KARNATAKA POWER TRANSMISSION CORPORATION LIMITED.

Estimate for Establishing 2x10MVA , 110/11 KV Substation at Padamandi in Ramadurga Taluk, Belagavi district and
Construction of 110kV SC Line on DC Towers from the existing 110/11 KV Sub Station Aratagal in Soundatti Tq to proposed
110/11 KV Sub Station Padmandi for a distance of 7.146 kms in Ramadurg tq, Belagavi dist along with construction of 110 KV
Terminal Bay at existing 110/33/11 KV Sub Station Aratagal in Soundatti Tq, Belagavi dist.

ABSTRACT

Sl. Amount in
Description
No. Lakhs
Estimate for establishment of 2X10MVA , 110/11 KV Substation at Padamandi in Ramadurga Taluk,
1 1321.68
Belagavi District.
Estimate for Construction of 110kV SC Line on DC Towers from the existing 110/11 KV Sub Station
2 Aratagal in Soundatti Tq to proposed 110/11 KV Sub Station Padmandi for a distance of 7.146 kms in 1038.14
Ramadurg tq, Belagavi dist.

Estimate for Construction of 110 KV Terminal Bay at existing 110/33/11 KV Sub Station Aratagal in
3 327.72
Soundatti Tq, Belagavi dist.

Total 2687.54
Say 2687.54 Lakhs

Assistant Engineer, Ele., Assistant Engineer, Civil.,


M.W. Sub-Division-II, KPTCL., Belagavi M.W. Division, KPTCL., Belagavi

Assistant Executive Engineer, Ele., Assistant Executive Engineer, Civil.,


M.W. Sub-Division-II, KPTCL., Belagavi M.W. Division, KPTCL., Belagavi

Executive Engineer, Ele., Executive Engineer, Ele.,


M.W. Division, KPTCL., Belagavi TL & SS Division, KPTCL, Belagavi.
Superintending Engineer Elec,
Transmission (W&M) Circle, KPTCL, Belagavi.
Report :- This estimate amounting to Rs. 2687.54 Lakhs has been prepared for Establishing 2x10MVA , 110/11 KV Substation at Padamandi in Ramadurga Taluk,
Belagavi district and Construction of 110kV SC Line on DC Towers from the existing 110/11 KV Sub Station Aratagal in Soundatti Tq to proposed 110/11 KV Sub
Station Padmandi for a distance of 7.146 kms in Ramadurg tq, Belagavi dist. The said project is approved in 89th TCCM held on 29.08.2022 and is included in the
APW for the FY 22-23, List – IV, substation works.

It is proposed for Establishing 2x10MVA , 110/11 KV Substation at Padamandi in Ramadurga Taluk, Belagavi district and Construction of 110kV SC Line
on DC Towers from the existing 110/11 KV Sub Station Aratagal in Soundatti Tq to proposed 110/11 KV Sub Station Padmandi for a distance of 7.146 kms in
Ramadurg tq, Belagavi dist.

The layout drawings for the proposed 110kV S/S at Padmandi has been approved by the Chief Engineer Electy, P&C, KPTCL, Bangalore vide letter No.
Letter No. CEE(P&C)/SET/EE-T3/AEE-5/KCO-107/42783/22-23/14742-50 D: 05.112.2022 and earthmat drawing by the Superintending Engineer Electy, R&D Centre,
KPTCL, Bangalore vide letter No.: SEE/R&D/EEE/KCO-116/F-72(10)/2022-23/4256-60 Date: 13.12.2022

The work of conducting detailed survey using modern survey techniques for proposed 110kV SC Line on DC Towers from the existing 110/11 KV Sub
Station Aratagal in Soundatti Tq to proposed 110/11 KV Sub Station Padmandi for a distance of 7.146 kms in Ramadurg tq, Belagavi district has been carried out by
M/s Durga Enterprises and the survey report is approved by the Superintending Engineer Ele, Transmission (W&M) circle, KPTCL, Belagavi vide O.M.No.
506/BGM/SEE/Tr(W&M)C/EE(O)/AEE-2/F.404/7694-98 Dated: 17.12.2022

Further, while preparing the estimate following points have been considered,
1. 1No of 11kV, 400A, 25kA double break isolator has been included in the estimate for Auxillary Transformer.
2. 11kV Double break isolators for Capacitor banks have been conisdered in item No. A20 along with capacitor bank and allied equipment. Hence, separate
provision for 11kV, 400A, 25kA double break isolators for capacitor bank has not been considered in the estimate.

3. 11kV cable termination structure for capacitor banks with associated civil works has been considered in the estimate .

4. A9(v) - 03 No's of 110kV pedestal insulator structures have been included in the estimate to avoid sagging of conductor between 110kV Isolator and CT
structure. Provision has also been made in civil portion.

4. 03 No's of 110kV solid core post insulator have been included in the estimate for 03 No's of 110kV pedestal insulator structures
Benefits :
(i) The voltage regulation will be well within the limits.
(ii)Reduction of load on 110kV Katkol s/s, 33kV Chunchanur s/s will be achieved
(iv) Future load growth can be catered.
(v) The consumers will get reliable power supply.

All the necessary provisions as per the approved Lay out are included in the estimate. Hence, this estimate may be sanctioned at an earliest.

Certificate : This estimate has been prepared as per Common SR Volume -VI 2023-24 and KPWD 23-24 UNI SR Volume-I for executing the work in most
economical and safe way.

Assistant Engineer, Ele., Assistant Executive Engineer, Ele.,


M.W. Sub-Division-II, KPTCL., Belagavi M.W. Sub-Division-II, KPTCL., Belagavi

Assistant Engineer, Civil., Assistant Executive Engineer, Civil.,


M.W. Division, KPTCL., Belagavi M.W. Division, KPTCL., Belagavi

Executive Engineer, Ele.,


M.W. Division, KPTCL., Belagavi
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED.

Estimate for establishment of 2X10MVA , 110/11 KV Substation at Padamandi in Ramadurga Taluk, Belagavi
District.

ABSTRACT - I ( As per new KPTCL SR-2023-24)

Sl.
Particulars Amount in Rs.
No.

1 Material Cost 80553000.00

2 Labour charges/ Erection Portion/Dismantling and test & commission Charges 2122000.00

3 Cost of Civil Engineering works 29077732.54

4 Basic Rate (Sum of Sl No1 to 3) 111752732.54

5 Area Specific Loading on Basic rate (Sl No-4) wherever applicable 0.00

6 Applicable GST on Sl.No. 4 & 5 20115491.86

Cost of the Estimate ( Sun of Sl No- 4 to 6)


7 131868224.40
Amount put tender
Statutory Charges such as PTCC, Electrical Inspectorate charges, Payment to Civic
8 300000.00
bodies, etc.,

9 Forest clearance, Tree/Crop cut compensation etc., 0.00

10 Land/Corridor/Tower foot area compensation etc., 0.00

11 Total cost of Estimated (Sum of Sl No. 7 to 10 ) 132168224.40

Say 1321.68 Lakhs


KARNATAKA POWER TRANSMISSION CORPORATION LIMITED

Estimate for establishment of 2X10MVA , 110/11 KV Substation at Padamandi in Ramadurga Taluk, Belagavi District.
Material & Erection Portion

Rates of MW SR 2023

Testing and
Sl. Erection Charges
Particulars Unit Qty Material Cost Commissioning Remarks
No

Rate Amount Rate Amount Rate Amount

A1 Power Transformers :

110/11 KV, 10 MVA, Delta / Star, Dyn11, 3 hase 50Hz, Core type
winding with OLTC, RTCC Panel etc complete, filled with Transil Oil,
with terminal connnectors suitable for DRAKE ACSR on 110kV side
KPTCL SR-2023 Part-1 ( Supply)
and Drake ACSR/2Nos. of 50x8mm copper flat for each phase from LV
Nos 2 11161040.00 22322080.00 266189.00 532378.00 48187.00 96374.00 Page No-25
side of transformer to cable at 11kv terminating structure with
Item No:1.12
suitable supporting insulators on LV side of transformer and 2Nos of
50mm x 8mm copper flats from Neutral Terminal to the Earthmat
through NCT alongwith necessary suppor pin insulator.

Circuit Breaker : 110 kV, 40 kA class, SF-6 Circuit Breaker with


terminal connector suitable for Al. tube/conductor with spring/semi-
KPTCL SR-2023 Part-1 ( Supply)
pneumatic/pneumatic type operating mechanism and mounting
A2 Nos. 2 703010.00 1406020.00 19302.00 38604.00 33813.00 67626.00 Page No-27
structure etc., as per technical specification.
Item No:3.3
a) For 110kV Line : 02 No.
b) For 10MVA 110/11kV Transformer : 2 Nos.

Isolators :
Isolators including marshalling box and suitable terminal connectors,
as required as per technical specification with solid core cylindrical
post insulators.

A) 110 KV,1250 A, 40 KA Class Double Break Manually Operated


isolators with terminal connectors suitable for DRAKE ACSR.
KPTCL SR-2023 Part-1 ( Supply)
a) Upright mounting type with earth switch. Page No-36
Set 1 381150.00 381150.00 10002.00 10002.00
(Live Point Height - 4600mm). Item No:9.10.1 & 9.10.2
b) Upright mounting type without earth switch.
Set 4 321860.00 1287440.00 10002.00 40008.00
(Live Point Height - 4600mm).
A3 B) 11 kV Isolators :
KPTCL SR-2023 Part-1 ( Supply)
i) 11 kV isolator, Double Break 1250A, 25kA capacity with rigid
Set 0 51675.00 0.00 777.00 0.00 Page No-76
bimetallic terminal connectors suitable for Drake ACSR for Incomer
Item No:50.1.1

i) 11 kV isolator, Double Break 400A, 25kA capacity with rigid


bimetallic terminal connectors suitable for coyote ACSR Auxiliary Set 1 21260.00 21260.00 1241.00 1241.00
transfromer ESCOM SR-2023 Part-2 ( Supply)
Page No-11
Item No:24.04 & 24.05
ii) 11 kV isolators, Single break 400A 25KA capacity with Roaster
set 11 18634.00 204974.00 1241.00 13651.00
switch and rigid bimetallic terminal suitable for coyote ACSR.
Rates of MW SR 2023

Testing and
Sl. Erection Charges
Particulars Unit Qty Material Cost Commissioning Remarks
No

Rate Amount Rate Amount Rate Amount

Current Transformer : Current transformer including Marshaling


box, single phase, oil filled out door type with rigid bimetallic
terminal connectors suitable for Drake ACSR.

i) 110 KV Class , 31.5KA.CT of ratio 400-200/1-1-1A for Tr. Line

Cores Purpose Acc Class Burden Vk Rct


Nos 0 135520.00 22322080.00 6394.00 12788.00 14101.00 28202.00
Core-1 Dist/Diff PS 800V 4Ohm at 400/1A
Core-2 Metering 0.2s 10VA
Core-3 Backup 5P20 30VA

ii) 110 KV Class , 31.5KA.CT of ratio 200-100/1-1-1A for Trf


KPTCL SR-2023 Part-1 ( Supply)
Page No-31
Cores Purpose Acc Class Burden Vk Rct Item No: 5.2.6 ,5.2.7 & 5.2.17
A4 Nos 6 134310.00 204974.00 6394.00 12788.00 14101.00 28202.00
Core-1 Dist/Diff PS 400V 2Ohm at 200/1A
Core-2 Metering 0.2s 10VA
Core-3 Backup 5P20 30VA

ii) 11 KV Class, 25kA, NCT of ratio 1200-800/1-1A for REFR


Protection (of similar rating and ratio as that of incommer of 11kV
Nos 2 56870.00 113740.00 832.00 1664.00
SWG) with termianl connector suitable for 2Nos of 50x8mm copper
flats.

Note:1. For details refer Annexure IIB:Techincal Parameters of current


Transformers for type and rating attached at the end of thi schedule.
2. All the Current transformers in each kv class shall be of one & the
same make & characteristic of 11KV NCT should be the same as that
of the Incomer CT of 11KV swithchgear . To ensure this, the 11KV NCT
should be procured from the supplier of 11kv switchgear only

Voltage Transformer :

a)Voltage Transformer, 110 KV, Single Phase, Oil filled outdoor type
including marshalling KIOSK with rigid bimetallic terminal connectors
Nos 3 150040.00 450120.00 6394.00 6394.00 14207.00 14207.00
suitable for Drake ACSR technical specification. Ratio : 110 kV/
√3/110 V/ √3 -110V/ √3 - 110V/ √3.
A5 KPTCL SR-2023 Part-1 ( Supply)
Cores Purpose Acc Class Burden Page No-33
Item No: 7.2
Core-1 Prot 3P 300VA

Core-2 Metering 0.2 200VA

Core-3 Open/De 3P 50VA

Surge Arrestor : Surge arrestors(Porcelain Housing) Metal Oxide Gap


less type as per technicaal specification.
Rates of MW SR 2023

Testing and
Sl. Erection Charges
Particulars Unit Qty Material Cost Commissioning Remarks
No

Rate Amount Rate Amount Rate Amount


i) 96 kV, 10 KA, Class -II (Station Medium Duty (SM)
Nos 6 43560.00 261360.00 2220.00 13320.00
- for Transformer & UG Cable
ii) 96 kV, 10 KA, Class -II (Station Low Duty (SL))
Nos 3 41140.00 123420.00 119.00 357.00
- for Overhead Line
A6
KPTCL SR-2023 Part-1 ( Supply)
Page No-33
3Nos each
Item No: 8.3 & 8.4
for 12feeders
ii) 9 kV, 10kA Class with connectors and clamps Nos 39 3025.00 117975.00 26.00 1014.00 DP and 3Nos
each for LV
side of Trf

Control and Relay Panels :110 kV Sub-station : Simplex 110 V DC


compatible to SCADA complete as per technical specification

a) For Power Transformer 10 MVA, 110/11 KV Nos 2 631620.00 1263240.00 5959.00 11918.00 42973.00 85946.00
b) For 110kV Transmission line Nos 0 456170.00 0.00 5959.00 0.00 42973.00 0.00

Note : 1. All the C&R panels and associated panels shall be one and KPTCL SR-2023 Part-1 ( Supply)
A7 the same make for uniformity and interchangeability of components. Page No-41
2. The accuracy class of metering core of CTs and VTs and ETV Meter Item No: 16.2.1 & 16.2.6
of C&R Panels shall be 0.2s accuracy class irrespective of what has
been indicated else where in the bid document.
3. The Electronic Tri-vector
meters of 0.2s accuracy class with ABT & TOD features, DLMS
protocol energy meter has to be provided.

Station Structure :

A) 110 KV side station stucture fabricated out of galvanized mild


steel structure including Bolts and Nuts

i) Station towers (verticals 1T1) - 0.986MT+0.068MT B&N= 1.054MT Nos 6 143331.76 859990.56 6032.04 36192.25

ii) Station beams (1B1) - 0.521MT+ 0.032MT B&N = 0.553MT Nos 3 75174.88 225524.64 3164.82 9494.46
KPTCL SR-2023 Part-5 ( Supply)
Station Structure 11kV side (on LV side of Transformer): Page No-246
fabricated out of galvanized mild steel structure including Bolts Item No: II A 1, 2, 6 &7
and Nuts

i) Station towers (verticals 3T1) - 0.57MT + 0.0285MT B&N = 0.599MT Nos 0 81315.63 0.00 3199.16 0.00

ii a) 3B1 of 33kv beam suitable for 10.4Meters bay width


Nos 0 35012.25 0.00 2397.94 0.00
(0.399MT+5% B&N) = 0.419MT Per Beam
ii b) 3B1 of 33kv beam suitable for 6.0Meters bay width 0.23MT +
Nos 0 32811.57 0.00 1384.97 0.00
0.0115 B&N = 0.242MT
A8
B) 11KV ODS nad take off structure
ESCOM SR-2023 Part-2 ( Supply)
i) Columns out of 9.5mtrs long RCC pole of 350kgs working load(using
Nos 0 7509.00 0.00 1709.00 0.00 Page No-03
TOR steel) for 11kv ODS
Item No:1.08
Rates of MW SR 2023

A8 Testing and
Sl. Erection Charges
Particulars Unit Qty Material Cost Commissioning Remarks
No

Rate Amount Rate Amount Rate Amount

ii) Beams out of Galvanised iron channels of size 100x50mm with KPTCL SR-2023 Part-5 ( Supply)
arrangements for stringing power conductor & mounting DB GOS at Page No-246
11KV side along with cleats, Bolts& Nuts etc., Item No: II B1 & 2

1B1 7.45Meters Long 0.068MT + 0.0034MT B&N =0.071MT Nos 0 9700.81 0.00 192.77
1B2 4.0Meters Long 0.036MT + 0.0018MT B&N =0.038MT Nos 0 5135.72 0.00 103.17
Rates of MW SR 2023

Testing and
Sl. Erection Charges
Particulars Unit Qty Material Cost Commissioning Remarks
No

Rate Amount Rate Amount Rate Amount

iii) Supplying and erection of DP sructures with all accessories using


Set 11 23015.00 253165.00 4751.00 52261.00
9.0mtrs long, 145kG WL suitable for mounting roaster GOS/Capacitor
ESCOM SR-2023 Part-2 ( Supply)
Page No-03 & 12
Item No:1.01 & 26.02
iv) Supplying and erection of D.P structures with all accessories for
Set 1 23015.00 23015.00 4751.00 4751.00
auxiliary transformer.

GI Mounting Stucture including Bolts &Nuts of lattice type

i) 110kV Isolators LPH 4600mm - 0.726MT + 0.026 B&N. = 0.752MT Set 7 102099.80 714698.60 4303.70 30125.87

ii) 110kV Current transformers (6Nos) & 11 kV NCT (1No) - 0.146 MT+
Nos 14 21499.28 300989.92 904.23 12659.28
0.012 B&N. = 0.158MT
KPTCL SR-2023 Part-5 ( Supply)
iii) 110kV Potential transformers - 0.137 MT+ 0.011 B&N. = 0.148MT Nos 3 20136.82 60410.46 847.00 2541.01 Page No-246
A9
Item No: II C
1, 2, 3, 4, 5 & 6
iv) Lightening arrestors 96kV - 0.0105MT+0.011 B&N. = 0.0.116MT Nos 12 15800.18 189602.16 663.87 7966.42

v) 110kV Pedestal Insulators.

a) 110kV Pedestal insulators (for bus) - 0.127MT+ 0.013 B&N. =


Nos 6 19067.18 114403.08 801.22 4807.32
0.140MT

b) 110kV High Pedestal Insultor (for transformer) - 0.134 MT+ 0.016


Nos 6 20444.16 122664.96 858.45 5150.70
B&N. = 0.150MT
vi) 11kV Cable termination structure for LV side of transformer
Nos 2 9850.61 19701.22 414.92 829.84
(0.069MT)

vii) 11kV Cable termination structure for capacitor banks 0.1MT) Nos 2 14265.90 28531.80 600.92 1201.83

BUS BAR FORMATION: Page No: 18 , Item No 8

a) DRAKE ACSR (including 110kV & 11kV side ) Mtrs 350 387.00 135450.00
KPTCL SR-2023 Part-1 ( Supply)
b) AAAC Moose (11kV Side) Mtrs 0 552.00 0.00 Page No-44
Item No: 20.2, 20.3, 20.4, 20.6 &
b) Coyote ACSR (11kV Side) Mtrs 30 139.00 4170.00
20.8
c) Earth wire 7/3.15 mm steel with clamp/lugs. Mtrs 150 88.00 13200.00

Bus Bar Formation MW SR 01.06.19, Pg No 90


A10 Main Bus using Drake ACSR
110 KV side = 1bay Bays 1 12087.00 12087.00

Main Bus using AAAC Moose


11 KV side = 11bay
Bays 0 12087.00 0.00
( 4Nos for each 11kV ODS and 1No for Bus coupler and 2Nos for LV KPTCL SR-2023 Part-2 ( Labour
side of Trf ) Portion)
Page No-122
Cross Bus using Drake ACSR Item No: 25
Bays 3 12087.00 36261.00
(110kV Line bays : 1 + 10MVA Transformer bay : 2)
Cross Bus using AAAC Moose
Bays 0 12087.00 0.00
(For all 14No 11kV Feeders and 2No Capacitor Banks) total=16
Rates of MW SR 2023 KPTCL SR-2023 Part-2 ( Labour
Portion)
Testing and Page No-122
Sl. Erection Charges Item No: 25
Particulars Unit Qty Material Cost Commissioning Remarks
No

Rate Amount Rate Amount Rate Amount

Cross Bus using Coyote ACSR : 11kV side Bays 0 7364.00 0.00

A11 Insulators:

i) Post insulators - Cylindrical Solid core as per IS 5350, Part II & III.

