Professional Documents
Culture Documents
NR, the NR logo are either registered trademarks or trademarks of NR Electric Co., Ltd. No NR
trademarks may be used without written permission. NR products appearing in this document may
be covered by P.R. China and foreign patents. NR Electric Co., Ltd. reserves all rights and
benefits afforded under P.R. China and international copyright and patent laws in its products,
including but not limited to software, firmware and documentation. NR Engineering Co., Ltd. is
licensed to use this document as well as all intellectual property rights owned or held by NR
Electric Co., Ltd, including but not limited to copyright, rights in inventions, patents, know-how,
trade secrets, trademarks and trade names, service marks, design rights, database rights and
rights in data, utility models, domain names and all similar rights.
The information in this document is provided for informational use only and does not constitute a
legal contract between NR and any person or entity unless otherwise specified. Information in this
document is subject to change without prior notice.
To the extent required the products described herein meet applicable IEC and IEEE standards,
but no such assurance is given with respect to local codes and ordinances because they vary
greatly.
Although every reasonable effort is made to present current and accurate information, this
document does not purport to cover all details or variations in equipment nor provide for every
possible contingency to be met in connection with installation, operation, or maintenance. Should
further information be desired or should particular problems arise which are not covered
sufficiently for your purposes, please do not hesitate to contact us.
Preface
Preface
Safety Information
This manual is not a complete index of all safety measures required for operation of the
equipment (module or device). However, it comprises important information that must be followed
for personal safety, as well as to avoid material damage. Information is highlighted and illustrated
as follows according to the degree of danger:
Indicates that property damage can result if the measures specified are
not taken.
Contact with instrument terminals can cause electrical shock that can
result in injury or death.
Use of this equipment in a manner other than specified in this manual can
impair operator safety safeguards provided by this equipment.
Have only qualified personnel service this equipment. If you are not
qualified to service this equipment, you can injure yourself or others, or
cause equipment damage.
DO NOT connect power to the relay until you have completed these
procedures and receive instruction to apply power. Equipment damage
can result otherwise.
Document Conventions
The abbreviations and acronyms in this manual are explained in “Appendix A Glossary”. The
Glossary also contains definitions of important terms.
For example: refer to Figure 1.1-1, refer to Table 1.1-1, reference to Section 1.1
Binary input signals, binary output signals, analogs, LED lights, buttons, and other fixed
meanings, should be written in double quotes and bold.
Symbols
AND Gate
OR Gate
Comparator
BI xxx
Signal input
SIG xxx
Setting input
SET xxx
Enable input
EN xxx
Timer
Timer
t
t
Timer
10ms 2ms
Timer
[Tset1] 0ms
Timer
0ms [Tset2]
Timer
[Tset1] [Tset2]
Generator
Transformer
Reactor
Motor
Capacitor
Busbar
Circuit breaker
52
Current transformer
3CT
*
Voltage transformer
3VT
Disconnector
Earth
Example
Ia, Ib, Ic, I0 IL1, IL2, IL3, IN IR, IY, IB, IN
Ua, Ub, Uc VL1, VL2, VL3 UR, UY, UB
Uab, Ubc, Uca VL12, VL23, VL31 URY, UYB, UBR
U0, U1, U2 VN, V1, V2 UN, U1, U2
Warranty
This product is covered by the standard NR 10-year warranty. For warranty details, please consult
the manufacturer or agent for warranty information.
Document Structure
This manual is a comprehensive work covering the theories of protection, control, supervision,
measurement, etc. and the structure & technical data of relevant hardware. Read the sections that
pertain to your application to gain valuable information about using this device. To concentrate on
the target sections of this manual as your job needs and responsibilities dictate. An overview of
each manual section and section topics follows.
1 Introduction
Introduces the features of this device, summarizes functions and applications of the device.
2 Technical Data
Lists device specifications, type tests, and ratings.
3 Protection Functions
Describes the function of various protection elements, gives detailed specifics on protection
scheme logic, and provides the relevant logic diagrams.
4 Control Functions
Describes the logic for the control of disconnectors and circuit breakers.
5 Measurement
Provides information on viewing fundamental and metering quantities for voltages and currents,
as well as power and energy metering data.
6 Supervision
Describes self-supervision technique to help diagnose potential difficulties should these occur and
includes the list of status notification messages. Provides a troubleshooting chart for common
device operation problems.
7 System Functions
Describes how to perform fundamental operations such as clock synchronization, communicating
with the device, switching active setting group, checking relay status, reading event reports and
SER (Sequential Events Recorder) records.
8 Hardware
Describes the hardware of the PCS S series device family and provides general information on
the product structure and the modules’ information.
9 Settings
Provides a list of all PCS-9611S settings and their ranges, unit, steps, defaults. The organization
of the settings is similar to the settings organization in the device and in the PCS-Studio
configuration tool.
Appendix A Glossary
Describes the abbreviations adopted in this manual.
Corresponding Version
Date Description of change
Document Software
1 Introduction
1
Table of Contents
List of Figures
1.1 Application
The PCS-9611S relay is a protection, control and monitoring unit for various primary equipment
1
(such as overhead line, underground cable and transformer etc.) on solidly grounded, impedance
grounded, Peterson coil grounded and ungrounded system. This relay is suitable for wall surface
mounted indoors or outdoors or flush mounted into a control panel.
Busbar
3VTs
52
67P 32R
3CTs
*
1CT
*
1CT
*
Load
1.2 Functions
1 Protection functions
1
Voltage control element for each stage
Optional direction element for each stage, including
67P forward direction, reverse direction and non-direction
Phase overcurrent protection
50/51P Optional definite-time characteristic and inverse-time
characteristic for each stage
Selectable trip purpose or alarm purpose for each stage
Harmonic control element for each stage
Up to 6 stages with independent logic
Optional direction element for each stage, including
forward direction, reverse direction and non-direction
Optional measured zero-sequence current or calculated
67G
Earth fault protection zero-sequence current
50/51G
Optional definite-time characteristic and inverse-time
characteristic for each stage
Selectable trip purpose or alarm purpose for each stage
Harmonic control element for each stage
Only measured zero-sequence current is supported
Up to 6 stages with independent logic
A.67G Another group of earth fault
Optional definite-time characteristic and inverse-time
A.50/51G overcurrent protection
characteristic for each stage
Selectable trip purpose or alarm purpose for each stage
Up to 2 stages with independent logic
Optional direction element for each stage, including
Negative-sequence overcurrent forward direction, reverse direction and non-direction
50/51Q
protection Optional definite-time characteristic and inverse-time
characteristic for each stage
Selectable trip purpose or alarm purpose for each stage
The measured zero-sequence current from the
high-precision CT is adopted
Up to 6 stages with independent logic
Optional direction element for each stage, including
50/51SEF Sensitive earth fault protection
forward direction, reverse direction and non-direction
Optional definite-time characteristic and inverse-time
characteristic for each stage
Selectable trip purpose or alarm purpose for each stage
Up to 2 stages with independent logic
nd th
Full-current RMS value includes 2 ~11 harmonic
50/51R RMS overcurrent protection
component
Selectable trip purpose or alarm purpose for each stage
Optional blocking condition, including circuit breaker
37 Undercurrent protection position and current criterion
Selectable trip purpose or alarm purpose for each stage
2 Control functions
3 Measurement functions
Energy metering (active and reactive energy are calculated in import and export direction
respectively)
Power (Apparent/Active/Reactive)
Power factor
Frequency
Event recorder including 1024 disturbance items, 1024 binary events, 1024 supervision
events, 256 control logs and 1024 device logs.
Disturbance recorder including 64 disturbance records with waveforms (The file format of
disturbance recorder is compatible with international COMTRADE file.)
4 Supervision functions
VT circuit supervision
CT circuit supervision
Self diagnostic
5 Communication functions
6 User Interfaces
Friendly HMI interface with LCD, easy-to-use keypad aids simple navigation and
set-point adjustment
Push buttons for open/close, switch for selection between local and remote control, and
user's login and logout authority management
Configuration tool—PCS-Studio
7 Additional functions
Fault location
Clock synchronization
PPS: Pulse per second (PPS) via RS-485 differential level or binary input
PPM: Pulse per minute (PPM) via RS-485 differential level or binary input
Cyber security
NERC CIP
IEC 62351
IEC 62443
IEEE 1686
1.3 Features
Unified software and hardware platform, comprehensive power grid solutions of protection,
control, measurement and monitoring, easy to use and maintain.
High reliability and redundancy design for drive systems of the sampling circuit and the output
circuit ensure that overall reliability of the device is high. Real-time sampling based on dual AD
can mutually check and detect the potential abnormality in the sampling circuit in time. The
control power supply of the output relay is independent with the control circuit of trigger signals,
which can prevent from undesired operation caused by the abnormality of drive circuit of
output relays.
Various function modules can satisfy various situations according to the different requirements
of users. Flexible and universal logic programming, user-defined configuration of BI/BOs,
buttons and LEDs and powerful analog programming are supported.
Modularized hardware design makes the device be easily upgraded or repaired by a qualified
service person. It can be mixed with different I/O modules, with online self-check and
monitoring function, and the device can be restored from abnormal operation only need to
replace a single abnormal module.
Support memory check and error correction function, ensure high reliability and safety.
Fully compatible with IEC 61850 edition 1 & edition 2, support MMS service, IEC 62351
communication service, GOOSE communication in station level & process level, SV
communication with multi-sampling rate.
Full comply with cyber security standards, including IEC62443, IEC62351, IEEE1686,
NERC-CIP, support role based access control (RBAC), security audit, security encryption
communication and security tool, improve the cyber security capability of devices.
Powerful COMTRADE fault and disturbance recording function is supported. The whole
recording time is automatically configurable by the fault duration, which is convenient to fault
analysis and replay. The recording sample rate is up to 9.6kHz.
1
Settable secondary rated current (1A/5A) and settable voltage threshold of binary input
Support small size and large size LCD, control and multifunction button
Support flush mounting, semi-flush mounting, surface mounting, wall mounting and other
mounting methods.
Cross screw IO, CT/VT terminals can support AWG12 specification connector and 4mm 2 lead
PCS-Studio engineering tool is the application software on the user's PC for the interface with
PCS S series devices providing all the related functionality. It ranges from device configuration
to full substation design of bay integration.
Support actual system phase sequence, either ABC or ACB, incorrect connection of actual
phase sequence can automatically be verified and relevant protection functions can be
blocked.
Equipped with high-speed large capacity output relay, its operation speed is less than 1ms and
its break capacity is up to 10A. The real-time supervision for output drive circuit can detect the
abnormality in advance.
Support setup up to 40 users and allow each user to own different password and access
authority.
Fully integrates multi functions into one device and can realize the protection and monitoring
protection, breaker failure protection, undercurrent protection etc. The breaker failure,
The overcurrent protection is combined with harmonic blocking and cold load pickup logic,
which can prevent mal-operation affected by inrush current while the transformer is no-load
energized.
Selectable IEC, ANSI inverse-time characteristic curves, also the curve can be defined by
Overvoltage and undervoltage protection support single phase and three phase operation
1
criteria setting, phase voltage and phase-to-phase voltage measurement mode are selectable,
Complete event recording function is provided: 64 latest protection operation reports, 1024
latest supervision records, 1024 latest control operation records, 1024 latest user operation
records and 1024 latest records of time tagged sequence of event (SOE) can be recorded.
2 Technical Data
Table of Contents
Linear to 0.05In~40In
Thermal withstand
-continuously 4In
-for 1s 100In
Linear to 0.01A~5A
Thermal withstand
-continuously 20A
-for 1s 300A
2 Linear to 1V~300V
100Vac/110Vac/115Vac/120Vac
250Vac
Burden
Up to 34 (6U, 1/3, ring ferrule), 41 (6U, 1/3, pin ferrule), 84 (6U, 1/2,
Number ring ferrule) or 105 (6U, 1/2, pin ferrule) binary inputs according to
2
Settable pickup voltage and dropout voltage
Up to 34 (6U, 1/3, ring ferrule), 41 (6U, 1/3, pin ferrule), 84 (6U, 1/2,
Number ring ferrule) or 105 (6U, 1/2, pin ferrule) binary inputs according to
Up to 34 (6U, 1/3, ring ferrule), 41 (6U, 1/3, pin ferrule), 84 (6U, 1/2,
Number ring ferrule) or 105 (6U, 1/2, pin ferrule) binary inputs according to
Tripping/signaling contact
0.5A@48Vdc
0.35A@110Vdc
0.20A@220Vdc
0.15A@250Vdc
0.5A@48Vdc
0.35A@110Vdc
Cyclic Capacity (2.5 cycle/second,
0.30A@125Vdc
L/R=40ms)
0.20A@220Vdc
0.15A@250Vdc
30A@3s
Short duration current
50A@1s
Up to 18 (6U, 1/3, ring ferrule), 22 (6U, 1/3, pin ferrule), 44 (6U, 1/2,
Number ring ferrule) or 56 (6U, 1/2, pin ferrule) binary outputs according to
10A@48V
10A@110V
Breaking capacity (L/R=40ms)
10A@125V
10A@250V 2
10A@48V L/R=40ms
Cyclic Capacity (4cycles in 1 second,
10A@110V L/R=40ms
followed by 2 minutes idle for thermal
10A@125V L/R=40ms
dissipation)
10A@250V L/R=20ms
30A@3s
Short duration current
50A@1s
Device structure Plug-in modular type @ rear side, integrated front plate
Protection Class
Pollution degree Ⅱ
Altitude <3000m
Max. capacity 32
Connector type LC
Type RS-232
Isolation 500Vdc
Overvoltage category Ⅲ
IEC 60255-26:2013
Frequency sweep
Radiated amplitude-modulated
Spot frequency
Radiated amplitude-modulated
IEC 60255-26:2013
Fast transient disturbance tests Power supply, I/O, Earth: class Ⅳ, 4kV, 5kHz, 5/50ns
IEC 60255-26:2013
Conducted RF Electromagnetic
Power supply, AC, I/O, Comm. Terminal: Class Ⅲ, 10Vrms, 150 2
kHz~80MHz
Disturbance
Spot frequency
IEC 61000-4-9:2016
Pulse Magnetic Field Immunity
class Ⅴ, 6.4/16μs, 1000A/m for 3s
IEC 60255-26:2013
Conducted emission 0.15MHz~0.50MHz: 79dB (μV) quasi peak, 66dB (μV) average
IEC 60255-26:2013
peak @3m
Above 1GHz
3GHz~6GHz: 60dB (μV/m) average, 80dB (μV/m)
peak @3m
- Voltage dips
Up to 200ms for dips to 40% of rated voltage without reset
-Voltage short interruptions
50ms for interruption without rebooting without energy storage board
(Typical configuration)
2 (Typical configuration)
2.6 Certifications
ISO9001:2008
ISO14001:2004
OHSAS18001:2007
ISO10012:2003
CMMI L5
Type Resolution
2.8 Terminals
2
AC voltage Screw terminals, 0.8~4mm lead M4 1.6~1.8 N⋅m
2
Contact I/O Screw terminals, 0.8~4mm lead M4 0.8~1.4 N⋅m
2
Grounding (Earthing) Connection BVR type, 0.8~4mm lead M3 0.6~0.8 N⋅m
2
Contact I/O Screw terminals, 0.3~3.3mm lead M2.5 0.4~0.6 N⋅m
2
2.9 Measurement Scope and Accuracy
characteristics)
Operating time delay accuracy ≤5% of calculated value + 0.5% current tolerance or 35ms
Operating time delay accuracy ≤5% of calculated value + 0.5% current tolerance or 35ms
Operating time delay accuracy ≤1%×Setting or 25ms (at 2 times current setting)
Operating time delay accuracy ≤1%×Setting or 40ms (at 1.1 times voltage setting) 2
Dropout time accuracy ≤30ms
Operating time delay accuracy ≤1%×Setting or 40ms (at 1.1 times voltage setting)
Operating time delay accuracy ≤1%×Setting or 40ms (at 1.1 times voltage setting)
Operating time delay accuracy ≤1%×Setting or 25ms (at 2 times voltage setting)
Operating time delay accuracy ≤1%×Setting or 25ms (at 0.5 times current setting)
Operating time delay accuracy ≤1%×Setting or 10ms (at 2 times current setting)
Dropout ratio 1
Operating time delay accuracy ≤1%×Setting or 25ms (at 2 times current setting)
2 Operating time delay accuracy ≤1%×Setting or 35ms (at 1.1 times voltage setting)
Tolerance will be higher in case of single-phase fault with high ground resistance.
3 Protection Functions
Table of Contents
List of Figures
Figure 3.5-1 The enabling and blocking logic of phase overcurrent protection .................. 3-8
Figure 3.5-2 Logic diagram of the fault detector element of phase overcurrent protection3-8
Figure 3.5-3 Logic diagram of the voltage control element of phase overcurrent protection3-9
Figure 3.5-4 The direction element operation characteristics when phase A voltage is
polarized ..................................................................................................................................... 3-10
Figure 3.5-5 Logic diagram of forward and reverse direction element of phase overcurrent
protection ................................................................................................................................... 3-12
Figure 3.5-6 Logic diagram of harmonic control element of phase overcurrent protection3-13
Figure 3.5-9 Definite-time dropout characteristic of phase overcurrent protection .......... 3-17
Figure 3.6-1 The enabling and blocking logic of earth fault overcurrent protection ......... 3-38
Figure 3.6-2 Logic diagram of the fault detector element of earth fault overcurrent
protection ................................................................................................................................... 3-38
Figure 3.6-3 The direction element operation characteristics when zero-sequence voltage
is polarized ................................................................................................................................. 3-39
3
Figure 3.6-4 Logic diagram of forward and reverse direction element of earth fault
overcurrent protection .............................................................................................................. 3-40
Figure 3.6-5 Logic diagram of harmonic control element of earth fault overcurrent
protection ................................................................................................................................... 3-41
Figure 3.6-8 Definite-time dropout characteristic of earth fault overcurrent protection ... 3-44
Figure 3.6-9 Inverse-time dropout characteristic curve of earth fault overcurrent protection3-45
Figure 3.6-10 Inverse-time dropout characteristic of earth fault overcurrent protection . 3-46
Figure 3.7-1 The enabling and blocking logic of another group of earth fault overcurrent
protection ................................................................................................................................... 3-63
Figure 3.7-2 Logic diagram of the fault detector element of another group of earth fault
overcurrent protection .............................................................................................................. 3-64
Figure 3.7-3 Definite-time operation characteristic curve of another group of earth fault
overcurrent protection .............................................................................................................. 3-65
Figure 3.7-4 Inverse-time operation characteristic curve of another group of earth fault
overcurrent protection .............................................................................................................. 3-66
Figure 3.7-5 Definite-time dropout characteristic of another group of earth fault overcurrent
protection ................................................................................................................................... 3-67
Figure 3.7-6 Inverse-time dropout characteristic curve of another group of earth fault
overcurrent protection .............................................................................................................. 3-68
Figure 3.7-7 Inverse-time dropout characteristic of another group of earth fault overcurrent
Figure 3.7-8 Logic diagram of another group of earth fault overcurrent protection ......... 3-70
Figure 3.8-1 The enabling and blocking logic of negative-sequence overcurrent protection3-83
Figure 3.8-2 Logic diagram of the fault detector element of negative-sequence overcurrent
protection ................................................................................................................................... 3-83
Figure 3.8-4 Logic diagram of forward and reverse direction element of negative-sequence
3 overcurrent protection .............................................................................................................. 3-85
Figure 3.9-1 The enabling and blocking logic of sensitive earth fault protection ............. 3-98
Figure 3.9-2 Logic diagram of the fault detector element of sensitive earth fault protection3-98
Figure 3.9-3 The direction element operation characteristics of sensitive earth fault
protection ................................................................................................................................... 3-99
Figure 3.9-4 Logic diagram of forward and reverse direction element of sensitive earth fault
protection ................................................................................................................................. 3-100
Figure 3.9-5 Definite-time operation characteristic curve of sensitive earth fault protection3-102
Figure 3.9-6 Inverse-time operation characteristic curve of sensitive earth fault protection3-103
Figure 3.9-7 Definite-time dropout characteristic of sensitive earth fault protection ..... 3-104
Figure 3.9-8 Inverse-time dropout characteristic curve of sensitive earth fault protection3-105
Figure 3.9-9 Inverse-time dropout characteristic of sensitive earth fault protection ...... 3-106
Figure 3.9-10 Logic diagram of sensitive earth fault protection ........................................ 3-107
Figure 3.10-1 The enabling and blocking logic of RMS overcurrent protection .............. 3-119
Figure 3.10-2 Logic diagram of the fault detector element of RMS overcurrent protection3-119
Figure 3.10-4 Definite-time dropout characteristic of RMS overcurrent protection ........ 3-121
Figure 3.11-1 The enabling and blocking logic of phase overvoltage protection ............ 3-124
Figure 3.11-2 Logic diagram of the fault detector element of phase overvoltage protection3-125
Figure 3.12-1 The enabling and blocking logic of residual overvoltage protection ........ 3-134
Figure 3.12-2 Logic diagram of the fault detector element of residual overvoltage
protection ................................................................................................................................. 3-135
Figure 3.15-1 The enabling and blocking logic of phase undervoltage protection ......... 3-148
Figure 3.15-2 Logic diagram of the fault detector element of phase undervoltage protection
................................................................................................................................................... 3-150
Figure 3.16-2 Logic diagram of the fault detector of overfrequency protection .............. 3-161
Figure 3.17-2 Logic diagram of the fault detector of underfrequency protection ............ 3-165
Figure 3.18-2 Logic diagram of the fault detector of frequency rate-of-change protection3-169
Figure 3.18-3 Operation characteristic curve of frequency rate-of-change protection ... 3-170
Figure 3.18-4 Function block diagram of frequency rate-of-change protection .............. 3-170
Figure 3.19-1 Logic diagram of enabling/disabling reverse power protection ................ 3-173
Figure 3.19-2 Logic diagram of the fault detector of reverse power protection .............. 3-173
Figure 3.19-3 Operation characteristic curve of reverse power protection ...................... 3-174
Figure 3.19-4 Function block diagram of reverse power protection ................................. 3-175
Figure 3.20-1 Function block diagram of cold load pickup logic....................................... 3-177
Figure 3.20-2 Logic diagram of cold load pickup logic ....................................................... 3-178
Figure 3.21-2 Logic diagram of the fault detector of undercurrent protection ................ 3-183
Figure 3.22-2 Logic of breaker failure initiating signal abnormality .................................. 3-190 3
Figure 3.22-3 Logic of breaker failure protection ................................................................ 3-190
Figure 3.23-1 The enabling and blocking logic of SOTF protection .................................. 3-192
Figure 3.23-3 Logic of earth fault overcurrent SOTF protection ........................................ 3-196
Figure 3.24-3 Logic diagram of the fault detector of unbalance current protection........ 3-199
Figure 3.24-4 Operation characteristic curve of unbalance current protection ............... 3-199
Figure 3.24-5 Function block diagram of unbalance current protection .......................... 3-200
Figure 3.25-2 Logic diagram of enabling/disabling unbalance voltage protection ......... 3-202
Figure 3.25-3 Logic diagram of the fault detector of unbalance voltage protection ....... 3-203
Figure 3.25-4 Operation characteristic curve of unbalance voltage protection ............... 3-203
Figure 3.25-5 Function block diagram of unbalance voltage protection .......................... 3-204
List of Tables
Table 3.6-1 Input/output signals of earth fault overcurrent protection ............................... 3-46
Table 3.7-1 Input/output signals of another group of earth fault overcurrent protection . 3-69
Table 3.7-2 Settings of another group of earth fault overcurrent protection ...................... 3-70
Table 3.9-1 Input/output signals of sensitive earth fault protection .................................. 3-106
Table 3.20-1 Input/output signals of cold load pickup logic ............................................... 3-177
Three-phase current element is responsible for pre-processing three phase currents and
calculating sequence components, amplitudes and phase angles of three phase currents, etc. All
calculated information of three-phase current element is used for protection logic calculation.
When any phase current is greater than 0.04In, the input current signals are valid and the valid
signal will be outputted for programmable logic application.
CT circuit supervision of three-phase current is carried out by the CTS element, which can refer to
Section 3.28 for details.
TCUR3P
in_ia I3P
in_ib Ia_Sec
in_ic Ib_Sec
Ic_Sec
I1_Sec
3 I2_Sec
3I0_Cal_Sec
Ang(Ia-Ib)
Ang(Ib-Ic)
Ang(Ic-Ia)
Ang(Ia)
Ang(Ib)
Ang(Ic)
Ang(3I0_Cal)
Alm_CTS
Flg_OnLoad
3.1.4 Settings
Access path:
Three-phase voltage element is responsible for pre-processing three phase voltages and
calculating sequence components, amplitudes and phases of three phase voltages, etc. All
calculated information of three-phase voltage element is used for the protection logic calculation.
VT circuit failure supervision of three-phase voltage is carried out by the VTS element, which can
refer to Section 3.27 for details.
TVOL3P
in_ua U3P
in_ub Ua_Sec
in_uc Ub_Sec
BI_En_VT Uc_Sec
U1_Sec
3 U2_Sec
3U0_Cal_Sec
Ang(Ua-Ub)
Ang(Ub-Uc)
Ang(Uc-Ua)
Ang(Ua)
Ang(Ub)
Ang(Uc)
Ang(3U0_Cal)
Alm_VTS
3.2.4 Settings
Access path:
One-phase current element is responsible for pre-processing measured one-phase current and
calculating the magnitude and the phase angle of the one-phase current, etc. All calculated
information of one-phase current element is used for the protection logic calculation.
TCUR1P
x.in_ip x.I1P
x.3I0_Ext_Sec
x.Ang(3I0_Ext)
x.Flg_OnLoad
Access path:
One-phase voltage element is responsible for pre-processing one-phase voltage and calculating
the magnitude and the phase angle of the one-phase voltage, etc. All calculated information of
one-phase voltage element is used for the protection logic calculation.
TVOL1P
in_up U1P
BI_En_VT U_Sec
Ang(U)
3.4.4 Settings
Access path:
EN 50/51Px.En &
50/51Px.On
SIG 50/51Px.Enable
&
SIG 50/51Px.Block ≥1 50/51Px.Blocked
SIG Fail_Device
&
50/51Px.Valid
Figure 3.5-1 The enabling and blocking logic of phase overcurrent protection
The logic diagram of the fault detector element of phase overcurrent protection is as follows:
SET Ia>0.95×[50/51Px.I_Set]
>=1
SET Ib>0.95×[50/51Px.I_Set] &
0 500ms &
SET Ic>0.95×[50/51Px.I_Set]
50/51Px.Pkp
SIG 50/51Px.On
SIG 50/51Px.Valid
&
FD.Pkp
SET [50/51Px.Opt_Trp/Alm]=Alm
Figure 3.5-2 Logic diagram of the fault detector element of phase overcurrent protection
When a fault occurs at the remote end of a feeder, the fault current is relatively small, so the
voltage control element can be adopted to increase the sensitivity for this kind of fault. Users can
enable or disable the voltage control element via the setting [50/51Px.En_Volt_Blk] (x=1~6). If the
VT circuit supervision function is enabled for the device, and the setting [50/51P.En_VTS_Blk] is
set as “1”, when VT circuit failure happens, the device will issue a VT circuit failure alarm signal
[VTS.Alm], and the voltage controlled phase overcurrent protection will be blocked. If the voltage
control element of phase overcurrent protection is not enabled, phase overcurrent protection will
not effected by VT circuit failure. The corresponding relationship between the phase-segregated
overcurrent element and the voltage control element is as follows.
Voltage control
Phase A Phase B Phase C
criterion
Phase-to-phase Uab<[50/51P.VCE.Upp] Uab<[50/51P.VCE.Upp] Ubc<[50/51P.VCE.Upp]
criterion Uca<[50/51P.VCE.Upp] Ubc<[50/51P.VCE.Upp] Uca<[50/51P.VCE.Upp] 3
Negative-sequence
U2>[50/51P.VCE.U2] U2>[50/51P.VCE.U2] U2>[50/51P.VCE.U2]
criterion
Zero-sequence
U0_Cal>[50/51P.VCE.3U0] U0_Cal>[50/51P.VCE.3U0] U0_Cal>[50/51P.VCE.3U0]
criterion
The relationship between the phase-to-phase criterion, the negative-sequence criterion and the
zero-sequence criterion is "or". The logic diagram of the voltage control element action is shown
below:
EN [50/51P.En_VTS_Blk] &
>=1
SIG VTS.Alm
>=1
SIG Uab, Ubc, Uca & 50/51P.VCE.Op
criterion
Voltage
EN [En_VT]
Figure 3.5-3 Logic diagram of the voltage control element of phase overcurrent protection
In order to ensure the selectivity of phase overcurrent protection, direction control element is
introduced. The setting [50/51Px.Opt_Dir] (x=1~6) is used for users to select the directional mode
of each stage of phase overcurrent protection: no direction, forward direction and reverse
direction are selectable.
Takes the phase A fault as an example, the polarization mode is set as “Up”, its operation
characteristics are shown in the figure below. The principle of phase B and phase C is the same. If
the positive-sequence voltage or the phase-to-phase voltage is polarized, the operation
The operation boundary of the forward direction element can be set by [50/51P.DIR.phi_Min_Fwd]
and [50/51P.DIR.phi_Max_Fwd]. The operation boundary of the reverse direction element can be
set by [50/51P.DIR.phi_Min_Rev] and [50/51P.DIR.phi_Max_Rev].
Ua
[50/51P.DIR.phi_Min_Fwd]
3 Non-operating
area
Ia
[50/51P.DIR.RCA]
Operating area in
reverse direction
[50/51P.DIR.phi_Max_Fwd]
[50/51P.DIR.phi_Min_Rev] Non-operating
area
Figure 3.5-4 The direction element operation characteristics when phase A voltage is polarized
Where:
The sensitivity angle of the direction control element (RCA) can be set by the setting
[50/51P.DIR.RCA].
The selection of the polarization voltage can be set by the setting [50/51P.DIR.Opt_PolarizedVolt].
The following table shows the relationship between the operating current, the polarized voltage
and the polarization mode.
Direction criterion
Polarization Faulty Operating
Polarized voltage Angle difference
mode phase current
Phase-A Positive-sequence
Phase A Angle_A=Angle(U1)-Angle(Ia)-RCA
current Ia voltage
Positive-sequence Phase-B Positive-sequence
Phase B Angle_B=Angle(U1)-Angle(Ib)-RCA-120º
voltage polarized current Ib voltage
Phase-C Positive-sequence
Phase C Angle_C=Angle(U1)-Angle(Ic)-RCA+120º
current Ic voltage
Phase-to-phase Phase-A Phase-to-phase
Phase A Angle_A=Angle(Ubc)-Angle(Ia)-RCA+90º
voltage polarized current Ia voltage Ubc
Phase-B Phase-to-phase
Phase B Angle_B=Angle(Uca)-Angle(Ib)-RCA+90º
current Ib voltage Uca
Phase-C Phase-to-phase
Phase C Angle_C=Angle(Uab)-Angle(Ic)-RCA+90º
current Ic voltage Uab
Phase-A Phase-to-ground
Phase A Angle_A=Angle(Ua)-Angle(Ia)-RCA
current Ia voltage Ua
Phase-to-ground Phase-B Phase-to-ground
Phase B Angle_B=Angle(Ub)-Angle(Ib)-RCA
voltage polarized current Ib voltage Ub
Phase-C Phase-to-ground
Phase C Angle_C=Angle(Uc)-Angle(Ic)-RCA
current Ic voltage Uc
In order to improve the reliability of the direction control element, the direction control element with 3
the above three polarization modes must be used in conjunction with the negative-sequence
direction criterion. The negative-sequence direction criterion is shown in the table below.
Therefore, the criterion for the three-phase direction control element is as follows:
The direction element calculation needs to judge the voltage threshold and current threshold. The
direction can be judged only when both of the voltage and current are greater than the threshold,
choose a different polarization mode, the selection of voltage and current, and the threshold are
not the same, the specific principles are:
The direction element has memory function that can eliminate the dead zone of the direction
element when the close up three-phase short circuit fault occurs. When the polarized voltage is
less than the minimum operating voltage setting [50/51P.DIR.U_Min], the positive-sequence
voltage before two cycles is used to judge the direction. The polarized voltage will not be used to
judge the direction until it is greater than [50/51P.DIR.U_Min]. The logic diagram of the forward
direction element and reverse direction element is shown as below.
EN [50/51P.En_VTS_Blk] &
3 >=1
SIG VTS.Alm
SIG Memorized U1
SET [50/51P.DIR.Opt_PolarizedVolt]
EN [En_VT]
EN [50/51P.En_VTS_Blk] &
>=1
SIG VTS.Alm
50/51P.RevDir.Op
SIG Three-phase voltages
criterion
SIG Memorized U1
SET [50/51P.DIR.Opt_PolarizedVolt]
EN [En_VT]
Figure 3.5-5 Logic diagram of forward and reverse direction element of phase overcurrent protection
Where:
Memorized U1: the positive-sequence memory voltage, it refers to the positive-sequence voltage
of two cycles before the polarized voltage is less than the minimum operating voltage setting
[50/51P.DIR.U_Min], and it is calculated from the three-phase voltage.
When transformer and other equipment are energized without any load, the inrush current may be
generated, which may cause the mal-operation of the phase overcurrent protection. According to
the characteristics of high secondary harmonic component in the inrush current and low
secondary harmonic component in common fault current, the secondary harmonic control element
is added to prevent the phase overcurrent protection from mal-operation due to inrush current. For
the harmonic control element, the harmonic blocking mode can be selected through the setting
[50/51P.HMB.Opt_Blk], it can support phase locking, cross locking, and maximum phase locking.
The correspondences are shown in the following table:
Setting Value
Phase A
Harmonic blocking criterion
Phase B Phase C
3
1 PhaseBlk Ia2/Ia1>[50/51P.HMB.K_Hm2] Ib2/Ib1>[50/51P.HMB.K_Hm2] Ic2/Ic1>[50/51P.HMB.K_Hm2]
2 CrossBlk (Ia2/Ia1) or (Ib2/Ib1) or (Ic2/Ic1)> [50/51P.HMB.K_Hm2]
Max(Ia2, Ib2, Ic2)/Ia1> Max(Ia2, Ib2, Ic2)/Ib1> Max(Ia2, Ib2, Ic2)/Ic1>
3 MaxPhaseBlk
[50/51P.HMB.K_Hm2] [50/51P.HMB.K_Hm2] [50/51P.HMB.K_Hm2]
Where:
When the fundamental current is greater than the setting [50/51P.HMB.I_Rls], the harmonic
blocking element of the corresponding phase is released.
The following figure shows the logic diagram of the harmonic control element of phase
overcurrent protection.
SET Imax>[50/51P.HMB.I_Rls]
SET [50/51P.HMB.Opt_Blk]
Figure 3.5-6 Logic diagram of harmonic control element of phase overcurrent protection
Where:
Phase overcurrent protection can operate without time delay or operate with a definite-time limit, it
can also operate with an inverse-time limit, the characteristic curve meets the IEC60255-3 and
ANSI C37.112 standards. Phase overcurrent protection can support definite-time limit, IEC &
ANSI standard inverse time limit and user-defined inverse-time limit, users can select the wanted
operating curve by the setting [50/51Px.Opt_Curve] (x=1~6), the relationship between the value of
the setting and the curve is shown in the table below.
3
ANSIDefTime ANSI Definite Time - - - -
ANSILTE ANSI Long Time Extremely Inverse 64.07 2.0 0.25 30
ANSILTV ANSI Long Time Very Inverse 28.55 2.0 0.712 13.46
ANSILT ANSI Long Time Inverse 0.086 0.02 0.185 4.6
IECN IEC Normal Inverse 0.14 0.02 0 -
IECV IEC Very inverse 13.5 1.0 0 -
IEC IEC Inverse 0.14 0.02 0 -
IECE IEC Extremely inverse 80.0 2.0 0 -
IECST IEC Short-time inverse 0.05 0.04 0 -
IECLT IEC Long-time inverse 120.0 1.0 0 -
IECDefTime IEC Definite Time - - - -
UserDefine Programmable
Only when the setting [50/51Px.Opt_Curve] is set as “UserDefine”, i.e. the user-defined
inverse-time characteristic is selected, the settings [50/51Px.K], [50/51Px.C] and [50/51Px.Alpha]
are useful, the inverse-time operating curve is determined by the three settings.
Definite-time characteristic
When I > Ip , the protection operates with a time delay of top (i.e. the value of the setting
[50/51Px.t_Op]), and the operation characteristic curve is shown in the following figure:
t op
3
IP I
Inverse-time characteristic
When I > Ip , the inverse-time accumulator begins to accumulate, and the operating time is
affected by the applied current I . The operating time will decrease with the current increasing,
but the operating time shall not less than tmin , i.e. the setting [50/51Px.tmin] (x=1~6). The
inverse-time operation characteristic equation is:
k
t
c TMS
(I / I P ) 1
Where:
3 t min
IP ID I
When the applied current is not a fixed value, but changes with time, the operating behavior of the
protection is shown in the following equation:
T0
1
t ( I )dt
0
1
Where:
The supported dropout characteristics of the phase overcurrent protection include instantaneous
dropout, definite-time dropout and ANSI inverse-time dropout.
When the operating curve is selected as ANSI inverse-time characteristic, the dropout
characteristic can be selected as instantaneous dropout, definite-time dropout and ANSI
inverse-time dropout.
Instantaneous dropout
Definite-time dropout
When I <0.95* Ip , the protection drops out with a time delay of tdr (i.e. the value of the setting
[50/51Px.t_DropOut]), and the dropout characteristic curve is shown in the following figure:
Start time
I>Ip
Start
signal
3
Operating
signal
Protection
Operating threshold operate
Operating
counter
t dr t dr t dr
Dropout time setting
Dropout time
Dropout time
Inverse-time dropout
When I > Ip , the inverse-time operating accumulator begins to accumulate, the accumulated
value after tp (Assuming tp is less than the theoretical operating time) is calculated according
to the following equation:
tp
1
I tp dt
0
t ( I )
At this time, if I <0.95* Ip , the protection element starts dropout, and the dropout characteristic
meets the following equation:
TR
1
I tp dt 0
t (I )
0 R
Where:
tr
tR 2
TMS
1 ( I / I P )
Where:
tr is the dropout time coefficient, it is the dropout time required for the current to drop to 0 after
3 the protection operates.
The inverse time dropout characteristic curve is shown in the figure below.
tr
IP I
The correspondence between the start signal, operating signal, and operating accumulator in the
inverse-time dropout characteristic is shown in the figure below:
Start time
I>Ip
Start
signal
Operating
signal
Operating threshold
Protection
operate
3
Operating
counter
50/51P
50/51Px.Enable 50/51Px.On
50/51Px.Block 50/51Px.Blocked
50/51Px.Valid
50/51Px.St
50/51Px.StA
50/51Px.StB
50/51Px.StC
50/51Px.Op
50/51Px.Op.PhA
50/51Px.Op.PhB
50/51Px.Op.PhC
50/51P.FwdDir.Op
50/51P.RevDir.Op
50/51Px.Alm
3.5.4 Logic
SET Ia>[50/51Px.I_Set]
EN [50/51Px.En_Volt_Blk]
SIG 50/51P.FwdDir.Op_A
selection
Direction
SIG 50/51P.RevDir.Op_A
3
SIG 50/51P.HMB.Op_A & & Timer
t
&
t
EN [50/51Px.En_Hm_Blk] 50/51Px.Op.PhA
SIG 50/51Px.Pkp
SET [50/51Px.Opt_Trp/Alm]=Trp
&
50/51Px.Alm.PhA
SET [50/51Px.Opt_Trp/Alm]=Alm
SIG 50/51Px.StA
>=1
SIG 50/51Px.StB 50/51Px.St
SIG 50/51Px.StC
SIG 50/51Px.Op.PhA
>=1
SIG 50/51Px.Op.PhB 50/51Px.Op
SIG 50/51Px.Op.PhC
SIG 50/51Px.Alm.PhA
>=1
SIG 50/51Px.Alm.PhB 50/51Px.Alm
SIG 50/51Px.Alm.PhC
3.5.5 Settings
Access path:
Default
No. Settings Range Unit Step Description
value
The low voltage blocking setting
1 50/51P.VCE.Upp 10~100 70 V 0.001 of the voltage control element of
phase overcurrent protection
Default
No. Settings Range Unit Step Description
value
The negative-sequence voltage
blocking setting of the voltage
2 50/51P.VCE.U2 2~57 8 V 0.001
control element of phase
overcurrent protection
The residual voltage setting (set
according to 3U0) of voltage
3 50/51P.VCE.3U0 2~57 8 V 0.001
control element of phase
overcurrent protection
Default
No. Settings Range Unit Step Description
value
The minimum operating voltage
setting for the direction control
12 50/51P.DIR.U_Min 1~10 4 V 0.001
element of phase overcurrent
protection
Logic setting to determine the
behavior of phase overcurrent
protection when VT circuit
supervision function is enabled
Disabled;
and VT circuit failure happens.
Disabled: phase overcurrent
3
13 50/51P.En_VTS_Blk Disabled - -
Enabled protection will not effected by VT
circuit failure
Enabled: voltage controlled
phase overcurrent protection will
be blocked by VT circuit failure
signal
The percent setting of the
50/51P.HMB.K_Hm
14 0.1~1 0.2 - 0.001 harmonic control element of
2
phase overcurrent protection
The current setting for releasing
15 50/51P.HMB.I_Rls 2~150 20 A 0.001 the harmonic control element of
phase overcurrent protection
The setting used to select the
harmonic blocking mode of
PhaseBlk phase overcurrent protection
50/51P.HMB.Opt_Bl
16 CrossBlk PhaseBlk - - PhaseBlk: phase blocking
k
MaxPhaseBlk CrossBlk: cross blocking
MaxPhaseBlk: maximum phase
blocking
The current setting of stage 1 of
17 50/51P1.I_Set 0.05~200 15 A 0.001
phase overcurrent protection
The operating time setting of
18 50/51P1.t_Op 0 ~100 0.1 s 0.001 stage 1 of phase overcurrent
protection
The dropout time setting of
19 50/51P1.t_DropOut 0 ~100 0 s 0.001 stage 1 of phase overcurrent
protection
Default
No. Settings Range Unit Step Description
value
The logic setting for
enabling/disabling the voltage
control element of stage 1 of
phase overcurrent protection
Disabled: stage 1 of phase
50/51P1.En_Volt_Bl Disabled; overcurrent protection is not
20 Disabled - -
k Enabled controlled by the voltage control
element
Default
No. Settings Range Unit Step Description
value
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
ANSILT; inverse-time operation
25 50/51P1.Opt_Curve IECDefTime - -
IECN;
IECV;
characteristic curve of stage 1 of
phase overcurrent protection.
3
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 1 of
50/51P1.Opt_Curve
26 DefTime; Inst - - phase overcurrent protection
_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
27 50/51P1.TMS 0.04~ 20 1 - 0.001 stage 1 of phase overcurrent
protection
The minimum operating time
28 50/51P1.tmin 0 ~10 0.02 s 0.001 setting of stage 1 of phase
overcurrent protection
The constant “k” of the
customized inverse-time
0.000
29 50/51P1.K 0.001~120 0.14 - operation characteristic of stage
1
1 of phase overcurrent
protection
The constant “α” of the
customized inverse-time
0.000
30 50/51P1.Alpha 0.01 ~3 0.02 - operation characteristic of stage
1
1 of phase overcurrent
protection
Default
No. Settings Range Unit Step Description
value
The constant “C” of the
customized inverse-time
0.000
31 50/51P1.C 0 ~1 0 - operation characteristic of stage
1
1 of phase overcurrent
protection
The current setting of stage 1 of
32 50/51P1.I_Set 0.05~200 15 A 0.001
phase overcurrent protection
The operating time setting of
Default
No. Settings Range Unit Step Description
value
The logic setting for
Disabled;
38 50/51P2.En Enabled - - enabling/disabling the stage 2 of
Enabled
phase overcurrent protection
Enabling stage 2 of phase
overcurrent protection operate
50/51P2.Opt_Trp/Al Trp;
39 Trp - - to trip or alarm.
m Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
3
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
ANSILT; inverse-time operation
40 50/51P2.Opt_Curve IECDefTime - -
IECN; characteristic curve of stage 2 of
IECV; phase overcurrent protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 2 of
50/51P2.Opt_Curve
41 DefTime; Inst - - phase overcurrent protection
_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
42 50/51P2.TMS 0.04~ 20 1 - 0.001 stage 2 of phase overcurrent
protection
The minimum operating time
43 50/51P2.tmin 0 ~10 0.02 s 0.001 setting of stage 2 of phase
overcurrent protection
The constant “k” of the
customized inverse-time
0.000
44 50/51P2.K 0.001~120 0.14 - operation characteristic of stage
1
2 of phase overcurrent
protection
Default
No. Settings Range Unit Step Description
value
The constant “α” of the
customized inverse-time
0.000
45 50/51P2.Alpha 0.01 ~3 0.02 - operation characteristic of stage
1
2 of phase overcurrent
protection
The constant “C” of the
customized inverse-time
0.000
46 50/51P2.C 0 ~1 0 - operation characteristic of stage
1
3 2 of
protection
phase overcurrent
Default
No. Settings Range Unit Step Description
value
The logic setting for
enabling/disabling the harmonic
control element of stage 3 of
phase overcurrent protection
Disabled: stage 3 of phase
50/51P3.En_Hm_Bl Disabled; overcurrent protection is not
52 Disabled - -
k Enabled controlled by the harmonic
control element
Enabled: stage 3 of phase
overcurrent protection is
3
controlled by the harmonic
control element
The logic setting for
Disabled;
53 50/51P3.En Enabled - - enabling/disabling the stage 3 of
Enabled
phase overcurrent protection
Enabling stage 3 of phase
overcurrent protection operate
50/51P3.Opt_Trp/Al Trp;
54 Trp - - to trip or alarm.
m Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
ANSILT; inverse-time operation
55 50/51P3.Opt_Curve IECDefTime - -
IECN; characteristic curve of stage 3 of
IECV; phase overcurrent protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
Default
No. Settings Range Unit Step Description
value
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 3 of
50/51P3.Opt_Curve
56 DefTime; Inst - - phase overcurrent protection
_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
Default
No. Settings Range Unit Step Description
value
The logic setting for
enabling/disabling the voltage
control element of stage 4 of
phase overcurrent protection
Disabled: stage 4 of phase
50/51P4.En_Volt_Bl Disabled; overcurrent protection is not
65 Disabled - -
k Enabled controlled by the voltage control
element
Enabled: stage 4 of phase
overcurrent protection is
3
controlled by the voltage control
element
Non_Directional The setting used to select the
Non_Directio
66 50/51P4.Opt_Dir Forward - - directional mode of stage 4 of
nal
Reverse phase overcurrent protection.
