3 - 31
®
ELFOSPACE 3-31
NEW GENERATION VERTICAL BUILT-IN WATER-SOURCE ROOM TERMINAL FOR MEDIUM
AND LARGE INSTALLATIONS
ELFOSPACE 3 - 31 (ACQUA)
Cooling Heating
Size
ELFOSYSTEM : [kW] [kW]
3 1.51 3.65
ELFOROOM 5 1.96 4.24
REPLACE: BT05A002GB-03
7 2.54 5.51
ELFOSPACE 9 3.03 6.08
11 3.73 7.74
ELFOENERGY
15 4.21 8.69
ELFOCONTROL 17 5.49 11.5
21 6.37 12.7
ELFOFRESH 25 7.44 14.3
31 9.03 17.1
Soft, yet not aggressive lines, homogeneously integrating in every installation room. Simple and intuitive controls, matched with a gentle
BT05A002GB-04
breeze caressing you. Silent operation and easy cleaning. These concepts have been the base for designing ELFOSPACE, the latest
generation room-type terminal ideal for every installation. Ten sizes with an endless range of accessories to meet every requirement of
system applications.
(MS =)Standard oulet (MS =)Standard oulet (MR =)90° air outlet (MR =)90° air outlet
(R3 =)Intake from below (RF =)Front air inlet (R3 =)Intake from below (RF =)Front air inlet
2
TERMINALS
3 - 31
FILTRATION
Easily removable air filter, composed of a metal frame incorporating the filte-
ring plate. It can be regenerated by water-washing, blowing, vacuuming. In
resin-coated and interwoven polyester acrylic cloth, with high efficiency. Suita-
ble for dusts and pollens (UNI-EN779, filtering degree G3, class M1).
TRAY
Condensate collecting tray with discharge Ø 21 mm (standard on the same
side of the hydraulic fittings) and thermal insulation (class M1).
ELECTRICAL PANEL
The standard unit is supplied equipped only motor cable, without command
panel and terminal board. In this way, the client can choose from a wide range
of command panels and terminal boards available as accessories.
ACCESSORIES
- Terminal block with minimum water temperature Klixon
- Control on the unit: off + 3 speed switch
- Control on board: BULB thermostat (3 speed.+off+E/l+Temp.selection)
- Control on the unit: BULB thermostat (3 speed + off + remote E/l +
Temp.selection)
- Control on the unit:BULB thermostat(3speed+off+E/I+temp.select.)+ min.
temperature thermostat
- Control on the unit:BULB thermostat + on/off heaters
- Remote control with 3 position switch + on/off for wall installation
- Remote control with E/I +3V +on/off for wall installation
- Plurifunctional remote control for wall installation
- Pluri-function room control for 0-10V valves
- hot water min. temperature thermostat
- Remote probe for ambient air temperature for electromechanical thermo-
stats.
- Control device for more units with a single room control.
- CLIVET TALK ROOM electronic (Elfo Control)
- Command keyboard mounted on- board
BT05A002GB-04
3
TERMINALS
3 - 31
Configuration
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12)
ELFOSPACE IN-V 3 MS R3 - TR - SX - - - - - -
3 MS(Std) R3 ( Std) - (Std) TR (Std) - (Std) SX ( Std) - (Std) - (Std) - (Std) - ( Std) - ( Std) - ( Std)
5 MR RF CTS TRM SP1 DX B14T RE KBI2 2V2 3V2 BRV
CTR HID-F1 (3-7-11-17-25)
7 KBI4 2V4 3V4
... HID-F2 10V2
31 HID-F3 10V4
HID-F4
HID-F5
HID-F6
NECESSARY CONFIGURATION STRING FOR SUPPLYING THE UNIT WITH THE INDICATED ELEMENTS/ACCESSORIES ALREADY MOUNTED ON THE APPLIANCE.
SX SX
MR
BT05A002GB-04
(MS =)Standard oulet (RF =)Front air inlet (MR =)90° air outlet (RF =)Front air inlet
DX DX
MS
SX DX DX
SX
SX SX
MR
RF
(SX)Water fittings to the left (SX)Water fittings to the left
(DX)Water fittings to the right RF (DX)Water fittings to the right
4
TERMINALS
3 - 31
Configuration
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12)
ELFOSPACE IN-H 3 MS R3 - TR - SX - - - - - -
3 MS( Std) R3 (Std) - (Std) TR (Std) - (Std) SX (Std) - (Std) - (Std) - (Std) - (Std) - (Std) - (Std)
5 RP CTS TRM SP1 DX B14T RE KBI2 2V2 3V2 BRODX
7 CTR (3-7-11-17-25) BROSX
KBI4 2V4 3V4
... 10V2
31 10V4
NECESSARY CONFIGURATION STRING FOR SUPPLYING THE UNIT WITH THE INDICATED ELEMENTS/ACCESSORIES ALREADY MOUNTED ON THE APPLIANCE.
(MS =)Standard oulet (R3 =)Intake from below (MS =)Standard oulet (RP =)rear intake
DX DX
SX SX
MS DX DX
MS
BT05A002GB-04
SX SX
R3 RP
5
TERMINALS
3 - 31
Configuration
(1) (2) (3) (4) (5) (6) (7) (8) (9) ( 10) (11) (12)
ELFOSPACE OUT-V 3 MS R3 - TR - SX - - - - - -
3 MS ( Std) R3 ( Std) - ( Std) TR ( Std) - ( Std) SX ( Std) - ( Std) - ( Std) - ( Std) - ( Std) - ( Std) - ( Std)
5 RF CTS TRM SP1 DX B14T RE KBI2 2V2 3V2 BRV
CTRD HID-F1 (3-7- 11-17-25)
7 KBI4 2V4 3V4
... HID-F2 10V2
31 HID-F3 10V4
HID-F4
HID-F5
HID-F6
NECESSARY CONFIGURATION STRING FOR SUPPLYING THE UNIT WITH THE INDICATED ELEMENTS/ACCESSORIES ALREADY MOUNTED ON THE APPLIANCE.
