac (@50Hz), which must be specified when
placed order. It is necessary to check whether the rated voltage of binary
input module complies with site DC power supply rating before put this
device in service.

PCS-9611S Feeder Relay 8-19


Date: 2019-04-24
8 Hardware

Voltage

300

157.5

138.6

125

110

78.75

69.3

62.5
55 Operation

30.24
24 Operation uncertain
15.12
12
No operation
0 24V 48V 110V 125V 220V 250V

Figure 8.4-9 Voltage dependence for binary inputs

 NR6601A

Each BI module is with a 26-pin connector for 25 binary inputs which share one common negative
power input and can be configurable. The pickup voltages and dropout voltages of the binary
8 inputs are settable by the setting [U_Pickup_BI] and [U_Dropoff_BI], and the range is from
50%Un to 80%Un.

8-20 PCS-9611S Feeder Relay


Date: 2019-04-24
8 Hardware

01 BI_01 BI_02 02

03 BI_03 BI_04 04

05 BI_05 BI_06 06

07 BI_07 BI_08 08

09 BI_09 BI_10 10

11 BI_11 BI_12 12

13 BI_13 BI_14 14

15 BI_15 BI_16 16

17 BI_17 BI_18 18

19 BI_19 BI_20 20

21 BI_21 BI_22 22

23 BI_23 BI_24 24

25 BI_25 BI_COM 26

Figure 8.4-10 View of binary input module (NR6601A)

A 26-pin connector is fixed on the binary input module. The terminal definition of the connector is
described as below.

Table 8.4-4 Terminal definition and description of binary input module (NR6601A)

Pin No. Symbol Description


01 BI_01 The No.1 programmable binary input
02
03
BI_02
BI_03
The No.2 programmable binary input
The No.3 programmable binary input
8
04 BI_04 The No.4 programmable binary input
05 BI_05 The No.5 programmable binary input
06 BI_06 The No.6 programmable binary input
07 BI_07 The No.7 programmable binary input
08 BI_08 The No.8 programmable binary input
09 BI_09 The No.9 programmable binary input
10 BI_10 The No.10 programmable binary input
11 BI_11 The No.11 programmable binary input
12 BI_12 The No.12 programmable binary input
13 BI_13 The No.13 programmable binary input
14 BI_14 The No.14 programmable binary input
15 BI_15 The No.15 programmable binary input

PCS-9611S Feeder Relay 8-21


Date: 2019-04-24
8 Hardware

16 BI_16 The No.16 programmable binary input


17 BI_17 The No.17 programmable binary input
18 BI_18 The No.18 programmable binary input
19 BI_19 The No.19 programmable binary input
20 BI_20 The No.20 programmable binary input
21 BI_21 The No.21 programmable binary input
22 BI_22 The No.22 programmable binary input
23 BI_23 The No.23 programmable binary input
24 BI_24 The No.24 programmable binary input
25 BI_25 The No.25 programmable binary input
26 BI_COM The common negative connection of the BI_01 to BI_25.

 NR6610A & NR6610B

Each BI module is with two 18-pin connectors for 32 binary inputs. The first 16 binary inputs share
one common negative power input and the last 16 binary inputs share another common negative
power input. All binary inputs are configurable. The pickup voltages and dropout voltages of the
binary inputs are settable by the setting [U_Pickup_BI] and [U_Dropoff_BI], and the range is from
50%Un to 80%Un. The difference between NR6610A and NR6610B is that NR6610A equips
single AD sampling and NR6610B equips dual AD sampling.

01 BI_01 19 BI_17

02 BI_02 20 BI_18

03 BI_03 21 BI_19

04 BI_04 22 BI_20

05 BI_05 23 BI_21

06 BI_06 24 BI_22

07 BI_07 25 BI_23

08 BI_08 26 BI_24

8 09

10
BI_09

BI_10
27

28
BI_25

BI_26

11 BI_11 29 BI_27

12 BI_12 30 BI_28

13 BI_13 31 BI_29

14 BI_14 32 BI_30

15 BI_15 33 BI_31

16 BI_16 34 BI_32

17 BI_COM 35 BI_COM

18 BI_COM 36 BI_COM

Figure 8.4-11 View of binary input module (NR6610A/B)

The terminal definition of the connector is described as below.

8-22 PCS-9611S Feeder Relay


Date: 2019-04-24
8 Hardware

Table 8.4-5 Terminal definition and description of binary input module (NR6610A/B)

Pin No. Symbol Description


01 BI_01 The No.1 programmable binary input
02 BI_02 The No.2 programmable binary input
03 BI_03 The No.3 programmable binary input
04 BI_04 The No.4 programmable binary input
05 BI_05 The No.5 programmable binary input
06 BI_06 The No.6 programmable binary input
07 BI_07 The No.7 programmable binary input
08 BI_08 The No.8 programmable binary input
09 BI_09 The No.9 programmable binary input
18-pin
10 BI_10 The No.10 programmable binary input
11 BI_11 The No.11 programmable binary input
12 BI_12 The No.12 programmable binary input
13 BI_13 The No.13 programmable binary input
14 BI_14 The No.14 programmable binary input
15 BI_15 The No.15 programmable binary input
16 BI_16 The No.16 programmable binary input
17
BI_COM The common negative connection of the BI_01 to BI_16.
18
19 BI_17 The No.17 programmable binary input
20 BI_18 The No.18 programmable binary input
21 BI_19 The No.19 programmable binary input
22 BI_20 The No.20 programmable binary input
23 BI_21 The No.21 programmable binary input
24 BI_22 The No.22 programmable binary input
25 BI_23 The No.23 programmable binary input
26 BI_24 The No.24 programmable binary input

18-pin
27
28
BI_25
BI_26
The No.25 programmable binary input
The No.26 programmable binary input
8
29 BI_27 The No.27 programmable binary input
30 BI_28 The No.28 programmable binary input
31 BI_29 The No.29 programmable binary input
32 BI_30 The No.30 programmable binary input
33 BI_31 The No.31 programmable binary input
34 BI_32 The No.32 programmable binary input
35
BI_COM The common negative connection of the BI_17 to BI_32.
36

8.4.6 Binary Output Module (NR6651/NR6652/NR6660)


The binary output module consists of some necessary contact outputs, and the binary outputs are
used as tripping and closing (protection, auto-reclosing or remote control) outputs or signal
outputs. It can receive tripping commands or closing commands from the CPU module, and then

PCS-9611S Feeder Relay 8-23


Date: 2019-04-24
8 Hardware

executes these commands. It also can output some alarm signals from the CPU module.

The device can provide four types of binary output modules: NR6651A, NR6651B, NR6652A and
NR6660A.

 NR6651A

The NR6651A provides 13 normal open contacts (NOC) with pickup relay control.

A 26-pin connector is fixed on the binary input module.

The terminal definition of the connector is shown as below.

BO_01 01 02

BO_02 03 04

BO_03 05 06

BO_04 07 08

BO_05 09 10

BO_06 11 12

BO_07 13 14

BO_08 15 16

BO_09 17 18

BO_10 19 20

BO_11 21 22

BO_12 23 24

8 BO_13 25 26

Figure 8.4-12 View of binary output module NR6651A

 NR6651B

The NR6651B provides 11 normal open contacts (NOC, the first 11 contacts) and 2 normal close
contacts (NCC, the last 2 contacts). These binary outputs are controlled by pickup relay.

A 26-pin connector is fixed on the binary input module.

The terminal definition of the connector is shown in as below.

8-24 PCS-9611S Feeder Relay


Date: 2019-04-24
8 Hardware

BO_01 01 02

BO_02 03 04

BO_03 05 06

BO_04 07 08

BO_05 09 10

BO_06 11 12

BO_07 13 14

BO_08 15 16

BO_09 17 18

BO_10 19 20

BO_11 21 22

BO_12 23 24

BO_13 25 26

Figure 8.4-13 View of binary output module NR6651B

 NR6652A

The NR6652A provides 4 normal open contacts (NOC, the first 4 contacts) with heavy capacity for
controlling the circuit breaker directly, and provides 4 general normal open contacts (NOC, the last
4 contacts). These binary outputs are controlled by pickup relay.

A 26-pin connector is fixed on the binary input module.

The terminal definition of the connector is shown in as below. 8

PCS-9611S Feeder Relay 8-25


Date: 2019-04-24
8 Hardware

BO_01 01 02

03 04

BO_02 05 06

07 08

BO_03 09 10

11 12

BO_04 13 14

15 16

17 18

BO_05 19 20

BO_06 21 22

BO_07 23 24

BO_08 25 26

Figure 8.4-14 View of binary output module NR6652A

 NR6660A

The NR6660A provides 17 normally open contacts (NOC, the first 17 contacts) and 2 normally
close contacts (NCC, the 16th and the 17th contacts). These binary outputs are controlled by
pickup relay.

Two 18-pin connectors are fixed on the binary input module.

8 The terminal definition of the connector is shown in Figure 8.4-15.

8-26 PCS-9611S Feeder Relay


Date: 2019-04-24
8 Hardware

BO_01 01 02

BO_02 03 04

BO_03 05 06

BO_04 07 08

BO_05 09 10

BO_06 11 12

BO_07 13 14

BO_08 15 16

BO_09 17 18

BO_10 19 20

BO_11 21 22

BO_12 23 24

BO_13 25 26

BO_14 27 28

BO_15 29 30

BO_16 32
31
BO_16 33

BO_17 35
34
BO_17 36

Figure 8.4-15 View of binary output module (NR6660A)

Each binary output can be set as a specified tripping output contact or a


signal output contact through PCS-Studio according to practical
application.

PCS-9611S Feeder Relay 8-27


Date: 2019-04-24
8 Hardware

8-28 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

9 Settings

Table of Contents

9.1 Global Settings ................................................................................................ 9-1


9.1.1 System Settings.................................................................................................................... 9-1

9.1.2 Device Settings..................................................................................................................... 9-2

9.1.3 Communication Settings ...................................................................................................... 9-4

9.1.4 Disturbance Fault Recording Settings ............................................................................... 9-16

9.1.5 Label Settings ..................................................................................................................... 9-16

9.1.6 Clock Synchronization Settings .......................................................................................... 9-16

9.1.7 Supervision Settings ........................................................................................................... 9-18

9.1.8 OutMap Settings ................................................................................................................. 9-19

9.2 Protection Settings ........................................................................................ 9-20


9.2.1 Phase Overcurrent Protection Settings .............................................................................. 9-20

9.2.2 Earth Fault Overcurrent Protection Settings ...................................................................... 9-36

9.2.3 Another Group of Earth Fault Overcurrent Protection Settings ......................................... 9-51

9.2.4 Negative-sequence Overcurrent Protection Settings......................................................... 9-63

9.2.5 Sensitive Earth Fault Protection Settings ........................................................................... 9-69

9.2.6 RMS Overcurrent Protection Settings ................................................................................ 9-80

9.2.7 Phase Overvoltage Protection Settings ............................................................................. 9-81

9.2.8 Residual Overvoltage Protection Settings ......................................................................... 9-84

9.2.9 Negative-sequence Overvoltage Protection Settings ........................................................ 9-85


9
9.2.10 Positive-sequence Overvoltage Protection Settings ........................................................ 9-86

9.2.11 Phase Undervoltage Protection Settings ......................................................................... 9-86

9.2.12 Frequency Protection Settings ......................................................................................... 9-91

9.2.13 Reverse Power Protection Settings ................................................................................. 9-94

9.2.14 Cold Load Pickup Logic Settings ..................................................................................... 9-95

9.2.15 Undercurrent Settings ...................................................................................................... 9-98

9.2.16 Breaker Failure Protection Settings ................................................................................. 9-98

PCS-9611S Feeder Relay 9-a


Date: 2019-04-24
9 Settings

9.2.17 Switch-on-to-Fault ProtectionSettings .............................................................................. 9-99

9.2.18 Unbalance Current Protection Settings .......................................................................... 9-101

9.2.19 Unbalance Voltage Protection Settings .......................................................................... 9-101

9.2.20 Fault Location Settings ................................................................................................... 9-102

9.3 Measurement and Control Settings ........................................................... 9-102


9.3.1 Function Settings .............................................................................................................. 9-102

9.3.2 Synchronism Check Settings ........................................................................................... 9-103

9.3.3 Double Point Status Settings ........................................................................................... 9-105

9.3.4 Control Settings ................................................................................................................ 9-106

9.3.5 Interlocking Logic Settings ............................................................................................... 9-107

9.4 Logic Links ................................................................................................... 9-109


9.4.1 GOOSE Receiving Links .................................................................................................. 9-109

List of Tables

Table 9.1-1 System settings ....................................................................................................... 9-1

Table 9.1-2 Device settings......................................................................................................... 9-3

Table 9.1-3 General communication settings ........................................................................... 9-4

Table 9.1-4 IEC61850 communication settings ........................................................................ 9-7

Table 9.1-5 DNP communication settings ................................................................................. 9-8

Table 9.1-6 IEC103 communication settings .......................................................................... 9-14

Table 9.1-7 GOOSE communication settings ......................................................................... 9-15

Table 9.1-8 Disturbance fault recording settings ................................................................... 9-16

Table 9.1-9 Label settings ......................................................................................................... 9-16


9 Table 9.1-10 Clock synchronization settings ......................................................................... 9-16

Table 9.1-11 Supervision settings ............................................................................................ 9-19

Table 9.2-1 Settings of phase overcurrent protection ........................................................... 9-20

Table 9.2-2 Settings of earth fault overcurrent protection .................................................... 9-36

Table 9.2-3 Settings of another group of earth fault overcurrent protection...................... 9-51

Table 9.2-4 Settings of negative-sequence overcurrent protection..................................... 9-64

Table 9.2-5 Settings of sensitive earth fault protection ........................................................ 9-69

9-b PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Table 9.2-6 Settings of RMS overcurrent protection ............................................................. 9-80

Table 9.2-7 Settings of phase overvoltage protection ........................................................... 9-81

Table 9.2-8 Settings of residual overvoltage protection ....................................................... 9-84

Table 9.2-9 Settings of negative-sequence overvoltage protection .................................... 9-85

Table 9.2-10 Settings of positive-sequence overvoltage protection ................................... 9-86

Table 9.2-11 Settings of phase undervoltage protection ...................................................... 9-87

Table 9.2-12 Settings of overfrequency protection................................................................ 9-91

Table 9.2-13 Settings of reverse power protection ................................................................ 9-94

Table 9.2-14 Settings of cold load pickup logic ..................................................................... 9-95

Table 9.2-15 Settings of undercurrent protection .................................................................. 9-98

Table 9.2-16 Settings of breaker failure protection................................................................ 9-98

Table 9.2-17 Settings of SOTF protection ............................................................................... 9-99

Table 9.2-18 Settings of unbalance current protection ....................................................... 9-101

Table 9.2-19 Settings of unbalance voltage protection ....................................................... 9-101

Table 3.34-3 Settings of fault location ................................................................................... 9-102

Table 9.4-1 GOOSE receiving links ........................................................................................ 9-109

PCS-9611S Feeder Relay 9-c


Date: 2019-04-24
9 Settings

9-d PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

9.1 Global Settings

9.1.1 System Settings


 Access path:

MainMenu  Settings  Global Settings  System Settings

Table 9.1-1 System settings

Default
No. Settings Range Unit Step Remark
value
The number of active setting group,
several setting groups can be configured
1 Active_Grp 1~30 1 - 1
for protection settings, and only one is
active at a time.
Name of the protected primary
Max 20
2 PrimaryEquip_Name - - - equipment, such as feeder, transformer,
characters
etc.
3 Opt_SysFreq 50, 60 50Hz Hz The system frequency.
Rated primary value of protection phase
4 Prot.I1n 0~9999 1000 A 1
CT
Rated secondary value of protection
5 Prot.I2n 1, 5 1 A -
phase CT
Rated primary value of the No.1
6 Neu.I1n 0~9999 1000 A 1
zero-sequence CT
Rated secondary value of the No.1
7 Neu.I2n 1, 5 1 A -
zero-sequence CT
Rated primary value of the No.2
8 Neu2.I1n 0~9999 1000 A 1
zero-sequence CT
Rated secondary value of the No.2
9 Neu2.I2n 1, 5 1 A -
zero-sequence CT
Rated primary value of sensitive
10 SEF.I1n 0~9999 1000 A 1
zero-sequence CT
Rated secondary value of sensitive
11 SEF.I2n 1 1 A -
zero-sequence CT 9
12 60/50.I1n 0~9999 1000 A 1 Rated primary value of unbalance CT
13 60/50.I2n 1, 5 1 A - Rated secondary value of unbalance CT
14 Prot.U1n 0~1100 10 kV 0.001 Rated primary value of protection VT
15 Prot.U2n 1~200 100 V 0.001 Rated secondary value of protection VT
16 Syn.U1n 0~1100 10 kV 0.001 Rated primary value of synchro-check VT
Rated secondary value of synchro-check
17 Syn.U2n 1~200 100 V 0.001
VT
18 Delt.U1n 0~1100 10 kV 0.001 Rated primary value of zero-sequence VT
19 Delt.U2n 1~200 100 V 0.001 Rated secondary value of zero-sequence

PCS-9611S Feeder Relay 9-1


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Remark
value
VT

20 60/59.U1n 0~1100 10 kV 0.001 Rated primary value of the unbalance VT


Rated secondary value of the unbalance
21 60/59.U2n 1~200 100 V 0.001
VT
The logic setting determines that whether
the CT polarity of the three-phase
Disabled;
22 Prot.En_RevCT Disabled - - protection CT is reversed.
Enabled
Enabled: The CT polarity is reversed
Disabled: The CT polarity is not reversed
The logic setting determines that whether
the CT polarity of the No.1
Disabled;
23 Neu.En_RevCT Disabled - - zero-sequence CT is reversed.
Enabled
Enabled: The CT polarity is reversed
Disabled: The CT polarity is not reversed
The logic setting determines that whether
the CT polarity of the No.2
Disabled;
24 Neu2.En_RevCT Disabled - - zero-sequence CT is reversed.
Enabled
Enabled: The CT polarity is reversed
Disabled: The CT polarity is not reversed
The logic setting determines that whether
the CT polarity of the sensitive
Disabled;
25 SEF.En_RevCT Disabled - - zero-sequence CT is reversed.
Enabled
Enabled: The CT polarity is reversed
Disabled: The CT polarity is not reversed
The logic setting determines that whether
the CT polarity of the unbalance CT is
Disabled;
26 60/50.En_RevCT Disabled - - reversed.
Enabled
Enabled: The CT polarity is reversed
Disabled: The CT polarity is not reversed
ABC;
27 Opt_PhSeq ABC - - Phase sequence of system.
ACB

9 28 En_VT
Disabled;
Enabled
Enabled - - Logic setting to put VT into service

9.1.2 Device Settings


 Access path:

MainMenu  Settings  Global Settings  Device Settings

9-2 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Table 9.1-2 Device settings

Default
No. Settings Range Unit Step Remark
value
Logic setting to enable/disable the
Disabled debugging port. Used for debugging
1 En_DebugPort Enabled - -
Enabled tool connection, program download,
variable debugging, etc.
Disabled Logic setting to enable/disable the
2 En_TelnetPort Enabled - -
Enabled Telnet port.
Enabled: Connecting to the device via
Disabled the software Teldevice is supported
3 En_VirtualLCDPort Enabled - -
Enabled Disabled: Connecting to the device via
the software Teldevice is not supported
Enabled: printing data to the software
Disabled Netpts is supported
4 En_NetPrintPort Enabled - -
Enabled Disabled: printing data to the software
Netpts is not supported
Disabled Override control password via local
5 En_NoCtrlPwd Enabled - -
Enabled LCD
6 Ctrl_Password 000~999 111 - - The control password via local LCD.
This setting is used to set the voltage
7 Un_BinaryInput 24~250 220 V -
level of the binary input module.
DC
Power supply mode of binary input
8 Opt_Pwr_BI AC50Hz DC - -
module
AC60Hz
This setting is used to set pickup
9 U_Pickup_BI 50%Un~80%Un 63 % 0.1
voltage of the binary input module.
This setting is used to set drop-off
10 U_Dropoff_BI 50%Un~80%Un 55 % 0.1
voltage of the binary input module.
Monitoring window of binary input jitter
11 Mon_Window_Jitter 0.000~500.000 1 0.001 s
processing
Times threshold to block binary input
12 Num_Blk_Jitter 2~500000 10 1 -
status change due to jitter
Blocking window of binary input status 9
13 Blk_Window_Jitter 0.000~500.000 1 0.001 s
change due to jitter
Times threshold to initiate immediately
14 Num_Reblk_Jitter 1~500000 10 1 - another blocking window of binary input
status change due to continuous jitter
The logic setting to enable/disable the
Disabled
15 En_Jitter_Blk Disabled - - jitter processing function in case of
Enabled
binary input voltage variation

PCS-9611S Feeder Relay 9-3


Date: 2019-04-24
9 Settings

9.1.3 Communication Settings


9.1.3.1 General Communication Settings

 Access path:

MainMenu  Settings  Global Settings  Comm Settings  General Comm Settings

Table 9.1-3 General communication settings

No. Settings Range Default value Unit Step Remark


0.0.0.0~
1 IP_LAN1 198.120.0.100 - - IP address of Ethernet port A
255.255.255.255
0.0.0.0~ Subnet mask of Ethernet port
2 Mask_LAN1 255.255.0.0 - -
255.255.255.255 A
0.0.0.0~
3 IP_LAN2 198.121.0.100 - - IP address of Ethernet port B
255.255.255.255
0.0.0.0~ Subnet mask of Ethernet port
4 Mask_LAN2 255.255.0.0 - -
255.255.255.255 B
Disabled Put Ethernet port B into
5 En_LAN2 Enabled - -
Enabled service
0.0.0.0~
6 IP_LAN3 198.122.0.100 - - IP address of Ethernet port C
255.255.255.255
0.0.0.0~ Subnet mask of Ethernet port
7 Mask_LAN3 255.255.0.0 - -
255.255.255.255 C
Disabled Put Ethernet port C into
8 En_LAN3 Disabled - -
Enabled service
0.0.0.0~
9 IP_LAN4 198.123.0.100 - - IP address of Ethernet port D
255.255.255.255
0.0.0.0~ Subnet mask of Ethernet port
10 Mask_LAN4 255.255.0.0 - -
255.255.255.255 D
Disabled Put Ethernet port D into
11 En_LAN4 Disabled - -
Enabled service
0.0.0.0~ IP address of the gateway
12 Gateway 0.0.0.0 - -
255.255.255.255 (router)
4800
9 9600
19200
13 Baud_Printer 19200 bps - Baud rate of printer port
38400
57600
115200
Disabled Enable/disable automatic
14 En_AutoPrint Disabled - -
Enabled printing function
Communication protocol of
IEC103
15 Protocol_RS485-1 IEC103 - - rear RS-485 serial port 1.
Modbus
IEC103: IEC60870-5-103

9-4 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

No. Settings Range Default value Unit Step Remark


protocol
Modbus: Modbus protocol
Communication protocol of
rear RS-485 serial port 2.
IEC103
16 Protocol_RS485-2 IEC103 - - IEC103: IEC60870-5-103
Modbus
protocol
Modbus: Modbus protocol
4800
9600
19200 Baud rate of rear RS-485
17 Baud_RS485-1 19200 bps -
38400 serial port 1.
57600
115200
4800
9600
19200 Baud rate of rear RS-485
18 Baud_RS485-2 19200 bps -
38400 serial port 2.
57600
115200
Communication address
between the device and the
19 Addr_RS485-1 0~255 100 - 1
SCADA or RTU via RS-485
serial port 1.
Communication address
between the device and the
20 Addr_RS485-2 0~255 100 - 1
SCADA or RTU via RS-485
serial port 2.
The setting is used to set the
21 Cfg_NetPorts_Bond 0~255 0 - - Ethernet ports that are used
as hot standby each other.
Normal;
The network method of the
1-2:Normal,3-4:HSR;
22 B01.Opt_NetMode Normal - - CPU module located in slot
1-2:Normal,3-4:PRP;
1-2:Normal,3-4:RSTP
No.1 9
1. [Cfg_NetPorts_Bond]

The setting is used to configure dual-networks switching, and it means that no dual-networks
switching is created when the setting is set as “0”. The device support a bond between any two
Ethernet ports, and the bond among three or above Ethernet ports is impermissible.

