PURLINS ID ( F I-I )

Span = 6.00 m
Spacing = 1.70 m
α = 10.00
Use 1 Tie Rod Φ12
1)- APPLIED FORCES :-
DEAD LOAD
C.sheets = 8.00 Kg/m2
WDL = 25.00 Kg/m\
WXDL = 0.0250 t/m\ WYDL = 0.0044 t/m\
MXDL = 0.1200 m.t MYDL = 0.0050 m.t
QXDL = 0.0800 t

LIVE LOAD
a)Uniform load
Roof is inaccessible
L.L. = 50.00 Kg/m2
WLL = 85.00 Kg/m\
WXLL = 0.0840 t/m\ WYLL = 0.0150 t/m\
MXLL = 0.3800 m.t MYLL = 0.0170 m.t
QXLL = 0.2600 t
b)100 Kg concentrated load
PX = 99.00 Kg PY = 18.00 Kg
MXLL = 0.1500 m.t MYLL = 0.0140 m.t
QXLL = 0.0500 t
MAX LIVE LOAD :-
MXLL = 0.3800 m.t MYLL = 0.0170 m.t
QXLL = 0.2600 t

WIND LOAD
Ce = -0.60
K = 1.00
q = 70.00 Kg/m2
WXWL = -0.4049 t/m\
MXWL = -1.8222 m.t Neglect wind load
QXWL = 0.00 t
ECG Project Name
Job Ref.
Engineering Consultants Group CHECKING AND PACKING HALL

Bldg. 2, Block 10, El Sefarat District Calc. By Date Checked By Date Rev.

P.O.Box No. 1167, Cairo 11511, Egypt. M.Nour Sheet No.


ECG Project Name
Job Ref.
Engineering Consultants Group CHECKING AND PACKING HALL

Bldg. 2, Block 10, El Sefarat District Calc. By Date Checked By Date Rev.

P.O.Box No. 1167, Cairo 11511, Egypt. M.Nour Sheet No.

FINAL DESIGN LOADS :-


MX = 0.5000 m.t Case a
MY = 0.0250 m.t
QX = 0.4000 t

2)- CHOICE OF SECTION :


Z 250X70X20X2 Single
h = 250 mm b = 70 mm Wt. = 6.38 kg/m
d = 20 mm t = 2 mm r = 8.00 mm
Sx = 57.88 cm 3
Sy = 10.08 cm 3

A = 8.13 cm 2
ey = 0.00 cm
rx = 9.43 cm ry = 2.92 cm

3)- CODE LIMITS FOR SLENDER SECTIONS. ECP P183-189 :


For Web h/t = 115.00 <200 OK
For Falange b/t = 25.00 <60 OK
For Lip d/t = 5.00 <40 OK

4)- CALCULATION OF EFFECTIVE PARTS :


FOR WEB
Web is Stiff subjected to Moment
Kσ = 23.90
ψ = -1
λp = 0.8282
ρ = 1.0616 >1
The hole web is fully effective
FOR LIP
Lip is Unstiff. Subjected to Moment.
Kσ = 0.43
ψ = 1
λp = 0.27
ρ = 0.95
The Lip is not fully effective
FOR FLANGE
Flange is Partially stiff subjected to Comp.
Kσ = 2.83
ψ = 1
λp = 0.5232
ECG Project Name
Job Ref.
Engineering Consultants Group CHECKING AND PACKING HALL

Bldg. 2, Block 10, El Sefarat District Calc. By Date Checked By Date Rev.

P.O.Box No. 1167, Cairo 11511, Egypt. M.Nour Sheet No.


ρ = 1.1807
ECG Project Name
Job Ref.
Engineering Consultants Group CHECKING AND PACKING HALL

Bldg. 2, Block 10, El Sefarat District Calc. By Date Checked By Date Rev.

P.O.Box No. 1167, Cairo 11511, Egypt. M.Nour Sheet No.

The hole Flange is fully effective


Sx = 57.70 cm3 Sy = 9.80 cm3
A = 8.11 cm2 rx = 9.43 cm
ry = 2.91 cm

5)- CHECK LATERAL TORSIONAL BUCKLING :


Luact = 0.00 cm Cb = 1.13
20bf/(Fy)^0.5 = 90.37 cm
Lumax Lumax = 0.36 m
1380Af.Cb/d.Fy = 36.386 cm
Luact < Lumax
FLTB1 = 1.392 t/cm2
FLTB2 = 1.392 t/cm2 There is no LTB
FLTB = 1.392 t/cm 2

fbc = 1.12 t/cm2 Safe

6)- CHECK SHEAR STRESS :


qall = 0.84 t/cm2
qw = 0.08 t/cm2 < qall Safe

7)- CHECK DEFLECTION :-


δL.L = 0.94 cm < span/300 Safe