(MS =)Standard oulet (R3 =)Intake from below (MS =)Standard oulet (RF =)Front air inlet
BT05A002GB-04
DX DX
DX DX
SX MS SX MS
SX SX
6
TERMINALS
3 - 31
Configuration
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12)
ELFOSPACE OUT-H 3 MS R3 - TR - SX - - - - - -
3 MS (Std) R3 (Std) - (Std) TR (Std) - (Std) SX (Std) - (Std) - (Std) - (Std) - (Std) - (Std) - (Std)
5 RP CTS TRM SP1 DX B14T RE KBI2 2V2 3V2 BRODX
CTR (3-7-11-17-25) BROSX
7 KBI4 2V4 3V4
... 10V2
31 10V4
NECESSARY CONFIGURATION STRING FOR SUPPLYING THE UNIT WITH THE INDICATED ELEMENTS/ACCESSORIES ALREADY MOUNTED ON THE APPLIANCE.
(RE)Electric heaters.
(1)Air supply (9)Equalizing valve
(MS)Standard oulet (-)Equalizing valve: not required
(2)Return standard unit
(R3)Floor air inlet (KBI2)2 tube water balancing kit = ball valve+water balancing kit
standard unit (KBI4)4 tube water balancing kit = 2 ball valves+2 water balancing kit
(RP)rear intake (10)2-ways valve
(3)electronic version (-)Shut-off valve on the system water connections: not required
(-)Electric version: not required standard unit
standard unit (2V2)ON/OFF 2 way valve kit for 2 tube system
(CTS)CLIVET TALK TERMINAL electronic for HID-T2 or HID-T3 thermostats (2V4)ON/OFF 2 way valve kit for 4 tube system
(ELFOControl) (11)three-way valve
(CTR)CLIVET TALK ROOM electronic (Elfo Control) (-)Three-way valve: not required
(4)Controls keyboard standard unit
(TR)terminal block for motor connection (3V2)3-way ON/OFF valve kit for 2-pipe systems
standard unit (3V4)3-way ON/OFF valve kit for 4-pipe systems
(TRM)Terminal block with minimum water temperature Klixon (10V2)0-10V 3 way valve kit for 2 tube system
(5)remote communication serial port (10V4)0-10V 3 way valve kit for 4 tube system
(-)Remote communication serial port: not required (12)auxiliary condensate collection tray
standard unit (-)Auxiliary condensate collection pan: not required
(SP1)RS485 remote communication serial port standard unit
(6)Water fittings (BRODX)Auxiliary condensate collection pan (horizontal installation;DX fittings)
(SX)Water fittings to the left (BROSX)Auxiliary condensate collection pan (horizontal installation; SX fittings)
standard unit
(DX)Water fittings to the right
(7)hot water coil
(-)Hot water coil: not required
standard unit
(B14T)1 row hot water additional coil for 4 tubes system
Available only for the following sizes: 3 - 7 - 11 - 17 - 25
(8)Electric heaters.
(-)Heating electric heaters: not required
standard unit
SX SX
BT05A002GB-04
MS MS
DX
SX
DX
DX
SX SX
R3
RP
R3
RP
7
TERMINALS
3 - 31
Size 3 5 7 9 11 15 17 21 25 31
COOLING
Cooling capacity 1 kW 1.07 1.31 1.74 2.02 2.71 2.99 3.66 4.12 4.71 7.39
Sensible capacity 1 kW 0.8 0.91 1.24 1.37 1.89 2.05 2.54 2.78 3.13 4.93
HEATING
Heat output 2 kW 2.43 2.63 3.55 3.82 5.32 5.82 7.16 7.71 8.56 13.5
AIR HANDLING SECTION FANS (OUTLET)
Air flow 3 l/s 56 57 69 71 108 111 163 167 258 266
(1) ambient air 26°C DB / 19.5°C WB (3) air flow with free outlet (0 Pa static pressure)
water inlet 7°C and outlet 12°C
(2) ambient temperature 20°C
water inlet 70°C and outlet 60°C
Size 3 5 7 9 11 15 17 21 25 31
COOLING
Cooling capacity 1 kW 1.27 1.6 2.11 2.52 3.24 3.62 4.4 5.04 5.97 8.22
Sensible capacity 1 kW 0.97 1.14 1.52 1.74 2.3 2.53 3.11 3.45 4.03 5.52
HEATING
Heat output 2 kW 2.97 3.34 4.41 4.9 6.53 7.21 8.84 9.69 11.1 15.2
AIR HANDLING SECTION FANS (OUTLET)
BT05A002GB-04
Air flow 3 l/s 81 83 100 103 153 157 230 237 346 356
(1) ambient air 26°C DB / 19.5°C WB (3) air flow with free outlet (0 Pa static pressure)
water inlet 7°C and outlet 12°C
(2) ambient temperature 20°C
water inlet 70°C and outlet 60°C
8
TERMINALS
3 - 31
(1) coil max. pressure. 15 bar is the water side max. pressure allowed in presence of accessoires(exemple 2-3 way valves)
SOUND LEVELS
FAN SPEED: Low speed (L) FAN SPEED: Medium speed (M)
Sound Power Level (dB) Sound Sound Power Level (dB) Sound
Sound Sound
pressure pressure
Size
Size
63 125 250 500 1000 2000 4000 8000 dB(A) dB(A) 63 125 250 500 1000 2000 4000 8000 dB(A) dB(A)
3 46 47 43 45 35 33 29 32 34 45 3 46 49 48 51 45 41 32 28 40 51
5 46 47 43 45 35 33 29 32 34 45 5 46 49 48 51 45 41 32 28 40 51
7 47 48 45 46 40 34 26 28 35 46 7 50 50 49 51 47 44 37 27 41 52
9 47 48 45 46 40 34 26 28 35 46 9 50 50 49 51 47 44 37 27 41 52
11 49 53 45 46 39 31 25 31 35 46 11 47 48 51 53 48 43 34 29 42 53
15 49 53 45 46 39 31 25 31 35 46 15 47 48 51 53 48 43 34 29 42 53
17 51 53 47 48 43 38 30 35 38 49 17 49 49 51 53 50 48 40 32 44 55
21 51 53 47 48 43 38 30 35 38 49 21 49 49 51 53 50 48 40 32 44 55
25 52 50 52 52 48 43 34 38 42 53 25 51 52 58 58 54 53 45 36 49 60
31 52 50 52 52 48 43 34 38 42 53 31 51 52 58 58 54 53 45 36 49 60
power level
Octave band (Hz) level
BT05A002GB-04
The sound pressure level is measured 1 metre from the external surface of the wall
63 125 250 500 1000 2000 4000 8000 dB(A) dB(A) mounted in view unit, for the built-in unit it is possible a sound pressure reduction of 2 dB
or higher. The determination of the sound pressure levels has been made with respect
3 50 51 52 55 49 46 38 30 44 55 to the UNI-EN-ISO 3744 certification.
