CHECKLIST OF BMS WORKS ACCOMPLISMENT @ PREMIUM & NATURA BLDG (CP08)

Design Coordinates, Inc.


PROJECT : SOUTHERN STAR FIT
CUSTOMER : ECOZONE PROPERTIES INC.
LOCATION : FIT PAGASPAS, TANAUAN BATANGAS
As of 23 Dec 2022

DDC Set-up, Graphics


Loopchecking & Loop Test / Pre Comm. And
Configuration & Creation & Data
Item # Location / Description Termination Functional Final Testing & Remarks Dependency / By Others
Database Points
Works Testing Commissioning
Creation Association
PREMIUM - B1, ADMIN AND WAREHOUSE
Valve Actuator not working in modulating only
1 AHU-B1-01A Done Done Done Done Open/Close position, No permanent power By others & Electrical
yet, No backbone
Valve Actuator not working in modulating only
2 AHU-B1-01B Done Done Done Done Open/Close position, No permanent power By others & Electrical
yet, No backbone
Valve Actuator not working in modulating only
3 AHU-B1-01C Done Done Done Done Open/Close position, No permanent power By others & Electrical
yet, No backbone
Valve Actuator not working in modulating only
4 AHU-B1-01D Done Done Done Done Open/Close position, No permanent power By others & Electrical
yet, No backbone
Valve Actuator not working in modulating only
5 PAHU-B1-01 Done Done Done Done Open/Close position, No permanent power By others & Electrical
yet, No backbone
6 WLDS-B1-MDF (Admin Bldg)
For integration Thru Bacnet/IP, required
7 By others
BTU METERING (B1 Admin) networking to monitor in BMS workstation
For integration Thru Bacnet/IP, required
8 By others
BTU METERING (B1 AHU Rm) networking to monitor in BMS workstation
For integration Thru Bacnet/IP, required
9 By others
BTU METERING (B1 Dispensary Rm) networking to monitor in BMS workstation
For integration Thru Bacnet/IP, required
10 By others
WATER METERING (B1 Admin) networking to monitor in BMS workstation
For integration Thru Bacnet/IP, required
11 By others
FIRE DETECTION & ALARM SYSTEM networking to monitor in BMS workstation

PREMIUM - B2 SPECIALTY FATS & INGREDIENTS


Valve Actuator not working in modulating only
1 AHU-B2-02A-2F Done Done Done Done Open/Close position, No permanent power By others & Electrical
yet, No backbone
Valve Actuator not working in modulating only
2 AHU-B2-02B-2F Done Done Done Done Open/Close position, No permanent power By others & Electrical
yet, No backbone
Valve Actuator not working in modulating only
3 PAHU-B2-02-2F Done Done Done Done Open/Close position, No permanent power By others & Electrical
yet, No backbone
Valve Actuator not working in modulating only
4 AHU-B2-03A-2F Done Done Done Done Open/Close position, No permanent power By others & Electrical
yet, No backbone
Valve Actuator not working in modulating only
5 AHU-B2-03B-2F Done Done Done Done Open/Close position, No permanent power By others & Electrical
yet, No backbone
Valve Actuator not working in modulating only
6 PAHU-B2-03-2F Done Done Done Done Open/Close position, No permanent power By others & Electrical
yet, No backbone
Valve Actuator not working in modulating only
7 AHU-B2-01A-3F Done Done Done Done Open/Close position, No permanent power By others & Electrical
yet, No backbone
Valve Actuator not working in modulating only
8 AHU-B2-01B-3F Done Done Done Done Open/Close position, No permanent power By others & Electrical
yet, No backbone
Valve Actuator not working in modulating only
9 AHU-B2-01B-3F Done Done Done Done Open/Close position, No permanent power By others & Electrical
yet, No backbone
Valve Actuator not working in modulating only
10 AHU-B2-01C-3F Done Done Done Done Open/Close position, No permanent power By others & Electrical
yet, No backbone
Installed Valve Actuator 220vac, BMS
11 PAHU-B2-01-3F Done Done Done Done requirement is 24vac, No permanent power By others & Electrical
yet, No backbone yet
12 WLDS-B2-MDF RM (AHU Rm)
13 WLDS-B2-Data Center (Admin Bldg) CANCEL
For integration Thru Bacnet/IP, required
14 BTU-1 METERING (B2 AHU Rm, 2F) By others
networking to monitor in BMS workstation
For integration Thru Bacnet/IP, required
15 BTU-2 METERING (B2 AHU Rm, 2F) By others
networking to monitor in BMS workstation
For integration Thru Bacnet/IP, required
16 BTU-3 METERING (B2 AHU Rm, 3F) By others
networking to monitor in BMS workstation
For integration Thru Bacnet/IP, required
17 BTU-4 METERING (B2 AHU Rm, 3F) By others
networking to monitor in BMS workstation
18 BTU-5 METERING (B2 GF) No layout By Comsec Subcon