KPTCL SR-2023 Part-1 ( Supply)


a) 110kV Class, 1Unit/Stack Stacks 21 12055.00 253155.00 444.00 9324.00 Page No-45
Item No: 21.1.3
b) 33kV Class, 1Unit/stack(to be used for 11kc side road crossing Stacks 0 0.00

ii) Disc insulators with hardwares :

Strings
i) Single Tension string using 9 Units each of 11kV 90kN Disc
Insulators along with bolted type tension clamp & hardware suitable 6 7763.00 46578.00
for Drake ACSR (110kV side).

Strings
ii) Single Tension string using 3 Units of each 11kV 90kN Disc
Insulators along with bolted type tension clamp & hardware suitable 0 4205.00 0.00
forAAAC Moose (on LV side of transformer for road crossing).

Strings
iii) Single Tension string using 2 Units of each 11kV 90kN Disc
Insulators along with bolted type tension clamp & hardware suitable 0 3612.00 0.00
for AAAC Moose (11kv side).
Strings

iv) Single Tension string using 1 Units of each 11kV 90kN Disc
KPTCL SR-2023 Part-1 ( Supply)
Insulators along with bolted type tension clamp & hardware suitable 0 1919.00 0.00
Page No-45 & 68
for Coyote ACSR (11kv side).
Item No: 21.2.3 & 47
Strings

v) Single Suspension string using 9 Units of each 11kV 90kN Disc


Insulators along with bolted type suspension clamp & hardware 3 6860.00 20580.00
suitable for Drake ACSR (110kV side).
Strings

vi) Single Suspension string using 3 Units of each 11kV 90kN Disc
Insulators along with suspension clamp & hardware suitable for AAAC 0 3302.00 0.00
Moose (on LV side of transformer ).
Strings

vii) Single Suspension string using 2 Units of each 11kV 90kN Disc
Insulators along with suspension clamp & hardware suitable for AAAC 0 2709.00 0.00
Moose (11kv side ).

A12 Hardwares :

a C type Wedge connector suitable for DRAKE - DRAKE Nos 9 2305.00 20745.00

C type Wedge connector suitable for LYNX - DRAKE (for 110kv line
b Nos 6 1921.00 11526.00
side)

KPTCL SR-2023 Part-1 ( Supply)


Page No- 69 & 70
Rates of MW SR 2023

Testing and
Sl. Erection Charges
Particulars Unit Qty Material Cost Commissioning Remarks
No

Rate Amount Rate Amount Rate Amount

c C type Wedge connector suitable for AAAC Moose-AAAC Moose 0 3378.00 0.00
KPTCL SR-2023 Part-1 ( Supply)
Page No- 69 & 70
Item No:47.5.5 And 47.10
Rates of MW SR 2023

Testing and
Sl. Erection Charges
Particulars Unit Qty Material Cost Commissioning Remarks
No

Rate Amount Rate Amount Rate Amount KPTCL SR-2023 Part-1 ( Supply)
Page No- 69 & 70
d C type Wedge connector suitable for Coyote -Coyote Nos 0 656.00 0.00 Item No:47.5.5 And 47.10

e C type Wedge connector suitable for AAAC Moose -Coyote Nos 0 1771.00 0.00

Post Insulator Clamp suitable single Drake ACSR & 110kV solid core
f Nos 18 1010.00 18180.00
insulator.

Auxillary transformer :

i) Supply & erection of Station Auxillary transformer with oil, outdoor


KPTCL SR-2023 Part-1 ( Supply)
type 100 KVA, 11 kV/433V, 3Ph, Vector group Dyn11, off load tap
A13 Page No-75
changer (with 5taps) with step up voltage 2.5% alongwith DOLO/HG-
Nos 1 386603.00 386603.00 18592.00 18592.00 Item No:56.3 & 57.3
fuse unit, LT Protection kit, distribution box and 9 kV, 10kA Class
ESCOM SR Part II (Distribution) Pg
surge arrestor with connectors and clamps and other accessories as
09 &12 Item No. 17.01 & 25.01
per specifications

A) LTAC Panel (Indoor) : LTAC Panel 415V as per technical


specification comprising of Voltmeter, Ammeter & 1No. ETV meter.
Nos 1 85910.00 85910.00 3207.00 3207.00
1No. I/C MCCB 200A + 2Nos 3 Phase, 63A OG HRC fuse + 2Nos 3
Phase 32 A OG HRC fuse + 6Nos 3Phase, 16A HRC fuse etc, complete. KPTCL SR-2023 Part-1 ( Supply)
A14 Page No- 39
Item No:11.2.2, 11.2.3
B) A.C. Distribution box (Out door) : AC distribution box single front
type, 6 terminals, 1200x1350x300mm, 1 I/C of 100A, MCCB 20kA + 6 Nos 1 72600.00 72600.00 2424.00 2424.00
O/G MCB 16A + 1 O/G of 100A, HRC fuse.

LT Power armoured UG Cable as per specifications. 0.00

KPTCL SR-2023 Part-1 ( Supply)


a) 1.1 kV, PVC Insulated 95 Sqmm Aluminium Cable, 4 core with
Mtrs 100 762.00 76200.00 15.00 1500.00 Page No- 40
glands/lugs/ferrules.
Item No:14.4
A15
b) 1.1 kV, PVC Insulated 25 Sqmm Copper Cable, 4 core with
Mtrs 150 866.00 129900.00 15.00 2250.00
glands/lugs/ferrules. KPTCL SR-2023 Part-1 ( Supply)
Page No- 40
c) 1.1 kV, PVC Insulated 10 Sqmm Copper Cable, 4 core with Item No:13.9 & 13.11
Mtrs 200 375.00 75000.00 15.00 3000.00
glands/lugs/ferrules.

Station Battery & Battery charger :

a) 110V, 200AH Battrery set (Plante type) consisting of 55 Nos of cells


Set 1 603790.00 603790.00 11621.00 11621.00
A16 with accessories as per specification.

b) Battery charger suitable for 110V, 100AH, Battery set consisting of


55Nos of cells with float cum booster type battery charger as per Set 1 169400.00 169400.00 1147.00 1147.00 30509.00 30509.00 KPTCL SR-2023 Part-1 ( Supply)
specification. Page No- 37,38,39
Item No:110.1.5, 10.2.4, & 11.2.3
Rates of MW SR 2023

Testing and
Sl. Erection Charges
Particulars Unit Qty Material Cost Commissioning Remarks
No
KPTCL SR-2023 Part-1 ( Supply)
Rate Amount Rate Amount Rate Amount Page No- 37,38,39
Item No:110.1.5, 10.2.4, & 11.2.3
DC Distribution Panel (indoor Type) as per technical specification
comprising of Earthfault indicator, Indication circuit for AC main
A17 Nos. 1 52030.00 52030.00 2426.00 2426.00
failure, 1No. 100A SFU for IC + 12 Nos, 32A SFU for O/G etc,
complete.
Rates of MW SR 2023

Testing and
Sl. Erection Charges
Particulars Unit Qty Material Cost Commissioning Remarks
No

Rate Amount Rate Amount Rate Amount


PVC Insulated Copper Control Cables : 1.1 KV PVC insulated Copper
Control Cable with glands/Lugs/Ferrules etc as per technical
specification.

i) 19 Core x 2.5 Sq.mm Mtrs 2500 525.00 1312500.00 15.00 37500.00

A18 ii) 4 Core x 6.0 Sq.mm Mtrs 2200 247.00 543400.00 15.00 33000.00
KPTCL SR-2023 Part-1 ( Supply)
iii) 4 Core x 2.5 Sqmm Mtrs 2000 142.00 284000.00 15.00 30000.00 Page No- 40
Item No:13
iv) 2 Core x 6 Sqmm Mtrs 2000 154.00 308000.00 15.00 30000.00

v) 2 Core x 2.5 Sqmm Mtrs 500 94.00 47000.00 15.00 7500.00

11KV Switch Gear :

11kV, 500MVA, Metal clad VCB Switch gear (1600A for Incomer and
1250A for feeders) outdoor type, each comprising of
2IC+12F+2CB+1BC+1AP (Remote Annunciation cum control panel)
with CT's & PT's etc., complete as per technical specifications.
Note: 1. The Remote Announciation cum Control panel is Simplex
type.
2. The Electronic Trivector meters with ABT features has to be
A19 provided. KPTCL SR-2023 Part-1 ( Supply)
Set 1 15607790.00 15607790.00 70754.00 70754.00 322558.00 322558.00 Page No- 28, 29
3. The switchgear for capacitor bank shall have necessary Over
Item No:4.3, 4.11
voltage / Under voltage / Circulating current relays and other
protection relays as per specification.
4. The Switchgear will be supplied by KPTCL and the Bidder has to
quote for complete scope of erection of Switchgear including moving
the Switchgear from the point of unloading to the point of erection,
erection of the complete Switchgear, wiring of Switchgear, testing &
commissioning etc., complete.

Capacitor Bank :

Design, Engineering, supply, erection (including civil works) and


testing, commissioning of 2.9 MVAR, 12.1 kV capacitor bank, star
connected double bank with internal fuses, terminal connectors, with
A20 suitable neutral CT & station class LA's, 0.2% series reactor on KPTCL SR-2023 Part-1 ( Supply)
neutral side with mounting structure for NCT, Capacitor bank, station Set 2 538450.00 1076900.00 22228.00 44456.00 Page No- 39
class LA's, series reactor etc., complete as per specification (including Item No:12.1.7
testing & commissioning).
Note : The 11kV SWG & remote announciation / control of the
capacitor bank is included in item No. A19.

A. 11kV XLPE UG Cable as per specification


Rates of MW SR 2023

Testing and
Sl. Erection Charges
Particulars Unit Qty Material Cost Commissioning Remarks
No

Rate Amount Rate Amount Rate Amount

a) 3x95 Sqmm XLPE Al. Cable ( to be run for Auxillary transformer KPTCL SR 2023 Part II (Distribution)
Mtrs 50 889.67 44483.30 61.30 3065.00
from 11kV SWG to Aux transformer) Pg No. 15, Item No: 36.01
A21
b) 1x1000 Sqmm XLPE Al. cable ( from 110/11kV transformer to 11kV KPTCL SR 2023 Part I (Supply) Pg
Mtrs 400 1185.00 474000.00 64.15 25660.00
SWG) No. 73, Item No: 49

c) 3x240 Sqmm XLPE Al. cable ( from 11kV SWG to 11kV take off DP KPTCL SR 2023 Part II (Distribution)
Mtrs 400 165.60 66240.00 64.46 25784.00
structure) Pg No. 15, Item No: 36.05

B. 11kV XLPE UG Cable termination kit(Heat Shrinkable


type) as per specification for the following sizes

i. 95 sqmm 3Core

a. Indoor Nos 1 3094.00 2658.00 2658.00


KPTCL SR 2023 Part II (Distribution)
Pg No. 20, Item No: 45.04 & 45.07
b. Outdoor Nos 1 3361.00 2658.00 2658.00

ii. 1000 sqmm 01 Core

a. Indoor Nos 8 3808.00 2658.00 21264.00


KPTCL SR 2023 Part I (Supply) Pg
No. 73, Item No: 50.3.1 & 50.3.2
b. Outdoor Nos 8 4060.00 2658.00 21264.00

iii. 240 sqmm 03 Core

a. Indoor Nos 13 3877.00 2658.00 34554.00


KPTCL SR 2023 Part II (Distribution)
Pg No. 20, Item No: 45.05 & 45.08
b. Outdoor Nos 13 4395.00 2658.00 34554.00

Equipment required for establishing SCADA Communication as


A22
per KPTCL Specifications:
a) Remote Terminal Unit (RTU) Nos 1 986150.00 986150.00
b) Data Concentrator Unit (DCU) Nos 1 37510.00 37510.00
KPTCL SR-2023 Part-1 ( Supply)
c) 2kVA online UPS (230V AC 1-phase, 50Hz) UPS with battery Page No- 47, 48
confirming to KPTCL specifications. Nos 1 168190.00 168190.00 Item No:24.1.1, 24.2, 24.3
Note: Satellite Communacation required will be arranged by SLDC

d) Site survey, wiring, installation, testing and commissioning of RTU,


Nos 1 31147.86 31147.86
DCU. (DCU installation to be done in RTU panel)

e) Integration of RTU, DCU, UPS with field equipments Nos 1 22322.63 22322.63

e) Cables

i. Current cables - Copper core with c/s 4.0sqmm multistrand 7 core Mtrs 100.00 280.74 28074.00

Page No-40
ii. Voltage cables - Copper core with c/s 2.5sqmm multistrand 4 core Mtrs 60.00 142.00 8520.00
Item No-13.6
Rates of MW SR 2023

Testing and
Sl. Erection Charges
Particulars Unit Qty Material Cost Commissioning Remarks
No

Rate Amount Rate Amount Rate Amount


iii. Signal cables - Armoured copper core with c/s 0.5sqmm
Mtrs 700.00 143.00 100100.00
multistrand 10 core

iv. Supply of control cables - Copper core with 1.5sqmm multistrand


Mtrs 180.00 155.00 27900.00
10 core, confirming to KPTCL specification (160m/Station).
KPTCL SR-2023 Part-1 ( Supply)
Page No- 48
Item No: 24.4
Rates of MW SR 2023

Testing and
Sl. Erection Charges
Particulars Unit Qty Material Cost Commissioning Remarks
No

Rate Amount Rate Amount Rate Amount KPTCL SR-2023 Part-1 ( Supply)
v. Supply of control cables - Copper core with 4sqmm multistrand 3 Page No- 48
core for AC input to UPS and UPS to RTU, confirming to KPTCL Mtrs 20.00 159.00 3180.00 Item No: 24.4
specification (15m/Station).

vi. Supply of control cables - Copper core with 32sqmm multistrand


Mtrs 40.00 380.00 15200.00
for battery, confirming to KPTCL specification (15m x 2 runs/Station).

Fire fighting equipment with necessary monting stands.


a) Mechanical Foam type Extinguisher
i) 50.0 litres Capacity Nos 4 10112.00 40448.00
ii) 9.0 litres Capacity Nos 4 4118.00 16472.00
b)Water type : (Gas Pressure type)
KPTCL SR-2023 Part-1 ( Supply)
i) 9.0 litres capacity Nos 6 6171.00 37026.00
Page No- 74
c) Carbon dioxide type
Item No:51
i) 4.5kg capacity Nos 6 8691.00 52146.00
d) Sand type
A23 i) G.I Bucket 15 Litres capacity Nos 12 603.00 7236.00
ii) Steel stands for the above to have 4 Buckets to each sections. Nos 3 2362.00 7086.00

e) Nitrogen Injection fire extinguishing system (NIFPS) including


Civil Engineering works like soak pit etc., as per recommendation
KPTCL SR-2023 Part-1 ( Supply)
of the supplier of the fire fighting system.(Providing NIFPS for
Set 2 1141635.00 2283270.00 Page No- 74
Power Transformer of rating 10MVA and above has been approved
Item No:53
vide KPTCL No. CEE9P&C)/SEE(Plg)/EEE(PSS-S)/KCO-95/F-
19172/2020-21/TCCM/3814-34/25.06.2020

Miscllaneous items like Rubber mat, first aid box, danger boards,
shocks treatments charts, water filter, door locks, fixograph, sub
station name board and other sundry items (Sizes/capacities to
be got approved).

1. Rubber mat 2000mmx1000mmx12mm size tested for 15kV class Nos 4 7500.00 30000.00

2. First aid box Nos 1 1000.00 1000.00


3. Shock treatment charts, hardboard, laminated with coloured
Nos 1 2000.00 2000.00
pictures & literature both in kannada & English.
4. Water filter cum Water purifier : Wall mounting type (Aqua - guard
Nos 1 18000.00 18000.00
A24 type)
5. Sub-station name board duly painted as per specification including
Nos 1 10000.00 10000.00
erection & civil works.

6. Fixograph of size 1.5mx2.5m with english / Kannada alphabets. Nos 1 5000.00 5000.00

7. Door locks 7 levers (Navatal make) Nos 5 3500.00 17500.00

8. Danger board (Prohibited) with support structure including fixing


Nos 1 1000.00 1000.00
infront of the gate.