5 50 51 52 55 49 46 38 30 44 55
7 52 53 54 55 52 50 43 34 46 57
9 52 53 54 55 52 50 43 34 46 57
11 48 49 55 57 53 49 41 33 47 58
15 48 49 55 57 53 49 41 33 47 58
17 50 52 56 58 55 53 46 38 49 60
21 50 52 56 58 55 53 46 38 49 60
25 55 57 63 63 59 58 51 42 54 65
31 55 57 63 63 59 58 51 42 54 65
9
TERMINALS
3 - 31
COOLING PERFORMANCE
TEMPERATURE INLET/OUTLET (°C)
Ta
Size (°C) 6 / 11 7 / 12 9 / 14 10 / 15 13 / 18
DB/WB
kWf kWs kWf kWs kWf kWs kWf kWs kWf kWs
22 / 15.4 0.95 0.91 0.86 0.83 0.69 0.69 0.60 0.60 0.37 0.37
24 / 17 1.19 1.06 1.07 0.98 0.85 0.84 0.75 0.75 0.53 0.53
26 / 18.6 1.49 1.19 1.33 1.12 1.06 0.97 0.95 0.90 0.70 0.69
3
27 / 19.5 1.68 1.25 1.51 1.18 1.21 1.04 1.09 0.97 0.79 0.76
28 / 20.3 1.86 1.32 1.68 1.25 1.36 1.11 1.23 1.04 0.89 0.82
30 / 21.9 2.26 1.45 2.07 1.38 1.71 1.24 1.54 1.17 1.07 0.97
22 / 15.4 1.22 1.12 1.10 1.03 0.87 0.86 0.76 0.76 0.49 0.49
24 / 17 1.55 1.29 1.38 1.20 1.09 1.03 0.96 0.94 0.67 0.67
26 / 18.6 1.93 1.45 1.73 1.36 1.38 1.19 1.23 1.10 0.88 0.84
5
27 / 19.5 2.17 1.52 1.96 1.43 1.58 1.26 1.41 1.17 1.01 0.91
28 / 20.3 2.39 1.60 2.17 1.51 1.78 1.34 1.60 1.25 1.13 0.99
30 / 21.9 2.88 1.75 2.66 1.67 2.23 1.49 2.02 1.41 1.40 1.15
22 / 15.4 1.59 1.48 1.43 1.36 1.14 1.13 1.00 1.00 0.64 0.64
24 / 17 2.02 1.70 1.80 1.59 1.42 1.36 1.25 1.25 0.88 0.88
26 / 18.6 2.51 1.91 2.25 1.79 1.80 1.57 1.60 1.46 1.15 1.12
7
27 / 19.5 2.82 2.00 2.54 1.89 2.06 1.67 1.84 1.55 1.31 1.22
28 / 20.3 3.10 2.10 2.82 1.99 2.31 1.77 2.08 1.66 1.47 1.32
30 / 21.9 3.72 2.30 3.44 2.19 2.89 1.97 2.62 1.86 1.82 1.53
22 / 15.4 1.91 1.69 1.70 1.56 1.32 1.31 1.16 1.16 0.78 0.78
24 / 17 2.43 1.94 2.16 1.81 1.69 1.56 1.49 1.43 1.02 1.02
26 / 18.6 2.99 2.16 2.70 2.04 2.16 1.79 1.93 1.66 1.33 1.28
9
27 / 19.5 3.34 2.27 3.03 2.14 2.47 1.89 2.21 1.77 1.53 1.39
28 / 20.3 3.66 2.38 3.35 2.25 2.77 2.00 2.49 1.88 1.74 1.50
30 / 21.9 4.34 2.61 4.04 2.48 3.44 2.23 3.13 2.11 2.19 1.73
22 / 15.4 2.35 2.13 2.10 1.97 1.66 1.65 1.46 1.46 0.96 0.96
24 / 17 2.98 2.45 2.65 2.29 2.09 1.97 1.84 1.81 1.28 1.28
26 / 18.6 3.69 2.74 3.31 2.58 2.65 2.26 2.36 2.10 1.66 1.62
11
27 / 19.5 4.12 2.87 3.73 2.71 3.03 2.40 2.71 2.24 1.91 1.76
28 / 20.3 4.52 3.01 4.13 2.85 3.40 2.54 3.06 2.38 2.15 1.91
30 / 21.9 5.39 3.29 5.01 3.14 4.24 2.83 3.85 2.67 2.67 2.20
22 / 15.4 2.64 2.37 2.38 2.19 1.89 1.83 1.66 1.65 1.07 1.07
24 / 17 3.37 2.72 3.00 2.54 2.36 2.18 2.08 2.00 1.43 1.43
26 / 18.6 4.17 3.05 3.74 2.87 2.98 2.51 2.65 2.33 1.86 1.79
15
27 / 19.5 4.66 3.20 4.21 3.02 3.40 2.66 3.04 2.48 2.15 1.94
28 / 20.3 5.12 3.35 4.66 3.17 3.82 2.81 3.43 2.63 2.42 2.10
BT05A002GB-04
30 / 21.9 6.09 3.67 5.65 3.49 4.76 3.14 4.33 2.96 3.04 2.43
22 / 15.4 3.47 3.15 3.10 2.91 2.44 2.43 2.15 2.15 1.42 1.42
24 / 17 4.39 3.62 3.91 3.38 3.07 2.91 2.71 2.67 1.89 1.89
26 / 18.6 5.43 4.04 4.87 3.80 3.89 3.33 3.47 3.10 2.46 2.39
17
27 / 19.5 6.06 4.23 5.49 4.00 4.45 3.53 3.98 3.30 2.82 2.60
28 / 20.3 6.66 4.43 6.07 4.20 4.99 3.74 4.49 3.50 3.17 2.81
30 / 21.9 7.94 4.85 7.37 4.62 6.23 4.16 5.66 3.93 3.94 3.25
10
TERMINALS
3 - 31
COOLING PERFORMANCE
TEMPERATURE INLET/OUTLET (°C)
Ta
Size (°C) 6 / 11 7 / 12 9 / 14 10 / 15 13 / 18
DB/WB
kWf kWs kWf kWs kWf kWs kWf kWs kWf kWs
22 / 15.4 4.04 3.54 3.59 3.28 2.81 2.75 2.47 2.47 1.65 1.65