PREMIUM - B6 (UTILITY BLDG)


1 B6 EXHAUST FAN-1 (TX-1) Done Done Done Done Ready for Final Testing
2 B6 EXHAUST FAN-2 (TX-1) Done Done Done Done Ready for Final Testing
3 B6 EXHAUST FAN-1 (TX-2) Done Done Done Done Ready for Final Testing
4 B6 EXHAUST FAN-2 (TX-2) Done Done Done Done Ready for Final Testing
5 B6 EXHAUST FAN-1 (GENSET) Done Done Done Done Ready for Final Testing
6 B6 EXHAUST FAN-2 (GENSET) Done Done Done Done Ready for Final Testing

Page 1 of 2
7 B6 EXHAUST FAN-3 (GENSET) Done Done Done Done Ready for Final Testing
8 B6 EXHAUST FAN-4 (GENSET) Done Done Done Done Ready for Final Testing
9 B6 EXHAUST FAN-5 (GENSET) Done Done Done Done Ready for Final Testing
10 B6 EXHAUST FAN-6 (GENSET) Done Done Done Done Ready for Final Testing
11 B6 GENSET x 3 Units Done Done Additional Cost Submitted No PO Yet
REMOVE TO BMS AND TRANSFER TO FUEL
12 B6 DAYTANK x 3 Units
OIL PUMP
For integration Thru Bacnet/IP, required
13 BTU-1 METERING (B6 Chiller Area) By others
networking to monitor in BMS workstation
For integration Thru Bacnet/IP, required
14 BTU-2 METERING (B6 Chiller Area) By others
networking to monitor in BMS workstation
B6 DISTRICT COOLING PLANT (CHI'S,
For integration Thru Bacnet/IP, required
15 SCHWP'S, PCHWP'S, COWP'S, CT'S & Done By others
CHILLER PLANT)
networking to monitor in BMS workstation
No workstation yet & Networking required for
16 BMS WORKSTATION @ Control Room Comsec / By others
setup and Integration for 3rd party

NATURA - C1A, ADMIN AND WAREHOUSE


Valve Actuator not working in modulating only
1 AHU-C1-01A Done Done Done Done Open/Close position, No permanent power By others & Electrical
yet, No backbone
Valve Actuator not working in modulating only
2 AHU-C1-01B Done Done Done Done Open/Close position, No permanent power By others & Electrical
yet, No backbone
Valve Actuator not working in modulating only
3 PAHU-C1-01 Done Done Done Done Open/Close position, No permanent power By others & Electrical
yet, No backbone
4 WLDS-C1A-MDF (Admin Bldg)
For integration Thru Bacnet/IP, required
5 BTU METERING (C1A Admin) By others
networking to monitor in BMS workstation
For integration Thru Bacnet/IP, required
6 BTU METERING (C1A AHU Rm) By others
networking to monitor in BMS workstation
For integration Thru Bacnet/IP, required
7 WATER METERING (B1 Admin) By others
networking to monitor in BMS workstation
For integration Thru Bacnet/IP, required
8 FIRE DETECTION & ALARM SYSTEM By others
networking to monitor in BMS workstation
No workstation yet & Networking required for
9 BMS WORKSTATION @ Control Room Comsec / By others
setup and Integration for 3rd party
NATURA - C1B, WAREHOUSE
Valve Actuator not working in modulating only
1 AHU-C1-02A Open/Close position, No permanent power By others & Electrical
yet, No backbone
Valve Actuator not working in modulating only
2 AHU-C1-02B Open/Close position, No permanent power By others & Electrical
yet, No backbone
Valve Actuator not working in modulating only
3 PAHU-C1-02 Open/Close position, No permanent power By others & Electrical
yet, No backbone
For integration Thru Bacnet/IP, required
4 BTU METERING (C1B AHU Rm) By others
networking to monitor in BMS workstation