Siemens LMS Diagnostic codes

Albatros- Albatros-Txt Diag- Diag-Txt LpbPrio Safety STV


Code Code
10 Outside sensor fault
610 Outside sensor fault (B9) (room model, plant frost protection, sensor 6
20 Boiler temperature 1 sensor fault value not plausible)
552 Electronic SLT flow sensor fault (B2) 9 X
249 Electronic SLT flow sensor fault (B2) 9 X X
591 Electronic SLT flow sensor fault (B2) 9
439 Short-circuit boiler flow sensor (B2) 6 X X
440 Open-circuit boiler flow sensor (B2) 6 X X
737 Electronic SLT flow sensor fault (B2) 6 X X
25 Boiler temperature solid fuel sensor fault
611 Boiler temperature solid fuel sensor fault (B22) 6
26 Common flow temperature sensor fault
612 Common flow temperature sensor fault (B10) (sensor missing, double 6
28 Flue gas temperature sensor fault configured, configured on slave, …)
539 Short-circuit flue gas sensor 9 X
540 Open-circuit flue gas sensor 9 X
543 Short-circuit flue gas sensor 6 X X
544 Open-circuit flue gas sensor 6 X X
30 Flow temperature 1 sensor fault
614 Flow temperature 1 sensor fault (B1) 6
31 Flow temperature 1 cooling sensor fault
615 Flow temperature 1 cooling sensor fault (B16) 6
32 Flow temperature 2 sensor fault
616 Flow temperature 2 sensor fault (B12) 6
38 Flow temperature primary controller sensor fault
51 Flow temperature primary controller sensor fault (B15) 6
40 Return temperature 1 sensor fault
553 Return temperature sensor fault (B7) 9 X
250 Return temperature sensor fault (B7) 9 X X
441 Short-circuit boiler return sensor (B7) 6 X X
442 Open-circuit boiler return sensor (B7) 6 X X
738 Return temperature sensor fault (B7) 6 X X
52 Return temperature sensor fault (B7) 6
46 Cascade return temperature sensor fault
53 Cascade return temperature sensor fault (B70) 6
47 Common return temperature sensor fault

1 of 20 09/12/2023
Siemens LMS Diagnostic codes

54 Common return temperature sensor fault (B73) 6


50 DHW temperature sensor/thermostat 1 fault
55 DHW temperature sensor/thermostat 1 fault (B3) 6
52 DHW temperature sensor/thermostat 2 fault
56 DHW temperature sensor/thermostat 2 fault (B31) 6
54 Flow temp dhw sensor fault
57 Flow temp dhw sensor fault (B35) 6
57 DHW circulating sensor fault
58 DHW circulating sensor fault (B39) 6
60 Room temperature 1 sensor fault
59 Room temperature 1 sensor fault 6
65 Room temperature 2 sensor fault
60 Room temperature 2 sensor fault 6
68 Room temperature 3 sensor fault
61 Room temperature 3 sensor fault 6
70 Storage tank temperature 1 (top) sensor fault
62 Storage tank temperature 1 (top) sensor fault (B4) 6
71 Storage tank temp 2 (bottom) sensor fault
63 Storage tank temp 2 (bottom) sensor fault (B41) 6
72 Storage tank temp 3 (middle) sensor fault
64 Storage tank temp 3 (middle) sensor fault (B42) 6
73 Collector temperature 1 sensor fault
65 Collector temperature 1 sensor fault (B6) 6
74 Collector temperature 2 sensor fault
66 Collector temperature 2 sensor fault (B61) 6
78 Water pressure sensor fault
789 Water refill, senor fault secondary side 9 X
793 Water refill, senor fault secondary side 9 X
506 water pressure sensor fault (short- or open-circuit) 9 X
758 water pressure sensor fault (short- or open-circuit) 9 X
786 Water refill, senor fault secondary side 6
797 Water refill, senor fault secondary side 6
291 water pressure sensor fault (short- or open-circuit) 6 X X
560 water pressure sensor fault (short- or open-circuit) 6 X X
81 LPB short-circuit or no bus power supply
67 LPB short-circuit or no bus power supply 6
82 LPB address collision
103 LPB address collision 3

