NG12
English Version
CONTENTS
1 - GENERAL PRESENTATION.....................................................................................................................4
1.1 POSSIBILITIES..............................................................................................................................................4
1.1.1 Basic Options .............................................................................................................................................4
1.1.2 Optional extra facilities (available at extra cost).......................................................................................5
1.2 THE MATERIAL ............................................................................................................................................5
1.2.1 NG12 card..................................................................................................................................................5
1.2.2 The down collective system call acceptance indicator card.......................................................................8
1.2.3 Position indicator cards : 1 wire per floor (Aux.2 or Aux. 3) ....................................................................9
1.2.4 Extension cards ........................................................................................................................................12
1.3 THE PROGRAM ..........................................................................................................................................21
2 - INSTALLATION ........................................................................................................................................22
2.1 CONNECTION ............................................................................................................................................22
2.1.1 Use during installation.............................................................................................................................22
2.1.2 Final connection ......................................................................................................................................22
2.2 PRECAUTIONS ...........................................................................................................................................23
2.2.1 Precaution against parasites....................................................................................................................23
2.2.2 Protection of the circuits (tracks and components)..................................................................................23
2.2.3 Checks before switching on the mains .....................................................................................................24
3 – PROGRAMMING......................................................................................................................................25
3.1 USING THE SHARP PCE 500.....................................................................................................................25
3.2 PARAMETER LIST ......................................................................................................................................25
3.2.1 Control system..........................................................................................................................................25
3.2.2 Erase all registered landing calls (pre-set MEA: No)..............................................................................25
3.2.3 Traction....................................................................................................................................................25
3.2.4 Fire Detection (Standard U36) ................................................................................................................25
3.2.5 Serial car link...........................................................................................................................................26
3.2.6 Switches inputs on TOC card ...................................................................................................................26
3.2.7 Floors served............................................................................................................................................26
3.2.8 Number of basement floors (floors 0, -1, -2, etc.) ....................................................................................26
3.2.9 Floor numbering ......................................................................................................................................26
3.2.10 Slow speed (pre-set MEA « 5 », particularity excepted) ..........................................................................26
3.2.11 Switch to slow speed on exiting the first vane ..........................................................................................28
3.2.12 Automatic return to zone or homing to a floor.........................................................................................28
3.2.13 Two entrances ..........................................................................................................................................28
3.2.14 Type of entrance.......................................................................................................................................29
3.2.15 Recording of the use of the stop button ....................................................................................................29
3.2.16 Advanced door opening............................................................................................................................29
3.2.17 Automatic door without end limit switches ..............................................................................................29
3.2.18 Selection of entrance ................................................................................................................................30
3.2.19 Door open timer (pre-set MEA 10s).........................................................................................................30
3.2.20 Timing before departure (pre-set MEA 3s) ..............................................................................................30
3.2.21 Photocells NO or NF................................................................................................................................30
3.2.22 Door close timer.......................................................................................................................................30
3.2.23 Fireman’s operation.................................................................................................................................31
3.2.24 Fireman' s mode with in-car adjustable spanner (pre-set MEA "no")......................................................31
3.2.25 Relevelling................................................................................................................................................31
3.2.26 Resetting ( pre-set MEA: lowest floor )....................................................................................................32
3.2.27 Slow speed fault ( pre-set MEA 7s for electric lifts, 14s for hydraulic lifts ) ...........................................32
3.2.28 Heat probe sensors...................................................................................................................................32
3.2.29 Multiplex ..................................................................................................................................................32
3.2.30 Flashing indicators ..................................................................................................................................33
3.2.31 Heavy blocking floors ..............................................................................................................................33
3.2.32 Position indicator.....................................................................................................................................33
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 3 / 3
1 - GENERAL PRESENTATION
MEA has designed the NG12 card on request of numerous clients desiring to take advantages of the NG02 (ease of use,
faultfinding etc.) for a basic control system (down collective simplex, for 12 floors).
Definitions of the entire notation used in this manual are summarised on the schematic-wiring diagram supplied with each
lift controller. The aim of this manual is to expand on the information given and to facilitate the installation and eventual
resolution of any faults.
1.1 POSSIBILITIES
Fi
g. 1.1
Terminals 1 et 2: Control System Inputs
No Without S.A.P.B 12 car dispatch outputs (entrances A/ B) and
Down collective 12 landing call inputs (entrances A/ B)
car U36 8 car dispatch outputs (entrances A and B)
Full collective 16 landing call inputs, 8 for going up and
Standard 8 for going down (entrances A/B)
serial S.A.P.B 8 car dispatch outputs (entrances A/ B)
With Down collective 8 call inputs (entrances A/B)
8 fire detection inputs (standard U36)
U36 6 car dispatch outputs (entrances A /B)
link Full collective
12 landing call inputs, 6 for going up and
Standard 6 for going down (entrances A/B)
6 fire detection inputs (standard U36)
3: 12 limit inputs
4: 12 Principle limit signal inputs with associated Led indicators
(AGH, AGB, Fireman’s operation, FOA, FFA etc.)
5: 2 Input for the displacement sensors and output for a 3-wire indicator.
6: 2 Heat sensor or thermistor inputs (spare contacts or thermistor CTP plus ‘lift in use’ indicator output for
S.A.P.B systems (24V 36W maxi) and corresponding 2A fuse.
7: Voltage output selection strap for the 3-wire position indicator D01 (5V or 24V)
See auxiliary cards 2 and 3 paragraph 1.2.3 (to position on 24V)
8: Output RS232 TTL for connection of the programming unit
9: 7 interface relays for
RM, RD: up and down relays
RGV, RPV: full and slow speed relays
ROA, RFA: open and close relays of entrance A
ISO: relevelling relay
10: Indicator showing the current floor, the operation being executed, the faults, and the parameters
programmed by the user.
11: 3 Inputs and leds indicators checking the safety of the lift
SECU3 : safety circuit (limit switch, safety gear, circuit breaker, etc.)
