The document provides instructions for installing a 1K Ohm resistor to disable the power monitoring PFI signal in an INFI90 power supply system. The PFI signal is designed to shut down the system if the bus voltage is out of tolerance, but often causes abnormal shutdowns in the field. To prevent this, a 1K Ohm resistor should be connected between the +5V dc bus and PFI signal to keep the PFI signal high at all times. It is important that the power system still has fault alarm configuration in case of any issues.
The document provides instructions for installing a 1K Ohm resistor to disable the power monitoring PFI signal in an INFI90 power supply system. The PFI signal is designed to shut down the system if the bus voltage is out of tolerance, but often causes abnormal shutdowns in the field. To prevent this, a 1K Ohm resistor should be connected between the +5V dc bus and PFI signal to keep the PFI signal high at all times. It is important that the power system still has fault alarm configuration in case of any issues.
The document provides instructions for installing a 1K Ohm resistor to disable the power monitoring PFI signal in an INFI90 power supply system. The PFI signal is designed to shut down the system if the bus voltage is out of tolerance, but often causes abnormal shutdowns in the field. To prevent this, a 1K Ohm resistor should be connected between the +5V dc bus and PFI signal to keep the PFI signal high at all times. It is important that the power system still has fault alarm configuration in case of any issues.
To install 1K Ohm resistor in order to disable INFI90 system power
supply monitoring system PFI signal
There is a power monitoring feature in the INFI90 power system,
(Power fail interrupt. A signal that causes active controllers to reset and the communication system to be bypassed, when generated in the system by an out of tolerance bus voltage.) Stop all the main modules in the cabinet. This function is designed to keep the main modules working normally. However, in the field often due to the wrong action of PFI caused the entire power plant to shut down. In order to prevent the abnormal shutdown the power plant due to the wrong action of PFI, a remedy is recommended. The specific work contents are as follows: 1. Prepare a 1 k Ω 1/2 w resistor, two pressure to splice line pressing 2. Pull out the PFI plug on the dc bus row and wrap it with insulating tape 3. To make good 1 kΩ resistor is connected to + 5 v dc bus and PFI
The purpose is to keep the PFI signal on the dc bus +5V at all times. Work is done.
While completing the above work, it should be noted that the power system should have fault alarm configuration on the loop. If necessary, an external power fault alarm relay can be installed.
PFI (Power fail interrupt. A signal that causes active controllers to
reset and the communication system to be bypassed, when generated in the system by an out of tolerance bus voltage.)