2 of 20 09/12/2023
Siemens LMS Diagnostic codes

83 BSB-Wire short-circuit or no communication


595 BSB-Wire short-circuit or no communication 8
84 BSB-Wire address collision
104 BSB-Wire address collision 3
85 BSB radio communication fault
604 BSB radio communication fault 8
91 Data loss in EEPROM
618 Data loss EEPROM 9 X
98 Mixing valve clipin 1 fault
605 Mixing valve clipin 1 fault 8
99 Mixing valve clipin 2 fault
606 Mixing valve clipin 2 fault 8
100 Two clock time masters
105 Two clock time masters 3
102 Clock time master without power reserve
106 Clock time master without power reserve 3
105 Maintenance message
87 Maintenance message 5
109 Supervision Boiler temp
592 Boiler alarm 9
287 Pump supervision after flame, flatnesstest 1 failed 6 X X
503 Flatnesstest1 with flow sensor after flame on fails; pump-circulation is 6 X X
504 active
Flatnesstest1 with return sensor after flame on fails; pump-circulation 6 X X
110 SLT lock-out is active
431 repetition SLT-temperature exceeded 9 X
432 SLT-temperature exceeded 9 X
433 SLT-temperature exceeded 9 X
434 SLT-temperature exceeded 9 X
435 SLT-temperature exceeded 9 X
436 Electronic SLT has cut out (residual heat) 9 X
437 Repetion error 426 exceed parameter value of GrenzeGradient 9 X
438 Repetition error 433 exceed parameter value GrenzeDeltaT 9 X
756 SLT-temperature exceeded 9 X
306 SLT-temperature exceeded 9 X
431 repetition SLT-temperature exceeded 9 X
432 SLT-temperature exceeded 9 X
433 SLT-temperature exceeded 9 X
434 SLT-temperature exceeded 9 X

3 of 20 09/12/2023
Siemens LMS Diagnostic codes

435 SLT-temperature exceeded 9 X


436 Electronic SLT has cut out (residual heat) 9 X
437 Repetion error 426 exceed parameter value of GrenzeGradient 9 X
438 Repetition error 433 exceed parameter value GrenzeDeltaT 9 X
412 open TL/SLT causes lockout 9 X
754 open TL/SLT causes lockout 9 X
305 open TL/SLT causes lockout 9 X
412 open TL/SLT causes lockout 9 X
421 Boiler return temperature is higher than/equal to (boiler temperature + 6 X X
820 Sd_RL_groesser_VL
Boiler return temperature- 2K)is higher than/equal to (boiler temperature + 6 X X
420 Sd_RL_groesser_VL
Boiler return temperature- 2K)is higher than (boiler temperature + 6 X X
819 Sd_RL_groesser_VL)
Boiler return temperature is higher than (boiler temperature + 6 X X
429 Sd_RL_groesser_VL)
reset criteria (Delta-T less than 1/2 dTkTrSTB) after error 433 not 6 X X
818 reached
reset criteria (Delta-T less than 1/2 dTkTrSTB) after error 433 not 6 X X
428 reached
dT is higher than design differential dTkTrSTB + 16K 6 X X
817 dT is higher than design differential dTkTrSTB + 16K 6 X X
427 reset critieria (boiler temperature less than boiler temperature set point 6 X X
816 and Delta-T
reset critierialess thantemperature
(boiler dTkTrSTB) less
for error
than 426 nottemperature
boiler reached set point 6 X X
426 and Delta-T
Boiler less than
temperature dTkTrSTB)
rises forallowed
faster than error 426 not reached
in TempGradMax 6 X X
815 Boiler temperature rises faster than allowed in TempGradMax 6 X X
430 Boiler flow temperature > TempKessMaxSTBSec 6 X X
814 Boiler flow temperature > TempKessMaxSTBSec 6 X X
419 Boiler flow temperature > TempKessMaxSTBSec 6 X X
813 Boiler flow temperature > TempKessMaxSTBSec 6 X X
425 Boiler return temperature > TempRuecMaxSTBSec 6 X X
812 Boiler return temperature > TempRuecMaxSTBSec 6 X X
424 Boiler return temperature not plausible (< 0° C) 6 X X
811 Boiler return temperature not plausible (< 0° C) 6 X X
423 Boiler flow temperature not plausible (> 124 °C) 6 X X
810 Boiler flow temperature not plausible (> 124 °C) 6 X X
422 Boiler flow temperature not plausible (< 0° C) 6 X X
809 Boiler flow temperature not plausible (< 0° C) 6 X X
550 open TL/SLT causes start prevention 6 X X
551 open TL/SLT causes start prevention 6 X X
111 Temp limiter safety shut-down
264 Temp limiter safety shut-down 8
117 Water pressure too high
309 Water pressure on input H1 too high (lock-out) 9 X