24 / 17 5.11 4.06 4.56 3.80 3.58 3.27 3.16 3.01 2.15 2.15
26 / 18.6 6.29 4.53 5.68 4.27 4.56 3.74 4.06 3.48 2.80 2.69
21
27 / 19.5 7.01 4.75 6.37 4.49 5.20 3.97 4.66 3.70 3.23 2.92
28 / 20.3 7.67 4.98 7.04 4.72 5.82 4.19 5.25 3.93 3.66 3.15
30 / 21.9 9.09 5.44 8.47 5.18 7.22 4.67 6.58 4.41 4.62 3.63
22 / 15.4 4.72 4.05 4.22 3.76 3.25 3.17 2.78 2.78 1.43 1.43
24 / 17 5.97 4.64 5.35 4.34 4.17 3.75 3.62 3.45 2.10 2.10
26 / 18.6 7.32 5.17 6.64 4.88 5.32 4.29 4.68 3.99 2.84 2.84
25
27 / 19.5 8.13 5.43 7.44 5.13 6.06 4.54 5.37 4.25 3.29 3.29
28 / 20.3 8.87 5.69 8.19 5.39 6.77 4.80 6.04 4.51 3.71 3.63
30 / 21.9 10.4 6.21 9.82 5.92 8.37 5.34 7.54 5.05 4.60 4.18
22 / 15.4 5.80 4.88 5.12 4.53 3.96 3.83 3.47 3.47 2.39 2.39
24 / 17 7.30 5.57 6.51 5.21 5.12 4.51 4.51 4.16 3.03 3.03
26 / 18.6 8.91 6.21 8.08 5.86 6.53 5.15 5.82 4.79 3.93 3.73
31
27 / 19.5 9.88 6.52 9.03 6.16 7.42 5.45 6.66 5.10 4.56 4.04
28 / 20.3 10.8 6.83 9.92 6.47 8.28 5.77 7.49 5.41 5.18 4.35
30 / 21.9 12.6 7.45 11.8 7.10 10.2 6.40 9.33 6.05 6.63 5.00
BT05A002GB-04
11
TERMINALS
3 - 31
HEATING PERFORMANCE
EXCHANGER WATER INLET TEMPERATURE (°C)
Size Ta (°C) 40 50 55 60 70 80
12
TERMINALS
3 - 31
HEATING PERFORMANCE
EXCHANGER WATER INLET TEMPERATURE (°C)
Size Ta (°C) 40 50 55 60 70 80
BT05A002GB-04
13
TERMINALS
3 - 31
ture of 10°C.
10
8
6
4
3
2
1
80 100 200 300 400 500 600 800 1000 2000 3000
Q (l/h)
%
100 1,0
90 0,9
80 0,8
70 0,7
60 0,6 Q = % AIR FLOW THAN NOMINAL AIR FLOW
FK = CAPACITIES' CORRECTION COEFFICIENT
KF
FK
0 0
0 10 20 30 40 50 60 70 80 90 100
%Q
Q 1.00 0.95 0.90 0.85 0.80 0.75 0.70 0.65 0.60 0.55 0.50 0.45 0.40 0.35 0.30
%Q 100 95 90 85 80 75 70 65 60 55 50 45 40 35 30
Kwf 1.00 0.97 0.95 0.92 0.89 0.87 0.84 0.81 0.77 0.74 0.71 0.67 0.63 0.59 0.55
Kws 1.00 0.97 0.93 0.90 0.86 0.83 0.79 0.76 0.72 0.68 0.64 0.60 0.55 0.51 0.46
Kwt 1.00 0.97 0.94 0.91 0.87 0.84 0.81 0.77 0.74 0.70 0.66 0.62 0.58 0.53 0.49
reductions of air flow-rate and cooling/heating capacity according to the static pressure
BT05A002GB-04
PU
Pa
0 Pa 20 Pa 40 Pa 60 Pa 0 Pa 20 Pa 40 Pa 60 Pa 0 Pa 20 Pa 40 Pa 60 Pa
ELFOSPACE 3-5-7-9 ELFOSPACE 11-15-17-21 ELFOSPACE 25
H 1 0,94 0,78 \ 1 0,96 0,88 0,71 1 0,97 0,93 0,85 PU = AVAILABLE STATIC PRESSURE
Kwf M 0,91 0,83 0,51 \ 0,92 0,88 0,77 \ 0,93 0,91 0,86 0,75 Q = AIR FLOW
HIGH SPEED (H)
L 0,75 0,63 \ \ 0,77 0,72 0,55 \ 0,81 0,78 0,73 0,57 MEDIUM SPEED (M)
H 1 0,92 0,73 \ 1 0,95 0,85 0,64 1 0,97 0,91 0,82 LOW SPEED (L)
KWF = COOLING CAPACITY IN KW
Kws M 0,89 0,79 0,42 \ 0,90 0,84 0,71 \ 0,91 0,88 0,82 0,69 KWS = SENSIBLE COOLING CAPACITY (KW)
L 0,69 0,55 \ \ 0,72 0,65 0,46 \ 0,76 0,73 0,66 0,48 KWT = HEATING CAPACITY (KW)
H 1 0,93 0,74 \ 1 0,95 0,86 0,66 1 0,97 0,92 0,83
Kwt M 0,89 0,80 0,45 \ 0,91 0,85 0,73 \ 0,92 0,89 0,83 0,71
L 0,71 0,58 \ \ 0,74 0,68 0,49 \ 0,77 0,74 0,68 0,50
H 1 0,88 0,61 \ 1 0,92 0,78 0,5 1 0,95 0,87 0,73
Q M 0,83 0,69 0,26 \ 0,85 0,77 0,59 \ 0,87 0,82 0,74 0,56
L 0,57 0,40 \ \ 0,60 0,52 0,30 \ 0,65 0,61 0,53 0,32
Technical data referring to the following conditions: Standard unit - atmospheric pressure 1013 mbar - electrical power supply 230V/1Ph/50Hz. Thermal and Cooling
Yield: Values calculated based on data measured in calorimetric chamber, ref. standards UNI 6552 , UNI 6552/A242.
