Project : 132/11kV WADI ABA SALEEL-1 S/S DOC. NO.

DATE

Contractor : L & T Qatar


End User : KAHRAMAA DESIGNED CHECKED APPROVED
Title : Roof UDY MIM VRP

113
Project: 132/11kV WADI ABA SALEEL-1 S/S DATE - 20.12.22
PART: Main Building Lower Roof PREPARED BY- SHB
TITLE : Design of Pedestal CHECKED BY- MIM
JOB NO. GTC/735A/2015

Design of Pedestal :
Data:
Compressive Strength of concrete fck = 28 N/mm2
2
Yield Stress of reinforcement fyk = 500 N/mm
2
fctm = 2.77 N/mm
Length of Pedestal = 6.927 m
Width of Pedestal = 0.35 m
Height of pedestal = 0.6 m
Weight of Equipment = 20 kN
Weight of pedestal = 36.37 kN

Design Calculations:
Total Compression Load = 20+36.37 kN
56.4 kN
Maximum Stress developed on the section = (56.37*1000) N/mm2
( Load /Area) (6.927*1000*0.35*1000))
0.02 N/mm2
0.02 N/mm2<11.2 N/mm2 HENCE SAFE

Stresse is within acceptable limit, so no rebar is required from structural point of view.

Effective depth of pedestal = 534 mm

Minimum percentage of steel = 0.26*fctm/fyk*b*d > 0.13% bd


= 769.1736 mm2

Provided steel 12 @125 = 904 mm2 HENCE SAFE

114
Project: 132/11kV WADI ABA SALEEL-1 S/S DATE - 20.12.22
PART: Main Building Lower Roof PREPARED BY- SHB
TITLE : Design of Water Tank Pedestal CHECKED BY- MIM
JOB NO. GTC/735A/2015

Design of Pedestal :
Data:
Compressive Strength of concrete fck = 28 N/mm2
2
Yield Stress of reinforcement fyk = 500 N/mm
2
fctm = 2.77 N/mm
Length of Pedestal = 2.53 m
Width of Pedestal = 1.52 m
Height of pedestal = 0.6 m
Weight of Equipment = 20 kN
Weight of pedestal = 57.68 kN

Design Calculations:
Total Compression Load = 20+57.68 kN
77.7 kN
Maximum Stress developed on the section = (77.68*1000) N/mm2
( Load /Area) (2.53*1000*1.52*1000))
0.02 N/mm2
0.02 N/mm2<11.2 N/mm2 HENCE SAFE

Stresse is within acceptable limit, so no rebar is required from structural point of view.

Effective depth of pedestal = 534 mm

Minimum percentage of steel = 0.26*fctm/fyk*b*d > 0.13% bd


= 769.1736 mm2

Provided steel 12 @125 = 904 mm2 HENCE SAFE

115
Project: 132/11kV WADI ABA SALEEL-1 S/S DATE - 20.12.22
PART: Main Building Lower Roof PREPARED BY- SHB
TITLE : Design of Pedestal CHECKED BY- MIM
JOB NO. GTC/735A/2015

Design of Pedestal :
Data:
Compressive Strength of concrete fck = 28 N/mm2
2
Yield Stress of reinforcement fyk = 500 N/mm
2
fctm = 2.77 N/mm
Length of Pedestal = 1.9 m
Width of Pedestal = 1.45 m
Height of pedestal = 0.6 m
Weight of Equipment = 20 kN
Weight of pedestal = 41.33 kN

Design Calculations:
Total Compression Load = 20+41.33 kN
61.3 kN
Maximum Stress developed on the section = (61.33*1000) N/mm2
( Load /Area) (1.9*1000*1.45*1000))
0.02 N/mm2
0.02 N/mm2<11.2 N/mm2 HENCE SAFE

Stresse is within acceptable limit, so no rebar is required from structural point of view.

Effective depth of pedestal = 534 mm

Minimum percentage of steel = 0.26*fctm/fyk*b*d > 0.13% bd


= 769.1736 mm2

Provided steel 12 @125 = 904 mm2 HENCE SAFE

116