4 of 20 09/12/2023
Siemens LMS Diagnostic codes

565 static pressure supervision (lock-out) 9 X


68 Water pressure on input H1 too high (start prevention) 6
566 static pressure supervision (start prevention) 6
118 Water pressure too low
310 Water pressure on input H1 too low (lock-out) 9 X
565 static pressure supervision (lock-out) 9 X
69 Water pressure on input H1 too low 6
566 static pressure supervision (start prevention) 6
119 Water pressure switch has cut out
295 pressure switch (lock-out) 9 X
563 pressure switch (lock-out) 9 X
294 pressure switch (start prevention) 6 X X
564 pressure switch (start prevention) 6 X X
121 Flow temp HC1 not reached
70 Flow temp HC1 not reached 6
122 Flow temp HC2 not reached
71 Flow temp HC2 not reached 6
125 Maximum boiler temperature exceeded
501 no temperature modification after flame on flow sensor 9 X
502 no temperature modification after flame on return sensor 9 X
740 Dynamic boiler temperature supervision (lock-out) 9 X
286 supervision temperature is exceeded for the 2nd time after finish of 9 X
500 tolerance time
supervision temperature is exceeded for the 2nd time after finish of 9 X
501 tolerance time modification after flame on flow sensor
no temperature 9 X
126 DHW charging temperature not reached
72 DHW charging temperature not reached 6
127 DHW legionella temperature not reached
73 DHW legionella temperature not reached 6
128 Loss of flame in operation
244 Repetition error counter exceeded 9 X
625 Repetition error counter exceeded 9 X
253 Loss of flame in operation 6 X X
394 Loss of flame in operation 6 X X
394 Loss of flame in operation 6 X X
834 Loss of flame in operation 6 X X
394 Loss of flame in operation 6 X X
835 Loss of flame in operation 6 X X
129 Wrong air supply

5 of 20 09/12/2023
Siemens LMS Diagnostic codes

130 Flue gas temperature max. limit exceeded


132 Gas pressure switch safety shut-down
262 Start prevention due to open gas pressure switch during safety time 6 X X
411 Start prevention due to open gas pressure switch during safety time 6 X X
261 Gas pressure switch is open 6 X X
409 Gas pressure switch is open 6 X X
410 Gas pressure switch is open 6 X X
133 Safety time for establishment of flame exceeded
625 Repetition error counter exceeded 9 X
757 Repetition error counter exceeded 9 X
245 Repetition error counter exceeded 9 X
625 Repetition error counter exceeded 9 X
395 Safety time for establishment of flame exceeded 6 X X
755 Safety time for establishment of flame exceeded 6 X X
254 Safety time for establishment of flame exceeded 6 X X
395 Safety time for establishment of flame exceeded 6 X X
146 Sensor/actuator configuration error
107 Configuration partial diagram 3
269 Wrong function for PWM pump 3
583 Partial diagram return controller and bypass pump are not allowed at 3
151 BMU fault internal the same time
330 error at closing ignition relay 9 X
331 error at opening ignition relay 9 X
332 error at closing gas valve relay 1 9 X
333 error at opening gas valve relay 1 9 X
336 error at closing the safety relay 9 X
337 error at opening the safety relay 9 X
152 Parameterization error
780 Plausiblity of burner control parameters violated 9 X X
781 Partial load is higher than ignition load 9 X X
782 Ignition load is higher than full load 9 X X
851 Operation Blockage is active 9 X X
180 Parameterization error 9 X
342 d. Parameter "VO_Modu_auf_VD" (Zeilee ???) oder 9 X
343 "VO_Modu_ab_VD" (Zeile ???) müssen
VO_Modu_auf or VO_Modu_ab >= 0,2 s sein.
is parameterized as 0 9 X
344 Software error µc1 9 X
179 Parameterization error 9 X X
345 Fault due to change of type of gas 9 X X

