PARTICLE SIZE ANALYSIS TEST REPORT

Client Petrojet / International Union Contracting Job No. 155104


Establishment
Project South Gas Compression Pipeline Order No. BQ-CMT-MO-23-00263
Location Haradh Report No. BQ-CMT-MR-23-00988
Sample Discription Soil Type (Agg. Base Course Class "B") Date Reported 15-Sep-2023
Source Barrak Nasser Al Dossari Est. Date Test Complete 13-Sep-2023
Sampled by Date Test Started
11/09/2023
MUHAMMAD ABID KHAN UMAR KHAN 00:00:00 +00:00
Sampled Received by MOHSIN NAQVI SYED MEHFOOZ HUSSAIN SHAH Date Sampled 09-Sep-2023
Tested by HARIDAS NAIR GOPAL CTTA: 192 Ambient Temp °C 24.0
Kasindra The procedure used to obtain the A√
Reported by
Mahato specimen (s) from the sample ASTM
Method
Mohamed Saheed Oven D-6913 B
Client Contact Mohamed
Moist √Air Dry
Dry
Sampling Plan / Method D-75 Apparatus used for Dispersion Separating Sieve Sieve # 4
Visual Classification By ASTM (GW-GM) Well Graded Ultrasonic Water Dispersion
D2487/2488 Gravel with Silt & Sand RFI # PTJ-SGCP-CIV-43555
Bath Shaker

U.S. SIEVE OPENING IN INCHES U.S. SIEVE NUMBERS HYDROMETER

3 2 1.5 3/4 1/2 3/8 4 6 8 10 16 20 30 40 50 70 100 200


100
90
80
Percent Finer

70
60
50
40
30
20
10
0
100 10 1 0.1 0.01 0.001
Grain Size, mm
Description of Sand / Gravel Particles:
Shape Hardness Specific Gravity
Aramco SAES-Q-006
Sieve Size
Inch (mm)
Passing % Specification SAES- Properties Tested
Q-006
Item Description Result Spec’s
1½ (37.5 mm) 100 100 1. Material finer than Sieve # 200 8.8 8-15
1 (25.0 mm) 88 60-100 2. Material Retained on Sieve # 40 71.0 -
3/4 (19 mm) 78 55-85 3. Liquid Limit (LL) Can’t be Molded 25 Max
1/2 (12.5 mm) 68 - 4. Plastic Limit (PL) Non plastic -
3/8 (9.5 mm) 65 - 5. Plasticity Index (PI) Non plastic 6% Max
#4 (4.75 mm) 55 35-60
#10 (2 mm) 48 25-50
#20 (850 μm) 39 -
#40 (425 μm) 29 15-30
#60 (250 μm) 20 -
#100 (150 μm) 13 -
#200 (75 μm) 8.8 8-15

(1) Tested material complies with Aramco specification SAES-Q-006 table 5 & 6 as Base course Class-B Material & (2) The result relate only to the
Remarks items tested. (3) Specification was not provided by the client. (4) The lab is responsible for all the information provided in the report, except when
information is provided by the customer.

Equipment Used: Sieve set (A51-040/A to T, Balance (A51-027), Washing Sieve # 200 (A51-005) & Oven (A51-034)

Checked By: Riyasat Ansari CTTA: 0344


Approved By: AlHerz AliHussain CTTA: 0060

- End of Report - *** The PDF document is electronically generated and digitally signed ***
LABORATORY COMPACTION CHARACTERISTICS OF SOIL
TEST REPORT
Petrojet / International Union Contracting 155104
Client Establishment Job No.
Project South Gas Compression Pipeline Order No. BQ-CMT-MO-23-00263
Location Haradh Report No. BQ-CMT-MR-23-01085
Sample Discription Soil Type (Agg. Base Course Class "B") Date Reported 15-Sep-2023
Source Barrak Nasser Al Dossari Est. Date Test Complete 14-Sep-2023
13/09/2023 00:00:00
Sampled by MUHAMMAD ABID KHAN UMAR KHAN Date Test Started
+00:00
Sampled Received by MOHSIN NAQVI SYED MEHFOOZ HUSSAIN SHAH Sampling Date 09-Sep-2023
Tested by HARIDAS NAIR GOPAL CTTA: 192 Ambient Temp °C 24.0
Mohamed Saheed
Reported by Kasindra Mahato Client Contact
Mohamed
RFI # PTJ-SGCP-CIV-43555 Result Providor FSCL ABQQ Lab
Sample preparation Group Name/Symbol of Sample (GW-GM) Well Graded Gravel with
Dry Method √Moist Silt & Sand
Method ( By ASTM D 2487/2488)

