MATERIAL TAKE-OFF LIST

PER DWG.
SI.NO DESCRIPTION QTY I/U STATUS REMARKS
REQ. CODE

SAND TRAP LOUVER (STL) : EXTRUDED ALUMINUM, ANODIZED WITH GALVANIZED


1 BIRD SCREEN WIRE MESH & WASHABLE-FILTER COMPLETE WITH SUPPORTS &
MOUNTING ARRANGEMENT, MANUFACTURER : GOLDENSTAR OR APPROVED EQUAL

STL-001 : 1200(MM) X 1050(MM) 1 EA


PRESSURE RELIEF DAMPER(PRD) : GALVANIZED STEEL
CONSTRUCTION, WITH GRAVITY LOUVERS WITH COUNTER WEIGHTS SET TO
2
OPEN 25PA PRESSURE C/W BIRD SCREEN.MAKE : SAFID OR
APPROVED EQUAL
PRD-001/PRD-002 : '400 MM X 200 MM 2 EA
WALL MOUNTED THERMOSTAT (THERMISTOR): (TS-003/TS-004) FOR MODULATING
OF AIR TEMPERATURE IN ROOM HAVE COILED SENSING ELEMENT CAPILLARY
TUBING ALLOWS SET POINT READ AND ADJUSTED THROUGH COVER.
3 2 EA
THROTTLING DIAL INSIDE CASE ADJUSTS PROPORTIONAL THROTTLING RANGE
WITH ELECT'L. RATING @ 24 TO 30VAC AND TEMP. RATING @ 200°F (93°C) FOR
55°F TO 163°F (13°C to 73°C) RANGE
TEMPERATURE TRANSMITTER. DUCT MOUNTED -5C TO 55C TEMP. RANGE, SHALL
4 BE CONNECTED TO HVAC DDC PANEL, MANUFACTURER: HONEYWELL OR APPROVED 2 EA
EQUAL

PRESSURE SENSOR. WALL MOUNTED 0 TO 50 Pa RANGE, SHALL BE CONNECTED


5 2 EA
TO HVAC DDC PANEL, MANUFACTURER: HONEYWELL OR APPROVED EQUAL

HUMIDITY SENSOR. DUCT MOUNTED 0 TO 50% RANGE, SHALL BE CONNECTED TO


6 1 EA
HVAC DDC PANEL, MANUFACTURER: HONEYWELL OR APPROVED EQUAL

SUPPLY AIR REGISTER,STAINLESS, DOUBLE DEFLECTION GRILLE PROVIDING AIR


DEFLECTION IN BOTH HORIZONTAL AND VERTICAL PLANES, FRAME AND BLADES
ARE EXTRUDED STAINLESS, DEFECTION OF BLADES ARE EASILY SET WITHOUT
7
USING SPECIAL TOOLS, ALL BLADE ARE AIRFOIL IN DESIGN. SUITABLE FOR HIGH
SIDEWALL, SOFFIT OR DUCT MOUNTING, DD-1-H OF GOLDEN STAR OR APPROVE
EQUAL
SAR-001 : 'NECK SIZE 300 MM X300 MM / FACE SIZE 350 MM X 350 MM. 1 EA
SAR-002 TO 004: NECK SIZE 600 MM X300 MM / FACE SIZE 650 MM X 350 MM. 3 EA
RETURN AIR RIGISTER,STAINLESS, FRAME AND BLADES ARE EXTRUDED STAINLESS,
AN OPPOSED BLADE DAMPER IS ATTACHED FOR VOLUME CONTROL OF AIR IN THE
8 RETURN STREAM AND IS LEVER TYPE OPERATED THROUGH THE FACE OF THE UNIT.
ALL BLADE ARE AIRFOIL IN DESIGN. FIXED BLADES. RG-2-H OF GOLDEN STAR OR
APPROVE EQUAL
RAR-001 TO 002: NECK SIZE 700 MM X350 MM / FACE SIZE 750 MM X 400 MM. 2 EA
EXHAUST AIR RIGISTER,STAINLESS, FRAME AND BLADES ARE EXTRUDED
STAINLESS, AN OPPOSED BLADE DAMPER IS ATTACHED FOR VOLUME CONTROL OF
9 AIR IN THE RETURN STREAM AND IS LEVER TYPE OPERATED THROUGH THE FACE
OF THE UNIT. ALL BLADE ARE AIRFOIL IN DESIGN. FIXED BLADES. RG-2-H OF
GOLDEN STAR OR APPROVE EQUAL
EAR-001 TO 002: NECK SIZE 300 MM X300 MM / FACE SIZE 350 MM X 350 MM. 2 EA
SUPPLY AIR DIFFUSERS: 4-WAY WITH OPPOSED BLADE DAMPER, EXTRUDED
10 ALUMINUM, PAINTED TO MATCH CEILING, NECK SIZE / FACE SIZE AS FOLLOWS:
MODEL 4SNOD OF GOLDEN STAR OR APPROVE EQUAL
SAD-003 : 150 X 150 Ø MM / 238 MM X 238 MM 1 EA
SAD-002 : 300 X 300 Ø MM / 388 MM X 388 MM 1 EA
SAD-001 : 450 X 450 Ø MM / 538 MM X 538 MM 1 EA
RETURN AIR DIFFUSERS: 4-WAY WITH OPPOSED BLADE DAMPER, EXTRUDED
11 ALUMINUM, PAINTED TO MATCH CEILING, NECK SIZE / FACE SIZE AS FOLLOWS:
MODEL 4SNOD OF GOLDEN STAR OR APPROVE EQUAL
RAD-001 : 450 X 450 Ø MM / 538 MM X 538 MM 1 EA