6 of 20 09/12/2023
Siemens LMS Diagnostic codes

346 d. Plausibilitätsverletzung: Solldrahzahl Volllast Max (SI) 9 X X


347 [3842.1]/[3843.1] <= Maximale
d. Plausibilitätsverletzung: Gebläsedrehzahl
Solldrehzahl (FA)(FA)
Volllast Max 96169530 <= 9 X X
348 Solldrehzahl Volllast Max (SI) [3842.1]/[3843.1]
d. Plausibilitätsverletzung: Solldrehzahl Teillast Min (SI) 9 X X
349 [3840.1]/[3841.1] => Solldrehzahl
d. Plausibilitätsverletzung: Stillstand
Solldrehzahl MaxMin
Teillast (FA) 9551
(FA) 9524/9525 => 9 X X
350 Solldrehzahl Teillast Min (SI) [3840.1]/[3841.1]
Condition N_TL (50) <= N_TL_Ex (590) violated 9 X X
351 Condition N_VL (46) > N_VL_Ex (591) violated 9 X X
352 Condition N_TL_Ex < N_VL_Ex violated 9 X X
353 d. Verletzung der Bedingung: [N_TL < N_TL_Exotengas]; 9 X X
354 [N_TL_Exotengas
Condition Ion_Ex_UG_TL < N_VO_Drift]
(592) <oder [N_TL_Exotengas
Ion_Ex_OG_TL <
(593) violated 9 X X
355 N_VO_Drift_Fls]
Condition Ion_Ex_UG_VL (594) < Ion_Ex_OG_VL (595) violated 9 X X
356 interpolation points of the control curve are not sorted accorting to fan 9 X X
518 speed (in ascending
Parameter B0_Start ororder)
B3_Start out of admissible range. Non 9 X X
519 conformingB0_Stop
Parameter conditionorBx_Minimum
B3_Stop out<= of Bx_Start
admissible<=range.
Bx_Maximum.
Non 9 X X
831 conforming
d. Parameter consition
MaximaleBx_Minimum <= Bx_Stop
Rücklauftemperatur für < Bx_Start
Drifttest <= als bei
höher 9 X X
832 Bx_Maximum.
STB
d. Funktion.Maximale Differenz Vorlauf-/Rücklauftemperatur für
Parameter 9 X X
850 Drifttest
fan speed istor
höher
time als bei STBfor
parameter Funktion.
ADA are not sorted correctly 9 X X
839 Parameterization error 9 X X
840 parameter error: flame threshold too small 9 X X
569 function not present in LMS 3
570 function not present in LMS 3
571 HX: Temperature limiter HK 3
573 HX: air pressur switch 3
574 HX: load signal 0..10V 3
575 H6 has double function (sec und nicht sec) 3
576 H7 has double function (sec und nicht sec) 3
577 B4 has double function (sec und nicht sec) 3
578 QX: bypass pump Q12 3
579 QX: cooling request K28 3
580 QX: water filling K34 3
581 EM: return flow controller 3
767 EM: double function 3
153 Unit manually locked
622 Reset button pressed too long 9 X
235 Unit manually locked 9 X
848 parameter setting finished. Reset to apply all changes 9 X
849 parameter setting finished. Reset to apply all changes 9 X
160 Fan speed threshold not reached
377 Fan speed threshold not reached: home run 9 X

7 of 20 09/12/2023
Siemens LMS Diagnostic codes

378 Fan speed threshold not reached: stand by 9 X


379 Fan speed threshold not reached: ignition 9 X
380 Fan speed threshold not reached: pre ventilation 9 X
381 Fan speed threshold not reached post ventilation 9 X
749 Fan speed threshold not reached 9 X
233 Fan speed threshold not reached 9 X
377 Fan speed threshold not reached: home run 9 X
378 Fan speed threshold not reached: stand by 9 X
379 Fan speed threshold not reached: ignition 9 X
380 Fan speed threshold not reached: pre ventilation 9 X
381 Fan speed threshold not reached post ventilation 9 X
162 APS does not close
397 Air pressure switch does not close 9 X
398 Air pressure switch does not close: pre ventilation 9 X
399 Air pressure switch does not close: ignition 9 X
752 Air pressure switch does not close 9 X
256 Air pressure switch does not close: pre ventilation 9 X
397 Air pressure switch does not close 9 X
398 Air pressure switch does not close: pre ventilation 9 X
399 Air pressure switch does not close: ignition 9 X
96 LP mode 5 and LP is open 6 X X
404 LP mode 5 and LP is open 6 X X
164 Flow/pressure switch HC fault
293 Flow/pressure switch HC fault 9 X
561 Flow/pressure switch HC fault (lock-out) 9 X
292 Flow/pressure switch HC fault 6 X X
562 Flow/pressure switch HC fault (start prevention) 6 X X
166 Air pressure switch does not open
396 Air pressure switch does not open 9 X
753 Air pressure switch does not open 9 X
255 Air pressure switch does not open: home run 9 X
396 Air pressure switch does not open 9 X
170 Water pressure primary
790 Water refill, senor fault primary side (lock-out) 9 X
794 Water refill, senor fault primary side (lock-out) 9 X
785 Water refill, senor fault primary side 6
798 Water refill, senor fault primary side 6
171 Alarm contact 1 active

8 of 20 09/12/2023
Siemens LMS Diagnostic codes

74 d. Alarmkontakt H1 6
800 d. Alarmkontakt H1 6
192 d. Alarmkontakt H4 6
805 d. Alarmkontakt H4 6
172 Alarm contact 2 active
189 d. Alarmkontakt H2 EM1 6
801 d. Alarmkontakt H2 EM1 6
190 d. Alarmkontakt H2 EM2 6
802 d. Alarmkontakt H2 EM2 6
191 d. Alarmkontakt H2 EM3 6
803 d. Alarmkontakt H2 EM3 6
193 d. Alarmkontakt H5 6
806 d. Alarmkontakt H5 6
173 Alarm contact 3 active
76 d. Alarmkontakt H6 6
194 d. Alarmkontakt H6 6
807 d. Alarmkontakt H6 6
174 Alarm contact 4 active
77 d. Alarmkontakt H3 6
804 d. Alarmkontakt H3 6
195 d. Alarmkontakt H7 6
808 d. Alarmkontakt H7 6
176 Water pressure 2 too high
312 Water pressure on input H2 (EM1) too high (lock-out) 9 X
565 static pressure supervision (lock-out) 9 X
512 Water pressure on input H2 (EM2) too high (lock-out) 9 X
565 static pressure supervision (lock-out) 9 X
514 Water pressure on input H2 (EM3) too high (lock-out) 9 X
565 static pressure supervision (lock-out) 9 X
196 Water pressure on input H2 (EM1) too high 6
198 Water pressure on input H2 (EM2) too high 6
200 Water pressure on input H2 (EM3) too high 6
177 Water pressure 2 too low
511 Water pressure on input H2 (EM1) too low 9 X
565 static pressure supervision (lock-out) 9 X
513 Water pressure on input H2 (EM2) too low 9 X
565 static pressure supervision (lock-out) 9 X
515 Water pressure on input H2 (EM3) too low 9 X
565 static pressure supervision (lock-out) 9 X
197 Water pressure on input H2 (EM1) too low 6

