You are on page 1of 18

Carlo SIngua Inocentes

1. What is “accessible” as circuit breaks off to supply the aids in tripping the overcurrent-
applied to wiring methods? motor. protective device.
Wiring that is readily available to
inspection, repair, removal, etc., 8. What is a small appliance 14. What is a pressure connector
without disturbing the building branch circuit? This is the circuit (solderless)? A device that
structure or finish. Not supplying one or more outlets establishes a good electrical
permanently enclosed by the connecting appliances only. connection between two or more
structure or finish of buildings. There is no permanently conductors by some means of
connected lighting on this circuit, mechanical pressure. A pressure
2. What is “accessible” as except the lighting that may be connector is used in place of
applied to equipment? built into an appliance. Refer to soldering connections and is
Equipment that may be readily outlets for small appliance loads required to be of an approved
reached without climbing over in kitchens, laundries, pantries, type.
obstacles or that is not in locked and dining and breakfast rooms
or other hard to reach areas. For of dwellings. 15. What is meant by “demand
example, panel boards in kitchen factor”? This is the ratio between
cabinets that are mounted in or 9. What is a general purpose the maximum demand on a
on the walls above washers and circuit? This is a branch circuit to system or part of a system and
dryers, or in closets or bath- which lighting and/or appliances the total connected load on the
rooms, are not accessible. may be connected. same sys- tem or part of the
Service-entrance equipment that system.
can be reached only by going 10. What is a multiwire branch
into a closet, behind a stairway, circuit? A multiwire branch circuit 16. What is meant by “explosion
or around some other obstacle has two or more ungrounded proof apparatus”? Apparatus
would not be considered conductors with a potential enclosed in a case that is able to
accessible. difference between them and sustain an explosion that may
also has a grounded (neutral) occur within the case and is also
3. What does “ampacity” mean? conductor with an equal potential able to prevent ignition of
The amount of flowing current (in difference between it and each specified gases or vapors
amperes) that a conductor can of the other wires. Examples are surrounding the enclosure
carry continuously for specific a three- wire 120/240-volt caused by sparks, flashes, or
use conditions and not exceed system or a 120/208-volt wye explosion of the gases or vapors
the temperature rating of the system, using two-or three-
conductor phase conductors and a 17. What is a feeder? The circuit
grounded conductor. However, conductors between the service
4. What does “dead front” mean? in either case, the “hot” wires equipment, or the source of a
No live (energized) parts are must not be tied to one phase separately derived system, and
exposed where a person but must be connected to the final branch- circuit
operates electrical equipment. different phases to make the overcurrent device or devices.
sys- tem a multiwire circuit Generally, feeders are com-
5. What does “approved” mean? paratively large in size and
Any appliance, wiring material or 11. What is a circuit breaker? A supply a feeder panel, which is
other electrical equipment that is device that is designed not only composed of a number of
acceptable to the enforcing to open and close a circuit non branch-circuit overcurrent
authorities. Underwriters automatically but also to open devices
Laboratory is (by far) the most the circuit automatically at a
acceptable authority to predetermined current-overload 18. What is a fitting? A
inspectors. value. The circuit breaker may mechanical device, such as a
be thermally or magnetically locknut or bushing, that is
6. What does “identified” mean operated. However, ambient intended primarily for a
as applied to equipment? It temperatures affect the mechanical, rather than an
means that the equipment will be operation of the thermally electrical, function.
suitable for the particular use or operated type, so that the trip
environment, that it has been value of the current is not as 19. What is meant by a
evaluated by a qualified stable as with the magnetic type. “ground”? An electrical
electrical testing organization, connection, either accidental or
and that it features a product 12. What is a current-carrying intentional, that exists between
listing or label indicating its conductor? A conductor that is an electrical circuit or equipment
suitability expected to carry current under and the earth, or some other
normal operating conditions. conducting body that serves in
7. What is a branch circuit? A place of the earth.
branch circuit is the portion of a
wiring system that extends 13. What is a noncurrent- 20. What does “grounded”
carrying conductor? One that
beyond the last overcurrent- mean? Connected to the earth or
protective device. In interpreting carries current only in the event to some other conducting body
of a malfunction of equipment or
this, you must not consider the that serves in place of the earth.
thermal cutout or the motor wiring. An equipment grounding
conductor is a good example. It
overload protection as the 21. What is a grounded
beginning of the branch circuit. is employed for protection and is conductor? A system or circuit
quite a necessary part of the
The branch circuit actually conductor that has been
begins at the final fusing or wiring system, but it is not used intentionally grounded.
to carry current except in the
circuit-breaker point where the
case of faulty operation, where it
22. What is a grounding entrance equipment of the risers at the pole or other
conductor? A conductor that is premises supplied. For overhead structure, or from transformers,
used to connect equipment, conductors, this includes the and the first point of connection
devices, or wiring systems with conductors from the last line pole to the service- entrance
grounding electrodes. (not including the service pole) to conductors in a terminal box.
the service equipment. The point of connection is
23. What is a grounding considered to be the point where
conductor (equipment)? The 32. What is a service cable? A the service conductors enter the
conductor used to connect service conductor manufactured building.
noncurrent-carrying metal parts in the form of a cable and
of equipment, raceways, and normally referred to as SE cable, 39. What is meant by “service
other enclosures to the system or USE cable raceway”? The rigid metal
grounding conductor at the conduit, electrical metallic tubing,
service and/or the grounding 33. What is meant by “service or other raceway that encloses
electrode conductor. drop”? The overhead conductors service-entrance conductors.
from the last pole or other aerial
24. What is a grounding support to and including the 40. What is meant by a “general-
electrode conductor? A splices, if any, connecting to the use switch”? A device intended
conductor used to connect the service-entrance conductors at for use as a switch in general
grounding electrode to the the building or other structure. If distribution and branch circuits. It
equipment grounding conductor there is a service pole with a is rated in amperes and is
and/or to the grounded meter on it, such as a farm capable of interrupting its rated
conductor of the circuit at the service pole, the service drop current at its rated voltage.
service. does not stop at the service pole;
all wires extending from this pole 41. What is meant by a “T-rated
25. What is a dwelling unit? A to a building or buildings are switch”? An AC general-use
dwelling unit includes one or service drops, as well as the snap switch that can be used (a)
more rooms used by one or conductors from the last line pole on resistive and inductive loads
more persons, with space for to the service pole that don’t exceed the ampere
sleeping, eating, living, and a rating at the voltage involved, (b)
permanent provision for cooking 34. What are service-entrance on tungsten-filament lighting
and sanitation. conductors (overhead system)? loads that don’t exceed the
That portion of the service ampere rating at 120 volts, and
26. What is an outlet? A point in conductors between the (c) on motor loads that don’t
the wiring system at which terminals of service equipment exceed 80% of their ampere
current is taken to supply some and a point outside the building, rating at the rated voltage.
equipment. clear of building walls, where
they are joined by a splice or tap 42. What is meant by an
27. What is meant by “rain- to the ser- vice drop, street main, “isolating switch”? A switch that
tight”? Capable of withstanding a or other source of supply. is intended to isolate an electric
beating rain without allowing circuit from its source of power. It
water to enter. 35. What are service-entrance has no interrupting rating and is
conductors (underground intended to be operated only
28. What is a receptacle? A system)? The service conductors after the circuit has been opened
receptacle is a contact device between the terminals of the by some other means.
installed at the outlet for the service equipment and the point
connection of a single of connection to the service 43. What is meant by a “motor-
attachment plug. A single lateral. Where service equipment circuit switch”?
receptacle is a single device with is located outside the building A switch, rated in horsepower,
no other contact device on the walls, there may be no service- that is capable of interrupting the
same yoke. A multiple receptacle entrance conductors, or they maximum operating overload
is a single device containing two may be entirely outside the current of a motor of the same
or more receptacles. building. horsepower rating as the switch,
at the rated voltage.
29. What does “rainproof” mean? 36. What are sets of service-
So constructed, protected, or entrance conductors? Sets of 44. What is meant by
treated as to prevent rain from service-entrance conductors are “watertight”? So constructed that
interfering with the successful taps that run from main service moisture won’t enter the
operation of the apparatus. conductors to service equipment. enclosing case.