The logic setting for
enabling/disabling the harmonic
control element of stage 4 of
phase overcurrent protection
Disabled: stage 4 of phase
50/51P4.En_Hm_Bl Disabled; overcurrent protection is not
67 Disabled - -
k Enabled controlled by the harmonic
control element
Enabled: stage 4 of phase
overcurrent protection is
controlled by the harmonic
control element
The logic setting for
Disabled;
68 50/51P4.En Enabled - - enabling/disabling the stage 4 of
Enabled
phase overcurrent protection
Enabling stage 4 of phase
overcurrent protection operate
50/51P4.Opt_Trp/Al Trp;
69 Trp - - to trip or alarm.
m Alm
Trp: for tripping purpose
Alm: for alarm purpose
Default
No. Settings Range Unit Step Description
value
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
ANSILT; inverse-time operation
70 50/51P4.Opt_Curve IECDefTime - -
3 IECN;
IECV;
characteristic curve of stage 4 of
phase overcurrent protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 4 of
50/51P4.Opt_Curve
71 DefTime; Inst - - phase overcurrent protection
_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
72 50/51P4.TMS 0.04~ 20 1 - 0.001 stage 4 of phase overcurrent
protection
The minimum operating time
73 50/51P4.tmin 0 ~10 0.02 s 0.001 setting of stage 4 of phase
overcurrent protection
The constant “k” of the
customized inverse-time
0.000
74 50/51P4.K 0.001~120 0.14 - operation characteristic of stage
1
4 of phase overcurrent
protection
The constant “α” of the
customized inverse-time
0.000
75 50/51P4.Alpha 0.01 ~3 0.02 - operation characteristic of stage
1
4 of phase overcurrent
protection
Default
No. Settings Range Unit Step Description
value
The constant “C” of the
customized inverse-time
0.000
76 50/51P4.C 0 ~1 0 - operation characteristic of stage
1
4 of phase overcurrent
protection
The current setting of stage 5 of
77 50/51P5.I_Set 0.05~200 15 A 0.001
phase overcurrent protection
The operating time setting of
78 50/51P5.t_Op 0 ~100 0.1 s 0.001 stage 5 of phase overcurrent
protection
3
The dropout time setting of
79 50/51P5.t_DropOut 0 ~100 0 s 0.001 stage 5 of phase overcurrent
protection
The logic setting for
enabling/disabling the voltage
control element of stage 5 of
phase overcurrent protection
Disabled: stage 5 of phase
50/51P5.En_Volt_Bl Disabled; overcurrent protection is not
80 Disabled - -
k Enabled controlled by the voltage control
element
Enabled: stage 5 of phase
overcurrent protection is
controlled by the voltage control
element
Non_Directional The setting used to select the
Non_Directio
81 50/51P5.Opt_Dir Forward - - directional mode of stage 5 of
nal
Reverse phase overcurrent protection.
The logic setting for
enabling/disabling the harmonic
control element of stage 5 of
phase overcurrent protection
Disabled: stage 5 of phase
50/51P5.En_Hm_Bl Disabled; overcurrent protection is not
82 Disabled - -
k Enabled controlled by the harmonic
control element
Enabled: stage 5 of phase
overcurrent protection is
controlled by the harmonic
control element
Default
No. Settings Range Unit Step Description
value
The logic setting for
Disabled;
83 50/51P5.En Enabled - - enabling/disabling the stage 5 of
Enabled
phase overcurrent protection
Enabling stage 5 of phase
overcurrent protection operate
50/51P5.Opt_Trp/Al Trp;
84 Trp - - to trip or alarm.
m Alm
Trp: for tripping purpose
Alm: for alarm purpose
3 ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
ANSILT; inverse-time operation
85 50/51P5.Opt_Curve IECDefTime - -
IECN; characteristic curve of stage 5 of
IECV; phase overcurrent protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 5 of
50/51P5.Opt_Curve
86 DefTime; Inst - - phase overcurrent protection
_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
87 50/51P5.TMS 0.04~ 20 1 - 0.001 stage 5 of phase overcurrent
protection
The minimum operating time
88 50/51P5.tmin 0 ~10 0.02 s 0.001 setting of stage 5 of phase
overcurrent protection
The constant “k” of the
customized inverse-time
0.000
89 50/51P5.K 0.001~120 0.14 - operation characteristic of stage
1
5 of phase overcurrent
protection
Default
No. Settings Range Unit Step Description
value
The constant “α” of the
customized inverse-time
0.000
90 50/51P5.Alpha 0.01 ~3 0.02 - operation characteristic of stage
1
5 of phase overcurrent
protection
The constant “C” of the
customized inverse-time
0.000
91 50/51P5.C 0 ~1 0 - operation characteristic of stage
1
5 of
protection
phase overcurrent
3
The current setting of stage 6 of
92 50/51P6.I_Set 0.05~200 15 A 0.001
phase overcurrent protection
The operating time setting of
93 50/51P6.t_Op 0 ~100 0.1 s 0.001 stage 6 of phase overcurrent
protection
The dropout time setting of
94 50/51P6.t_DropOut 0 ~100 0 s 0.001 stage 6 of phase overcurrent
protection
The logic setting for
enabling/disabling the voltage
control element of stage 6 of
phase overcurrent protection
Disabled: stage 6 of phase
50/51P6.En_Volt_Bl Disabled; overcurrent protection is not
95 Disabled - -
k Enabled controlled by the voltage control
element
Enabled: stage 6 of phase
overcurrent protection is
controlled by the voltage control
element
Non_Directional The setting used to select the
Non_Directio
96 50/51P6.Opt_Dir Forward - - directional mode of stage 6 of
nal
Reverse phase overcurrent protection.
Default
No. Settings Range Unit Step Description
value
The logic setting for
enabling/disabling the harmonic
control element of stage 6 of
phase overcurrent protection
Disabled: stage 6 of phase
50/51P6.En_Hm_Bl Disabled; overcurrent protection is not
97 Disabled - -
k Enabled controlled by the harmonic
control element
Default
No. Settings Range Unit Step Description
value
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 6 of
50/51P6.Opt_Curve
101 DefTime; Inst - - phase overcurrent protection
_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
102 50/51P6.TMS 0.04~ 20 1 - 0.001 stage 6 of phase overcurrent
protection
3
The minimum operating time
103 50/51P6.tmin 0 ~10 0.02 s 0.001 setting of stage 6 of phase
overcurrent protection
The constant “k” of the
customized inverse-time
0.000
104 50/51P6.K 0.001~120 0.14 - operation characteristic of stage
1
6 of phase overcurrent
protection
The constant “α” of the
customized inverse-time
0.000
105 50/51P6.Alpha 0.01 ~3 0.02 - operation characteristic of stage
1
6 of phase overcurrent
protection
The constant “C” of the
customized inverse-time
0.000
106 50/51P6.C 0 ~1 0 - operation characteristic of stage
1
6 of phase overcurrent
protection
The device can provide six stages of earth fault overcurrent protection with independent logic.
Each stage can be independently set as definite-time characteristics or inverse-time
characteristics. The dropout characteristics can be set as instantaneous dropout, definite-time
dropout or inverse-time dropout. Users can choose whether it is blocked by the direction control
element or the harmonic control element, users can also choose whether it is controlled by cold
load pickup. The direction control element can be set as no direction, forward direction and
reverse direction. The zero-sequence current used by earth fault overcurrent protection can be
calculated zero-sequence current or the measured zero-sequence current, it can operate to trip or
alarm, it can be enabled or blocked by the external binary input.
Earth fault overcurrent protection can be enabled or disabled via the settings or binary input
signals, for some specific applications, the protection needs to be blocked by the external signal,
so the device provides a function block input signal to be used to block earth fault overcurrent
protection. The enabling and blocking logic of earth fault overcurrent protection is shown in the
3 figure below:
EN 50/51Gx.En &
50/51Gx.On
SIG 50/51Gx.Enable
&
SIG 50/51Gx.Block ≥1 50/51Gx.Blocked
SIG Fail_Device
&
50/51Gx.Valid
Figure 3.6-1 The enabling and blocking logic of earth fault overcurrent protection
The logic diagram of the fault detector element of earth fault overcurrent protection is as follows:
EN [50/51Gx.Opt_Trp/Alm]=Alm
Figure 3.6-2 Logic diagram of the fault detector element of earth fault overcurrent protection
In order to ensure the selectivity of earth fault overcurrent protection, direction control element is
introduced. The setting [50/51Gx.Opt_Dir] (x=1~6) is used for users to select the directional mode
of each stage of earth fault overcurrent protection: no direction, forward direction and reverse
direction are selectable.
The operation boundary of the forward direction element can be set by [50/51G.DIR.phi_Min_Fwd]
and [50/51G.DIR.phi_Max_Fwd]. The operation boundary of the reverse direction element can be
set by [50/51G.DIR.phi_Min_Rev] and [50/51G.DIR.phi_Max_Rev].
-U0
[50/51G.DIR.phi_Min_Fwd]
Non-operating I0
area
Operating area in
[50/51G.DIR.phi_Max_Rev] forward direction
[50/51G.DIR.RCA]
Operating area in
reverse direction
3
[50/51G.DIR.phi_Max_Fwd]
Non-operating
area
[50/51G.DIR.phi_Min_Rev]
Figure 3.6-3 The direction element operation characteristics when zero-sequence voltage is polarized
Where:
The sensitivity angle of the direction control element (RCA) can be set by the setting
[50/51G.DIR.RCA].
-[50/51G.DIR.phi_Min_Fwd]<angle<[50/51G.DIR.phi_Max_Fwd]
180-[50/51G.DIR.phi_Min_Rev]<angle<180+[50/51G.DIR.phi_Max_Rev]
The following table shows the relationship between the operating current, the polarized voltage
and the polarization mode.
Polarized
Polarization mode Operating current Angle difference
voltage
Zero-sequence Calculated residual current 3I0_Cal -3U0 angle=angle(-3U0)-angle(3I0_Cal)-RCA
voltage polarized Measured residual current 3I0_Ext -3U0 angle=angle(-3U0)-angle(3I0_Ext)-RCA
The logic diagram of the forward direction element and reverse direction element is as follows.
EN [50/51G.En_VTS_Blk] &
>=1
SIG VTS.Alm
direction
Forward
criterion
50/51G.FwdDir.Op
SIG 3U0_Cal
3 EN [En_VT] &
SIG Prot.BI_En_VT
EN [50/51G.En_VTS_Blk] &
>=1
SIG VTS.Alm
& >=1
SIG 3I0_Ext, 3I0_Cal 50/51G.RevDir.Op
direction
Reverse
criterion
SIG 3U0_Cal
EN [En_VT] &
SIG Prot.BI_En_VT
Figure 3.6-4 Logic diagram of forward and reverse direction element of earth fault overcurrent protection
Where:
Zero-sequence harmonic control element can be used together with earth fault overcurrent
protection when harmonic blocking is required, the zero-sequence current can be the calculated
zero-sequence current or the measured zero-sequence current.
When the fundamental zero-sequence current is greater than the setting [50/51G.HMB.I_Rls], the
harmonic blocking element is released.
The following figure shows the logic diagram of the harmonic control element of earth fault
overcurrent protection.
SET 3I0>[50/51G.HMB.I_Rls]
&
SIG 3I0_Ext or 3I0_Cal
50/51G.Hm_Op
Harmonic
blocking
logi c
3
SET 3I02/3I0>[50/51G.HMB.K_Hm2]
Figure 3.6-5 Logic diagram of harmonic control element of earth fault overcurrent protection
Where:
3I0_Ext, 3I0_Cal: the measured residual current and the calculated residual current
Earth fault overcurrent protection can operate without time delay or operate with a definite-time
limit, it can also operate with an inverse-time limit, the characteristic curve meets the IEC60255-3
and ANSI C37.112 standards. Earth fault overcurrent protection can support definite-time limit,
IEC & ANSI standard inverse time limit and user-defined inverse-time limit, users can select the
wanted operating curve by the setting [50/51Gx.Opt_Curve], the relationship between the value of
the setting and the curve is shown in the table below.
Only when the setting [50/51Gx.Opt_Curve] is set as “UserDefine”, i.e. the user-defined
inverse-time characteristic is selected, the settings [50/51Gx.K], [50/51Gx.C] and [50/51Gx.Alpha]
are useful, the inverse-time operating curve is determined by the three settings.
Definite-time characteristic
When I 0 > I 0 p , the protection operates with a time delay of top (i.e. the value of the setting
[50/51Gx.t_Op]), and the operation characteristic curve is shown in the following figure:
3 t
t op
I0p I0
Figure 3.6-6 Definite-time operation characteristic curve of earth fault overcurrent protection
Inverse-time characteristic
When I 0 > I 0 p , the inverse-time accumulator begins to accumulate, and the operating time is
affected by the applied current I 0 . The larger current is, the smaller the operating time is, but not
unlimited. When the current is large enough to a certain threshold ( I 0 p ), the inverse-time
operating time will not continue to decrease, then the operation characteristic becomes the
definite-time characteristic, and the operating time is tmin , i.e. the setting [50/51Gx.tmin]. The
inverse-time operation characteristic equation is:
k
t
c TMS
(I 0 / I 0P ) 1
Where:
t min
I0P ID I0
Figure 3.6-7 Inverse-time operation characteristic curve of earth fault overcurrent protection
When the applied zero-sequence current I 0 is not a fixed value, but changes with time, the
operating behavior of the protection is shown in the following equation:
T0
1
t ( I )dt
0 0
1
Where:
The supported dropout characteristics of the earth fault overcurrent protection include
instantaneous dropout, definite-time dropout and ANSI inverse-time dropout.
When the operating curve is selected as ANSI inverse-time characteristic, the dropout
characteristic can be selected as instantaneous dropout, definite-time dropout and ANSI
inverse-time dropout.
Instantaneous dropout
Definite-time dropout
When I 0 <0.95* I 0 p , the protection drops out with a time delay of tdr (i.e. the value of the
setting [50/51Gx.t_DropOut]), the dropout characteristic curve is shown in the following figure:
Start time
I0>I0p
3
Start
signal
Operating
signal
Protection
Operating threshold operate
Operating
counter
t dr t dr t dr
Dropout time setting
Dropout time
Dropout time
Inverse-time dropout
When I 0 > I 0 p , the inverse-time operating accumulator begins to accumulate, the accumulated
value after tp (Assuming tp is less than the theoretical operating time) is calculated according
to the following equation:
tp
1
Itp t(I
0
0
dt
)
At this time, if I 0 <0.95* I 0 p , the protection element starts dropout, and the dropout characteristic
meets the following equation:
TR
1
I tp dt 0
0
t R ( I )
Where:
tr
tR 2
TMS
1 ( I / I P )
Where:
tr is the dropout time coefficient, it is the dropout time required for the current to drop to 0 after
the protection operates.
The inverse time dropout characteristic curve is shown in the figure below.
tr
I0 P I0
Figure 3.6-9 Inverse-time dropout characteristic curve of earth fault overcurrent protection
The correspondence between the start signal, operating signal, and operating accumulator in the
inverse-time dropout characteristic is shown in the figure below:
Start time
I0>I0p
Start
signal
Operating
signal
3 Operating threshold
Protection
operate
Operating
counter
50/51G
50/51Gx.Enable 50/51Gx.On
50/51Gx.Block 50/51Gx.Blocked
50/51Gx.Valid
50/51Gx.St
50/51Gx.Op
50/51Gx.Alm
50/51Gx.FwdDir.Op
50/51Gx.RevDir.Op
3.6.4 Logic
3
SET 3I0>[50/51Gx.3I0_Set]
EN [50/51Gx.En_Hm_Blk]
SIG 50/51Gx.Pkp
&
50/51Gx.Op
SET [50/51Gx.Opt_Trp/Alm]=Trp
&
50/51Gx.Alm
SET [50/51Gx.Opt_Trp/Alm]=Alm
3.6.5 Settings
Access path:
Default Uni
No. Settings Range Step Description
value t
The relay characteristic angle
of the direction control
1 50/51G.DIR.RCA -180~179 45 deg 1
element of earth fault
overcurrent protection
Default Uni
No. Settings Range Step Description
value t
The minimum boundary of the
50/51G.DIR.phi_Min_ forward direction element of
2 10~90 90 deg 1
Fwd earth fault overcurrent
protection
The maximum boundary of the
50/51G.DIR.phi_Max_ forward direction element of
3 10~90 90 deg 1
Fwd earth fault overcurrent
protection
3 50/51G.DIR.phi_Min_
The minimum boundary of the
reverse direction element of
4 10~90 90 deg 1
Rev earth fault overcurrent
protection
The maximum boundary of the
50/51G.DIR.phi_Max_ reverse direction element of
5 10~90 90 deg 1
Rev earth fault overcurrent
protection
The minimum operating
current setting for the direction
6 50/51G.DIR.I_Min (0.05~1)In 0.05 - 0.001
control element of earth fault
overcurrent protection
The minimum operating
voltage setting for the direction
7 50/51G.DIR.U_Min 1~10 4 V 0.001
control element of earth fault
overcurrent protection
Logic setting to determine the
behavior of earth fault
overcurrent protection when
VT circuit supervision function
is enabled and VT circuit
failure happens.
Disabled;
8 50/51G.En_VTS_Blk Disabled - - Disabled: earth fault
Enabled
overcurrent protection will not
effected by VT circuit failure
Enabled: voltage controlled
earth fault overcurrent
protection will be blocked by
VT circuit failure signal
The percent setting of the
harmonic control element of
9 50/51G.HMB.K_Hm2 0.1~1 0.2 - 0.001
earth fault overcurrent
protection
Default Uni
No. Settings Range Step Description
value t
The current setting for
releasing the harmonic control
10 50/51G.HMB.I_Rls 2~150 20 A 0.001
element of earth fault
overcurrent protection
The setting used to select the
residual current that used for
stage 1 of earth fault
Ext; overcurrent protection
11 50/51G1.Opt_3I0 Ext - -
Cal Ext: the measured residual
current
3
Cal: the calculated residual
current
The current setting of stage 1
12 50/51G1.3I0_Set 0.05~200 15 A 0.001 of earth fault overcurrent
protection
The operating time setting of
13 50/51G1.t_Op 0 ~100 0.1 s 0.001 stage 1 of earth fault
overcurrent protection
The dropout time setting of
14 50/51G1.t_DropOut 0 ~100 0 s 0.001 stage 1 of earth fault
overcurrent protection
The setting used to select the
directional mode of stage 1 of
Non_Direction
earth fault overcurrent
al; Non_Directio
15 50/51G1.Opt_Dir - - protection.
Forward; nal
1: no direction;
Reverse
2: forward direction;
3: reverse direction.
The logic setting for
enabling/disabling the
harmonic control element of
the stage 1 of earth fault
overcurrent protection
Disabled: stage 1 of earth fault
Disabled;
16 50/51G1.En_Hm_Blk Disabled - - overcurrent protection is not
Enabled
controlled by the harmonic
control element
Enabled: stage 1 of earth fault
overcurrent protection is
controlled by the harmonic
control element
Default Uni
No. Settings Range Step Description
value t
The logic setting for
Disabled; enabling/disabling the stage 1
17 50/51G1.En Enabled - -
Enabled of earth fault overcurrent
protection
Enabling stage 1 earth fault
overcurrent protection operate
Trp;
18 50/51G1.Opt_Trp/Alm Trp - - to trip or alarm.
Alm
Trp: for tripping purpose
3 ANSIE;
Alm: for alarm purpose
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
The setting for selecting the
ANSILTV;
inverse-time operation
ANSILT;
19 50/51G1.Opt_Curve IECDefTime - - characteristic curve of stage 1
IECN;
of earth fault overcurrent
IECV;
protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
characteristic curve of stage 1
Inst;
50/51G1.Opt_Curve_ of earth fault overcurrent
20 DefTime; Inst - -
DropOut protection
IDMT
Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
21 50/51G1.TMS 0.04~ 20 1 - 0.001 stage 1 of earth fault
overcurrent protection
The minimum operating time
22 50/51G1.tmin 0 ~10 0.02 s 0.001 setting of stage 1 of earth fault
overcurrent protection
Default Uni
No. Settings Range Step Description
value t
The constant “k” of the
customized inverse-time
23 50/51G1.K 0.001~120 0.14 - 0.0001 operation characteristic of
stage 1 of earth fault
overcurrent protection
The constant “α” of the
customized inverse-time
24 50/51G1.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of
stage 1 of
overcurrent protection
earth fault
3
The constant “C” of the
customized inverse-time
25 50/51G1.C 0 ~1 0 - 0.0001 operation characteristic of
stage 1 of earth fault
overcurrent protection
The setting used to select the
residual current that used for
stage 2 of earth fault
Ext; overcurrent protection
26 50/51G2.Opt_3I0 Ext - -
Cal Ext: the measured residual
current
Cal: the calculated residual
current
The current setting of stage 2
27 50/51G2.3I0_Set 0.05~200 15 A 0.001 of earth fault overcurrent
protection
The operating time setting of
28 50/51G2.t_Op 0 ~100 0.1 s 0.001 stage 2 of earth fault
overcurrent protection
The dropout time setting of
29 50/51G2.t_DropOut 0 ~100 0 s 0.001 stage 2 of earth fault
overcurrent protection
The setting used to select the
directional mode of stage 2 of
Non_Direction
earth fault overcurrent
al; Non_Directio
30 50/51G2.Opt_Dir - - protection.
Forward; nal
1: no direction;
Reverse
2: forward direction;
3: reverse direction.
Default Uni
No. Settings Range Step Description
value t
The logic setting for
enabling/disabling the
harmonic control element of
the stage 2 of earth fault
overcurrent protection
Disabled: stage 2 of earth fault
Disabled;
31 50/51G2.En_Hm_Blk Disabled - - overcurrent protection is not
Enabled
controlled by the harmonic
3 control element
Enabled: stage 2 of earth fault
overcurrent protection is
controlled by the harmonic
control element
The logic setting for
Disabled; enabling/disabling the stage 2
32 50/51G2.En Enabled - -
Enabled of earth fault overcurrent
protection
Enabling stage 2 earth fault
overcurrent protection operate
Trp;
33 50/51G2.Opt_Trp/Alm Trp - - to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
The setting for selecting the
ANSILTV;
inverse-time operation
ANSILT;
34 50/51G2.Opt_Curve IECDefTime - - characteristic curve of stage 2
IECN;
of earth fault overcurrent
IECV;
protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
Default Uni
No. Settings Range Step Description
value t
The setting for selecting the
inverse-time dropout
characteristic curve of stage 2
Inst;
50/51G2.Opt_Curve_ of earth fault overcurrent
35 DefTime; Inst - -
DropOut protection
IDMT
Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
Default Uni
No. Settings Range Step Description
value t
The operating time setting of
43 50/51G3.t_Op 0 ~100 0.1 s 0.001 stage 3 of earth fault
overcurrent protection
The dropout time setting of
44 50/51G3.t_DropOut 0 ~100 0 s 0.001 stage 3 of earth fault
overcurrent protection
The setting used to select the
directional mode of stage 3 of
Non_Direction
3 45 50/51G3.Opt_Dir
al; Non_Directio
- -
earth
protection.
fault overcurrent
Forward; nal
1: no direction;
Reverse
2: forward direction;
3: reverse direction.
The logic setting for
enabling/disabling the
harmonic control element of
the stage 3 of earth fault
overcurrent protection
Disabled: stage 3 of earth fault
Disabled;
46 50/51G3.En_Hm_Blk Disabled - - overcurrent protection is not
Enabled
controlled by the harmonic
control element
Enabled: stage 3 of earth fault
overcurrent protection is
controlled by the harmonic
control element
The logic setting for
Disabled; enabling/disabling the stage 3
47 50/51G3.En Enabled - -
Enabled of earth fault overcurrent
protection
Enabling stage 3 earth fault
overcurrent protection operate
Trp;
48 50/51G3.Opt_Trp/Alm Trp - - to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose
Default Uni
No. Settings Range Step Description
value t
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
The setting for selecting the
ANSILTV;
inverse-time operation
ANSILT;
49 50/51G3.Opt_Curve IECDefTime - - characteristic curve of stage 3
IECN;
IECV;
of earth fault overcurrent 3
protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
characteristic curve of stage 3
Inst;
50/51G3.Opt_Curve_ of earth fault overcurrent
50 DefTime; Inst - -
DropOut protection
IDMT
Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
51 50/51G3.TMS 0.04~ 20 1 - 0.001 stage 3 of earth fault
overcurrent protection
The minimum operating time
52 50/51G3.tmin 0 ~10 0.02 s 0.001 setting of stage 3 of earth fault
overcurrent protection
The constant “k” of the
customized inverse-time
53 50/51G3.K 0.001~120 0.14 - 0.0001 operation characteristic of
stage 3 of earth fault
overcurrent protection
The constant “α” of the
customized inverse-time
54 50/51G3.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of
stage 3 of earth fault
overcurrent protection
Default Uni
No. Settings Range Step Description
value t
The constant “C” of the
customized inverse-time
55 50/51G3.C 0 ~1 0 - 0.0001 operation characteristic of
stage 3 of earth fault
overcurrent protection
The setting used to select the
residual current that used for
stage 4 of earth fault
3 56 50/51G4.Opt_3I0
Ext;
Cal
Ext - -
overcurrent protection
Ext: the measured residual
current
Cal: the calculated residual
current
The current setting of stage 4
57 50/51G4.3I0_Set 0.05~200 15 A 0.001 of earth fault overcurrent
protection
The operating time setting of
58 50/51G4.t_Op 0 ~100 0.1 s 0.001 stage 4 of earth fault
overcurrent protection
The dropout time setting of
59 50/51G4.t_DropOut 0 ~100 0 s 0.001 stage 4 of earth fault
overcurrent protection
The setting used to select the
directional mode of stage 4 of
Non_Direction
earth fault overcurrent
al; Non_Directio
60 50/51G4.Opt_Dir - - protection.
Forward; nal
1: no direction;
Reverse
2: forward direction;
3: reverse direction.
The logic setting for
enabling/disabling the
harmonic control element of
the stage 4 of earth fault
overcurrent protection
Disabled: stage 4 of earth fault
Disabled;
61 50/51G4.En_Hm_Blk Disabled - - overcurrent protection is not
Enabled
controlled by the harmonic
control element
Enabled: stage 4 of earth fault
overcurrent protection is
controlled by the harmonic
control element
Default Uni
No. Settings Range Step Description
value t
The logic setting for
Disabled; enabling/disabling the stage 4
62 50/51G4.En Enabled - -
Enabled of earth fault overcurrent
protection
Enabling stage 4 earth fault
overcurrent protection operate
Trp;
63 50/51G4.Opt_Trp/Alm Trp - - to trip or alarm.
Alm
Trp: for tripping purpose
ANSIE;
Alm: for alarm purpose
3
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
The setting for selecting the
ANSILTV;
inverse-time operation
ANSILT;
64 50/51G4.Opt_Curve IECDefTime - - characteristic curve of stage 4
IECN;
of earth fault overcurrent
IECV;
protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
characteristic curve of stage 4
Inst;
50/51G4.Opt_Curve_ of earth fault overcurrent
65 DefTime; Inst - -
DropOut protection
IDMT
Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
66 50/51G4.TMS 0.04~ 20 1 - 0.001 stage 4 of earth fault
overcurrent protection
The minimum operating time
67 50/51G4.tmin 0 ~10 0.02 s 0.001 setting of stage 4 of earth fault
overcurrent protection
Default Uni
No. Settings Range Step Description
value t
The constant “k” of the
customized inverse-time
68 50/51G4.K 0.001~120 0.14 - 0.0001 operation characteristic of
stage 4 of earth fault
overcurrent protection
The constant “α” of the
customized inverse-time
69 50/51G4.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of
3 stage 4 of
overcurrent protection
earth fault
Default Uni
No. Settings Range Step Description
value t
The logic setting for
enabling/disabling the
harmonic control element of
the stage 5 of earth fault
overcurrent protection
Disabled: stage 5 of earth fault
Disabled;
76 50/51G5.En_Hm_Blk Disabled - - overcurrent protection is not
Enabled
controlled by the harmonic
control element
Enabled: stage 5 of earth fault
3
overcurrent protection is
controlled by the harmonic
control element
The logic setting for
Disabled; enabling/disabling the stage 5
77 50/51G5.En Enabled - -
Enabled of earth fault overcurrent
protection
Enabling stage 5 earth fault
overcurrent protection operate
Trp;
78 50/51G5.Opt_Trp/Alm Trp - - to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
The setting for selecting the
ANSILTV;
inverse-time operation
ANSILT;
79 50/51G5.Opt_Curve IECDefTime - - characteristic curve of stage 5
IECN;
of earth fault overcurrent
IECV;
protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
Default Uni
No. Settings Range Step Description
value t
The setting for selecting the
inverse-time dropout
characteristic curve of stage 5
Inst;
50/51G5.Opt_Curve_ of earth fault overcurrent
80 DefTime; Inst - -
DropOut protection
IDMT
Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
Default Uni
No. Settings Range Step Description
value t
The operating time setting of
88 50/51G6.t_Op 0 ~100 0.1 s 0.001 stage 6 of earth fault
overcurrent protection
The dropout time setting of
89 50/51G6.t_DropOut 0 ~100 0 s 0.001 stage 6 of earth fault
overcurrent protection
The setting used to select the
directional mode of stage 6 of
Non_Direction
90 50/51G6.Opt_Dir
al; Non_Directio
- -
earth
protection.
fault overcurrent
3
Forward; nal
1: no direction;
Reverse
2: forward direction;
3: reverse direction.
The logic setting for
enabling/disabling the
harmonic control element of
the stage 6 of earth fault
overcurrent protection
Disabled: stage 6 of earth fault
Disabled;
91 50/51G6.En_Hm_Blk Disabled - - overcurrent protection is not
Enabled
controlled by the harmonic
control element
Enabled: stage 6 of earth fault
overcurrent protection is
controlled by the harmonic
control element
The logic setting for
Disabled; enabling/disabling the stage 6
92 50/51G6.En Enabled - -
Enabled of earth fault overcurrent
protection
Enabling stage 6 earth fault
overcurrent protection operate
Trp;
93 50/51G6.Opt_Trp/Alm Trp - - to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose
Default Uni
No. Settings Range Step Description
value t
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
The setting for selecting the
ANSILTV;
inverse-time operation
ANSILT;
94 50/51G6.Opt_Curve IECDefTime - - characteristic curve of stage 6
3 IECN;
IECV;
of earth fault overcurrent
protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
characteristic curve of stage 6
Inst;
50/51G6.Opt_Curve_ of earth fault overcurrent
95 DefTime; Inst - -
DropOut protection
IDMT
Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
96 50/51G6.TMS 0.04~ 20 1 - 0.001 stage 6 of earth fault
overcurrent protection
The minimum operating time
97 50/51G6.tmin 0 ~10 0.02 s 0.001 setting of stage 6 of earth fault
overcurrent protection
The constant “k” of the
customized inverse-time
98 50/51G6.K 0.001~120 0.14 - 0.0001 operation characteristic of
stage 6 of earth fault
overcurrent protection
The constant “α” of the
customized inverse-time
99 50/51G6.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of
stage 6 of earth fault
overcurrent protection
Default Uni
No. Settings Range Step Description
value t
The constant “C” of the
customized inverse-time
100 50/51G6.C 0 ~1 0 - 0.0001 operation characteristic of
stage 6 of earth fault
overcurrent protection
Another group of earth fault overcurrent protection can be enabled or disabled via the settings or
binary input signals, for some specific applications, the protection needs to be blocked by the
external signal, so the device provides a function block input signal to be used to block another
group of earth fault overcurrent protection. The enabling and blocking logic of another group of
earth fault overcurrent protection is shown in the figure below:
EN A.50/51Gx.En &
A.50/51Gx.On
SIG A.50/51Gx.Enable
&
SIG A.50/51Gx.Block ≥1 A.50/51Gx.Blocked
SIG Fail_Device
&
A.50/51Gx.Valid
Figure 3.7-1 The enabling and blocking logic of another group of earth fault overcurrent protection
The logic diagram of the fault detector element of another group of earth fault overcurrent
protection is as follows:
EN [A.50/51Gx.Opt_Trp/Alm]=Alm
Figure 3.7-2 Logic diagram of the fault detector element of another group of earth fault overcurrent
protection
Only when the setting [A.50/51Gx.Opt_Curve] is set as “UserDefine”, i.e. the user-defined
inverse-time characteristic is selected, the settings [A.50/51Gx.K], [A.50/51Gx.C] and
[A.50/51Gx.Alpha] are useful, the inverse-time operating curve is determined by the three
settings.
Definite-time characteristic
When I 0 > I 0 p , the protection operates with a time delay of top (i.e. the value of the setting
[A.50/51Gx.t_Op]), and the operation characteristic curve is shown in the following figure:
3
t op
I0p I0
Figure 3.7-3 Definite-time operation characteristic curve of another group of earth fault overcurrent
protection
Inverse-time characteristic
When I 0 > I 0 p , the inverse-time accumulator begins to accumulate, and the operating time is
affected by the applied current I 0 . The operating time will decrease with the current increasing,
but the operating time shall not less than tmin , i.e. the setting [A.50/51Gx.tmin]. The inverse-time
operation characteristic equation is:
k
t
c TMS
(I 0 / I 0P ) 1
Where:
3 t min
I0P ID I0
Figure 3.7-4 Inverse-time operation characteristic curve of another group of earth fault overcurrent
protection
When the applied zero-sequence current I 0 is not a fixed value, but changes with time, the
operating behavior of the protection is shown in the following equation:
T0
1
t ( I )dt
0 0
1
Where:
The supported dropout characteristics of another group of earth fault overcurrent protection
include instantaneous dropout, definite-time dropout and ANSI inverse-time dropout.
When the operating curve is selected as ANSI inverse-time characteristic, the dropout
characteristic can be selected as instantaneous dropout, definite-time dropout and ANSI
inverse-time dropout.
Instantaneous dropout
Definite-time dropout
When I 0 <0.95* I 0 p , the protection drops out with a time delay of tdr (i.e. the value of the
setting [A.50/51Gx.t_DropOut]), and the dropout characteristic curve is shown in the following
figure:
Start time
I0>I0p
Start
signal
3
Operating
signal
Protection
Operating threshold operate
Operating
counter
t dr t dr t dr
Dropout time setting
Dropout time
Dropout time
Figure 3.7-5 Definite-time dropout characteristic of another group of earth fault overcurrent protection
Inverse-time dropout
When I 0 > I 0 p , the inverse-time operating accumulator begins to accumulate, the accumulated
value after tp (Assuming tp is less than the theoretical operating time) is calculated according
to the following equation:
tp
1
Itp t(I
0
0
dt
)
At this time, if I 0 <0.95* I 0 p , the protection element starts dropout, and the dropout characteristic
meets the following equation:
TR
1
I tp dt 0
0
t R ( I )
Where:
tr
tR 2
TMS
1 ( I / I P )
Where:
tr is the dropout time coefficient, it is the dropout time required for the current to drop to 0 after
the protection operates.
The inverse time dropout characteristic curve is shown in the figure below.
tr
I0 P I0
Figure 3.7-6 Inverse-time dropout characteristic curve of another group of earth fault overcurrent
protection
The correspondence between the start signal, operating signal, and operating accumulator in the
inverse-time dropout characteristic is shown in the figure below:
Start time
I0>I0p
Start
signal
Operating
signal
Operating threshold
Protection
operate
3
Operating
counter
Figure 3.7-7 Inverse-time dropout characteristic of another group of earth fault overcurrent protection
A.50/51G
A.50/51Gx.On
A.50/51Gx.Enable A.50/51Gx.Blocked
A.50/51Gx.Block A.50/51Gx.Valid
A.50/51Gx.St
A.50/51Gx.Op
A.50/51Gx.Alm
3.7.4 Logic
A.50/51Gx.St
Timer &
SET 3I0>[A.50/51Gx.3I0_Set] & A.50/51Gx.Op
t
3 SIG A.50/51Gx.Pkp
t
Figure 3.7-8 Logic diagram of another group of earth fault overcurrent protection
3.7.5 Settings
Access path:
Default
No. Settings Range Unit Step Description
value
The current setting of
stage 1 of another group of
1 A.50/51G1.3I0_Set 0.05~200 15 A 0.001
earth fault overcurrent
protection
The operating time setting
of stage 1 of another group
2 A.50/51G1.t_Op 0 ~100 0.1 s 0.001
of earth fault overcurrent
protection
The dropout time setting of
stage 1 of another group of
3 A.50/51G1.t_DropOut 0 ~100 0 s 0.001
earth fault overcurrent
protection
The logic setting for
enabling/disabling the
Disabled;
4 A.50/51G1.En Enabled - - stage 1 of another group of
Enabled
earth fault overcurrent
protection
Default
No. Settings Range Unit Step Description
value
Enabling stage 1 of
another group of earth fault
Trp; overcurrent protection
5 A.50/51G1.Opt_Trp/Alm Trp - -
Alm operate to trip or alarm.
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
3
ANSIDefTime;
ANSILTE; The setting for selecting
ANSILTV; the inverse-time operation
ANSILT; characteristic curve of
6 A.50/51G1.Opt_Curve IECDefTime - -
IECN; stage 1 of another group of
IECV; earth fault overcurrent
IEC; protection.
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting
the inverse-time dropout
characteristic curve of
stage 1 of another group of
Inst; earth fault overcurrent
A.50/51G1.Opt_Curve_D
7 DefTime; Inst - - protection
ropOut
IDMT Inst: instantaneous
dropout
DefTime: definite-time
dropout
IDMT: inverse-time dropout
The time multiplier setting
of stage 1 of another group
8 A.50/51G1.TMS 0.04~ 20 1 - 0.001
of earth fault overcurrent
protection
The minimum operating
time setting of stage 1 of
9 A.50/51G1.tmin 0 ~10 0.02 s 0.001
another group of earth fault
overcurrent protection
Default
No. Settings Range Unit Step Description
value
The constant “k” of the
customized inverse-time
operation characteristic of
10 A.50/51G1.K 0.001~120 0.14 - 0.0001
stage 1 of another group of
earth fault overcurrent
protection
The constant “α” of the
customized inverse-time
Default
No. Settings Range Unit Step Description
value
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE; The setting for selecting
ANSILTV; the inverse-time operation
ANSILT; characteristic curve of
18 A.50/51G2.Opt_Curve IECDefTime - -
IECN;
IECV;
stage 2 of another group of
earth fault overcurrent
3
IEC; protection.
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting
the inverse-time dropout
characteristic curve of
stage 2 of another group of
Inst; earth fault overcurrent
A.50/51G2.Opt_Curve_D
19 DefTime; Inst - - protection
ropOut
IDMT Inst: instantaneous
dropout
DefTime: definite-time
dropout
IDMT: inverse-time dropout
The time multiplier setting
of stage 2 of another group
20 A.50/51G2.TMS 0.04~ 20 1 - 0.001
of earth fault overcurrent
protection
The minimum operating
time setting of stage 2 of
21 A.50/51G2.tmin 0 ~10 0.02 s 0.001
another group of earth fault
overcurrent protection
The constant “k” of the
customized inverse-time
operation characteristic of
22 A.50/51G2.K 0.001~120 0.14 - 0.0001
stage 2 of another group of
earth fault overcurrent
protection
Default
No. Settings Range Unit Step Description
value
The constant “α” of the
customized inverse-time
operation characteristic of
23 A.50/51G2.Alpha 0.01 ~3 0.02 - 0.0001
stage 2 of another group of
earth fault overcurrent
protection
The constant “C” of the
customized inverse-time
3 24 A.50/51G2.C 0 ~1 0 - 0.0001
operation characteristic of
stage 2 of another group of
earth fault overcurrent
protection
The current setting of
stage 3 of another group of
25 A.50/51G3.3I0_Set 0.05~200 15 A 0.001
earth fault overcurrent
protection
The operating time setting
of stage 3 of another group
26 A.50/51G3.t_Op 0 ~100 0.1 s 0.001
of earth fault overcurrent
protection
The dropout time setting of
stage 3 of another group of
27 A.50/51G3.t_DropOut 0 ~100 0 s 0.001
earth fault overcurrent
protection
The logic setting for
enabling/disabling the
Disabled;
28 A.50/51G3.En Enabled - - stage 3 of another group of
Enabled
earth fault overcurrent
protection
Enabling stage 3 of
another group of earth fault
Trp; overcurrent protection
29 A.50/51G3.Opt_Trp/Alm Trp - -
Alm operate to trip or alarm.
Trp: for tripping purpose
Alm: for alarm purpose
Default
No. Settings Range Unit Step Description
value
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE; The setting for selecting
ANSILTV; the inverse-time operation
ANSILT; characteristic curve of
30 A.50/51G3.Opt_Curve IECDefTime - -
IECN;
IECV;
stage 3 of another group of
earth fault overcurrent
3
IEC; protection.
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting
the inverse-time dropout
characteristic curve of
stage 3 of another group of
Inst; earth fault overcurrent
A.50/51G3.Opt_Curve_D
31 DefTime; Inst - - protection
ropOut
IDMT Inst: instantaneous
dropout
DefTime: definite-time
dropout
IDMT: inverse-time dropout
The time multiplier setting
of stage 3 of another group
32 A.50/51G3.TMS 0.04~ 20 1 - 0.001
of earth fault overcurrent
protection
The minimum operating
time setting of stage 3 of
33 A.50/51G3.tmin 0 ~10 0.02 s 0.001
another group of earth fault
overcurrent protection
The constant “k” of the
customized inverse-time
operation characteristic of
34 A.50/51G3.K 0.001~120 0.14 - 0.0001
stage 3 of another group of
earth fault overcurrent
protection
Default
No. Settings Range Unit Step Description
value
The constant “α” of the
customized inverse-time
operation characteristic of
35 A.50/51G3.Alpha 0.01 ~3 0.02 - 0.0001
stage 3 of another group of
earth fault overcurrent
protection
The constant “C” of the
customized inverse-time
3 36 A.50/51G3.C 0 ~1 0 - 0.0001
operation characteristic of
stage 3 of another group of
earth fault overcurrent
protection
The current setting of
stage 4 of another group of
37 A.50/51G4.3I0_Set 0.05~200 15 A 0.001
earth fault overcurrent
protection
The operating time setting
of stage 4 of another group
38 A.50/51G4.t_Op 0 ~100 0.1 s 0.001
of earth fault overcurrent
protection
The dropout time setting of
stage 4 of another group of
39 A.50/51G4.t_DropOut 0 ~100 0 s 0.001
earth fault overcurrent
protection
The logic setting for
enabling/disabling the
Disabled;
40 A.50/51G4.En Enabled - - stage 4 of another group of
Enabled
earth fault overcurrent
protection
Enabling stage 4 of
another group of earth fault
Trp; overcurrent protection
41 A.50/51G4.Opt_Trp/Alm Trp - -
Alm operate to trip or alarm.
Trp: for tripping purpose
Alm: for alarm purpose
Default
No. Settings Range Unit Step Description
value
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE; The setting for selecting
ANSILTV; the inverse-time operation
ANSILT; characteristic curve of
42 A.50/51G4.Opt_Curve IECDefTime - -
IECN;
IECV;
stage 4 of another group of
earth fault overcurrent
3
IEC; protection.
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting
the inverse-time dropout
characteristic curve of
stage 4 of another group of
Inst; earth fault overcurrent
A.50/51G4.Opt_Curve_D
43 DefTime; Inst - - protection
ropOut
IDMT Inst: instantaneous
dropout
DefTime: definite-time
dropout
IDMT: inverse-time dropout
The time multiplier setting
of stage 4 of another group
44 A.50/51G4.TMS 0.04~ 20 1 - 0.001
of earth fault overcurrent
protection
The minimum operating
time setting of stage 4 of
45 A.50/51G4.tmin 0 ~10 0.02 s 0.001
another group of earth fault
overcurrent protection
The constant “k” of the
customized inverse-time
operation characteristic of
46 A.50/51G4.K 0.001~120 0.14 - 0.0001
stage 4 of another group of
earth fault overcurrent
protection
Default
No. Settings Range Unit Step Description
value
The constant “α” of the
customized inverse-time
operation characteristic of
47 A.50/51G4.Alpha 0.01 ~3 0.02 - 0.0001
stage 4 of another group of
earth fault overcurrent
protection
The constant “C” of the
customized inverse-time
3 48 A.50/51G4.C 0 ~1 0 - 0.0001
operation characteristic of
stage 4 of another group of
earth fault overcurrent
protection
The current setting of
stage 5 of another group of
49 A.50/51G5.3I0_Set 0.05~200 15 A 0.001
earth fault overcurrent
protection
The operating time setting
of stage 5 of another group
50 A.50/51G5.t_Op 0 ~100 0.1 s 0.001
of earth fault overcurrent
protection
The dropout time setting of
stage 5 of another group of
51 A.50/51G5.t_DropOut 0 ~100 0 s 0.001
earth fault overcurrent
protection
The logic setting for
enabling/disabling the
Disabled;
52 A.50/51G5.En Enabled - - stage 5 of another group of
Enabled
earth fault overcurrent
protection
Enabling stage 5 of
another group of earth fault
Trp; overcurrent protection
53 A.50/51G5.Opt_Trp/Alm Trp - -
Alm operate to trip or alarm.
Trp: for tripping purpose
Alm: for alarm purpose
Default
No. Settings Range Unit Step Description
value
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE; The setting for selecting
ANSILTV; the inverse-time operation
ANSILT; characteristic curve of
54 A.50/51G5.Opt_Curve IECDefTime - -
IECN;
IECV;
stage 5 of another group of
earth fault overcurrent
3
IEC; protection.
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting
the inverse-time dropout
characteristic curve of
stage 5 of another group of
Inst; earth fault overcurrent
A.50/51G5.Opt_Curve_D
55 DefTime; Inst - - protection
ropOut
IDMT Inst: instantaneous
dropout
DefTime: definite-time
dropout
IDMT: inverse-time dropout
The time multiplier setting
of stage 5 of another group
56 A.50/51G5.TMS 0.04~ 20 1 - 0.001
of earth fault overcurrent
protection
The minimum operating
time setting of stage 5 of
57 A.50/51G5.tmin 0 ~10 0.02 s 0.001
another group of earth fault
overcurrent protection
The constant “k” of the
customized inverse-time
operation characteristic of
58 A.50/51G5.K 0.001~120 0.14 - 0.0001
stage 5 of another group of
earth fault overcurrent
protection
Default
No. Settings Range Unit Step Description
value
The constant “α” of the
customized inverse-time
operation characteristic of
59 A.50/51G5.Alpha 0.01 ~3 0.02 - 0.0001
stage 5 of another group of
earth fault overcurrent
protection
The constant “C” of the
customized inverse-time
3 60 A.50/51G5.C 0 ~1 0 - 0.0001
operation characteristic of
stage 5 of another group of
earth fault overcurrent
protection
The current setting of
stage 6 of another group of
61 A.50/51G6.3I0_Set 0.05~200 15 A 0.001
earth fault overcurrent
protection
The operating time setting
of stage 6 of another group
62 A.50/51G6.t_Op 0 ~100 0.1 s 0.001
of earth fault overcurrent
protection
The dropout time setting of
stage 6 of another group of
63 A.50/51G6.t_DropOut 0 ~100 0 s 0.001
earth fault overcurrent
protection
The logic setting for
enabling/disabling the
Disabled;
64 A.50/51G6.En Enabled - - stage 6 of another group of
Enabled
earth fault overcurrent
protection
Enabling stage 6 of
another group of earth fault
Trp; overcurrent protection
65 A.50/51G6.Opt_Trp/Alm Trp - -
Alm operate to trip or alarm.
Trp: for tripping purpose
Alm: for alarm purpose
Default
No. Settings Range Unit Step Description
value
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE; The setting for selecting
ANSILTV; the inverse-time operation
ANSILT; characteristic curve of
66 A.50/51G6.Opt_Curve IECDefTime - -
IECN;
IECV;
stage 6 of another group of
earth fault overcurrent
3
IEC; protection.