The devices communicate with SAS by station level network. In order to ensure reliable
communication, dual networks (i.e., network 1 and network 2) are adopted. Another special
communication mode based on dual networks is that Ethernet port 1 and Ethernet port 2 of the

PCS-9611S Feeder Relay 9-5


Date: 2019-04-24
9 Settings

device own the same IP address and MAC address, and network 1 and network 2 are used as hot
standby each other. When both network 1 and network 2 are normal, any of them is used to
communicate between the device and SAS. The device will automatically switch to the other
healthy network when one network is abnormal, which will not affect normal communication.

Taking a CPU module with four Ethernet ports as an example, each bit is corresponding with an
Ethernet port, i.e., Bit0, Bit1, Bit2 and Bit3 are corresponding with Ethernet port 1, Ethernet port 2,
Ethernet port 3 and Ethernet port 4 respectively. If a bond between Ethernet port 1 and Ethernet 2
is created, the setting [Cfg_NetPorts_Bond] is set as “3”. The specific setting is as below.

Bonding Bonding Bonding

Ethernet port 1 Ethernet port 2 Ethernet port 1 Ethernet port 3 Ethernet port 1 Ethernet port 4

Setting Setting Setting


Bit3 Bit2 Bit1 Bit0 Bit3 Bit2 Bit1 Bit0 Bit3 Bit2 Bit1 Bit0
Value Value Value

0 0 1 1 3 0 1 0 1 5 1 0 0 1 9

Bonding Bonding Bonding

Ethernet port 2 Ethernet port 3 Ethernet port 2 Ethernet port 4 Ethernet port 3 Ethernet port 4

Setting Setting Setting


Bit3 Bit2 Bit1 Bit0 Bit3 Bit2 Bit1 Bit0 Bit3 Bit2 Bit1 Bit0
Value Value Value

0 1 1 0 6 1 0 1 0 10 1 1 0 0 12

Ethernet port 1: Bit0, Ethernet port 2: Bit1, Ethernet port 3: Bit2, Ethernet port 4: Bit3

The switching logic is as below.

 After the device is powered on, network 1 is selected when the link status of both network 1
and network 2 are normal.

 When the link status of network 1 is abnormal, network 2 is selected if network 2 is normal.

9  When the link status of network 1 is abnormal, network 1 is kept to work if network 2 is also
abnormal.

 When network 2 is working, network 2 is kept to work even if network 1 has been restored to
normal. The device will be switched to network 1 only if network 2 is abnormal.

9.1.3.2 IEC61850 Communication Settings

 Access path:

MainMenu  Settings  Global Settings  Comm Settings  IEC61850 Settings

9-6 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Table 9.1-4 IEC61850 communication settings

Default
No. Settings Range Unit Step Remark
value
The identification of the IED in
IEC 61850 protocol.
It cannot be an empty string and
shall be unique within an SCL
file. IEDNAME should be less
than 20 characters comprising
1 IEDNAME - TEMPLATE - -
letters or digits or underline ( _ ),
and it is case sensitive.
If this setting is modified, the IED
name in ".cid" file will be
changed simultaneously and
vice versa.
It is used to set the change
detection threshold for suddenly
sending measurement value to
2 Threshold_Measmt_Net 0~100.00 1 % 0.01
the SCADA via the device's
Ethernet port using IEC 61850
protocol
Measurement values zero drift
3 ThAbs_Measmt 0.001~0.5 0.02 - 0.001
suppression threshold
If users need to support the
Disabled quality change upload function,
4 En_Send_MMS_Qual_Chg Disabled - -
Enabled this parameter should be set as
“1”
It is used to select the network
mode of MMS network for the
communication with SCADA
SingleNet
0: Single network
5 Opt_DualNetMode_MMS HotStdby SingleNet - -
1: Hot standby mode (always
ColdStdby
two ports in service)
2: Cold standby mode (only one 9
port in service)
The logic setting to
Disabled
6 En_IEC62351_TCP_Port Disabled - - enable/disable TCP port in
Enabled
IEC62351 protocol
The logic setting to
Disabled
7 En_IEC61850_TCP_Port Enabled - - enable/disable TCP port in
Enabled
IEC61850 protocol

9.1.3.3 DNP Communication Settings

 Access path:

PCS-9611S Feeder Relay 9-7


Date: 2019-04-24
9 Settings

MainMenu  Settings  Global Settings  Comm Settings  DNP Settings

Table 9.1-5 DNP communication settings

Default
No. Settings Range Unit Step Remark
value
The logic setting to
Disabled
1 En_TCP1_DNP Disabled - - enable/disable the No.1
Enabled
network DNP client
The local address of the
2 Addr_Slave_TCP1_DNP 0~65519 2 - 1
No.1 network DNP client
The master address of the
3 Addr_Master_TCP1_DNP 0~65519 1 - 1
No.1 network DNP client
The IP address of the
0.0.0.0~
4 IP_Master_TCP1_DNP 0.0.0.0 - - master of the No.1 network
255.255.255.255
DNP client
The communication map
5 Opt_Map_TCP1_DNP 0~4 0 - 1 of the No.1 network DNP
client
The timeout of the
6 t_AppLayer_TCP1_DNP 1~5 3 s 1 application layer of the
No.1 network DNP client
The heartbeat time interval
7 t_KeepAlive_TCP1_DNP 0~7200 120 s 1 of the No.1 network DNP
client
The logic setting to
enable/disable the
Disabled
8 En_UR_TCP1_DNP Disabled - - unsolicited message
Enabled
function of the No.1
network DNP client
The online retransmission
number for sending the
9 Num_URRetry_TCP1_DNP 2~10 3 - 1
unsolicited message of the
No.1 network DNP client

9 The offline retransmission


interval for sending the
10 t_UROfflRetry_TCP1_DNP 1~5000 60 s 1
unsolicited message of the
No.1 network DNP client
The default class level of
11 Class_BI_TCP1_DNP 0~3 1 - 1 the “Binary Input” of the
No.1 network DNP client
The default class level of
12 Class_AI_TCP1_DNP 0~3 2 - 1 the “Analog Input” of the
No.1 network DNP client
13 t_Select_TCP1_DNP 0~240 30 s 1 The selection timeout of

9-8 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Remark
value
the remote control and
remote adjustment of No.1
network DNP client
The time interval of the
time synchronization
14 t_TimeSynIntvl_TCP1_DNP 0~3600 180 s 1
function of the No.1
network DNP client
The “OBJ1” default
1-BISingleBit
15 Obj01DefltVar_TCP1_DNP 1-BISingleBit - - variation of the No.1
2-BIWithStatus
network DNP client
1-BIChWoutT The “OBJ2” default
2-BIChWithA
16 Obj02DefltVar_TCP1_DNP 2-BIChWithAbsTime - - variation of the No.1
bsTime
3-BIChWithRelTime network DNP client
1-AI32Int
2-AI16Int The “OBJ30” default
3-AI32IntWo
17 Obj30DefltVar_TCP1_DNP 3-AI32IntWoutF - - variation of the No.1
utF
4-AI16IntWoutF network DNP client
5-AI32Flt
1-AI32IntEvWoutT The “OBJ32” default
1-AI32IntEv
18 Obj32DefltVar_TCP1_DNP 2-AI16IntEvWoutT - - variation of the No.1
WoutT
5-AI32FltEvWoutT network DNP client
1-AO32Int The “OBJ40” default
19 Obj40DefltVar_TCP1_DNP 2-AO16Int 1-AO32Int - - variation of the No.1
3-AO32Flt network DNP client
The logic setting to
Disabled
20 En_TCP2_DNP Disabled - - enable/disable the No.2
Enabled
network DNP client
The local address of the
21 Addr_Slave_TCP2_DNP 0~65519 2 - 1
No.2 network DNP client
The master address of the
22 Addr_Master_TCP2_DNP 0~65519 1 - 1
No.2 network DNP client

23 IP_Master_TCP2_DNP
0.0.0.0~
0.0.0.0 - -
The IP address of the
master of the No.2 network
9
255.255.255.255
DNP client
The communication map
24 Opt_Map_TCP2_DNP 0~4 0 - 1 of the No.2 network DNP
client
The timeout of the
25 t_AppLayer_TCP2_DNP 1~5 3 s 1 application layer of the
No.2 network DNP client
The heartbeat time interval
26 t_KeepAlive_TCP2_DNP 0~7200 120 s 1
of the No.2 network DNP

PCS-9611S Feeder Relay 9-9


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Remark
value
client
The logic setting to
enable/disable the
Disabled
27 En_UR_TCP2_DNP Disabled - - unsolicited message
Enabled
function of the No.2
network DNP client
The online retransmission
number for sending the
28 Num_URRetry_TCP2_DNP 2~10 3 - 1
unsolicited message of the
No.2 network DNP client
The offline retransmission
interval for sending the
29 t_UROfflRetry_TCP2_DNP 1~5000 60 s 1
unsolicited message of the
No.2 network DNP client
The default class level of
30 Class_BI_TCP2_DNP 0~3 1 - 1 the “Binary Input” of the
No.2 network DNP client
The default class level of
31 Class_AI_TCP2_DNP 0~3 2 - 1 the “Analog Input” of the
No.2 network DNP client
The selection timeout of
the remote control and
32 t_Select_TCP2_DNP 0~240 30 s 1
remote adjustment of No.2
network DNP client
The time interval of the
time synchronization
33 t_TimeSynIntvl_TCP2_DNP 0~3600 180 s 1
function of the No.2
network DNP client
The “OBJ1” default
1-BISingleBit
34 Obj01DefltVar_TCP2_DNP 1-BISingleBit - - variation of the No.2
2-BIWithStatus
network DNP client

9 35 Obj02DefltVar_TCP2_DNP
1-BIChWoutT
2-BIChWithAbsTime
2-BIChWithA
- -
The
variation
“OBJ2”
of the
default
No.2
bsTime
3-BIChWithRelTime network DNP client
1-AI32Int
2-AI16Int The “OBJ30” default
3-AI32IntWo
36 Obj30DefltVar_TCP2_DNP 3-AI32IntWoutF - - variation of the No.2
utF
4-AI16IntWoutF network DNP client
5-AI32Flt
1-AI32IntEvWoutT The “OBJ32” default
1-AI32IntEv
37 Obj32DefltVar_TCP2_DNP 2-AI16IntEvWoutT - - variation of the No.2
WoutT
5-AI32FltEvWoutT network DNP client

9-10 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Remark
value
1-AO32Int The “OBJ40” default
38 Obj40DefltVar_TCP2_DNP 2-AO16Int 1-AO32Int - - variation of the No.2
3-AO32Flt network DNP client
The logic setting to
Disabled
39 En_TCP3_DNP Disabled - - enable/disable the No.3
Enabled
network DNP client
The local address of the
40 Addr_Slave_TCP3_DNP 0~65519 2 - 1
No.3 network DNP client
The master address of the
41 Addr_Master_TCP3_DNP 0~65519 1 - 1
No.3 network DNP client
The IP address of the
0.0.0.0~
42 IP_Master_TCP3_DNP 0.0.0.0 - - master of the No.3 network
255.255.255.255
DNP client
The communication map
43 Opt_Map_TCP3_DNP 0~4 0 - 1 of the No.3 network DNP
client
The timeout of the
44 t_AppLayer_TCP3_DNP 1~5 3 s 1 application layer of the
No.3 network DNP client
The heartbeat time interval
45 t_KeepAlive_TCP3_DNP 0~7200 120 s 1 of the No.3 network DNP
client
The logic setting to
enable/disable the
Disabled
46 En_UR_TCP3_DNP Disabled - - unsolicited message
Enabled
function of the No.3
network DNP client
The online retransmission
number for sending the
47 Num_URRetry_TCP3_DNP 2~10 3 - 1
unsolicited message of the
No.3 network DNP client
The offline retransmission
interval for sending the
9
48 t_UROfflRetry_TCP3_DNP 1~5000 60 s 1
unsolicited message of the
No.3 network DNP client
The default class level of
49 Class_BI_TCP3_DNP 0~3 1 - 1 the “Binary Input” of the
No.3 network DNP client
The default class level of
50 Class_AI_TCP3_DNP 0~3 2 - 1 the “Analog Input” of the
No.3 network DNP client
51 t_Select_TCP3_DNP 0~240 30 s 1 The selection timeout of

PCS-9611S Feeder Relay 9-11


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Remark
value
the remote control and
remote adjustment of No.3
network DNP client
The time interval of the
time synchronization
52 t_TimeSynIntvl_TCP3_DNP 0~3600 180 s 1
function of the No.3
network DNP client
The “OBJ1” default
1-BISingleBit
53 Obj01DefltVar_TCP3_DNP 1-BISingleBit - - variation of the No.3
2-BIWithStatus
network DNP client
1-BIChWoutT The “OBJ2” default
2-BIChWithA
54 Obj02DefltVar_TCP3_DNP 2-BIChWithAbsTime - - variation of the No.3
bsTime
3-BIChWithRelTime network DNP client
1-AI32Int
2-AI16Int The “OBJ30” default
3-AI32IntWo
55 Obj30DefltVar_TCP3_DNP 3-AI32IntWoutF - - variation of the No.3
utF
4-AI16IntWoutF network DNP client
5-AI32Flt
1-AI32IntEvWoutT The “OBJ32” default
1-AI32IntEv
56 Obj32DefltVar_TCP3_DNP 2-AI16IntEvWoutT - - variation of the No.3
WoutT
5-AI32FltEvWoutT network DNP client
1-AO32Int The “OBJ40” default
57 Obj40DefltVar_TCP3_DNP 2-AO16Int 1-AO32Int - - variation of the No.3
3-AO32Flt network DNP client
The logic setting to
Disabled
58 En_TCP4_DNP Disabled - - enable/disable the No.4
Enabled
network DNP client
The local address of the
59 Addr_Slave_TCP4_DNP 0~65519 2 - 1
No.4 network DNP client
The master address of the
60 Addr_Master_TCP4_DNP 0~65519 1 - 1
No.4 network DNP client

9 61 IP_Master_TCP4_DNP
0.0.0.0~
0.0.0.0 - -
The IP address of the
master of the No.4 network
255.255.255.255
DNP client
The communication map
62 Opt_Map_TCP4_DNP 0~4 0 - 1 of the No.4 network DNP
client
The timeout of the
63 t_AppLayer_TCP4_DNP 1~5 3 s 1 application layer of the
No.4 network DNP client
The heartbeat time interval
64 t_KeepAlive_TCP4_DNP 0~7200 120 s 1
of the No.4 network DNP

9-12 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Remark
value
client
The logic setting to
enable/disable the
Disabled
65 En_UR_TCP4_DNP Disabled - - unsolicited message
Enabled
function of the No.4
network DNP client
The online retransmission
number for sending the
66 Num_URRetry_TCP4_DNP 2~10 3 - 1
unsolicited message of the
No.4 network DNP client
The offline retransmission
interval for sending the
67 t_UROfflRetry_TCP4_DNP 1~5000 60 s 1
unsolicited message of the
No.4 network DNP client
The default class level of
68 Class_BI_TCP4_DNP 0~3 1 - 1 the “Binary Input” of the
No.4 network DNP client
The default class level of
69 Class_AI_TCP4_DNP 0~3 2 - 1 the “Analog Input” of the
No.4 network DNP client
The selection timeout of
the remote control and
70 t_Select_TCP4_DNP 0~240 30 s 1
remote adjustment of No.4
network DNP client
The time interval of the
time synchronization
71 t_TimeSynIntvl_TCP4_DNP 0~3600 180 s 1
function of the No.4
network DNP client
The “OBJ1” default
1-BISingleBit
72 Obj01DefltVar_TCP4_DNP 1-BISingleBit - - variation of the No.4
2-BIWithStatus
network DNP client

73 Obj02DefltVar_TCP4_DNP
1-BIChWoutT
2-BIChWithAbsTime
2-BIChWithA
- -
The
variation
“OBJ2”
of the
default
No.4
9
bsTime
3-BIChWithRelTime network DNP client
1-AI32Int
2-AI16Int The “OBJ30” default
3-AI32IntWo
74 Obj30DefltVar_TCP4_DNP 3-AI32IntWoutF - - variation of the No.4
utF
4-AI16IntWoutF network DNP client
5-AI32Flt
1-AI32IntEvWoutT The “OBJ32” default
1-AI32IntEv
75 Obj32DefltVar_TCP4_DNP 2-AI16IntEvWoutT - - variation of the No.4
WoutT
5-AI32FltEvWoutT network DNP client

PCS-9611S Feeder Relay 9-13


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Remark
value
1-AO32Int The “OBJ40” default
76 Obj40DefltVar_TCP4_DNP 2-AO16Int 1-AO32Int - - variation of the No.4
3-AO32Flt network DNP client

9.1.3.4 IEC103 Communication Settings

 Access path:

MainMenu  Settings  Global Settings  Comm Settings  IEC103 Settings

Table 9.1-6 IEC103 communication settings

No. Settings Range Default value Unit Step Remark


Current
The language of group caption of
Language;
IEC103 protocol
Fixed Current
1 Opt_Caption_103 - - It is recommended to be set as “1” if the
Chinese; Language
device communicate with SCADA in
Fixed
Chinese.
English
This setting is only used for IEC 103
protocol. If NR network IEC103 protocol
is used, the setting must be set as “1”.
Disabled
2 En_Broadcast_LAN1 Disabled - - 0: the device does not send UDP
Enabled
messages through Ethernet port A;
1: the device sends UDP messages
through Ethernet port A.
This setting is only used for IEC 103
protocol. If NR network IEC103 protocol
is used, the setting must be set as “1”.
Disabled
3 En_Broadcast_LAN2 Disabled - - 0: the device does not send UDP
Enabled
messages through Ethernet port B;
1: the device sends UDP messages
through Ethernet port B.
This setting is only used for IEC 103
9 protocol. If NR network IEC103 protocol
is used, the setting must be set as “1”.
Disabled
4 En_Broadcast_LAN3 Disabled - - 0: the device does not send UDP
Enabled
messages through Ethernet port C;
1: the device sends UDP messages
through Ethernet port C.
This setting is only used for IEC 103
Disabled protocol. If NR network IEC103 protocol
5 En_Broadcast_LAN4 Disabled - -
Enabled is used, the setting must be set as “1”.
0: the device does not send UDP

9-14 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

No. Settings Range Default value Unit Step Remark


messages through Ethernet port D;
1: the device sends UDP messages
through Ethernet port D.
This setting is used to set the data
format for sending waveform list using
IEC 60870-5-103.
DisturbData;
6 Fmt_Wave_Sent File - - DisturbData: Send the waveform list in
File
ASDU23 mode;
File: Send the waveform list in ASDU222
mode.
It is used to set the change detection
threshold for suddenly sending
7 Threshold_Measmt_Net 0~100.00 1.00 % 0.01 measurement value to the SCADA via
the device's Ethernet port using IEC
60870-5-103
It is used to set the time period for
sending the measurement value to
8 Period_Measmt_Net 0~65535 30 s 1
SCADA via the device's Ethernet port
using IEC 60870-5-103 or IEC 61850.

9.1.3.5 GOOSE Communication Settings

 Access path:

MainMenu  Settings  Global Settings  Comm Settings  GOOSE Settings

Table 9.1-7 GOOSE communication settings

No. Settings Range Default value Unit Step Remark


The GOOSE receiving mode.
DoubleFrameChk: double frame
DoubleFrameChk
1 Opt_RecvMode_GOOSE SingleFrameChk - - check mode;
SingleFrameChk
SingleFrameChk: single frame
check mode;
Disabled Logic setting to enable/disable
2 En_NetA_GOOSE
Enabled
Enabled - -
GOOSE net A 9
Disabled Logic setting to enable/disable
3 En_DualNet_GOOSE Disabled - -
Enabled GOOSE double-net mode
Logic setting to enable/disable
GOOSE complex-net mode.
GOOSE complex-net mode: for
Disabled
4 En_ComplexNet_GOOSE Disabled - - the GOOSE receiving, some
Enabled
control blocks adopt dual-net
receiving and other control blocks
adopt single-net receiving.

PCS-9611S Feeder Relay 9-15


Date: 2019-04-24
9 Settings

9.1.4 Disturbance Fault Recording Settings


 Access path:

MainMenu  Settings  Global Settings  DFR Settings

Table 9.1-8 Disturbance fault recording settings

Default
No. Settings Range Unit Step Remark
value
Waveform recorded duration before the
1 RecDur_PreTrigDFR 0~1 0.1 s 0.001
trigger element operating
Waveform recorded duration after the
2 RecDur_PostFault 0~10 5 s 0.001
fault happens
The maximum waveform recorded
3 MaxRecDur_PostTrigDFR 0~10 10 s 0.001 duration after the trigger element
operating

9.1.5 Label Settings


 Access path:

MainMenu  Settings  Global Settings  Label Settings

Table 9.1-9 Label settings

No. Symbol Default value Description

GOOSE_Link0 Label setting of GOOSE communication link 000 of the


1 Bx.Name_000_GCommLink
module located in slot No.x.

2 …… …… ……

GOOSE_Link127 Label setting of GOOSE communication link 127 of the


3 Bx.Name_127_GCommLink
module located in slot No.x.

These settings are used to definite the label of each GOOSE communication link. The label of
each GOOSE communication link will influence the displayed contents of all reports, settings and
metering that related with each GOOSE communication link.

9.1.6 Clock Synchronization Settings


9  Access path:

MainMenu  Settings  Global Settings  ClockSyn Settings

Table 9.1-10 Clock synchronization settings

No Default
Settings Range Unit Step Remark
. value
Conventional Select the time
1 Opt_TimeSyn SAS NoTimeSyn - - synchronization mode of the
NoTimeSyn device.

9-16 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

No Default
Settings Range Unit Step Remark
. value
The local time zone also
2 OffsetHour_UTC -12~12 8 - 1 refered to as the hour offset
hour from UTC .
The offset minute of local time
3 OffsetMinute_UTC 0~60 0 - 1
from UTC.
The IP address of the server
0.0.0.0~ when SNTP time
4 IP_Server_SNTP 0.0.0.0 - -
255.255.255.255 synchronization mode is
selected
The subnet mask of the server
0.0.0.0~ when SNTP time
5 Mask_Server_SNTP 0.0.0.0 - -
0.0.255.255 synchronization mode is
selected
The IP address of the standby
IP_StandbyServer_S 0.0.0.0~ server when SNTP time
6 0.0.0.0 - -
NTP 255.255.255.255 synchronization mode is
selected
The logic setting is used to
Disabled
7 DST.En Disabled - - enable or disable Daylight
Enabled
Saving Time (DST)
It is used to set the minute
offset of DST, i.e. the
8 DST.OffsetMinute 0~255 60 - 1
difference between DST time
and local time
Jan, Feb, Mar,
DST.MonthInYear_St Apr, May, Jun, It is used to set the start month
9 Mar - -
art Jul, Aug, Sep, of DST.
Oct, Nov, Dec
DST.WeekInMonth_S 1st, 2nd, 3nd, It is used to set the start week
10 1st - -
tart 4th, Last of DST.
Sunday, Monday,

11
DST.DayInWeek_Star
Tuesday,
Wednesday, Sunday - -
It is used to set the start day of 9
t DST.
Thursday, Friday,
Saturday
It is used to set the start hour
12 DST.HourInDay_Start 0~23 3 - 1
of DST.
Jan, Feb, Mar,
DST.MonthInYear_En Apr, May, Jun, It is used to set the end month
13 Oct - -
d Jul, Aug, Sep, of DST.
Oct, Nov, Dec
14 DST.WeekInMonth_E 1st, 2nd, 3nd, 1st - - It is used to set the end week

PCS-9611S Feeder Relay 9-17


Date: 2019-04-24
9 Settings

No Default
Settings Range Unit Step Remark
. value
nd 4th, Last of DST.
Sunday, Monday,
Tuesday,
It is used to set the end day of
15 DST.DayInWeek_End Wednesday, Sunday - -
DST.
Thursday, Friday,
Saturday
It is used to set the end hour of
16 DST.HourInDay_End 0~23 9 - 1
DST.