SECU4 : car or landing doors
SECU6 : locking
12: 24V-power supply for the card with fuse protection 500mA with timed action.
13: 5 supplementary outputs to control following relays :
PAN: request for “Tobia” emergency manoeuvring (see “ ” fault)
ROB: opening of entrance B
RFB: closing of entrance B
SC01: lift car lighting timer
SC02: control of CAME contactor
14: EEPROM memory containing the programmed parameters of the installation (see 1.3. / III)
15: Microprocessor
16: EPROM memory containing the operating program (see 1.3)
17: RAM memory
18: Connection for the hall lanterns card with down collective (see 1.2.2)
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 8 / 8
This card controls the operation of the call acceptance indicators for the car and landings.
As shown in the diagram below the return for the call acceptance indicator is the same wire as for the call buttons.
Fig. 1.2
• Transforming a S.A.P.B controller into a down collective does not require the addition of
additional wiring.
• There is also the possibility to have call acceptance, lift in service indicator, with a S.A.P.B system
as with a down collective.
•
Warning
Be careful: The CFL terminal and the two direction arrows relays only appear on cards that have been sold
from June 1996.
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 9 / 9
1.2.3 Position indicator cards : 1 wire per floor (Aux.2 or Aux. 3 or Aux5)
In the case of a bulb or other position indicator that does not require a 3 wires connection, it is necessary to use one of these
two interfaces to be connected on the indicator output D01 (see 1.2.1/5 and 1.2.1/7).
Cards : I422 , TOC 24 floors, COM_X. (CP8 and COM_D never used)
The RS232 serial port is very used to wide up the possibilities of the NG12 card.
1) To construct an NG12 DUPLEX system, two I422 cards are used (see 5.2.2.1):
Fig. 1.6
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 13 / 13
2) To construct a "serial link" between the car and the controller (see NOTE) it is necessary to use one
I422 card and one TOC card:
Fig. 1.7
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 14 / 14
3) To construct a NG12 DUPLEX and a serial link between the cars and the controllers the use of two
COM_D / COM_X cards and two TOC cards are necessary:
COM_D COM_D
COM_X COM_X
Fig. 1.8
NOTE: the "serial link" between the controller and the car makes the wiring easier. Each door open/close limits
contact, photocell contact, door open / close and dispatch call button and indicator are all connected to the TOC
card indeed. All the data are supplied through 4 wires whatever is the number of floors (until 24 floors).
1: Printed circuit.
2: Connector for link with either a second I422 card or the TOC card
This card is the input/ output module on the roof of the car. It is provided to manage all the data for a car serving 8 floors
with 2 entrances. To manage 16 floors it is necessary to add a CP8 card and for 24 floors 2 CP8 cards.
Fig. 1.10 - The assembly schematic of the TOC Card.
Fig. 1.11 - The TOC card with connectors provided for pre-wiring
Note: These inputs have the same function as on the NG12 card; so in case of use of the TOC card, do not plug
anything on the inputs with the same name on the NG12 card.
JP1 : serial link : serial port for a connection with the I422 or the COM_X card (see 5.2.2.1 / 2).
JP2 : 24V power supply and earth terminal
JP3 : connector for “STARRET” display
JP4 : no
JP5 : 24 car calls buttons inputs and car call acceptance (entrance A / B) + commons calls and car call acceptance
indicators.
JP6 : Information car inputs
J1 : connector for a connection with the CP8 card (floors extension)
J2 : connector for a connection with auxiliary cards (not used)
This card permits the extension of the number of dispatch calls of the car.
This card, as the COM_D card, permits the doubling of the serial socket of the NG12 card with additional functions :
• Duplex operation
• Remote control
• Supervision
• Serial link with TOC card on the roof of the car lift
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 21 / 21
• J1 : No
• J2 : Link with TOC card
• J3 : Link with the COM_X card (lift B if Duplex)
• J4 : Link with the phone type DICTIS on the roof of the car (for remote control)
• J5 : Link with NG12 card
• J6 : 24V power supply
• J7 : Link with MODEM for the supervision
The program which is contained in the EPROM (see 1.2.1/16) is unique whatever is the installation or the card to be fitted.
There is only the program of the parameters (Cf.1.2.1/14) and the controller wiring that makes the difference between two
installations. It is therefore possible to switch round the two NG12 cards by:
Finally to allow the upgrading of existing installations, so as new standards, new software are created. Anyway they
remain compatible with all the other cards previously used.
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 22 / 22
2 - INSTALLATION
2.1 CONNECTION
If you want to use the controller while adjustment, make the following temporary connections:
ATTENTION: Before the final operation, do not forget to remove any temporary connection made during the
temporary use of the controller.
To connect your installation, see the schematics provided with the controller on delivery. Nevertheless, please find
hereafter a description of the different contacts to use.
NOTE: With a down collective, the program controls the order in which the landing calls are handled:
- When going up from the basement to the ground floor
- When going down from other floors.
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 23 / 23
• Diverse Contacts (Cf. 1.2.1/3 and 4; 1.2.4.2/7, /8, /9, /10, /11):
•
AGH, AGB: High speed limit switch (up and down).
NC: These contacts force the slow speed at top floor level and reset the selector (program).
The positioning of these contacts in the shaft is extremely important for the position pulsing of
the lift car (see 3.2.9 and 4.1.1).
BFR Door-close-contact, NO, operated by door close button in lift car (see 3.2.19).
CCO NC contact, which open if the main contact(s) fails to drop out when the lift stops, e.g. contact
welded. Pre-wired by MEA, (see 4.3.3/02).
CEA Safety edge, door open contact entrance A programmable (see 3.2.18)
COM Full load contact, NO, closes at full load
EL 1 to 4 Special applications with refer to the schematic-wiring diagram supplied with the
controller.
FFA Door close contact, NC, opens when door closes entrance A
FOA Door open contact, NC, opens when door opens entrance A
FOB, FFB, CEB Identical to the entrance A but for entrance B
OLE Standard hydraulic contact, NO (see 4.3.3/0F)
PCA Attendant control contact or car priority, NO, closes when mode in operation
(see 4.2.1/17).