Air flow rate and static pressure: values measured with case ref. standards AMCA 210-74 fig.11 and duct + diaphragm ref. standards CNR-UNI 10023.
14
TERMINALS
ACCESSORIES / CONFIGURATIONS 3 - 31
ELFOSpace OUT IN
Type of installation V H V H
TR terminal block for motor connection CA - CA -
TRM Terminal block with minimum water temperature Klixon CA - CA -
HID-F1 Control on the unit: off+3 speed switch CA - CA -
HID-F2 Control on the unit: BULB thermostat (3 speeds + off + E/I + Temp. selection) C - C -
HID-F3 Control on the unit: BULB thermostat (3 speeds + off + E/I remote + Temp. selection) C - C -
HID-F4 Control on the unit:BULB thermostat + min. temperature thermostat CA - CA -
HID-F5 Control on the unit:BULB thermostat + on/off heaters C - C -
ELECTRICAL VERSIONS
PV90 Support plinth with cover for in-view vertical units h=90mm A - - -
VARIANTS
PV155 Support plinth with cover for in-view vertical units h=155mm A - - -
PVG155 Support plinth with cover h=155mm and intake grille for in-view vertical units A - - -
PPV Rear cover panel for OUT-V without support feet A - - -
PPV90 Rear cover panel for OUT-V with support feet h=90mm A - - -
PPV155 Rear cover panel for OUT-V with support feet h=155mm A - - -
FTZ Galvanized steel plate falseframe - - A A
PNA Pre-painted panel with outlet and intake grilles - - A A
MS Standard oulet C C C C
M90 90° air outlet - - C -
R3 Floor air inlet C C C C
BT05A002GB-04
RF Front intake C - C -
RP Rear inlet - C - C
SER Manual outside air damper for Vertical and horizontal installation A A A A
AERAULIC VARIATIONS
TR - terminal block for motor connection TRM - Terminal block with minimum water temperature
TM
Fan connection terminal board Mammut connecting terminal with thermostat of
min water temperature
MV MV
Functions: Functions:
4-position switch (OFF/3 speed) 4-position switch (OFF/3 speed)
1
switch Summer/Winter
bulb thermostat on the intake 1
room temperature control
0
2 0
1 3 2
0 1 3
0
Configuration Detail
separately supplied accessories Configuration Detail
HID-F3 - Control on the unit: BULB thermostat (3 HID-F4 - Control on the unit:BULB thermostat
speed + off + remote E/l + Temp.selection) (3speed+off+E/I+temp.select.)+ min. temperature
Functions:
TA TM
4-position switch (OFF/3 speed) Functions:
switch Summer/Winter 4-position switch (OFF/3 speed) TA
bulb thermostat on the intake switch Summer/Winter
room temperature control bulb thermostat on the intake
It is different from the HID-F2 because the 1 room temperature control
Summer/Winter section is remotized in Minimum hot water temperature thermostat
order to make the centrally switching. It is different from HID-F2 because the water min. 1
0
2 temperature clickson is present.
1 3 0
2
0
1 3
Configuration Detail
0
Configuration Detail separately supplied accessories
HID-F5 - Control on the unit:BULB thermostat + on/ HID-F6 - Control mounted on unit's side:
off heaters multi-function electronic room thermostat
BT05A002GB-04
The electronic control mounted on board the HID-F6 unit has the following
Functions: functions:
4-position switch (OFF/3 speed) -3 fan speed
switch Summer/Winter RE -on/off valve management both for the 2 pipe
room temperature control and the 4 pipe systems
electric heater on/off control -manual summer/winter divertion
-activation/deactivation of the antistratification
TA function
-possibility of setting two different
configurations: thermostat motor + thermostat
valves or only thermostat valves with motor
1 always running
-adjustable range of set point temperature
0
(handle lock)
2 -possibility of setting/modifying the distance
1 3 between the automatic speeds
0 -unit control via minimum temperature
thermostat of TM water (sold seperately)
16
TERMINALS
3 - 31
HID-E1 - Remote control with 3 position switch + on/off for wall installation
electromechanical room thermostat HID-E1 for wall installation.
It allows:
-the selection of 3 speeds (MIN-MED-MAX)
-the manual change Summer/Winter
The TM hot water min. temperature Clickson can be connected.
Dimensions: 184x82x27 mm
HID-E2 - Remote control with E/I +3V +on/off for wall installation
HID-E2 electromechanical room thermostat for wall installation
It allows:
-setting of the desidered temperature (10-30°C)
-selection of the 3 speeds (MIN - MED - MAX)
-on/off
-manual mode switching Summer / Winter
-unbroken ventilation or controlled by a thermostat
It can be connected to the remote air probe
PTAB - Remote probe for ambient air temperature for electromechanical thermostats.
