You are on page 1of 4

Honeywell

DESIGN DOCUMENTATION
FUNCTIONAL DESCRIPTION

FOR
WEATHER STATION

SIT TEMASEK POLYTECNIC

25th JUNE, 2013

Project: SIT- TEMASEK POLYTECNIC Page 1 of 4


Document: SIT_TP_ WS_ FDS
Date: 25th June-2013
Rev: 0
Honeywell

Revision History

Rev Date Description Prepared By Checked By Approved By


Initial
0 25th-June-2013 Honeywell
Release

Project: SIT- TEMASEK POLYTECNIC Page 2 of 4


Document: SIT_TP_ WS_ FDS
Date: 25th June-2013
Rev: 0
Honeywell

Table of Contents

1. WEATHER STATION........................................................................................4
1.1 SYSTEM DESCRIPTION...................................................................................4
1.2 HARDWARE POINT SUMMARY......................................................................4

Project: SIT- TEMASEK POLYTECNIC Page 3 of 4


Document: SIT_TP_ WS_ FDS
Date: 25th June-2013
Rev: 0
Honeywell

1. WEATHER STATION
1.1 System Description
The monitoring points from the Weather station WXT520 (located on the roof
of the building) are Outside Air Temperature, Barometric pressure, Outside
Air Relative Humidity, Rainfall output, Wind speed and Wind direction.

BACnet Gateway IG04 is a protocol gateway between the WXT520 weather


transmitter and BACnet network. The Gateway communicates directly with
the Weather transmitter using dedicated RS-485 channel.

BACnet/IP

The 10 base T Ethernet port on the Gateway provides access to the BAC/IP
network. The BAC/IP setting must be configured to be compatible with
BACnet system in to which the Weather station is being integrated.

1.2 Hardware Point Summary


Engineering I/O
Tag Name Description Type
Unit Characteristics
WS
Tag Names will prefix with
WS-XX-YY/ EAF-XX-YY
where
XX = 01, 02, 03, .etc represents the Floor Level.
YY = 01, 02, 03… etc represents the Equipment Number.
_OaT Outside Air Temperature AI ºC -52 – 60 oC
_BaroPress Barometric pressure AI hPa 600-1100hpa
_OaRH Outside Air Relative AI % 0-100%
Humidity
_Rainfall Rainfall output AI mm NA
_WindSpd Wind speed AI m/s 0-60m/s
_WindDir Wind direction AI Deg-angular 0-360o

NOTES
1. A plant identifier to make the “Tag Name” plant specific will prefix the
above “Tag Names” directly following the building identifier. The tag
names are as shown in the table.
2. An underscore will then be inserted followed by text that will identify the
point function. The text will be a mix of uppercase and lowercase.
3. For example, the on/off status of the WS- SIT2-01-03 will have the “Tag
Name” of WS-SIT2-01-03 _Sts.

Project: SIT- TEMASEK POLYTECNIC Page 4 of 4


Document: SIT_TP_ WS_ FDS
Date: 25th June-2013
Rev: 0