PMO/PDE Ascent / Decent contact, NO (see 3.2.28).
POM Fireman’s switch contact, NO, closed in fire mode
REM, RED Up/down contacts, NO, close when up/down buttons are pressed on the car
top control.
REV Inspection contact, NC, opens when the car top control is put on inspection
SUR Lift overloaded contact, NO, closes at overload
• Sensors
FAI: The lower displacement sensor contact (B)
FAS: The top displacement sensor contact (A)
TH1/TH2: Heat probe or thermistor (3kOhms at 110°C) of the traction motor.
Shunt if not provided.
2.2 PRECAUTIONS
All possible precautions have been taken with respect to parasites, to counter human error, markings, with each card.
Nevertheless it is recommended that you take the following precautions:
To check the wiring and avoid a deterioration or a destruction of a card (in case of error), make sure by carrying out these
two tests (see below) before connecting the 24V (contacts 1 to 7).
• First test: Verify that there is no voltage greater than 30V (ac or dc) between the 24V terminal
and the earth bar.
• Second test: Repeat the first test but for the voltage between the 24V terminal and the terminal
REF “24CC” card power supply.
3 – PROGRAMMING
Parameters of the installation necessary to configure the NG12 card are memorised at the factory as per the purchase order.
Parameters can be changed by using the SHARP PCE 500 programmer. It is also possible to parameterise a card in stock.
Note: The programming of parameters is possible while the lift operates. Cut and then restore the electrical current for the
modified parameters to be registered.
This parameter is available only with a full collective system and must only be used with a simplex arrangement.
• If you enter “No” : the calls will be erased normally according to the direction of the car. The car
/landing calls for rising will be erased by going up, and the car / landing calls for descending will
be erased by going down, and both if there is no more car or landing calls registered.
• If you enter “Yes” : each time a car stops at floor all registered car calls, landing. up and landing
down calls of the designated floor shall be erased irrespective of the direction of travel. In the case
of a double entrance the erasing will correspond with the doors which open. The choice of this
option allows futile trips being made in buildings where the occupants have in the habit of
pressing both up and down landing button at the same time.
3.2.3 Traction
• If the lift car is at another floor than the one of the fire, the landing and car calls at the burning
floor are forbidden.
• If the car is at the same floor as the fire :
door open is forbidden
door closing (if open when fire was detected)
car is sent to another floor
The fire detection inputs are taken from the landing and car call inputs because of this if the U36 parameter is chosen it is
important that the total floor number parameter (see 3.2.6) does not exceed the maximum number of floors imposed by the
control system.
This parameter permits the use of the TOC and COM_D with the NG12 (see 1.2.4).
Communication between these 2 cards is only possible by entering “yes”.
By entering "yes", REV, REM, RED, FFA, FOB, CEA, FFB, FOB, CEB, SUR, BFR, COM, PCA, OLE "information"
switches are to be connected on the TOC card inputs or on the NG12 card inputs.
Switches are not to be connected on both cards at the same time. In any case, the car call buttons are connected on the TOC
and CP8 cards.
The program only uses this parameter in a down collective system to indicate the main floor where the car dispatch calls
switches are inverted (up direction at the main floor and basement). On other control systems the parameter is not
indicated.
This numbering comes into play at the level of the car and landing position indicator output, D01, (see 1.2.1/5) and has no
affect on the response to landing calls (down collective), or the numbers shown by the card indicator which always starts at
0 whatever the case.
The parameter adjust the floor numbers shown by the position indicator (-9, + 23).
IMPORTANT: From now, any parameter relative to the other floors is calculated according to your responses in 3.2.8.1 /
3.2.8.2 /3.2.8.3.
With this parameter you can select the point to signal the controller to switch to slow speed, whatever is the floor.
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 27 / 27
For example if you have a small distance interfloor distance by choosing «2», the lift will travel practically the whole
distance at slow speed. Pay attention to the PV fault timer (see 3.2.24).
It is essential in all cases that the terminal slowing (AGH or AGB) switch is positioned before the position chosen for the
switch to slow speed vane at both terminal floors.
Fig 3.2
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 28 / 28
Operation of example 1:
The lift car ascends just until the final stopping limit switch (AGH) the right hand digit of the card indicator illuminate
while the leds of the displacement sensors FAI, FAS (see 1.2.1/5) are still illuminated. The leds go out, then they each light
up twice before the final stop at floor level. This is the signal that the lift met then left two vanes.
At the terminal floors the two digits of the card indicator and the two leds remain illuminated to show the lift is at the
extreme of its travel.
Note: The left hand digit of the card indicator illuminates to show the lift is exactly at level even at intermediate floors.
Terminal floor
Fig 3.3
Note: To make the adjustment easier, choose an odd number for the slowing vane.
This question only appears when the exit from the first vane has been chosen in the question 3.2.9 for switching to slow
speed. If you answer “yes” the lift will travel the complete interfloor distance at slow speed if the EL1 input is activated. If
you chose to answer “no”, the lift starts at full speed then switches to slow speed on exiting the first vane.
(a) No lift car door: landing doors, no car door or manual car door
(b) Automatic door: powered car door (s ) linked to landing doors by a clutch.
(c) Powered door, car only: manual landing door, car door (s) controlled
by the lift controller, they remain open at the floor.
(d) Independent car door: manual landing doors, car doors controlled independently of the lift controller.
Note: For the lifts with 2 entrances it is possible to have a different type of door at each entrance. In this case pay
particularly close attention to the schematic-wiring diagram supplied with the controller.
If you answer by yes and there is a break in the security circuit before SECU 3 and while the lift is moving with registered
car calls, all the calls are erased. Make another car call or cut SECU 4 to restart.
If the answer is “yes” to this option the lift starts to open its door from the moment the car enters the door zone. As a result
of this the door safety circuit is by passed.