30. What is meant by the term 37. What is meant by “service 45. What is meant by
“service”? The conductors and equipment”? The necessary “weatherproof”? So constructed
equipment for delivering equipment, usually consisting of or protected that exposure to the
electrical energy from the circuit break- ers or switches and weather won’t interfere with
secondary distribution system fuses and their accessories, successful operation. Raintight
the street main, the distribution located near the point of where or watertight may fulfill the
feeder, or the transformer—to supply conductors enter a requirements for “weatherproof.”
the wiring system on the building, structure, or an However, weather conditions
premises. This includes the otherwise defined area, and vary, and consideration should
serviceentrance equipment and intended to constitute the main be given to conditions resulting
the grounding electrode. control and means to cut off the from snow, ice, dust, and
supply. temperature extremes.
31. What are service
conductors? The portion of the 38. What is meant by “service 46. What is the percentage of
supply conductors that extend lateral”? The underground allowable voltage drop for
from the street main, duct, or service conductors between feeders that are used for power
transformers to the service- the street main, including any
and heating loads? Maximum of 56. Do fluorescent lamps
3%. produce a stroboscopic effect? 67. When are rules in the nec
47. What is the percentage of Explain. Yes. This effect is due mandatory and when are they
allowable voltage drop for to the fact that at 60 hertz the advisory? When the word “shall”
feeders that are used for lighting current passes through zero 120 is used, the rules are mandatory.
loads? Maximum of 3%. times a second.
68. According to the nec, what
48. Give some examples of 57. How can the strobe effect be are voltages? Throughout the
equipment that causes compensated for in a two-bulb Code, the voltage considered
inductive reactance. Motors, system? When the power factor shall be that at which the circuit
transformers, choke coils, relay is corrected, the capacitor is so operates. This is often
coils, ballasts. con- nected that at the instant expressed as, for exam- ple, 600
the current in one bulb is passing volts, nominal
49. When only inductive through zero, the current in the
reactance is present in an ac other bulb is not at zero, and the 69. When referring to
circuit, what happens to the strobe effect goes unnoticed. conductors, what material is
current in relation to the voltage? referred to? Copper, unless
The current is said to lag behind 58. What is another way to otherwise specified. When other
the voltage. minimize the strobe effect? By materials are to be used, the
using a higher frequency, such wire sizes must be changed
50. What is a preheated-type as 400 hertz. accordingly
fluorescent tube? There are two
external contacts at each end of 59. Does a 400-hertz frequency 70. In what manner must the
a glass tube. Each set of have any other advantages? work be executed? All electrical
contacts is connected to a Yes. Smaller and lighter ballasts equipment must be installed in a
specially treated tungsten can be used. This makes it neat and work- manlike manner
filament. The inside of the tube is feasible to use simple
coated with a fluorescent capacitance-type ballasts, which 71. May wooden plugs be
powder, the type of powder used produce an overall gain in used for mounting equipment
controls the color output of the efficiency. in masonry, concrete, plaster,
tube. The tube is filled with an etc.? No
inert gas, such as argon, and a 60. Does frequent starting and
small drop of mercury to facilitate stopping of fluorescent lighting 72. How must conductors be
starting. affect the bulb life? The life of spliced or joined together? They
fluorescent bulbs is affected by must be spliced or joined
51. What kind of light does the starting and stop- ping. A bulb together by approved splicing
fluorescent bulb produce within that is constantly left on will have devices or by brazing, welding,
the bulb itself? Ultraviolet light. a much longer life than one that or soldering with a fusible metal
is turned on and off frequently. or alloy
52. Do the filaments stay lit
during the operation of a 61. When lighting an outdoor 73. When soldering, what
fluorescent bulb? Explain. No. activity area with large precautions must be used? All
They remain lit only at the start incandescent bulbs, how can the joints or splices must be
to vaporize the mercury; they are light output of the bulbs be electrically and mechanically
then shut off by the starter. increased? By using bulbs of a secure before soldering and then
Current is supplied to one lower voltage rating than that of soldered with a noncorrosive flux
contact on each end, thereby the source of supply. For This does not apply to
sustaining the mercury arc within example, by using a bulb that is conductors for grounding
the tube. rated at 105 volts on a 120-volt purposes; soldering is not
supply, the output can be allowed on these conductors.
53. Is a fluorescent fixture more increased by roughly 30%, but
efficient than an incandescent the life of the bulb will be cut by 74. How should splices or joints
fixture? Yes. However, no fixed about 10%. be insulated? They must be
efficiency can be quoted covered with an insulation that is
because it varies with the size of 62. How is the light output of equivalent to the original
the bulb, the ballast, etc. As a lamps rated? In lumens. conductor insulation
rule of thumb, a 40-watt 63. How are light levels rated?
fluorescent bulb is generally In foot-candles. 75. Can an autotransformer be
considered to put out about the 64. What is a foot-candle? The used on an ungrounded system?
same amount of light as a 100- amount of direct light emitted by The autotransformer must have
watt incandescent bulb. one international can- dle on a a grounded conductor that is
square foot of surface, every part common to both primary and
54. Does room temperature of which is one foot away. secondary circuits and tied into a
affect the operation of grounded conductor on the
fluorescent lamps? Yes. The 65. Is the nec a law? It is not a system supplying the
normal fluorescent lamp is law, but it is adopted into laws autotransformer An
designed for operation at 50 F or that are established by autotransformer may be used to
higher. governmental agencies; it may extend or add an individ- ual
be adopted in its entirety, in part, branch circuit in an existing
55. If the operating temperature or with amendments. installation for equipment load
is expected to be below 50°F, without the connection to a
what measures should be taken 66. Who has the responsibility similar grounded conductor
when using fluorescent lamps? for Code interpretations? The when transforming from a
Use special lamps and starters administrative authority that has nominal 208-volt supply or
that are designed for lower jurisdiction over endorsement of similarly from 240 volts to 208
temperatures. the Code has the responsibility volts.
for making Code interpretations
76. On No. 6 or smaller grounding purposes be receptacle. This includes wall
conductors, what means must be identified? By the use of a green space that is 2 feet or wider and
used for the identification of the color, or green with one or more any space occupied by sliding
grounded conductors? Insulated yellow stripes, or by being bare panels on exterior walls.
conductors of No. 6 or (only grounding conductors may Sliding glass panels are
smaller, when used as be bare). excepted. At least one outlet
grounded conductors, must be must be installed for the laundry.
white, natural gray, or colored 83. Can green-colored wire be
(but never green) with three used for circuit wires? No. 90. A fastened-in-place
longitudinal white stripes. On Green is intended for appliance is located on a 15-
Type MI cable, the conductors identification of equipment- or 20- ampere branch circuit on
must be distinctively marked at grounding conductors only which there is a lighting fixture.
the ter- minal during installation What is the maximum rating that
84. What voltage is used would be permitted on the
77. How should conductors between conductors that supply appliance? 50 percent of the
larger than No. 6 be marked to lamp- holders of the screw- branch circuit rating
indi- cate the grounded wire? By shell type, receptacles, and
the use of white, natural gray, or appliances in dwellings? 91. A cord-and-plug-connected
colored (but never green) Generally speaking, a voltage of appliance is used on a 15- or 20-
insulation with three longitudinal 120 volts between conductors is ampere branch circuit. What is
white stripes, or by identifying considered the maximum. There the maximum rating permitted for
with a distinctive white marking are, however, some exceptions the appliance? 80 percent of the
at the terminals during branch circuit rating
installation 85. How must you ground the
grounding terminal of a 92. What is the smallest size
78. How is the high-leg grounding- type receptacle? By wire permissible for a feeder
conductor of a 4-wire delta the use of an equipment- circuit? No. 10 wire
identified? When the midpoint of grounding conductor of green
one phase is grounded to supply cov- ered wire, green with one or 93. What are the permissible
lighting and similar loads on a more yellow stripes, or bare voltage drops allowable on
4wire delta-connected conduc- tors. However, the feeders and branch circuits? On
secondary, the phase conductor armor of Type AC metal-clad feeders, not more than 3 percent
with the higher voltage to ground cable, the sheath of MI cable, or for power, heating, and lighting
shall be orange in color or be a metallic raceway is acceptable loads or combinations thereof,
indicated by tagging or other as a grounding means. PEC and a total maximum voltage
effective means at the point does not permit the general use drop not to exceed 5 percent for
where a connection is to be of flexi- ble metal conduit as a conductors and for combinations
made if the neutral conductor is grounding means unless it and of feeders and branch circuits
present the connec- tors are listed.
94. What is the basis for figuring
79. On a grounded system, 86. How can you ground the the general lighting loads in
which wire must be connected to grounding terminal on a occupancies? They are figured
the screw shell of a lampholder? grounding- type receptacle on on a volt-amperes-per-square-
The grounded conductor extensions to existing systems? foot basi
Run the grounding conductor to
80. What will determine the a grounded water pipe near the 95. What measurements are
classification of branch circuits? equipment used to determine the number of
The maximum permitted setting watts per square foot? The
or rating of the overcurrent- 87. What is the minimum size for outside dimensions of the
protective device in the circuit branch-circuit conductors? They building and the number of
cannot be smaller than No. 8 for floors, not including open
81. What color-coding is required ranges of 83⁄4 kW or higher porches or garage
on multiwire branch circuits? The rating and not smaller than No.
grounded conductor of a branch 14 for other loads 96. What is the unit load per
circuit shall be identi- fied by a square foot (in volt-amperes) for
continuous white or natural gray 88. What is the requirement a hospital? 2 volt-amperes
color. Whenever con- ductors of concerning all receptacles on 15-
different systems are installed in and 20-ampere branch circuits? 97. What is the unit load per
the same raceway, box, auxiliary All receptacles on 15- and 20- square foot (in volt-amperes) for
gutter, or other types of ampere branch circuits must be a school? 3 volt-amperes
enclosures, one system of the grounding type. A single
grounded conductor, if required, receptacle installed on an indi- 98. How many volt-amperes per
shall have an outer covering of vidual branch circuit must have a square foot are required to be
white or natural gray. Each other rating of not less than the rat- ing included for general-purpose
system grounded conductor, if of the branch circuit. receptacle outlets when a set of
required, shall have an outer plans does not show their
covering of white with an identifi- 89. What are the requirements locations in an office building? 1
able colored stripe (not green) for spacing receptacles in volt-ampere per square foot
running along dwelling occupancies? All
the insulation or another means receptacles in kitchens, family 99. What is the unit load per
of identification. Ungrounded rooms, dining rooms, living square foot (in volt-amperes) for
conductors of dif- ferent voltages rooms, parlors, libraries, dens, a warehouse used for storage?
shall be a different color or sun rooms, recreation rooms, 1⁄4 volt-ampere
