LEGEND:
A 10A, TYPE A, CURVE C, 30mA RCBO EARTH ROD
A
FEEDER PILLAR (FP-BSB2) DOUBLE-POLE COPPER CLAD STEEL ROD NO LESS
LOCATED IN "MAINTENANCE ZONE" AT NORTH OF BRIDGE THAN 16mm DIAMETER

BS88 TYPE FUSE. SEE DRAWING SUB-MAINS CABLING

FOR RATING OF DEVICE (REFER TO CABLE SCHEDULE FOR DETAILS)

1
A1-1/BSB2-1 A2-1/BSB2-1 A2-2/BSB2-1 A2-3/BSB2-1 A2-4/BSB2-1 A2-5/BSB2-1 A2-6/BSB2-1 A2-7/BSB2-1 A2-8/BSB2-1 A2-9/BSB2-1 A2-10/BSB2-1 A2-11/BSB2-1 A2-12/BSB2-1 A2-13/BSB2-1 A2-14/BSB2-1 A2-15/BSB2-1 A2-16/BSB2-1 A2-17/BSB2-1 A2-18/BSB2-1 A2-19/BSB2-1 A2-20/BSB2-1 A2-21/BSB2-1 A2-22/BSB2-1 A2-23/BSB2-1 A3-1/BSB2-1
10A RCBO
"A" TYPE LIGHT FITTING. MULTIPLE
2 FINAL CIRCUIT CABLING (XLPE INSULATED,
TYPES. SEE LUMINAIRE SCHEDULE
A1-2/BSB2-1 A2-46/BSB2-1 A2-45/BSB2-1 A2-44/BSB2-1 A2-43/BSB2-1 A2-42/BSB2-1 A2-41/BSB2-1 A2-40/BSB2-1 A2-39/BSB2-1 A2-38/BSB2-1 A2-37/BSB2-1 A2-36/BSB2-1 A2-35/BSB2-1 A2-34/BSB2-1 A2-33/BSB2-1 A2-32/BSB2-1 A2-31/BSB2-1 A2-30/BSB2-1 A2-29/BSB2-1 A2-28/BSB2-1 A2-27/BSB2-1 A2-26/BSB2-1 A2-25/BSB2-1 A2-24/BSB2-1 A3-2/BSB2-1 TUFF SHEATHED)
10A RCBO FOR MORE INFORMATION
(REFER TO CABLE SCHEDULE FOR DETAILS)
3

B Contactor 10A RCBO


A1-3/BSB2-1 A2-47/BSB2-1 A2-48/BSB2-1 A2-49/BSB2-1 A2-50/BSB2-1 A2-51/BSB2-1 A2-52/BSB2-1 A2-53/BSB2-1 A2-54/BSB2-1 A2-55/BSB2-1 A2-56/BSB2-1 A2-57/BSB2-1 A2-58/BSB2-1 A2-59/BSB2-1 A2-60/BSB2-1 A2-61/BSB2-1 A2-62/BSB2-1 A2-63/BSB2-1 A2-64/BSB2-1 A2-65/BSB2-1 A2-66/BSB2-1 A2-67/BSB2-1 A2-68/BSB2-1 A2-69/BSB2-1 A3-3/BSB2-1
"B" TYPE LIGHT FITTING. MULTIPLE B
FINAL CIRCUIT CABLING (H07RN-F FLEXIBLE
TYPES. SEE LUMINAIRE SCHEDULE
4 RUBBER CABLE)
A1-4/BSB2-1 A2-70/BSB2-1 A2-71/BSB2-1 A2-72/BSB2-1 A2-73/BSB2-1 A2-74/BSB2-1 A2-75/BSB2-1 A2-76/BSB2-1 A2-77/BSB2-1 A2-78/BSB2-1 A2-79/BSB2-1 A2-80/BSB2-1 A2-81/BSB2-1 A2-82/BSB2-1 A2-83/BSB2-1 A2-84/BSB2-1 A2-85/BSB2-1 A2-86/BSB2-1 A2-87/BSB2-1 A2-88/BSB2-1 A3-4/BSB2-1 FOR MORE INFORMATION
10A RCBO
(REFER TO CABLE SCHEDULE FOR DETAILS)