1. [Opt_TimeSyn]

There are three selections for clock synchronization of the device, each selection includes
different time clock synchronization signals shown in following table.

Item Description
IRIG-B (RS-485): IRIG-B via RS-485 differential level.
PPS (RS-485): Pulse per second (PPS) via RS-485 differential level.
IRIG-B (Fiber): IRIG-B via optical-fibre interface.
Conventional PPS (Fiber): Pulse per second (PPS) via optical-fibre interface.
IEEE1588 (Fiber): Clock message via IEEE1588.
PPM (DIN): Pulse per minute (PPM) via the binary input [BI_TimeSyn].
PPS (DIN): Pulse per second (PPS) via the binary input [BI_TimeSyn].
SNTP(PTP): Unicast (point to point) SNTP mode via Ethernet network.
SNTP(BC): Broadcast SNTP mode via Ethernet network.
SAS
IEC103: Clock messages through IEC103 protocol.
MODBUS: Clock messages through MODBUS protocol.
If time synchronization function is not needed for the device, this option can be
NoTimeSyn
selected.

1) When “SAS” is selected, if there is no conventional clock synchronization signal, the device
will not send the alarm signal [Alm_TimeSyn]. When “Conventional” mode is selected, if there
is no conventional clock synchronization signal, “SAS” mode will be enabled automatically
with the alarm signal [Alm_TimeSyn] being issued simultaneously.

9 2) When “NoTimeSyn” mode is selected, the device will not send time synchronization alarm
signal.

The clock message via IEC103 protocol is INVALID when the device
receives the IRIG-B signal through RC-485 port.

9.1.7 Supervision Settings


 Access path:

9-18 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

MainMenu  Settings  Global Settings  Superv Settings

Table 9.1-11 Supervision settings

Default
No. Settings Range Unit Step Remark
value
The calculated residual current
1 CTS.3I0_Set 0~200 0.1 A 0.001 setting of CT circuit supervision
function.
The calculated residual voltage
2 CTS.3U0_Set 0~200 30 V 0.001 setting of CT circuit supervision
function.
Delay pick-up time setting for CT
3 CTS.t_DPU 0~100 10 s 0.001
circuit failure
Delay drop-off time setting for CT
4 CTS.t_DPO 0~100 10 s 0.001
circuit failure
Disabled Enabling/disabling CT circuit
5 CTS.En Disabled - -
Enabled supervision function.
Positive-sequence voltage setting
6 VTS.U1_Set 0~100 30 V 0.01
of VT circuit supervision function.
Residual voltage setting of VT
7 VTS.3U0_Set 0~100 8 V 0.01
circuit supervision function.
Negative-sequence voltage
8 VTS.U2_Set 0~100 8 V 0.01 setting of VT circuit supervision
function.
Delay pick-up time setting for VT
9 VTS.t_DPU 0~30 1.25 s 0.001
circuit failure
Delay drop-off time setting for VT
10 VTS.t_DDO 0~30 10 s 0.001
circuit failure
Disabled Enabling/disabling VT circuit
11 VTS.En Disabled - -
Enabled supervision function.

9.1.8 OutMap Settings


 Access path:

MainMenu  Settings  Global Settings  OutMap Settings 9


No. Name Range Unit Default Description
OutMapxxx 00000000~ Tripping logic setting of programmable trip
1 - 0
(xxx=001, 002…120) FFFF FFFF output map xxx
t_Dwell_xxx_OutMap The pulse width setting of programmable
2 0.000~0.500 s 0.060
(xxx=001, 002…032) trip output map xxx

PCS-9611S Feeder Relay 9-19


Date: 2019-04-24
9 Settings

9.2 Protection Settings


9.2.1 Phase Overcurrent Protection Settings
 Access path:

MainMenu  Settings  Protection Settings  OC Settings

Table 9.2-1 Settings of phase overcurrent protection

Default
No. Settings Range Unit Step Description
value
The low voltage blocking setting
1 50/51P.VCE.Upp 10~100 70 V 0.001 of the voltage control element of
phase overcurrent protection
The negative-sequence voltage
blocking setting of the voltage
2 50/51P.VCE.U2 2~57 8 V 0.001
control element of phase
overcurrent protection
The residual voltage setting (set
according to 3U0) of voltage
3 50/51P.VCE.3U0 2~57 8 V 0.001
control element of phase
overcurrent protection
The relay characteristic angle of
4 50/51P.DIR.RCA -180~179 45 deg 1 the direction control element of
phase overcurrent protection
The relay negative-sequence
50/51P.DIR.RCA_N characteristic angle of the
5 -180~179 45 deg 1
egOC direction control element of
phase overcurrent protection
The minimum boundary of the
50/51P.DIR.phi_Min
6 10~90 90 deg 1 forward direction element of
_Fwd
phase overcurrent protection
The maximum boundary of the
50/51P.DIR.phi_Ma
7 10~90 90 deg 1 forward direction element of
x_Fwd
phase overcurrent protection
9 The minimum boundary of the
50/51P.DIR.phi_Min
8 10~90 90 deg 1 reverse direction element of
_Rev
phase overcurrent protection
The maximum boundary of the
50/51P.DIR.phi_Ma
9 10~90 90 deg 1 reverse direction element of
x_Rev
phase overcurrent protection

9-20 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The voltage polarization mode
for direction control element of
phase overcurrent protection
Upp; Upp: phase-to-phase voltage
50/51P.DIR.Opt_Pol
10 Up; Upp - - polarized
arizedVolt
U1 Up: phase-to-ground voltage
polarized
U1: positive-sequence voltage
polarized
The minimum operating current
setting for the direction control
11 50/51P.DIR.I_Min (0.05~1)In 0.05 - 0.001
element of phase overcurrent
protection
The minimum operating voltage
setting for the direction control
12 50/51P.DIR.U_Min 1~10 4 V 0.001
element of phase overcurrent
protection
Logic setting to determine the
behavior of phase overcurrent
protection when VT circuit
supervision function is enabled
and VT circuit failure happens.
Disabled; Disabled: phase overcurrent
13 50/51P.En_VTS_Blk Disabled - -
Enabled protection will not effected by VT
circuit failure
Enabled: voltage controlled
phase overcurrent protection will
be blocked by VT circuit failure
signal
The percent setting of the
50/51P.HMB.K_Hm
14 0.1~1 0.2 - 0.001 harmonic control element of
2
phase overcurrent protection
The current setting for releasing
9
15 50/51P.HMB.I_Rls 2~150 20 A 0.001 the harmonic control element of
phase overcurrent protection
The setting used to select the
harmonic blocking mode of
PhaseBlk phase overcurrent protection
50/51P.HMB.Opt_Bl
16 CrossBlk PhaseBlk - - PhaseBlk: phase blocking
k
MaxPhaseBlk CrossBlk: cross blocking
MaxPhaseBlk: maximum phase
blocking

PCS-9611S Feeder Relay 9-21


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The current setting of stage 1 of
17 50/51P1.I_Set 0.05~200 15 A 0.001
phase overcurrent protection
The operating time setting of
18 50/51P1.t_Op 0 ~100 0.1 s 0.001 stage 1 of phase overcurrent
protection
The dropout time setting of
19 50/51P1.t_DropOut 0 ~100 0 s 0.001 stage 1 of phase overcurrent
protection
The logic setting for
enabling/disabling the voltage
control element of stage 1 of
phase overcurrent protection
Disabled: stage 1 of phase
50/51P1.En_Volt_Bl Disabled; overcurrent protection is not
20 Disabled - -
k Enabled controlled by the voltage control
element
Enabled: stage 1 of phase
overcurrent protection is
controlled by the voltage control
element
Non_Directional The setting used to select the
Non_Directio
21 50/51P1.Opt_Dir Forward - - directional mode of stage 1 of
nal
Reverse phase overcurrent protection.
The logic setting for
enabling/disabling the harmonic
control element of stage 1 of
phase overcurrent protection
Disabled: stage 1 of phase
50/51P1.En_Hm_Bl Disabled; overcurrent protection is not
22 Disabled - -
k Enabled controlled by the harmonic
control element

9 Enabled: stage 1 of phase


overcurrent protection is
controlled by the harmonic
control element
The logic setting for
Disabled;
23 50/51P1.En Enabled - - enabling/disabling the stage 1 of
Enabled
phase overcurrent protection

9-22 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
Enabling stage 1 of phase
overcurrent protection operate
50/51P1.Opt_Trp/Al Trp;
24 Trp - - to trip or alarm.
m Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
ANSILT; inverse-time operation
25 50/51P1.Opt_Curve IECDefTime - -
IECN; characteristic curve of stage 1 of
IECV; phase overcurrent protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 1 of
50/51P1.Opt_Curve
26 DefTime; Inst - - phase overcurrent protection
_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
27 50/51P1.TMS 0.04~ 20 1 - 0.001 stage 1 of phase overcurrent
protection

28 50/51P1.tmin 0 ~10 0.02 s 0.001


The minimum operating time
setting of stage 1 of phase
9
overcurrent protection
The constant “k” of the
customized inverse-time
0.000
29 50/51P1.K 0.001~120 0.14 - operation characteristic of stage
1
1 of phase overcurrent
protection

PCS-9611S Feeder Relay 9-23


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The constant “α” of the
customized inverse-time
0.000
30 50/51P1.Alpha 0.01 ~3 0.02 - operation characteristic of stage
1
1 of phase overcurrent
protection
The constant “C” of the
customized inverse-time
0.000
31 50/51P1.C 0 ~1 0 - operation characteristic of stage
1
1 of phase overcurrent
protection
The current setting of stage 1 of
32 50/51P1.I_Set 0.05~200 15 A 0.001
phase overcurrent protection
The operating time setting of
33 50/51P2.t_Op 0 ~100 0.1 s 0.001 stage 2 of phase overcurrent
protection
The dropout time setting of
34 50/51P2.t_DropOut 0 ~100 0 s 0.001 stage 2 of phase overcurrent
protection
The logic setting for
enabling/disabling the voltage
control element of stage 2 of
phase overcurrent protection
Disabled: stage 2 of phase
50/51P2.En_Volt_Bl Disabled; overcurrent protection is not
35 Disabled - -
k Enabled controlled by the voltage control
element
Enabled: stage 2 of phase
overcurrent protection is
controlled by the voltage control
element
Non_Directional The setting used to select the
Non_Directio
9 36 50/51P2.Opt_Dir Forward
Reverse
nal
- - directional mode of stage 2 of
phase overcurrent protection.

9-24 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The logic setting for
enabling/disabling the harmonic
control element of stage 2 of
phase overcurrent protection
Disabled: stage 2 of phase
50/51P2.En_Hm_Bl Disabled; overcurrent protection is not
37 Disabled - -
k Enabled controlled by the harmonic
control element
Enabled: stage 2 of phase
overcurrent protection is
controlled by the harmonic
control element
The logic setting for
Disabled;
38 50/51P2.En Enabled - - enabling/disabling the stage 2 of
Enabled
phase overcurrent protection
Enabling stage 2 of phase
overcurrent protection operate
50/51P2.Opt_Trp/Al Trp;
39 Trp - - to trip or alarm.
m Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
ANSILT; inverse-time operation
40 50/51P2.Opt_Curve IECDefTime - -
IECN; characteristic curve of stage 2 of
IECV; phase overcurrent protection.
IEC;
IECE;
IECST;
9
IECLT;
IECDefTime;
UserDefine

PCS-9611S Feeder Relay 9-25


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 2 of
50/51P2.Opt_Curve
41 DefTime; Inst - - phase overcurrent protection
_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
42 50/51P2.TMS 0.04~ 20 1 - 0.001 stage 2 of phase overcurrent
protection
The minimum operating time
43 50/51P2.tmin 0 ~10 0.02 s 0.001 setting of stage 2 of phase
overcurrent protection
The constant “k” of the
customized inverse-time
0.000
44 50/51P2.K 0.001~120 0.14 - operation characteristic of stage
1
2 of phase overcurrent
protection
The constant “α” of the
customized inverse-time
0.000
45 50/51P2.Alpha 0.01 ~3 0.02 - operation characteristic of stage
1
2 of phase overcurrent
protection
The constant “C” of the
customized inverse-time
0.000
46 50/51P2.C 0 ~1 0 - operation characteristic of stage
1
2 of phase overcurrent
protection
The current setting of stage 3 of
47 50/51P3.I_Set 0.05~200 15 A 0.001
phase overcurrent protection
The operating time setting of

9 48 50/51P3.t_Op 0 ~100 0.1 s 0.001 stage 3 of phase overcurrent


protection
The dropout time setting of
49 50/51P3.t_DropOut 0 ~100 0 s 0.001 stage 3 of phase overcurrent
protection

9-26 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The logic setting for
enabling/disabling the voltage
control element of stage 3 of
phase overcurrent protection
Disabled: stage 3 of phase
50/51P3.En_Volt_Bl Disabled; overcurrent protection is not
50 Disabled - -
k Enabled controlled by the voltage control
element
Enabled: stage 3 of phase
overcurrent protection is
controlled by the voltage control
element
Non_Directional The setting used to select the
Non_Directio
51 50/51P3.Opt_Dir Forward - - directional mode of stage 3 of
nal
Reverse phase overcurrent protection.
The logic setting for
enabling/disabling the harmonic
control element of stage 3 of
phase overcurrent protection
Disabled: stage 3 of phase
50/51P3.En_Hm_Bl Disabled; overcurrent protection is not
52 Disabled - -
k Enabled controlled by the harmonic
control element
Enabled: stage 3 of phase
overcurrent protection is
controlled by the harmonic
control element
The logic setting for
Disabled;
53 50/51P3.En Enabled - - enabling/disabling the stage 3 of
Enabled
phase overcurrent protection
Enabling stage 3 of phase

54
50/51P3.Opt_Trp/Al Trp;
Trp - -
overcurrent protection operate
to trip or alarm.
9
m Alm
Trp: for tripping purpose
Alm: for alarm purpose

PCS-9611S Feeder Relay 9-27


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
ANSILT; inverse-time operation
55 50/51P3.Opt_Curve IECDefTime - -
IECN; characteristic curve of stage 3 of
IECV; phase overcurrent protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 3 of
50/51P3.Opt_Curve
56 DefTime; Inst - - phase overcurrent protection
_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
57 50/51P3.TMS 0.04~ 20 1 - 0.001 stage 3 of phase overcurrent
protection
The minimum operating time
58 50/51P3.tmin 0 ~10 0.02 s 0.001 setting of stage 3 of phase
overcurrent protection
The constant “k” of the
customized inverse-time
0.000

9
59 50/51P3.K 0.001~120 0.14 - operation characteristic of stage
1
3 of phase overcurrent
protection
The constant “α” of the
customized inverse-time
0.000
60 50/51P3.Alpha 0.01 ~3 0.02 - operation characteristic of stage
1
3 of phase overcurrent
protection

9-28 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The constant “C” of the
customized inverse-time
0.000
61 50/51P3.C 0 ~1 0 - operation characteristic of stage
1
3 of phase overcurrent
protection
The current setting of stage 4 of
62 50/51P4.I_Set 0.05~200 15 A 0.001
phase overcurrent protection
The operating time setting of
63 50/51P4.t_Op 0 ~100 0.1 s 0.001 stage 4 of phase overcurrent
protection
The dropout time setting of
64 50/51P4.t_DropOut 0 ~100 0 s 0.001 stage 4 of phase overcurrent
protection
The logic setting for
enabling/disabling the voltage
control element of stage 4 of
phase overcurrent protection
Disabled: stage 4 of phase
50/51P4.En_Volt_Bl Disabled; overcurrent protection is not
65 Disabled - -
k Enabled controlled by the voltage control
element
Enabled: stage 4 of phase
overcurrent protection is
controlled by the voltage control
element
Non_Directional The setting used to select the
Non_Directio
66 50/51P4.Opt_Dir Forward - - directional mode of stage 4 of
nal
Reverse phase overcurrent protection.
The logic setting for
enabling/disabling the harmonic
control element of stage 4 of
phase overcurrent protection
Disabled: stage 4 of phase
9
50/51P4.En_Hm_Bl Disabled; overcurrent protection is not
67 Disabled - -
k Enabled controlled by the harmonic
control element
Enabled: stage 4 of phase
overcurrent protection is
controlled by the harmonic
control element

PCS-9611S Feeder Relay 9-29


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The logic setting for
Disabled;
68 50/51P4.En Enabled - - enabling/disabling the stage 4 of
Enabled
phase overcurrent protection
Enabling stage 4 of phase
overcurrent protection operate
50/51P4.Opt_Trp/Al Trp;
69 Trp - - to trip or alarm.
m Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
ANSILT; inverse-time operation
70 50/51P4.Opt_Curve IECDefTime - -
IECN; characteristic curve of stage 4 of
IECV; phase overcurrent protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 4 of
50/51P4.Opt_Curve
71 DefTime; Inst - - phase overcurrent protection
_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout

9
The time multiplier setting of
72 50/51P4.TMS 0.04~ 20 1 - 0.001 stage 4 of phase overcurrent
protection
The minimum operating time
73 50/51P4.tmin 0 ~10 0.02 s 0.001 setting of stage 4 of phase
overcurrent protection
The constant “k” of the
customized inverse-time
0.000
74 50/51P4.K 0.001~120 0.14 - operation characteristic of stage
1
4 of phase overcurrent
protection

9-30 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The constant “α” of the
customized inverse-time
0.000
75 50/51P4.Alpha 0.01 ~3 0.02 - operation characteristic of stage
1
4 of phase overcurrent
protection
The constant “C” of the
customized inverse-time
0.000
76 50/51P4.C 0 ~1 0 - operation characteristic of stage
1
4 of phase overcurrent
protection
The current setting of stage 5 of
77 50/51P5.I_Set 0.05~200 15 A 0.001
phase overcurrent protection
The operating time setting of
78 50/51P5.t_Op 0 ~100 0.1 s 0.001 stage 5 of phase overcurrent
protection
The dropout time setting of
79 50/51P5.t_DropOut 0 ~100 0 s 0.001 stage 5 of phase overcurrent
protection
The logic setting for
enabling/disabling the voltage
control element of stage 5 of
phase overcurrent protection
Disabled: stage 5 of phase
50/51P5.En_Volt_Bl Disabled; overcurrent protection is not
80 Disabled - -
k Enabled controlled by the voltage control
element
Enabled: stage 5 of phase
overcurrent protection is
controlled by the voltage control
element
Non_Directional The setting used to select the
Non_Directio
81 50/51P5.Opt_Dir Forward
Reverse
nal
- - directional mode of stage 5 of
phase overcurrent protection.
9

PCS-9611S Feeder Relay 9-31


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The logic setting for
enabling/disabling the harmonic
control element of stage 5 of
phase overcurrent protection
Disabled: stage 5 of phase
50/51P5.En_Hm_Bl Disabled; overcurrent protection is not
82 Disabled - -
k Enabled controlled by the harmonic
control element
Enabled: stage 5 of phase
overcurrent protection is
controlled by the harmonic
control element
The logic setting for
Disabled;
83 50/51P5.En Enabled - - enabling/disabling the stage 5 of
Enabled
phase overcurrent protection
Enabling stage 5 of phase
overcurrent protection operate
50/51P5.Opt_Trp/Al Trp;
84 Trp - - to trip or alarm.
m Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
ANSILT; inverse-time operation
85 50/51P5.Opt_Curve IECDefTime - -
IECN; characteristic curve of stage 5 of
IECV; phase overcurrent protection.
IEC;

9
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine

9-32 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 5 of
50/51P5.Opt_Curve
86 DefTime; Inst - - phase overcurrent protection
_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
87 50/51P5.TMS 0.04~ 20 1 - 0.001 stage 5 of phase overcurrent
protection
The minimum operating time
88 50/51P5.tmin 0 ~10 0.02 s 0.001 setting of stage 5 of phase
overcurrent protection
The constant “k” of the
customized inverse-time
0.000
89 50/51P5.K 0.001~120 0.14 - operation characteristic of stage
1
5 of phase overcurrent
protection
The constant “α” of the
customized inverse-time
0.000
90 50/51P5.Alpha 0.01 ~3 0.02 - operation characteristic of stage
1
5 of phase overcurrent
protection
The constant “C” of the
customized inverse-time
0.000
91 50/51P5.C 0 ~1 0 - operation characteristic of stage
1
5 of phase overcurrent
protection
The current setting of stage 6 of
92 50/51P6.I_Set 0.05~200 15 A 0.001
phase overcurrent protection
The operating time setting of
93 50/51P6.t_Op 0 ~100 0.1 s 0.001 stage 6 of phase overcurrent
protection
9
The dropout time setting of
94 50/51P6.t_DropOut 0 ~100 0 s 0.001 stage 6 of phase overcurrent
protection

PCS-9611S Feeder Relay 9-33


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The logic setting for
enabling/disabling the voltage
control element of stage 6 of
phase overcurrent protection
Disabled: stage 6 of phase
50/51P6.En_Volt_Bl Disabled; overcurrent protection is not
95 Disabled - -
k Enabled controlled by the voltage control
element
Enabled: stage 6 of phase
overcurrent protection is
controlled by the voltage control
element
Non_Directional The setting used to select the
Non_Directio
96 50/51P6.Opt_Dir Forward - - directional mode of stage 6 of
nal
Reverse phase overcurrent protection.
The logic setting for
enabling/disabling the harmonic
control element of stage 6 of
phase overcurrent protection
Disabled: stage 6 of phase
50/51P6.En_Hm_Bl Disabled; overcurrent protection is not
97 Disabled - -
k Enabled controlled by the harmonic
control element
Enabled: stage 6 of phase
overcurrent protection is
controlled by the harmonic
control element
The logic setting for
Disabled;
98 50/51P6.En Enabled - - enabling/disabling the stage 6 of
Enabled
phase overcurrent protection
Enabling stage 6 of phase

9
overcurrent protection operate
50/51P6.Opt_Trp/Al Trp;
99 Trp - - to trip or alarm.
m Alm
Trp: for tripping purpose
Alm: for alarm purpose

9-34 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
ANSILT; inverse-time operation
100 50/51P6.Opt_Curve IECDefTime - -
IECN; characteristic curve of stage 6 of
IECV; phase overcurrent protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 6 of
50/51P6.Opt_Curve
101 DefTime; Inst - - phase overcurrent protection
_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
102 50/51P6.TMS 0.04~ 20 1 - 0.001 stage 6 of phase overcurrent
protection
The minimum operating time
103 50/51P6.tmin 0 ~10 0.02 s 0.001 setting of stage 6 of phase
overcurrent protection
The constant “k” of the
customized inverse-time
0.000
104 50/51P6.K 0.001~120 0.14 -
1
operation characteristic of stage
6 of phase overcurrent
9
protection
The constant “α” of the
customized inverse-time
0.000
105 50/51P6.Alpha 0.01 ~3 0.02 - operation characteristic of stage
1
6 of phase overcurrent
protection

PCS-9611S Feeder Relay 9-35


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The constant “C” of the
customized inverse-time
0.000
106 50/51P6.C 0 ~1 0 - operation characteristic of stage
1
6 of phase overcurrent
protection

9.2.2 Earth Fault Overcurrent Protection Settings


 Access path:

MainMenu  Settings  Protection Settings  ROC Settings

Table 9.2-2 Settings of earth fault overcurrent protection

Default Uni
No. Settings Range Step Description
value t
The relay characteristic angle
of the direction control
1 50/51G.DIR.RCA -180~179 45 deg 1
element of earth fault
overcurrent protection
The minimum boundary of the
50/51G.DIR.phi_Min_ forward direction element of
2 10~90 90 deg 1
Fwd earth fault overcurrent
protection
The maximum boundary of the
50/51G.DIR.phi_Max_ forward direction element of
3 10~90 90 deg 1
Fwd earth fault overcurrent
protection
The minimum boundary of the
50/51G.DIR.phi_Min_ reverse direction element of
4 10~90 90 deg 1
Rev earth fault overcurrent
protection
The maximum boundary of the
50/51G.DIR.phi_Max_ reverse direction element of
9 5
Rev
10~90 90 deg 1
earth fault overcurrent
protection
The minimum operating
current setting for the direction
6 50/51G.DIR.I_Min (0.05~1)In 0.05 - 0.001
control element of earth fault
overcurrent protection
The minimum operating
voltage setting for the direction
7 50/51G.DIR.U_Min 1~10 4 V 0.001
control element of earth fault
overcurrent protection

9-36 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default Uni
No. Settings Range Step Description
value t
Logic setting to determine the
behavior of earth fault
overcurrent protection when
VT circuit supervision function
is enabled and VT circuit
failure happens.
Disabled;
8 50/51G.En_VTS_Blk Disabled - - Disabled: earth fault
Enabled
overcurrent protection will not
effected by VT circuit failure
Enabled: voltage controlled
earth fault overcurrent
protection will be blocked by
VT circuit failure signal
The percent setting of the
harmonic control element of
9 50/51G.HMB.K_Hm2 0.1~1 0.2 - 0.001
earth fault overcurrent
protection
The current setting for
releasing the harmonic control
10 50/51G.HMB.I_Rls 2~150 20 A 0.001
element of earth fault
overcurrent protection
The setting used to select the
residual current that used for
stage 1 of earth fault
Ext; overcurrent protection
11 50/51G1.Opt_3I0 Ext - -
Cal Ext: the measured residual
current
Cal: the calculated residual
current
The current setting of stage 1
12 50/51G1.3I0_Set 0.05~200 15 A 0.001 of earth fault overcurrent
protection
The operating time setting of
9
13 50/51G1.t_Op 0 ~100 0.1 s 0.001 stage 1 of earth fault
overcurrent protection
The dropout time setting of
14 50/51G1.t_DropOut 0 ~100 0 s 0.001 stage 1 of earth fault
overcurrent protection

PCS-9611S Feeder Relay 9-37


Date: 2019-04-24
9 Settings

Default Uni
No. Settings Range Step Description
value t
The setting used to select the
directional mode of stage 1 of
Non_Direction
earth fault overcurrent
al; Non_Directio
15 50/51G1.Opt_Dir - - protection.
Forward; nal
1: no direction;
Reverse
2: forward direction;
3: reverse direction.
The logic setting for
enabling/disabling the
harmonic control element of
the stage 1 of earth fault
overcurrent protection
Disabled: stage 1 of earth fault
Disabled;
16 50/51G1.En_Hm_Blk Disabled - - overcurrent protection is not
Enabled
controlled by the harmonic
control element
Enabled: stage 1 of earth fault
overcurrent protection is
controlled by the harmonic
control element
The logic setting for
Disabled; enabling/disabling the stage 1
17 50/51G1.En Enabled - -
Enabled of earth fault overcurrent
protection
Enabling stage 1 earth fault
overcurrent protection operate
Trp;
18 50/51G1.Opt_Trp/Alm Trp - - to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose

9-38 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default Uni
No. Settings Range Step Description
value t
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
The setting for selecting the
ANSILTV;
inverse-time operation
ANSILT;
19 50/51G1.Opt_Curve IECDefTime - - characteristic curve of stage 1
IECN;
of earth fault overcurrent
IECV;
protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
characteristic curve of stage 1
Inst;
50/51G1.Opt_Curve_ of earth fault overcurrent
20 DefTime; Inst - -
DropOut protection
IDMT
Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
21 50/51G1.TMS 0.04~ 20 1 - 0.001 stage 1 of earth fault
overcurrent protection
The minimum operating time
22 50/51G1.tmin 0 ~10 0.02 s 0.001 setting of stage 1 of earth fault
overcurrent protection
The constant “k” of the

23 50/51G1.K 0.001~120 0.14 - 0.0001


customized
operation
inverse-time
characteristic of
9
stage 1 of earth fault
overcurrent protection
The constant “α” of the
customized inverse-time
24 50/51G1.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of
stage 1 of earth fault
overcurrent protection

PCS-9611S Feeder Relay 9-39


Date: 2019-04-24
9 Settings

Default Uni
No. Settings Range Step Description
value t
The constant “C” of the
customized inverse-time
25 50/51G1.C 0 ~1 0 - 0.0001 operation characteristic of
stage 1 of earth fault
overcurrent protection
The setting used to select the
residual current that used for
stage 2 of earth fault
Ext; overcurrent protection
26 50/51G2.Opt_3I0 Ext - -
Cal Ext: the measured residual
current
Cal: the calculated residual
current
The current setting of stage 2
27 50/51G2.3I0_Set 0.05~200 15 A 0.001 of earth fault overcurrent
protection
The operating time setting of
28 50/51G2.t_Op 0 ~100 0.1 s 0.001 stage 2 of earth fault
overcurrent protection
The dropout time setting of
29 50/51G2.t_DropOut 0 ~100 0 s 0.001 stage 2 of earth fault
overcurrent protection
The setting used to select the
directional mode of stage 2 of
Non_Direction
earth fault overcurrent
al; Non_Directio
30 50/51G2.Opt_Dir - - protection.
Forward; nal
1: no direction;
Reverse
2: forward direction;
3: reverse direction.
The logic setting for
enabling/disabling the

9 harmonic control element of


the stage 2 of earth fault
overcurrent protection
Disabled: stage 2 of earth fault
Disabled;
31 50/51G2.En_Hm_Blk Disabled - - overcurrent protection is not
Enabled
controlled by the harmonic
control element
Enabled: stage 2 of earth fault
overcurrent protection is
controlled by the harmonic
control element

9-40 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default Uni
No. Settings Range Step Description
value t
The logic setting for
Disabled; enabling/disabling the stage 2
32 50/51G2.En Enabled - -
Enabled of earth fault overcurrent
protection
Enabling stage 2 earth fault
overcurrent protection operate
Trp;
33 50/51G2.Opt_Trp/Alm Trp - - to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
The setting for selecting the
ANSILTV;
inverse-time operation
ANSILT;
34 50/51G2.Opt_Curve IECDefTime - - characteristic curve of stage 2
IECN;
of earth fault overcurrent
IECV;
protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
characteristic curve of stage 2
Inst;
50/51G2.Opt_Curve_ of earth fault overcurrent
35 DefTime; Inst - -
DropOut protection
IDMT
Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
9
The time multiplier setting of
36 50/51G2.TMS 0.04~ 20 1 - 0.001 stage 2 of earth fault
overcurrent protection
The minimum operating time
37 50/51G2.tmin 0 ~10 0.02 s 0.001 setting of stage 2 of earth fault
overcurrent protection

PCS-9611S Feeder Relay 9-41


Date: 2019-04-24
9 Settings

Default Uni
No. Settings Range Step Description
value t
The constant “k” of the
customized inverse-time
38 50/51G2.K 0.001~120 0.14 - 0.0001 operation characteristic of
stage 2 of earth fault
overcurrent protection
The constant “α” of the
customized inverse-time
39 50/51G2.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of
stage 2 of earth fault
overcurrent protection
The constant “C” of the
customized inverse-time
40 50/51G2.C 0 ~1 0 - 0.0001 operation characteristic of
stage 2 of earth fault
overcurrent protection
The setting used to select the
residual current that used for
stage 3 of earth fault
Ext; overcurrent protection
41 50/51G3.Opt_3I0 Ext - -
Cal Ext: the measured residual
current
Cal: the calculated residual
current
The current setting of stage 3
42 50/51G3.3I0_Set 0.05~200 15 A 0.001 of earth fault overcurrent
protection
The operating time setting of
43 50/51G3.t_Op 0 ~100 0.1 s 0.001 stage 3 of earth fault
overcurrent protection
The dropout time setting of
44 50/51G3.t_DropOut 0 ~100 0 s 0.001 stage 3 of earth fault

9 overcurrent protection
The setting used to select the
directional mode of stage 3 of
Non_Direction
earth fault overcurrent
al; Non_Directio
45 50/51G3.Opt_Dir - - protection.
Forward; nal
1: no direction;
Reverse
2: forward direction;
3: reverse direction.

9-42 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default Uni
No. Settings Range Step Description
value t
The logic setting for
enabling/disabling the
harmonic control element of
the stage 3 of earth fault
overcurrent protection
Disabled: stage 3 of earth fault
Disabled;
46 50/51G3.En_Hm_Blk Disabled - - overcurrent protection is not
Enabled
controlled by the harmonic
control element
Enabled: stage 3 of earth fault
overcurrent protection is
controlled by the harmonic
control element
The logic setting for
Disabled; enabling/disabling the stage 3
47 50/51G3.En Enabled - -
Enabled of earth fault overcurrent
protection
Enabling stage 3 earth fault
overcurrent protection operate
Trp;
48 50/51G3.Opt_Trp/Alm Trp - - to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
The setting for selecting the
ANSILTV;
inverse-time operation
ANSILT;
49 50/51G3.Opt_Curve IECDefTime - - characteristic curve of stage 3
IECN;
of earth fault overcurrent
IECV;
IEC;
protection. 9
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine

PCS-9611S Feeder Relay 9-43


Date: 2019-04-24
9 Settings

Default Uni
No. Settings Range Step Description
value t
The setting for selecting the
inverse-time dropout
characteristic curve of stage 3
Inst;
50/51G3.Opt_Curve_ of earth fault overcurrent
50 DefTime; Inst - -
DropOut protection
IDMT
Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
51 50/51G3.TMS 0.04~ 20 1 - 0.001 stage 3 of earth fault
overcurrent protection
The minimum operating time
52 50/51G3.tmin 0 ~10 0.02 s 0.001 setting of stage 3 of earth fault
overcurrent protection
The constant “k” of the
customized inverse-time
53 50/51G3.K 0.001~120 0.14 - 0.0001 operation characteristic of
stage 3 of earth fault
overcurrent protection
The constant “α” of the
customized inverse-time
54 50/51G3.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of
stage 3 of earth fault
overcurrent protection
The constant “C” of the
customized inverse-time
55 50/51G3.C 0 ~1 0 - 0.0001 operation characteristic of
stage 3 of earth fault
overcurrent protection
The setting used to select the
residual current that used for

9 Ext;
stage 4 of
overcurrent protection
earth fault

56 50/51G4.Opt_3I0 Ext - -
Cal Ext: the measured residual
current
Cal: the calculated residual
current
The current setting of stage 4
57 50/51G4.3I0_Set 0.05~200 15 A 0.001 of earth fault overcurrent
protection

9-44 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default Uni
No. Settings Range Step Description
value t
The operating time setting of
58 50/51G4.t_Op 0 ~100 0.1 s 0.001 stage 4 of earth fault
overcurrent protection
The dropout time setting of
59 50/51G4.t_DropOut 0 ~100 0 s 0.001 stage 4 of earth fault
overcurrent protection
The setting used to select the
directional mode of stage 4 of
Non_Direction
earth fault overcurrent
al; Non_Directio
60 50/51G4.Opt_Dir - - protection.
Forward; nal
1: no direction;
Reverse
2: forward direction;
3: reverse direction.
The logic setting for
enabling/disabling the
harmonic control element of
the stage 4 of earth fault
overcurrent protection
Disabled: stage 4 of earth fault
Disabled;
61 50/51G4.En_Hm_Blk Disabled - - overcurrent protection is not
Enabled
controlled by the harmonic
control element
Enabled: stage 4 of earth fault
overcurrent protection is
controlled by the harmonic
control element
The logic setting for
Disabled; enabling/disabling the stage 4
62 50/51G4.En Enabled - -
Enabled of earth fault overcurrent
protection
Enabling stage 4 earth fault

63 50/51G4.Opt_Trp/Alm
Trp;
Trp - -
overcurrent protection operate
to trip or alarm.
9
Alm
Trp: for tripping purpose
Alm: for alarm purpose

PCS-9611S Feeder Relay 9-45


Date: 2019-04-24
9 Settings

Default Uni
No. Settings Range Step Description
value t
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
The setting for selecting the
ANSILTV;
inverse-time operation
ANSILT;
64 50/51G4.Opt_Curve IECDefTime - - characteristic curve of stage 4
IECN;
of earth fault overcurrent
IECV;
protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
characteristic curve of stage 4
Inst;
50/51G4.Opt_Curve_ of earth fault overcurrent
65 DefTime; Inst - -
DropOut protection
IDMT
Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
66 50/51G4.TMS 0.04~ 20 1 - 0.001 stage 4 of earth fault
overcurrent protection
The minimum operating time
67 50/51G4.tmin 0 ~10 0.02 s 0.001 setting of stage 4 of earth fault
overcurrent protection
The constant “k” of the

9
customized inverse-time
68 50/51G4.K 0.001~120 0.14 - 0.0001 operation characteristic of
stage 4 of earth fault
overcurrent protection
The constant “α” of the
customized inverse-time
69 50/51G4.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of
stage 4 of earth fault
overcurrent protection

9-46 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default Uni
No. Settings Range Step Description
value t
The constant “C” of the
customized inverse-time
70 50/51G4.C 0 ~1 0 - 0.0001 operation characteristic of
stage 4 of earth fault
overcurrent protection
The setting used to select the
residual current that used for
stage 5 of earth fault
Ext; overcurrent protection
71 50/51G5.Opt_3I0 Ext - -
Cal Ext: the measured residual
current
Cal: the calculated residual
current
The current setting of stage 5
72 50/51G5.3I0_Set 0.05~200 15 A 0.001 of earth fault overcurrent
protection
The operating time setting of
73 50/51G5.t_Op 0 ~100 0.1 s 0.001 stage 5 of earth fault
overcurrent protection
The dropout time setting of
74 50/51G5.t_DropOut 0 ~100 0 s 0.001 stage 5 of earth fault
overcurrent protection
The setting used to select the
directional mode of stage 5 of
Non_Direction
earth fault overcurrent
al; Non_Directio
75 50/51G5.Opt_Dir - - protection.
Forward; nal
1: no direction;
Reverse
2: forward direction;
3: reverse direction.
The logic setting for
enabling/disabling the
harmonic control element of
the stage 5 of earth fault
9
overcurrent protection
Disabled: stage 5 of earth fault
Disabled;
76 50/51G5.En_Hm_Blk Disabled - - overcurrent protection is not
Enabled
controlled by the harmonic
control element
Enabled: stage 5 of earth fault
overcurrent protection is
controlled by the harmonic
control element

PCS-9611S Feeder Relay 9-47


Date: 2019-04-24
9 Settings

Default Uni
No. Settings Range Step Description
value t
The logic setting for
Disabled; enabling/disabling the stage 5
77 50/51G5.En Enabled - -
Enabled of earth fault overcurrent
protection
Enabling stage 5 earth fault
overcurrent protection operate
Trp;
78 50/51G5.Opt_Trp/Alm Trp - - to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
The setting for selecting the
ANSILTV;
inverse-time operation
ANSILT;
79 50/51G5.Opt_Curve IECDefTime - - characteristic curve of stage 5
IECN;
of earth fault overcurrent
IECV;
protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
characteristic curve of stage 5
Inst;
50/51G5.Opt_Curve_ of earth fault overcurrent
80 DefTime; Inst - -
DropOut protection
IDMT
Inst: instantaneous dropout

9
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
81 50/51G5.TMS 0.04~ 20 1 - 0.001 stage 5 of earth fault
overcurrent protection
The minimum operating time
82 50/51G5.tmin 0 ~10 0.02 s 0.001 setting of stage 5 of earth fault
overcurrent protection

9-48 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default Uni
No. Settings Range Step Description
value t
The constant “k” of the
customized inverse-time
83 50/51G5.K 0.001~120 0.14 - 0.0001 operation characteristic of
stage 5 of earth fault
overcurrent protection
The constant “α” of the
customized inverse-time
84 50/51G5.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of
stage 5 of earth fault
overcurrent protection
The constant “C” of the
customized inverse-time
85 50/51G5.C 0 ~1 0 - 0.0001 operation characteristic of
stage 5 of earth fault
overcurrent protection
The setting used to select the
residual current that used for
stage 6 of earth fault
Ext; overcurrent protection
86 50/51G6.Opt_3I0 Ext - -
Cal Ext: the measured residual
current
Cal: the calculated residual
current
The current setting of stage 6
87 50/51G6.3I0_Set 0.05~200 15 A 0.001 of earth fault overcurrent
protection
The operating time setting of
88 50/51G6.t_Op 0 ~100 0.1 s 0.001 stage 6 of earth fault
overcurrent protection
The dropout time setting of
89 50/51G6.t_DropOut 0 ~100 0 s 0.001 stage 6 of earth fault
overcurrent protection
The setting used to select the
9
directional mode of stage 6 of
Non_Direction
earth fault overcurrent
al; Non_Directio
90 50/51G6.Opt_Dir - - protection.
Forward; nal
1: no direction;
Reverse
2: forward direction;
3: reverse direction.

PCS-9611S Feeder Relay 9-49


Date: 2019-04-24
9 Settings

Default Uni
No. Settings Range Step Description
value t
The logic setting for
enabling/disabling the
harmonic control element of
the stage 6 of earth fault
overcurrent protection
Disabled: stage 6 of earth fault
Disabled;
91 50/51G6.En_Hm_Blk Disabled - - overcurrent protection is not
Enabled
controlled by the harmonic
control element
Enabled: stage 6 of earth fault
overcurrent protection is
controlled by the harmonic
control element
The logic setting for
Disabled; enabling/disabling the stage 6
92 50/51G6.En Enabled - -
Enabled of earth fault overcurrent
protection
Enabling stage 6 earth fault
overcurrent protection operate
Trp;
93 50/51G6.Opt_Trp/Alm Trp - - to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
The setting for selecting the
ANSILTV;
inverse-time operation
ANSILT;
94 50/51G6.Opt_Curve IECDefTime - - characteristic curve of stage 6
IECN;
of earth fault overcurrent

9
IECV;
protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine

9-50 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default Uni
No. Settings Range Step Description
value t
The setting for selecting the
inverse-time dropout
characteristic curve of stage 6
Inst;
50/51G6.Opt_Curve_ of earth fault overcurrent
95 DefTime; Inst - -
DropOut protection
IDMT
Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
96 50/51G6.TMS 0.04~ 20 1 - 0.001 stage 6 of earth fault
overcurrent protection
The minimum operating time
97 50/51G6.tmin 0 ~10 0.02 s 0.001 setting of stage 6 of earth fault
overcurrent protection
The constant “k” of the
customized inverse-time
98 50/51G6.K 0.001~120 0.14 - 0.0001 operation characteristic of
stage 6 of earth fault
overcurrent protection
The constant “α” of the
customized inverse-time
99 50/51G6.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of
stage 6 of earth fault
overcurrent protection
The constant “C” of the
customized inverse-time
100 50/51G6.C 0 ~1 0 - 0.0001 operation characteristic of
stage 6 of earth fault
overcurrent protection

9.2.3 Another Group of Earth Fault Overcurrent Protection Settings


 Access path:
9
MainMenu  Settings  Protection Settings  ROC2 Settings

Table 9.2-3 Settings of another group of earth fault overcurrent protection

Default
No. Settings Range Unit Step Description
value
The current setting of
stage 1 of another group of
1 A.50/51G1.3I0_Set 0.05~200 15 A 0.001
earth fault overcurrent
protection

PCS-9611S Feeder Relay 9-51


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The operating time setting
of stage 1 of another group
2 A.50/51G1.t_Op 0 ~100 0.1 s 0.001
of earth fault overcurrent
protection
The dropout time setting of
stage 1 of another group of
3 A.50/51G1.t_DropOut 0 ~100 0 s 0.001
earth fault overcurrent
protection
The logic setting for
enabling/disabling the
Disabled;
4 A.50/51G1.En Enabled - - stage 1 of another group of
Enabled
earth fault overcurrent
protection
Enabling stage 1 of
another group of earth fault
Trp; overcurrent protection
5 A.50/51G1.Opt_Trp/Alm Trp - -
Alm operate to trip or alarm.
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE; The setting for selecting
ANSILTV; the inverse-time operation
ANSILT; characteristic curve of
6 A.50/51G1.Opt_Curve IECDefTime - -
IECN; stage 1 of another group of
IECV; earth fault overcurrent
IEC; protection.
IECE;

9
IECST;
IECLT;
IECDefTime;
UserDefine

9-52 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The setting for selecting
the inverse-time dropout
characteristic curve of
stage 1 of another group of
Inst; earth fault overcurrent
A.50/51G1.Opt_Curve_D
7 DefTime; Inst - - protection
ropOut
IDMT Inst: instantaneous
dropout
DefTime: definite-time
dropout
IDMT: inverse-time dropout
The time multiplier setting
of stage 1 of another group
8 A.50/51G1.TMS 0.04~ 20 1 - 0.001
of earth fault overcurrent
protection
The minimum operating
time setting of stage 1 of
9 A.50/51G1.tmin 0 ~10 0.02 s 0.001
another group of earth fault
overcurrent protection
The constant “k” of the
customized inverse-time
operation characteristic of
10 A.50/51G1.K 0.001~120 0.14 - 0.0001
stage 1 of another group of
earth fault overcurrent
protection
The constant “α” of the
customized inverse-time
operation characteristic of
11 A.50/51G1.Alpha 0.01 ~3 0.02 - 0.0001
stage 1 of another group of
earth fault overcurrent
protection
The constant “C” of the
customized inverse-time
9
operation characteristic of
12 A.50/51G1.C 0 ~1 0 - 0.0001
stage 1 of another group of
earth fault overcurrent
protection
The current setting of
stage 2 of another group of
13 A.50/51G2.3I0_Set 0.05~200 15 A 0.001
earth fault overcurrent
protection

PCS-9611S Feeder Relay 9-53


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The operating time setting
of stage 2 of another group
14 A.50/51G2.t_Op 0 ~100 0.1 s 0.001
of earth fault overcurrent
protection
The dropout time setting of
stage 2 of another group of
15 A.50/51G2.t_DropOut 0 ~100 0 s 0.001
earth fault overcurrent
protection
The logic setting for
enabling/disabling the
Disabled;
16 A.50/51G2.En Enabled - - stage 2 of another group of
Enabled
earth fault overcurrent
protection
Enabling stage 2 of
another group of earth fault
Trp; overcurrent protection
17 A.50/51G2.Opt_Trp/Alm Trp - -
Alm operate to trip or alarm.
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE; The setting for selecting
ANSILTV; the inverse-time operation
ANSILT; characteristic curve of
18 A.50/51G2.Opt_Curve IECDefTime - -
IECN; stage 2 of another group of
IECV; earth fault overcurrent
IEC; protection.
IECE;