identified by other means and bedrooms must be installed
so that no point along the wall 100. What voltages are used for
82. How must a conductor that is space, measured horizontally, is purposes of computing feeder
used only for equipment and more than 6 feet from a
and branchcircuit loads when unbalanced load for electric number connected between any
other voltages are not specified? ranges is consid- ered to be 70 two phases
120, 120/240, 208Y/120, 240, percent of the load on the
480Y/277, 480, and 600 volts ungrounded conductors 120. What is the maximum
111. How is the neutral load on a demand for two household
101. How are continuous and 5-wire, 2-phase system deter- electric ranges, wallmounted
noncontinuous loads for feeder mined? It is figured at 140 ovens, counter-mounted cooking
rat- ings calculated? Branch percent of the load on the units, and other household
circuits must be rated no less ungrounded conductors cooking appliances rated at over
than the noncontinuous load, 112. How may the neutral- 13⁄4 kW? 11 kW for ratings not
plus at least 125 percent of the feeder load on a 3-wire dc or over 12 kW
continuous load single- phase 3-wire ac system
be determined? The 70 percent 121. What computations are
102. Are unfinished basements demand factor may be used on required for commercial
of dwellings used in figuring range loads, and a further cooking equipment? See nec,
watts per square foot? Yes, if demand factor of 70 percent may Table 220.20.
adaptable for future use. If these be used on that portion of the s
spaces are not adapt- able, they unbalanced load in excess of 122. When computing the total
are not used 200 amperes load of a feeder for an electric
heating system and an air-
103. What loads are used in 113. How do you calculate the conditioning system that won’t
figuring outlets for other than unbalanced load on a 4-wire, 3- be used simultaneously, must
general illumination? Outlets phase system? The 70 percent both loads be added? No. The
supplying specific loads and demand factor may be used on smaller of the two can be omitted
appliances must use the ampere range loads, and a further
rating of the appliance. Outlets demand factor of 70 percent may 123. What are the minimum
supplying heavy-duty be used on that portion of the requirements for service-drop
lampholders must use 600 unbalanced load in excess of conductors? They must be of
voltamperes; calculations for 200 amperes sufficient size to carry the
other outlets must use 180 volt- load that is required of them,
amperes 114. Can you make a reduction but they musn’t be smaller than
on the neutral feeder load where No. 8 copper wire or No. 6
104. What load must be figured discharge lighting, data aluminum, except under limited
for show-window lighting? Not processing, or similar equipment load conditions where they may
less than 200 volt-amperes for is involved? No reduction can be not be smaller than No. 12
each linear foot measured made on the neutral capacity for harddrawn copper
horizontally along the base the portion of the load that
consists of electric discharge 124. What is the minimum
105. What are the receptacle lighting, data processing, or clearance for service drops
requirements in dwelling similar equipment. The load on over buildings? They shall have
occupancies for kitchen, family the neutral feeder must be taken a minimum clearance of 8 feet .
room, laundry, pantry, dining at 100 percent of the However, if the voltage does not
room, and break- fast room? ungrounded conduc- tors exceed 300 volts between
There shall be a minimum of two conductors and the roof has a
20-ampere small-appliance 115. Why do discharge lighting slope of not less than 4 inches in
circuits for the kitchen, family loads require no reduction in 12 inches, the clearance may be
room, pantry, dining room, and neu- tral feeder capacity? a minimum of 3 feet
breakfast room. There should Because of the effect of the third 125. What is the minimum height
also be a minimum of one 20- harmonic on the current value in of point of attachment of service
ampere circuit for the laundry the neutral feeder. In fact, it’s drops? 10 feet
sometimes necessary to
106. What is the unit load per oversize the neutral in such 126. What is the minimum
square foot (in volt-amperes) for circuits. The same effect occurs clearance of service drops over
a store? 3 volt-amperes when a great deal of data com- mercial areas, parking lots,
processing equipment is agricultural areas, and other
107. Outlets for heavy-duty connected to the circuits. areas sub- ject to truck traffic?
lampholders are to be based on 18 feet
a load of how many volt- 116. Are demand factors
amperes? 600 applicable to electric ranges? 127. What is the minimum
Yes. clearance of service drops over
108. Are demand factors side- walks? 12 feet
permitted in determining feeder 117. Can demand factors be
loads? Yes used on electric-clothes-dryer 128. What is the minimum
loads in the same manner as clearance of service drops over
109. What size feeders must be they are used on electric drive- ways, alleys, and public
installed in dwelling ranges? Yes roads? 18 feet
occupancies? The computed
load of a feeder must not be less 118. The demand factor for five 129. What is the minimum
than the sum of all branch circuit household electric clothes dryers clearance of service drops over
loads supplied by the feeder. is calculated at what residen- tial driveways? 12 feet
The demand factors can be used percentage? 80 percent
in the calculation of feeder sizes. 130. Can a bare neutral
119. Where two or more single- conductor be buried in the
110. When figuring the neutral phase ranges are supplied by a ground in an underground
load to electric ranges, what is 3-phase, 4-wire feeder, how is service? No; it must be
the maximum unbalanced load the total load computed? On the insulated, unless it is in a duct or
considered to be? The maximum basis of twice the maximum conduit .There is an exception:
bare copper for direct burial building, whichever is most 350, 400, 450, 500, 600, 700,
where bare copper is judged to convenient 800, 1000, 1200, 1600, 2000,
be suitable for the soil 2500, 3000, 4000, 5000, 6000
conditions. 139. What must the service
disconnecting means consist of? 147. Where can an overcurrent
131. Where underground service It may consist of not more than device be used in a grounded
conductors are carried up a pole, six switches or six circuit conductor? No overcurrent
to what minimum height must breakers in a common enclosure device shall be placed in any
they be given mechanical or in a group of separate enclo- permanently grounded
protection? 8 feet sures, provided that they are conductor, except as follows:
grouped together. Two or three Where the overcurrent device
132. Is sealing required where single-pole switches or circuit simultaneously opens all con-
underground ducts or conduits breakers may be installed on ductors of the circuit . A fuse
enter buildings? Yes, to prevent multi- wire circuits and counted shall also be inserted in the
the entrance of gases or as one, provided they have grounded conductor when the
moisture into the building. Spare handle ties or handles, so that supply is 3wire, 3-phase ac,
or unused conduits and ducts not more than six operations of one conductor grounded
must also be sealed the hand are required to
disconnect all circuits 148. May fuses be arranged in
133. What is the minimum size parallel? No, except as factory
of service-entrance conductor 140. What may be connected assembled in parallel and
nor- mally allowed? Any ahead of the service entrance approved as a unit
approved conductor having an discon- necting switch? Service
ampacity equal to the sum of the fuses, meters, high-impedance 149. May breakers be
noncontinuous loads, plus 125 shunt circuits (such as potential paralleled? No, only circuit
percent of continuous loads. coils of meters), supply breakers assembled in parallel
However, if the service entrance conductors for time switches, that are tested and approved as
conductors terminate in an surge-protection capacitors, a single unit
overcurrent device and assembly instrument transformers,
listed for operation at 100 lightning arresters, solar electric 150. Are the secondary
percent of its rating, the 125 systems, interconnected electric conductors of transformer
percent multiplier need not be power production sources, and feeder taps required to have
used circuits for emergency systems overcurrent protection?
(such as fire-pump equipment,
134. What is the minimum size etc.) 151. In what position must a
service for a single-family knife switch with fuses be
dwelling with an initial load of 10 141. In multiple-occupancy mounted? Why? In a vertical
kVA or more? The service must dwellings, must each occupant position, so that when the switch
be a minimum of 100 amperes have access to his disconnecting is opened, the blades won’t
for a 3-wire service means? Yes, except if the close by gravity; the line side
disconnects are under constant must be connected so that when
135. A residence has more than supervision and maintenance; in the switch is opened, the fuses
six 2-wire branch circuits. What this case, they can be accessible will be deenergized
is the minimum size of service to the building management only
required for this residence? The 152. When overcurrent-
service entrance conductors 142. Is it permissible to install protective device enclosures are
shall have an ampacity of not overcurrent-protective devices in mounted in a damp location,
less than 100 amperes for a 3- the grounded service conductor? what precautions must be taken?
wire service Overcurrent-protective devices The enclosures must be of an
may not be installed in the identified type for the location
136. Are splices permitted in grounded service conductor and must be mounted with at
service-entrance conductors? unless a circuit breaker is used least a 1⁄4-inch air space
Yes. They may be spliced with that between the wall or supporting
clamped or bolted connections; surface
or buried splices may be made 143. What is the minimum size
with a listed underground splice of service-entrance conductors 153. Where may Edison-base
kit operating at over 600 volts? plug fuses be used? Plug fuses
They musn’t be smaller than No. of the Edison-base type shall be
137. Are conductors other than 6 wire, unless in cable, where used only for replacement in
service-entrance conductors per- they may be a minimum of No. 8 existing installations where there
mitted in the same raceways or 144. What is the maximum is no evidence of overfusing or
cables? No, except for grounding circuit protection allowed with tampering
conductors and load flexible cords, sizes No. 16 or
management control conductors No. 18, and tinsel cord? 30 and 154. What is the maximum
20 amperes voltage rating of plug fuses? 125
138. What must be provided for volts
the disconnection of service con- 145. What is the maximum
ductors from building overcurrent protection allowed 155. What precautions must be
conductors? Some means must on cords of 20 amperes taken if plug fuses are used on
be provided for disconnecting all capacity? 50 amperes new installations? Fuses,
of the building conductors from fuseholders, and adapters
the service-entrance conductors, 146. Give the standard ratings must be so designed that
and this means must be located (in amperes) for fuses and circuit other Type S fuses may not be
in a readily accessible point breakers. Standard ratings are used
nearest the point of entrance of 15, 20, 25, 30, 35, 40, 45, 50,
the service conductors, on either 60, 70, 80, 90, 100, 110, 125, 156. What are the size
the out- side or inside of the 150, 175, 200, 225, 250, 300, classifications of Type S fuses
and adapters? Not exceeding together. However, this 6-foot
125 volts at 0–15 amperes, 16– 165. What are the grounding rule is a Fine Print Note and not
20 amperes, and 21–30 requirements when two or more a requirement of the nec.
amperes buildings are supplied from one
service? Where two or more 171. What is meant by effective
157. What is a Type S fuse? A buildings or structures are grounding? The path to ground
dual element fuse with special supplied from a common service, must be permanent and
threads so that fuses larger than the grounded system in each continuous, must be capable of
what the circuit was designed for building or structure is required safely handling the currents that
may not be used. They are to have a grounded electrode as may be imposed on the ground,
designed to make tampering or described in PEC, connected to and must have sufficiently low
bridging difficult the metal enclosure of the impedance to limit the potential
building disconnecting means above ground to facilitate the
158. Why are systems and and to the ac system grounded opening of the overcurrent
circuits grounded? To limit the cir- cuit conductor on the supply devices. The earth may not be