The remote room air sensor can be connected to the HID-E_ room thermostats complete with sensor input (HID-E1 excepted).
DPC - Control device for more units with a single room control.
Control device from single thermostat for max. 4 units compatible with HID-E electromechanical thermostats_
separately supplied accessories
17
TERMINALS
3 - 31
CTS - CLIVET TALK TERMINAL electronic for HID-T2 or HID-T3 thermostats(ELFOControl) Configuration Detail
This is a card for control of the unit which, in addition to basic functions, allows it to be connected to
a network of similar units managed centrally by ELFOControl, which in turn can be connected to a
supervisor, moreover it can also manage a linked mini-net ,of maximum 8 units, by RS485 or Wire-
less serial ports, with a Master-Slave system. This type of electronic card is suited for communica-
ting via RS485 or wireless if connected to SP1 or SPZB devices.
The microprocessor control installed in the unit receives operating settings from one of the following
devices:
HID-T2 - room control for wall installation
HID-T3 - room control for wall installation with humidity probe
– ELFOControl Its functions are:
- control of minimum temperature of system water temperature
- manual or automatic control of fan speed
- control of ON-OFF water valve
- digital input for remote on/off function or winter/summer
- control of fan / actuator of external air shutter
- on/off control of electrical heating element or cumulative alarm relay.
The room temperature probe includes the ClivetTalkTerminalSpace electronics.
Unit configuration in which, for control of the motor, an electronic device has been developed for the control of AC single-phase motors. It is dedicated in particular
to the linear control of speed of the motor of the fan coils.
This device allows constant variation of ventilation without changing the sound level.
For control of ventilation, we have adopted the ELFO CONTROL ROOM electronics, whose main characteristics are:
- control of minimum temperature of system water temperature
- fan control via proportional signal 0-10v
- possible control of water valve ON-OFF / electrostatic filter/heating element
- digital input for remote on/off function or winter/summer
- control of actuator of fresh air shutter
The ambient temperature probe includes the ClivetTalkRoom electronics.
In addition to the basic functions, CLIVET TALK ROOM, can be connected to a network of similar units that are centrally managed by ELFOControl, which in turn
can be connected to a supervisor, and via an RS485 or wireless port can single-handedly manage a mini-network of up to 8 units with a master-slave type system.
This type of electronic card is suited for communicating via RS485 or wireless if connected to SP1 devices. The microprocessor control installed in the unit recei-
ves operating settings from one of the following devices:
HID-T2 - room control for wall installation
HID-T3 - room control for wall installation with humidity probe
- ELFOControl
CTRD - ClivetTalkRoom electronics with unit on-board display (Elfo Control) optional accessory
On-board control panel with spacious display lets you interact with the main functions of Elforoom electronics:
-On/Off
-Display of ambient temperature
-Setting the desired temperature
-Manual speed selection
-Automatic selection of speed, which will adjust the air flow rate until the set value is reached
-Silent operation
- Selection of economic operation
Change Summer/winter automatically or manually with digital input
-Management of diagnostics with specific code for type of error
The unit on-board environmental control makes it possible to interface directly with the adjustment module of the units
equipped with ClivetTalkRoom electronics and to manage one or more units.
The HID-T2 room thermostat makes it possible to interface with the regulation module of units equipped with
ClivetTalkTerminal Space electronics and to manage one or more thermostat units.
The room thermostat allows the following functions:
-Setting of desired temperature
- Selection of the three speeds (MIN - MED - MAX) manually or automatically
-On/off
_ Change Summer/winter automatically or manually with digital input
- Selection of economic operation
-Setting of unit operation parameters
-Setting of fan-only mode
-Control of external air shutter and control of motorized air outlet grille, if present
-Management of diagnostics with specific code for type of error
Dimensions: 184X82X27 mm
The thermostat is connected to the unit by means of a shielded twisted pair at a distance of up to 15 m.
For connections to the ELFOControl network, refer to the specific sections.
18
TERMINALS
3 - 31
Configuration Detail
separately supplied accessories
RE - Electric heaters L
Electrical heating elements manufactured in accordance with international standards on electricity and
safety, shielded with aluminium heat exchanging fins.
They are supplied complete with an automatic-reset safety thermostat and power relay.
Standard: electrical heating elements installed inside the unit with electrical cables 230V/1Ph/50Hz.
Note:
- Accessory suitable for all versions with 2-tube system (1 coil)
BT05A002GB-04
- dual-stage heating element with possibility to connect them reducing by 1/3 the power (for example from
1.5 kW to 1 kW).
Size 3 5 7 9 11 15 17 21 25 31
1 kW X X - - - - - - - -
1.5 kW - - X X - - - - - -
2 kW - - - - X X - - - -
3 kW - - - - - - X X X X
ELFOSPACE
3 7 11 17 25
Ti To
kwt 70/60°C 70 60 H W 1790 3010 4280 6370 8440
70 60 M W 1600 2690 3880 5770 7760
70 60 L W 1270 2140 3150 4680 6510
kwt 50/44°C 50 44 H W 1070 1800 2560 3820 5060
50 44 M W 960 1610 2310 3460 4650
50 44 L W 760 1280 1890 2810 3910
Q H2O 70 60 H l/h 154 259 369 548 726
Dp H2O 70 60 H kPa 8,1 11,7 21,3 43,4 56.8
Q H m³/h 360 447 665 1003 1472
M m³/h 299 371 565 853 1281
L m³/h 205 255 399 602 957
Rated technical data with free outlet (External static High speed (H)
pressure = 0 Pa). Medium speed (M) (1) STANDARD WATER COIL
Ambient air temperature: 20°C Low speed (L) (2) 1 ROW HOT WATER ADDITIONAL COIL
(Ti)Inlet water temperature (3) WATER FITTINGS
(To)Outlet water temperature
(kwt)Heat output
(Q H20)Water flow-rate
Configuration Detail
(Dp H20)Pressure drop water
(Q)Air flow
10
8
6
4
3
2
Kit composed of ball valve, stopper and copper fittings suitable for all versions (vertical unit with cabinet, horizontal
with cabinet, vertical recessed and horizontal recessed) for units with connections either on right or left.
