Calculation:
Let’s first consider Base KVA and KV for HT and LT Side.
Base KVA for HT side (H.T. Breaker and Transformer Primary) is 6 MVA
Base KV for HT side (H.T. Breaker and Transformer Primary) is 6.6 KV
Base KVA for LT side (Transformer Secondary and down Stream) is 2.5 MVA
Base KV for LT side (Transformer Secondary and down Stream) is 415V
(3) Fault Level from Primary Side of Transformer to Secondary side of Transformer:
Transformer Rating is 2.5 MVA and Transformer Impedance is 6%.
% Reactance at Base KVA = (Base KVA x % impedance at Rated KVA) / Rated KVA
% Reactance at Base KVA = (2.5X6)/2.5
% Reactance at Base KVA =6%
U. Reactance of the Transformer(Z Pu) =% Reactance /100
U. Reactance of the Transformer(Z Pu)= 6/100=0.06 Ω—–(8)
Total P.U. impedance up to Transformer Secondary Winding(Z Pu-c)=(Z Pu)+(Z Pu-b)=(7)+(8)
Total P.U. impedance up to Transformer Secondary Winding(Z Pu-c)=0.06+0.02070
Total P.U. impedance up to Transformer Secondary Winding(Z Pu-c)=0.0807 Ω—–(9)
Fault MVA at Transformer Secondary Winding = Base MVA / Z Pu-c
Fault MVA at Transformer Secondary Winding = 2.5/0.0807
Fault MVA at Transformer Secondary Winding =31 MVA
Fault Current = Fault MVA / Base KV
Fault Current = 31 / (1.732×0.415)