9 of 20 09/12/2023
Siemens LMS Diagnostic codes

199 Water pressure on input H2 (EM2) too low 6


201 Water pressure on input H2 (EM3) too low 6
178 Limit thermostat HC1
108 Limit thermostat HC1 3
771 Limit thermostat HC 3
772 Limit thermostat HC 3
179 Limit thermostat HC2
109 Limit thermostat HC2 3
771 Limit thermostat HC 3
772 Limit thermostat HC 3
183 Unit in parameterization mode
301 Unit in parameterization mode (lock-out) 9 X
770 Unit in parameterization mode (parameter stick) 9 X
176 Start prevention due to adjustment of fuel parameters in Sitherm Pro 6 X X

340 Start prevention after change of type of gas 6 X X


341 Start prevention for setting the ignition and supervision range 6 X X
303 Unit in parameterization mode (start prevention) 6 X X
193 Start prevention
845 Start prevention 6 X X
846 Contact start prevention is active 6 X X
195 Water refill time
787 Maximum refil time per charging exceeded (lock-out) 9 X
791 Maximum refil time per charging exceeded (lock-out) 9 X
783 Maximum refil time per charging exceeded 6
795 Maximum refil time per charging exceeded 6
196 Water refill time/week
788 Maximum refil time per week exceeded (lock-out) 9 X
792 Maximum refil time per week exceeded (lock-out) 9 X
784 Maximum refil time per week exceeded 6
796 Maximum refil time per week exceeded 6
217 Sensor fault
765 Short-circuit of ionisation electrode 6 X X
766 Short-circuit of ionisation electrode 6 X X
241 Flow temperature sensor for yield measurement fault
80 Flow temperature sensor for yield measurement fault 6
242 Return temperature sensor for yield measurement fault

81 Return temperature sensor for yield measurement fault 6


243 Swimming pool sensor fault

10 of 20 09/12/2023
Siemens LMS Diagnostic codes

82 Swimming pool sensor fault (B13) 6


260 Flow sensor 3
320 d. Vorlauftemperatur 3 Fühlerfehler 3
270 Exc temp diff h' exch
507 Temperature difference between DryFire sensor and flow temperature 9 X
sensor after flatnesstest exceeded (lock-out)
744 Temperature difference between DryFire sensor and flow temperature 9 X
sensor after flatnesstest exceeded (lock-out)
317 Grid frequency OOR
275 Mains frequency outside specification 6 X X
461 Mains frequency outside specification 6 X X
320 DHW charging temp sensor fault
83 DHW charging temp sensor fault 6
321 DHW outlet sensor fault
84 DHW outlet sensor fault 6
322 Water pressure 3 too high
516 Water pressure on input H3 too high (lock-out) 9 X
565 static pressure supervision (lock-out) 9 X
85 Water pressure on input H3 too high 6
323 Water pressure 3 too low
517 Water pressure on input H3 too low (lock-out) 9 X
565 static pressure supervision (lock-out) 9 X
86 Water pressure on input H3 too low 6
324 Same sensor Input BX
110 Same sensor Input BX 3
325 Same sensor Input BX/extension module
111 Same sensor Input BX/extension module 3
326 Same sensor Input BX/mixing valve group
112 Same sensor Input BX/mixing valve group 3
327 Same function mixing valve group
113 Same function extension module 3
328 Same function mixing valve group
114 Same function mixing valve group 3
329 Same funct ext module/mixing valve group
115 Same funct ext module/mixing valve group 3
330 Sensor input BX1 no function
116 Sensor input BX1 no function 3
331 Sensor input BX2 no function
117 Sensor input BX2 no function 3
332 Sensor input BX3 no function

