PROJECT TITLE 132kV GIS Substation at Torrent Kazipur OUR CLIENT DRAWING NUMBER & REV NO. KZP-GIS-SIE-LAYOUT-E-001 Following points shall be verified by both Preparer and Reviewer and final signed checklist shall be maintained in project folder: Review Status SL. (Yes / NA / Deviation no.) CHECK NO. Preparer Reviewer Section no along with Bay descriptions are marked above each section view and 1 Yes is matching with the section marking in Plan Layout PD sensor shown at current locations as per PD Configuration rule book and is 2 Yes matching with the location shown in gas SLD 3 All typical from plan layout is covered with the total number of section views Yes 4 Reference drawing table (including Gas SLD / Customer layout) is included Yes Notes regarding “Compartment accessories, Location of PD Sensors, Maximum 5 Yes weight of gas compartment” are included 6 Reference Axis-Z are marked, and all dimensions are linked with this Axis Yes 7 Internal clearance between GIS and nearest building wall is marked on both sides Yes 8 CB Removal / maintenance space is clearly marked as per Product type Yes Standard IEC Notes “Ventilation requirement & Closed Operating area safety” are 9 Yes included 10 Section marking is correctly matching with the orientation of section views Yes Equipment legends (Q0, Q1, T1 etc.) are clearly marked and is correctly matching 11 Yes with equipment sequence in Gas SLD 12 Minimum Crane Tonnage and hook height requirements are clearly marked Yes 13 FGL & FFL levels are clearly marked and is verified with Customer layout Yes 14 Centralized / Decentralized Gas monitoring is matching with Gas SLD Yes 15 Equipment legend table is included, and all equipment’s are covered Yes 16 Typical details of Busduct wall opening is included for projects with Busducts NA 17 Dimension from top of GIS to bottom of crane hook is marked Yes 18 Busbar & LCC heights are marked Yes 19 LCC is shown as Floor mounted / Integrated as per data pool and plan layout Yes 20 Reversing Module is not used on either of DS for 400kV GIS Configuration NA 21 Circuit symbols are added in section view and configuration verified with SLD Yes