Total length of piping from Pump room to Farthest equivalent length for
fittings nos total length
ii Hydrant Point 150 mtr 80mm dia pipe
Diameter of pipe 150 mm 90 elbow 4 4.30 17.2
Equivalent length for fittings 192 mtr Tee 29 5.50 159.5
Total Length 342 mtr Butterfly valve 3 1.13 3.39
Friction Loss 1.83 bar Flow switch 1 1 1
Others 2 5.5 11
3 Terminal Pressure maintained at furthest Fixture 3.5 bar 192.09
4 Static Head = Vertical Lift 110 mtr
11 bar
Total pressure required 16.3 bar
Total length of piping from Pump room to Farthest equivalent length for
fittings nos total length
ii Hydrant Point 150 mtr 80mm dia pipe
Diameter of pipe 150 mm 90 elbow 4 4.30 17.2
Equivalent length for fittings 192 mtr Tee 29 5.50 159.5
Total Length 342 mtr Butterfly valve 3 1.13 3.39
Friction Loss 0.28 bar Flow switch 1 1 1
Others 2 5.5 11
3 Terminal Pressure maintained at furthest Fixture 1 bar 192.09
4 Static Head = Vertical Lift 110 mtr
11 bar
Total pressure required 12.3 bar