n° Ø kvs
1 BALL VALVE 1/2" 3.5
2 BALANCING REGULATING VALVE 1/2" 2.5
1
20
TERMINALS
3 - 31
2V2) - ON/OFF 2 way valve kit for 2 tube system Configuration Detail Separately supplied accessories
3V2 - 3-way ON/OFF valve kit for 2-pipe systems Configuration Detail Separately supplied accessories
10V2 - 0-10V 3 way valve kit for 2 tube system Configuration Detail Separately supplied accessories
2V4 - ON/OFF 2 way valve kit for 4 tube system optional accessory
¾2
3V4 - 3-way ON/OFF valve kit for 4-pipe systems optional accessory
10V4 - 0-10V 3 way valve kit for 4 tube system optional accessory
Valve kit complete with electro-thermal servo-control, for all versions (vertical unit with cabinet, horizontal with cabinet,
vertical recessed and horizontal recessed) for units with connections either on right or left.
ΔP max kv
n° Ø kvs
(kPa) by pass
1 COIL (STANDARD) 3/4" 1.7 80 1.2
2 ADDITIONAL COIL 1/2" 2.5 70 1.8
10
8
6
4 Q = WATER FLOW
3 DP = PRESSURE DROP
1
1000
2000
3000
4000
100
200
300
400
500
600
800
Q (l/h)
The auxiliary tub makes it possible to collect the condensation of the unit's connection tubes
and valves. It is constructed in plastic material.
This accessory is suitable for: installation on all sizes, both for units with coupling on either the
right or left.
BT05A002GB-04
Configuration Detail
separately supplied accessories
The auxiliary tub makes it possible to collect the condensation of the unit's connection tubes and
valves. Made of painted galvanized sheet metal with external thermal insulation (class M1), this
accessory is suitable for installation on all sizes.
Configuration Detail
separately supplied accessories
21
TERMINALS
3 - 31 INSTALLATION VARIANTS
Support feet
PI90 - Support feet for built-in vertical units h=90mm
PV90 - Rear cover panel for OUT-V with support feet h=90mm
PV155 - Rear cover panel for OUT-V with support feet h=155mm
Realized in pre-painted plate with total closing of the under mobile. Complete of intake grille
in ABS removable to allow the air filter cleaning.
PPV90 - Rear cover panel for OUT-V with support feet h=90mm
PPV155 - Rear cover panel for OUT-V with support feet h=155mm
22
TERMINALS
3 - 31
AERAULIC VARIATIONS
SER - Manual outside air damper for Vertical and horizontal installation
The galvanised steel plate damper, installed at the base of the unit at the intake, lets a certain amount of
fresh air into the environment, which is controlled manually (adjustable opening), or with motorised ON/
OFF command The damper can be motorised using the ON/OFF (230/1/50 power supply). The damper
can be used on both the vertical and horizontal units. For units installed in view, accessory PV155
(support feet with cover for vertical units in view, h=155) or PVG155 (support feet with cover for vertical
units in view, h=155, and intake grill) must be fitted.
23
TERMINALS
3 - 31
Telescopic extension 0-100 mm, suitable for connection onto plenum PRM
(outlet air plenum), PRA (air intake straight plenum), PR90M (90° air outlet
plenum), PR90A (90° air inlet plenum), in galvanized plate, is used to convey
the air of the ceased units.
The air ducts with flexible hoses may be especially suited for simplifying the
coupling of the unit with the fixed ducts or with grilles.
24
TERMINALS
3 - 31
AIR FILTER
Air outlet grille without filter suitable for connection on PRM (air outlet
plenum), PRA (straight air intake plenum), PR90M (90° air outlet plenum),
PR90A (90° air intake plenum), PRT (telescopic extension 0-100 mm.) with
outer frame in sheet metal painted white (RAL 9010) + internal grille with
fixed fins in ABS, grey (RAL 7035).
Air suction grille with air filter (suitable for the connection on any plenum) with
external pre-painted metal plate frame (RAL 9010) + internal grille with fixed
BT05A002GB-04
AGRM
AGRA
140
25
TERMINALS
3 - 31
DIMENSIONAL DRAWING
A 115 60
155 B 115 40 115
Ø 1/2"
10
2
4
25
3
70
135
35 = = 1
230
470
450
5
335
Ø 21
260
35
190
120
220
A 7
C
155
220
OUTV
Size 3 5 7 9 11 15 17 21 25 31
A mm 670 670 870 870 1070 1070 1270 1270 1470 1470
B mm 400 400 600 600 800 800 1000 1000 1200 1200
BT05A002GB-04
C mm 220 220 220 220 220 220 220 220 220 220
Length mm 670 670 870 870 1070 1070 1270 1270 1470 1470
Depth mm 220 220 220 220 220 220 220 220 220 220
Height mm 470 470 470 470 470 470 470 470 470 470
Operating weight kg 13.5 14 16.4 17.2 22.5 23.5 26 27.5 30 31.5
Shipping weight kg 17.5 18 20.5 21.5 27.5 28.5 32 33.5 36 38
26
TERMINALS
3 - 31
DIMENSIONAL DRAWING
40
2
115
115
220
7
155
60
1 4
25
6 3
A 5
155 B 115 Ø 20
105 40
25 25
10