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting
the inverse-time dropout
characteristic curve of
stage 6 of another group of
Inst; earth fault overcurrent
A.50/51G6.Opt_Curve_D
67 DefTime; Inst - - protection
ropOut
IDMT Inst: instantaneous
dropout
DefTime: definite-time
dropout
IDMT: inverse-time dropout
The time multiplier setting
of stage 6 of another group
68 A.50/51G6.TMS 0.04~ 20 1 - 0.001
of earth fault overcurrent
protection
The minimum operating
time setting of stage 6 of
69 A.50/51G6.tmin 0 ~10 0.02 s 0.001
another group of earth fault
overcurrent protection
The constant “k” of the
customized inverse-time
operation characteristic of
70 A.50/51G6.K 0.001~120 0.14 - 0.0001
stage 6 of another group of
earth fault overcurrent
protection
Default
No. Settings Range Unit Step Description
value
The constant “α” of the
customized inverse-time
operation characteristic of
71 A.50/51G6.Alpha 0.01 ~3 0.02 - 0.0001
stage 6 of another group of
earth fault overcurrent
protection
The constant “C” of the
customized inverse-time
3 72 A.50/51G6.C 0 ~1 0 - 0.0001
operation characteristic of
stage 6 of another group of
earth fault overcurrent
protection
Negative-sequence overcurrent protection can be enabled or disabled via the settings or binary
input signals, for some specific applications, the protection needs to be blocked by the external
signal, so the device provides a function block input signal to be used to block negative-sequence
overcurrent protection. The enabling and blocking logic of negative-sequence overcurrent
protection is shown in the figure below:
EN [50/51Qx.En] &
50/51Qx.On
SIG 50/51Qx.Enable
&
SIG 50/51Qx.Block ≥1 50/51Qx.Blocked
SIG Fail_Device
&
50/51Qx.Valid
Figure 3.8-1 The enabling and blocking logic of negative-sequence overcurrent protection
3
The logic diagram of the fault detector element of negative-sequence overcurrent protection is as
follows:
SET [50/51Qx.Opt_Trp/Alm]=Alm
Figure 3.8-2 Logic diagram of the fault detector element of negative-sequence overcurrent protection
The operation boundary of the forward direction element can be set by [50/51Q.DIR.phi_Min_Fwd]
and [50/51Q.DIR.phi_Max_Fwd]. The operation boundary of the reverse direction element can be
set by [50/51Q.DIR.phi_Min_Rev] and [50/51Q.DIR.phi_Max_Rev].
-U2
[50/51Q.DIR.phi_Min_Fwd]
Non-operating I2
area
[50/51Q.DIR.phi_Max_Rev]
Operating area in
forward direction
[50/51Q.DIR.RCA]
3 Operating area in
reverse direction
[50/51Q.DIR.phi_Max_Fwd]
Non-operating
area
[50/51Q.DIR.phi_Min_Rev]
Figure 3.8-3 The direction element operation characteristics of negative-sequence overcurrent protection
Where:
The sensitivity angle of the direction control element (RCA) can be set by the setting
[50/51Q.DIR.RCA].
The following table shows the relationship between the operating current, the polarized voltage
and the polarization mode.
Polarized
Polarization mode Operating current Angle difference
voltage
Negative-sequence
Negative-sequence current I2 -U2 Angle=Angle(-U2)-Angle(I2)-RCA
voltage polarized
The logic diagram of the forward direction element and reverse direction element is as follows.
EN [50/51Q.En_VTS_Blk] &
>=1
SIG VTS.Alm
& >=1
SIG I2 50/51Q.FwdDir.Op
direction
Forward
criterion
SIG U2
EN [En_VT] & 3
SIG Prot.BI_En_VT
EN [50/51Q.En_VTS_Blk] &
>=1
SIG VTS.Alm
& >=1
SIG I2 50/51Q.RevDir.Op
direction
Reverse
criterion
SIG U2
EN [En_VT] &
SIG Prot.BI_En_VT
Figure 3.8-4 Logic diagram of forward and reverse direction element of negative-sequence overcurrent
protection
Only when the setting [50/51Qx.Opt_Curve] is set as “UserDefine”, i.e. the user-defined
inverse-time characteristic is selected, the settings [50/51Qx.K], [50/51Qx.C] and [50/51Qx.Alpha]
are useful, the inverse-time operating curve is determined by the three settings.
Definite-time characteristic
When I 2 > I 2 p , the protection operates with a time delay of top (i.e. the value of the setting
[50/51Qx.t_Op]), and the operation characteristic curve is shown in the following figure:
t op
I2p I2
Inverse-time characteristic
When I 2 > I 2 p , the inverse-time accumulator begins to accumulate, and the operating time is
affected by the applied current I 2 . The operating time will decrease with the current increasing,
but the operating time shall not less than tmin , i.e. the setting [50/51Qx.tmin]. The inverse-time
operation characteristic equation is:
Where:
t min
I2P ID I2
When the applied negative-sequence overcurrent current I 2 is not a fixed value, but changes
with time, the operating behavior of the protection is shown in the following equation:
Where:
When the operating curve is selected as ANSI inverse-time characteristic, the dropout
characteristic can be selected as instantaneous dropout, definite-time dropout and ANSI
inverse-time dropout.
Instantaneous dropout
Definite-time dropout
When I 2 <0.95* I 2 p , the protection drops out with a time delay of tdr (i.e. the value of the
setting [50/51Qx.t_DropOut]), and the dropout characteristic curve is shown in the following
figure:
Start time
I2>I2p
Start
signal
Operating
signal
3
Protection
Operating threshold operate
Operating
counter
t dr t dr t dr
Dropout time setting
Dropout time
Dropout time
Inverse-time dropout
When I 2 > I 2 p , the inverse-time operating accumulator begins to accumulate, the accumulated
value after tp (Assuming tp is less than the theoretical operating time) is calculated according
to the following equation:
tp
1
I tp dt
0
t ( I 2 )
At this time, if I 2 <0.95* I 2 p , the protection element starts dropout, and the dropout characteristic
meets the following equation:
TR
1
I tp dt 0
0
tR ( I 2 )
Where:
Where:
tr is the dropout time coefficient, it is the dropout time required for the current to drop to 0 after
the protection operates.
When 0.95* I 2 p < I 2 < I 2 p , the accumulator will neither accumulate nor drop out
The inverse time dropout characteristic curve is shown in the figure below.
tr
The correspondence between the start signal, operating signal, and operating accumulator in the
inverse-time dropout characteristic is shown in the figure below:
Start time
I2>I2p
Start
signal
Operating
signal
Operating threshold
Protection
operate
3
Operating
counter
50/51Q
50/51Qx.On
50/51Qx.Enable
50/51Qx.Blocked
50/51Qx.Block
50/51Qx.Valid
50/51Qx.St
50/51Qx.Op
50/51Qx.Alm
50/51Q.FwdDir.Op
50/51Q.RevDir.Op
3 3.8.4 Logic
SET I2>[50/51Qx.I2_Set]
50/51Qx.St
SIG 50/51Q.FwdDir.Op
&
& Timer
selection
Direction
t
SIG 50/51Q.RevDir.Op
t
SET [50/51Qx.Opt_Dir]
SIG 50/51Qx.Pkp
&
50/51Qx.Op
SET [50/51Qx.Opt_Trp/Alm]=Trp
&
50/51Qx.Alm
SET [50/51Qx.Opt_Trp/Alm]=Alm
3.8.5 Settings
Access path:
Default
No. Settings Range Unit Step Description
value
The relay characteristic angle
of the direction control
1 50/51Q.DIR.RCA -180~179 45 deg 1
element of negative-sequence
overcurrent protection
The minimum boundary of the
50/51Q.DIR.phi_Min_ forward direction element of
2 10~90 90 deg 1
Fwd negative-sequence
overcurrent protection
Default
No. Settings Range Unit Step Description
value
The maximum boundary of the
50/51Q.DIR.phi_Max forward direction element of
3 10~90 90 deg 1
_Fwd negative-sequence
overcurrent protection
The minimum boundary of the
50/51Q.DIR.phi_Min_ reverse direction element of
4 10~90 90 deg 1
Rev negative-sequence
overcurrent protection
50/51Q.DIR.phi_Max
The maximum boundary of the
reverse direction element of
3
5 10~90 90 deg 1
_Rev negative-sequence
overcurrent protection
The minimum operating
current setting for the direction
6 50/51Q.DIR.I_Min (0.05~1)In 0.05 - 0.001 control element of
negative-sequence
overcurrent protection
The minimum operating
voltage setting for the direction
7 50/51Q.DIR.U_Min 1.0~10.0 4 V 0.001 control element of
negative-sequence
overcurrent protection
Logic setting to determine the
behavior of
negative-sequence
overcurrent protection when
VT circuit supervision function
is enabled and VT circuit
failure happens.
Disabled;
8 50/51Q.En_VTS_Blk Disabled - - Disabled: negative-sequence
Enabled
overcurrent protection will not
effected by VT circuit failure
Enabled: voltage controlled
negative-sequence
overcurrent protection will be
blocked by VT circuit failure
signal
The current setting of stage 1
9 50/51Q1.I2_Set 0.05~200 15 A 0.001 of negative-sequence
overcurrent protection
Default
No. Settings Range Unit Step Description
value
The operating time setting of
10 50/51Q1.t_Op 0.03 ~100 0.1 s 0.001 stage 1 of negative-sequence
overcurrent protection
The dropout time setting of
11 50/51Q1.t_DropOut 0 ~100 0 s 0.001 stage 1 of negative-sequence
overcurrent protection
The setting used to select the
directional mode of stage 1 of
Non_Direction
3 12 50/51Q1.Opt_Dir
al Non_Directio
- -
negative-sequence
overcurrent protection.
Forward nal
1: no direction;
Reverse
2: forward direction;
3: reverse direction.
The logic setting for
Disabled; enabling/disabling the stage 1
13 50/51Q1.En Enabled - -
Enabled of negative-sequence
overcurrent protection
Enabling stage 1 of
negative-sequence
Trp; overcurrent protection operate
14 50/51Q1.Opt_Trp/Alm Trp - -
Alm to trip or alarm.
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
The setting for selecting the
ANSILTV;
inverse-time operation
ANSILT;
15 50/51Q1.Opt_Curve IECDefTime - - characteristic curve of stage 1
IECN;
of negative-sequence
IECV;
overcurrent protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
Default
No. Settings Range Unit Step Description
value
The setting for selecting the
inverse-time dropout
characteristic curve of stage 1
Inst;
50/51Q1.Opt_Curve_ of negative-sequence
16 DefTime; Inst - -
DropOut overcurrent protection
IDMT
Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
Default
No. Settings Range Unit Step Description
value
The setting used to select the
directional mode of stage 2 of
Non_Direction
negative-sequence
al Non_Directio
25 50/51Q2.Opt_Dir - - overcurrent protection.
Forward nal
1: no direction;
Reverse
2: forward direction;
3: reverse direction.
The logic setting for
3 26 50/51Q2.En
Disabled;
Enabled
Enabled - -
enabling/disabling the stage 2
of negative-sequence
overcurrent protection
Enabling stage 2 of
negative-sequence
Trp; overcurrent protection operate
27 50/51Q2.Opt_Trp/Alm Trp - -
Alm to trip or alarm.
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
The setting for selecting the
ANSILTV;
inverse-time operation
ANSILT;
28 50/51Q2.Opt_Curve IECDefTime - - characteristic curve of stage 2
IECN;
of negative-sequence
IECV;
overcurrent protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
characteristic curve of stage 2
Inst;
50/51Q2.Opt_Curve_ of negative-sequence
29 DefTime; Inst - -
DropOut overcurrent protection
IDMT
Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
Default
No. Settings Range Unit Step Description
value
The time multiplier setting of
30 50/51Q2.TMS 0.04~ 20 1 - 0.001 stage 2 of negative-sequence
overcurrent protection
The minimum operating time
setting of stage 2 of
31 50/51Q2.tmin 0 ~10 0.02 s 0.001
negative-sequence
overcurrent protection
The constant “k” of the
The device can provide six stages of sensitive earth fault protection with independent logic. Each
stage can be independently set as definite-time characteristics or inverse-time characteristics.
The dropout characteristics can be set as instantaneous dropout, definite-time dropout or
inverse-time dropout. Users can choose whether it is blocked by the direction control element.
The direction control element can be set as no direction, forward direction and reverse direction.
The zero-sequence current used by sensitive earth fault protection is the measured
zero-sequence current from the high-precision CT. Sensitive earth fault protection can operate to
trip or alarm, it can be enabled or blocked by the external binary input.
Sensitive earth fault protection can be enabled or disabled via the settings or binary input signals,
for some specific applications, the protection needs to be blocked by the external signal, so the
device provides a function block input signal to be used to block sensitive earth fault protection.
The enabling and blocking logic of sensitive earth fault protection is shown in the figure below:
EN 50/51SEFx.En &
50/51SEFx.On
SIG 50/51SEFx.Enable
&
SIG 50/51SEFx.Block ≥1 50/51SEFx.Blocked
SIG Fail_Device
&
50/51SEFx.Valid
3
Figure 3.9-1 The enabling and blocking logic of sensitive earth fault protection
The logic diagram of the fault detector element of sensitive earth fault protection is as follows:
EN [50/51SEFx.Opt_Trp/Alm]=Alm
Figure 3.9-2 Logic diagram of the fault detector element of sensitive earth fault protection
In order to ensure the selectivity of sensitive earth fault protection, direction control element is
introduced. The setting [50/51SEFx.Opt_Dir] (x: 1~6) is used for users to select the directional
mode of each stage of sensitive earth fault protection: no direction, forward direction and reverse
direction are selectable.
-U0
[50/51SEF.DIR.phi_Min_Fwd]
Non-operating Isef
area
Operating area in
[50/51SEF.DIR.phi_Max_Rev] forward direction
[50/51SEF.DIR.RCA] 3
Operating area in
reverse direction
[50/51SEF.DIR.phi_Max_Fwd]
Non-operating
area
[50/51SEF.DIR.phi_Min_Rev]
Figure 3.9-3 The direction element operation characteristics of sensitive earth fault protection
Where:
The sensitivity angle of the direction control element (RCA) can be set by the setting
[50/51SEF.DIR.RCA].
-[50/51SEF.DIR.phi_Min_Fwd]<angle<[50/51SEF.DIR.phi_Max_Fwd]
180-[50/51SEF.DIR.phi_Min_Rev]<angle<180+[50/51SEF.DIR.phi_Max_Rev]
The following table shows the relationship between the operating current, the polarized voltage
and the polarization mode.
Polarized
Polarization mode Operating current Angle difference
voltage
Zero-sequence The sensitive earth fault current
-3U0 Angle=Angle(-3U0)-Angle(Isef)-RCA
voltage polarized Isef
The logic diagram of the forward direction element and reverse direction element is as follows.
EN [50/51SEF.En_VTS_Blk] &
>=1
SIG VTS.Alm
SIG Isef
& >=1
Forward direction
50/51SEF.Fwd Dir.Op
3
criterion
SIG 3U0_Cal
EN [En_VT]
EN [50/51SEF.En_VTS_Blk] &
>=1
SIG VTS.Alm
SIG Isef
& >=1
Reverse direction
50/51SEF.RevDir.Op
criterion
SIG 3U0_Cal
EN [En_VT]
Figure 3.9-4 Logic diagram of forward and reverse direction element of sensitive earth fault protection
Sensitive earth fault protection can operate without time delay or operate with a definite-time limit,
it can also operate with an inverse-time limit, the characteristic curve meets the IEC60255-3 and
ANSI C37.112 standards. Sensitive earth fault protection can support definite-time limit, IEC &
ANSI standard inverse time limit and user-defined inverse-time limit, users can select the wanted
operating curve by the setting [50/51SEFx.Opt_Curve] (x=1~6), the relationship between the
value of the setting and the curve is shown in the table below.
Only when the setting [50/51SEFx.Opt_Curve] is set as “UserDefine”, i.e. the user-defined
inverse-time characteristic is selected, the settings [50/51SEFx.K], [50/51SEFx.C] and
[50/51SEFx.Alpha] are useful, the inverse-time operating curve is determined by the three
settings.
Definite-time characteristic
When Isef > Isef _ set , the protection operates with a time delay of top (i.e. the value of the setting
[50/51SEFx.t_Op]), and the operation characteristic curve is shown in the following figure:
t op
I sef_set Isef
Figure 3.9-5 Definite-time operation characteristic curve of sensitive earth fault protection
Inverse-time characteristic
When Isef > Isef _ set , the inverse-time accumulator begins to accumulate, and the operating time
is affected by the applied current Isef . The operating time will decrease with the current
increasing, but the operating time shall not less than tmin , i.e. the setting [50/51SEFx.tmin]. The
inverse-time operation characteristic equation is:
Where:
t min 3
I Sef_set ID Isef
Figure 3.9-6 Inverse-time operation characteristic curve of sensitive earth fault protection
When the applied zero-sequence current Isef is not a fixed value, but changes with time, the
operating behavior of the protection is shown in the following equation:
T0
1
t(I
0 sef )
dt 1
Where:
The supported dropout characteristics of the sensitive earth fault protection include instantaneous
dropout, definite-time dropout and ANSI inverse-time dropout.
When the operating curve is selected as ANSI inverse-time characteristic, the dropout
characteristic can be selected as instantaneous dropout, definite-time dropout and ANSI
inverse-time dropout.
Instantaneous dropout
When Isef <0.95* Isef _ set , the protection drops out immediately.
Definite-time dropout
When Isef <0.95* Isef _ set , the protection drops out with a time delay of tdr (i.e. the value of the
setting [50/51SEFx.t_DropOut]), and the dropout characteristic curve is shown in the following
figure:
Start time
Isef>Isef_set
3 Start
signal
Operating
signal
Protection
Operating threshold operate
Operating
counter
t dr t dr t dr
Dropout time setting
Dropout time
Dropout time
Inverse-time dropout
When Isef > Isef _ set , the inverse-time operating accumulator begins to accumulate, the
accumulated value after tp (Assuming tp is less than the theoretical operating time) is
calculated according to the following equation:
tp
1
I tp dt
0
t ( I sef )
At this time, if Isef <0.95* Isef _ set , the protection element starts dropout, and the dropout
characteristic meets the following equation:
TR
1
I tp dt 0
0
t R ( I sef )
Where:
When Isef <0.95* Isef _ set , the inverse-time dropout characteristic equation is as follows:
Where:
tr is the dropout time coefficient, it is the dropout time required for the current to drop to 0 after
the protection operates.
The inverse time dropout characteristic curve is shown in the figure below.
tr
Isef_set Isef
Figure 3.9-8 Inverse-time dropout characteristic curve of sensitive earth fault protection
The correspondence between the start signal, operating signal, and operating accumulator in the
inverse-time dropout characteristic is shown in the figure below:
Start time
Isef>Isef_set
Start
signal
Operating
signal
3 Operating threshold
Protection
operate
Operating
counter
50/51SEF
50/51SEFx.Enable 50/51SEFx.On
50/51SEFx.Block 50/51SEFx.Blocked
50/51SEFx.Valid
50/51SEFx.St
50/51SEFx.Op
50/51SEFx.Alm
50/51SEF.FwdDir.Op
50/51SEF.RevDir.Op
3.9.4 Logic
3
SET Isef>[50/51SEFX.3I0_Set]
50/51SEFx.St
SIG 50/51SEF.FwdDir.Op
&
& Timer
selection
Direction
t
SIG 50/51SEF.RevDir.Op
t
SET [50/51SEFx.Opt_Dir]
SIG 50/51SEFx.Pkp
&
50/51SEFx.Op
SET [50/51SEFx.Opt_Trp/Alm]=Trp
&
50/51SEFx.Alm
SET [50/51SEFx.Opt_Trp/Alm]=Alm
3.9.5 Settings
Access path:
Default
No. Settings Range Unit Step Description
value
The relay characteristic angle of
1 50/51SEF.DIR.RCA -180~179 45 deg 1 the direction control element of
sensitive earth fault protection
The minimum boundary of the
50/51SEF.DIR.phi_Mi
2 10~90 90 deg 1 forward direction element of
n_Fwd
sensitive earth fault protection
The maximum boundary of the
50/51SEF.DIR.phi_M
3 10~90 90 deg 1 forward direction element of
ax_Fwd
sensitive earth fault protection
Default
No. Settings Range Unit Step Description
value
The minimum boundary of the
50/51SEF.DIR.phi_Mi
4 10~90 90 deg 1 reverse direction element of
n_Rev
sensitive earth fault protection
The maximum boundary of the
50/51SEF.DIR.phi_M
5 10~90 90 deg 1 reverse direction element of
ax_Rev
sensitive earth fault protection
The minimum operating current
setting for the direction control
6 50/51SEF.DIR.I_Min (0.05~1)In 0.05 - 0.001
3 element of sensitive earth fault
protection
The minimum operating voltage
setting for the direction control
7 50/51SEF.DIR.U_Min 1.0~10.0 4 V 0.001
element of sensitive earth fault
protection
Logic setting to determine the
behavior of sensitive earth fault
protection when VT circuit
supervision function is enabled
and VT circuit failure happens.
50/51SEF.En_VTS_Bl Disabled; Disabled: sensitive earth fault
8 Disabled - -
k Enabled protection will not effected by VT
circuit failure
Enabled: voltage controlled
sensitive earth fault protection
will be blocked by VT circuit
failure signal
The current setting of stage 1 of
9 50/51SEF1.3I0_Set 0.005~2 1 A 0.001
sensitive earth fault protection
The operating time setting of
10 50/51SEF1.t_Op 0 ~100 0.1 s 0.001 stage 1 of sensitive earth fault
protection
The dropout time setting of
50/51SEF1.t_DropOu
11 0 ~100 0 s 0.001 stage 1 of sensitive earth fault
t
protection
Non_Directional The setting used to select the
Non_Dire
12 50/51SEF1.Opt_Dir Forward - - directional mode of stage 1 of
ctional
Reverse sensitive earth fault protection.
The logic setting for
Disabled;
13 50/51SEF1.En Enabled - - enabling/disabling the stage 1 of
Enabled
sensitive earth fault protection
Default
No. Settings Range Unit Step Description
value
Enabling stage 1 of sensitive
earth fault protection operate to
50/51SEF1.Opt_Trp/ Trp;
14 Trp - - trip or alarm.
Alm Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
3
ANSILTE;
ANSILTV; The setting for selecting the
50/51SEF1.Opt_Curv ANSILT; IECDefTi inverse-time operation
15 - -
e IECN; me characteristic curve of stage 1 of
IECV; sensitive earth fault protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 1 of
50/51SEF1.Opt_Curv
16 DefTime; Inst - - sensitive earth fault protection
e_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
17 50/51SEF1.TMS 0.04~ 20 1 - 0.001 stage 1 of sensitive earth fault
protection
The minimum operating time
18 50/51SEF1.tmin 0 ~10 0.02 s 0.001 setting of stage 1 of sensitive
earth fault protection
The constant “k” of the
customized inverse-time
19 50/51SEF1.K 0.001~120 0.14 - 0.0001 operation characteristic of stage
1 of sensitive earth fault
protection
Default
No. Settings Range Unit Step Description
value
The constant “α” of the
customized inverse-time
20 50/51SEF1.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of stage
1 of sensitive earth fault
protection
The constant “C” of the
customized inverse-time
21 50/51SEF1.C 0 ~1 0 - 0.0001 operation characteristic of stage
3 1 of
protection
sensitive earth fault
Default
No. Settings Range Unit Step Description
value
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
50/51SEF2.Opt_Curv ANSILT; IECDefTi inverse-time operation
28 - -
e IECN;
IECV;
me characteristic curve of stage 2 of
sensitive earth fault protection.
3
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 2 of
50/51SEF2.Opt_Curv
29 DefTime; Inst - - sensitive earth fault protection
e_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
30 50/51SEF2.TMS 0.04~ 20 1 - 0.001 stage 2 of sensitive earth fault
protection
The minimum operating time
31 50/51SEF2.tmin 0 ~10 0.02 s 0.001 setting of stage 2 of sensitive
earth fault protection
The constant “k” of the
customized inverse-time
32 50/51SEF2.K 0.001~120 0.14 - 0.0001 operation characteristic of stage
2 of sensitive earth fault
protection
The constant “α” of the
customized inverse-time
33 50/51SEF2.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of stage
2 of sensitive earth fault
protection
Default
No. Settings Range Unit Step Description
value
The constant “C” of the
customized inverse-time
34 50/51SEF2.C 0 ~1 0 - 0.0001 operation characteristic of stage
2 of sensitive earth fault
protection
The current setting of stage 3 of
35 50/51SEF3.3I0_Set 0.005~2 1 A 0.001
sensitive earth fault protection
The operating time setting of
Default
No. Settings Range Unit Step Description
value
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 3 of
50/51SEF3.Opt_Curv
42 DefTime; Inst - - sensitive earth fault protection
e_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
43 50/51SEF3.TMS 0.04~ 20 1 - 0.001 stage 3 of sensitive earth fault
protection
3
The minimum operating time
44 50/51SEF3.tmin 0 ~10 0.02 s 0.001 setting of stage 3 of sensitive
earth fault protection
The constant “k” of the
customized inverse-time
45 50/51SEF3.K 0.001~120 0.14 - 0.0001 operation characteristic of stage
3 of sensitive earth fault
protection
The constant “α” of the
customized inverse-time
46 50/51SEF3.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of stage
3 of sensitive earth fault
protection
The constant “C” of the
customized inverse-time
47 50/51SEF3.C 0 ~1 0 - 0.0001 operation characteristic of stage
3 of sensitive earth fault
protection
The current setting of stage 4 of
48 50/51SEF4.3I0_Set 0.005~2 1 A 0.001
sensitive earth fault protection
The operating time setting of
49 50/51SEF4.t_Op 0 ~100 0.1 s 0.001 stage 4 of sensitive earth fault
protection
The dropout time setting of
50/51SEF4.t_DropOu
50 0 ~100 0 s 0.001 stage 4 of sensitive earth fault
t
protection
Non_Directional The setting used to select the
Non_Dire
51 50/51SEF4.Opt_Dir Forward - - directional mode of stage 4 of
ctional
Reverse sensitive earth fault protection.
The logic setting for
Disabled;
52 50/51SEF4.En Enabled - - enabling/disabling the stage 4 of
Enabled
sensitive earth fault protection
Default
No. Settings Range Unit Step Description
value
Enabling stage 4 of sensitive
earth fault protection operate to
50/51SEF4.Opt_Trp/ Trp;
53 Trp - - trip or alarm.
Alm Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
3 ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
50/51SEF4.Opt_Curv ANSILT; IECDefTi inverse-time operation
54 - -
e IECN; me characteristic curve of stage 4 of
IECV; sensitive earth fault protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 4 of
50/51SEF4.Opt_Curv
55 DefTime; Inst - - sensitive earth fault protection
e_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
56 50/51SEF4.TMS 0.04~ 20 1 - 0.001 stage 4 of sensitive earth fault
protection
The minimum operating time
57 50/51SEF4.tmin 0 ~10 0.02 s 0.001 setting of stage 4 of sensitive
earth fault protection
The constant “k” of the
customized inverse-time
58 50/51SEF4.K 0.001~120 0.14 - 0.0001 operation characteristic of stage
4 of sensitive earth fault
protection
Default
No. Settings Range Unit Step Description
value
The constant “α” of the
customized inverse-time
59 50/51SEF4.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of stage
4 of sensitive earth fault
protection
The constant “C” of the
customized inverse-time
60 50/51SEF4.C 0 ~1 0 - 0.0001 operation characteristic of stage
4 of
protection
sensitive earth fault
3
The current setting of stage 5 of
61 50/51SEF5.3I0_Set 0.005~2 1 A 0.001
sensitive earth fault protection
The operating time setting of
62 50/51SEF5.t_Op 0 ~100 0.1 s 0.001 stage 5 of sensitive earth fault
protection
The dropout time setting of
50/51SEF5.t_DropOu
63 0 ~100 0 s 0.001 stage 5 of sensitive earth fault
t
protection
Non_Directional The setting used to select the
Non_Dire
64 50/51SEF5.Opt_Dir Forward - - directional mode of stage 5 of
ctional
Reverse sensitive earth fault protection.
The logic setting for
Disabled;
65 50/51SEF5.En Enabled - - enabling/disabling the stage 5 of
Enabled
sensitive earth fault protection
Enabling stage 5 of sensitive
earth fault protection operate to
50/51SEF5.Opt_Trp/ Trp;
66 Trp - - trip or alarm.
Alm Alm
Trp: for tripping purpose
Alm: for alarm purpose
Default
No. Settings Range Unit Step Description
value
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
50/51SEF5.Opt_Curv ANSILT; IECDefTi inverse-time operation
67 - -
3 e IECN;
IECV;
me characteristic curve of stage 5 of
sensitive earth fault protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 5 of
50/51SEF5.Opt_Curv
68 DefTime; Inst - - sensitive earth fault protection
e_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
69 50/51SEF5.TMS 0.04~ 20 1 - 0.001 stage 5 of sensitive earth fault
protection
The minimum operating time
70 50/51SEF5.tmin 0 ~10 0.02 s 0.001 setting of stage 5 of sensitive
earth fault protection
The constant “k” of the
customized inverse-time
71 50/51SEF5.K 0.001~120 0.14 - 0.0001 operation characteristic of stage
5 of sensitive earth fault
protection
The constant “α” of the
customized inverse-time
72 50/51SEF5.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of stage
5 of sensitive earth fault
protection
Default
No. Settings Range Unit Step Description
value
The constant “C” of the
customized inverse-time
73 50/51SEF5.C 0 ~1 0 - 0.0001 operation characteristic of stage
5 of sensitive earth fault
protection
The current setting of stage 6 of
74 50/51SEF6.3I0_Set 0.005~2 1 A 0.001
sensitive earth fault protection
The operating time setting of
75 50/51SEF6.t_Op 0 ~100 0.1 s 0.001 stage 6 of sensitive earth fault
protection
3
The dropout time setting of
50/51SEF6.t_DropOu
76 0 ~100 0 s 0.001 stage 6 of sensitive earth fault
t
protection
Non_Directional The setting used to select the
Non_Dire
77 50/51SEF6.Opt_Dir Forward - - directional mode of stage 6 of
ctional
Reverse sensitive earth fault protection.
The logic setting for
Disabled;
78 50/51SEF6.En Enabled - - enabling/disabling the stage 6 of
Enabled
sensitive earth fault protection
Enabling stage 6 of sensitive
earth fault protection operate to
50/51SEF6.Opt_Trp/ Trp;
79 Trp - - trip or alarm.
Alm Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
50/51SEF6.Opt_Curv ANSILT; IECDefTi inverse-time operation
80 - -
e IECN; me characteristic curve of stage 6 of
IECV; sensitive earth fault protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
Default
No. Settings Range Unit Step Description
value
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 6 of
50/51SEF6.Opt_Curv
81 DefTime; Inst - - sensitive earth fault protection
e_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
the fault current with more harmonic component is generated in the system, the amplitude is
larger than the current threshold of RMS overcurrent protection, the RMS overcurrent protection
will operate.
RMS overcurrent protection can be enabled or disabled via the settings or binary input signals, for
some specific applications, the protection needs to be blocked by the external signal, so the
device provides a function block input signal to be used to block RMS overcurrent protection. The
enabling and blocking logic of RMS overcurrent protection is shown in the figure below:
3
EN 50/51Rx.En &
50/51Rx.On
SIG 50/51Rx.Enable
&
SIG 50/51Rx.Block ≥1 50/51Rx.Blocked
SIG Fail_Device
&
50/51Rx.Valid
Figure 3.10-1 The enabling and blocking logic of RMS overcurrent protection
The logic diagram of the fault detector element of RMS overcurrent protection is as follows:
EN [50/51Rx.Opt_Trp/Alm]=Alm
Figure 3.10-2 Logic diagram of the fault detector element of RMS overcurrent protection
RMS overcurrent protection can operate without time delay or operate with a definite-time limit,
the characteristic curve meets the IEC60255-3 and ANSI C37.112 standards.
When IRMS is larger than the current setting, the protection operates with a time delay of top (i.e.
the value of the setting [50/51Rx.t_Op]), and the operation characteristic curve is shown in the
following figure:
t 0p
3
IRMSp IRMS
The supported dropout characteristics of the phase overvoltage protection include instantaneous
dropout and definite-time dropout.
Instantaneous dropout
Definite-time dropout
When I RMS <0.95* I RMSP , the protection drops out with a time delay of tdr (i.e. the value of the
setting [50/51Rx.t_DropOut]), and the dropout characteristic curve is shown in the following figure:
Start time
IRMS >Iset
Start
signal
Operating
signal
3
Protection
Operating threshold operate
Operating
counter
t dr t dr t dr
Dropout time setting
Dropout time
Dropout time
50/51R
50/51Rx.Enable 50/51Rx.On
50/51Rx.Blocked
50/51Rx.Block
50/51Rx.Valid
50/51Rx.St
50/51Rx.StA
50/51Rx.StB
50/51Rx.StC
50/51Rx.Op
50/51Rx.Op.PhA
50/51Rx.Op.PhB
50/51Rx.Op.PhC
50/51Rx.Alm
3.10.4 Logic
50/51Rx.St
Timer &
SET IRMS>[50/51Rx.I_Set] & 50/51Rx.Op
t
t
SIG 50/51Rx.Pkp
3.10.5 Settings
Access path:
Default
No. Settings Range Unit Step Description
value
The current setting of stage 1 of RMS
1 50/51R1.I_Set 0.05~200 15 A 0.001
overcurrent protection
Default
No. Settings Range Unit Step Description
value
The operating time setting of stage 1 of
2 50/51R1.t_Op 0 ~100 0.1 s 0.001
RMS overcurrent protection
The dropout time setting of stage 1 of
3 50/51R1.t_DropOut 0 ~100 0 s 0.001
RMS overcurrent protection
Disabled; The logic setting for enabling/disabling the
4 50/51R1.En Enabled - -
Enabled stage 1 of RMS overcurrent protection
Enabling stage 1 of RMS overcurrent
Trp; protection operate to trip or alarm.
5 50/51R1.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose 3
Alm: for alarm purpose
The current setting of stage 2 of RMS
6 50/51R2.I_Set 0.05~200 15 A 0.001
overcurrent protection
The operating time setting of stage 2 of
7 50/51R2.t_Op 0 ~100 0.1 s 0.001
RMS overcurrent protection
The dropout time setting of stage 2 of
8 50/51R2.t_DropOut 0 ~100 0 s 0.001
RMS overcurrent protection
Disabled; The logic setting for enabling/disabling the
9 50/51R2.En Enabled - -
Enabled stage 2 of RMS overcurrent protection
Enabling stage 2 of RMS overcurrent
Trp; protection operate to trip or alarm.
10 50/51R2.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose
Alm: for alarm purpose
Users can select phase voltage or phase-to-phase voltage for the protection calculation via the
setting [59P.Opt_Up/Upp]. If it is set as “Up”, phase voltage criterion is selected, and if it is set to
“Upp”, phase-to-phase voltage criterion is selected.
Users can select “1-out-of-3” or “3-out-of-3” logic for the protection criterion via the setting
[59P.Opt_1P/3P]. If it is set as “1P”, phase overvoltage protection can operate if any
phase/phase-to-phase voltage is greater than the voltage setting. If it is set as “3P”, phase
overvoltage protection cannot operate unless three phase/phase-to-phase voltages are greater
than the voltage setting.
Phase overvoltage protection can be enabled or disabled via the settings or binary input signals,
for some specific applications, overvoltage protection needs to be blocked by the external signal,
so the device provides a function block input signal to be used to block overvoltage protection.
The enabling and blocking logic of phase overvoltage protection is shown in the figure below:
3 EN 59Px.En &
59Px.On
SIG 59Px.Enable
&
SIG 59Px.Block ≥1 59Px.Blocked
SIG Fail_Device
&
59Px.Valid
Figure 3.11-1 The enabling and blocking logic of phase overvoltage protection
The logic diagram of the fault detector element of phase overvoltage protection is as follows:
SET [59P.Opt_Up/Upp]=Upp
SET Uab>[U_DropOut]
>=1
SET Ubc>[U_DropOut] &
SET Uca>[U_DropOut]
SET [59P.Opt_1P/3P]=1P
&
SET [59P.Opt_1P/3P]=3P >=1
SET Uab>[U_DropOut]
&
&
SET Ubc>[U_DropOut]
SET Uca>[U_DropOut]
3
SET Ua>[U_DropOut]
>=1
SET Ub>[U_DropOut] &
SET Uc>[U_DropOut]
SET [59P.Opt_1P/3P]=1P
SET Uc>[U_DropOut]
& &
0 500ms &
SET [59P.Opt_Up/Upp]=Up x.59Px.Pkp
SIG 59Px.On
SIG 59Px.Valid
&
FD.Pkp
SET [59Px.Opt_Trp/Alm]=Alm
Figure 3.11-2 Logic diagram of the fault detector element of phase overvoltage protection
Where:
Phase overvoltage protection can operate with a definite-time limit, it can also operate with an
inverse-time limit, the characteristic curve meets the IEC60255-3 and ANSI C37.112 standards.
Phase overvoltage protection can support definite-time limit, IEC & ANSI standard inverse time
limit and user-defined inverse-time limit, users can select the wanted operating curve by the
setting [59Px.Opt_Curve] (x=1, 2), the relationship between the value of the setting and the curve
is shown in the table below.
When the setting [59Px.Opt_Curve] is set as “InvTime_U”, the operation characteristic is the
corresponding selected operating curve type, and the settings [59Px.K], [59Px.C] and
[59Px.Alpha] are useless.
When the setting [59Px.Opt_Curve] is set as “UserDefine”, i.e. the user-defined inverse-time
characteristic is selected, the inverse-time operating curve is determined by the settings [59Px.K],
[59Px.C] and [59Px.Alpha].
Definite-time characteristic
3 When U > Up , the protection operates with a time delay of top (i.e. the value of the setting
[59Px.t_Op]), and the operation characteristic curve is shown in the following figure:
t op
Up U
Inverse-time characteristic
When U > Up , the inverse-time accumulator begins to accumulate, and the operating time is
affected by the applied voltage U . The larger voltage is, the smaller the operating time is, but not
unlimited. When the voltage is large enough to a certain threshold ( Up ), the inverse-time
operating time will not continue to decrease, then the operation characteristic becomes the
definite-time characteristic, and the operating time is tmin , i.e. the setting [59Px.tmin]. The
inverse-time operation characteristic equation is:
k
t
c TMS
(U / U P ) 1
Where:
t min
UP UD U
When the applied voltage is not a fixed value, but changes with time, the operating behavior of the
protection is shown in the following equation:
T0
1
t (U )dt
0
1
Where:
The supported dropout characteristics of the phase overvoltage protection include instantaneous
dropout and definite-time dropout.
Instantaneous dropout
Definite-time dropout
When U <[59Px.K_DropOut]* Up , the protection drops out with a time delay of tdr (i.e. the value
of the setting [59Px.t_DropOut]), and the dropout characteristic curve is shown in the following
figure:
Start time
U>Up
Start
signal
3
Operating
signal
Protection
Operating threshold operate
Operating
counter
t dr t dr t dr
Dropout time setting
Dropout time
Dropout time
59P
59Px.Enable 59Px.On
59Px.Block 59Px.Blocked
59Px.Valid
59Px.St
59Px.StA
59Px.StB 3
59Px.StC
59Px.Op
59Px.Op.PhA
59Px.Op.PhB
59Px.Op.PhC
59Px.Alm
3.11.4 Logic
SET [59P.Opt_Up/Upp]=Upp
SET Uab>[59Px.U_Set]
>=1
SET Ubc>[59Px.U_Set] &
SET Uca>[59Px.U_Set]
SET [59P.Opt_1P/3P]=1P
&
SET [59P.Opt_1P/3P]=3P >=1 >=1
SET Uab>[59Px.U_Set]
&
3 SET Ubc>[59Px.U_Set]
&
SET Uca>[59Px.U_Set]
SET [59P.Opt_Up/Upp]=Up
SET Ua>[59Px.U_Set]
>=1
SET Ub>[59Px.U_Set] &
SET Uc>[59Px.U_Set]
SET [59P.Opt_1P/3P]=1P
&
SET [59P.Opt_1P/3P]=3P >=1
SET Ua>[59Px.U_Set]
&
& 59Px.St
SET Ub>[59Px.U_Set]
& Timer
SET Uc>[59Px.U_Set] t
&
t
SIG 59Px.Pkp 59Px.Op
SET [59Px.Opt_Trp/Alm]=Trp
&
59Px.Alm
SET [59Px.Opt_Trp/Alm]=Alm
3.11.5 Settings
Access path:
Default
No. Settings Range Unit Step Description
value
Option of phase-to-phase
voltage or phase voltage for
Up; overvoltage protection
1 59P.Opt_Up/Upp Upp - -
Upp Up: phase voltage
Upp: phase-to-phase
voltage
Option of 1-out-of-3 mode or
3P;
3-out-of-3 mode for 3
2 59P.Opt_1P/3P 3P - - overvoltage protection
1P
3P: 3-out-of-3 mode
1P: 1-out-of-3 mode
The voltage setting of stage
3 59P1.U_Set 57.7~200 115 V 0.001 1 of phase overvoltage
protection
The dropout coefficient of
4 59P1.K_DropOut 0.93 ~1.00 0.98 - 0.001 stage 1 of phase
overvoltage protection
The operating time setting of
5 59P1.t_Op 0.1 ~100 1 s 0.001 stage 1 of phase
overvoltage protection
The dropout time setting of
6 59P1.t_DropOut 0 ~100 0 s 0.001 stage 1 of phase
overvoltage protection
The logic setting for
Disabled; enabling/disabling the stage
7 59P1.En Enabled - -
Enabled 1 of phase overvoltage
protection
Enabling stage 1 of phase
overvoltage protection
Trp;
8 59P1.Opt_Trp/Alm Trp - - operate to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose
The setting for selecting the
ANSIDefTime;
inverse-time operation
IECDefTime;
9 59P1.Opt_Curve IECDefTime - - characteristic curve of stage
UserDefine;
1 of phase overvoltage
InvTime_U
protection.
Default
No. Settings Range Unit Step Description
value
The setting for selecting the
inverse-time dropout
characteristic curve of stage
Inst; 1 of phase overvoltage
10 59P1.Opt_Curve_DropOut Inst - -
DefTime protection
Inst: instantaneous dropout
DefTime: definite-time
dropout
Default
No. Settings Range Unit Step Description
value
The logic setting for
Disabled; enabling/disabling the stage
20 59P2.En Enabled - -
Enabled 2 of phase overvoltage
protection
Enabling stage 2 of phase
overvoltage protection
Trp;
21 59P2.Opt_Trp/Alm Trp - - operate to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose
The setting for selecting the
3
ANSIDefTime;
inverse-time operation
IECDefTime;
22 59P2.Opt_Curve IECDefTime - - characteristic curve of stage
UserDefine;
2 of phase overvoltage
InvTime_U
protection.
The setting for selecting the
inverse-time dropout
characteristic curve of stage
Inst; 2 of phase overvoltage
23 59P2.Opt_Curve_DropOut Inst - -
DefTime protection
Inst: instantaneous dropout
DefTime: definite-time
dropout
The time multiplier setting of
24 59P2.TMS 0.04~ 20 1 - 0.001 stage 2 of phase
overvoltage protection
The minimum operating time
25 59P2.tmin 0 ~10 0.02 s 0.001 setting of stage 2 of phase
overvoltage protection
The constant “k” of the
customized inverse-time
26 59P2.K 0.001~120 1 - 0.0001 operation characteristic of
stage 2 of phase
overvoltage protection
The constant “α” of the
customized inverse-time
27 59P2.Alpha 0.01 ~3 1 - 0.0001 operation characteristic of
stage 2 of phase
overvoltage protection
Default
No. Settings Range Unit Step Description
value
The constant “C” of the
customized inverse-time
28 59P2.C 0 ~1 0 - 0.0001 operation characteristic of
stage 2 of phase
overvoltage protection
Residual overvoltage protection can be enabled or disabled via the settings or binary input signals,
for some specific applications, residual overvoltage protection needs to be blocked by the external
signal, so the device provides a function block input signal to be used to block residual
overvoltage protection. The enabling and blocking logic of residual overvoltage protection is
shown in the figure below:
EN 59Gx.En &
59Gx.On
SIG 59Gx.Enable
&
SIG 59Gx.Block ≥1 59Gx.Blocked
SIG Fail_Device
&
59Gx.Valid
Figure 3.12-1 The enabling and blocking logic of residual overvoltage protection
The logic diagram of the fault detector element of residual overvoltage protection is as follows:
SET [59G.Opt_3U0]=Cal
≥1
SET 3U0_Ext> U_DropOut &
& 59Gx.Pkp
SET [59Gx.Opt_3U0]=Ext 0 500ms
&
SIG 59Gx.On &
FD.Pkp
SIG
EN
59Gx.Valid
[59Gx.Opt_Trp/Alm]=Alm
3
Figure 3.12-2 Logic diagram of the fault detector element of residual overvoltage protection
Where:
Residual overvoltage protection can operate with a settable time delay. When U 0 > U 0 p , the
protection operates with a time delay of top (i.e. the value of the setting [59Gx.t_Op]), and the
operation characteristic curve is shown in the following figure:
t op
U0p U0
Instantaneous dropout
Definite-time dropout
When U 0 <[59Gx.K_DropOut]* U 0 p , the protection drops out with a time delay of tdr (i.e. the
value of the setting [59Gx.t_DropOut]), and the dropout characteristic curve is shown in the
following figure:
3 Start time
U0>U0p
Start
signal
Operating
signal
Protection
Operating threshold operate
Operating
counter
t dr t dr t dr
Dropout time setting
Dropout time
Dropout time
59G
59Gx.Enable 59Gx.On
59Gx.Block 59Gx.Blocked
59Gx.Valid
59Gx.St
59Gx.Op
59Gx.Alm
3.12.4 Logic
SET [59G.Opt_3U0]=Cal
≥1 &
[59Gx.t_Op] [59Gx.t_DropOut]
SET 3U0_Ext> [59Gx.3U0_Set] & &
59Gx.Op
SET [59Gx.Opt_3U0]=Ext
SIG 59Gx.Pkp
3.12.5 Settings
Access path:
Default
No. Settings Range Unit Step Description
value
Option of measured residual voltage or
calculated residual voltage for residual
Ext;
1 59G.Opt_3U0 Cal - - overvoltage protection
Cal
Ext: the measured residual voltage
Cal: the calculated residual voltage
Default
No. Settings Range Unit Step Description
value
The voltage setting of stage 1 of residual
2 59G1.3U0_Set 1~200 50 V 0.001
overvoltage protection
The dropout coefficient of stage 1 of residual
3 59G1.K_DropOut 0.93 ~1 0.98 - 0.001
overvoltage protection
The operating time setting of stage 1 of
4 59G1.t_Op 0.1 ~100 1 s 0.001
residual overvoltage protection
The dropout time setting of stage 1 of
5 59G1.t_DropOut 0 ~100 0 s 0.001
residual overvoltage protection
When the system has a broken-conductor, reverse phase sequence or inter-phase voltage
imbalance, the negative-sequence voltage increases, and the negative-sequence overvoltage
protection can reflect the system imbalance fault. It is used to protect the equipment from
insulation breakdown or premature aging due to overvoltage. The negative-sequence overvoltage
protection can also be used to alarm for prompting users the system voltage state is abnormal at
this moment.
Negative-sequence overvoltage protection can be enabled or disabled via the settings or binary
input signals, for some specific applications, overvoltage protection needs to be blocked by the
external signal, so the device provides a function block input signal to be used to block
overvoltage protection. The enabling and blocking logic of negative-sequence overvoltage
protection is shown in the figure below: 3
The logic diagram of enabling/disabling negative-sequence overvoltage protection is shown as
below.
