Professional Documents
Culture Documents
Qualification:
• B.Sc. Electrical Engineering (UET, Lahore)
• M.Sc. Engineering Management (UET, Lahore)
• MBA (Finance), IBA, University of the Punjab
Experience:
• 12 years experience in Protection & Control
• Represented P&C Department in Grid Code revision, Pakistan’s
first ever Kotlakhpat SVC, Lahore-Matiari HVDC
Transmission Line and Stability Control System (SCS) Projects
Outline
• Basics
• Transformer Protection
• Transmission Line Protecion
• Bus Differential Protection
• Breaker Failure Protection
• Shunt Reactor Protection
• Cross-trip Schemes
• Way Forward and Future Trends
3
Basics
What is System Protection?
4
Basics
Purpose of System Protection
5
Basics
What Components (Equipment) Do We Protect?
• Transformers, Reactors
• Transmission Lines
• Buses
• Switchgears
• Capacitor banks
6
Basics
What Components (Equipment) Do We Protect?
Substation
Consumers
Primary
Consumers
Secondary
220kV or 132kV Consumers
7
Basics
Typical Bulk Power System
Generation-typically at 4-20kV
Transmission-typically at 220-765kV
Subtransmission-typically at 66-132kV
9
Basics
Desirable Protection Attributes
~
Generator XFMR Bus Line Bus XFMR Bus Motor
11
Basics
How Overlapping Is Achieved
CTs are located at both sides of CB-fault CTs are located at one side of CB-fault
between CTs is cleared from both remote sides between CTs is sensed by both relays, remote right
side operate only.
12
Basics
C37.2:
Device
Numbers
• Partial listing
13
Basics
One Line Diagram
14
Basics
Fault Types (Shunt)
15
Basics
Series Faults
16
Basics
Study of a Fault
17
Basics
AC & DC Current Components of Fault Current
19
Basics
Info is Required to Apply Protection
Substation
Consumers
Primary
Consumers
Secondary
220kV or 132kV Consumers
22
Transformer Protection
Power transformers are expensive, and are a long lead-
time item (1 year or longer) so protection must be effective
23
Transformer Protection
Construction
24
Transformer Protection
Construction
25
Transformer Protection
• Winding-to-winding faults
• Winding-to-ground faults
• Bushing faults
26
Transformer Protection
Transformer Damage Curve
27
Transformer Protection
28
Transformer Protection
Protection Methods
1. Fuse Protection
2. Overcurrent Protection
3. Differential Protection
4. Restricted Earth Fault Protection
5. Mechanical Protections
29
Transformer Protection
1. Fuse Protection
30
Transformer Protection
2. Overcurrent Protection
Overcurrent Relays
31
Transformer Protection
2. Overcurrent Protection
32
Transformer Protection
2. Overcurrent Protection
Instantaneous OC (IOC) & Definite Time OC
(50, 50N, 50G)
33
Transformer Protection
2. Overcurrent Protection
Time Overcurrent Protection (51, 51N, 51G)
Multiples of pick-up
34
Transformer Protection
2. Overcurrent Protection
Time OC (TOC) Coordination
CTI
Distribution 35
Substation
Transformer Protection
2. Overcurrent Protection
Time OC (TOC) Coordination
36
Transformer Protection
3. Differential Protection
37
Transformer Protection
3. Differential Protection
1 pu
• Note CT polarity dots IP
CT-X CT-Y IP
• This is a through-
IS IS
current representation
• Perfect waveforms, no
saturation Relay
IR-X IR-Y
+1
1 + (-1) = 0
Current, pu
-1
DIFF CURRENT
38
Transformer Protection
3. Differential Protection
2 pu 2 pu
+2
Current, pu 2 + (+2) = 4
-2
39
DIFF CURRENT
Transformer Protection
3. Differential Protection
Through Fault 40
Transformer Protection
3. Differential Protection
Zone of
Protection
41
Transformer Protection
3. Differential Protection
Zone of
Protection
42
Transformer Protection
3. Differential Protection
Some terms relating to differential protection:
• Restraining current
• Inrush
• 2nd Harmonic
43
Transformer Protection
3. Differential Protection
44
Transformer Protection
4. Restricted Earth Fault Protection
45
Transformer Protection
4. Restricted Earth Fault Protection
46
Transformer Protection
4. Restricted Earth Fault Protection
47
Transformer Protection
5. Mechanical Protections
• Pressure Relief Device (PRD)
• Main Buchholz Relay
• Tap Changer Buchholz Relay
• Temperature Gauges
48
Transmission Line Protection
Substation
Consumers
Primary
Consumers
Secondary
220kV or 132kV Consumers
49
Transmission Line Protection
What Can Go Wrong?
Faults
Fault Types:
• Single line-to-ground
• Line-to-line
• Three Phase
• Line-to-line-to-ground
51
Transmission Line Protection
Types of T/Line Protections
52
Transmission Line Protection
Non-Directional Overcurrent Protection
• Non-Directional
• Relay responds to overcurrent condition
• Instantaneous (IOC) device #50
• Time Overcurrent (TOC) device #51
• Various curve types, including inverse, very inverse,
extremely inverse
53
Transmission Line Protection
Non-Directional Overcurrent Protection
54
Transmission Line Protection
Non-Directional Overcurrent Protection
55
Transformer Protection
Non-Directional Overcurrent Protection
E
D
C
56
Transmission Line Protection
Non-Directional Overcurrent Protection
57
Transmission Line Protection
Non-Directional Overcurrent Protection
Non-Directional Relay
Non-Directional Relay
58
Transmission Line Protection
Directional Overcurrent Protection
59
Transmission Line Protection
Directional Overcurrent Protection
60
Transmission Line Protection
Distance Protection
• When a fault occurs on a line, the current rises significantly and the
voltage collapses significantly.