2060
2050
2040 2025
2030
2020
Dry Density, kg/m3

2010
2000
1990
1980
1970 8.7
1960
1950
1940
1930
1920
1910
3 4 5 6 7 8 9 10 11 12 13 14 15
Water Content, %

Method: ASTM D-1557 Method “C” Correction for Oversize Material ASTM D- 4718

Optimum Moisture Content, % 8.7 Oversize Fraction (Ret. 19.0 mm Sieve), % 22.2
Maximum Dry Density, kg/m3 2025 Moisture Content of Oversize Fraction, % 0.7
Equipment Used: Oven (A51-034), Balance (A51-027), Bulk Specific Gravity (ASTM C-127) 2.501
Proctor Ramer) A51-079) & Proctor Mold (A51-003E)
Corrected Optimum Moisture Content % 6.9
Corrected Maximum Dry Density, kg/m3 2114
(1) Optimum moisture content and Maximum Dry density values are taken from peak of graph. (2)The result relate only to the items
Remarks tested. (3) Specification was not provided by the client. (4) The lab is responsible for all the information provided in the report, except
when information is provided by the customer.(5) Measured expended uncertainty: MDD +0.5%, OMC 1.1%

Checked By: Riyasat Ansari CTTA: 0344


Approved By: AlHerz AliHussain CTTA: 0060

- End of Report - *** The PDF document is electronically generated and digitally signed ***
CBR-DRY DENSITY RELATION TEST REPORT
Client International Union Contracting Establishment Order No. BQ-CMT-MO-23-00263

Project South Gas Compression Pipeline Report No. BQ-CMT-MR-23-01198

Location Haradh Date Reported 21-Sep-2023

Supplier / Source Barrak Nasser Al Dossari Est. Date Sampled 09-Sep-2023


Sampling Plan /
Sample Location Inplace Sample @ Jobsite Method ASTM D 1883

Test Location FSCL Abqaiq Lab Client Contact Mohamed Saheed Mohamed
Result Provider FSCL Abqaiq Lab Ambient Temp. 0C 23.5
Sample By MUHAMMAD ABID KHAN UMAR KHAN RFI No. PTJ-SGCP-CIV-43555
Test Started Date 16/09/2023 00:00:00 +00:00 Test Complete
21-Sep-2023
Date
Material Agg. Base Course Class “B”
Test by MATHEW KANNYAKONIL CHERIAN CTTA: 727

16
15
14
13
12
11
10
Stress, MPa

9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9 10
Penetration, m m 10 blow s
25 blow s
56 blow s

Dry Density,
Blows Swell, % CBR @ 2.5 mm CBR @ 5.1 mm
Kg/m3
10 1911 0.15 35.5 48.4
25 2010 0.12 65.2 77.7
56 2116 0.08 84.2 95.2
Max. Dry Density, Kg/m3 2114 Opt. Moisture, % 6.9
1. The test result of CBR comply with SAES-Q-006 Sec. 5.2.1 Table-7. 2.The results relate only to the items tested. 3. Specification was
Remarks not provided by the client. 4.The lab is responsible for all the information provided in the report, except when information is provided by
the customer.