9. Equipment name plates and earthing name plates including fixing


Nos 60 12000.00 720000.00
at out door yard.
Rates of MW SR 2023

Testing and
Sl. Erection Charges
Particulars Unit Qty Material Cost Commissioning Remarks
No

Rate Amount Rate Amount Rate Amount


A25 Maintenance Tools and Plants :
a) Portable(mobile) oil pump (1/2 HP Air pump 500 to 1000 gallons) Nos 1 20247.00 20247.00
b) Telescopic ladder Aluminium 6 Mtr. Height. Nos 1 22622.00 22622.00
c) Ring spanner set (12 No's per set) Set 1 880.00 880.00
d) Tube spanner set (12 No's per set) Set 1 1435.00 1435.00
e) Pipe wrench 24 Inch Nos 2 1250.00 2500.00
f) Pipe wrench 18 Inch Nos 2 692.00 1384.00
g) Hydraullic crimping tools up to 1000 Sqmm. Nos 1 62013.00 62013.00
h) Rubber hand gloves(15 KV tested) Pairs 3 293.00 879.00
i) Rechargeable 5 W LED Hand Torch Nos 2 1279.00 2558.00
j) Insulated cutting pliers, Taparia make
1) 12 inch size. Nos 3 393.00 1179.00
2) 8 inch size. Nos 3 236.00 708.00
k) Live Line tester Nos 2 311.00 622.00
l) Screw driver 18 " Nos 3 223.00 669.00
m) Screw driver 12 " Nos 3 75.00 225.00
n) Hammer 8 lbs. Nos 2 497.00 994.00
o) Hammer 2 lbs. Nos 2 249.00 498.00
p) Chain pulley block 5 ton Nos 1 41836.00 41836.00
q) Hydraullic jack 5 ton Nos 4 7048.00 28192.00
r) Pipe derrick Set 1 27831.00 27831.00
s) Allen keys Set 1 478.00 478.00
t) Box spanners with handle, Taparia make (12 nos. set) Set 1 4467.00 4467.00 KPTCL SR-2023 Part-1 ( Supply)
u) Transil oil dielectric breakdown test kit. Nos 1 101535.00 101535.00 Page No- 53,54
v) Insulation Tester (megger) 2.5 to 5 KV Nos 1 55308.00 55308.00 Item No:35
w) Insulation Tester (megger) 500 V Nos 1 17606.00 17606.00
x) SF6 Gass leak detector Nos 1 65242.00 65242.00
y) Multimeter electromchanical type Nos 1 3674.00 3674.00
z) Multimeter Electronic type Nos 1 7991.00 7991.00
aa) Hydro meter for specific gravity of battery Nos 1 658.00 658.00

bb) DC Voltmeter range -5V to +5V Nos 1 2700.00 2700.00

cc) Hydrometer syringe suitable for vent holes Nos 1 900.00 900.00
dd) Specific gravity correction chart Nos 1 900.00 900.00
ee) Wall mounting type holder for hydrometer Nos 1 2700.00 2700.00
ff) Thermometer with mounting holder Nos 1 2700.00 2700.00
gg) Rubber appron Nos 1 1912.00 1912.00
hh) Pippete Nos 1 788.00 788.00
ii) Protective goggles Nos 1 900.00 900.00
jj) Acid resisting Jars (4 pint capacity) Nos 1 900.00 900.00
kk) Rubber Shoes knee height pairs 2 2138.00 4276.00
ll) Glass funnel Nos 2 676.00 1352.00
mm) Earthing Sticks Nos 6 1755.00 10530.00
A26
Furniture for Control room staff and maintenance staff
a) Steel Almirahs 6.5 feet
Nos 2 10000.00 20000.00
Rates of MW SR 2023

Testing and
Sl. Erection Charges
A26 Particulars Unit Qty Material Cost Commissioning Remarks
No

Rate Amount Rate Amount Rate Amount


b) Steel Almirahs 6.5 feet with glass panel doors
Nos 1 8000.00 8000.00
c) Officer's Tables Nos 2 9000.00 18000.00
d) Steel Slotted Angle rack (big size) Nos 4 2500.00 10000.00
e) Steel Slotted Angle rack (small size) Nos 4 2000.00 8000.00
f) Steel Dust bins Nos 4 400.00 1600.00
g) Executive revolving chairs Nos 2 8000.00 16000.00
h) "S" Type arm chairs Nos 6 1500.00 9000.00
i) Steel folding chairs Nos 4 500.00 2000.00
STATION & YARD LIGHTING (OUTDOOR) :
A27
(To be designed, assessed & quoted by the bidder)

Design of Station yard illumination in confirmity with the illumination


levels mentioned in the technical specification, supply & erection of
station yard illumination materials /equipment including lamp post
1 L/s 1 300,000.00
(fabricated galvanised structures), Illumination fittings, control gears,
UG/OH cables, conduit pipes, control boxes etc,. including necessary
civil works, complete

A28 Misc & Rounding Off L/S 1 742.30 911.54 911.54 1376.00 1376.00

Grand Total 80553000.00 1447000.00 675000.00

-2000.00 0.00

Assistant Engineer, Ele., Assistant Executive Engineer, Ele.,


M.W. Sub-Division-II, KPTCL., Belagavi M.W. Sub-Division-II, KPTCL., Belagavi

Executive Engineer, Ele.,


M.W.Division, KPTCL., Belagavi.
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED

Estimate for establishment of 2X10MVA , 110/11 KV Substation at Padamandi in Ramadurga Taluk, Belagavi District.
Calculation sheet for Erection, Testing and Commissioning Charges
Sl. Unit Rate in
Particulars Unit Qty
No Rs.
A1 Power Transformer :-
i) Erection of 10 MVA 110/11 KV Power Transformer :- KPTCL SR 2023, Pg No: 116
Moving the transformer on the plinth maximum allowable distance is 50 mtr.
a) MT/Mtr 1200.00 80.00
(30x40 = 1200 MT /mtr)
b) i) Assembly of transformer parts like bushing,radiators etc., MT 38 1134.00
ii) Filteration of oil using filter set of contractor to bring the insulation value to IE specfication Litre 16000.00 7.00
iii) Fabrication of transformer railing and embedding in transformer plinth L/s 1 1626.00
Wiring of Transformer marshling box, bucholtz relay, fixing thermometer, OLTC upto control panel and
c) assisting in testing and commissioning by RT/MT/Firm Engineers L/s 1 13471.00
ii)10MVA to 20MVA Tr.
Total Erection Cost
ii) Wiring, Testing and Commissioning Charges : KPTCL SR 2023, Pg No: 116
a)Wiring :- Inspection of wires, ferruling, crimping and termination of wires. Wiring of protective devices,
a) Each 1.00 14180.00
OLTC, RTCC etc.,
b) Testing and Commissioning :-
1) Ration test
2) S.C Test
3) Excitation test
4) Magnetic balance test
5) Vector group test
6) Induced high voltage test
7) OLTC operation Each 1.00 34007.00
8) Protective devices operation checks
9) Stability checks : For Differntial and REFR protection.
10) Winding Resistance Test
11) Insulation Resistance test.
12) Tan Delta & Capacitance Test
Sl. Unit Rate in
Particulars Unit Qty
No Rs.
13) Transformer Mounted Protective devices Test.
14) Sweep frequency response (SFR) test
Wiring, Testing and Commissioning Charges
A2 Circuit Breaker :
i) Erection of 110kV Breakers :- KPTCL SR 2023, Pg No: 117
Erection, asssembly, alignment & interpole wiring of breakers with its connected equipments including
a) set 1 10815.00
movement from the point of unloading to the point of erection.
Wiring : Identification, Ferruling,crimping and termination of wires in Breaker & wiring upto control
c) Set 1 8487.00
panel/relay panels. MW SR 2019, Pg No: 85
Total Erection Cost
ii) Testing and Commissioning Charges: KPTCL SR 2023, Pg No: 117
Testing and Commissioning Charges :- Test for insulation level, gas leakage testing for travel time,trip &
close timings Local trip close test, Remote trip ans close test, Tripping through relays, operation of interlocks Set 1 33813.00
etc.
Wiring, Testing and Commissioning Charges
A3 Isolators :
A) Erection of 110kV Isolators:- KPTCL SR 2023, Pg No: 119
Assembly, erection alignment and wiring including movement from the pointof unloading to the point of
erection.
i) Upright Set 1 8701.00
ii) Assiting in testing and commissioning Set 1 1301.00
Total Erection Cost
B) Erection of 11 KV Isolators:- ESCOM SR-2023-24 Page No-48 item No: 13.03
i) 11 KV Isolator double break 1250A 25 KA (For Incomer) Nos 1 1214.00
ii) 11 KV Isolator double break 400A 25 KA (For Capacitor bank) Nos 1 1214.00
iii) 11 KV Isolator single break 400A Roaster GOS (For 11kV Feeders) Nos 1 1241.00
A4 Current transformer :
i) Erection of Current transformer 110 KV Class : KPTCL SR 2023, Pg No: 118
Set
a) Erection of CT's and wiring including movement from the point of unloading to the point of erection. 1 6394.00
(3Nos)
Total Erection Cost
Sl. Unit Rate in
Particulars Unit Qty
No Rs.

c) Wiring, Testing and commissioning Charges of Current Transformers : KPTCL SR 2023, Pg No: 117

Set
Wiring : Inspection of wiring, Ferrulimg, crimpimg of lugs, connection up to marshling box and control panel. 1 2837.00
(3Nos)
Set
Testing and Commissioning of CT's: Insulation, Polarity, Ratio & Excitation tests. 1 11264.00
(3Nos)
Wiring, Testing and Commissioning Charges
iii) 11 KV NCT :- KPTCL SR 2023, Pg No: 118
Erection of NCTs including movement from the point of unloading to the point of erection with grounding
a) Nos 1 733.00
connection.
b) Assiting in testing and commissioning Nos 1 99.00
Total Erection Cost
A5 Voltage transformers :
i) Erection of 110 KV Potential transformer : KPTCL SR 2023, Pg No: 118
Set
a) Erection of PT's and wiring including movement from the point of unloading to the point of erection. 1 6394.00
(3Nos)
Total Erection Cost
Wiring, Testing and commissioning Charges for 110kV Potential Transformers :
c)
KPTCL SR 2023, Pg No: 118
Set
Wiring : Inspection of wiring, Ferrulimg, crimpimg of lugs, connection up to marshling box and control panel. 1 2837.00
(3Nos)
Set
Testing and Commissioning of PT's: Insulation, Polarity, Ratio & Excitation tests. KPTCL SR 2023, Pg No: 118 1 11370.00
(3Nos)
Wiring, Testing and Commissioning Charges
A6 Surge Arrestors :
i) Erection of 110 KV Lightning Arrestors: KPTCL SR 2023, Pg No: 119
Erection of lightning arrestors and wiring including movement from the point of unloading to the point of
Set 1 2220.00
erection.
ii) Erection of 9KV, 10kA Lightning Arrestors : ESCOM SR-2023-24 Page No-48 item No: 13.06 Nos 1 119.00
A7 Control and Relay Panel :
a) Erection of Control and Relay Panel : KPTCL SR 2023, Pg No: 120
Sl. Unit Rate in
Particulars Unit Qty
No Rs.

Erection of control panels,alignment and fixing properly to foundation base including movement from the Per
1 5959.00
point of unloading to the point of erection. Panel
Total Erection Cost
c) Wiring, Testing and Commissioning : KPTCL SR 2023, Pg No: 120
Per
Wiring of C&R Panels: Identification, ferruling, crimping, termination of wires in C&R panels. 1 8510.00
Panel
Testing & Commissioning of C&R Panels :
Testing for insulation level, testing of relays, control operations for closing tripping etc, interlock, alram Per
1 34463.00
annunciation & Indications checks Panel
Wiring, Testing and Commissioning Charges
A8 Station Structures :
Erection of Station Structures :-
a) 110kV side station structures fabricated galvanised steel structures : KPTCL SR 2023, Pg No: 116 Item No-8
a &b
i) Station Towers 1T1 MT 1.054 5723.00
ii) Station Beams 1B1 MT 0.553 5723.00
Station Structure 11kV side (on LV side of Transformer):
i) Station towers (verticals 3T1)(Without peak) : MT 0.559 5723.00
ii a) 3B1 of 33kV beam suitable for 10.4Meters bay width : (0.399MT+5% ) = 0.419MT MT 0.419 5723.00
ii b) 3B1 of 33kV beam suitable for 6.0Meters bay width : (0.23MT+5%) = 0.242MT MT 0.242 5723.00
b) 11kV Side
i) Columns out of 9.0mtrs long RCC pole of 300kgs working load(using TOR steel) for 11kV ODS in
Nos 1 1709.00
Hard Latterite Soil as per ESCOM SR-2023-24 Page No-43 item No: 1.1.3

ii) Beams out of Galvanised iron channels of size 100x50mm with arrangements for stringing
power conductor & mounting DB GOS at 11KV side along with cleats, Bolts& Nuts etc.,

1B1 7.45Meters Long (0.068MT+5% B&N)=0.0714MT MT 0.071 2715.00


1B2 4.0Meters Long (0.036MT+5% B&N)= 0.0378MT MT 0.038 2715.00

iii) 11kV D.P.Structures with all accessories using 9 Mtrs. Long , 145 Kgs. WL,RCC poles including H frame
suitable for mounting roaster GOS with provision for fixing 9KV lighting arrestor etc, complete in Hard Set 1 4751.00
Latterite Soil as per ESCOM SR-2023-24 Page No-43 & 48 item No: 1.1.3, 13.03 & 13.06
Sl. Unit Rate in
Particulars Unit Qty
No Rs.

iv) 11kV D.P.Structures with all accessories using 9 Mtrs. Long , 145 Kgs. WL,RCC poles including H frame
suitable for mounting GOS with provision for fixing 9KV lighting arrestor etc, complete for auxiliary Set 1 4751.00
transformer in Hard Latterite Soil as per ESCOM SR-2023-24 Page No-43 & 48 item No: 1.1.3, 13.03 & 13.06

A9 Mounting Structures:-
Erection of Mounting Structures:- MW SR 2019, Pg No: 84
i) 110 KV Isolator (0.724+5%= 0.760MT) MT 0.752 5723.00
ii) 110 KV CT's & NCT (0.142+5%=0.1491MT) MT 0.158 5723.00
iii) 110 KV PT's ( 0.142+5% = 0.149MT) MT 0.148 5723.00
iv) 96 kV LA's (0.069+ 5%=0.072MT) MT 0.116 5723.00
v) a) 110 KV Pedestal Insulator (0.140+ 5%=0.147MT) MT 0.140 5723.00
b) 110 KV High Pedestal Insulator (0.22+ 5%=0.231MT) MT 0.150 5723.00
c) 11 KV Isolator mounting structure for Capacitor Bank (0.1+ 5%=0.105MT) MT 5723.00
A11 Insulators :
i) Post Insulators Cylinidrical solid core : KPTCL SR 2023, Pg No: 119 Item No-19
Per
a) 110 KV Side 1 444.00
Stack
A13 Auxillary transformer : KPTCL SR 2023, Pg No: 75 Item No-56.3
Station Auxillary transformer with oil, Bushing termination type on both HT &LT side, outdoor type 100 KVA,
11 KV/433V, 3Ph, Vector group Dyn11, off load tap changer (with 5taps) with step up voltage 2.5% as per Nos 1 18592.00
specification. MW SR 2019, Pg No: 36
A14 Erection of LTAC Panel (Indoor) : KPTCL SR 2023, Pg No: 121 Item No-23 h Nos 1 3207.00
A15 Laying of LT Power Cable :- KPTCL SR 2023, Pg No: 120 Item No-22 b
a) 1.1 KV, 95 sqmm 4 Core Al cable Rmtr 1 15.00
b) 1.1 KV, 25 sqmm 4 Core Copper cbale Rmtr 1 15.00
c) 1.1 KV, 10 sqmm 4 Core Copper cbale Rmtr 1 15.00
A16 Erection of Battery Set & Battery Charger (110V) :- KPTCL SR 2023, Pg No: 124 Item No-28
a) Installing, assembling,filling of acid, wiring, test charging and discharging Battery set. Set 1 11621.00
b) Erection of Battery Charger and Wiring Nos 1 1147.00
Testing & Commisioning of Battery Charger (110V) :- KPTCL SR 2023, Pg No: 125 Item No-28
Wiring :- Identifiataion, ferruling, crimping & connecting
i) AC Supply cable upto 2 sources. Per Set 1 6057.00
Sl. Unit Rate in
Particulars Unit Qty
No Per Set 1 Rs.
6057.00
ii) Load cable connection at charger end upto 10 load points.
Testing:-
i) AC supply phase sequence,
ii) Testing of output DC Voltage in Boost/Float/Trickle/variation as per order/requirement.
iii) Testing for repel factor.
Commissioning:-
Per Set 1 24452
i) Fixing of Boost Volatge level,
Sl. Per Set 1 Unit Rate in
24452
Particulars Unit Qty
No Rs.
ii) Fixing of Float voltage level.
iii) Fixing of Trickle voltage level.
iv) Testing of alram indication &load circuit , auto/manual change over etc.
V) Full load test in Boost & Trickle modes
Wiring, Testing and Commissioning Charges
A17 Erection of DC distribution Panel (Indoor) : KPTCL SR 2023, Pg No: 121 Item No-23 h Nos 1 2426.00
A18 PVC Insulated Copper Control Cables : KPTCL SR 2023, Pg No: 120 Item No-22 b
Laying of control cables from equipments to control panels Rmtr 1.0 15.00
Erection of 11 KV Switchgears (MCVCB) comprising of 2 IC + 12F +1BC+ 2CB + 1AP :
KPTCL SR 2023, Pg No: 121-122 Item No-24
a) Erection, alignment & fixing to the foundation outdoor type 11 KV switchgear panel/unit including
Per
movement from the point of unloading to the point of erection. 17 2081.00
Panel
i) 11kV Outdoor Switchgear

A19 ii) 11kV Koisk Per


17 2081.00
Panel
Total Erection Cost
c) wiring, Testing & Commisioning :
Wiring : Identification of wires, ferruling, crimping & termination of wires for annunication etc. Per
17 18974.00
Testing of Relays, CT's PT's & Breaker for operation Panel
Wiring, Testing and Commissioning Charges
Capacitor Bank:-
Erection of Capacitor Bank:- KPTCL SR 2023, Pg No: 119 Item No-20
A20
a) Erection,Testing & commissioning of 11 KV, 2.9 MVAR star connected capacitor bank with reactors. Set 1 22228.00

A15 Laying of UG XLPE Cable :- KPTCL SR 2023, Part II (Distribution) Pg No: 52 Item No-21.01, 21.02 & 21.04
a) 3C x 95sqmm Rmtr 1 61.30
b) 3C x 240 sqmm Rmtr 1 64.15
c) 1C x 1000sqmm Rmtr 1 64.46

Assistant Engineer, Ele., Assistant Executive Engineer, Ele.,


Sl. Unit Rate in
Particulars Unit Qty
No Rs.
Major Works Sub Division-II, KPTCL., Belagavi. Major Works Sub Division-II, KPTCL., Belagavi.
TRANSMISSION CORPORATION LIMITED

KV Substation at Padamandi in Ramadurga Taluk, Belagavi District.

Amount in Rs

96000.00

43092.00
112000.00
1626.00

13471.00

266189.00

14180.00

34007.00
Amount in Rs

48187.00

10815.00

8487.00

19302.00

33813.00

33813.00

8701.00
1301.00
10002.00

1214.00
777.00
1241.00

6394.00
6394.00
Amount in Rs

2837.00

11264.00
14101.00

733.00
99.00
832.00

6394.00

6394.00

2837.00

11370.00
14207.00

2220.00
119.00
Amount in Rs

5959.00

5959.00

8510.00

34463.00
42973.00

6032.04
3164.82

3199.16
2397.94
1384.97

1709.00

192.77
103.17

4751.00
Amount in Rs

4751.00

4303.70
904.23
847.00
663.87
801.22
858.45
0.00

444.00

18592.00

3207.00

15.00
15.00
15.00

11621.00
1147.00

6057.00
Amount in Rs
6057.00

24452
24452in Rs
Amount

30509.00
2426.00

15.00

35377.00

35377.00

70754.00

322558.00
322558.00

22228.00

61.30
64.15
64.46

Assistant Executive Engineer, Ele.,


Amount in Rs

Major Works Sub Division-II, KPTCL., Belagavi.


KARNATAKA POWER TRANSMISSION CORPORATION LTD.,

Estimate for establishment of 2X10MVA , 110/11 KV Substation at Padamandi in Ramadurga Taluk, Belagavi District.