9
IECST;
IECLT;
IECDefTime;
UserDefine

9-54 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The setting for selecting
the inverse-time dropout
characteristic curve of
stage 2 of another group of
Inst; earth fault overcurrent
A.50/51G2.Opt_Curve_D
19 DefTime; Inst - - protection
ropOut
IDMT Inst: instantaneous
dropout
DefTime: definite-time
dropout
IDMT: inverse-time dropout
The time multiplier setting
of stage 2 of another group
20 A.50/51G2.TMS 0.04~ 20 1 - 0.001
of earth fault overcurrent
protection
The minimum operating
time setting of stage 2 of
21 A.50/51G2.tmin 0 ~10 0.02 s 0.001
another group of earth fault
overcurrent protection
The constant “k” of the
customized inverse-time
operation characteristic of
22 A.50/51G2.K 0.001~120 0.14 - 0.0001
stage 2 of another group of
earth fault overcurrent
protection
The constant “α” of the
customized inverse-time
operation characteristic of
23 A.50/51G2.Alpha 0.01 ~3 0.02 - 0.0001
stage 2 of another group of
earth fault overcurrent
protection
The constant “C” of the
customized inverse-time
9
operation characteristic of
24 A.50/51G2.C 0 ~1 0 - 0.0001
stage 2 of another group of
earth fault overcurrent
protection
The current setting of
stage 3 of another group of
25 A.50/51G3.3I0_Set 0.05~200 15 A 0.001
earth fault overcurrent
protection

PCS-9611S Feeder Relay 9-55


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The operating time setting
of stage 3 of another group
26 A.50/51G3.t_Op 0 ~100 0.1 s 0.001
of earth fault overcurrent
protection
The dropout time setting of
stage 3 of another group of
27 A.50/51G3.t_DropOut 0 ~100 0 s 0.001
earth fault overcurrent
protection
The logic setting for
enabling/disabling the
Disabled;
28 A.50/51G3.En Enabled - - stage 3 of another group of
Enabled
earth fault overcurrent
protection
Enabling stage 3 of
another group of earth fault
Trp; overcurrent protection
29 A.50/51G3.Opt_Trp/Alm Trp - -
Alm operate to trip or alarm.
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE; The setting for selecting
ANSILTV; the inverse-time operation
ANSILT; characteristic curve of
30 A.50/51G3.Opt_Curve IECDefTime - -
IECN; stage 3 of another group of
IECV; earth fault overcurrent
IEC; protection.
IECE;

9
IECST;
IECLT;
IECDefTime;
UserDefine

9-56 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The setting for selecting
the inverse-time dropout
characteristic curve of
stage 3 of another group of
Inst; earth fault overcurrent
A.50/51G3.Opt_Curve_D
31 DefTime; Inst - - protection
ropOut
IDMT Inst: instantaneous
dropout
DefTime: definite-time
dropout
IDMT: inverse-time dropout
The time multiplier setting
of stage 3 of another group
32 A.50/51G3.TMS 0.04~ 20 1 - 0.001
of earth fault overcurrent
protection
The minimum operating
time setting of stage 3 of
33 A.50/51G3.tmin 0 ~10 0.02 s 0.001
another group of earth fault
overcurrent protection
The constant “k” of the
customized inverse-time
operation characteristic of
34 A.50/51G3.K 0.001~120 0.14 - 0.0001
stage 3 of another group of
earth fault overcurrent
protection
The constant “α” of the
customized inverse-time
operation characteristic of
35 A.50/51G3.Alpha 0.01 ~3 0.02 - 0.0001
stage 3 of another group of
earth fault overcurrent
protection
The constant “C” of the
customized inverse-time
9
operation characteristic of
36 A.50/51G3.C 0 ~1 0 - 0.0001
stage 3 of another group of
earth fault overcurrent
protection
The current setting of
stage 4 of another group of
37 A.50/51G4.3I0_Set 0.05~200 15 A 0.001
earth fault overcurrent
protection

PCS-9611S Feeder Relay 9-57


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The operating time setting
of stage 4 of another group
38 A.50/51G4.t_Op 0 ~100 0.1 s 0.001
of earth fault overcurrent
protection
The dropout time setting of
stage 4 of another group of
39 A.50/51G4.t_DropOut 0 ~100 0 s 0.001
earth fault overcurrent
protection
The logic setting for
enabling/disabling the
Disabled;
40 A.50/51G4.En Enabled - - stage 4 of another group of
Enabled
earth fault overcurrent
protection
Enabling stage 4 of
another group of earth fault
Trp; overcurrent protection
41 A.50/51G4.Opt_Trp/Alm Trp - -
Alm operate to trip or alarm.
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE; The setting for selecting
ANSILTV; the inverse-time operation
ANSILT; characteristic curve of
42 A.50/51G4.Opt_Curve IECDefTime - -
IECN; stage 4 of another group of
IECV; earth fault overcurrent
IEC; protection.
IECE;

9
IECST;
IECLT;
IECDefTime;
UserDefine

9-58 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The setting for selecting
the inverse-time dropout
characteristic curve of
stage 4 of another group of
Inst; earth fault overcurrent
A.50/51G4.Opt_Curve_D
43 DefTime; Inst - - protection
ropOut
IDMT Inst: instantaneous
dropout
DefTime: definite-time
dropout
IDMT: inverse-time dropout
The time multiplier setting
of stage 4 of another group
44 A.50/51G4.TMS 0.04~ 20 1 - 0.001
of earth fault overcurrent
protection
The minimum operating
time setting of stage 4 of
45 A.50/51G4.tmin 0 ~10 0.02 s 0.001
another group of earth fault
overcurrent protection
The constant “k” of the
customized inverse-time
operation characteristic of
46 A.50/51G4.K 0.001~120 0.14 - 0.0001
stage 4 of another group of
earth fault overcurrent
protection
The constant “α” of the
customized inverse-time
operation characteristic of
47 A.50/51G4.Alpha 0.01 ~3 0.02 - 0.0001
stage 4 of another group of
earth fault overcurrent
protection
The constant “C” of the
customized inverse-time
9
operation characteristic of
48 A.50/51G4.C 0 ~1 0 - 0.0001
stage 4 of another group of
earth fault overcurrent
protection
The current setting of
stage 5 of another group of
49 A.50/51G5.3I0_Set 0.05~200 15 A 0.001
earth fault overcurrent
protection

PCS-9611S Feeder Relay 9-59


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The operating time setting
of stage 5 of another group
50 A.50/51G5.t_Op 0 ~100 0.1 s 0.001
of earth fault overcurrent
protection
The dropout time setting of
stage 5 of another group of
51 A.50/51G5.t_DropOut 0 ~100 0 s 0.001
earth fault overcurrent
protection
The logic setting for
enabling/disabling the
Disabled;
52 A.50/51G5.En Enabled - - stage 5 of another group of
Enabled
earth fault overcurrent
protection
Enabling stage 5 of
another group of earth fault
Trp; overcurrent protection
53 A.50/51G5.Opt_Trp/Alm Trp - -
Alm operate to trip or alarm.
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE; The setting for selecting
ANSILTV; the inverse-time operation
ANSILT; characteristic curve of
54 A.50/51G5.Opt_Curve IECDefTime - -
IECN; stage 5 of another group of
IECV; earth fault overcurrent
IEC; protection.
IECE;

9
IECST;
IECLT;
IECDefTime;
UserDefine

9-60 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The setting for selecting
the inverse-time dropout
characteristic curve of
stage 5 of another group of
Inst; earth fault overcurrent
A.50/51G5.Opt_Curve_D
55 DefTime; Inst - - protection
ropOut
IDMT Inst: instantaneous
dropout
DefTime: definite-time
dropout
IDMT: inverse-time dropout
The time multiplier setting
of stage 5 of another group
56 A.50/51G5.TMS 0.04~ 20 1 - 0.001
of earth fault overcurrent
protection
The minimum operating
time setting of stage 5 of
57 A.50/51G5.tmin 0 ~10 0.02 s 0.001
another group of earth fault
overcurrent protection
The constant “k” of the
customized inverse-time
operation characteristic of
58 A.50/51G5.K 0.001~120 0.14 - 0.0001
stage 5 of another group of
earth fault overcurrent
protection
The constant “α” of the
customized inverse-time
operation characteristic of
59 A.50/51G5.Alpha 0.01 ~3 0.02 - 0.0001
stage 5 of another group of
earth fault overcurrent
protection
The constant “C” of the
customized inverse-time
9
operation characteristic of
60 A.50/51G5.C 0 ~1 0 - 0.0001
stage 5 of another group of
earth fault overcurrent
protection
The current setting of
stage 6 of another group of
61 A.50/51G6.3I0_Set 0.05~200 15 A 0.001
earth fault overcurrent
protection

PCS-9611S Feeder Relay 9-61


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The operating time setting
of stage 6 of another group
62 A.50/51G6.t_Op 0 ~100 0.1 s 0.001
of earth fault overcurrent
protection
The dropout time setting of
stage 6 of another group of
63 A.50/51G6.t_DropOut 0 ~100 0 s 0.001
earth fault overcurrent
protection
The logic setting for
enabling/disabling the
Disabled;
64 A.50/51G6.En Enabled - - stage 6 of another group of
Enabled
earth fault overcurrent
protection
Enabling stage 6 of
another group of earth fault
Trp; overcurrent protection
65 A.50/51G6.Opt_Trp/Alm Trp - -
Alm operate to trip or alarm.
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE; The setting for selecting
ANSILTV; the inverse-time operation
ANSILT; characteristic curve of
66 A.50/51G6.Opt_Curve IECDefTime - -
IECN; stage 6 of another group of
IECV; earth fault overcurrent
IEC; protection.
IECE;

9
IECST;
IECLT;
IECDefTime;
UserDefine

9-62 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The setting for selecting
the inverse-time dropout
characteristic curve of
stage 6 of another group of
Inst; earth fault overcurrent
A.50/51G6.Opt_Curve_D
67 DefTime; Inst - - protection
ropOut
IDMT Inst: instantaneous
dropout
DefTime: definite-time
dropout
IDMT: inverse-time dropout
The time multiplier setting
of stage 6 of another group
68 A.50/51G6.TMS 0.04~ 20 1 - 0.001
of earth fault overcurrent
protection
The minimum operating
time setting of stage 6 of
69 A.50/51G6.tmin 0 ~10 0.02 s 0.001
another group of earth fault
overcurrent protection
The constant “k” of the
customized inverse-time
operation characteristic of
70 A.50/51G6.K 0.001~120 0.14 - 0.0001
stage 6 of another group of
earth fault overcurrent
protection
The constant “α” of the
customized inverse-time
operation characteristic of
71 A.50/51G6.Alpha 0.01 ~3 0.02 - 0.0001
stage 6 of another group of
earth fault overcurrent
protection
The constant “C” of the
customized inverse-time
9
operation characteristic of
72 A.50/51G6.C 0 ~1 0 - 0.0001
stage 6 of another group of
earth fault overcurrent
protection

9.2.4 Negative-sequence Overcurrent Protection Settings


 Access path:

MainMenu  Settings  Protection Settings  NegOC Settings

PCS-9611S Feeder Relay 9-63


Date: 2019-04-24
9 Settings

Table 9.2-4 Settings of negative-sequence overcurrent protection

Default
No. Settings Range Unit Step Description
value
The relay characteristic angle
of the direction control
1 50/51Q.DIR.RCA -180~179 45 deg 1
element of negative-sequence
overcurrent protection
The minimum boundary of the
50/51Q.DIR.phi_Min_ forward direction element of
2 10~90 90 deg 1
Fwd negative-sequence
overcurrent protection
The maximum boundary of the
50/51Q.DIR.phi_Max forward direction element of
3 10~90 90 deg 1
_Fwd negative-sequence
overcurrent protection
The minimum boundary of the
50/51Q.DIR.phi_Min_ reverse direction element of
4 10~90 90 deg 1
Rev negative-sequence
overcurrent protection
The maximum boundary of the
50/51Q.DIR.phi_Max reverse direction element of
5 10~90 90 deg 1
_Rev negative-sequence
overcurrent protection
The minimum operating
current setting for the direction
6 50/51Q.DIR.I_Min (0.05~1)In 0.05 - 0.001 control element of
negative-sequence
overcurrent protection
The minimum operating
voltage setting for the direction
7 50/51Q.DIR.U_Min 1.0~10.0 4 V 0.001 control element of
negative-sequence
overcurrent protection
9

9-64 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
Logic setting to determine the
behavior of
negative-sequence
overcurrent protection when
VT circuit supervision function
is enabled and VT circuit
failure happens.
Disabled;
8 50/51Q.En_VTS_Blk Disabled - - Disabled: negative-sequence
Enabled
overcurrent protection will not
effected by VT circuit failure
Enabled: voltage controlled
negative-sequence
overcurrent protection will be
blocked by VT circuit failure
signal
The current setting of stage 1
9 50/51Q1.I2_Set 0.05~200 15 A 0.001 of negative-sequence
overcurrent protection
The operating time setting of
10 50/51Q1.t_Op 0.03 ~100 0.1 s 0.001 stage 1 of negative-sequence
overcurrent protection
The dropout time setting of
11 50/51Q1.t_DropOut 0 ~100 0 s 0.001 stage 1 of negative-sequence
overcurrent protection
The setting used to select the
directional mode of stage 1 of
Non_Direction
negative-sequence
al Non_Directio
12 50/51Q1.Opt_Dir - - overcurrent protection.
Forward nal
1: no direction;
Reverse
2: forward direction;
3: reverse direction.

Disabled;
The logic setting
enabling/disabling the stage 1
for
9
13 50/51Q1.En Enabled - -
Enabled of negative-sequence
overcurrent protection
Enabling stage 1 of
negative-sequence
Trp; overcurrent protection operate
14 50/51Q1.Opt_Trp/Alm Trp - -
Alm to trip or alarm.
Trp: for tripping purpose
Alm: for alarm purpose

PCS-9611S Feeder Relay 9-65


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
The setting for selecting the
ANSILTV;
inverse-time operation
ANSILT;
15 50/51Q1.Opt_Curve IECDefTime - - characteristic curve of stage 1
IECN;
of negative-sequence
IECV;
overcurrent protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
characteristic curve of stage 1
Inst;
50/51Q1.Opt_Curve_ of negative-sequence
16 DefTime; Inst - -
DropOut overcurrent protection
IDMT
Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
17 50/51Q1.TMS 0.04~ 20 1 - 0.001 stage 1 of negative-sequence
overcurrent protection
The minimum operating time
setting of stage 1 of
18 50/51Q1.tmin 0 ~10 0.02 s 0.001
negative-sequence
overcurrent protection

9
The constant “k” of the
customized inverse-time
19 50/51Q1.K 0.001~120 0.14 - 0.0001 operation characteristic of
stage 1 of negative-sequence
overcurrent protection
The constant “α” of the
customized inverse-time
20 50/51Q1.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of
stage 1 of negative-sequence
overcurrent protection

9-66 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The constant “C” of the
customized inverse-time
21 50/51Q1.C 0 ~1 0 - 0.0001 operation characteristic of
stage 1 of negative-sequence
overcurrent protection
The current setting of stage 2
22 50/51Q2.I2_Set 0.05~200 15 A 0.001 of negative-sequence
overcurrent protection
The operating time setting of
23 50/51Q2.t_Op 0.03 ~100 0.1 s 0.001 stage 2 of negative-sequence
overcurrent protection
The dropout time setting of
24 50/51Q2.t_DropOut 0 ~100 0 s 0.001 stage 2 of negative-sequence
overcurrent protection
The setting used to select the
directional mode of stage 2 of
Non_Direction
negative-sequence
al Non_Directio
25 50/51Q2.Opt_Dir - - overcurrent protection.
Forward nal
1: no direction;
Reverse
2: forward direction;
3: reverse direction.
The logic setting for
Disabled; enabling/disabling the stage 2
26 50/51Q2.En Enabled - -
Enabled of negative-sequence
overcurrent protection
Enabling stage 2 of
negative-sequence
Trp; overcurrent protection operate
27 50/51Q2.Opt_Trp/Alm Trp - -
Alm to trip or alarm.
Trp: for tripping purpose
Alm: for alarm purpose

PCS-9611S Feeder Relay 9-67


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
The setting for selecting the
ANSILTV;
inverse-time operation
ANSILT;
28 50/51Q2.Opt_Curve IECDefTime - - characteristic curve of stage 2
IECN;
of negative-sequence
IECV;
overcurrent protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
characteristic curve of stage 2
Inst;
50/51Q2.Opt_Curve_ of negative-sequence
29 DefTime; Inst - -
DropOut overcurrent protection
IDMT
Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
30 50/51Q2.TMS 0.04~ 20 1 - 0.001 stage 2 of negative-sequence
overcurrent protection
The minimum operating time
setting of stage 2 of
31 50/51Q2.tmin 0 ~10 0.02 s 0.001
negative-sequence
overcurrent protection

9
The constant “k” of the
customized inverse-time
32 50/51Q2.K 0.001~120 0.14 - 0.0001 operation characteristic of
stage 2 of negative-sequence
overcurrent protection
The constant “α” of the
customized inverse-time
33 50/51Q2.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of
stage 2 of negative-sequence
overcurrent protection

9-68 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The constant “C” of the
customized inverse-time
34 50/51Q2.C 0 ~1 0 - 0.0001 operation characteristic of
stage 2 of negative-sequence
overcurrent protection

9.2.5 Sensitive Earth Fault Protection Settings


 Access path:

MainMenu  Settings  Protection Settings  SEF Settings

Table 9.2-5 Settings of sensitive earth fault protection

Default
No. Settings Range Unit Step Description
value
The relay characteristic angle of
1 50/51SEF.DIR.RCA -180~179 45 deg 1 the direction control element of
sensitive earth fault protection
The minimum boundary of the
50/51SEF.DIR.phi_Mi
2 10~90 90 deg 1 forward direction element of
n_Fwd
sensitive earth fault protection
The maximum boundary of the
50/51SEF.DIR.phi_M
3 10~90 90 deg 1 forward direction element of
ax_Fwd
sensitive earth fault protection
The minimum boundary of the
50/51SEF.DIR.phi_Mi
4 10~90 90 deg 1 reverse direction element of
n_Rev
sensitive earth fault protection
The maximum boundary of the
50/51SEF.DIR.phi_M
5 10~90 90 deg 1 reverse direction element of
ax_Rev
sensitive earth fault protection
The minimum operating current
setting for the direction control
6 50/51SEF.DIR.I_Min (0.05~1)In 0.05 - 0.001
element of sensitive earth fault
protection 9
The minimum operating voltage
setting for the direction control
7 50/51SEF.DIR.U_Min 1.0~10.0 4 V 0.001
element of sensitive earth fault
protection

PCS-9611S Feeder Relay 9-69


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
Logic setting to determine the
behavior of sensitive earth fault
protection when VT circuit
supervision function is enabled
and VT circuit failure happens.
50/51SEF.En_VTS_Bl Disabled; Disabled: sensitive earth fault
8 Disabled - -
k Enabled protection will not effected by VT
circuit failure
Enabled: voltage controlled
sensitive earth fault protection
will be blocked by VT circuit
failure signal
The current setting of stage 1 of
9 50/51SEF1.3I0_Set 0.005~2 1 A 0.001
sensitive earth fault protection
The operating time setting of
10 50/51SEF1.t_Op 0 ~100 0.1 s 0.001 stage 1 of sensitive earth fault
protection
The dropout time setting of
50/51SEF1.t_DropOu
11 0 ~100 0 s 0.001 stage 1 of sensitive earth fault
t
protection
Non_Directional The setting used to select the
Non_Dire
12 50/51SEF1.Opt_Dir Forward - - directional mode of stage 1 of
ctional
Reverse sensitive earth fault protection.
The logic setting for
Disabled;
13 50/51SEF1.En Enabled - - enabling/disabling the stage 1 of
Enabled
sensitive earth fault protection
Enabling stage 1 of sensitive
earth fault protection operate to
50/51SEF1.Opt_Trp/ Trp;
14 Trp - - trip or alarm.
Alm Alm
Trp: for tripping purpose
Alm: for alarm purpose

9-70 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
50/51SEF1.Opt_Curv ANSILT; IECDefTi inverse-time operation
15 - -
e IECN; me characteristic curve of stage 1 of
IECV; sensitive earth fault protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 1 of
50/51SEF1.Opt_Curv
16 DefTime; Inst - - sensitive earth fault protection
e_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
17 50/51SEF1.TMS 0.04~ 20 1 - 0.001 stage 1 of sensitive earth fault
protection
The minimum operating time
18 50/51SEF1.tmin 0 ~10 0.02 s 0.001 setting of stage 1 of sensitive
earth fault protection
The constant “k” of the
customized inverse-time
19 50/51SEF1.K 0.001~120 0.14 - 0.0001 operation characteristic of stage
1 of sensitive earth fault
9
protection
The constant “α” of the
customized inverse-time
20 50/51SEF1.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of stage
1 of sensitive earth fault
protection

PCS-9611S Feeder Relay 9-71


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The constant “C” of the
customized inverse-time
21 50/51SEF1.C 0 ~1 0 - 0.0001 operation characteristic of stage
1 of sensitive earth fault
protection
The current setting of stage 2 of
22 50/51SEF2.3I0_Set 0.005~2 1 A 0.001
sensitive earth fault protection
The operating time setting of
23 50/51SEF2.t_Op 0 ~100 0.1 s 0.001 stage 2 of sensitive earth fault
protection
The dropout time setting of
50/51SEF2.t_DropOu
24 0 ~100 0 s 0.001 stage 2 of sensitive earth fault
t
protection
Non_Directional The setting used to select the
Non_Dire
25 50/51SEF2.Opt_Dir Forward - - directional mode of stage 2 of
ctional
Reverse sensitive earth fault protection.
The logic setting for
Disabled;
26 50/51SEF2.En Enabled - - enabling/disabling the stage 2 of
Enabled
sensitive earth fault protection
Enabling stage 2 of sensitive
earth fault protection operate to
50/51SEF2.Opt_Trp/ Trp;
27 Trp - - trip or alarm.
Alm Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the

9 28
50/51SEF2.Opt_Curv
e
ANSILT;
IECN;
IECDefTi
me
- -
inverse-time operation
characteristic curve of stage 2 of
IECV; sensitive earth fault protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine

9-72 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 2 of
50/51SEF2.Opt_Curv
29 DefTime; Inst - - sensitive earth fault protection
e_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
30 50/51SEF2.TMS 0.04~ 20 1 - 0.001 stage 2 of sensitive earth fault
protection
The minimum operating time
31 50/51SEF2.tmin 0 ~10 0.02 s 0.001 setting of stage 2 of sensitive
earth fault protection
The constant “k” of the
customized inverse-time
32 50/51SEF2.K 0.001~120 0.14 - 0.0001 operation characteristic of stage
2 of sensitive earth fault
protection
The constant “α” of the
customized inverse-time
33 50/51SEF2.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of stage
2 of sensitive earth fault
protection
The constant “C” of the
customized inverse-time
34 50/51SEF2.C 0 ~1 0 - 0.0001 operation characteristic of stage
2 of sensitive earth fault
protection
The current setting of stage 3 of
35 50/51SEF3.3I0_Set 0.005~2 1 A 0.001
sensitive earth fault protection
The operating time setting of
36 50/51SEF3.t_Op 0 ~100 0.1 s 0.001 stage 3 of sensitive earth fault
protection
9
The dropout time setting of
50/51SEF3.t_DropOu
37 0 ~100 0 s 0.001 stage 3 of sensitive earth fault
t
protection
Non_Directional The setting used to select the
Non_Dire
38 50/51SEF3.Opt_Dir Forward - - directional mode of stage 3 of
ctional
Reverse sensitive earth fault protection.
The logic setting for
Disabled;
39 50/51SEF3.En Enabled - - enabling/disabling the stage 3 of
Enabled
sensitive earth fault protection

PCS-9611S Feeder Relay 9-73


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
Enabling stage 3 of sensitive
earth fault protection operate to
50/51SEF3.Opt_Trp/ Trp;
40 Trp - - trip or alarm.
Alm Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
50/51SEF3.Opt_Curv ANSILT; IECDefTi inverse-time operation
41 - -
e IECN; me characteristic curve of stage 3 of
IECV; sensitive earth fault protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 3 of
50/51SEF3.Opt_Curv
42 DefTime; Inst - - sensitive earth fault protection
e_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
43 50/51SEF3.TMS 0.04~ 20 1 - 0.001 stage 3 of sensitive earth fault
protection