excess voltage to ground, which side of the building or structure used as the only equipment-
might occur from lightning or disconnecting means grounding conductor
exposure to other higher-voltage
sources 166. Is it required to ground a 172. What is a grounding
separately derived system, and if electrode conductor used for?
159. Is it necessary to ground so, where? Premises wiring The grounding conductor for
one wire on a two-wire dc systems that are required by circuits is used for grounding
system with not more than 300 PEC to be grounded shall be equipment, conduit, and other
volts between conductors? Yes, grounded if the phase metal raceways, including
in practically every case, conductors are not physically service conduit, cable sheath,
although there are a few excep- connected to another supply etc. 7-54 What appliances
tions system. They shall be grounded may be grounded to the neutral
at the transformer, generator, or conductor? Electric ranges and
160. When should ac systems other source of sup- ply, or at the electric clothes dryers, provided
be grounded? Ac circuits and switchboard on the supply side that the neutral is not smaller
systems must be grounded of the disconnecting means than No. 10 copper wire .
However, this is not allowed for
161. When is the next higher 167. When must metal, equipment that is fed from feeder
overcurrent protective device noncurrent-carrying parts of fixed panels, in mobile homes, or in
permit- ted to protect a equip- ment that are likely to recreational vehicles.
conductor where a standard fuse become energized be grounded?
or circuit breaker is not When supplied by metal-clad 173. Three-wire SE cable with a
available? In general up to 800 wiring, when located in damp or bare neutral is sometimes used
amperes wet places, when within reach of for connecting ranges and
a person who can make con- dryers. Is it permissible to use
162. When do circuits of 50 volts tact with a grounded surface or this type of cable when the
or less to ground have to be object or within reach of a per- branch circuit originates from a
grounded? When do they not son standing on the ground, feeder panel? No. The neutral
have to be grounded? Circuits of when in hazardous must be insulated
less than 50 volts need not be locations, or where any switches,
grounded unless they are enclosures, etc., are accessible 174. What equipment, other than
supplied from systems to unquali- fied persons electric ranges and clothes dry-
exceeding 150 volts to ground, ers, may be grounded to the
where they are supplied by 168. Must metal buildings be grounding conductor? The
transformers from ungrounded grounded? If excessive metal in grounding conductor on the
systems, or where they run or on buildings may become supply side of the service-
overhead outside buildings energized and is subject to disconnecting means may
personal contact, adequate ground the equipment, meter
163. If a grounded conductor is bonding and grounding will housing, etc. The load side of
not going to be used in a provide additional safety the
building, must this grounded Disconnecting means cannot be
conductor be run to each 169. What is the exception to used for grounding any
service? Yes. The grounded grounding the noncurrent- equipment other than electric
conductor must be run to each carrying parts of portable tools ranges and dryers
service. It need not be taken and appliances? Portable tools
farther than the service and appliances may have double 175. How should continuity at
equipment if it won’t be required insulation. If they have, they service equipment be assured?
in any of the circuits must be so marked and won’t Threaded couplings and bosses,
require grounding as well as thread less couplings
164. Is it necessary to ground and connections in rigid conduit
each service on a grounded 170. What are the grounding or EMT (electrical metal- lic
ac system? Each individual requirements when lightning tubing), must be wrench tight.
service must have a ground, and rods and conductors are Bonding jumpers must be used
this ground must be connected present? Lightning protection around concentric and eccentric
on the supply side of the service- ground terminals must be knockouts and ordinary lock-
disconnecting means. If there is bonded to the building’s nuts and bushings cannot be
only one service from a grounding system. In addition, used for bonding
transformer, there must be metal enclosures with
additional ground connection at conductors should be kept at 176. On flush-mounted
the transformer or elsewhere in least 6 feet away from lightning grounded-type receptacles, is it
the transformer circuit for the conductors. Where this is not necessary to bond the green
installation to be approved practical, they must be bonded grounding screw of the
receptacle to the equip- ment from point of attachment to grounding a telephone system?
ground? Yes, with a few cabinet or enclosure to the point Yes, if attached to a rigid metal
exceptions of attachment to the ground base that is seated on the water
clamp or fitting. Metal enclosures pipe or other ground electrode
177. Can conduit serve as the that are not physically and and listed for the purpose
equipment ground? Except for a electrically continuous must be
few cases, such as special bonded to the grounding elect- 192. What special precautions
precautions in hazardous trode conductor at both ends of must be taken in the use of
locations, conduit, armoured the metal enclosure ground clamps? They must be
cable, metal raceways, etc., can 185. May aluminum be used for made of a material suitable for
serve as the equipment ground a grounding electrode use in connec- tion with the
conductor? Yes, but it may not materials that they are attaching
178. What is the preferred type come in contact with masonry or to because elec- trolysis may
of grounding electrode? A metal the earth and cannot be run occur if they are made of
underground water system closer than 18 inches from the different metals. All surfaces
where there are 10 feet or more earth must be clean and free of paint
of buried metal pipe, including or corrosion
well casings that are bonded to 186. If a water pipe is used as
the system, is the preferred the grounding electrode, what 193. May aluminum grounding
grounding electrode .A made pre- cautions must be taken? conductors be run to cold water
electrode shall also be used in The grounding connection piping? Yes, but any clamps
addition to the buried metal should be made at the point of used with aluminum grounding
water pipe. water-service entrance. If this conduc- tors must be approved
cannot be done and there is a for the purpose
179. What is a “made” water meter on the premises, the
electrode? A made grounding water meter must be bonded 194. May conductors of different
electrode may be a driven pipe, with a jumper of sufficient length, systems occupy the same enclo-
driven rod, buried plate, or other so that the water meter may be sure? Conductors for light and
metal underground system read- ily removed without power systems of 600 volts or
approved for the purpose of disturbing the bonding. The less may occupy the same
grounding the equipment cold-water piping must be used, enclosure. The individual circuits
and it should be checked to may be ac or dc, but the
180. What are the requirements make certain that there are no conductors must all be insulated
for plate electrodes? They insulated connections in the for the maximum voltage of any
musn’t have less than 2 square piping conductor in the enclosure
feet (.186 square meter) of except emergency systems
surface exposed to the soil. 187. Where nonmetallic water
Electrodes of iron or steel must pipe serves an apartment 195. May conductors of systems
be at least 1⁄4 inch (6.4mm) building, what grounding over 600 volts occupy the same
thick; if made of nonferrous procedures are recommended? enclosure as conductors carrying
metal, it must be at least 0.06 The ground must also be bonded less than 600 volts? Under
inch (1.5mm) thick to the interior metal water piping certain conditions
system, including the hot-water
181. What should be the piping, and also to the sewer, 196. If the secondary voltage on
resistance of made electrodes? gas piping, air tracts, etc. This electric-discharge lamps is 1000
If a single made electrode does will provide additional safety volts or less, may its wiring
not measure a resistance to occupy the same fixture
ground of 25 ohms or less, it 188. When reinforcing bar is enclosure as the branch-circuit
must be supplemented by used as the grounding electrode, conductors? Yes, if insulated for
another electrode that is not less are clamps required to be listed the secondary voltage involved
than 6 feet away from the first for connecting the grounding
electrode conduct- tor to the rebar? Yes. 197. Is it permissible to run
Exothermic welding is also control, relay, or ammeter
182. May grounding electrode permitted conductors that are used in
conductors be spliced? No, connection with a motor or
splices are not permitted; 189. Can solder be used to starter in the same enclosure as
grounding electrode conductors attach connections to the the motor-circuit conductors?
must be one piece for their entire grounding conductor? Solder is Yes, if the insulation of all the
length, although there are some never permitted; exothermic conductors is enough for the
exceptions welding or listed press- sure highest voltage encountered
connectors are to be used
183. What is the smallest size 198. When boxes, fittings,
grounding electrode conductor 190. What means must be taken conduit, etc., are used in damp
permissible? to maintain continuity at metal or cor- rosive places, how must
No. 4 wire or larger may be boxes when non-metallic they be protected? They must be
attached to buildings; No. 6 wire systems of wiring are used so protected by a coating of
may be used if properly stapled that the equipment ground wire approved corrosion- resistant
to prevent physical damage; and will be continuous? The material
No. 8 wire may be used if in equipment grounds must be
conduit or armoured cable for attached by means of a 199. In damp locations, what
pro- section grounding screw (boxes are now precautions must be taken
available with a tapped hole against the corrosion of boxes,
184. When a grounding having 10/32 threads) or by fitting, conduit, etc.? There must
electrode conductor is enclosed some other listed means be an air space of at least 1 inch
in a metal enclosure, how is the between the wall 4 or supporting
metal enclosure to be installed? 191. Are sheet-metal straps material and any surface-
It must be electrically continuous considered adequate for mounted conduit fit- tings, etc.
207. When conductors are used derating factor to the current-
200. When raceways extend underground in concrete slabs or carrying capacity? Three current-
from an area of one temperature other masonry that comes in carrying conductors (neutrals not
into an area of a widely different direct contact with the earth, or included); when more than three
temperature, what precautions where Condensation or current-carrying conductors are
must be taken? Precautions accumulated moisture in run, a derating factor must be
must be taken to prevent the raceways is apt to occur, what applied
circulation of air from a warmer characteristic must the insulation
to a colder section through the have? It must be suitable for use 216. What are the derating
raceway in a wet location factors for more than three
current- carrying conductors in
201. When raceways and raceways or cables? 4 to 6
conductors are run through 208. Name some insulations conductors 80% rating 7 to 9
studs, joints, and/or rafters, what permitted for use in a wet conductors 70% rating 10 to 24
precautions must be taken? location. RHW, TW, THW, conductors 70% rating 25 to 42
They should be run near the THWN, and XHHW type cable conductors 60% rating 43
appropriate center of the wood conductors and above 50%
members or at least 11⁄4 inches 209. What are the cable rating
from the nearest edge; if the requirements for buried
mem- bers have to be notched conductors? Cables of one or 217. In derating, how is the
or a 11⁄4-inch protection more conductors for direct burial neutral conductor considered?
cannot be given, the conduit or in the earth must be Type USE Normally, the current in the
conductors must be covered by cable, except for branch circuits neutral conductor is only the
a steel plate not less than 1/6 and feeders, which may use unbalanced current. Therefore, if
inch in thickness Type UF cable. Type UF cable the system is well balanced, the
cannot be used for service wires neutral is not considered as a
202. How much wire must be current-carrying conductor and
allowed at outlets and switch 210. What other rules apply to would not enter into derating
