ADDENDUM

ADDENDUM NUMBER: 2

DATE OF ISSUE: July 28, 2020

PROJECT: Campground Upgrades Phase 3 at Jarvis Bay Provincial


Park

TENDER NUMBER: 21TDRPCR400

To All Bidders:

This addendum shall be read in conjunction with the above mentioned tender
documents. The corrections in this addendum shall govern.

In lieu of specified copper teck cables, the equivalent aluminum XLPE


insulated cables are acceptable for main feeders (utility to PDC D1), and
branch circuit conductors (PDC D1 to PDC D2, PDC to washrooms and
shelters), providing the above ground exposed wiring to be protected by rigid
metal conduits. Such conduit system shall be hot-dip galvanized and complete
with all fittings suitable for wet location installation.

Additional bonding conductors shall be provided (size per CEC 2018 table 16) if
using un-armoured cables.

Coordinate with the PDC supplier and include proper lugs if using aluminum
cables.