11 of 20 09/12/2023
Siemens LMS Diagnostic codes

118 Sensor input BX3 no function 3


333 Sensor input BX4 no function
119 Sensor input BX4 no function 3
335 Sensor input BX21 no function
211 Sensor input BX21 no function Extension module 1 3
213 Sensor input BX21 no function Extension module 2 3
215 Sensor input BX21 no function Extension module 3 3
336 Sensor input BX22 no function
212 Sensor input BX22 no function Extension module 1 3
214 Sensor input BX22 no function Extension module 2 3
216 Sensor input BX22 no function Extension module 3 3
337 Sensor input B1 no function
123 Sensor input B1 no function 3
338 Sensor input B12 no function
124 Sensor input B12 no function 3
339 Collector pump Q5 missing
125 Collector pump Q5 missing 3
340 Collector pump Q16 missing
126 Collector pump Q16 missing 3
341 Collector sensor B6 missing
127 Collector sensor B6 missing 3
342 Solar charging DHW sensor B31 missing
128 Solar charging DHW sensor B31 missing 3
343 Solar integration missing
129 Solar integration missing 3
344 Solar actuator buffer K8 missing
130 Solar actuator buffer K8 missing 3
345 Solar actuator swimming pool K18 missing
131 Solar actuator swimming pool K18 missing 3
346 Solid fuel boiler pump Q10 missing
132 Solid fuel boiler pump Q10 missing 3
347 Solid fuel boiler comparative sensor missing
133 Solid fuel boiler comparative sensor missing 3
348 Solid fuel boiler address error
134 Solid fuel boiler address error 3
349 Buffer return temp valve Y15 missing
135 Buffer return temp valve Y15 missing 3
350 Buffer address error
136 Buffer address error (example not device adresse 1) 3
351 Precontr/primary pump address error

12 of 20 09/12/2023
Siemens LMS Diagnostic codes

137 Precontr/primary pump address error (example not device adresse 1) 3

352 Hydraulic balancing address error


138 Hydraulic balancing address error (example not device adresse 1) 3
353 Cascade flow sensor B10 missing
139 Cascade flow sensor B10 missing 3
371 Flow temp HC3
188 Flow temperature HC3 6
372 Limit thermostat HC3
210 Limit thermostat heat circuit 3 3
771 Limit thermostat HC 3
772 Limit thermostat HC 3
373 Extension module 3
607 Extension module 3 8
374 Sitherm Pro calculation
274 Repetition error counter for r-value exceeded 9 X
625 Repetition error counter exceeded 9 X
223 SithermPro calulation r-value exceeds defined borders 6 X X
359 control value is out of admissible range 6 X X
360 calculated target of nominal steps is higher than parameter limit. Bad 6 X X
gas or gas pressure too low
361 calculated target of nominal steps is lower than parameter limit. Gas 6 X X
pressure too high ?
362 present stepper motor position is higher than parameter limit. Bad gas 6 X X
or gas pressure too low
363 present stepper motor position is lower than parameter limit. Gas 6 X X
pressure too high ?
364 present ionisation current out of the setted range 6 X X
365 present R_value out of setted range 6 X X
375 BV stepper motor
228 d. Verriegelungsfehler des Brennstoffventil-Schrittmotors 9 X
366 open circuit of the connection to the stepper motor or open circuit 9 X
within stepper motor
367 Checkback circuit of CombOptimiz stepper motor faulty 9 X
230 d. Fehler des Brennstoffventil-Schrittmotors 9 X X
368 Supply voltage for CombOptimiz stepper motor too low 9 X X
369 Supply voltage for CombOptimiz stepper motor too high 9 X X
370 d. Startverhinderung bei einem Schrittmotorunterbruch 9 X X
376 Drift test limit value
231 d. SithermPro Fehler bei Ausführung des Drifttests 9 X

13 of 20 09/12/2023
Siemens LMS Diagnostic codes

371 Control difference has exceeded parameterized upper limit [DPA645] 9 X

372 Control difference has dropped below parameterized lower limit (646) 9 X

373 d. Elektrodendrifttest führte 4 mal in Folge zur Startverhinderung. 9 X


Problem: Gebl-Drehzahl (Versorgungsspg.) oder Ionisationsstrom
nicht im Band
221 verification of fand speed range in Sitherm Pro failed 6 X X
357 d. Gebläsedrehzahl nicht im definiertem Band des Exemplarabgleich; 6 X X
schwankende Versorgungsspannung oder falsche Leistungsvorgaben
in Teil- oder Volllast.
358 d. Ionisationsstrom oder Gebläsedrehzahl beim Elektrodendrifttest 6 X X
nicht im definierten Bereich. Problem: Versorgungsspannung, Gebl-
PWM-Vorgabe
768 d. Regelwert Grenzverletzung während dem Drifttest. Drifttest 6 X X
IonSollwert wurde nicht erreicht.
769 d. Ionisationsstrom Absturz während Drifttest. Evtl. Mitkopplung oder 6 X X
Drifttest IonSollwert zu groß.
821 d. Wert bei Überprüfung während des Drifttests außerhalb des 3 X X
erlaubten Bereichs
822 d. Minimale Stromdifferenz während dem Drifttest hat den Grenzwert 3 X X
unterschritten
823 d. Maximale Stromdifferenz während dem Drifttest hat den Grenzwert 3 X X
überschritten
824 d. Schwelle für Schrittdifferenz in der Einschwingphase des Drifttests 3 X X
verletzt.
825 d. Maximum des Ionisationstroms nicht am Ende des Drifttest. Strom 3 X X
muss in den letzten 5 Sekunden des Tests das Maximum erreichen.