boxes for connections and buried conductors? All
splices? There must be at least 6 conductors, including the neutral, 218. In determining the current in
inches of free conductor left for must be buried in the same the neutral conductor of a wye
mak- ing the connections . It is a trench and be continuous system, how is the neutral
good practice, however, to leave (without any splice). Extra classed? In a 4-wire, 3-phase,
more than 6 inches of free mechanical protection may be wyes-connected system, a
conductor at each box. required, such as a covering common conductor carries
board, concrete pad, or raceway approximately the same current
as the other conductors and is
203. What precautions must be 211. What is the minimum size therefore not considered a
taken to prevent induced of conductors allowed by the neutral in determining the
currents in metal enclosures? PEC? For power work, the derating of current capacity
When conductors carry ac, all smallest size is No. 14.
phase wires and the neutral wire, However, smaller sizes are 219. What size must the
if one is used, and all equipment allowed for controls and in conductors be for a parallel
grounding conductors must run special circum- stances feeder or service? At least 1/0
in the same raceway. When and larger for aluminum, copper-
single conductors must be 212. What is the ruling on clad aluminum, or copper
passed through metal having stranded conductors? Except for conductors
magnetic properties (iron and bus bars, Type MI cable, and
steel), slotting the metal between pool bonding, conductors of No. 220. What are the minimum
the holes will help keep down the 8 and larger must be stranded sizes for conductors when
inductive effect operated at a voltage of 0
213. What is the minimum size through 2000 volts? No. 14
204. When it is necessary to run of conductors that may be copper, No. 12 aluminum or
wires through air-handling ducts paralleled? Conductors in sizes copper-clad aluminum, with
or plenums, what precautions 1/0 and larger may be run in exceptions
must be taken? The conductors multiple, though there are 221. Where installed in
must be run in conduit, electrical exceptions raceways, stranded conductors
metallic tubing, intermediate of what size must be used? No.
metal conduit, flexible steel 214. When conductors are run in 8 and larger
conduit with lead-covered parallel, what factors must be
conductors, metal-clad cable, considered? Each phase or 222. What are the temperature
Type MI cable, inter- mediate neutral, if used, must be the limitations of conductors?
metal conduit, or in a Plenum- same length and of the same
rated cable conductor material; have the 223. What are the principal
same circular-mil area and the determinants of conductor
205. Does temporary wiring, same type of insulation; and be operating temperatures? The
such as for construction, arranged to terminate at both maximum temperature that the
Christmas lighting, carnivals, ends so that there will be equal conductor can with- stand over a
etc., come under the PEC? Yes distribution of current between prolonged period of time without
the conductors. Phases must be serious degradation
206. Are ground-fault circuit coordinated to eliminate Any
interrupters required on induction currents that may be 224. How are grounded
temporary wiring for construction caused to flow in the race- ways conductors identified? They must
sites? Yes, on all 15- and 20- be white or natural gray in color
ampere branch circuits ( 215. How many conductors may
be run in raceways or cables 225. How are equipment
without having to apply a grounding conductors identified?
They must be green, green with 236. Are cable trays intended to a name taken from the Bronx
a yellow stripe, or bare ( be used with ordinary branch Cable Company
circuit conductor? No. They are
226. How are ungrounded not intended for this purpose 245. What is metal-clad cable
conductors identified? They must commonly called? Type MC
be distinguished by colors other 237. Do cable trays have to be cable
than white, gray, or green used as a complete system, or
may they be used as only partial 246. What is Type MC cable?
227. What does the term cable supports? They must be Type MC cables are power and
“electrical ducts” mean? Suitable used as a complete system, control cables in the size range
electrical raceways, run including boxes and fittings from No. 14 and larger for
underground and embedded in copper and No. 12 and larger for
concrete or earth 238. Is grounding required on aluminum and copper-clad
metallic cable trays? They must aluminum. The metal enclosures
228. What is the ampacity of a be grounded but must not be are either a covering of
No. 6 AWG copper type THW used as the neutral conductor. If interlocking metal tape or a
conductor? 65 amperes used as the equipment- smooth, impervious, close-fitting,
grounding conductor, they must or corrugated tube.
229. What are the ampacity meet the requirements of PEC Supplemental protection of an
correction factors for a Type ac outer covering of corrosion-
cable assembly when the 239. Is open wiring on insulators, resistant material is required
ambient temperature is other commonly known as knob-and- where such protection is needed
than 30ºC (86ºF)? tube wiring, recognized by the
Code? Yes, although it is almost 247. What is Type AC cable?
230. What is the maximum never approved by inspectors for Type AC cables are branch-
operating temperature for a new installations. It is in the PEC circuit and feeder cables with an
Type? THWN conductor? 75ºC primarily because a great deal of armor of flexible metal tape.
(167ºF) in wet locations 231. it has been previously installed Cable of the AC type must have
Under what conditions can a and must be properly maintained an internal bonding strip of
Type XHHW conductor are used copper or aluminum in tight
in a wet location? When it is 240. What is Type MI cable? physical con- tact with the armor
rated at a temperature of 75ºC Type MI cable is a cable in which for its entire length
(167ºF) one or more electrical
conductors are insulated with a 248. At what intervals must Type
232. What are the requirements highly compressed refractory MC cable be supported?
when more than one calculated mineral insulation (magnesium At intervals not exceeding 6 feet
or tabulated ampacity could oxide) and enclosed in a liquid-
apply for a given circuit length? tight and gas-tight metallic 249. At what intervals must Type
The lowest value shall be used sheathing (copper) AC cable be supported? At
intervals of not more than 41⁄4
233. Give the ampacities for 241. Where can Type MI cable feet and within 12 inches of
Types ac or NM conductor be used? This is one wiring boxes and fittings, except where
assemblies based on an ambient material that can be used for cable is fished and except
air temperature of 30ºC (86ºF). practically every conceivable lengths of not over 2 feet at
type of service or circuit. When it terminals where flexibility
234. What advantages would is exposed to cinder fill or other
two parallel 500-MCM cables destructive corrosive conditions, 250. How may bends be made in
have over one 1000-MCM it must be protected by materials Type AC cable? Bends must be
cable? They would be easier to suitable for these conditions made so that the cables are not
handle and to pull into raceways. damaged. The radius of the
According to PEC, RH wire has 242. What precautions must be curve of the inner edge of any
a current-carrying capacity of taken with Type MI cable to pre- bend must not be less than 5
545 amperes, whereas 500- vent the entrance of moisture? times the diameter of Type AC
MCM cable has a current- Where Type MI cable cable
carrying capacity of 380 terminates, an approved seal
amperes. Therefore, two 500- must be provided immediately 251. What extra precaution is
MCM cables in parallel would after stripping to prevent the necessary with Type AC cable
have the same circular-mil area entrance of moisture into the when attaching fittings? An
as one 1000-MCM cable and a mineral insulation; the approved insulating bushing or
current-carrying capacity of 760 conductors must be insulated equivalent approved protection
amperes compared to the 545- with an approved insulation must be provided between the
ampere current-carrying capacity where they extend beyond the conductors and the armor
of one 1000-MCM cable. This is sheath
approximately 40 percent more 252. What is nonmetallic-
current-carrying capacity for the 243. Does the outer sheath of sheathed cable? Nonmetallic-
two 500-MCM cables. In Type MI cable meet the sheathed cable is an assembly
addition, there is usually a cost requirements for equipment of two or more insulated
advantage by using two 500- grounding? Yes. It provides an conductors having an outer
MCM conductors, rather than excellent path for equipment sheath of moisture- resistant,
one 1000-MCM conductor. grounding purposes but not for flame-retardant, nonmetallic
use as a grounded or neutral material
235. May THW insulated conductor
conductors be run through a 253. What are the available
continuous row of fluorescent 244. What is armored cable sizes of nonmetallic-sheathed
fixtures? Yes commonly called? Type AC cable? Sizes No. 14 to No. 2
cable, or in some locations “BX,” (AWG) inclusive
254. What is the difference are of the thermoplastic or which could prove destructive to
between Type NM and Type rubber type. However, service- the system
NMC? Cables? In addition to entrance cable without individual
having flame-retardant and insulation on the grounded 270. When subject to cinder fill,
moisture-resistant covering, (neutral) conductor can be used what precautions must be taken
Type NMC cable must also be to sup- ply ranges or clothes with rigid metal conduit? It must
fungus-resistant and corrosion- dryers when the cable does not be protected by a minimum of 2
resistant have an outer metallic covering inches of noncinder concrete
and does not exceed 150
255. Where may Type NM cable volts to ground. It may also be 271. What is the minimum size
be used? It may be used for used as a feeder when it of rigid metal conduit? 1⁄2-inch
exposed and concealed work in supplies other buildings on the trade size, with a few exceptions
normally dry locations. It may same premises. SE cable with a
also be installed or fished in the bare neutral must not originate in 272. What are the
air voids of masonry block or tile a feeder panel requirements for couplings on
walls, where such walls are not rigid metal conduit? Threaded or
exposed to excessive moisture 264. Describe underground threadless couplings and
or dampness feeder and branch-circuit cable. connectors must be made tight.
Underground feeder and Where installed in wet locations
256. In dwelling occupancies, branch-circuit cable must be or buried in concrete masonry or
what, if any, restrictions have an approved Type UF cable in fill, the type used must prevent
been added? Types NM and sizes No. 14 copper or No. 12 water from entering the conduit
NMC cables are permitted in aluminum or copper-clad
one- and two- family dwellings or aluminum to No. 4 0 AWG, 273. Are running threads
multifamily dwellings and other inclusive. The ampacity of Type permitted on rigid metal conduit?
structures not exceeding three UF cable shall be that of 60ºC They cannot be used on conduit
floors above grade (140ºF) conductors in for connections at couplings
accordance with PEC. In
257. Where may Type NMC addition, the cable can include a 274. What is the maximum
cable be installed? Where bare conductor for equipment number of bends permitted in
exposed to corrosive fumes or grounding purposes only. The rigid metal conduit between
vapors, for exposed and overall covering must also be outlets? Not more than 4 quarter
concealed work, in dry and moist suitable for direct burial in the bends, or a total of 360º; this
or damp places, and inside or earth includes offsets, etc., at outlets
outside of masonry block or tile and fittings
walls 265. What is required as
overcurrent protection for Type 275. After a cut is made in rigid
258. Where is it not permissible UF cable? Underground feeder metal conduit, what precaution
to use Type NM or Type NMC? and branch-circuit cable may be must be taken? All cut ends of
cable? As service-entrance used underground, including conduits must be reamed to
cable, in commercial garages, in direct burial, provided they have remove any rough ends that
theaters, and similar locations, over- current protection that might damage the wire when it is
except as provided in the PEC, does not exceed the capacity of pulled in
Article 518, “Places of Assembly” the conductors
276. What are the principal
259. What supports are 266. May conductors of the determinants of conductor
necessary for Types NM and same circuit be run in separate operating temperatures? The
NMC cable? The installation trenches? All conductors of the maximum temperature that the