Checked By: AlHerz AliHussain CTTA: 0060


Approved By: Riyasat Ansari CTTA: 0344

*** The PDF document is electronically generated and digitally signed ***
CBR-DRY DENSITY RELATION TEST REPORT
Client International Union Contracting Establishment Order No. BQ-CMT-MO-23-00263

Project South Gas Compression Pipeline Report No. BQ-CMT-MR-23-01198

Location Haradh Date Reported 21-Sep-2023

Supplier / Source Barrak Nasser Al Dossari Est. Date Sampled 09-Sep-2023


Sampling Plan /
Sample Location Inplace Sample @ Jobsite Method ASTM D 1883

Test Location FSCL Abqaiq Lab Client Contact Mohamed Saheed Mohamed
0C
Result Provider FSCL Abqaiq Lab Ambient Temp. 23.5
Sample By MUHAMMAD ABID KHAN UMAR KHAN RFI No. PTJ-SGCP-CIV-43555
Test Started Date 16/09/2023 00:00:00 +00:00 Test Complete Date 21-Sep-2023
Material Agg. Base Course Class “B”
Test by MATHEW KANNYAKONIL CHERIAN CTTA: 727

120
115
110
Corrected CBR @ 5.1 mm Penetration

105
100
95
90
85
80
75
70
65
60
55
50
45
40
35
30
1910 1930 1950 1970 1990 2010 2030 2050 2070 2090 2110
Dry Density, kg/m 3

Method ASTM D-1883

Optimum Moisture, % 6.9 CBR @ 95% MDD 74.0


Maximum Dry Density, Kg/m3 2114 CBR @ 100% MDD 95.0
Test Information
* Condition of Sample Soaked Yes/No
* Top 1 inch moisture after soaking 7.3 %
* Surcharge weight used 4.54 Kg
* percent material retained on 19.00 sieve 22.2 %
1. The test result of CBR comply with SAES-Q-006 Sec. 5.2.1 Table-7. 2.The results relate only to the items tested. 3. Specification was
Remarks not provided by the client. 4.The lab is responsible for all the information provided in the report, except when information is provided by
the customer.

Checked By: AlHerz AliHussain CTTA: 0060


Approved By: Riyasat Ansari CTTA: 0344

- End of Report - *** The PDF document is electronically generated and digitally signed ***
Construction Materials_Testing Laboratory 1,;\];9 qflO13l11l[
AbqaiqBranch Z -- -f;-.
Certificate # 3512.02 .,..,:i};'il'{#.lh4"gj,i]#ffi :,",-,."-F""o-suhaimi
SUMMARY OF TEST REPORT
Glient Petrojet / lnternational Union Job No.
1 551 04
Contractinq Establ ishment
Proiect South Gas Compression Pipeline Lab No. BQ-CMT-MO-23-00263

Material Aqq. Base Coarse Class-B Date Sampled 09-Sep-2023


Source Barrak NasserAl Dossary Crusher Date Reported 20-Sep-2023

Location Haradh Sample Received by 1 O-Seo-2023

Test Location FSCL Abqaiq Lab Date Tested '13-19-Sep-2023

Ambient Temp oC
Sampling By Muhamed Abid Khan 23.0

Result Provider FSCL Abqaiq Lab Test Method Various test method

Client Contact Mohamed Saheed Mohamed Sampling


ASTM D75
Planffest Method

Saudi Aramco
Specification
Properties Tested Test Method Results sAES-O-006
Table-6

Can't be
Liquid limit ASTM D 4318 25 max.
moulded

Plasticity lndex ASTM D 4318 Non plastic 6 max

Los Angeles Abrasion yo ASTM C-131 38.6 40 max.

Thin and Elongated Pieces by weight %


5 max.
ASTM D4791 0
1/5 length ( Larger than 25mm)
o
Friable Particles ASTM C-142 0.4 3.0 max

Soundness Magnesium Sulphate o/o


19.6 25 max.
Coarse Aqoreqate
Soundness Magnesium Sulphate yo
ASTM C-88
14.4 25 max.
Fine Aqoreqate

Remarks: Above Physical test result of Base Coarse Class-B Material compliance with Saudi Aramco Specification
SAES-Q-006 Table-6 Section 5.2.1
The results relate only to the items tested. Specification was not provided by the client.
The lab is responsible for all the information provided in the report, except when information is provided by the custom.er

Tested by: Mathew K.C


CTTA # 0727 !l I Division
; ! atr- Ol)
iii,rl0411O
', . .: irsl Berorts)
Reviewed by:
Sr. Lab Supervisor .*Ci-di byHiyasat
Sr. Lab
CTTA # 0060 -End of Report- CTTA

Form No. MAT.4.15 I lssue. 01 I Rev.04 Date: 01 January 2022