5
A1-5/BSB2-1 A2-89/BSB2-1 A2-90/BSB2-1 A2-91/BSB2-1 A2-92/BSB2-1 A2-93/BSB2-1 A2-94/BSB2-1 A2-95/BSB2-1 A2-96/BSB2-1 A2-97/BSB2-1 A2-98/BSB2-1 A2-99/BSB2-1 A2-100/BSB2-1 A2-101/BSB2-1 A2-102/BSB2-1 A2-103/BSB2-1 A2-104/BSB2-1 A3-5/BSB2-1 "C" TYPE LIGHT FITTING. SEE
10A RCBO
FITTING TYPE REFERENCE
240W LIGHTING LUMINAIRE SCHEDULE FOR
UNIQUE FITTING REFERENCE
MORE INFORMATION AX-
XX/BSBX-X
6 DRIVER/6-WAY SERVING DISTRIBUTION BOARD
10A RCBO REFERENCE NUMBER
JUNCTION BOX

3 x 2.5mm HO7RN Flex 7 BRIDGE SPAN LUMINAIRES B1-1/BSB2-1 B1-2/BSB2-1 CONTACTOR WITH OVERRIDE
16A RCBO 7-PIN NEMA SOCKET WITH
SWITCH (REFER TO DRAWING
PHOTOCELL
125A STAND ALONE FOR NUMBER OF POLE'S)
8 BRIDGE SPAN LUMINAIRES
SWITCH-DISCONNECTOR UNIT
16A RCBO

1)
B1-3/BSB2-1 B1-4/BSB2-1
C C
BSB2-
FEEDER PILLAR ENCLOSURE.
WAYS 7 TO 22 ARE ASSIGNED TO THE SUPPLY OF THE BRIDGE SPAN LUMINAIRES. FOR MORE INFORMATION SEE
ST150030-ARU-ELC-06-Z15-
DB-
W AY SP&N ALL CIRCUITS ARE TO BE FED BY 16A, TYPE A, CURVE C, 30mA, RCBO DOUBLE-POLE CIRCUIT-BREAKERS.
DRG-LE-0005 (FEEDER PILLAR
FOR DETAILS OF BRIDGE SPAN LUMINAIRES REFER TO DRAWINGS ST150030-ATK-ELC-06-Z15-DRG-LE-0006 B1-5/BSB2-1 B1-6/BSB2-1
ON BOARD (

CABLE SCHEDULE DETAILS)


and ST150030-ATK-ELC-06-Z15-DRG-LE-0008.

21 BRIDGE SPAN LUMINAIRES REFERENCE PHASE CONDUCTOR SIZE CABLE MAKE-UP CABLE TYPE CPC
100A 34-

16A RCBO DISTRIBUTION BOARD. ALL DB'S TO BE:


B1-7/BSB2-1 B1-8/BSB2-1 SUB-MAINS CABLING
125A RATED BUSBAR
BUTI

22 SUB-00 25mm² 1x1x2C MULTICORE 70°C THERMOPLASTIC INSULATED ARMOURED CU TABLE 4D4 SWA + 16mm² SEP.
BRIDGE SPAN LUMINAIRES 25KA FOR 50MS AT 230V
16A RCBO
STRI

SUB-01 25mm² 1x3x1C SINGLE-CORE 70°C THERMOPLASTIC NON-ARM CU TABLE 4D1 16mm² SEPARATE SEE DRAWING FOR NUMBER OF OUTGOING
WAYS
SUB-02 16mm² 1x3x1C SINGLE-CORE 70°C THERMOPLASTIC NON-ARM CU TABLE 4D1 10mm² SEPARATE
Surge Type
23 B2-1/BSB2-1 B2-2/BSB2-1
DI