SIG 59Qx.Enable
& 59Qx.Blocked
SIG 59Qx.Block ≥1
SIG Fail_Device
& 59Qx.Valid
When the negative-sequence overvoltage protection is enabled and no external blocking signal is
input, if the negative-sequence voltage is larger than the voltage setting multiplied by the dropout
coefficient setting of the negative-sequence overvoltage protection, the negative-sequence
overvoltage protection will pick up.
The logic diagram of the fault detector of the negative-sequence overvoltage protection is shown
as below.
SIG 59Qx.Valid
EN [59Qx.Opt_Trp/Alm]=Alm
Figure 3.13-2 Logic diagram of the fault detector of negative-sequence overvoltage protection
Where:
Negative-sequence overvoltage protection can operate with a definite-time limit, the characteristic
curve meets the IEC60255-3 and ANSI C37.112 standards.
When the negative-sequence voltage is larger than the voltage setting, the protection operates
with a time delay of top (i.e. the value of the setting [59Qx.t_Op]), and the operation
characteristic curve is shown in the following figure:
t
3
t op
U2p U2
Instantaneous dropout
When U2 <[ 59Qx.K_DropOut]*[59Qx.U2_Set] (x: 1~2), the protection drops out immediately.
Definite-time dropout
When U2 <[59Qx.K_DropOut]*[59Qx.U2_Set] (x: 1~2), the protection drops out with a time delay
of tdr (i.e. the value of the setting [59Qx.t_DropOut]), and the dropout characteristic curve is
shown in the following figure:
Start time
U 2> U2p
Start signal
Operating
signal
3
Protection
Operating threshold operate
Operating
counter
t dr t dr t dr
Dropout time setting
Dropout time
Dropout time
59Q
59Qx.Enable 59Qx.On
59Qx.Block 59Qx.Blocked
59Qx.Valid
59Qx.St
59Qx.Op
59Qx.Alm
3.13.4 Logic
59Qx.St
3.13.5 Settings
Access path:
12 59Q2.Opt_Trp/Alm
Trp;
Trp - -
overvoltage operate to trip or alarm. 3
Alm Trp: for tripping purpose
Alm: for alarm purpose
Positive-sequence overvoltage protection can be enabled or disabled via the settings or binary
input signals, for some specific applications, overvoltage protection needs to be blocked by the
external signal, so the device provides a function block input signal to be used to block
overvoltage protection. The enabling and blocking logic of positive-sequence overvoltage
protection is shown in the figure below:
SIG 59Pos.Enable
& 59Pos.Blocked
SIG 59Pos.Block ≥1
SIG Fail_Device
& 59Pos.Valid
When the positive-sequence overvoltage protection is enabled and no external blocking signal is
input, if the positive-sequence voltage is larger than the voltage setting multiplied by the dropout
coefficient setting of the positive-sequence overvoltage protection, the positive-sequence
overvoltage protection will pick up.
The logic diagram of the fault detector of the positive-sequence overvoltage protection is shown
as below.
3 SIG 59Pos.Valid
EN [59Pos.Opt_Trp/Alm]=Alm
Figure 3.14-2 Logic diagram of the fault detector of positive-sequence overvoltage protection
Where:
Positive-sequence overvoltage protection can operate with a definite-time limit, the characteristic
curve meets the IEC60255-3 and ANSI C37.112 standards.
When the positive-sequence voltage is larger than the voltage setting, the protection operates
with a time delay of top (i.e. the value of the setting [59Pos.t_Op]), and the operation
characteristic curve is shown in the following figure:
t op
U 1p U1
Instantaneous dropout
When U <[ 59Pos.K_DropOut]*[59Pos.U1_Set] (x: 1~2), the protection drops out immediately.
1
Definite-time dropout
When U <[59Pos.K_DropOut]*[59Pos.U1_Set] (x: 1~2), the protection drops out with a time delay
1
of tdr (i.e. the value of the setting [59Pos.t_DropOut]), and the dropout characteristic curve is
shown in the following figure: 3
Start time
U 1> U1p
Start signal
Operating
signal
Protection
Operating threshold operate
Operating
counter
t dr t dr t dr
Dropout time setting
Dropout time
Dropout time
59Pos
59Pos.Enable 59Pos.On
59Pos.Block 59Pos.Blocked
59Pos.Valid
59Pos.St
59Pos.Op
59Pos.Alm
3.14.4 Logic
59Pos.St
3.14.5 Settings
Access path:
Taking into account that the role of undervoltage protection is to remove the running device from
the system, but in order to prevent that undervoltage protection is always operating when it is not
charged, the breaker closed position check criterion is added, users can choose to detect the
breaker position, current or no-check as the releasing condition for the protection.
In addition, the undervoltage protection also provides the alarm function, prompting the voltage
drop of the system, it allows users to find the cause timely, and preventing further deterioration of
the fault. Each stage of phase undervoltage protection can be independently set as definite-time
characteristics or inverse-time characteristics. The dropout characteristics can be set as
instantaneous dropout and definite-time dropout.
Users can select phase voltage or phase-to-phase voltage for the protection calculation via the
setting [27P.Opt_Up/Upp]. If it is set as “0”, phase voltage criterion is selected, and if it is set to “1”,
phase-to-phase voltage criterion is selected.
Users can select “1-out-of-3” or “3-out-of-3” logic for the protection criterion via the setting
The breaker closed position check mode is configured via the setting [27P.Opt_LogicMode], it
includes:
[27P.Opt_LogicMode]=None: no-check;
Undervoltage protection can be enabled or disabled via the settings or binary input signals, for
some specific applications, undervoltage protection needs to be blocked by the external signal, so
the device provides a function block input signal to be used to block undervoltage protection. The
enabling and blocking logic of undervoltage protection is shown in the figure below:
EN 27Px.En &
27Px.On
SIG 27Px.Enable
&
SIG 27Px.Block ≥1 27Px.Blocked
SIG Fail_Device
&
27Px.Valid
Figure 3.15-1 The enabling and blocking logic of phase undervoltage protection
The logic diagram of the fault detector element of phase undervoltage protection is as follows:
SET [27P.Opt_1P/3P]=3P
&
SET [27P.Opt_Up/Upp]=Upp
SET Uab<[U_DropOut]
&
SET Ubc<[U_DropOut]
SET Uca<[U_DropOut]
>=1
&
SET [27P.Opt_1P/3P]=1P
SET Uab<[U_DropOut]
>=1
SET Ubc<[U_DropOut] 3
SET Uca<[U_DropOut]
SET [27P.Opt_1P/3P]=3P
&
SET [27P.Opt_Up/Upp]=Up
SET Ua<[U_DropOut]
&
SET Ub<[U_DropOut] >=1
SET Uc<[U_DropOut]
>=1 Pickup voltage criterion
&
SET [27P.Opt_1P/3P]=1P
SET Ua<[U_DropOut]
>=1
SET Ub<[U_DropOut]
SET Uc<[U_DropOut]
SET [27P.Opt_LogicMode]=None
>=1
&
>=1
SET [27P.Opt_LogicMode]=CurrOrCBPos
&
&
SET [27P.Opt_LogicMode]=CurrAndCBPos
&
EN [27Px.En_VTS_Blk]
SIG 27Px.On
SIG 27Px.Valid
3
SET [27Px.Opt_Trp/Alm]=Alm
Figure 3.15-2 Logic diagram of the fault detector element of phase undervoltage protection
Where:
Undervoltage protection can operate with a definite-time limit, it can also operate with an
inverse-time limit, the characteristic curve meets the IEC60255-3 and ANSI C37.112 standards.
Undervoltage protection can support definite-time limit, IEC & ANSI standard inverse time limit
and user-defined inverse-time limit, users can select the wanted operating curve by the setting
[27Px.Opt_Curve] (x=1 or 2), the relationship between the value of the setting and the curve is
shown in the table below.
When the setting [27Px.Opt_Curve] is set as “InvTime_U”, the operation characteristic is the
corresponding selected operating curve type, and the settings [27Px.K], [27Px.C] and
[27Px.Alpha] are useless.
When the setting [27Px.Opt_Curve] is set as “UserDefine”, i.e. the user-defined inverse-time
characteristic is selected, the inverse-time operating curve is determined by the settings [27Px.K],
[27Px.C] and [27Px.Alpha].
Definite-time characteristic
When U < Up , the protection operates with a time delay of top (i.e. the value of the setting
[27Px.t_Op]), and the operation characteristic curve is shown in the following figure:
t op
3
Up U
Inverse-time characteristic
When U < Up , the inverse-time accumulator begins to accumulate, and the operating time is
affected by the applied voltage U . The lower voltage is, the smaller the operating time is, but not
unlimited. When the voltage is low enough to a certain threshold ( Up ), the inverse-time operating
time will not continue to decrease, then the operation characteristic becomes the definite-time
characteristic, and the operating time is tmin , i.e. the setting [27Px.tmin]. The inverse-time
operation characteristic equation is:
k
t
c TMS
1 (U / U P )
Where:
3 t min
UD UP U
When the applied voltage is not a fixed value, but changes with time, the operating behavior of the
protection is shown in the following equation:
T0
1
t (U )dt
0
1
Where:
Instantaneous dropout
Definite-time dropout
When U >[27Px.K_DropOut]* Up , the protection drops out with a time delay of tdr (i.e. the value
of the setting [27Px.t_DropOut]), and the dropout characteristic curve is shown in the following
figure:
Start time
U<Up
Start
signal
Operating
signal
3
Protection
Operating threshold operate
Operating
counter
t dr t dr t dr
Dropout time setting
Dropout time
Dropout time
27P
27Px.Enable 27Px.On
27Px.Block 27Px.Blocked
27Px.Valid
27Px.St
27Px.StA
27Px.StB
27Px.StC
27Px.Op
27Px.Op.PhA
27Px.Op.PhB
27Px.Op.PhC
27Px.Alm
3.15.4 Logic
SET [27P.Opt_1P/3P]=3P
&
SET [27P.Opt_Up/Upp]=Upp
SET Uab<[27Px.U_Set]
&
SET Ubc<[27Px.U_Set]
SET Uca<[27Px.U_Set]
>=1
&
SET [27P.Opt_1P/3P]=1P
SET Uab<[27Px.U_Set]
>=1
3
SET Ubc<[27Px.U_Set]
SET Uca<[27Px.U_Set]
SET [27P.Opt_1P/3P]=3P
&
SET [27P.Opt_Up/Upp]=Up
SET Ua<[27Px.U_Set]
&
SET Ub<[27Px.U_Set] >=1
SET Uc<[27Px.U_Set]
>=1 Voltage criterion
&
SET [27P.Opt_1P/3P]=1P
SET Ua<[27Px.U_Set]
>=1
SET Ub<[27Px.U_Set]
SET Uc<[27Px.U_Set]
SIG 27Px.On
SIG 27Px.Pkp
&
27Px.Op
SET [27Px.Opt_Trp/Alm]=Trp
&
27Px.Alm
SET [27Px.Opt_Trp/Alm]=Alm
Where:
3.15.5 Settings
Access path:
Default
3
No. Settings Range Unit Step Description
value
Option of phase-to-phase
voltage or phase voltage
for stage x of
Up;
1 27P.Opt_Up/Upp Upp - - undervoltage protection
Upp
Up: phase voltage
Upp: phase-to-phase
voltage
Option of 1-out-of-3 mode
or 3-out-of-3 mode for
3P; stage x of undervoltage
2 27P.Opt_1P/3P 3P - -
1P protection
3P: 3-out-of-3 mode
1P: 1-out-of-3 mode
Breaker closed position
check mode
None: no check
Curr: check the current
None; CBPos: check the
Curr; normally open auxiliary
3 27P.Opt_LogicMode CBPos; Curr - - contact
CurrOrCBPos; CurrOrCBPos: check the
CurrAndCBPos current and normally open
auxiliary contact
CurrAndCBPos: check the
current or normally open
auxiliary contact
The voltage setting of
4 27P1.U_Set 5~120 80 V 0.001 stage 1 of phase
undervoltage protection
The dropout coefficient of
5 27P1.K_DropOut 1~1.2 1.03 - 0.001 stage 1 of phase
undervoltage protection
Default
No. Settings Range Unit Step Description
value
The operating time setting
6 27P1.t_Op 0.1 ~100 1 s 0.001 of stage 1 of phase
undervoltage protection
The dropout time setting
7 27P1.t_DropOut 0 ~100 0 s 0.001 of stage 1 of phase
undervoltage protection
Logic setting to determine
the behavior of stage 1 of
phase undervoltage
protection when VT circuit
3
supervision function is
Disabled;
8 27P1.En_VTS_Blk Disabled - - enabled and VT circuit
Enabled
failure happens.
0: it is not effected by VT
circuit failure
1: it will be blocked by VT
circuit failure signal
The logic setting for
enabling/disabling the
Disabled; stage 1 of phase
9 27P1.En Enabled - -
Enabled undervoltage protection
0: disabling
1: enabling
Enabling stage 1 of phase
undervoltage protection
Trp;
10 27P1.Opt_Trp/Alm Trp - - operate to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose
The setting for selecting
ANSIDefTime;
the inverse-time operation
IECDefTime;
11 27P1.Opt_Curve IECDefTime - - characteristic curve of
UserDefine;
stage 1 of phase
InvTime_U
undervoltage protection.
The setting for selecting
the inverse-time dropout
characteristic curve of
stage 1 of phase
Inst;
12 27P1.Opt_Curve_DropOut Inst - - undervoltage protection
DefTime
Inst: instantaneous
dropout
DefTime: definite-time
dropout
Default
No. Settings Range Unit Step Description
value
The time multiplier setting
13 27P1.TMS 0.04~ 20 1 - 0.001 of stage 1 of phase
undervoltage protection
The minimum operating
time setting of stage 1 of
14 27P1.tmin 0.03 ~10 0.03 s 0.001
phase undervoltage
protection
The constant “k” of the
Default
No. Settings Range Unit Step Description
value
Logic setting to determine
the behavior of stage 2 of
phase undervoltage
protection when VT circuit
supervision function is
Disabled;
22 27P2.En_VTS_Blk Disabled - - enabled and VT circuit
Enabled
failure happens.
0: it is not effected by VT
circuit failure
1: it will be blocked by VT
3
circuit failure signal
The logic setting for
enabling/disabling the
Disabled; stage 2 of phase
23 27P2.En Enabled - -
Enabled undervoltage protection
0: disabling
1: enabling
Enabling stage 2 of phase
undervoltage protection
Trp;
24 27P2.Opt_Trp/Alm Trp - operate to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose
The setting for selecting
ANSIDefTime;
the inverse-time operation
IECDefTime;
25 27P2.Opt_Curve IECDefTime - - characteristic curve of
UserDefine;
stage 2 of phase
InvTime_U
undervoltage protection.
The setting for selecting
the inverse-time dropout
characteristic curve of
stage 2 of phase
Inst;
26 27P2.Opt_Curve_DropOut Inst - - undervoltage protection
DefTime
Inst: instantaneous
dropout
DefTime: definite-time
dropout
The time multiplier setting
27 27P2.TMS 0.04~ 20 1 0.001 of stage 2 of phase
undervoltage protection
Default
No. Settings Range Unit Step Description
value
The minimum operating
time setting of stage 2 of
28 27P2.tmin 0.03 ~10 0.03 s 0.001
phase undervoltage
protection
The constant “k” of the
customized inverse-time
29 27P2.K 0.001~120 0.14 - 0.0001 operation characteristic of
stage 2 of phase
3 undervoltage protection
The constant “α” of the
customized inverse-time
30 27P2.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of
stage 2 of phase
undervoltage protection
The constant “C” of the
customized inverse-time
31 27P2.C 0 ~1 0 - 0.0001 operation characteristic of
stage 2 of phase
undervoltage protection
Frequency is an important index of the power quality, which can reflect the balance of the output
power of the generator and the active power of the load. The increase of frequency indicates that
the output power of the system is much larger than that of the load. When the system frequency is
greater than the predefined setting, the overfrequency protection will operate for removing some
part of active power supplies from the system.
Overfrequency protection protection can be enabled or disabled via the settings or binary input
signals, for some specific applications, overfrequency protection needs to be blocked by the
external signal, so the device provides a function block input signal to be used to block
overfrequency protection. The enabling and blocking logic of overfrequency protection is shown in
the figure below:
SIG 81Ox.Enable
& 81Ox.Blocked
SIG 81Ox.Block ≥1
SIG Fail_Device
& 81Ox.Valid
The logic diagram of the fault detector of the overfrequency protection is shown in Figure 3.16-2.
& 81Ox.Pkp
0ms 500ms
&
SIG 81Ox.On
FD.Pkp
SIG 81Ox.Valid
The overfrequency protection has definite-time delay characteristic complied with IEC 60255-3
and ANSI C37.112. If the system frequency is greater than the frequency setting [81Ox.f_Set] (x:
1~6), the overfrequency protection will operate after the time setting [81Ox.t_Op] (x: 1~6).
t op
fp f
The overfrequency protection is with instantaneous dropout characteristic. If the system frequency
is less than the setting [81Ox.f_Set] (x: 1~6), the overfrequency protection will drop out at once.
81O
81Ox.Enable 81Ox.On
81Ox.Blocked
81Ox.Block
81Ox.Valid
81Ox.St
81Ox.Op
3.16.4 Logic
&
SET Upp_min>[81.Upp_Blk] [81Ox.t_Op] 0 81Ox.Op
SIG 81Ox.Pkp
3
Figure 3.16-5 Logic diagram of overfrequency protection
3.16.5 Settings
Access path:
Frequency is an important index of the power quality, which can reflect the balance of the output
power of the generator and the active power of the load. The decrease of frequency indicates that
the output power of the system is much less than that of the load. When the system frequency is
less than the predefined setting, the underfrequency protection will operate for shedding some
part of loads from the system.
This device provides six stages of underfrequency protection. If the system frequency is less than
the predefined setting, this protection will operate for shedding some part of loads from the system.
The underfrequency protection is with independent definite-time delay characteristic and with
instantaneous dropout characteristic.
The underfrequency protection can be enabled or disabled by the settings. If the setting [81Ux.En]
(x: 1~6) is set as “1”, and the signal [81Ux.Enable] (x: 1~6) is “1” and the signal [81Ux.Block] (x:
1~6) is “0”. For some special application, the underfrequency protection needs to be blocked by
external signal, the input signal [81Ux.Block] (x: 1~6) is provided for this purpose.
SIG 81Ux.Enable
& 81Ux.Blocked
SIG 81Ux.Block ≥1
SIG Fail_Device
& 81Ux.Valid
The logic diagram of the fault detector of the underfrequency protection is shown in Figure 3.17-2.
& 81Ux.Pkp
0ms 500ms
&
SIG 81Ux.On
FD.Pkp
SIG 81Ux.Valid
The underfrequency protection has definite-time delay characteristic complied with IEC 60255-3
and ANSI C37.112. If the system frequency is less than the frequency setting [81Ux.f_Set] (x:
1~6), the underfrequency protection will operate after the time setting [81Ux.t_Op] (x: 1~6).
t op
3
fp f
81U
81Ux.Enable 81Ux.On
81Ux.Block 81Ux.Blocked
81Ux.Valid
81Ux.St
81Ux.Op
3.17.4 Logic
&
SET Upp_min>[81.Upp_Blk] [81Ux.t_Op] 0 81Ux.Op
SIG 81Ux.Pkp
3
Figure 3.17-5 Logic diagram of underfrequency protection
3.17.5 Settings
Access path:
Frequency rate-of-change reflects the balance of the output power of the generator and the active
power of the load. It can reflect the increase of active load power and the decrease of frequency.
When the frequency changes too fast, it is generally considered that the system has a fault, and
the frequency rate-of-change protection can operate in such a situation.
This device provides six stages of frequency rate-of-change protection. If the system frequency
rate-of-change is greater than the predefined setting, this protection will operate. The frequency
rate-of-change protection is with independent definite-time delay characteristic and with
instantaneous dropout characteristic.
The frequency rate-of-change protection can be enabled or disabled by the settings. If the setting
[81Rx.En] (x: 1~6) is set as “1”, and the signal [81Rx.Enable] (x: 1~6) is “1” and the signal
[81Rx.Block] (x: 1~6) is “0”. For some special application, the frequency rate-of-change protection
needs to be blocked by external signal, the input signal [81Rx.Block] (x: 1~6) is provided for this
purpose.
SIG 81Rx.Enable
& 81Rx.Blocked
SIG 81Rx.Block ≥1
SIG Fail_Device
& 81Rx.Valid
The logic diagram of the fault detector of the frequency rate-of-change protection is shown in
Figure 3.18-2.
SIG 81Rx.Valid
Figure 3.18-2 Logic diagram of the fault detector of frequency rate-of-change protection
The frequency rate-of-change protection has definite-time delay characteristic complied with IEC
60255-3 and ANSI C37.112. If the absolute value of the system frequency rate-of-change is
greater than the absolute value of setting [81Rx.df/dt_Set] (x: 1~6), the frequency rate-of-change
protection will operate after the time setting [81Rx.t_Op] (x: 1~6).
The operation characteristic curve of the frequency rate-of-change protection is shown in Figure
3.18-3.
top
3
-df/dtset df/dtset
-df/dt df/dt
81R
81Rx.Enable 81Rx.On
81Rx.Blocked
81Rx.Block
81Rx.Valid
81Rx.St
81Rx.Op
3.18.4 Logic
81Rx.St
SET Upp_min > [81.Upp_VCE]
≥1
df/dt < 0 & &
3
SET
df/dt < [81Rx.df/dt_Set] [81Rx.t_Op] 0 81Rx.Op
&
SET f < [81Rx.f_Pkp]
SIG 81Rx.Pkp
3.18.5 Settings
Access path:
If a power supply failure occurs on the feeder, the synchronous motors become generators due to
the inertia of their load and the induction motors become generators. The aim of the reverse
power protection is to detect the inverse flow of energy and to ensure that the motor does not feed
the fault which has appeared on the network.
power protection is with independent definite-time delay characteristic and with instantaneous
dropout characteristic.
The reverse power protection can be enabled or disabled by the settings. If the setting [32Rx.En]
(x: 1~2) is set as “1”, and the signal [32Rx.Enable] (x: 1~2) is “1” and the signal [32Rx.Block] (x:
1~2) is “0”. For some special application, the reverse power protection needs to be blocked by
external signal, the input signal [32Rx.Block] (x: 1~2) is provided for this purpose.
The logic diagram of enabling/disabling reverse power protection is shown in Figure 3.19-1.
& 32Rx.Blocked
SIG 32Rx.Block ≥1
SIG Fail_Device
& 32Rx.Valid
When the reverse power protection is enabled and no external blocking signal is input, if the
reverse power is greater than the power setting of the reverse power protection, the reverse
power protection will pick up.
The logic diagram of the fault detector of the reverse power protection is shown in Figure 3.19-2.
SIG P<0
32Rx.Pkp
SIG 32Rx.On
SIG 32Rx.Valid
EN [32Rx.Opt_Trp/Alm]=Alm
Figure 3.19-2 Logic diagram of the fault detector of reverse power protection
Where:
[32Rx.P_Set] (x: 1~2) is the power setting of the stage x reverse power protection.
[32R.U1_VCE] is the setting of the positive-sequence voltage control element of the reverse
power protection.
[32R.I1_CCE] is the positive-sequence current setting of the current control element of the
reverse power protection.
[32R.U2_VCE] is the setting of the negative-sequence voltage control element of the reverse
3 power protection.
The reverse power protection has definite-time delay characteristic complied with IEC 60255-3
and ANSI C37.112. If the power value is less than “0”, and the absolute power value is greater
than the power setting of the reverse power protection [32Rx.P_Set] (x: 1~2), the reverse power
protection will operate after the time setting [32Rx.t_Op] (x: 1~2).
The operation characteristic curve of reverse power protection is shown in Figure 3.19-3.
top
P1 P1set
The reverse power protection is with instantaneous dropout characteristic. If the power is greater
than “0” or the power is less than the power setting [32Rx.P_Set] (x: 1~2) multiplied by 0.95, the
reverse power protection will drop out at once.
32R
32Rx.Enable 32Rx.On
32Rx.Block 32Rx.Blocked
32Rx.Valid
32Rx.St
32Rx.Op
32Rx.Alm
3
Figure 3.19-4 Function block diagram of reverse power protection
3.19.4 Logic
SIG P<0
≥1
SET I1 < [32R.I1_CCE]
3 SIG 32Rx.Pkp
3.19.5 Settings
Access path:
3
3.20 Cold Load Pickup Logic (CLP)
The cold load pickup (CLP) logic which is included within this relay serves to either inhibit the
selected protective elements for an appointed duration, or to raise the settings of the selected
protective elements. Therefore, it allows the protection settings to be set closer to the load profile
by automatically increasing them following circuit energization. The CLP logic thus provides
stability, whilst maintaining protection during starting.
If the CLP logic is operated, the CLP settings are enabled for the overcurrent protection and the
zero-sequence overcurrent protection respectively. After the dropout time delay of the CLP logic
has elapsed, the normal protection settings are applied. And if a fast resetting signal is received,
the normal protection settings are applied after the pre-define short resetting time delay.
CLP
CLP.in_init CLP.On
CLP.in_shortRst CLP.Blocked
CLP.Valid
3.20.4 Logic
SET [CLP.Opt_LogicMode] = 0
≥1
SE T
EN CLP.On tCold 0ms
S Q
&
SIG CLP.BI_52b R
CLR
Q
SET [CLP.Opt_LogicMode] = 1 tRst 0ms
3
≥1
& &
tS hort Rst 0ms
SIG CLP.In_ShortRst
SIG CLP.St_50/51
≥1
SIG CLP.in_Init
&
CLP.Op
EN CLP.On
Where:
CLP.Onload is the signal denotes anyone of the phase currents is greater than 0.04In.
CLP.BI_52b is the binary input for inputting the normally closed contact of the circuit breaker.
CLP.St_50/51 is the binary signal which denotes anyone of the selected protective elements
picked up.
“CLP.On” is the signal for denoting the cold load pickup logic function is enabled.
“tCold” is the setting [CLP.t_Cold], the time setting for ensuring the cold load condition is met.
“tRst” is the setting [CLP.t_Rst], the time setting for resetting the cold load pickup logic function.
“tShortRst” is the setting [CLP.t_ShortRst], the time setting for fast resetting the cold load pickup logic
function.
3.20.5 Settings
Access path:
The undercurrent protection can remove the device from the system by detecting the smaller load
current when the load is lost, the capacitor is lost of voltage and the motor is running without any
load.
Undercurrent protection can be enabled or disabled via the settings or binary input signals, for
some specific applications, undercurrent protection needs to be blocked by the external signal, so
3 the device provides a function block input signal to be used to block undercurrent protection. The
enabling and blocking logic of undercurrent protection is shown in the figure below:
SIG 37.Enable
& 37.Blocked
SIG 37.Block ≥1
SIG Fail_Device
& 37.Valid
When the undercurrent protection is enabled and no external blocking signal is input, if the
detected current is less than the current setting multiplied by 1.10 of the undercurrent protection,
the undercurrent protection will pick up.
Users can select “1-out-of-3” or “3-out-of-3” logic for the protection criterion via the setting
[37.Opt_1P/3P]. If it is set as “1P”, undercurrent protection can operate if any phase current is
smaller than the current setting. If it is set as “3P”, undercurrent protection cannot operate unless
three phase currents are smaller than the current setting.
The circuit breaker position with/without the current condition can be used as an auxiliary criterion
for undercurrent protection, which can be configured via the setting [37.Opt_LogicMode].
The logic diagram of the fault detector of the undercurrent protection is shown as below.
SIG Ia<1.10×[37.I_Set]
>=1
SIG Ib<1.10×[37.I_Set] &
SIG Ic<1.10×[37.I_Set]
>=1
Pickup current criterion
SET [37.Opt_1P/3P]=1P
SIG Ia<1.10×[37.I_Set]
&
SIG Ib<1.10×[37.I_Set] &
SIG Ic<1.10×[37.I_Set]
SET [37.Opt_1P/3P]=3P
3
SET [37.Opt_LogicMode]=None
>=1
&
>=1
SET [37.Opt_LogicMode]=CurrOrCBPos
&
&
SET [37.Opt_LogicMode]=CurrAndCBPos
SET [37.Opt_Trp/Alm]=Alm
The undercurrent protection has definite-time operation characteristic complied with IEC 60255-3
and ANSI C37.112. If the load current is less than the current setting of the undercurrent
protection [37.I_Set], the undercurrent protection will operate after the time setting [37.t_Op].
t op
Ip I
The undercurrent protection is with instantaneous dropout characteristic. If the load current is
larger than the current setting [37.I_Set] multiplied by 1.10, the undercurrent protection will drop
out immediately.
37
37.Enable 37.On
37.Block 37.Blocked
37.Valid
37.St
37.StA
37.StB
37.StC
37.Op
37.Op.PhA
37.Op.PhB
37.Op.PhC
37.Alm
3.21.4 Logic
SIG Ia<[37.I_Set]
>=1
SIG Ib<[37.I_Set] &
SIG Ic<[37.I_Set]
>=1
Current criterion
SET [37.Opt_1P/3P]=1P
SIG Ia<[37.I_Set]
&
SIG Ib<[37.I_Set] &
3 SIG Ic<[37.I_Set]
SET [37.Opt_1P/3P]=3P
SIG 37.Pkp
&
37.Op
SET [37.Opt_Trp/Alm]=Trp
&
37.Alm
SET [37.Opt_Trp/Alm]=Alm
Where:
3.21.5 Settings
Access path:
None;
Curr;
CurrAnd The setting of the CB position check
4 37.Opt_LogicMode CBPos; - -
CBPos mode.
CurrAndCBPos;
CurrOrCBPos
Disabled; The logic setting of the undercurrent
5 37.En Enabled - -
Enabled protection
Enabling undercurrent protection
Trp; operate to trip or alarm.
6 37.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose
Alm: for alarm purpose
3
3.22 Breaker Failure Protection (50BF)
When a fault happens to the power system, the device will operate to trip the circuit breaker, and
the fault will be isolated by opening the circuit breaker. If the circuit breaker fails to open within the
certain time due to some abnormalities (for example, low tripping pressure), the fault may cause
system stability being destroyed or electrical equipment being damaged. Breaker failure
protection is adopted to issue a backup tripping command to trip adjacent circuit breakers, and
isolate the fault as requested by the device.
According to the tripping information from the device and the auxiliary information (the current and
the position) of target circuit breaker, breaker failure protection constitutes the criterion to
discriminate whether the target circuit fails to open. If the criterion is confirmed, breaker failure
protection will operate to trip the target circuit breaker with the time delay [50BF.t_ReTrp], trip it
again with the time delay [50BF.t1_Op] and trip the adjacent circuit breakers with the time delay
[50BF.t2_Op]. As a special backup protection, breaker failure protection can quickly isolate the
fault, reduce the affected range by the fault, keep system stability and prevent generators,
transformers and other primary equipments from seriously damaged.
For breaker failure protection, re-trip and two time delays are available.
3.22.1.1 Re-trip
When breaker failure protection receives initiating signal of tripping and phase overcurrent
element of any phase operates, the device will issue tripping command to re-trip the target circuit
breaker with the time delay [50BF.t_ReTrp]. In order to improve the sensitivity, both
zero-sequence overcurrent element and negative-sequence overcurrent element are added,
which can be enabled or disabled by the settings [50BF.En_3I0_3P] and [50BF.En_I2_3P].
As similar as re-trip, the device will operate to re-trip the target circuit breaker again with the time
delay [50BF.t1_Op] when the relevant operating criterion is satisfied.
As similar as re-trip, the device will operate to trip the adjacent circuit breakers with the time delay
[50BF.t2_Op] when the relevant operating criterion is satisfied.
Where:
3 = A, B or C
Where:
Where:
is negative-sequence current
For some special fault (for example, mechanical protection or overvoltage protection operating),
maybe faulty current is very small and current criterion of breaker failure protection is not met, in
order to make breaker failure protection can also operate under the above situation, an input
signal "50BF.ExTrp_WOI" is equipped to initiate breaker failure protection, once the input signal is
energized, normally closed auxiliary contact of circuit breaker is chosen in addition to breaker
failure current check to trigger breaker failure timer. The device takes current as priority with CB
auxiliary contact "50BF.52b" as an option criterion for breaker failure check.
When the initiating signal of breaker failure protection is energized for longer than 10s, an alarm
signal "50BF.Alm_Init" will be issued, and will drop out with a time delay of 10s.
50BF
50BF.Enable 50BF.On
50BF.Block 50BF.Blocked
50BF.ExTrp3P 50BF.Valid
50BF.ExTrp_WOI 50BF.St
50BF.Op_ReTrp3P
50BF.Op_t1 3
50BF.Op_t2
50BF.Alm_Init
3.22.4 Logic
EN [50BF.En] &
50BF.On
SIG 50BF.Enable
&
SIG 50BF.Block >=1 50BF.Blocked
SIG Fail_Device
&
50BF.Valid
3
Figure 3.22-1 Logic of enabling breaker failure protection
&
EN [50BF.En_Alm_Init] 50BF.Alm_Init
SIG 50BF.Valid
SIG 50BF.Alm_Init
EN [50BF.En_ReTrp]
EN [50BF.En_Ip]
SET IC>[50BF.I_Set]
&
SIG 50BF.ExtTrp3P
&
EN [50BF.En_3I0_3P] &
SET 3I0>[50BF.3I0_Set]
>=1 &
& >=1 [50BF.t1_Op] 0 50BF.Op_t1
EN [50BF.En_I2_3P] &
SET I2>[50BF.I2_Set]
SIG 50BF.ExtTrp_WOI
>=1
& 50BF.St
EN [50BF.En_CB_Ctrl]
SIG 50BF.52b
EN [50BF.En_t1]
&
[50BF.t2_Op] 0 50BF.Op_t2
EN [50BF.En_t2]
Where:
3.22.5 Settings
Access path:
The SOTF protection can be enabled or disabled via the settings or binary input signals, for some
specific applications, the protection needs to be blocked by the external signal, so the device
provides a function block input signal to be used to block RMS overcurrent protection. The
enabling and blocking logic of the SOTF protection is shown in the figure below:
EN 50PSOTF.En &
50PSOTF.On
SIG 50PSOTF.Enable
&
SIG 50PSOTF.Block ≥1 50PSOTF.Blocked
SIG Fail_Device
&
50PSOTF.Valid
EN 50GSOTF.En &
50GSOTF.On
SIG 50GSOTF.Enable
&
SIG 50GSOTF.Block ≥1 50GSOTF.Blocked
SIG Fail_Device
&
50GSOTF.Valid
The SOTF protection must be initiated by auto-reclosing signal or manual closing signal, the
initiating time can be set by the setting [STOF.t_En]. After the acceleration condition is satisfied,
the SOTF protection will operate with a time delay of [50PSOTF.t_Op]/ [50GSOTF.t_Op].
The device provides a variety of accelerated tripping modes by manual closing signal, which can
choose circuit breaker position, external binary signal of manual closing.
When the circuit breaker is in open position while the device does not pick up, then manual
closing signal will be kept for a certain time which is determined by the setting [SOTF.t_En], and
SOTF protection will be enabled.
2. External binary signal of manual closing (The setting [SOTF.Opt_Mode_ManCls] shall be set
3
as "ManClsBI"or "ManClsBI/CBPos")
When external binary input of manual closing is energized, then manual closing signal will be kept
for a certain time which is determined by the setting [SOTF.t_En], and SOTF protection will be
enabled.
When the SOTF protection is used for the transformer bay, large inrush current generated during
manual closing and auto-reclosing maybe lead to an undesired operation of SOTF protection.
Second harmonic blocking can be selected by the setting
[50PSOTF.En_Hm2_Blk]/[50GSOTF.En_Hm2_Blk] to prevent the mal-operation due to inrush
current. The harmonic blocking characteristic of the phase overcurrent SOTF protection is
consistent with that of phase overcurrent protection. The harmonic blocking characteristic of the
earth fault overcurrent SOTF protection is consistent with that of earth fault overcurrent protection.
In order to improve the reliability, phase overcurrent SOTF protection can select phase voltage
element, phase-to-phase voltage element, zero-sequence voltage element and
negative-sequence voltage element as auxiliary criterion.
50PSOTF 50GSOTF
50PSOTF.Valid 50GSOTF.Valid
50PSOTF.Op
50GSOTF.Op
50PSOTF.St
50GSOTF.St
3.23.4 Logic
SIG 52b_PhA
>=1
SIG 52b_PhB
SIG 52b_PhC
&
SIG FD.Pkp
SET [SOTF.Opt_Mode_ManCls]=ManClsBI/CBPos
&
SIG FD.Pkp
SIG ManCls
SET Ia>[50PSOTF.I_Set]
>=1
SET Ib>[50PSOTF.I_Set]
SET Ic>[50PSOTF.I_Set]
EN [50PSOTF.En_Hm2_Blk]
SET Ua<[50PSOTF.Up_Set]
>=1
SET Ub<[50PSOTF.Up_Set]
SET Uc<[50PSOTF.Up_Set]
&
3
EN [50PSOTF.En_Up_UV]
SET Uab<[50PSOTF.Upp_Set]
>=1 >=1
SET Ubc<[50PSOTF.Upp_Set] &
SET Uca<[50PSOTF.Upp_Set]
EN [50PSOTF.En_Upp_UV]
EN [50PSOTF.En_3U0_OV]
EN [50PSOTF.En_Up_UV]
>=1
EN [50PSOTF.En_Upp_UV]
EN [50PSOTF.En_U2_OV]
EN [50PSOTF.En_3U0_OV]
&
SIG FD.Pkp & [50PSOTF.t_Op] 0 50PSOTF.Op
&
SIG 50PSOTF.Block 50PSOTF.On
EN [50PSOTF.En]
SET [50/51G1.En_Hm2_Blk]
SIG FD.Pkp
EN [50GSOTF.En]
3.23.5 Settings
Access path:
The unbalance current protection is adopted for the internal fault of capacitor bank with
double-star connection. The fault causes the capacitance reactance of a phase branch to be
changed, makes three phase reactance unequal and the unbalance current will be generated at
neutral point.
The application of the unbalance current protection in the capacitor bank with double-star
connection is shown in following figure.
60/50N
This device provides two stages of unbalance current protection. If the unbalance current is
greater than the predefined setting, this protection will operate. The unbalance current protection
is with independent definite-time delay characteristic and with instantaneous dropout
characteristic.
The unbalance current protection can be enabled or disabled by the settings. If the setting
[60/50-x.En] (x: 1~2) is set as “1”, and the signal [60/50-x.Enable] (x: 1~2) is “1” and the signal
[60/50-x.Block] (x: 1~2) is “0”. For some special application, the unbalance current protection
needs to be blocked by external signal, the input signal [60/50-x.Block] (x: 1~2) is provided for this
purpose.
The logic diagram of enabling/disabling unbalance current protection is shown in Figure 3.24-2.
SIG 60/50-x.Enable
& 60/50-x.Blocked
SIG 60/50-x.Block ≥1
SIG Fail_Device
& 60/50-x.Valid
When the unbalance current protection is enabled and no external blocking signal is input, if the
unbalance current is greater than the current setting multiplied by 0.95 of the unbalance current
protection, the unbalance current protection will pick up.
The logic diagram of the fault detector of unbalance current protection is shown in Figure 3.24-3.
SIG 60/50-x.Valid
EN [60/50-x.Opt_Trp/Alm]=Alm
3
Figure 3.24-3 Logic diagram of the fault detector of unbalance current protection
The unbalance current protection has definite-time delay characteristic complied with IEC
60255-3 and ANSI C37.112. If the unbalance current is greater than the voltage setting of the
unbalance current protection [60/50-x.I_Set] (x: 1~2), the unbalance current protection will
operate after the time setting [60/50-x.t_Op] (x: 1~2).
The operation characteristic curve of unbalance current protection is shown in Figure 3.24-4.
t op
I u_set Iu
The unbalance current protection is with instantaneous dropout characteristic. If the unbalance
current is less than the current setting [60/50-x.I_Set] (x: 1~2) multiplied by 0.95, the unbalance
current protection will drop out at once.
60/50
60/50-x.Enable 60/50-x.On
60/50-x.Block 60/50-x.Blocked
60/50-x.Valid
60/50-x.St
60/50-x.Op
60/50-x.Alm
3.24.4 Logic
60/50-x.St
3.24.5 Settings
Access path:
The unbalance voltage protection is adopted for the internal fault of capacitor bank with
double-star connection. The fault causes the capacitance reactance of a phase branch to be
changed, makes three phase reactance unequal and the unbalance voltage will be generated at
neutral point.
The application of the unbalance voltage protection for a capacitor bank with double-star
connection is shown in following figure.
60/59N
This device supports two stages of unbalance voltage protection. If the unbalance voltage is
greater than the predefined setting, this protection will operate. The unbalance voltage protection
is with independent definite-time delay characteristic and with instantaneous dropout
characteristic. In order to adapt to different applications, unbalance voltage protection can operate
to trip or alarm, it can be enabled or blocked by the external binary input.
Unbalance voltage protection can be enabled or disabled via the settings or binary input signals,
for some specific applications, unbalance voltage protection needs to be blocked by the external
signal, so the device provides a function block input signal to be used to block unbalance voltage
protection. The enabling and blocking logic of unbalance voltage protection is shown in the figure
below:
SIG 60/59-x.Enable
& 60/59-x.Blocked
SIG 60/59-x.Block ≥1
SIG Fail_Device
& 60/59-x.Valid
When the unbalance voltage protection is enabled and no external blocking signal is input, if the
unbalance voltage is greater than the voltage setting multiplied by 0.95, the unbalance voltage
protection will pick up.
The logic diagram of the fault detector of unbalance voltage protection is shown as below.
SIG 60/59-x.Valid
EN [60/59-x.Opt_Trp/Alm]=Alm
3
Figure 3.25-3 Logic diagram of the fault detector of unbalance voltage protection
The unbalance voltage protection can operate with a definite-time limit, the characteristic curve
meets the IEC60255-3 and ANSI C37.112 standards.
When the unbalance voltage (Uub) is larger than the voltage setting, the protection operates with a
time delay of top (i.e. the value of the setting [60/59-x.U_Set] (x=1~2)), and the operation
characteristic curve is shown in the following figure:
t op
Uu_set Uu
The unbalance voltage protection is with instantaneous dropout characteristic. If the unbalance
voltage is less than the voltage setting multiplied by 0.95, the unbalance voltage protection will
drop out immediately.
60/59
60/59-x.Enable 60/59-x.On
60/59-x.Block 60/59-x.Blocked
60/59-x.Valid
60/59-x.St
60/59-x.Op
60/59-x.Alm
3.25.4 Logic
60/59-x.St
3.25.5 Settings
Access path:
Besides overhead lines, other equipment failure, such as cables, busbar, transformer fault and so
on, are generally permanent fault, and AR is not initiated after faulty feeder is tripped. For some
mixed circuits, such as overhead line with a transformer unit, hybrid transmission lines, etc., it is
required to ensure that AR is only initiated for faults overhead line section, or make a choice
according to the situation.
device can be connected to the device via input signal to initiate integrated AR.
3.26.1.1 Enable AR
EN [79.En] &
>=1
SET [79.Opt_Enable]=Setting &
79.On
SET [79.Opt_Enable]=Setting&Config &
79.Off
SIG 79.Enable
SIG 79.Block
3.26.1.2 AR Ready
AR must be ready to operate before performing reclosing. The output signal [79.Ready] means
that the auto-reclosure can perform at least one time of reclosing function, i.e., breaker
open-close-open.
When the device is energized or after the settings are modified, AR cannot be ready unless the
following conditions are met:
1. AR is enabled.
2. The circuit breaker is ready, such as, normal storage energy and no low pressure signal.
3. The duration of the circuit breaker in closed position pre-fault is greater than the setting
[79.t_CBClsd].
After AR operates, it must reset, i.e. [79.Active]=0, in addition to the above conditions for reclosing
again.
When there is a fault on an overhead line, the concerned circuit breakers will be tripped normally.
After the fault is cleared, the tripping signal will drop out immediately. In case the circuit breaker is
in failure, etc., and the tripping signal of the circuit breaker maintains and in excess of the time
delay [79.t_PersistTrp], AR will be blocked, as shown in following figure
The input signal [79.CB_Healthy] must be energized before AR gets ready. Because most circuit
breakers can finish one complete process: open-closed-open, it is necessary that circuit breaker
has enough energy before reclosing. When the time delay of AR is exhausted, AR will be blocked
if the input signal [79.CB_Healthy] is still not energized within time delay [79.t_CBReady]. If this
function is not required, the input signal [79.CB_Healthy] can be not to configure, and its state will
be thought as “1” by default.
In order to block AR reliably even if the signal of manually open circuit breaker not connected to
the input signal of blocking AR, when the circuit breaker is open by manually and there is CB
position input under normal conditions, AR will be blocked with the time delay of 100ms if AR is
3
not initiated and no any trip signal.
When AR is disabled, AR fails, synchronism check fails or last shot is reached, or when the
internal blocking condition of AR is met. AR will be discharged immediately and next AR will be
disabled. When the input signal [79.LockOut] is energized, AR will be blocked immediately. The
blocking flag of AR will be also controlled by the internal blocking condition of AR. When the
blocking flag of AR is valid, AR will be blocked immediately. The logic of AR ready is shown as
below
AR will be blocked immediately once the blocking condition of AR appears, but the blocking
condition of AR will drop out with a time delay [79.t_DDO_BlkAR] after blocking signal disappears.
>=1
SIG CB closed position [79.t_CBClsd] 100ms &
SIG 79.Active >=1
SIG 79.On
When any protection element operates to trip, the device will output a signal [79.Active] until AR
drop out (Reset Command). Any tripping signal can be from external protection device or internal
protection element.
3.26.1.3 AR Initiation
AR can be initiated by tripping signal of line protection, and the tripping signal may be from
internal trip signal or external trip signal.
When AR is ready to reclosing (“79.Ready”=1) and the tripping signal is received, this tripping
signal will be kept in the device, and AR will be initiated after the tripping signal drops out. The
tripping signal kept in the device will be cleared after the completion of AR sequence (Reset
Command). Its logic is shown as below.
& AR Initiation
SIG 79.Ready
2. AR initiated by CB state
AR can be initiated by CB state by setting the setting [79.En_CBInit]. Under normal conditions,
when AR is ready to reclose (“79.Ready”=1), AR will be initiated if circuit breaker is open and
corresponding phase current is nil. AR initiated by CB state logic is shown as below. Usually
normally closed contact of circuit breaker is used to reflect CB state.
SIG CB open
&
EN [79.En_CBInit] & AR Initiation
SIG 79.Ready
3
Figure 3.26-5 CB state initiating AR
3.26.1.4 AR Reclosing
When the dead time delay of AR expires after AR is initiated, if the synchronism check is enabled,
the release of reclosing signal shall be subject to the result of synchronism check.
After the dead time delay of AR expires, if the synchronism check is still unsuccessful within the
time delay [79.t_wait_Chk], the signal of synchronism check failure ("79.Fail_Chk") will be output
and the AR will be blocked. If 3-pole AR with no-check is enabled, the condition of synchronism
check success ("25.RSYN_OK") will always be established. And the signal of synchronism check
success ("25.RSYN_OK") from the synchronism check logic can be applied by AR inside the
device or outside the device.
SIG 79.Ok_Chk
Reclosing pulse length may be set through the setting [79.t_PW_AR]. For the circuit breaker
without anti-pump interlock, the setting [79.En_CutPulse] is available to control the reclosing
pulse. When this function is enabled, if the device operates to trip during reclosing, the reclosing
pulse will drop out immediately, so as to prevent multi-shot reclosing onto fault. After the reclosing
signal is issued, AR will drop out with time delay [79.t_Reclaim], and can carry out next reclosing.