The contacts responsible for this shunt must comply with the standards in force (see En 81 14.1.2.2 and 14.1.2.3). To this
end we use either a NC floor level switch, or any kind of unit to provide a supplementary pulse to the controller.
Fig 3.4
This parameter does not appear if you have opted either for option b or c in § 3.2.12 '
Type of entrance' .
If the entrance has open/close limits contacts reply “yes”.
If the entrance does not have l open/close limits reply “no”.
At the beginning of the door opening, the timer operates and the door open relay contact is cut at the end of the time
interval. It is identical for closing but the closing relay contact is cut.
"Double journey" faults are cancelled.
Adjustment of door open / close timer is made through the NG12 card keys (Cf 4.0.4.6 and 4.0.4.7).
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 30 / 30
In the case of two entrances it is possible to chose which entrance to open (A or B or A and B).
Example :
etc.
A
B
B
A
This parameter appears only whether you chose (b) or (c) in § 3.2.12 ' Type of entrance’ and answered by yes at § 3.2.14
"Automatic doors with end limit switches".
In that case, put a value in seconds equal to the time for the door to move (opening or closing) plus several seconds (60s
maxi.).
If the door takes a time higher than the one parameterised before reaching the corresponding end limit switch, the open /
close door contact is also no longer supplied, as if the end limit switch was activated.
NOTE: If the door travel time is exceed while opening the door will attempt to close after the normal timed interval
(controlled by dwell timer).
On the other hand if the door travel time is exceed on closing and that there is no outstanding calls for the lift to serve, the
door remains just until a new call is registered. This note does not apply on inspection mode.
3.2.21 Photocells NO or NF
• Cell NO: In that case the contact is open as long as the cell is not covered.
It closes as soon as the cell is covered. The safety edge, cell and door open button contacts are wired in parallel.
• Cell NF: It is the contrary of cell NO. Safety edge, cell, and door reopening button are to be wired in
series.
Note: it is imperative that the safety edge contacts, cell, and door open button are all of the same type NO or NF.
When the door is open, three timers are coming into play:
• Adjustable timer "door remains open" (Cf. 4.0.4 and 4.0.4.3).
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 31 / 31
• Dwell timer, adjustable from 1 to 10s that starts as soon as the door is open and as a call is
registered.
• Door close button that reduces the dwell timer to 1 second.
As soon as one of these three timers is reached, the door closes.
Note: In the case of reopening for whatever reason (call, photocell, etc.) the timers are restarted.
3.2.24 Fireman's mode with in-car adjustable spanner (pre-set MEA "no")
3.2.25 Relevelling
Attention: the use of this parameter is not advised for hydraulic lifts due to the possibility of pressure loss causing the
pump to function continuously.
Note : It is recommended to use a distance between upper and lower displacement sensors of no more than 20mm
(TMS03).
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 32 / 32
• One sensor doors open two sensors doors closed one sensor relevelling.
The use of this parameter makes the relevelling by one sensor possible, with the landing door open (car light on) and by
two sensors with landing door closed and car light off.
Note: Whatever the option chosen for revelling with doors open (compulsory on hydraulic lifts), it is necessary to shunt the
door safety circuits under control of contacts in conformity with the current standards in force (see En81 14.1.2.2, 14.1.2.3).
This parameter can be twined with the pre door opening so only one door safety circuit shunting device is necessary.
3.2.27 Slow speed fault ( pre-set MEA 7s for electric lifts, 14s for hydraulic lifts )
If a problem happened during the slow speed operation of the lift the motor stops after the selected time interval, (as if it
was at floor level) to avoid a useless overheating. All calls are erased, (car and landing calls with simplex).
The lift is ready to restart on the next call.
This function does not work when the lift is resetting and the timed interval defaults automatically to 14seconds when the
interfloor at slow speed option has been selected (only car calls are erased with Multiplex system).
When TH1/TH2 input is cut or that the motor thermistor detects an overheating.
• either the lift continue until the very next floor
• or the lift stops immediately
In both cases the lift restarts when normal conditions are restored.
3.2.29 Multiplex
By answering "yes” to this parameter allows you to enter the multiplex menu (see 5).
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 33 / 33
Upper heavy traffic floor: This parameter is very useful if a heavy upward blocking is required. As soon as the PMO input
is activated, the lift car goes down to the floor defined by this parameter without stopping for any down calls. This function
can be twined with a time clock or key switch. If this parameter is not required press the key without entering a
number.
Lower heavy traffic floor: This parameter, PDE is identical to the above but is used in the case of a heavy downward
blocking.
This parameter permits all the dispatch calls to be erased if a given number of stops are carried out without the photocell
being cut in the case of automatic car and landing doors or without the landing door being opened in all other cases.
By answering “yes”, answer the question “number of stops to erase all the calls”.
Answer “yes” to this parameter allows to access to menu where are gathered all the special requirements for the Russian
controllers. Once the menu is open, choose among the following options shown by the Sharp:
• KLM board: if you enter "yes" to this question it shows that the KLM board is being
parameterised.
• Dispatcher: if you enter “yes” to this parameter it cancels the relevelling function of the ISO
relay. The PDE input becomes “PAIS information” instead of the ascent/decent contact. When
the PDE input is activated for more than 3 minutes or the extremities of the security circuit are cut
(input SE6) for more than 3 minutes the ISO relay is activated and a fault is recorded
(Cf. 4.3.3/di).
• Traction motor double journey: If you wish to modify the value of the double journey answer
“yes” to the following and indicate the value of the time interval from 4 to 20 seconds. If the
answer is “no” the value of the time interval is fixed at 20 seconds as required by the reference
EN81 10.6.2.2.
3.2.35 On inspection, stop on AGB and AGH contacts (pre-set M.E.A "yes")
By answering "no" to this question, it allows not being stopped in the shaft by AGB and AGH contacts.
If you enter "yes", the inspection mode will be interrupted as soon as the lift car reaches the AGB or AGH contacts.