9
The minimum operating time
44 50/51SEF3.tmin 0 ~10 0.02 s 0.001 setting of stage 3 of sensitive
earth fault protection
The constant “k” of the
customized inverse-time
45 50/51SEF3.K 0.001~120 0.14 - 0.0001 operation characteristic of stage
3 of sensitive earth fault
protection

9-74 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The constant “α” of the
customized inverse-time
46 50/51SEF3.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of stage
3 of sensitive earth fault
protection
The constant “C” of the
customized inverse-time
47 50/51SEF3.C 0 ~1 0 - 0.0001 operation characteristic of stage
3 of sensitive earth fault
protection
The current setting of stage 4 of
48 50/51SEF4.3I0_Set 0.005~2 1 A 0.001
sensitive earth fault protection
The operating time setting of
49 50/51SEF4.t_Op 0 ~100 0.1 s 0.001 stage 4 of sensitive earth fault
protection
The dropout time setting of
50/51SEF4.t_DropOu
50 0 ~100 0 s 0.001 stage 4 of sensitive earth fault
t
protection
Non_Directional The setting used to select the
Non_Dire
51 50/51SEF4.Opt_Dir Forward - - directional mode of stage 4 of
ctional
Reverse sensitive earth fault protection.
The logic setting for
Disabled;
52 50/51SEF4.En Enabled - - enabling/disabling the stage 4 of
Enabled
sensitive earth fault protection
Enabling stage 4 of sensitive
earth fault protection operate to
50/51SEF4.Opt_Trp/ Trp;
53 Trp - - trip or alarm.
Alm Alm
Trp: for tripping purpose
Alm: for alarm purpose

PCS-9611S Feeder Relay 9-75


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
50/51SEF4.Opt_Curv ANSILT; IECDefTi inverse-time operation
54 - -
e IECN; me characteristic curve of stage 4 of
IECV; sensitive earth fault protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 4 of
50/51SEF4.Opt_Curv
55 DefTime; Inst - - sensitive earth fault protection
e_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
56 50/51SEF4.TMS 0.04~ 20 1 - 0.001 stage 4 of sensitive earth fault
protection
The minimum operating time
57 50/51SEF4.tmin 0 ~10 0.02 s 0.001 setting of stage 4 of sensitive
earth fault protection
The constant “k” of the
customized inverse-time

9
58 50/51SEF4.K 0.001~120 0.14 - 0.0001 operation characteristic of stage
4 of sensitive earth fault
protection
The constant “α” of the
customized inverse-time
59 50/51SEF4.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of stage
4 of sensitive earth fault
protection

9-76 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The constant “C” of the
customized inverse-time
60 50/51SEF4.C 0 ~1 0 - 0.0001 operation characteristic of stage
4 of sensitive earth fault
protection
The current setting of stage 5 of
61 50/51SEF5.3I0_Set 0.005~2 1 A 0.001
sensitive earth fault protection
The operating time setting of
62 50/51SEF5.t_Op 0 ~100 0.1 s 0.001 stage 5 of sensitive earth fault
protection
The dropout time setting of
50/51SEF5.t_DropOu
63 0 ~100 0 s 0.001 stage 5 of sensitive earth fault
t
protection
Non_Directional The setting used to select the
Non_Dire
64 50/51SEF5.Opt_Dir Forward - - directional mode of stage 5 of
ctional
Reverse sensitive earth fault protection.
The logic setting for
Disabled;
65 50/51SEF5.En Enabled - - enabling/disabling the stage 5 of
Enabled
sensitive earth fault protection
Enabling stage 5 of sensitive
earth fault protection operate to
50/51SEF5.Opt_Trp/ Trp;
66 Trp - - trip or alarm.
Alm Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the

67
50/51SEF5.Opt_Curv
e
ANSILT;
IECN;
IECDefTi
me
- -
inverse-time operation
characteristic curve of stage 5 of
9
IECV; sensitive earth fault protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine

PCS-9611S Feeder Relay 9-77


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 5 of
50/51SEF5.Opt_Curv
68 DefTime; Inst - - sensitive earth fault protection
e_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
69 50/51SEF5.TMS 0.04~ 20 1 - 0.001 stage 5 of sensitive earth fault
protection
The minimum operating time
70 50/51SEF5.tmin 0 ~10 0.02 s 0.001 setting of stage 5 of sensitive
earth fault protection
The constant “k” of the
customized inverse-time
71 50/51SEF5.K 0.001~120 0.14 - 0.0001 operation characteristic of stage
5 of sensitive earth fault
protection
The constant “α” of the
customized inverse-time
72 50/51SEF5.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of stage
5 of sensitive earth fault
protection
The constant “C” of the
customized inverse-time
73 50/51SEF5.C 0 ~1 0 - 0.0001 operation characteristic of stage
5 of sensitive earth fault
protection
The current setting of stage 6 of
74 50/51SEF6.3I0_Set 0.005~2 1 A 0.001
sensitive earth fault protection
The operating time setting of

9 75 50/51SEF6.t_Op 0 ~100 0.1 s 0.001 stage 6 of sensitive earth fault


protection
The dropout time setting of
50/51SEF6.t_DropOu
76 0 ~100 0 s 0.001 stage 6 of sensitive earth fault
t
protection
Non_Directional The setting used to select the
Non_Dire
77 50/51SEF6.Opt_Dir Forward - - directional mode of stage 6 of
ctional
Reverse sensitive earth fault protection.
The logic setting for
Disabled;
78 50/51SEF6.En Enabled - - enabling/disabling the stage 6 of
Enabled
sensitive earth fault protection

9-78 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
Enabling stage 6 of sensitive
earth fault protection operate to
50/51SEF6.Opt_Trp/ Trp;
79 Trp - - trip or alarm.
Alm Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
50/51SEF6.Opt_Curv ANSILT; IECDefTi inverse-time operation
80 - -
e IECN; me characteristic curve of stage 6 of
IECV; sensitive earth fault protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 6 of
50/51SEF6.Opt_Curv
81 DefTime; Inst - - sensitive earth fault protection
e_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
82 50/51SEF6.TMS 0.04~ 20 1 - 0.001 stage 6 of sensitive earth fault
protection

83 50/51SEF6.tmin 0 ~10 0.02 s 0.001


The minimum operating time
setting of stage 6 of sensitive
9
earth fault protection
The constant “k” of the
customized inverse-time
84 50/51SEF6.K 0.001~120 0.14 - 0.0001 operation characteristic of stage
6 of sensitive earth fault
protection

PCS-9611S Feeder Relay 9-79


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The constant “α” of the
customized inverse-time
85 50/51SEF6.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of stage
6 of sensitive earth fault
protection
The constant “C” of the
customized inverse-time
86 50/51SEF6.C 0 ~1 0 - 0.0001 operation characteristic of stage
6 of sensitive earth fault
protection

9.2.6 RMS Overcurrent Protection Settings


 Access path:

MainMenu  Settings  Protection Settings  RMS OC Settings

Table 9.2-6 Settings of RMS overcurrent protection

Default
No. Settings Range Unit Step Description
value
The current setting of stage 1 of RMS
1 50/51R1.I_Set 0.05~200 15 A 0.001
overcurrent protection
The operating time setting of stage 1 of
2 50/51R1.t_Op 0 ~100 0.1 s 0.001
RMS overcurrent protection
The dropout time setting of stage 1 of
3 50/51R1.t_DropOut 0 ~100 0 s 0.001
RMS overcurrent protection
Disabled; The logic setting for enabling/disabling the
4 50/51R1.En Enabled - -
Enabled stage 1 of RMS overcurrent protection
Enabling stage 1 of RMS overcurrent
Trp; protection operate to trip or alarm.
5 50/51R1.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose
Alm: for alarm purpose
The current setting of stage 2 of RMS
9 6 50/51R2.I_Set 0.05~200 15 A 0.001
overcurrent protection
The operating time setting of stage 2 of
7 50/51R2.t_Op 0 ~100 0.1 s 0.001
RMS overcurrent protection
The dropout time setting of stage 2 of
8 50/51R2.t_DropOut 0 ~100 0 s 0.001
RMS overcurrent protection
Disabled; The logic setting for enabling/disabling the
9 50/51R2.En Enabled - -
Enabled stage 2 of RMS overcurrent protection

9-80 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
Enabling stage 2 of RMS overcurrent
Trp; protection operate to trip or alarm.
10 50/51R2.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose
Alm: for alarm purpose

9.2.7 Phase Overvoltage Protection Settings


 Access path:

MainMenu  Settings  Protection Settings  OV Settings

Table 9.2-7 Settings of phase overvoltage protection

Default
No. Settings Range Unit Step Description
value
Option of phase-to-phase
voltage or phase voltage for
Up; overvoltage protection
1 59P.Opt_Up/Upp Upp - -
Upp Up: phase voltage
Upp: phase-to-phase
voltage
Option of 1-out-of-3 mode or
3-out-of-3 mode for
3P;
2 59P.Opt_1P/3P 3P - - overvoltage protection
1P
3P: 3-out-of-3 mode
1P: 1-out-of-3 mode
The voltage setting of stage
3 59P1.U_Set 57.7~200 115 V 0.001 1 of phase overvoltage
protection
The dropout coefficient of
4 59P1.K_DropOut 0.93 ~1.00 0.98 - 0.001 stage 1 of phase
overvoltage protection
The operating time setting of
5 59P1.t_Op 0.1 ~100 1 s 0.001 stage 1 of phase
overvoltage protection 9
The dropout time setting of
6 59P1.t_DropOut 0 ~100 0 s 0.001 stage 1 of phase
overvoltage protection
The logic setting for
Disabled; enabling/disabling the stage
7 59P1.En Enabled - -
Enabled 1 of phase overvoltage
protection

PCS-9611S Feeder Relay 9-81


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
Enabling stage 1 of phase
overvoltage protection
Trp;
8 59P1.Opt_Trp/Alm Trp - - operate to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose
The setting for selecting the
ANSIDefTime;
inverse-time operation
IECDefTime;
9 59P1.Opt_Curve IECDefTime - - characteristic curve of stage
UserDefine;
1 of phase overvoltage
InvTime_U
protection.
The setting for selecting the
inverse-time dropout
characteristic curve of stage
Inst; 1 of phase overvoltage
10 59P1.Opt_Curve_DropOut Inst - -
DefTime protection
Inst: instantaneous dropout
DefTime: definite-time
dropout
The time multiplier setting of
11 59P1.TMS 0.04~ 20 1 - 0.001 stage 1 of phase
overvoltage protection
The minimum operating time
12 59P1.tmin 0 ~10 0.02 s 0.001 setting of stage 1 of phase
overvoltage protection
The constant “k” of the
customized inverse-time
13 59P1.K 0.001~120 1 - 0.0001 operation characteristic of
stage 1 of phase
overvoltage protection
The constant “α” of the
customized inverse-time

9 14 59P1.Alpha 0.01 ~3 1 - 0.0001 operation characteristic of


stage 1 of phase
overvoltage protection
The constant “C” of the
customized inverse-time
15 59P1.C 0 ~1 0 - 0.0001 operation characteristic of
stage 1 of phase
overvoltage protection
The voltage setting of stage
16 59P2.U_Set 57.7~200 115 V 0.001 2 of phase overvoltage
protection

9-82 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The dropout coefficient of
17 59P2.K_DropOut 0.93 ~1.00 0.98 - 0.001 stage 2 of phase
overvoltage protection
The operating time setting of
18 59P2.t_Op 0.1 ~100 1 s 0.001 stage 2 of phase
overvoltage protection
The dropout time setting of
19 59P2.t_DropOut 0 ~100 0 s 0.001 stage 2 of phase
overvoltage protection
The logic setting for
Disabled; enabling/disabling the stage
20 59P2.En Enabled - -
Enabled 2 of phase overvoltage
protection
Enabling stage 2 of phase
overvoltage protection
Trp;
21 59P2.Opt_Trp/Alm Trp - - operate to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose
The setting for selecting the
ANSIDefTime;
inverse-time operation
IECDefTime;
22 59P2.Opt_Curve IECDefTime - - characteristic curve of stage
UserDefine;
2 of phase overvoltage
InvTime_U
protection.
The setting for selecting the
inverse-time dropout
characteristic curve of stage
Inst; 2 of phase overvoltage
23 59P2.Opt_Curve_DropOut Inst - -
DefTime protection
Inst: instantaneous dropout
DefTime: definite-time
dropout

24 59P2.TMS 0.04~ 20 1 - 0.001


The time multiplier setting of
stage 2 of phase
9
overvoltage protection
The minimum operating time
25 59P2.tmin 0 ~10 0.02 s 0.001 setting of stage 2 of phase
overvoltage protection
The constant “k” of the
customized inverse-time
26 59P2.K 0.001~120 1 - 0.0001 operation characteristic of
stage 2 of phase
overvoltage protection

PCS-9611S Feeder Relay 9-83


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The constant “α” of the
customized inverse-time
27 59P2.Alpha 0.01 ~3 1 - 0.0001 operation characteristic of
stage 2 of phase
overvoltage protection
The constant “C” of the
customized inverse-time
28 59P2.C 0 ~1 0 - 0.0001 operation characteristic of
stage 2 of phase
overvoltage protection

9.2.8 Residual Overvoltage Protection Settings


 Access path:

MainMenu  Settings  Protection Settings  ROV Settings

Table 9.2-8 Settings of residual overvoltage protection

Default
No. Settings Range Unit Step Description
value
Option of measured residual voltage or
calculated residual voltage for residual
Ext;
1 59G.Opt_3U0 Cal - - overvoltage protection
Cal
Ext: the measured residual voltage
Cal: the calculated residual voltage
The voltage setting of stage 1 of residual
2 59G1.3U0_Set 1~200 50 V 0.001
overvoltage protection
The dropout coefficient of stage 1 of residual
3 59G1.K_DropOut 0.93 ~1 0.98 - 0.001
overvoltage protection
The operating time setting of stage 1 of
4 59G1.t_Op 0.1 ~100 1 s 0.001
residual overvoltage protection
The dropout time setting of stage 1 of
5 59G1.t_DropOut 0 ~100 0 s 0.001
residual overvoltage protection
9 The logic setting for enabling/disabling the
Disabled; stage 1 of residual overvoltage protection
6 59G1.En Enabled - -
Enabled 0: disabling
1: enabling
Enabling stage 1 of residual overvoltage
Trp; protection operate to trip or alarm.
7 59G1.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose
Alm: for alarm purpose
The voltage setting of stage 2 of residual
8 59G2.3U0_Set 1~200 50 V 0.001
overvoltage protection

9-84 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The dropout coefficient of stage 2 of residual
9 59G2.K_DropOut 0.93 ~1 0.98 - 0.001
overvoltage protection
The operating time setting of stage 2 of
10 59G2.t_Op 0.1 ~100 1 s 0.001
residual overvoltage protection
The dropout time setting of stage 2 of
11 59G2.t_DropOut 0 ~100 0 s 0.001
residual overvoltage protection
The logic setting for enabling/disabling the
Disabled; stage 2 of residual overvoltage protection
12 59G2.En Enabled - -
Enabled 0: disabling
1: enabling
Enabling stage 2 of residual overvoltage
Trp; protection operate to trip or alarm.
13 59G2.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose
Alm: for alarm purpose

9.2.9 Negative-sequence Overvoltage Protection Settings


 Access path:

MainMenu  Settings  Protection Settings  NegOV Settings

Table 9.2-9 Settings of negative-sequence overvoltage protection

No. Setting Range Default Unit Step Description


The voltage setting of the stage 1 of
1 59Q1.U2_Set 2~100 15 V 0.001
negative-sequence overvoltage protection
The dropout coefficient setting of the stage
2 59Q1.K_DropOut 0.93~1 0.98 - 0.001 1 of negative-sequence overvoltage
protection
The time setting of the stage 1 of
3 59Q1.t_Op 0.1~100 1 s 0.001
negative-sequence overvoltage protection
The dropout time setting of the stage 1 of
4 59Q1.t_DropOut 0~100 0 s 0.001
negative-sequence overvoltage protection

9
Disabled; The logic setting of the stage 1 of
5 59Q1.En Enabled - -
Enabled negative-sequence overvoltage protection
Enabling stage 1 of negative-sequence
Trp; overvoltage operate to trip or alarm.
6 59Q1.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose
Alm: for alarm purpose
The voltage setting of the stage 2 of
7 59Q2.U2_Set 2~100 15 V 0.001
negative-sequence overvoltage protection
The dropout coefficient setting of the stage
8 59Q2.K_DropOut 0.93~1 0.98 - 0.001 2 of negative-sequence overvoltage
protection

PCS-9611S Feeder Relay 9-85


Date: 2019-04-24
9 Settings

The time setting of the stage 2 of


9 59Q2.t_Op 0.1~100 1 s 0.001
negative-sequence overvoltage protection
The dropout time setting of the stage 2 of
10 59Q2.t_DropOut 0~100 0 s 0.001
negative-sequence overvoltage protection
Disabled; The logic setting of the stage 2 of
11 59Q2.En Enabled - -
Enabled negative-sequence overvoltage protection
Enabling stage 2 of negative-sequence
Trp; overvoltage operate to trip or alarm.
12 59Q2.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose
Alm: for alarm purpose

9.2.10 Positive-sequence Overvoltage Protection Settings


 Access path:

MainMenu  Settings  Protection Settings  PosOV Settings

Table 9.2-10 Settings of positive-sequence overvoltage protection

No. Setting Range Default Unit Step Description


The voltage setting of the
1 59Pos.U1_Set 2~100 60 V 0.001
positive-sequence overvoltage protection
The dropout coefficient setting of the
2 59Pos.K_DropOut 0.93~1 0.98 - 0.001
positive-sequence overvoltage protection
The time setting of the positive-sequence
3 59Pos.t_Op 0.1~100 1 s 0.001
overvoltage protection
The dropout time setting of the
4 59Pos.t_DropOut 0~100 0 s 0.001
positive-sequence overvoltage protection
Disabled; The logic setting of the positive-sequence
5 59Pos.En Enabled - -
Enabled overvoltage protection
Enabling the positive-sequence
Trp; overvoltage operate to trip or alarm.
6 59Pos.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose
Alm: for alarm purpose

9.2.11 Phase Undervoltage Protection Settings


9  Access path:

MainMenu  Settings  Protection Settings  UV Settings

9-86 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Table 9.2-11 Settings of phase undervoltage protection

Default
No. Settings Range Unit Step Description
value
Option of phase-to-phase
voltage or phase voltage
for stage x of
Up;
1 27P.Opt_Up/Upp Upp - - undervoltage protection
Upp
Up: phase voltage
Upp: phase-to-phase
voltage
Option of 1-out-of-3 mode
or 3-out-of-3 mode for
3P; stage x of undervoltage
2 27P.Opt_1P/3P 3P - -
1P protection
3P: 3-out-of-3 mode
1P: 1-out-of-3 mode
Breaker closed position
check mode
None: no check
Curr: check the current
None; CBPos: check the
Curr; normally open auxiliary
3 27P.Opt_LogicMode CBPos; Curr - - contact
CurrOrCBPos; CurrOrCBPos: check the
CurrAndCBPos current and normally open
auxiliary contact
CurrAndCBPos: check the
current or normally open
auxiliary contact
The voltage setting of
4 27P1.U_Set 5~120 80 V 0.001 stage 1 of phase
undervoltage protection
The dropout coefficient of
5 27P1.K_DropOut 1~1.2 1.03 - 0.001 stage 1 of phase 9
undervoltage protection
The operating time setting
6 27P1.t_Op 0.1 ~100 1 s 0.001 of stage 1 of phase
undervoltage protection
The dropout time setting
7 27P1.t_DropOut 0 ~100 0 s 0.001 of stage 1 of phase
undervoltage protection

PCS-9611S Feeder Relay 9-87


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
Logic setting to determine
the behavior of stage 1 of
phase undervoltage
protection when VT circuit
supervision function is
Disabled;
8 27P1.En_VTS_Blk Disabled - - enabled and VT circuit
Enabled
failure happens.
0: it is not effected by VT
circuit failure
1: it will be blocked by VT
circuit failure signal
The logic setting for
enabling/disabling the
Disabled; stage 1 of phase
9 27P1.En Enabled - -
Enabled undervoltage protection
0: disabling
1: enabling
Enabling stage 1 of phase
undervoltage protection
Trp;
10 27P1.Opt_Trp/Alm Trp - - operate to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose
The setting for selecting
ANSIDefTime;
the inverse-time operation
IECDefTime;
11 27P1.Opt_Curve IECDefTime - - characteristic curve of
UserDefine;
stage 1 of phase
InvTime_U
undervoltage protection.
The setting for selecting
the inverse-time dropout
characteristic curve of
stage 1 of phase
Inst;

9
12 27P1.Opt_Curve_DropOut Inst - - undervoltage protection
DefTime
Inst: instantaneous
dropout
DefTime: definite-time
dropout
The time multiplier setting
13 27P1.TMS 0.04~ 20 1 - 0.001 of stage 1 of phase
undervoltage protection

9-88 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The minimum operating
time setting of stage 1 of
14 27P1.tmin 0.03 ~10 0.03 s 0.001
phase undervoltage
protection
The constant “k” of the
customized inverse-time
15 27P1.K 0.001~120 0.14 - 0.0001 operation characteristic of
stage 1 of phase
undervoltage protection
The constant “α” of the
customized inverse-time
16 27P1.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of
stage 1 of phase
undervoltage protection
The constant “C” of the
customized inverse-time
17 27P1.C 0 ~1 0 - 0.0001 operation characteristic of
stage 1 of phase
undervoltage protection
The voltage setting of
18 27P2.U_Set 5~120 80 V 0.001 stage 2 of phase
undervoltage protection
The dropout coefficient of
19 27P2.K_DropOut 1~1.2 1.03 - 0.001 stage 2 of phase
undervoltage protection
The operating time setting
20 27P2.t_Op 0.1 ~100 1 s 0.001 of stage 2 of phase
undervoltage protection
The dropout time setting
21 27P2.t_DropOut 0 ~100 0 s 0.001 of stage 2 of phase
undervoltage protection
Logic setting to determine
the behavior of stage 2 of
9
phase undervoltage
protection when VT circuit
supervision function is
Disabled;
22 27P2.En_VTS_Blk Disabled - - enabled and VT circuit
Enabled
failure happens.
0: it is not effected by VT
circuit failure
1: it will be blocked by VT
circuit failure signal

PCS-9611S Feeder Relay 9-89


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The logic setting for
enabling/disabling the
Disabled; stage 2 of phase
23 27P2.En Enabled - -
Enabled undervoltage protection
0: disabling
1: enabling
Enabling stage 2 of phase
undervoltage protection
Trp;
24 27P2.Opt_Trp/Alm Trp - operate to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose
The setting for selecting
ANSIDefTime;
the inverse-time operation
IECDefTime;
25 27P2.Opt_Curve IECDefTime - - characteristic curve of
UserDefine;
stage 2 of phase
InvTime_U
undervoltage protection.
The setting for selecting
the inverse-time dropout
characteristic curve of
stage 2 of phase
Inst;
26 27P2.Opt_Curve_DropOut Inst - - undervoltage protection
DefTime
Inst: instantaneous
dropout
DefTime: definite-time
dropout
The time multiplier setting
27 27P2.TMS 0.04~ 20 1 0.001 of stage 2 of phase
undervoltage protection
The minimum operating
time setting of stage 2 of
28 27P2.tmin 0.03 ~10 0.03 s 0.001
phase undervoltage

9 protection
The constant “k” of the
customized inverse-time
29 27P2.K 0.001~120 0.14 - 0.0001 operation characteristic of
stage 2 of phase
undervoltage protection
The constant “α” of the
customized inverse-time
30 27P2.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of
stage 2 of phase
undervoltage protection

