Letter No : GEC-GMRC/PH-2/PKG-C1/2023/ Date : 09-12-2023
To,
Project Manager,
Afcons Infrastructure Limited,
Casting Yar, CH:0, Indora Circle,
Gandhinagar-382007,
Gujarat, India.
Sub: Urgent Attention Required – Deviations in Tie-Down Works at P4-14 P1, B1 & C1
(Drawing No. 2363/DSN/TW/D/083-R2)
Upon conducting a thorough inspection, our team has identified several observations that
require your urgent attention and corrective action. The following deviations from the
approved drawing have been observed:
The top and bottom end plates are not in accordance with the Submittal Drawing
specifications (As per Drw. 200 x 200 x 60), immediate corrective measures are
necessary.
A spreader beam of insufficient size was utilized for tie-down, contrary to the
specified drawing (as per Drw. ISMC 300). This poses a potential risk and must be
rectified promptly.
The PT Bars were not fixed as per the Submittal Drawing, and their Improper
placement requires immediate attention to ensure structural integrity and Safety.
Page 1 of 5
4. Use of Sub-standard Cross Beams:
Nonstandard cross beams were used for tie-down at the P4-14 P1 segment, This
non-compliance needs to be addressed promptly.
Your immediate attention to rectify these above observations and implement the necessary
corrective actions.
(Surendra Kumar)
Project Director