北京贝利工程注意 Engineering Notice

To install 1K Ohm resistor in order to disable INFI90 system power


supply monitoring system PFI signal

There is a power monitoring feature in the INFI90 power system,


(Power fail interrupt. A signal that causes active controllers to reset
and the communication system to be bypassed, when generated in
the system by an out of tolerance bus voltage.)
Stop all the main modules in the cabinet. This function is designed
to keep the main modules working normally. However, in the field
often due to the wrong action of PFI caused the entire power plant to
shut down.
In order to prevent the abnormal shutdown the power plant due to
the wrong action of PFI, a remedy is recommended. The specific
work contents are as follows:
1. Prepare a 1 k Ω 1/2 w resistor, two pressure to splice line
pressing
2. Pull out the PFI plug on the dc bus row and wrap it with
insulating tape
3. To make good 1 kΩ resistor is connected to + 5 v dc bus and
PFI
 
The purpose is to keep the PFI signal on the dc bus +5V at all
times. Work is done.
 
While completing the above work, it should be noted that the power
system should have fault alarm configuration on the loop. If
necessary, an external power fault alarm relay can be installed.

PFI (Power fail interrupt. A signal that causes active controllers to


reset and the communication system to be bypassed, when
generated in the system by an out of tolerance bus voltage.)