With reference to the above-mentioned letter the Meter Testing/Sealing Committee visited the 220kV G/S
NTDC Chishtian for Testing/Sealing of Primary & Backup Energy Meters and addressing MDI reading
issue of Primary Energy meters.
CT Ratio
PT Ratio
Sr. Accuracy
Running
Remarks
Sr. No.
Meter
Make
N=10
N=20
N=30
Class
Load
Type
No.
Name of Circuit
ISKRA
T-1 MT860S 1200/
1. Primary Energy Meter 48MW 0.2s 1600/1 0.156% 0.144% 0.179% Satisfactory
Sr. No. 1
Meter Constant=100,000imp/kWh
66 213 635
ISKRA
T-2 MT860S 1200/
2. Primary Energy Meter 48MW 0.2s 1600/1 0.169% 0.188% 0.171% Satisfactory
Sr. No. 1
Meter Constant=100,000imp/kWh
66 213 689
ISKRA
T-4 MT860S 1200/
3. Primary Energy Meter 48MW 0.2s 1200/1 0.054% 0.046% 0.056% Satisfactory
Sr. No. 1
Meter Constant=100,000imp/kWh
70 702 575
ISKRA
Auxiliary Transformer MT860S 100/
4. Primary Energy Meter 57KW 0.2s 40/1 0.181% 0.178% 0.187% Satisfactory
Sr. No. 1
Meter Constant=100,000imp/kWh
66 362 491
Elster
T-1 A1800 1200/
5. Backup Energy Meter 48MW 0.2s 1600/1 0.192% 0.182% 0.186% Satisfactory
Sr. No. 1
Meter Constant=10,000imp/kWh
02817003
Elster
T-2 A1800 1200/
6. Backup Energy Meter 48MW 0.2s 1600/1 -0.101% -0.104% -0.106% Satisfactory
Sr. No. 1
Meter Constant=10,000imp/kWh
02817000
HEXING
T-4 HXT300 1200/
7. Backup Energy Meter 48MW 0.2s 1600/1 0.164% 0.189% 0.171% Satisfactory
Sr. No. 1
Meter Constant=10,000 imp/kWh
20127297
4. Measurement period for MDI recording changed from 15 min to 30 min for T-1, T-2, and T-4 primary
energy meters. The revised MDI values and complete DRO is attached as Annex – I to this report.
5. Auxiliary Backup Energy Meters (Sr. No 08) is non-compliant energy meter as per MC 4.2 and accuracy
is not satisfactory as well. The concerned quarter may be approached for replacement of energy meter
Page 1 of 2
[
6. Metering circuit and metering panels were resealed using security slips bearing serial nos. as follows:
a. Primary Energy Metering Security Slips: BL184761-68 (08 Nos.)
b. Backup Energy Metering Security Slips: BL184755-60 (06 Nos.)
c. T-1 CVT Security Slips: BL184731-34 & 0695833 (Old)
d. T-1 CT Security Slips: BL184735-38
e. T-2 CVT Security Slips: BL184739-40, 0695843 & 45 (Old)
f. T-2 CT Security Slips: BL184741-44
g. T-4 CVT Security Slips: BL184745, 51-55.
h. T-4 CT Security Slips: BL184746-50
Page 2 of 2
Annex - I DRO of Energy Meters before and after changing MDI Measurement Period