SPARE
10A RCBO SUB-03 2.5mm² 1x1x3C XLPE INSULATED, TUFF-SHEATHED NON ARMOURED CABLES (TO BS 5467) TABLE 4D4 INTEGRAL
2 SUB-04 25mm² 1x1x2C MULTICORE 70°C THERMOPLASTIC INSULATED ARMOURED CU TABLE 4D4 SWA + 16mm² SEP.
D D
3 x 2.5mm HO7RN Flex
24 SPARE CLOSE COUPLED SURGE PROTECTION
10A RCBO SUB-05 25mm² 1x1x2C MULTICORE 70°C THERMOPLASTIC INSULATED ARMOURED CU TABLE 4D4 SWA + 16mm² SEP.
B3-1/BSB2-1 B3-2/BSB2-1 ENCLOSURE COMPLETE WITH:
INTEGRAL SURGE
SUB-06 2.5mm² 1x1x3C XLPE INSULATED, TUFF-SHEATHED NON ARMOURED CABLES (TO BS 5467) TABLE 4D4 - 2 PHASE SWITCH FOR ISOLATION
PROTECTION
WAYS 23 TO 31 ARE RESERVED AS SPARE WAYS. ALL CIRCUITS ARE TO BE FITTED WITH 10A, TYPE A, CURVE C, FINAL-CIRCUIT CABLING - 63A BS88 FUSE
30mA RCBO DOUBLE-POLE CIRCUIT-BREAKERS. - TYPE 1 & 2 SURGE PROTECTION DEVICE
CABLING BETWEEN DB AND FIRST LUMINAIRE 2.5MM² 1x1x3C XLPE INSULATED, TUFF-SHEATHED NON ARMOURED CABLES (TO BS 5467) TABLE 4D4 INTEGRAL

Contactor CABLING BETWEEN LUMINAIRES 2.5MM² 1x1x3C H07RN-F FLEXIBLE RUBBER CABLE INTEGRAL

30 SPARE
10A RCBO
FEEDER PILLAR (FP-BSB3)

63A
31 SPARE LOCATED IN "MAINTENANCE ZONE" AT SOUTH OF BRIDGE
10A RCBO

32 PILLAR LIGHT
E 10A RCBO E

33 PILLAR HEATING 1
10A RCBO A1-1/BSB3-1 A2-1/BSB3-1 A2-2/BSB3-1 A2-3/BSB3-1 A2-4/BSB3-1 A2-5/BSB23-1 A2-6/BSB3-1 A2-7/BSB3-1 A2-8/BSB3-1 A2-9/BSB3-1 A2-10/BSB3-1 A2-11/BSB3-1 A2-12/BSB3-1 A2-13/BSB3-1 A2-14/BSB3-1 A2-15/BSB3-1 A2-16/BSB3-1 A2-17/BSB3-1 A2-18/BSB3-1 A2-19/BSB3-1 A2-20/BSB3-1 A2-21/BSB3-1 A3-1/BSB3-1
10A RCBO

34 PILLAR SOCKET OUTLET 2


10A RCBO A1-2/BSB3-1 A2-22/BSB3-1 A2-23/BSB3-1 A2-24/BSB3-1 A2-25/BSB3-1 A2-26/BSB3-1 A2-27/BSB3-1 A2-28/BSB3-1 A2-29/BSB3-1 A2-30/BSB3-1 A2-31/BSB3-1 A2-32/BSB3-1 A2-33/BSB3-1 A2-34/BSB3-1 A2-35/BSB3-1 A2-36/BSB3-1 A2-37/BSB3-1 A2-38/BSB3-1 A2-39/BSB3-1 A2-40/BSB3-1 A2-41/BSB3-1 A2-42/BSB3-1 A3-2/BSB3-1
Surge Type
10A RCBO

125A 6 way SP&N 1&2 3


10A RCBO A1-3/BSB3-1 A2-43/BSB3-1 A2-44/BSB3-1 A2-45/BSB3-1 A2-46/BSB3-1 A2-47/BSB3-1 A2-48/BSB3-1 A2-49/BSB3-1 A2-50/BSB3-1 A2-51/BSB3-1 A2-52/BSB3-1 A2-53/BSB3-1 A2-54/BSB3-1 A2-55/BSB3-1 A2-56/BSB3-1 A2-57/BSB3-1 A2-58/BSB3-1 A2-59/BSB3-1 A2-60/BSB3-1 A2-61/BSB3-1 A2-62/BSB3-1 A2-63/BSB3-1 A3-3/BSB3-1

