Input:
Characteristic Strength of Concrete fc = 40 N/mm2
Characteristic Strength HYSD Bars fy = 414 N/mm2
Width of Raft (W) = 1.75 m
Length of Raft (L) = 2.6 m
Depth of Raft (D) = 0.6 m
Width of Pedestal (Wp) = 0.43 m
Length of Pedestal (Lp) = 0.46 m
Height of Pedestal (H) = 0.33 m
Number of pedestal = 4 Nos.
DN1200:
Diameter of Pipe = 1200 mm
Density of Water = 10 KN/m3
Area of Pipe = 1.131 m2
Thickness of pipe = 12 mm .. Confirmed by Piping department, thickness of pipe is
Perimeter of Pipe = 3769.91 mm between 10 to 12 mm
Spacing of support = 5.7 m
Lateral Load in Longitudinal & Transverse directions has been conservatively considered as 30% of vertical
load
Longitudinal shear & = 25.41 KN
Transverse shear
DN600:
Diameter of Pipe = 600 mm
Density of Water = 10 KN/m3
Area of Pipe = 0.283 m2
Thickness of pipe = 10 mm .. Confirmed by Piping department, thickness of pipe is
Perimeter of Pipe = 1884.96 mm between 8 to 10 mm
Spacing of support = 5.7 m
Lateral Load in Longitudinal & Transverse directions has been conservatively considered as 30% of vertical
load
Longitudinal shear & = 7.37 KN .. each support
Transverse shear
Forces at base of Raft,
Selfweight of Raft = 68.25 KN
Weight of Pedestal = 6.53 KN
Vertical load of 600 Dia pipe = 24.55 KN
Vertical load of 900 Dia pipe = 84.71 KN
Self weight of Steel structure = 3 KN
Total vaertical load = 187.04 KN
Design of raft:
Max base presssure = 82.18 KN/m2
Cantilever projection = 0.333 m
Moment = 4.56 KNm
Factored moment = 7.29 KNm
Strength Reduction Factor for Flexure = 0.9
Flexural Resistance Factor = Ru = Mu / Φbd2 = 0.03
Area of Steel required = 40 mm2
Minimum area of reinforcement = 1080 mm2
b) vc = asd + 2 - sqrt(fc')
bo 12 40 for interior columns
30 for edge columns
= 3.88 Mpa 20 for corner columns
c) vc = 1 sqrt(fc')
3
= 2.108 Mpa
Pn = Pu/0.65 69.08 KN
C) Compute g = 0.567
rg << 0.01
The cl. 10.8.4 of ACI 318 states that for a compression member with cross section larger than the
required by consideration of loading ,it shall be permitted to base the minimum reinf and strength on
reduced area equal to one half of the total area .
Referring to SP-17(97) of ACI, Columns 7.8 percentage of steel is less than 0.01.
rg << 0.01
However cl. 10.8.4 of ACI 318M states that reduced effective area shall not be less than one-half the total area.
= 121.2 KN
Min. area of shear reinforcement shall be provided where Vu exceeds fVc/2. (ACI 318, cl. 11.5.5)
fVc/2 = 60.61 > 40.66 No need of shear reinforcement
Input:
Characteristic Strength of Concrete fc = 40 N/mm2
Characteristic Strength HYSD Bars fy = 414 N/mm2
Width of Raft (W) = 1.18 m
Length of Raft (L) = 2.2 m
Depth of Raft (D) = 0.4 m
Width of Pedestal (Wp) = 1.18 m
Length of Pedestal (Lp) = 1.12 m
Height of Pedestal (H) = 0.627 m
Number of pedestal = 1 Nos.
Depth of foundation = 1 m
DN1000:
Diameter of Pipe = 1000 mm
Density of Water = 10 KN/m3
Area of Pipe = 0.785 m2
Thickness of pipe = 12 mm .. Confirmed by Piping department, thickness of pipe is
Perimeter of Pipe = 3141.59 mm between 10 to 12 mm
Spacing of support = 5.7 m
Lateral Load in Longitudinal has been considered as 30% of vertical load & Transverse directions has been
considered as 10% of vertical load
Longitudinal shear = 18.49 KN
Transverse shear 6.16 KN
Forces at base of Raft,
Selfweight of Raft = 25.96 KN
Weight of Pedestal = 20.72 KN
Vertical load of pipe = 61.64 KN
Soil weight = 13.76 KN
Total vaertical load = 122.08 KN
Design of raft:
Max base presssure = 100.00 KN/m2
Cantilever projection = 0.55 m
Moment = 15.13 KNm
Factored moment = 24.20 KNm
Strength Reduction Factor for Flexure = 0.9
Flexural Resistance Factor = Ru = Mu / Φbd2 = 0.22
Area of Steel required = 187 mm2
Minimum area of reinforcement = 0.0018A = 720 mm2
b) vc = asd + 2 - sqrt(fc')
bo 12 40 for interior columns
30 for edge columns
= 2.19 Mpa 20 for corner columns
c) vc = 1 sqrt(fc')
3
= 2.108 Mpa
Pn = Pu/0.65 151.72 KN
C) Compute g = 0.842
rg << 0.01
The cl. 10.8.4 of ACI 318 states that for a compression member with cross section larger than the
required by consideration of loading ,it shall be permitted to base the minimum reinf and strength on
reduced area equal to one half of the total area .
Referring to SP-17(97) of ACI, Columns 7.8 percentage of steel is less than 0.01.
rg << 0.01
However cl. 10.8.4 of ACI 318M states that reduced effective area shall not be less than one-half the total area.
= 961.4 KN
Min. area of shear reinforcement shall be provided where Vu exceeds fVc/2. (ACI 318, cl. 11.5.5)
fVc/2 = 480.68 > 29.59 No need of shear reinforcement
Input:
Characteristic Strength of Concrete fc = 40 N/mm2
Characteristic Strength HYSD Bars fy = 414 N/mm2
Width of Base slab (W) = 3.51 m
Thickness of Base slab (D) = 0.25 m Actual thickness is equal to or more
than the considered
Though it is sliding support, Lateral Load in Longitudinal & Transverse directions has been conservatively
considered as 30% of vertical load
b) vc = asd + 2 - sqrt(fc')
bo 12 40 for interior columns
30 for edge columns
= 1.83 Mpa 20 for corner columns
c) vc = 1 sqrt(fc')
3
= 2.108 Mpa
Pn = Pu/0.65 76.20 KN
C) Compute g = 0.662
rg << 0.01
The cl. 10.8.4 of ACI 318 states that for a compression member with cross section larger than the
required by consideration of loading ,it shall be permitted to base the minimum reinf and strength on
reduced area equal to one half of the total area .
Referring to SP-17(97) of ACI, Columns 7.8 percentage of steel is less than 0.01.
rg << 0.01
However cl. 10.8.4 of ACI 318M states that reduced effective area shall not be less than one-half the total area.
= 482.6 KN
Min. area of shear reinforcement shall be provided where Vu exceeds fVc/2. (ACI 318, cl. 11.5.5)
fVc/2 = 241.28 > 21.01 No need of shear reinforcement