must not be subject to damage, same circuit must be run in the conductor can withstand over a
and the cable must be secured same trench or raceway prolonged period of time without
in place at intervals not serious degradation
exceeding 41⁄2 feet and 267. What depth must UF cable
supported within 12 inches from be buried? In general, UF cable 277. How are grounded
boxes and fittings must be buried at a depth of 24 conductors identified?
inches or more. However, there They must be white or natural
260. What are the two types of are circumstances under which it gray in color
service-entrance cable? Type can be buried at lesser depths
SE and Type USE 278. How are equipment
268. May UF cable be used for grounding conductors identified?
261. What type of outer sheath interior wiring? Yes, but it must They must be green, green with
does a Type SE cable have? It be installed in accordance with a yellow stripe, or bare
has a flame-retardant, Article 334 and must not be 279. How are ungrounded
moisture-resistant covering exposed to direct sunlight unless conductors identified? They must
it is specifically identified for this be distinguished by colors other
262. What type of outer sheath purpose than white, gray, or green
does Type USE cable have? For
underground use, it has a 269. Where can rigid metal 280. What does the term
moisture-resistant covering but is conduit are used? Practically “electrical ducts” mean? Suitable
not required to have a flame- everywhere; however, rigid metal electrical raceways run
retardant covering conduit protected solely by underground and embedded in
enamel cannot be used concrete or earth
263. Can service-entrance cable outdoors. Also, where
be used as branch-circuit practicable, dissimilar metals 281. What are the requirements
conductors or feeder should not come in contact when more than one calculated
conductors? It may be used for anywhere in the system to avoid or tabulated ampacity could
interior wiring systems only when the possibility of galvanic action, apply for a given circuit length?
all circuit conductors of the cable The lowest value shall be used
current-carrying conductors at
282. What is intermediate metal any cross section (unless 302. What are the requirements
conduit? It is a metal conduit, derated); signal circuits or for pendant boxes? Pendant
similar to rigid metal conduit, but starter-control wires are not boxes must be supported by
slightly lighter weight included either multiconductor cords or
cables in an approved manner,
283. What precautions should be 294. Are splices permitted in or by conduit
taken when installing rigid non- wireways? Yes, provided that the
metallic conduit in extreme cold? conductors with splices do not 303. Can a box be used to
They should not be used in take up more than 75 percent of support a ceiling fan? Yes
areas where they will be the area of the wireway at any
subjected to damage, since they point 304. What protection must be
can become brittle at low given to conductors entering
temperatures 295. May the wireways be open boxes or fittings? They must be
at the ends? No. The dead ends protected from abrasion, and the
284. May plastic water pipe be must be closed openings through which
used as conduit? No. It may not conductors enter must be
be used for this purpose 296. Is the equipment-grounding adequately closed
conductor used in figuring the
285. What uses are permitted for number of conductors allowed in 305. In what position must knife
rigid nonmetallic conduit? For a box? Yes, but only one switches be mounted? Single-
600 volts or less, except for conductor is to be counted throw knife switches must be
direct burial where it is not less mounted so that gravity won’t
than 18 inches below grade and 297. What is the purpose of tend to close them. Double-throw
where the voltage exceeds 600 auxiliary gutters? They are used knife switches may be mounted
volts, in which case it must be to supplement wiring spaces at either vertically or horizontally;
encased in 2 inches of concrete; meter centers, distribution however, if mounted vertically, a
in concrete walls, floors, and centers, switchboards, and locking device must be provided
ceilings; in locations subject to similar points of wiring systems; to ensure that the blades remain
severe corrosive influences; in they may enclose conductors or in the open position when so
cinder fill; and in wet locations bus bars but cannot be used to set
enclose switches, overcurrent
286. Where is the use of non- devices, or other appliances or 306. Do switches and circuit
metallic rigid conduit prohibited? apparatuses breakers have to be accessible
In hazardous locations, for the and grouped? Yes. Switches and
support of fixtures or other 298. What is the maximum circuit breakers, as far as is
equipment, where subject to number of conductors permitted practical, must be readily
physical damage, or where high in auxiliary gutters, and what accessible
temperatures are present is the maximum percentage of
fill allowed? The maximum fill 307. What is the maximum
287. Where must expansion cannot exceed 20 percent of the number of overcurrent devices
joints is used on rigid nonmetallic interior cross-sectional area. A permitted on one panel board?
conduit? Where required to maximum of 30 current-carrying Not more than 42 overcurrent
compensate for thermal conductors at any cross section devices of a lighting and
expansion and con- traction (unless dated); signal circuits or appliance branch-circuit panel
when the expansion starter-control wires are not board can be installed in any one
included cabinet or cutout box. A two-pole
288. Are bushings required when circuit breaker is considered as
rigid nonmetallic conduit is 299. What is the current-carrying two overcurrent devices, and a
used? Yes capacity of bus bars in auxiliary three-pole circuit breaker is
289. What is electrical metallic gutters? The current carried considered as three overcurrent
tubing (EMT)? continuously in bare copper bars devices in the interpretation of
A thin-walled metal raceway in auxiliary gutters shall not the question
exceed 1000 amperes per
290. May more or fewer square inch of cross section of
the conductor. For 308. How would you define a
conductors be contained in EMT lighting and appliance branch-
than in rigid metal conduit? The aluminum bars the current
carried continuously shall not circuit panel board? A branch-
same number of wires applies to circuit panel board that has more
both raceways exceed 700 amperes per square
inch of cross section of the than 10 percent of its
overcurrent devices rated 30
291. When EMT is exposed to conductor
amps or less
moisture or used outdoors, what
types of fittings must be used? 300. May taps and splices be
309. What methods are specified
They must be rain-tight fittings made in auxiliary gutters? Yes;
however, splices may not occupy in the Code for protecting
conductors in trenches from
292. When EMT is buried in more than 75 percent of the
concrete, what type fittings must crosssectional area at any point. damage due to ground
movement? Coiling the
be used? They must be All taps must be identified as to
concrete-tight fittings the circuit or equipment that they conductor or cable 8-136 Must
all underground metal conduit
supply
293. What is the maximum and fittings be grounded?
Generally yes, but an exception
number of conductors permitted 301. May round boxes be used
in metal wireways, and what is as outlet, switch, or junction is made for a metal conduit
elbow in a rigid non-metallic
the maximum percentage of fill? boxes? No. They cannot be used
The maximum fill cannot exceed where conduits or connectors conduit run, if it is no less than
18 inches below grade, or if it is
20 percent of the interior cross- with locknuts or bushings are
sectional area. A maximum of 30 used
beneath a 4-inchthick concrete cord? For jacketed cords 332. How must fixtures be
slab furnished with an appliance grounded? They may be
connected to metal raceways,
310. What is a primary cell? A 321. Under what conditions may the armor of metal-clad cable,
primary cell is a cell that multiconductor cables rated at etc., if properly installed and
produces electric current from an over 600 volts, nominal, be grounded, or a separate
electrochemical reaction but is used? To connect mobile equipment-grounding conductor
not capable of being recharged. equipment and mobile not smaller than No. 14 wire may
machinery be used
311. What is a secondary cell? A
cell that is capable of being 322. What precautions are 333. On motor-driven
recharged by passing an electric necessary when installing fixture appliances, what disconnecting
current through it in the opposite wires in temperatures colder means must be provided, and
direction from the discharging than 10°C (14° F)? Exercise care how must it be located? The
current. during installation, since the switch or circuit breaker that
conductors may become brittle serves as the disconnecting
means on a stationary motor-
312. How are automobile driven appliance must be located
batteries rated? In ampere- 323. What is the maximum within sight of the motor
hours. operating temperature of a Type controller or be capable of being
TFFN fixture wire? 90 C locked in the open position
313. Explain the meaning of
ampere-hours. At full charge, the 324. What are the requirements 334. On all space-heating
battery is capable of delivering x for fixtures installed near systems, what is the main
number of amperes for y number combustible materials? They requirement? All heating
of hours; e.g., a 100-ampere- must be constructed, installed, or equipment must be installed in
hour battery would be capable of equipped with shades or guards an approved manner
delivering 10 amperes for 10 so that combustible materials
hours, 1 ampere for 100 hours, won’t be subjected to
etc. temperatures in excess of 90 C 335. What are the requirements
(194 F) for heating cables? Heating
314. When adding water to a car cables must be supplied
battery, what precautions should complete with factory-
325. Under what condition may a assembled nonheating leads of
be observed? Use distilled water fixture is installed in a show
only, and fill the cells only to their at least 7 feet in length
window? When it is chain-
pre- scribed levels. supported and externally wired 336. What markings must be
present on heating cables? Each
315. Will a discharged car 326. When a fixture weighs more unit length must have a
battery freeze easier than a fully than 50 pounds, may it be sup- permanent marking located
charged battery? Yes. ported from the outlet box? It within 3 inches of the terminal
must be supported end of the nonheating leads, with
316. How can a lead-acid battery independently of the outlet box the manufacturer’s name or
be recharged? By connecting it identification symbol, catalog
to a dc source at slightly higher 327. What precautions must be number, and the rating in volts
than battery voltage and passing taken in conductors for movable and watts or amperes. The leads
a high current through it in the parts of fixtures? Stranded on a 240-volt cable must be red;
opposite direction from the conductors must be used and on a 120-volt cable the leads are
discharging current. must be arranged so that the yellow; 208-volt cable leads are
weight of the fixture or movable blue; and on a 277-volt cable the
317. What derating factors must parts won’t put tension on the leads are brown
be applied to a flexible cord that conductors. These measures
contains six current-carrying must be taken to protect the 337. What clearance must be
conductors? 80 percent of the conductors given to wiring in ceilings?
value Wiring above heated ceilings
328. What types of insulation are and contained within thermal
318. What are the requirements, permitted within 3 inches of a insulation must be spaced not
with respect to exposed live ballast within a ballast less than 2 inches above the
parts, on lighting fixtures? There compartment? Conductors rated heated ceiling and will be
may be no live parts exposed, at 90 C (194 F) considered as operating at 50 C.
except on cleat receptacles and Wiring above heated ceilings
lamp holders that are located at and located over thermal
329. Which wire must be
least 8 feet above the floor insulation having a minimum
connected to the screw shells
thickness of 2 inches requires no
of lampholders?
319. What must be done to correction for temperature.
The grounded, or white,
flexible cords and cables where Wiring located within a joist
conductor
they pass through holes in space having no thermal
covers, outlets boxes, or similar insulation must be spaced not
330. What is the maximum less than 2 inches above the
enclosures? They require
protection in the form of wattage permitted on a medium heated ceiling and will be
lamp base? 300 watts considered as operating at 50
bushings or fittings