FLEXIBLE DUCT : INSULATED FLEXIBLE DUCT WITH OUTER ALUMINUM FOIL


12
NOMINAL NECK DIA

Ø 150 MM 1 EA
Ø 300 MM 1 EA
Ø 450 MM 1 EA
NOTES : 1. CONSTRUCTION CONTRACTOR SHALL VERIFY AND PROVIDE ALL QUANTITIES OF CONTRACTOR SUPPLIED MATERIAL REQUIRED
TO PERFORM THE WORK, AS DETAILED, ON THE CONSTRUCTION DRAWINGS. CONTRACTOR DRAWING NUMBER
SA016-01-5001-EN-1001

RE-ISSUED FOR CONSTRUCTION


COMPILED BY REV. REFERENCE DRAWING
CHECKED DATE PROJECT ENGR DATE
SASEC SNN 01 MKA 07/14/22 RCM 07/14/22 06-GF60-Q-001,06-GR60-D-002
06-GR60-D-003,06-GR60-S-005
PROJ. CODE C.N. PHASE ENG. ITEM AREA START-UP DATE PRELIMINARY REVISION
- HVAC SWCC BA. LIMIT 03/31/22 FINAL X REVISION 01
DISCIPLINE MATERIAL TAKE-OFF HVAC SYSTEM SHEET 002
HVAC ELECTRICAL / CONTROL BUILDING
PLANT SWCC YANBU PHASE-3 PROJECT 06-GR60-T-007
- YANBU SAUDI ARABIA
MATERIAL TAKE-OFF LIST

PER DWG.
SI.NO DESCRIPTION QTY I/U STATUS REMARKS
REQ. CODE
SHEET METAL, GALVANIZED: 0.55 MM THK. (GA.24) 1250 MM X 2500 MM LG, ASTM
13 A653M, COLD ROLLED, HOT-DIP-ZINC-COATED CHROMATED, OR CHEMICALLY 4.9 SM
PASSIVATED, NOT PHOSPATED, FLAT

SHEET METAL, STAINLESS STEEL: 0.02 MM THK., ASTM A653M, COLD ROLLED, HOT-
14 DIP-ZINC-COATED CHROMATED, OR CHEMICALLY PASSIVATED, NOT PHOSPATED, 10.77 SM
FLAT

SHEET METAL, GALVANIZED: 0.55 MM THK. (GA.24) 1250 MM X 2500 MM LG, ASTM
15 A653M, COLD ROLLED, HOT-DIP-ZINC-COATED CHROMATED, OR CHEMICALLY 152.15 SM
PASSIVATED, NOT PHOSPATED, FLAT

SHEET METAL, STAINLESS STEEL: 0.02 MM THK., ASTM A653M, COLD ROLLED, HOT-
16 DIP-ZINC-COATED CHROMATED, OR CHEMICALLY PASSIVATED, NOT PHOSPATED, 3.25 SM
FLAT

SHEET METAL, GALVANIZED: 0.70 MM THK. (GA.22) 1250 MM X 2500 MM LG, ASTM
17 A653M, COLD ROLLED, HOT-DIP-ZINC-COATED CHROMATED, OR CHEMICALLY 59.28 SM
PASSIVATED, NOT PHOSPATED, FLAT
INSULATION: FLEXIBLE BLANKET/ ROLL, 1.2M. WIDTH x 25MM THK. FIBERGLASS, 24
KG/M3 DENSITY, SURFACE BURNING CHARACTERISTICS, WHEN TESTED AS PER
18 ASTM 84/ NFPA 255/ UL 723 THE MAX. FLAME SPREAD INDEX/ SMOKE DEVELOPED 113.22 SM
INDEX RATING IS NOT MORE THAN 25/50 WITH REINFORCED ALUMINUM FOIL
VAPOR BARRIER
INSULATION: FLEXIBLE BLANKET/ ROLL, 1.2M. WIDTH x 50MM THK. FIBERGLASS, 48
KG/M3 DENSITY, SURFACE BURNING CHARACTERISTICS, WHEN TESTED AS PER
19 ASTM 84/ NFPA 255/ UL 723 THE MAX. FLAME SPREAD INDEX/ SMOKE DEVELOPED 108.06 SM
INDEX RATING IS NOT MORE THAN 25/50 WITH REINFORCED ALUMINUM FOIL
VAPOR BARRIER