20
470 LA
210
230
470
220
240
5 90
= =
120
Ø 20
OUTH
Size 3 5 7 9 11 15 17 21 25 31
A mm 670 670 870 870 1070 1070 1270 1270 1470 1470
B mm 400 400 600 600 800 800 1000 1000 1200 1200
Length mm 670 670 870 870 1070 1070 1270 1270 1470 1470
Depth mm 470 470 470 470 470 470 470 470 470 470
Height mm 220 220 220 220 220 220 220 220 220 220
Operating weight kg 14.7 15.2 18 18.8 24.5 25.5 28.4 29.9 32.8 34.3
Shipping weight kg 18.5 19 22.5 23.5 29.5 31 34.5 36 39.5 41
BT05A002GB-04
27
TERMINALS
3 - 31
DIMENSIONAL DRAWING
A 115 60
2
25 D 25 40 115
Ø 1/2"
4
70
135
35 = = 1
230
Ø 21
B
B
5
335
30
260
190
120 C
25 25
30
A
7
C
120
15
15 D 15
B
6
BT05A002GB-04
INV
Size 3 5 7 9 11 15 17 21 25 31
A mm 450 450 650 650 850 850 1050 1050 1250 1250
B mm 450 450 450 450 450 450 450 450 450 450
C mm 215 215 215 215 215 215 215 215 215 215
D mm 400 400 600 600 800 800 1000 1000 1200 1200
Length mm 450 450 650 650 850 850 1050 1050 1250 1250
Depth mm 215 215 215 215 215 215 215 215 215 215
Height mm 450 450 450 450 450 450 450 450 450 450
Operating weight kg 10.7 11.2 13.5 14.3 19.5 20.5 22.9 24.4 26.8 28.3
Shipping weight kg 14 15 17.5 18.5 24.5 25.5 28.5 30 33 34.5
28
TERMINALS
3 - 31
DIMENSIONAL DRAWING
40
2
30
115
215
115
110
7
60
25
15 15
1 4
25
105 B 40 6
5 3
Ø 20
A
105 B 40
25 25
450
7
210
230
450
215
90
240
5 = = A
120
Ø 20
6
(1) WATER INLET (STANDARD UNIT)
(2) WATER OUTLET (STANDARD UNIT)
(3) ADDITIONAL COIL WATER INLET (4 PIPE-INSTALLATION)
(4) ADDITIONAL COIL WATER OUTLET (4 PIPE- INSTALLATION)
(5) CONDENSATE DISCHARGE
(6) AIR FLOW
STANDARD AIR INLET
(7) AIR FLOW
STANDARD OULET
INH
Size 3 5 7 9 11 15 17 21 25 31
BT05A002GB-04
A mm 545 545 745 745 945 945 1145 1145 1345 1345
B mm 400 400 600 600 800 800 1000 1000 1200 1200
Length mm 545 545 745 745 945 945 1145 1145 1345 1345
Depth mm 450 450 450 450 450 450 450 450 450 450
Height mm 215 215 215 215 215 215 215 215 215 215
Operating weight kg 11.1 11.6 13.9 14.7 199.9 20.9 23.3 24.8 27.2 28.7
Shipping weight kg 15 15 18 19 25 26 28.5 30.5 33 35
29
TERMINALS
3 - 31
FUNCTIONAL CLEARANCES
BUILT-IN VERSION:
The installer must ensure that they are masked with appropriate panels (false ceilings, false walls, cover panels, etc.), which must also provide fixed protection.
The protective panels must be secured using systems that require tools to open (e.g. screws), so as to prevent the user from accessing the dangerous parts,
(98/37/CEE) such as sharp edges and corners, electrical parts, moving fans, etc. The panels must be designed to be removed (using tools!) to ensure complete
access to the unit, to avoid breaking or damaging structures and the masking (plasterboard, false ceilings, etc.) when special maintenance and/or replacement of
the unit is required.
NOTE : THE MEASURES ARE REFERRED TO MIN. DISTANCES EXCEPT POSSIBLE NOTES REPORTED BELOW THE IMAGE
200
200
200 150
MIN 10 200
150
A: -90 mm standard
-90 mm with PI90 plinth
-155 mm with PI155 plinth
200
200
200 150
C
BT05A002GB-04
200
150
30
TERMINALS
3 - 31
air exhaust
Technical data referred to the following conditions: Standard Unit (without installed accessories),
Electrical power 230V/1Ph/50Hz,
Atmospheric pressure 1013 mbar
Rated technical data with free outlet (External static pressure = 0 Pa).
Q = AIR FLOW (1) Air flow: Values taken with tank ref. law AMCA 210-74 duct + diaphragm ref. law CNR-UNI 10023
(V) FAN SPEED
HIGH SPEED (H)
MEDIUM SPEED (M)
LOW SPEED (L)
BT05A002GB-04
TERMINALS
3 - 31
CLIVET SPA CLIVET UK LTD CLIVET SAS CLIVET ESPAÑA S.A. CLIVET GmbH CLIVET NEDERLAND B.V. CLIVET RUSSIA CLIVET MIDEAST FZC CLIVET TF AIR SYSTEMS (P) LTD.
Feltre (BL) ITALY Fareham (Hampshire) U.K. Verrierès le Buisson - FRANCE Madrid - SPAIN Norderstedt - GERMANY Amersfoort - Netherlands Moscow - RUSSIA Dubai - UAE Malur - INDIA
Tel. + 39 0439 3131 Tel. + 44 (0) 1489 572238 Tel. + 33 (0)1 69 20 25 75 Tel. + 34 91 6658280 Tel. +49 (0) 40 32 59 57-0 Tel. + 31 (0) 33 7503420 Tel. +74956462009 Tel. +97 14 3518501 Tel. +91 8151 232683/5
Fax + 39 0439 313300 Fax + 44 (0) 1489 573033 Fax + 33 (0)1 69 20 60 76 Fax + 34 91 6657806 Fax +49 (0) 40 32 59 57-194 Fax + 31 (0) 33 7503424 Fax +74956462009 Fax +97 14 3518502 Fax +91-8151-232684
info@clivet.it info@clivet-uk.co.uk info.fr@clivet.com info@clivet.es info.de@clivet.com info@clivet.nl info.ru@clivet.com info@clivetme.com info@clivettfa.com
The data contained in this bulletin is not binding and may be changed by the manufacturer without prior notice. All reproduction, even partial, is prohibited.
© Copyright - CLIVET S.p.A. - Feltre (BL) - Italy