320. Under what conditions may 331. What is the maximum lamp 338. What are the restricted
wattage permitted for a mogul areas for heating?
a light blue colored insulation is
used for the identification of a lamp base? 1500 watts Heating panels must not extend
grounded conductor in a flexible beyond the room or area in
which they originate; cables
must not be installed in closets, 346. If a branch circuit supplies in its most easily ignitable
over cabinets that extend to the only one motor, how large must concentration
ceiling, under walls or partitions the conductor size of the branch
or over walls or partitions that circuit be in comparison to the 353. What precautions must be
extend to the ceiling cur- rent rating of the motor? The taken when installing intrinsically
branch-circuit conductors should safe circuits? They are required
339. What clearance must be be figured at not less than 125 to be physically separated from
provided for heating cables and percent of the full-load current wiring of all other circuits that are
panels from fixtures, boxes, and rating of the motor not intrinsically safe and from
openings? Panels and heating separate intrinsically safe circuits
cables must be separated by a 347. How shall equipment for
distance of at least 8 inches from hazardous (classified) locations 354. What is a Class I, Division 2
lighting fixtures, outlets, and be marked? Approved location? Locations in which
junction boxes, and 2 inches equipment shall be marked to flammable volatile liquids or
from ventilation openings and show the class, group, and flammable gases are handled,
other such openings in room operating temperature or processed, or used, but in which
surfaces, or at least a sufficient temperature range, based on the hazardous liquids, vapors, or
area must be provided 340. May operation in a 40 C ambient for gases will normally be confined
embedded cables be spliced? which it is approved Exceptions within closed containers or
Only when absolutely necessary, are made for equipment of the closed systems from which they
and then only by approved nonheat-producing type, such as can escape only in case of
means; in no case may the junction boxes, conduit, and accidental rupture or breakdown
length of the cable be altered fittings, which are not required to of such containers or systems, or
have a marked operating in case of abnormal operation of
341. May heating cable be temperature. equipment; in which hazardous
installed in walls? No concentrations of gases or
348. What is a Class I location? vapors are normally prevented
342. How must hermetic-type These are locations in which by positive mechanical
refrigeration compressors be flammable gases or vapors are, ventilation, but which might
marked? They must have a or may be, present in the air in become hazardous through
nameplate, giving the quantities sufficient to produce failure or abnormal operation of
manufacturer’s name, the phase, explosive or ignitable mixtures the ventilating equipment; or
voltage, frequency, and full-load which are adjacent to a Class I,
current in amperes of the motor 349. What is a Class I, Division 1 Division 1 location and to which
current when the compressor is location? Locations in which hazardous concentrations of
delivering the rated output. If the hazardous concentrations of gases or vapors might
motor has a protective device, flammable gases or vapors exist occasionally be communicated
the name- plate must be continuously, intermittently, or unless such communication is
marked “Thermal Protection.” periodically under normal prevented by adequate positive-
For complete details operating conditions; in which pressure
hazardous concentrations of
343. When using switches, such gases or vapors may exist ventilation from a source of clean
fuses, and other disconnecting frequently because of repair or air, and effective safeguards
means, must the voltage of the maintenance operations or against ventilation failure are
switch coincide with that of the because of leakage; or in which provided
motor? Yes. The voltage rating breakdown or faulty operations
of the switch may not be less of equipment or processes that 355. What are Class II locations?
than 115 percent of the full load might release hazardous Locations that are hazardous
current rating of the motor concentrations of flammable because of the presence of
gases or vapors might also combustible dust
cause simultaneous failure of
344. If a switch is used that has electrical equipment
a current rating larger than is 356. What are Class II, Division
required, may it be adapted for 1 locations? Locations in which
less current? Yes, adapters of 350. What is a group A combustible dust is, or may be,
the approved type are available atmosphere in a hazardous in suspension in the air
for reducing the fuse size of the (classified) location? One that continuously, intermittently, or
switch; fuses larger than the contains acetylene periodically under normal
switch rating, however, may not operating conditions in quantities
be used. 351. What is a group C sufficient to pro- duce explosive
atmosphere in a hazardous or ignitable mixtures; where
345. May the enclosures for (classified) location? One that mechanical failure or abnormal
controllers and disconnecting contains cyclopropane, operation of machinery or
means for motors be used as ethylether, ethylene, or gases or equipment might cause such
junction boxes? Enclosures for vapors of equivalent hazard mixtures to be produced and
controllers and disconnecting might also provide a source of
means for motors may not be 352. What is intrinsically safe ignition through simultaneous
used as junction boxes, auxiliary wiring and equipment? failure of electrical equipment,
gutters, or raceways for Equipment and wiring that is not operation of protective devices,
conductors feeding through or capable of releasing sufficient or from other causes; or in which
tapping off to the other electrical or thermal energy dusts of an electrical conducting
apparatus unless designs are under normal or abnormal nature may be present
employed that provide adequate conditions to cause ignition of a
space for this purpose specific flammable or 357. What are Class II, Division
combustible atmospheric mixture 2 locations? Locations in which
combustible dust won’t normally
be in suspension in the air or is 14-25 What type of wiring must permitted, bonding jumpers must
not likely to be thrown into be used in Class I, Division 2 be provided around such conduit
suspension by the normal areas? Threaded rigid metal
operation of equipment or conduit, threaded steel 373. Is surge protection required
apparatus in quantities sufficient intermediate metal conduit, in Class I locations? No, but if
to produce explosive or ignitable enclosed gasketed busways, or installed, lightning-protection
mixtures, but where deposits or Type PLTC cable in accordance devices are required on all
accumulations of such dust may with the provisions of Article 725, ungrounded conductors. They
be sufficient to interfere with the Type MI, MC, MV, TC, or SNM must be connected ahead of the
safe dissipation of heat from cable with approved termination service-disconnecting means
electrical equipment and fittings and must be bonded to the race-
apparatus, or where such way at the service entrance
deposits or accumulations of 365. What type of fittings must
dust on, in, or in the vicinity of be used in Class I, Division 2 374. What are some of the
electrical equipment might be areas? Only boxes, fittings, and
ignited by arcs, sparks, or precautions that must be taken
joints that are approved for this when transformers are used in
burning material from such location
equipment Class II, Division 1 locations?
Transformers containing a
366. Why is sealing needed in flammable liquid must be
358. What are Class III conduit systems and not in Type installed only in approved vaults
locations? Locations that are MI cable systems in Class I that are constructed so that a fire
hazardous because of the areas? Seals are provided in cannot be communicated to the
pressure of easily ignitable fibers conduit systems to minimize the hazardous area. Transformers
or flyings, but in which such pas- sage of gases, vapors, or that don’t contain a flammable
fibers or flyings are not likely to fumes from one portion of the liquid must also be installed in
be suspended in the air in electrical vaults or must be enclosed in
quantities sufficient to pro- duce tight metal housings without
ignitable mixtures ventilation
367. When connecting conduit to
switches, circuit breakers, etc.,
359. What are Class III, Division where must seals be placed? As 375. What type of wiring must be
1 locations? Locations in which close as possible to the installed in Class II, Division 1
easily ignitable fibers or enclosure, but not more than 18 locations? Rigid metal conduit
materials producing combustible inches away (threaded), threaded steel
flyings are handled, intermediate metal conduit, or
manufactured, or used Type MI cable must be used.
368. When a conduit leaves a
Class I, Division 1 location, Boxes and fittings must have
360. What are Class III, Division where must the seal be located? threaded bosses and tight-fitting
2 locations? Locations in which The seal must be placed at the covers and must be approved for
easily ignitable fibers are stored first fitting when a conduit leaves the location
or handled, except in process or this area; it may be on either
manufacture of the product side of the boundary 376. What type of wiring must be
installed in Class II, Division 2
361. Where may meters, 369. When a conduit leaves a locations? Rigid metal conduit,
instruments, and relays is Class I, Division 2 location, intermediate metal conduit, dust-
mounted in Class I, Division 1 where must the seal be located? tight wireways, electrical metallic
locations? Within enclosures The seal must be placed at the tubing, or Type MI, MC, or SNM
approved for this location first fitting when a conduit leaves cable. Boxes, fittings, and joints
this area; it may be on either must be made to minimize the
362. Where may meters, side of the boundary entrance of dust
instruments, and relays with
make-and- break contacts be 370. If there is a chance that 377. Is grounding and bonding
mounted in Class I, Division 2 liquid will accumulate at a seal, necessary in Class II locations?
locations? Immersed in oil or what precautions must be taken? Yes. All exposed noncurrent-
hermetically sealed against An approved seal for periodic carrying parts of equipment must
vapor or gases draining of any accumulation be grounded. Locknuts and
must be provided bushings are not adequate
363. What type of wiring must be grounding; they must use
used in Class I, Division 1 371. What must be provided for bonding jumpers
areas? Rigid metal conduit switches, motor controllers,
(threaded), intermediate metal relays, fuses, or circuit breakers 378. Is surge protection required
conduit, or Type MI cable in Class I locations? They must in Class II locations?
be provided with enclosures and If installed, lightning-protection
364. What type of fittings must must be approved for the devices of the proper type are
be used in Class I, Division 1 location required on all ungrounded
areas? All boxes, fittings, and conductors; they must be
joints must be threaded. At least 372. Is grounding necessary in connected ahead of the
five full threads must be used Class I locations? Yes. It is servicedisconnecting means and
and must be fully engaged, and highly important. All exposed must be bonded to the raceway
all materials, including flexible noncurrent-carrying parts of at the service entrance
connections, must be equipment are required to be
approved (explosion-proof) by grounded. Locknuts and 379. What type of wiring is
the inspecting authority for these bushings are not adequate required in Class III, Division 1
locations grounding; they must have locations? Threaded rigid metal
bonding jumpers around them. conduit, threaded steel
Where flexible conduit is used as intermediate metal conduit, or
Types MI, MC, SNM; boxes and between closet and desktop?
fittings must have tight-fitting 100 meters. 16-22 May communications
covers. There must not be any circuits share a raceway with a
screw-mounting holes within the 16-8 What is the most widely community antenna television
box through which sparks might used type of data cable? system? Yes
escape Unshielded twisted pair, also
known as UTP. 16-23 What types of
380. What vehicles are included communication cables may be
under the commercial-garages 16-9 Must telecommunications installed in cable trays? Types
classification? These locations test equipment be listed? No MPP, MPR, MPG, MP, CMP,
include places of storage, CMR, CMG, and CM
repairing, or servicing of self- A city block
propelled vehicles, including
16-24 What is meant by the
passenger automobiles, buses,
trucks, tractors, etc., in which 16-11 What types of distribution word “premises”? A user
circuits don’t require protectors? property on the far side of the
flammable liquids or flammable
gases are used for fuel or power Underground circuits that are demarcation point
unlikely to contact power circuits
(
16-25 How should CATV
381. What is a gasoline- 16-12 How far must conductors be installed on power
communication circuits be poles? Below power conductors
dispensing and service station?
This includes locations where separated from lightning
protection conductors? 6 feet, 16-26 What part of a coaxial
gasoline or other volatile
flammable gases are transferred but exceptions are made cable must be grounded? The
when this spacing is outer conductive sheath.
to the fuel tanks (including
auxiliary fuel tanks) of self- “impractical.”
propelled vehicles. Lubritoriums, 16-27 What is the required
service rooms, repair rooms, 16-13 What restriction is clearance above a roof for a
offices, sales-rooms, compressor placed on the installation path coaxial cable entering a
rooms, and similar locations of a grounding conductor for building? 8 feet, with two
communication circuits? That it exceptions.
be run in a straight line
382. What types of conductors
are typically found in a set of 16-28 If a grounding conductor
network-powered broadband 16-14 May a metal power for a coaxial system is run in
cables? Coaxial, twisted-pair, service conduit serve as the metal conduit, what other
fiber optic, and power grounding electrode conductor requirement must be met? Both
conductors for a communication grounding ends of the raceway must be
system? Yes bonded to the grounding
383. What is a fault protective conductor, terminal, or electrode
device? A device for a network- 16-15 What part of a
communications cable must be
powered broadband system that 16-29 What types of conductors
is designed to protect people grounded? The metallic sheath.
are typically found in a set of
and equipment in the case of network-powered broadband
faults in the system 16-16 Where must a cables? Coaxial, twisted-pair,
communications cable be fiber optic, and power
grounded once it enters a conductors (
16-1 Which is the primary article
of the PEC governing data building? As close as possible to
the point of entrance.
cabling? 16-30 What is a fault protective
device?
16-17 What option to grounding A device for a network-powered
exists? The interruption of the broadband system that is
16-2 When data conductors cable sheath with an insulating designed to protect people and
enter buildings, how far must interrupting device.
they be kept from power drops? equipment in the case of faults in
the system
A minimum of 12 inches
16-18 When a protector is
installed on a mobile home, what 16-32 May network-powered
16-3 What is a “protector”? A is the minimum size of conductor broadband cables be installed
type of surge suppression device that it must be bonded with? No.
specifically designed for with messenger wire? Yes
12 AWG
communication circuits
16-33 What is the minimal
16-19 What rating of clearance above roofs for
16-4 What is the minimum size communication cable is network- powered broadband
of grounding conductor for designed for installation in
communication circuits? No. 14 cables? 8 feet, with exceptions
plenums? Type CMP for garages, overhangs, and
AWG
sloped roofs.
16-20 What rating of
16-5 Is firestopping required for communication cable is 16-34 Are protectors required
data cables that pass through designed for installation in
fire-resistant barriers? Yes for network-powered broadband
risers? Type CMR systems? Yes