The reclaim timer is started when the CB closing signal is given. The reclaim timer defines a time
from the issue of the reclosing command, after which the reclosing function resets. Should a new
trip occur during this time, it is treated as a continuation of the first fault.
&
SIG Three- phase Trip 79.AR_Out
&
EN [ 79.En _ CutPulse]
>=1
&
79.AR_Out [79.t_ Reclaim] 0ms Reset Command
3
SIG
For line fault, the fault will be cleared after the device operates to trip. When the following cases
appear, the reclosing is unsuccessful.
1. If any protection element operates to trip when AR is enabled ("79.On"=1) and AR is not
ready ("79.Ready"=0), the device will output the signal "79.Failed".
2. For one-shot AR, if the tripping signal is received again within reclaim time after the reclosing
pulse is issued, the reclosing shall be considered as unsuccessful.
3. For multi-shot AR, if the reclosing times are equal to the setting value of AR number and the
tripping signal is received again after the last reclosing pulse is issued, the reclosing shall be
considered as unsuccessful.
SIG 79.On
&
SIG 79.Ready
79.Inprog
SIG
&
SIG 79.AR_Blkd
>=1 3
SIG AR Pulse &
[79.t_Fail ] 0
&
SIG CB closed
EN [79.En_ FailCheck ]
&
79.Succeeded
&
0 [79.t_Fail ]
0s 2s 79.Completed
The device may be set up into one-shot or multi-shot AR. Through the setting [79.Num], the
maximum number of reclosing attempts may be set up to 4 times. Generally, only one-shot AR is
selected. Some corresponding settings may be hidden if one-shot AR is selected.
[79.Num]=1
It means one-shot reclosing. Line protection device will operate to trip when a transient fault
occurs on the line and AR will be initiated. After the dead time delay for AR is expired, the device
will send reclosing pulse, and then AR will drop out after the time delay [79.t_Reclaim] to ready for
the next reclosing. For permanent fault, the device will operate to trip again after the reclosing is
performed, and the device will output the signal of reclosing failure "79.Failed".
[79.Num]>1
It means multi-shot reclosing. For multi-shot reclosing, line protection device will operate to trip
when a transient fault occurs on the line and AR will be initiated. After the dead time delay of the
first reclosing is expired, the device will send reclosing pulse, and then AR will drop out after the
time delay [79.t_Reclaim] to ready for the next reclosing. For permanent fault, the device will
operate to trip again after the reclosing is performed, and then AR is initiated after the tripping
contact drops off. After the time delay for AR is expired, the device will send reclosing pulse. The
sequence is repeated until the reclosing is successful or the maximum permit reclosing number
[79.Num] is reached.
The following two examples indicate typical time sequence of AR process for transient fault and
Signal
Fault
Trip
CB 52b
3 79.t_Reclaim
Open [79.t_Reclaim]
79.Active
79.Inprog [79.t_Dd_3PS1]
79.Inprog_3P [79.t_Dd_3PS1]
79.Ok_Chk
AR Out [79.t_PW_AR]
79.Perm_Trp3P
79.Failed
Time
Signal
Fault
Trip
Open Open
52b
[79.t_Reclaim]
79.t_Reclaim
79.Active
79.Inprog 3
79.Inprog_3P1 [79.t_Dd_3PS1]
79.Inprog_3PS2 [79.t_Dd_3PS2]
79.Ok_Chk
79.Perm_Trp3P
79.Failed 200ms
Time
79
79.Block 79.Off
79. Inprog
79. Inprog_3P
79.Inprog _ 3PS1
79.Inprog _ 3PS2
79.Inprog _ 3PS3
79.Inprog _ 3PS4
79.Failed
79.Succeeded
79.Completed
79.Fail_Chk
1 79.On AR is enabled.
2 79.Off AR is disabled.
3 79.Close AR operates.
4 79.Ready AR have been ready for reclosing cycle.
5 79.AR_Blkd AR is blocked.
6 79.Active AR logic is active.
7 79.Inprog AR cycle is in progress
8 79.Inprog_3P 3-pole AR cycle is in progress
9 79.Inprog_3PS1 First 3-pole AR cycle is in progress
10 79.Inprog_3PS2 Second 3-pole AR cycle is in progress
11 79.Inprog_3PS3 Third 3-pole AR cycle is in progress 3
12 79.Inprog_3PS4 Fourth 3-pole AR cycle is in progress
AR status
0: AR is preprocessed
13 79.Status 1: AR is ready.
2: AR is in progress.
3: AR is successful.
14 79.Failed Auto-reclosing fails
15 79.Succeeded Auto-reclosing is successful
16 79.Fail_Chk Synchrocheck for AR fails
17 79.Completed AR is completed.
3.26.4 Settings
Access path:
Default
No. Settings Range Unit Step Description
value
Maximum number of reclosing
1 79.Num 1~4 1 - 1
attempts
Dead time of first shot 3-pole
2 79.t_Dd_3PS1 0~600 0.600 s 0.001
reclosing
Dead time of second shot 3-pole
3 79.t_Dd_3PS2 0~600 0.600 s 0.001
reclosing
Dead time of third shot 3-pole
4 79.t_Dd_3PS3 0~600 0.600 s 0.001
reclosing
Dead time of fourth shot 3-pole
5 79.t_Dd_3PS4 0~600 0.600 s 0.001
reclosing
Time delay of circuit breaker in
6 79.t_CBClsd 0~600 5.000 s 0.001
closed position before reclosing
Default
No. Settings Range Unit Step Description
value
Time delay to wait for CB healthy,
and begin to timing when the input
signal [79.CB_Healthy] is
7 79.t_CBReady 0~600 5.000 s 0.001
de-energized and if it is not
energized within this time delay, AR
will be blocked.
Maximum wait time for synchronism
8 79.t_Wait_Chk 0~600 10.000 s 0.001
check
The purpose of VT circuit supervision is to detect whether VT circuit is normal. Some protection
functions should be disabled when VT circuit fails.
VT circuit failure can be caused by many reasons, such as fuse blown due to short-circuit fault,
poor contact of VT circuit, VT maintenance and so on. The device can detect them and issue an
alarm signal to block relevant protection functions. However, the alarm of VT circuit failure should
not be issued when the following cases happen.
2. Only current protection functions are enabled and VT is not connected to the device.
VT circuit supervision can detect failure of single-phase, two-phase and three-phase on protection
VT. Under normal condition, the device continuously supervises input voltage from VT, VT circuit
failure signal will be activated if residual voltage exceeds the threshold value or positive-sequence 3
voltage is lower than the threshold value. If the device is under pickup state due to system fault or
other abnormality, VT circuit supervision will be disabled.
Under normal conditions, the device detects residual voltage greater than the setting
[VTS.3U0_Set] to determine single-phase or two-phase VT circuit failure, and detect three times
positive-sequence voltage less than the setting [VTS.U1_Set] to determine three-phase VT circuit
failure. Upon detecting abnormality on VT circuit, an alarm will comes up after a time delay of
[VTS.t_DPU] and drop off with a time delay of [VTS.t_DDO] after VT circuit restored to normal.
VT (secondary circuit) MCB auxiliary contact as a binary input can be connected to the binary
input circuit of the device. If MCB is open (i.e. [VTS.MCB_VT] is energized), the device will
consider the VT circuit is not in a good condition and issues an alarm without a time delay. If the
auxiliary contact is not connected to the device, VT circuit supervision will be issued with time
delay as mentioned in previous paragraph.
When VT is not connected into the device, the alarm will be not issued if the system setting
[En_VT] is set as "Disabled". However, the alarm is still issued if the binary input [VTS.MCB_VT]
is energized, no matter that the logic setting [En_VT] is set as “Enabled” or “Disabled”.
VTS
VTS.Enable VTS.Alm
VTS.Block VTS.InstAlm
VTS.MCB_VT
3.27.5 Logic
&
3 SIG FD.Pkp
SET 3U0>[VTS.3U0_Set]
>=1
SET U1<[VTS.U1_Set] &
>=1 If "FD.Pkp" operates, the circuit of time
SET [VTS.Opt_VT]=Bay & delay will be interrupted.
[VTS.t_DPU] [VTS.t_DDO]
SIG 52b (Three phases) >=1
&
SIG Ip > 0.04In
>=1
BI Prot.BI_En_VT >=1
VTS.Alm
EN [En_VT]
EN [VTS.En]
&
SIG VTS.Enable
SIG VTS.Block
If fault detector element operates or automatic reclosing cycle is in progress, and VT circuit failure
signal have been detected, then the VT circuit failure signal will be maintained, only when the fault
detector element and automatic reclosing element are all drop-off, VT circuit supervision will
return to normal operation.
3.27.6 Settings
Access path:
CTS
CTS.Enable CTS.On
CTS.Block CTS.Blocked
CTS.Valid
CTS.Alm
3.28.4 Logics
EN [CTS.En] &
CTS.On
SIG CTS.Enable
&
SIG CTS.Block >=1 CTS.Blocked
SIG Fail_Device
&
CTS.Valid
SIG IA<0.06In
>=1
SIG IB<0.06In
SIG IC<0.06In
3.28.5 Settings
Access path:
Default
No. Settings Range Unit Step Remark
value
The calculated residual
1 CTS.3I0_Set 0.00~200.00 0.1 A 0.001 current setting of CT circuit
supervision function.
The calculated residual
2 CTS.3U0_Set 0.00~200.00 30 V 0.001 voltage setting of CT circuit
supervision function.
Delay pick-up time setting
3 CTS.t_DPU 0.000~100.000 1.25 s 0.001
for CT circuit failure
Delay drop-off time setting
4 CTS.t_DPO 0.000~100.000 10 s 0.001
for CT circuit failure
Disabled Enabling/disabling CT circuit
5 CTS.En Disabled - -
Enabled supervision function.
4 Control Functions
Table of Contents
List of Figures
Figure 4.1-1 Logic diagram of switchgear control ................................................................... 4-2
Figure 4.2-1 Relationship between reference and synchronous voltages ........................... 4-9
Figure 4.3-2 Voltage connection for one-and-half breakers arrangement .......................... 4-17
Figure 4.3-3 Voltage selection for double busbar arrangement ........................................... 4-19
Figure 4.3-4 Voltage selection for 3/2 breakers arrangement (closing a bus CB) ............. 4-20
Figure 4.3-5 Voltage selection for 3/2 breakers arrangement (closing the tie CB) ............ 4-21
List of Tables
4
Table 4.1-1 Remote/Local control mode switch logic.............................................................. 4-3
Table 4.2-1 Input signals of manual closing synchronism check ........................................ 4-10
Table 4.2-2 Output signals of manual closing synchronism check ..................................... 4-11
A control command can realize various control signals such as the CB/DS/ES opening/closing. In
order to ensure the reliability of the control output, a locking circuit is added to each control object.
The operation is strictly in accordance with the selection, check and execution steps, to ensure 4
that the control operation can be safely and reliably implemented. In addition, the device has a
hardware self-checking and blocking function to prevent hardware damage from mal-operation
output.
When the device is in the remote-control mode, the control command may be sent via the IEC
60870-5-103 or IEC 61850 protocol; when it is in the local control mode, the local operation may
be performed on the device LCD or panel handle.
3. If the selection is successful, the protocol module sends an execution command, otherwise it
sends a cancel command;
When the device is in the maintenance status, it can still respond to local control commands.
The switchgear control function can cooperate with functions such as synchronism check and
interlocking criteria calculation to complete the output of the corresponding operation command. It
can realize the normal control output in one bay and the interlocking and programmable logic
configuration between bays.
Module Description
CSWI Control of circuit breaker (CB), disconnector switch (DS) or earthing switch (ES)
RMTLOC Remote or local control mode
XCBR Synthesis of CB position, three-phase or phase separated
Module Description
XSWI Synthesis of DS/ES position
SXCBR/SCSWI Trip statistics of CB/DS/ES
RSYN Synchronism check for CB closing
CILO Interlocking logic for CB/DS/ES control
MCSWI Manual control of CB/DS/ES
The initiation of a control command may be sent to the device by the SCADA or the NCC through
protocol IEC 60870-5-103 or IEC 61850. It may also be the operation of the device LCD or the
manual triggering through configured signal. The command is sent by the CPU to the control
module for processing, and a control record is made on the CPU module according to the control
result.
4
SCADA/NCC IEC 60870-5-103
CPU
CSWI BO
IEC 61850
Control
Record
Local LCD
BI contact
Since the source of a control command may be SAS or NCC, or may be triggered by the device
LCD or terminal contact, it is necessary to provide a remote/local control mode switch function.
The remote/local control mode switch function determines whether the device is in the remote or
the local control permission state through the configuration of terminal contact, function key, or
binary signal. Each control object provides a remote/local input, and the control module
determines the current control authority to be remote or local according to the input value. By
default, if the input is not configured, any control operation is blocked.
A double point status (DPS), which usually indicates switchgear status, can be derived from 2
ordinary binary inputs. The signification of a DPS is shown in the following table. For switchgear
4
status, only the 2 statuses "01" and "10" indicating respectively the positions opening and closing
are valid. The other 2 statuses "00" and "11", i.e. intermediate or bad status, will cause the alarm
"DPS.Alm".
The unit also supports the DPS synthesis through switchgear opening and closing positions after
jittering processing. The synthetic DPS contains original SOE timestamp. The CB control function
supports phase-segregated position inputs and can synthesize these inputs into general position.
In accordance with the control object, the DPS synthesis function is divided into 2 modules: XCBR
and XSWI. The XCBR is mainly used for CB position synthesis, including phase-segregated
positions, while the XSWI is used DS or ES position synthesis.
The trip statistics function takes the opening position as input count the trip times. For CB, this
device supports general trip statistics. The tripping statistics function is triggered by DPS change.
The statistics result is stored in non-volatile memory for power-off holding.
Use the clear command from the menu in local LCD or customized binary signal to reset the trip
statistics.
4.1.2.4 Interlocking
The interlocking function will influence the control operation output. When the function is enabled,
the device determines whether the control operation is permitted based on the interlocking logic
result. Each control object is equipped with an independent interlocking logic which supports
unlocking operation through a binary signal.
The interlocking function is very important for the control operation of switchgears. During the
operation of primary equipment, the positions of the relevant equipment must be correct for
operation permission. For remote control, i.e. command from SAS or NCC, this device could
judge the interlocking logic depending on the message within the command; for local control
through device LCD or terminal contact, please use the corresponding logic setting to
enable/disable the interlocking function.
The switchgear control function supports manual control function that can be configured with a
terminal contact or binary signal to trigger the control operation.
The manual control function supports the control input configuration of selection and open/close.
When the control object selection input is configured, the signal "1" indicates that the current
control object has to be selected before a control operation; if the control object selection input is
not configured, the control command can be directly issued without judgment of selection.
For applications such as signal reset and function enable/disable, the control mode is generally
direct control, i.e. execution without selection before, direct control with normal security in IEC
61850.
The direct control function provides remote/local switch and interlocking configurations. The
control command is usually issued directly by the SAS. It also supports the command triggered by
binary signal.
CSWI:XCBR CSWI:XSWI
in_Remote in_Remote
in_Local in_Local
in_Pos_NO
in_Pos_NO
in_Pos_NC
in_Pos_NC
in_N_Trp
in_N_Trp
in_Rsyn
in_EnaOpn in_EnaOpn
in_EnaCls in_EnaCls
in_CILO_Bypass in_CILO_Bypass
in_Manual_Sel in_Manual_Sel
in_Manual_Opn
in_Manual_Opn
in_Manual_Cls
in_Manual_Cls
4.1.5 Logics
SIG DPS_A = ON
&
DPS = ON
SIG DPS_B = ON
SIG DPS_C = ON
SET [CSWI**.DPS.En_Alm]
≥1 CSWI** interlocking
Local command from device function activated
SIG
LCD with "InterlockChk"
≥1
&
Contact triggered manual
SIG
opening/closing operation
EN [CSWI**.En_Opn_Blk] ≥1
EN [CSWI**.En_Cls_Blk]
SIG in_Manual_Opn=1
≥1
SIG in_Manual_Opn=1
& Opn_Exec_Man
SIG Opn_Enabled =1
SIG in_Manual_Cls=1
≥1
&
4
SIG in_Manual_Sel =1
SIG in_Manual_Cls=1
& Cls_Exec_Man
SIG Cls_Enabled =1
4.1.6 Settings
Table 4.1-3 Settings of control function
When two asynchronous systems are connected together, due to phase difference between the
two systems, larger impact will be led to the system during closing. Thus, closing operation is
applied with the synchronism check to avoid this situation and maintain the system stability. The
synchronism check includes synchro-check and dead charge check.
The comparative relationship between the reference voltage and the synchronization voltage for
synchro-check is as follow. Furthermore, the measured three-phase voltages for synchro-check
should not exceed the overvoltage threshold [25.U_OV] or lag the undervoltage threshold
[25.U_UV].
U_Ref
U_Syn
This figure shows the characteristics of synchro-check element used for CB closing if both
reference and synchronous sides are live. The element operates if the voltage difference,
frequency difference, slip frequency difference and phase angle difference are all within their 4
setting ranges.
The difference between the reference voltage and the synchronization voltage is checked by
the following equation
The frequency difference between the reference side and the synchronization side is
checked by the following equation
|f(U_Ref)-f(U_Syn)| ≤ [25.f_Diff]
df/dt ≤ [25.df/dt]
The phase difference between the reference voltage and the synchronization voltage is
checked by the following equation
∆δ ≤ [25.phi_Diff]
The dead charge check mode checks only the synchro-check voltage. Several dead charge check
modes are supported in using the setting [25.Opt_Mode_DdChk]. The device compares the
reference side and the synchronous side voltages at both sides of circuit breaker with the settings
[25.U_LvChk] and [25.U_DdChk]. When the voltage is higher than [25.U_LvChk], the
corresponding side is regarded as live. When the voltage is lower than [25.U_DdChk], the
corresponding side is regarded as dead.
The synchronism check function is suitable for several applications. According to different
applications, user needs to configure different voltage input channel. For both the reference side
and the synchronous side, the voltage input channel may be single phase or three-phase.
While configuring through the PCS-Studio software, user can configure three phase or single
phase voltage channel for reference and synchronization inputs.
In the meantime, the voltage selection logic can be adopted for the synchronism check input
channel, please refer to the following section.
in_ref_A
in_ref_B
in_ref_C
in_syn_A
in_syn_B
in_syn_C
in_25_Blk
in_Dd_Blk
in_Lv_Blk
in_SYN_Blk
in_25_Bypass
in_vol_chk
in_syn_chk
4.2.4 Logics
4 SET
SET
f_Syn ≤ [25.f_UV]
f_Syn ≥ [25.f_OV]
SIG 25.SynChk_OK
SIG Cmd with synchro-check
SET [25.Opt_Valid Mo de] = Se tting & SynChk Success
&
EN [25.En_ Syn Ch k] ≥1
≥1
SET [25.Opt_Valid Mo de] = Config
&
SIG in_S yn _Ch k
&
SIG Cmd without synchro-check
4.2.5 Settings
Table 4.2-3 Settings of synchronism check
4 SynLvRefDd/SynDdRefLv
AnySideDd
Threshold for voltage
17 25.U_DdChk 17.32 0~100 0.01 V
dead check
Threshold for voltage
18 25.U_LvChk 34.64 0~100 0.01 V
live check
Threshold of duration
19 25.t_Reset 5 0~60 1 s
for synchro-check
Circuit breaker closing
time. It is the time
from receiving closing
20 25.t_Close_CB 20 0~2000 1 ms
command pulse till the
CB is completely
closed.
25.Opt_Mode_DdChk
1 SynDdRefDd Dead check for both the reference and the synchronization sides
2 SynLvRefDd Live check for synchronization side and dead check for reference side
3 SynDdRefLv Dead check for synchronization side and live check for reference side
6 SynLvRefDd/SynDdRefLv Option 2 or 3
7 AnySideDd Option 1, 2 or 3
For double busbars, selection of appropriate voltage signals from Bus1 and Bus2 for
synchronizing are required. Line VT signal is taken as reference to check synchronizing with
the voltage after voltage selection function. Selection approach is as follows.
Bus2
Bus1
DS1 DS2
4
UB1
UB2
DS1.DPS
CB
DS2.DPS
Ua
UL1 Ub
Line
Uc
For double busbars, three-phases voltages from Bus1 VT and Bus2 VT via switching is used
for protection calculations or measurements and meanwhile used as reference side of
synchronism check. Single-phase voltage from line VT is used as synchronizing side of
synchronism check. Selection approach is as follows.
Bus2
Bus1
DS1 DS2
Ua
UB1 Ub
Uc
Ua
UB2 Ub
Uc
CB
DS1.DPS
DS2.DPS
4
UL1
Line
Bus1
UB1
Bus1_CB.DPS Bus1_CB
Line 1
Ua
UL1 Ub
Uc DS1
DS1.DPS
Tie_CB.DPS Tie_CB
Line 2
UL2 4
DS2.DPS
DS2
Bus2_CB.DPS Bus2_CB
UB2
Bus2
VolSwitch
in_UB1_A_Chn Ref_Chn_A
in_UB1_B_Chn Ref_Chn_B
in_UB1_C_Chn Ref_Chn_C
in_UB2_A_Chn Syn_Chn_A
Syn_Chn_B
in_UB2_B_Chn
Syn_Chn_C
in_UB2_C_Chn
in_UL1_A_Chn
in_UL1_B_Chn
in_UL1_C_Chn
in_UL2_A_Chn
4 in_UL2_B_Chn
in_UL2_C_Chn
in_Bus1_CB
in_Tie_CB
in_Bus2_CB
in_DS1
in_DS2
&
Alm_Invalid_Sel
UB1 U_Syn
UB2
SIG DS1.DPS=ON
SIG DS1.DPS=OFF
SIG Bus1_CB.DPS=ON
SIG DS2.DPS=ON
SIG DS2.DPS=OFF
SIG Bus2_CB.DPS=ON
UL1_Sel
&
UL2_Sel
&
UB2_Sel
4 &
Alm_Invalid_Sel
UL1 U_Ref
UL2
UB2
UB1 U_Syn
Figure 4.3-5 Voltage selection for 3/2 breakers arrangement (closing a bus CB)
UL1 Uref
UB1
UL2 Usyn
4
UB2
&
>=1
& Alm_Invalid_Sel
Figure 4.3-6 Voltage selection for 3/2 breakers arrangement (closing the tie CB)
4.3.5 Settings
Table 4.3-3 Settings of voltage selection
5 Measurement
Table of Contents
10
11
f
Neu.I_Pri
Frequency of protection voltage
A
5
12 SEF.I_Pri The sensitive residual current measured from the high-precision CT A
1 Ang (Ua-Ia) Phase angle between phase-A voltage and phase-A current °
2 Ang (Ub-Ib) Phase angle between phase-B voltage and phase-B current °
3 Ang (Uc-Ic) Phase angle between phase-C voltage and phase-C current °
4 Ang (Ua-Ub) Phase angle between phase-A voltage and phase-B voltage °
5 Ang (Ub-Uc) Phase angle between phase-B voltage and phase-C voltage °
6 Ang (Uc-Ua) Phase angle between phase-C voltage and phase-A voltage °
7 Ang (Ia-Ib) Phase angle between phase-A current and phase-B current °
8 Ang (Ib-Ic) Phase angle between phase-B current and phase-C current °
9 Ang (Ic-Ia) Phase angle between phase-C current and phase-A current °
11 Ang (Ub) Phase angle between phase-B voltage and the referenced angle °
12 Ang (Uc) Phase angle between phase-C voltage and the referenced angle °
13 Ang (Ia) Phase angle between phase-A current and the referenced angle °
14 Ang (Ib) Phase angle between phase-B current and the referenced angle °
15 Ang (Ic) Phase angle between phase-C current and the referenced angle °
Phase angle between the external measured residual current and the
16 Neu.Ang (I) °
referenced angle
Phase angle between the external measured residual current and the
17 SEF.Ang (I) °
referenced angle
19 60/50.Ang (I) Phase angle between the unbalance current and the referenced angle °
Phase angle between the external measured residual voltage and the
20 Delt.Ang (U) °
referenced angle
5 21 Syn.Ang (U)
Phase angle between the synchronism check used voltage and the
referenced angle
°
22 60/59.Ang (U) Phase angle between the unbalance voltage and the referenced angle °
1 Pa_Pri
3 Pc_Pri
4 Qa_Pri
6 Qc_Pri
8 Sb_Pri
9 Sc_Pri
13 Cosa
15 Cosc
5.1.5 Harmonics
1 U_Hm01_Pri kV
2 U_Hm02_Pri kV
3 U_Hm03_Pri kV 5
4 U_Hm04_Pri kV
5 U_Hm05_Pri kV
6 U_Hm06_Pri kV
7 U_Hm07_Pri kV
9 U_Hm09_Pri kV
10 U_Hm10_Pri kV
11 U_Hm11_Pri kV
12 U_Hm12_Pri kV
13 U_Hm13_Pri kV
14 U_Hm14_Pri kV
15 U_Hm15_Pri kV
1 Ia_Sec Phase-A current (summation current for double circuit breakers mode) A
2 Ib_Sec Phase-B current (summation current for double circuit breakers mode) A
3 Ic_Sec Phase-C current (summation current for double circuit breakers mode) A
1 Ang (Ua-Ia) Phase angle between phase-A voltage and phase-A current °
2 Ang (Ub-Ib) Phase angle between phase-B voltage and phase-B current °
3 Ang (Uc-Ic) Phase angle between phase-C voltage and phase-C current °
4 Ang (Ua-Ub) Phase angle between phase-A voltage and phase-B voltage °
5 Ang (Ub-Uc) Phase angle between phase-B voltage and phase-C voltage °
6 Ang (Uc-Ua) Phase angle between phase-C voltage and phase-A voltage °
7 Ang (Ia-Ib) Phase angle between phase-A current and phase-B current °
8 Ang (Ib-Ic) Phase angle between phase-B current and phase-C current °
9 Ang (Ic-Ia) Phase angle between phase-C current and phase-A current °
11 Ang (Ub) Phase angle between phase-B voltage and the referenced angle °
12 Ang (Uc) Phase angle between phase-C voltage and the referenced angle °
13 Ang (Ia) Phase angle between phase-A current and the referenced angle °
14 Ang (Ib) Phase angle between phase-B current and the referenced angle °
15 Ang (Ic) Phase angle between phase-C current and the referenced angle °
Phase angle between the external measured residual current and the
16 Neu.Ang (I) °
referenced angle
17 SEF.Ang (I) Phase angle between the external measured residual current and the °
referenced angle
19 60/50.Ang (I) Phase angle between the unbalance current and the referenced angle °
Phase angle between the external measured residual voltage and the
20 Delt.Ang (U) °
referenced angle
Phase angle between the synchronism check used voltage and the
21 Syn.Ang (U) °
referenced angle
22 60/59.Ang (U) Phase angle between the unbalance voltage and the referenced angle °
4
3I0_Sec
U1_Sec
Residual current
V
5
5 U2_Sec The negative-sequence voltage V
1 Pa_Sec
3 Pc_Sec
4 Qa_Sec
6 Qc_Sec
7 Sa_Sec
9 Sc_Sec
13 Cosa
15 Cosc
5.2.5 Harmonics
1 U_Hm01_Sec V
2 U_Hm02_Sec V
3 U_Hm03_Sec V
4 U_Hm04_Sec V
5 U_Hm05_Sec V
6 U_Hm06_Sec V
7 U_Hm07_Sec V
9 U_Hm09_Sec V
10 U_Hm10_Sec V
5 11 U_Hm11_Sec V
12 U_Hm12_Sec V
13 U_Hm13_Sec V
14 U_Hm14_Sec V
15 U_Hm15_Sec V
5.3.1 Synchrocheck
U a 3 U nn
4 Ua_Devn Deviation of phase A voltage %
U nn
U b 3 U nn
5 Ub_Devn Deviation of phase B voltage %
U nn
U c 3 U nn
6 Uc_Devn Deviation of phase C voltage %
U nn
15
10 THD_Ua U
i 2
2
Hm _ i %
THD
U Hm _1
6 Supervision
Table of Contents
List of Figures
Figure 6.4-1 Principle of the TCS function with two binary inputs ........................................ 6-4
List of Tables
6.1 Overview
Protection system is in quiescent state under normal conditions, and it is required to respond
promptly for faults occurred on power system. When the device is in energizing process before
the LED “HEALTHY” is on, the device need to be checked to ensure no abnormality. Therefore,
the automatic supervision function, which checks the health of the protection system when startup
and during normal operation, plays an important role.
The numerical relay based on the microprocessor operations is suitable for implementing this
automatic supervision function of the protection system.
In case a defect is detected during initialization when DC power supply is provided to the device,
the device will be blocked with indication and alarm of relay out of service. It is suggested a trial
recovery of the device by re-energization. Please contact supplier if the device is still failure.
When a failure is detected by the automatic supervision, it is followed by a LCD message, LED
indication and alarm contact outputs. The failure alarm is also recorded in event recording report
and can be printed if required.
All hardware has real-time monitoring functions, such as CPU module monitoring, communication
interface status monitoring, power supply status monitoring. 6
The monitoring function of CPU module also includes processor self-check, memory self-check
and so on. The processor self-check is checked by designing execution instructions and data
operations. Check whether the processor can execute all instructions correctly, and whether it can
correctly calculate complex data operations to determine whether it works normally. For
peripherals, it can monitor the status of the interface module, check the input and output data,
send the communication interface and receive self-loop detection. Memory self-check is used to
detect unexpected memory errors in the running process. It can effectively prevent program logic
abnormality caused by memory errors.
The status monitoring of communication interface also includes Ethernet communication interface
monitoring and differential channel communication interface monitoring. By accessing the status
register of the communication interface, the state of the corresponding interface is obtained, such
as the state of connection, the number of sending frames, the number of frames received, and the
number of wrong frames. According to the statistics of the acquired interface state, it is judged
whether the interface work is abnormal.
The hardware supervision also includes the power supply status monitoring. The voltage
monitoring chip is used by all the power supplies. The reset voltage threshold is preset to the reset
monitoring circuit. When the power supply is abnormal, the voltage monitoring chip will output the
reset signal to control CPU to be in the reset state and avoid the wrong operation.
In the process of operation, the safety allowance should always be kept and no overload
phenomenon is allowed. When the user configures logic components with PCS-Studio, the
PCS-Studio automatically calculates the time required for the theoretical execution of the
configured components. When the security limit is exceeded, the PCS-Studio will indicate that the
configuration error is not allowed to download the current configuration to the device.
During the operation of the device, there is a lot of data exchange between modules. The number
of data exchanges is related to the number of logical components configured by the user. When
the configuration is too large to cause the number of data exchange to exceed the upper limit
supported by the device, the PCS-Studio prompts the configuration error.
The initialization of the device depends on the configuration files of each module. The user
configured logical components will eventually be embodied in the configuration file, limited to the
hardware memory space. When the configuration file size is more than the upper limit, the
PCS-Studio prompts the configuration error.
The DDR3 memory chip has the function of ECC (Error Checking and Correcting) to eliminate
unexpected changes in memory caused by electromagnetic interference. The chip memory has
parity function. When an error occurs, the system can detect anomalies immediately, and
eliminate the logic abnormity caused by memory errors.
In addition to the above hardware memory reliability measures, the device software is also
constantly checking the memory during operation, including code, constant data, and so on. Once
the error detection, the system will automatically restart the restore operation. If they detect the
error immediately after the restart, it may be the result of a permanent fault locking device
hardware, only at the moment and not restart.
The reliability of the device is largely determined by the reliability of the export drive. By reading
the driving state of the binary output relay, the alarm signal will be generated and the device is
immediately blocked to prevent the relay from mal-operation when the device is not given a
tripping order and the binary output relay driver is detected in the effective state.
The CPU chip needs to be able to ensure long-term stability under the permissible working
temperature of the specification. Therefore, it is necessary to monitor the working temperature
monitored by CPU.
The device is blocked when the actual hardware configuration is not consistent with the hardware
configuration file. Compared with pre configured modules, this device will be blocked if more
module is inserted, fewer module is inserted, and wrong modules is inserted.
1. Each hardware module configuration check code needs to be consistent with CPU module.
The device CPU module stores the configuration check codes of other modules. In initialization
procedure, it checks whether the configuration check code of each module is consistent with the
stored code in CPU module, and if it is not consistent, this device is blocked.
2. The hardware modules and process interface versions need to be consistent with the CPU
module.
If the system is incompatible with the upgrade, it will upgrade the internal interface version. At this
moment, each hardware module and process will be upgraded synchronously, otherwise the
version of the interface will be inconsistent.
The configuration text formed by the device calibration visualization project includes checking
whether the check code is wrong or not. 6
4. Whether any setting is over the range, whether it needs to confirm the settings.
If the setting exceeds the configuration range, the device is blocked; if some settings are added, it
is necessary to confirm the new values through the LCD.
In the operation procedure, the CPU module sends a time synchronization command to other
module, each module repeats heartbeat message to the CPU module, if it does not respond or the
heartbeat is abnormal, then this device is blocked.
2. Check whether the settings of other modules are consistent with the CPU module.
The actual values of all the settings in the CPU module are initialized to send to the corresponding
slave modules. In the process of operation, the setting values stored in the CPU module and the
setting values of other modules will be checked one by one. If they are not consistent, this device
will issue the alarm signal "Fail_Settings".
The sampling circuit of this device is designed as dual-design scheme. Each analog sampling
channel is sampled by two groups of ADC. The sampling data is self checking and inter checking
in real time. If any sampling circuit is abnormal, the device reports the alarm signal [Alm_Sample],
and the protection function related to the sampling channel is disabled at the same time. When
the sampling circuit returns to normal state, the related protection is not blocked after 10s.
The secondary circuit supervision function includes current transformer supervision (CTS),
voltage transformer supervision (VTS) and tripping/closing circuit supervision.
CTS function
The purpose of the CTS function is to detect whether the current transformer circuit is failed. In
some cases, if the CT is failed (broken-conductor, short-circuit), related protective element should
be blocked for preventing this device from mal-operation.
See further details about the CTS function, please refer Chapter 3.
VTS function
The purpose of the VTS function is to detect whether the VT analog input is normal. Because
some function, such as synchronism check, will be influenced by a voltage input failure.
The VT circuit failure can be caused by many reasons, such as fuse blown due to short-circuit
6 fault, poor contact of VT circuit, VT maintenance and so on. The device can detect the failure, and
then issue an alarm signal and block relevant function.
See further details about the VTS function, please refer Chapter 3.
The tripping circuit supervision function can be realized by program the logic function of this
device through the PCS-Studio according to the practical application experience of the user. In
this manual, a scheme which uses two independent binary inputs to supervise the tripping circuit
is recommended.
The following figure show the recommended scheme for tripping circuit supervision and the logic
diagram of the TCS function.
DC+ DC-
52a TC
BTJ
52b
Figure 6.4-1 Principle of the TCS function with two binary inputs
Where:
[BI_02] is the binary input which is serial connected with the “52b” contact.
The well-designed debounce technique is adopted in this device, and the state change of binary
input within “Debounce time” will be ignored. As shown in Figure 6.5-1.
Binary input
state
0
6
Debounce time of Debounce time of
delayed pickup delayed dropout
Time
All binary inputs should setup necessary debounce time to prevent the device from undesired
operation due to transient interference or mixed connection of AC system and DC system. When
the duration of binary input is less than the debounce time, the state of the binary input will be
ignored. When the duration of binary input is greater than the debounce time, the state of the
binary input will be validated and wrote into SOE.
In order to meet flexible configurable requirement for different project field, all binary inputs
provided by the device are configurable. Through the configuration tool, this device provides two
parameters to setup debounce time of delayed pickup and dropout based on specific binary
signal.
1. Type 1
This type of binary inputs includes enable/disable of protection functions, AR mode selection,
“BI_RstTarg”, “BI_Maintenance”, disconnector position, settings group switch, open and
close command of circuit breaker and disconnector, enable/disable of auxiliary functions (for
example, manually trigger recording). They are on the premise of reliability, and the
debounce time of delayed pickup and delayed dropout is recommended to set as 100ms at
least.
6 2. Type 2
This type of binary inputs include breaker failure initiating binary inputs,
“CSWIxx.Cmd_LocCtrl”, “CSWIxx.Cmd_RmtCtrl” and so on.
Debounce time
The debounce time of delayed pickup and delayed dropout is recommended to set as
15ms, in order to prevent binary signals from mal-operation due to mixed connection of
AC system and DC system.
The debounce time of delayed pickup and delayed dropout is recommended to set as
(-t1+ t2+Time delay)≥15ms, in order to prevent binary signals from mal-operation due to
mixed connection of AC system and DC system. Where, “t1” is the debounce time of
delayed pickup, and “t2” is the debounce time of delayed dropout.
3. Type 3
This type of binary inputs is usually used as auxiliary input condition, and the debounce time
of delayed pickup and delayed dropout is recommended to set as 5ms.
When users have their own reasonable setting principles, they can set the
debounce time related settings according to their own setting principles.
This device can handle repetitive signal or so-called jitter via binary input module with the following
settings:
[Num_Blk_Jitter] N, times threshold to block binary input status change due to jitter
[Blk_Window_Jitter] T', blocking window of binary input status change due to jitter
For a binary input voltage variation, if the jitter processing function is enabled, its handling
principle is:
1. During the T,
If the actual jitter times < N, the block will not be initiated and the status change of this
6
binary input will be considered.
If the actual jitter times ≥ N, the T' is initiated, and the status change of binary input will
be ignored during the T'.
If the actual jitter times < N', the block window will expire. The final status of this binary
input will be compared to the original one before T', so as to determine whether there is a
change or not.
If the actual jitter times ≥ N', the T' will be initiated again immediately (i.e. restart the
timer), and the status change of binary input will be ignored during the next T'.
Debounce time
(rising edge)
n=N
initiate jitter block
Signal after
debounce & jitter
n=N processing
n=5<N=7 Prolong blocking
window
T
T t7 t8
t11
t5 t6
T T T
t1 t2 t3 t4 t9 t10 t
6 ②Green line Blocking signal of binary input status change due to jitter
③Blue line Binary input status after debounce and jitter processing
3. T = t2 - t1
n=5<N
No blocking, ② stays at 0 and ③ is tracing the voltage variation to create SOE events.
4. T = t4 - t3, at t5
n=7=N
Jitter blocking, no more SOE event, ② changes its status to 1 and ③ stops the tracing.
5. T' = t6 - t5
At t7, n = 5 =N', the processing prolongs the blocking immediately due to jitter
Jitter blocking continues, no SOE event, ② stays at 1 and ③ keeps its status.
6. T'= t8 - t7
At t9, n = 5 =N', the processing prolongs the blocking immediately due to jitter.
Jitter blocking continues, no SOE event, ② stays at 1 and ③ keeps its status.
7. T'= t10 - t9
n = 2 < N'
At t10, jitter unblocking, ② changes its status to 0 and ③ keeps its status.
8. At t11
The tripping counter statistics function supports statistics of the tripping operation, such as circuit
breakers, disconnectors and so on. For phase separation circuit breaker, when the position of
phase A, B, and C is detected from close state to open state, the total position tripping counter is
added, and the tripping counter is added once when the position of the disconnector is detected
from close state to open state.
In addition, the statistics of the number of state change of circuit breakers and disconnectors are
also provided. The state change counter will add one when the position is detected from close
state to open state or from open state to close state.
Hardware circuit and operation status of this device are self-supervised continuously. If any
abnormal condition is detected, information or report will be displayed and a corresponding alarm
will be issued.
A minor abnormality may block a certain number of protections functions while the other functions
can still work. However, if severe hardware failure or abnormality, such as PWR module failure,
DC converter failure and so on, are detected, all protection functions will be blocked and the LED
“HEALTHY” will be extinguished and blocking output contacts “BO_Fail” will be given. The
protective device then cannot work normally and maintenance is required to eliminate the failure.
All the alarm signals and the corresponding handling suggestions are listed below.
If the device is blocked or alarm signal is sent during operation, please do find out its reason with
the help of self-diagnostic record. If the reason cannot be found at site, please notify the factory
NR. Please do not simply press button “TARGET RESET” on the protection panel or re-energize
on the device.
No
Item Description Handling suggestion
.
Fail Signals (Device will be blocked)
The signal is issued with other
This signal will be issued if any fail
specific fail signals, and please
1 Fail_Device signal picks up and it will drop off when
refer to the handling suggestion
all fail signals drop off.
other specific alarm signals.
6 This signal will be issued if any
Please inform the manufacture
2 Fail_DeviceInit hardware or software failure is detected
or the agent for repair.
in the device initialization process.
1. Go to the menu
“Information→Borad Info”,
check the abnormality
This signal will be issued due to information.
mismatch between the configuration of 2. For the abnormality board, if
3 Fail_BoardConfig
plug-in modules and the designing the board is not used, then
drawing of an applied-specific project. remove, and if the board is
used, then check whether the
board is installed properly and
work normally.
Check whether the CCD
process level configuration file
This signal will be issued if the CCD
of this device is exist and
process level configure file is parsed
4 Fail_ProcLevelConfig whether the file content is
wrongly or the type in the file is
correct. May need to download
inconsistent with the actual device.
and update the correct CCD
process level configuration file.
After configuration file is updated, Please check the settings
5 Fail_SettingItem_Chgd
settings of the file and settings saved mentioned in the prompt
No
Item Description Handling suggestion
.
on the device are not matched. This message on the LCD, and go to
signal will be issued instantaneously the menu “Settings” and select
and will be latched unless the “Confirm_Settings” item to
recommended handling suggestion is confirm settings. Then, the
adopted. device will restore to normal
operation stage.
Please reset setting values
The value of any setting is out of scope. according to the range
This signal will be issued described in the instruction
6 Fail_Setting_OvRange instantaneously and will be latched manual, then re-power or reboot
unless the recommended handling the device and the device will
suggestion is adopted. restore to normal operation
state.
The alarm signal will be issued
instantaneously when an error is found
7 Fail_Memory
during checking memory data, and
usually, it will automatically drop out. Please inform the manufacture
The board fails to register the variable, or the agent for repair.
because of abnormal board, insufficient
8 Fail_BoardRegister
memory space, or incorrect
configuration. 6
The configuration process does not run
9 Fail_ProcessConfig
properly. View the menu "Initialization
The board fails to be initialized, Error" to check the detailed
because of abnormal board, insufficient reason, and send the reason to
10 Fail_BoardInit
memory space, or incorrect the manufacture or the agent.
configuration.
Error is found during checking settings.
It means inappropriate or incorrect
settings for some application scenarios
are checked.
11 Fail_Settings Please check the settings
This signal will be issued
instantaneously and will be latched
unless the recommended handling
suggestion is adopted.
Sampling error, it means that the DC 1. Please make the device out
component contained in the sample is of service.
too large or there is some problem 2. Then check if the analog input
12 Fail_Sample during the mutual-check of double AD modules and wiring connectors
sample value. connected to those modules are
This signal will be issued installed at the position.
instantaneously and will be latched 3. Re-power the device, if it is
No
Item Description Handling suggestion
.
unless the recommended handling still invalid, please replace the
suggestion is adopted. CPU module.
Alarm Signals (Device will not be blocked)
The signal is issued with other
The device is abnormal. This signal will
specific alarm signals, and
be issued if any alarm signal picks up
13 Alm_Device please refer to the handling
and it will drop off when all alarm
suggestion other specific alarm
signals drop off.
signals.
This signal will be issued if any
hardware or software configuration Please inform the manufacture
14 Alm_DeviceInit
wrong is detected in the device or the agent to deal with it.
initialization process.
Users may pay no attention to
the alarm signal in the project
commissioning stage, but it is
needed to download the latest
package file (including correct
The error is found during checking the version checksum file) provided
version of software downloaded to the by R&D engineer to make the
15 Alm_Version device. This signal will be issued alarm signal disappear. Then
6 instantaneously and will drop off users get the correct software
instantaneously. version. It is not allowed that the
alarm signal is issued on the
device already has been put into
service. The devices having
being put into service so that
the alarm signal disappears.
Alarm signal indicating that the
equipment is in maintenance state (the Check the binary input
16 Alm_Maintenance
binary input [BI_Maintenance] is [BI_Maintenance].
energized.
The device is in the communication test No special treatment is needed,
mode. This signal will be issued and disable the communication
17 Alm_CommTest
instantaneously and will drop off test function after the completion
instantaneously. of the test.
Management procedure will upload and
check the parameters and settings of
Put the protective device out of
each protection plug-in module
18 Alm_Settings_MON service at once. Inform the
regularly, if the parameters and settings
factory or agency to maintain it.
are inconsistent, the alarm signal will be
issued.
19 Alm_BI_SettingGrp The active group set by settings in Please check the value of
No
Item Description Handling suggestion
.
device and that set by binary input are setting [Active_Grp] and binary
not matched. This signal will issued input of indicating active group,
instantaneously and will drop off and make them matched. Then
instantaneously. the “ALARM” LED will be
extinguished and the
corresponding alarm message
will disappear and the device
will restore to normal operation
state.
1. Check whether the selected
clock synchronization mode
matches the clock
synchronization source;
2. Check whether the wiring
connection between the device
and the clock synchronization
source is correct
3. Check whether the setting for
selecting clock synchronization
The time synchronization abnormality (i.e. [Opt_TimeSyn]) is set
20 Alm_TimeSyn
alarm. correctly. If there is no clock 6
synchronization, please set the
setting [Opt_TimeSyn] as ”No
TimeSyn”.
After the abnormality is
removed, the “ALARM” LED will
be extinguished and the
corresponding alarm message
will disappear and the device
will restore to normal operation
state.
The memory of CPU plug-in module is Please inform the manufacture
21 Alm_Insuf_Memory
insufficient. or the agent to deal with it.
The configuration file of IEC103 is
detected to be not correct when this file Please inform the manufacture
22 Alm_CfgFile_IEC103
is parsed in the device initialization or the agent to deal with it.
process.
CPU module detects that some module
23 Alm_Board is reset due to the abnormality during
Please inform the manufacture
the device operating.
or the agent to deal with it.
An abnormality is detected during the
24 Bx.Alm_Board
module self-check.
No
Item Description Handling suggestion
.
No sufficient NOR flash space used to
25 Alm_Insuf_NORflash
store the program in CPU module
The settings which are stored in CPU
26 Alm_Settings module are different with the settings
which are used by other modules.
Please refer to the fault
Disturbance fault recording settings are
27 Alm_Settings_DFR recording configuration related
set wrongly
contents, i.e. Section 7.4.
Check the setting of network
The network mode is inconsistent, such
mode, or upload the device log
as the setting is set as HSR mode, but
28 Alm_NetMode_Unmatched and confirm with the
the actual operation mode is PRP
manufacturer or agent whether
mode.
the network mode is supported.
The device's master process is
Please check the load of the
29 Alm_master abnormal and it is blocked for more
device.
than 1 minute.
The configuration file of DNP client 1 is
30 Alm_CfgFile_TCP1_DNP
incorrect.
The configuration file of DNP client 2 is Please contact the configuration
31 Alm_CfgFile_TCP2_DNP
incorrect. engineer to check and confirm
6 32 Alm_CfgFile_TCP3_DNP
The configuration file of DNP client 3 is the contents of DNP
incorrect. configuration file.
The configuration file of DNP client 4 is
33 Alm_CfgFile_TCP4_DNP
incorrect.
No special treatment is needed,
The device is in the binary output test and disable the binary output
34 Alm_BOTest
mode. test function after the completion
of the test.