827 d. Drehzahl wurde während dem Drifttest nicht erreicht oder konnte 3 X X
nicht gehalten werden.
836 d. Rücklauftemperatur oder Temperaturdifferenz zu hoch 3 X X
377 Drift test prevented
266 d. Sitherm Pro Drifttest wird intern verhindert 9 X
418 Drift test counter monitor has exceeded parameterized limit(657) 9 X
378 Repetition internal
382 Repetition speed
384 Extraneous light
391 Extraneous light (lock-out) 9 X
392 Extraneous light (lock-out) 9 X

14 of 20 09/12/2023
Siemens LMS Diagnostic codes

748 Extraneous light (lock-out) 9 X


251 Extraneous light (lock-out) 9 X
391 Extraneous light (lock-out) 9 X
392 Extraneous light (lock-out) 9 X
252 Extraneous light (start prevention) 6 X X
393 Extraneous light (start prevention) 6 X X
385 Mains undervoltage
554 Mains undervoltage 9 X X
555 Mains undervoltage 9 X X
386 Fan speed tolerance
374 Fan speed tolerance exceeded: ignition 9 X
375 Fan speed tolerance exceeded: partial load 9 X
750 Fan speed tolerance exceeded 9 X
232 Fan speed tolerance exceeded 9 X
374 Fan speed tolerance exceeded: ignition 9 X
375 Fan speed tolerance exceeded: partial load 9 X
234 Fan speed tolerance exceeded: home run 6 X X
382 Fan speed tolerance exceeded: post purge 6 X X
383 Fan speed tolerance exceeded: ignition 6 X X
384 Fan speed tolerance exceeded: ignition 6 X X
385 Fan speed tolerance exceeded: full load 6 X X
386 Fan speed tolerance exceeded: partial load 6 X X
387 Fan speed tolerance exceeded: home run 6 X X
388 Fan speed tolerance exceeded: stand-by 6 X X
389 Fan speed tolerance exceeded: pre purge 6 X X
390 Fan speed tolerance exceeded: post purge 6 X X
531 Fan speed tolerance exceeded: pre purge 6 X X
532 Fan speed tolerance exceeded: post purge 6 X X
534 Fan speed tolerance exceeded: post purge 6 X X
387 Air pressure tolerance
416 air pressure switch not closed: ignition 9 X
417 air pressure switch not closed: pre purge 9 X
751 air pressure switch not closed 9 X
265 air pressure switch not closed 9 X
416 air pressure switch not closed: ignition 9 X
417 air pressure switch not closed: pre purge 9 X
258 air pressure switch open 6 X X
401 air pressure switch open: post purge 6 X X
402 air pressure switch open: pre purge 6 X X
403 air pressure switch open: ignition 6 X X

15 of 20 09/12/2023
Siemens LMS Diagnostic codes

257 air pressure switch closed 6 X X


400 air pressure switch closed: home run 6 X X
388 DHW sensor no function
830 configuration error sensor input B3/B38 3
391 Room controller 1
392 Room controller 2
393 Room controller 3
426 Check flue gas damper
527 malfunction of flue gas damper 9 X
528 malfunction of flue gas damper 9 X
427 Config flue gas damper
525 Parameterization flue gas damper 3
429 Dyn water pres too high
559 Dynamic water pressure too high (lock-out) 9 X
759 Dynamic water pressure too high (lock-out) 9 X
288 Dynamic water pressure too high (start prevention) 6 X X
558 Dynamic water pressure too high (start prevention) 6 X X
430 Dyn water pres too low
763 Dynamic water pressure too low (lock-out) 9 X
764 Dynamic water pressure too low (lock-out) 9 X
289 Dynamic water pressure too low (start prevention) 6 X X
557 Dynamic water pressure too low (start prevention) 6 X X
431 Primary exch sensor
547 Short-circuit primary heatexchanger sensor B26 (lock-out) 9 X
548 Open-circuit primary heatexchanger sensor B26 (lock-out) 9 X
742 primary heat exchanger sensor fault (lock-out) 9 X
520 primary heat exchanger sensor fault 6
545 Short-circuit primary heatexchanger sensor B26 (start prevention) 6 X X
546 Open-circuit primary heatexchanger sensor B26 (start prevention) 6 X X
743 primary heat exchanger sensor fault (start prevention) 6 X X
432 Function ground missing
745 missing earth connection causes relay feedback error 9 X
746 missing earth connection causes safety relay feedback error 9 X
747 missing earth connection causes gas valve relay feedback error 9 X
433 Heat exch temp
307 temperature primary heat exchaner too high 9 X
508 overheat protection limiter function active (lock-out). The temperature 9 X
is or was higher than TaAbschalt OR measured temperature not
plausible
308 temperature primary heat exchaner too high 6 X X

