Professional Documents
Culture Documents
******
Step 1: Prepare the Single Line Diagram of the entire electrical network clearly
showing all network components, Short Circuit Protective Devices, etc.
Step 2: Impedance values of most of the network components are given in Ohms,
except for the Utility Source, transformers, generators and motors.
Step 3: Vide Cl. 8.3.2.1 of IS 13234, the equivalent impedance ZQ of the source is:
c U2nQ
ZQ = ---------
S” kQ
If the 11kV Source Fault Level is not known: Vide Clause 8.1.1.4 of IS 2026-Part 1:
“the short-circuit apparent power of the system at the transformer location shall be
specified by the purchaser in his enquiry in order to obtain the value for the
symmetrical short-circuit current to be used for the design and the tests. If the short-
circuit level is not specified the value given in Table 4 shall be used.” (Refer
Annexure)
Now, find RQ & XQ. (RQ = 0.1 XQ & XQ = 0.995 ZQ – vide Cl. 8.3.2.1 of IS 13234).
(Note: When calculating the fault current at the secondary side of a transformer
which is feeding the fault and which is connected to this supply source on the HV
side, then this Source Impedance must be converted into an equivalent impedance
ZQt, referred to the low-voltage side of the transformer. This is done by:
1
ZQt = ZQ x ----, where, tr = the rated transformation ratio of the transformer.
t2r
Step 4: Conversion of Transformer Impedance, Resistance & Reactance (Cl. 8.3.2.2)
ukT U2rT
ZT = ------- x ------
100% SrT
XT = √Z2T – R2T
Step 5: Overhead Lines (Cl. 8.3.2.3): The effective resistance per unit length R’L of
overhead lines at the medium conductor temperature of 20oC may be calculated
from the nominal cross section qn and the resistivity ρ:
ρ
’
RL = ----
qn
The reactance per unit length X’L for overhead lines may be calculated, assuming
transposition, from:
µo { 0.25 d }
X’L = 2πf --- { ------ + logn --- }
2π { n r }
{ 0.25 d }
X’L = f µo { ------ + logn --- }
{ n r }
where,
3
d = √dL1L2 dL2L3 dL3L1 ; Geometric mean radius between conductors.
r = Radius of a single conductor. In case of conductor bundles, ‘r’ is to be
substituted by n√nrRn-1, with the bundle radius R.
n = No. of bundled conductors; for single conductors, n = 1.
{ 0.25 d }
X’L = 0.0628 { ------ + logn --- } Ω/km.
{ n r }
Step 6: The resistance & reactance of low-voltage & high-voltage cables may be
taken from the manufacturer’s data (vide Cl. 8.3.2.3).
Step 9: Determine total impedance upto the point of fault by Zk = √R2k + X2k
Step 10: Calculate the initial symmetrical short circuit current upto the point of
fault, by the formula (Cl. 9.1.1.1):
c Un
”
I k = ---------
√3 Zk
Now, calculate the peak short circuit current at the point of fault by the formula:
ip = χ √2 I”k, where,
Step 11: Motors contribution: Vide Cl. 8.3.2.5, it is not necessary to take into
account the contribution to the short circuit from asynchronous motors or group of
asynchronous motors which have a total rated current less than 1% of the initial
symmetrical short circuit current I”k calculated without the influence of motors.
(i.e.) if ΣIrM < 0.01 I”k the contribution from motors can be neglected. Otherwise,
1 UrM 1 U2rM
ZM = ---------- x -------- = --------- x ------ (Cl. 11.5.3.5)
ILR/IrM √3 IrM ILR/IrM SrM
Now, initial symmetrical short circuit current supplied by the motor, for a fault at
the motor terminals is:
c Un
”
I kM = ---------
√3 ZM
cUn
”
I kM = --------------------------------- = c 6 IrM
√3 {(1/6) x (UrM /√3 IrM)}
So, we can see that for a fault at the motor terminals, the motor contribution will be
equal to the locked rotor current or the starting current of the motor.
The following may be used with sufficient accuracy (vide Clause 11.5.3.5):
RM/XM = 0.10, with XM = 0.995 ZM for high-voltage motors with powers PrM per pair
of poles >/= 1 MW
RM/XM = 0.15, with XM = 0.989 ZM for high-voltage motors with powers PrM per pair
of poles < 1 MW
RM/XM = 0.42, with XM = 0.922 ZM for low-voltage motor groups with connection
cables.
For faults away from the motor terminals, the contribution from the motors can be
calculated from the above formulae, but by replacing ZM with effective impedance
upto the point of fault, including the impedances of the cables, etc.
Or if the fault is away from the motor, involving a cable, we can safely assume that
the cable impedance will limit this motor contributed fault current to (c 5 IrM).
Step 1: Convert %x”d of the generator into Ohmic values, to obtain XG:
10 x (%x”d ) x (kV)2
XG (in Ω) = --------------------------
kVA
where,
Step 2: Now, the resistance of the generator, ‘RG’ is normally given as a % of ‘XG’.
The following values of sufficient accuracy may be used (vide Clause 11.5.3.6):
RG = 0.05 XG for generators with UrG > 1 kV and SrG >/= 1OOMVA
RG = 0.07 XG for generators with UrG > 1 kV and SrG < 1OOMVA
Un c
KG = ------ --------------------------
UrG 1 + [(x”d ) (Sin φrG)]
where,
KG = Generator Correction Factor
Un = Nominal System Voltage, in V
URG = Generator Rated Voltage, in V
c = Voltage Correction Factor
x” d = Sub-transient Reactance of the Generator, in p.u. form
Sin φrG = √(1 – Cos2φrG)
CosφrG = Rated Power Factor of the Generator
Step 4: Now find out the Corrected Generator Resistance (RGK) & the Corrected
Generator Reactance (XGK):
RGK = KG x RG
XGK = KG x XG
Step 5: Once you know the RGK & XGK, add all ‘X’ & ‘R’ up to the point of fault and
proceed as before.
ANNEXURE
Table – 1
Typical values of No-load loss, Full load loss & Percentage Impedance for Oil-filled
Transformers (Courtesy: Kirloskar Electric Co.)
Table – 2
36 1000
145 10000
245 20000
300 30000
420 40000