25mm Singles 4
CALCULATED VALUES (NOTE 13): A1-4/BSB3-1 A2-64/BSB3-1 A2-65/BSB3-1 A2-66/BSB3-1 A2-67/BSB3-1 A2-68/BSB3-1 A2-69/BSB3-1 A2-70/BSB3-1 A2-71/BSB3-1 A2-72/BSB3-1 A2-73/BSB3-1 A2-74/BSB3-1 A2-75/BSB3-1 A2-76/BSB3-1 A2-77/BSB3-1 A2-78/BSB3-1 A2-79/BSB3-1 A2-80/BSB3-1 A2-81/BSB3-1 A3-4/BSB3-1
10A RCBO
PHASE FAULT CURRENT MAX: 2.086KA
10mm 3 core
EARTH FAULT LOOP IMPEDANCE (ZS): 21.27152 O 5
A1-5/BSB3-1 A2-82/BSB3-1 A2-83/BSB3-1 A2-84/BSB3-1 A2-85/BSB3-1 A2-86/BSB3-1 A2-87/BSB3-1 A2-88/BSB3-1 A2-89/BSB3-1 A2-90/BSB3-1 A2-91/BSB3-1 A2-92/BSB3-1 A2-93/BSB3-1 A2-94/BSB3-1 A3-5/BSB3-1
1 2 3 4 5 6
10A RCBO
F F
240W LIGHTING
6 DRIVER/6-WAY

125A 6 way SP&N


C1-3/BSB1-2 10A RCBO
JUNCTION BOX

7 BRIDGE SPAN LUMINAIRES B1-1/BSB3-1 B1-2/BSB3-1


16A RCBO

8 BRIDGE SPAN LUMINAIRES


C1-2/BSB1-2 125A STAND ALONE
16A RCBO
B1-3/BSB3-1 B1-4/BSB3-1

1)
SWITCH-DISCONNECTOR UNIT FEEDER PILLAR (FP-BSB2) FEEDER PILLAR (FP-BSB3)

BSB3-
WAYS 7 TO 22 ARE ASSIGNED TO THE SUPPLY OF THE BRIDGE SPAN LUMINAIRES.
2 X 7-PIN NEMA SOCKET WITH ALL CIRCUITS ARE TO BE FED BY 16A, TYPE A, CURVE C, 30mA, RCBO DOUBLE-POLE CIRCUIT-BREAKERS.

DB-
W AY SP&N

PLE)

PLE)
PHOTOCELL FOR LIGHTING CONTROL FOR DETAILS OF BRIDGE SPAN LUMINAIRES REFER TO DRAWINGSST150030-ATK-ELC-06-Z15-DRG-LE-
0006 B1-5/BSB3-1 B1-6/BSB3-1
(Located centrally of STAIR
bridgeOF
span)
ON BOARD (
C1-1/BSB1-2
(LOCATED ON NORTH BRIDGE)

DGE STRUCTURE

DGE STRUCTURE
andST150030-ATK-ELC-06-Z15-DRG-LE-0008.

M ULTI

M ULTI
FUTURE USE.

N
G G

THI
NOTE 16)

NOTE 16)
OTHER EXPOSED

OTHER EXPOSED
Circuit not part of phase 2 21 BRIDGE SPAN LUMINAIRES

LLAR

LLAR
100A 34-

EARTH BAR W I
M ETALW ORK (

M ETALW ORK (
16A RCBO
hand over. JC B1-7/BSB3-1 B1-8/BSB3-1

ENCLOSURE

ENCLOSURE
FEEDER PI

FEEDER PI
BUTI

1
BSB2-

BSB3-
22 BRIDGE SPAN LUMINAIRES

SPARE (

SPARE (
16A RCBO
STRI

BRI

BRI
DB-

DB-
23 SPARE B2-1/BSB3-1 B2-2/BSB3-1

Surge
DI

10A RCBO
NG

LLAR SOCKET

Type 1 & 2
LLAR HEATI

2 2
24 SPARE 16mm 16mm
10A RCBO B3-1/BSB3-1 B3-2/BSB3-1
OUTLET
LLAR
SPARE

SPARE

SPARE

SPARE

GHT
SPARE

SPARE

SPARE

WAYS 23 TO 31 ARE RESERVED AS SPARE WAYS. ALL CIRCUITS ARE TO BE FITTED WITH 10A, TYPE A, CURVE C,
PI

PI
PI
LI

30mA RCBO DOUBLE-POLE CIRCUIT-BREAKERS.


