You are on page 1of 3

LOAD ESTIMATION - 88th HOTEL ELLA

Nominal Current Actual current Total current


Floor Equipment Wattage Quantity Diversity
(A) (A) (A)
LED light (12W) 12 93 0.065217391304 0.3 0.0195652174 1.8195652174
Ceiling fan 75 6 0.407608695652 0.5 0.2038043478 1.222826087
Hair dryer 1200 6 6.521739130435 0.2 1.3043478261 7.8260869565
3 Floor
Kettle 750 6 4.076086956522 0.2 0.8152173913 4.8913043478
TV 60 6 0.326086956522 1 0.3260869565 1.9565217391
AC 570.4 3 3.1 1 3.1 9.3

LED light (12W) 12 93 0.065217391304 0.3 0.0195652174 1.8195652174


Ceiling fan 75 6 0.407608695652 0.5 0.2038043478 1.222826087
Hair dryer 1200 6 6.521739130435 0.2 1.3043478261 7.8260869565
2 Floor
Kettle 750 6 4.076086956522 0.2 0.8152173913 4.8913043478
TV 60 6 0.326086956522 1 0.3260869565 1.9565217391
AC 570.4 3 3.1 1 3.1 9.3

LED light (12W) 12 103 0.065217391304 0.3 0.0195652174 2.0152173913


Ceiling fan 75 6 0.407608695652 0.5 0.2038043478 1.222826087
Hair dryer 1200 6 6.521739130435 0.2 1.3043478261 7.8260869565
1 Floor
Kettle 750 6 4.076086956522 0.2 0.8152173913 4.8913043478
TV 60 6 0.326086956522 1 0.3260869565 1.9565217391
AC 570.4 3 3.1 1 3.1 9.3

Fridge 120 1 0.652173913043 0.5 0.3260869565 0.3260869565


Rice cooker 1 6.4 0.4 6.55
Cooler 240 1 1.304347826087 0.5 0.652173913 0.652173913
Micro wave 240 1 1.304347826087 0.53 0.6913043478 0.6913043478
Blender 600 1 3.260869565217 0.5 1.6304347826 1.6304347826
Kitchen & Heater 1500 1 8.152173913043 0.5 4.0760869565 4.0760869565
Ground
Floor Bread toaster 1350 1 7.336956521739 0.5 3.6684782609 3.6684782609
Freezer 3000 1 16.304347826087 1 16.304347826 16.304347826
System air 240 1 1.304347826087 0.5 0.652173913 0.652173913
Dryer 1350 1 7.336956521739 0.4 2.9347826087 2.9347826087
Washine 2200 1 11.95652173913 0.4 4.7826086957 4.7826086957
Machine

LED light 1 26 20 0.141304347826 0.8 0.1130434783 2.2608695652


LED light 2 36 0 0.195652173913 0.8 0.1565217391 0
Extension Socket outlets
184 10 1 0.4 0.4 4
, BDB1 (13A)
Socket outlets
1288 2 7 0.4 2.8 5.6
(13A) dedicated

LED light 1 26 17 0.141304347826 0.8 0.1130434783 1.9217391304


LED light 2 36 0 0.195652173913 0.8 0.1565217391 0
Socket outlets
BDB2 184 8 1 0.4 0.4 3.2
(13A)
Socket outlets
1288 2 7 0.4 2.8 5.6
(13A) dedicated

1
Nominal Current Actual current Total current
Floor Equipment Wattage Quantity Diversity
(A) (A) (A)

LED light 1 26 20 0.141304347826 0.8 0.1130434783 2.2608695652


LED light 2 36 0 0.195652173913 0.8 0.1565217391 0
GDB1 Socket outlets
184 3 1 0.4 0.4 1.2
(Garden) (13A)
Socket outlets
1288 0 7 0.4 2.8 0
(13A) dedicated

LED light 1 26 17 0.141304347826 0.8 0.1130434783 1.9217391304


LED light 2 36 5 0.195652173913 0.8 0.1565217391 0.7826086957
Socket outlets
RDB1 184 10 1 0.4 0.4 4
(13A)
Socket outlets
1288 0 7 0.4 2.8 0
(13A) dedicated

LED light 1 26 66 0.141304347826 0.8 0.1130434783 7.4608695652


LED light 2 36 0 0.195652173913 0.8 0.1565217391 0
Socket outlets
184 18 1 0.4 0.4 7.2
(13A)
Dinning &
Kitcken Socket outlets 1288 0 7 0.4 2.8 0
(13A) dedicated
Dish Washer 3500 1 19.02173913043 0.4 7.6086956522 7.6086956522
Freezer 1300 0 7.065217391304 1 7.0652173913 0
Cooking hood 2000 1 10.86956521739 0.5 5.4347826087 5.4347826087
TOTAL SINGLE PHASE CURRENT (A) 183.96521739
TOTAL THREE PHASE CURRENT (A) 61.32173913

2
ELECTRICAL LOAD ESTIMATION

UPGRADING OF EXISTING ELECTRICAL DISTRIBUTION SYSTEM

DESCRIPTION

This is a commercial building with 60A, thee phase power supply. Due to expansions upgrading of power
supply will be required. Load estimation for the buildng is as follows.

INSTALLATION ADDRESS

Nominal Actual Total current


Floor Equipment Wattage Quantity Diversity
Current (A) current (A) (A)
LED light (12W) 12 289 0.07 0.80 0.05 15.08
Ceiling fan 75 18 0.41 0.50 0.20 3.67
Hair dryer 1200 18 6.52 0.20 1.30 23.48
Kettle 750 18 4.08 0.20 0.82 14.67
TV 60 18 0.33 1.00 0.33 5.87
AC 570 9 3.10 1.00 3.10 27.90
Fridge 120 1 0.65 0.50 0.33 0.33
Rice cooker 1 6.40 0.40 6.55
Old
240 1 1.30 0.50 0.65 0.65
Building Cooler
Micro wave 240 1 1.30 0.53 0.69 0.69
Blender 600 1 3.26 0.50 1.63 1.63
Heater 1500 1 8.15 0.50 4.08 4.08
Bread toaster 1350 1 7.34 0.50 3.67 3.67
Freezer 3000 1 16.30 1.00 16.30 16.30
System air 240 1 1.30 0.50 0.65 0.65
Dryer 1350 1 7.34 0.40 2.93 2.93
Washine Machine 2200 1 11.96 0.40 4.78 4.78

LED light 1 26 140 0.14 0.80 0.11 15.83


LED light 2 36 25 0.20 0.80 0.16 3.91
Socket outlets (13A) 184 59 1.00 0.50 0.50 29.50
Socket outlets (13A)
1288 22 7.00 0.50 3.50 77.00
Extention dedicated
Dish Washer 3500 1 19.02 0.40 7.61 7.61
Freezer 1300 0 7.07 1.00 7.07 0.00
Cooking hood 2000 1 10.87 0.50 5.43 5.43
Lift 15000 1 81.52 0.50 40.76 40.76
Total single phase Current (A) 312.98 A
Future expansions (15%) 46.95 A
Total three pahse Current (A) 119.98 A
Expected maximum demand in kVA 82.78 kVA

Considering the above calculation 85kVA, 3 phase electricity supply can be recommended to the premises.

Prepared By : Eng. J.G.D. S. De Silva


Consultant Electrical Engineer
M-8383