This option allows high speed lifts an easier access to the landing door top floor, situated over the AGH contact. In that
case end terminal switches for inspection mode are compulsory.
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 34 / 34
This function allows the lift car stationary at a predetermined floor (Cf. 4.2.1.).
Cf. 4.2.1
(parametro accessibile solo con il programmatore esterno MEAF110). Questo paramettro permette di indicare quale
cabina deve servire alla funzione Pompieri in conformità alla norma CEN81-72. Prima però si dovrà programmare il
piano Pompieri in cabina (entrata della scheda =PCA) (cfr. 3.2.20 e 3.2.21).
Secondo la norma in vigore sono possibili tre opzioni:
- EN81-72 (Francese): 2 entrate PMO e EL3 sono utilizzate per collegare il pulsante di apertura porte A e B.
- Inglese / Russa : identiche alla EN81-72 con specificità proprie a
ciascuno di questi paesi.
This parameter has no significance for the operation. Press the key if you do not have a name for the installation.
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 35 / 35
4 - EXPLOITATION
• A flashing display indicates the operation mode (see 4.2) and alternately the current floor position
• A fixed display indicates the current floor
The NG12 is always on operating mode. Pressing on the PRG key for one second carries out the switch from programming
mode.
To leave the programming mode press the PRG key again (all the new parameters values will be also memorised). The
NG12 returns automatically to the operating mode if no keys are touched while about ten seconds.
PRG
Floor number + +
(1sec)
+ + +
+ + +
+ + +
+ + +
DEF -- DEF
+ + DEF
+ + PRG
Once parameter values are shown on the indicator, just press once on the DEF key to display its value. Then, the left hand
side indicator point turns off and the right-hand flashes.
To return to the parameter or modify another parameter, just press once on DEF again.
The modification of parameters values is carried out by using the + and - keys.
It should be noted that for different parameters the same keys do not have the same function.
The table below shows the effect of each key according to the nature (bit, timer, counter).
KIND OF
PARAMETERS BIT TIMER COUNTER
KEYS
Action on Rising of the value
Set to 0 Not assigned
Key ( + ) until its maximum
Action on Decreasing of
Set to 0 Not assigned
Key ( - ) the value until its
minimum
Action on
Not assigned Not Reset to 0
( + ) and ( - )
assigned
simultaneously
Example of programming:
Object: setting slow speed inspection, and automatic return to floor at 10min. This example shows programming steps and
what will be displayed by pressing on the designated button.
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 39 / 39
Example: to count the number of start carried out it is necessary to wire as follows:
The value shown by the counter after ten thousand five hundred and twenty two starts would be:
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 41 / 41
Fig. 4.5
Display Définition
BC2 BC0
BP2 BP0
BC3 BC1
BP3 BP1
BC6 BC4
BP6 BP4
BC7 BC5
BP7 BP5
BC10 BC8
BP10 BP8
BC11 BC9
BP11 BP9
4.2 OPERATION
4.2.1 Resetting
When powered up, the lift goes to resetting to a parameterised top floor level whether it is not already at one top floor level
(Cf. 3.2.2.3).
But if it is already at a top floor level (AGH or AGB activated), it goes systematically to the opposite top floor.
During the resetting, the car/landing display shows any floor level.
The NG12 card indicator shows .
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 42 / 42
Fig 4.6
Then the lift travels at full speed just to the terminal-slowing switch, at the other end of the shaft, at which point it switches
to slow speed.
Fig 4.7
Finally having passed the slowing vane at the terminal floor, the lift rests at floor level with its (Cf. 3.2.9) doors
closed.
Fig 4.8
Note: If the lift overtravels at the terminal floor, check that the number of vanes with respect to the slowing parameter (see
3.2.9).
Check the condenser C1 used to filter the 24V supply to the armoire.
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 43 / 43
4.2.2 Pulsing
4.2.2.1 Vanes
Vanes are the components, which cause the displacement sensors to pulse the controller. The displacement sensors and the
vanes can be optical or electro-magnetically operated devices, this in no way effects the controller operation. Whatever the
installation, there must be four vanes between each floor arranged as shown here.
Fig. 4.9
At the terminal floors to have a door-opening zone which conforms to the requirements of the standard En81, and put
above and below floor level.
The number of vanes that are required in the whole shaft can be calculated by the formula:
Attention: The length of the vanes and the distance between two vanes is very important.
The pulsing of the selector by the displacement sensors will not function properly if the minimum distance between each
consecutive vane does not conform to the formula:
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 44 / 44
Example: A lift 1.6 m/s using a TMS03 without serial link with the car:
Fig 4.12
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 45 / 45
Fig 4.13
The display is fixed but can be alternated with the operation being executed (see 4.2)
4.3.1 Operations
Operations are discussed in order of priority. So for example the function can not be overridden by the function,
but the reverse is possible.
Start authorisation
This function shall be parameterised through the Sharp computer. This is allowed to move only when the PMO input is
activated.
This operation can be used too in case of starting on power unit.
The "heavy traffic" function is inactive by going up.
Inspection
If the lift car top control station has been switched to inspection, the REV contact is or has been opened and no calls
registering is possible.
In that mode the lift moves:
- upwards when the REM contact is closed,
- downwards when the RED contact is closed.
If the CEA contact for entrance A or CEB for entrance B is closed the corresponding doors open during the period the
contacts are closed (door timers do not operate).
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 46 / 46
If the contact BFR is closed the doors close while the contact remains closed. In any case if REM or RED are closed the
doors close immediately. The lift car moves at the speed selected by the parameter (Cf. 4.0.4.6).
• In a simplex system: if the lift is switched from inspection to normal operation (REV input is
activated), push a landing or car call buttons to restart.
• The lift goes also to resetting (cf. 4.1.1).
• In a duplex system: the lift departs to reset as soon as REV contact is made.
Note: If the panel control is on "serial link" with the car (cf 1.2.4.), "REV", "REM" and "RED" inputs are on
the TOC card.