AIR DUCT CLADDING: ALUMINUM SHEET, 0.4 MM THK, 900MM WIDTH x 2400MM
20 LENGTH, GR ALLOY 3003, ASTM - B209, NON-HEAT TREATABLE MODERATE 108.06 SM
STRENGTH, WELD ABLE AND HIGH CORROSION RESISTANT. (FOR OUTSIDE)

COPPER PIPES, TYPE "L" WITH 25MM THK,ARMAFLEX INSULATION AND DENSO
TAPE WRAPPING.
21 196 LM
7/8" DIA.-HOT GAS LINE
5/8" DIA.-LIQUID LINE

DRAIN PIPE : Ø 20 MM (3/4" Ø) SCH 40 PVC PIPE OR RTR PIPE WITH P-TRAP &
22 10 LM
ACCESSORIES FOR 01SAB90AH401 & 01SAB90AH402

DRAIN PIPE : Ø 25 MM (1" Ø) SCH 40 PVC PIPE OR RTR PIPE WITH P-TRAP &
23 1.6 LM
ACCESSORIES FOR 01SAB90AH301 & 01SAB90AH302
ANTI VIBRATION PAD: MOLDED IN NATURAL RUBBER FOR MAX. RESILIENCE AND
24 VIBRATION ISOLATION, STD. NEOPRENE FOR LONGER LIFE CROSS-RIBBED, STD. 12 EA
SIZE MODEL: USWP-300MM X 300MM X 19MM THK.
'ROD, THREADED: 10 MM (3/8 IN DIA), 1.8 M (6 FT) LG, STEEL BODY, GALV.
25 62 EA
FINISH, 20 THREAD /INCH HANGER WITH CONTINUOS THREAD

26 NUT, HEX: MACHINE SCREW, 1/4-20, CS, ASTM A194, GR 2H 1 LS

27 'WASHER, FLAT/PLAIN: 1/4 IN BOLT, 13/32 IN ID, 1 LS

ANGLE BAR, STRUCTURAL: 40 MM X 40 MM X 3 MM THK CS BODY, 6 M LG, BLACK


28 20 EA
FINISH, HOT ROLLED, ASTM A36, DIN 17100 OR BS4360, L-SHAPE

29 STRAPPING BAND: 0.51 MM (0.020 IN) THK, 19.1 MM (3/4 IN) WD, PVC, 31M / ROLL 1 LS

TAPE: DUCT, PRESSURE SENSITIVE, HIGH TEMP. RESISTANT, MULTI-PURPOSE


30 SOFT-FOIL, 63.5 MM WIDE, 60 YD LONG, 0.3MM THK. FOIL BACKING 0-220°F, 1 LS
SMACN AFTS-100-73, UL-181 OR UL_181A-P,
'FLEXIBLE DUCT CONNECTORS, 75MMx100MMx75MM (DURO-DYNE BRAND OR
31 1 BOX
APPROVED EQUAL)

NOTES : 1. CONSTRUCTION CONTRACTOR SHALL VERIFY AND PROVIDE ALL QUANTITIES OF CONTRACTOR SUPPLIED MATERIAL REQUIRED
TO PERFORM THE WORK, AS DETAILED, ON THE CONSTRUCTION DRAWINGS. CONTRACTOR DRAWING NUMBER
SA016-01-5001-EN-1001

RE-ISSUED FOR CONSTRUCTION


COMPILED BY REV.
REFERENCE DRAWING
CHECKED DATE PROJECT ENGR DATE

SASEC SNN 01 MKA 07/14/22 RCM 07/14/22 06-GF60-Q-001,06-GR60-D-002


06-GR60-D-003,06-GR60-S-005
PROJ. CODE C.N. PHASE ENG. ITEM AREA START-UP DATE PRELIMINARY REVISION
- HVAC SWCC BA. LIMIT 03/31/22 FINAL X REVISION 01
DISCIPLINE MATERIAL TAKE-OFF HVAC SYSTEM SHEET 003
HVAC ELECTRICAL / CONTROL BUILDING
PLANT SWCC YANBU PHASE-3 PROJECT 06-GR60-T-007
- YANBU SAUDI ARABIA