LIVE LOAD ANALYSIS Considering Beam A1 – B2

*For Live Load

WLL = 4.8 kPa

Considering Beam A1 – B1
2
4.8 kN /m (6 m)
W’ =
3
W’ = 9.6 kN/m

Considering Beam A2 – A3

4.8 kN /m2 (4.5 m)


W’ = ¿
6
W’ = 8.78 kN/m

Considering Beam A1 – A2 W’ =
2
4.8 kN /m (6 m)
¿
6
W’ = 9.6 kN/m

4.8 kN /m2 (4.5 m)


W’ =
3
W’ = 7.2 kN/m
*For Beam

- Beam Dimension: 250 mm x 300 mm

*Beam Cases (Live Loads)

BM1 = 8.78 kN/m

BM2 = 7.2 kN/m

BM3 = 2 (7.2) kN/m

BM3 = 14.4 kN/m

BM4 = 8.78 kN/m + 9.6 kN/m

BM4 = 18.38 kN/m

BM5 = 9.6 kN/m

BM6 = 2(9.6 kN/m)

BM6 = 19.2 kN/m

BM7 = 19.2 kN/m

*Factored Loads (consider only 25% of live load


as per section 12.7.2 of ASCE 7-16

BM1 = 1.6(8.78) (25%) =3.512 kN/m

BM2 = 1.6(7.2) (25%) = 2.88kN/m

BM3 = 1.6(14.4) (25%) = 5.76 kN/m

BM4 = 1.6(18.38) (25%) = 7.352 kN/m

BM5 = 1.6(9.6) (25%) = 3.84 kN/m

BM6 = 1.6(19.2) (25%) = 7.68 kN/m

BM7 = 1.6(19.2) (25%) = 7.68 kN/m