By safety measures, "REV" input is considered as not made if the communication is cut between the TOC card and the
NG12 card (green led on the TOC card lights off, so the NG12 card lays out .
Solution:
• In case of a simplex installation, check:
the connection of the I422 card on the NG12 card
the connection of the 4 serial link wires between the TOC card and the I422 card, the
ground braid of the screened wire (NG12 controller'
s side only).
The contact CEB is activated, the doors reopen and rest open until the contact is activated.
Reset
Cf. 4.1.1
Fireman’s operation
The POM contact NO is closed, by the operation of the fireman’s switch, there are two things that can happen:
• If the lift is moving: all calls assigned are erased, and the lift stops at the first possible floor. The
doors remain closed and the lift departs for the evacuation floor programmed (see 3.2.21). When
at the evacuation floor the doors rest in the open position, the card indicator shows fireman’s
mode.
• Then if a car call is made, only a car call, the doors close, the lift departs for the floor where it
stops leaving its doors open.
Note: If the safety edge, or photocell contacts operate when the door closes the car call is erased
and has to be registered again.
• If the lift is already at a floor: the operation is exactly the same; the doors close immediately, the
safety edge and photocell remain non operational until the evacuation level is reached.
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 47 / 47
Note: To return to normal from Fireman’s operation it is necessary for the lift to be returned to
the evacuation floor otherwise the lift remains in Fireman’s mode.
Attendant control
This function cannot be put into operation if the lift is not stationary at floor level.
At stop, as soon as the PCA contact is closed all calls are erased. The car door opens and remains open.
As soon as a car call is made (unique call), door close and lift goes at the designated floor or remains door open.
Note: If the safety edge or photocells are activated during the door closing, the call is erased and has to be
registered again.
: Full load
: Out of service
This function should be parameterised with the Sharp computer by indicating the floor the car should park. If the PDE
input is made the lift car stops at the next floor and goes to the "out of service" programmed floor.
There is only a landing call at the floor the car is waiting or an action on the cell input that makes the door reopening
possible.
Going down closes the "heavy traffic" function.
Operation to bring the car lift alongside the quay from the Out of Service function.
This operation is useful when you adjust the car landing with a mobile quay that is over the landing level. It permits the
car to go up by activating the REM input or to go down by activating the RED input without executing the inspection
mode.
Once the PDE input is activated, the lift stops at the "out of service" programmed floor.
An action on REM or RED makes the lift car move on slow speed (slow speed fault is inhibited).
Schematic:
In order to allow this operation door open, a parity control of the car position is compulsory (maxi. 1,65m over the level).
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 48 / 48
4.4 FAULTS
Each time a fault occurs it is recorded, even after a cut in the mains power supply. There are actually 38 different types of
faults. These can be registered several times up to a total of 254 faults thereby giving a historical record over several
breakdowns.
4.4.1 Displaying
It is necessary to press the DEF button below the indicator to make the fault flashing (Cf. 1.2.1./10 and 4.0).
The faults are displayed one by one starting with the last or presently occurring to the first recorded. The return to the floor
number display is automatic.
Example: Three consecutive cuts in the main power, door close timer fault, locking fault gives the following display
4.4.2 Erasing
To clear the fault recorder press both the above buttons DEF and PRG simultaneously.
If after this a fault is still shown it is a fault presently occurring.
Resetting
This fault is recorded each time the lift resets, this could be due to minute breaks in the power supply or returning from
‘Test’ control to ‘normal’ after using the inspection control and fault 1h, 1b, 9A, Ad.
In conformity with the standards in force, it is necessary to verify that the power supply contacts for the lift motor have not
welded together or are blocked in the closed position, before any other flight.
To comply with this requirement a series of contacts NC are linked to the power contacts and wired to the input CCO.
If one of these contacts remains open when stop, the "02" default is recorded.
The lift restarts, as the contact is no longer blocked.
Cf. 3.2.24.
Checking the terminal-slowing switch, the slowing vanes distance, and the slowing parameter programmed, repairs this.
Overload
Direction fault
This fault can only occur during the resetting function. There are three possible causes:
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 49 / 49
• The cells of the displacement sensors in effect are mounted upside-down with respect to the lift’s
movement when going up FAI plusses first instead of FAS, when going down FAS plusses first
instead of FAI.
• The terminal slowing switches, have been wired upside down with respect to the shaft: when going
up it is AGB that acts instead of AGH and when going down AGH acts instead of AGB.
This fault ‘locks’ the system, cut then restore the mains power supply.
Using bigger vanes, increasing the distance between vanes, or reducing the distance between the displacement sensors
FAS and FAI (cf. 4.1.2.1) can repair this.
This fault is recorded when one of the terminals ‘REF’, ‘D01’, ‘V+’, ‘VOC’, ‘TH1’, ‘TH2’, ‘24dc’ are or have been
shorted to earth. The lift is only stopped if the fault persist for more than 15 seconds. The lift can be reinstated once the
short circuit has been removed.
This fault is memorised if the car or landing position indicator display output is or has been connected to the REF terminal.
In this case the information transmitted to the display is stopped and can only return after the mains power supply has been
cut and then restored. This fault allows the corresponding output to be protected.
Fire detection
If the U36 parameter has been programmed, this fault is recorded when a fire detection input is cut. Each fire detection
inputs cut is individually recorded. For the operation (see 3.2.4)
Hydraulic fault
To suit to the standards requirements regarding hydraulic lifts, a relay FC, with contacts, which can be manually opened, is
powered when the ram reaches the limit of its travel. The relay closing activates the input “OLE” and the fault is recorded.
All the car and landing calls are erased. When the lift car is lowered from the full extension position the only function
which still operate are reset, in the downwards direction, relevelling, door open and close.
The fault is repaired by pressing on the relay arm, while the lift is being lowered, until the relay FC is disarmed (see 4.0.4
and 4.0.4.1).
The fault is repaired by replacing or reprogramming the memory (Cf. 1.2.1/14), then cut and restore electrical power, to
reinstate the lift.