SL. No PARTICULARS Length Bredth Depth Unit (Cmt) Nos Qty Total QTY
Earth work excavation for foundation by Mechanical means for all works & depth upto 3Mtrs as per drawing and technical
specifications, including setting out, shoring, strutting, barricading, caution lights, removal of stumps and other deleterious
matter,
excavated surface leveled and sides neatly dressed disposing off the excavated stuff or sorting & stacking the selected stuff
1 for reuse in a radius of 50 m and lift upto 1.5 m including cost of labour, tools & other
appurtenaces required to complete the work.
1.15.1 In ordinary/Soft rock without blasting upto 1.5m Depth (Vol-1, Chapter-1 , Item No: 1.15.1)

Station Electrcal portion


10MVA Transformer- 3.4 4.1 1 Cmtr 2 13.94 27.880
110KV CLASS Circuit breaker- 1.87 1.87 1.5 Cmtr 2 5.24535 10.491
110KV 1T1 Station Tower - 2.5 2.5 1.5 Cmtr 6 9.375 56.250
33KV tower 3T1 - 1.45 1.45 1.5 Cmtr 0 3.15375 0.000
110 KV CT/ PT/HPI/NCT - 1.1 1.1 1.2 Cmtr 20 1.452 29.040
110KV LA / PI- 0.95 0.95 1.2 Cmtr 18 1.083 19.494
110KV isolator - 0.75 0.575 1.25 Cmtr 5 0.5390625 2.695
11kV 2.9 MVAR capacitor bank - 0.75 0.75 1.05 Cmtr 8 0.590625 4.725
11kV cable terminating structure for LV side of power transformer and capacitor bank - 0.75 0.75 1.05 Cmtr 8 0.590625 4.725
0.95 0.7 1.05 Cmtr 0 0.69825 0.000
11KV switch gear -
0.55 0.55 1.05 Cmtr 0 0.317625 0.000
Auxillary transformer platfrom - 1.6 1.6 0.5 Cmtr 1 1.28 1.280
9/9.5M RCC pole - 0.7 0.7 1.5 Cmtr 24 0.735 17.640
Lattice type yard lighting - 1.1 1.1 1.2 Cmtr 12 1.452 17.424
Earthmat formatiion - 1 0.5 0.9 Cmtr 2143 0.45 964.350
Nitrogen Fire Extinguisher system panel - 0.9 0.45 0.4 Cmtr 4 0.162 0.648
outdoor ACDB - 0.5 0.3 0.4 Cmtr 2 0.06 0.120
laying of 1x1000sqmm XLPE UG cable - 1 0.8 0.6 Cmtr 400 0.48 192.000
laying of 3x240 sqmm XLPE UG cable - 1 0.6 0.6 Cmtr 400 0.36 144.000
laying of 3x95 sqmm XLPE UG cable - 1 0.3 0.6 Cmtr 50 0.18 9.000
Total 1348.762
Earth work excavation for foundation by Mechanical means for all works & depth upto 3Mtrs as per drawing and technical
specifications, including setting out, shoring, strutting, barricading, caution lights, removal of stumps and other deleterious
matter,
excavated surface leveled and sides neatly dressed disposing off the excavated stuff or sorting & stacking the selected stuff
2 for reuse in a radius of 50 m and lift upto 1.5 m including cost of labour, tools & other
appurtenaces required to complete the work.
1.15.2 In ordinary/Soft rock without blasting Depth exceeding 1.5Mtr, But not Exceeding 3Mtrs (Vol-1, Chapter-1 , Item No:
1.15.2)

Station Electrcal portion


110KV CLASS Circuit breaker- 1.87 1.87 0.2 Cmtr 2 0.69938 1.399
110KV 1T1 Station Tower - 2.5 2.5 1.1 Cmtr 6 6.875 41.250
33KV tower 3T1 - 1.45 1.45 1 Cmtr 0 2.1025 0.000
9/9.5M RCC pole - 0.7 0.7 0.1 Cmtr 24 0.049 1.176
Total 43.825
Providing and laying in position plain cement concrete for levellingcourse for all works in foundation. The granite/trap/basalt
crushedgraded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed, laid in layers not exceeding
150 mm thickness, well compacted using plate vibrators, including all lead & lifts, cost of all materials of quality, labour,
Usage charges of machineries, curing, and all the other appurtenances required to complete the work as per technical
3 specifications. (The cost of steel reinforcement & formwork shall be paid separately)
Mix 1:4:8 Using 40 mm nominal size graded crushed coarse aggregates Vol-1, Charter-2 , Item No-2.1.2

Station Electrcal portion


10MVA Transformer- 3.4 4.1 0.1 Cmtr 2 1.394 2.788
110KV CLASS Circuit breaker- 1.87 1.87 0.1 Cmtr 2 0.34969 0.699
110KV 1T1 Station Tower - 2.5 2.5 0.1 Cmtr 6 0.625 3.750
33KV tower 3T1 - 1.45 1.45 0.1 Cmtr 0 0.21025 0.000
110 KV CT/ PT/HPI/NCT - 1.1 1.1 0.1 Cmtr 20 0.121 2.420
110KV LA / PI- 0.95 0.95 0.1 Cmtr 18 0.09025 1.624
110KV isolator - 0.75 0.575 0.1 Cmtr 5 0.043125 0.216
11KV 2.9 MVAr capacitor bank - 0.75 0.75 0.1 Cmtr 8 0.05625 0.450
11kV cable terminating structure for LV side of power transformer and capacitor bank -
0.75 0.75 0.1 Cmtr 8 0.05625 0.450
0.95 0.7 0.1 Cmtr 0 0.0665 0.000
11KV switch gear -
0.55 0.55 0.1 Cmtr 0 0.03025 0.000
Auxillary transformer platfrom - 1.6 1.6 0.1 Cmtr 1 0.256 0.256
9/9.5M RCC pole - 0.7 0.7 0.1 Cmtr 24 0.049 1.176
Lattice type yard lighting - 1.1 1.1 0.1 Cmtr 12 0.121 1.452
Nitrogen Fire Extinguisher system panel - 0.9 0.45 0.1 Cmtr 4 0.0405 0.162
outdoor ACDB - 0.5 0.3 0.1 Cmtr 2 0.015 0.030
Total 15.474
Providing and laying in position Reinforced cement concrete for all Foundation works. The granite/trap/basalt crushed graded
coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticizers laid in finished layers,
well compacted using needle vibrators, including all lead & lifts, cost of all materials, quality confirming to the requirements
of relevant IS codes , labour, Usage charges of machinery, curing and all the other appurtenances required to complete the
4 work as per technical specifications. (The cost of steel reinforcement & formwork to be paid separately) 2.2.1.1 M20 Design
Mix Using 20 mm nominal size graded crushed coarse
aggregates Vol-1, Chapter-2 Item No-2.2.1

Station Electrcal portion


10MVA Transformer- 3.1 3.8 1.2 Cmtr 2 14.136 28.272
110KV CLASS Circuit breaker- Raft 1.72 1.72 0.3 Cmtr 2 0.88752 1.775
110KV CLASS Circuit breaker- Column 0.97 0.97 1.8 Cmtr 2 1.69362 3.387
110KV 1T1 Station Tower - Raft 2.5 2.5 0.3 Cmtr 6 1.875 11.250
110KV 1T1 Station Tower -Column 1.3 1.3 2.5 Cmtr 6 4.225 25.350
33KV tower 3T1 - Raft 1.3 1.3 0.3 Cmtr 0 0.507 0.000
33KV tower 3T1 - Column 1 1 2.3 Cmtr 0 2.3 0.000
110 KV CT/ PT/HPI/NCT - Raft 0.9 0.9 0.2 Cmtr 20 0.162 3.240
111 KV CT/ PT/HPI/NCT - Column 0.6 0.6 0.9 Cmtr 20 0.324 6.480
110KV LA / PI-Raft 0.9 0.9 0.2 Cmtr 18 0.162 2.916
110KV LA / PI-Column 0.45 0.45 0.9 Cmtr 18 0.18225 3.281
110KV isolator - Raft 0.65 0.475 0.3 Cmtr 5 0.092625 0.463
110KV isolator - Column 0.45 0.275 1.3 Cmtr 5 0.160875 0.804
11KV 2.9 MVAR capacitor bank -Raft 0.65 0.65 0.2 Cmtr 8 0.0845 0.676
11KV 2.9 MVAR capacitor bank -Column 0.5 0.5 1.1 Cmtr 8 0.275 2.200
11KV cable terminating structure for LV side of power transformer and capacitor bank - Raft 0.65 0.65 0.2 Cmtr 8 0.0845 0.676

11KV cable terminating structure for LV side of power transformer and capacitor bank - Column 0.5 0.5 1.1 Cmtr 8 0.275 2.200
0.95 0.7 0.2 Cmtr 0 0.133 0.000
11KV switch gear - Raft
0.55 0.55 0.2 Cmtr 0 0.0605 0.000
0.9 0.6 1.1 Cmtr 0 0.594 0.000
11KV switch gear - Column
0.45 0.45 1.1 Cmtr 0 0.22275 0.000
Auxillary transformer platfrom 1.6 1.6 0.1 Cmtr 1 0.256 0.256
9/9.5M RCC pole - Raft 0.6 0.6 0.2 Cmtr 24 0.072 1.728
9/9.5M RCC pole - Column 0.5 0.5 1.6 Cmtr 24 0.4 9.600
Lattice type yard lighting -Raft 0.9 0.9 0.2 Cmtr 12 0.162 1.944
Lattice type yard lighting -Column 0.6 0.6 0.9 Cmtr 12 0.324 3.888
Nitrogen Fire Extinguisher system panel - 0.8 0.35 0.7 Cmtr 4 0.196 0.784
outdoor ACDB - 0.6 0.35 0.7 Cmtr 2 0.147 0.294
Total 111.464
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations and other similar works etc. in layers
5 not exceeding 20cm in depth, consolidating each deposited layer by ramming and
watering, lead up to 50 m and lift upto 1.5 m.Vol-1,7/1.9
Station Electrcal portion
110KV CLASS Circuit breaker- Cmtr 2 6.73 13.460
110KV 1T1 Station Tower - Cmtr 6 10.15 60.900
33KV tower 3T1 - Cmtr 0 2.45 0.000
110 KV CT/ PT/HPI/NCT - Cmtr 20 0.966 19.320
110KV LA / PI- Cmtr 18 0.739 13.302
110KV isolator - Cmtr 5 1.71 8.550
11KV 2.9 MVAR capacitor bank - Cmtr 8 0.925 7.400
11KV cable terminating structure for LV side of power transformer and capacitor bank - Cmtr 8 0.925 7.400
9/9.5M RCC pole - Cmtr 24 0.384 9.216
Lattice type yard lighting - Cmtr 12 0.966 11.592
Formation of earthmat Cmtr 2143 0.3 642.900
laying of 1x1000sqmm XLPE UG cable - Cmtr 400 0.46 182.370
laying of 3x240 sqmm XLPE UG cable - Cmtr 400 0.34 137.500
laying of 3x95 sqmm XLPE UG cable - Cmtr 50 0.07 3.687
Total 1117.60
Filling approved earth (excluding rock) in trenches, plinth, sides of foundations and other similar works etc. in layers not
exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m.
6 1 0.5 0.3 Cmtr 2143 0.15 321.450

Providing Thermo-Mechanically Treated bars of grade Fe-500D or more Steel reinforcement for R.C.C. work including
straightening, cutting, bending, placing in position, binding and anchoring to adjacent members whereever necessary
7 complete as per Design including cost of material, labour, usage charges complete as per specifications. (The
laps and wastages shall not be measured separately) Vol-2,84/11.32

Station Electrcal portion


10MVA Transformer- Cmtr 2 1413.6 2827.200
110KV CLASS Circuit breaker- Cmtr 2 516 1032.000
110KV 1T1 Station Tower - Cmtr 6 610 3660.000
33KV tower 3T1 - Cmtr 0 281 0.000
110 KV CT/ PT/HPI/NCT - Cmtr 20 48.6 972.000
110KV LA / PI- Cmtr 18 34.4 619.200
110KV isolator - Cmtr 5 152.1 760.500
11KV 2.9 MV AR capacitor bank - Cmtr 8 143.8 1150.400
11KV cable terminating structure for LV side of power transformer and capacitor bank -
Cmtr 8 143.8 1150.400
11KV switch gear - Cmtr 0 129 0.000
Auxillary transformer platfrom - Cmtr 1 22.5 22.500
9/9.5M RCC pole - Cmtr 24 40 960.000
Lattice type yard lighting - Cmtr 12 48.6 583.200
Nitrogen Fire Extinguisher system panel - Cmtr 4 19.6 78.400
outdoor ACDB - Cmtr 2 14.7 29.400
Total 13845.200
Assistant Engineer, Ele., Assistant Executive Engineer, Ele.,
Major Works Sub Division-II, KPTCL., Belagavi. Major Works Sub Division-II, KPTCL., Belagavi.
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED

Estimate for establishment of 2X10MVA , 110/11 KV Substation at Padamandi in Ramadurga Taluk, Belagavi District.
Sl.
Particulars Unit Qty. Base Rate Amount
No.

Earth work in surface excavation by mechanical means for lowering & leveling the ground for all works other than
foundation in all kinds of soils & upto depth not exceeding 300mm as per drawing and technical specifications, including
setting out, shoring, strutting, barricading, caution lights, removal of stumps and other deleterious matter including
dressing of excavated surfaces, disposing off or levelling the excavated earth or sorting & stacking the selected earth for
B1 cmt 272.5 95.00 25887.50
reuse in a radius of 50 m and lift upto 1.5 m including cost of labour, tools, usage of machinery & other appurtenances
required to complete the work. (V1/Pg8/1.12)
In all kinds of soils upto 300 mm depth F.G.L Considered as Road Level +0.3m= 633.330m (A Copy of statement is
enclosed)

Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical
specifications, including setting out, shoring, strutting, barricading, caution lights, including dressing of excavated
surfaces, disposing off or levelling the excavated earth or sorting & stacking the selected earth for reuse in a radius of 50 m
B2 and lift upto 1.5 m including cost of labour, tools, usage of machinery & other appurtenaces required to complete the work cmt 2714.22 102.00 276850.44
(V1/Pg8/1.14.1)
In all kinds of soils Depth upto 3 m depth F.G.L Considered as Road Level +0.3m= 633.330m (A Copy of statement is
enclosed)

Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical
specifications, including setting out, shoring, strutting, barricading, caution lights, including dressing of excavated
surfaces, disposing off or levelling the excavated earth or sorting & stacking the selected earth for reuse in a radius of 50 m
B3 cmt 1459.26 363.00 529712.11
and lift upto 1.5 m including cost of labour, tools, usage of machinery & other appurtenaces required to complete the work
(V1/Pg8/1.15.1)
In ordinary/soft rock without blasting upto 1.5 m depth
Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical
specifications, including setting out, shoring, strutting, barricading, caution lights, including dressing of excavated
surfaces, disposing off or levelling the excavated earth or sorting & stacking the selected earth for reuse in a radius of 50 m
B4 cmt 143.82 425.00 61125.52
and lift upto 1.5 m including cost of labour, tools, usage of machinery & other appurtenaces required to complete the work
(V1/Pg8/1.15.2)
In ordinary/soft rock Depth exceeding 1.5 m, but not exceeding 3 m
Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical
specifications, including setting out, shoring, strutting, barricading, caution lights, including dressing of excavated
surfaces, disposing off or levelling the excavated earth or sorting & stacking the selected earth for reuse in a radius of 50 m
B5 cmt 100.00 554.00 55400.00
and lift upto 1.5 m including cost of labour, tools, usage of machinery & other appurtenaces required to complete the work
(V1/Pg8/1.16.1)
In hard Rock ( requiring blasting) Depth upto 1.50m
Sl.
Particulars Unit Qty. Base Rate Amount
No.

Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical
specifications, including setting out, shoring, strutting, barricading, caution lights, including dressing of excavated
surfaces, disposing off or levelling the excavated earth or sorting & stacking the selected earth for reuse in a radius of 50 m
B6 cmt 100.00 623.00 62300.00
and lift upto 1.5 m including cost of labour, tools, usage of machinery & other appurtenaces required to complete the work
(V1/Pg8/1.16.12)
In hard Rock ( requiring blasting) Depth exceeding 1.5 m, but not exceeding 3 m

Construction of Embankment by excavating the available approved Gravel/ Murrum deposited at a place or borrow pits
during or prior excavation with all lifts and lead, transportation to site, spreading, grading to required slope and
compacting to meet the requirement complete as per specifications, including cost of labour,rolling,water,all
materials,usage& all other appurtenaces requiredto complete the work. If the height of embankment construction is more
B7 cmt 5932.51 474.00 2812009.74
than 1.50 m add 5% per m³ for every 1.50 m height or part there of Deduct 5% per m³ if rollers are not used and tamping is
done manually
Add 8% per m³ for works under foul & sullage situation. F.G.L Considered as Road Level +0.3m= 633.330m (A Copy of
statement is enclosed)

Providing and laying in position Cement Concrete for levelling course for all works in foundation. The granite/trap/basalt
crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed, laid in layers not exceeding
B8 150 mm thickness, well compacted using plate vibrators, including all lead & lifts, cost of all materials of quality, labour, cmt 311.54 5664.00 1764582.41
Usage charges of machinery, curing, and all the other appurtenances required to complete the work as per technical
specifications. Mix 1:4:8 Using 40 mm nominal size graded crushed coarse aggregates (V1/Pg15/2.1.2)

Cattle Trap-1.70

Providing and laying in position Cement Concrete for all Foundation works. The granite/trap/basalt crushed graded
coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticizers laid in finished
layers, well compacted using needle vibrators, including all lead & lifts, cost of all materials, quality confirming to the
B9 cmt 209.17 6475.61 1354531.06
requirements of relevant IS codes, labour, Usage charges of machinery, curing, form work, centering & scaffolding and all
the other appurtenances required to complete the work as per technical specifications (V1/Pg15/2.2.1)
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates For foundation add at 3%

Providing and laying in position Cement Concrete for all Foundation works. The granite/trap/basalt crushed graded
coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticizers laid in finished
layers, well compacted using needle vibrators, including all lead & lifts, cost of all materials, quality confirming to the
B10 cmt 34.80 8487.45 295363.26
requirements of relevant IS codes, labour, Usage charges of machinery, curing, form work, centering & scaffolding and all
the other appurtenances required to complete the work as per technical specifications (V1/Pg15/2.2.1)
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates For foundation of drains add at 35%
Sl.
Particulars Unit Qty. Base Rate Amount
No.

Providing and laying in position Cement Concrete for all Foundation works. The granite/trap/basalt crushed graded
coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticizers laid in finished
layers, well compacted using needle vibrators, including all lead & lifts, cost of all materials, quality confirming to the
B11 requirements of relevant IS codes, labour, Usage charges of machinery, curing, form work, centering & scaffolding and all cmt 66.63 6915.70 460793.09
the other appurtenances required to complete the work as per technical specifications (V1/Pg15/2.2.1)
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates For foundation of retaining wall add at
10% for formwork

Providing and laying in position Cement Concrete for all Foundation works. The granite/trap/basalt crushed graded
coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticizers laid in finished
layers, well compacted using needle vibrators, including all lead & lifts, cost of all materials, quality confirming to the
B12 cmt 6.26 10687.90 66906.25
requirements of relevant IS codes, labour, Usage charges of machinery, curing, form work, centering & scaffolding and all
the other appurtenances required to complete the work as per technical specifications (V1/Pg15/2.2.1)
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates For column upto PB add at 70%

Providing and laying in Cement Concrete for all Basement & surface level works, return walls, retaining walls, sunken
floors etc. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant
IS Codes machine mixed with super plasticisers, laid in layers, well compacted using needle vibrators, providing weep
holes wherever necessary, including all lead & lifts, cost of all materials of quality, labour, Usage charges of machinery,
B13 cmt 4.56 9484.50 43249.32
curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical
specifications.
(V1/Pg16/2.3.1)
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates For PB add at 50%

Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works,
Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse
aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well
compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the
B14 cmt 12.39 10608.00 131433.12
requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all
other appurtenances required to complete the work as per technical specifications. (V1/Pg16/2.5.1)
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates For Beams & lintels add at 60% Ground
floor

Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works,
Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse
aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well
compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the
B15 cmt 0.00 10714.08 0.00
requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all
other appurtenances required to complete the work as per technical specifications. (V1/Pg16/2.5.1)
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates For Beams & lintels add at 60% - First
Fllor
Sl.
Particulars Unit Qty. Base Rate Amount
No.

Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works,
Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse
aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well
compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the
B16 cmt 12.29 11271.00 138520.59
requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all
other appurtenances required to complete the work as per technical specifications. (V1/Pg16/2.5.1)
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates For columns of super structure add at
70% Ground floor

Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works,
Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse
aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well
compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the
B17 cmt 0.00 11383.71 0.00
requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all
other appurtenances required to complete the work as per technical specifications. (V1/Pg16/2.5.1)
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates For columns of super structure add at
70% - First floor

Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works,
Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse
aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well
B18 compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the cmt 39.18 9945.00 389645.10
requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all
other appurtenances required to complete the work as per technical specifications. (V1/Pg16/2.5.1)
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates For Roof slab add at 50% - Ground floor

Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works,
Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse
aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well
B19 compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the cmt 0.00 10044.45 0.00
requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all
other appurtenances required to complete the work as per technical specifications. (V1/Pg16/2.5.1)
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates For Roof slab add at 50% -First Floor
Sl.
Particulars Unit Qty. Base Rate Amount
No.

Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works,
Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse
aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well
compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the
B20 cmt 9613.50 0.00
requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all
other appurtenances required to complete the work as per technical specifications. (V1/Pg16/2.5.1)
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates For Chejjas & Canopy of CRB add at 45%
for formwork

Providing and laying in position Cement Concrete for levelling course for all works in foundation. The granite/trap/basalt
crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed, laid in layers not exceeding
150 mm thickness, well compacted using plate vibrators, including all lead & lifts, cost of all materials of quality, labour,
B21 cmt 52.3 6527.85 341406.56
Usage charges of machinery, curing, form work, centering & scaffolding and all the other appurtenances required to
complete the work as per technical specifications. Mix 1:3:6 Using 20 mm nominal size graded crushed coarse aggregate
for DPC sill coping & screed concrete add at 5% (V1/Pg15/2.14)

Providing and laying in position Cement Concrete for levelling course for all works in foundation. The granite/trap/basalt
crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed, laid in layers not exceeding
150 mm thickness, well compacted using plate vibrators, including all lead & lifts, cost of all materials of quality, labour,
B22 cmt 52.63 6217.00 327200.71
Usage charges of machinery, curing, form work, centering & scaffolding and all the other appurtenances required to
complete the work as per technical specifications. Mix 1:3:6 (M10) Using 20 mm nominal size graded crushed coarse
aggregates for plinth protection & floor concrete of CRB (V.1, I.No.2.1.4, P.No.15)

Construction of M40 Grade un-reinforced, dowel jointed, plain cement concrete pavement over a prepared sub base in
recommended proportions, coarse and fine aggregate conforming to IS 383:2016, maximum size of coarse aggregate not
exceeding 25 mm, mixed in a batching and mixing plant as per approved mix design transported to site, laid with a slip
form paver finisher, spread, compacted and finished in a continuous operation including provision of contraction,
B23 cmt 112.5 9514.05 1070330.63
expansion, construction and longitudinal joints, joint filler, separation membrane, sealant primer, joint sealant, debonding
strip, dowel bar, tie rod, admixtures, curing, form work, centering & scaffolding compound, steel channels, finishing to
lines and grades as per drawing (I.No.6.2.1 P.N.49, V3)
M40 OPC @ 420 kg/m3 For Road add at 5% formwork

Providing Size Stone masonry with hard stone in foundation & plinth with Cement mortar 1:6 (1 cement : 6 coarse sand)
B24 cmt 697.34 6389.00 4455305.26
(V2/Pg9/5.4)
Providing Brick work with common burnt clay Non Modular bricks of class designation 3.5 in superstructure above
plinth level in all shapes and sizes in Cement mortar 1:6 (1 cement : 6 coarse sand) including cost of all materials, labour,
B25 CMT 78.22 7969.00 623335.18
scaffolding and usage charges of machinery & other incidental charges complete as per the direction of engineer incharge
of work. (V2/Pg14/6.8)
Providing and constructing load bearing wall with Solid Concrete blocks of size 400x200x200mm having block density
more than 1800kg/m3 and minimum compressive strength of 4.00 N/mm2 conforming to IS 2185 (Part - I) - 2005 and
B26 SMT 873.15 1310.00 1143826.50
constructed with CM 1:4 as per IS 2572:2005 including cost of all materials, labour, scaffolding and curing, usage charges of
machinery etc complete as per specifications (V2/Pg17/6.32)
Sl.
Particulars Unit Qty. Base Rate Amount
No.

Providing and fixing Heat Resistant Terrace Tiles (300 mm x 300 mm x 20 mm) with SRI (solar refractive index) > 78, solar
reflection > 0.70 and initial emittance > 0.75 on waterproof and sloped surface of terrace, laid on 20 mm thick cement sand
B27 mortar in the ratio of 1:4 (1 cement : 4 coarse sand) and grouting the joints with mix of white cement & marble powder in SMT 155.00 1405.00 217775.00
ratio of 1:1, including rubbing and polishing of the surface upto 3 cuts complete, including providing skirting upto 150 mm
height along the parapet walls in the same manner as per direction of incharge V2/Pg29/7.46)

Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations and other similar works etc. in
B28 layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift CMT 1489.36 266.00 396169.20
upto 1.5 m. (V1/Pg7/1.9)

Refilling available earth around trenches/pipelines, cables in layers not exceeding 20 cms in depth, compacting each
B29 deposited layer by ramming after watering with a lead upto 50 m, and lift upto 1.5 m. Including cost of all labour complete Cmt 150 160.00 24000.00
as per specifications (V1/Pg7/1.10)

Filling approved earth (excluding rock) in trenches, plinth, sides of foundations and other similar works etc. in layers not
B30 Cmt 321.45 433.00 139187.85
exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m.

FALSE CEILING
Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections,
power pressed from M.S. sheets and galvanized with zinc coating of 120 g/m2 (both side inclusive) as per IS : 277 and
consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37mm, at 1200 mm centre to centre,
one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed
to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger
fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the
ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450
mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out
B30 of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high SMT 0.00 1146.00 0.00
having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450
mm centre, with 25mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and
perimeter channel with the help of dry wall screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and finishing to a
flush finish of tapered and square edges of the board with recommended jointing compound, jointing tapes , finishing with
jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as
per manufacturer's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts
made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the
Engineer in Charge but excluding the cost of painting with with 12.5 mm thick tapered edge gypsum moisture resistant
board (V2/Pg25/7.32.3)
Sl.
Particulars Unit Qty. Base Rate Amount
No.
Providing 15 mm cement plaster on rough side of single or half brick wall finished with a floating coat of neat cement of
mix: 1:4 (1 cement: 4 fine sand) to brick masonry including rounding off corners wherever required smooth rendering,
B31 SMT 804.20 349.00 280665.80
providing and removing scaffolding, including cost of materials, labour, curing complete as per specifications and as per
directions of Engineer-in-charge. (V2/Pg42/8.5.2)

Providing 20 mm cement plaster of mix :1:4 (1 cement: 4 fine sand) to brick/stone masonary including rounding off
B32 corners wherever required smooth rendering, providing and removing scaffolding, including cost of materials, labour, SMT 2058.83 354.00 728825.82
curing complete as per specifications and as per directions of Engineer-in-charge (V2/Pg41/8.3.1)
Sl.
Particulars Unit Qty. Base Rate Amount
No.
Providing Flush/ Ruled pointing: Pointing on stone work with cement mortar 1:3 (1 cement : 3 fine sand) after raking joints
B33 to depth nicely lining, including cost of materials, labour, curing as per specifications and as SMT 572.96 255.00 146104.80
per directions of Engineer-in-charge. (V2/Pg44/8.19.1)
Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear
portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average)
thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white
B34 SMT 128.00 2852.00 365056.00
cement slurry admixed with pigment of matching shade including rubbing , curing and polishing etc. all complete as
specified and as directed by the Engineer-in-Charge. ** Polished Granite stone slab Black, Cat Eye, River Pink or
equivalent.. (V2/Pg63/9.24)

Providing and fixing 10 mm thick acid and/or alkali resistant tiles of approved make and colour using acid and/or alkali
resisting mortar bedding for Bathrooms: Toilet: Chemically exposed areas and joints filled with acid
B35 and/or alkali resisting cement as per IS : 4457, complete as per the direc tion of Engineer-in- Charge. SMT 12.75 1246.00 15886.50
In flooring on a bed of 10 mm thick mortar 1:4 (1 acid proof cement : 4 coarse sand) with Acid and alkali resistant tile
(V2/Pg59/ 9.7.1)

Providing and fixing 10 mm thick acid and/or alkali resistant tiles of approved make and colour using acid and/or alkali
resisting mortar bedding for Bathrooms: Toilet: Chemically exposed areas and joints filled with acid and/or alkali resisting
cement as per IS : 4457, complete as per the direction of Engineer-in- Charge.
B36 SMT 58.00 1260.00 73080.00
In dado/skirting on 12 mm thick mortar 1:4 (1 acid proof cement : 4 coarse sand) with Acid and alkali resistant tile
(V2/Pg60/9.7.2)

Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thick ness to be specified by the manufacturer), of 1st
quality conforming to IS : 15622, of approved make, in all colours, shades, except White, Ivory, Grey, Fume Red Brown, laid
B37 SMT 4.98 889.00 4427.22
on 20 mm thick bed of cement mortar 1:4 (1 Cement : 4 Coarse sand), jointing with grey cement slurry @ 3.3 kg/ m2
including pointing the joints with white cement and matching pigments etc., complete (V2/Pg60/9.11)

Providing skirting, dadooing, rises of steps with white glazed tiles 6mm thick on 10mm thick cement plaster 1:3 and
B38 jointed with white cement slurry over existing rough plaster surface using glazed tiles of approved make and size smt 50.60 1392.00 70435.20
including cost of materials, labour, complete as per specifications. (V2/Pg65/9.38)
Providing and laying Vitrified tiles in different sizes (thickness to be specified by manufacturer), with water absorption less
than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, over 12 mm thick bed of cement mortar
B39 smt 57.00 1392.00 79344.00
1:3 (1 cement: 3 coarse sand), jointing with grey cement slurry @ 3.3 kg/ m2 including grouting the joint with white cement
& matching pigments etc. complete

Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over
B40 the plastered wall surface to prepare the surface even and smooth complete as per specifications and as per directions of smt 357.00 100.00 35700.00
Engineer in charge-inside (V2/Pg50/8.51)
Sl.
Particulars Unit Qty. Base Rate Amount
No.

Finishing walls with 100% Premium acrylic emulsion paint having VOC less than 50 gm/litre and UV resistance as per IS
15489:2004, Alkali & fungal resistance, dirt resistance exterior paint of required shade (Company Depot Tinted) with silicon
additives, New work (Two coats applied @ 1.43 litre/ 10 m². Over and including priming coat of exterior primer applied @
B41 smt 520.00 156.00 81120.00
0.90 litre/10 m² with paint of approved quality to give an even shade, after thoroughly brooming the surface to remove all
dirt, dust, mortar drops and foreign matter including preparing the surface even and sand paper smooth, cost of materials,
labour complete as per specifications and as per directions of Engineer-in-charge. (V2/Pg46/8.32)

Finishing walls with Acrylic Smooth exterior paint of required shade :New work (Two coat applied @ 1.67 ltr/10 m² over
and including priming coat of exterior primer applied @ 2.20 kg/10 m²) with paint of approved quality to give an even
B42 shade, after thoroughly brooming the surface to remove all dirt, dust, mortar drops and foreign matter smt 2750.45 174.00 478578.30
including preparing the surface even and sand paper smooth, cost of materials, labour complete as per specifications and as
per directions of Engineer-in-charge. (V2/Pg46/8.30)

Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade :Two
coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture after
B37 thoroughly brooming the surface to remove all dirt, dust, mortar drops and foreign matter including preparing the surface smt 348.00 167.00 58116.00
even and sand paper smooth, cost of materials, labour complete
as per specifications and as per directions of Engineer-in-charge (V2/Pg48/8.41)

Providing and laying to required line and slope roofing with corrugated asbestos cement sheet 6mm. thick fixed with
B38 galvanised iron J or L hooks, bolts and nuts 8mm. dia C.I plain and bitumen washers over the existing purlins, rafters and Sqmtr 211.00 332.00 70052.00
trusses including cost of materials, labour, complete as per specification V2/Pg23/7.17)

Providing and fixing ridges, hips with asbestos cement sheet roofing with G.I. J or L hooks, bolts and nuts 8mm . dia
B39 G.I.plain and bitumen washers, serrated or plain wings, adjustable ridges, including cost of materials, M 20.00 299.00 5980.00
labour, complete as per specification( V2/Pg23/7.21)
Steel Fabrication: Supplying, fitting and placing TMT FE 550 / 550D Steel Reinforcement including cost of all materials,
machinery, labour, cleaning, straightening, cutting, bending, hooking, laping/welding joints, tying with binding wire /
B40 kg 10300.00 89.46 921438.00
soft annealed steel wire and other ancilary operations complete as per drawing and technical specification Buildings
(V1/Pg18/2.11a)
Steel Fabrication: Supplying, fitting and placing TMT FE 550 / 550D Steel Reinforcement including cost of all materials,
machinery, labour, cleaning, straightening, cutting, bending, hooking, laping/welding joints, tying with binding wire /
B41 kg 28146.95 79.01 2223890.52
soft annealed steel wire and other ancilary operations complete as per drawing and technical specification All other type of
structures (V1/Pg18/2.11h)
Providing and fixing in position collapsible steel shutters with vertical channels 20x10x2 mm and braced with flat iron
diagonals 20x5 mm size, with top and bottom rail of T-iron 40x40x6 mm, with 40 mm dia steel pulleys, complete with bolts,
B42 nuts, locking arrangement, stoppers, handles, including applying a priming coat of approved steel primer including cost of smt 6.00 8276.00 49656.00
materials ,labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-
Charge. (V2/Pg77/11.3)
Sl.
Particulars Unit Qty. Base Rate Amount
No.

Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard
tubular sections/appropriate sections and other sections of approved make conforming to IS: 733 and IS:1285, fixing with
dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides
with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and
jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P.
B43 brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, kg 380.00 571.00 216980.00
paneling and dash fasteners to be paid for separately) :For shutters of doors, windows & ventilators including providing
and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM
rubber / neoprene gasket required (Fittings shall be paid for separately) Powder coated aluminium (minimum thickness of
powder coating 50 micron) including cost of materials, labour, usage charges of machinery complete as per specifications.
(V2/Pg88/11.35.2.2)

Providing and fixing double action hydraulic floor spring of approved brand manufacture conforming to IS : 6315, having
brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kg, for doors,
including cost of cutting floors, embedding in floors as required and making good the same matching to the existing floor
B43 Each 4.00 2804.00 11216.00
finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the
direction of Engineer-in-charge: With brass cover plate minimum 1.25 mm thickness including cost of materials, labour,
usage charges of machinery complete as per specifications.. (V2/Pg90/11.38.2.)

Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board
conforming to IS: 12823 Grade l Type ll, in panelling fixed in aluminum doors, windows shutters and partition frames with
B44 C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of ngineer-in charge: Pre- smt 4.00 983.00 3932.00
laminated particle board with decorative lamination on one side and balancing lamination on other side including cost of
materials, labour, usage charges of machinery complete as per specifications.(V2/Pg89/11.36.1.)

Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber /
neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of
B45 smt 38.00 1171.00 44498.00
aluminium snap beading shall be paid in basic item):With float glass panes of 5 mm thickness (weight not less than 12.50
kg/m²) including cost of materials, labour, usage charges of machinery complete as per specifications (V2/Pg89/11.37.2)

Providing and fixing aluminium tubular handle bar 32 mm outer dia,3.0 mm thick & 2100 mm long with SS screws
etc .complete as per direction of Engineer-in-Charge.: Polyester powder coated minimum thickness 50 micron aluminium
B46 Nos 12.00 659.00 7908.00
tubular handle bar including cost of materials, labour, usage charges of machinery complete as per specifications.
(V2/Pg92/11.46.3)
Providing and fixing bright finished brass butt hinges with necessary screws etc. Complete-125x85x5.5 mm (heavy type)
B47 Nos 6.00 275.00 1650.00
(V2/Pg107/12.75.1)
CRB-6

Providing and fixing bright finished brass tower bolts (barrel type) with necessary screws etc. complete : 250x10mm
B48 Each 4.00 435.00 1740.00
(V2/Pg107/12.76.1)
Sl.
Particulars Unit Qty. Base Rate Amount
No.

Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board
conforming to IS: 12823 Grade l Type ll, in panelling fixed in aluminum doors, windows shutters and partition frames with
B49 C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of ngineer-in charge: Pre- Sqm 4.00 897.00 3588.00
laminated particle board with decorative lamination on one side and balancing lamination on other side including cost of
materials, labour, usage charges of machinery complete as per specifications. (V2/Pg89/11.36.2)

Filling the gap in between aluminium/ stone/ wood frame and adjacent RCC/Brick/ Stone/ wood/ Ceramic/ Gypsum
work by providing weather/structural non sag elastomeric PU sealant over backer rod of approved quality as per
B50 architectural drawings and direction of Engineer-in-charge complete, complying to ASTM C920, DIN 18540- F & ISO 11600 m 166.00 296.00 49136.00
Upto 20 mm depth and 20 mm width including cost of materials, labour, usage charges of machinery complete as per
specifications.(V2/Pg94/11.53.3)
Providing and fixing Brass 100mm mortice latch and lock with 6 levers without pair of handles (best make of approved
B51 quality) for aluminium doors including necessary cutting and making good etc. complete including cost of materials, No 4.00 437.00 1748.00
labour, usage charges of machinery complete as per specifications (V2/Pg93/11.47)

Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS :
B52 No 6.00 130.00 780.00
1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete (V2/Pg105/12.63)

Providing and fixing sliding window lock, ISI marked, transparent or dyed to required colour or shade, with necessary
B53 No 6.00 200.00 1200.00
screws etc. Complete (Market rate)

Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding,
grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel
nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts
B54 etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer- kg 310.00 565.00 175150.00
in- charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories
such as nuts bolts, fasteners etc.) including cost of materials, labour, usage charges of machinery complete as per
specifications and as per directions of the Engineer-in-Charge (V2/Pg85/11.28)

Providing & fixing 30mm thick factory made rigid foam Prelam Panelled Door Shutters made from M.S. tube of 19x19mm,
19 gauge for stiles and 15x15mm for top & bottom rails, covered with heat moulded Prelaminated PVC C Channel of 5mm
thick sheet & 30x50mm wide to form stiles & 5mm thick & 75mm wide Prelaminated PVC Sheets for top rail, lock rail &
bottom rail on either side & 5mm thick, 20mm wide cross PVC sheet as gap insert for top rail & bottom rail, Panelling of
B55 smt 2366.00 0.00
5mm thick PVC sheet Prelaminated on either side fitted in the M.S. frame, Sealed to the stiles & rails with PVC Designer
beading on either side & joined together with solvent cement adhesive etc., Complete as per manufacturers specification &
direction of Engineer-in-charge fixed to frames with 3 nos of 75mm Aluminium hinges. with both side prelam
(V2/Pg104/12.55.1)

Providing Mathi/Nandi wood frames of doors, windows, clerestory windows, ventilators and other frames, wrought,
B56 framed or assembled including making plaster groves (excluding cost of cement concrete and side clamps ), but including Cum 0.10 124202.00 12420.20
cost of materials, labour, usage charges complete as per specifications.) (V2/Pg99/12.12)
Sl.
Particulars Unit Qty. Base Rate Amount
No.