H H
10A 10A 10A 10A 10A 10A 10A 10A 10A
63A 6A 63A 63A 6A 63A 63A
RCBO RCBO RCBO RCBO RCBO RCBO RCBO RCBO RCBO
30
02

03

04

SPARE
06
05
SUB-

SUB-

SUB-

SUB-
SUB-

10A RCBO

1 2 3 4 5 6 1 2 3 4 5 6 7 8 9 10
31
10A RCBO
SPARE
NOTE : All Surge Protection - 10mm Singles
FEEDER PILLAR (FP-BSB1)
63A
DISTRIBUTION BOARD (DB-BSB1-2) DISTRIBUTION BOARD (DB-BSB1-1) 32 PILLAR LIGHT

NG
125A 6-WAY SP&N 125A DIN RAIL ENCLOSURE SP&N 10A RCBO

ON

ON
CES /
10mm 3core

RED)

RED)
AL BONDI

PLE)

NG PROTECTI

NG PROTECTI
Surge Type
(NOTE 12)
33 PILLAR HEATING

C SERVI
125A SWITCH-DISCONNECTOR 125A SWITCH-DISCONNECTOR

F REQUI

F REQUI
M ULTI
1&2
10A RCBO

CE

NOTE 16)
DUAL
(WITHIN DISTRIBUTION BOARD) (WITHIN DISTRIBUTION BOARD)

BSB1 SURGE
CURRENT DEVI

LLAR

ON

POTENTI
34 PILLAR SOCKET OUTLET

ELEM ENTS (
ENCLOSURE
300M A RESI

SUPPRESSI
I I

FEEDER PI

TO M ETALI
10A RCBO

I
1

SYSTEM (

SYSTEM (
ON/

BSB1-

BSB1-
125A 6 way SP&N Surge

GHTNI

GHTNI

SPARE (
CALCULATED VALUES (NOTE 13):

SCONNECTI
Type 1 & 2
SURGE

EQUI
PHASE FAULT CURRENT MAX.: 11.897KA

DB-

DB-
FP-
PROTECTION

LI

LI
EARTH FAULT LOOP IMPEDANCE (ZS): 21.02636 O

NK
Sub-01

TEST LI
CALCULATED VALUES (NOTE 13)
2
PHASE FAULT CURRENT MAX: 0.987KA 70mm

DI
300mA TIME-DELAYED L N
RCD EARTH FAULT LOOP IMPEDANCE (ZS): 21.58542 O 2
16mm
RESIDUAL CURRENT DEVICE
N

25mm 2core
OFF
125A STAND ALONE AUTO ON
SWITCH-DISCONNECTOR UNIT 2
70mm
(LOCKABLE)
FEEDER PILLAR (FP-BSB1)
EARTH ELECTRODE
Sub-00 LOCATED IN BOORD STREET L N L N
J SYSTEM J
100A DNO CUT-OUT 230V, 50Hz, SINGLE PHASE.
FUSE RATING AND METERING ARRANGEMENT TO BE
DNO FEEDER PILLAR
CONFIRMED BY DNO UPON APPLICATION.
PROPOSED TO BE LOCATED IN DNO Feeder Pillar INDICATIVE PHOTOCELL AND CONTACTOR

Located in South Compound


ASSUMED SUPPLY CHARACTERISTICS (NOTE 13):
BOORD STREET ADJACENT TO FP-BSB1 CONNECTION DETAIL INDICATIVE EARTHING SCHEMATIC
MAXIMUM PROSPECTIVE FAULT CURRENT (IPF): 16KA
EXTERNAL EARTH FAULT LOOP IMPEDANCE (ZE): 21O

Key plan NOTES: Project Title


1. DO NOT SCALE FROM THIS DRAWING. 8. THE CONTRACTOR SHALL CARRY OUT ALL FINAL CONNECTIONS BETWEEN ISOLATORS, FIXED
2. THIS DRAWING SHOULD BE VIEWED IN COLOUR. EQUIPMENT, AND LIGHT FITTINGS AS DETAILED ON THE DRAWINGS.
Silvertown Tunnel Boord Street Footbridge
3. THIS DRAWING SHALL BE READ IN CONJUNCTION WITH ALL OTHER PROJECT DOCUMENTS, 9. ALL ISOLATION DEVICES SHALL HAVE THE ABILITY TO BE PADLOCKED WITHOUT PROPRIETY
SPECIFICATIONS AND DRAWINGS. IN PARTICULAR THIS DRAWING SHOULD BE READ IN DEVICE. Originator
10.THE BRIDGE HAS ANTICIPATED MAXIMUM LOAD DEMAND OF 9.39KW/ 40.84A (SINGLE-PHASE). Main Electrical and Lighting
CONJUNCTION WITH:
K - LIGHTING LAYOUT DRAWINGS: ST150030-ARU-ELC-06-ZZ-DRG-LE-0004, THIS FIGURE IS INCLUSIVE OF 20% SPARE CAPACITY. K
11.ALL PROTECTIVE DEVICES SUPPLYING THE OUTGOING WAYS ON DISTRIBUTION BOARD ARUP Schematic
ST150030-ARU-ELC-06-ZZ-DRG-LE-0005, AND ST150030-ATK-ELC-06-Z15-DRG-LE-0018.
ed