Sampling abnormality alarm, indicating
Please check the data sampling
35 Alm_Sample that the data sampling quality is sent
quality
abnormally.
DPS abnormality signal, if the circuit
breaker position is intermediate or bad,
this alarm will be issued.
36 Breaker.DPS.Alm
This signal will pick up and drop off with
a time delay defined by
Check the corresponding DPS
[CSWI**.DPS.t_Alm].
signal
DPS abnormality signal, if the switch 0x
position is intermediate or bad, this
Switch0x.DPS.Alm
37 alarm will be issued.
(x=1~9)
This signal will pick up and drop off with
a time delay defined by
No
Item Description Handling suggestion
.
[CSWI**.DPS.t_Alm].
The initiating signal of breaker failure Check the initiating contact of
38 50BF.Alm_Init
protection is energized consistently. breaker failure protection
Please check the corresponding
CT circuit fails.
CT secondary circuit. After the
This signal will pick up with a time delay
39 CTS.Alm abnormality is eliminated, the
[CTS.t_DPU] and will drop off with a
device returns to normal
time delay [CTS.t_DDO].
operation state.
Please check the corresponding
VT circuit fails.
VT secondary circuit. After the
This signal will pick up with a time delay
40 VTS.Alm abnormality is eliminated, the
[VTS.t_DPU] and will drop off with a
device returns to normal
time delay [VTS.t_DDO].
operation state.
GOOSE alarm signals
It is an overall alarm signal and will be
issued if any of the following alarm Please check Ethernet switch of
signals is generated: GOOSE network, GOOSE
41 GAlm_Overall
“GAlm_AStorm”, “GAlm_BStorm”, configuration file and GOOSE
“GAlm_CfgFile”, “XX.GAlm_ADisc”, network.
“XX.GAlm_BDisc”, “XX.GAlm_Cfg”
Where:
7 System Functions
Table of Contents
The device supports various kinds of clock synchronization methods, including hardware clock
synchronization and software clock synchronization.
IRIG-B: IRIG-B via RS-485 differential level, TTL level or optical fiber interface
PPS: Pulse per second (PPS) via RS-485 differential level or binary input
PPM: Pulse per minute (PPM) via RS-485 differential level or binary input
The device provides a priority-based adaptive clock synchronization scheme, which means that
the device can automatically identify multiple clock synchronization sources in the same clock
synchronization mode and choose the highest priority of lock synchronization sources.
When the setting [Opt_TimeSyn] is set as "Conventional", the device can automatically identify
clock synchronization signal among IRIG-B, PPS, PPM and IEC1588. If IRIG-B, PPS, PPM and
IEC1588 exist at the same time, the device selects IRIG-B in priority. If PPS, PPM and IEC1588
exist at the same time, the device selects IEEE1588 in priority.
When the setting [Opt_TimeSyn] is set as "SAS", the device can automatically identify whether
there is valid hardware clock synchronization signal. The device selects hardware clock
synchronization signal or the combination of hardware clock synchronization signal plus software
clock synchronization signal in priority.
When the device adopts SNTP to realize clock synchronization, [IP_Server_SNTP] and
[IP_StandbyServer_SNTP] shall be set correctly.
[IP_Server_SNTP] is the address of SNTP clock synchronization server which sends SNTP timing
messages to the relay or BCU. [IP_StandbyServer_SNTP] is the address of standby SNTP clock
synchronization server.
device adopts the setting whose value is not equal to "000.000.000.000" as SNTP server address
and receives unicast SNTP synchronization message.
7.2.1 Overview
The device can provide real-time state information, including analog quantities (such primary
measurement value, secondary measurement value, metering value and so on) and status
quantities (supervision status, input status, output status and so on). By check these state
information, operators can know operation state of the protected equipment and whether the
device is healthy.
These state information can be gained via local HMI. The menu path is:
1. Analog quantities
7
MainMenu "Measurements" "Primary Values"
2. Status quantities
Using the virtual LCD tool, the corresponding content can be viewed through the same menu path
as local LCD.
Device's state information can be uploaded into clients through message communication. For
differential protocols, the state information can be gained through corresponding communication
service.
The device can print the current state information, so that the operator can observe and save the
current operation condition. The access path is:
7.3.1 Overview
The device can store the latest 1024 time-stamped disturbance records, 1024 time-stamped
binary events, 1024 time-stamped supervision events, 256 time-stamped control logs and 1024
time-stamped device logs. All the records are stored in non-volatile memory, and when the
available space is exhausted, the oldest record is automatically overwritten by the latest one.
The device is under automatic supervision all the time. If there are any failure or abnormal
condition detected, such as, chip damaged, VT circuit failure and so on, it will be logged in event
records. Supervision events include signal name, its value before and after changing, and the
time precision is up to 1ms.
When there is a binary input is energized or de-energized, i.e., its state has changed from “0” to “1”
or from “1” to “0”, it will be logged in event records. Binary events include signal name, its value
before and after changing, and the time precision is up to 1ms.
setting, etc., they will be logged in event records. Device logs include signal name, its value
before and after changing, and the time precision is up to 1ms.
When an operator executes a control command via local LCD, PCS-Studio or communication
client, it will be logged in control logs. Control logs include time stamp, controlled object, control
origination, control position, operation condition ,interlocking condition, control command and
operation result.
The device provides corresponding menus to view event recorders. The menu path is:
Using the virtual LCD tool, the corresponding content can be viewed through the same menu path
as local LCD.
Event recorders can be uploaded into clients through corresponding communication service of the 7
protocol (including IEC60870-5-103, IEC61850, DNP3.0).
The device can print event recorders, so that the operator can observe and save the current
operation condition. The access path is:
7.4.1 Overview
Fault recorder can be used to have a better understanding of the behavior of the power network
and related primary and secondary equipment during and after a disturbance. Analysis of the
recorded data provides valuable information that can be used to improve existing equipment. This
information can also be used when planning for and designing new installations.
The fault recorder is comprised of the report and the waveform, which can be triggered by pickup
signals, trip signals and configurable binary signal [BI_TrigDFR].
The fault memory of the device is automatically updated with every recording. When the fault
memory is filled completely, the oldest records are overwritten automatically. Thus, the most
recent recordings are always stored safely. The maximum number of recordings is 32.
1. Sequence number
Each operation will be recorded with a sequence number in the record and displayed on LCD
screen.
The date and time is recorded when a system fault is detected. The time resolution is 1ms.
An operating time (not including the operating time of output relays) is recorded in the record. The
time resolution is 1ms.
4. Fault information
The overall duration of a single fault recording comprises the total duration of the configurable
recording criterion, the pre-trigger time and the post-trigger time. With the fault recording
parameter, these components can be individually set. The pre-trigger waveform recorded duration
is configured via the setting [RecDur_PreTrigDFR]. The waveform recorded duration after the fault
disappears is configured via the setting [RecDur_PostFault]. The maximum post-trigger waveform
recorded duration is configured via the setting [MaxRecDur_PostTrigDFR].
4. [MaxRecDur_PostTrigDFR]
Trigger point
The pickup recording time cannot be set. It continues as long as any valid trigger condition, binary
or analog, persists (unless limited by the limit time, which is determined by the setting
[MaxRecDur_PostTrigDFR]).
The recording time begins after all activated triggers are reset. Use the setting [RecDur_PostFault]
to set this time.
Use the setting [MaxRecDur_PostTrigDFR] to set this time. If the summation of pickup recording
time and post-fault recording time is larger than maximal post-trigger recording time, the
post-trigger recording time shall be equal to the setting [MaxRecDur_PostTrigDFR].
The device provides corresponding menus to check fault recording. The menu path is:
Using the virtual LCD tool, the corresponding content can be viewed through the same menu path
as local LCD.
Fault recording can be uploaded into clients through corresponding communication service of the
protocol (including IEC60870-5-103, IEC61850, DNP3.0).
7
7.4.4.4 Access by Printer
The device can print fault recording, so that the operator can observe and save the current
operation condition. The access path is:
The device provides maintenance state, i.e., the binary input [BI_Maintenance] is energized,
which is convenient for maintenance work. For adopting conventional CT/VT, binary inputs and
binary outputs, maintenance state has no influence on protection logics. For binary inputs and
binary outputs by GOOSE connections. During device maintenance, the object will send GOOSE
message with Test quality attribute. The Test quality attribute indicates to the receiver device that
the object received via a GOOSE message was created under test conditions and not operating
conditions. If the Test quality attribute received is different with the object's Test quality attribute,
binary inputs and binary outputs by GOOSE connections will be affected based on different types
of binary inputs and binary outputs. For SV (Sampling Value) message, if the Test quality attribute
received is different with the object's Test quality attribute, the relevant protection functions will be
blocked.
For IEC60870-5-103 protocol, only the messages in link layer maintained, service messages in
the application layer which is uploaded automatically are blocked, and service messages in the
application layer which is issued by the client are rejected. For IEC61850 protocol, all Test quality
attribute set as "1". For DNP3.0 and ModBus protocol, they are not affected.
The device provides Test Mode to allow all protection elements, supervision events and binary
events to fulfill communication test, but to avoid the output contacts to close. During
communication test, protection functions are not affected, the signals generated by
communication test are recorded in relevant reports, and event recording and fault recording will
not stop recording disturbance information. The alarm signal "Alm_CommTest" will be issued to
indicate the operator when activating Test Mode and exiting Test Mode.
Communication test can be gained via local HMI and the virtual HMI, the corresponding content
can be viewed through the following menu paths:
Events Simulation
7 Forced Measurements
If no input operation is carried out within 60s, this test will exit and return to
the previous menu automatically.
entering and exiting of output test mode will be recorded in Superv Events. During the output test,
the protection functions will not stop, nor will the all recording functions.
Output test can be gained via the local LCD or virtual HMI of a debugging PC, the corresponding
content can be viewed through the following menu paths:
Contacts Outputs
GOOSE Outputs
The device provides target reset which can be used to reset local signals (including magnetic
latching output relays), latched LEDs, and confirm pop-up windows of reports. The function does
not affect the protection logic and communication function. There are several ways to reset.
Press the command pushbutton “ESC”+“ENT” on operation panel of the device under
main interface
Press the command pushbutton " TARGET RESET" on operation panel of the device
For different applications users can save the respective function settings in so-called settings
groups, and if necessary enable them quickly. Up to 10 different settings groups can be saved in
the device. In the process, only one settings group is active at any given time. During operation,
the operator can switch between setting groups.
The device will be temporarily blocked during switching setting groups. During temporary device
blocking, the device will loss protection functions and communication functions. Alarm signals
"Fail_Device" and "Alm_Device" will be issued. There are several ways to switch setting groups.
Press the command pushbutton “MENU” under main interface (password is required)
There are 2 appropriate input signals available for switching setting group via binary inputs.
These input signals allow selection of the settings group via a binary code. If one of two
signals changes, the signal image present will result in switching over to the appropriate
settings group. If only 2 settings groups must be switched over, only 1 binary input is required.
The following table shows the possible binary codes and applicable setting groups.
The communication protocols IEC 60870-5-103 or IEC 61850 can be used for switching the
setting groups via a communication connection.
8 Hardware
Table of Contents
List of Figures
Figure 8.1-3 Typical rear view of this device (pin-ferrule-terminal modules) ............................ 8-3 8
Figure 8.1-4 Typical rear view of this device (ring-ferrule-terminal modules) ........................... 8-4
List of Tables
Table 8.4-1 Terminal definition and description of power supply module ............................... 8-11
Table 8.4-2 Terminal definition and description of power supply module ............................... 8-11
Table 8.4-4 Terminal definition and description of binary input module (NR6601A) ............... 8-21
Table 8.4-5 Terminal definition and description of binary input module (NR6610A/B) .......... 8-23
8.1 Overview
The modular design of this device allows this device to be easily upgraded or repaired by a
qualified service person. The faceplate is hinged to allow easy access to the configurable
modules, and back-plugging structure design makes it easy to repair or replace any module.
This device adopts one 32-bit ARM core in the CPU chip as control core for management and
monitoring function, and adopts another 32-bit ARM core in the CPU chip for all the protection
calculation. The parallel processing of sampled data can be realized in each sampling interval to
ensure ultrahigh reliability and safety of the device.
This device is developed on the basis of our latest software and hardware platform, and the new
platform major characteristics are of high reliability, networking and great capability in
anti-interference. See Figure 8.1-1 for the hardware diagram.
External
Binary Input
Pickup
ECVT Relay
ETHERNET
+E
LCD
Clock SYN
Power
Uaux LED ARM2
Supply
RJ45
Keypad
PRINT
The items can be flexibly configured depending on the situations like sampling method of the
device (conventional CT/VT or ECT/EVT), and the mode of binary output (conventional binary
output or GOOSE binary output). The configurations for PCS S series based on microcomputer
are classified into standard and optional modules.
HMI module is comprised of LCD, keypad, LED indicators and multiplex RJ45 ports for user
as human-machine interface.
PWR module converts DC 250/220/125/110V into various DC voltage levels for modules of
the device.
CPU module provides functions like communication with SAS, event record, setting
management etc., and performs filtering, sampling, protection calculation and fault detector
calculation.
AI module converts AC current and voltage from current transformers and voltage
transformers respectively to small voltage signal.
BI module provides binary inputs via opto-couplers with rating voltage among AC110V/220V
or DC24V/48V/110V/125V/220V/250V (configurable).
BO module provides output contacts for tripping, and signal output contact for annunciation
signal, remote signal, fault and disturbance signal, operation abnormal signal etc.
Following figures show front and rear views of this device respectively.
B01 B02 & B03 B04 B05 B06 P1 B01 B02 & B03 B04 P1
NR6106AA NR6641-6I5U Option Option Option NR6310A NR6106AA NR6641-6I5U Option NR6310A
BI_01+ 01 BI_01+ 01
01 I1 I1n 02 01 I1 I1n 02
BI_01- 02 BI_01- 02
03 I2 I2n 04 BI_02+ 03 03 I2 I2n 04 BI_02+ 03
BI_02- 04 BI_02- 04
NET 05 I3 I3n 06 BI_COM 05 NET 05 I3 I3n 06 BI_COM 05
BI_03 06 BI_03 06
LC 07 I4 I4n 08 LC 07 I4 I4n 08
BI_04 07 BI_04 07
LC BI_05 08 LC BI_05 08
09 I5 I5n 10 09 I5 I5n 10
BI_06 09 BI_06 09
11 I6 I6n 12 BI_07 10 11 I6 I6n 12 BI_07 10
BI_08 11 BI_08 11
13 14 BI_09 12 13 14 BI_09 12
13 13
8
15 U1 U1n 16 BO_01 15 U1 U1n 16 BO_01
14 14
17 U2 U2n 18 15 17 U2 U2n 18 15
BO_02 BO_02
16 16
01 1A 19 U3 U3n 20 17 01 1A 19 U3 U3n 20 17
BO_03 BO_03
02 1B 18 02 1B 18
03 SGND 21 U4 U4n 22 19 03 SGND 21 U4 U4n 22 19
BO_04 BO_04
04 2A 20 04 2A 20
23 U5 U5n 24 23 U5 U5n 24
05 2B 21 05 2B 21
06 SGND BO_05 06 SGND
BO_05
22 22
07 SYN+ 07 SYN+
23 23
08 SYN- BO_Fail 08 SYN- BO_Fail
24 24
09 SGND 09 SGND
PWR+ 25 PWR+ 25
10 SYN-TTL 10 SYN-TTL
PWR- 26 PWR- 26
COM
485-1B 0102 Ia
0202
SGND 0103
0203
485-2A 0104 Ib
0204
COM
485-2B 0105
0205
SGND 0106
Ic
SYN+ 0107 0206
Clock SYN
SYN- 0108 0207
SGND 0109 I0
0208
TTL 0110
0209
I0
Multiplex RJ45 0210
0211
AI plug-in module
Isef
P101 + BI_01 0212
0213
P102 -
0214
- P103 + BI_02
0215
P104 - U0
0216
P106 + BI_03 0217
Ux
0218
P107 + BI_04 0219
Ua
0220
PWR plug-in module
…
0221
P112 + BI_09 Ub
0222
P105 0223
P113 Uc
BO_01 0224
P114
P115
P116 BO_02
…
P121
P122 BO_05
P123
P124 BO_Fail
PWR+ P125
External DC power Power
supply
PWR- P126 Supply
8
Grounding Bus
B01 B02 & B03 B04 B05 B06 P1 B01 B02 & B03 B04 P1
NR6106AA NR6641-6I5U Option Option Option NR6305A NR6106AA NR6641-6I5U Option NR6305A
13 14 13 BO_01 14 13 14 13 BO_01 14
CONSOLE CONSOLE
Ground Ground
COM
485-1B 0102 Ia
0202
SGND 0103
0203
485-2A 0104 Ib
0204
COM
485-2B 0105
0205
SGND 0106
Ic
SYN+ 0107 0206
Clock SYN
SYN- 0108 0207
SGND 0109 I0
0208
TTL 0110
0209
I0
Multiplex RJ45 0210
0211
AI plug-in module
Isef
P101 + BI_01 0212
0213
P102 -
0214
- P103 + BI_02
0215
P104 - U0
0216
P106 + BI_03 0217
Ux
0218
P107 + BI_04 0219
Ua
0220
PWR plug-in module
…
0221
P112 + BI_09 Ub
0222
P105 0223
P113 Uc
BO_01 0224
P114
P115
P116 BO_02
…
P121
P122 BO_05
P123
P124 BO_Fail
PWR+ P125
External DC power Power
supply
PWR- P126 Supply
8
Grounding Bus
8.3 CT Requirement
8.3.1 CT Types
Generally there are three types of CT: high remanence, low remanence and no
remanence.
Low remanence: TPY, PR, and the residual magnetism does not exceed 10% of the
saturation flux.
The high residual magnetism CT may have large residual magnetism. When the fault
non-periodic component and residual magnetism are in the same direction, the CT
saturation degree will be more serious. The following CT type checking calculation takes
into account the maximum residual magnetism of CT and the maximum non periodic
component on the site.
8.3.2 CT Requirement
Rated secondary limit e.m.f (volts) formula:
Esl3′ = k3×Ipnt×Isn×(Rct+Rb)/Ipn
Esl4′ = k4×Ipcf4×Isn×(Rct+Rb)/Ipn
Maximum fault current through two bridge CB but not transformer when
Ipcf2
8 out-zone fault (amps)
1. K Value Requirement
While: k1=2,k3=30,k4=1.
If both CTs of double CB are low remanence type, and with the same model, then k1=2,
k2=1.5, k3=30, k4=1.
Otherwise: k1=2,k2=2,k3=30,k4=1.
2. Example
= 30×5×(1+60/25)=510V
Esl1′ = k1×Ipcf1×Isn×(Rct+Rb)/Ipn
= 2×Ipcf1 ×Isn×(Rct+(Rr+2×RL))/Ipn
= 2×40000×5×(1+(0.1+2×0.5))/2000=420V
Esl3′ = k3×Ipnt×Isn×(Rct+Rb)/Ipn
=30×1500*5*(1+(0.1+2×0.5)) /2000=236.25V
output. It has an input voltage range as described in Chapter 2 Technical Data. The standardized
output voltages are +5Vdc and +12Vdc. The tolerances of the output voltages are continuously
monitored.
The +5Vdc output provides power supply for all the electrical elements that need +5Vdc power
supply in this device.
The use of an external miniature circuit breaker is recommended. The miniature circuit breaker
must be in the on position when the device is in operation and in the off position when the device
is in cold reserve.
8
Figure 8.4-1 View of power supply module
Three types of power supply modules are provided: NR6305A, NR6305B and NR6310A. The
NR6305B is same as the NR6305A except that the NR6105B can support at least 500ms power
supply interruption.
The power supply module also provides 9 binary inputs, 5 binary outputs and a device failure
binary output. A 26-pin connector is fixed on the power supply module. The terminal definition of
the connector is described as below.
The power supply module also provides 9 binary inputs, 5 binary outputs and a device failure
binary output. A 22-pin connector and a 4-pin connector are fixed on the power supply module.
The terminal definition of the connector is described as below.
The PWR module a grounding screw for device grounding. The grounding
screw shall be connected to grounding screw and then connected to the
earth copper bar of panel via dedicated grounding wire.
convert the AC analog signals to corresponding DC signals for fulfilling the demand of the
electrical level standard. A high-accuracy clock chip is contained in this module, it provide
accurate current time for this device.
The main functional details of the CPU module are listed as below:
The CPU module can calculate protective elements (such as overcurrent element) on the
basis of the analog sampled values (voltages and currents) and binary inputs, then it does
logical judgment function and decides whether the device needs to trip or close.
Communication function
The CPU module can effectively manage all communication procedures, and reliably send
out some useful information through its various communication interfaces. These interfaces
are used to communicate with a SAS or a RTU. It also can communicate with the human
machine interface module. If an event occurs (such as SOE, protective tripping event etc.),
this module will send out the relevant event information through these interfaces, and make it
be easily observed by the user.
Auxiliary calculation
Based on the voltage and current inputs, the CPU module also can calculate out the metering
values, such as active power, reactive power and power factor etc. All these values can be
sent to a SAS or a RTU through the communication interfaces.
This module can respond the commands from the keypad of this device and show the results
on the LCD and LED indicators of this device. It also can show the operation situation and
event information for the users through the LCD and LED indicators.
Time synchronization
This module has a local clock chip and an interface to receive time synchronized signals from
external clock source. These signals include PPS (pulse per second) signal and IRIG-B
8
signal. Basing on the timing message (from SAS or RTU) and the PPS signal, or basing on
the IRIG-B signal, this module can synchronize local clock with the standard clock.
Do NOT look into the end of an optical fiber connected to an optical port.
09 SGND
TTL 10 SYN-TTL Cable
The correct connection is shown in Figure 8.4-3. Generally, the shielded cable with two pairs of
twisted pairs inside shall be applied. One pair of the twisted pairs are respectively used to connect
the “+” and “–” terminals of difference signal. The other pair of twisted pairs are used to connect
the signal ground of the communication interface. The module reserves a free terminal for all the
communication ports. The free terminal has no connection with any signal of the device, and it is
used to connect the external shields of the cable when connecting multiple devices in series. The
external shield of the cable shall be grounded at one of the ends only.
B 02
COM
SGND 03
cable with single point earthing
04
To the screen of other coaxial
Clock SYN
SYN- 02
SGND 03
04
Cable
RTS 05
PRINT
TXD 06
SGND 07
The 2nd RS-485 port also can be configured as a printer port through the
For the analog input module, if the plug is not put in the socket, external CT circuit is closed itself.
Just shown as below.
Plug
Socket
In
Out
8 In
Out
There are several types of analog input modules. The rated current is adaptive (1A/5A). Please
declare which kind of AI module is needed before ordering. Maximum linear range of the current
converter is 40In.
NR6641-6I5U: 6CT+5VT
NR6641-4I4U: 4CT+4VT
NR6641-4I7U: 4CT+7VT
Some connection examples of the current transformers and voltage transformers which are
supported by this relay are shown in this section. If one of the analog inputs has no input in a
practical engineering, the relevant input terminals should be disconnected.
A B C A B C
Ia Ia
Ian Ian
Ib Ib
Ibn Ibn
Ic Ic
Icn Icn
I01
I01n I01
(1) I01n
A B C (3)
Ia
Ian
Ib I0s
Ibn I0sn
Ic
(4)
Icn
I01 I02
I01n I02n
(2) (5)
Where:
(1) Current connections to three current transformers with a star-point connection for ground
current (zero-sequence current or residual current).
(2) Current connections to three current transformers with a separate ground current
8 transformer (summation current transformer or core balance current transformer).
(3) Current connections to two current transformers with a separate ground current
transformer (summation current transformer or core balance current transformer), only
for ungrounded or compensated networks.
(4) Current connection to a core balance neutral current transformer for sensitive ground
fault detection, only for ungrounded or compensated networks.
A B C A B C
Ux
52 52 52 Ux 52 52 52
Uxn
Uxn
Ua Ua
Ub Ub
Uc Uc
Un Un
U0 U0
U0n U0n
(1) (2)
Where:
There are three kinds of BI modules available, NR6601A, NR6610A and NR6610B. The binary
input module can respectively provide 25 or 32 binary inputs.
8
The rated voltage of binary input is optional: 24Vdc, 30Vdc, 48Vdc, 110Vdc,
125V, 220V, 110Vac or 220Vac (@50Hz), which must be specified when
placed order. It is necessary to check whether the rated voltage of binary
input module complies with site DC power supply rating before put this
device in service.
Voltage
300
157.5
138.6
125
110
78.75
69.3
62.5
55 Operation
30.24
24 Operation uncertain
15.12
12
No operation
0 24V 48V 110V 125V 220V 250V
NR6601A
Each BI module is with a 26-pin connector for 25 binary inputs which share one common negative
power input and can be configurable. The pickup voltages and dropout voltages of the binary
8 inputs are settable by the setting [U_Pickup_BI] and [U_Dropoff_BI], and the range is from
50%Un to 80%Un.
01 BI_01 BI_02 02
03 BI_03 BI_04 04
05 BI_05 BI_06 06
07 BI_07 BI_08 08
09 BI_09 BI_10 10
11 BI_11 BI_12 12
13 BI_13 BI_14 14
15 BI_15 BI_16 16
17 BI_17 BI_18 18
19 BI_19 BI_20 20
21 BI_21 BI_22 22
23 BI_23 BI_24 24
25 BI_25 BI_COM 26
A 26-pin connector is fixed on the binary input module. The terminal definition of the connector is
described as below.
Table 8.4-4 Terminal definition and description of binary input module (NR6601A)
Each BI module is with two 18-pin connectors for 32 binary inputs. The first 16 binary inputs share
one common negative power input and the last 16 binary inputs share another common negative
power input. All binary inputs are configurable. The pickup voltages and dropout voltages of the
binary inputs are settable by the setting [U_Pickup_BI] and [U_Dropoff_BI], and the range is from
50%Un to 80%Un. The difference between NR6610A and NR6610B is that NR6610A equips
single AD sampling and NR6610B equips dual AD sampling.
01 BI_01 19 BI_17
02 BI_02 20 BI_18
03 BI_03 21 BI_19
04 BI_04 22 BI_20
05 BI_05 23 BI_21
06 BI_06 24 BI_22
07 BI_07 25 BI_23
08 BI_08 26 BI_24
8 09
10
BI_09
BI_10
27
28
BI_25
BI_26
11 BI_11 29 BI_27
12 BI_12 30 BI_28
13 BI_13 31 BI_29
14 BI_14 32 BI_30
15 BI_15 33 BI_31
16 BI_16 34 BI_32
17 BI_COM 35 BI_COM
18 BI_COM 36 BI_COM
Table 8.4-5 Terminal definition and description of binary input module (NR6610A/B)
18-pin
27
28
BI_25
BI_26
The No.25 programmable binary input
The No.26 programmable binary input
8
29 BI_27 The No.27 programmable binary input
30 BI_28 The No.28 programmable binary input
31 BI_29 The No.29 programmable binary input
32 BI_30 The No.30 programmable binary input
33 BI_31 The No.31 programmable binary input
34 BI_32 The No.32 programmable binary input
35
BI_COM The common negative connection of the BI_17 to BI_32.
36
executes these commands. It also can output some alarm signals from the CPU module.
The device can provide four types of binary output modules: NR6651A, NR6651B, NR6652A and
NR6660A.
NR6651A
The NR6651A provides 13 normal open contacts (NOC) with pickup relay control.
BO_01 01 02
BO_02 03 04
BO_03 05 06
BO_04 07 08
BO_05 09 10
BO_06 11 12
BO_07 13 14
BO_08 15 16
BO_09 17 18
BO_10 19 20
BO_11 21 22
BO_12 23 24
8 BO_13 25 26
NR6651B
The NR6651B provides 11 normal open contacts (NOC, the first 11 contacts) and 2 normal close
contacts (NCC, the last 2 contacts). These binary outputs are controlled by pickup relay.
BO_01 01 02
BO_02 03 04
BO_03 05 06
BO_04 07 08
BO_05 09 10
BO_06 11 12
BO_07 13 14
BO_08 15 16
BO_09 17 18
BO_10 19 20
BO_11 21 22
BO_12 23 24
BO_13 25 26
NR6652A
The NR6652A provides 4 normal open contacts (NOC, the first 4 contacts) with heavy capacity for
controlling the circuit breaker directly, and provides 4 general normal open contacts (NOC, the last
4 contacts). These binary outputs are controlled by pickup relay.
BO_01 01 02
03 04
BO_02 05 06
07 08
BO_03 09 10
11 12
BO_04 13 14
15 16
17 18
BO_05 19 20
BO_06 21 22
BO_07 23 24
BO_08 25 26
NR6660A
The NR6660A provides 17 normally open contacts (NOC, the first 17 contacts) and 2 normally
close contacts (NCC, the 16th and the 17th contacts). These binary outputs are controlled by
pickup relay.
BO_01 01 02
BO_02 03 04
BO_03 05 06
BO_04 07 08
BO_05 09 10
BO_06 11 12
BO_07 13 14
BO_08 15 16
BO_09 17 18
BO_10 19 20
BO_11 21 22
BO_12 23 24
BO_13 25 26
BO_14 27 28
BO_15 29 30
BO_16 32
31
BO_16 33
BO_17 35
34
BO_17 36
9 Settings
Table of Contents
9.2.3 Another Group of Earth Fault Overcurrent Protection Settings ......................................... 9-51
List of Tables
Table 9.2-3 Settings of another group of earth fault overcurrent protection...................... 9-51
Default
No. Settings Range Unit Step Remark
value
The number of active setting group,
several setting groups can be configured
1 Active_Grp 1~30 1 - 1
for protection settings, and only one is
active at a time.
Name of the protected primary
Max 20
2 PrimaryEquip_Name - - - equipment, such as feeder, transformer,
characters
etc.
3 Opt_SysFreq 50, 60 50Hz Hz The system frequency.
Rated primary value of protection phase
4 Prot.I1n 0~9999 1000 A 1
CT
Rated secondary value of protection
5 Prot.I2n 1, 5 1 A -
phase CT
Rated primary value of the No.1
6 Neu.I1n 0~9999 1000 A 1
zero-sequence CT
Rated secondary value of the No.1
7 Neu.I2n 1, 5 1 A -
zero-sequence CT
Rated primary value of the No.2
8 Neu2.I1n 0~9999 1000 A 1
zero-sequence CT
Rated secondary value of the No.2
9 Neu2.I2n 1, 5 1 A -
zero-sequence CT
Rated primary value of sensitive
10 SEF.I1n 0~9999 1000 A 1
zero-sequence CT
Rated secondary value of sensitive
11 SEF.I2n 1 1 A -
zero-sequence CT 9
12 60/50.I1n 0~9999 1000 A 1 Rated primary value of unbalance CT
13 60/50.I2n 1, 5 1 A - Rated secondary value of unbalance CT
14 Prot.U1n 0~1100 10 kV 0.001 Rated primary value of protection VT
15 Prot.U2n 1~200 100 V 0.001 Rated secondary value of protection VT
16 Syn.U1n 0~1100 10 kV 0.001 Rated primary value of synchro-check VT
Rated secondary value of synchro-check
17 Syn.U2n 1~200 100 V 0.001
VT
18 Delt.U1n 0~1100 10 kV 0.001 Rated primary value of zero-sequence VT
19 Delt.U2n 1~200 100 V 0.001 Rated secondary value of zero-sequence
Default
No. Settings Range Unit Step Remark
value
VT
9 28 En_VT
Disabled;
Enabled
Enabled - - Logic setting to put VT into service
Default
No. Settings Range Unit Step Remark
value
Logic setting to enable/disable the
Disabled debugging port. Used for debugging
1 En_DebugPort Enabled - -
Enabled tool connection, program download,
variable debugging, etc.
Disabled Logic setting to enable/disable the
2 En_TelnetPort Enabled - -
Enabled Telnet port.
Enabled: Connecting to the device via
Disabled the software Teldevice is supported
3 En_VirtualLCDPort Enabled - -
Enabled Disabled: Connecting to the device via
the software Teldevice is not supported
Enabled: printing data to the software
Disabled Netpts is supported
4 En_NetPrintPort Enabled - -
Enabled Disabled: printing data to the software
Netpts is not supported
Disabled Override control password via local
5 En_NoCtrlPwd Enabled - -
Enabled LCD
6 Ctrl_Password 000~999 111 - - The control password via local LCD.
This setting is used to set the voltage
7 Un_BinaryInput 24~250 220 V -
level of the binary input module.
DC
Power supply mode of binary input
8 Opt_Pwr_BI AC50Hz DC - -
module
AC60Hz
This setting is used to set pickup
9 U_Pickup_BI 50%Un~80%Un 63 % 0.1
voltage of the binary input module.
This setting is used to set drop-off
10 U_Dropoff_BI 50%Un~80%Un 55 % 0.1
voltage of the binary input module.
Monitoring window of binary input jitter
11 Mon_Window_Jitter 0.000~500.000 1 0.001 s
processing
Times threshold to block binary input
12 Num_Blk_Jitter 2~500000 10 1 -
status change due to jitter
Blocking window of binary input status 9
13 Blk_Window_Jitter 0.000~500.000 1 0.001 s
change due to jitter
Times threshold to initiate immediately
14 Num_Reblk_Jitter 1~500000 10 1 - another blocking window of binary input
status change due to continuous jitter
The logic setting to enable/disable the
Disabled
15 En_Jitter_Blk Disabled - - jitter processing function in case of
Enabled
binary input voltage variation
Access path:
The setting is used to configure dual-networks switching, and it means that no dual-networks
switching is created when the setting is set as “0”. The device support a bond between any two
Ethernet ports, and the bond among three or above Ethernet ports is impermissible.
The devices communicate with SAS by station level network. In order to ensure reliable
communication, dual networks (i.e., network 1 and network 2) are adopted. Another special
communication mode based on dual networks is that Ethernet port 1 and Ethernet port 2 of the
device own the same IP address and MAC address, and network 1 and network 2 are used as hot
standby each other. When both network 1 and network 2 are normal, any of them is used to
communicate between the device and SAS. The device will automatically switch to the other
healthy network when one network is abnormal, which will not affect normal communication.
Taking a CPU module with four Ethernet ports as an example, each bit is corresponding with an
Ethernet port, i.e., Bit0, Bit1, Bit2 and Bit3 are corresponding with Ethernet port 1, Ethernet port 2,
Ethernet port 3 and Ethernet port 4 respectively. If a bond between Ethernet port 1 and Ethernet 2
is created, the setting [Cfg_NetPorts_Bond] is set as “3”. The specific setting is as below.
Ethernet port 1 Ethernet port 2 Ethernet port 1 Ethernet port 3 Ethernet port 1 Ethernet port 4
0 0 1 1 3 0 1 0 1 5 1 0 0 1 9
Ethernet port 2 Ethernet port 3 Ethernet port 2 Ethernet port 4 Ethernet port 3 Ethernet port 4
0 1 1 0 6 1 0 1 0 10 1 1 0 0 12
Ethernet port 1: Bit0, Ethernet port 2: Bit1, Ethernet port 3: Bit2, Ethernet port 4: Bit3
After the device is powered on, network 1 is selected when the link status of both network 1
and network 2 are normal.
When the link status of network 1 is abnormal, network 2 is selected if network 2 is normal.
9 When the link status of network 1 is abnormal, network 1 is kept to work if network 2 is also
abnormal.
When network 2 is working, network 2 is kept to work even if network 1 has been restored to
normal. The device will be switched to network 1 only if network 2 is abnormal.
Access path:
Default
No. Settings Range Unit Step Remark
value
The identification of the IED in
IEC 61850 protocol.
It cannot be an empty string and
shall be unique within an SCL
file. IEDNAME should be less
than 20 characters comprising
1 IEDNAME - TEMPLATE - -
letters or digits or underline ( _ ),
and it is case sensitive.
If this setting is modified, the IED
name in ".cid" file will be
changed simultaneously and
vice versa.
It is used to set the change
detection threshold for suddenly
sending measurement value to
2 Threshold_Measmt_Net 0~100.00 1 % 0.01
the SCADA via the device's
Ethernet port using IEC 61850
protocol
Measurement values zero drift
3 ThAbs_Measmt 0.001~0.5 0.02 - 0.001
suppression threshold
If users need to support the
Disabled quality change upload function,
4 En_Send_MMS_Qual_Chg Disabled - -
Enabled this parameter should be set as
“1”
It is used to select the network
mode of MMS network for the
communication with SCADA
SingleNet
0: Single network
5 Opt_DualNetMode_MMS HotStdby SingleNet - -
1: Hot standby mode (always
ColdStdby
two ports in service)
2: Cold standby mode (only one 9
port in service)
The logic setting to
Disabled
6 En_IEC62351_TCP_Port Disabled - - enable/disable TCP port in
Enabled
IEC62351 protocol
The logic setting to
Disabled
7 En_IEC61850_TCP_Port Enabled - - enable/disable TCP port in
Enabled
IEC61850 protocol
Access path:
Default
No. Settings Range Unit Step Remark
value
The logic setting to
Disabled
1 En_TCP1_DNP Disabled - - enable/disable the No.1
Enabled
network DNP client
The local address of the
2 Addr_Slave_TCP1_DNP 0~65519 2 - 1
No.1 network DNP client
The master address of the
3 Addr_Master_TCP1_DNP 0~65519 1 - 1
No.1 network DNP client
The IP address of the
0.0.0.0~
4 IP_Master_TCP1_DNP 0.0.0.0 - - master of the No.1 network
255.255.255.255
DNP client
The communication map
5 Opt_Map_TCP1_DNP 0~4 0 - 1 of the No.1 network DNP
client
The timeout of the
6 t_AppLayer_TCP1_DNP 1~5 3 s 1 application layer of the
No.1 network DNP client
The heartbeat time interval
7 t_KeepAlive_TCP1_DNP 0~7200 120 s 1 of the No.1 network DNP
client
The logic setting to
enable/disable the
Disabled
8 En_UR_TCP1_DNP Disabled - - unsolicited message
Enabled
function of the No.1
network DNP client
The online retransmission
number for sending the
9 Num_URRetry_TCP1_DNP 2~10 3 - 1
unsolicited message of the
No.1 network DNP client
Default
No. Settings Range Unit Step Remark
value
the remote control and
remote adjustment of No.1
network DNP client
The time interval of the
time synchronization
14 t_TimeSynIntvl_TCP1_DNP 0~3600 180 s 1
function of the No.1
network DNP client
The “OBJ1” default
1-BISingleBit
15 Obj01DefltVar_TCP1_DNP 1-BISingleBit - - variation of the No.1
2-BIWithStatus
network DNP client
1-BIChWoutT The “OBJ2” default
2-BIChWithA
16 Obj02DefltVar_TCP1_DNP 2-BIChWithAbsTime - - variation of the No.1
bsTime
3-BIChWithRelTime network DNP client
1-AI32Int
2-AI16Int The “OBJ30” default
3-AI32IntWo
17 Obj30DefltVar_TCP1_DNP 3-AI32IntWoutF - - variation of the No.1
utF
4-AI16IntWoutF network DNP client
5-AI32Flt
1-AI32IntEvWoutT The “OBJ32” default
1-AI32IntEv
18 Obj32DefltVar_TCP1_DNP 2-AI16IntEvWoutT - - variation of the No.1
WoutT
5-AI32FltEvWoutT network DNP client
1-AO32Int The “OBJ40” default
19 Obj40DefltVar_TCP1_DNP 2-AO16Int 1-AO32Int - - variation of the No.1
3-AO32Flt network DNP client
The logic setting to
Disabled
20 En_TCP2_DNP Disabled - - enable/disable the No.2
Enabled
network DNP client
The local address of the
21 Addr_Slave_TCP2_DNP 0~65519 2 - 1
No.2 network DNP client
The master address of the
22 Addr_Master_TCP2_DNP 0~65519 1 - 1
No.2 network DNP client
23 IP_Master_TCP2_DNP
0.0.0.0~
0.0.0.0 - -
The IP address of the
master of the No.2 network
9
255.255.255.255
DNP client
The communication map
24 Opt_Map_TCP2_DNP 0~4 0 - 1 of the No.2 network DNP
client
The timeout of the
25 t_AppLayer_TCP2_DNP 1~5 3 s 1 application layer of the
No.2 network DNP client
The heartbeat time interval
26 t_KeepAlive_TCP2_DNP 0~7200 120 s 1
of the No.2 network DNP
Default
No. Settings Range Unit Step Remark
value
client
The logic setting to
enable/disable the
Disabled
27 En_UR_TCP2_DNP Disabled - - unsolicited message
Enabled
function of the No.2
network DNP client
The online retransmission
number for sending the
28 Num_URRetry_TCP2_DNP 2~10 3 - 1
unsolicited message of the
No.2 network DNP client
The offline retransmission
interval for sending the
29 t_UROfflRetry_TCP2_DNP 1~5000 60 s 1
unsolicited message of the
No.2 network DNP client
The default class level of
30 Class_BI_TCP2_DNP 0~3 1 - 1 the “Binary Input” of the
No.2 network DNP client
The default class level of
31 Class_AI_TCP2_DNP 0~3 2 - 1 the “Analog Input” of the
No.2 network DNP client
The selection timeout of
the remote control and
32 t_Select_TCP2_DNP 0~240 30 s 1
remote adjustment of No.2
network DNP client
The time interval of the
time synchronization
33 t_TimeSynIntvl_TCP2_DNP 0~3600 180 s 1
function of the No.2
network DNP client
The “OBJ1” default
1-BISingleBit
34 Obj01DefltVar_TCP2_DNP 1-BISingleBit - - variation of the No.2
2-BIWithStatus
network DNP client
9 35 Obj02DefltVar_TCP2_DNP
1-BIChWoutT
2-BIChWithAbsTime
2-BIChWithA
- -
The
variation
“OBJ2”
of the
default
No.2
bsTime
3-BIChWithRelTime network DNP client
1-AI32Int
2-AI16Int The “OBJ30” default
3-AI32IntWo
36 Obj30DefltVar_TCP2_DNP 3-AI32IntWoutF - - variation of the No.2
utF
4-AI16IntWoutF network DNP client
5-AI32Flt
1-AI32IntEvWoutT The “OBJ32” default
1-AI32IntEv
37 Obj32DefltVar_TCP2_DNP 2-AI16IntEvWoutT - - variation of the No.2
WoutT
5-AI32FltEvWoutT network DNP client
Default
No. Settings Range Unit Step Remark
value
1-AO32Int The “OBJ40” default
38 Obj40DefltVar_TCP2_DNP 2-AO16Int 1-AO32Int - - variation of the No.2
3-AO32Flt network DNP client
The logic setting to
Disabled
39 En_TCP3_DNP Disabled - - enable/disable the No.3
Enabled
network DNP client
The local address of the
40 Addr_Slave_TCP3_DNP 0~65519 2 - 1
No.3 network DNP client
The master address of the
41 Addr_Master_TCP3_DNP 0~65519 1 - 1
No.3 network DNP client
The IP address of the
0.0.0.0~
42 IP_Master_TCP3_DNP 0.0.0.0 - - master of the No.3 network
255.255.255.255
DNP client
The communication map
43 Opt_Map_TCP3_DNP 0~4 0 - 1 of the No.3 network DNP
client
The timeout of the
44 t_AppLayer_TCP3_DNP 1~5 3 s 1 application layer of the
No.3 network DNP client
The heartbeat time interval
45 t_KeepAlive_TCP3_DNP 0~7200 120 s 1 of the No.3 network DNP
client
The logic setting to
enable/disable the
Disabled
46 En_UR_TCP3_DNP Disabled - - unsolicited message
Enabled
function of the No.3
network DNP client
The online retransmission
number for sending the
47 Num_URRetry_TCP3_DNP 2~10 3 - 1
unsolicited message of the
No.3 network DNP client
The offline retransmission
interval for sending the
9
48 t_UROfflRetry_TCP3_DNP 1~5000 60 s 1
unsolicited message of the
No.3 network DNP client
The default class level of
49 Class_BI_TCP3_DNP 0~3 1 - 1 the “Binary Input” of the
No.3 network DNP client
The default class level of
50 Class_AI_TCP3_DNP 0~3 2 - 1 the “Analog Input” of the
No.3 network DNP client
51 t_Select_TCP3_DNP 0~240 30 s 1 The selection timeout of
Default
No. Settings Range Unit Step Remark
value
the remote control and
remote adjustment of No.3
network DNP client
The time interval of the
time synchronization
52 t_TimeSynIntvl_TCP3_DNP 0~3600 180 s 1
function of the No.3
network DNP client
The “OBJ1” default
1-BISingleBit
53 Obj01DefltVar_TCP3_DNP 1-BISingleBit - - variation of the No.3
2-BIWithStatus
network DNP client
1-BIChWoutT The “OBJ2” default
2-BIChWithA
54 Obj02DefltVar_TCP3_DNP 2-BIChWithAbsTime - - variation of the No.3
bsTime
3-BIChWithRelTime network DNP client
1-AI32Int
2-AI16Int The “OBJ30” default
3-AI32IntWo
55 Obj30DefltVar_TCP3_DNP 3-AI32IntWoutF - - variation of the No.3
utF
4-AI16IntWoutF network DNP client
5-AI32Flt
1-AI32IntEvWoutT The “OBJ32” default
1-AI32IntEv
56 Obj32DefltVar_TCP3_DNP 2-AI16IntEvWoutT - - variation of the No.3
WoutT
5-AI32FltEvWoutT network DNP client
1-AO32Int The “OBJ40” default
57 Obj40DefltVar_TCP3_DNP 2-AO16Int 1-AO32Int - - variation of the No.3
3-AO32Flt network DNP client
The logic setting to
Disabled
58 En_TCP4_DNP Disabled - - enable/disable the No.4
Enabled
network DNP client
The local address of the
59 Addr_Slave_TCP4_DNP 0~65519 2 - 1
No.4 network DNP client
The master address of the
60 Addr_Master_TCP4_DNP 0~65519 1 - 1
No.4 network DNP client
9 61 IP_Master_TCP4_DNP
0.0.0.0~
0.0.0.0 - -
The IP address of the
master of the No.4 network
255.255.255.255
DNP client
The communication map
62 Opt_Map_TCP4_DNP 0~4 0 - 1 of the No.4 network DNP
client
The timeout of the
63 t_AppLayer_TCP4_DNP 1~5 3 s 1 application layer of the
No.4 network DNP client
The heartbeat time interval
64 t_KeepAlive_TCP4_DNP 0~7200 120 s 1
of the No.4 network DNP
Default
No. Settings Range Unit Step Remark
value
client
The logic setting to
enable/disable the
Disabled
65 En_UR_TCP4_DNP Disabled - - unsolicited message
Enabled
function of the No.4
network DNP client
The online retransmission
number for sending the
66 Num_URRetry_TCP4_DNP 2~10 3 - 1
unsolicited message of the
No.4 network DNP client
The offline retransmission
interval for sending the
67 t_UROfflRetry_TCP4_DNP 1~5000 60 s 1
unsolicited message of the
No.4 network DNP client
The default class level of
68 Class_BI_TCP4_DNP 0~3 1 - 1 the “Binary Input” of the
No.4 network DNP client
The default class level of
69 Class_AI_TCP4_DNP 0~3 2 - 1 the “Analog Input” of the
No.4 network DNP client
The selection timeout of
the remote control and
70 t_Select_TCP4_DNP 0~240 30 s 1
remote adjustment of No.4
network DNP client
The time interval of the
time synchronization
71 t_TimeSynIntvl_TCP4_DNP 0~3600 180 s 1
function of the No.4
network DNP client
The “OBJ1” default
1-BISingleBit
72 Obj01DefltVar_TCP4_DNP 1-BISingleBit - - variation of the No.4
2-BIWithStatus
network DNP client
73 Obj02DefltVar_TCP4_DNP
1-BIChWoutT
2-BIChWithAbsTime
2-BIChWithA
- -
The
variation
“OBJ2”
of the
default
No.4
9
bsTime
3-BIChWithRelTime network DNP client
1-AI32Int
2-AI16Int The “OBJ30” default
3-AI32IntWo
74 Obj30DefltVar_TCP4_DNP 3-AI32IntWoutF - - variation of the No.4
utF
4-AI16IntWoutF network DNP client
5-AI32Flt
1-AI32IntEvWoutT The “OBJ32” default
1-AI32IntEv
75 Obj32DefltVar_TCP4_DNP 2-AI16IntEvWoutT - - variation of the No.4
WoutT
5-AI32FltEvWoutT network DNP client
Default
No. Settings Range Unit Step Remark
value
1-AO32Int The “OBJ40” default
76 Obj40DefltVar_TCP4_DNP 2-AO16Int 1-AO32Int - - variation of the No.4
3-AO32Flt network DNP client
Access path:
Access path:
Default
No. Settings Range Unit Step Remark
value
Waveform recorded duration before the
1 RecDur_PreTrigDFR 0~1 0.1 s 0.001
trigger element operating
Waveform recorded duration after the
2 RecDur_PostFault 0~10 5 s 0.001
fault happens
The maximum waveform recorded
3 MaxRecDur_PostTrigDFR 0~10 10 s 0.001 duration after the trigger element
operating
2 …… …… ……
These settings are used to definite the label of each GOOSE communication link. The label of
each GOOSE communication link will influence the displayed contents of all reports, settings and
metering that related with each GOOSE communication link.
