Water Tank
INPUT DATA
ROOF THICK. WALL THICK. FLOOR THICK. Fcu Fy TANK LENGTH TANK WIDTH TANK HEIGHT COVER AREA
0.3 0.3 0.4 350 4200 12 12 3 112.36
To avoid floating of under ground tanks due to Up Lift, factor of safety against Up Lift
factor of safety against Up Lift must be taken into consideration
L1 = 12.3 m1 = 0.76
L2 = 12.3 m2 = 0.76
α1 0.5
r1 = 1 β1 0.5
Wα1 1.181057692
W floor = 2.36211538 Wβ1 1.181057692
FOR THE WALL IN THE SHORT DIR.
L= 12.3 m1 = 0.76
H= 3 m2 = 0.87
3.5816091954
0.27920410783
α2 0.993959735
r2= 3.5816092 VERTICAL β2 0.006040265
Wα2 2.981879204
W tri. = 3 Wβ2 0.018120796
W HL = 0.0135906 T/M2
JOINT b
MEMBER b-a b-b'
DIST. FACTORS 0.72179961 0.27820039
F.E.M -1.7892437 14.8901849
B.M -9.4562542 -3.644687
FINAL MOMENTS -11.245498 11.2454979
Ma = 0 Na-b = 4.64
Mb = 11.2454979 Nb-a = 11.90350481
Mc = 7.44509243 Nb-c = 2.981879204
FOR THE WALL IN THE LONG DIR.
L= 12.3 m1 = 0.76
H= 3 m2 = 0.87
3.5816091954
0.27920410783
α3 0.993959735
r2= 3.5816092 VERTICAL β3 0.006040265
Wα3 2.981879204
W tri. = 3 Wβ3 0.018120796
W HL = 0.0135906 T/M2
FIXED END MOMENT
JOINT b
MEMBER b-a b-b'
DIST. FACTORS 0.72179961 0.27820039
F.E.M -1.789476 14.8901849
B.M -9.4560865 -3.6446223
FINAL MOMENTS-11.245563 11.2455625
Ma = 0 Na-b = 4.64
Mb = 11.2455625 Nb-a = 11.90350481
Mc = 7.44509243 Nb-c = 2.981879204
FOR THE HORIZONTAL STRIP AT H/4
Pu (t) = 17.8552572
Mu (m.t) = 16.8682468
Pu (t) = 4.47281881
Mu (m.t) = 11.1676386
Pu (t) = 17.8552572
Mu (m.t) = 16.8683438
Pu (t) = 0.12537325
Mu (m.t) = 0.25701517
Pu (t) = 0.12537325
Mu (m.t) = 0.12850759
R = 0 NEGLECT PU AS (cm2) = 0.1058355
ASmin (cm2) = 4.5
USE Ø16 @17cm
Pu (t) = 0.12537325
Mu (m.t) = 0.12850759