Providing and fixing flush door shutter made out of solid core block board type, well seasoned , chemicaly treated hard
wood battens and internal frame with minimum 45 mm wide wooden frame alround door shutters covered with cross
B57 bonded wooden sheets (core veneer) hot pressed and fastened on both sides of the door useing liquid phenol formaldehyde smt 3.50 3005.00 10517.50
resin as per IS specifications 2202 (part-I) 1991. from manufacturer complete as per spcification.--do- 30 mm thick both side
commercial composite polymer laminated sal wood shutter (V2/Pg105/12.57.3)

Providing & fixing factory made PVC Door frame of size 50x47mm with a wall thickness of 5mm, made out of extruded
5mm rigid PVC foam sheet metered cut at corners & jointed 2 No.s of 150mm long brackets of 15x15mm M.S Square tube,
B58 the entire door frame to be reinforced with 19x19mm M.S Square tube of 19 gauge. The door frame to be fixed to the wall m 0.00 318.00 0.00
using M.S. Screws of 65/80mm size complete as per manufacturers specification & direction of Engineer-in-charge.
(V2/Pg104/12.54)

Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through
their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets,
side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of
B59 providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength smt 2633.00 0.00
conforming to IS: 4454 - part 1 and M.S. top cover of required thickness for rolling shutters. 80x1.25 mm M.S. laths with 1.25
mm thick top cover including cost of materials, labour, usage charges of machinery complete as per specifications and as
per directions of the Engineer-in-Charge. (V2/Pg78/11.6.1)

Supplying PVC ringtite pipes conforming to IS 4985:2000 with latest amendments and conveying to worksite, rolling and
lowering into trenches, laying true to line and level and perfect linking at joints, testing and commissioning, including
loading unloading at both destinations and cuts of pipes wherever necessary including jointing of PVC pipes and specials
B60 (excluding cost of specials) with jointing of approved type, with all labour with all lead & lift including encasing the pipe Rmtr 460.00 411.00 189060.00
alround to a depth of not less than 15 cms. with soft gravel or selected earth available from the excavation etc. complete and
giving necessary hydraulic test to the required pressure as per ISS (Contractor will make his own arrangements for
procuring water for testing) etc. for: PVC pipes 110mm dia., 6 kg/sqcm & class 3 (V5/Pg102/10.1.7)

Supplying, lowering, laying, jointing, testing and commissioning of Glazed Stone Ware Pipes of following dia, conforming
to IS 651:1992, IS 4127 with latest amendments, including conveying to work site, caulking with hemp dipped in tar and
jointing with CM 1:1.5 using OPC, perfect linking and curing for 10 days and testing with water etc. with all lead, lifts and
B61 Rmtr 50.00 466.00 23300.00
as per Technical Specifications. The cost to include the cost of all jointing materials, necessary survey works for laying of
sewer lines etc. complete. The contractor will make own arrangements for procuring water for testing 150 mm dia. pipes
(V.5,SOR code T030B P.No. 184)

Providing and fixing water closet squatting pan (Indian type W.C. pan ) with 100 mm sand cast Iron P or S trap, 10 litre
low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to
B62 IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and Each 2.00 4884.00 9768.00
floors wherever required:. White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests
(V2/Pg131/14.1.1)
Sl.
Particulars Unit Qty. Base Rate Amount
No.
Providing and fixing white vitreous china flat back or wall corner type lipped front urinal basin of 430x260x350 mm and
340x410x265 mm sizes respectively with automatic flushing cistern with standard flush pipe and C.P. brass spreaders with
B63 brass unions and G.I clamps complete, including painting of fittings and brackets, cutting and making good the walls and Each 0.00 6784.00 0.00
floors wherever required. Range of two urinal basins with 5 litre white P.V.C. automatic flushing cistern.
(Vo2/Pg131/14.4.2)

Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard
B64 pattern, including painting of fittings and brackets, cutting and making good the walls wherever require:. White Vitreous Each 2.00 3082.00 6164.00
China Wash basin size 630x450 mm with a pair of 15 mm C.P. brass pillar taps (V2/Pg132/14.7.1)

Providing and fixing mirror of superior glass (of approved quality) and of required shape and size with plastic moulded
B65 frame of approved make and shade with 6 mm thick hard board backing : Oval shape 450x350 mm (outer dimensions) Each 2.00 1066.00 2132.00
(V2/Pg136/14.32.3)
Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS: 12701 marked, with cover and
B66 suitable locking arrangment and making necessary holes for inlet, outlet and overflow pipes but without fitting and the L 2000.00 9.00 18000.00
base support for tank. (V2/Pg123/13.34)
Providing, Laying and Fixing GI pipes conforming to IS 1239:1990 with latest amendments complete with GI fittings
(excluding the cost of fittings) with cuts and threads wherever necessary, including testing for water tightness, with all lead
B67 Rmtr 50.00 363.00 18150.00
and commissioning. (contractor will make his own arrangements for procuring water for testing) For Heavy Duty GI pipe
of 20mm dia (V.5, SOR code. N020B,C & F, P.No. 142) (V.5/Pg110/11.3.2)
Providing, Laying and Fixing GI pipes conforming to IS 1239:1990 with latest amendments complete with GI fittings
(excluding the cost of fittings) with cuts and threads wherever necessary, including testing for water tightness, with all lead
B68 Rmtr 50.00 359.00 17950.00
and commissioning. (contractor will make his own arrangements for procuring water for testing) For Heavy Duty GI pipe
of 25mm dia for CRB (V/Pg110/11.3.3)
Providing, Laying and Fixing GI pipes conforming to IS 1239:1990 with latest amendments complete with GI fittings
(excluding the cost of fittings) with cuts and threads wherever necessary, including testing for water tightness, with all lead
B69 Rmtr 50.00 679.00 33950.00
and commissioning. (contractor will make his own arrangements for procuring water for testing) For Heavy Duty GI pipe
of 50mm dia for CRB (V/Pg110/11.3.6)
Providing and fixing PTMT stop cock of approved quality and colour 20 mm nominal bore, 89 mm long, weighing not less
B70 NO 4.00 144.00 576.00
than 88 g (V.2 I.No. 13.18.2, P.No. 118)
Providing and fixing PTMT stop cock of approved quality and colour 15 mm nominal bore, 86 mm long, weighing not less
B71 No 4.00 131.00 524.00
than 88 g (V2/Pg120/13.18.1)
Providing and fixing Structural Steel work riveted, bolted or welded in built up sections, trusses and framed work,
including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete including
B72 Kg 16191.82 113.00 1829675.66
cost of materials, labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-
in-Charge. (V2/Pg77/11.2)

Constructing brick masonry chamber of internal dimension 600x600mm and depth of 600mm (inner dimensions) with
B73 modular bricks of CD 75 in cement mortar 1:6, bed concrete 150mm thick with 1:3:6, plastering 12 mm thick with cement Each 8.00 5454.00 43632.00
mortar 1:4, CC 1:2:4 coping 75mm thk for fixing CI cover & frame etc. excluding the cost of CI frame and cover..
Sl.
Particulars Unit Qty. Base Rate Amount
No.

Constructing brick masonry chamber of internal dimension 450x450mm and depth of 600mm (inner dimensions) with
B74 modular bricks of CD 75 in cement mortar 1:6, bed concrete 150mm thick with 1:3:6, plastering 12 mm thick with cement Each 22.00 4236.00 93192.00
mortar 1:4, CC 1:2:4 coping 75mm thk for fixing CI cover & frame etc. excluding the cost of CI frame and cover..

Supplying, laying and jointing HDPE pipes of specified grade and conforming to IS 4984-2016 with latest ammendments
and conveying to work site including loading and unloading at both destinations and rolling and lowering into trenches,
laying true to line and jointing of pipes and specials with electrofusion welding, giving hydraulic test as per relevant ISS
with all lead and lifts including encasing the pipe alround to a depth of not less than 15 cms. with soft gravel or selected
B75 Rmtr 63.00 321.00 20223.00
earth available from the excation, testing and commissioning. The rate is exclusive of required specials and fittings
wherever necessary like saddle Tee, stub ends, flanged sets, bedns, reducers etc. complete (Contractor will make his own
arrangements for procuring water for testing) etc. Note: Upto 110mm dia Coil shall be used. (V5/Pg90/9.1.3) HDPE Grade
PE80-PN6.0 - 90mm dia
Providing and fixing Rainy dual capacity self-cleaning roof top rain water harvesting filter or equivalent filter of FL-200
B76 No 1.00 15000.00 15000.00
specification suitable for a catchment area of about 500Sqm. (MR)
Providing and fixing ladder for easy maintenance of Sump tank of Rain water Harvesting (MR) No 1.00 5000.00 5000.00
Providing, supplying to work site,Single Phase Submersible Pump Sets of 100mm dia (4 inch) suitable for bore well
B77 confirming to IS 8034-2000 specifications,with testing of as per instructions of engineer incharge of work and latest No 1.00 15418.00 15418.00
amendments 1.50 HP/1.1KW 12 STG (V5/Pg126/13.7.3)
Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with
B78 2 mm dia wire or nuts, bolts and washers as required complete as per the direction of Engineer-in-charge. (Made of G.I. Smt 591.64 803.00 475086.92
wire of dia 4 mm (V2/Pg95/11.58)

Fencing with G.I. barbed wire Angle iron post placed at required distance embedded in cement concrete blocks, every
15th post, last but one end post and corner post shall be strutted on both sides and end post on one side only and provided
with horizontal lines and two diagonals interwoven with horizontal wires, of barbed wire weighing 9.38 kg per 100 m
B79 Rmtr 4527.60 18.00 81496.80
(minimum), between the two posts fitted and fixed with G.I. staples, turn buckles etc. complete. (Cost of posts, struts, earth
work and concrete work to be paid for separately). Payment to be made per metre cost of
total length of barbed wire used. (V2/Pg95/11.57.1) With G.I. barbed wire

Supplying PVC ringtite pipes conforming to IS 4985:2000 with latest amendments and conveying to worksite, rolling and
lowering into trenches, laying true to line and level and perfect linking at joints, testing and commissioning, including
loading unloading at both destinations and cuts of pipes wherever necessary including jointing of PVC pipes and specials
(excluding cost of specials) with jointing of approved type, with all labour with all lead & lift including encasing the pipe
B80 Rmtr 60.00 101.00 6060.00
alround to a depth of not less than 15 cms. with soft gravel or selected earth available from the Kxcavation etc. complete
and giving necessary hydraulic test to the required pressure as per ISS (Contractor will make his own arrangements for
procuring water for testing) etc. for: pipeline from borewell to CRB PVC pipes 50mm dia., 6 kg/sqcm & class 5
(V5/Pg102/10.1.3)
Sl.
Particulars Unit Qty. Base Rate Amount
No.

Supplying PVC ringtite pipes conforming to IS 4985:2000 with latest amendments and conveying to worksite, rolling and
lowering into trenches, laying true to line and level and perfect linking at joints, testing and commissioning, including
loading unloading at both destinations and cuts of pipes wherever necessary including jointing of PVC pipes and specials
(excluding cost of specials) with jointing of approved type, with all labour with all lead & lift including encasing the pipe
B81 Rmtr 110.00 161.00 17710.00
alround to a depth of not less than 15 cms. with soft gravel or selected earth available from the Kxcavation etc. complete
and giving necessary hydraulic test to the required pressure as per ISS (Contractor will make his own arrangements for
procuring water for testing) etc. for:
PVC pipes 63mm dia., 6 kg/sqcm & class 3 (V5/Pg102/10.1.4)

Sinking borewell of 165mm dia. clear, using super fast hydraulic rig of capacity 300 PSIG & above 1100 CMF and above, in
all strata of earth, including over burden upto 20M, fixing of casing pipes, collars and cap with ncessary cutting, threading
and welding including transportation of rig and supporting vehicles, crew charges, cost of consumables, cost of yield test at
B82 Rmt 50.00 370 18500.00
the final depth with a minimum working of compressor for one hour etc. complete. The cost excludes the cost of casing
pipes, collars and caps etc.) for: Borewell depth of 0 to 50 m (V.5, SOR code O010A, P.No. 151) - Water supply Upto 50.00
mtrs.

Sinking borewell of 165mm dia. clear, using super fast hydraulic rig of capacity 300 PSIG & above 1100 CMF and above, in
all strata of earth, including over burden upto 20M, fixing of casing pipes, collars and cap with ncessary cutting, threading
and welding including transportation of rig and supporting vehicles, crew charges, cost of consumables, cost of yield test at
B83 Rmt 50.00 464 23200.00
the final depth with a minimum working of compressor for one hour etc. complete. The cost excludes the cost of casing
pipes, collars and caps etc.) for:Borewell depth of 50 to 100 m (V.5, SOR code O010B, P.No. 151)

Sinking borewell of 165mm dia. clear, using super fast hydraulic rig of capacity 300 PSIG & above 1100 CMF and above, in
all strata of earth, including over burden upto 20M, fixing of casing pipes, collars and cap with ncessary cutting, threading
and welding including transportation of rig and supporting vehicles, crew charges, cost of consumables, cost of yield test at
B84 Rmt 50.00 493 24650.00
the final depth with a minimum working of compressor for one hour etc. complete. The cost excludes the cost of casing
pipes,
collars and caps etc.) for: Borewell depth of 100 to 150 m (V.5, SOR code O010C, P.No. 151)

Sinking borewell of 165mm dia. clear, using super fast hydraulic rig of capacity 300 PSIG & above 1100 CMF and above, in
all strata of earth, including over burden upto 20M, fixing of casing pipes, collars and cap with ncessary cutting, threading
and welding including transportation of rig and supporting vehicles, crew charges, cost of consumables, cost of yield test at
B85 Rmt 50.00 572 28600.00
the final depth with a minimum working of compressor for one hour etc. complete. The cost excludes the cost of casing
pipes,
collars and caps etc.) for: Borewell depth of 150 to 200 m (V.5, SOR code O010D, P.No. 151)

Supply of ISI mark 175mm nominal bore,plain and steel casing pipe grade of steel Fe 410 of wall thickness conforming to
IS 4270-2001 and latest ammendments, electrical resistance welded steel tubes, material and conforming to IS 1387-1993 and
manufactured by basic open hearth electric or basic oxygen process in random length of 5-7m both ends.threaded
B86 Rmt 20.00 1933.00 38660.00
conforming to IS 554-1985 one end fixed with socket conforming to IS 4270-2001 and the other end with screwed pipes all
shall be responsibaly free from defects. The tubes shall be responsible straight end should be with ISI marking weighing
25.10kg/m.prices include Collar-Medium duty (V5/121/12.32)
Sl.
Particulars Unit Qty. Base Rate Amount
No.

Providing and laying at site of work MS casing caps as per IS 1239 (part- II) 1982 with all latest amendments if any for any
dia. The thickness of plate used for covering one end shall be 3mm (minimum). The dimensions of caps and colars shall be
B87 Each 1.00 164.00 164.00
strictly as per IS 1239 (Part-II) 1982 with all amendments including cost of material and labour charges for fixing, if any etc.
complete with all lead and lifts and as directed by the Engineer in charge (V5/Pg121/12.34)

Geophysical investigation at site for sinking borewells for supplying drinking water to the habitation either through the
Hand Pump MWS or P.W.S.S, by vertical electrical sounding by adopting Venner or Schlumbergers’s method, including
reconnaissance survey of geological formation. Geophysical investigation of existing ground water in the vicinity, its
quality, quantity and acceptability of the users, indicating the location of the site, recommended depth of casing pipe
required to seal the top unconsolidated formation including an extra depth of 1.0 metre in consolidated formation for
B89 proper seating of casing pipe, depth of drilling required to cover full depth of aquifer proposed to be tapped, probable Each 1.00 5288.00 5288.00
yield and other information required including transportation of instruments and accessories to work site, engaging
technical personal and labour required etc. NOTE: 1) Additional rate on item 1&2 is allowed for drilling in over burden and
fixing Casing pipes beyond 20 M (for fixing Casing pipes only) a) Above 20 M and upto 30 M - 15%, b) Above 30 M - 30%
(Measurement of overburden is restricted to the depth of casing pipe fixed excluding initial depth of 20M and projection
above ground level). 2) A sum of Rs. 100/- is to be deducted for Dry Borewell towards yield test. (V5/Pg118/12.04)

PUMPSET :
Providing,supplying to work site, Submersible Pump Set of 150mm dia suitable for bore well and confirming to IS 8034-
B90 2000;3Phase, SS Bowl & Impeller with Low volt Motor as per specifications,as per necessary ammendments and Each 1.00 36719.00 36719.00
instructions of engineer incharge of work. For HP For 6.50 HP
6.50 HP - 90 LPM @ 132 m = 12 STG Outlet Dia - 2.00” (V5/Pg128/13.14.7)
SUBMERSIBLE CABLE
B91 Supply and delivery at site Brand new best make PVC insulated cable of Flat 3 core (sheathed) of nominal cross sectional Rmt 145.00 135.00 19575.00
area as per IS 694-1990 with ISI Mark and as per its latest amendments. 1x3x4 m2 (V5/Pg129/13.22.3)
PRESSURE GAUGE :
Supply and delivery at site of brand new best make pressure gauge bourdon type as per IS 778/1984 with ISI Mark and as
B92 Each 1.00 654.00 654.00
per its latest amendments - Size 100 mm (V5/Pg129/13.23.3)

GATE VALVE :
Supply and delivery at site of brand new best make gate valve as per IS 778/1984 with ISI Mark and as per its latest
B93 Each 2.00 1250.00 2500.00
amendments Size 50 mm (V5/Pg129/13.24.1)

NON - RETURN VALVE :


B94 Supply and delivery at site of brand new best make non-return valve as per IS 778/1984 with ISI Mark and as per its latest Each 1.00 1250.00 1250.00
amendments Size 50 mm (V5/Pg129/13.25.1)
Sl.
Particulars Unit Qty. Base Rate Amount
No.

ix) Control Panel BOARD-A:


Supply, installing,testing and commissioning COMMON control panel consisting of the following INCOMING:1 No set of
Phase indicating lamps with SFU of suitable rating 1 No, Analog Ammeter, 1 No Analog Voltmeter 1ni with Phase selector
switch, Isolating switch OUTGOING for Main Electrical Pump: 1 No. MCB 1 No. DOL of S/D Starter suitable for respective
B95 Each 1.00 15900.00 15900.00
HP 1 No. Electrcal Protection Like single Phase preventor, under voltage over Volage, under current over current & dry run
protection suitable for the pump described above 1 no Indoor typ e NOTE: 1) DOLDirect Online Starter 2)S-D- Star Delta
Starter for outdoor Upto 6 HP pumps (V5/Pg130/13.23.3)

POWER CAPACITOR :
Supply and delivery at site best indigenous brand new power capacitor as per IS 2834/1986 with latest amendments with
B96 KPTCL authorities and erection, electrification and commissioning of the same at the location of respective pump sets. KVAR 1.00 550.00 550.00
(V5/Pg130/13.25)

MCB : Supply and delivery at site delivery of best indigenous brand new MCB (Miniature Circuit Breakers) of required
Per 3
B97 capacity as per IS 88228/1978 and its latest amendments and with ISI Mark of 6/10/16/20/25/40 Amps with scalable box. 1.00 1150.00 1150.00
poles
(V5/Pg130/13.26)
GALVANISED MILD STEEL TUBES:
Supply and delivery of galvanized mild steel tubes of 6mtr standard length heavy duty (C Class) as per IS 1239 (Part-I)
B98 Each 1.00 3050.00 3050.00
1990 with latest amendments with ISI Mark (one end fitted with Heavy Duty collar and other end fitted with protective
cover) 50 mm (V5/Pg130/13.27.1)

Erection elctrification & Commissioning works of pumpsets :


Labour charges for Erection, Electrification and commissioning of Pump sets, including aligning and balancing of all items
B99 including supply and erection of two pair of supporting clamps, bore well caps, cable clips and water tight gland cable Job 1.00 6500.00 6500.00
protectors, bolts, nuts, valve and gauges,tools and equipments etc., involved in the job as per specifications, with necessary
tests as per specifications, with testing of as per instructions of engineer incharge of work (V5/Pg130/13.32)