Bi-Quantity Relay;
Directional Relay;
Requires Voltage &
Detects Direction on
Current Input from VT
base of CT Star Point.
& PT respectively
62
Transmission Line Protection
Distance Protection
63
Transmission Line Protection
Distance Protection
64
Transmission Line Protection
Distance Protection
Mho X-tics
65
Transmission Line Protection
Distance Protection
Quad X-tics
66
Transmission Line Protection
Distance Protection
67
Transmission Line Protection
Distance Protection
Impedance = R+jX 68
Transmission Line Protection
X ZL
Distance Protection
T2 XB
XA
T1
21 21
A B
Source
69
Transmission Line Protection
Distance Protection
Load Encroachment
71
Transmission Line Protection
Distance Protection
Power Swing
72
Transmission Line Protection
Distance Protection
75
Transmission Line Protection
Pilot / Tele-protection Schemes
• BLOCKING
76
Transmission Line Protection
Pilot / Tele-protection Schemes
77
Transmission Line Protection
Pilot / Tele-protection Schemes
78
Transmission Line Protection
Pilot / Tele-protection Schemes
Permissive over-reaching transfer trip (POTT)
80
Transmission Line Protection
Pilot / Tele-protection Schemes
81
Transmission Line Protection
Over-voltage Protection
59 59
82
Transmission Line Protection
Auto Recloser & Synchronism Check Relays
Auto Recloser Relays Both Single Phase & Three Auto Recloser are a way to
are used to give an Phase Reclosing can be enhance system stability
Automatic try to CB for done. by restoring the T/Line.
closing following the NTDC adopts Three Phase
tripping. Tripping & Reclosing.
For Closing on Live Line & Live Bus
AR can be Single Shot or Conditions, Synchronism Check is required.
Multi Shot (2,3,…). Δf = 0.1 Hz.
On EHV T/Lines, AR is ΔV = 10%
normally Single Shot. Δθ = 25 – 30o
Closing Command is sent after fulfilling
above criteria.
83
Transmission Line Protection
Line Differential Protection
84
Transmission Line Protection
Line Differential Protection
85
Bus Differential Protection
Bus Differential: Current into Bus must equal current out of Bus
86
Bus Differential Protection
Bus Fault
87
Bus Differential Protection
88
Bus Differential Protection
Double bus,
breaker-and-a- half
89
Breaker Failure Protection
Breaker Failure Protection
500 kV T/Line
Grid Station A Grid Station B
91
Breaker Failure Protection
Breaker Failure Protection
500 kV T/Line
Grid Station A Grid Station B
92
Breaker Failure Protection
Breaker Failure Protection
500 kV T/Line
Grid Station A Grid Station B
93
Breaker Failure Protection
Breaker Failure Protection
500 kV T/Line
Grid Station A Grid Station B
94
Breaker Failure Protection
Breaker Failure Protection
500 kV T/Line
Grid Station A Grid Station B
95
Shunt Reactor Protection
Shunt reactor Protection
Cross Trip Schemes are Normally the below Cross Trip Schemes
used to protect the mentioned Cross Trip ensures healthy operation
NTDC’s EHV system from Schemes have been of EHV System by
tripping on Overload, implemented for 500 kV detecting the Overload /
Under Voltage, Under T/Line: Under Voltage etc. on EHV
Frequency or Over ➢ Overloading Detection by system & tripping the 132
Frequency etc. condition. OC & EF Relays. kV T/Lines or
➢ Under Voltage Detection Transformers.
by Under Voltage Relays. This ensures safe, stable
➢ Under / Over Frequency & reliable operation of
is detected by EHV System.
Under/Over Frequency
Relays respectively.
97
Way Forward
• The Conventional Protection & Control Schemes comprising of
Binary Inputs / Outputs wiring, analog / digital meters & mimic
buses etc. requires high amount of field cabelling & wiring etc.
• The current trend in Substation Control Schemes is to automate
the Substation Control (Substation Automations System) using
the Fiber Optic Communications, Front End Computers & hence
avoids large amount field wiring.
• The Binary Inputs / Outputs have been shifted to fiber optic
communication compliant to IEC 61850 – Worldwide adapted
standard for Communication inside the Substations.
• Front End Computers / Operator Workstation are used to
Monitor & Control the compete substation.
98
Way Forward
Volt Level 1 Volt Level 1 Volt Level 2/3 Volt Level 2/3
IEC LAN PRP1A LAN PRP1B LAN PRP2A LAN PRP2B
61850/62439-3
PRP
Bay Level
Communication Bay 1 Bay 1 Control Bay 1 Bay 1 Control Common
Protection IED IED Protection IED IED Control IEDs
99
SAS Concept Diagram
Way Forward
• In Station Bus based Substations, the Relays / Bay Control Units
are connected to Conventional CTs / PTs for measurement of
Currents & Voltages respectively via Copper Cables.
• The latest technology in SAS is to use Merging Units with
Conventional CTs / PTs. Merging Units communicate the
Current / Voltage Signals to Relays / BCUs over communication
network.
• The Communication network formed between Merging Units &
Relays / BCUs is called as Process Bus. Such Substations are
called as Smart Digital Substations. Hence the complete
substation has been digitalized.
• A sample concept diagram of Smart Digital Substations is as
under;
100
Way Forward
e
Copper
1N 1N
1L 1L
Fiber Optic
Merging 2L 1L
Merging 2L 1L
2N 1N 2N 1N
Unit Unit
101
T1
T1
Way Forward
102
QUESTIONS?