16 of 20 09/12/2023
Siemens LMS Diagnostic codes

509 overheat protection limiter function active (start prevention). The 6 X X


temperature is or was higher than TaAbschalt OR measured
temperature not plausible

17 of 20 09/12/2023
LMS Diagnostic CoPreliminary, subject to change

Remark: If other codes appear which are not listed here ==> very specific in
listed here ==> very specific internal error, please contact Siemens
Albatro Albatros-Txt Diag- Diag-Txt LpbPrio Safety STV STOER Auto FA
s-Code 305
Code open TL/SLT causes lockout 9 X X Del LOCK
306 SLT-temperature exceeded 9 X X LOCK
412 open TL/SLT causes lockout, lockout input 9 X X LOCK_REMOTE_UNLOCKABLE
419 Boiler flow temperature > TempKessMaxSTBSec 6 X X OUTOP
420 Boiler return temperature is higher than (boiler temperature + Sd_RL_groesser_VL) 6 X X OUTOP
421 Boiler return temperature is higher than/equal to (boiler temperature + Sd_RL_groesser_VL - 2K) 6 X X OUTOP
422 Boiler flow temperature not plausible (< 0° C) 6 X X OUTOP
423 Boiler flow temperature not plausible (> 124 °C) 6 X X OUTOP
424 Boiler return temperature not plausible (< 0° C) 6 X X OUTOP
425 Boiler return temperature > TempRuecMaxSTBSec 6 X X OUTOP
426 Boiler temperature rises faster than allowed in TempGradMax 6 X X OUTOP
427 reset critieria (boiler temperature less than boiler temperature set point and Delta-T less than dTkTrSTB) for error 426 not reached 6 X X OUTOP
428 dT is higher than design differential dTkTrSTB + 16K 6 X X OUTOP
429 reset criteria (Delta-T less than 1/2 dTkTrSTB) after error 433 not reached 6 X X OUTOP
430 Boiler flow temperature > TempKessMaxSTBSec 6 X X OUTOP
431 repetition SLT-temperature exceeded 9 X X LOCK_REMOTE_UNLOCKABLE
432 SLT-temperature exceeded 9 X X LOCK_REMOTE_UNLOCKABLE
433 SLT-temperature exceeded 9 X X LOCK_REMOTE_UNLOCKABLE
434 SLT-temperature exceeded 9 X X LOCK_REMOTE_UNLOCKABLE
435 SLT-temperature exceeded 9 X X LOCK_REMOTE_UNLOCKABLE
436 Electronic SLT has cut out (residual heat) 9 X X LOCK_REMOTE_UNLOCKABLE
437 Repetion error 426 exceed parameter value of GrenzeGradient 9 X X LOCK_REMOTE_UNLOCKABLE
438 Repetition error 433 exceed parameter value GrenzeDeltaT 9 X X LOCK_REMOTE_UNLOCKABLE
550 open TL/SLT causes start prevention 6 X X OUTOP
551 open TL/SLT causes start prevention 6 X X OUTOP
754 open TL/SLT causes lockout 9 X X LOCK_REMOTE_UNLOCKABLE
756 SLT-temperature exceeded 9 X X LOCK_REMOTE_UNLOCKABLE
809 Boiler flow temperature not plausible (< 0° C) 6 X X OUTOP
810 Boiler flow temperature not plausible (> 124 °C) 6 X X OUTOP
811 Boiler return temperature not plausible (< 0° C) 6 X X OUTOP
812 Boiler return temperature > TempRuecMaxSTBSec 6 X X OUTOP
813 Boiler flow temperature > TempKessMaxSTBSec 6 X X OUTOP
814 Boiler flow temperature > TempKessMaxSTBSec 6 X X OUTOP
815 Boiler temperature rises faster than allowed in TempGradMax 6 X X OUTOP
816 reset critieria (boiler temperature less than boiler temperature set point and Delta-T less than dTkTrSTB) for error 426 not reached 6 X X OUTOP
817 dT is higher than design differential dTkTrSTB + 16K 6 X X OUTOP
818 reset criteria (Delta-T less than 1/2 dTkTrSTB) after error 433 not reached 6 X X OUTOP
819 Boiler return temperature is higher than (boiler temperature + Sd_RL_groesser_VL) 6 X X OUTOP
820 Boiler return temperature is higher than/equal to (boiler temperature + Sd_RL_groesser_VL - 2K) 6 X X OUTOP

110 SLT lock-out