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 50 / 50
The "VOC" output protects itself from overload of short circuit to earth (light on earth) by neutralising all the 24 outputs
indicators and registering the "OL" fault. To reinstate the « lift in use » indicators cut then restore the electrical power, after
curing the problem.
This fault is recorded when the TH1 and TH2 inputs are cut.
By hydraulic lifts, when the heat probe is activated, the car can move to the down direction.
Note:
If the lift is equipped with a thermistor, shunt the terminals « TH1 » and « TH2 » then erase the fault (see
4.3.2),
If the fault remains the inputs TH1 and TH2 on the card are defective,
If not check the thermistors
When the inputs TH1 and TH2 have returned to normal the lift restart.
his fault appears if the CCO input contact remains closed during the travel of the car.
This fault is recorded when there is a break in the security circuit before terminal Secu. 3.
The fault is repaired by checking all the contacts (stop buttons, safety gear, etc.). The lift can be reinstated when the break
is reconnected.
Drop in the 24V power supply while the car lift if moving
The voltage at the power supply input of the card is monitored permanently.
If it drops below 18V during operation this fault is recorded.
This fault is repaired by checking the power supply network (micro power cuts) 24Vdc. Do not forget the associated
capacitor.
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 51 / 51
Note: when the voltage returns above the 18V threshold, the lift goes to reset.
This fault can only appear if the NG12 card has a bad communication with the TOC card during more than 2 seconds or
that the TOC card indicates to the NG12 card that the serial link is perturbed.
Locking fault
This fault is recorded if a call is registered and the locking procedure is not completed (Sécu. 6 is activated) at the end of
the programmed timed interval (Cf. 4.0.4.5).
To find the floor where the locking fault has occurred subtracts 20 from the number shown.
Example: If 31 is shown that gives 31-20 = 11 the fault is at the eleventh floor, as shown by the controller card display.
• With automatic doors, they open again then close after the timed interval if the door close button
is pressed (see 3.2.19).
• With manual landing doors the retiring cam is "off" then at the end of the timed interval it is
"instructed" to retract again (see 3.2.17).
For the two types of entrances, after the third attempt to close and lock the doors, all landing or car calls assigned are
erased. The next landing or car call made causes the lift to renew its attempt to close and lock the doors.
To repair the fault: check lock contacts, wiring to the lock, and if there is any obstruction to the door closing properly.
Note: If the fault occurs in when the lift is resetting at the fifth attempt the reset is abandoned. It is then necessary to cut
then restore the electrical power
An identical fault as 13 but for contacts. The break in the safety circuit is effective between terminals 4 and 6. To find the
floor where the locking fault has occurred subtract 50 from the number shown.
Example: If 55 is shown that gives 55-50 = 5 the fault is at the fifth floor, as counted by the controller card display.
Double Journey fault when traction motor is raising the lift car
This fault recorded when one of the cells of the displacement sensor does not pulse within 20 seconds of the other.
To repair the fault: check the contacts, brake, the motor supply, the filter capacitor C1for the 24V supply for the controller
and the interface relays on the card. The fault causes the lift to stop: cut then restore the current to reinstate the lift.
To test the Double journey protection is working, disconnect the RGV output and make a call.
Double Journey fault when traction motor is lowering the lift car
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 52 / 52
Identical to 7h above but occurs when traction motor is lowering the lift car.
The AGB contact have remained open when the lift car has arrived at the top of the lift shaft or when the lift car can not
move downward due to a landing or car call registered.
The two sets of contacts (AGH and AGB) are broken at the same time, when one of the contact sets return to the correct
state the lift resets itself in the corresponding direction.
To repair the fault: check the state of the contacts, the lower terminal box as well as their connection.
See 3.2.16
Check:
- The door open limit switch and its connections,
- The power supply to the door motor,
- The door open contact,
- The ROA relay on the card.
When the car stops exactly at floor level, the dot on the position indicator lights to show it is precisely at the floor (see
4.1.1).
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 53 / 53
In normal operation, the two leds FAI and FAS are illuminated (see 1.2.1.5). If the dot, which indicates the car is exactly at
floor level is illuminated whereas one of the two leds is "off" an “ out of step ” selection fault is recorded. The lift keeps on
moving anyway.
Note: A single fault of this type is recorded between two mains power supply failures.
If the controller is equipped with a Tobia system after a mains power failure the EL3 input of the NG12 is activated and the
fault recorded (see Tobia documentation).
Anti nuisance
This fault is recorded if the lift car overshoots the door zone five consecutive times.
All the calls registered are erased and the lift departs to reset.
Dispatch
After three unsuccessful attempts, this fault is memorised and the request of relevelling is cancelled until the next
travel.
This is due to the door zone shunting system, which do not succeed in establishing the security inputs SE4 and SE6 on the
card.
To repair this fault: check that the nivelator, the impulsor and the parity control circuit are good running.
5 MULTIPLEX
In this chapter we shall treat only the information concerning the management of landing calls in a duplex system. For the
operation of single controllers, please refer to the previous chapters.
5.1 PRINCIPLE
The duplex is constructed by linking two standard NG12 controllers.
One of the controllers is programmed as the ‘Master’ the other as the ‘Slave’ using the Sharp PCE500.
The landing push button are wired in parallel to both controllers.
If a fire detection system is provided the contacts are also wired in parallel with both controllers, therefore if one lift breaks
down the other can continue to operate as a simplex system.
5.1.2 Possibilities
5.2 INSTALLATION
As the method of connection is standard for the basic controller (see 2.1)
Installing two I422 interfaces carries out the communication between the two controllers or two COM_D cards connected
to the NG12 cards by screened cable.
Attention: When connecting the wires respect the polarity indicated on the interface connect the screening of the cable to
earth.