Ercerion of panel board & meter board Unit :


Labour charges for erection of outdoor type panel board and meter board units with all necessary materials and labour,
B100 Job 1.00 1450.00 1450.00
tools and equipmentsincluding providing cement concrete foundation bed etc., complete as per specification, with testing
of as per instructions of engineer incharge of work.(V5/Pg131/13.34)
Main connections:
B101 Providing main connection from pole PVC insulated sheathed steel wire cable in new trench as per IS 1554/ 1988 with Rmt 145.00 135.00 19575.00
latest amendments with ISI mark from KPTCL pole to meter board unit. (V5/Pg131/13.36)
Earthing :
Earthing: Providing and fixing and wiring earth electrode for grounding circuits IC cutouts and other equipments on the
meter board in the pit. The pits should be filled up with equal proportion of salt and charcoal 150mm around the pipe to
B102 Job 1.00 3750.00 3750.00
complete depth. The connection from the pipe to the conduits etc. is to established through GI wire of sizes as per clause
7.3.3 of IS 732 using 12mm bolts, nuts, washers and check nuts, the pipe shall have 16 through holes of 12mm dia.
(V5/Pg131/13.39)
Sl.
Particulars Unit Qty. Base Rate Amount
No.
Jelly Spreading (20-25 mm) : Supplying and providing jelly in the station yard of uniform thickness of 100 mm
B103 including the cost of materials, labour charges, required tools and plants etc., complete. Work shall be carried out as per the Sqmtr 7843.00 177.30 1390563.90
instructions of Engineer in-charge of works as per the standard procedure.(V6/Pg158/1)

Providing S&S RCC SPUN / VIBRATED CAST PIPES (REINFORCED) pipes NP-3 Class conforming to IS:458-1988 with
latest amentments using ordinary portland cement, for sanitary works and conveying to work site, rolling and lowering
into trenches, laying true to line and level including loading and unloading at both destinations and jointing of pipes and
specials, perfect linking of joints with jack to correct position including cost of jointing materials, i.e, rubber rings
B104 Rmtr 60.00 1332.00 79920.00
conforming to IS: 5382 for S&S RCC pipes, with all leads and lifts as directed and giving necessary hydraulic test as per ISS
to the required pressure and commissioning etc. complete. (Contractor will make his own arrangements for procuring
water for testing). Before the execution of the work, the contractor shall carry out the survey. RCC NP3 Class pipe of 300
mm dia. for Cable duct E & F Type (V5/Pg188/16.3.2)

Providing S&S RCC SPUN / VIBRATED CAST PIPES (REINFORCED) pipes NP-3 Class conforming to IS:458-1988 with
latest amentments using ordinary portland cement, for sanitary works and conveying to work site, rolling and lowering
into trenches, laying true to line and level including loading and unloading at both destinations and jointing of pipes and
specials, perfect linking of joints with jack to correct position including cost of jointing materials, i.e, rubber rings
B105 Rmtr 25.00 4854.00 121350.00
conforming to IS: 5382 for S&S RCC pipes, with all leads and lifts as directed and giving necessary hydraulic test as per ISS
to the required pressure and commissioning etc. complete. (Contractor will make his own arrangements for procuring
water for testing). Before the execution of the work, the contractor shall carry out the survey. RCC NP3 Class pipe of 900
mm dia. for culvert (V5/Pg18/721)

Wiring

Point wiring using Copper wire without switch.


Supplying and wiring adopting loop system in existing PVC Conduit /casing capping casing capping using 2x1.5Sqmm
(Phase & Neutral) & 1x1.0 sqmm (Earth wire) FRLS multi strand PVC insulated copper wire (confirming to IS-694: and
Each
B106 latest amendments) without control switch shall be fixed on the existing plastic sheet/ gang box, 15.00 269.00 4035.00
Point
the other end of the wires shall be terminated with sufficient loose length in a wood/PVC round block. complete for each
outlet.
a) Short point up to 3Mtr from tapping point to out let via switch box (V6/P3/Pg5/2.1.1)

Point wiring using Copper wire without switch.


Supplying and wiring adopting loop system in existing PVC Conduit /casing capping casing capping using 2x1.5Sqmm
(Phase & Neutral) & 1x1.0 sqmm (Earth wire) FRLS multi strand PVC insulated copper wire (confirming to IS-694: and
Each
B107 latest amendments) without control switch shall be fixed on the existing plastic sheet/ gang box, 19.00 379.00 7201.00
Point
the other end of the wires shall be terminated with sufficient loose length in a wood/PVC round block. complete for each
outlet.
b) Medium point above 3Mtr up to 6Mtr from tapping point to out let via switch box(V6/P3/Pg5/2.1.2)
Sl.
Particulars Unit Qty. Base Rate Amount
No.

Point wiring using Copper wire without switch.


Supplying and wiring adopting loop system in existing PVC Conduit /casing capping using copper PVC insulated multi
Each
B108 strand 2x1.5Sqmm copper wire without switch, the other end of the wires shall be terminated with sufficient loose length 10.00 555.00 5550.00
Point
in a wood/PVC round block. complete for each outlet.( 4/9) - II. Point wiring using class B Materialsc) Long point above
6Mtr up to 10Mtr from tapping point to out let via switch box (V6/P3/Pg5/2.1.3)

Point wiring using Copper wire without switch.


Supplying and wiring adopting loop system in existing PVC Conduit /casing capping casing capping using 2x1.5Sqmm
(Phase & Neutral) & 1x1.0 sqmm (Earth wire) FRLS multi strand PVC insulated copper wire (confirming to IS-694: and Each
B109 4.00 677.00 2708.00
latest amendments) without control switch shall be fixed on the existing plastic sheet/ gang box, Point
the other end of the wires shall be terminated with sufficient loose length in a wood/PVC round block. complete for each
outlet. Two outlet in a row, above 3Mtr up to 6Mtr from tapping point to out let via switches box (V6/P3/Pg5/2.2.4)

Point wiring using Copper wire without switch.


Supplying and wiring adopting loop system in existing PVC Conduit /casing capping casing capping using 2x1.5Sqmm
(Phase & Neutral) & 1x1.0 sqmm (Earth wire) FRLS multi strand PVC insulated copper wire (confirming to IS-694: and Each
B110 4.00 989.00 3956.00
latest amendments) without control switch shall be fixed on the existing plastic sheet/ gang box, the other end of the wires Point
shall be terminated with sufficient loose length in a wood/PVC round block. complete for each outlet. Three outlet in a
row, above 6Mts up to 10Mtr from tapping point to out let via switches box (V6/P3/Pg5/2.2.5)

Concealed Conduit System Supplying heavy gauge PVC conduit pipe ...... mm dia..........mm thick confirming to IS 2509
with suitable size bends, metal/PVC Junction boxes, adhesive paste etc., and running before concreting the slab. The
B111 conduit should be tied to the reinforcement rods by using binding wires and unused ways of junction boxes and pipe ends Per Mtr 150.00 78.00 11700.00
should be covered using PVC end enclosures, run with 18SWG GI fish wire wherever necessary 25mm dia 2mm thick
(V6/P3/Pg2/1.2.2)

Concealed Conduit System Supplying heavy gauge PVC conduit pipe ...... mm dia..........mm thick confirming to IS 2509
with suitable size bends, metal/PVC Junction boxes, adhesive paste etc., and running before concreting the slab. The
B112 conduit should be tied to the reinforcement rods by using binding wires and unused ways of junction boxes and pipe ends Per Mtr 100.00 66.00 6600.00
should be covered using PVC end enclosures, run with 18SWG GI fish wire
wherever necessary 19/20mm dia 2mm thick (V6/P3/Pg2/1.2.1)

Supplying heavy gauge PVC Conduit Pipe .... dia ....... mm thick with suitable size bends, metal junction boxes adhesive
B113 paste etc., by groove cutting in the wall and fixing by bracing U or J hooks and cement plastering upto the wall surface and Per Mtr 68.00 0.00
run with 18 SWG GI fish wire run throughout the conduit wherever necessary 19/20mm dia 2mm thick (V6/P3/Pg2/1.3.1)
Sl.
Particulars Unit Qty. Base Rate Amount
No.

Supplying heavy gauge PVC Conduit Pipe .... dia ....... mm thick with suitable size bends, metal junction boxes adhesive
B114 paste etc., by groove cutting in the wall and fixing by bracing U or J hooks and cement plastering upto the wall surface and Per Mtr 200.00 79.00 15800.00
run with 18 SWG GI fish wire run throughout the conduit wherever necessary 25mm dia 2mm thick (V6/P3/Pg2/1.3.2)

Supplying 6A flush type socket and 6 A flush type SP switch either surface/flush mounting in existing gang box or in
B115 4mm thick plastic sheet and fixing over a flush mounted wooden box and wiring using necessary capacity wires as Each 4.00 128.00 512.00
required as per IS 1293 and IS 3854. 6A 2 Way (V6/P3/Pg8/3.1.1)
Supplying 6A flush type socket and 6 A flush type SP switch either surface/flush mounting in existing gang box or in
B116 4mm thick plastic sheet and fixing over a flush mounted wooden box and wiring using necessary capacity wires as Each 4.00 147.00 588.00
required as per IS 1293 and IS 3854. 6A 3/5 Way (V6/P3/Pg8/3.1.2)
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS
B117 Each 6.00 326.00 1956.00
1293.32A DP SwitchV(6/P3/Pg9/3.6.9)
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS
B118 Each 6.00 236.00 1416.00
1293. 6/16A Universal Socket V6/P3/Pg9/3.6.10)
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS
B119 Each 6.00 156.00 936.00
1293. TV/ Telephone Socket (V6/P3/Pg9/3.6.11)
Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low
B120 conductor resistance single core in open or concealed system of wiring with specified IS 694:201 1.5 sqmm Mtr. 81.00 26.00 2106.00
(V6/P3/Pg5/2.3.2)
Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low
B121 conductor resistance single core in open or concealed system of wiring with specified IS 694:201 2.5 sqmm Mtr. 212.00 42.00 8904.00
(V6/P3/Pg5/2.3.3)

Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low
B122 Mtr. 204.00 63.00 12852.00
conductor resistance single core in open or concealed system of wiring with specified IS 694:201 4 sqmm (V6/P3/Pg5/2.3.4)

Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low
B123 Mtr. 408.00 92.00 37536.00
conductor resistance single core in open or concealed system of wiring with specified IS 694:201 6 sqmm (V6/P3/Pg5/2.3.5)

Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low
B124 conductor resistance single core in open or concealed system of wiring with specified IS 694:201 10 sqmm Mtr. 0.00 167.00 0.00
(V6/P3/Pg5/2.3.6)
Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low
B125 conductor resistance single core in open or concealed system of wiring with specified IS 694:201 16 sqmm Mtr. 0.00 318.00 0.00
(V6/P3/Pg5/2.3.7)

Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The
B126 Each 3.00 138.00 414.00
box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall 1-2Way (V6/P3/Pg8/3.4.1)

Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The
B127 Each 19.00 177.00 3363.00
box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall 4-5Way (V6/P3/Pg8/3.4.3)
Sl.
Particulars Unit Qty. Base Rate Amount
No.
Supplying and fixing surface/flush mounting unbreakable PVC modular box suitable for mounting modular switch plates
B128 with due groove cutting in Brick/C.C wall, including necessary rawl plugs, Machine/NF screws etc., complete 4-5Way 0.00
(V6/P3/Pg8/3.3.3)

Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The
B129 Each 1.00 220.00 220.00
box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall 6Way (V6/P3/Pg8/3.4.4)

Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The
B130 Each 1.00 261.00 261.00
box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall 8Way (V6/P3/Pg8/3.4.5)

Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The
B131 Each 1.00 319.00 319.00
box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall 10-12Way (V6/P3/Pg8/3.4.6)

Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The
B132 Each 1.00 363.00 363.00
box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall 16Way (V6/P3/Pg8/3.4.7)

Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back
B132 plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box 1 to 2 Module Each 3.00 137.00 411.00
(V6/P3/Pg8/3.5.1)

Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back
B133 plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box Each 19.00 175.00 3325.00
4 Module (V6/P3/Pg8/3.5.3)

Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back
B134 plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box Each 3.00 234.00 702.00
6 Module (V6/P3/Pg8/3.5.4)

Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back
B135 plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box Each 3.00 284.00 852.00
8 Module (V6/P3/Pg8/3.5.5)

Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back
B136 plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box Each 3.00 344.00 1032.00
10-12 Module (V6/P3/Pg8/3.5.6)

Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS
B137 Each 48.00 180.00 8640.00
1293. 16Amps one way switch (V6/P3/Pg9/3.6.7)
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS
B138 Each 30.00 102.00 3060.00
1293. 6Amps one way switch (V6/P3/Pg9/3.6.1)
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS
B139 Each 21.00 171.00 3591.00
1293. 6Amps 3 Way Socket (V6/P3/Pg9/3.6.3)
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS
B140 Each 18.00 236.00 4248.00
1293. 6/16Amps Universal Socket (V6/P3/Pg9/3.6.10)
Sl.
Particulars Unit Qty. Base Rate Amount
No.
Supplying and fixing one of 230 V Ding dong bell and a flush type bell push with gang box fixed on necessary wooden or
B141 Each 1.00 246.00 246.00
rawl plugs using NF screws with Remote (V6/P3/Pg48/12.2.1)
Supplying of 1440rpm heavy duty exhaust fan with bracket blades suitable to operate on 230V 50Hz, AC Supply complete.
B142 Each 2.00 2969.00 5938.00
- 12" Sweep (300mm) (V6/P3/Pg30/6.2.1)
Supplying of 1440rpm heavy duty exhaust fan with bracket blades suitable to operate on 230V 50Hz, AC Supply complete.
B143 Each 2.00 4446.00 8892.00
- 15" Sweep (450mm) (V6/P3/Pg30/6.2.2)
Supplying capacitor type ceiling fan complete with down rod blades, shackle, canopies etc., for operation on 230 volts, 50
B144 cycles. Single phase AC supply conforming to ISS-374-1979 and with double ball bearing system 48" Sweep (1200mm) Each 4.00 2984.00 11936.00
Regular model (V6/P3/Pg30/6.3.1)
Fixing a ceiling/wall mounting fan of all capacities and all types to the existing 'S'' hook with fan regulator to the existing
B145 board together with supplying and fixing 5 A. ceiling rose, necessary length of 23 / 0.0076 inch PVC insulated twin twisted Each 4.00 171.00 684.00
copper wire and wiring. (V6/P3/Pg57/13.10)

Fixing one exhaust fan after making a suitable notch in the wall and finishing with cement mortar and colouring to match
B146 the existing wall or brackets, with bolts and nuts and a 5 A, ceiling rose with sufficient length of 23 / 0.0076 inch PVC Each 707.00 0.00
insulated twin core wire of approved make with wire mesh and wooden frame (V6/P3/Pg57/13.13)

Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS
B147 1293. Each 357.00 0.00
Stepped Fan Regulator Two Module (V6/P3/Pg57/3.6.4)

Supplying and fixing regular MCB distribution boards on wall / wood board / flush mounting using required clamps,
B148 bolts, nuts etc., with provision for fixing suitable type capacity MCB's single phase / 3 phase / single door with powder Each 1.00 2329.00 2329.00
coated painting etc., Made out of 14 SWG MS enclosur - Double Door 12Way SP &N (V6/P3/Pg18/5.19.9)

Supplying and fixing regular MCB distribution boards on wall / wood board / flush mounting using required clamps,
B149 bolts, nuts etc., with provision for fixing suitable type capacity MCB's single phase / 3 phase / single door with powder Each 1.00 1791.00 1791.00
coated painting etc., Made out of 14 SWG MS enclosur - Double Door 6 Way SP &N (V6/P3/Pg18/5.19.7)

Supplying & fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C'
B150 Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required Each 3.00 415.00 1245.00
confirming to IEC 60898 6-32A SP ((V6/P3/Pg17/5.18.1)

Supplying & fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C'
B151 Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required Each 1.00 811.00 811.00
confirming to IEC 60898 50-63A SP ((V6/P3/Pg17/5.18.3)

Supplying, fixing and wiring Residual current circuit breaker (RCCB) 240/450V upto 300mA sensitivity on existing wood/
B152 Each 1.00 5147.00 5147.00
panel board. 32-40 Amps 4 pole ((V6/P3/Pg18/5.20.8)
Supplying and drawing PVC flexible one pair telephone unarmoured tinned copper cable
B153 Rmt. 1.00 21.00 21.00
2Pair (V6/P3/Pg36/8.2.2)
Sl.
Particulars Unit Qty. Base Rate Amount
No.
Supplying and drawing 3 core flat PVC sheathed submersible pump cable manufactured with electrolytic grade copper
with flexible copper with low resistance conductor confirming to13:8130-1984 and virgin grade PVC insulation and powder
B154 Mtr 20.00 413.00 8260.00
coating extruded PVC sheathed suitable for working voltage upto 1100 Volts as per IS-694:1990. 3 core 10sqmm
(V6/P3/Pg7/2.6.4)
Supplying and drawing Flexible Multicore Cable manufactured with electrolytic grade flexible copper with low conductor
B155 confirming to IS 8130-1984 and (Virgin) PVC insulation sheathed suitable for working voltage upto 1100 Volts as per IS- Mtr 20.00 297.00 5940.00
694:1990 4 core 6 sqmm (V6/P3/Pg7/2.5.23)
Supply and laying double walled corrugated (DWC) HDPE Pipe including all necessary connecting
B156 Sockets/Couplings/Tees/ Bends/ End-caps of same materials in exisiting trench as per IS 14930 part -II suitable for Mtr 30.00 331.00 9930.00
drawing under ground cables.(73/19) - m) 90mm OD / 76mm ID (P 63 SL NO 7.20.5)
Supplying tinned copper lugs and crimping and wiring to terminal point for wire of the following sizes. 95 sqmm Long
B157 Each 2.00 129.00 258.00
Barrel (V6/ESCOM SR/Pg26/81/I.59.05)
Supplying tinned copper lugs and crimping and wiring to terminal point for wire of the following sizes - 150 sqmm Long
B158 Each 2.00 183.00 366.00
Barrel (V6/ESCOM SR/Pg26/81/I.59.07)

Supplying, fixing, wiring, earth electrode for grounding conduits, I.C. cutouts and other equipments on the meter board
using 40mm dia 2.90mm thick GI pipe 2.5 mtr long buried in a pit. The pit should be filled with equal proprotion of salt
B159 and charcoal 150mm alround the pipe to complete depth. The connection from the pipe to the conduit etc, is to be No 2.00 3510.00 7020.00
established through GI wire of size as per ISI specification 7.3.3. of IS 732 using 12mm dia bolts, nuts, washers and
checknuts etc., the pipe shall have 16 through holes of 12 mm dia.(V6/P3/Pg54/12.56)

Supplying fixing and wiring earth electrode for grounding of lifts, transformers, DG sets etc using 40mm dia 2.9mm thick
2.5 mtr long GI pipe with GI funnel with mesh and suitable size reducer fixed on the top of the earth electrode. The funnel
should be enclosed in a CC chamber of 400x400x400mm with a cast iron cover. The earth electrode shall have staggered
B160 Each 1.00 4256.00 4256.00
holes of 12mm dia and the electrode should be covered 150mm alround with alternate layers of salt and charcoal from the
bottom of the CC chamber. The connection from the electrode is to be established through GI strip using GI bolts and nuts.
(V6/P3/Pg54/12.57)
GI/Copper strips for grounding connections, using necessary fixing materials as required. 600x600x3mm copper plate
B161 Each 25.00 7421.00 185525.00
(V6/P3/Pg55/12.58.11)