9-90 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Default
No. Settings Range Unit Step Description
value
The constant “C” of the
customized inverse-time
31 27P2.C 0 ~1 0 - 0.0001 operation characteristic of
stage 2 of phase
undervoltage protection

9.2.12 Frequency Protection Settings


 Access path:

MainMenu  Settings  Protection Settings  FreqProt Settings

Table 9.2-12 Settings of overfrequency protection

No. Setting Range Default Unit Step Description


The setting of the low voltage blocking
1 81.Upp_Blk 10~150 70 V 0.001 element of the frequency protection
(phase-to-phase voltage)
The frequency setting of the stage 1 of
2 81O1.f_Set 50~65 52 Hz 0.001
overfrequency protection
The time setting of the stage 1 of
3 81O1.t_Op 0.1~100 0.3 s 0.001
overfrequency protection
Disabled; The logic setting of the stage 1 of
4 81O1.En Enabled - -
Enabled overfrequency protection
The frequency setting of the stage 2 of
5 81O2.f_Set 50~65 52 Hz 0.001
overfrequency protection
The time setting of the stage 2 of
6 81O2.t_Op 0.1~100 0.3 s 0.001
overfrequency protection
Disabled; The logic setting of the stage 2 of
7 81O2.En Enabled - -
Enabled overfrequency protection
The frequency setting of the stage 3 of
8 81O3.f_Set 50~65 52 Hz 0.001
overfrequency protection
The time setting of the stage 3 of
9 81O3.t_Op 0.1~100 0.3 s 0.001

9
overfrequency protection
Disabled; The logic setting of the stage 3 of
10 81O3.En Enabled - -
Enabled overfrequency protection
The frequency setting of the stage 4 of
11 81O4.f_Set 50~65 52 Hz 0.001
overfrequency protection
The time setting of the stage 4 of
12 81O4.t_Op 0.1~100 0.3 s 0.001
overfrequency protection
Disabled; The logic setting of the stage 4 of
13 81O4.En Enabled - -
Enabled overfrequency protection
The frequency setting of the stage 5 of
14 81O5.f_Set 50~65 52 Hz 0.001
overfrequency protection

PCS-9611S Feeder Relay 9-91


Date: 2019-04-24
9 Settings

The time setting of the stage 5 of


15 81O5.t_Op 0.1~100 0.3 s 0.001
overfrequency protection
Disabled; The logic setting of the stage 5 of
16 81O5.En Enabled - -
Enabled overfrequency protection
The frequency setting of the stage 6 of
17 81O6.f_Set 50~65 52 Hz 0.001
overfrequency protection
The time setting of the stage 6 of
18 81O6.t_Op 0.1~100 0.3 s 0.001
overfrequency protection
Disabled; The logic setting of the stage 6 of
19 81O6.En Enabled - -
Enabled overfrequency protection
The frequency setting of the stage 1 of
26 81U1.f_Set 45~60 48 Hz 0.001
underfrequency protection
The time setting of the stage 1 of
27 81U1.t_Op 0.1~100 0.3 s 0.001
underfrequency protection
Disabled; The logic setting of the stage 1 of
28 81U1.En Enabled - -
Enabled underfrequency protection
The frequency setting of the stage 2 of
29 81U2.f_Set 45~60 48 Hz 0.001
underfrequency protection
The time setting of the stage 2 of
30 81U2.t_Op 0.1~100 0.3 s 0.001
underfrequency protection
Disabled; The logic setting of the stage 2 of
31 81U2.En Enabled - -
Enabled underfrequency protection
The frequency setting of the stage 3 of
32 81U3.f_Set 45~60 48 Hz 0.001
underfrequency protection
The time setting of the stage 3 of
33 81U3.t_Op 0.1~100 0.3 s 0.001
underfrequency protection
Disabled; The logic setting of the stage 3 of
34 81U3.En Enabled - -
Enabled underfrequency protection
The frequency setting of the stage 4 of
35 81U4.f_Set 45~60 48 Hz 0.001
underfrequency protection
The time setting of the stage 4 of
36 81U4.t_Op 0.1~100 0.3 s 0.001
underfrequency protection
Disabled; The logic setting of the stage 4 of
37 81U4.En Enabled - -
9 Enabled underfrequency protection
The frequency setting of the stage 5 of
38 81U5.f_Set 45~60 48 Hz 0.001
underfrequency protection
The time setting of the stage 5 of
39 81U5.t_Op 0.1~100 0.3 s 0.001
underfrequency protection
Disabled; The logic setting of the stage 5 of
40 81U5.En Enabled - -
Enabled underfrequency protection
The frequency setting of the stage 6 of
41 81U6.f_Set 45~60 48 Hz 0.001
underfrequency protection
The time setting of the stage 6 of
42 81U6.t_Op 0.1~100 0.3 s 0.001
underfrequency protection

9-92 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Disabled; The logic setting of the stage 6 of


43 81U6.En Enabled - -
Enabled underfrequency protection
The rate-of-change setting of the stage x of
44 81R1.df/dt_Set -5~5 0.5 Hz/s 0.001
frequency rate-of-change protection
The time setting of the stage x of frequency
45 81R1.t_Op 0.1~100 0.1 s 0.001
rate-of-change protection
The pickup frequency setting of the stage x
46 81R1.f_Pkp 45~65 50 Hz 0.001
of frequency rate-of-change protection
Disabled; The logic setting of the stage x of frequency
47 81R1.En Enabled - -
Enabled rate-of-change protection
The rate-of-change setting of the stage 1 of
48 81R2.df/dt_Set -5~5 0.5 Hz/s 0.001
frequency rate-of-change protection
The time setting of the stage 1 of frequency
49 81R2.t_Op 0.1~100 0.1 s 0.001
rate-of-change protection
The pickup frequency setting of the stage 1
50 81R2.f_Pkp 45~65 50 Hz 0.001
of frequency rate-of-change protection
Disabled; The logic setting of the stage 1 of frequency
51 81R2.En Enabled - -
Enabled rate-of-change protection
The rate-of-change setting of the stage 2 of
52 81R3.df/dt_Set -5~5 0.5 Hz/s 0.001
frequency rate-of-change protection
The time setting of the stage 2 of frequency
53 81R3.t_Op 0.1~100 0.1 s 0.001
rate-of-change protection
The pickup frequency setting of the stage 2
54 81R3.f_Pkp 45~65 50 Hz 0.001
of frequency rate-of-change protection
Disabled; The logic setting of the stage 2 of frequency
55 81R3.En Enabled - -
Enabled rate-of-change protection
The rate-of-change setting of the stage 3 of
56 81R4.df/dt_Set -5~5 0.5 Hz/s 0.001
frequency rate-of-change protection
The time setting of the stage 3 of frequency
57 81R4.t_Op 0.1~100 0.1 s 0.001
rate-of-change protection
The pickup frequency setting of the stage 3
58 81R4.f_Pkp 45~65 50 Hz 0.001
of frequency rate-of-change protection
Disabled; The logic setting of the stage 3 of frequency
59 81R4.En Enabled - -
Enabled rate-of-change protection 9
The rate-of-change setting of the stage 4 of
60 81R5.df/dt_Set -5~5 0.5 Hz/s 0.001
frequency rate-of-change protection
The time setting of the stage 4 of frequency
61 81R5.t_Op 0.1~100 0.1 s 0.001
rate-of-change protection
The pickup frequency setting of the stage 4
62 81R5.f_Pkp 45~65 50 Hz 0.001
of frequency rate-of-change protection
Disabled; The logic setting of the stage 4 of frequency
63 81R5.En Enabled - -
Enabled rate-of-change protection
The rate-of-change setting of the stage 5 of
64 81R6.df/dt_Set -5~5 0.5 Hz/s 0.001
frequency rate-of-change protection

PCS-9611S Feeder Relay 9-93


Date: 2019-04-24
9 Settings

The time setting of the stage 5 of frequency


65 81R6.t_Op 0.1~100 0.1 s 0.001
rate-of-change protection
The pickup frequency setting of the stage 5
66 81R6.f_Pkp 45~65 50 Hz 0.001
of frequency rate-of-change protection
Disabled; The logic setting of the stage 5 of frequency
67 81R6.En Enabled - -
Enabled rate-of-change protection

9.2.13 Reverse Power Protection Settings


 Access path:

MainMenu  Settings  Protection Settings  RevPower Settings

Table 9.2-13 Settings of reverse power protection

No. Setting Range Default Unit Step Description


The voltage setting of the
1 32R.U1_VCE 5~60 5 V 0.001 positive-sequence voltage control element
of the reverse power protection
The positive-sequence current setting of
2 32R.I1_CCE 0.01~1 0.1 p.u. 0.001 the current control element of the reverse
power protection
The voltage setting of the
3 32R.U2_VCE 8~60 8 V 0.001 negative-sequence voltage control element
of the reverse power protection
The power setting of the stage 1 of reverse
4 32R1.P_Set 0.1~10 0.15 p.u. 0.001
power protection
The time setting of the stage 1 of reverse
5 32R1.t_Op 0.01~100 0.1 s 0.001
power protection
Disabled; The logic setting of the stage 1 of reverse
6 32R1.En Enabled - -
Enabled power protection
Enabling stage 1 of reverse power
Trp; protection operate to trip or alarm.
7 32R1.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose
Alm: for alarm purpose
The power setting of the stage 2 of reverse
9 8 32R2.P_Set 0.1~10 0.15 p.u. 0.001
power protection
The time setting of the stage 2 of reverse
9 32R2.t_Op 0.01~100 0.1 s 0.001
power protection
Disabled; The logic setting of the stage 2 of reverse
10 32R2.En Enabled - -
Enabled power protection
Enabling stage 2 of reverse power
Trp; protection operate to trip or alarm.
11 32R2.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose
Alm: for alarm purpose

9-94 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

9.2.14 Cold Load Pickup Logic Settings


 Access path:

MainMenu  Settings  Protection Settings  CLP Settings

Table 9.2-14 Settings of cold load pickup logic

No. Setting Range Default Unit Step Description


The setting for selecting the cold load
Curr;
1 CLP.Opt_LogicMode CBPos - - initiation condition.
CBPos
Curr: current; CBPos: CB position.
The time setting for ensuring the cold
2 CLP.t_Cold 0~4000 3 s 0.001
load condition is met
The time setting for resetting the cold
3 CLP.t_Rst 0~4000 3 s 0.001
load pickup logic
The time setting for fast resetting the cold
4 CLP.t_ShortRst 0~600 1 s 0.001
load pickup logic
Disabled; The logic setting of the cold load pickup
5 CLP.En Enabled - -
Enabled logic function
The multiple setting of the stage 1 of
6 50/51P1.CLP.IMult 1~10 1 - 0.001 overcurrent protection when CLP is
active
The time setting of the stage 1 of
7 50/51P1.CLP.t_Op 0~100 0.1 s 0.001 overcurrent protection when CLP is
active
The time multiplier setting of the stage 1
8 50/51P1.CLP.TMS 0.05~100 1 s 0.001 of IDMT overcurrent protection when CLP
is active
The multiple setting of the stage 1 of
9 50/51G1.CLP.IMult 1~10 1 - 0.001 zero-sequence overcurrent protection
when CLP is active
The time setting of the stage 1 of
10 50/51G1.CLP.t_Op 0~100 0.1 s 0.001 zero-sequence overcurrent protection
when CLP is active

11 50/51G1.CLP.TMS 0.05~100 1 s 0.001


The time multiplier setting of the stage 1
of zero-sequence IDMT overcurrent
9
protection when CLP is active
The multiple setting of the stage 2 of
12 50/51P2.CLP.IMult 1~10 1 - 0.001 overcurrent protection when CLP is
active
The time setting of the stage 2 of
13 50/51P2.CLP.t_Op 0~100 0.1 s 0.001 overcurrent protection when CLP is
active

PCS-9611S Feeder Relay 9-95


Date: 2019-04-24
9 Settings

The time multiplier setting of the stage 2


14 50/51P2.CLP.TMS 0.05~100 1 s 0.001 of IDMT overcurrent protection when CLP
is active
The multiple setting of the stage 2 of
15 50/51G2.CLP.IMult 1~10 1 - 0.001 zero-sequence overcurrent protection
when CLP is active
The time setting of the stage 2 of
16 50/51G2.CLP.t_Op 0~100 0.1 s 0.001 zero-sequence overcurrent protection
when CLP is active
The time multiplier setting of the stage 2
17 50/51G2.CLP.TMS 0.05~100 1 s 0.001 of zero-sequence IDMT overcurrent
protection when CLP is active
The multiple setting of the stage 3 of
18 50/51P3.CLP.IMult 1~10 1 - 0.001 overcurrent protection when CLP is
active
The time setting of the stage 3 of
19 50/51P3.CLP.t_Op 0~100 0.1 s 0.001 overcurrent protection when CLP is
active
The time multiplier setting of the stage 3
20 50/51P3.CLP.TMS 0.05~100 1 s 0.001 of IDMT overcurrent protection when CLP
is active
The multiple setting of the stage 3 of
21 50/51G3.CLP.IMult 1~10 1 - 0.001 zero-sequence overcurrent protection
when CLP is active
The time setting of the stage 3 of
22 50/51G3.CLP.t_Op 0~100 0.1 s 0.001 zero-sequence overcurrent protection
when CLP is active
The time multiplier setting of the stage 3
23 50/51G3.CLP.TMS 0.05~100 1 s 0.001 of zero-sequence IDMT overcurrent
protection when CLP is active
The multiple setting of the stage 4 of
24 50/51P4.CLP.IMult 1~10 1 - 0.001 overcurrent protection when CLP is
active

9 25 50/51P4.CLP.t_Op 0~100 0.1 s 0.001


The time setting of the stage 4 of
overcurrent protection when CLP is
active
The time multiplier setting of the stage 4
26 50/51P4.CLP.TMS 0.05~100 1 s 0.001 of IDMT overcurrent protection when CLP
is active
The multiple setting of the stage 4 of
27 50/51G4.CLP.IMult 1~10 1 - 0.001 zero-sequence overcurrent protection
when CLP is active

9-96 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

The time setting of the stage 4 of


28 50/51G4.CLP.t_Op 0~100 0.1 s 0.001 zero-sequence overcurrent protection
when CLP is active
The time multiplier setting of the stage 4
29 50/51G4.CLP.TMS 0.05~100 1 s 0.001 of zero-sequence IDMT overcurrent
protection when CLP is active
The multiple setting of the stage 5 of
30 50/51P5.CLP.IMult 1~10 1 - 0.001 overcurrent protection when CLP is
active
The time setting of the stage 5 of
31 50/51P5.CLP.t_Op 0~100 0.1 s 0.001 overcurrent protection when CLP is
active
The time multiplier setting of the stage 5
32 50/51P5.CLP.TMS 0.05~100 1 s 0.001 of IDMT overcurrent protection when CLP
is active
The multiple setting of the stage 5 of
33 50/51G5.CLP.IMult 1~10 1 - 0.001 zero-sequence overcurrent protection
when CLP is active
The time setting of the stage 5 of
34 50/51G5.CLP.t_Op 0~100 0.1 s 0.001 zero-sequence overcurrent protection
when CLP is active
The time multiplier setting of the stage 5
35 50/51G5.CLP.TMS 0.05~100 1 s 0.001 of zero-sequence IDMT overcurrent
protection when CLP is active
The multiple setting of the stage 6 of
36 50/51P6.CLP.IMult 1~10 1 - 0.001 overcurrent protection when CLP is
active
The time setting of the stage 6 of
37 50/51P6.CLP.t_Op 0~100 0.1 s 0.001 overcurrent protection when CLP is
active
The time multiplier setting of the stage 6
38 50/51P6.CLP.TMS 0.05~100 1 s 0.001 of IDMT overcurrent protection when CLP
is active

39 50/51G6.CLP.IMult 1~10 1 - 0.001


The multiple setting of the stage 6 of
zero-sequence overcurrent protection
9
when CLP is active
The time setting of the stage 6 of
40 50/51G6.CLP.t_Op 0~100 0.1 s 0.001 zero-sequence overcurrent protection
when CLP is active
The time multiplier setting of the stage 6
41 50/51G6.CLP.TMS 0.05~100 1 s 0.001 of zero-sequence IDMT overcurrent
protection when CLP is active

PCS-9611S Feeder Relay 9-97


Date: 2019-04-24
9 Settings

9.2.15 Undercurrent Settings


 Access path:

MainMenu  Settings  Protection Settings  UC Settings

Table 9.2-15 Settings of undercurrent protection

No. Setting Range Default Unit Step Description


The current setting of the
1 37.I_Set 0.1~5 0.5 A 0.001
undercurrent protection
The time setting of the undercurrent
2 37.t_Op 0.1~100 0.1 s 0.001
protection
The setting for selecting the
1P;
3 37.Opt_1P/3P 3P - - three-phase criterion (3P) or
3P
single-phase criterion (1P)
None;
Curr;
CurrAnd The setting of the CB position check
4 37.Opt_LogicMode CBPos; - -
CBPos mode.
CurrAndCBPos;
CurrOrCBPos
Disabled; The logic setting of the undercurrent
5 37.En Enabled - -
Enabled protection
Enabling undercurrent protection
Trp; operate to trip or alarm.
6 37.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose
Alm: for alarm purpose

9.2.16 Breaker Failure Protection Settings


 Access path:

MainMenu  Settings  Protection Settings  BFP Settings

Table 9.2-16 Settings of breaker failure protection

No. Setting Range Default Unit Step Description


The phase current setting of breaker
9 1 50BF.I_Set 0.05~200 1.000 A 0.001
failure protection
The zero-sequence current setting of
2 50BF.3I0_Set 0.05~200 1.000 A 0.001
breaker failure protection
The negative-sequence current setting of
3 50BF.I2_Set 0.05~200 1.000 A 0.001
breaker failure protection
The re-trip time delay of breaker failure
4 50BF.t_ReTrp 0~20 0.050 s 0.001
protection
The first time delay of breaker failure
5 50BF.t1_Op 0~20 0.100 s 0.001
protection

9-98 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

The second time delay of breaker failure


6 50BF.t2_Op 0~20 0.200 s 0.001
protection
Disabled Enabling/disabling breaker failure
7 50BF.En Enabled - -
Enabled protection
Disabled Enabling/disabling re-trip function of
8 50BF.En_ReTrp Enabled - -
Enabled breaker failure protection
Disabled Enabling/disabling first time delay of
9 50BF.En_t1 Disabled - -
Enabled breaker failure protection
Disabled Enabling/disabling second time delay of
10 50BF.En_t2 Disabled - -
Enabled breaker failure protection
Enabling/disabling phase overcurrent
Disabled
11 50BF.En_Ip Disabled - - element of breaker failure protection via
Enabled
three-phases initiating signal
Enabling/disabling zero-sequence
Disabled overcurrent element of breaker failure
12 50BF.En_3I0_3P Disabled - -
Enabled protection via three-phases initiating
signal
Enabling/disabling negative-sequence
Disabled overcurrent element of breaker failure
13 50BF.En_I2_3P Disabled - -
Enabled protection via three-phases initiating
signal
Enabling/disabling breaker failure
Disabled
14 50BF.En_CB_Ctrl Disabled - - protection be initiated by normally closed
Enabled
contact of circuit breaker
Disabled Enabling/disabling abnormality check of
15 50BF.En_Alm_Init Disabled - -
Enabled breaker failure initiating signal

9.2.17 Switch-on-to-Fault ProtectionSettings


 Access path:

MainMenu  Settings  Protection Settings  SOTF Settings

Table 9.2-17 Settings of SOTF protection

No. Setting Range Default Unit Step Description


The initiating time for the SOTF 9
1 SOTF.t_En 0.2~100 3 s 0.001
protection
Option of manual SOTF mode
ManClsBI:initiated by input signal of
ManClsBI
manual config
SOTF.Opt_Mode_Man CBPos
2 CBPos - - CBPos:initiaed by CB position
Cls ManClsBI/
ManClsBI/CBPos:initiated by either
CBPos
input signal of manual closing or CB
postition

PCS-9611S Feeder Relay 9-99


Date: 2019-04-24
9 Settings

Current setting of phase overcurrent


3 50PSOTF.I_Set 0.05~200 1 A 0.001
SOTF protection
Voltage setting for phase
4 50PSOTF.Up_Set 0~200 1 V 0.001
undervoltage supervision logic
Voltage setting for phase-to-phase
5 50PSOTF.Upp_Set 0~200 1 V 0.001
undervoltage supervision logic
Voltage setting for negative-sequence
6 50PSOTF.U2_Set 0~200 1 V 0.001
overvoltage supervision logic
Voltage setting for zero-sequence
7 50PSOTF.3U0_Set 0~200 1 V 0.001
overvoltage supervision logic
Time delay for phase overcurrent
8 50PSOTF.t_Op 0~100 0.1 s 0.001
SOTF protection
Disabled Enabling/disabling phase overcurrent
9 50PSOTF.En Enabled - -
Enabled SOTF protection
Enabling/disabling second harmonic
Disabled
10 50PSOTF.En_Hm2_Blk Enabled - - blocking for phase overcurrent SOTF
Enabled
protection
Enabling/disabling phase
Disabled
11 50PSOTF.En_Up_UV Enabled - - undervoltage supervision logic for
Enabled
phase overcurrent SOTF protection
Enabling/disabling phase-to-phase
Disabled
12 50PSOTF.En_Upp_UV Enabled - - undervoltage supervision logic for
Enabled
phase overcurrent SOTF protection
Enabling/disabling
Disabled negative-sequence overvoltage
13 50PSOTF.En_U2_OV Enabled - -
Enabled supervision logic for phase
overcurrent SOTF protection
Enabling/disabling zero-sequence
Disabled
14 50PSOTF.En_3U0_OV Enabled - - overvoltage supervision logic for
Enabled
phase overcurrent SOTF protection
The option of the residual current
used by earth fault overcurrent SOTF
Ext
15 50GSOTF.Opt_3I0 Cal - - protection
Cal
9 Ext: the measured residual current
Cal: the calculated residual current
Current setting of earth fault
16 50GSOTF.3I0_Set 0.05~200 1 A 0.001
overcurrent SOTF protection
Time delay for earth fault overcurrent
17 50GSOTF.t_Op_3P 0~100 0.1 s 0.001
SOTF protection
Disabled Enabling/disabling earth fault
18 50GSOTF.En Enabled - -
Enabled overcurrent SOTF protection
Enabling/disabling earth fault
Disabled
19 50GSOTF.En_Hm2_Blk Disabled - - overcurrent SOTF protection blocked
Enabled
by harmonic

9-100 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

9.2.18 Unbalance Current Protection Settings


 Access path:

MainMenu  Settings  Protection Settings  UnbalCurr Settings

Table 9.2-18 Settings of unbalance current protection

No. Setting Range Default Unit Step Description


The current setting of stage 1 of
1 60/50-1.I_Set 0.02~200 1 A 0.001
unbalance current protection
The operating time setting of stage 1 of
2 60/50-1.t_Op 0.05~100 0.1 s 0.001
unbalance current protection
Disabled; The logic setting for enabling/disabling
3 60/50-1.En Enabled - -
Enabled stage 1 of unbalance current protection
Enabling stage 1 of unbalance current
Trp; protection operate to trip or alarm.
4 60/50-1.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose
Alm: for alarm purpose
The current setting of stage 2 of
5 60/50-2.I_Set 0.02~200 1 A 0.001
unbalance current protection
The operating time setting of stage 2 of
6 60/50-2.t_Op 0.05~100 0.1 s 0.001
unbalance current protection
Disabled; The logic setting for enabling/disabling
7 60/50-2.En Enabled - -
Enabled stage 2 of unbalance current protection
Enabling stage 2 of unbalance current
Trp; protection operate to trip or alarm.
8 60/50-2.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose
Alm: for alarm purpose

9.2.19 Unbalance Voltage Protection Settings


 Access path:

MainMenu  Settings  Protection Settings  UnbalVolt Settings

Table 9.2-19 Settings of unbalance voltage protection

No. Setting Range Default Unit Step Description 9


The voltage setting of the stage 1 of
1 60/59-1.U_Set 1~63.5 50 V 0.001
unbalance voltage protection
The time setting of the stage 1 of
2 60/59-1.t_Op 0.1~100 1 s 0.001
unbalance voltage protection
Disabled; The logic setting for enabling/disabling
3 60/59-1.En Enabled - -
Enabled stage 1 of unbalance voltage protection

PCS-9611S Feeder Relay 9-101


Date: 2019-04-24
9 Settings

Enabling stage 1 of unbalance voltage


Trp; protection operate to trip or alarm.
4 60/59-1.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose
Alm: for alarm purpose
The voltage setting of the stage 2 of
5 60/59-2.U_Set 1~63.5 50 V 0.001
unbalance voltage protection
The time setting of the stage 2 of
6 60/59-2.t_Op 0.1~100 1 s 0.001
unbalance voltage protection
Disabled; The logic setting for enabling/disabling
7 60/59-2.En Enabled - -
Enabled stage 2 of unbalance voltage protection
Enabling stage 2 of unbalance voltage
Trp; protection operate to trip or alarm.
8 60/59-2.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose
Alm: for alarm purpose

9.2.20 Fault Location Settings


 Access path:

MainMenu  Settings  Protection Settings  FL Settings

Table 9.2-20 Settings of fault location

Default
No. Settings Range Unit Step Remark
value
Positive-sequence reactance of the whole
1 X1L (0~4Unn)/In 10 Ω 0.001
line (secondary value)
Positive-sequence resistance of the whole
2 R1L (0~4Unn)/In 1 Ω 0.001
line (secondary value)
Zero-sequence reactance of the whole
3 X0L (0~4Unn)/In 20 Ω 0.001
line (secondary value)
Zero-sequence resistance of the whole
4 R0L (0~4Unn)/In 3 Ω 0.01
line (secondary value)
5 LineLength 0~1000 100 km 0.01 Total length of the whole line

9.3 Measurement and Control Settings


9

In this section, the "XXXX" stands for bay indication. By default, it could be
BayMMXU, BusMMXU, etc. and it is configurable through the configuration
tool PCS-Studio.