Fig 5.2 Schematic diagram for a duplex system without serial car link
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 56 / 56
5.2.2.2 Schematic for a duplex system with a car serial link with COM_D card
Fig 5.3 Schematic diagram for a duplex system with serial car link
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 57 / 57
5.2.2.3 Schematic for a duplex system with a car serial link with COM_X card
NG12 card
Master TX+
TX-
RX-
RX+
COM_X
TX+
NG12 card
TX-
Slave
RX-
RX+
COM_X
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 58 / 58
Connect the sharp to the RS232 socket of the controller chosen as the “Master” controller and answer the following
questions.
5.3.1.1 Multiplex
This parameter is used to define the duplex mode, answer “yes”.
5.3.1.8 Return to authorised zone after automatic return (pre-set MEA: "no")
This option appears only when an automatic return is programmed (Cf. 3.2.10). If the answer is "no", after a lift car
automatic return, this latter is no longer allowed to return to a zoning floor if it is at the automatic return floor.
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 59 / 59
5.3.2.1 Multiplex ?
This parameter is used to define the duplex mode , answer “yes”.
5.4 OPERATION
5.4.1 Indicator
When the duplex is functioning correctly the indicator on the two NG12 cards show the floor without flashing., if not they
show the following flashing errors:
Check:
-if the communication interfaces are correctly in place
-if the two interfaces are correctly connected
A lift is unavailable when it can no longer respond to a landing call in the required time.
During the period of unavailability the controller transmit the calls initially assigned to that lift to another lift best disposed
to respond.
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 60 / 60
• Faults: 02, 04, 06, 7d, 7h, 08, 9A,9d,9h,0F, 0H, 0t, bA,0°
• Functions: 0-, 17, CC, 0P, 0r
• Sécu 3 cut
• After the third attempt to lock the door, (faults 20 to 43) or after the door open/close time is
exceeded (faults bO, bF, A0, AF) the lift is unavailable for 1 minute. A new cycle is also starting
again.
• If the safety edge, photocell, or door open contacts are opened the lift is unavailable for the
following 20 seconds. In the case of manual doors if the door can stays open for more than 20
seconds the lift becomes unavailable.
• The lift becomes available when the photocell or safety edge contacts open or the manual door
closes again closes.
• If the lift can not move after a dispatch call because one of the terminal limit switches AGB or
AGH remains closed, then the lift is unavailable for 1 mn.
• While the lift is moving to a upper or lower heavy traffic, the lift car is unavailable (Cf. 3.2.2.8.)
NOTA: the lift becomes available again as soon as the unavailability conditions disappear.
The three leds at the front of the COM_D card show the state of the communication between the COM_D card and the car
(led CAB), the other COM_D (led COM_D) and the NG12 card (led NG12).
The three leds at the front of the COM_X card show the state of the communication between the COM_X card and the car
(TOC card), the other COM_X and the NG12 card.
• The communication is correct if the led flashes slowly (500ms)
• The communication is not correct if the led flashes rapidly (100ms)
• If the ‘NG12’ led 7 flashes rapidly, check:
If the RS232 plug is correctly connected to the NG12 card (see 1.2.4 and 5.2.2)
If the NG12 parameters are correctly programmed and the controller is receiving power
from the power supply.
• If the ‘TOC’ led 8 flashes rapidly, check:
If the COM_X card is correctly connected to the TOC card (see 5.2.2)
If the TOC card is power supplied
If the cable between the two connectors of the two COM_X cards is correctly connected
(see 5.2.2)
If the other COM_X card is receiving power from the power supply
• The two leds (red and green) indicate the state of the communication of the serial link RS422.
• If the red led flashes, it indicates that the I422 card is receiving data from the exterior.
• If the green led flashes, it indicates that the I422 card is transmitting data to the exterior.
• If the green led does not flash, check:
The RS232 plug is right connected to the NG12 card (see 1.2.1.4/4 and 5.2.2.1.)
The NG12 is right adjusted (parameters) and power supplied.
• If the red led does not flash, check:
The RS232 plug is right connected to the NG12 card ( see 1.2.1.4/7 and 5.2.2.1)
The RX+ and RX- wires are right connected (see 5.2.2.1).
• A single lift stationary at floor level with no call assigned, available, car priority finished: all the
calls at this floor are assigned to this lift.
• A single lift with calls assigned, available: only calls, which are in the same direction as the calls
already assigned to this lift, are served.
• Two lifts without calls assigned, available, car priority finished: calls are assigned to the first lift
car arrived.
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 62 / 62
• A lift car stationary at a floor is available to respond to all call in the upward and downward
direction
• A lift car moving is available for all calls in the same direction
• The two lift cars have no calls assigned and are at different floors
Fig. 5.4
Fig 5.5
The first call shall be assigned to the car, which came to rest first.
Réf : NBE002_02.doc
Date : 13/09/2002
MANUAL Page : 63 / 63
5.5.4 A car moves away from the other with no calls assigned
Fig 5.6
Fig. 5.7
The car (2) answers all the up calls from its starting floor up to car (1). The car (1) answers all the down calls. It answers
the up calls below car (2) if it is the closest and according to the blocking formula (Cf. 5.5.8.).
Fig. 5.8
Fig. 5.9
The car 2 serves all the up calls starting from its floor.
The car 1 serves all the down calls just up to car 2 and eventually above if the car 2 is overloaded according to the blocking
formula (see.5.5.8.).
• The number of calls that are in the same direction as car 2 and from which car 1 is to be sent is
calculated in the following manner:
Example: car 1 is parked at the ground floor. Car 2 is moving to the up direction, is in front of the 2nd floor and is taking on
3 calls:
Car 2 has 3 calls: that is higher than the result of the formula (2) and that makes the car 1 be sent even if it is lower than the
car 2 for answering the landing calls.
• During the travel of the lift the areas of calls acceptance can be modified.
• The ‘Master’ controller attributes calls according to the possibility of a car to respond. In
consequence It is possible that a call given to one car will be removed if a second car is in a better
position to respond. When a car has neither a landing or a car call to respond, it stops at the next
floor doors and does not open the doors.