Supplying and running GI/Copper conductor for grounding and (along with other wires in conduit system of wiring)
B162 m 105.00 0.00
using necessary suitable size clamps, nails, guttas/spacers etc. Copper wire. c) 8 SWG

Supplying and fixing angle iron frame work fabricated out of M.S. angle iron.. and M.S. flat … with bolts, washers etc., and
B163 Rmtr 15.00 395.00 5925.00
painted with 2 coats of red oxide and then two coats of approved paint. 50x50x6mm (V6/P3/Pg20/5.41.2)

B164 Supplying, fixing and wiring 0 to 600Volts 96x96mm AC Voltmeter on existing panel/wood board. (V6/P3/Pg18/5.22) Each 4.00 452.00 1808.00

B165 Supplying, fixing and wiring 0 to 1500amps CT operated AC analog type Ammeter With out CT) (V6/P3/Pg18/5.26) Each 4.00 480.00 1920.00

Supplying and fixing Electronic Trivector Meter (ETV) suitable for operation LT operation and -CT operated meter in
B166 Each 4.00 4390.00 17560.00
polycarbonate body in class 0.5 accuracy as per IS 14697 and completely wired (V6/P3/Pg19/5.31)
B167 Supplying, fixing and wiring rotary selector switch suitable for Ammeter. (V6/P3/Pg19/5.27) Each 4.00 200.00 800.00
Sl.
Particulars Unit Qty. Base Rate Amount
No.
Supplying, fixing and wiring 50/5 to 400/5Amps 5VA burden Current Transformer class 0.5 accurecy with Tape Wound
B168 Each 4.00 562.00 2248.00
(V6/P3/Pg19/5.34)
Supplying and fixing of LED type panel board indicating lamp with required colour suitable for 230/440v A.C. 50 Hz
B169 Each 10.00 515.00 5150.00
12/24v D.C (V6/P3/Pg19/5.38)
Supplying ......... amps rated 3phase with neutral bus bar using required capacity electrolytic alluminium strips covered
with heat shrinkable coloured PVC sleeve, mounted on phenolic/FRP/DMC insulator which are mounted on powder
B170 coated 40x6mm M.S.flat frame work in existing panel board. The bus bar shall have suitable holes for termination of Rmtr 20.00 5625.00 112500.00
incoming and outgoing cables as per IS specification with necessary botls,nuts and washers etc., complete. 600Amps
4x75x10mm Alluminium Strips (V6/Pg20/5.40.4)

Earth work excavation for pipeline trenches in all kinds of soils by mechanical means as per drawing and technical
specifications, including setting out, construction of shoring, strutting, barricading, caution lights, bracing, using sight rails
B171 & bonding rods at every 100 mm wherever necessary as directed, removal of stumps and other deleterious matter, dressing cum 220.00 262.00 57640.00
of sides and levelling the bottom of trench to the extent required , utilising the available excavated earth locally for the
work etc., and all other appurtenances complete in the following strata.(V1/P10/1.17.1)

Providing M-Sand : Supplying and filling in plinth, foundations / UG cable work with approved M-sand including
watering, ramming, consolidating and dressing. The rate includes the cost of material, labour charges,
B172 cum 1965.00 0.00
required tools and plants etc., complete. Work shall be carried out as per the instructions of Engineer- in-charge of
works as per the standard procedure. (V6/P158/3)

Supplying, fixing and wiring earth leakage relay with core balanced current transformer suitable for single phase 50 Hz
B173 AC with latest microcontroller based, digital readout of percentage leakage current, programmable delay/auto/manual Each 1.00 9255.00 9255.00
reset facility suitable to mount on DIN rail/ flush mounting on panel board. (V6/P3/Pg18/5.21)

Supplying and fixing Moulded Case Circuit Breaker (MCCB) over the existing wood/panel board using necessary screws,
bolts, nuts, necessary phase separators, handle and wiring complete. Protection of Overload and Short circuitwith
adjustable thermal magnetic release, Micro processor release shall have Earth Fault as per IS/IEC 60947-2 . (Icu=100% lcs).
In 4P MCCB, all Poles should have protection for Short-Cicrcuit/Over Load. For Microprocessor MCCBS Facility for
B174 Each 1.00 17040.00 17040.00
segregating Priority and Non-Priority loads must be available in the MCCB. MCCB shall be provided with double
insulation (insulation between front cover and internal power circuits to avoid any accidental
contact with live current carrying path with the front cover open). Multi-pole breakers shall be designed to break all the
poles simultaneously and they shall have a single mechanism THREE POLE 200Amps 36kA(V6/P3/Pg17/5.15.6)

Supplying of Switch disconnector fuse unit (TPN) HRC type (but without HRC fuses). With AC-23A duty and as per IS-
B175 Each 1.00 5798.00 5798.00
13947 - 125Amps (V6/P3/Pg15/5.8.3)
Sl.
Particulars Unit Qty. Base Rate Amount
No.

SSupply of LED Streetlight luminaire with pressure die cast aluminium housing body for optimal thermal dissipation.
Lamp compartment comprising of anti glare clear diffuser with Injection moulded polycarbonate material, delivering
superior light output Rated life Burning Hrs 50000 hr @ Lumen Maintenance of 70%, maximum light intensity should be
between 60 degrees to 70 degrees. CCT > 5500K, IP66 optical and electrical compartment & impact resistance of complete
luminaire > IK08. Power Factor >0.9 with mains, Surge Protection- Min 5KV along with Over voltage/ Overload, short
circuit/miss-wiring protection. Compatible for pole mounting with outer dia of 40mm to 50mm. Universal Voltage driver
to operate wide voltage range from 100V to 270V 50/60Hz application. Compliance to IS 10322/IEC 60598, LM 79 & LM 80
Adherence with RoHS. UL approved MCPCB. Top access street light with single screw to ensure ease of maintenance at the
B176 Each 4.00 4024.00 16096.00
sight site location with minimized minimal tools. LED Light fixture with ........W System Power consumption. LED
Efficiency>1301m/w, nominal CRI >75. Luminaire
manufacturer should have in-house facility accredited by NABL/CPRI & any Government certified agency & Design &
Development facility certified by ISO 9001:2008. Housing with supplier word mark /name shall be
Engraved / Embossing on the die cast housing/ Body part. Warranty of 2 Years against any manufacturing defect working
under standard electrical conditions as mentioned above should be given by LED manufacturer &
Cree/Nichia/Lumileds/Osram make LED Source.
40Watts (V6/P3/Pg46/11.8.2)

Fabricating supplying and mounting MS box made out ....SWG suitable for floor /wall mounting, fully weather proof with
provision for better heat dissipation, provided with hinged front cover, equipped with tamper proof locking arrangements,
B177 SqCm 12000.00 0.43 5160.00
with suitable size clamps with necessary cable entry pipe with gland and box should be finished with 7tanks treatment
with powder coated paint and finally finished with approved colour etc., complete - 16SWG (P 15 SL NO 5.42.2)

Supplying of recess mounting non integrated type LED down light 18W luminaire comprising of pressure decast/
extruded aluminium housing, with spring loaded false ceiling clA, LED of Power/COB with CCT 6500 degree K, CRI>
70%. efficacy >100 lumen per W, 120degree beam spread, life> 25000 burning hours and Compliance to IS10322/ IEC
60598, LM 79 & LM 80. The lamp compartment is enclosed with anti glare opal diffuser which enhances the lighting level.
B178 LED's are driven by HF electronic driver integrated in a separate control gear assembly., with PF > 0.95, power loss Each 4.00 3138.00 12552.00
should< 5% of lamp Wage, short circuit & open circuit protection to be integrated in the circuit, THD less than 20%, Life as
per LM 79. The operating input voltage should be between 130 to 275 V. BIS Approved and Tested by NABL/CPRI
accredited laboratory with 2 years Warranty against any manufacturing defect working under standard electrical
condition. (V6/P3/Pg44/11.6.1)
Supplying of feet -PVC Batten with integrated LED tube LED light fitting 1 x 4' - 36/40 W W with high quality diffuser
with Life of 25000 burning hours & 70% lumen maintenance with CRI > 80. Power Input: 220-240V@ 50/60Hz & Power
B179 Each 24.00 1269.00 30456.00
factor >0.9 along with CE approved. 2 years Warranty against any manufacturing defect working under standard electrical
condition (V6/P3/Pg43/11.3.3)
Supplying of feet -PVC Batten with integrated LED tube LED light fitting 1 x 2' - 9/10 W with high quality diffuser with
Life of 25000 burning hours & 70% lumen maintenance with CRI > 80. Power Input: 220-240V@ 50/60Hz & Power factor
B180 Each 12.00 551.00 6612.00
>0.9 along with CE approved. 2 years Warranty against any manufacturing defect working under standard electrical
condition (V6/P3/Pg43/11.3.1)
Sl.
Particulars Unit Qty. Base Rate Amount
No.
Supply of round/square recess/surface mounted rolling type LED Down light withLED square or round down light 5-6W
GU 10 LED Lamp Rib Fabricated from diecast aluminium with white powder coated prewired to mains connector & has
swivelling unit of aluminium die cast eye ball & LED Lamp position retained by circular wire spring, with Life of 25000
B181 Each 12.00 571.00 6852.00
burning hours & 70% lumen maintenance with CRI > 80. Power Input: 220-240V @50/60Hz & Power factor >0.9 along with
CE approved. 2years Warranty against any manufacturing defect working under standard electrical condition
(V6/P3/Pg44/11.5.1)
Supplying and Fixing of ---- mm dia class A GI pipe bracket upto 2 ms long bent at suitable angle and fixing to this bracket
B182 street light fitting of all capacities to GI or GI or rail or RCC pole / wall using suitable clamps, bolts, and nuts and wiring Each 1.00 1045.00 1045.00
using suitable capacity wires. Using 32mm dia G.I.Pipe (V6/P3/Pg56/13.1.2)

Fabricating, supplying and erection of ... ms long hot dip Galvanized Octagonal hot dip Pole with BSEN 10025 grade S 355
JO steel plate for shaft, IS 2062 for base plate with door opening arrangements, including suitable boards, Bakelite sheet and
MCBs as per IS specifications suitable to withstand the wind speed of 47 m/s for .......m
Pole in single section and single joint welded as per IS 9595/IS10178AWS having dimensions bottom ..... mm , top.... mm
B183 with 3 mm thick, suitable base plate and 4Nos of ..... long J bolts along with template and the Pole shall be hot dip Each 1.00 6300.00 6300.00
galvanized in single dipping with not less than 65micron as per ASTM-A123 and 153 etc., (excluding foundation) as per
drawing appended.
3 m - Top 70 mm and Bottom 130 mm dia (V6/P3/Pg11/4.2.1)

Fixing all types and all capacities of fluorescent /false ceiling / spot light / CFL / LED fittings indoor on the wall/
B184 ceiling / rafters / girders using 23/0.0076" twin twisted PVC insulated wires, required Nos of round blocks and clamps. Each 20.00 122.00 2440.00
(V6/P3/Pg11/4.2.1)

Fixing halogen/metal halide /SVL/IL/LED floodlight fitting over existing pole / wall ceiling including clA, bolts, nuts
B185 Each 20.00 162.00 3240.00
and wiring using suitable capacity wires. V6/P3/Pg56/13.5)

Supplying 25 litres capacity vertical/horizontal type wall mounting Electrical water heater with 22 SWG copper/SS sheet
metal inner Container tinned inside and anticorrosive paint outside and 20 SWG M.S. sheet metal outer cover filled with
glass wool between inner and outer container for thermal insulation complete. The inlet and outlet pipes so arranged that
water flow inside results in water to flow out from the inner container without turbulence. The Inner container shall have
B186 Each 0.00 10242.00 0.00
direct immersion type copper tube nickel plate. 2kW capacity element with a neon indicator fitted with 20A capacity 25 to
85 degree Centigrade range thermostat. The water heater shall completely be wired with 40/0.0076 inch 3 core copper
flexible wire of 1.5 meters length and the outer container provided with heavy gauge brackets for wall mounting.
(V6/P3/Pg34/7.1.3)
Erection charges for fixing a upto 30 Litres capacity wall mounting electric geysers using bolts, flat at one end nut and
B189 washers at the other end for through bolts and nuts and washers with 150x450x600mm back plate and wiring complete Each 0.00 664.00 0.00
with 15A 3pin top. (V6/P3/Pg57/13.15.1)
Sl.
Particulars Unit Qty. Base Rate Amount
No.

Supplying ......TR split Air conditioners suitable for operation on A/C supply single phase 50 Hz 230 V with hermetically
sealed compressor with air cooled condenser, motor capacitor and start run capacitors, relay and over load protector
internal unit, with one indoor and one outdoor unit The condenser unit will be placed outside the
B190 Each 0.00 47683.00 0.00
room on the terrace to avoid noise including standard length of suitable size copper tubing covered with insulation tube.
(High wall chorded/cordless) suitable capacity 3 core sheathed/ PVC copper cable and a battery operated wireless remote
uni for 1.50 Tonnes capacity (V6/P3/Pg31/6.7.2)

Supplying ......TR split Air conditioners suitable for operation on A/C supply single phase 50 Hz 230 V with hermetically
sealed compressor with air cooled condenser, motor capacitor and start run capacitors, relay and over load protector
internal unit, with one indoor and one outdoor unit The condenser unit will be placed outside the
B191 Each 0.00 54048.00 0.00
room on the terrace to avoid noise including standard length of suitable size copper tubing covered with insulation tube.
(High wall chorded/cordless) suitable capacity 3 core sheathed/ PVC copper cable and a battery operated wireless remote
uni for 2 Tonnes capacity (V6/P3/Pg31/6.7.3)

Installation charges for split type air conditioner with allied works for one indoor and one outdoor unit is to be mounted
B192 Each 0.00 3175.00 0.00
on suitable Angle Iron support upto 3.0 Ton split/cassette type A/C(V6/P3/Pg32/6.12)
Providing and laying in position Cement Concrete for levelling course for all works in foundation. The
granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine
mixed, laid in layers not exceeding 150 mm thickness, well compacted using plate vibrators, including all
B193 cum 0.00 5338.00 0.00
lead & lifts, cost of all materials of quality, labour, Usage charges of machinery, curing, and all the other
appurtenances required to complete the work as per technical specifications.
Mix 1:5:10 Using 40 mm and down size graded crushed coarse aggregate(V1/P15/2.1.1)

Providing S&S RCC SPUN / VIBRATED CAST PIPES (REINFORCED) pipes NP-3 Class conforming to IS:458-1988 with
latest amentments using ordinary portland cement, for sanitary works and conveying to work site, rolling and lowering
into trenches, laying true to line and level including loading and unloading at both destinations and jointing of pipes and
specials, perfect linking of joints with jack to correct position including cost of jointing materials, i.e, rubber rings
B194 Rmtr 12.50 3140.00 39250.00
conforming to IS: 5382 for S&S RCC pipes, with all leads and lifts as directed and giving necessary hydraulic test as per ISS
to the required pressure and commissioning etc. complete. (Contractor will make his own arrangements for procuring
water for testing). Before the execution of the work, the contractor shall carry out the survey. RCC NP3 Class pipe of 600
mm dia. for Culvert (V5/Pg188/16.317)

Finishing with Epoxy paint (two coats) at all locations prepared and applied as per manufacturer's specifications including
appropriate priming coat, preparation of surface, etc. complete. On concrete work including
B195 Sqmtr 165.00 172.00 28380.00
preparing the surface after thorougly cleaning oil, grease, dirt and foreign matter, cost of materials, labour complete as per
specifications and as per directions of Engineer-in-charge (V2/Pg48/8.36.2) FOR KERB STONE

Total 29077732.54

Assistant Engineer, Ele., Assistant Engineer Civil


Sl.
Particulars Unit Qty. Base Rate Amount
No.
Major Works Sub Division-II, KPTCL., Belagavi. Major Works Division KPTCL., Belagavi.

Assistant Executive Engineer, Ele., Assistant Executive Engineer Civil


Major Works Sub Division-II, KPTCL., Belagavi. Major Works Division, KPTCL., Belagavi.
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED

Estimate for establishment of 2X10MVA , 110/11 KV Substation at Padamandi in Ramadurga Taluk, Belagavi District.

Civil Rate analysis for Transmission Line Works as per KPWD SR 2023

Sl.No Particulars Unit Rate in Rs


Earth Work Excavation

Earth work in surface excavation by mechanical means for lowering & leveling the ground for all
works other than foundation in all kinds of soils & upto depth not exceeding 300mm as per drawing
and technical specifications, including setting out, shoring, strutting, barricading, caution lights,
1 removal of stumps and other deleterious matter including dressing of excavated surfaces, disposing
off or levelling the excavated earth or sorting & stacking the selected earth for reuse in a radius of
50 m and lift upto 1.5 m including cost of labour, tools, usage of machinery & other appurtenances
required to complete the work. (V1/Pg8/1.12)

Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per
drawing and technical specifications, including setting out, shoring, strutting, barricading, caution
lights, including dressing of excavated surfaces, disposing off or levelling the excavated earth or
2
sorting & stacking the selected earth for reuse in a radius of 50 m and lift upto 1.5m including cost
of labour, tools, usage of machinery & other appurtenaces required to complete the work
(V1/Pg8/1.12)

a In all kinds of soil (V1/Pg8/1.14.1) 102.00


b In all kinds of soil(Cost of dewatering up to 5% for Wet black cotton soil & Partial submerged soil) 107.10
(V1/Pg8/1.14.1)
In ordinary/soft rock without blasting Depth exceeding 1.5 m, but not exceeding 3 m
c 425.00
(V1/Pg8/1.15.1)
In ordinary/soft rock without blasting Depth exceeding 1.5 m, but not exceeding 3 m (Cost of De-
d 446.25
watering upto 7.5 % for submerged fissured rock/soft fissured rock) (V1/Pg9/1.15.2)
e In Hard Rock ( requiring blasting) Depth upto 1.50m (V1/Pg9/1.16.1) 623.00

Providing and laying in position Cement Concrete for levelling course for all works in foundation.
The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS
Codes machine mixed, laid in layers not exceeding 150 mm thickness, well compacted using plate
3
vibrators, including all lead & lifts, cost of all materials of quality, labour, Usage charges of
machinery, curing, and all the other appurtenances required to complete the work as per technical
specifications. (V1/Pg15/2.1)

a Mix 1:3:6 Using 40 mm nominal size graded crushed coarse aggregates 5989.00
Sl.No Particulars Unit Rate in Rs
b Mix 1:4:8 Using 40 mm nominal size graded crushed coarse aggregates 5664.00

Providing and laying in position Cement Concrete for all Foundation works. The granite/trap/basalt
crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with
super plasticizers laid in finished layers, well compacted using needle vibrators, including all lead &
4
lifts, cost of all materials, quality confirming to the requirements of relevant IS codes, labour, Usage
charges of machinery, curing and all the other appurtenances required to complete the work as per
technical specifications. (V1/Pg15/2.2)

a M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates 6287.00

Supplying, fitting and placing TMT FE 550 / 550D Steel Reinforcement including cost of all materials,
5 machinery, labour, cleaning, straightening, cutting, bending, hooking, laping/welding joints, tying
with binding wire / soft annealed steel wire and other ancilary operations complete as per drawing
and technical specification. (V1/Pg18/2.1h)

a All other type of structures as per KPWD 79.01

Assistant Engineer, Ele., Assistant Executive Engineer, Ele., Assistant Executive Engineer, Civil.,
M.W. Sub-Div-II, KPTCL., Belagavi. M.W. Sub-Div-II, KPTCL., Belagavi. M.W. Division, KPTCL., Belagavi.

You might also like