9.3.1 Function Settings


 Access path:

9-102 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

Main Menu  Settings  Meas Control Settings  Function Settings

No. Setting Default Range Step Unit Remark


Ia-Ib-Ic or
1 Opt_CT_Measmt Ia-Ib-Ic - - Source selection of current measurement
Ia-Ic

2 ZeroDrift_U 0.20 0.00~1.00 0.01 %


Threshold to limit the zero-drift influence of
voltage, current or power due to temperature or
3 ZeroDrift_I 0.20 0.00~1.00 0.01 % other environmental factors. A measured value
less than this setting will be regarded as a zero
drift and ignored.
4 ZeroDrift_PQ 0.50 0.00~1.00 0.01 %

5 Neu.ZeroDrift_I 0.20 0.00~1.00 0.01 % Threshold to limit the zero-drift influence of


6 Neu2.ZeroDrift_I 0.20 0.00~1.00 0.01 % corresponding current due to temperature or
other environmental factors. A measured value
7 60/50.ZeroDrift_I 0.20 0.00~1.00 0.01 % less than this setting will be regarded as a zero
drift and ignored.
8 Delt.ZeroDrift_U 0.20 0.00~1.00 0.01 % Threshold to limit the zero-drift influence of

9 Syn.ZeroDrift_U 0.20 0.00~1.00 0.01 % corresponding voltage due to temperature or


other environmental factors. A measured value
10 60/59.ZeroDrift_U 0.20 0.00~1.00 0.01 % less than this setting will be regarded as a zero
drift and ignored.

9.3.2 Synchronism Check Settings


 Access path:

Main Menu  Settings  Meas Control Settings  Syn Settings

No. Setting Default Range Step Unit Description


Selection of circuit
NoVolSel, DblBusOneCB,
1 Opt_CBConfig NoVolSel - - breaker arrangement
3/2BusCB, 3/2TieCB
for voltage selection
Selection of decision
2 25.Opt_ValidMode Setting Setting or Config - - mode for synchronism
check
Logic setting for 9
synchro-check (valid
3 25.En_SynChk Enabled Disabled or Enabled - - only if the setting
[25.Opt_ValidMode] =
Setting)
Logic setting for dead
charge check (valid
4 25.En_DdChk Enabled Disabled or Enabled - - only if the setting
[25.Opt_ValidMode] =
Setting)

PCS-9611S Feeder Relay 9-103


Date: 2019-04-24
9 Settings

No. Setting Default Range Step Unit Description


Percentage threshold
5 25.U_UV 80.00 0~100 0.01 % of under voltage for
CB closing blocking
Percentage threshold
6 25.U_OV 170.00 100~170 0.01 % of over voltage for CB
closing blocking
Percentage threshold
7 25.f_UF 45.000 45~65 0.001 Hz of under frequency for
CB closing blocking
Percentage threshold
8 25.f_OF 65.000 45~65 0.001 Hz of over frequency for
CB closing blocking
Selection of voltage
9 25.Opt_U_SynChk Ua Ua, Ub, Uc, Uab, Ubc, Uca - -
for synchronism check
Threshold of voltage
10 25.U_Diff_Set 10.00 0~100 0.01 V difference for
synchronism check
Logic setting for
11 25.En_f_Diff_Chk Enabled Disabled or Enabled - - frequency difference
check
Threshold of
12 25.f_Diff_Set 0.50 0~2 0.01 Hz frequency difference
for synchronism check
Logic setting for
13 25.En_df/dt_Chk Enabled Disabled or Enabled - - frequency variation
difference check
Threshold of
14 25.df/dt_Set 1.00 0~2 0.01 Hz/s frequency variation for
synchronism check.
Threshold of phase
15 25.phi_Diff_Set 15.00 0~180 0.01 ° difference for
synchronism check

9 16 25.phi_Comp 0.00 0~360 0.01 °


Compensation angle
of phase difference for
synchronism check
SynDdRefDd
SynLvRefDd
SynDdRefLv
Selection of dead
17 25.Opt_Mode_DdChk AnySideDd RefDd - -
charge check mode
SynDd
SynLvRefDd/SynDdRefLv
AnySideDd
18 25.U_DdChk 17.32 0~100 0.01 V Threshold for voltage

9-104 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

No. Setting Default Range Step Unit Description


dead check
Threshold for voltage
19 25.U_LvChk 34.64 0~100 0.01 V
live check
Threshold of duration
20 25.t_Reset 5 0~60 1 s
for synchro-check
Circuit breaker closing
time. It is the time
from receiving closing
21 25.t_Close_CB 20 0~2000 1 ms
command pulse till the
CB is completely
closed.

9.3.3 Double Point Status Settings


 Access path:

Main Menu  Settings  Meas Control Settings  DPS Settings

No. Setting Default Range Step Unit Description


Delay Pick Up (DPU) time, i.e.
1 Breaker.DPS.t_DPU 500 0~60000 1 ms debounce time, for DPS of the circuit
breaker
Disabled or Logic setting for DPS alarm of the
2 Breaker.DPS.En_Alm Disabled - -
Enabled circuit breaker
Operation time delay of DPS alarm of
3 Breaker.DPS.t_Alm 500 0~60000 1 ms
the circuit breaker
Delay Pick Up (DPU) time, i.e.
4 Switch01.DPS.t_DPU 500 0~60000 1 ms
debounce time, for DPS of switch 01
Disabled or Logic setting for DPS alarm of switch
5 Switch01.DPS.En_Alm Disabled - -
Enabled 01
Operation time delay of DPS alarm of
6 Switch01.DPS.t_Alm 500 0~60000 1 ms
switch 01
Delay Pick Up (DPU) time, i.e.
7 Switch02.DPS.t_DPU 500 0~60000 1 ms
debounce time, for DPS of switch 02

8 Switch02.DPS.En_Alm Disabled
Disabled or
- -
Logic setting for DPS alarm of switch 9
Enabled 02
Operation time delay of DPS alarm of
9 Switch02.DPS.t_Alm 500 0~60000 1 ms
switch 02
Delay Pick Up (DPU) time, i.e.
10 Switch03.DPS.t_DPU 500 0~60000 1 ms
debounce time, for DPS of switch 03
Disabled or Logic setting for DPS alarm of switch
11 Switch03.DPS.En_Alm Disabled - -
Enabled 03
Operation time delay of DPS alarm of
12 Switch03.DPS.t_Alm 500 0~60000 1 ms
switch 03

PCS-9611S Feeder Relay 9-105


Date: 2019-04-24
9 Settings

Delay Pick Up (DPU) time, i.e.


13 Switch04.DPS.t_DPU 500 0~60000 1 ms
debounce time, for DPS of switch 04
Disabled or Logic setting for DPS alarm of switch
14 Switch04.DPS.En_Alm Disabled - -
Enabled 04
Operation time delay of DPS alarm of
15 Switch04.DPS.t_Alm 500 0~60000 1 ms
switch 04
Delay Pick Up (DPU) time, i.e.
16 Switch05.DPS.t_DPU 500 0~60000 1 ms
debounce time, for DPS of switch 05
Disabled or Logic setting for DPS alarm of switch
17 Switch05.DPS.En_Alm Disabled - -
Enabled 05
Operation time delay of DPS alarm of
18 Switch05.DPS.t_Alm 500 0~60000 1 ms
switch 05
Delay Pick Up (DPU) time, i.e.
19 Switch06.DPS.t_DPU 500 0~60000 1 ms
debounce time, for DPS of switch 06
Disabled or Logic setting for DPS alarm of switch
20 Switch06.DPS.En_Alm Disabled - -
Enabled 06
Operation time delay of DPS alarm of
21 Switch06.DPS.t_Alm 500 0~60000 1 ms
switch 06
Delay Pick Up (DPU) time, i.e.
22 Switch07.DPS.t_DPU 500 0~60000 1 ms
debounce time, for DPS of switch 07
Disabled or Logic setting for DPS alarm of switch
23 Switch07.DPS.En_Alm Disabled - -
Enabled 07
Operation time delay of DPS alarm of
24 Switch07.DPS.t_Alm 500 0~60000 1 ms
switch 07
Delay Pick Up (DPU) time, i.e.
25 Switch08.DPS.t_DPU 500 0~60000 1 ms
debounce time, for DPS of switch 08
Disabled or Logic setting for DPS alarm of switch
26 Switch08.DPS.En_Alm Disabled - -
Enabled 08
Operation time delay of DPS alarm of
27 Switch08.DPS.t_Alm 500 0~60000 1 ms
switch 08
Delay Pick Up (DPU) time, i.e.
28 Switch09.DPS.t_DPU 500 0~60000 1 ms
debounce time, for DPS of switch 09
Disabled or Logic setting for DPS alarm of switch
29 Switch09.DPS.En_Alm Disabled - -
9 Enabled 09
Operation time delay of DPS alarm of
30 Switch09.DPS.t_Alm 500 0~60000 1 ms
switch 09

9.3.4 Control Settings


 Access path:

Main Menu  Settings  Meas Control Settings  Control Settings

No. Setting Default Range Step Unit Description


1 Breaker.t_PW_Opn 500 0~60000 1 ms Pulse Width (PW), i.e. holding time, for opening

9-106 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

No. Setting Default Range Step Unit Description


output of the circuit breaker
Pulse Width (PW), i.e. holding time, for closing
2 Breaker.t_PW_Cls 500 0~60000 1 ms
output of the circuit breaker
Pulse Width (PW), i.e. holding time, for direct
3 Switch01.t_PW_Opn 500 0~60000 1 ms
opening output of switch 01
Pulse Width (PW), i.e. holding time, for direct
4 Switch01.t_PW_Cls 500 0~60000 1 ms
closing output of switch 01
Pulse Width (PW), i.e. holding time, for direct
5 Switch02.t_PW_Opn 500 0~60000 1 ms
opening output of switch 02
Pulse Width (PW), i.e. holding time, for direct
6 Switch02.t_PW_Cls 500 0~60000 1 ms
closing output of switch 02
Pulse Width (PW), i.e. holding time, for direct
7 Switch03.t_PW_Opn 500 0~60000 1 ms
opening output of switch 03
Pulse Width (PW), i.e. holding time, for direct
8 Switch03.t_PW_Cls 500 0~60000 1 ms
closing output of switch 03
Pulse Width (PW), i.e. holding time, for direct
9 Switch04.t_PW_Opn 500 0~60000 1 ms
opening output of switch 04
Pulse Width (PW), i.e. holding time, for direct
10 Switch04.t_PW_Cls 500 0~60000 1 ms
closing output of switch 04
Pulse Width (PW), i.e. holding time, for direct
11 Switch05.t_PW_Opn 500 0~60000 1 ms
opening output of switch 05
Pulse Width (PW), i.e. holding time, for direct
12 Switch05.t_PW_Cls 500 0~60000 1 ms
closing output of switch 05
Pulse Width (PW), i.e. holding time, for direct
13 Switch06.t_PW_Opn 500 0~60000 1 ms
opening output of switch 06
Pulse Width (PW), i.e. holding time, for direct
14 Switch06.t_PW_Cls 500 0~60000 1 ms
closing output of switch 06
Pulse Width (PW), i.e. holding time, for direct
15 Switch07.t_PW_Opn 500 0~60000 1 ms
opening output of switch 07
Pulse Width (PW), i.e. holding time, for direct
16 Switch07.t_PW_Cls 500 0~60000 1 ms
closing output of switch 07
Pulse Width (PW), i.e. holding time, for direct

9
17 Switch08.t_PW_Opn 500 0~60000 1 ms
opening output of switch 08
Pulse Width (PW), i.e. holding time, for direct
18 Switch08.t_PW_Cls 500 0~60000 1 ms
closing output of switch 08
Pulse Width (PW), i.e. holding time, for direct
19 Switch09.t_PW_Opn 500 0~60000 1 ms
opening output of switch 09
Pulse Width (PW), i.e. holding time, for direct
20 Switch09.t_PW_Cls 500 0~60000 1 ms
closing output of switch 09

9.3.5 Interlocking Logic Settings


 Access path:

PCS-9611S Feeder Relay 9-107


Date: 2019-04-24
9 Settings

Main Menu  Settings  Meas Control Settings  Interlock Settings

No. Setting Default Range Step Unit Description


Logic setting for interlocking logic
Disabled or
1 Breaker.En_CILO_Opn Disabled - - control of opening output of the circuit
Enabled
breaker.
Logic setting for interlocking logic
Disabled or
2 Breaker.En_CILO_Cls Disabled - - control of closing output of the circuit
Enabled
breaker.
Logic setting for interlocking logic
Disabled or
3 Switch01.En_CILO_Opn Disabled - - control of direct opening output of
Enabled
switch 01.
Logic setting for interlocking logic
Disabled or
4 Switch01.En_CILO_Cls Disabled - - control of direct closing output of
Enabled
switch 01.
Logic setting for interlocking logic
Disabled or
5 Switch02.En_CILO_Opn Disabled - - control of direct opening output of
Enabled
switch 02.
Logic setting for interlocking logic
Disabled or
6 Switch02.En_CILO_Cls Disabled - - control of direct closing output of
Enabled
switch 02.
Logic setting for interlocking logic
Disabled or
7 Switch03.En_CILO_Opn Disabled - - control of direct opening output of
Enabled
switch 03.
Logic setting for interlocking logic
Disabled or
8 Switch03.En_CILO_Cls Disabled - - control of direct closing output of
Enabled
switch 03.
Logic setting for interlocking logic
Disabled or
9 Switch04.En_CILO_Opn Disabled - - control of direct opening output of
Enabled
switch 04.
Logic setting for interlocking logic
Disabled or
10 Switch04.En_CILO_Cls Disabled - - control of direct closing output of
Enabled
switch 04.
Logic setting for interlocking logic
9 11 Switch05.En_CILO_Opn Disabled
Disabled
Enabled
or
- - control of direct opening output of
switch 05.
Logic setting for interlocking logic
Disabled or
12 Switch05.En_CILO_Cls Disabled - - control of direct closing output of
Enabled
switch 05.
Logic setting for interlocking logic
Disabled or
13 Switch06.En_CILO_Opn Disabled - - control of direct opening output of
Enabled
switch 06.
Disabled or Logic setting for interlocking logic
14 Switch06.En_CILO_Cls Disabled - -
Enabled control of direct closing output of

9-108 PCS-9611S Feeder Relay


Date: 2019-04-24
9 Settings

No. Setting Default Range Step Unit Description


switch 06.
Logic setting for interlocking logic
Disabled or
15 Switch07.En_CILO_Opn Disabled - - control of direct opening output of
Enabled
switch 07.
Logic setting for interlocking logic
Disabled or
16 Switch07.En_CILO_Cls Disabled - - control of direct closing output of
Enabled
switch 07.
Logic setting for interlocking logic
Disabled or
17 Switch08.En_CILO_Opn Disabled - - control of direct opening output of
Enabled
switch 08.
Logic setting for interlocking logic
Disabled or
18 Switch08.En_CILO_Cls Disabled - - control of direct closing output of
Enabled
switch 08.
Logic setting for interlocking logic
Disabled or
19 Switch09.En_CILO_Opn Disabled - - control of direct opening output of
Enabled
switch 09.
Logic setting for interlocking logic
Disabled or
20 Switch09.En_CILO_Cls Disabled - - control of direct closing output of
Enabled
switch 09.

9.4 Logic Links

Logic link is a special logic setting which can be configured through local HMI or remote PC.

These logic links provide a convenient way for the operator to put the function in service or out of
service remotely away from an unattended substation.

9.4.1 GOOSE Receiving Links


 Access path:

MainMenu  Settings  Logic Links  GOOSE Recv Links

Table 9.4-1 GOOSE receiving links

No. Settings Range


Default
Remark
9
value

@Bx.Name_000_GCommLink. Disabled
1 Enabled GOOSE receiving link 000 is enabled or disabled
GLink_Recv Enabled

Disabled
2 …… Enabled ……
Enabled

@Bx.Name_127_GCommLink. Disabled
3 Enabled GOOSE receiving link 127 is enabled or disabled
GLink_Recv Enabled

@Bx.Name_000_GCommLink is the set value of the label setting of [Bx.Name_000_GCommLink],

PCS-9611S Feeder Relay 9-109


Date: 2019-04-24
9 Settings

@Bx.Name_127_GCommLink is the set value of the label setting of


[Bx.Name_127_GCommLink].

9-110 PCS-9611S Feeder Relay


Date: 2019-04-24
Appendix A Glossary

Appendix A Glossary
The abbreviations adopted in this manual are listed as below.

A BOM Binary Output Module

"a" Contact is breaker auxiliary contact (ANSI C


Standard Device Number 52A) that closes
when the breaker is closed and opens when C37.94 IEEE/ANSI protocol used when
the breaker is open. sending binary signals between IEDs

AC Alternating current CB Circuit breaker

A/D converter Analog-to-digital converter CID Configured IED Description

AI Analog input COMTRADE Standard Common Format for


Transient Data Exchange format for
ANSI American National Standards Institute
Disturbance recorder according to IEEE/ANSI
AR Autoreclosing C37.111, 1999 / IEC 60255-24

ASDU Application Service Data Unit – An CPU Central Processing Unit


ASDU can consist of one or more identical
CRC Cyclic Redundancy Check
information objects. A sequence of the same
information elements, for example measured CT Current Transformer
values, is identified by the address of the
CTS Current Circuit Supervision
information object. The address of the
information object defines the associated
D
address of the first information element of the
sequence. A consecutive number identifies the
DBDL Dead Bus Dead Line
subsequent information elements. The number
builds on this address in integral increments DBLL Dead Bus Live Line
(+1).
DC Direct Current

B DLLB Dead Line Live Bus

DNP Distributed Network Protocol as per IEEE


"b" Contact is breaker auxiliary contact (ANSI
Std 1815-2012
Standard Device Number 52B) that closes
when the breaker is open and opens when the DPFC Deviation of Power Frequency
breaker is closed. Component–In case of a fault occurred in the
power system, the fault component could be
BFP Breaker failure protection
analyzed into three parts: the power frequency
BI Binary Input components before the fault, the power
frequency variables during the fault and the
BO Binary Output
transient variables during the fault. DPFC is A
BIM Binary Input Module the power frequency variable during the fault.

PCS-9611S Feeder Relay 1


Date: 2019-04-24
Appendix A Glossary

DSP Digital Signal Processor L


DTT Direct Transfer Trip Scheme
LCD Liquid Crystal Display

E LED Light-emitting Diode

EHV Extra High Voltage M


EMC Electromagnetic Compatibility
MCB Miniature Circuit Breaker

F MMS Manufacturing Message Specification

MOV Metal-oxide Varistor


FL Fault Location

FR Fault Recorder O

G OLTC On-load Tap Changer

OOS Out-of-Step
G.703 Electrical and functional description for
digital lines used by local telephone
P
companies. Can be transported over balanced
and unbalanced lines
PD Pole Discrepancy
GIS Gas-insulated Switchgear
PDTT Permissive Direct Transfer Trip
GOOSE Generic Object-Oriented Substation
PL Programmable Logic
Event
POTT Permissive Overreaching Transfer Trip
GPS Global Positioning System
PPM Pulse Per Minute
H
PPS Pulse Per Second

HMI Human-machine Interface PRP Parallel Redundancy Protocol

HSR High-availability Seamless Redundancy PUTT Permissive Underreaching Transfer Trip

HV High-voltage
R
HVDC High-voltage Direct Current
RMS Root Mean Square
I
RSTP Rapid Spanning Tree Protocol

ICD IED Capability Description RTD Resistance Temperature Detector

IEC International Electrotechnical Commission RTU Remote Terminal Unit

IED Intelligent Electronic Device


S
A IRIG-B InterRange Instrumentation Group
Time code format B SA Substation Automation

2 PCS-9611S Feeder Relay


Date: 2019-04-24
Appendix A Glossary

SCADA Supervision, Control And Data SOTF Switch-Onto-Fault


Acquisition
STP Rapid Spanning Tree Protocol
SCD Substation Configuration Description
T
SCL Substation Configuration Description
Language
TCS Trip Circuit Supervision
SLD Single-line Diagram
TCP/IP Transmission Control Protocol over
SIR Source-to-line Impedance Ratio Internet Protocol

SNMP Simple Network Management Protocol


U
–An Internet standard protocol and serves for
the administration of nodes in an IP network.
UTC Coordinated Universal Time
SNTP Simple Network Time Protocol – A
protocol for the synchronization of clocks via W
the Internet. With SNTP, client computers can
synchronize their clocks via the Internet with a WI Weak end infeed
time server.
V
SOE Sequence of Events – An ordered,
time-stamped log of status changes at binary
VT Voltage transformer
inputs (also referred to as state inputs). SOE is
used to restore or analyze the performance, or VTS Voltage Circuit Supervision
an electrical power system itself, over a certain
period of time.

A list of function numbers used to represent electrical protection and control element. The device
function numbers used in this manual include the following:

21 Distance element 52 AC circuit breaker

25 Synchronism-check element 59 Overvoltage element

27 Undervoltage element 67 Directional overcurrent element

32 Power element 68 Power swing blocking element

37 Undercurrent element 78 Out-of-step element

46 Phase-balance current element 79 Reclosing element

49 Thermal overload element 81 Frequency element

50 Instantaneous overcurrent element 85 Pilot element

51 Definite-time or inverse-time overcurrent 87 Differential element


element
A
These numbers are frequently used within a suffix letter to further designate their application. The
suffix letters used in this instruction manual include the following:

PCS-9611S Feeder Relay 3


Date: 2019-04-24
Appendix A Glossary

P Phase element N Neutral/Ground element

G Residual/Ground element Q Negative-sequence element

4 PCS-9611S Feeder Relay


Date: 2019-04-24

You might also like