- DESIGN REPORTS AND APPENDICES: ST150030-ARU-BAS-06-Z15-RPT-LE-0001 AND DB-BSB1-2, MUST HAVE A [ICS] RATED SERVICE BREAKING CAPACITY OF e=15KA. Location
ct

ST150030-ATK-ELC-06-Z15-RPT-LE-0001 12.ALL CALCULATED VALUES ARE BASED UPON ASSUMED SUPPLY CHARACTERISTICS.
Redline Drawing
i

- ELECTRICAL DISTRIBUTION AND EQUIPMENT LAYOUT: ST150030-ARU-ELC-06-Z15-DRG-LE-0004 ASSUMED SUPPLY CHARACTERISTICS HAVE BEEN CHOSEN BASED UPON THE GUIDANCE OF
r

X01 29/07/23 Greenwich


Rest

ENGINEERING RECOMMENDATIONS (ENA) P23/2:2018 AND P25/2:2017. CALCULATED VALUES


- LIGHTING AND ELECTRICAL DISTRIBUTION DETAILS DRAWING: JC LF
ST150030-ARU-ELC-06-Z15-DRG-LE-0004 ARE STATED BASED UPON THE LOAD END OF THE SUPPLY CABLE.
Asset Classification
THE CONTRACTOR SHOULD DO A FULL SITE SURVEY, ENSURING THAT ALL CONSTRAINTS ARE 13.ALL EARTH BARS SHALL BE HARD DRAWN COPPER 50MM (WIDE) X 3MM (DEEP), MOUNTED ON P00 19/07/21

UNDERSTOOD BEFORE ANY ORDERS ARE PLACED. INSULATING SPACERS. EARTH BAR LENGTHS SHOULD BE DETERMINED ON SITE BASED UPON --- --- --- --- ---

4. INSTALLATION, TESTING AND COMMISSIONING OF ELECTRICAL WORKS ARE TO COMPLY FULLY REQUIRED NUMBER OF CONNECTIONS. Issued for Detailed Design Electrical Systems
P01 12/11/21
WITH THE “REQUIREMENTS FOR ELECTRICAL INSTALLATIONS”BS 7671:2018 (IET WIRING 14.MAIN EQUIPOTENTIAL BONDING CONDUCTORS SHALL BE SINGLE CORE PVC NON ARMOURED AO RN --- --- ---
GREEN AND YELLOW. Lifecycle
5. REGULATIONS 18TH EDITION). Issued for Detailed Design
ELECTRICAL CONTRACTOR TO INCLUDE FOR ALL OUTGOING WAYS TO BE C/W ENGRAVED 15.ALL EARTH BAR SPARE WAYS TO BE PRE-DRILLED COMPLETE WITH TERMINAL BOLTS. 25% P02 03/02/22

TRAFFOLYTE LABEL SECURELY FIXED. SPARE CAPACITY SHALL BE ALLOWED ON ALL EARTH BARS AT PRACTICAL COMPLETION. AO RN --- --- ---
Detailed Design
L L
6. ALL SWITCHBOARD AND DISTRIBUTION BOARDS WILL BE PROVIDED WITH A MINIMUM OF 25% 16.THE EARTHING INSTALLATION SHALL BE IN ACCORDANCE WITH THE LATEST VERSIONS OF BS Issued for Detailed Design
P03 05/04/22
SPARE OUTGOING WAYS. 7671 AND BS 7430. Suitability Drawing Number Rev.
X01
AO RN LE --- ---
7. THE CONTRACTOR SHALL SUPPLY AND INSTALL LAMINATED TYPED CIRCUIT CHARTS TO THE 17.THE ARMOUR/SHEATH OF ALL LV CABLES SHALL BE BONDED TO EARTH ON BOTH THE
Purpose / Description
INSIDE OF ALL DISTRIBUTION BOARD COVERS. SUPPLY AND LOAD ENDS OF THE CABLE. Rev Date
S3 For Review & Comment ST150030-ARU-ELC-06-Z15-DRG-LE-0006 P03
Drawn T. Checked T. Approved P. Approved Authorised