16-21 What rating of 16-35 What is the minimum size


16-7 For structured cabling, what communication cable is of grounding conductor that may
is the horizontal distance limit designed for installation under be used for network-powered
carpets? Type CMUC
broadband systems? No. 14 time-consuming and difficult 16-57 Name two types of
AWG process. communications signals. Analog
and digital.
16-36 May a power service 16-45 Optical fiber cables don’t
enclosure serve as a grounding carry electricity. Why are they 16-58 In general, what type of
electrode for a network-powered covered within the PEC? For two signal is better? Digital; it
broadband system? Yes reasons: first, because they are provides a much clearer and
often installed with electrical stronger signal.
16-37 If separate electrodes are cables and by the same
used for power system installers; second, because they 16-59 What is a protector?
grounding and for network- are dependent upon the Protectors are surge-suppressor-
powered broadband grounding, electrical and electronic type devices. They are required
what is required? The two equipment to which they are for many outdoor
electrodes must be bonded with connected. communication circuits
a conductor of no less than No. 6
AWG. An exception is made for 16-46 Does the PEC cover all 16-60 What is the smallest
bonding at mobile homes, if the optical fiber installations? No. grounding conductor that can be
mobile home is supplied with used for communication circuits?
power via cord and plug, or 16-47 Can optical fiber cables No. 14 copper
where the mobile home has no be installed in cable trays? Yes
service equipment or
disconnecting means 16-61 What steps must be taken
16-48 What types of optical fiber when communication grounding
cables are allowed in plenums? conductors are installed in metal
16-38 What is the maximum Types OFNP and OFPC. Also, if conduit? The metal conduit must
permitted length for Type BLX installed according to the rules of be bonded on both ends
cable? 50 feet PEC, OFNR, OFCR, OFN,
OFNG, OFC, and OFCG may 16-62 Should communication
16-39 What types of network- also be installed in plenums grounds be bonded to power
powered broadband cables may system grounds? Yes
be installed in plenum areas? 16-49 What does the term
Type BLP. Type BLX is also photovoltaic mean? Generating
acceptable, provided that it is 16-63 How far must
electricity from light. communication circuits be
installed according to the
requirements of PEC separated from power circuits?
16-50 What is a photovoltaic At least 2 inches
cell? A special type of
16-40 What are the maximum semiconductor that generates a
and minimum sizes of Type ITC 16-64 In what part of the PEC
small volt- age when exposed to would you find requirements for
cable conductors? A minimum of light, generally about one half
No. 22 AWG and a maximum of fire alarm systems and circuits?
volt.
No. 12 AWG are permitted for
Instrumentation Tray Cables 16-65 What is a closed-loop
16-51 What type of electricity do system? A special type of power
photovoltaic cells generate? distribution that is controlled
16-41 Why are optical fiber Direct current only. jointly by signals from the
cables preferable to copper controlling equipment and the
conductors for communications? utilization equipment.
Because they can carry many 16-52 What is an array? An
assembly of photovoltaic panels
times as many signals, with far
less degradation of the signals. 16-66 What types of
16-53 Why are blocking diodes disconnects are required in data
One pair of optical fiber cables
can carry thousands of required for photovoltaic processing areas? They require
systems? a disconnect for all electronic
telephone conversations with
better clarity and requiring far To prevent battery currents from equipment in these areas. In
flowing backward through the addition, there must be another
fewer amplifiers along its path.
photovoltaic cells when no disconnect for all HVAC
sunlight is present. equipment in these areas. These
16-42 What are the three basic can be combined into one unit
parts of optical fiber cables? The
core, the cladding, and the outer 16-54 Do photovoltaic systems
require special disconnects? 16-67 Are ventilated underfloor
covering.
Yes. A disconnecting means areas in computer rooms
must be installed that will exempted from the special air-
16-43 What are the two most handling area requirements
disconnect photovoltaic
important things to remember PEC? Yes
when installing optical fiber conductors from all other system
conductors
cables? First, that the pulling
force should not be applied to 16-69 Conductors from a
16-55 Can any recognized type television antenna to a building
the optical fiber, but to a
“strength member.” Second, that of wiring be used for photovoltaic must be kept how far from a
systems? Yes 120/240 electrical service? 2 feet
optical fiber cables cannot be
sharply bent.
16-56 Must a 12-volt 16-70 How far apart must
photovoltaic system be supports for antenna cables be
16-44 What is the most difficult
operation of connecting optical grounded? No placed? No specific distance is
mentioned in the Code, just that
fiber cables? Terminating or
splicing them. This can be a they must be made secure
16-71 What size conductor is
required to connect a
communications grounding
electrode and a power grounding
electrode? At least No. 6 AWG
copper

16-72 Which article of the Code


covers cable television systems?
Article 820 covers all such
systems that are wired in coaxial
cable, as almost all cable TV
systems are..

16-74 How far must coaxial


cables be kept from the
conductors of lighting systems?
6 feet

16-75 What size conductor is


required to connect a television
sys- tem grounding electrode
and a power grounding
electrode? At least No. 6 AWG
copper

16-76 Which conductor of a


coaxial cable can be grounded?
When the cable is to be
grounded, it is the outer
conductor that is connected to
ground

16-77 What types of coaxial


cables may be run as risers in a
building? Types CATVP. Types
CATVR, MPP, CMP, MPR, and
CMR may be used if installed
according to PEC

16-80 What is the minimum size


of conductor that can be used to
interconnect storage batteries?
No. 2/0 AWG copper

16-81 What do the letters OFCP


represent for type OFCP cable?
Optical Fiber Conductive
Plenum.

You might also like