You are on page 1of 1

Reg: 34269B COSMOS Ref: Chk_SGP0/2023/J6779

6. Annex for Boiler internal / external examination


Item description AOF1

All boilers WR | SR | NA

BLR010 Examination of logbook. | |


BLR020 External examination of the boiler, including :
- fitting
- valves | |
- water, steam and fuel systems
- gaugeglass mountings
BLR030 Examination of securing arrangements of boiler feet, rolling and ramming
| |
stays.
BLR040 Verification of remote control of safety devices (valves, mountings).
mou | |
BLR050 Internal examination of the boiler, including :
- combustion chambers (oil fired boilers)
- furnaces
- refractories | |
- tubes
- casing
- bottom and front walls
BLR060 Hydraulic test of boiler (in case of repairs or when internal examination
| |
could not be fully conducted).
BLR070 Thickness measurements of tubes and plates, as deemed necessary. | |
BLR080 Non-destructive tests for detection of possible defects in plating and shells,
| |
pipes and stays, as deemed necessary.
BLR090 Internal examination of accessories and mountings, valves, indicators and
| |
safety valves.
BLR100 Verification of the adjustment of safety valves; Examination and test of
| |
boiler safety valves and relieving gears.
BLR110 Examination of the boiler under working pressure. | |
BLR120 Review of the following records since the last survey : operation,
| |
maintenance, repair history, feedwater chemistry.
Additional items for oil fired boilers WR | SR | NA

BLR130 Visual examination of forced circulation pumps. | |


BLR140 Examination of fuel-supply pipes between pumps and burners, fuel tank
| |
valves, pipes and deck control gear.
BLR150 Examination of burners in operation, verification of burner safety devices. | |
BLR160 Examination of superheater, economizer and air heater. | |

Additional items for thermal oil heaters WR | SR | NA

BLR170 Verification of the analysis of thermal fluid. | |


BLR180 Examination and test of the thermal fluid temperature safety device and
| |
control.
BLR190 Examination and test of the thermal fluid flow meter. | |
BLR200 Examination and test of device for low thermal fluid level in the expansion
| |
tank.
BLR210 Examination and test of other regulation and safety systems. | |
BLR220 Internal examination of the boiler - (every five years), including :
- combustion chambers (oil fired boilers)
- furnaces
- refractories | |
- tubes
- casing
- bottom and front walls
BLR230 Thickness measurements of tubes and plates, as deemed necessary. -
| |
(every five years)
BLR240 Non-destructive tests for detection of possible defects in plating and shells,
| |
pipes and stays, as deemed necessary. - (every five years)
BLR250 For thermal oil heaters heated by exhaust gas, examination and test of the
permanent system for extinguishing and cooling in the event of fire, for | |
instance a pressure water spraying system - (every five years)
BLR260 Visual examination of forced circulation pumps. - (every five years) | |

Bureau Veritas Marine & Offshore


The latest published Rules of Bureau Veritas Marine & Offshore and the General Conditions therein are Page 5/10
applicable

You might also like