No Default
Settings Range Unit Step Remark
. value
Conventional Select the time
1 Opt_TimeSyn SAS NoTimeSyn - - synchronization mode of the
NoTimeSyn device.
No Default
Settings Range Unit Step Remark
. value
The local time zone also
2 OffsetHour_UTC -12~12 8 - 1 refered to as the hour offset
hour from UTC .
The offset minute of local time
3 OffsetMinute_UTC 0~60 0 - 1
from UTC.
The IP address of the server
0.0.0.0~ when SNTP time
4 IP_Server_SNTP 0.0.0.0 - -
255.255.255.255 synchronization mode is
selected
The subnet mask of the server
0.0.0.0~ when SNTP time
5 Mask_Server_SNTP 0.0.0.0 - -
0.0.255.255 synchronization mode is
selected
The IP address of the standby
IP_StandbyServer_S 0.0.0.0~ server when SNTP time
6 0.0.0.0 - -
NTP 255.255.255.255 synchronization mode is
selected
The logic setting is used to
Disabled
7 DST.En Disabled - - enable or disable Daylight
Enabled
Saving Time (DST)
It is used to set the minute
offset of DST, i.e. the
8 DST.OffsetMinute 0~255 60 - 1
difference between DST time
and local time
Jan, Feb, Mar,
DST.MonthInYear_St Apr, May, Jun, It is used to set the start month
9 Mar - -
art Jul, Aug, Sep, of DST.
Oct, Nov, Dec
DST.WeekInMonth_S 1st, 2nd, 3nd, It is used to set the start week
10 1st - -
tart 4th, Last of DST.
Sunday, Monday,
11
DST.DayInWeek_Star
Tuesday,
Wednesday, Sunday - -
It is used to set the start day of 9
t DST.
Thursday, Friday,
Saturday
It is used to set the start hour
12 DST.HourInDay_Start 0~23 3 - 1
of DST.
Jan, Feb, Mar,
DST.MonthInYear_En Apr, May, Jun, It is used to set the end month
13 Oct - -
d Jul, Aug, Sep, of DST.
Oct, Nov, Dec
14 DST.WeekInMonth_E 1st, 2nd, 3nd, 1st - - It is used to set the end week
No Default
Settings Range Unit Step Remark
. value
nd 4th, Last of DST.
Sunday, Monday,
Tuesday,
It is used to set the end day of
15 DST.DayInWeek_End Wednesday, Sunday - -
DST.
Thursday, Friday,
Saturday
It is used to set the end hour of
16 DST.HourInDay_End 0~23 9 - 1
DST.
1. [Opt_TimeSyn]
There are three selections for clock synchronization of the device, each selection includes
different time clock synchronization signals shown in following table.
Item Description
IRIG-B (RS-485): IRIG-B via RS-485 differential level.
PPS (RS-485): Pulse per second (PPS) via RS-485 differential level.
IRIG-B (Fiber): IRIG-B via optical-fibre interface.
Conventional PPS (Fiber): Pulse per second (PPS) via optical-fibre interface.
IEEE1588 (Fiber): Clock message via IEEE1588.
PPM (DIN): Pulse per minute (PPM) via the binary input [BI_TimeSyn].
PPS (DIN): Pulse per second (PPS) via the binary input [BI_TimeSyn].
SNTP(PTP): Unicast (point to point) SNTP mode via Ethernet network.
SNTP(BC): Broadcast SNTP mode via Ethernet network.
SAS
IEC103: Clock messages through IEC103 protocol.
MODBUS: Clock messages through MODBUS protocol.
If time synchronization function is not needed for the device, this option can be
NoTimeSyn
selected.
1) When “SAS” is selected, if there is no conventional clock synchronization signal, the device
will not send the alarm signal [Alm_TimeSyn]. When “Conventional” mode is selected, if there
is no conventional clock synchronization signal, “SAS” mode will be enabled automatically
with the alarm signal [Alm_TimeSyn] being issued simultaneously.
9 2) When “NoTimeSyn” mode is selected, the device will not send time synchronization alarm
signal.
The clock message via IEC103 protocol is INVALID when the device
receives the IRIG-B signal through RC-485 port.
Default
No. Settings Range Unit Step Remark
value
The calculated residual current
1 CTS.3I0_Set 0~200 0.1 A 0.001 setting of CT circuit supervision
function.
The calculated residual voltage
2 CTS.3U0_Set 0~200 30 V 0.001 setting of CT circuit supervision
function.
Delay pick-up time setting for CT
3 CTS.t_DPU 0~100 10 s 0.001
circuit failure
Delay drop-off time setting for CT
4 CTS.t_DPO 0~100 10 s 0.001
circuit failure
Disabled Enabling/disabling CT circuit
5 CTS.En Disabled - -
Enabled supervision function.
Positive-sequence voltage setting
6 VTS.U1_Set 0~100 30 V 0.01
of VT circuit supervision function.
Residual voltage setting of VT
7 VTS.3U0_Set 0~100 8 V 0.01
circuit supervision function.
Negative-sequence voltage
8 VTS.U2_Set 0~100 8 V 0.01 setting of VT circuit supervision
function.
Delay pick-up time setting for VT
9 VTS.t_DPU 0~30 1.25 s 0.001
circuit failure
Delay drop-off time setting for VT
10 VTS.t_DDO 0~30 10 s 0.001
circuit failure
Disabled Enabling/disabling VT circuit
11 VTS.En Disabled - -
Enabled supervision function.
Default
No. Settings Range Unit Step Description
value
The low voltage blocking setting
1 50/51P.VCE.Upp 10~100 70 V 0.001 of the voltage control element of
phase overcurrent protection
The negative-sequence voltage
blocking setting of the voltage
2 50/51P.VCE.U2 2~57 8 V 0.001
control element of phase
overcurrent protection
The residual voltage setting (set
according to 3U0) of voltage
3 50/51P.VCE.3U0 2~57 8 V 0.001
control element of phase
overcurrent protection
The relay characteristic angle of
4 50/51P.DIR.RCA -180~179 45 deg 1 the direction control element of
phase overcurrent protection
The relay negative-sequence
50/51P.DIR.RCA_N characteristic angle of the
5 -180~179 45 deg 1
egOC direction control element of
phase overcurrent protection
The minimum boundary of the
50/51P.DIR.phi_Min
6 10~90 90 deg 1 forward direction element of
_Fwd
phase overcurrent protection
The maximum boundary of the
50/51P.DIR.phi_Ma
7 10~90 90 deg 1 forward direction element of
x_Fwd
phase overcurrent protection
9 The minimum boundary of the
50/51P.DIR.phi_Min
8 10~90 90 deg 1 reverse direction element of
_Rev
phase overcurrent protection
The maximum boundary of the
50/51P.DIR.phi_Ma
9 10~90 90 deg 1 reverse direction element of
x_Rev
phase overcurrent protection
Default
No. Settings Range Unit Step Description
value
The voltage polarization mode
for direction control element of
phase overcurrent protection
Upp; Upp: phase-to-phase voltage
50/51P.DIR.Opt_Pol
10 Up; Upp - - polarized
arizedVolt
U1 Up: phase-to-ground voltage
polarized
U1: positive-sequence voltage
polarized
The minimum operating current
setting for the direction control
11 50/51P.DIR.I_Min (0.05~1)In 0.05 - 0.001
element of phase overcurrent
protection
The minimum operating voltage
setting for the direction control
12 50/51P.DIR.U_Min 1~10 4 V 0.001
element of phase overcurrent
protection
Logic setting to determine the
behavior of phase overcurrent
protection when VT circuit
supervision function is enabled
and VT circuit failure happens.
Disabled; Disabled: phase overcurrent
13 50/51P.En_VTS_Blk Disabled - -
Enabled protection will not effected by VT
circuit failure
Enabled: voltage controlled
phase overcurrent protection will
be blocked by VT circuit failure
signal
The percent setting of the
50/51P.HMB.K_Hm
14 0.1~1 0.2 - 0.001 harmonic control element of
2
phase overcurrent protection
The current setting for releasing
9
15 50/51P.HMB.I_Rls 2~150 20 A 0.001 the harmonic control element of
phase overcurrent protection
The setting used to select the
harmonic blocking mode of
PhaseBlk phase overcurrent protection
50/51P.HMB.Opt_Bl
16 CrossBlk PhaseBlk - - PhaseBlk: phase blocking
k
MaxPhaseBlk CrossBlk: cross blocking
MaxPhaseBlk: maximum phase
blocking
Default
No. Settings Range Unit Step Description
value
The current setting of stage 1 of
17 50/51P1.I_Set 0.05~200 15 A 0.001
phase overcurrent protection
The operating time setting of
18 50/51P1.t_Op 0 ~100 0.1 s 0.001 stage 1 of phase overcurrent
protection
The dropout time setting of
19 50/51P1.t_DropOut 0 ~100 0 s 0.001 stage 1 of phase overcurrent
protection
The logic setting for
enabling/disabling the voltage
control element of stage 1 of
phase overcurrent protection
Disabled: stage 1 of phase
50/51P1.En_Volt_Bl Disabled; overcurrent protection is not
20 Disabled - -
k Enabled controlled by the voltage control
element
Enabled: stage 1 of phase
overcurrent protection is
controlled by the voltage control
element
Non_Directional The setting used to select the
Non_Directio
21 50/51P1.Opt_Dir Forward - - directional mode of stage 1 of
nal
Reverse phase overcurrent protection.
The logic setting for
enabling/disabling the harmonic
control element of stage 1 of
phase overcurrent protection
Disabled: stage 1 of phase
50/51P1.En_Hm_Bl Disabled; overcurrent protection is not
22 Disabled - -
k Enabled controlled by the harmonic
control element
Default
No. Settings Range Unit Step Description
value
Enabling stage 1 of phase
overcurrent protection operate
50/51P1.Opt_Trp/Al Trp;
24 Trp - - to trip or alarm.
m Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
ANSILT; inverse-time operation
25 50/51P1.Opt_Curve IECDefTime - -
IECN; characteristic curve of stage 1 of
IECV; phase overcurrent protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 1 of
50/51P1.Opt_Curve
26 DefTime; Inst - - phase overcurrent protection
_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
27 50/51P1.TMS 0.04~ 20 1 - 0.001 stage 1 of phase overcurrent
protection
Default
No. Settings Range Unit Step Description
value
The constant “α” of the
customized inverse-time
0.000
30 50/51P1.Alpha 0.01 ~3 0.02 - operation characteristic of stage
1
1 of phase overcurrent
protection
The constant “C” of the
customized inverse-time
0.000
31 50/51P1.C 0 ~1 0 - operation characteristic of stage
1
1 of phase overcurrent
protection
The current setting of stage 1 of
32 50/51P1.I_Set 0.05~200 15 A 0.001
phase overcurrent protection
The operating time setting of
33 50/51P2.t_Op 0 ~100 0.1 s 0.001 stage 2 of phase overcurrent
protection
The dropout time setting of
34 50/51P2.t_DropOut 0 ~100 0 s 0.001 stage 2 of phase overcurrent
protection
The logic setting for
enabling/disabling the voltage
control element of stage 2 of
phase overcurrent protection
Disabled: stage 2 of phase
50/51P2.En_Volt_Bl Disabled; overcurrent protection is not
35 Disabled - -
k Enabled controlled by the voltage control
element
Enabled: stage 2 of phase
overcurrent protection is
controlled by the voltage control
element
Non_Directional The setting used to select the
Non_Directio
9 36 50/51P2.Opt_Dir Forward
Reverse
nal
- - directional mode of stage 2 of
phase overcurrent protection.
Default
No. Settings Range Unit Step Description
value
The logic setting for
enabling/disabling the harmonic
control element of stage 2 of
phase overcurrent protection
Disabled: stage 2 of phase
50/51P2.En_Hm_Bl Disabled; overcurrent protection is not
37 Disabled - -
k Enabled controlled by the harmonic
control element
Enabled: stage 2 of phase
overcurrent protection is
controlled by the harmonic
control element
The logic setting for
Disabled;
38 50/51P2.En Enabled - - enabling/disabling the stage 2 of
Enabled
phase overcurrent protection
Enabling stage 2 of phase
overcurrent protection operate
50/51P2.Opt_Trp/Al Trp;
39 Trp - - to trip or alarm.
m Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
ANSILT; inverse-time operation
40 50/51P2.Opt_Curve IECDefTime - -
IECN; characteristic curve of stage 2 of
IECV; phase overcurrent protection.
IEC;
IECE;
IECST;
9
IECLT;
IECDefTime;
UserDefine
Default
No. Settings Range Unit Step Description
value
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 2 of
50/51P2.Opt_Curve
41 DefTime; Inst - - phase overcurrent protection
_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
42 50/51P2.TMS 0.04~ 20 1 - 0.001 stage 2 of phase overcurrent
protection
The minimum operating time
43 50/51P2.tmin 0 ~10 0.02 s 0.001 setting of stage 2 of phase
overcurrent protection
The constant “k” of the
customized inverse-time
0.000
44 50/51P2.K 0.001~120 0.14 - operation characteristic of stage
1
2 of phase overcurrent
protection
The constant “α” of the
customized inverse-time
0.000
45 50/51P2.Alpha 0.01 ~3 0.02 - operation characteristic of stage
1
2 of phase overcurrent
protection
The constant “C” of the
customized inverse-time
0.000
46 50/51P2.C 0 ~1 0 - operation characteristic of stage
1
2 of phase overcurrent
protection
The current setting of stage 3 of
47 50/51P3.I_Set 0.05~200 15 A 0.001
phase overcurrent protection
The operating time setting of
Default
No. Settings Range Unit Step Description
value
The logic setting for
enabling/disabling the voltage
control element of stage 3 of
phase overcurrent protection
Disabled: stage 3 of phase
50/51P3.En_Volt_Bl Disabled; overcurrent protection is not
50 Disabled - -
k Enabled controlled by the voltage control
element
Enabled: stage 3 of phase
overcurrent protection is
controlled by the voltage control
element
Non_Directional The setting used to select the
Non_Directio
51 50/51P3.Opt_Dir Forward - - directional mode of stage 3 of
nal
Reverse phase overcurrent protection.
The logic setting for
enabling/disabling the harmonic
control element of stage 3 of
phase overcurrent protection
Disabled: stage 3 of phase
50/51P3.En_Hm_Bl Disabled; overcurrent protection is not
52 Disabled - -
k Enabled controlled by the harmonic
control element
Enabled: stage 3 of phase
overcurrent protection is
controlled by the harmonic
control element
The logic setting for
Disabled;
53 50/51P3.En Enabled - - enabling/disabling the stage 3 of
Enabled
phase overcurrent protection
Enabling stage 3 of phase
54
50/51P3.Opt_Trp/Al Trp;
Trp - -
overcurrent protection operate
to trip or alarm.
9
m Alm
Trp: for tripping purpose
Alm: for alarm purpose
Default
No. Settings Range Unit Step Description
value
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
ANSILT; inverse-time operation
55 50/51P3.Opt_Curve IECDefTime - -
IECN; characteristic curve of stage 3 of
IECV; phase overcurrent protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 3 of
50/51P3.Opt_Curve
56 DefTime; Inst - - phase overcurrent protection
_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
57 50/51P3.TMS 0.04~ 20 1 - 0.001 stage 3 of phase overcurrent
protection
The minimum operating time
58 50/51P3.tmin 0 ~10 0.02 s 0.001 setting of stage 3 of phase
overcurrent protection
The constant “k” of the
customized inverse-time
0.000
9
59 50/51P3.K 0.001~120 0.14 - operation characteristic of stage
1
3 of phase overcurrent
protection
The constant “α” of the
customized inverse-time
0.000
60 50/51P3.Alpha 0.01 ~3 0.02 - operation characteristic of stage
1
3 of phase overcurrent
protection
Default
No. Settings Range Unit Step Description
value
The constant “C” of the
customized inverse-time
0.000
61 50/51P3.C 0 ~1 0 - operation characteristic of stage
1
3 of phase overcurrent
protection
The current setting of stage 4 of
62 50/51P4.I_Set 0.05~200 15 A 0.001
phase overcurrent protection
The operating time setting of
63 50/51P4.t_Op 0 ~100 0.1 s 0.001 stage 4 of phase overcurrent
protection
The dropout time setting of
64 50/51P4.t_DropOut 0 ~100 0 s 0.001 stage 4 of phase overcurrent
protection
The logic setting for
enabling/disabling the voltage
control element of stage 4 of
phase overcurrent protection
Disabled: stage 4 of phase
50/51P4.En_Volt_Bl Disabled; overcurrent protection is not
65 Disabled - -
k Enabled controlled by the voltage control
element
Enabled: stage 4 of phase
overcurrent protection is
controlled by the voltage control
element
Non_Directional The setting used to select the
Non_Directio
66 50/51P4.Opt_Dir Forward - - directional mode of stage 4 of
nal
Reverse phase overcurrent protection.
The logic setting for
enabling/disabling the harmonic
control element of stage 4 of
phase overcurrent protection
Disabled: stage 4 of phase
9
50/51P4.En_Hm_Bl Disabled; overcurrent protection is not
67 Disabled - -
k Enabled controlled by the harmonic
control element
Enabled: stage 4 of phase
overcurrent protection is
controlled by the harmonic
control element
Default
No. Settings Range Unit Step Description
value
The logic setting for
Disabled;
68 50/51P4.En Enabled - - enabling/disabling the stage 4 of
Enabled
phase overcurrent protection
Enabling stage 4 of phase
overcurrent protection operate
50/51P4.Opt_Trp/Al Trp;
69 Trp - - to trip or alarm.
m Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
ANSILT; inverse-time operation
70 50/51P4.Opt_Curve IECDefTime - -
IECN; characteristic curve of stage 4 of
IECV; phase overcurrent protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 4 of
50/51P4.Opt_Curve
71 DefTime; Inst - - phase overcurrent protection
_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
9
The time multiplier setting of
72 50/51P4.TMS 0.04~ 20 1 - 0.001 stage 4 of phase overcurrent
protection
The minimum operating time
73 50/51P4.tmin 0 ~10 0.02 s 0.001 setting of stage 4 of phase
overcurrent protection
The constant “k” of the
customized inverse-time
0.000
74 50/51P4.K 0.001~120 0.14 - operation characteristic of stage
1
4 of phase overcurrent
protection
Default
No. Settings Range Unit Step Description
value
The constant “α” of the
customized inverse-time
0.000
75 50/51P4.Alpha 0.01 ~3 0.02 - operation characteristic of stage
1
4 of phase overcurrent
protection
The constant “C” of the
customized inverse-time
0.000
76 50/51P4.C 0 ~1 0 - operation characteristic of stage
1
4 of phase overcurrent
protection
The current setting of stage 5 of
77 50/51P5.I_Set 0.05~200 15 A 0.001
phase overcurrent protection
The operating time setting of
78 50/51P5.t_Op 0 ~100 0.1 s 0.001 stage 5 of phase overcurrent
protection
The dropout time setting of
79 50/51P5.t_DropOut 0 ~100 0 s 0.001 stage 5 of phase overcurrent
protection
The logic setting for
enabling/disabling the voltage
control element of stage 5 of
phase overcurrent protection
Disabled: stage 5 of phase
50/51P5.En_Volt_Bl Disabled; overcurrent protection is not
80 Disabled - -
k Enabled controlled by the voltage control
element
Enabled: stage 5 of phase
overcurrent protection is
controlled by the voltage control
element
Non_Directional The setting used to select the
Non_Directio
81 50/51P5.Opt_Dir Forward
Reverse
nal
- - directional mode of stage 5 of
phase overcurrent protection.
9
Default
No. Settings Range Unit Step Description
value
The logic setting for
enabling/disabling the harmonic
control element of stage 5 of
phase overcurrent protection
Disabled: stage 5 of phase
50/51P5.En_Hm_Bl Disabled; overcurrent protection is not
82 Disabled - -
k Enabled controlled by the harmonic
control element
Enabled: stage 5 of phase
overcurrent protection is
controlled by the harmonic
control element
The logic setting for
Disabled;
83 50/51P5.En Enabled - - enabling/disabling the stage 5 of
Enabled
phase overcurrent protection
Enabling stage 5 of phase
overcurrent protection operate
50/51P5.Opt_Trp/Al Trp;
84 Trp - - to trip or alarm.
m Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
ANSILT; inverse-time operation
85 50/51P5.Opt_Curve IECDefTime - -
IECN; characteristic curve of stage 5 of
IECV; phase overcurrent protection.
IEC;
9
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
Default
No. Settings Range Unit Step Description
value
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 5 of
50/51P5.Opt_Curve
86 DefTime; Inst - - phase overcurrent protection
_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
87 50/51P5.TMS 0.04~ 20 1 - 0.001 stage 5 of phase overcurrent
protection
The minimum operating time
88 50/51P5.tmin 0 ~10 0.02 s 0.001 setting of stage 5 of phase
overcurrent protection
The constant “k” of the
customized inverse-time
0.000
89 50/51P5.K 0.001~120 0.14 - operation characteristic of stage
1
5 of phase overcurrent
protection
The constant “α” of the
customized inverse-time
0.000
90 50/51P5.Alpha 0.01 ~3 0.02 - operation characteristic of stage
1
5 of phase overcurrent
protection
The constant “C” of the
customized inverse-time
0.000
91 50/51P5.C 0 ~1 0 - operation characteristic of stage
1
5 of phase overcurrent
protection
The current setting of stage 6 of
92 50/51P6.I_Set 0.05~200 15 A 0.001
phase overcurrent protection
The operating time setting of
93 50/51P6.t_Op 0 ~100 0.1 s 0.001 stage 6 of phase overcurrent
protection
9
The dropout time setting of
94 50/51P6.t_DropOut 0 ~100 0 s 0.001 stage 6 of phase overcurrent
protection
Default
No. Settings Range Unit Step Description
value
The logic setting for
enabling/disabling the voltage
control element of stage 6 of
phase overcurrent protection
Disabled: stage 6 of phase
50/51P6.En_Volt_Bl Disabled; overcurrent protection is not
95 Disabled - -
k Enabled controlled by the voltage control
element
Enabled: stage 6 of phase
overcurrent protection is
controlled by the voltage control
element
Non_Directional The setting used to select the
Non_Directio
96 50/51P6.Opt_Dir Forward - - directional mode of stage 6 of
nal
Reverse phase overcurrent protection.
The logic setting for
enabling/disabling the harmonic
control element of stage 6 of
phase overcurrent protection
Disabled: stage 6 of phase
50/51P6.En_Hm_Bl Disabled; overcurrent protection is not
97 Disabled - -
k Enabled controlled by the harmonic
control element
Enabled: stage 6 of phase
overcurrent protection is
controlled by the harmonic
control element
The logic setting for
Disabled;
98 50/51P6.En Enabled - - enabling/disabling the stage 6 of
Enabled
phase overcurrent protection
Enabling stage 6 of phase
9
overcurrent protection operate
50/51P6.Opt_Trp/Al Trp;
99 Trp - - to trip or alarm.
m Alm
Trp: for tripping purpose
Alm: for alarm purpose
Default
No. Settings Range Unit Step Description
value
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
ANSILT; inverse-time operation
100 50/51P6.Opt_Curve IECDefTime - -
IECN; characteristic curve of stage 6 of
IECV; phase overcurrent protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 6 of
50/51P6.Opt_Curve
101 DefTime; Inst - - phase overcurrent protection
_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
102 50/51P6.TMS 0.04~ 20 1 - 0.001 stage 6 of phase overcurrent
protection
The minimum operating time
103 50/51P6.tmin 0 ~10 0.02 s 0.001 setting of stage 6 of phase
overcurrent protection
The constant “k” of the
customized inverse-time
0.000
104 50/51P6.K 0.001~120 0.14 -
1
operation characteristic of stage
6 of phase overcurrent
9
protection
The constant “α” of the
customized inverse-time
0.000
105 50/51P6.Alpha 0.01 ~3 0.02 - operation characteristic of stage
1
6 of phase overcurrent
protection
Default
No. Settings Range Unit Step Description
value
The constant “C” of the
customized inverse-time
0.000
106 50/51P6.C 0 ~1 0 - operation characteristic of stage
1
6 of phase overcurrent
protection
Default Uni
No. Settings Range Step Description
value t
The relay characteristic angle
of the direction control
1 50/51G.DIR.RCA -180~179 45 deg 1
element of earth fault
overcurrent protection
The minimum boundary of the
50/51G.DIR.phi_Min_ forward direction element of
2 10~90 90 deg 1
Fwd earth fault overcurrent
protection
The maximum boundary of the
50/51G.DIR.phi_Max_ forward direction element of
3 10~90 90 deg 1
Fwd earth fault overcurrent
protection
The minimum boundary of the
50/51G.DIR.phi_Min_ reverse direction element of
4 10~90 90 deg 1
Rev earth fault overcurrent
protection
The maximum boundary of the
50/51G.DIR.phi_Max_ reverse direction element of
9 5
Rev
10~90 90 deg 1
earth fault overcurrent
protection
The minimum operating
current setting for the direction
6 50/51G.DIR.I_Min (0.05~1)In 0.05 - 0.001
control element of earth fault
overcurrent protection
The minimum operating
voltage setting for the direction
7 50/51G.DIR.U_Min 1~10 4 V 0.001
control element of earth fault
overcurrent protection
Default Uni
No. Settings Range Step Description
value t
Logic setting to determine the
behavior of earth fault
overcurrent protection when
VT circuit supervision function
is enabled and VT circuit
failure happens.
Disabled;
8 50/51G.En_VTS_Blk Disabled - - Disabled: earth fault
Enabled
overcurrent protection will not
effected by VT circuit failure
Enabled: voltage controlled
earth fault overcurrent
protection will be blocked by
VT circuit failure signal
The percent setting of the
harmonic control element of
9 50/51G.HMB.K_Hm2 0.1~1 0.2 - 0.001
earth fault overcurrent
protection
The current setting for
releasing the harmonic control
10 50/51G.HMB.I_Rls 2~150 20 A 0.001
element of earth fault
overcurrent protection
The setting used to select the
residual current that used for
stage 1 of earth fault
Ext; overcurrent protection
11 50/51G1.Opt_3I0 Ext - -
Cal Ext: the measured residual
current
Cal: the calculated residual
current
The current setting of stage 1
12 50/51G1.3I0_Set 0.05~200 15 A 0.001 of earth fault overcurrent
protection
The operating time setting of
9
13 50/51G1.t_Op 0 ~100 0.1 s 0.001 stage 1 of earth fault
overcurrent protection
The dropout time setting of
14 50/51G1.t_DropOut 0 ~100 0 s 0.001 stage 1 of earth fault
overcurrent protection
Default Uni
No. Settings Range Step Description
value t
The setting used to select the
directional mode of stage 1 of
Non_Direction
earth fault overcurrent
al; Non_Directio
15 50/51G1.Opt_Dir - - protection.
Forward; nal
1: no direction;
Reverse
2: forward direction;
3: reverse direction.
The logic setting for
enabling/disabling the
harmonic control element of
the stage 1 of earth fault
overcurrent protection
Disabled: stage 1 of earth fault
Disabled;
16 50/51G1.En_Hm_Blk Disabled - - overcurrent protection is not
Enabled
controlled by the harmonic
control element
Enabled: stage 1 of earth fault
overcurrent protection is
controlled by the harmonic
control element
The logic setting for
Disabled; enabling/disabling the stage 1
17 50/51G1.En Enabled - -
Enabled of earth fault overcurrent
protection
Enabling stage 1 earth fault
overcurrent protection operate
Trp;
18 50/51G1.Opt_Trp/Alm Trp - - to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose
Default Uni
No. Settings Range Step Description
value t
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
The setting for selecting the
ANSILTV;
inverse-time operation
ANSILT;
19 50/51G1.Opt_Curve IECDefTime - - characteristic curve of stage 1
IECN;
of earth fault overcurrent
IECV;
protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
characteristic curve of stage 1
Inst;
50/51G1.Opt_Curve_ of earth fault overcurrent
20 DefTime; Inst - -
DropOut protection
IDMT
Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
21 50/51G1.TMS 0.04~ 20 1 - 0.001 stage 1 of earth fault
overcurrent protection
The minimum operating time
22 50/51G1.tmin 0 ~10 0.02 s 0.001 setting of stage 1 of earth fault
overcurrent protection
The constant “k” of the
Default Uni
No. Settings Range Step Description
value t
The constant “C” of the
customized inverse-time
25 50/51G1.C 0 ~1 0 - 0.0001 operation characteristic of
stage 1 of earth fault
overcurrent protection
The setting used to select the
residual current that used for
stage 2 of earth fault
Ext; overcurrent protection
26 50/51G2.Opt_3I0 Ext - -
Cal Ext: the measured residual
current
Cal: the calculated residual
current
The current setting of stage 2
27 50/51G2.3I0_Set 0.05~200 15 A 0.001 of earth fault overcurrent
protection
The operating time setting of
28 50/51G2.t_Op 0 ~100 0.1 s 0.001 stage 2 of earth fault
overcurrent protection
The dropout time setting of
29 50/51G2.t_DropOut 0 ~100 0 s 0.001 stage 2 of earth fault
overcurrent protection
The setting used to select the
directional mode of stage 2 of
Non_Direction
earth fault overcurrent
al; Non_Directio
30 50/51G2.Opt_Dir - - protection.
Forward; nal
1: no direction;
Reverse
2: forward direction;
3: reverse direction.
The logic setting for
enabling/disabling the
Default Uni
No. Settings Range Step Description
value t
The logic setting for
Disabled; enabling/disabling the stage 2
32 50/51G2.En Enabled - -
Enabled of earth fault overcurrent
protection
Enabling stage 2 earth fault
overcurrent protection operate
Trp;
33 50/51G2.Opt_Trp/Alm Trp - - to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
The setting for selecting the
ANSILTV;
inverse-time operation
ANSILT;
34 50/51G2.Opt_Curve IECDefTime - - characteristic curve of stage 2
IECN;
of earth fault overcurrent
IECV;
protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
characteristic curve of stage 2
Inst;
50/51G2.Opt_Curve_ of earth fault overcurrent
35 DefTime; Inst - -
DropOut protection
IDMT
Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
9
The time multiplier setting of
36 50/51G2.TMS 0.04~ 20 1 - 0.001 stage 2 of earth fault
overcurrent protection
The minimum operating time
37 50/51G2.tmin 0 ~10 0.02 s 0.001 setting of stage 2 of earth fault
overcurrent protection
Default Uni
No. Settings Range Step Description
value t
The constant “k” of the
customized inverse-time
38 50/51G2.K 0.001~120 0.14 - 0.0001 operation characteristic of
stage 2 of earth fault
overcurrent protection
The constant “α” of the
customized inverse-time
39 50/51G2.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of
stage 2 of earth fault
overcurrent protection
The constant “C” of the
customized inverse-time
40 50/51G2.C 0 ~1 0 - 0.0001 operation characteristic of
stage 2 of earth fault
overcurrent protection
The setting used to select the
residual current that used for
stage 3 of earth fault
Ext; overcurrent protection
41 50/51G3.Opt_3I0 Ext - -
Cal Ext: the measured residual
current
Cal: the calculated residual
current
The current setting of stage 3
42 50/51G3.3I0_Set 0.05~200 15 A 0.001 of earth fault overcurrent
protection
The operating time setting of
43 50/51G3.t_Op 0 ~100 0.1 s 0.001 stage 3 of earth fault
overcurrent protection
The dropout time setting of
44 50/51G3.t_DropOut 0 ~100 0 s 0.001 stage 3 of earth fault
9 overcurrent protection
The setting used to select the
directional mode of stage 3 of
Non_Direction
earth fault overcurrent
al; Non_Directio
45 50/51G3.Opt_Dir - - protection.
Forward; nal
1: no direction;
Reverse
2: forward direction;
3: reverse direction.
Default Uni
No. Settings Range Step Description
value t
The logic setting for
enabling/disabling the
harmonic control element of
the stage 3 of earth fault
overcurrent protection
Disabled: stage 3 of earth fault
Disabled;
46 50/51G3.En_Hm_Blk Disabled - - overcurrent protection is not
Enabled
controlled by the harmonic
control element
Enabled: stage 3 of earth fault
overcurrent protection is
controlled by the harmonic
control element
The logic setting for
Disabled; enabling/disabling the stage 3
47 50/51G3.En Enabled - -
Enabled of earth fault overcurrent
protection
Enabling stage 3 earth fault
overcurrent protection operate
Trp;
48 50/51G3.Opt_Trp/Alm Trp - - to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
The setting for selecting the
ANSILTV;
inverse-time operation
ANSILT;
49 50/51G3.Opt_Curve IECDefTime - - characteristic curve of stage 3
IECN;
of earth fault overcurrent
IECV;
IEC;
protection. 9
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
Default Uni
No. Settings Range Step Description
value t
The setting for selecting the
inverse-time dropout
characteristic curve of stage 3
Inst;
50/51G3.Opt_Curve_ of earth fault overcurrent
50 DefTime; Inst - -
DropOut protection
IDMT
Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
51 50/51G3.TMS 0.04~ 20 1 - 0.001 stage 3 of earth fault
overcurrent protection
The minimum operating time
52 50/51G3.tmin 0 ~10 0.02 s 0.001 setting of stage 3 of earth fault
overcurrent protection
The constant “k” of the
customized inverse-time
53 50/51G3.K 0.001~120 0.14 - 0.0001 operation characteristic of
stage 3 of earth fault
overcurrent protection
The constant “α” of the
customized inverse-time
54 50/51G3.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of
stage 3 of earth fault
overcurrent protection
The constant “C” of the
customized inverse-time
55 50/51G3.C 0 ~1 0 - 0.0001 operation characteristic of
stage 3 of earth fault
overcurrent protection
The setting used to select the
residual current that used for
9 Ext;
stage 4 of
overcurrent protection
earth fault
56 50/51G4.Opt_3I0 Ext - -
Cal Ext: the measured residual
current
Cal: the calculated residual
current
The current setting of stage 4
57 50/51G4.3I0_Set 0.05~200 15 A 0.001 of earth fault overcurrent
protection
Default Uni
No. Settings Range Step Description
value t
The operating time setting of
58 50/51G4.t_Op 0 ~100 0.1 s 0.001 stage 4 of earth fault
overcurrent protection
The dropout time setting of
59 50/51G4.t_DropOut 0 ~100 0 s 0.001 stage 4 of earth fault
overcurrent protection
The setting used to select the
directional mode of stage 4 of
Non_Direction
earth fault overcurrent
al; Non_Directio
60 50/51G4.Opt_Dir - - protection.
Forward; nal
1: no direction;
Reverse
2: forward direction;
3: reverse direction.
The logic setting for
enabling/disabling the
harmonic control element of
the stage 4 of earth fault
overcurrent protection
Disabled: stage 4 of earth fault
Disabled;
61 50/51G4.En_Hm_Blk Disabled - - overcurrent protection is not
Enabled
controlled by the harmonic
control element
Enabled: stage 4 of earth fault
overcurrent protection is
controlled by the harmonic
control element
The logic setting for
Disabled; enabling/disabling the stage 4
62 50/51G4.En Enabled - -
Enabled of earth fault overcurrent
protection
Enabling stage 4 earth fault
63 50/51G4.Opt_Trp/Alm
Trp;
Trp - -
overcurrent protection operate
to trip or alarm.
9
Alm
Trp: for tripping purpose
Alm: for alarm purpose
Default Uni
No. Settings Range Step Description
value t
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
The setting for selecting the
ANSILTV;
inverse-time operation
ANSILT;
64 50/51G4.Opt_Curve IECDefTime - - characteristic curve of stage 4
IECN;
of earth fault overcurrent
IECV;
protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
characteristic curve of stage 4
Inst;
50/51G4.Opt_Curve_ of earth fault overcurrent
65 DefTime; Inst - -
DropOut protection
IDMT
Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
66 50/51G4.TMS 0.04~ 20 1 - 0.001 stage 4 of earth fault
overcurrent protection
The minimum operating time
67 50/51G4.tmin 0 ~10 0.02 s 0.001 setting of stage 4 of earth fault
overcurrent protection
The constant “k” of the
9
customized inverse-time
68 50/51G4.K 0.001~120 0.14 - 0.0001 operation characteristic of
stage 4 of earth fault
overcurrent protection
The constant “α” of the
customized inverse-time
69 50/51G4.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of
stage 4 of earth fault
overcurrent protection
Default Uni
No. Settings Range Step Description
value t
The constant “C” of the
customized inverse-time
70 50/51G4.C 0 ~1 0 - 0.0001 operation characteristic of
stage 4 of earth fault
overcurrent protection
The setting used to select the
residual current that used for
stage 5 of earth fault
Ext; overcurrent protection
71 50/51G5.Opt_3I0 Ext - -
Cal Ext: the measured residual
current
Cal: the calculated residual
current
The current setting of stage 5
72 50/51G5.3I0_Set 0.05~200 15 A 0.001 of earth fault overcurrent
protection
The operating time setting of
73 50/51G5.t_Op 0 ~100 0.1 s 0.001 stage 5 of earth fault
overcurrent protection
The dropout time setting of
74 50/51G5.t_DropOut 0 ~100 0 s 0.001 stage 5 of earth fault
overcurrent protection
The setting used to select the
directional mode of stage 5 of
Non_Direction
earth fault overcurrent
al; Non_Directio
75 50/51G5.Opt_Dir - - protection.
Forward; nal
1: no direction;
Reverse
2: forward direction;
3: reverse direction.
The logic setting for
enabling/disabling the
harmonic control element of
the stage 5 of earth fault
9
overcurrent protection
Disabled: stage 5 of earth fault
Disabled;
76 50/51G5.En_Hm_Blk Disabled - - overcurrent protection is not
Enabled
controlled by the harmonic
control element
Enabled: stage 5 of earth fault
overcurrent protection is
controlled by the harmonic
control element
Default Uni
No. Settings Range Step Description
value t
The logic setting for
Disabled; enabling/disabling the stage 5
77 50/51G5.En Enabled - -
Enabled of earth fault overcurrent
protection
Enabling stage 5 earth fault
overcurrent protection operate
Trp;
78 50/51G5.Opt_Trp/Alm Trp - - to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
The setting for selecting the
ANSILTV;
inverse-time operation
ANSILT;
79 50/51G5.Opt_Curve IECDefTime - - characteristic curve of stage 5
IECN;
of earth fault overcurrent
IECV;
protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
characteristic curve of stage 5
Inst;
50/51G5.Opt_Curve_ of earth fault overcurrent
80 DefTime; Inst - -
DropOut protection
IDMT
Inst: instantaneous dropout
9
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
81 50/51G5.TMS 0.04~ 20 1 - 0.001 stage 5 of earth fault
overcurrent protection
The minimum operating time
82 50/51G5.tmin 0 ~10 0.02 s 0.001 setting of stage 5 of earth fault
overcurrent protection
Default Uni
No. Settings Range Step Description
value t
The constant “k” of the
customized inverse-time
83 50/51G5.K 0.001~120 0.14 - 0.0001 operation characteristic of
stage 5 of earth fault
overcurrent protection
The constant “α” of the
customized inverse-time
84 50/51G5.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of
stage 5 of earth fault
overcurrent protection
The constant “C” of the
customized inverse-time
85 50/51G5.C 0 ~1 0 - 0.0001 operation characteristic of
stage 5 of earth fault
overcurrent protection
The setting used to select the
residual current that used for
stage 6 of earth fault
Ext; overcurrent protection
86 50/51G6.Opt_3I0 Ext - -
Cal Ext: the measured residual
current
Cal: the calculated residual
current
The current setting of stage 6
87 50/51G6.3I0_Set 0.05~200 15 A 0.001 of earth fault overcurrent
protection
The operating time setting of
88 50/51G6.t_Op 0 ~100 0.1 s 0.001 stage 6 of earth fault
overcurrent protection
The dropout time setting of
89 50/51G6.t_DropOut 0 ~100 0 s 0.001 stage 6 of earth fault
overcurrent protection
The setting used to select the
9
directional mode of stage 6 of
Non_Direction
earth fault overcurrent
al; Non_Directio
90 50/51G6.Opt_Dir - - protection.
Forward; nal
1: no direction;
Reverse
2: forward direction;
3: reverse direction.
Default Uni
No. Settings Range Step Description
value t
The logic setting for
enabling/disabling the
harmonic control element of
the stage 6 of earth fault
overcurrent protection
Disabled: stage 6 of earth fault
Disabled;
91 50/51G6.En_Hm_Blk Disabled - - overcurrent protection is not
Enabled
controlled by the harmonic
control element
Enabled: stage 6 of earth fault
overcurrent protection is
controlled by the harmonic
control element
The logic setting for
Disabled; enabling/disabling the stage 6
92 50/51G6.En Enabled - -
Enabled of earth fault overcurrent
protection
Enabling stage 6 earth fault
overcurrent protection operate
Trp;
93 50/51G6.Opt_Trp/Alm Trp - - to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
The setting for selecting the
ANSILTV;
inverse-time operation
ANSILT;
94 50/51G6.Opt_Curve IECDefTime - - characteristic curve of stage 6
IECN;
of earth fault overcurrent
9
IECV;
protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
Default Uni
No. Settings Range Step Description
value t
The setting for selecting the
inverse-time dropout
characteristic curve of stage 6
Inst;
50/51G6.Opt_Curve_ of earth fault overcurrent
95 DefTime; Inst - -
DropOut protection
IDMT
Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
96 50/51G6.TMS 0.04~ 20 1 - 0.001 stage 6 of earth fault
overcurrent protection
The minimum operating time
97 50/51G6.tmin 0 ~10 0.02 s 0.001 setting of stage 6 of earth fault
overcurrent protection
The constant “k” of the
customized inverse-time
98 50/51G6.K 0.001~120 0.14 - 0.0001 operation characteristic of
stage 6 of earth fault
overcurrent protection
The constant “α” of the
customized inverse-time
99 50/51G6.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of
stage 6 of earth fault
overcurrent protection
The constant “C” of the
customized inverse-time
100 50/51G6.C 0 ~1 0 - 0.0001 operation characteristic of
stage 6 of earth fault
overcurrent protection
Default
No. Settings Range Unit Step Description
value
The current setting of
stage 1 of another group of
1 A.50/51G1.3I0_Set 0.05~200 15 A 0.001
earth fault overcurrent
protection
Default
No. Settings Range Unit Step Description
value
The operating time setting
of stage 1 of another group
2 A.50/51G1.t_Op 0 ~100 0.1 s 0.001
of earth fault overcurrent
protection
The dropout time setting of
stage 1 of another group of
3 A.50/51G1.t_DropOut 0 ~100 0 s 0.001
earth fault overcurrent
protection
The logic setting for
enabling/disabling the
Disabled;
4 A.50/51G1.En Enabled - - stage 1 of another group of
Enabled
earth fault overcurrent
protection
Enabling stage 1 of
another group of earth fault
Trp; overcurrent protection
5 A.50/51G1.Opt_Trp/Alm Trp - -
Alm operate to trip or alarm.
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE; The setting for selecting
ANSILTV; the inverse-time operation
ANSILT; characteristic curve of
6 A.50/51G1.Opt_Curve IECDefTime - -
IECN; stage 1 of another group of
IECV; earth fault overcurrent
IEC; protection.
IECE;
9
IECST;
IECLT;
IECDefTime;
UserDefine
Default
No. Settings Range Unit Step Description
value
The setting for selecting
the inverse-time dropout
characteristic curve of
stage 1 of another group of
Inst; earth fault overcurrent
A.50/51G1.Opt_Curve_D
7 DefTime; Inst - - protection
ropOut
IDMT Inst: instantaneous
dropout
DefTime: definite-time
dropout
IDMT: inverse-time dropout
The time multiplier setting
of stage 1 of another group
8 A.50/51G1.TMS 0.04~ 20 1 - 0.001
of earth fault overcurrent
protection
The minimum operating
time setting of stage 1 of
9 A.50/51G1.tmin 0 ~10 0.02 s 0.001
another group of earth fault
overcurrent protection
The constant “k” of the
customized inverse-time
operation characteristic of
10 A.50/51G1.K 0.001~120 0.14 - 0.0001
stage 1 of another group of
earth fault overcurrent
protection
The constant “α” of the
customized inverse-time
operation characteristic of
11 A.50/51G1.Alpha 0.01 ~3 0.02 - 0.0001
stage 1 of another group of
earth fault overcurrent
protection
The constant “C” of the
customized inverse-time
9
operation characteristic of
12 A.50/51G1.C 0 ~1 0 - 0.0001
stage 1 of another group of
earth fault overcurrent
protection
The current setting of
stage 2 of another group of
13 A.50/51G2.3I0_Set 0.05~200 15 A 0.001
earth fault overcurrent
protection
Default
No. Settings Range Unit Step Description
value
The operating time setting
of stage 2 of another group
14 A.50/51G2.t_Op 0 ~100 0.1 s 0.001
of earth fault overcurrent
protection
The dropout time setting of
stage 2 of another group of
15 A.50/51G2.t_DropOut 0 ~100 0 s 0.001
earth fault overcurrent
protection
The logic setting for
enabling/disabling the
Disabled;
16 A.50/51G2.En Enabled - - stage 2 of another group of
Enabled
earth fault overcurrent
protection
Enabling stage 2 of
another group of earth fault
Trp; overcurrent protection
17 A.50/51G2.Opt_Trp/Alm Trp - -
Alm operate to trip or alarm.
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE; The setting for selecting
ANSILTV; the inverse-time operation
ANSILT; characteristic curve of
18 A.50/51G2.Opt_Curve IECDefTime - -
IECN; stage 2 of another group of
IECV; earth fault overcurrent
IEC; protection.
IECE;
9
IECST;
IECLT;
IECDefTime;
UserDefine
Default
No. Settings Range Unit Step Description
value
The setting for selecting
the inverse-time dropout
characteristic curve of
stage 2 of another group of
Inst; earth fault overcurrent
A.50/51G2.Opt_Curve_D
19 DefTime; Inst - - protection
ropOut
IDMT Inst: instantaneous
dropout
DefTime: definite-time
dropout
IDMT: inverse-time dropout
The time multiplier setting
of stage 2 of another group
20 A.50/51G2.TMS 0.04~ 20 1 - 0.001
of earth fault overcurrent
protection
The minimum operating
time setting of stage 2 of
21 A.50/51G2.tmin 0 ~10 0.02 s 0.001
another group of earth fault
overcurrent protection
The constant “k” of the
customized inverse-time
operation characteristic of
22 A.50/51G2.K 0.001~120 0.14 - 0.0001
stage 2 of another group of
earth fault overcurrent
protection
The constant “α” of the
customized inverse-time
operation characteristic of
23 A.50/51G2.Alpha 0.01 ~3 0.02 - 0.0001
stage 2 of another group of
earth fault overcurrent
protection
The constant “C” of the
customized inverse-time
9
operation characteristic of
24 A.50/51G2.C 0 ~1 0 - 0.0001
stage 2 of another group of
earth fault overcurrent
protection
The current setting of
stage 3 of another group of
25 A.50/51G3.3I0_Set 0.05~200 15 A 0.001
earth fault overcurrent
protection
Default
No. Settings Range Unit Step Description
value
The operating time setting
of stage 3 of another group
26 A.50/51G3.t_Op 0 ~100 0.1 s 0.001
of earth fault overcurrent
protection
The dropout time setting of
stage 3 of another group of
27 A.50/51G3.t_DropOut 0 ~100 0 s 0.001
earth fault overcurrent
protection
The logic setting for
enabling/disabling the
Disabled;
28 A.50/51G3.En Enabled - - stage 3 of another group of
Enabled
earth fault overcurrent
protection
Enabling stage 3 of
another group of earth fault
Trp; overcurrent protection
29 A.50/51G3.Opt_Trp/Alm Trp - -
Alm operate to trip or alarm.
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE; The setting for selecting
ANSILTV; the inverse-time operation
ANSILT; characteristic curve of
30 A.50/51G3.Opt_Curve IECDefTime - -
IECN; stage 3 of another group of
IECV; earth fault overcurrent
IEC; protection.
IECE;
9
IECST;
IECLT;
IECDefTime;
UserDefine
Default
No. Settings Range Unit Step Description
value
The setting for selecting
the inverse-time dropout
characteristic curve of
stage 3 of another group of
Inst; earth fault overcurrent
A.50/51G3.Opt_Curve_D
31 DefTime; Inst - - protection
ropOut
IDMT Inst: instantaneous
dropout
DefTime: definite-time
dropout
IDMT: inverse-time dropout
The time multiplier setting
of stage 3 of another group
32 A.50/51G3.TMS 0.04~ 20 1 - 0.001
of earth fault overcurrent
protection
The minimum operating
time setting of stage 3 of
33 A.50/51G3.tmin 0 ~10 0.02 s 0.001
another group of earth fault
overcurrent protection
The constant “k” of the
customized inverse-time
operation characteristic of
34 A.50/51G3.K 0.001~120 0.14 - 0.0001
stage 3 of another group of
earth fault overcurrent
protection
The constant “α” of the
customized inverse-time
operation characteristic of
35 A.50/51G3.Alpha 0.01 ~3 0.02 - 0.0001
stage 3 of another group of
earth fault overcurrent
protection
The constant “C” of the
customized inverse-time
9
operation characteristic of
36 A.50/51G3.C 0 ~1 0 - 0.0001
stage 3 of another group of
earth fault overcurrent
protection
The current setting of
stage 4 of another group of
37 A.50/51G4.3I0_Set 0.05~200 15 A 0.001
earth fault overcurrent
protection
Default
No. Settings Range Unit Step Description
value
The operating time setting
of stage 4 of another group
38 A.50/51G4.t_Op 0 ~100 0.1 s 0.001
of earth fault overcurrent
protection
The dropout time setting of
stage 4 of another group of
39 A.50/51G4.t_DropOut 0 ~100 0 s 0.001
earth fault overcurrent
protection
The logic setting for
enabling/disabling the
Disabled;
40 A.50/51G4.En Enabled - - stage 4 of another group of
Enabled
earth fault overcurrent
protection
Enabling stage 4 of
another group of earth fault
Trp; overcurrent protection
41 A.50/51G4.Opt_Trp/Alm Trp - -
Alm operate to trip or alarm.
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE; The setting for selecting
ANSILTV; the inverse-time operation
ANSILT; characteristic curve of
42 A.50/51G4.Opt_Curve IECDefTime - -
IECN; stage 4 of another group of
IECV; earth fault overcurrent
IEC; protection.
IECE;
9
IECST;
IECLT;
IECDefTime;
UserDefine
Default
No. Settings Range Unit Step Description
value
The setting for selecting
the inverse-time dropout
characteristic curve of
stage 4 of another group of
Inst; earth fault overcurrent
A.50/51G4.Opt_Curve_D
43 DefTime; Inst - - protection
ropOut
IDMT Inst: instantaneous
dropout
DefTime: definite-time
dropout
IDMT: inverse-time dropout
The time multiplier setting
of stage 4 of another group
44 A.50/51G4.TMS 0.04~ 20 1 - 0.001
of earth fault overcurrent
protection
The minimum operating
time setting of stage 4 of
45 A.50/51G4.tmin 0 ~10 0.02 s 0.001
another group of earth fault
overcurrent protection
The constant “k” of the
customized inverse-time
operation characteristic of
46 A.50/51G4.K 0.001~120 0.14 - 0.0001
stage 4 of another group of
earth fault overcurrent
protection
The constant “α” of the
customized inverse-time
operation characteristic of
47 A.50/51G4.Alpha 0.01 ~3 0.02 - 0.0001
stage 4 of another group of
earth fault overcurrent
protection
The constant “C” of the
customized inverse-time
9
operation characteristic of
48 A.50/51G4.C 0 ~1 0 - 0.0001
stage 4 of another group of
earth fault overcurrent
protection
The current setting of
stage 5 of another group of
49 A.50/51G5.3I0_Set 0.05~200 15 A 0.001
earth fault overcurrent
protection
Default
No. Settings Range Unit Step Description
value
The operating time setting
of stage 5 of another group
50 A.50/51G5.t_Op 0 ~100 0.1 s 0.001
of earth fault overcurrent
protection
The dropout time setting of
stage 5 of another group of
51 A.50/51G5.t_DropOut 0 ~100 0 s 0.001
earth fault overcurrent
protection
The logic setting for
enabling/disabling the
Disabled;
52 A.50/51G5.En Enabled - - stage 5 of another group of
Enabled
earth fault overcurrent
protection
Enabling stage 5 of
another group of earth fault
Trp; overcurrent protection
53 A.50/51G5.Opt_Trp/Alm Trp - -
Alm operate to trip or alarm.
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE; The setting for selecting
ANSILTV; the inverse-time operation
ANSILT; characteristic curve of
54 A.50/51G5.Opt_Curve IECDefTime - -
IECN; stage 5 of another group of
IECV; earth fault overcurrent
IEC; protection.
IECE;
9
IECST;
IECLT;
IECDefTime;
UserDefine
Default
No. Settings Range Unit Step Description
value
The setting for selecting
the inverse-time dropout
characteristic curve of
stage 5 of another group of
Inst; earth fault overcurrent
A.50/51G5.Opt_Curve_D
55 DefTime; Inst - - protection
ropOut
IDMT Inst: instantaneous
dropout
DefTime: definite-time
dropout
IDMT: inverse-time dropout
The time multiplier setting
of stage 5 of another group
56 A.50/51G5.TMS 0.04~ 20 1 - 0.001
of earth fault overcurrent
protection
The minimum operating
time setting of stage 5 of
57 A.50/51G5.tmin 0 ~10 0.02 s 0.001
another group of earth fault
overcurrent protection
The constant “k” of the
customized inverse-time
operation characteristic of
58 A.50/51G5.K 0.001~120 0.14 - 0.0001
stage 5 of another group of
earth fault overcurrent
protection
The constant “α” of the
customized inverse-time
operation characteristic of
59 A.50/51G5.Alpha 0.01 ~3 0.02 - 0.0001
stage 5 of another group of
earth fault overcurrent
protection
The constant “C” of the
customized inverse-time
9
operation characteristic of
60 A.50/51G5.C 0 ~1 0 - 0.0001
stage 5 of another group of
earth fault overcurrent
protection
The current setting of
stage 6 of another group of
61 A.50/51G6.3I0_Set 0.05~200 15 A 0.001
earth fault overcurrent
protection
Default
No. Settings Range Unit Step Description
value
The operating time setting
of stage 6 of another group
62 A.50/51G6.t_Op 0 ~100 0.1 s 0.001
of earth fault overcurrent
protection
The dropout time setting of
stage 6 of another group of
63 A.50/51G6.t_DropOut 0 ~100 0 s 0.001
earth fault overcurrent
protection
The logic setting for
enabling/disabling the
Disabled;
64 A.50/51G6.En Enabled - - stage 6 of another group of
Enabled
earth fault overcurrent
protection
Enabling stage 6 of
another group of earth fault
Trp; overcurrent protection
65 A.50/51G6.Opt_Trp/Alm Trp - -
Alm operate to trip or alarm.
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE; The setting for selecting
ANSILTV; the inverse-time operation
ANSILT; characteristic curve of
66 A.50/51G6.Opt_Curve IECDefTime - -
IECN; stage 6 of another group of
IECV; earth fault overcurrent
IEC; protection.
IECE;
9
IECST;
IECLT;
IECDefTime;
UserDefine
Default
No. Settings Range Unit Step Description
value
The setting for selecting
the inverse-time dropout
characteristic curve of
stage 6 of another group of
Inst; earth fault overcurrent
A.50/51G6.Opt_Curve_D
67 DefTime; Inst - - protection
ropOut
IDMT Inst: instantaneous
dropout
DefTime: definite-time
dropout
IDMT: inverse-time dropout
The time multiplier setting
of stage 6 of another group
68 A.50/51G6.TMS 0.04~ 20 1 - 0.001
of earth fault overcurrent
protection
The minimum operating
time setting of stage 6 of
69 A.50/51G6.tmin 0 ~10 0.02 s 0.001
another group of earth fault
overcurrent protection
The constant “k” of the
customized inverse-time
operation characteristic of
70 A.50/51G6.K 0.001~120 0.14 - 0.0001
stage 6 of another group of
earth fault overcurrent
protection
The constant “α” of the
customized inverse-time
operation characteristic of
71 A.50/51G6.Alpha 0.01 ~3 0.02 - 0.0001
stage 6 of another group of
earth fault overcurrent
protection
The constant “C” of the
customized inverse-time
9
operation characteristic of
72 A.50/51G6.C 0 ~1 0 - 0.0001
stage 6 of another group of
earth fault overcurrent
protection
Default
No. Settings Range Unit Step Description
value
The relay characteristic angle
of the direction control
1 50/51Q.DIR.RCA -180~179 45 deg 1
element of negative-sequence
overcurrent protection
The minimum boundary of the
50/51Q.DIR.phi_Min_ forward direction element of
2 10~90 90 deg 1
Fwd negative-sequence
overcurrent protection
The maximum boundary of the
50/51Q.DIR.phi_Max forward direction element of
3 10~90 90 deg 1
_Fwd negative-sequence
overcurrent protection
The minimum boundary of the
50/51Q.DIR.phi_Min_ reverse direction element of
4 10~90 90 deg 1
Rev negative-sequence
overcurrent protection
The maximum boundary of the
50/51Q.DIR.phi_Max reverse direction element of
5 10~90 90 deg 1
_Rev negative-sequence
overcurrent protection
The minimum operating
current setting for the direction
6 50/51Q.DIR.I_Min (0.05~1)In 0.05 - 0.001 control element of
negative-sequence
overcurrent protection
The minimum operating
voltage setting for the direction
7 50/51Q.DIR.U_Min 1.0~10.0 4 V 0.001 control element of
negative-sequence
overcurrent protection
9
Default
No. Settings Range Unit Step Description
value
Logic setting to determine the
behavior of
negative-sequence
overcurrent protection when
VT circuit supervision function
is enabled and VT circuit
failure happens.
Disabled;
8 50/51Q.En_VTS_Blk Disabled - - Disabled: negative-sequence
Enabled
overcurrent protection will not
effected by VT circuit failure
Enabled: voltage controlled
negative-sequence
overcurrent protection will be
blocked by VT circuit failure
signal
The current setting of stage 1
9 50/51Q1.I2_Set 0.05~200 15 A 0.001 of negative-sequence
overcurrent protection
The operating time setting of
10 50/51Q1.t_Op 0.03 ~100 0.1 s 0.001 stage 1 of negative-sequence
overcurrent protection
The dropout time setting of
11 50/51Q1.t_DropOut 0 ~100 0 s 0.001 stage 1 of negative-sequence
overcurrent protection
The setting used to select the
directional mode of stage 1 of
Non_Direction
negative-sequence
al Non_Directio
12 50/51Q1.Opt_Dir - - overcurrent protection.
Forward nal
1: no direction;
Reverse
2: forward direction;
3: reverse direction.
Disabled;
The logic setting
enabling/disabling the stage 1
for
9
13 50/51Q1.En Enabled - -
Enabled of negative-sequence
overcurrent protection
Enabling stage 1 of
negative-sequence
Trp; overcurrent protection operate
14 50/51Q1.Opt_Trp/Alm Trp - -
Alm to trip or alarm.
Trp: for tripping purpose
Alm: for alarm purpose
Default
No. Settings Range Unit Step Description
value
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
The setting for selecting the
ANSILTV;
inverse-time operation
ANSILT;
15 50/51Q1.Opt_Curve IECDefTime - - characteristic curve of stage 1
IECN;
of negative-sequence
IECV;
overcurrent protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
characteristic curve of stage 1
Inst;
50/51Q1.Opt_Curve_ of negative-sequence
16 DefTime; Inst - -
DropOut overcurrent protection
IDMT
Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
17 50/51Q1.TMS 0.04~ 20 1 - 0.001 stage 1 of negative-sequence
overcurrent protection
The minimum operating time
setting of stage 1 of
18 50/51Q1.tmin 0 ~10 0.02 s 0.001
negative-sequence
overcurrent protection
9
The constant “k” of the
customized inverse-time
19 50/51Q1.K 0.001~120 0.14 - 0.0001 operation characteristic of
stage 1 of negative-sequence
overcurrent protection
The constant “α” of the
customized inverse-time
20 50/51Q1.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of
stage 1 of negative-sequence
overcurrent protection
Default
No. Settings Range Unit Step Description
value
The constant “C” of the
customized inverse-time
21 50/51Q1.C 0 ~1 0 - 0.0001 operation characteristic of
stage 1 of negative-sequence
overcurrent protection
The current setting of stage 2
22 50/51Q2.I2_Set 0.05~200 15 A 0.001 of negative-sequence
overcurrent protection
The operating time setting of
23 50/51Q2.t_Op 0.03 ~100 0.1 s 0.001 stage 2 of negative-sequence
overcurrent protection
The dropout time setting of
24 50/51Q2.t_DropOut 0 ~100 0 s 0.001 stage 2 of negative-sequence
overcurrent protection
The setting used to select the
directional mode of stage 2 of
Non_Direction
negative-sequence
al Non_Directio
25 50/51Q2.Opt_Dir - - overcurrent protection.
Forward nal
1: no direction;
Reverse
2: forward direction;
3: reverse direction.
The logic setting for
Disabled; enabling/disabling the stage 2
26 50/51Q2.En Enabled - -
Enabled of negative-sequence
overcurrent protection
Enabling stage 2 of
negative-sequence
Trp; overcurrent protection operate
27 50/51Q2.Opt_Trp/Alm Trp - -
Alm to trip or alarm.
Trp: for tripping purpose
Alm: for alarm purpose
Default
No. Settings Range Unit Step Description
value
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
The setting for selecting the
ANSILTV;
inverse-time operation
ANSILT;
28 50/51Q2.Opt_Curve IECDefTime - - characteristic curve of stage 2
IECN;
of negative-sequence
IECV;
overcurrent protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
characteristic curve of stage 2
Inst;
50/51Q2.Opt_Curve_ of negative-sequence
29 DefTime; Inst - -
DropOut overcurrent protection
IDMT
Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
30 50/51Q2.TMS 0.04~ 20 1 - 0.001 stage 2 of negative-sequence
overcurrent protection
The minimum operating time
setting of stage 2 of
31 50/51Q2.tmin 0 ~10 0.02 s 0.001
negative-sequence
overcurrent protection
9
The constant “k” of the
customized inverse-time
32 50/51Q2.K 0.001~120 0.14 - 0.0001 operation characteristic of
stage 2 of negative-sequence
overcurrent protection
The constant “α” of the
customized inverse-time
33 50/51Q2.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of
stage 2 of negative-sequence
overcurrent protection
Default
No. Settings Range Unit Step Description
value
The constant “C” of the
customized inverse-time
34 50/51Q2.C 0 ~1 0 - 0.0001 operation characteristic of
stage 2 of negative-sequence
overcurrent protection
Default
No. Settings Range Unit Step Description
value
The relay characteristic angle of
1 50/51SEF.DIR.RCA -180~179 45 deg 1 the direction control element of
sensitive earth fault protection
The minimum boundary of the
50/51SEF.DIR.phi_Mi
2 10~90 90 deg 1 forward direction element of
n_Fwd
sensitive earth fault protection
The maximum boundary of the
50/51SEF.DIR.phi_M
3 10~90 90 deg 1 forward direction element of
ax_Fwd
sensitive earth fault protection
The minimum boundary of the
50/51SEF.DIR.phi_Mi
4 10~90 90 deg 1 reverse direction element of
n_Rev
sensitive earth fault protection
The maximum boundary of the
50/51SEF.DIR.phi_M
5 10~90 90 deg 1 reverse direction element of
ax_Rev
sensitive earth fault protection
The minimum operating current
setting for the direction control
6 50/51SEF.DIR.I_Min (0.05~1)In 0.05 - 0.001
element of sensitive earth fault
protection 9
The minimum operating voltage
setting for the direction control
7 50/51SEF.DIR.U_Min 1.0~10.0 4 V 0.001
element of sensitive earth fault
protection
Default
No. Settings Range Unit Step Description
value
Logic setting to determine the
behavior of sensitive earth fault
protection when VT circuit
supervision function is enabled
and VT circuit failure happens.
50/51SEF.En_VTS_Bl Disabled; Disabled: sensitive earth fault
8 Disabled - -
k Enabled protection will not effected by VT
circuit failure
Enabled: voltage controlled
sensitive earth fault protection
will be blocked by VT circuit
failure signal
The current setting of stage 1 of
9 50/51SEF1.3I0_Set 0.005~2 1 A 0.001
sensitive earth fault protection
The operating time setting of
10 50/51SEF1.t_Op 0 ~100 0.1 s 0.001 stage 1 of sensitive earth fault
protection
The dropout time setting of
50/51SEF1.t_DropOu
11 0 ~100 0 s 0.001 stage 1 of sensitive earth fault
t
protection
Non_Directional The setting used to select the
Non_Dire
12 50/51SEF1.Opt_Dir Forward - - directional mode of stage 1 of
ctional
Reverse sensitive earth fault protection.
The logic setting for
Disabled;
13 50/51SEF1.En Enabled - - enabling/disabling the stage 1 of
Enabled
sensitive earth fault protection
Enabling stage 1 of sensitive
earth fault protection operate to
50/51SEF1.Opt_Trp/ Trp;
14 Trp - - trip or alarm.
Alm Alm
Trp: for tripping purpose
Alm: for alarm purpose
Default
No. Settings Range Unit Step Description
value
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
50/51SEF1.Opt_Curv ANSILT; IECDefTi inverse-time operation
15 - -
e IECN; me characteristic curve of stage 1 of
IECV; sensitive earth fault protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 1 of
50/51SEF1.Opt_Curv
16 DefTime; Inst - - sensitive earth fault protection
e_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
17 50/51SEF1.TMS 0.04~ 20 1 - 0.001 stage 1 of sensitive earth fault
protection
The minimum operating time
18 50/51SEF1.tmin 0 ~10 0.02 s 0.001 setting of stage 1 of sensitive
earth fault protection
The constant “k” of the
customized inverse-time
19 50/51SEF1.K 0.001~120 0.14 - 0.0001 operation characteristic of stage
1 of sensitive earth fault
9
protection
The constant “α” of the
customized inverse-time
20 50/51SEF1.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of stage
1 of sensitive earth fault
protection
Default
No. Settings Range Unit Step Description
value
The constant “C” of the
customized inverse-time
21 50/51SEF1.C 0 ~1 0 - 0.0001 operation characteristic of stage
1 of sensitive earth fault
protection
The current setting of stage 2 of
22 50/51SEF2.3I0_Set 0.005~2 1 A 0.001
sensitive earth fault protection
The operating time setting of
23 50/51SEF2.t_Op 0 ~100 0.1 s 0.001 stage 2 of sensitive earth fault
protection
The dropout time setting of
50/51SEF2.t_DropOu
24 0 ~100 0 s 0.001 stage 2 of sensitive earth fault
t
protection
Non_Directional The setting used to select the
Non_Dire
25 50/51SEF2.Opt_Dir Forward - - directional mode of stage 2 of
ctional
Reverse sensitive earth fault protection.
The logic setting for
Disabled;
26 50/51SEF2.En Enabled - - enabling/disabling the stage 2 of
Enabled
sensitive earth fault protection
Enabling stage 2 of sensitive
earth fault protection operate to
50/51SEF2.Opt_Trp/ Trp;
27 Trp - - trip or alarm.
Alm Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
9 28
50/51SEF2.Opt_Curv
e
ANSILT;
IECN;
IECDefTi
me
- -
inverse-time operation
characteristic curve of stage 2 of
IECV; sensitive earth fault protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
Default
No. Settings Range Unit Step Description
value
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 2 of
50/51SEF2.Opt_Curv
29 DefTime; Inst - - sensitive earth fault protection
e_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
30 50/51SEF2.TMS 0.04~ 20 1 - 0.001 stage 2 of sensitive earth fault
protection
The minimum operating time
31 50/51SEF2.tmin 0 ~10 0.02 s 0.001 setting of stage 2 of sensitive
earth fault protection
The constant “k” of the
customized inverse-time
32 50/51SEF2.K 0.001~120 0.14 - 0.0001 operation characteristic of stage
2 of sensitive earth fault
protection
The constant “α” of the
customized inverse-time
33 50/51SEF2.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of stage
2 of sensitive earth fault
protection
The constant “C” of the
customized inverse-time
34 50/51SEF2.C 0 ~1 0 - 0.0001 operation characteristic of stage
2 of sensitive earth fault
protection
The current setting of stage 3 of
35 50/51SEF3.3I0_Set 0.005~2 1 A 0.001
sensitive earth fault protection
The operating time setting of
36 50/51SEF3.t_Op 0 ~100 0.1 s 0.001 stage 3 of sensitive earth fault
protection
9
The dropout time setting of
50/51SEF3.t_DropOu
37 0 ~100 0 s 0.001 stage 3 of sensitive earth fault
t
protection
Non_Directional The setting used to select the
Non_Dire
38 50/51SEF3.Opt_Dir Forward - - directional mode of stage 3 of
ctional
Reverse sensitive earth fault protection.
The logic setting for
Disabled;
39 50/51SEF3.En Enabled - - enabling/disabling the stage 3 of
Enabled
sensitive earth fault protection
Default
No. Settings Range Unit Step Description
value
Enabling stage 3 of sensitive
earth fault protection operate to
50/51SEF3.Opt_Trp/ Trp;
40 Trp - - trip or alarm.
Alm Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
50/51SEF3.Opt_Curv ANSILT; IECDefTi inverse-time operation
41 - -
e IECN; me characteristic curve of stage 3 of
IECV; sensitive earth fault protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 3 of
50/51SEF3.Opt_Curv
42 DefTime; Inst - - sensitive earth fault protection
e_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
43 50/51SEF3.TMS 0.04~ 20 1 - 0.001 stage 3 of sensitive earth fault
protection
9
The minimum operating time
44 50/51SEF3.tmin 0 ~10 0.02 s 0.001 setting of stage 3 of sensitive
earth fault protection
The constant “k” of the
customized inverse-time
45 50/51SEF3.K 0.001~120 0.14 - 0.0001 operation characteristic of stage
3 of sensitive earth fault
protection
Default
No. Settings Range Unit Step Description
value
The constant “α” of the
customized inverse-time
46 50/51SEF3.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of stage
3 of sensitive earth fault
protection
The constant “C” of the
customized inverse-time
47 50/51SEF3.C 0 ~1 0 - 0.0001 operation characteristic of stage
3 of sensitive earth fault
protection
The current setting of stage 4 of
48 50/51SEF4.3I0_Set 0.005~2 1 A 0.001
sensitive earth fault protection
The operating time setting of
49 50/51SEF4.t_Op 0 ~100 0.1 s 0.001 stage 4 of sensitive earth fault
protection
The dropout time setting of
50/51SEF4.t_DropOu
50 0 ~100 0 s 0.001 stage 4 of sensitive earth fault
t
protection
Non_Directional The setting used to select the
Non_Dire
51 50/51SEF4.Opt_Dir Forward - - directional mode of stage 4 of
ctional
Reverse sensitive earth fault protection.
The logic setting for
Disabled;
52 50/51SEF4.En Enabled - - enabling/disabling the stage 4 of
Enabled
sensitive earth fault protection
Enabling stage 4 of sensitive
earth fault protection operate to
50/51SEF4.Opt_Trp/ Trp;
53 Trp - - trip or alarm.
Alm Alm
Trp: for tripping purpose
Alm: for alarm purpose
Default
No. Settings Range Unit Step Description
value
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
50/51SEF4.Opt_Curv ANSILT; IECDefTi inverse-time operation
54 - -
e IECN; me characteristic curve of stage 4 of
IECV; sensitive earth fault protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 4 of
50/51SEF4.Opt_Curv
55 DefTime; Inst - - sensitive earth fault protection
e_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
56 50/51SEF4.TMS 0.04~ 20 1 - 0.001 stage 4 of sensitive earth fault
protection
The minimum operating time
57 50/51SEF4.tmin 0 ~10 0.02 s 0.001 setting of stage 4 of sensitive
earth fault protection
The constant “k” of the
customized inverse-time
9
58 50/51SEF4.K 0.001~120 0.14 - 0.0001 operation characteristic of stage
4 of sensitive earth fault
protection
The constant “α” of the
customized inverse-time
59 50/51SEF4.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of stage
4 of sensitive earth fault
protection
Default
No. Settings Range Unit Step Description
value
The constant “C” of the
customized inverse-time
60 50/51SEF4.C 0 ~1 0 - 0.0001 operation characteristic of stage
4 of sensitive earth fault
protection
The current setting of stage 5 of
61 50/51SEF5.3I0_Set 0.005~2 1 A 0.001
sensitive earth fault protection
The operating time setting of
62 50/51SEF5.t_Op 0 ~100 0.1 s 0.001 stage 5 of sensitive earth fault
protection
The dropout time setting of
50/51SEF5.t_DropOu
63 0 ~100 0 s 0.001 stage 5 of sensitive earth fault
t
protection
Non_Directional The setting used to select the
Non_Dire
64 50/51SEF5.Opt_Dir Forward - - directional mode of stage 5 of
ctional
Reverse sensitive earth fault protection.
The logic setting for
Disabled;
65 50/51SEF5.En Enabled - - enabling/disabling the stage 5 of
Enabled
sensitive earth fault protection
Enabling stage 5 of sensitive
earth fault protection operate to
50/51SEF5.Opt_Trp/ Trp;
66 Trp - - trip or alarm.
Alm Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
67
50/51SEF5.Opt_Curv
e
ANSILT;
IECN;
IECDefTi
me
- -
inverse-time operation
characteristic curve of stage 5 of
9
IECV; sensitive earth fault protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
Default
No. Settings Range Unit Step Description
value
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 5 of
50/51SEF5.Opt_Curv
68 DefTime; Inst - - sensitive earth fault protection
e_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
69 50/51SEF5.TMS 0.04~ 20 1 - 0.001 stage 5 of sensitive earth fault
protection
The minimum operating time
70 50/51SEF5.tmin 0 ~10 0.02 s 0.001 setting of stage 5 of sensitive
earth fault protection
The constant “k” of the
customized inverse-time
71 50/51SEF5.K 0.001~120 0.14 - 0.0001 operation characteristic of stage
5 of sensitive earth fault
protection
The constant “α” of the
customized inverse-time
72 50/51SEF5.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of stage
5 of sensitive earth fault
protection
The constant “C” of the
customized inverse-time
73 50/51SEF5.C 0 ~1 0 - 0.0001 operation characteristic of stage
5 of sensitive earth fault
protection
The current setting of stage 6 of
74 50/51SEF6.3I0_Set 0.005~2 1 A 0.001
sensitive earth fault protection
The operating time setting of
Default
No. Settings Range Unit Step Description
value
Enabling stage 6 of sensitive
earth fault protection operate to
50/51SEF6.Opt_Trp/ Trp;
79 Trp - - trip or alarm.
Alm Alm
Trp: for tripping purpose
Alm: for alarm purpose
ANSIE;
ANSIV;
ANSIN;
ANSIM;
ANSIDefTime;
ANSILTE;
ANSILTV; The setting for selecting the
50/51SEF6.Opt_Curv ANSILT; IECDefTi inverse-time operation
80 - -
e IECN; me characteristic curve of stage 6 of
IECV; sensitive earth fault protection.
IEC;
IECE;
IECST;
IECLT;
IECDefTime;
UserDefine
The setting for selecting the
inverse-time dropout
Inst; characteristic curve of stage 6 of
50/51SEF6.Opt_Curv
81 DefTime; Inst - - sensitive earth fault protection
e_DropOut
IDMT Inst: instantaneous dropout
DefTime: definite-time dropout
IDMT: inverse-time dropout
The time multiplier setting of
82 50/51SEF6.TMS 0.04~ 20 1 - 0.001 stage 6 of sensitive earth fault
protection
Default
No. Settings Range Unit Step Description
value
The constant “α” of the
customized inverse-time
85 50/51SEF6.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of stage
6 of sensitive earth fault
protection
The constant “C” of the
customized inverse-time
86 50/51SEF6.C 0 ~1 0 - 0.0001 operation characteristic of stage
6 of sensitive earth fault
protection
Default
No. Settings Range Unit Step Description
value
The current setting of stage 1 of RMS
1 50/51R1.I_Set 0.05~200 15 A 0.001
overcurrent protection
The operating time setting of stage 1 of
2 50/51R1.t_Op 0 ~100 0.1 s 0.001
RMS overcurrent protection
The dropout time setting of stage 1 of
3 50/51R1.t_DropOut 0 ~100 0 s 0.001
RMS overcurrent protection
Disabled; The logic setting for enabling/disabling the
4 50/51R1.En Enabled - -
Enabled stage 1 of RMS overcurrent protection
Enabling stage 1 of RMS overcurrent
Trp; protection operate to trip or alarm.
5 50/51R1.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose
Alm: for alarm purpose
The current setting of stage 2 of RMS
9 6 50/51R2.I_Set 0.05~200 15 A 0.001
overcurrent protection
The operating time setting of stage 2 of
7 50/51R2.t_Op 0 ~100 0.1 s 0.001
RMS overcurrent protection
The dropout time setting of stage 2 of
8 50/51R2.t_DropOut 0 ~100 0 s 0.001
RMS overcurrent protection
Disabled; The logic setting for enabling/disabling the
9 50/51R2.En Enabled - -
Enabled stage 2 of RMS overcurrent protection
Default
No. Settings Range Unit Step Description
value
Enabling stage 2 of RMS overcurrent
Trp; protection operate to trip or alarm.
10 50/51R2.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose
Alm: for alarm purpose
Default
No. Settings Range Unit Step Description
value
Option of phase-to-phase
voltage or phase voltage for
Up; overvoltage protection
1 59P.Opt_Up/Upp Upp - -
Upp Up: phase voltage
Upp: phase-to-phase
voltage
Option of 1-out-of-3 mode or
3-out-of-3 mode for
3P;
2 59P.Opt_1P/3P 3P - - overvoltage protection
1P
3P: 3-out-of-3 mode
1P: 1-out-of-3 mode
The voltage setting of stage
3 59P1.U_Set 57.7~200 115 V 0.001 1 of phase overvoltage
protection
The dropout coefficient of
4 59P1.K_DropOut 0.93 ~1.00 0.98 - 0.001 stage 1 of phase
overvoltage protection
The operating time setting of
5 59P1.t_Op 0.1 ~100 1 s 0.001 stage 1 of phase
overvoltage protection 9
The dropout time setting of
6 59P1.t_DropOut 0 ~100 0 s 0.001 stage 1 of phase
overvoltage protection
The logic setting for
Disabled; enabling/disabling the stage
7 59P1.En Enabled - -
Enabled 1 of phase overvoltage
protection
Default
No. Settings Range Unit Step Description
value
Enabling stage 1 of phase
overvoltage protection
Trp;
8 59P1.Opt_Trp/Alm Trp - - operate to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose
The setting for selecting the
ANSIDefTime;
inverse-time operation
IECDefTime;
9 59P1.Opt_Curve IECDefTime - - characteristic curve of stage
UserDefine;
1 of phase overvoltage
InvTime_U
protection.
The setting for selecting the
inverse-time dropout
characteristic curve of stage
Inst; 1 of phase overvoltage
10 59P1.Opt_Curve_DropOut Inst - -
DefTime protection
Inst: instantaneous dropout
DefTime: definite-time
dropout
The time multiplier setting of
11 59P1.TMS 0.04~ 20 1 - 0.001 stage 1 of phase
overvoltage protection
The minimum operating time
12 59P1.tmin 0 ~10 0.02 s 0.001 setting of stage 1 of phase
overvoltage protection
The constant “k” of the
customized inverse-time
13 59P1.K 0.001~120 1 - 0.0001 operation characteristic of
stage 1 of phase
overvoltage protection
The constant “α” of the
customized inverse-time
Default
No. Settings Range Unit Step Description
value
The dropout coefficient of
17 59P2.K_DropOut 0.93 ~1.00 0.98 - 0.001 stage 2 of phase
overvoltage protection
The operating time setting of
18 59P2.t_Op 0.1 ~100 1 s 0.001 stage 2 of phase
overvoltage protection
The dropout time setting of
19 59P2.t_DropOut 0 ~100 0 s 0.001 stage 2 of phase
overvoltage protection
The logic setting for
Disabled; enabling/disabling the stage
20 59P2.En Enabled - -
Enabled 2 of phase overvoltage
protection
Enabling stage 2 of phase
overvoltage protection
Trp;
21 59P2.Opt_Trp/Alm Trp - - operate to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose
The setting for selecting the
ANSIDefTime;
inverse-time operation
IECDefTime;
22 59P2.Opt_Curve IECDefTime - - characteristic curve of stage
UserDefine;
2 of phase overvoltage
InvTime_U
protection.
The setting for selecting the
inverse-time dropout
characteristic curve of stage
Inst; 2 of phase overvoltage
23 59P2.Opt_Curve_DropOut Inst - -
DefTime protection
Inst: instantaneous dropout
DefTime: definite-time
dropout
Default
No. Settings Range Unit Step Description
value
The constant “α” of the
customized inverse-time
27 59P2.Alpha 0.01 ~3 1 - 0.0001 operation characteristic of
stage 2 of phase
overvoltage protection
The constant “C” of the
customized inverse-time
28 59P2.C 0 ~1 0 - 0.0001 operation characteristic of
stage 2 of phase
overvoltage protection
Default
No. Settings Range Unit Step Description
value
Option of measured residual voltage or
calculated residual voltage for residual
Ext;
1 59G.Opt_3U0 Cal - - overvoltage protection
Cal
Ext: the measured residual voltage
Cal: the calculated residual voltage
The voltage setting of stage 1 of residual
2 59G1.3U0_Set 1~200 50 V 0.001
overvoltage protection
The dropout coefficient of stage 1 of residual
3 59G1.K_DropOut 0.93 ~1 0.98 - 0.001
overvoltage protection
The operating time setting of stage 1 of
4 59G1.t_Op 0.1 ~100 1 s 0.001
residual overvoltage protection
The dropout time setting of stage 1 of
5 59G1.t_DropOut 0 ~100 0 s 0.001
residual overvoltage protection
9 The logic setting for enabling/disabling the
Disabled; stage 1 of residual overvoltage protection
6 59G1.En Enabled - -
Enabled 0: disabling
1: enabling
Enabling stage 1 of residual overvoltage
Trp; protection operate to trip or alarm.
7 59G1.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose
Alm: for alarm purpose
The voltage setting of stage 2 of residual
8 59G2.3U0_Set 1~200 50 V 0.001
overvoltage protection
Default
No. Settings Range Unit Step Description
value
The dropout coefficient of stage 2 of residual
9 59G2.K_DropOut 0.93 ~1 0.98 - 0.001
overvoltage protection
The operating time setting of stage 2 of
10 59G2.t_Op 0.1 ~100 1 s 0.001
residual overvoltage protection
The dropout time setting of stage 2 of
11 59G2.t_DropOut 0 ~100 0 s 0.001
residual overvoltage protection
The logic setting for enabling/disabling the
Disabled; stage 2 of residual overvoltage protection
12 59G2.En Enabled - -
Enabled 0: disabling
1: enabling
Enabling stage 2 of residual overvoltage
Trp; protection operate to trip or alarm.
13 59G2.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose
Alm: for alarm purpose
9
Disabled; The logic setting of the stage 1 of
5 59Q1.En Enabled - -
Enabled negative-sequence overvoltage protection
Enabling stage 1 of negative-sequence
Trp; overvoltage operate to trip or alarm.
6 59Q1.Opt_Trp/Alm Trp - -
Alm Trp: for tripping purpose
Alm: for alarm purpose
The voltage setting of the stage 2 of
7 59Q2.U2_Set 2~100 15 V 0.001
negative-sequence overvoltage protection
The dropout coefficient setting of the stage
8 59Q2.K_DropOut 0.93~1 0.98 - 0.001 2 of negative-sequence overvoltage
protection
Default
No. Settings Range Unit Step Description
value
Option of phase-to-phase
voltage or phase voltage
for stage x of
Up;
1 27P.Opt_Up/Upp Upp - - undervoltage protection
Upp
Up: phase voltage
Upp: phase-to-phase
voltage
Option of 1-out-of-3 mode
or 3-out-of-3 mode for
3P; stage x of undervoltage
2 27P.Opt_1P/3P 3P - -
1P protection
3P: 3-out-of-3 mode
1P: 1-out-of-3 mode
Breaker closed position
check mode
None: no check
Curr: check the current
None; CBPos: check the
Curr; normally open auxiliary
3 27P.Opt_LogicMode CBPos; Curr - - contact
CurrOrCBPos; CurrOrCBPos: check the
CurrAndCBPos current and normally open
auxiliary contact
CurrAndCBPos: check the
current or normally open
auxiliary contact
The voltage setting of
4 27P1.U_Set 5~120 80 V 0.001 stage 1 of phase
undervoltage protection
The dropout coefficient of
5 27P1.K_DropOut 1~1.2 1.03 - 0.001 stage 1 of phase 9
undervoltage protection
The operating time setting
6 27P1.t_Op 0.1 ~100 1 s 0.001 of stage 1 of phase
undervoltage protection
The dropout time setting
7 27P1.t_DropOut 0 ~100 0 s 0.001 of stage 1 of phase
undervoltage protection
Default
No. Settings Range Unit Step Description
value
Logic setting to determine
the behavior of stage 1 of
phase undervoltage
protection when VT circuit
supervision function is
Disabled;
8 27P1.En_VTS_Blk Disabled - - enabled and VT circuit
Enabled
failure happens.
0: it is not effected by VT
circuit failure
1: it will be blocked by VT
circuit failure signal
The logic setting for
enabling/disabling the
Disabled; stage 1 of phase
9 27P1.En Enabled - -
Enabled undervoltage protection
0: disabling
1: enabling
Enabling stage 1 of phase
undervoltage protection
Trp;
10 27P1.Opt_Trp/Alm Trp - - operate to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose
The setting for selecting
ANSIDefTime;
the inverse-time operation
IECDefTime;
11 27P1.Opt_Curve IECDefTime - - characteristic curve of
UserDefine;
stage 1 of phase
InvTime_U
undervoltage protection.
The setting for selecting
the inverse-time dropout
characteristic curve of
stage 1 of phase
Inst;
9
12 27P1.Opt_Curve_DropOut Inst - - undervoltage protection
DefTime
Inst: instantaneous
dropout
DefTime: definite-time
dropout
The time multiplier setting
13 27P1.TMS 0.04~ 20 1 - 0.001 of stage 1 of phase
undervoltage protection
Default
No. Settings Range Unit Step Description
value
The minimum operating
time setting of stage 1 of
14 27P1.tmin 0.03 ~10 0.03 s 0.001
phase undervoltage
protection
The constant “k” of the
customized inverse-time
15 27P1.K 0.001~120 0.14 - 0.0001 operation characteristic of
stage 1 of phase
undervoltage protection
The constant “α” of the
customized inverse-time
16 27P1.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of
stage 1 of phase
undervoltage protection
The constant “C” of the
customized inverse-time
17 27P1.C 0 ~1 0 - 0.0001 operation characteristic of
stage 1 of phase
undervoltage protection
The voltage setting of
18 27P2.U_Set 5~120 80 V 0.001 stage 2 of phase
undervoltage protection
The dropout coefficient of
19 27P2.K_DropOut 1~1.2 1.03 - 0.001 stage 2 of phase
undervoltage protection
The operating time setting
20 27P2.t_Op 0.1 ~100 1 s 0.001 of stage 2 of phase
undervoltage protection
The dropout time setting
21 27P2.t_DropOut 0 ~100 0 s 0.001 of stage 2 of phase
undervoltage protection
Logic setting to determine
the behavior of stage 2 of
9
phase undervoltage
protection when VT circuit
supervision function is
Disabled;
22 27P2.En_VTS_Blk Disabled - - enabled and VT circuit
Enabled
failure happens.
0: it is not effected by VT
circuit failure
1: it will be blocked by VT
circuit failure signal
Default
No. Settings Range Unit Step Description
value
The logic setting for
enabling/disabling the
Disabled; stage 2 of phase
23 27P2.En Enabled - -
Enabled undervoltage protection
0: disabling
1: enabling
Enabling stage 2 of phase
undervoltage protection
Trp;
24 27P2.Opt_Trp/Alm Trp - operate to trip or alarm.
Alm
Trp: for tripping purpose
Alm: for alarm purpose
The setting for selecting
ANSIDefTime;
the inverse-time operation
IECDefTime;
25 27P2.Opt_Curve IECDefTime - - characteristic curve of
UserDefine;
stage 2 of phase
InvTime_U
undervoltage protection.
The setting for selecting
the inverse-time dropout
characteristic curve of
stage 2 of phase
Inst;
26 27P2.Opt_Curve_DropOut Inst - - undervoltage protection
DefTime
Inst: instantaneous
dropout
DefTime: definite-time
dropout
The time multiplier setting
27 27P2.TMS 0.04~ 20 1 0.001 of stage 2 of phase
undervoltage protection
The minimum operating
time setting of stage 2 of
28 27P2.tmin 0.03 ~10 0.03 s 0.001
phase undervoltage
9 protection
The constant “k” of the
customized inverse-time
29 27P2.K 0.001~120 0.14 - 0.0001 operation characteristic of
stage 2 of phase
undervoltage protection
The constant “α” of the
customized inverse-time
30 27P2.Alpha 0.01 ~3 0.02 - 0.0001 operation characteristic of
stage 2 of phase
undervoltage protection
Default
No. Settings Range Unit Step Description
value
The constant “C” of the
customized inverse-time
31 27P2.C 0 ~1 0 - 0.0001 operation characteristic of
stage 2 of phase
undervoltage protection
9
overfrequency protection
Disabled; The logic setting of the stage 3 of
10 81O3.En Enabled - -
Enabled overfrequency protection
The frequency setting of the stage 4 of
11 81O4.f_Set 50~65 52 Hz 0.001
overfrequency protection
The time setting of the stage 4 of
12 81O4.t_Op 0.1~100 0.3 s 0.001
overfrequency protection
Disabled; The logic setting of the stage 4 of
13 81O4.En Enabled - -
Enabled overfrequency protection
The frequency setting of the stage 5 of
14 81O5.f_Set 50~65 52 Hz 0.001
overfrequency protection
Default
No. Settings Range Unit Step Remark
value
Positive-sequence reactance of the whole
1 X1L (0~4Unn)/In 10 Ω 0.001
line (secondary value)
Positive-sequence resistance of the whole
2 R1L (0~4Unn)/In 1 Ω 0.001
line (secondary value)
Zero-sequence reactance of the whole
3 X0L (0~4Unn)/In 20 Ω 0.001
line (secondary value)
Zero-sequence resistance of the whole
4 R0L (0~4Unn)/In 3 Ω 0.01
line (secondary value)
5 LineLength 0~1000 100 km 0.01 Total length of the whole line
In this section, the "XXXX" stands for bay indication. By default, it could be
BayMMXU, BusMMXU, etc. and it is configurable through the configuration
tool PCS-Studio.
8 Switch02.DPS.En_Alm Disabled
Disabled or
- -
Logic setting for DPS alarm of switch 9
Enabled 02
Operation time delay of DPS alarm of
9 Switch02.DPS.t_Alm 500 0~60000 1 ms
switch 02
Delay Pick Up (DPU) time, i.e.
10 Switch03.DPS.t_DPU 500 0~60000 1 ms
debounce time, for DPS of switch 03
Disabled or Logic setting for DPS alarm of switch
11 Switch03.DPS.En_Alm Disabled - -
Enabled 03
Operation time delay of DPS alarm of
12 Switch03.DPS.t_Alm 500 0~60000 1 ms
switch 03
9
17 Switch08.t_PW_Opn 500 0~60000 1 ms
opening output of switch 08
Pulse Width (PW), i.e. holding time, for direct
18 Switch08.t_PW_Cls 500 0~60000 1 ms
closing output of switch 08
Pulse Width (PW), i.e. holding time, for direct
19 Switch09.t_PW_Opn 500 0~60000 1 ms
opening output of switch 09
Pulse Width (PW), i.e. holding time, for direct
20 Switch09.t_PW_Cls 500 0~60000 1 ms
closing output of switch 09
Logic link is a special logic setting which can be configured through local HMI or remote PC.
These logic links provide a convenient way for the operator to put the function in service or out of
service remotely away from an unattended substation.
@Bx.Name_000_GCommLink. Disabled
1 Enabled GOOSE receiving link 000 is enabled or disabled
GLink_Recv Enabled
Disabled
2 …… Enabled ……
Enabled
@Bx.Name_127_GCommLink. Disabled
3 Enabled GOOSE receiving link 127 is enabled or disabled
GLink_Recv Enabled
Appendix A Glossary
The abbreviations adopted in this manual are listed as below.
FR Fault Recorder O
OOS Out-of-Step
G.703 Electrical and functional description for
digital lines used by local telephone
P
companies. Can be transported over balanced
and unbalanced lines
PD Pole Discrepancy
GIS Gas-insulated Switchgear
PDTT Permissive Direct Transfer Trip
GOOSE Generic Object-Oriented Substation
PL Programmable Logic
Event
POTT Permissive Overreaching Transfer Trip
GPS Global Positioning System
PPM Pulse Per Minute
H
PPS Pulse Per Second
HV High-voltage
R
HVDC High-voltage Direct Current
RMS Root Mean Square
I
RSTP Rapid Spanning Tree Protocol
A list of function numbers used to represent electrical protection and control element. The device
function numbers used in this manual include the following: