You are on page 1of 928

1 2 3 4 5 6 7 8

A A

B B

B 24/11/2020 2nd FOR APPROVED

A 12/10/2020 1st FOR APPROVED

REV. DATE DESCRIPTION

CUSTOMER

C C
POWER ENGINEERING CONSULTING J.S.C. 2

PROJECT

TAN THUAN OFFSHORE WIND POWER PLANT

D D

LOCATION

TAN THUAN OFFSHORE WIND POWER PLANT

DRAW. NAME STAMP

- CONTROL, PROTECTION & MEASUREMENT PRINCIPLE DIAGRAM


E E
- LAYOUT CONTROL PROTECTION PANEL

DRAWING NO. PECC2/TT-110KV/BASIC

STANDARD: IEC PAGE: A00 TOTAL NO. OF PAGE: 5

DESIGNED NGUYEN VAN NHAT CONTRACTOR

CHECKED NGUYEN VAN CHUNG


F F
APPROVED NGUYEN DINH TUAN
ENERGY TECHNOLOGY
JOINT STOCK COMPANNY
DATE 24/11/2020 Rev.: B

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

PAGE DESCRIPTION REV. X PAGE DESCRIPTION REV. X

=BASIC/A00 PRINCIPLE DIAGRAMS & LAYOUT OF CONT. & PROT. PANEL B


A A
=BASIC/A01 TABLE OF CONTENTS : =BASIC/A00 - =BASIC/A04 B
=BASIC/A02 SYMBOL OF FUNCTIONS B
=BASIC/A03 CONTROL, PROTECTION & MEASUREMENT PRINCIPLE DIAGRAM B
=BASIC/A04 LAYOUT DRAWING B

B B

C C

D D

E E

X: AUTOMATIC PAGE MODIFIED

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =BASIC


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY DATE 24/11/2020
APPROVED NGUYEN DINH TUAN TABLE OF CONTENTS : =BASIC/A00 - =BASIC/A04 PECC2/TT-110KV/BASIC
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

KÝ HIỆU MÔ TẢ KÝ HIỆU MÔ TẢ

21/21N DISTANCE PROTECTION 86 TRIP-LOCKOUT RELAY


A A
25 SYNCHROCHECK 87B BUSBAR DIFFERENTIAL PROTECTION

26 THERMAL PROTECTION 87L LINE DIFFERENTIAL PROTECTION

27 UNDERVOLTAGE PROTECTION 87N RESTRICTED GROUND FAULT PROTECTION

33 POSITION BLOCK RELAY 87S STUB DIFFERENTIAL PROTECTION

49 THERMAL OVERLOAD PROTECTION 87T TRANSFORMER DIFFERENTIAL PROTECTION

50 INSTANTANEOUS OVERCURRENT PROTECTION 90 AUTOMATIC CONTROL VOLTAGE RELAY


B B
50BF CIRCUIT-BREAKER FAILURE PROTECTION 94 TRIPPING RELAY

50G INSTANTANEOUS GROUND OVERCURRENT PROTECTION 96 GAS RELAY

50N INSTANTANEOUS NEUTRAL OVERCURRENT PROTECTION FR FAULT RECORDER

51 TIME OVERCURRENT PROTECTION FL FAULT LOCATOR

51G TIME GROUND OVERCURRENT PROTECTION SOTF SWITCH ON TO FAULT

51N TIME NEUTRAL OVERCURRENT PROTECTION BCU BAY CONTROL UNIT


C C
5IUb UNBALANCE OVERCURRENT PROTECTION A CURRENT MEASUREMENT FUNCTION

51/27 VOLTAGE CONTROLLED OVERCURRENT V VOLTAGE MEASUREMENT FUNCTION

59 OVERVOLTAGE PROTECTION f FREQUENCY MEASUREMENT FUNCTION

59N ZEZO-SEQUENCE OVERVOLTAGE PROTECTION ‎cosφ POWER FACTOR MEASUREMENT FUNCTION

63 PRESSURE RELAY W EFFECTIVE POWER MEASUREMENT FUNCTION

D 64 GROUND DETECTOR RELAY VAR REACTIVE POWER MEASUREMENT FUNCTION D

67 DIRECTIONAL OVERCURRENT RELAY Wh ACTIVE ENERGY MEASUREMENT FUNCTION

67N DIRECTIONAL OVERCURRENT PROTECTION FOR GROUND FAULTS VARh REACTIVE ENERGY MEASUREMENT FUNCTION

67NS DIRECTIONAL SENSITIVE GROUND-FAULT DETECTION

68 POWER-SWING BLOCKING

71 LEVEL OIL RELAY


E E
74 TRIP CIRCUIT SUPERVISION

79 AUTO RECLOSING

81 FREQUENCY PROTECTION

85 COMBINATION OF PROTECTION

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =BASIC


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY BASIC DRAWING DATE 24/11/2020
APPROVED NGUYEN DINH TUAN SYMBOL OF FUNCTIONS PECC2/TT-110KV/BASIC
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

110kV DAM DOI SUBSTATION 110kV DONG HAI SUBSTATION


XF21 110 0.11 0.11 110 0.11 0.11 XF21
F21(P445) kV kV F21(P445)
3 3 3 QL09 3 3 3
XF21 67/67N 51/51N 50/50N 68 M
67/67N 51/51N 50/50N 68 XF21
A 85 FR 21/21N 85 FR 21/21N
A
#16: TO FR

27/59 LVT 27/59


LVT1 XF87B F87B(P746)
XF87B
#10: FROM CT E01
XF87L #5: FROM CT E02 XF87L

#17: TO FR
F87L(P543) #7: TO FR (7KE85)
87B 50BF F87L(P543)
XF87L QE76 QE76 #8: TO FR (7KE85)
87L FR 21/21N 67/67N 50/50N CL: 0.5 QL07 CL: 0.5 87L FR 21/21N 67/67N 50/50N
XF87L
M
F21(P445) QL07 M XF87L XF87L
XF21
CL: 0.5 XF21 CL: 0.5
51/51N 85 FL 25/79 SOTF QE75 21/21N 67/67N 50/50N 68 QE75 51/51N 85 FL 25/79 SOTF
CL: 3P CL: 5P20 51/51N 85 FL FR SOTF
CL: 3P
XTV1 XTC1 CL: 5P20 XTC1 XTV1
PMF(ELITE 448) XTV1 PMF(ELITE 448)
CL: 0.5 F272(P141)
CT-123kV 27/59, 81 CL: 0.5
U,I,P,Q,f,pF... CL: 0.5
400-800-1200 XTV2
CT-123kV U,I,P,Q,f,pF...
XTV2 CL: 0.5 XTV1
CL: 5P20 /1/1/1/1/1A F271(P141)
400-800-1200
BCU(C264) 27/59, 81 BCU(C264)
XTC2 CL: 5P20 /1/1/1/1A CL: 5P20
XTC2

#11: FROM VT C12

#13: FROM VT C11


XTV3 XTV2
25/BCU VDF-10 BJ-8RP CL: 5P20 25/BCU
F74-1, F74-2 F86-1, F86-2

#14: TO PMV1 (E03)


=E05+CRP5

#13: TO F271 (E05)


QF01 QF01
#11: TO F21 (E05)

VDF-10 BJ-8RP BJ-8RP VDF-10


=E04+CRP4 F74-1, F74-2 F86-1, F86-2 F86-1, F86-2 F74-1, F74-2 =E03+CRP3
B B
XTV3 QE25 QE15 XTV3
XTC3 XTC3

CL: 5P20
CL: 0.5
CL: 0.5
QL02

CL: 5P20
CL: 5P20
PMT(A1700) CL:0.5 M QL01 M PMT(A1700) CL:0.5
U,I,P,Q,kWh,kVArh... QL02 QL01 U,I,P,Q,kWh,kVArh...
C12 QF01
M M C11
=E00+MP1 =E00+MP1
110 0.11 0.11 110 0.11 0.11
kV QL02 M QE24 QE25 CT-123kV QE15 QE14 M QL01 kV
3 3 3 3 3 3
QE25 600-800-1200 #15: TO FR (7KE85) QE25
CL: 3P CL: 3P /1/1/1/1A CL: 3P CL: 3P
CL: 0.5 CL: 0.5 CL: 0.5 CL: 0.5
XTV4
CL: 0.5 CL: 0.5 BCU(C264) XTC1 CL: 0.5 CL: 0.5
CL: 0.2 CL: 0.2 QF01 25/BCU QF01 CL: 0.2 CL: 0.2
CT-123kV PMV1(AN32)
CL: 5P20 200-400-600 U CL: 5P20

XTV1 XTC1 CL: 5P20 /1/1/1/1/1A PMV2(AN32) XTV3 CL: 5P20 XTC1 XTV1
PMT(A1700) CL:0.2 #6: TO FR (7KE85) #9: TO FR (7KE85) PMT(A1700) CL:0.2
C CL: 0.2 U CL: 0.2
C
U,I,P,Q,kWh,kVArh... =E05+CRP5 CT-123kV U,I,P,Q,kWh,kVArh...
CL: 0.5 200-400-600 CL: 0.5
XTV2 XTC2 XTC2 XTV2
PMT(A1700) CL: 0.5 CL: 5P20 /1/1/1/1/1A CL: 5P20 PMT(A1700) CL: 0.5
#5: TO F87B (P746) #10: TO F87B (P746)
U,I,P,Q,kWh,kVArh... XTV1 XTC1 U,I,P,Q,kWh,kVArh...
FR(7KE85) #6: CT E02
=E00+MP2 XTV3 XTC2
#7:FROM F87L(E04) =E00+MP1
XTV2 XTC3
#16: FROM LVT E04 FR #15: CT E05
XTV1 XTC1 XTV5 XTC4 XTC1 XTV1
PMF(ELITE 448) #8:FROM F87L(E03) PMF(ELITE 448)
XTV4 XTC5
U,I,P,Q,f,pF... HV-BCT CL: 0.5 CL: 0.5 HV-BCT U,I,P,Q,f,pF...
XTV3 96 26 26 96 XTV3
XTC3 CL: 5P20 XTC6 CL: 5P20 XTC3
CL: 5P20

CL: 5P20
BCU(C264) 71 63 XTV6 PQ1 (7KG95)
63 71 CL: 5P20 BCU(C264)
XTV4 CL: 5P20 U XTV4
BCU XTC7
BCU
XTV7

#17: FROM LVT E03


PQ2 (7KG95)

#9: CT E01
D XTV2 F90 (C264) XTC2 U
XTC2 F90 (C264) XTV2 D
=E00+FR
90 90
#17: TO PQ1 (7KG95)

#16: TO PQ2 (7KG95)


CL: 5P20 CL: 5P20
XF67 F67(P143) CL: 0.5 CL: 0.5 F67(P143) XF67
CL: 5P20 CL: 5P20
67/67N 51/51N 50/50N XF67 CL: 5P20 CL: 5P20 XF67 50/50N 51/51N 67/67N

TO TRANSDUCER

TO TRANSDUCER

TO TRANSDUCER

TO TRANSDUCER
#16: FROM BCU

#17: FROM BCU


27/59 86 25 #1 TO F67-J13 CL: 5P20 CL: 5P20 #1 TO F67-J01 25 86 27/59
XF87T MV-BCT T2 T1 MV-BCT XF87T
F87T(P643) MV 22KV - LS MV 22KV - LS F87T(P643)
CL: 0.5 CL: 0.5
TO MP2 PANEL TO MP1 PANEL
87T 50/51 50/51N 64 64 50/51N 50/51 87T
-38 -38
50REF1 50REF2 49 49 50REF2 50REF1
CT-24KV CT-24KV
#1: TO FR (7KE85)

#2: TO PQ1 (7KG95)

#4: TO PQ1 (7KG95)

#3: TO FR (7KE85)
CL: 0.5 CL: 0.5
1500-2500 TO MP2 PANEL TO MP1 PANEL 1500-2500
BJ-8RP VDF-10
/1/1/1A CL: 5P20 CL: 5P20 /1/1/1A VDF-10 BJ-8RP
E E
=E02+CRP2 F86-1, F86-2 F74-1, F74-2 CL: 5P20 CL: 5P20 F74-1, F74-2 F86-1, F86-2
=E01+CRP1

J
J13 432 431 J01
C42 C41
-24 TU-C42 TU-C41 -14
22 0.11 0.11 22 0.11 0.11
kV kV
3 3 3 3 3 3
CL: 0.5 CL: 0.5
TO MP2 PANEL TO MP2 PANEL

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =BASIC


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY BASIC DRAWING
CONTROL, PROTECTION & MEASUREMENT PRINCIPLE
DATE 24/11/2020
APPROVED NGUYEN DINH TUAN PECC2/TT-110KV/BASIC
DIAGRAM
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A
FRONT VIEW FRONT VIEW FRONT VIEW FRONT VIEW FRONT VIEW

ENTEC =E05+CRP5 ENTEC =E04+CRP4 ENTEC =E03+CRP3 ENTEC =E02+CRP2 ENTEC =E01+CRP1

BUS SECTION BAY TO 110kV DAM DOI TO 110kV DONG HAI T2 TRANSFORMER BAY T1 TRANSFORMER BAY

SW SW

F87B F87L F87L F87T F87T


MiCOM P 746 MiCOM P 143 MiCOM P 143 MiCOM P 143 MiCOM P 143

ALARM ALARM ALARM ALARM ALARM ALARM ALARM ALARM ALARM ALARM

ALARM ALARM ALARM ALARM ALARM ALARM ALARM ALARM ALARM ALARM

ALARM ALARM ALARM ALARM ALARM ALARM ALARM ALARM ALARM ALARM

ALARM
c ALARM ALARM
c ALARM ALARM
c ALARM ALARM
c ALARM ALARM
c ALARM

c LEAR ALARM c LEAR ALARM c LEAR ALARM c LEAR ALARM c LEAR ALARM
READ READ READ READ READ
ALARM ALARM ALARM ALARM ALARM
ENTER ENTER ENTER ENTER ENTER
ALARM ALARM ALARM ALARM ALARM

ALARM ALARM ALARM ALARM ALARM


SCHNEIDER ALSTOM ALSTOM ALSTOM ALSTOM

F21 F21 F21 F67 F67


B MiCOM P P142 MiCOM P P142 MiCOM P P142
MiCOM P 143 MiCOM P 143 B
ALARM ALARM ALARM ALARM
ALARM ALARM ALARM ALARM ALARM
ALARM ALARM ALARM
ALARM ALARM
ALARM ALARM ALARM ALARM ALARM
ALARM ALARM ALARM
ALARM ALARM
ALARM ALARM ALARM ALARM ALARM
c ALARM
c ALARM
ALARM
c ALARM
c ALARM ALARM
c ALARM
ALARM ALARM ALARM ALARM
c LEAR ALARM c LEAR ALARM
c LEAR ALARM c LEAR ALARM
c LEAR ALARM READ
ALARM
READ
ALARM
READ READ READ ENTER ENTER
ALARM ALARM ALARM
ENTER ENTER ENTER ALARM ALARM
ALARM ALARM ALARM
ALARM ALARM
ALARM ALARM ALARM ALSTOM ALSTOM
ALSTOM ALSTOM ALSTOM

BCU BCU BCU BCU BCU


PMV1 PMV2
V ALARM

ALARM

ALARM

ALARM
c

V
ALARM

ALARM

ALARM

ALARM
c ALARM

ALARM

ALARM

ALARM
c ALARM

ALARM

ALARM

ALARM
c ALARM

ALARM

ALARM

ALARM
c

ALARM ALARM ALARM ALARM ALARM

ALARM ALARM ALARM ALARM ALARM

ALARM
o I L/R
ALARM
o I L/R
ALARM
o I L/R
ALARM
o I L/R
ALARM
o I L/R
ALARM ALARM ALARM ALARM ALARM

S.VS1 S.VS2
S.AM1 S.M/S/I S.R/O/L S.L/R S.ES S.AM1 S.M/S/I S.R/O/L S.L/R S.ES

S.B/M S.25 S.50BF S.87B S.AM2 S.FC1 S.FC2 PLF1 PLF2 S.AM2 S.FC1 S.FC2 PLF1 PLF2

C S.LT P.LC S.86


HI
PTP
DIGITAL MULTI METER
HI
PTO
DIGITAL MULTI METER
HI
PTW1
DIGITAL MULTI METER
HI
PTW2
DIGITAL MULTI METER
HI
PTP
DIGITAL MULTI METER
HI
PTO
DIGITAL MULTI METER
HI
PTW1
DIGITAL MULTI METER
HI
PTW2
DIGITAL MULTI METER
C
2200

GO GO GO GO GO GO GO GO

LO LO LO LO LO LO LO LO
MD MD MD MD MD MD MD MD
MT4W Autonics MT4W Autonics MT4W Autonics MT4W Autonics MT4W Autonics MT4W Autonics MT4W Autonics MT4W Autonics

F271 -SQL02 PMF PMF PMF PMF


-SQE24 S.RE S.LT S.RE S.LT S.RE S.LT S.RE S.LT
MiCOM P P142
-SQL02 -SQL01 -SQL02 -SQL01
ALARM

ALARM
ALARM

ALARM
-SQE25 S.B/M S.87L -SQE25 S.B/M S.87L -SQE15 S.B/M S.QE25 S.B/M S.QE15
ALARM ALARM
c
-SQF01
ALARM ALARM I U P Q I U P Q I U P Q I U P Q

c LEAR ALARM
READ
ALARM
ENTER

S.25 S.25
ALARM

ALARM
S.25 S.81 -SQF01 S.25 S.81 -SQF01 -SQF01 -SQF01
ALSTOM
P.LC P.LC P.LC P.LC P.LC

F272 -SQL01 S.79 S.79 S.81 S.81


MiCOM P P142 -SQE15 -SQE75 -SQE75
T2 T1
ALARM ALARM
-SQL07 -SQL07
ALARM ALARM

ALARM ALARM

ALARM
c ALARM

c LEAR
READ
ENTER
ALARM

ALARM -SQL09 F90 F90


-SQE14 -SQE76 -SQE76
ALARM

ALARM
ALSTOM
22KV 22KV
D D

F861 F862 F741 F742 F861 F862 F741 F742 F861 F862 F741 F742 F861 F862 F741 F742 F861 F862 F741 F742

XTV3 XTV4 XTV3 XTV3 XTC3 XTV3 XTV4 XTC3


XF87B.1
XF87B.2
XF87B.3

XF87T.1
XF87T.2

XF87T.1
XF87T.2
XTV3 XTV4
XF271
XF272

XF87L

XF87L
XF21

XF21

XF21

XF67

XF67
XTC XTV1 XTV2 XTC1 XTC2 XTV1 XTV2 XTC1 XTC2 XTV1 XTV2 XTC1 XTC2 XTV1 XTV2 XTC1 XTC2 XTV1 XTV2

E E
100 800 800 800 800 800

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =BASIC


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE =E00+SP/A00

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY BASIC DRAWING DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LAYOUT DRAWING PECC2/TT-110KV/BASIC
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

B B

B 24/11/2020 2nd FOR APPROVED

A 12/10/2020 1st FOR APPROVED

REV. DATE DESCRIPTION

CUSTOMER

C C
POWER ENGINEERING CONSULTING J.S.C. 2

PROJECT

TAN THUAN OFFSHORE WIND POWER PLANT

D D

LOCATION

TAN THUAN OFFSHORE WIND POWER PLANT

DRAW. NAME STAMP

E =E00+SP: SERVER PANEL E

DRAWING NO. PECC2/TT-110KV/SERVER

STANDARD: IEC PAGE: A00 TOTAL NO. OF PAGE: 16

DESIGNED NGUYEN VAN NHAT CONTRACTOR

CHECKED NGUYEN VAN CHUNG


F F
APPROVED NGUYEN DINH TUAN
ENERGY TECHNOLOGY
JOINT STOCK COMPANNY
DATE 24/11/2020 Rev.: B

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

PAGE DESCRIPTION REV. X PAGE DESCRIPTION REV. X

=E00+SP/A00 SERVER PANEL B


A A
=E00+SP/A01 TABLE OF CONTENTS : =E00+SP/A00 - =E00+SP/X107 B
=E00+SP/A02 LIST OF EQUIPMENTS C
=E00+SP/B01 OUTLINE DRAWING B
=E00+SP/D01 AC POWER SUPPLY B
=E00+SP/D02 AC POWER SUPPLY B
=E00+SP/G01 DC POWER SUPPLY B

B =E00+SP/G02 DC POWER SUPPLY B B


=E00+SP/X100 Terminal diagram =E00+SP-XAC1 B
=E00+SP/X101 Terminal diagram =E00+SP-XAC2 B
=E00+SP/X102 Terminal diagram =E00+SP-XAC3 B
=E00+SP/X103 Terminal diagram =E00+SP-XAC4 B
=E00+SP/X104 Terminal diagram =E00+SP-XDC B
=E00+SP/X105 Terminal diagram =E00+SP-XDC1 B
C =E00+SP/X106 Terminal diagram =E00+SP-XDC2 B C

=E00+SP/X107 Terminal diagram =E00+SP-X9 B

D D

E E

X: AUTOMATIC PAGE MODIFIED

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY SERVER PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN TABLE OF CONTENTS : =E00+SP/A00 - =E00+SP/X107 PECC2/TT-110KV/SERVER

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

NO. SYMBOL DESCRIPTION MANUFACTORY CODE QTY. UNIT NOTE CUBICLE

1 HIS HIS COMPUTER ADVANTECH ACP-4340 01 Pcs =E00+SP


A A
2 GTW1 GATEWAY 1 COMPUTER ADVANTECH ACP-4340 01 Pcs =E00+SP

3 GTW2 GATEWAY 2 COMPUTER ADVANTECH ACP-4340 01 Pcs =E00+SP

4 GPS GPS TIME SERVER HOPF 8030NTS/GPS 01 Pcs =E00+SP

5 SW ETHERNET SWITCH KYLAND SICOM3024P-2GX4M20T-ST05-HV-HV 01 Pcs =E00+SP

6 INV1, 2 INVERTER YUCOO YKDA-HD2000 02 Pcs =E00+SP

7 FQAC1 MCB AC FOR LIGHTING AND HEATING LEGRAND DX3 01 SET =E00+SP
B B
8 FQINV1.2, FQINV2.2 MCB AC INCOMING FOR INVERTER LEGRAND DX3 02 SET =E00+SP

9 FQINV1.1, FQINV2.1 MCB DC INCOMING FOR INVERTER LEGRAND DX3 DC 02 SET =E00+SP

10 FQINV MCB AC OUTGOINGFOR INVERTER LEGRAND DX3 01 SET =E00+SP

11 FQAC2 MCB AC FOR TABLE CONTROL LEGRAND DX3 01 SET =E00+SP

FQDC1, FQDC2
12 MCB DC FOR SWITCH AND GPS LEGRAND DX3 DC 03 SET =E00+SP
FQDC3

13 FQDC4, FQDC5 MCB DC FOR COMPUTER LEGRAND DX3 DC 03 SET =E00+SP


C C
14 KQP, KQP1 CONTACTOR ABB ESB25 02 SET =E00+SP

15 XDC..., XAC... POWER TERMINALS DEGSON PC6 01 LOT =E00+SP

16 F1, F2, F3, F4 FAN VN 220VAC 04 SET =E00+SP

17 B0 THERMOSTAT CYMAX 01 SET =E00+SP

18 B1 DOOR LIMIT SWITCH CHINA 01 SET =E00+SP

D 19 E0 HEATING RESISTER CYMAX 01 SET =E00+SP D

20 E1 LIGHTING LAMP CHINA 01 SET =E00+SP

21

22

23

24

E 25
E

26

27

28

29

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY SERVER PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LIST OF EQUIPMENTS PECC2/TT-110KV/SERVER
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

FRONT VIEW REAR VIEW SIDE VIEW


A A
ENTEC =E00+SP

NOTE
GPS
TAG NAME DESCRIPTION
GTW1 GATEWAY COMPUTER 1
MCB AC MCB DC
GTW2 GATEWAY COMPUTER 2
INV1, 2 INVERTER
SWITCH1
SWITCH ETHERNET SWITCH
GTW1 GPS GPS TIME SERVER

B B
Advantech

GTW2
2200

Advantech

GTW2

Advantech

C C
INV1

INV2

B B

D 100 A 800 750


D
800 NAMEPALTE (SCALE 1:5)
B-B
100

C =E00+SP

45
750
800
200
746
550
800

C (Scale 1:5) REMARK:


E 4x∅14 IP DEGREE: IP41 E
Ø14 APPLICATION STANDARD: IEC60529
25 MATERIAL: STEEL
750 STEEL THICKNESS: 2mm
PAINT COLOR: RAL7032
800 DOOR APPLY AREA: FRONT AND REAR
OPEN DOOR: 180°

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE D01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY SERVER PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN OUTLINE DRAWING PECC2/TT-110KV/SERVER
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=N00+AC

POWER FOR LIGHTING


A AND HEATING A

-W089
L1 1 -XAC1 1 -XAC1 2 INV1.L
=N00+AC/D06.2 / / D02.2
220 VAC
N1 2 -XAC1 4 -XAC1 5 INV1.N
=N00+AC/D06.2 / / D02.2
-W090
L2 1 -XAC2 1 -XAC2 2 INV2.L
=N00+AC/D06.2 / / D02.5
220 VAC
N2 2 -XAC2 4 -XAC2 5 INV2.N
=N00+AC/D06.2 / / D02.5
-W091

=N00+AC/D07.2 /
L3 1 -XAC5 1 -XAC5 2
B 220 VAC
B
=N00+AC/D07.2 /
N3 2 -XAC5 3 -XAC5 4

1 3

-FQAC1
2P-16A I> I>

C 2 4 C

LIGHTING FAN HEATING SOCKET

C
-B0 P
D 0÷90°C F H D
1
-B1
6A 2

x1 x1 x1 x1

-FAN 1 -FAN 2 -FAN 3 -FAN 4


E 1
x2 x2 x2 x2
1
E

-E1 -XSK
8W 16A
2 2

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE D01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE D02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY SERVER PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN AC POWER SUPPLY PECC2/TT-110KV/SERVER
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A AC POWER FOR DC POWER FOR AC POWER FOR DC POWER FOR A


INVERTER INVERTER INVERTER INVERTER

D01.7

D01.7

D01.7

D01.7
G01.7

G01.7

G01.7

G01.7
DCINV1+

DCINV2+
DCINV1-

DCINV2-
INV1.N

INV2.N
INV1.L

INV2.L
1 3 1 3 1 3 1 3
B B
-FINV1.2 -FINV1.1 -FINV2.2 -FINV2.1
2P-32A I> I> 2P-32A I> I> 2P-32A I> I> 2P-32A I> I>

2 4 2 4 2 4 2 4

AC_IN:L AC_IN:N DC_IN:L+ DC_IN:L- AC_IN:L AC_IN:N DC_IN:L+ DC_IN:L-


INV1 AC_INPUT DC_INPUT INV2 AC_INPUT DC_INPUT

2kVA 2kVA
INVERTER - YUCOO - YDKHD INVERTER - YUCOO - YDKHD

AC_OUTPUT AC_OUTPUT
C C
AC_OUT:L AC_OUT:N AC_OUT:L AC_OUT:N

1 2 /D02.3 A1
7 8 /D02.3
-KQP
R3 R4 /D02.6
220VDC A2
R5 R6 /D02.6

1 7 R3 R5
D -KQP D
/D02.3 2 8 R4 R6

1 3 1 3

POWER FOR
-FINV -FQAC2 TABLE CONTROL
E E
2P-32A I> I> =T00+WAN 2P-16A I> I>

2 4 -W094 2 4
-XAC4 2 1 -XINV 1

-XAC4 4 2 -XINV 3
-XAC4 1 3

-XAC3 1 3 2 4
No.3
POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00
DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE D02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE G01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY SERVER PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN AC POWER SUPPLY PECC2/TT-110KV/SERVER
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=N00+DC
PS1 FOR PS2 FOR PS FOR PS1 FOR PS2 FOR
SWITCH SWITCH GPS COMPUTER COMPUTER
-W092

A =N00+DC/G04.3 /
DC1+ 1 -XDC 1 2 3 A

=N00+DC/G04.3 /
DC1- 2 -XDC 4 5 6

-W093

=N00+DC/G04.3 /
DC2+ 1 -XDC 7 8 9

=N00+DC/G04.3 /
DC2- 2 -XDC 10 11 12

B DCINV1+ B
/ D02.3

DCINV1-
/ D02.3

1 2 /G01.4 1
DCINV2+
/ D02.6
7 8 /G01.5
-KQP1
R3 R4 /G01.5
220VDC
DCINV2-
R5 R6 /G01.6 2 / D02.6

1 7 R3 R5
-KQP1
C /G01.5
C
2 8 R4 R6

1 3 1 3 1 3 1 3 1 3

-FQDC1 -FQDC2 -FQDC3 -FQDC4 -FQDC5


D 2P-10A I> I> 2P-10A I> I> 2P-10A I> I> 2P-20A I> I> 2P-20A I> I> D
2 4 2 4 2 4 2 4 2 4

L+ L- L+ L- V+ V-
-SW GPS
-XDC1 1 2 3 4 5 6 7 8 -XDC2 1 2 3 4 5 6 7 8

GTW1.1+

GTW2.1+

GTW1.2+

GTW2.2+
GTW1.1-

GTW2.1-

GTW1.2-

GTW2.2-
HIS.1+

HIS.2+
HIS.1-

HIS.2-
E POWER FOR E
COMPUTER

G02.2

G02.4

G02.6

G02.2

G02.4

G02.7

G02.2

G02.5

G02.7

G02.3

G02.5

G02.7
-PE

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE G01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE G02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY SERVER PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN DC POWER SUPPLY PECC2/TT-110KV/SERVER
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

POWER SUPPLIES FOR POWER SUPPLIES FOR POWER SUPPLIES FOR


GATEWAY 1 COMPUTER GATEWAY 2 COMPUTER HIS COMPUTER

G01.6

G01.6

G01.7

G01.8

G01.6

G01.6

G01.7

G01.8

G01.6

G01.6

G01.7

G01.8
GTW1.1+

GTW1.2+

GTW2.1+

GTW2.2+
GTW1.1-

GTW1.2-

GTW2.1-

GTW2.2-

HIS.1+

HIS.2+
HIS.1-

HIS.2-
B B

C C

L+ L- L+ L- L+ L- L+ L- L+ L- L+ L-
-GTW1 GTW2 HIS

D D

-PE

E E
-X9 3 4 5

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE G02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X100

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY SERVER PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN DC POWER SUPPLY PECC2/TT-110KV/SERVER
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+SP-XAC1 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=N00 +AC 26 1 /D01.2
2 =E00 +SP FINV1.2 1 /D01.6
=N00 +AC 28 4 /D01.2

B 5 =E00 +SP FINV1.2 3 /D01.6 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X100 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X101

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY SERVER PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+SP-XAC1 PECC2/TT-110KV/SERVER
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+SP-XAC2 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=N00 +AC 26 1 /D01.2
2 =E00 +SP FINV2.2 1 /D01.6
=N00 +AC 28 4 /D01.2

B 5 =E00 +SP FINV2.2 3 /D01.6 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X101 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X102

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY SERVER PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+SP-XAC2 PECC2/TT-110KV/SERVER
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+SP-XAC3 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
1 =E00 +SP FQAC2 2 /D02.6
2 /D02.6
3 =E00 +SP FQAC2 4 /D02.6

B 4 /D02.6 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X102 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X103

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY SERVER PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+SP-XAC3 PECC2/TT-110KV/SERVER
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+SP-XAC4 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
1 =E00 +SP FINV 2 /D02.3
=T00 +WAN -XINV 1 2 /D02.3
3 =E00 +SP FINV 4 /D02.3

B =T00 +WAN -XINV 3 4 /D02.3 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X103 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X104

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY SERVER PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+SP-XAC4 PECC2/TT-110KV/SERVER
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+SP-XDC A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E00 +SP -FQDC1 1 1 =N00 +DC XT1 3 /G01.2
=E00 +SP -FINV1.1 1 2 =E00 +SP KQP1 1 /G01.6
3 =E00 +SP FQDC5 1 /G01.8

B =E00 +SP -FQDC1 3 4 =N00 +DC XT1 4 /G01.2 B


=E00 +SP -FINV1.1 3 5 =E00 +SP KQP1 7 /G01.6
6 =E00 +SP FQDC5 3 /G01.8
=E00 +SP -FQDC2 1 7 =N00 +DC XT2 3 /G01.2
=E00 +SP -FQDC4 1 8 =E00 +SP KQP1 R3 /G01.6
9 =E00 +SP FINV2.1 1 /G01.8
=E00 +SP -FQDC2 3 10 =N00 +DC XT2 4 /G01.2
=E00 +SP -FQDC4 3 11 =E00 +SP KQP1 R5 /G01.6
12 =E00 +SP FINV2.1 3 /G01.8

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X104 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X105

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY SERVER PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+SP-XDC PECC2/TT-110KV/SERVER
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+SP-XDC1 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E00 +SP -PS1 L+ 1 /G01.6
=E00 +SP -PS1 L+ 2 /G01.6
=E00 +SP -PS1 L+ 3 /G01.6

B 4 =E00 +SP FQDC4 2 /G01.6 B


=E00 +SP -PS1 L- 5 =E00 +SP FQDC4 4 /G01.6
=E00 +SP -PS1 L- 6 /G01.6
=E00 +SP -PS1 L- 7 /G01.6
8 /G01.7

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X105 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X106

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY SERVER PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+SP-XDC1 PECC2/TT-110KV/SERVER
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+SP-XDC2 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E00 +SP -PS2 L+ 1 /G01.7
=E00 +SP -PS2 L+ 2 /G01.7
=E00 +SP -PS2 L+ 3 /G01.7

B 4 =E00 +SP FQDC5 2 /G01.8 B


=E00 +SP -PS2 L- 5 =E00 +SP FQDC5 4 /G01.8
=E00 +SP -PS2 L- 6 /G01.8
=E00 +SP -PS2 L- 7 /G01.8
8 /G01.8

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X106 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X107

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY SERVER PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+SP-XDC2 PECC2/TT-110KV/SERVER
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+SP-X9 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
1 =N00 +DC X9 3 =N00+DC/R11.8
2 =N00 +DC X9 4 =N00+DC/R11.8
3 /G02.6

B 4 /G02.6 B
5 /G02.7

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X107 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE +FR/A00

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY SERVER PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+SP-X9 PECC2/TT-110KV/SERVER
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

B B

B 24/11/2020 2nd FOR APPROVED

A 12/10/2020 1st FOR APPROVED

REV. NGÀY MÔ TẢ CHI TIẾT

KHÁCH HÀNG

C C
POWER ENGINEERING CONSULTING J.S.C. 2

DỰ ÁN

TAN THUAN OFFSHORE WIND POWER PLANT

D D

NƠI LẮP ĐẶT:

TAN THUAN OFFSHORE WIND POWER PLANT

TÊN BẢN VẼ: ĐÓNG DẤU:

E =E00+FR : FAULT RECORDER AND POWER QUAILTY PANEL E

MÃ BẢN VẼ: PECC2/TT-110KV/FR

TIÊU CHUẨN: IEC TRANG: A00 TỔNG SỐ TRANG: 45

THIẾT KẾ NGUYEN VAN NHAT NHÀ THẦU:

KIỂM TRA NGUYEN VAN CHUNG


F F
DUYỆT NGUYEN DINH TUAN
CÔNG TY CỔ PHẦN ENTEC
KỸ THUẬT NĂNG LƯỢNG
NGÀY Rev.: B

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

PAGE DESCRIPTION REV. X PAGE DESCRIPTION REV. X

=E00+FR/A00 FAULT RECORDER AND POWER QUAILTY PANEL B =E00+FR/X114 Terminal diagram =E00+FR-X54 B
A A
=E00+FR/A01 TABLE OF CONTENTS : =E00+FR/A00 - =E00+FR/Z08 B =E00+FR/X115 Terminal diagram =E00+FR-X55 B
=E00+FR/A02 CONTROL, PROTECTION & MEASUREMENT PRINCIPLE DIAGRAM B =E00+FR/X116 Terminal diagram =E00+FR-X56 B
=E00+FR/A03 LIST OF EQUIPMENTS C =E00+FR/X117 Terminal diagram =E00+FR-X57 B
=E00+FR/B02 LAYOUT DRAWING B =E00+FR/Z01 REFERENCE FAULT RECORDER: 7KE85 B
=E00+FR/D01 AC POWER SUPPLY B =E00+FR/Z02 REFERENCE FAULT RECORDER: 7KE85 B
=E00+FR/G01 DC POWER SUPPLY B =E00+FR/Z03 REFERENCE FAULT RECORDER: 7KE85 B

B =E00+FR/G02 DC POWER SUPPLY B =E00+FR/Z04 REFERENCE FAULT RECORDER: 7KE85 B B


=E00+FR/N01 SIGNAL SEND TO BCU B =E00+FR/Z05 REFERENCE FAULT RECORDER: 7KE85 B
=E00+FR/R01 BINNARY INPUTS OF FR B =E00+FR/Z06 REFERENCE FAULT RECORDER: 7KE85 B
=E00+FR/R02 BINNARY INPUTS OF FR B =E00+FR/Z07 REFERENCE CURRENT AND VOLTAGE TESTBLOCK B
=E00+FR/R03 BINNARY INPUTS OF FR B =E00+FR/Z08 REFERENCE POWER QUAILTY B
=E00+FR/R04 BINNARY INPUTS OF FR B
=E00+FR/R05 BINNARY INPUTS OF FR B
C =E00+FR/S01 CURRENT CIRCUIT FOR RELAY B C

=E00+FR/S02 CURRENT CIRCUIT FOR RELAY B


=E00+FR/S03 VOLTAGE CIRCUIT FOR RELAY B
=E00+FR/S04 VOLTAGE CIRCUIT FOR RELAY B
=E00+FR/W01 SPARE CIRCUIT B
=E00+FR/X100 Terminal diagram =E00+FR-XAC B
=E00+FR/X101 Terminal diagram =E00+FR-XDC1 B
D D
=E00+FR/X102 Terminal diagram =E00+FR-XDC2 B
=E00+FR/X103 Terminal diagram =E00+FR-XDC3 B
=E00+FR/X104 Terminal diagram =E00+FR-X8 B
=E00+FR/X105 Terminal diagram =E00+FR-X41 B
=E00+FR/X106 Terminal diagram =E00+FR-X42 B
=E00+FR/X107 Terminal diagram =E00+FR-X43 B

E =E00+FR/X108 Terminal diagram =E00+FR-X44 B E


=E00+FR/X109 Terminal diagram =E00+FR-X45 B
=E00+FR/X110 Terminal diagram =E00+FR-X46 B
=E00+FR/X111 Terminal diagram =E00+FR-X47 B
=E00+FR/X112 Terminal diagram =E00+FR-X51 B
=E00+FR/X113 Terminal diagram =E00+FR-X52 B
X: AUTOMATIC PAGE MODIFIED

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN TABLE OF CONTENTS : =E00+FR/A00 - =E00+FR/Z08 PECC2/TT-110KV/FR

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

110kV DAM DOI SUBSTATION 110kV DONG HAI SUBSTATION


110 0.11 0.11 110 0.11 0.11
kV kV
3 3 3 QL09 3 3 3
M

A A
LVT1 LVT

QE76 QE76
QL07 M QL07 M CL: 0.5
QE75 CL: 0.5
QE75
CL: 3P CL: 5P20 CL: 3P
#17:FROM F87L(E04)
CL: 0.5 CL: 5P20
CT-123kV CL: 0.5
CL: 0.5
400-800-1200 CT-123kV
CL: 0.5
CL: 5P20 /1/1/1/1/1A 400-800-1200
CL: 5P20 /1/1/1/1A CL: 5P20
CT-123kV CL: 5P20
600-800-1200
QF01 QF01
/1/1/1/1A
B B
QE25 QE15

CL: 5P20
CL: 0.5
CL: 0.5
QL02

CL: 5P20
CL: 5P20
M QL01 M

QL02 QL01
C12 QF01
M M C11
110 0.11 0.11 110 0.11 0.11
kV QL02 M QE24 QE25 QE15 QE14 M QL01 kV
3 3 3 3 3 3
QE25 #15:TO FR
QE25
CL: 3P CL: 3P
CL: 0.5 CL: 0.5

QF01 QF01
CT-123kV
CL: 5P20 200-400-600 CL: 5P20
CL: 5P20 /1/1/1/1/1A XTV1 XTC1 CL: 5P20
C #6:TO FR FR(7KE85) #6: CT E02 #9:TO FR C
CL: 0.2 CL: 0.2
XTV3 XTC2 CT-123kV
CL: 0.5 CL: 0.5
#7:FROM F87L(E04) 200-400-600
CL: 5P20
XTV2 XTC3
CL: 5P20 /1/1/1/1/1A
#15: CT E05
FR
XTV5 XTC4
#8:FROM F87L(E03)
XTV4 XTC5
HV-BCT CL: 0.5 CL: 0.5 HV-BCT
96 26 26 96
CL: 5P20 CL: 5P20
CL: 5P20

CL: 5P20
CL: 5P20
71 63 63 71 CL: 5P20

PQ1 (7KG95) XTC6


XTV6

#9: CT E01
D U D

XTV7 XTC7
#17: FROM LVT E03

CL: 5P20
CL: 0.5 PQ2 (7KG95) CL: 0.5
CL: 5P20
CL: 5P20 CL: 5P20
CL: 5P20 U CL: 5P20

#1 TO F67-J13 CL: 5P20 CL: 5P20 #1 TO F67-J01


MV-BCT T2 =E00+FR T1 MV-BCT

CL: 0.5 CL: 0.5

-38 -38
CT-24KV CT-24KV
CL: 0.5 CL: 0.5
1500-2500 1500-2500

#16: FROM BCU E01


#17: FROM BCU E02
/1/1/1A CL: 5P20 CL: 5P20 /1/1/1A
E E
CL: 5P20 CL: 5P20

J
J13 432 431 J01
C42 C41
-14 TU-C41 TU-C42 -24
22 0.11 0.11 22 0.11 0.11
kV kV
3 3 3 3 3 3

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL
CONTROL, PROTECTION & MEASUREMENT PRINCIPLE
DATE 24/11/2020
APPROVED NGUYEN DINH TUAN PECC2/TT-110KV/FR
DIAGRAM
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

NO. SYMBOL DESCRIPTION MANUFACTORY CODE QTY. UNIT NOTE CUBICLE

1 FR FAULT RECORDER SIEMENS 7KE85 - P1N162072 01 Pcs =E00+FR


A A
2 PQ1, PQ2 POWER QUAILTY SIEMENS 7KG9501-0AA01-2AA1 02 Pcs =E00+FR

3 XTC... CURRENT TESTBLOCK FUJI KTT-AW4 B M 07 Pcs =E00+FR

4 XTV... VOLTAGE TESTBLOCK FUJI KTT-VW4 B M 07 Pcs =E00+FR

5 FQAC MCB AC FOR LIGHTING AND HEATING LEGRAND DX3 01 Pcs =E00+FR

6 FQ... MCB DC LEGRAND DX3 DC 05 Pcs =E00+FR

7 FQAC1 MCB AC FOR LIGHTING AND HEATING LEGRAND DX3 01 SET =E00+FR
B B
8 KQP CONTACTOR ABB ESB25 01 SET =E00+FR

9 XDC..., XAC... POWER TERMINALS DEGSON PC6 01 LOT =E00+FR

10 X5... VOLTAGE TERMINALS DEGSON PC6 01 LOT =E00+FR

11 X4... CURRENT TERMINALS DEGSON PCTK 01 LOT =E00+FR

12 X8 SIGNAL TERMINALS DEGSON PC4 01 LOT =E00+FR

13 B0 THERMOSTAT CYMAX 01 SET =E00+FR


C C
14 B1 DOOR LIMIT SWITCH CHINA 01 SET =E00+FR

15 E0 HEATING RESISTER CYMAX 01 SET =E00+FR

16 E1 LIGHTING LAMP CHINA 01 SET =E00+FR

17

18

D 19 D

20

21

22

23

24

E 25
E

26

27

28

29

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LIST OF EQUIPMENTS PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

FRONT VIEW SIDE VIEW REAR VIEW


A A
ENTEC =E00+FR

EQUIPMENTS
=E00+FR
TAG NAME DESCRIPTION
FR... FAULT RECORDER AND PHASE AGLE MEASURING UNIT DEVICE
PQ... POWER QUALITY MONITORING DEVICE
XTC, XTV CURRENT TESTBLOCK, VOLTAGE TESTBLOCK
Error
SIEMENS SIEMENS SIEMENS SIEMENS SIEMENS
Run
SIPROTEC SIPROTEC SIPROTEC SIPROTEC SIPROTEC

B B
SIEMENS SIEMENS
SIPROTEC SIPROTEC
2200

SIEMENS
PQ1 RUN ERROR SICAM Q SIEMENS
PQ2 RUN ERROR SICAM Q

H1 F1 F2 F3 F4 H2 H1 F1 F2 F3 F4 H2

XTC1 XTC2 XTC3 XTC4

XTC6 XTC7 XTC7

C XTV1 XTV2 XTV3 XTV4 C


XTV5 XTV6 XTV7
100

800 750 800


800
D D
TOP VIEW BOTTOM VIEW BASE NAME PLATE (SCALE 1:5)
4x∅14

100 C
=E00+FR

45
750
800
200
800

750

C (Scale 1:5) REMARK:


Ø14 IP DEGREE: IP41
E E
APPLICATION STANDARD: IEC60529
25
MATERIAL: STEEL
4x∅8 STEEL THICKNESS: 2mm
550 PAINT COLOR: RAL7032
800 750 DOOR APPLY AREA: FRONT AND REAR
OPEN DOOR: 180°

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE D01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LAYOUT DRAWING PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E00+MP1 +FR =E01+CRP1

POWER FOR
A LIGHTING AND HEATING A

-W021
ACL1 1 -XAC 1 -XAC 2 ACL1
+MP1/D01.7/ / =E01+/D01.1
220 VAC
ACL2 2 -XAC 3 -XAC 4 ACL2
+MP1/D01.7/ / =E01+/D01.1

ACL3 3 -XAC 5 -XAC 6 ACL3


+MP1/D01.7/ / =E01+/D01.1

ACN 4 -XAC 7 -XAC 8 ACN


+MP1/D01.7/ / =E01+/D01.1

B 1 3 12 14 96 98 B

-FQAC 11 95
2P-16A I> I>

/N01.2

/N01.5
2 4

LIGHTING HEATING SOCKET


C C

1 1
-B1 -B0
2 0÷90°C 2

D D

1 1
1 1

-E0 -E1 -E2 -XSK


220VAC 220VAC 2 220VAC 2 220VAC
2 60W 60W 2
E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE D01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE G01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN AC POWER SUPPLY PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=N00+DC +FR =E01+CRP1

A A
DC2 DC2
POWER SUPPLY POWER SUPPLY

-W022
DC1+ 1 -XDC1 1 -XDC1 2 DC1+
=N00+DC/G05.3 / =E01+/G01.1
220VDC
DC1- 2 -XDC1 3 -XDC1 4 DC1-
=N00+DC/G05.3 / =E01+/G01.1

-W023
DC2+ 1 -XDC2 1 -XDC2 2 DC2+
=N00+DC/G05.3 / =E01+/G01.1
B B
220VDC
DC2- 2 -XDC2 3 -XDC2 4 DC2-
=N00+DC/G05.3 / =E01+/G01.1

1 3 1 3
12 14 96 98 12 14 96 98

-FQDC2 11 95 -FQDC1 11 95
2P-10A I> I> 2P-10A I> I>

/N01.4

/N01.5

/N01.4

/N01.5
C 2 4 2 4 C

1 1 2 /G01.5
7 8 /G01.5
-KQP1
220VDC R3 R4 /G01.4
2 R5 R6 /G01.4

R3 R5 1 7
D -KQP1 D
/G01.6 R4 R6 2 8

DC-
/ G02.1

DC+
/ G02.1

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE G01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE G02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN DC POWER SUPPLY PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+FR

A POWER SUPPLY POWER SUPPLY POWER SUPPLY A


FOR FR RELAY FOR PQ1 FOR PQ2

DC+
G01.6
DC-
G01.6

-XDC3 1 4 -XDC3 5 2 -XDC3 6 3

B B

1 3 1 3 1 3
12 14 96 98 12 14 96 98 12 14 96 98

-FQFR 11 95 -FQPQ1 11 95 -FQPQ2 11 95


2P-10A I> I> 2P-10A I> I> 2P-10A I> I>
/N01.4

/N01.5

/N01.4

/N01.5

/N01.4

/N01.5
C 2 4 2 4 2 4 C

FR+
-X8 1
R01.2
FR-
-X8 13
R01.2
D D

B1 B2 A1 A2 A1 A2 L+ L- L+ L-
FR IO2 FR IO7 FR IO8 PQ1 H PQ2 H
/Z01 -PS /Z06.3 -PS /Z06.6 -PS /Z08.6 -PS /Z08.4 -PS
E E
7KE85 7KE85 7KE85 7KG95 7KG95

-PE

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE G02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN DC POWER SUPPLY PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+FR

A MCB AC MCB DC MCB A


FR FAIL
OFF OFF TRIP

96
12 -FQAC 95 98
-FQFR 11 14 /D01.4 - FR B7
IO2
/G02.2 /Z01
96
12 14 -FQFR
B 12 95 98 B
-FQAC -FQPQ111 14 /G02.2
/D01.4 11
/G02.6 B10
96
12 -FQPQ195 98
-FQPQ211 14 /G02.6
/G02.7
96
12 -FQPQ295 98
-FQDC111 14 /G02.7
/G01.5
96
C 12 -FQDC195 98 C
-FQDC211 14 /G01.5
/G01.4
96
-FQDC295 98
/G01.4

-X8 16 17 18 19 20
D D

-W041 2 3 4 5 6

=E05+CRP5
F271.FR+

FR.FAIL
FR.DCO

FR.MCB
FR.ACO

E E
=E05+/N15.2 /

=E05+/N15.2 /

=E05+/N15.3 /

=E05+/N15.4 /
=E05+/N15.2/

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN SIGNAL SEND TO BCU PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

=E01+CRP1
A CB E01-QF01 CB E01-QF01 =E01+CRP1 =E01+CRP1 =E01+CRP1 =E01+CRP1 A
TRANS.PROTECTION SPARE
OPENED CLOSED F87T TRIP F67 TRIP F861 TRIP F862 TRIP
TRIP
FR+
FR+
G02.5 / R02.2
-X8 2 -X8 3
-W042 1 -W037 1

=E01+CRP1
FR+

FR+
=E01+MK

=E01+/R11.2

=E01+/R11.5
B B

C C
/ =E01+/R11.3

/ =E01+/R11.2

/ =E01+/R11.5

/ =E01+/R11.6

/ =E01+/R11.7

/ =E01+/R11.7

/ =E01+/R11.8
CBE01.O

CBE01.C

E01.F87T

E01.F67

E01.861

E01.862

E01.K94
-W042 2 3 -W037 2 3 4 5 6
D D

X8 21 22 23 24 25 26 27 28

D1 D2 D3 D4 D7 D8 D11 D12
- FR IO1
/Z01
BI1.1 BI1.2 BI1.3 BI1.4 BI1.5 BI1.6 BI1.7 BI1.8
/Z01.7 /Z01.7 /Z01.7 /Z01.7 /Z01.7 /Z01.7 /Z01.7 /Z01.7

E C13 C14 D5 D6 D9 D10 D13 D14 E


FR-
/ R02.2

-X8 14
FR- -X8 15
G02.5

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUTS OF FR PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

=E02+CRP2
CB E02-QF01 CB E02-QF01 =E02+CRP2 =E02+CRP2 =E02+CRP2 =E02+CRP2
TRANS.PROTECTION SPARE
OPENED CLOSED F87L TRIP F67 TRIP F861 TRIP F862 TRIP
A TRIP A
FR+
FR+
R01.7 / R03.2
-X8 4 -X8 5
-W043 1 -W038 1

FR+

FR+
=E02+CRP2
=E02+MK

=E02+/R11.2

=E02+/R11.5
B B

/ =E02+/R11.3

/ =E02+/R11.2

/ =E02+/R11.5

/ =E02+/R11.6

/ =E02+/R11.7

/ =E02+/R11.7

/ =E02+/R11.8
C C
CBE02.O

CBE02.C

E02.F87T

E02.F67

E02.861

E02.862

E02.K94
-W043 2 3 -W038 2 3 4 5 6

D D
X8 29 30 31 32 33 34 35 36

D1 D2 D3 D4 D7 D8 D11 D12
- FR IO3
/Z02
BI3.1 BI3.2 BI3.3 BI3.4 BI3.5 BI3.6 BI3.7 BI3.8
/Z02.6 /Z02.6 /Z02.6 /Z02.6 /Z02.6 /Z02.6 /Z02.6 /Z02.6

C13 C14 D5 D6 D9 D10 D13 D14


FR-
E FR- E
R01.7 / R03.2

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUTS OF FR PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A CB E03-QF01 CB E03-QF01 =E03+CRP3 =E03+CRP3 =E03+CRP3 =E03+CRP3 A


SPARE SPARE
OPENED CLOSED F87L TRIP F21 TRIP F861 TRIP F862 TRIP

FR+
FR+
R02.7 / R04.2
-X8 6 -X8 7
-W044 1 -W039 1

FR+

FR+
=E03+CRP3
=E03+MK

=E03+/R08.2

=E03+/R08.5
B B

C C
/ =E03+/R08.3

/ =E03+/R08.2

/ =E03+/R08.5

/ =E03+/R08.6

/ =E03+/R08.7

/ =E03+/R08.7
CBE03.O

CBE03.C

E03.F87L

E03.F21

E03.861

E03.862
-W044 2 3 -W039 2 3 4 5
D D

X8 37 38 39 40 41 42 43 44

D1 D2 D3 D4 D7 D8 D11 D12
- FR IO4
/Z03
BI4.1 BI4.2 BI4.3 BI4.4 BI4.5 BI4.6 BI4.7 BI4.8
/Z03.6 /Z03.6 /Z03.6 /Z03.6 /Z03.6 /Z03.6 /Z03.6 /Z03.6

E C13 C14 D5 D6 D9 D10 D13 D14 E


FR-
FR-
R02.7 / R04.2

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUTS OF FR PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

CB E04-QF01 CB E04-QF01 =E04+CRP4 =E04+CRP4 =E04+CRP4 =E04+CRP4


SPARE SPARE
OPENED CLOSED F87L TRIP F21 TRIP F861 TRIP F862 TRIP
A A
FR+
FR+
R03.7 / R05.1
-X8 8 -X8 9
-W045 1 -W040 1

FR+

FR+
=E04+MK

=E04+CRP4
=E04+/R08.2

=E04+/R08.5
B B

/ =E04+/R08.3

/ =E04+/R08.2

/ =E04+/R08.5

/ =E04+/R08.6

/ =E04+/R08.7

/ =E04+/R08.7
C C
CBE04.O

CBE04.C

E04.F87L

E04.F21

E04.861

E04.862
-W045 2 3 -W040 2 3 4 5

D D
X8 45 46 47 48 49 50 51 52

D1 D2 D3 D4 D7 D8 D11 D12
- FR IO5
/Z04
BI5.1 BI5.2 BI5.3 BI5.4 BI5.5 BI5.6 BI5.7 BI5.8
/Z04.6 /Z04.6 /Z04.6 /Z04.6 /Z04.6 /Z04.6 /Z04.6 /Z04.6

C13 C14 D5 D6 D9 D10 D13 D14


FR-
E FR- E
R03.7 / R05.1

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R05

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUTS OF FR PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A CB E05-QF01 CB E05-QF01 =E05+CRP5 =E05+CRP5 =E05+CRP5 =E05+CRP5 =E05+CRP5 =E05+CRP5 A


SPARE SPARE SPARE
OPENED CLOSED F87B TRIP F21 TRIP F271 TRIP F272 TRIP F861 TRIP F862 TRIP

FR+ -X8 12
R04.7
-X8 10 -X8 11
-W046 1 -W041 1

FR+

FR+
=E05+CRP5
=E05+MK

=E05+/R10.1

=E05+/R10.4
B B

C C
/ =E05+/R10.3

/ =E05+/R10.2

/ =E05+/R10.5

/ =E05+/R10.5

/ =E05+/R10.6

/ =E05+/R10.7

/ =E05+/R10.8

/ =E05+/R10.8
CBE05.O

CBE05.C

E05.F87B

E05.F21

E05.271

E05.272

E05.F861

E05.F862
-W046 2 3 -W041 7 8 9 10 11 12
D D

X8 53 54 55 56 57 58 59 60 61 62 63

D1 D2 D3 D4 D7 D8 D11 D12 B12 B13 B14


- FR IO6 IO2
/Z05
BI6.1 BI6.2 BI6.3 BI6.4 BI6.5 BI6.6 BI6.7 BI6.8 BI2.1 BI2.2 BI2.3
/Z05.6 /Z05.6 /Z05.6 /Z05.6 /Z05.6 /Z05.6 /Z05.6 /Z05.6 /Z01.2 /Z01.2 /Z01.2

E C13 C14 D5 D6 D9 D10 D13 D14 B11 E


FR-
R04.7

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R05 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE S01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUTS OF FR PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E01+MK =E02+MK =E03+CRP3

A A
CT E01 BAY CLASS 5P20 CT E02 BAY CLASS 5P20 CT E03 BAY CLASS 5P20

=E01+/S02.2

=E01+/S02.2

=E01+/S02.3

=E01+/S02.3

=E02+/S02.2

=E02+/S02.2

=E02+/S02.3

=E02+/S02.3

=E03+/S03.2

=E03+/S03.2

=E03+/S03.2

=E03+/S03.3
E01.CTN

E02.CTN

E03.CTN
E01.CTA

E01.CTC

E02.CTA

E02.CTC

E03.CTA

E03.CTC
E01.CTB

E02.CTB

E03.CTB
B B

-W024 1 2 3 4 -W025 1 2 3 4 -W026 1 2 3 4

C C
-X41 1 2 3 4 -X42 1 2 3 4 -X43 1 2 3 4

1 3 5 7 1 3 5 7 1 3 5 7
-XTC1 -XTC2 -XTC3
/Z07.5 /Z07.5 /Z07.6
D D
2 4 6 8 2 4 6 8 2 4 6 8

- FR IO1 A1 A3 A5 A7 - FR IO3 A1 A3 A5 A7 - FR IO4 A1 A3 A5 A7


/Z01 /Z02 /Z03
I1 I2 I3 I4 I1 I2 I3 I4 I1 I2 I3 I4
E E
A2 A4 A6 A8 A2 A4 A6 A8 A2 A4 A6 A8

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE S01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE S02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CURRENT CIRCUIT FOR RELAY PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E04+CRP4 =E05+MK =E01+CRP1 =E02+CRP2

A A
CT E04 BAY CLASS 5P20 CT E05 BAY CLASS 5P20 CT E01 LCB CLASS 5P20 CT E05 LCB CLASS 5P20

=E01+/T02.2

=E01+/T02.2

=E01+/T02.2

=E01+/T02.3

=E02+/T02.2

=E02+/T02.2

=E02+/T02.2

=E02+/T02.3
=E04+/S03.2

=E04+/S03.2

=E04+/S03.2

=E04+/S03.3

=E05+/S05.2

=E05+/S05.2

=E05+/S05.2

=E05+/S05.2
E04.CTN

E05.CTN
E04.CTA

E04.CTC

E05.CTA

E05.CTC
E04.CTB

E05.CTB

E1.CTN

E2.CTN
E1.CTA

E1.CTC

E2.CTA

E2.CTC
E1.CTB

E2.CTB
B B

-W027 1 2 3 4 -W028 1 2 3 4 -W029 1 2 3 4 -W030 1 2 3 4

-X44 1 2 3 4 -X45 1 2 3 4 -X46 1 2 3 4 -X47 1 2 3 4

C 1 3 5 7 1 3 5 7 1 3 5 7 1 3 5 7 C
-XTC4 -XTC5 -XTC6 -XTC7
/Z07.6 /Z07.6 /Z07.7 /Z07.7

2 4 6 8 2 4 6 8 2 4 6 8 2 4 6 8

- FR IO5 A1 A3 A5 A7 - FR IO6 A1 A3 A5 A7 - PQ1 E A1 B1 C1 N2 - PQ2 E A1 B1 C1 N2


/Z04 /Z05 /Z08.6 /Z08.4
D I1 I2 I3 I4 I1 I2 I3 I4 IA IB IC IN IA IB IC IN D

A2 A4 A6 A8 A2 A4 A6 A8 A2 B2 C2 N1 A2 B2 C2 N1

-X461 1 2 3 4 -X471 1 2 3 4

-W047 1 2 3 4 -W048 1 2 3 4

E E

+TRANDUCER

X ... X ... X ... X ... X ... X ... X ... X ...

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE S02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE S03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CURRENT CIRCUIT FOR RELAY PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E03+CRP3 =E01+CRP1

A A

LINE VT CLASS: 3P BUS VT C11 CLASS: 3P BUS VT C11 CLASS: 0.5

=E01+/T01.7

=E01+/T01.7

=E01+/T01.8

=E01+/T01.8
=E03+/S04.1

=E03+/S04.2

=E03+/S04.2

=E03+/S04.2

=E01+/S03.6

=E01+/S03.6

=E01+/S03.6

=E01+/S03.7

E01.BVTN1
E01.BVTA1

E01.BVTC1
E01.BVTB1
E01.BVTN
E01.BVTA

E01.BVTC
E01.BVTB
E03.LVTN
E03.LVTA

E03.LVTC
E03.LVTB

B B

+TRANDUCER
-W033 1 2 3 4 -W031 1 2 3 4 -W032 1 2 3 4

-X52 1 2 3 4 -X51 1 2 3 4 -X56 1 2 3 4


-W049
C -X56 2 1 -X ... C

-X56 4 2 -X ...

-X56 6 3 -X ...

-X56 8 4 -X ...

1 3 5 7 1 3 5 7 1 3 5 7 1 3 5 7
-XTV2 -XTV1 -XTV3 -XTV6
/Z07.5 /Z07.5 /Z07.6 /Z07.7
D D

2 4 6 8 2 4 6 8 2 4 6 8 2 4 6 8

A B C N
E FR IO3 B1 B3 B5 B7 FR IO1 B1 B3 B5 B7 FR IO4 B1 B3 B5 B7 PQ1 F E
/Z02 /Z01 /Z03
V1 V2 V3 V4 V1 V2 V3 V4 V1 V2 V3 V4 VA VB VC

B2 B4 B6 B8 B2 B4 B6 B8 B2 B4 B6 B8

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE S03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE S04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN VOLTAGE CIRCUIT FOR RELAY PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E04+CRP4 =E02+CRP2

A A

LINE VT E04 CLASS: 3P BUS VT C12 CLASS: 3P BUS VT C12 CLASS: 0.5

=E02+/T01.7

=E02+/T01.7

=E02+/T01.8

=E02+/T01.8
=E04+/S04.1

=E04+/S04.2

=E04+/S04.2

=E04+/S04.2

=E02+/S03.6

=E02+/S03.6

=E02+/S03.6

=E02+/S03.7

E02.BVTN1
E02.BVTA1

E02.BVTC1
E02.BVTB1
E02.BVTN
E02.BVTA

E02.BVTC
E02.BVTB
E04.LVTN
E04.LVTA

E04.LVTC
E04.LVTB

B B

+TRANDUCER
-W034 1 2 3 4 -W035 1 2 3 4 -W036 1 2 3 4

-X54 1 2 3 4 -X55 1 2 3 4 -X57 1 3 5 7


-W050
C -X57 2 1 -X ... C

-X57 4 2 -X ...

-X57 6 3 -X ...

-X57 8 4 -X ...

1 3 5 7 1 3 5 7 1 3 5 7
-XTV4 -XTV5 -XTV7
/Z07.6 /Z07.6 /Z07.7
D D

2 4 6 8 2 4 6 8 2 4 6 8

A B C N
E FR IO5 B1 B3 B5 B7 FR IO6 B1 B3 B5 B7 PQ2 F E
/Z04 /Z05
V1 V2 V3 V4 V1 V2 V3 V4 VA VB VC

B2 B4 B6 B8 B2 B4 B6 B8

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE S04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE W01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN VOLTAGE CIRCUIT FOR RELAY PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

B B

X8 64 65 66 67 68 69 70

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE W01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X100

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN SPARE CIRCUIT PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+FR-XAC A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E00 +MP1 -XAC 2 1 /D01.2
=E01 +CRP1 -XAC 1 2 /D01.7
=E00 +MP1 -XAC 4 3 /D01.2

B =E01 +CRP1 -XAC 3 4 /D01.7 B


=E00 +MP1 -XAC 6 5 =E00 +FR FQAC 1 /D01.2
=E01 +CRP1 -XAC 5 6 /D01.7
=E00 +MP1 -XAC 8 7 =E00 +FR FQAC 3 /D01.2
=E01 +CRP1 -XAC 7 8 /D01.7

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X100 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X101

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+FR-XAC PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+FR-XDC1 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=N00 +DC -XT1 13 1 =E00 +FR FQDC1 1 /G01.3
2 =E01 +CRP1 XDC1 1 /G01.7
=N00 +DC -XT1 14 3 =E00 +FR FQDC1 3 /G01.3

B 4 =E01 +CRP1 XDC1 3 /G01.7 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X101 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X102

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+FR-XDC1 PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+FR-XDC2 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=N00 +DC 13 1 =E00 +FR FQDC2 1 /G01.3
2 =E01 +CRP1 XDC2 1 /G01.7
=N00 +DC 14 3 =E00 +FR FQDC2 3 /G01.3

B 4 =E01 +CRP1 XDC2 3 /G01.7 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X102 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X103

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+FR-XDC2 PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+FR-XDC3 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E00 +FR -FQFR 1 1 =E00 +FR KQP1 2 /G02.2
=E00 +FR -FQPQ1 3 2 /G02.6
=E00 +FR -FQPQ2 3 3 /G02.7

B =E00 +FR -FQFR 3 4 =E00 +FR KQP1 8 /G02.2 B


=E00 +FR -FQPQ1 1 5 /G02.6
=E00 +FR -FQPQ2 1 6 /G02.7

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X103 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X104

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+FR-XDC3 PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+FR-X8 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
1 =E00 +FR FR-IO8-PS A1 /G02.4 =E03 +CRP3 -X3 5 41 =E00 +FR FR-IO4-BI4.5 D7 /R03.5
=E01 +MK -X3 27 2 /R01.3 =E03 +CRP3 -X3 6 42 =E00 +FR FR-IO4-BI4.6 D8 /R03.5
=E01 +CRP1 -X3 1 3 /R01.4 43 =E00 +FR FR-IO4-BI4.7 D11 /R03.6

B =E02 +MK -X3 17 4 /R02.3 44 =E00 +FR FR-IO4-BI4.8 D12 /R03.6 B


=E02 +CRP2 -X3 17 5 /R02.4 =E04 +MK 55 45 =E00 +FR FR-IO5-BI5.1 D1 /R04.3
=E03 +MK -X3 44 6 /R03.3 =E04 +MK -X3 54 46 =E00 +FR FR-IO5-BI5.2 D2 /R04.3
=E03 +CRP3 -X3 2 7 /R03.4 =E04 +CRP4 -X3 20 47 =E00 +FR FR-IO5-BI5.3 D3 /R04.4
=E04 +MK -X3 52 8 /R04.3 =E04 +CRP4 -X3 21 48 =E00 +FR FR-IO5-BI5.4 D4 /R04.4
=E04 +CRP4 -X3 19 9 /R04.4 =E04 +CRP4 -X3 22 49 =E00 +FR FR-IO5-BI5.5 D7 /R04.5
=E05 +MK -X3 54 10 /R05.2 =E04 +CRP4 -X3 23 50 =E00 +FR FR-IO5-BI5.6 D8 /R04.5
=E05 +CRP5 -X3 55 11 /R05.3 51 =E00 +FR FR-IO5-BI5.7 D11 /R04.6
12 /R05.3 52 =E00 +FR FR-IO5-BI5.8 D12 /R04.6
13 =E00 +FR FR-IO8-PS A2 /G02.4 =E05 +MK 57 53 =E00 +FR FR-IO6-BI6.1 D1 /R05.2
C =E00 +FR BI1.1 C13 14 /R01.3 =E05 +MK -X3 56 54 =E00 +FR FR-IO6-BI6.2 D2 /R05.2 C
15 /R01.3 =E05 +CRP5 -X3 56 55 =E00 +FR FR-IO6-BI6.3 D3 /R05.3
=E05 +CRP5 X22 2 16 =E00 +FR FQAC 12 /N01.2 =E05 +CRP5 -X3 57 56 =E00 +FR FR-IO6-BI6.4 D4 /R05.3
=E05 +CRP5 X22 9 17 =E00 +FR FQAC 11 /N01.3 =E05 +CRP5 -X3 58 57 =E00 +FR FR-IO6-BI6.5 D7 /R05.4
=E05 +CRP5 X22 10 18 =E00 +FR FQDC2 11 /N01.3 =E05 +CRP5 -X3 59 58 =E00 +FR FR-IO6-BI6.6 D8 /R05.4
=E05 +CRP5 X22 11 19 =E00 +FR FQDC2 98 /N01.5 =E05 +CRP5 -X3 60 59 =E00 +FR FR-IO6-BI6.7 D11 /R05.5
=E05 +CRP5 X22 12 20 =E00 +FR FR-IO2-LC B10 /N01.6 =E05 +CRP5 -X3 61 60 =E00 +FR FR-IO6-BI6.8 D12 /R05.5
=E01 +MK 30 21 =E00 +FR FR-IO1-BI1.1 D1 /R01.3 =E00 +FR BI2.1 B12 61 /R05.6
=E01 +MK -X3 29 22 =E00 +FR FR-IO1-BI1.2 D2 /R01.3 =E00 +FR BI2.2 B13 62 /R05.7
D =E01 +CRP1 -X3 2 23 =E00 +FR FR-IO1-BI1.3 D3 /R01.4 =E00 +FR BI2.3 B14 63 /R05.7 D
=E01 +CRP1 -X3 3 24 =E00 +FR FR-IO1-BI1.4 D4 /R01.4 64 /W01.2
=E01 +CRP1 -X3 4 25 =E00 +FR FR-IO1-BI1.5 D7 /R01.5 65 /W01.3
=E01 +CRP1 -X3 5 26 =E00 +FR FR-IO1-BI1.6 D8 /R01.5 66 /W01.3
=E01 +CRP1 -X3 6 27 =E00 +FR FR-IO1-BI1.7 D11 /R01.6 67 /W01.3
28 =E00 +FR FR-IO1-BI1.8 D12 /R01.6 68 /W01.3
=E02 +MK 25 29 =E00 +FR FR-IO3-BI3.1 D1 /R02.3 69 /W01.3
=E02 +MK -X3 22 30 =E00 +FR FR-IO3-BI3.2 D2 /R02.3 70 /W01.3
=E02 +CRP2 -X3 18 31 =E00 +FR FR-IO3-BI3.3 D3 /R02.4

E =E02 +CRP2 -X3 19 32 =E00 +FR FR-IO3-BI3.4 D4 /R02.4 E


=E02 +CRP2 -X3 20 33 =E00 +FR FR-IO3-BI3.5 D7 /R02.5
=E02 +CRP2 -X3 21 34 =E00 +FR FR-IO3-BI3.6 D8 /R02.5
=E02 +CRP2 -X3 22 35 =E00 +FR FR-IO3-BI3.7 D11 /R02.6
36 =E00 +FR FR-IO3-BI3.8 D12 /R02.6
=E03 +MK 47 37 =E00 +FR FR-IO4-BI4.1 D1 /R03.3
=E03 +MK -X3 46 38 =E00 +FR FR-IO4-BI4.2 D2 /R03.3
=E03 +CRP3 -X3 3 39 =E00 +FR FR-IO4-BI4.3 D3 /R03.4
=E03 +CRP3 -X3 4 40 =E00 +FR FR-IO4-BI4.4 D4 /R03.4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X104 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X105

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+FR-X8 PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+FR-X41 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E00 +FR 1 1 =E01 +MK X42 1 /S01.1
=E00 +FR 3 2 =E01 +MK X42 2 /S01.2
=E00 +FR 5 3 =E01 +MK X42 3 /S01.2

B =E00 +FR 7 4 =E01 +MK X42 4 /S01.2 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X105 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X106

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+FR-X41 PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+FR-X42 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E00 +FR 1 1 =E02 +MK X42 1 /S01.4
=E00 +FR 3 2 =E02 +MK X42 2 /S01.4
=E00 +FR 5 3 =E02 +MK X42 3 /S01.5

B =E00 +FR 7 4 =E02 +MK X42 4 /S01.5 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X106 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X107

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+FR-X42 PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+FR-X43 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E00 +FR 1 1 =E03 +CRP3 X411 1 /S01.7
=E00 +FR 3 2 =E03 +CRP3 X411 2 /S01.7
=E00 +FR 5 3 =E03 +CRP3 X411 3 /S01.7

B =E00 +FR 7 4 =E03 +CRP3 X411 4 /S01.7 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X107 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X108

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+FR-X43 PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+FR-X44 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E00 +FR 1 1 =E04 +CRP4 X411 1 /S02.1
=E00 +FR 3 2 =E04 +CRP4 X411 2 /S02.2
=E00 +FR 5 3 =E04 +CRP4 X411 3 /S02.2

B =E00 +FR 7 4 =E04 +CRP4 X411 4 /S02.2 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X108 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X109

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+FR-X44 PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+FR-X45 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E00 +FR 1 1 =E05 +MK X41 1 /S02.3
=E00 +FR 3 2 =E05 +MK X41 2 /S02.3
=E00 +FR 5 3 =E05 +MK X41 3 /S02.4

B =E00 +FR 7 4 =E05 +MK X41 4 /S02.4 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X109 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X110

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+FR-X45 PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+FR-X46 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E00 +FR C1 1 1 =E01 +CRP1 X45 1 /S02.5
=E00 +FR 3 2 =E01 +CRP1 X45 2 /S02.5
=E00 +FR 5 3 =E01 +CRP1 X45 3 /S02.6

B =E00 +FR 7 4 =E01 +CRP1 X45 4 /S02.6 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X110 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X111

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+FR-X46 PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+FR-X47 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E00 +FR C1 1 1 =E02 +CRP2 X45 1 /S02.7
=E00 +FR 3 2 =E02 +CRP2 X45 2 /S02.7
=E00 +FR 5 3 =E02 +CRP2 X45 3 /S02.7

B =E00 +FR 7 4 =E02 +CRP2 X45 4 /S02.8 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X111 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X112

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+FR-X47 PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+FR-X51 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E00 +FR 1 1 =E01 +CRP1 X52 2 /S03.3
=E00 +FR 3 2 =E01 +CRP1 X52 4 /S03.3
=E00 +FR 5 3 =E01 +CRP1 X52 6 /S03.3

B =E00 +FR 7 4 =E01 +CRP1 X52 8 /S03.4 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X112 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X113

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+FR-X51 PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+FR-X52 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E00 +FR 1 1 =E03 +CRP3 X53 1 /S03.1
=E00 +FR 3 2 =E03 +CRP3 X53 3 /S03.1
=E00 +FR 5 3 =E03 +CRP3 X53 5 /S03.2

B =E00 +FR 7 4 =E03 +CRP3 X53 7 /S03.2 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X113 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X114

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+FR-X52 PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+FR-X54 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E00 +FR 1 1 =E04 +CRP4 X53 1 /S04.2
=E00 +FR 3 2 =E04 +CRP4 X53 3 /S04.2
=E00 +FR 5 3 =E04 +CRP4 X53 5 /S04.2

B =E00 +FR 7 4 =E04 +CRP4 X53 7 /S04.2 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X114 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X115

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+FR-X54 PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+FR-X55 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E00 +FR 1 1 =E02 +CRP2 X52 2 /S04.4
=E00 +FR 3 2 =E02 +CRP2 X52 4 /S04.4
=E00 +FR 5 3 =E02 +CRP2 X52 6 /S04.4

B =E00 +FR 7 4 =E02 +CRP2 X52 8 /S04.5 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X115 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X116

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+FR-X55 PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+FR-X56 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E00 +FR 1 1 =E01 +CRP1 X51 2 /S03.6
=E00 +FR 3 2 =E01 +CRP1 X51 4 /S03.6
=E00 +FR 5 3 =E01 +CRP1 X51 6 /S03.7

B =E00 +FR 7 4 =E01 +CRP1 X51 8 /S03.7 B


=E00 +TRANDUCER -X ... 2 /S03.7
=E00 +TRANDUCER -X ... 4 /S03.7
=E00 +TRANDUCER -X ... 6 /S03.7
=E00 +TRANDUCER -X ... 8 /S03.7

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X116 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X117

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+FR-X56 PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+FR-X57 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E00 +FR 1 1 =E02 +CRP2 X51 2 /S04.6
=E00 +TRANDUCER -X ... 2 /S04.7
=E00 +TRANDUCER -X ... 4 /S04.7

B =E00 +FR 3 3 =E02 +CRP2 X51 4 /S04.6 B


=E00 +TRANDUCER -X ... 6 /S04.7
=E00 +FR 5 5 =E02 +CRP2 X51 6 /S04.6
=E00 +TRANDUCER -X ... 8 /S04.7
=E00 +FR 7 7 =E02 +CRP2 X51 8 /S04.7

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X117 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+FR-X57 PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+FR

FUNCTION FR - 7KE85 FUNCTION FR - 7KE85 FR FUNCTION


A A

IO2 IO1 IO1


+ = S
B1 Power A1 C1
_ (~)
/G02.2 CURRENT CIRCUIT E01 BAY - PHASE A /S01.1 BO1.4
B2 = Supply A2 I1 C2
A3
CURRENT CIRCUIT E01 BAY - PHASE B /S01.2 I2
A4
S F
B3 CURRENT CIRCUIT E01 BAY - PHASE C
A5 C6
BO2.1 /S01.2 I3 BO1.5
B4 A6 C4
B B
A7 C3
CURRENT CIRCUIT E01 BAY - PHASE N /S01.2 I4
A8
F
B8 C10
BO2.2 BO1.6
B6 C8
B5 B1 C7
VOLTAGE CIRCUIT E01 - PHASE A /S03.3 V1
B2

B9 B3 C13
FR HƯ HỎNG /N01.6 LC VOLTAGE CIRCUIT E01 - PHASE B /S03.3 V2 BI1.1 /R01.3 CB E01-QF01 OPENED
B7 B4 D1
C C
B10 VOLTAGE CIRCUIT E01 - PHASE C /S03.3 B5 C14
V3 BI1.2 /R01.3 CB E01-QF01 CLOSED
B6 D2

B11 B7 D5
VOLTAGE CIRCUIT E01 - PHASE N /S03.4 V4 BI1.3 /R01.4 =E01+CRP1 F87T TRIP
B8 D3
SPARE /R05.6 B12 BI2.1
D6
BI1.4 /R01.4 =E01+CRP1 F67 TRIP
SPARE /R05.7 B14 BI2.2 D4
F
SPARE /R05.7 B13 BI2.3 B9 D7
BO1.1 BI1.5 /R01.5 =E01+CRP1 F861 TRIP
D B10 D9 D
F
B11 D8
BO1.2 BI1.6 /R01.5 =E01+CRP1 F862 TRIP
E 2 x FO B12 D10
F
F B13 D13
BO1.3 BI1.7 /R01.6 =E01+CRP1 TRANS.PROTECTION TRIP
B14 D11
G D-sub 9
D14
BI1.8 /R01.6 SPARE
H D-sub 15 D12

J RJ45 E
E E
K RJ45

PS201 IO202

7KE85 - P1N109055

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE FAULT RECORDER: 7KE85 PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

FUNCTION FR - 7KE85 FR FUNCTION


A A

IO3 IO3
S
A1 C1
CURRENT CIRCUIT E02 BAY - PHASE A/S01.4 BO3.4
A2 I1 C2

A3
CURRENT CIRCUIT E02 BAY - PHASE B/S01.4 I2
A4
F
A5 C6
CURRENT CIRCUIT E02 BAY - PHASE C/S01.5 I3 BO3.5
B A6 C4 B
A7 C3
CURRENT CIRCUIT E02 BAY - PHASE N/S01.5 I4
A8
F
C10
BO3.6
C8

B1 C7
VOLTAGE CIRCUIT E02 - PHASE A /S03.1 V1
B2

B3 C13
VOLTAGE CIRCUIT E02 - PHASE B /S03.1 V2 BI3.1 /R02.3 CB E02-QF01 OPENED
C B4 D1 C
VOLTAGE CIRCUIT E02 - PHASE C /S03.2 B5 C14
V3 BI3.2 /R02.3 CB E02-QF01 CLOSED
B6 D2

B7 D5
VOLTAGE CIRCUIT E02 - PHASE N /S03.2 V4 BI3.3 /R02.4 =E02+CRP2 F87L TRIP
B8 D3

D6
BI3.4 /R02.4 =E02+CRP2 F67 TRIP
D4
F
B9 D7
BO3.1 BI3.5 /R02.5 =E02+CRP2 F861 TRIP
D B10 D9 D
F
B11 D8
BO3.2 BI3.6 /R02.5 =E02+CRP2 F862 TRIP
B12 D10
F
B13 D13
BO3.3 BI3.7 /R02.6 =E02+CRP2 TRANS.PROTECTION TRIP
B14 D11

D14
BI3.8 /R02.6 SPARE
D12

E E

IO202

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE FAULT RECORDER: 7KE85 PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+FR
FUNCTION FR - 7KE85 FR FUNCTION

A A

IO4 IO4
S
A1 C1
CURRENT CIRCUIT E03 BAY - PHASE A /S01.7 BO4.4
A2 I1 C2

A3
CURRENT CIRCUIT E03 BAY - PHASE B /S01.7 I2
A4
F
CURRENT CIRCUIT E03 BAY - PHASE C A5 C6
/S01.7 I3 BO4.5
A6 C4
B A7 C3
B
CURRENT CIRCUIT E03 BAY - PHASE N /S01.7 I4
A8
F
C10
BO4.6
C8

B1 C7
VOLTAGE CIRCUIT E03 - PHASE A /S03.4 V1
B2

B3 C13
VOLTAGE CIRCUIT E03 - PHASE B /S03.5 V2 BI4.1 /R03.3 CB E03-QF01 OPENED
B4 D1
C B5 C14
C
VOLTAGE CIRCUIT E03 - PHASE C /S03.5 V3 BI4.2 /R03.3 CB E03-QF01 CLOSED
B6 D2
B7 D5
VOLTAGE CIRCUIT E03 - PHASE N /S03.5 V4 BI4.3 /R03.4 =E03+CRP3 F87L TRIP
B8 D3

D6
BI4.4 /R03.4 =E03+CRP3 F21 TRIP
D4
F
B9 D7
BO4.1 BI4.5 /R03.5 =E03+CRP3 F861 TRIP
B10 D9
D F
D
B11 D8
BO4.2 BI4.6 /R03.5 =E03+CRP3 F862 TRIP
B12 D10
F
B13 D13
BO4.3 BI4.7 /R03.6 SPARE
B14 D11

D14
BI4.8 /R03.6 SPARE
D12

E E

IO202

7KE85 - P1N109055

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE FAULT RECORDER: 7KE85 PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+FR
FUNCTION FR - 7SJ85 FR FUNCTION

A A

IO5 IO5
S
A1 C1
CURRENT CIRCUIT E04 BAY - PHASE A /S02.1 BO5.4
A2 I1 C2

A3
CURRENT CIRCUIT E04 BAY - PHASE B /S02.2 I2
A4
F
CURRENT CIRCUIT E04 BAY - PHASE C A5 C6
/S02.2 I3 BO5.5
A6 C4
B A7 C3
B
CURRENT CIRCUIT E04 BAY - PHASE N /S02.2 I4
A8
F
C10
BO5.6
C8

B1 C7
VOLTAGE CIRCUIT E01 - PHASE A /S04.2 V1
B2

B3 C13
VOLTAGE CIRCUIT E01 - PHASE B /S04.2 V2 BI5.1 /R04.3 CB E04-QF01 OPENED
B4 D1
C B5 C14
C
VOLTAGE CIRCUIT E01 - PHASE C /S04.2 V3 BI5.2 /R04.3 CB E04-QF01 CLOSED
B6 D2
B7 D5
VOLTAGE CIRCUIT E01 - PHASE N /S04.2 V4 BI5.3 /R04.4 =E04+CRP4 F87L TRIP
B8 D3

D6
BI5.4 /R04.4 =E04+CRP4 F21 TRIP
D4
F
B9 D7
BO5.1 BI5.5 /R04.5 =E04+CRP4 F861 TRIP
B10 D9
D F
D
B11 D8
BO5.2 BI5.6 /R04.5 =E04+CRP4 F862 TRIP
B12 D10
F
B13 D13
BO5.3 BI5.7 /R04.6 SPARE
B14 D11

D14
BI5.8 /R04.6 SPARE
D12

E E

IO202

7KE85 - P1N109055

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z05

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE FAULT RECORDER: 7KE85 PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+FR
FUNCTION FR - 7SJ85 FR FUNCTION

A A

IO6 IO6
S
A1 C1
CURRENT CIRCUIT E05 BAY - PHASE A /S02.3 BO6.4
A2 I1 C2

A3
CURRENT CIRCUIT E05 BAY - PHASE B /S02.3 I2
A4
F
CURRENT CIRCUIT E05 BAY - PHASE C A5 C6
/S02.4 I3 BO6.5
A6 C4
B A7 C3
B
CURRENT CIRCUIT E05 BAY - PHASE N /S02.4 I4
A8
F
C10
BO6.6
C8

B1 C7
VOLTAGE CIRCUIT E02 - PHASE A /S04.4 V1
B2

B3 C13
VOLTAGE CIRCUIT E02 - PHASE B /S04.4 V2 BI6.1 /R05.2 CB E05-QF01 OPENED
B4 D1
C B5 C14
C
VOLTAGE CIRCUIT E02 - PHASE C /S04.4 V3 BI6.2 /R05.2 CB E05-QF01 CLOSED
B6 D2
B7 D5
VOLTAGE CIRCUIT E02 - PHASE N /S04.5 V4 BI6.3 /R05.3 =E05+CRP5 F87B TRIP
B8 D3

D6
BI6.4 /R05.3 =E05+CRP5 F21 TRIP
D4
F
B9 D7
BO6.1 BI6.5 /R05.4 =E05+CRP5 F271 TRIP
B10 D9
D F
D
B11 D8
BO6.2 BI6.6 /R05.4 =E05+CRP5 F272 TRIP
B12 D10
F
B13 D13
BO6.3 BI6.7 /R05.5 =E05+CRP5 F861 TRIP
B14 D11

D14
BI6.8 /R05.5 =E05+CRP5 F862 TRIP
D12

E E

IO202

7KE85 - P1N109055

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z05 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z06

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE FAULT RECORDER: 7KE85 PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A FUNCTION FR -7KE85 FUNCTION FR -7KE85 A

IO7 F
IO8 F
A1 + = A1 + =
POWER SUPPLY /G02.3 (~) PS POWER SUPPLY /G02.4 (~) PS
_ _
A2 = A2 =

B B

C C

D D

E E

PS203 PS203

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z06 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z07

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE FAULT RECORDER: 7KE85 PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+FR

CURRENT TEST BLOCK


A A
L1 L2 L3
-KTT-AW4
XTC1 XTC2 XTC3 XTC4 XTC5 XTC6 XTC7
S1
1 2
S2

S1
3 4

EQUIPMENT
S2

B B
S1 /S01.1 /S01.4 /S01.6 /S02.1 /S02.3 /S02.5 /S02.7
5 6
S2

7 8

C C

VOLTAGE TEST BLOCK

L1 L2 L3
-KTT-VW4
XTV1 XTV2 XTV3 XTV4 XTV5 XTV6 XTV7
1a
1 2
1n
D D
1a
3 4

EQUIPMENT
1n

1a /S03.3 /S03.1 /S03.4 /S04.1 /S04.4 /S03.6 /S04.6


5 6
1n

7 8
E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z07 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z08

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE CURRENT AND VOLTAGE TESTBLOCK PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+FR

A A

PQ2 PQ1 1
E E
CURRENT
2
A1
AI1 3
CURRENT CIRCUIT - PHASE A /S02.7 CURRENT CIRCUIT - PHASE A /S02.5
B A2
B
4
B1
AI2 5
CURRENT CIRCUIT - PHASE B /S02.7 CURRENT CIRCUIT - PHASE B /S02.5
B2
6
C1
AI3 7
CURRENT CIRCUIT - PHASE C /S02.7 CURRENT CIRCUIT - PHASE C /S02.6
C2
8
AI4
9
C PQ2 PQ1 C
F F VOLTAGE

/S04.6 VOLTAGE CIRCUIT E01 - PHASE A /S03.6 A


VOLTAGE CIRCUIT E05 - PHASE A B1
B BO1
VOLTAGE CIRCUIT E05 - PHASE B /S04.6 VOLTAGE CIRCUIT E01 - PHASE B /S03.6

/S04.6 VOLTAGE CIRCUIT E01 - PHASE C /S03.7 C B2


VOLTAGE CIRCUIT E05 - PHASE C BO2
N COM

PQ2 PQ1
H H POWER

D L+ D
POWER SUPPLY /G02.7 POWER SUPPLY /G02.6
L-

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z08 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE +MP1/A00

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY FAUL RECORDER AND POWER QUAILTY PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE POWER QUAILTY PECC2/TT-110KV/FR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

B B

B 24/11/2020 2nd FOR APPROVED

A 12/10/2020 1st FOR APPROVED

REV. DATE DESCRIPTION

CUSTOMER

C C
POWER ENGINEERING CONSULTING J.S.C. 2

PROJECT

TAN THUAN OFFSHORE WIND POWER PLANT

D D

LOCATION

TAN THUAN OFFSHORE WIND POWER PLANT

DRAW. NAME STAMP

E =E00+MP1: TARIFF METER PANEL E

DRAWING NO. PECC2/TT-110KV/MP1

STANDARD: IEC PAGE: A00 TOTAL NO. OF PAGE: 28

DESIGNED NGUYEN VAN NHAT CONTRACTOR

CHECKED NGUYEN VAN CHUNG


F F
APPROVED NGUYEN DINH TUAN
ENERGY TECHNOLOGY
JOINT STOCK COMPANNY
DATE 24/11/2020 Rev.: B

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

PAGE DESCRIPTION REV. X PAGE DESCRIPTION REV. X

=E00+MP1/A00 WIRING DIAGRAMS FOR METERING PANEL B


A A
=E00+MP1/A01 TABLE OF CONTENTS : =E00+MP1/A00 - =E00+MP1/Z02 B
=E00+MP1/A02 LIST OF EQUIPMENTS C
=E00+MP1/B01 LAYOUT DRAWING B
=E00+MP1/D01 AC POWER SUPPLY FOR METERING PANEL B
=E00+MP1/R01 SIGNAL FOR BCU B
=E00+MP1/T01 CURRENT, VOLTAGE CIRCUIT FOR MAIN TARIFF METER B

B =E00+MP1/T02 CURRENT, VOLTAGE CIRCUIT FOR B.UP TARIFF METER B B


=E00+MP1/T03 CURRENT, VOLTAGE CIRCUIT FOR B.UP TARIFF METER B
=E00+MP1/T03.a CURRENT, VOLTAGE CIRCUIT FOR B.UP TARIFF METER B
=E00+MP1/T04 CURRENT, VOLTAGE CIRCUIT FOR B.UP TARIFF METER B
=E00+MP1/T05 CURRENT, VOLTAGE CIRCUIT FOR B.UP TARIFF METER B
=E00+MP1/T06 CURRENT, VOLTAGE CIRCUIT FOR B.UP TARIFF METER B
=E00+MP1/X100 Terminal diagram =E00+MP1-XAC B
C =E00+MP1/X101 Terminal diagram =E00+MP1-X8 B C

=E00+MP1/X102 Terminal diagram =E00+MP1-X41 B


=E00+MP1/X103 Terminal diagram =E00+MP1-X42 B
=E00+MP1/X104 Terminal diagram =E00+MP1-X43 B
=E00+MP1/X105 Terminal diagram =E00+MP1-X44 B
=E00+MP1/X106 Terminal diagram =E00+MP1-X45 B
=E00+MP1/X107 Terminal diagram =E00+MP1-X46 B
D D
=E00+MP1/X108 Terminal diagram =E00+MP1-X51 B
=E00+MP1/X109 Terminal diagram =E00+MP1-X52 B
=E00+MP1/X110 Terminal diagram =E00+MP1-X53 B
=E00+MP1/X111 Terminal diagram =E00+MP1-X54 B
=E00+MP1/X112 Terminal diagram =E00+MP1-X55 B
=E00+MP1/Z01 MEASURING DEVICES REFERENCE B

E =E00+MP1/Z02 VOLTAGE/CURENT TEST BLOCKS REFERENCE B E

X: AUTOMATIC PAGE MODIFIED

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN TABLE OF CONTENTS : =E00+MP1/A00 - =E00+MP1/Z02 PECC2/TT-110KV/MP1

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

NO. SYMBOL DESCRIPTION MANUFACTORY CODE QTY. UNIT NOTE CUBICLE

1 PMT... TARRIF METTER ELSTER A1700 01 Pcs =E00+MP1


A A
2 XTC... CURRENT TESTBLOCK FUJI KTT-AW4 B M 07 Pcs =E00+MP1

3 XTV... VOLTAGE TESTBLOCK FUJI KTT-VW4 B M 07 Pcs =E00+MP1

4 FQAC MCB AC FOR LIGHTING AND HEATING LEGRAND DX3 01 Pcs =E00+MP1

5 XAC POWER TERMINALS DEGSON PC6 01 LOT =E00+MP1

6 X5... VOLTAGE TERMINALS DEGSON PC6 01 LOT =E00+MP1

7 X4... CURRENT TERMINALS DEGSON PCTK 01 LOT =E00+MP1


B B
8 X8 SIGNAL TERMINALS DEGSON PC4 01 LOT =E00+MP1

9 B0 THERMOSTAT CYMAX 01 SET =E00+MP1

10 B1 DOOR LIMIT SWITCH CHINA 01 SET =E00+MP1

11 E0 HEATING RESISTER CYMAX 01 SET =E00+MP1

12 E1 LIGHTING LAMP CHINA 01 SET =E00+MP1

13
C C
14

15

16

17

18

D 19 D

20

21

22

23

24

E 25
E

26

27

28

29

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LIST OF EQUIPMENTS PECC2/TT-110KV/MP1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

FRONT VIEW SIDE VIEW REAR VIEW

ENTEC =E00+MP1
EQUIPMENT
A A
TAD NAME FUNCTION
=E00+MP1 PTM TARIFF METER (A1700)
PTM PTM PTM XTC CURRENT TEST BLOCK FOR TARIFF METER
XTV VOLTAGE TEST BLOCK FOR TARIFF METER

PTM PTM PTM

B B
2200

XTC1 XTC2 XTC3 XTC4

XTC6 XTC7 XTC8

C XTV1 XTV2 XTV3 XTV4


C
XTV5 XTV6 XTV7
100

800 750 800


D D
800
TOP VIEW BOTTOM VIEW BASE NAME PLATE (SCALE 1:5)
4x∅14
100

C =E00+MP1

45
750
800
200
800

750

E REMARK: E
C (Scale 1:5) IP DEGREE: IP41
Ø14 APPLICATION STANDARD: IEC60529
25 MATERIAL: STEEL
STEEL THICKNESS: 2mm
4x∅8 PAINT COLOR: RAL7032
550
DOOR APPLY AREA: FRONT AND REAR
800 750 OPEN DOOR: 180°

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE D01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LAYOUT DRAWING PECC2/TT-110KV/MP1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E00+MP2 +MP1 =E00+FR

POWER SUPPLY
A FOR HEATING AND LIGHTING A

-W051
ACL1 1 -XAC 1 -XAC 2 ACL1
+MP2/D01.7/ / +FR/D01.1

ACL2 2 -XAC 3 -XAC 4 ACL2


+MP2/D01.7/ / +FR/D01.1

ACL3 3 -XAC 5 -XAC 6 ACL3


+MP2/D01.7/ / +FR/D01.1

ACN 4 -XAC 7 -XAC 8 ACN


+MP2/D01.7/ / +FR/D01.1

B B
1 3 12 14 96 98

-FQAC 11 95
2P-16A I> I>

/R01.4

/R01.5
2 4

LIGHTING HEATING SOCKET


C C

1 1
-B1 -B0
6A 2 0÷90°C 2

D D

1 1
1 1

-E0 -E1 -E2 -XSK


8W 60W 2 60W 2 16A
2 2
E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE D01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN AC POWER SUPPLY FOR METERING PANEL PECC2/TT-110KV/MP1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E00+MP1

A E00+MP1 E00+MP1 A
MCB AC OFF MCB TRIPPED

12 14 96 98
-FQAC -FQAC
B /D01.4 /D01.4
B
11 95

-X8 1 2 3 4 5

-W052 1 2 3

C C

MP1.MCBO

MP1.MCBT
F272.MP1+
=E05+CRP5

=E05+/N16.2 /

=E05+/N16.3 /
=E05+/N16.2

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE T01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN SIGNAL FOR BCU PECC2/TT-110KV/MP1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

=C11+VTB =E01+CT

A A

=E01+/T03.2

=E01+/T03.3

=E01+/T03.2

=E01+/T03.3

=E01+/T03.3

=E01+/T03.3
=E05+/S01.3

=E05+/S01.3

=E05+/S01.3

=E05+/S01.3

E01CT0.2.A1

E01CT0.2.C1
E01CT0.2.B1
E01CT0.2.A

E01CT0.2.C
E01CT0.2.B
BVT0.2.N
BVT0.2.A

BVT0.2.C
BVT0.2.B
B B

-W053 1 2 3 4 -W054 1 2 -W055 1 2 -W056 1 2

-X51 1 2 3 4 -X41 1 4 2 5 3 6

PE

C C

D D
SEAL-IN POINT

1 3 5 7 1 3 5 7
-XTV1 -XTC1
/Z02.5 /Z02.5

2 4 6 8 2 4 6 8
SEAL-IN POINT SEAL-IN POINT

E 2 5 8 11 1 4 7 E
-PMT1
/Z01.3
UA UB UC IA IB IC
MAIN TARIFF METER FOR E01 (131) BAY

3 6 9

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE T01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE T02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CURRENT, VOLTAGE CIRCUIT FOR MAIN TARIFF METER PECC2/TT-110KV/MP1

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

=C11+VTB =E01+CT

A A

=E01+/T03.5

=E01+/T03.6

=E01+/T03.5

=E01+/T03.6

=E01+/T03.6

=E01+/T03.6
=E05+/S01.6

=E05+/S01.6

=E05+/S01.6

=E05+/S01.6

E01CT0.5.A1

E01CT0.5.C1
E01CT0.5.B1
E01CT0.5.A

E01CT0.5.C
E01CT0.5.B
BVT0.5.N
BVT0.5.A

BVT0.5.C
BVT0.5.B
B B

-W057 1 2 3 4 -W058 1 2 -W059 1 2 -W060 1 2

-X52 1 2 3 4 -X42 1 4 2 5 3 6

PE
C C

D D
SEAL-IN POINT

1 3 5 7 1 3 5 7
-XTV2 -XTC2
/Z02.5 /Z02.5

2 4 6 8 2 4 6 8
SEAL-IN POINT SEAL-IN POINT

E 2 5 8 11 1 4 7 E
-PMT2
/Z01.3
UA UB UC IA IB IC
BACK UP TARIFF METER FOR E01 (131) BAY

3 6 9

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE T02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE T03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CURRENT, VOLTAGE CIRCUIT FOR B.UP TARIFF METER PECC2/TT-110KV/MP1

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

=E03+VTB =E03+CT

A A

=E03+/T03.4

=E03+/T03.5

=E03+/T03.4

=E03+/T03.5

=E03+/T03.4

=E03+/T03.5
=E03+/S01.3

=E03+/S01.3

=E03+/S01.3

=E03+/S01.3

E03CT0.5.A1

E03CT0.5.C1
E03CT0.5.B1
E03CT0.5.A

E03CT0.5.C
E03CT0.5.B
LVT0.5.N
LVT0.5.A

LVT0.5.C
LVT0.5.B
B B

-W061 1 2 3 4 -W062 1 2 -W063 1 2 -W064 1 2

-X53 1 2 3 4 -X43 1 4 2 5 3 6

PE
C C

D D
SEAL-IN POINT

1 3 5 7 1 3 5 7
-XTV3 -XTC3
/Z02.5 /Z02.5

2 4 6 8 2 4 6 8
SEAL-IN POINT SEAL-IN POINT

E 2 5 8 11 1 4 7 E
-PMT3
/Z01.3
UA UB UC IA IB IC
BACK UP TARIFF METER FOR E03 (171) BAY

3 6 9

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE T03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE T03.a

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CURRENT, VOLTAGE CIRCUIT FOR B.UP TARIFF METER PECC2/TT-110KV/MP1

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

=E04+VTB =E04+CT

A A

=E04+/S01.3

=E04+/S01.3

=E04+/S01.3

=E04+/S01.3

=E04+/T03.4

=E04+/T03.5

=E04+/T03.4

=E04+/T03.5

=E04+/T03.4

=E04+/T03.5
E04CT0.5.A1

E04CT0.5.C1
E04CT0.5.B1
E4LVT0.5.N

E04CT0.5.A

E04CT0.5.C
E04CT0.5.B
E4LVT0.5.A

E4LVT0.5.C
E4LVT0.5.B
B B

-W070 1 2 3 4 -W071 1 2 -W072 1 2 -W073 1 2

-X54 1 2 3 6 -X44 1 4 2 5 3 6

PE
C C

D D
SEAL-IN POINT

1 3 5 7 1 3 5 7
-XTV4 -XTC4
/Z02.6 /Z02.6

2 4 6 8 2 4 6 8
SEAL-IN POINT SEAL-IN POINT

E 2 5 8 11 1 4 7 E
-PMT4
/Z01.3
UA UB UC IA IB IC
BACK UP TARIFF METER FOR E04 (172) BAY

3 6 9

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE T03.a F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE T04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CURRENT, VOLTAGE CIRCUIT FOR B.UP TARIFF METER PECC2/TT-110KV/MP1

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

=C41+J01

A A

XUC 1 2 3 4 XIC 1 2 3 4

B B

-W069 1 2 3 4 -W065 1 2 3 4

-X55 1 2 3 4 -X45 1 2 3 4

C C

D D
SEAL-IN POINT

1 3 5 7 1 3 5 7
-XTV5 -XTC5
/Z02.6 /Z02.6

2 4 6 8 2 4 6 8
SEAL-IN POINT SEAL-IN POINT

E 2 5 8 11 1 4 7 E
-PMT5
/Z01.3
UA UB UC IA IB IC
BACK UP TARIFF METER FOR J01 (431) BAY

3 6 9

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE T04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE T05

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CURRENT, VOLTAGE CIRCUIT FOR B.UP TARIFF METER PECC2/TT-110KV/MP1

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

=C41+J02 =C41+J04

A A

XUC 1 2 3 4 X ... X ... X ... ...

B B

-W066 1 2 3 4 -W067 1 2 3 4

-X56 1 2 3 4 -X46 1 2 3 4

C N C
/ T06.2

C
/ T06.2

B
/ T06.2

A
/ T06.2

D D
SEAL-IN POINT

1 3 5 7 1 3 5 7
-XTV6 -XTC6
/Z02.6 /Z02.6

2 4 6 8 2 4 6 8
SEAL-IN POINT SEAL-IN POINT

E 2 5 8 11 1 4 7 E
-PMT6
/Z01.3
UA UB UC IA IB IC
BACK UP TARIFF METER FOR J04 (471) BAY

3 6 9

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE T05 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE T06

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CURRENT, VOLTAGE CIRCUIT FOR B.UP TARIFF METER PECC2/TT-110KV/MP1

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

=C41+J05

A A

X ... X ... X ... ...

B B

-W068 1 2 3 4

-X47 1 2 3 4

C T05.4
N C

T05.4
C

T05.4
B

T05.4
A

D D
SEAL-IN POINT

1 3 5 7 1 3 5 7
-XTV7 -XTC7

2 4 6 8 2 4 6 8
SEAL-IN POINT SEAL-IN POINT

E 2 5 8 11 1 4 7 E
-PMT7
/Z01.3
UA UB UC IA IB IC
BACK UP TARIFF METER FOR J05 (473) BAY

3 6 9

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE T06 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X100

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CURRENT, VOLTAGE CIRCUIT FOR B.UP TARIFF METER PECC2/TT-110KV/MP1

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+MP1-XAC A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E00 +MP2 -XAC 2 1 /D01.2
=E00 +FR -XAC 1 2 /D01.6
=E00 +MP2 -XAC 4 3 =E00 +MP1 FQAC 1 /D01.2

B =E00 +FR -XAC 3 4 /D01.6 B


=E00 +MP2 -XAC 6 5 /D01.2
=E00 +FR -XAC 5 6 /D01.6
=E00 +MP2 -XAC 8 7 =E00 +MP1 FQAC 3 /D01.2
=E00 +FR -XAC 7 8 /D01.6

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X100 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X101

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+MP1-XAC PECC2/TT-110KV/MP1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+MP1-X8 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E05 +CRP5 X23 2 1 =E00 +MP1 FQAC 12 /R01.3
2 /R01.4
=E05 +CRP5 X23 9 3 =E00 +MP1 FQAC 11 /R01.4

B =E05 +CRP5 X23 10 4 =E00 +MP1 FQAC 95 /R01.5 B


5 /R01.5

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X101 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X102

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+MP1-X8 PECC2/TT-110KV/MP1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+MP1-X41 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +CT-PA +CT-PA-PA 3S1 1 =E00 +MP1 XTC1-C1 1 /T01.6
=E01 +CT-PB +CT-PB-PB 3S1 2 =E00 +MP1 XTC1-C2 3 /T01.6
=E01 +CT-PC +CT-PC-PC 3S1 3 =E00 +MP1 XTC1-C3 5 /T01.7

B =E01 +CT-PA +CT-PA-PA 3S4 4 =E00 +MP1 PE /T01.6 B


=E01 +CT-PB +CT-PB-PB 3S4 5 /T01.6
=E01 +CT-PC 3S4 6 =E00 +MP1 XTC1-C4 7 /T01.7

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X102 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X103

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+MP1-X41 PECC2/TT-110KV/MP1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+MP1-X42 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +CT-PA 4S1 1 =E00 +MP1 XTC2-C1 1 /T02.6
=E01 +CT-PB +CT-PB-PB 4S1 2 =E00 +MP1 XTC2-C2 3 /T02.6
=E01 +CT-PC +CT-PC-PC 4S1 3 =E00 +MP1 XTC2-C3 5 /T02.7

B =E01 +CT-PA +CT-PA-PA 4S4 4 =E00 +MP1 PE /T02.6 B


=E01 +CT-PB +CT-PB-PB 4S4 5 /T02.6
=E01 +CT-PC 4S4 6 =E00 +MP1 XTC2-C4 7 /T02.7

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X103 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X104

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+MP1-X42 PECC2/TT-110KV/MP1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+MP1-X43 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +CT-PA +CT-PA-PA 3S1 1 =E00 +MP1 XTC3-C1 1 /T03.6
=E03 +CT-PB +CT-PB-PB 3S1 2 =E00 +MP1 XTC3-C2 3 /T03.6
=E03 +CT-PC +CT-PC-PC 3S1 3 =E00 +MP1 XTC3-C3 5 /T03.7

B =E03 +CT-PA +CT-PA-PA 3S4 4 =E00 +MP1 PE /T03.6 B


=E03 +CT-PB +CT-PB-PB 3S4 5 /T03.6
=E03 +CT-PC 3S4 6 =E00 +MP1 XTC3-C4 7 /T03.7

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X104 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X105

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+MP1-X43 PECC2/TT-110KV/MP1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+MP1-X44 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E04 +CT-PA +CT-PA-PA 3S1 1 =E00 +MP1 XTC4-C1 1 /T03.a.6
=E04 +CT-PB +CT-PB-PB 3S1 2 =E00 +MP1 XTC4-C2 3 /T03.a.6
=E04 +CT-PC +CT-PC-PC 3S1 3 =E00 +MP1 XTC4-C3 5 /T03.a.7

B =E04 +CT-PA +CT-PA-PA 3S4 4 =E00 +MP1 PE /T03.a.6 B


=E04 +CT-PB +CT-PB-PB 3S4 5 /T03.a.6
=E04 +CT-PC 3S4 6 =E00 +MP1 XTC4-C4 7 /T03.a.7

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X105 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X106

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+MP1-X44 PECC2/TT-110KV/MP1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+MP1-X45 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=C41 +J01 XIC 1 1 =E00 +MP1 XTC5-C1 1 /T04.6
=C41 +J01 2 2 =E00 +MP1 XTC5-C2 3 /T04.6
=C41 +J01 3 3 =E00 +MP1 XTC5-C3 5 /T04.7

B =C41 +J01 4 4 =E00 +MP1 XTC5-C4 7 /T04.7 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X106 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X107

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+MP1-X45 PECC2/TT-110KV/MP1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+MP1-X46 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=C41 +J04 X ... 1 =E00 +MP1 XTC6-C1 1 /T05.6
=C41 +J04 X ... 2 =E00 +MP1 XTC6-C2 3 /T05.6
=C41 +J04 X ... 3 =E00 +MP1 XTC6-C3 5 /T05.7

B =C41 +J04 X ... 4 =E00 +MP1 XTC6-C4 7 /T05.7 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X107 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X108

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+MP1-X46 PECC2/TT-110KV/MP1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+MP1-X51 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=C11 +VTB X51 7 1 =E00 +MP1 XTV1-C1 1 /T01.2
=E00 +MP1 C2 3 2 =C11 +VTB X51 8 /T01.3
=E00 +MP1 C3 5 3 =C11 +VTB X51 9 /T01.3

B =E00 +MP1 C4 7 4 =C11 +VTB X51 10 /T01.3 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X108 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X109

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+MP1-X51 PECC2/TT-110KV/MP1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+MP1-X52 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=C11 +VTB X52 7 1 =E00 +MP1 XTV2-C1 1 /T02.2
=E00 +MP1 C2 3 2 =C11 +VTB X52 8 /T02.3
=E00 +MP1 C3 5 3 =C11 +VTB X52 9 /T02.3

B =E00 +MP1 C4 7 4 =C11 +VTB X52 10 /T02.3 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X109 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X110

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+MP1-X52 PECC2/TT-110KV/MP1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+MP1-X53 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +VTB X51 7 1 =E00 +MP1 XTV3-C1 1 /T03.2
=E00 +MP1 C2 3 2 =E03 +VTB X51 8 /T03.3
=E00 +MP1 C3 5 3 =E03 +VTB X51 9 /T03.3

B =E00 +MP1 C4 7 4 =E03 +VTB X51 10 /T03.3 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X110 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X111

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+MP1-X53 PECC2/TT-110KV/MP1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+MP1-X54 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E04 +VTB X51 7 1 =E00 +MP1 XTV4-C1 1 /T03.a.2
=E04 +VTB X51 8 2 =E00 +MP1 XTV4-C2 3 /T03.a.3
=E04 +VTB X51 9 3 =E00 +MP1 XTV4-C3 5 /T03.a.3

B =E04 +VTB X51 10 6 =E00 +MP1 XTV4-C4 7 /T03.a.3 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X111 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X112

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+MP1-X54 PECC2/TT-110KV/MP1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+MP1-X55 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=C41 +J01 XUC 1 1 =E00 +MP1 XTV5-C1 1 /T04.2
=C41 +J01 2 2 =E00 +MP1 XTV5-C2 3 /T04.3
=C41 +J01 3 3 =E00 +MP1 XTV5-C3 5 /T04.3

B =C41 +J01 4 4 =E00 +MP1 XTV5-C4 7 /T04.3 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X112 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+MP1-X55 PECC2/TT-110KV/MP1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E00+MP1

A A

TARIFF METER

B B
RS485 RS485

RJ12 RJ12

1 2 3 4 5 6 7 8 9 11

IA UA IB UB IC UC UN

-PMT1 /T01.2

C C
-PMT2 /T02.2

-PMT3 /T03.2

-PMT4 /T03.a.2

-PMT5 /T04.2

-PMT6 /T05.2

-PMT7 /T06.2
D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN MEASURING DEVICES REFERENCE PECC2/TT-110KV/MP1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A
CURRENT TEST BLOCK

L1 L2 L3
-KTT-AW4
XTC1 XTC2 XTC3 XTC4 XTC5 XTC6

S1
1 2
S2

S1
3 4

EQUIPMENT
B B
S2

S1 /T01.6 /T02.6 /T03.6 /T03.a.6 /T04.6 /T05.6


5 6
S2

7 8

C C

VOLTAGE TEST BLOCK

L1 L2 L3
-KTT-VW4 XTV1 XTV2 XTV3 XTV4 XTV5 XTV6

1a
D 1 2 D
1n

1a
3 4

EQUIPMENT
1n
/T01.2 /T02.2 /T03.2 /T03.a.2 /T04.2 /T05.2
1a
5 6
1n

E E
7 8

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE +MP2/A00

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN VOLTAGE/CURENT TEST BLOCKS REFERENCE PECC2/TT-110KV/MP1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

B B

B 24/11/2020 2nd FOR APPROVED

A 12/10/2020 1st FOR APPROVED

REV. DATE DESCRIPTION

CUSTOMER

C C
POWER ENGINEERING CONSULTING J.S.C. 2

PROJECT

TAN THUAN OFFSHORE WIND POWER PLANT

D D

LOCATION

TAN THUAN OFFSHORE WIND POWER PLANT

DRAW. NAME STAMP

E =E00+MP2: TARIFF METER PANEL E

DRAWING NO. PECC2/TT-110KV/MP2

STANDARD: IEC PAGE: A00 TOTAL NO. OF PAGE: 27

DESIGNED NGUYEN VAN NHAT CONTRACTOR

CHECKED NGUYEN VAN CHUNG


F F
APPROVED NGUYEN DINH TUAN
ENERGY TECHNOLOGY
JOINT STOCK COMPANNY
DATE 24/11/2020 Rev.: B

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

PAGE DESCRIPTION REV. X PAGE DESCRIPTION REV. X

=E00+MP2/A00 WIRING DIAGRAMS FOR METERING PANEL B


A A
=E00+MP2/A01 TABLE OF CONTENTS : =E00+MP2/A00 - =E00+MP2/Z02 B
=E00+MP2/A02 LIST OF EQUIPMENTS C
=E00+MP2/B01 LAYOUT DRAWING B
=E00+MP2/D01 AC POWER SUPPLY FOR METERING PANEL B
=E00+MP2/R01 SIGNAL FOR BCU B
=E00+MP2/T01 CURRENT, VOLTAGE CIRCUIT FOR MAIN TARIFF METER B

B =E00+MP2/T02 CURRENT, VOLTAGE CIRCUIT FOR B.UP TARIFF METER B B


=E00+MP2/T04 CURRENT, VOLTAGE CIRCUIT FOR B.UP TARIFF METER B
=E00+MP2/T05 CURRENT, VOLTAGE CIRCUIT FOR B.UP TARIFF METER B
=E00+MP2/T06 CURRENT, VOLTAGE CIRCUIT FOR B.UP TARIFF METER B
=E00+MP2/T07 CURRENT, VOLTAGE CIRCUIT FOR B.UP TARIFF METER B
=E00+MP2/T08 CURRENT, VOLTAGE CIRCUIT FOR B.UP TARIFF METER B
=E00+MP2/X101 Terminal diagram =E00+MP2-XAC B
C =E00+MP2/X102 Terminal diagram =E00+MP2-X8 B C

=E00+MP2/X103 Terminal diagram =E00+MP2-X41 B


=E00+MP2/X104 Terminal diagram =E00+MP2-X42 B
=E00+MP2/X105 Terminal diagram =E00+MP2-X43 B
=E00+MP2/X106 Terminal diagram =E00+MP2-X44 B
=E00+MP2/X107 Terminal diagram =E00+MP2-X45 B
=E00+MP2/X108 Terminal diagram =E00+MP2-X46 B
D D
=E00+MP2/X109 Terminal diagram =E00+MP2-X47 B
=E00+MP2/X111 Terminal diagram =E00+MP2-X51 B
=E00+MP2/X112 Terminal diagram =E00+MP2-X52 B
=E00+MP2/X113 Terminal diagram =E00+MP2-X54 B
=E00+MP2/Z01 MEASURING DEVICES REFERENCE B
=E00+MP2/Z02 VOLTAGE/CURENT TEST BLOCKS REFERENCE B

E E

X: AUTOMATIC PAGE MODIFIED

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN TABLE OF CONTENTS : =E00+MP2/A00 - =E00+MP2/Z02 PECC2/TT-110KV/MP2

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

NO. SYMBOL DESCRIPTION MANUFACTORY CODE QTY. UNIT NOTE CUBICLE

1 PMT... TARRIF METTER ELSTER A1700 01 Pcs =E00+MP2


A A
2 XTC... CURRENT TESTBLOCK FUJI KTT-AW4 B M 07 Pcs =E00+MP2

3 XTV... VOLTAGE TESTBLOCK FUJI KTT-VW4 B M 07 Pcs =E00+MP2

4 FQAC MCB AC FOR LIGHTING AND HEATING LEGRAND DX3 01 Pcs =E00+MP2

5 XAC POWER TERMINALS DEGSON PC6 01 LOT =E00+MP2

6 X5... VOLTAGE TERMINALS DEGSON PC6 01 LOT =E00+MP2

7 X4... CURRENT TERMINALS DEGSON PCTK 01 LOT =E00+MP2


B B
8 X8 SIGNAL TERMINALS DEGSON PC4 01 LOT =E00+MP2

9 B0 THERMOSTAT CYMAX 01 SET =E00+MP2

10 B1 DOOR LIMIT SWITCH CHINA 01 SET =E00+MP2

11 E0 HEATING RESISTER CYMAX 01 SET =E00+MP2

12 E1 LIGHTING LAMP CHINA 01 SET =E00+MP2

13
C C
14

15

16

17

18

D 19 D

20

21

22

23

24

E 25
E

26

27

28

29

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LIST OF EQUIPMENTS PECC2/TT-110KV/MP2
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

FRONT VIEW SIDE VIEW REAR VIEW

ENTEC =E00+MP2
EQUIPMENT
A A
TAD NAME FUNCTION
=E00+MP1 PTM TARIFF METER (A1700)
PTM PTM PTM XTC CURRENT TEST BLOCK FOR TARIFF METER
XTV VOLTAGE TEST BLOCK FOR TARIFF METER

PTM PTM PTM

B B

PTM PTM
2200

XTC1 XTC2 XTC3 XTC4

XTC5 XTC6 XTC7 XTC8

C XTV1 XTV2 XTV3 XTV4


C
XTV5 XTV6 XTV7 XTV8
100

800 750 800


D D
800
TOP VIEW BOTTOM VIEW BASE NAME PLATE (SCALE 1:5)
4x∅14
100

C =E00+MP2

45
750
800
200
800

750

E REMARK: E
C (Scale 1:5) IP DEGREE: IP41
Ø14 APPLICATION STANDARD: IEC60529
25 MATERIAL: STEEL
STEEL THICKNESS: 2mm
4x∅8 PAINT COLOR: RAL7032
550
DOOR APPLY AREA: FRONT AND REAR
800 750 OPEN DOOR: 180°

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE D01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LAYOUT DRAWING PECC2/TT-110KV/MP2
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=N00+AC +MP2 =E00+MP1

POWER SUPPLY
A FOR HEATING AND LIGHTING A

-W074
ACL1 1 -XAC 1 -XAC 2 ACL1
=N00+AC/D06.5/ / +MP1/D01.1

ACL2 3 -XAC 3 -XAC 4 ACL2


=N00+AC/D06.5/ / +MP1/D01.1

ACL3 2 -XAC 5 -XAC 6 ACL3


=N00+AC/D06.6/ / +MP1/D01.1

ACN 4 -XAC 7 -XAC 8 ACN


=N00+AC/D06.6/ / +MP1/D01.1

B B
1 3 12 14 96 98

-FQAC 11 95
2P-16A I> I>

/R01.4

/R01.5
2 4

LIGHTING HEATING SOCKET


C C

1 1
-B1 -B0
6A 2 0÷90°C 2

D D

1 1
1 1

-E0 -E1 -E2 -XSK


8W 60W 2 60W 2 16A
2 2
E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE D01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN AC POWER SUPPLY FOR METERING PANEL PECC2/TT-110KV/MP2
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E00+MP2

A E00+MP2 E00+MP2 A
MCB AC OFF MCB TRIPPED

12 14 96 98
-FQAC -FQAC
B /D01.4 /D01.4
B
11 95

-X8 1 2 3 4 5

-W075 1 2 3

C C

MP2.MCBO

MP2.MCBT
F272.MP2+
=E05+CRP5

=E05+/N16.4 /

=E05+/N16.4 /
=E05+/N16.4

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE T01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN SIGNAL FOR BCU PECC2/TT-110KV/MP2
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

=C12+VTB =E02+CT

A A

=E02+/T03.2

=E02+/T03.3

=E02+/T03.2

=E02+/T03.3

=E02+/T03.3

=E02+/T03.3
=E05+/S03.3

=E05+/S03.3

=E05+/S03.3

=E05+/S03.3

E02CT0.2.A1

E02CT0.2.C1
E02CT0.2.B1
E02CT0.2.A

E02CT0.2.C
E02CT0.2.B
BVT0.2.N
BVT0.2.A

BVT0.2.C
BVT0.2.B
B B

-W076 1 2 3 4 -W077 1 2 -W078 1 2 -W079 1 2

-X51 1 2 3 6 -X41 1 4 2 5 3 6

PE

C C

D D
SEAL-IN POINT

1 3 5 7 1 3 5 7
-XTV1 -XTC1
/Z02.5 /Z02.5

2 4 6 8 2 4 6 8
SEAL-IN POINT SEAL-IN POINT

E 2 5 8 11 1 4 7 E
-PMT1
/Z01.3
UA UB UC IA IB IC

3 6 9

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE T01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE T02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CURRENT, VOLTAGE CIRCUIT FOR MAIN TARIFF METER PECC2/TT-110KV/MP2

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

=C12+VTB =E02+CT

A A

=E02+/T03.5

=E02+/T03.6

=E02+/T03.5

=E02+/T03.6

=E02+/T03.6

=E02+/T03.6
=E05+/S03.6

=E05+/S03.6

=E05+/S03.6

=E05+/S03.6

E02CT0.5.A1

E02CT0.5.C1
E02CT0.5.B1
E02CT0.5.A

E02CT0.5.C
E02CT0.5.B
BVT0.5.N
BVT0.5.A

BVT0.5.C
BVT0.5.B
B B

-W080 1 2 3 4 -W081 1 2 -W082 1 2 -W083 1 2

-X52 1 2 3 6
-X42 1 4 2 5 3 6

PE
C C

D D
SEAL-IN POINT

1 3 5 7 1 3 5 7
-XTV2 -XTC2
/Z02.5 /Z02.5

2 4 6 8 2 4 6 8
SEAL-IN POINT SEAL-IN POINT

E 2 5 8 11 1 4 7 E
-PMT2
/Z01.3
UA UB UC IA IB IC

3 6 9

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE T02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE T04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CURRENT, VOLTAGE CIRCUIT FOR B.UP TARIFF METER PECC2/TT-110KV/MP2

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

=C42+J13

A A

X ... X ... X ... ... X ... X ... X ... ...

B B

-W088 1 2 3 4 -W084 1 2 3 4

-X53 1 2 3 4 -X43 1 2 3 4

C C

D D
SEAL-IN POINT

1 3 5 7 1 3 5 7
-XTV3 -XTC3
/Z02.5 /Z02.5

2 4 6 8 2 4 6 8
SEAL-IN POINT SEAL-IN POINT

E 2 5 8 11 1 4 7 E
-PMT3
/Z01.3
UA UB UC IA IB IC

3 6 9

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE T04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE T05

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CURRENT, VOLTAGE CIRCUIT FOR B.UP TARIFF METER PECC2/TT-110KV/MP2

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

=C42+J12 =C42+J11

A A

X ... X ... X ... ... X ... X ... X ... ...

B B

-W085 1 2 3 4 -W086 1 2 3 4

-X54 1 2 3 4 -X44 1 2 3 4

C N C
/ T06.2

C
/ T06.2

B
/ T06.2

A
/ T06.2

D D
SEAL-IN POINT

1 3 5 7 1 3 5 7
-XTV4 -XTC4
/Z02.6 /Z02.6

2 4 6 8 2 4 6 8
SEAL-IN POINT SEAL-IN POINT

E 2 5 8 11 1 4 7 E
-PMT4
/Z01.3
UA UB UC IA IB IC

3 6 9

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE T05 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE T06

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CURRENT, VOLTAGE CIRCUIT FOR B.UP TARIFF METER PECC2/TT-110KV/MP2

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

=C42+J10

A A

X ... X ... X ... ...

B B

-W087 1 2 3 4

-X45 1 2 3 4

C N N C
T05.4 / T07.2

C C
T05.4 / T07.2

B B
T05.4 / T07.2

A A
T05.4 / T07.2

D D
SEAL-IN POINT

1 3 5 7 1 3 5 7
-XTV5 -XTC5
/Z02.6 /Z02.6

2 4 6 8 2 4 6 8
SEAL-IN POINT SEAL-IN POINT

E 2 5 8 11 1 4 7 E
-PMT5
/Z01.3
UA UB UC IA IB IC

3 6 9

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE T06 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE T07

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CURRENT, VOLTAGE CIRCUIT FOR B.UP TARIFF METER PECC2/TT-110KV/MP2

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

=C42+J09

A A

X ... X ... X ... ...

B B

-X46 1 2 3 4

C N N C
T06.4 / T08.2

C C
T06.4 / T08.2

B B
T06.4 / T08.2

A A
T06.4 / T08.2

D D
SEAL-IN POINT

1 3 5 7 1 3 5 7
-XTV6 -XTC6
/Z02.6 /Z02.6

2 4 6 8 2 4 6 8
SEAL-IN POINT SEAL-IN POINT

E 2 5 8 11 1 4 7 E
-PMT6
/Z01.3
UA UB UC IA IB IC

3 6 9

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE T07 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE T08

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CURRENT, VOLTAGE CIRCUIT FOR B.UP TARIFF METER PECC2/TT-110KV/MP2

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

=C42+J08

A A

X ... X ... X ... ...

B B

-X47 1 2 3 4

C T07.4
N C

T07.4
C

T07.4
B

T07.4
A

D D
SEAL-IN POINT

1 3 5 7 1 3 5 7
-XTV7 -XTC7
/Z02.6 /Z02.6

2 4 6 8 2 4 6 8
SEAL-IN POINT SEAL-IN POINT

E 2 5 8 11 1 4 7 E
-PMT7
/Z01.3
UA UB UC IA IB IC

3 6 9

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE T08 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X101

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CURRENT, VOLTAGE CIRCUIT FOR B.UP TARIFF METER PECC2/TT-110KV/MP2

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+MP2-XAC A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=N00 +AC 33 1 =E00 +MP2 FQAC 1 /D01.2
=E00 +MP1 -XAC 1 2 /D01.6
=N00 +AC 34 3 /D01.2

B =E00 +MP1 -XAC 3 4 /D01.6 B


=N00 +AC 35 5 /D01.2
=E00 +MP1 -XAC 5 6 /D01.6
=N00 +AC 36 7 =E00 +MP2 FQAC 3 /D01.2
=E00 +MP1 -XAC 7 8 /D01.6

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X101 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X102

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+MP2-XAC PECC2/TT-110KV/MP2
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+MP2-X8 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E05 +CRP5 X23 3 1 =E00 +MP2 FQAC 12 /R01.3
2 /R01.4
=E05 +CRP5 X23 11 3 =E00 +MP2 FQAC 11 /R01.4

B =E05 +CRP5 X23 12 4 =E00 +MP2 FQAC 95 /R01.5 B


5 /R01.5

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X102 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X103

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+MP2-X8 PECC2/TT-110KV/MP2
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+MP2-X41 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +CT-PA +CT-PA-PA 3S1 1 =E00 +MP2 XTC1-C1 1 /T01.6
=E02 +CT-PB +CT-PB-PB 3S1 2 =E00 +MP2 XTC1-C2 3 /T01.6
=E02 +CT-PC +CT-PC-PC 3S1 3 =E00 +MP2 XTC1-C3 5 /T01.7

B =E02 +CT-PA +CT-PA-PA 3S4 4 =E00 +MP2 PE /T01.6 B


=E02 +CT-PB +CT-PB-PB 3S4 5 /T01.6
=E02 +CT-PC 3S4 6 =E00 +MP2 XTC1-C4 7 /T01.7

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X103 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X104

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+MP2-X41 PECC2/TT-110KV/MP2
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+MP2-X42 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +CT-PA 4S1 1 =E00 +MP2 XTC2-C1 1 /T02.6
=E02 +CT-PB +CT-PB-PB 4S1 2 =E00 +MP2 XTC2-C2 3 /T02.6
=E02 +CT-PC +CT-PC-PC 4S1 3 =E00 +MP2 XTC2-C3 5 /T02.7

B =E02 +CT-PA +CT-PA-PA 4S4 4 =E00 +MP2 PE /T02.6 B


=E02 +CT-PB +CT-PB-PB 4S4 5 /T02.6
=E02 +CT-PC 4S4 6 =E00 +MP2 XTC2-C4 7 /T02.7

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X104 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X105

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+MP2-X42 PECC2/TT-110KV/MP2
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+MP2-X43 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=C42 +J13 X ... 1 =E00 +MP2 XTC3-C1 1 /T04.6
=C42 +J13 X ... 2 =E00 +MP2 XTC3-C2 3 /T04.6
=C42 +J13 X ... 3 =E00 +MP2 XTC3-C3 5 /T04.7

B =C42 +J13 X ... 4 =E00 +MP2 XTC3-C4 7 /T04.7 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X105 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X106

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+MP2-X43 PECC2/TT-110KV/MP2
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+MP2-X44 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=C42 +J11 X ... 1 =E00 +MP2 XTC4-C1 1 /T05.6
=C42 +J11 X ... 2 =E00 +MP2 XTC4-C2 3 /T05.6
=C42 +J11 X ... 3 =E00 +MP2 XTC4-C3 5 /T05.7

B =C42 +J11 X ... 4 =E00 +MP2 XTC4-C4 7 /T05.7 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X106 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X107

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+MP2-X44 PECC2/TT-110KV/MP2
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+MP2-X45 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=C42 +J10 X ... 1 =E00 +MP2 XTC5-C1 1 /T06.6
=C42 +J10 X ... 2 =E00 +MP2 XTC5-C2 3 /T06.6
=C42 +J10 X ... 3 =E00 +MP2 XTC5-C3 5 /T06.7

B =C42 +J10 X ... 4 =E00 +MP2 XTC5-C4 7 /T06.7 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X107 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X108

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+MP2-X45 PECC2/TT-110KV/MP2
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+MP2-X46 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=C42 +J09 X ... 1 =E00 +MP2 XTC6-C1 1 /T07.6
=C42 +J09 X ... 2 =E00 +MP2 XTC6-C2 3 /T07.6
=C42 +J09 X ... 3 =E00 +MP2 XTC6-C3 5 /T07.7

B =C42 +J09 X ... 4 =E00 +MP2 XTC6-C4 7 /T07.7 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X108 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X109

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+MP2-X46 PECC2/TT-110KV/MP2
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+MP2-X47 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=C42 +J08 X ... 1 =E00 +MP2 XTC7-C1 1 /T08.6
=C42 +J08 X ... 2 =E00 +MP2 XTC7-C2 3 /T08.6
=C42 +J08 X ... 3 =E00 +MP2 XTC7-C3 5 /T08.7

B =C42 +J08 X ... 4 =E00 +MP2 XTC7-C4 7 /T08.7 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X109 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X111

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+MP2-X47 PECC2/TT-110KV/MP2
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+MP2-X51 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=C12 +VTB X51 7 1 =E00 +MP2 XTV1-C1 1 /T01.2
=C12 +VTB X51 8 2 =E00 +MP2 XTV1-C2 3 /T01.3
=C12 +VTB X51 9 3 =E00 +MP2 XTV1-C3 5 /T01.3

B =C12 +VTB X51 10 6 =E00 +MP2 XTV1-C4 7 /T01.3 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X111 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X112

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+MP2-X51 PECC2/TT-110KV/MP2
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+MP2-X52 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=C12 +VTB X52 7 1 =E00 +MP2 XTV2-C1 1 /T02.2
=C12 +VTB X52 8 2 =E00 +MP2 XTV2-C2 3 /T02.3
=C12 +VTB X52 9 3 =E00 +MP2 XTV2-C3 5 /T02.3

B =C12 +VTB X52 10 6 =E00 +MP2 XTV2-C4 7 /T02.3 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X112 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X113

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+MP2-X52 PECC2/TT-110KV/MP2
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E00+MP2-X54 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=C42 +J12 X ... 1 =E00 +MP2 XTV4-C1 1 /T05.2
=C42 +J12 X ... 2 =E00 +MP2 XTV4-C2 3 /T05.3
=C42 +J12 X ... 3 =E00 +MP2 XTV4-C3 5 /T05.3

B =C42 +J12 X ... 4 =E00 +MP2 XTV4-C4 7 /T05.3 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X113 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E00+MP2-X54 PECC2/TT-110KV/MP2
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E00+MP2

A A

TARIFF METER

B B
RS485 RS485

RJ12 RJ12

1 2 3 4 5 6 7 8 9 11

IA UA IB UB IC UC UN

-PMT1 /T01.2

C C
-PMT2 /T02.2

-PMT3 /T04.2

-PMT4 /T05.2

-PMT5 /T06.2

-PMT6 /T07.2

-PMT7 /T08.2
D D
-PMT8

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN MEASURING DEVICES REFERENCE PECC2/TT-110KV/MP2
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E00+MP2

A A
CURRENT TEST BLOCK

L1 L2 L3
-KTT-AW4
XTC1 XTC2 XTC3 XTC4 XTC5 XTC6 XTC7 XTC8

S1
1 2
S2

S1
3 4

EQUIPMENT
B B
S2

S1 /T01.6 /T02.6 /T04.6 /T05.6 /T06.6 /T07.6 /T08.6


5 6
S2

7 8

C C

VOLTAGE TEST BLOCK

L1 L2 L3
-KTT-VW4 XTV1 XTV2 XTV3 XTV4 XTV5 XTV6 XTV7 XTV8

1a
D 1 2 D
1n

1a
3 4

EQUIPMENT
1n
/T01.2 /T02.2 /T04.2 /T05.2 /T06.2 /T07.2 /T08.2
1a
5 6
1n

E E
7 8

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E00


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE =E01+/A00

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY WIRING DIAGRAMS FOR METERING PANEL DATE 24/11/2020
APPROVED NGUYEN DINH TUAN VOLTAGE/CURENT TEST BLOCKS REFERENCE PECC2/TT-110KV/MP2
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

B B

B 24/11/2020 2nd FOR APPROVED

A 12/10/2020 1st FOR APPROVED

REV. DATE DESCRIPTION

CUSTOMER

C C
POWER ENGINEERING CONSULTING J.S.C. 2

PROJECT

TAN THUAN OFFSHORE WIND POWER PLANT

D D

LOCATION

TAN THUAN OFFSHORE WIND POWER PLANT

DRAW. NAME STAMP

E =E01+CRP1: CONTROL&PROTECTION PANEL FOR TRANS. T1 E


=E01+MK: MARSHALLING KIOSK FOR TRANS. BA

DRAWING NO. PECC2/TT-110KV/E01-131

STANDARD: IEC PAGE: A00 TOTAL NO. OF PAGE: 89

DESIGNED NGUYEN VAN NHAT CONTRACTOR

CHECKED NGUYEN VAN CHUNG


F F
APPROVED NGUYEN DINH TUAN
ENERGY TECHNOLOGY
JOINT STOCK COMPANNY
DATE 24/11/2020 Rev.: B

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

PAGE DESCRIPTION REV. X PAGE DESCRIPTION REV. X

=E01/A00 WIRING DIAGRAMS FOR 110KV TRANSFORMER BAY B =E01/N05 SEND TRIP CIRCUIT B
A A
=E01/A01 TABLE OF CONTENTS : =E01/A00 - =E01/W01 B =E01/N06 BINNARY INPUT F67 B
=E01/A01.a TABLE OF CONTENTS : =E01/Z01 - =E01+MK/X113 B =E01/N07 INTERNAL PROTECTION TRANSFORMER TRIP B
=E01/A02 DEVICE SYMBOL B =E01/N08 INTERNAL PROTECTION TRANSFORMER TRIP B
=E01/A03 FUNCTION SYMBOL B =E01/N09 INTERNAL PROTECTION TRANSFORMER TRIP B
=E01/A04 SECONDARY CIRCUIT SYMBOL B =E01/N10 BINNARY INPUT F87T B
=E01/A05 LIST OF EQUIPMENTS: =E01+CRP1 C =E01/N11 SIGNAL SEND TO F87B B

B =E01/A06 LIST OF EQUIPMENTS: =E01+CRP1 C =E01/N12 BINNARY INPUT OF F87B B B


=E01/A07 LIST OF EQUIPMENTS: =E01+MK C =E01/N13 LOAD SHEDDING CIRCUIT B
=E01/B01 CONTROL, PROTECTION & MEASUREMENT PRINCIPLE DIAGRAM B =E01/P01 INTERLOCKING FOR CB, DS, ES B
=E01/B02 TRIPPING MATRIX B =E01/P02 INTERLOCKING FOR CB, DS, ES B
=E01/B03 LAYOUT DRAWING B =E01/Q01 INDICATOR CIRCUIT B
=E01/B04 LAYOUT DRAWING MARSHALLING KIOSK =E01+MK B =E01/Q02 TAP POSITION AND THERMAL WINDING INDICATOR CIRCUIT B
=E01/B05 OPERATION LOGIC DIAGRAM FOR DS E01-QL01 B =E01/R01 BINNARY INPUT BCU B
C =E01/B06 OPERATION LOGIC DIAGRAM FOR ES E01-QE15 B =E01/R02 BINNARY INPUT BCU B C

=E01/B07 CLOSING LOGIC DIAGRAM FOR CB E01-QF01 B =E01/R03 BINNARY INPUT BCU B
=E01/B08 OPENING LOGIC DIAGRAM FOR CB E01-QF01 B =E01/R04 BINNARY INPUT BCU B
=E01/D01 AC POWER SUPPLY FOR CONTROL PANEL B =E01/R05 BINNARY INPUT BCU B
=E01/D02 AC POWER SUPPLY FOR MARSHALLING KIOSK B =E01/R06 BINNARY INPUT BCU B
=E01/D03 AC POWER SUPPLY FOR CB, DS, ES B =E01/R07 BINNARY INPUT BCU B
=E01/G01 DC POWER SUPPLY FOR CONTROL PANEL B =E01/R08 BINNARY INPUT F90 B
D D
=E01/G02 DC POWER SUPPLY FOR CONTROL PANEL B =E01/R09 BINNARY INPUT F90 B
=E01/G03 DC POWER SUPPLY FOR CONTROL PANEL B =E01/R10 MULTIPLED SIGNAL CIRCUIT AND LAMP INDICATOR FOR FAN OPERATOR B
=E01/G04 DC POWER SUPPLY FOR HV EQUIPMENT B =E01/R11 SEND SIGNAL CIRCUIT B
=E01/M01 CONTROL CIRCUIT DS E01-QL01 B =E01/R12 MODBUS RS485 CIRCUIT B
=E01/M02 OLTC CONTROL CIRCUIT B =E01/S01 CURRENT CIRCUIT OF RELAY F87T B
=E01/M03 OLTC CONTROL CIRCUIT B =E01/S02 CURRENT CIRCUIT OF RELAY B

E =E01/M04 FAN CONTROL CIRCUIT B =E01/S03 CURRENT, VOLTAGE CIRCUIT OF RELAY F67 B E
=E01/M05 CLOSING CIRCUIT CB E01-QF01 B =E01/S04 CURRENT, VOLTAGE OF RELAY F90 B
=E01/N01 TRIPPING CIRCUIT 1 CB E01-QF01 B =E01/T01 CURRENT, VOLTAGE CIRCUIT FOR BCU B
=E01/N02 TRIPPING CIRCUIT 2 CB E01-QF01 B =E01/T02 CURRENT, VOLTAGE CIRCUIT FOR BCU B
=E01/N03 TRIP-LOCKOUT 1 CIRCUIT B =E01/T03 CURRENT CIRCUIT FOR METTERING PANEL B
=E01/N04 TRIP-LOCKOUT2 CIRCUIT B =E01/W01 SPARE CIRCUIT B
X: AUTOMATIC PAGE MODIFIED

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A01.a

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN TABLE OF CONTENTS : =E01/A00 - =E01/W01 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

PAGE DESCRIPTION REV. X PAGE DESCRIPTION REV. X

=E01/Z01 REFERENCE F87T P643 B =E01+CRP1/X110 Terminal diagram =E01+CRP1-X12 B


A A
=E01/Z02 REFERENCE F87T P643 B =E01+CRP1/X111 Terminal diagram =E01+CRP1-X20 B
=E01/Z03 REFERENCE F67 P143 B =E01+CRP1/X112 Terminal diagram =E01+CRP1-X21 B
=E01/Z04 REFERENCE F67 P143 B =E01+CRP1/X113 Terminal diagram =E01+CRP1-X22 B
=E01/Z05 REFERENCE BCU C264 B =E01+CRP1/X114 Terminal diagram =E01+CRP1-X42 B
=E01/Z06 REFERENCE BCU C264 B =E01+CRP1/X115 Terminal diagram =E01+CRP1-X43 B
=E01/Z07 REFERENCE BCU C264 B =E01+CRP1/X116 Terminal diagram =E01+CRP1-X44 B

B =E01/Z08 REFERENCE F90 (REG-DA) B =E01+CRP1/X117 Terminal diagram =E01+CRP1-X45 B B


=E01/Z09 REFERENCE CONTROL DEVICES B =E01+CRP1/X118 Terminal diagram =E01+CRP1-X51 B
=E01/Z10 REFERENCE CONTROL DEVICES B =E01+CRP1/X119 Terminal diagram =E01+CRP1-X52 B
=E01/Z11 REFERENCE INDICATOR METTER B =E01+CRP1/X120 Terminal diagram =E01+CRP1-X53 B
=E01/Z12 REFERENCE CURRENT AND VOLTAGE TESTBLOCK B =E01+CRP1/X121 Terminal diagram =E01+CRP1-X54 B
=E01/Z13 REFERENCE RELAY F74 B =E01+CRP1/X122 Terminal diagram =E01+CRP1-X91 B
=E01/Z14 REFERENCE RELAY TESTBLOCK B =E01+CRP1/X123 Terminal diagram =E01+CRP1-X410 B
C =E01/Z15 CB REFERENCE (GL312F1/GE) B =E01+CRP1/X124 Terminal diagram =E01+CRP1-X411 B C

=E01/Z16 CB REFERENCE (GL312F1/GE) B =E01+CRP1/X125 Terminal diagram =E01+CRP1-X412 B


=E01/Z17 CB REFERENCE (GL312F1/GE) B =E01+CRP1/X126 Terminal diagram =E01+CRP1-X413 B
=E01/Z18 CB REFERENCE (GL312F1/GE) B =E01+MK/X100 Terminal diagram =E01+MK-XAC B
=E01/Z19 DS REFERENCE B =E01+MK/X101 Terminal diagram =E01+MK-XAC1 B
=E01/Z20 DS REFERENCE B =E01+MK/X102 Terminal diagram =E01+MK-XDC B
=E01/Z21 DS REFERENCE B =E01+MK/X103 Terminal diagram =E01+MK-XDC1 B
D D
=E01/Z22 ES REFERENCE B =E01+MK/X104 Terminal diagram =E01+MK-XDC2 B
=E01/Z23 ES REFERENCE B =E01+MK/X105 Terminal diagram =E01+MK-X3 B
=E01+CRP1/X100 Terminal diagram =E01+CRP1-XAC B =E01+MK/X106 Terminal diagram =E01+MK-X7 B
=E01+CRP1/X101 Terminal diagram =E01+CRP1-XDC1 B =E01+MK/X107 Terminal diagram =E01+MK-X8 B
=E01+CRP1/X102 Terminal diagram =E01+CRP1-XDC2 B =E01+MK/X108 Terminal diagram =E01+MK-X10 B
=E01+CRP1/X103 Terminal diagram =E01+CRP1-XDC3 B =E01+MK/X109 Terminal diagram =E01+MK-X11 B

E =E01+CRP1/X104 Terminal diagram =E01+CRP1-X3 B =E01+MK/X110 Terminal diagram =E01+MK-X20 B E


=E01+CRP1/X105 Terminal diagram =E01+CRP1-X7 B =E01+MK/X111 Terminal diagram =E01+MK-X41 B
=E01+CRP1/X106 Terminal diagram =E01+CRP1-X8 B =E01+MK/X112 Terminal diagram =E01+MK-X42 B
=E01+CRP1/X107 Terminal diagram =E01+CRP1-X9 B =E01+MK/X113 Terminal diagram =E01+MK-X45 B
=E01+CRP1/X108 Terminal diagram =E01+CRP1-X10 B
=E01+CRP1/X109 Terminal diagram =E01+CRP1-X11 B
X: AUTOMATIC PAGE MODIFIED

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A01.a F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN TABLE OF CONTENTS : =E01/Z01 - =E01+MK/X113 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION


A A
M
THREE WINDING TRANSFORMER 3 UNIT POTENTIAL TRANSFORMER A AMMETER MCCB CÓ ĐỘNG CƠ ĐIỀU KHIỂN

TWO WINDING TRANSFORMER 2 UNIT POTENTIAL TRANSFORMER V VOLTMETER MCCB, MCB

AUTO TRANSFORMER SURGE ARRESTOR W WATTMETER RESISTOR


B B

CURRENT TRANSFORMER WYE VAR VAR METER FUSE

REACTOR DELTA ‎cosφ POWER FACTOR METER BATTERY

CAPACITOR OPEN DELTA Hz FREQUENCY METER INVERTER


C C

REACTOR EARTHING Wh WATTHOUR METER DIODE

HIGH VOLTAGE CIRCUIT BREAKER INTERLOCKING VARh VAr METER

MEDIUM CIRCUIT BREAKER LATCHING DEVICE AMPE SWITCH


D D

DAO CẮM HỢP BỘ TRUNG ÁP M CONTROL MOTOR VOLT SWITCH

DISCONECTOR CONTROL KEY RELAY TEST BLOCK

E
EARTH SWITCH ~ ALTERNATIVE CURRENT VOLTAGE/CURRENT TEST BLOCK
E

LOAD DISCONECTOR DIRECT CURENT LAMP

CONTACTOR

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN DEVICE SYMBOL PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

KÝ HIỆU MÔ TẢ KÝ HIỆU MÔ TẢ

21/21N DISTANCE PROTECTION 86 TRIP-LOCKOUT RELAY


A A
25 SYNCHROCHECK 87B BUSBAR DIFFERENTIAL PROTECTION

26 THERMAL PROTECTION 87L LINE DIFFERENTIAL PROTECTION

27 UNDERVOLTAGE PROTECTION 87N RESTRICTED GROUND FAULT PROTECTION

33 POSITION BLOCK RELAY 87S STUB DIFFERENTIAL PROTECTION

49 THERMAL OVERLOAD PROTECTION 87T TRANSFORMER DIFFERENTIAL PROTECTION

50 INSTANTANEOUS OVERCURRENT PROTECTION 90 AUTOMATIC CONTROL VOLTAGE RELAY


B B
50BF CIRCUIT-BREAKER FAILURE PROTECTION 94 TRIPPING RELAY

50G INSTANTANEOUS GROUND OVERCURRENT PROTECTION 96 GAS RELAY

50N INSTANTANEOUS NEUTRAL OVERCURRENT PROTECTION FR FAULT RECORDER

51 TIME OVERCURRENT PROTECTION FL FAULT LOCATOR

51G TIME GROUND OVERCURRENT PROTECTION SOTF SWITCH ON TO FAULT

51N TIME NEUTRAL OVERCURRENT PROTECTION BCU BAY CONTROL UNIT


C C
5IUb UNBALANCE OVERCURRENT PROTECTION A CURRENT MEASUREMENT FUNCTION

51/27 VOLTAGE CONTROLLED OVERCURRENT V VOLTAGE MEASUREMENT FUNCTION

59 OVERVOLTAGE PROTECTION f FREQUENCY MEASUREMENT FUNCTION

59N ZEZO-SEQUENCE OVERVOLTAGE PROTECTION ‎cosφ POWER FACTOR MEASUREMENT FUNCTION

63 PRESSURE RELAY W EFFECTIVE POWER MEASUREMENT FUNCTION

D 64 GROUND DETECTOR RELAY VAR REACTIVE POWER MEASUREMENT FUNCTION D

67 DIRECTIONAL OVERCURRENT RELAY Wh ACTIVE ENERGY MEASUREMENT FUNCTION

67N DIRECTIONAL OVERCURRENT PROTECTION FOR GROUND FAULTS VARh REACTIVE ENERGY MEASUREMENT FUNCTION

67NS DIRECTIONAL SENSITIVE GROUND-FAULT DETECTION

68 POWER-SWING BLOCKING

71 LEVEL OIL RELAY


E E
74 TRIP CIRCUIT SUPERVISION

79 AUTO RECLOSING

81 FREQUENCY PROTECTION

85 COMBINATION OF PROTECTION

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN FUNCTION SYMBOL PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

KÝ HIỆU MÔ TẢ KÝ HIỆU MÔ TẢ KÝ HIỆU MÔ TẢ KÝ HIỆU MÔ TẢ


A A

NORMALY OPEN CONTACT (NO) RELAY TEST BLOCK CONTACT LAMP EARTHING BAR

NORMALY CLOSE CONTACT (NC) CURRENT/VOLTAGE TEST BLOCK CONTACT LIGHTS BELL

CHANGE OVER CONTACT (CO) SOLENOID / COIL SOCKET HOOTER


B B

CONTACTOR NORMALY OPEN CONTACT ON DELAY COIL SURGE ARRESTOR MEARSUREMENT DEVICE

CONTACTOR NORMALY CLOSE CONTACT LATCHED COIL FUSE V VOLMETTER

NORMALLY OPEN ON BUTTON BINARY INPUT RELAY HEATER A AMMETTER


C C

NORMALLY CLOSED OFF BUTTON ANALOG INPUT RELAY RESISTOR

PUSH BUTTON (DETENT) POWER SUPPLY DIODE

SELECTOR SWITCH CONTACT CONVERTER CAPACITOR


D D

~
LIMIT SWITCH CONTACT RECTIFIER REACTOR/CURRENT-VOLTAGE INPUT RELAY

TEMPERATURE CONTROLER CONTACT INVERTER TERMINAL


~

MAKE CONTACT DELAYED WHEN


COUNTER DRAWOUT TERMINAL
E CLOSING E

MAKE CONTACT DELAYED WHEN


MCCB/MCB DIODE TERMINAL
OPENING I>

FUSE TERMINAL

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A05

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN SECONDARY CIRCUIT SYMBOL PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

NO. SYMBOL DESCRIPTION MANUFACTORY CODE QTY. UNIT NOTE CUBICLE

1 F87T TRANSFORMER DIFFERENTIAL PROTECTION RELAY SCHNEIDER P64331QA6M0B68M 01 Pcs 16BI + 16BO + 2LC IEC61850 =E01+CRP1
A A
2 F67 DIRECTIONAL OVER CURRENT RELAY SCHNEIDER P14331QA7M0B58L 01 Pcs 16BI + 14BO + 2LC IEC61850 =E01+CRP1

3 BCU BAY CONTROL UNIT SCHNEIDER C264U11M6A10013302100031111D10 01 Pcs 58BI + 26BO + 2ST IEC61850 =E01+CRP1

REG-DA B0 I0 H0 F1 M1 S0 T0 K1
4 F90 AUTO VOLTAGE REGULATOR RELAY A-EBERLE 01 Pcs 16BI+12BO+1AI+1xRS232+ 1xLC IEC61850 =E01+CRP1
E00 D0 C00 XW93.1 G2 A2

5 PMF MULTIFUNCTION METTER CEWE ELITE 448 01 Pcs =E01+CRP1

6 XF... RELAY TESTBLOCK FUJI TSB-14-11111111111111-V 03 Pcs =E01+CRP1

7 F86... TRIP AND LOCKOUT RELAY ARTECHE BJ-8RP 02 Pcs 8CO =E01+CRP1
B B
8 F74... TRIPPING SUPERVISORY RELAY ARTECHE VDF-10 02 Pcs 2CO =E01+CRP1

9 XTC... CURRENT TESTBLOCK FUJI KTT-AW4 B M 03 Pcs =E01+CRP1

10 XTV... VOLTAGE TESTBLOCK FUJI KTT-VW4 B M 04 Pcs =E01+CRP1

11 SQF01 CONTROL AND DISCREPANCY SWITCH FOR CB FUJI BHL-3B3111-220L1-W-Y-B-L54-Y07E 01 Pcs =E01+CRP1

12 SQL01 CONTROL AND DISCREPANCY SWITCH FOR DS FUJI BHL-3B3111-220L1-W-Y-B-L54-Z07E 01 Pcs =E01+CRP1

13 SQE... SEMAPHORE FOR ES FUJI SPSR-30S-DC220-BB 01 Pcs =E01+CRP1


C C
14 S.B/M "BCU/MIMIC" SELECTOR SWITCH SALZER SA25-FA 6015-61009-M1-I-F-3-BS-0 01 Pcs =E01+CRP1

15 S.25 "SYN./BYPASS" SELECTOR SWITCH SALZER SA25-FA 6037-61638-M1-I-F-3-BS-0 01 Pcs =E01+CRP1

16 S.L/R "LOCAL/REMOTE" SELECTOR SWITCH FOR FAN AND OLTC SALZER SA25-FA 6037-61638-M1-I-F-3-BS-0 01 Pcs =E01+CRP1

17 S.M/S/I "MASTER/SLAVE/INDEPENTDENT" SELECTOR SWITCH SALZER SA25-FA 6027-61669-M1-I-F-3-BS-0 01 Pcs =E01+CRP1

18 S.AM1, S.AM2 "AUTO/MAN" SELECTOR SWITCH SALZER SA25-FA 6037-61638-M1-I-F-3-BS-0 02 Pcs =E01+CRP1

D 19 S.CF1/S.CF2 "ON/OFF" SELECTOR SWITCH SALZER SA25-FA 6037-61638-M1-I-F-3-BS-0 02 Pcs =E01+CRP1 D

20 S.RL "RAISER/OFF/LOWER" SELECTOR SWITCH SALZER SA25-FA 3000-61762-M1-I-F-3-BS-0 01 Pcs =E01+CRP1

21 PW 220VAC/VDC - 24VDC CONVERTER OMRON S8JC-Z05024C 01 Pcs =E01+CRP1

PTO, PTP
22 TRANSFORMER INDICATOR METTER AUTONICS MT4W-DA-18 04 Pcs =E01+CRP1
PTW1, PTW2

23 KT... TRIPPING AUXILARY RELAY FINDER 55.34 01 Lot =E01+CRP1

24 K.... AUXILARY RELAY IDEC RU4S 01 Lot =E01+CRP1

E 25 FQAC MCB AC FOR LIGHTING AND HEATING LEGRAND DX3 01 Pcs 2P-16A-6kA =E01+CRP1
E

26 FQ... MCB DC LEGRAND DX3 DC 01 Lot 2P-10A-16kA =E01+CRP1

27 KQP CONTACTOR ABB ESB25 01 Pcs =E01+CRP1

28 XAC, XDC POWER TERMINALS DEGSON PC6 01 Lot =E01+CRP1

29 X4... CURRENT TERMINALS DEGSON PCTK 01 Lot =E01+CRP1

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A05 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A06

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LIST OF EQUIPMENTS: =E01+CRP1 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

NO. SYMBOL DESCRIPTION MANUFACTORY CODE QTY. UNIT NOTE CUBICLE

30 X... SIGNAL TERMINALS DEGSON PC4 01 Lot =E01+CRP1


A A
31 B0 THERMOSTAT CYMAX =E01+CRP1

32 B1 DOOR LIMIT SWITCH CHINA =E01+CRP1

33 E0 HEATING RESISTER CYMAX =E01+CRP1

34 E1 LIGHTING LAMP CHINA =E01+CRP1

35

36
B B
37

38

39

40

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A06 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A07

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LIST OF EQUIPMENTS: =E01+CRP1 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

NO. SYMBOL DESCRIPTION MANUFACTORY CODE QTY. UNIT NOTE CUBICLE

1 FQAC, FQAC1 MCB AC LEGRAND DX3 02 Pcs 2P-16A-6kA =E01+MK


A A
2 FQCB, FQDS MCB DC LEGRAND DX3 DC 02 Pcs 2P-16A-16kA =E01+MK

3 KQP CONTACTOR ABB ESB25 01 Pcs =E01+MK

4 XAC, XDC POWER TERMINALS DEGSON PC6 01 Lot =E01+MK

5 X4... CURRENT TERMINALS DEGSON PCTK 01 Lot =E01+MK

6 X5... VOLTAGE TERMINALS DEGSON PC6 01 Lot =E01+MK

7 X... SIGNAL TERMINALS DEGSON PC4 01 Lot =E01+MK


B B
8 B0 THERMOSTAT CYMAX =E01+MK

9 B1 DOOR LIMIT SWITCH CHINA =E01+MK

10 E0 HEATING RESISTER CYMAX =E01+MK

11 E1 LIGHTING LAMP CHINA =E01+MK

12

13
C C
14

15

16

17

18

D 19 D

20

21

22

23

24

E 25
E

26

27

28

29

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A07 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LIST OF EQUIPMENTS: =E01+MK PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

P2 E01+CRP1
CL: 5P20
CT TO F87B
CL: 0.5
200-400-600
TO METTERING PANEL
/1/1/1/1/1A CL: 0.2
TO METTERING PANEL XTC1 XTV1
CL: 5P20
TO FR
CL: 5P20 PMF (ELITE 448)
P1
U, I, P, Q, f, pF, ...
E01 QF01
B XTV3 B
110 0.11 0.11
kV QE15 XTC3 BCU
3 3 3 M QL01 XTV4
C11 BCU (C264)

XTC2 XTV2
96B 96P P2 CL: 0.5
CL: 0.5
26W 26Q HVCT
CL: 5P20
F90 (C264) 90 FR
CL: 3P 200-400-600
/1/1/1A
CL: 5P20
63 71Q
C CT P1 C
200-400-600

P2
/1/1A
P1
T1
P2 P1
XF67
CT F67 (P143)
1600-2000
XF67
/1/1A P1
CL: 0.5 67/67N 27/59 74 SOTF
HVCT CL: 5P20
1600-2000 TO F67 22KV INCOMING 50/51N 50/51 FR 25 XF67
/1/1/1A
CL: 5P20

P2

XF87T

D D
F87T (P643)
CL: 5P20 CL: 5P20

87T 64 49 50/51
CL: 5P20 CL: 5P20
FR

FROM TU C41
-38
P1
CL: 0.5
CL: 5P20
VOLTAGE CIRCUIT TO METTERING PANEL
1500/2500 CL: 5P20 BJ-8RP VDF-10
CURRENT CIRCUIT
E /1/1/1A E
P2 F86-1, F86-2 F74-1, F74-2

J13 QF01

C41
22 0.11 0.11
kV
3 3 3
CL: 0.5

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE
CONTROL, PROTECTION & MEASUREMENT PRINCIPLE
24/11/2020
APPROVED NGUYEN DINH TUAN PECC2/TT-110KV/E01-131
DIAGRAM
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

CIRCUIT BREAKER =E01+CRP1 +J01 =E05+CRP5 =E03+CRP3 TC-C41


EQUIPMENT
E01-QF01 J01-QF01 -F87T -F861 -F862 -F67 -F87B -F861 -F862 -F861 -F862
PANEL

BLOCK BLOCK SET SET START EXT. START SET SET SET SET
SYMBOL TYPE FUNCTION TC1 TC2 CC TC 94 50BF
CC CC 86 86 50BF TRIP 50BF 86 86 86 86

-F87T P643 87T, 87N, 94,50,51 X X X X X X X X


B B
67/67N, 50/51,
-F67 P143 50/51N, SOTF
X X X X X X X X

=E01
+CRP1 -F741 VDF-10 74 TCS X

-F742 VDF-10 74 TCS X

-F861 BJ-8RP 86 X X X X

-F862 BJ-8RP 86 X X X X

C 50BF BAY E01 (STAGE 1) X X X X X* C

50BF BAY E01 (STAGE 2) X X X X X X

50BF BAY E03 (STAGE 2) X X X X


=E05
-F87B P746
+CRP5
50BF BAY E05 (STAGE 2) X X X X

87B X X X* X X X X

-F27 P141 59, 81 X X


D D
67/67N, 50/51, 50/51 X X*

50BF X X
+J01 -F67
74 TCS X

86 X X

INTERNAL PROTECTION
=T1+LCB
TRANS. T1
X X X X
E E
50BF TC-C41 X X

NOTE:
X*: AUTO START
TCS: TRIP COIL SUPERVISOR

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN TRIPPING MATRIX PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

FRONT VIEW SIDE VIEW REAR VIEW


A A
ENTEC =E01+CRP1
EQUIPMENT
T1 TRANSFORMER BAY

F87T TAG NAME DESCRIPTION


MiCOM P 143

=E01+WR
ALARM ALARM

ALARM ALARM

ALARM

ALARM

c LEAR
READ
c
ALARM

ALARM

ALARM
BCU BAY CONTROL UNIT
ALARM
ENTER
ALARM

ALARM
ALSTOM

F67 DIRECTIONAL OVERCURRENT PROTECTION RELAY


F67
MiCOM

ALARM
P 143

ALARM
F87T TRANSFORMER DIFFERENTIAL PROTECTION RELAY
ALARM ALARM

ALARM ALARM

c ALARM

TRANSFORMER VOLTAGE REGULATOR


ALARM

c LEAR
READ
ENTER
ALARM

ALARM

ALARM

ALARM
F90
ALSTOM

F741, F742 TRIPPING CIRCUIR SUPERVISION RELAY


BCU
MiCOM P 143

ALARM

ALARM
ALARM

ALARM
F861, F862 RƠLE TRIP-LOCKOUT
ALARM ALARM

ALARM
c ALARM

c LEAR ALARM

PMF MULTIFUNCTION METER


READ
ALARM
ENTER
ALARM

ALARM
ALSTOM

B PTW1, PTW2, PTO, PTP INDICATOR WINDING TEMPERATURE, OIL TEMPERATURE AND TAP POSITION B
S.AM1 S.M/S/I S.R/O/L S.L/R S.ES
SQF01 DISCREPANCY CONTROL SWITCH FOR CB
S.AM2 S.FC1 S.FC2 PLF1 PLF2
SQL01; SQE15 DISCREPANCY CONTROL SWITCH FOR DS; ES
PTP PTO PTW1 PTW2 S.B/M
HI

GO

LO
DIGITAL MULTI METER
HI

GO

LO
DIGITAL MULTI METER
HI

GO

LO
DIGITAL MULTI METER
HI

GO

LO
DIGITAL MULTI METER "MIMIC/BCU" SELECTOR SWITCH
MD MD MD MD
2200

MT4W Autonics MT4W Autonics MT4W Autonics MT4W Autonics

S.25 " SYN./BYPASS" SELECTOR SWITCH

PMF S.R/L "LOCAL/REMOTE" SELECTOR SWITCH


S.RE S.LT
-SQL01
S.B/M S.QE15 S.AM1; S.AM2 "AUTO/MANUAL" SELECTOR SWITCH
I U P Q

S.25
P.LC -SQF01 S.R/O/L "RAISE/OFF/LOWER" SELECTOR SWITCH
S.81
T1
S.M/S/I "MASTER/SLAVE/INDEP." SELECTOR SWITCH
S.CF1;S.CF2 "ON/OFF" SELECTOR SWITCH FOR CONTROL FAN
F90
S.RE RESET 86 PUSH BUTTON
C 22KV
C
S.LT LAMP TEST PUSH BUTTON
F861 F862 F741 F742
S.ES EMERGENCY STOP PUSH BUTTON
P.F1; P.F2; P.LC LAMP INDICATOR FOR: FAN1; FAN2; CB CONTROL AT LOCAL
XF87T.1
XF87T.2

XTC.MF XTV.MF XTV.90


XF... RELAY TESTBLOCK
XF67

XTC.BC XTC.90 XTV1.BC XTV2.BC


XC.., XV.. CURRENT TESTBLOCK, VOLTAGE TESTBLOCK

100 800 750 800


800
D D
TOP VIEW BOTTOM VIEW BASE NAME PLATE (SCALE 1:5)
4x∅14
100
C =E01+CRP1

45
750
800
200
800

800
750

C (Scale 1:5) REMARK:


E IP DEGREE: IP41 E
Ø14 APPLICATION STANDARD: IEC60529
25 MATERIAL: STEEL
STEEL THICKNESS: 2mm
4x∅8 PAINT COLOR: RAL7032
800 550 DOOR APPLY AREA: REAR
OPEN DOOR: 180°

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LAYOUT DRAWING PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

864 570 REMOVE FRONT DOOR REMOVE BACK DOOR


A 1500 A

B B

C C
450 800
800
506

A-A
TOP VIEW

D D
450
75 300
470

4x∅14

25 750
760 800
E LEGEND: E
- PROTECTION CLASS: IP55
- STANDARD: IEC60529
- THICKNESS: 2mm
-MATERIAL:SUS 302
- OPEN FROM FRONT DOOR
- ALL DIMENSIONS ARE IN MILLIMETER

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B05

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LAYOUT DRAWING MARSHALLING KIOSK =E01+MK PECC2/TT-110KV/E01-131

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SCADA LEVEL PANEL LEVEL EQUIPMENT LEVEL


A A
OPEN/CLOSE COMMAND DS E03-QL01 FROM SCADA

BCU "LOCAL/REMOTE" ON "LOCAL"

&
OPEN/CLOSE COMMAND DS E01-QL01 FROM BCU
&
HMI "LOCAL/REMOTE" ON "REMOTE"
≥1
≥1 &
HMI "LOCAL/REMOTE" ON "LOCAL"
&
B BCU "LOCAL/REMOTE" ON "REMOTE" B
&
OPEN/CLOSE COMMAND DS E01-QL01 FROM HMI
SOFT INTERLOCKING *
HMI LEVEL
BCU
DS "REM./LOC./MAN." SWITCH ON "REMOTE"

MIMIC

C C
&
MIMIC "BCU/MIMIC" SWITCH ON "BCU"
E01 QF01

QE15
M QL01 MIMIC "BCU/MIMIC" SWITCH ON "MIMIC" &
C11
& ≥1
OPEN/CLOSE COMMAND DS E01-QL01 FROM CONTROL SWITCH
&
D D
OPEN/CLOSE
T1 ≥1 DS E01-QL01
CB E01-QF01 OPEN

ES E01-QE15 FULLY OPEN

ES J01-QE38 FULLY OPEN


&
* SOFT INTERLOCKING
CB E01-QF01 OPEN ES E03-QE14 FULLY OPEN

E E
-38 ES E01-QE15 FULLY OPEN
&
J01 OPEN/CLOSE COMMAND AT LOCAL
ES J01-QE38 FULLY OPEN &
DS "REM./LOC./MAN." SWITCH ON "LOCAL" &
QF01 ES E05-QE14 FULLY OPEN OPEN/CLOSE BY HANDLE ≥1
C41
DS "REM./LOC./MAN." SWITCH ON "MAN" &

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B05 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B06

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN OPERATION LOGIC DIAGRAM FOR DS E01-QL01 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

EQUIPMENT LEVEL
A A

B B

DS E01-QL01 FULLY OPEN


C C
OPEN/CLOSE

CB J01-QF01 AT TEST POSITION


& ES E01-QE15
E01 QF01

QE15
M QL01
C11

D D
T2

E E
-38

J01

QF01

C41

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B06 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B07

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN OPERATION LOGIC DIAGRAM FOR ES E01-QE15 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SCADA LEVEL PANEL LEVEL EQUIPMENT LEVEL


A A
CLOSE COMMAND CB E03-QF01 FROM SCADA
SF6 LOCKOUT
BCU "LOCAL/REMOTE" ON "LOCAL"

& SPRING CHARGED


CLOSE COMMAND CB E03-QF01 FORM BCU
&
HMI "LOCAL/REMOTE" ON "REMOTE"
≥1 INTERLOCKING INSIDE CB IS OK

≥1 &
HMI "LOCAL/REMOTE" ON "LOCAL"
& CB "LOCAL/REMOTE" SWITCH ON "LOCAL"
B BCU "LOCAL/REMOTE" ON "REMOTE" B
&
CLOSE COMMAND CB E03-QF01 FROM HMI CLOSE COMMAND FROM EQUIP.
SOFT INTERLOCKING
DS E01-QL01 FULLY OPEN
&
HMI LEVEL
BCU
CB J01-QF01 AT TEST POSITTION
MIMIC
BCU "BCU/MIMIC" ON "BCU"

SYNCHRO IS OK &
C "SYN./BYPASS" SELECT SWITCH ON "SYN." & C
≥1 &
"SYN./BYPASS" SELECT SWITCH ON "BYPASS"
E03 QF01 CLOSE
& CB E03-QF01
QE15 CB "LOCAL/REMOTE" SWITCH ON "REMOTE"
M QL01 TRIPPING CIRCUIT IS NOT OK
C11
RELAY LOCKOUT OPERATED &
≥1
BCU/MIMIC ON "MIMIC"
D D
T2
CLOSE COMMAND CB E03-QF01 FROM CONTROL SWITCH

&
SYNCHRO IS OK &
"SYN./BYPASS" SELECT SWITCH ON "SYN." &
≥1
"SYN./BYPASS" SELECT SWITCH ON "BYPASS" DS E01-QL01 CLOSE

E CB J01-QF01 AT SERVICE POSITTION E


-38
SOFT INTERLOCKING
J01

DS E01-QL01 CLOSE

QF01 &
CB J01-QF01 AT SERVICE POSITTION
C41

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B07 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B08

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CLOSING LOGIC DIAGRAM FOR CB E01-QF01 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

PANEL LEVEL EQUIPMENT LEVEL


A
SCADA LEVEL A

OPEN COMMAND CB FROM SCADA

& &
HMI "LOCAL/REMOTE" ON "REMOTE" BCU "LOCAL/REMOTE" ON "REMOTE" SF6 LOCKOUT

≥1
HMI LEVEL ≥1
B OPEN COMMAND FROM BCU B
OPEN COMMAND CB FROM HMI CB "LOCAL/REMOTE" SWITCH ON "LOCAL"
&
& BCU "LOCAL/REMOTE" ON "LOCAL" &
HMI "LOCAL/REMOTE" ON "LOCAL" OPENING COMMAND FROM EQUIP.

BCU

C OPEN CB QF01 C
& & TRIP CIRCUIT 1
BCU/MIMIC SWITCH ON "BCU" CB "LOCAL/REMOTE" SWITCH ON "REMOTE"
E03 QF01

QE15
& ≥1
M QL01 ≥1
C11

BCU/MIMIC SWITCH ON "MIMIC"

&
OPENING COMMAND FROM CONTROL SWITCH
D D
T2

PROTECTION RELAY OPERATED

RELAY F861 OPERATED

RELAY F862 OPERATED

E E
-38 PROTECTION RELAY OPERATED
≥1
J01 RELAY F861 OPERATED OPEN CB QF01
& TRIP CIRCUIT 2
RELAY F862 OPERATED
SF6 LOCKOUT
QF01

C41
MIMIC
POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01
DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B08 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE D01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN OPENING LOGIC DIAGRAM FOR CB E01-QF01 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E00+FR +CRP1 =E02+CRP2

POWER SUPPLY
A FOR HEATING AND LIGHTING A

-W095
ACL1 1 -XAC 1 -XAC 2 ACL1
=E00+FR/D01.7/ / =E02/D01.1

ACL2 2 -XAC 3 -XAC 4 ACL2


=E00+FR/D01.7/ / =E02/D01.1

ACL3 3 -XAC 5 -XAC 6 ACL3


=E00+FR/D01.7/ / =E02/D01.1

ACN 4 -XAC 7 -XAC 8 ACN


=E00+FR/D01.7/ / =E02/D01.1

B B
1 3 12 14 96 98

-FQAC 11 95
2P-16A I> I>

/R07.3

/R07.4
2 4

LIGHTING HEATING SOCKET


C C

1 1
-B1 -B0
6A 2 0÷90°C 2

D D

1 1
1 1

-E0 -E1 -E2 -XSK


8W 60W 2 60W 2 16A
2 2
E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE D01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE D02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN AC POWER SUPPLY FOR CONTROL PANEL PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=N00+AC +MK =E03+MK

POWER SUPPLY AC POWER SUPPLY


HEATING & LIGHTING HV EQUIPMENT
A -W121 A
L1 1 -XAC 1 -XAC 2 L1
=N00+AC/D06.7/ / =E03/D02.1

L2 2 -XAC 3 -XAC 4 L2
=N00+AC/D06.7/ / =E03/D02.1

L3 3 -XAC 5 -XAC 6 L3
=N00+AC/D06.7/ / =E03/D02.1

N 4 -XAC 7 -XAC 8 N
=N00+AC/D06.7/ / =E03/D02.1

B B

1 3 12 14 96 98 1 3 12 14 96 98

-FQAC1 11 95 -FQAC2 11 95
2P-16A I> I> 2P-16A I> I>

/R03.2

/R03.4

/R03.2

/R03.4
2 4 2 4
C C

.AC.L
/ D03.3

.AC.N
/ D03.3

LAMP HEAT SOCKET

D D

1
1 1 -B0
-B1 -B2 0÷90°C 2
6A 2 6A 2 1

-XSK
16A

1 1 2
E 1 1 E
-E1 -E2 -E0 -E3
8W 8W 60W 2 60W 2
2 2

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE D02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE D03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN AC POWER SUPPLY FOR MARSHALLING KIOSK PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+MK

A A

AC POWER SUPPLY AC POWER SUPPLY AC POWER SUPPLY


CB E01-QF01 DS E01-QL01 ES E01-QE15

.AC.L
D02.5

220 VAC
B .AC.N B
D02.5

-XAC1 1 3 2 4

-W123 1 2 -W124 1 2

-W122 1 2

+QF01 +QL01 +QE15


C C

TB1 1 2 -X1 20 21 -XT2 20 21


1

3
F1 F1 F1
2

4
D D

IL H IL H IL H
/Z16.6 /Z19.7 /Z22.6

E LAMP HEAT LAMP HEAT LAMP HEAT


E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE D03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE G01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN AC POWER SUPPLY FOR CB, DS, ES PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E00+FR +CRP1 =E02+CRP2

DC2 POWER SUPPLY


A -W096
POWER SUPPLY BCU A
DC1+ 1 -XDC1 1 -XDC1 2 DC1+
=E00+FR/G01.7 / =E02/G01.1

DC1- 2 -XDC1 3 -XDC1 4 DC1-


=E00+FR/G01.7 / =E02/G01.1

-W097
DC2+ 1 -XDC2 1 -XDC2 2 DC2+
=E00+FR/G01.7 / =E02/G01.1

DC2- 2 -XDC2 3 -XDC2 4 DC2-


=E00+FR/G01.7 / =E02/G01.1

B B

1 3 1 3
12 14 96 98 12 14 96 98

-FQDC2 11 95 -FQDC1 11 95
2P-10A I> I> 2P-10A I> I>

/R07.8

/R07.8

/R07.7

/R07.8
2 4 2 4

1 2 /G01.5
1 7 8 /G01.5
C C
-KQP1 R3 R4 /G01.4
220VDC R5 R6 /G01.4
2

R3 R5 1 7
-KQP1
/G01.6 R4 R6 2 8

DC-
D / G02.1 D
DC+
/ G02.1

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE G01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE G02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN DC POWER SUPPLY FOR CONTROL PANEL PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1
POWER SUPPLY POWER SUPPLY POWER SUPPLY POWER SUPPLY POWER SUPPLY
RELAY F87T BCU INDICATOR METTER INDICATOR FOR METTERING

A A

DC+ DC+
G01.6 /G03.1

DC- DC-
G01.6 /G03.1

-XDC3 1 11 2 12 3 13 4 14 5 15

B 1 3
12 14 96 98
1 3
12 14 96 98
1 3
12 14 96 98
1 3
12 14 96 98
1 3
12 14 96 98 B

-FQ87T 11 95 -FQBCU 11 95 -FQPM 11 95 -FQSI 11 95 -FQMF 11 95


2P-10A I> I> 2P-10A I> I> 2P-10A I> I> 2P-10A I> I> 2P-10A I> I>
/R07.5

/R07.5

/N06.3

/N06.3

/R07.6

/R07.5

/R07.3

/R07.6

/R07.7

/R07.7
2 4 2 4 2 4 2 4 2 4

C C
P N
1 2
-PW
AC AC PMF
3 SI+ /Z12.6
GND /Q01.1 -PS
SI-
4 5 /Q01.1 ELITE 448

-PE -X7 1 4

-PE
D 87T+ BCU+ D
/ N07.2 /R01.1

87T- BCU-
/ N07.2 /R01.1

X12 1 5 X8 1 7

2 1 23 24 8 9 8 9 8 9 8 9
F87T J BCU A -PTP -PTO -PTW1 -PTW2
/Z01.3 /Z05.2 /Z11.3 /Z11.5 /Z11.3 /Z11.5
-PS -PS
E GND GND GND GND E
P643 C264
MT4W MT4W MT4W MT4W

-PE

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE G02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE G03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN DC POWER SUPPLY FOR CONTROL PANEL PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

A A
POWER SUPPLY POWER SUPPLY POWER SUPPLY POWER SUPPLY POWER SUPPLY
RELAY F67 RELAY F90 TC2 TC1 CLOSING CIRCUIT

G02.8
DC+

G02.8
DC-

-XDC3 6 16 7 17 8 18 9 19 10 20

B B

1 3 1 3 1 3 1 3 1 3
12 14 96 98 12 14 96 98 12 14 96 98 12 14 96 98 12 14 96 98

-FQ67 11 95 -FQ90 11 95 -FQTC2 11 95 -FQTC1 11 95 -FQCB 11 95


2P-10A I> I> 2P-10A I> I> 2P-10A I> I> 2P-10A I> I> 2P-10A I> I>
/R07.5

/R07.5

/R07.6

/R07.4

/R07.4

/R07.7

/R07.4

/R07.6

/R07.6

/R07.7
2 4 2 4 2 4 2 4 2 4

C C
F67+ F90+ TC2+ TC1+ C+
/ N06.1 /M02.2 /N02.1 /N01.1 /M05.1

F67- F90- TC2- TC1- C-


/ N06.1 /M02.1 /N02.6 /N01.7 /M05.5

X21 1 5 X22 1 6 -X20 1 6 -X10 1 4 X11 1 3

-W117 8 9 -W115 5 6 11 12

D D
+MK
-X20 4 5 -X10 5 6 X11 1 2

-W140 18 19 -W142 10 11 12 14

+QF01 -TB1 9 10 -TB1 7 8 -TB1 5 6


J2 J1 21 22
F67 J F90
/Z03.3 /Z08
-PS -PS MCB5 MCB4 MCB3
E E
P143 REG-DA TC2+

TC1+
TC2-

TC1-

CC+

CC-
N02.2 /

N02.2 /

N01.1 /

N01.1 /

M05.1 /

M05.1 /
-PE

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE G03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE G04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN DC POWER SUPPLY FOR CONTROL PANEL PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E02+MK +MK

DC POWER SUPPLY DC POWER SUPPLY


A FOR CB MOTOR FOR DS, ES MOTOR A
-W132
DC+ 1 -XDC 1 -XDC 2
=E02/G04.7

DC- 2 -XDC 3 -XDC 4


=E02/G04.7

1 3 1 3
12 14 96 98 12 14 96 98

-FQCB 11 95 -FQDS 11 95
2P-16A I> I> 2P-16A I> I>

/R03.3

/R03.5

/R03.3

/R03.5
B B
2 4 2 4

-XDC2 2 ES+
/ P02.1
-XDC2 4 ES-
/ P02.1

-XDC1 1 2 -XDC2 1 3

-W125 1 2 -W126 1 2

C C

+QF01 +QL01

X1 450 460

-X1 1 2 -X1 5 4

D QM1 D
1

DSQ1+

DSQ1-
Q1
2

3
Q1

M01.2 /

M01.2 /
4
/Z19.3 M
1 5
Q1
/Z16.3 6
M
E E

POWER SUPPLY POWER SUPPLY POWER SUPPLY


FOR CB MOTOR FOR DS MOTOR FOR CONTROL CIRCUIT

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE G04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE M01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN DC POWER SUPPLY FOR HV EQUIPMENT PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

A CLOSE DS QL01 OPEN DS QL01 CLOSE DS QL01 OPEN DS QL01 A


FROM MIMIC FROM MIMIC FROM BCU FROM BCU

6 8 2 3
1
-SQL01 BCU E
-S.B/M

Push close

Push open
/Z09.1 C3 C4 /Z05.6
/Z09.1 -DO1 -DO2
MIMIC /Z05.6 /Z05.6
2
B 5 7 1 4 B

-X3 7 X3 8 X3 9 X3 10

-W115 1 2 3 4

+MK INT_QL01+ INT_QL01-


C P01.5 P01.5 C
-X3 1 3 5 6
INTERLOCKING CIRCUIT

-W138 1 2 3 4

+QL01
-X1 4A -X1 4B -X1 8 -X1 7 -X1 9A
DSQ1+
G04.5
D D
-X1 6A -X1 6B SB3

SA1 SA1 SA1 SA1 -X1 9

-KA1
-KM1 -KM2 -SB2 -SB1

-KA4

CS1 CS2
E E
KA4 KM2 KM1 /Z20.3
-QM1

CLOSE OPEN
DSQ1- -X1 12
G04.5

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE M01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE M02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CONTROL CIRCUIT DS E01-QL01 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

RAISE TAP. LOW TAP. RAISE COMMAND & AUTO LOWER COMMAND & AUTO
FROM MIMIC FROM MIMIC FROM F90 FROM F90
A A
F90+ F90+
G03.4/ / R09.3
-X22 2 -X22 3

5 1

-S.M/S/I
/Z10.1
INDEP. MASTER

6 2
B B

1
-S.L/R
/Z10.4
LOCAL
2

LOWER
RAISE
7 45 41
-S.A/M1 -F90
/Z10.1 /Z08
R1 R2
C MAN /Z08.6 /Z08.6 C

8 46 42

LOWER
RAISE

1 3
-S.R/O/L
/Z10.6
RAISE LOWER
D D
2 4

1 5 2 6
-KF90 -KF90
/R10.4 9 /R10.4 10
18 19
-F90
/Z08 5 9 /M03.4 5 9 /M03.3
1 1
E7 E8 14 6 10 /M03.3 14 6 10 /M03.4
E /Z08.3 /Z08.3 2 2 E
KSCR KSCL
7 11 7 11
220VDC 13 3 220VDC 13 3
8 12 8 12
20 4 4

-X22 7 -X22 8 -X22 9

G03.4/
F90-

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE M02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE M03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN OLTC CONTROL CIRCUIT PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

LOWER RAISE EMERGENCY STOP EMERGENCY STOP


A FROM BCU A

LOWER

RAISE
1
1 5 1 5 BCU D -S.ES 3
/Z05.4 /Z09.5
-KSCL -KSCR -DO1
/M02.6 9 /M02.5 9 /Z05.4 4
B B
2

2 6 2 6
-KSCR -KSCL
/M02.5 10 /M02.6 10

X22 10 11 12 13 14

C -W120 2 3 4 5 6 C

=T1+OLTC

-X1 12 -X1 10 -X1 11 -X1 14 -X1 15

-S32 S3

D D

-Q1
/
L1

S4 S5
-K1 -K2

E E
K2 K1

K1 K2 Q1

/
N
LOWER RAISE EMERGENCY STOP

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE M03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE M04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN OLTC CONTROL CIRCUIT PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1
ON/OFF ON/OFF ON/OFF ON/OFF
AUTO MODE MANUAL MODE CONTROL FAN
FAN GROUP 1 FAN GROUP 2 FAN GROUP 1 FAN GROUP 2
AUTOMATIC FROM BCU
FROM BCU FROM BCU
A A
5 9
-S.L/R
/Z10.4
LOCAL LOCAL

6 10

AUTO

MAN.

MAN.
1 3 7 1 1 3 7 9
-S.A/M2 SCF1 SCF2 - BCU D
B /Z10.1 /Z10.4 /Z10.4 /Z05.4 DO2 DO4 DO5
B
AUTO MAN. MAN. /Z05.4 /Z05.4 /Z05.4

2 4 8 2 2 4 8 10

C C
-X3 11 12 13 14

-W113 1 2 3 4

=T1+LCB
-X2 1 X2 2 3 4 5 6

D D
1S2 1S1 C5A
.L1 L1
4.5:E / /

Stop 1 Stop 2
C1 C2 C3 C4
-OTI -WTI1

Start 1 Start 2
E C5A C3 C3 C4 C4 E

C2 C1

C2 C1 C5 C5A C3 C4 MC1 MC2

.N1 N1
4.5:E / /

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE M04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE M05

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN FAN CONTROL CIRCUIT PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

CLOSE CB QF01 CLOSE cmd. CLOSE CB QF01 CLOSE CB QF01


START SOTF
A FROM BCU WITH SYN. FROM MIMIC FROM BCU A
C+
G03.8
X11 2 C-
G03.8
X11 4 X11 5 13
-S.B/M
/Z09.1
14 10
F861 10 11 MIMIC
/N03.6 F741 14
1 /Z13.4 6 6
B -SQF01 B

Push close
5 1 15 /Z09.1 5
BCU E F67 D F67 F F67 G
/Z05.6 -DO3 /Z03 BI1 /Z03.6 BI16 /Z04 -DO9
14 10 5
F862 10 11 /Z05.6 /Z03.6 /Z03.6
/N04.7 F742 6 2 16 6
1 /Z13.4 6 1 3
-S.25
SYN. BYPASS
2 4

C C
X11 6 7
-W115 13 14

+MK
X11 9
INT_CB+ INT_CB- INT_CBR- INT_CBR+
P01.1 P01.1 P01.3 P01.3

X11 3 X11 5 X11 7


-W142 13 15 16
D D

+QF01

PBS1 -TB1 14 -TB1 15 TB1 18 TB1 17

G03.8/
CC+
3 4
7 5
43A
6
E E

CLOSING COIL

-52CC
/Z15.2

G03.8/
CC-

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE M05 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CLOSING CIRCUIT CB E01-QF01 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

A OPEN Cmd. CB OPEN Cmd. CB F87T TRIP F67 TRIP F861 F862 TRIP CIRCUIRT SUPERVISOR 1 A
FROM MIMIC FROM BCU TC1 QF01 TC1 QF01 TRIP TC1 TRIP TC1 CB E01-QF01

TC1+ TC1-
G03.7 G03.7/
X10 2 3 -X10 5 6

TC1+
N03.1

15 TC1-
1 1
N03.1
-S.B/M F87T H F67 H
B /Z09.1 MIMIC /Z02 BO1 /Z04 -BO1
B
16 /Z02.6 /Z04.6
1 2
2 2 F861 20 21 F862 20 21 + -
/N03.6 /N04.7 -F741
/Z13.2 K3

8 7 1 9 2 2

-SQF01 BCU E -XF872 -XF67 K1 K2


Push open

K1 K2
/Z09.1 C4 /Z05.6 /Z14.4 /Z14.5
-DO4
/Z05.6
12 4 8
7 8 2 10

C C
T.TC1 /N03.1
-X10 7 X10 8 -X10 10 11

-W115 7 8 9 10

+MK
X10 1 2 3 4
-W142 6 7 8 9

D +QF01 TC1+ TB1 16 TB1 11 12 13 D


G03.6

3
PBS2
7 5
4
43A
6

-A3

TRIPPING COIL 1 1 3

E -P1 -P2 E
-S1 -S1
2 4

-A2 -52TC1
/Z15.4

G03.6/
TC1-

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE
TRIPPING CIRCUIT 1
24/11/2020
APPROVED NGUYEN DINH TUAN PECC2/TT-110KV/E01-131
CB E01-QF01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1
F87T TRIP F67 TRIP F861 F862 TRIP CIRCUIRT SUPERVISOR 2
TC2 QF01 TC QF01 TRIP TC2 TRIP TC2 CB E01-QF01

TC2+ TC2+ TC2-


A G03.6 N04.1 G03.6 A
-X20 2
-X20 7 8

3 11
-XF872 -XF67
/Z14.4 /Z14.5

TC2-
N04.1
4 12
B 862 F861 30 31 F862 30 31 1 2 B
/ N04.5 /N03.6 /N04.7
-F742 + -
3 3 3 3
/Z13.2 K3

F87T H F67 H
/Z02 BO2 /Z04 -BO2 K1 K2
K1 K2

/Z02.6 /Z04.6

4 4 12 4 8

T.TC2 /N04.1

C C
X20 9 11 12

-W117 10 11 12

+MK
X20 1 2 3

-W140 15 16 17

+QF01
D TC2+ TB1 26 TB1 23 24 25 D
G03.5

3
PBS2
7 5
4
43A
6

-A4
TRIPPING COIL 2
5

E -P2 E
-S1 -S1
6

-A4 -52TC2
/Z15.7

TC2-
G03.5

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE
TRIPPING CIRCUIT 2
24/11/2020
APPROVED NGUYEN DINH TUAN PECC2/TT-110KV/E01-131
CB E01-QF01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

A 50BF(E01,E05), F87B INTERNAL LOAD F87T TRIP F67 TRIP RESET A


F87B TRIP
TRIP SEND F861 PROTECTION TRIP SHEDDING LOCKOUT 1 LOCKOUT 1 LOCKOUT F861

N01.7/
TC1+

X10 12 X10 13

K94.TC1+
-W112 8

=E05+CRP5 5 5
F87T H F67 H

E01.TC1+

N09.1 /
B /Z02 BO3 /Z04 BO3
B
/Z02.6 /Z04.6

6 6

=E05/N05.2 /

K81 3 7
/N13.4
9 3
11
BCU E -S.RL
/Z05.6 /Z09.7
-DO5
/Z05.6
=E05/N05.2

=E05/N05.3

C C

N09.1
10 4
5 13
-XF872 -XF67
E01.F861

/Z14.4 /Z14.5
E01.TC1

K94.861 6 14

-W112 7 9

D X10 9 X10 14 X10 15 D


/ N01.4
T.TC1

SET RESET
b d
-F861
a c

N01.8/
TC1-
E E

11 1 /M05.2 51 5 /R06.2
10 50
21 2 /N01.6 61 6 /R11.7
20 60
31 3 /N02.5 70 7
30 71
41 4 /N11.6 80 8
40 81

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN TRIP-LOCKOUT 1 CIRCUIT PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

A 50BF(E01,E05), F87B 50BF J01 TRIP LOAD F67 TRIP F87T TRIP RESET A
F87B TRIP LOCKOUT 2 LOCKOUT 2
TRIP SEND F862 LOCKOUT 2 SHEDDING LOCKOUT F862

N02.5/
TC2+
X20 3 X20 4 X20 5 X20 16
-W112 10 -W119 11

K94.TC2+
=E05+CRP5

=C41+J01
862
XC 55 N02.5/

E01.TC2+

N09.5 /
B B

7 7
F67 H F87T H
=E05/N05.5 /

/Z04 BO4 /Z02 BO4


/Z04.6 /Z02.6
K81 4 8
8 8
/N13.4
11 3*
12
BCU E -S.RL
=E05/N05.5

=E05/N05.6

/Z05.6 /Z09.7
-DO6
/Z05.6
C C

N09.5
12 4*
7
E01.F862
E01.TC2

XC 56 -XF872
/Z14.4

K94.862
8
-W112 11 12 -W119 12

X20 10 X20 13 14 15
D D
/ N02.4
T.TC2

SET RESET
b d
-F862
a c

N02.7/
TC2-
E E

11 1 /M05.2 51 5 /R06.3
10 50
21 2 /N01.6 61 6 /R11.7
20 60
31 3 /N02.6 70 7
30 71
41 4 /N11.7 80 8
40 81

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N05

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN TRIP-LOCKOUT2 CIRCUIT PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

F87T TRIP F67 TRIP 50BF BAY E03 F87T TRIP F67 TRIP
MV 22KV MV 22KV SET 86, 50BF 24KV SIDE MV 22KV MV 22KV
A A

MV22+
/ N09.1
X3 15 16

-W112 1

=E05+CRP5
9 9 11 11

E01.BF+
B F87T H F67 H F87T H F67 H B
/Z02 BO5 /Z04 BO5 /Z02 BO6 /Z04 BO6
/Z02.6 /Z04.6 /Z02.6 /Z04.6

10 10 12 12

=E05/N05.7 /
9

=E05/N05.7
-XF872 11
/Z14.4 -XF872
/Z14.4

C 10 C

E01.BF
12
N09.1/
K94.MV

-W112 2

X3 17 X3 18
X3 19 X3 20

-W119 1 2 3 4
D D

=C41+J01

XC 13
XC 14 XC 11 XC 12

SET 86, 50BF TRIP CB J01


E E
CUIBLE: J01 CUIBLE: J01

PAGE: =MV22+J01/Q03 PAGE: =MV22+J01/Q03

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N05 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N06

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN SEND TRIP CIRCUIT PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

A A
BCU F87T MCB BCU MCB BCU MCB VTC41 CL:3P
SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE
FAILED FAILED OFF TRIP OFF BLOCK 25

F67+
G03.2
X21 2 3 4

-W119 13

B B

=C41+J01
XY 23

5 11
-BCU A -
F87T J 12 14 96 98
/Z05.2 /Z01.3 -FQBCU -FQBCU
/Z01.3 /G02.3 11 /G02.3 95
C C
6 12

XY 24

-W119 14

X21 8 9 10 11 12 13 14 15 16 17

D D

4 6 8 10 12 14 16 2 4 6 8 10 12 14
F67 D F
/Z03 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 BI14 BI15
/Z03.6 /Z03.6 /Z03.6 /Z03.6 /Z03.6 /Z03.6 /Z03.6 /Z03.6 /Z03.6 /Z03.6 /Z03.6 /Z03.6 /Z03.6 /Z03.6

3 5 7 9 11 13 15 3 5 7 9 11 13

E E
X21 6 X21 7
F67-
G03.2

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N06 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N07

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT F67 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1
BUCHHOLZ RELAY RAPID PRESSURE RELAY OIL TEMP. 22KV WINDING TEMP.
TRIP OF TRANSFORMER TRIP RELAY TRIP RELAY TRIP

A A
SAFETY VAL OIL FLOW RAPID PRESSURE RELAY 110KV WINDING TEMP.
TRIP RELAY TRIP OF OLTC TRIP RELAY TRIP

87T+ 87T+
G02.2 / N10.1

X12 2
=T1+LCB -W113 5

B B

X5 9

C C
X5 11 12 13 14 15 16 17 18

-W113 7 8 9 10 11 12 13 14

X12 8 9 10 11 12 13 14 15

KT1 KT2 KT3 KT4 KT5 KT6 KT7 KT8


D / N08.2 / N08.2 / N08.2 / N08.2 / N08.2 / N08.2 / N08.2 / N08.2 D

2 4 6 8 10 12 14 16
F87T D
/Z01
BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8
/Z01.6 /Z01.6 /Z01.6 /Z01.6 /Z01.6 /Z01.6 /Z01.6 /Z01.6

E 1 3 5 7 9 11 13 15 E

87T-
/ N10.1

-X12 6 -X12 7
87T- KT-
G02.2 / N08.2

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N07 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N08

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN INTERNAL PROTECTION TRANSFORMER TRIP PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

A A

BUCHHOLZ RELAY RAPID PRESSURE RELAY OIL TEMP. 22KV WINDING TEMP.
TRIP OF TRANSFORMER TRIP RELAY TRIP RELAY TRIP
SAFTY VAL OIL FLOW RAPID PRESSURE RELAY 110KV WINDING TEMP.
TRIP RELAY TRIP OF OLTC TRIP RELAY TRIP

N07.6/
KT8
B B

N07.6/
KT7

N07.5/
KT6

N07.4/
KT5

N07.4/
KT4
C C

N07.3/
KT3

N07.3/
KT2

N07.2/
KT1

D D

14 14 14 14 14 14 14 14
-KT1 -KT2 -KT3 -KT4 -KT5 -KT6 -KT7 -KT8
220VDC 13 220VDC 13 220VDC 13 220VDC 13 220VDC 13 220VDC 13 220VDC 13 220VDC 13

E N07.6/
KT- E

5 9 /N09.2 5 9 /N09.2 5 9 /N09.2 5 9 /N09.3 5 9 /N09.3 5 9 /N09.4 5 9 /N09.4 5 9 /N09.4


1 1 1 1 1 1 1 1
6 10 /N09.5 6 10 /N09.6 6 10 /N09.6 6 10 /N09.7 6 10 /N09.7 6 10 /N09.7 6 10 /N09.8 6 10 /N09.8
2 2 2 2 2 2 2 2
7 11 /N09.2 7 11 /N09.2 7 11 /N09.2 7 11 /N09.3 7 11 /N09.3 7 11 /N09.4 7 11 /N09.4 7 11 /N09.4
3 3 3 3 3 3 3 3
8 12 /N09.5 8 12 /N09.6 8 12 /N09.6 8 12 /N09.7 8 12 /N09.7 8 12 /N09.7 8 12 /N09.8 8 12 /N09.8
4 4 4 4 4 4 4 4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N08 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N09

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN INTERNAL PROTECTION TRANSFORMER TRIP PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

A A

N03.4/
K94.TC1+ N04.4/
K94.TC2+

1 5 1 5 1 5 1 5 1 5 1 5 1 5 1 5 2 6 2 6 2 6 2 6 2 6 2 6 2 6 2 6
B B
-KT1 -KT2 -KT3 -KT4 -KT5 -KT6 -KT7 -KT8 -KT1 -KT2 -KT3 -KT4 -KT5 -KT6 -KT7 -KT8
/N08.2 9 /N08.3 9 /N08.4 9 /N08.4 9 /N08.5 9 /N08.5 9 /N08.6 9 /N08.6 9 /N08.2 10 /N08.3 10 /N08.4 10 /N08.4 10 /N08.5 10 /N08.5 10 /N08.6 10 /N08.6 10

/ N03.4
K94.861 / N04.4
K94.862

C C

N05.4/
MV22+ R11.8/
FR.K94+

D 3 7 3 7 3 7 3 7 3 7 3 7 3 7 3 7 4 8 4 8 4 8 4 8 4 8 4 8 4 8 4 8 D
-KT1 -KT2 -KT3 -KT4 -KT5 -KT6 -KT7 -KT8 -KT1 -KT2 -KT3 -KT4 -KT5 -KT6 -KT7 -KT8
/N08.2 11 /N08.3 11 /N08.4 11 /N08.4 11 /N08.5 11 /N08.5 11 /N08.6 11 /N08.6 11 /N08.2 12 /N08.3 12 /N08.4 12 /N08.4 12 /N08.5 12 /N08.5 12 /N08.6 12 /N08.6 12

/ N05.2
K94.MV / R11.8
FR.K94-

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N09 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N10

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN INTERNAL PROTECTION TRANSFORMER TRIP PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

A A

BUCHHOLZ RELAY LOW LEVEL OIL HIGH LEVEL OIL LOW LEVEL OIL HIGH LEVEL OIL OIL TEMP. 110KV WINDING TEMP. 22KV WINDING TEMP.
ALARM OF TRANS. ALARM OF TRANS. ALARM OF OLTC ALARM OF OLTC ALARM RELAY ALARM RELAY ALARM RELAY ALARM

87T+
N07.3

X12 3 X12 4
-W113 6

B B

=T1+LCB
-X6 6

C C

-X6 11 12 13 14 15 20 27 34

-W113 15 16 17 18 19 -W114 14 15 16

D D

X12 16 X12 17 X12 18 X12 19 X12 20 X12 21 X12 22 X12 23

2 4 6 8 10 12 14 16
F87T F
/Z01.6
E BI9 BI10 BI11 BI12 BI13 BI14 BI15 BI16
E
/Z01.6 /Z01.6 /Z01.6 /Z01.6 /Z01.6 /Z01.6 /Z01.6 /Z01.6

1 3 5 7 9 11 13 15

87T-
N07.7

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N10 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N11

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT F87T PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

A F87T TRIP F67 TRIP F861 TRIP F862 TRIP A


START 50BF START 50BF START 50BF BAY E03 START 50BF BAY E03

15 1
B F87T H F67 G B
/Z02 BO8 /Z04 BO8
/Z02.6 /Z04.3

16 2 F861 40 41 F862 40 41
/N03.6 /N04.7
4 4

13 15
-XF872 -XF67
C /Z14.4 /Z14.5 C

14 16

-X3 21 22

-W112 3 4

D D

=E05+CRP5
F87B.E01+

E01.50BF
=E05/N12.2 /
=E05/N12.2

E E

F87T, F67 BAY E03


START 50BF

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N11 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N12

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN SIGNAL SEND TO F87B PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+MK

CB E01-QF01 CB E01-QF01 DS E01-QL01 DS E01-QL01


A CLOSED OPENED CLOSED OPENED A

-X3 7 8 9

-W140 2 -W138 5

+QF01 +QL01
B B

TB2 1 TB2 25 -X2 13 -X2 15

S2-1 S2-5 CS1-7 -CS1-8


/Z18.1 /Z18.5 /Z21.5 /Z21.5

C C

-TB2 2 -TB2 26 -X2 14 -X2 16

-W140 3 4 -W138 6 7
D D

-X3 10 11 12 13

-W127 1 2 3 4 5

=E05+CRP5
E01.MK+

E01.DSO
E01.CBO

E01.DSC
E01.CBC

E E
=E05/N09.2 /

=E05/N09.3 /

=E05/N09.3 /

=E05/N09.4 /
=E05/N09.2/

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N12 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N13

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT OF F87B PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E0X+XXX +CRP1 =E03+CRP3

A A

-W111
-X91 1 LOAD SHEDDING LEVEL 1 2 1 LV1.
/ =E03/N05.1

-X91 3 LOAD SHEDDING LEVEL 2 4 2 LV2.


/ =E03/N05.1

-X91 5 LOAD SHEDDING LEVEL 3 6 3 LV3.


/ =E03/N05.1

B -X91 7 LOAD SHEDDING LEVEL 4 8 4 LV4. B


/ =E03/N05.1

-X91 9 COM 10 5 COM.


/ =E03/N05.1

LEVEL 1

LEVEL 2

LEVEL 3

LEVEL 4
4 6 8 10
-S.81
C /Z09.1 C

14
-K81
D 220VDC 13 D

5 9
E 1 E
6 10
2
7 11 /N03.4
3
8 12 /N04.4
4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N13 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE P01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LOAD SHEDDING CIRCUIT PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

+MK
INTETLOCKING FOR INTETLOCKING FOR
INTETLOCKING FOR
CLOSE CB QF01 CLOSE CB QF01
A CLOSE/OPEN DS QL01 A
AT LOCAL AT REMOTE

INT_CB+ INT_CBR+ INT_QL01+


M05.2 M05.8 M01.3
-X11 4 -X3 2
-W137 1

-W138 14 -W138 15 -W140 1

=C41+J01
+QL01 -X2 3 +QL01 -X2 1 +QF01 -TB2 27 XE 5

B B

ES J01-QE38 OPENED
DS QL01 OPENED

CB QF01 OPENED
DS QL01 CLOSED
-CS1-2 -CS1-1 S2-6
/Z21.4 /Z21.3 /Z18.5

-X2 4 -X2 2 TB2 28 XE 6


C C
-W138 16 -W138 17 -W140 5 -W137 2

-X11 10 -X11 11 -X3 14 -X3 16


-W136 2

-W137 11 -W137 12 -W143 1

E5.Q14+
=E05+MK
=C41+J01

=C41+J01
-XB 5 -XB 3 +QE15 -XT2 3

=E05/P02.7 /
ES E05-QE24 OPENED
D D
CB J01 AT SERVICE

ES QE15 OPENED
CB J01 AT TEST

-CS1-2
/Z23.3

=E05/P02.7
E5.Q14-
-XB 6 -XB 4 -XT2 4
E -W143 2 E
-W137 9 -W137 10

-W136 1

-X11 6 -X11 8 -X3 15 -X3 4

INT_CB- INT_CBR- INT_QL01-


M05.4 M05.6 M01.4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE P01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE P02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN INTERLOCKING FOR CB, DS, ES PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+MK LIÊN ĐỘNG THAO TÁC =E05+MK
DNĐ QE15 -W138 -W136
10 -X3 21 3
E1.Q1+
ES+ / =E05/P04.3
A G04.6 A
-X3 17 +QL01 -X2 35
-W138 8

DS QL01 OPENED
+QL01 -X2 31 -CS1-18
/Z21.7
DS QL01 OPENED

-CS1-16 -X2 36
B /Z21.6 B

11 -X3 22 4
E1.Q1-
/ =E05/P04.3

-X2 32
-W138 9
=C41+J01
-W137
12 -X3 23 5 -XC 7
-X3 18
-W137 3
+QL01 -X2 27

C C
=C41+J01

-X... ...

DS QL01 OPENED
CB J01-QF01 AT TEST

INTERLOCKING

-CS1-14 CUIBLE: J01


/Z21.6
PAGE: =MV22+J01/Q02

-X2 28

-X... ...
13 -X3 24 6 -XC 8
D D
-W137 4

-W143
5 -X3 25 7 -XC 3
ES-
G04.6
-X3 19 -X3 20 +QE15 -XT2 27

-W143 3 4

ES QE15 OPENED
+QE15 INTERLOCKING
-XT2 1 2 -CS1-8
E /Z23.4 CUIBLE: J01
E
13
-S4 PAGE: =MV22+J01/Q01
14
-XT2 28
-KA4
/Z22.4
6 -X3 26 8 -XC 4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE P02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Q01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN INTERLOCKING FOR CB, DS, ES PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1
S. CONTROL CB QF01 CB QF01 DS E01-QL01 ES E01-QE15

LAMT TEST AT "LOCAL" OPENED CLOSED OPENED CLOSED OPENED CLOSED


A A
G02.6/
SI+
-X7 2 -X7 3
-W117 1

+MK
-X7 1 -X7 2 -X7 3 -X7 4
-W140 6 -W139 1 -W143 7

+QF01 +QL01 +QE15


TB2 31 TB2 5 -X2 19 17 -XT2 19 17

B B

S2 S2 CS1 CS1 CS1 CS1


/Z18.6 /Z18.2 /Z21.5 /Z21.5 /Z23.5 /Z23.4

TB2 32 TB2 6 -X2 20 18 -XT2 20 18

-W140 7 8 -W139 2 3 -W143 8 9

-X7 5 6 7 8 9 10

C -W117 2 3 4 5 6 7 C
-X7 8 9 10 11 12 13
9 11 9 11
-SQF01 -SQL01
/Z09.1 /Z09.1
2 1
SQE15
/Z09.5 3
10 12 10 12

K+
/ R10.5
D 3 D
1 5 1 5 2 6 3 7
-S.LT -KLCB -KST2 -KST2 -KST2
/Z09.5 /R10.4 /Q01.2 /Q01.2 /Q01.2
9 9 10 11
TEST

4 X1 X1
X1 -SQF01 -SQL01
14 14 PL01 /Z09.1 /Z09.1
-KST2 -KST1 /Z09.5 X2
220VDC 13 220VDC 13 X2 X2

E K- E
/ R10.5
-X7 5 -X7 6 -X7 7
G02.6/
SI-

5 9 /Q01.4 5 9 /R10.6
1 1
6 10 /Q01.5 6 10 /R10.7
2 2
7 11 /Q01.6 7 11
3 3
8 12 8 12
4 4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Q01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Q02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN INDICATOR CIRCUIT PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

A TEMPERATURE OF TEMPERATURE OF TEMPERATURE OF A


TAP POSITION SIGNAL
OIL TRANSFORMER 110KV WINDING 22KV WINDING

B B

64
F90
/Z08
-AI1

63

C 5 5 5 5 C
PTP PTO PTW1 PTW2
/Z11.3 /Z11.5 /Z11.3 /Z11.5
-AI -AI -AI -AI

3 3 3 3

-X7 14 15 16 17 18 19 20 21

-W098 1 2 -W114 1 2 3 4 5 6
D D

=T1+OLTC =T1+LCB

(+) (-) (+) (-) (+) (-) (+) (-)


AI04 11 14 X3 1 X3 2 3 4 7 8

E E
4-20mA 4-20mA 4-20mA 4-20mA

ANALOG OUPUT

CUIBLE: LOCAL

PAGE: =D1/10

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Q02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN TAP POSITION AND THERMAL WINDING INDICATOR CIRCUIT PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

=E01+QF01
A =E01+QF01 =E01+QF01 =E01+QF01 =E01+QF01 =E01+QF01 =E01+QF01 A
CONTROL SPARE
CB OPENED CB CLOSED SF6 ALARM SF6 LOCKOUT SPRING DISCHARED MCB OFFF
AT LOCAL
BCU+ BCU+
G02.4 R04.1
-X8 2
-W116 1

+MK BCU+
R02.1
-X8 1
B -W141 1 B

+QF01

TB2 29 3 TB1 40 -TB1 42 44 51 46 30 32 34 36 38

S2 S2 A2 A3 A4-1 LS-1 43A MCB1 MCB2 MCB3 MCB4 MCB5


/Z18.5 /Z18.2 /Z17.4 /Z17.4 /Z17.5 /Z17.6 /Z17.5 /Z17.2 /Z17.3 /Z17.3 /Z17.3 /Z17.4

C C

TB2 20 4 TB1 41 -TB1 43 45 52 47 31 33 35 37 39

-W141 2 3 4 5 6 7 8

X8 4 5 6 7 8 9 10

-W116 2 3 4 5 6 7 8
D D

X8 10 11 12 13 14 15 16 17
CBL
/ R10.1
1 2 4 5 7 8 10 11
- BCU I
/Z06.3
DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8
/Z06.3 /Z06.3 /Z06.3 /Z06.3 /Z06.3 /Z06.3 /Z06.3 /Z06.3

E 3 6 9 12 E
BCU-
R02.1

-X8 8

BCU- -X8 9
G02.4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT BCU PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+MK

DS E01-QL01 DS E01-QL01 DS E01-QL01 DS E01-QL01 ES E01-QE15 ES E01-QE15 DS E01-QL01


SPARE
OPENED CLOSED CTR. AT LOCAL MCB OFF OPENED CLOSED MCB OFF
A A
BCU+ BCU+
R01.2 R03.1
-X8 2 -X8 3
-W139 4 -W143 10

+QL01 +QE15

X2 23 -X2 21 -X2 77 -X2 83 -X2 87 -X2 75 -X2 73 XT2 7 -XT2 1 -XT2 87


B B

CS1 CS1 SA1 QF1 QF3 KA1 QM1 CS1 CS1 QF3
/Z21.6 /Z21.5 /Z20.7 /Z20.7 /Z19.8 /Z19.5 /Z19.5 /Z23.3 /Z23.3 /Z22.8

X2 24 -X2 22 -X2 80 -X2 84 -X2 88 -X2 76 -X2 74 XT2 8 -XT2 2 -XT2 88

C C
-W139 5 6 7 8 -W143 11 12 13

-X8 11 12 13 14 15 16 17

+CRP1
-W116 9 10 11 12 -W118 1 2 3

-X8 18 19 20 21 22 23 24 25
D D

13 14 16 17 19 20 22 23
- BCU I
/Z06.3
DI9 DI10 DI11 DI12 DI13 DI14 DI15 DI16
/Z06.3 /Z06.3 /Z06.3 /Z06.3 /Z06.3 /Z06.3 /Z06.3 /Z06.3

E 15 18 21 24 E

BCU- BCU-
R01.8 R03.1

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT BCU PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+MK

=E01+MK =E01+MK =E01+MK


SPARE SPARE SPARE SPARE SPARE
MCB AC OFF MCB DC OFF MCB TRIP
A A
BCU+
R02.8

12 14 12 14 12 14 12 14 96 98 96 98 96 98 96 98
-FQAC1 -FQAC2 -FQCB -FQDS -FQAC1 -FQAC2 -FQCB -FQDS
B /D02.3 /D02.5 /G04.3 /G04.4 /D02.3 /D02.5 /G04.3 /G04.4
B
11 11 11 11 95 95 95 95

C C

-X8 18 19 20

+CRP1
-W118 4 5 6

-X8 26 27 28 29 30 31 32 33
D D

1 2 4 5 7 8 10 11
- BCU J
/Z06.4
DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8
/Z06.5 /Z06.5 /Z06.5 /Z06.5 /Z06.5 /Z06.5 /Z06.5 /Z06.5

E 3 6 9 12 E

BCU- BCU-
R02.8 R04.1

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT BCU PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

=E05+CRP5 =C41+J01 =C41+J01 =C41+J01 =C41+J01 MCB VT C41 CL: 0.5 OFF FAN GROUP 1 FAN GROUP 2
A MCB VT CL:0.5 OFF RELAY FAIL MCB RELAY OFF SWITCH FAIL MCB SWITCH OFF BLOCK 25 RUNNING RUNNING A
BCU+ BCU+
R01.8 /R06.1
-X8 3 -X8 4 -X8 5 -X8 6
-W112 5 -W119 5

=C41+J01 =T1+LCB
=E05+CRP5

E01.BCU+

-XY 15
B B
BCU+
=E05/R08.2 /

/R05.1
-X0 1 -X0 3

C C
/=E05/R08.3

-XY 90 -XY 16 -X3 22 -X3 22 -X3 22 X0 2 X0 4


MCBVT10.5

D D
-W112 6 -W119 6 7 8 9 10 -W114 7 8

-X8 34 35 36 37 38 39 40 41
F1 F2
R10.1 R10.1

13 14 16 17 19 20 21 22
- BCU J
/Z06.4
E DI9 DI10 DI11 DI12 DI13 DI14 DI15 DI16
E
/Z06.4 /Z06.5 /Z06.5 /Z06.5 /Z06.5 /Z06.5 /Z06.5 /Z06.5

15 18 21 23

BCU- BCU-
R03.8 R05.1

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R05

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT BCU PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

A A

FAN GROUP 1 FAN GROUP 2 FAN FAN =T1+LCB


SPARE
IS OK IS OK AT AUTO AT LOCAL MCB OFF

=T1+LCB

B B

R04.7/
BCU+
X0 5 7 9 11 13 15 17 19 21 24 X6 8

C C

X0 6 8 10 12 14 16 18 20 22 25 X6 28

-W114 9 10 11 12 13
D D

X8 42 43 44 45 46 47

1 2 4 5 7 8
- BCU K
/Z06.6
DI1 DI2 DI3 DI4 DI5 DI6
E /Z06.6 /Z06.6 /Z06.6 /Z06.6 /Z06.6 /Z06.6 E

3 6 9

BCU- BCU-
R04.8 R06.1

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R05 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R06

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT BCU PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

A A
F861 F862 TCS1 TCS2 S.S. "BCU/MIMIC" S.S. "LOCAL/REMOTE" TRANS. S.S. "AUTO/MAN" TRANS. S.S. "SYN./BYPASS"
OPERATED OPERATED FAIL FAIL AT MIMIC AT REMOTE AT MAN AT SYN.

BCU+ BCU+
R04.8 / R07.1

B B

17 12 12
50 51 50 51 13 9 13 9 1
F861 F862 -S.B/M -S.L/R -S.A/M2
F741 F742 -S.25
/N03.7 /N04.7 /Z09.1 /Z10.4 /Z10.1
5 5 /Z13.3 5 /Z13.3 5
/Z09.4 MIMIC /Z10.6 REMOTE /Z10.3 MAN SYN.
2
18 11 11

C C

D D

10 11 13 14 16 17 19 20
- BCU K
/Z06.6
DI7 DI8 DI9 DI10 DI11 DI12 DI13 DI14
/Z06.6 /Z06.6 /Z06.6 /Z06.6 /Z06.6 /Z06.6 /Z06.6 /Z06.6

12 14 18 21
E E

BCU- BCU-
R05.8 R07.1

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R06 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R07

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT BCU PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

=E01+CRP1 =E01+CRP1 =E01+CRP1


F67 FAIL F90 FAIL SPARE SPARE SPARE SPARE SPARE
MCB AC OFF MCB DC OFF MCB TRIP
A A

BCU+
R06.8

12 14 12 14 12 14 12 14 12 14 12 14 12 14 12 14 12 14 12 14 12 14
-FQSI -FQTC1 -FQTC2 -FQ67 -FQ87T -FQ90 -FQPM -FQCB -FQMF -FQDC1 -FQDC2
/G02.6 11 /G03.6 11 /G03.5 11 /G03.1 11 /G02.1 11 /G03.3 11 /G02.4 11 /G03.8 11 /G02.7 11 /G01.5 11 /G01.4 11
B B

11
- F67 J -F90 55 12 14
/Z03.3 /Z08
-R13 -FQAC
/Z08.6 54 56 /D01.4 11
12

96 98 96 98 96 98 96 98 96 98 96 98 96 98 96 98 96 98 96 98 96 98 96 98
F90F
/ R10.1 -FQAC -FQ90 -FQ87T -FQ67 -FQPM -FQSI -FQTC1 -FQTC2 -FQCB -FQMF -FQDC1 -FQDC2
C /D01.4 /G03.3 95 /G02.1 /G03.1 /G02.4 /G02.6 /G03.6 /G03.5 /G03.8 /G02.7 /G01.5 /G01.4
C
95 95 95 95 95 95 95 95 95 95 95

D D

X8 48 49 50 51 52

22 23 1 2 4 5 7 8 10 11
BCU K H
/Z06.6
DI15 DI16 DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8
E /Z06.6 /Z06.6 /Z07.3 /Z07.3 /Z07.3 /Z07.3 /Z07.3 /Z07.3 /Z07.3 /Z07.3 E

24 3 6 9 12

BCU- BCU-
R06.7 R10.1

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R07 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R08

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT BCU PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1
OLTC IN SLAVE MODE OLTC IN AUTO MODE
OLTC IN SLAVE MODE OLTC IN AUTO MODE SELECTED FROM BCU SELECTED FROM BCU
A A
OLTC IN MASTER MODE OLTC IN INDE. MODE OLTC IN MANUAL MODE
OLTC IN MASTER MODE OLTC IN INDE. MODE OLTC IN MANUAL MODE SELECTED FROM BCU SELECTED FROM BCU SELECTED FROM BCU

.F90+
R09.5

13 15
-S.L/R
/Z10.4
/Z10.6 LOCAL /Z10.7 LOCAL
B B
14 16

7 9 11 1 3 11 13 15 19 22
-S.M/S/I -S.A/M1 BCU D
/Z10.1 /Z10.1 /Z05.4 -DO6 -DO7 DO8 -DO9 -DO10
/Z10.3 MASTER /Z10.3 SLAVE /Z10.3 INDE /Z10.2 AUTO /Z10.2 MAN /Z05.4 /Z05.4 /Z05.4 /Z05.4 /Z05.4

8 10 12 2 4 12 14 16 21 24

C C

D D

12 13 14 16 17
-F90
/Z08
E E2 E3 E4 E5 E6
E
/Z08.3 /Z08.3 /Z08.3 /Z08.3 /Z08.3

20

.F90- .F90-
R08.5 R08.1

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R08 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R09

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT F90 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

TAP CHANGER
SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE
A IN OPERATION A

F90+ .F90+
M02.7 R08.2

-X22 4 -X22 5
-W120 1

=T1+OLTC
X1 276
B B

C C
X1 300

-W120 7

-X22 15 16 17 18 19 20 21 22 23

D D

11 23 24 25 26 28 29 30 31
-F90
/Z08

E1 E9 E10 E11 E12 E13 E14 E15 E16


/Z08.3 /Z08.3 /Z08.3 /Z08.3 /Z08.3 /Z08.3 /Z08.3 /Z08.3 /Z08.3
E E

15 27 32

.F90-

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R09 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R10

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT F90 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

FAN GROUP 1 FAN GROUP 2 F90 CB CONTROL


A RUNNING RUNNING HEALTHY AT LOCAL FAN GROUP1 FAN GROUP2 A
RUNNING RUNNING

R01.6/
CBL Q01.7/
K+

B B
R07.2/
F90F

R04.7/
F2 1 5 1 5 1 5 2 6
-KSF1 -KST1 -KSF2 -KST1
/R10.2 9 /Q01.2 9 /R10.3 9 /Q01.2 10

C R04.6/
F1 C

D D

14 14 14 14 X1 X1
-KSF1 -KSF2 -KF90 KLCB P.CF1 P.CF2
220VDC 13 220VDC 13 220VDC 13 220VDC 13 /Z09.5 X2 /Z09.5 X2

R07.8/
BCU- Q01.7/
K-

E E
5 9 /R10.6 5 9 /R10.7 5 9 /M02.4 5 9 /Q01.3
1 1 1 1
6 10 6 10 6 10 /M02.4 6 10
2 2 2 2
7 11 7 11 7 11 7 11
3 3 3 3
8 12 8 12 8 12 8 12
4 4 4 4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R10 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R11

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN MULTIPLED SIGNAL CIRCUIT AND LAMP INDICATOR FOR FAN OPERATORPECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+MK +CRP1
CB E01-QF01 CB E01-QF01
CLOSED OPENED
A A

F87T TRIP F67 TRIP F861 TRIP F862 TRIP INTERNAL TRANS.
SEND TO FR SEND TO FR SEND TO FR SEND TO FR PROTECTION TRIP

-X3 27 28

-W142 1
FR.K94+
/ N09.5
+QF01

B B
TB2 9 TB2 33
14 14
F87T H F67 H 60 61 60 61
/Z02 BO7 /Z04 BO7
F861 F862
/Z02.6 /Z04.6 /N03.7 /N04.7
6 6
15 15
S3-1 S3-5
/Z18.2 /Z18.6

C C

/ N09.5
-TB2 10 -TB2 34

FR.K94-
-W142 2 3

D D
-X3 29 30 -X3 1 -X3 2 -X3 3 -X3 4 -X3 5 -X3 6

=E00+FR

E01.F87T
CBE01.O
CBE01.C

E01.K94
E01.861

E01.862
E01.F67
FR+

FR+
E E
=E00+FR/R01.3 /

=E00+FR/R01.3 /

=E00+FR/R01.4 /

=E00+FR/R01.4 /

=E00+FR/R01.5 /

=E00+FR/R01.5 /

=E00+FR/R01.6 /
=E00+FR/R01.3 /

=E00+FR/R01.4 /

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R11 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R12

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN SEND SIGNAL CIRCUIT PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E02+CRP2 +CRP1 =N00+AC

A A

-W110
B A+ 1 A+ B
=E02/R12.8 / / =N00+AC/R06.2

B- 2 B-
=E02/R12.8 / / =N00+AC/R06.2

-X9 1 6 2 7 3 8 4 9 5 10

C C

9 10 9 10 9 10 9 10 2 3
PTO PTW1 PTW2 PTP PMF
/Z11.5 A(+) B(-) /Z11.3 A(+) B(-) /Z11.5 A(+) B(-) /Z11.3 A(+) B(-) /Z12.6 A(+) B(-)
RS485 RS485 RS485 RS485 RS485

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R12 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE S01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN MODBUS RS485 CIRCUIT PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CT =T1+CT =C41+J01
CORE 1 - CL: 3P,200-400- 600 /1A
GE
TYPE: OSKF145
NEUTRAL CT 110KV NEUTRAL CT 22KV
200-400-600/1/1/1/1A
A 5P20/5P20/0.5/0.5/5P20 CORE 2 - CL: 5P20 CORE 2 - CL: 5P20 A
A B C 200-400- 600 /1A 12000- 1600 /1A

CURRENT FOR F87T

CUIBLE: INCOMING

PAGE: =MV22+J01/T03

1S1 1S1 1S1 1S4 1S4 1S4 2S1 2S4 2S1 2S4
B B

+MK =T1+LCB
-W133 -W134
1 -W135
1 1 -W134
2 -W133
2 2

X4 O21 O24 X4 1O21 1O23


-X41 1 2 3 4 5 6 XIC 5 XIC 6 XIC 7 XIC 8

PE
C C

+CRP1
-W099 1 2 3 4 -W100 1 2 -W101 1 2 -W102 1 2 3 4

-X410 1 2 3 4 -X411 1 2 -X412 1 2 -X413 1 2 3 4

D D

1 3 5 7 9 11 13 15 17 19 21 23
-XF871
/Z14.4

2 4 6 8 10 12 14 16 18 20 22 24

24 26 28 16 14 18 20 22
E F87T C E
/Z01.3
IA(1) IB(1) IC(1) IY(HV) IY(LV) IA(2) IB(2) IC(2)

23 25 27 15 13 17 19 21

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE S01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE S02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CURRENT CIRCUIT OF RELAY F87T PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CT
GE
TYPE: OSKF145
200-400-600/1/1/1/1A
A A
5P20/5P20/0.5/0.5/5P20 CORE 2 - CL: 5P20, 200-400- 600 /1A CORE 5 - CL: 5P20, 200-400- 600 /1A
A B C A B C

B B

2S1 2S1 2S1 2S4 2S4 2S4 5S1 5S1 5S1 5S4 5S4 5S4

C C

+MK
-W133 -W134
3 -W135
3 3 -W134
4 -W133
4 4 -W128 -W129
1 -W130
1 1 -W129
2 -W128
2 2

X42 1 2 3 4 5 6 X45 1 2 3 4 5 6

D D

PE PE
-W131 1 2 3 4

=E00+FR =E05+CRP5
E01.CTN

E01.CTN
E01.CTA

E01.CTC

E01.CTA

E01.CTC
E01.CTB

E01.CTB
E E
=E00+FR/S01.1

=E00+FR/S01.2

=E00+FR/S01.2

=E00+FR/S01.2

=E05/S06.1

=E05/S06.2

=E05/S06.2

=E05/S06.2
CT E01 TO FR CT E01 TO F87B

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE S02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE S03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CURRENT CIRCUIT OF RELAY PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=T1+CT =E03+CRP3 =E00+FR =C41+J01
BUSHING TYPE CT TRANS. 110KV
CORE 2: CL: 5P20 RATIO 600/1A

A A

A B C BUSBAR VOLTAGE C11 - CL: 3P BUSBAR VOLTAGE C11 - CL: 3P BUSBAR VOLTAGE C41-CL: 3P

PHASE B (SYN CHECK)

B B
2S1 2S1 2S1 2S4 2S4 2S4

=E00+FR/S03.3

=E00+FR/S03.3

=E00+FR/S03.3

=E00+FR/S03.4
=E03/S04.7

=E03/S04.7

=E03/S04.8

=E03/S04.8
=T1+LCB

X4 A21 B21 C21 A24 B24 C24

BVT13P.N
BVT13P.A

BVT13P.C
BVT13P.B

E01.BVTA

E01.BVTB

E01.BVTC

E01.BVTN
XY 20 XY 22

PE

C C

+CRP1
-W103 1 2 3 4 -W104 1 2 3 4 -W105 1 2

X52 1 3 5 7 X52 2 4 6 8 X54 1 2

-X42 1 2 3 4

D D

1 3 5 7 21 23 25 27 17 19
-XF67
/Z14.5

2 4 6 8 22 24 26 28 18 20

3 6 8 12 19 20 21 22 23
E F67 C E
/Z03
IA IB IC IN VA VB VC VS

2 5 7 11 24

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE S03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE S04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CURRENT, VOLTAGE CIRCUIT OF RELAY F67 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=T1+CT =C41+J01
BUSHING TYPE CT TRANS. 22KV BUSHING TYPE CT TRANS. 110KV
CORE 2: CL: 5P20 RATIO 2000/1A CORE 3: CL: 5P20 RATIO 600/1A
A A B C A A

VOLTAGE FROM CVT 22KV CLASS 0.5

VOLTAGE 22KV

CUIBLE: INCOMING

PAGE: =MV22+EX/Q03

2S1 2S1 2S1 2S4 2S4 2S4 3S1 3S4


B B

=T1+LCB

XY 25 26 27 28
X4 2A21 2B21 2C21 2C23 2B23 2A23 X4 A31 X4 A34

PE
C C

=C41+J01 +CRP1
-W107 1 2 3 4

-W019 1 2 3 4 -W106 1 2

X53 1 2 3 4

XIC 9 10 11 12
-X43 1 2
VB
/ T02.6

VN
D / T02.6 D

TO F67 INCOMING PANEL


1 3 1 3
-XTC2 -XTV2
/Z12.4 /Z12.4

2 4 2 4

E E

F90 1 21
/Z08
I1 U1

3 22

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE S04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE T01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CURRENT, VOLTAGE OF RELAY F90 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=T1+CT =E03+CRP3 =E00+FR
BUSHING TYPE CT TRANS. 110KV
BUSBAR VOLTAGE C11 - CL: 0.5

A A B C 110 0.11 A
kV
3 3

=E00+FR/S03.6

=E00+FR/S03.6

=E00+FR/S03.7

=E00+FR/S03.7
=E03/T02.7

=E03/T02.8

=E03/T02.8

=E03/T02.8
2S1 2S1 2S1 2S4 2S4 2S4
B B

=T1+LCB

BVT10.5.N
BVT10.5.A

BVT10.5.C
BVT10.5.B

E01.BVTA1

E01.BVTB1

E01.BVTC1

E01.BVTN1
X4 A21 B21 C21 A24 B24 C24

PE

+CRP1
-W109 1 2 3 4

-W108 1 2 3 4

C C
-X51 1 3 5 7 -X51 2 4 6 8

-X44 1 2 3 4

V.A
/ T02.4

V.B
/ T02.4

V.C
D / T02.5 D
V.N
/ T02.5
1 5 7 1 3 5 7
3
-XTC1 -XTV1
/Z12.4 /Z12.4

2 6 8 2 4 6 8
4
V1 V2 V3 22
PMF S1 S1 S1
E /Z12.6 E
I1 I2 I3 V1 V2 V3

S2 S2 S2
N
A

C
B
T02.2

T02.2

T02.2

T02.3

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE T01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE T02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CURRENT, VOLTAGE CIRCUIT FOR BCU PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

A A

/T01.1

/T01.2

/T01.2

/T01.3

/T01.6

/T01.6

/T01.6

/T01.6
A

V.A

V.B

V.C

V.N
S04.8/
VN

B S04.8/
VB B

1 5 7 1 3 5 7 1 3
3
-XTC3 -XTV3 -XTV4
/Z12.4 /Z12.4 /Z12.5

C C
2 6 8 2 4 6 8 2 4
4

BCU L 15 11 7 3 21 23 25 27

/Z07.6
IA.1A IB.1A IC.1A IN.1A U V W N

16 12 8 4 22 24 26 28

D D

-X45 1 2 3 4

=E00+FR
E1.CTN
E1.CTA

E1.CTC
E1.CTB

E E
=E00+FR/S02.5

=E00+FR/S02.5

=E00+FR/S02.6

=E00+FR/S02.6

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE T02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE T03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CURRENT, VOLTAGE CIRCUIT FOR BCU PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CT
GE
TYPE: OSKF145
200-400-600/1/1/1/1A
A A
5P20/5P20/0.5/0.5/5P20 CORE 3 - CL: 5P20, 200-400- 600 /1A CORE 4 - CL: 5P20, 200-400- 600 /1A
A B C A B C

B B

3S1 3S1 3S1 3S4 3S4 3S4 4S1 4S1 4S1 4S4 4S4 4S4

C C

=E00+MP1
E01CT0.2.C1

E01CT0.2.A1

E01CT0.5.C1

E01CT0.5.A1
E01CT0.2.B1

E01CT0.5.B1
E01CT0.2.A

E01CT0.2.C

E01CT0.5.A

E01CT0.5.C
E01CT0.2.B

E01CT0.5.B
D D
=E00+MP1/T01.6

=E00+MP1/T01.6

=E00+MP1/T01.7

=E00+MP1/T01.7

=E00+MP1/T01.6

=E00+MP1/T01.6

=E00+MP1/T02.6

=E00+MP1/T02.6

=E00+MP1/T02.7

=E00+MP1/T02.7

=E00+MP1/T02.6

=E00+MP1/T02.6
E E

CT E01 TO PMT CLASS 0.2 CT E01 TO PMT CLASS 0.5

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE T03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE W01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CURRENT CIRCUIT FOR METTERING PANEL PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1 +MK

A A

-X3 23 24 25 26 27 28 29 30 -X3 31 32 33 34 35 36 37 38 39 40

-X7 22 23 24 25 -X7 11 12 13 14 15
B B

-X8 53 54 55 56 57 58 59 60 -X8 21 22 23 24 25 26 27 28 29 30

-X10 16 17 18 19 20 -X10 7 8 9 10 11 12 13 14 15

-X11 8 9 10 11 12 13 14 15 -X11 12 13 14 15 16 17 18 19 20

-X12 24 25 26 27 28 29 30
C C
-X20 17 18 19 20 -X20 6 7 8 9 10 11 12 13 14 15

-X21 18 19 20 21 22 23 24 25

-X22 24 25 26 27 28 29 30

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE W01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN SPARE CIRCUIT PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

FUNCTION F87T P643 F87T FUNCTION


A A

C D
24 1
CURRENT INPUT PHASE A 110 kV SIDE /S01.1 IA(1) BI1 /N07.2 SAFETY VAL TRIP
23 2

26 3
CURRENT INPUT PHASE B 110kV SIDE /S01.2 IB(1) BI2 /N07.3 BUCHHOLZ RELAY TRIP
25 4

28 5
CURRENT INPUT PHASE C 110kV SIDE /S01.2 IC(1) BI3 /N07.3 OIL FLOW RELAY TRIP
B 27 6 B
18 7
CURRENT INPUT PHASE A 24KV SIDE /S01.6 IA(2) BI4 /N07.4 RAPID PRESSURE RELAY OF TRANSFORMER TRIP
17 8

20 9
CURRENT INPUT PHASE B 24KV SIDE /S01.7 IB(2) BI5 /N07.4 RAPID PRESSURE RELAY OF OLTC TRIP
19 10

22 11
CURRENT INPUT PHASE C 24KV SIDE /S01.7 IC(2) BI6 /N07.5 OIL TEMP. RELAY TRIP
21 12

F87T E 13
BI7 /N07.5 110KV WINDING TEMP. RELAY TRIP
C 24 14 C
IA(3)
23 15
BI8 /N07.6 22KV WINDING TEMP. RELAY TRIP
26 16
IB(3)
25 F F87T
28 1
IC(3) BI9 /N10.2 BUCHHOLZ RELAY ALARM
27 2

F87T C 3
BI10 /N10.3 LOW LEVEL OIL OF TRANS. ALARM
12 4
IY(TV)
D 11 5 D
BI11 /N10.3 HIGH LEVEL OIL OF TRANS. ALARM
14 6
NEUTRAL CURRENT INPUT 24KV SIDE /S01.4 IY(LV)
13 7
BI12 /N10.4 LOW LEVEL OIL OF OLTC ALARM
16 8
NEUTRAL CURRENT INPUT 110KV SIDE /S01.4 IY(HV)
15 9
BI13 /N10.5 HIGH LEVEL OIL OF OLTC ALARM
F87T J 10

1 11
POWER SUPPLY /G02.2 AUX BI14 /N10.5 OIL TEMP. RELAY ALARM
SUPPLY 12
2
E E
13
BI15 /N10.6 110KV WINDING TEMP. RELAY ALARM
11 14
F87T FAILURE /N06.2 15
12
BI16 /N10.7 22KV WINDING TEMP. RELAY ALARM
13 16

14

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE F87T P643 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

FUNCTION F87T P643 F87T FUNCTION


A A

G H
1 1
BO9 BO1 /N01.4 F87T TRIP TC1 QF01
2 2

3 3
BO10 BO2 /N02.3 F87T TRIP TC2 QF01
4 4

5 5
BO11 BO3 /N03.5 F87T TRIP LOCKOUT 1
B 6 6 B
7 7
BO12 BO4 /N04.6 F87T TRIP LOCKOUT 2
8 8

9 9
BO13 BO5 /N05.2 F87T TRIP MV 22KV
10 10

11 11
BO14 BO6 /N05.7 F87T TRIP MV 22KV
12 12

13 13

14 BO15 BO7 14 /R11.5 F87T TRIP SEND TO FR


C C
15 15
16 16

17 BO16 BO8 17 /N11.4 F87T TRIP START 50BF

18 18

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE F87T P643 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

FUNCTION F67 P143 F67 CHỨC NĂNG


A A

C D
5A
1 1
BI1 /M05.5 START SOTF
1A
CURRENT INPUT PHASE A /S03.1 2 IA 2

3 3
5A BI2 /N06.1 BCU FAILED
4 4
1A
CURRENT INPUT PHASE B /S03.2 5 IB 5
BI3 /N06.2 F87T FAILED
B 6 6 B
5A
7 7
BI4 /N06.3 MCB BCU OFF
1A
CURRENT INPUT PHASE C /S03.2 8 IC 8

9 9
5A BI5 /N06.3 MCB BCU TRIP
10 10
1A
CURRENT INPUT PHASE N /S03.3 11 IN 11
BI6 /N06.4 MCB VTC41 CL:3P OFF BLOCK 25
12 12
5A
13 13
BI7 /N06.4 SPARE
1A
C 14 IN_SEN. 14 C
15 15
BI8 /N06.5 SPARE
19 16
VOLTAGE INPUT BVT C11 PHASE A /S03.4 VA
F F67
20 1
VOLTAGE INPUT BVT C11 PHASE B /S03.5 VB BI9 /N06.5 SPARE
2

21 3
VOLTAGE INPUT BVT C11 PHASE C /S03.5 VC BI10 /N06.6 SPARE
22 4
D 5 D
23 BI11 /N06.6 SPARE
6
CURRENT INPUT PHASE C /S03.7 VS
24
7
BI12 /N06.7 SPARE
8

F67 9
J BI13 /N06.7 SPARE
10
1
AUX
POWER SUPPLY /G03.2 SUPPLY
11
2 BI14 /N06.8 SPARE
12
E E
13
11 BI15 /N06.8 SPARE
F67 FAIL /R07.1 14
12
15
13 BI16 /M05.6 CLOSE cmd. WITH SYN.
16
14

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE F67 P143 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

FUNCTION F67 P143 F67 CHỨC NĂNG


A A

G H
1 1
F67 TRIP START 50BF /N11.5 BO8 BO1 /N01.5 F67 TRIP TC1 QF01
2 2

3 3
BO9 BO2 /N02.4 F67 TRIP TC QF01
4 4

5 5
BO10 BO3 /N03.6 F67 TRIP LOCKOUT 1
B 6 6 B
7 7
BO11
8 BO4 8 /N04.5 F67 TRIP LOCKOUT 2

9 9

10 10

11 BO5 11 /N05.3 F67 TRIP MV 22KV


BO12
12 12

13 13

14 BO13 BO6 14 /N05.8 F67 TRIP MV 22KV


C C
15 15
16 16

17 BO14 BO7 17 /R11.6 F67 TRIP SEND TO FR


18 18

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z05

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE F67 P143 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

A A

MODULE BIU241 BCU BCU BCU


FUNCTION MODULE DOU201 FUNCTION FUNCTION
- A D E

O2 1 1
DO1 /M03.5 EMERGENCY STOP FROM BCU /M01.7 CLOSE DS QL01 FROM BCU
2 2
O1 3 3
DO2 /M04.6 CONTROL FAN AUTOMATIC FROM BCU /M01.7 OPEN DS QL01 FROM BCU
4 4
B B
WD 6 /N06.1 BCU FAIL 5
DO3 /M05.4 CLOSE CB QF01 FROM BCU
5 6

VIN
7 7
+ DO4 /M04.7 ON/OFF FAN GROUP 1 FROM BCU /N01.3 OPEN Cmd. CB FROM BCU
DI1 8
- 8
VIN
- 9 9
DI2
+ DO5 /M04.8 ON/OFF FAN GROUP 2 FROM BCU /N03.7 RESET LOCKOUT F861
10 10

11 11
DO6 /R08.5 OLTC IN MASTER MODE SELECTED FROM BCU /N04.7 RESET LOCKOUT F862
RS232/ RXD/TB
RS485 12 12
C SERIAL
C
SG(0V)
LINK 1
13 13
DO7 /R08.6 OLTC IN SLAVE MODE SELECTED FROM BCU
TXD/TA
14 14
SG(0V)
RS232/
RS422/ 15 15
RS485 DO8 /R08.6 OLTC IN INDE. MODE SELECTED FROM BCU
CTS
16 16
RXD/TB
17 17
SERIAL
LINK 2 TXD/TA
18 18
RTS/RB
19 19

D
RA
20 DO9 21 /R08.7 OLTC IN AUTO MODE SELECTED FROM BCU D
RCD
21 20

= + 23 22
GND /G02.3
22 DO10 24 /R08.7 OLTC IN MANUAL MODE SELECTED FROM BCU
_
= 24 23
Power
Supply

E E

C264U11M6A10013302100001111D10

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z05 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z06

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE BCU C264 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

A A

BCU BCU BCU


MODULE DIU200 FUNCTION FUNCTION FUNCTION
- I - J - K
VIN
+
VIN
+ 1 /R01.2 =E01+QF01 CB OPENED /R03.2 =E01+MK MCB AC OFF /R05.2 FAN GROUP 1 IS OK
DI2 DI1
- - 2 /R01.3 =E01+QF01 CB CLOSED /R03.3 =E01+MK MCB DC OFF /R05.4 FAN GROUP 2 IS OK

3
B VIN
+
VIN
+ 4 /R01.3 =E01+QF01 SF6 ALARM /R03.4 =E01+MK MCB TRIP /R05.6 FAN AT AUTO B
DI4 DI3
- - 5 /R01.4 =E01+QF01 SF6 LOCKOUT /R03.4 SPARE /R05.6 FAN AT LOCAL

6
VIN
+
VIN
+ 7 /R01.5 =E01+QF01 SPRING DISCHARED /R03.5 SPARE /R05.7 =T1+LCB MCB OFF
DI6 DI5
- - 8 /R01.5 =E01+QF01 CONTROL AT LOCAL /R03.6 SPARE /R05.7 SPARE

9
VIN
+
VIN
+ 10 /R01.6 =E01+QF01 MCB OFFF /R03.6 SPARE /R06.2 F861 OPERATED
DI8 DI7
- - 11 /R01.7 SPARE /R03.7 SPARE /R06.3 F862 OPERATED

C 12 C
VIN VIN
13 /R02.2 DS E01-QL01 OPENED /R04.2 =E05+CRP5 MCB VT CL:0.5 OFF /R06.4 TCS1 FAIL
+ +
DI10 DI9
- - 14 /R02.3 DS E01-QL01 CLOSED /R04.2 =C41+J01 RELAY FAIL /R06.4 TCS2 FAIL

15
VIN
+
VIN
+ 16 /R02.3 DS E01-QL01 CTR. AT LOCAL /R04.3 =C41+J01 MCB RELAY OFF /R06.5 S.S. "BCU/MIMIC" AT MIMIC
DI12 DI11
- - 17 /R02.4 DS E01-QL01 MCB OFF /R04.4 =C41+J01 SWITCH FAIL /R06.6 S.S. "LOCAL/REMOTE" TRANS. AT REMOTE

18
VIN
+
VIN
+ 19 /R02.6 ES E01-QE15 OPENED /R04.4 =C41+J01 MCB SWITCH OFF /R06.7 S.S. "AUTO/MAN" TRANS. AT MAN
D DI14 DI13 D
- - 20 /R02.6 ES E01-QE15 CLOSED /R04.5 MCB VT C41 CL: 0.5 OFF BLOCK 25 /R06.7 S.S. "SYN./BYPASS" AT SYN.

21
VIN
+
VIN
+ 22 /R02.7 DS E01-QL01 MCB OFF /R04.6 FAN GROUP 1 RUNNING /R07.1 F67 FAIL
DI16 DI15
- - 23 /R02.7 SPARE /R04.7 FAN GROUP 2 RUNNING /R07.2 F90 FAIL

24

E E

C264U11M6A10013302100001111D10

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z06 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z07

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE BCU C264 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E01+CRP1

A A
BCU
MODULE TMU220 FUNCTION
- L
BCU IN.5A
MODULE CCU200 FUNCTION
-H
1 2
VIN
+
VIN
+ 1 /R07.3 =E01+CRP1 MCB AC OFF IN.1A /T02.3 CURRENT CIRCUIT BAY E01-PHASE N
DI2 DI1
- - 2 /R07.3 =E01+CRP1 MCB DC OFF
3 4
3
IC.5A
VIN
+
VIN
+ 4 /R07.4 =E01+CRP1 MCB TRIP
B DI4 DI3 5 6 B
- - 5 /R07.4 SPARE
IC.1A /T02.2 CURRENT CIRCUIT BAY E01-PHASE C
6 7 8
VIN
+
VIN
7 /R07.5 SPARE
DI6 DI5 IB.5A
- - 8 /R07.6 SPARE 9 10
9
IB.1A /T02.2 CURRENT CIRCUIT BAY E01-PHASE B
VIN
+
VIN
+ 10 /R07.6 SPARE 11 12
DI8 DI7
- - 11 /R07.7 SPARE
IA.5A
12 13 14
C C
13
IA.1A /T02.2 CURRENT CIRCUIT BAY E01-PHASE A
CO1 14 15 16
15

16 17 18
CO2
17
X
18 19 20

19
U /T02.4 VOLTAGE CIRCUIT BVT C11 PHASE A
D CO3 20 21 22 D
21
V /T02.4 VOLTAGE CIRCUIT BVT C11 PHASE B
22 23 24
CO4
23
W /T02.5 VOLTAGE CIRCUIT BVT C11 PHASE C
24 25 26

N /T02.7 VOLTAGE CIRCUIT TU4T2 PHASE B


27 28

E E

C264U11M6A10013302100001111D10

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z07 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z08

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE BCU C264 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E01+CRP1

FUNCTION -F90 -F90 FUNCTION


REG-DA
A A
1 56
CURRENT CIRCUIT BUSHING CT-PHASE A /S04.4 I1
3 Life Contact R13 55 /R07.2 F90 FAIL
54

2 Auto 19
VOLTAGE CIRCUIT TU-C41 PHASE A /S04.6 U1
5 R12 20
Manual 21

21 + R11 47
_ = Power
POWER SUPPLY /G03.3 =
22 Supply R10 48
B R9 49 B
TAP CHANGER IN OPERATION /R09.3 11 E1 TC in op. R8 50
OLTC IN MASTER MODE /R08.2 12 E2 Progr. R7 51
OLTC IN SLAVE MODE /R08.2 13 E3 Progr. R6 52
OLTC IN INDE. MODE /R08.3 14 E4 Progr. 53
15
OLTC IN AUTO MODE /R08.4 16 E5 Auto 46
OLTC IN MANUAL MODE /R08.4 17 E6 Manual 45
Raise R1 /M02.5 RAISE COMMAND & AUTO FROM F90
RAISE TAP. FROM MIMIC /M02.2 18 E7 Progr. 44
LOW TAP. FROM MIMIC /M02.3 19 E8 Progr. 43
20 42
SPARE /R09.3 23 E9 BCD1
Lower
41
R2 /M02.6 LOWER COMMAND & AUTO FROM F90
C SPARE /R09.4 24 E10 BCD2 40 C
/R09.4 25 E11 BCD4 39
/R09.5 26 E12 BCD8 38
Progr. R3
27 37
/R09.5 28 E13 BCD10 36
Progr. R4
/R09.6 29 E14 BCD20 35
/R09.6 30 E15 BCD sgn 34
Progr. R5
/R09.7 31 E16 Progr. 33
32
GND
86
63 + CTS
85
TAP POSITTION SIGNAL /Q02.1 _ AI1 RTS
64 84
D COM2 RS232 RxD D
83
TxD
82
81

Rx-
80
Rx+
79
COM3 RS485 Tx-
78
Tx+
77

E E
100BASE-TX

RJ45

A-EBERLE: REG-DA B0 H0 F1 M1 S0 T0 K1 E00 D0 C00 XW94 G2 A2

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z08 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z09

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE F90 (REG-DA) PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1
SELECTED SWITCH "BCU/MIMIC": SA16-FA 6037-61042/SALZER
PUSH BUTTON 1NO
PUSH BUTTON RESET LOCKOUT 2 NO
A MIMIC X X X X X X X X X A
3 3 3*

1 3 5 7 9 11 13 15 17
MIMIC
BCU

4 4 4*

2 4 6 8 10 12 14 16 18 -S.LT /Q01.2 GREEN -S.RL /N03.8 /N04.8 RED

-S.ES /M03.6 GREEN


S.B/M /M01.4 /M05.7 /N01.2 /R06.5

B B

LAMP FOR CB AT LOCAL, FAN RUNNING

X1
CLOSE X

OPEN X
LED X2
INDICATOR
PUSH CLOSE X X
C /Q01.3 RED C
-PL01 CB E03-QF01 AT "LOCAL"
PUSH OPEN X X

-P.CF1 /R10.6 FAN GROUP1 RUNNING RED


Push close

Push close
Push open

Push open

1 3 5 7 9 11 L1
-P.CF2 /R10.7 FAN GROUP1 RUNNING RED
close
open

2 4 6 8 10 12 L2

D D
-SQF01 /M05.7 /N01.2 /Q01.4 /Q01.5 /Q01.5
ES SEMAPHORE: SPSR/FUJI
-SQL01 /M01.5 /M01.6 /Q01.6 /Q01.6 /Q01.6

+(~)
SELECT SWITCH "OFF/1/2/3/4" : SA25/SALZER
ES Semaphore

FUJI
2 1 2 1 2
1 SPSR
OFF

91-230 VAC/DC
1
2
3
4

-(~) 3 3
E E
2 4 6 8 10
-SQE15 /Q01.7

-S.81 /N13.4 /N13.4 /N13.5 /N13.5

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z09 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z10

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE CONTROL DEVICES PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

A A

SELECTOR SWITCH "MASTER/SLAVE/INDEP.":


SA25/SALZER
SELECTED SWITCH "LOCAL/REMOTE": SA25/SALZER

MASTER X X LOCAL X X X X X X

SLAVE X X REMOTE X X X X X X

B INDEP. X X
B
1 3 5 7 9 11 13 15 17 19 21 23

REMOTE
LOCAL
1 3 5 7 9 11
MASTER

INDEN.
SLAVE

2 4 6 8 10 12 14 16 18 20 22 24

2 4 6 8 10 12
S.L/R /M02.2 /M04.3 /M04.4 /R06.6 /R08.2 /R08.4

S.M/S/I /M02.3 /M02.2 /R08.2 /R08.2 /R08.3

C C
SELECTED SWITCH ."RAISE/OFF/LOWER" SA25/SALZER
SELECTED SWITCH "AUTO/MANUAL": SA25/SALZER SELECTED SWITCH "ON/OFF": SA25/SALZER

AUTO X X X ON X X X RAISE X X

MANUAL X X X OFF X X X LOWER X X

1 3 5 7 9 11 1 3 5 7 9 11 1 3 5 7
MANUAL

LOWER
RAISE
AUTO

OFF
ON
D D
2 4 6 8 10 12 2 4 6 8 10 12 2 4 6 8

-S.R/O/L /M02.2 /M02.3


S.A/M1 /R08.4 /R08.4 /M02.2 SCF1 /M04.4

S.A/M2 /M04.3 /M04.3 /M04.4 /R06.7 SCF2 /M04.6

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z10 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z11

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE CONTROL DEVICES PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

A A

Digital Meter -PTP FUNCTION -PTO FUNCTION


MT4W

Com (1÷20)
10
1 - 19 /R12.6 MODBUS PROTOCOL /R12.3 MODBUS PROTOCOL
9

+
= 3
B TEMPERATURE OF OIL TRANSFORMER B
4-20mA /Q02.1 TAP POSITTION SIGNAL /Q02.3
= _ 5

6
Hold Zero
7

~ 8
Power
Supply
24VDC /G02.4 POWER SUPPLY /G02.5 POWER SUPPLY
= 9

C C

Digital Meter -PTW1 FUNCTION -PTW2 FUNCTION


MT4W
Com (1÷20)

10
D 0-150°C /R12.4 MODBUS PROTOCOL /R12.5 MODBUS PROTOCOL D
9

+
= 3
4-20mA /Q02.5 TEMPERATURE OF 110KV WINDING /Q02.7 TEMPERATURE OF 22KV WINDING
= _ 5

6
Hold Zero
7
E E
~ 8
Power
Supply
24VDC /G02.6 POWER SUPPLY /G02.7 POWER SUPPLY
= 9

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z11 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z12

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE INDICATOR METTER PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

CURRENT TEST BLOCK


A Multi-function -PMF CHỨC NĂNG A
L1 L2 L3 ELITE
-KTT-AW4
XTC1 XTC2 XTC3
V1 /T01.5
S1 V1 VOLTAGE CIRCUIT PHASE A
1 2
S2

V2 /T01.5
S1 V2 VOLTAGE CIRCUIT PHASE B
3 4

EQUIPMENT
S2
B B
S1 /T01.1 /S04.4 /T02.1 V3 V3 /T01.6 VOLTAGE CIRCUIT PHASE C
5 6
S2

VN VN
7 8
S1
/T01.1
I1 CURRENT CIRCUIT BAY-PHASE A
S2

S1
/T01.2
C I2 CURRENT CIRCUIT BAY-PHASE B
C
S2

S1
VOLTAGE TEST BLOCK /T01.2
I3 CURRENT CIRCUIT BAY-PHASE C
S2
L1 L2 L3
-KTT-VW4
XTV1 XTV2 XTV3 XTV4
1a Tx
1 2 2
1n
RS485 RS232 Rx /R12.7 MODBUS PROTOCOL
D 3 D
1a GND
3 4 5
EQUIPMENT

1n

1a /T01.5 /S04.6 /T02.4 /T02.6


5 6
1n

7 8 + (L)
= P
E Power (~) E
Supply - (N) /G02.7 POWER SUPPLY
= N

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z12 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z13

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE CURRENT AND VOLTAGE TESTBLOCK PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

A A

TRIP SUPERVISION RELAY

5 6 1

B
VDF-10 B

K1 K2

C C

K3-1 K3-2
K1 K2 K3

D 9 13 10 14 12 4 8 2 D

-F741 TRIP CIRCUIRT SUPERVISOR 1 CB E01-QF01


/R06.3 /M05.3
/N01.7

-F742 /R06.4 TRIP CIRCUIRT SUPERVISOR 2 CB E01-QF01


/M05.3
/N02.7
E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z13 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z14

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE RELAY F74 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP1

RELAY TEST BLOCK


A A

TSB-14 XF871 XF872 XF67

1 2 /S01.1 /N01.4 /S03.1

3 4 /S01.2 /N02.3 /S03.2

B B
5 6 /S01.2 /N03.5 /S03.2

7 8 /S01.2 /N04.6 /S03.3

9 10 /S01.4 /N05.3 /N01.5

11 12 /S01.4 /N05.8 /N02.4


C C

13 14 /S01.4 /N11.4 /N03.6

15 16 /S01.5 /N11.5

17 18 /S01.6 /S03.7

D D
19 20 /S01.7 /S03.8

21 22 /S01.7 /S03.4

23 24 /S01.7 /S03.5

E E
25 26 /S03.5

27 28 /S03.5

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z14 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z15

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE RELAY TESTBLOCK PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

TC1 TC2
LOCAL CLOSE REMOTE AUTO LOCAL REMOTE P.D.
TC1 SF6 PRESSURE LOCAL REMOTE P.D.
TC2 SF6 PRESSURE
A SUPVN. SUPVN. SUPVN. SUPVN. A
INTELOCK CLOSE RECLOSE TRIP 1 TRIP 1 TRIP POST CLOSE ALARM & LOCKOUT TRIP 2 TRIP 2 TRIP POST CLOSE LOCKOUT
PRE CLOSE PRE CLOSE

220VDC1 TB1 15 14 TB1 18 19 TB1 17 220VDC2 TB1 22 TB1 16 TB1 11 12 TB1 13 220VDC3 TB1 27 TB1 26 TB1 23 24 TB1 25

MCB3 MCB4 MCB5


TB1 J1 K71 TB1 J3 K171 TB1 J1 K371
5 7 9
K13A K9 K17 K71
3
PBS1 3 3
4
PBS2 PBS2
4 TB1 20 TB1 21 4 TB1 30
3 1
B L 0 R
DMA DMA
B
K21 K13 K3 K5 K7 K321 K313 K303 K305 K307
43A
1 3 5
2
7 5 7 5
L O R L O R
K11 43A 43A
P1 P2 P2

K17 6 6

2 4 6

21
TB1 23 24 TB1 32
21
94
C 22 C

K701

31 31 21

A3 A3 A4
32
32 22
K703

31
A4
32
K17 K73 K173 K373
K705

D 9 13 1 D
S1 94 S1 11 13
10 2 3 5
14
K707
S1 S1 S1 S1
4 12 6 14
9
K25 K325
LS
10

K709
1 1
1 K79
52CC 52TC1 52TC2
A1 A1 A1 A1
2 2 2
94 A2 A3 A4
K74
A2 A2 A2 A2
E E
MCB3 MCB4 MCB5
TB1 J2 K72 TB1 J2 K172 TB1 J2 K372
6 8 10

TB1 31

=E01 -QF01 /M05.4 /N01.3 /N02.3

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z15 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z16

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CB REFERENCE (GL312F1/GE) PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A MOTOR CIRCUIT HEATING & LIGHTING CIRCUIT A

220VDC 220V AC
TB1
M1 (Ph)
TB1 MCB2
3 1 H1
1 2
MPCB1 1
2
B B
M3

H3
3

MPCB1
4

1
LS
2

1 1
C M5 C
DS TH
2 2
M7

X1 H5 H7
M A1

M TR1 X1 1
A2 IL H
X2
X2 2

M6

D D

LS
3

M4

6
220V AC
MPCB1 (N)
E 5
MCB2 E
TB1 TB1
M2 H2 H4
4
3 4
2

=E01 -QF01 /G04.3 /D03.3

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z16 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z17

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CB REFERENCE (GL312F1/GE) PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

CLOSING AND TRIPPING COIL 1 SUPPLY MCB TRIPPED ALARM


A A

HEATING AND LIGHTING SUPPLY MCB TRIPPED ALARM

TRIPPING COIL 1 SUPPLY MCB TRIPPED ALARM

TRIPPING COIL 2 SUPPLY MCB TRIPPED ALARM


MOTOR SUPPLY MCB TRIPPED ALARM

SF6 GAS 2ND STAGE (P2) LOCKOUT

SF6 GAS 2ND STAGE (P2) LOCKOUT

REMOTE POSITION SIEMENSECTED

SPRING CHARGE FAILURE ALARM


LOCAL POSITION SIEMENSECTED
SF6 GAS 1ST STAGE (P1) ALARM

SPRING CHARGED 1NDI ALARM.


B B

SPRING DISCHARGED ALARM


C C
TB1 30 TB1 32 TB1 34 TB1 36 TB1 38 TB1 40 TB1 42 TB1 44 TB1 47 TB1 48 TB1 49 TB1 51 TB2 49

X1-1 X1-3 X1-5 X1-7 X1-9 X3-11 X3-21 X4-2 X4-3 X5-1 X6-1 X7-1

15 13
L O R 15
11 11 11 11 11 13 13 13 11 5
43A
MPCB1 MCB2 MCB3 MCB4 MCB5 A2 A3 A4 LS TR1 LS
14 16 18
12 12 12 12 12 14 14 14 6
D 12 D
X1-2 X1-4 X1-6 X1-8 X1-10 X3-12 X3-22 X4-1 X5-2 X6-2 X7-2

TB1 31 TB1 33 TB1 35 TB1 37 TB1 39 TB1 41 TB1 43 TB1 45 TB1 46 TB1 50 TB1 52 TB2 50

=E01 -QF01 /R01.6 /R01.6 /R01.7 /R01.7 /R01.8 /R01.3 /R01.4 /R01.4 /R01.5 /R01.5
E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z17 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z18

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CB REFERENCE (GL312F1/GE) PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

B B

AUXILIARY CONTACTS

C MC SPARE AUXILIARY CONTACTS 12NO+12NC C

TB2 1 TB2 3 TB2 5 TB2 7 TB2 9 TB2 11 TB2 13 TB2 15 TB2 21 TB2 23 TB2 25 TB2 27 TB2 29 TB2 31 TB2 33 TB2 35 TB2 37 TB2 39 TB2 41 TB2 43 TB2 45 TB2 47
TB2 17 TB2 19

3 1 3 5 1 3 5 11
1 5 7 7 7 9 11 15 15 9 11 9 13 15
13 15
S2 S2
S3 S3 S3 S3 S4 S4 S4 S4 S4 S4
S2 S2 S2 S2 S1 S2 S3 S3 S3 S4 S4
S3
D 2
4 6 8
2 4 6 8
2 4 6 8 10 12 16 10 12 10 12 14 16
D
16 14 16

U20 U24 U28 U32


U35

TB2 2 TB2 4 TB2 6 TB2 8 TB2 10 TB2 12 TB2 14 TB2 18 TB2 22 TB2 26 TB2 28 TB2 30 TB2 32 TB2 34 TB2 36 TB2 38 TB2 40 TB2 44 TB2 46 TB2 48
TB2 16 TB2 20 TB2 24 TB2 42

=E01 -QF01 /N12.3 /R01.3 /Q01.5 /R11.2 /N12.4 /P01.6 /R01.2 /Q01.4 /R11.3

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z18 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z19

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CB REFERENCE (GL312F1/GE) PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

MOTOR CIRCUIT CMM 400/800 SIGNALLINGS HEATING & LIGHTING CIRCUIT SIGNALLINGS

A A

220VDC
-X1 1 2

1 3 5

-QM1
I> I> I>

2 4 6
B B

1 1 1
KM2 KM1 R3
2 2 2
C C
3 3 -1NC -1NC
KM2 KM1 KM1 KM2
4 4 -2NC -2NC

1
13 5 A1
-M1
M SQ100 KM2 -KA1
300W 14 6 A2
D 2 D

5
KM1
6

E E
=E01 - QL01 /G04.4 /R02.4 /R02.5 /D03.5 /R02.4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z19 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z20

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN DS REFERENCE PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

CONTROL CIRCUIT SIGNALLINGS


A A

220 VDC

B B

C C

D D

=E01 - QL01 /M01.5 /R02.4 /R02.3

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z20 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z21

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN DS REFERENCE PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A AUXILIARY CONTACTS A

DS CLOSED

B B

C C

DS OPENED

D D

=E01 -QL01 /P01.4 /P01.2 /N12.5 /N12.5 /Q01.6 /Q01.6 /R02.3 /R02.2 /P02.5 /P02.2 /P02.5
E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z21 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z22

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN DS REFERENCE PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

INTERLOCKING CIRCUIT HEATING CIRCUIT SIGNALLINGS


A A

B B

C C

D D

E E

- +QE15 /P02.3 /D03.6 /R02.7

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z22 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z23

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN ES REFERENCE PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

AUXILIARY CONTACTS

A A

B B

C C

D D

E E

- +QE15 /R02.6 /P01.6 /R02.6 /P02.5 /Q01.7 /Q01.7

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z23 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE +CRP1/X100

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN ES REFERENCE PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+CRP1-XAC A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E00 +FR -XAC 2 1 =E01 +CRP1 FQAC 1 +/D01.2
=E02 +CRP2 -XAC 1 2 +/D01.7
=E00 +FR -XAC 4 3 +/D01.2

B =E02 +CRP2 -XAC 3 4 +/D01.7 B


=E00 +FR -XAC 6 5 +/D01.2
=E02 +CRP2 -XAC 5 6 +/D01.7
=E00 +FR -XAC 8 7 =E01 +CRP1 FQAC 3 +/D01.2
=E02 +CRP2 -XAC 7 8 +/D01.7

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X100 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X101

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+CRP1-XAC PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+CRP1-XDC1 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E00 +FR -XDC1 2 1 =E01 +CRP1 FQDC1 1 +/G01.2
2 =E02 +CRP2 XDC1 1 +/G01.7
=E00 +FR -XDC1 4 3 =E01 +CRP1 FQDC1 3 +/G01.2

B 4 =E02 +CRP2 XDC1 3 +/G01.7 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X101 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X102

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+CRP1-XDC1 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+CRP1-XDC2 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E00 +FR -XDC2 2 1 =E01 +CRP1 FQDC2 1 +/G01.2
2 =E02 +CRP2 XDC2 1 +/G01.7
=E00 +FR -XDC2 4 3 =E01 +CRP1 FQDC2 3 +/G01.2

B 4 =E02 +CRP2 XDC2 3 +/G01.7 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X102 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X103

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+CRP1-XDC2 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+CRP1-XDC3 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +CRP1 -FQ87T 1 1 =E01 +CRP1 KQP1 2 +/G02.1
=E01 +CRP1 -FQBCU 1 2 +/G02.3
=E01 +CRP1 -FQPM 1 3 +/G02.4

B =E01 +CRP1 -FQSI 1 4 +/G02.6 B


=E01 +CRP1 -FQMF 1 5 +/G02.7
=E01 +CRP1 -FQ67 1 6 +/G03.1
=E01 +CRP1 -FQ90 1 7 +/G03.3
=E01 +CRP1 -FQTC2 1 8 +/G03.5
=E01 +CRP1 -FQTC1 1 9 +/G03.6
=E01 +CRP1 -FQCB 1 10 +/G03.8
=E01 +CRP1 -FQ87T 3 11 =E01 +CRP1 KQP1 8 +/G02.2
=E01 +CRP1 -FQBCU 3 12 +/G02.3
=E01 +CRP1 -FQPM 3 13 +/G02.4
C =E01 +CRP1 -FQSI 3 14 +/G02.6 C
=E01 +CRP1 -FQMF 3 15 +/G02.7
=E01 +CRP1 -FQ67 3 16 +/G03.2
=E01 +CRP1 -FQ90 3 17 +/G03.3
=E01 +CRP1 -FQTC2 3 18 +/G03.5
=E01 +CRP1 -FQTC1 3 19 +/G03.6
=E01 +CRP1 -FQCB 3 20 +/G03.8

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X103 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X104

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+CRP1-XDC3 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+CRP1-X3 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E00 +FR -X8 3 1 =E01 +CRP1 F87T-H-BO7 14 +/R11.5
=E00 +FR 23 2 =E01 +CRP1 F87T-H-BO7 15 +/R11.5
=E00 +FR 24 3 =E01 +CRP1 F67-H-BO7 15 +/R11.6

B =E00 +FR 25 4 =E01 +CRP1 F861-R 6 +/R11.7 B


=E00 +FR 26 5 =E01 +CRP1 F862-R 6 +/R11.7
=E00 +FR 27 6 =E01 +CRP1 KT1 12 +/R11.8
=E01 +MK -X3 1 7 =E01 +CRP1 BCU-E-DO1 2 +/M01.2
=E01 +MK 3 8 =E01 +CRP1 S.B/M-C1 2 +/M01.4
=E01 +MK 5 9 =E01 +CRP1 SQL01-C3 5 +/M01.5
=E01 +MK 6 10 =E01 +CRP1 SQL01-C4 7 +/M01.6
=T1 +LCB -X2 1 11 =E01 +CRP1 S.L/R-C3 5 +/M04.2
=T1 +LCB X2 2 12 =E01 +CRP1 S.A/M2-C1 2 +/M04.3
=T1 +LCB 4 13 =E01 +CRP1 SCF1-C1 2 +/M04.4
C =T1 +LCB 6 14 =E01 +CRP1 SCF2-C1 2 +/M04.6 C
=E01 +CRP1 BO5 9 15 =C41 +J01 XC 13 +/N05.2
=E05 +CRP5 15 16 =E01 +CRP1 KT1 7 +/N05.4
=C41 +J01 XC 14 17 =E01 +CRP1 XF872-C5 10 +/N05.3
18 =E05 +CRP5 X3 16 +/N05.4
=C41 +J01 XC 11 19 =E01 +CRP1 F87T-H-BO6 11 +/N05.6
=C41 +J01 XC 12 20 =E01 +CRP1 F87T-H-BO6 12 +/N05.7
=E05 +CRP5 X12 7 21 =E01 +CRP1 F87T-H-BO8 15 +/N11.2
=E05 +CRP5 X12 37 22 =E01 +CRP1 XF872-C7 14 +/N11.4
D 23 +/W01.1 D
24 +/W01.1
25 +/W01.2
26 +/W01.2
27 +/W01.2
28 +/W01.2
29 +/W01.2
30 +/W01.2

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X104 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X105

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+CRP1-X3 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+CRP1-X7 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
1 =E01 +CRP1 FQSI 2 +/G02.6
=E01 +MK -X7 1 2 =E01 +CRP1 S.LT-C1 3 +/Q01.4
3 +/Q01.4

B 4 =E01 +CRP1 FQSI 4 +/G02.6 B


5 =E01 +CRP1 KST2 13 +/Q01.2
6 =E01 +CRP1 PL01 X2 +/Q01.3
7 +/Q01.8
=E01 +MK -X7 5 8 =E01 +CRP1 SQF01-C5 9 +/Q01.4
=E01 +MK 6 9 =E01 +CRP1 SQF01-C6 11 +/Q01.5
=E01 +MK 7 10 =E01 +CRP1 SQL01-C5 9 +/Q01.6
=E01 +MK 8 11 =E01 +CRP1 SQL01-C6 11 +/Q01.6
=E01 +MK 9 12 =E01 +CRP1 SQE15 2 +/Q01.7
=E01 +MK 10 13 =E01 +CRP1 SQE15 1 +/Q01.7
C =T1 +OLTC AI04 11 14 =E01 +CRP1 PTP-AI 3 +/Q02.1 C
=T1 +OLTC 14 15 =E01 +CRP1 F90-AI1 64 +/Q02.2
=T1 +LCB X3 1 16 =E01 +CRP1 PTO-AI 3 +/Q02.3
=T1 +LCB X3 2 17 =E01 +CRP1 PTO-AI 5 +/Q02.4
=T1 +LCB 3 18 =E01 +CRP1 PTW1-AI 3 +/Q02.5
=T1 +LCB 4 19 =E01 +CRP1 PTW1-AI 5 +/Q02.6
=T1 +LCB 7 20 =E01 +CRP1 PTW2-AI 3 +/Q02.7
=T1 +LCB 8 21 =E01 +CRP1 PTW2-AI 5 +/Q02.7
22 +/W01.1
D 23 +/W01.1 D
24 +/W01.2
25 +/W01.2

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X105 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X106

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+CRP1-X7 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+CRP1-X8 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +CRP1 -PS 23 1 =E01 +CRP1 FQBCU 2 +/G02.3 =T1 +LCB X0 4 41 =E01 +CRP1 BCU-J-DI16 22 +/R04.7
=E01 +MK -X8 1 2 +/R01.2 =T1 +LCB X0 6 42 =E01 +CRP1 BCU-K-DI1 1 +/R05.2
=E05 +CRP5 -X3 47 3 +/R04.2 =T1 +LCB 14 43 =E01 +CRP1 BCU-K-DI2 2 +/R05.4

B =C41 +J01 -XY 15 4 +/R04.2 =T1 +LCB 22 44 =E01 +CRP1 BCU-K-DI3 4 +/R05.6 B
5 +/R04.6 =T1 +LCB 25 45 =E01 +CRP1 BCU-K-DI4 5 +/R05.6
6 =E01 +CRP1 F861-R 51 +/R04.8 =T1 +LCB X6 28 46 =E01 +CRP1 BCU-K-DI5 7 +/R05.7
=E01 +CRP1 -PS 24 7 =E01 +CRP1 FQBCU 4 +/G02.3 47 =E01 +CRP1 BCU-K-DI6 8 +/R05.7
=E01 +CRP1 DI1 3 8 +/R01.2 =E01 +CRP1 DI4 5 48 +/R07.4
9 +/R01.3 =E01 +CRP1 DI5 7 49 +/R07.5
=E01 +MK X8 4 10 =E01 +CRP1 BCU-I-DI1 1 +/R01.2 =E01 +CRP1 DI6 8 50 +/R07.6
=E01 +MK 5 11 =E01 +CRP1 BCU-I-DI2 2 +/R01.3 =E01 +CRP1 DI7 10 51 +/R07.6
=E01 +MK 6 12 =E01 +CRP1 BCU-I-DI3 4 +/R01.3 =E01 +CRP1 DI8 11 52 +/R07.7
=E01 +MK 7 13 =E01 +CRP1 BCU-I-DI4 5 +/R01.4 53 +/W01.1
C =E01 +MK 8 14 =E01 +CRP1 BCU-I-DI5 7 +/R01.5 54 +/W01.1 C
=E01 +MK 9 15 =E01 +CRP1 BCU-I-DI6 8 +/R01.5 55 +/W01.2
=E01 +MK 10 16 =E01 +CRP1 BCU-I-DI7 10 +/R01.6 56 +/W01.2
17 =E01 +CRP1 BCU-I-DI8 11 +/R01.7 57 +/W01.2
=E01 +MK -X8 11 18 =E01 +CRP1 BCU-I-DI9 13 +/R02.2 58 +/W01.2
=E01 +MK 12 19 =E01 +CRP1 BCU-I-DI10 14 +/R02.3 59 +/W01.2
=E01 +MK 13 20 =E01 +CRP1 BCU-I-DI11 16 +/R02.3 60 +/W01.2
=E01 +MK 14 21 =E01 +CRP1 BCU-I-DI12 17 +/R02.4
=E01 +MK 15 22 =E01 +CRP1 BCU-I-DI13 19 +/R02.6
D =E01 +MK 16 23 =E01 +CRP1 BCU-I-DI14 20 +/R02.6 D
=E01 +MK 17 24 =E01 +CRP1 BCU-I-DI15 22 +/R02.7
25 =E01 +CRP1 BCU-I-DI16 23 +/R02.7
=E01 +MK -X8 18 26 =E01 +CRP1 BCU-J-DI1 1 +/R03.2
=E01 +MK 19 27 =E01 +CRP1 BCU-J-DI2 2 +/R03.3
=E01 +MK 20 28 =E01 +CRP1 BCU-J-DI3 4 +/R03.4
29 =E01 +CRP1 BCU-J-DI4 5 +/R03.4
30 =E01 +CRP1 BCU-J-DI5 7 +/R03.5
31 =E01 +CRP1 BCU-J-DI6 8 +/R03.6

E 32 =E01 +CRP1 BCU-J-DI7 10 +/R03.6 E


33 =E01 +CRP1 BCU-J-DI8 11 +/R03.7
=E05 +CRP5 48 34 =E01 +CRP1 BCU-J-DI9 13 +/R04.2
=C41 +J01 -XY 90 35 =E01 +CRP1 BCU-J-DI10 14 +/R04.2
=C41 +J01 -XY 16 36 =E01 +CRP1 BCU-J-DI11 16 +/R04.3
=C41 +J01 -X3 22 37 =E01 +CRP1 BCU-J-DI12 17 +/R04.4
=C41 +J01 -X3 22 38 =E01 +CRP1 BCU-J-DI13 19 +/R04.4
=C41 +J01 -X3 22 39 =E01 +CRP1 BCU-J-DI14 20 +/R04.5
=T1 +LCB X0 2 40 =E01 +CRP1 BCU-J-DI15 21 +/R04.6

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X106 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X107

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+CRP1-X8 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+CRP1-X9 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +CRP1 9 1 =E02 +CRP2 X9 5 +/R12.3
=E01 +CRP1 9 2 +/R12.4
=E01 +CRP1 9 3 +/R12.5

B =E01 +CRP1 9 4 +/R12.6 B


=E01 +CRP1 2 5 =N00 +AC X9 1 +/R12.7
=E01 +CRP1 10 6 =E02 +CRP2 X9 10 +/R12.3
=E01 +CRP1 10 7 +/R12.4
=E01 +CRP1 10 8 +/R12.5
=E01 +CRP1 10 9 +/R12.6
=E01 +CRP1 3 10 =N00 +AC X9 3 +/R12.7

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X107 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X108

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+CRP1-X9 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+CRP1-X10 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +MK -X10 5 1 =E01 +CRP1 FQTC1 2 +/G03.6
2 =E01 +CRP1 S.B/M-C8 15 +/N01.2
3 =E01 +CRP1 F87T-H-BO1 1 +/N01.4

B =E01 +MK 6 4 =E01 +CRP1 FQTC1 4 +/G03.6 B


5 =E01 +CRP1 F741-K 2 +/N01.7
6 +/N01.8
=E01 +MK X10 1 7 =E01 +CRP1 BCU-E-DO4 8 +/N01.3
=E01 +MK -X10 2 8 =E01 +CRP1 XF872-C1 2 +/N01.4
=E05 +CRP5 X3 10 9 +/N03.2
=E01 +MK -X10 3 10 =E01 +CRP1 F741-K 4 +/N01.7
=E01 +MK -X10 4 11 =E01 +CRP1 F741-K 8 +/N01.7
=E01 +CRP1 -K 1 12 =E05 +CRP5 X3 9 +/N03.2
=E01 +CRP1 -K81 7 13 =E01 +CRP1 KT1 5 +/N03.4
C =E05 +CRP5 11 14 +/N03.3 C
=E01 +CRP1 -KT1 9 15 =E01 +CRP1 K81 11 +/N03.4
16 +/W01.1
17 +/W01.1
18 +/W01.2
19 +/W01.2
20 +/W01.2

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X108 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X109

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+CRP1-X10 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+CRP1-X11 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +MK X11 1 1 =E01 +CRP1 FQCB 2 +/G03.8
2 =E01 +CRP1 F861-S 10 +/M05.3
=E01 +MK X11 2 3 =E01 +CRP1 FQCB 4 +/G03.8

B =E01 +CRP1 BI1 1 4 +/M05.5 B


5 +/M05.6
=E01 +MK X11 7 6 =E01 +CRP1 F67-D-BI1 2 +/M05.5
=E01 +MK X11 9 7 =E01 +CRP1 S.25-C2 4 +/M05.7
8 +/W01.1
9 +/W01.1
10 +/W01.2
11 +/W01.2
12 +/W01.2
13 +/W01.2
C 14 +/W01.2 C
15 +/W01.2

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X109 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X110

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+CRP1-X11 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+CRP1-X12 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +CRP1 -PS 2 1 =E01 +CRP1 FQ87T 2 +/G02.1
=T1 +LCB X5 9 2 +/N07.2
3 =T1 +LCB X6 6 +/N10.2

B 4 +/N10.3 B
=E01 +CRP1 -PS 1 5 =E01 +CRP1 FQ87T 4 +/G02.2
6 =E01 +CRP1 F87T-D-BI1 1 +/N07.2
=E01 +CRP1 -KT1 13 7 +/N07.2
=T1 +LCB X5 11 8 =E01 +CRP1 F87T-D-BI1 2 +/N07.2
=T1 +LCB 12 9 =E01 +CRP1 F87T-D-BI2 4 +/N07.3
=T1 +LCB 13 10 =E01 +CRP1 F87T-D-BI3 6 +/N07.3
=T1 +LCB 14 11 =E01 +CRP1 F87T-D-BI4 8 +/N07.4
=T1 +LCB 15 12 =E01 +CRP1 F87T-D-BI5 10 +/N07.4
=T1 +LCB 16 13 =E01 +CRP1 F87T-D-BI6 12 +/N07.5
C =T1 +LCB 17 14 =E01 +CRP1 F87T-D-BI7 14 +/N07.5 C
=T1 +LCB 18 15 =E01 +CRP1 F87T-D-BI8 16 +/N07.6
=T1 +LCB -X6 11 16 =E01 +CRP1 F87T-F-BI9 2 +/N10.2
=T1 +LCB 12 17 =E01 +CRP1 F87T-F-BI10 4 +/N10.3
=T1 +LCB 13 18 =E01 +CRP1 F87T-F-BI11 6 +/N10.3
=T1 +LCB 14 19 =E01 +CRP1 F87T-F-BI12 8 +/N10.4
=T1 +LCB 15 20 =E01 +CRP1 F87T-F-BI13 10 +/N10.5
=T1 +LCB 20 21 =E01 +CRP1 F87T-F-BI14 12 +/N10.5
=T1 +LCB 27 22 =E01 +CRP1 F87T-F-BI15 14 +/N10.6
D =T1 +LCB 34 23 =E01 +CRP1 F87T-F-BI16 16 +/N10.7 D
24 +/W01.1
25 +/W01.1
26 +/W01.2
27 +/W01.2
28 +/W01.2
29 +/W01.2
30 +/W01.2

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X110 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X111

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+CRP1-X12 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+CRP1-X20 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +MK -X20 4 1 =E01 +CRP1 FQTC2 2 +/G03.5
2 =E01 +CRP1 XF872-C2 3 +/N02.3
=E05 +CRP5 12 3 +/N04.2

B =C41 +J01 XC 55 4 +/N04.3 B


=E01 +CRP1 -KT1 6 5 =E01 +CRP1 K81 8 +/N04.4
=E01 +MK 5 6 =E01 +CRP1 FQTC2 4 +/G03.5
7 =E01 +CRP1 F742-K 2 +/N02.7
8 +/N02.8
=E01 +MK X20 1 9 =E01 +CRP1 F87T-H-BO2 4 +/N02.3
=E05 +CRP5 13 10 +/N04.2
=E01 +MK 2 11 =E01 +CRP1 F742-K 4 +/N02.7
=E01 +MK 3 12 =E01 +CRP1 F742-K 8 +/N02.7
=E05 +CRP5 14 13 +/N04.2
C =C41 +J01 XC 56 14 +/N04.3 C
=E01 +CRP1 -KT1 10 15 =E01 +CRP1 K81 12 +/N04.4
16 =E01 +CRP1 K81 8 +/N04.7
17 +/W01.1
18 +/W01.1
19 +/W01.2
20 +/W01.2

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X111 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X112

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+CRP1-X20 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+CRP1-X21 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +CRP1 -PS J2 1 =E01 +CRP1 FQ67 2 +/G03.1
2 =E01 +CRP1 BCU-A-WD 5 +/N06.1
3 =C41 +J01 XY 23 +/N06.4

B 4 +/N06.4 B
=E01 +CRP1 -PS J1 5 =E01 +CRP1 FQ67 4 +/G03.2
6 =E01 +CRP1 F67-D-BI2 3 +/N06.1
7 +/N06.2
=E01 +CRP1 BI6 12 8 =C41 +J01 XY 24 +/N06.4
=E01 +CRP1 BI7 14 9 +/N06.4
=E01 +CRP1 BI8 16 10 +/N06.5
=E01 +CRP1 BI9 2 11 +/N06.5
=E01 +CRP1 BI10 4 12 +/N06.6
=E01 +CRP1 BI11 6 13 +/N06.6
C =E01 +CRP1 BI12 8 14 +/N06.7 C
=E01 +CRP1 BI13 10 15 +/N06.7
=E01 +CRP1 BI14 12 16 +/N06.8
=E01 +CRP1 BI15 14 17 +/N06.8
18 +/W01.1
19 +/W01.1
20 +/W01.2
21 +/W01.2
22 +/W01.2
D 23 +/W01.2 D
24 +/W01.2
25 +/W01.2

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X112 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X113

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+CRP1-X21 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+CRP1-X22 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +CRP1 -PS 21 1 =E01 +CRP1 FQ90 2 +/G03.3
2 =E01 +CRP1 S.M/S/I-C3 5 +/M02.2
3 =E01 +CRP1 F90-R1 45 +/M02.5

B 4 =T1 +OLTC X1 276 +/R09.3 B


5 =E01 +CRP1 S.L/R-C7 13 +/R09.4
=E01 +CRP1 -PS 22 6 =E01 +CRP1 FQ90 4 +/G03.3
7 =E01 +CRP1 F90-E7 20 +/M02.2
8 =E01 +CRP1 KSCR 13 +/M02.5
9 +/M02.7
=T1 +OLTC -X1 12 10 =E01 +CRP1 KSCL 5 +/M03.2
=T1 +OLTC -X1 10 11 =E01 +CRP1 KSCR 10 +/M03.3
=T1 +OLTC -X1 11 12 =E01 +CRP1 KSCL 10 +/M03.4
=T1 +OLTC -X1 14 13 =E01 +CRP1 BCU-D-DO1 1 +/M03.4
C =T1 +OLTC -X1 15 14 =E01 +CRP1 BCU-D-DO1 2 +/M03.5 C
=E01 +CRP1 E1 11 15 =T1 +OLTC X1 300 +/R09.3
=E01 +CRP1 E9 23 16 +/R09.3
=E01 +CRP1 E10 24 17 +/R09.4
=E01 +CRP1 E11 25 18 +/R09.4
=E01 +CRP1 E12 26 19 +/R09.5
=E01 +CRP1 E13 28 20 +/R09.5
=E01 +CRP1 E14 29 21 +/R09.6
=E01 +CRP1 E15 30 22 +/R09.6
D =E01 +CRP1 E16 31 23 +/R09.7 D
24 +/W01.1
25 +/W01.1
26 +/W01.2
27 +/W01.2
28 +/W01.2
29 +/W01.2
30 +/W01.2

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X113 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X114

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+CRP1-X22 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+CRP1-X42 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=T1 +LCB X4 A21 1 =E01 +CRP1 XF67-C1 1 +/S03.1
=T1 +LCB B21 2 =E01 +CRP1 XF67-C2 3 +/S03.2
=T1 +LCB C21 3 =E01 +CRP1 XF67-C3 5 +/S03.2

B =T1 +LCB A24 4 =E01 +CRP1 XF67-C4 7 +/S03.3 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X114 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X115

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+CRP1-X42 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+CRP1-X43 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=T1 +LCB X4 A31 1 =E01 +CRP1 XTC2 1 +/S04.4
=T1 +LCB X4 A34 2 =E01 +CRP1 XTC2 3 +/S04.5

B B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X115 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X116

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+CRP1-X43 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+CRP1-X44 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=T1 +LCB X4 A21 1 =E01 +CRP1 XTC1 1 +/T01.1
=T1 +LCB B21 2 =E01 +CRP1 XTC1 3 +/T01.2
=T1 +LCB C21 3 =E01 +CRP1 XTC1 5 +/T01.2

B =T1 +LCB A24 4 =E01 +CRP1 XTC1 7 +/T01.3 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X116 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X117

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+CRP1-X44 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+CRP1-X45 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +CRP1 IA.1A 16 1 =E00 +FR X46 1 +/T02.2
=E01 +CRP1 IB.1A 12 2 =E00 +FR X46 2 +/T02.2
=E01 +CRP1 IC.1A 8 3 =E00 +FR X46 3 +/T02.2

B =E01 +CRP1 IN.1A 4 4 =E00 +FR X46 4 +/T02.3 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X117 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X118

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+CRP1-X45 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+CRP1-X51 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +CRP1 1 1 =E03 +CRP3 X54 2 +/T01.5
2 =E00 +FR X56 1 +/T01.7
=E01 +CRP1 3 3 =E03 +CRP3 X54 4 +/T01.5

B 4 =E00 +FR X56 2 +/T01.7 B


=E01 +CRP1 5 5 =E03 +CRP3 X54 6 +/T01.6
6 =E00 +FR X56 3 +/T01.8
=E01 +CRP1 7 7 =E03 +CRP3 X54 8 +/T01.6
8 =E00 +FR X56 4 +/T01.8

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X118 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X119

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+CRP1-X51 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+CRP1-X52 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +CRP1 C11 21 1 =E03 +CRP3 X52 2 +/S03.4
2 =E00 +FR X51 1 +/S03.6
=E01 +CRP1 C12 23 3 =E03 +CRP3 X52 4 +/S03.5

B 4 =E00 +FR X51 2 +/S03.6 B


=E01 +CRP1 C13 25 5 =E03 +CRP3 X52 6 +/S03.5
6 =E00 +FR X51 3 +/S03.6
=E01 +CRP1 C14 27 7 =E03 +CRP3 X52 8 +/S03.5
8 =E00 +FR X51 4 +/S03.7

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X119 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X120

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+CRP1-X52 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+CRP1-X53 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +CRP1 1 1 =C41 +J01 XY 25 +/S04.6
=E01 +CRP1 1 2 =C41 +J01 XY 26 +/S04.6
3 =C41 +J01 XY 27 +/S04.7

B =E01 +CRP1 3 4 =C41 +J01 XY 28 +/S04.7 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X120 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X121

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+CRP1-X53 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+CRP1-X54 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +CRP1 C9 17 1 =C41 +J01 XY 20 +/S03.7
=E01 +CRP1 C10 19 2 =C41 +J01 XY 22 +/S03.8

B B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X121 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X122

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+CRP1-X54 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+CRP1-X91 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +CRP1 C2 4 1 +/N13.2
=E03 +CRP3 -X91 1 2 +/N13.7
=E01 +CRP1 C3 6 3 +/N13.2

B =E03 +CRP3 -X91 3 4 +/N13.7 B


=E01 +CRP1 C4 8 5 +/N13.2
=E03 +CRP3 -X91 5 6 +/N13.7
=E01 +CRP1 C5 10 7 +/N13.2
=E03 +CRP3 -X91 7 8 +/N13.7
=E01 +CRP1 -K81 13 9 +/N13.2
=E03 +CRP3 -X91 9 10 +/N13.7

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X122 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X123

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+CRP1-X91 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+CRP1-X410 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +MK -X41 1 1 =E01 +CRP1 XF871-C1 1 +/S01.1
=E01 +MK 2 2 =E01 +CRP1 XF871-C2 3 +/S01.2
=E01 +MK 3 3 =E01 +CRP1 XF871-C3 5 +/S01.2

B =E01 +MK 4 4 =E01 +CRP1 XF871-C4 7 +/S01.2 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X123 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X124

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+CRP1-X410 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+CRP1-X411 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=T1 +LCB X4 O21 1 =E01 +CRP1 XF871-C5 9 +/S01.4
=T1 +LCB O24 2 =E01 +CRP1 XF871-C6 11 +/S01.4

B B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X124 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X125

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+CRP1-X411 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+CRP1-X412 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=T1 +LCB X4 1O21 1 =E01 +CRP1 XF871-C7 13 +/S01.4
=T1 +LCB 1O23 2 =E01 +CRP1 XF871-C8 15 +/S01.5

B B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X125 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X126

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+CRP1-X412 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+CRP1-X413 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=C41 +J01 XIC 5 1 =E01 +CRP1 XF871-C9 17 +/S01.6
=C41 +J01 XIC 6 2 =E01 +CRP1 XF871-C10 19 +/S01.7
=C41 +J01 XIC 7 3 =E01 +CRP1 XF871-C11 21 +/S01.7

B =C41 +J01 XIC 8 4 =E01 +CRP1 XF871-C12 23 +/S01.7 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X126 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE +MK/X100

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+CRP1-X413 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+MK-XAC A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=N00 +AC 37 1 =E01 +MK FQAC1 1 +/D02.2
=E03 +MK -XAC 1 2 +/D02.6
3 =N00 +AC XT1 38 +/D02.2

B =E03 +MK -XAC 3 4 =E01 +MK FQAC2 1 +/D02.6 B


5 =N00 +AC XT1 39 +/D02.2
=E03 +MK -XAC 5 6 +/D02.6
=E01 +MK -FQAC1 3 7 =N00 +AC XT1 40 +/D02.2
=E03 +MK -XAC 8 8 =E01 +MK FQAC2 3 +/D02.6

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X100 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X101

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+MK-XAC PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+MK-XAC1 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +QF01 TB1 1 1 =E01 +MK FQAC2 2 +/D03.3
=E01 +QL01 -X1 20 2 =E01 +QE15 XT2 20 +/D03.4
=E01 +QF01 2 3 =E01 +MK FQAC2 4 +/D03.3

B =E01 +QL01 21 4 =E01 +QE15 XT2 21 +/D03.5 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X101 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X102

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+MK-XAC1 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+MK-XDC A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +MK -XDC 2 1 =E01 +MK FQCB 1 +/G04.2
2 =E01 +MK FQDS 1 +/G04.8
=E02 +MK -XDC 4 3 =E01 +MK FQCB 3 +/G04.2

B 4 =E01 +MK FQDS 3 +/G04.8 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X102 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X103

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+MK-XDC PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+MK-XDC1 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +QF01 X1 450 1 =E01 +MK FQCB 2 +/G04.3
=E01 +QF01 -X1 460 2 =E01 +MK FQCB 4 +/G04.3

B B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X103 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X104

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+MK-XDC1 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+MK-XDC2 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +QL01 -X1 1 1 =E01 +MK FQDS 2 +/G04.4
=E01 +MK -X3 17 2 +/G04.5
=E01 +QL01 2 3 =E01 +MK FQDS 4 +/G04.4

B =E01 +MK -X3 20 4 +/G04.5 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X104 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X105

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+MK-XDC2 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+MK-X3 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +QL01 -X1 4A 1 =E01 +CRP1 X3 7 +/M01.2
=E01 +QF01 -TB2 27 2 +/P01.6
=E01 +QL01 -X1 4B 3 =E01 +CRP1 X3 8 +/M01.4

B 4 =E05 +MK X3 29 +/P01.7 B


=E01 +QL01 -X1 8 5 =E01 +CRP1 X3 9 +/M01.5
=E01 +QL01 -X1 7 6 =E01 +CRP1 X3 10 +/M01.6
=E01 +QF01 TB2 1 7 =E05 +CRP5 X12 2 +/N12.3
=E01 +QL01 -X2 13 8 +/N12.5
9 +/N12.5
=E05 +CRP5 X12 15 10 =E01 +QF01 TB2 2 +/N12.3
=E05 +CRP5 16 11 =E01 +QF01 TB2 26 +/N12.4
=E05 +CRP5 17 12 =E01 +QL01 X2 14 +/N12.5
=E05 +CRP5 18 13 =E01 +QL01 X2 16 +/N12.5
C =E01 +QE15 -XT2 3 14 =E01 +QF01 TB2 28 +/P01.6 C
=C41 +J01 XE 5 15 =E01 +QE15 XT2 4 +/P01.6
=E05 +MK -X3 28 16 =C41 +J01 XE 6 +/P01.7
=E01 +QL01 -X2 31 17 =E01 +MK XDC2 2 +/P02.2
=C41 +J01 -X... ... 18 =E01 +QL01 X2 32 +/P02.2
=E01 +QE15 -XT2 1 19 =C41 +J01 X... ... +/P02.2
=E01 +QE15 2 20 =E01 +MK XDC2 4 +/P02.3
=E05 +MK -X3 47 21 =E01 +QL01 X2 35 +/P02.6
=E05 +MK -X3 48 22 =E01 +QL01 X2 36 +/P02.6
D =C41 +J01 -XC 7 23 =E01 +QL01 X2 27 +/P02.6 D
=C41 +J01 -XC 8 24 =E01 +QL01 X2 28 +/P02.6
=C41 +J01 -XC 3 25 =E01 +QE15 XT2 27 +/P02.6
=C41 +J01 -XC 4 26 =E01 +QE15 XT2 28 +/P02.6
=E01 +QF01 TB2 9 27 =E00 +FR X8 2 +/R11.2
28 +/R11.3
=E00 +FR 22 29 =E01 +QF01 TB2 10 +/R11.2
=E00 +FR X8 21 30 =E01 +QF01 TB2 34 +/R11.3
31 +/W01.6

E 32 +/W01.6 E
33 +/W01.6
34 +/W01.6
35 +/W01.6
36 +/W01.6
37 +/W01.7
38 +/W01.7
39 +/W01.7
40 +/W01.7

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X105 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X106

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+MK-X3 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+MK-X7 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +QF01 TB2 31 1 =E01 +CRP1 X7 2 +/Q01.4
=E01 +QL01 -X2 19 2 +/Q01.6
=E01 +QE15 -XT2 19 3 +/Q01.7

B 4 +/Q01.7 B
=E01 +QF01 TB2 32 5 =E01 +CRP1 X7 8 +/Q01.4
=E01 +QF01 TB2 6 6 =E01 +CRP1 X7 9 +/Q01.5
=E01 +QL01 -X2 20 7 =E01 +CRP1 X7 10 +/Q01.6
=E01 +QL01 18 8 =E01 +CRP1 X7 11 +/Q01.6
=E01 +QE15 -XT2 20 9 =E01 +CRP1 X7 12 +/Q01.7
=E01 +QE15 18 10 =E01 +CRP1 X7 13 +/Q01.7
11 +/W01.6
12 +/W01.6
13 +/W01.6
C 14 +/W01.6 C
15 +/W01.6

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X106 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X107

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+MK-X7 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+MK-X8 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +QF01 TB2 29 1 =E01 +CRP1 X8 2 +/R01.2
=E01 +QL01 X2 23 2 +/R02.2
=E01 +QE15 XT2 7 3 =E01 +MK FQAC1 12 +/R02.6

B =E01 +QF01 TB2 20 4 =E01 +CRP1 X8 10 +/R01.2 B


=E01 +QF01 4 5 =E01 +CRP1 X8 11 +/R01.3
=E01 +QF01 TB1 41 6 =E01 +CRP1 X8 12 +/R01.3
=E01 +QF01 -TB1 43 7 =E01 +CRP1 X8 13 +/R01.4
=E01 +QF01 52 8 =E01 +CRP1 X8 14 +/R01.5
=E01 +QF01 47 9 =E01 +CRP1 X8 15 +/R01.5
=E01 +QF01 31 10 =E01 +CRP1 X8 16 +/R01.6
=E01 +QL01 X2 24 11 =E01 +CRP1 X8 18 +/R02.2
=E01 +QL01 -X2 22 12 =E01 +CRP1 X8 19 +/R02.3
=E01 +QL01 -X2 80 13 =E01 +CRP1 X8 20 +/R02.3
C =E01 +QL01 -X2 84 14 =E01 +CRP1 X8 21 +/R02.4 C
=E01 +QE15 XT2 8 15 =E01 +CRP1 X8 22 +/R02.6
=E01 +QE15 -XT2 2 16 =E01 +CRP1 X8 23 +/R02.6
=E01 +QE15 -XT2 88 17 =E01 +CRP1 X8 24 +/R02.7
=E01 +MK -FQAC1 11 18 =E01 +CRP1 X8 26 +/R03.2
=E01 +MK -FQCB 11 19 =E01 +CRP1 X8 27 +/R03.3
=E01 +MK -FQAC1 95 20 =E01 +CRP1 X8 28 +/R03.4
21 +/W01.6
22 +/W01.6
D 23 +/W01.6 D
24 +/W01.6
25 +/W01.6
26 +/W01.6
27 +/W01.7
28 +/W01.7
29 +/W01.7
30 +/W01.7

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X107 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X108

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+MK-X8 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+MK-X10 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +QF01 TB1 16 1 =E01 +CRP1 X10 7 +/N01.3
=E01 +QF01 TB1 11 2 =E01 +CRP1 X10 8 +/N01.4
=E01 +QF01 TB1 12 3 =E01 +CRP1 X10 10 +/N01.7

B =E01 +QF01 TB1 13 4 =E01 +CRP1 X10 11 +/N01.7 B


=E01 +QF01 -TB1 7 5 =E01 +CRP1 X10 1 +/G03.6
=E01 +QF01 -TB1 8 6 =E01 +CRP1 X10 4 +/G03.6
7 +/W01.6
8 +/W01.6
9 +/W01.6
10 +/W01.6
11 +/W01.6
12 +/W01.6
13 +/W01.7
C 14 +/W01.7 C
15 +/W01.7

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X108 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X109

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+MK-X10 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+MK-X11 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +QF01 -TB1 5 1 =E01 +CRP1 X11 1 +/G03.8
=E01 +QF01 -TB1 6 2 =E01 +CRP1 X11 3 +/G03.8
=E01 +QF01 -TB1 14 3 +/M05.2

B =E01 +QL01 -X2 3 4 +/P01.2 B


=E01 +QF01 -TB1 15 5 +/M05.3
6 =C41 +J01 XB 6 +/P01.2
=E01 +QF01 TB1 18 7 =E01 +CRP1 X11 6 +/M05.5
8 =C41 +J01 XB 4 +/P01.4
=E01 +QL01 -X2 1 9 =E01 +CRP1 X11 7 +/M05.7
=C41 +J01 -XB 5 10 =E01 +QL01 X2 4 +/P01.2
=C41 +J01 -XB 3 11 =E01 +QL01 X2 2 +/P01.4
12 +/W01.6
13 +/W01.6
C 14 +/W01.6 C
15 +/W01.6
16 +/W01.6
17 +/W01.6
18 +/W01.7
19 +/W01.7
20 +/W01.7

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X109 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X110

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+MK-X11 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+MK-X20 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +QF01 TB1 23 1 =E01 +CRP1 X20 9 +/N02.3
=E01 +QF01 TB1 24 2 =E01 +CRP1 X20 11 +/N02.7
=E01 +QF01 TB1 25 3 =E01 +CRP1 X20 12 +/N02.7

B =E01 +QF01 -TB1 9 4 =E01 +CRP1 X20 1 +/G03.5 B


=E01 +QF01 -TB1 10 5 =E01 +CRP1 X20 6 +/G03.5
6 +/W01.6
7 +/W01.6
8 +/W01.6
9 +/W01.6
10 +/W01.6
11 +/W01.6
12 +/W01.7
14 +/W01.7
C 13 +/W01.7 C
15 +/W01.7

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X110 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X111

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+MK-X20 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+MK-X41 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +CT-PA +CT-PA-PA 1S1 1 =E01 +CRP1 X410 1 +/S01.1
=E01 +CT-PB +CT-PB-PB 1S1 2 =E01 +CRP1 X410 2 +/S01.2
=E01 +CT-PC +CT-PC-PC 1S1 3 =E01 +CRP1 X410 3 +/S01.2

B =E01 +CT-PC 1S4 4 =E01 +CRP1 X410 4 +/S01.2 B


5 =E01 +CT-PB PB 1S4 +/S01.2
=E01 +MK PE 6 =E01 +CT-PA PA 1S4 +/S01.3

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X111 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X112

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+MK-X41 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+MK-X42 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +CT-PA +CT-PA-PA 2S1 1 =E00 +FR X41 1 +/S02.2
=E01 +CT-PB +CT-PB-PB 2S1 2 =E00 +FR X41 2 +/S02.2
=E01 +CT-PC +CT-PC-PC 2S1 3 =E00 +FR X41 3 +/S02.3

B =E01 +CT-PC 2S4 4 =E00 +FR X41 4 +/S02.3 B


=E01 +CT-PB +CT-PB-PB 2S4 5 +/S02.3
=E01 +CT-PA +CT-PA-PA 2S4 6 =E01 +MK PE +/S02.3

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X112 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X113

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+MK-X42 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E01+MK-X45 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +CT-PA 5S1 1 =E05 +CRP5 X451 1 +/S02.6
=E01 +CT-PB +CT-PB-PB 5S1 2 =E05 +CRP5 X451 2 +/S02.6
=E01 +CT-PC +CT-PC-PC 5S1 3 =E05 +CRP5 X451 3 +/S02.6

B =E01 +CT-PC 5S4 4 =E05 +CRP5 X451 4 +/S02.6 B


=E01 +CT-PB +CT-PB-PB 5S4 5 +/S02.7
=E01 +CT-PA +CT-PA-PA 5S4 6 =E01 +MK PE +/S02.7

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E01


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X113 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE =E02+/A00

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T1 - 131 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E01+MK-X45 PECC2/TT-110KV/E01-131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

B B

B 24/11/2020 2nd FOR APPROVED

A 12/10/2020 1st FOR APPROVED

REV. DATE DESCRIPTION

CUSTOMER

C C
POWER ENGINEERING CONSULTING J.S.C. 2

PROJECT

TAN THUAN OFFSHORE WIND POWER PLANT

D D

LOCATION

TAN THUAN OFFSHORE WIND POWER PLANT

DRAW. NAME STAMP

E =E02+CRP2: CONTROL&PROTECTION PANEL FOR TRANS. T2 E


=E02+MK: MARSHALLING KIOSK FOR TRANS. BAY

DRAWING NO. PECC2/TT-110KV/E02-132

STANDARD: IEC PAGE: A00 TOTAL NO. OF PAGE: 89

DESIGNED NGUYEN VAN NHAT CONTRACTOR

CHECKED NGUYEN VAN CHUNG


F F
APPROVED NGUYEN DINH TUAN
ENERGY TECHNOLOGY
JOINT STOCK COMPANNY
DATE 24/11/2020 Rev.: B

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

PAGE DESCRIPTION REV. X PAGE DESCRIPTION REV. X

=E02/A00 WIRING DIAGRAMS FOR 110KV TRANSFORMER BAY B =E02/N05 SEND TRIP CIRCUIT B
A A
=E02/A01 TABLE OF CONTENTS : =E02/A00 - =E02/W01 B =E02/N06 BINNARY INPUT F67 B
=E02/A01.a TABLE OF CONTENTS : =E02/Z01 - =E02+MK/X113 B =E02/N07 INTERNAL PROTECTION TRANSFORMER TRIP B
=E02/A02 DEVICE SYMBOL B =E02/N08 INTERNAL PROTECTION TRANSFORMER TRIP B
=E02/A03 FUNCTION SYMBOL B =E02/N09 INTERNAL PROTECTION TRANSFORMER TRIP B
=E02/A04 SECONDARY CIRCUIT SYMBOL B =E02/N10 BINNARY INPUT F87T B
=E02/A05 LIST OF EQUIPMENTS: =E02+CRP2 C =E02/N11 SIGNAL SEND TO F87B B

B =E02/A06 LIST OF EQUIPMENTS: =E02+CRP2 C =E02/N12 BINNARY INPUT OF F87B B B


=E02/A07 LIST OF EQUIPMENTS: =E02+MK C =E02/N13 LOAD SHEDDING CIRCUIT B
=E02/B01 CONTROL, PROTECTION & MEASUREMENT PRINCIPLE DIAGRAM B =E02/P01 INTERLOCKING FOR CB, DS, ES B
=E02/B02 TRIPPING MATRIX B =E02/P02 INTERLOCKING FOR CB, DS, ES B
=E02/B03 LAYOUT DRAWING B =E02/Q01 INDICATOR CIRCUIT B
=E02/B04 LAYOUT DRAWING MARSHALLING KIOSK =E03+MK B =E02/Q02 TAP POSITION AND THERMAL WINDING INDICATOR CIRCUIT B
=E02/B05 OPERATION LOGIC DIAGRAM FOR DS E02-QL02 B =E02/R01 BINNARY INPUT BCU B
C =E02/B06 OPERATION LOGIC DIAGRAM FOR ES E02-QE25 B =E02/R02 BINNARY INPUT BCU B C

=E02/B07 CLOSING LOGIC DIAGRAM FOR CB E02-QF01 B =E02/R03 BINNARY INPUT BCU B
=E02/B08 OPENING LOGIC DIAGRAM FOR CB E02-QF01 B =E02/R04 BINNARY INPUT BCU B
=E02/D01 AC POWER SUPPLY FOR CONTROL PANEL B =E02/R05 BINNARY INPUT BCU B
=E02/D02 AC POWER SUPPLY FOR MARSHALLING KIOSK B =E02/R06 BINNARY INPUT BCU B
=E02/D03 AC POWER SUPPLY FOR CB, DS, ES B =E02/R07 BINNARY INPUT BCU B
=E02/G01 DC POWER SUPPLY FOR CONTROL PANEL B =E02/R08 BINNARY INPUT F90 B
D D
=E02/G02 DC POWER SUPPLY FOR CONTROL PANEL B =E02/R09 BINNARY INPUT F90 B
=E02/G03 DC POWER SUPPLY FOR CONTROL PANEL B =E02/R10 MULTIPLED SIGNAL CIRCUIT AND LAMP INDICATOR FOR FAN OPERATOR B
=E02/G04 DC POWER SUPPLY FOR HV EQUIPMENT B =E02/R11 SEND SIGNAL CIRCUIT B
=E02/M01 CONTROL CIRCUIT DS E02-QL02 B =E02/R12 MODBUS RS485 CIRCUIT B
=E02/M02 OLTC CONTROL CIRCUIT B =E02/S01 CURRENT CIRCUIT OF RELAY F87T B
=E02/M03 OLTC CONTROL CIRCUIT B =E02/S02 CURRENT CIRCUIT OF RELAY B

E =E02/M04 FAN CONTROL CIRCUIT B =E02/S03 CURRENT, VOLTAGE CIRCUIT OF RELAY F67 B E
=E02/M05 CLOSING CIRCUIT CB E02-QF01 B =E02/S04 CURRENT, VOLTAGE OF RELAY F90 B
=E02/N01 TRIPPING CIRCUIT 1 CB E02-QF01 B =E02/T01 CURRENT, VOLTAGE CIRCUIT FOR BCU B
=E02/N02 TRIPPING CIRCUIT 2 CB E02-QF01 B =E02/T02 CURRENT, VOLTAGE CIRCUIT FOR BCU B
=E02/N03 TRIP-LOCKOUT 1 CIRCUIT B =E02/T03 CURRENT CIRCUIT FOR METTERING PANEL B
=E02/N04 TRIP-LOCKOUT2 CIRCUIT B =E02/W01 SPARE CIRCUIT B
X: AUTOMATIC PAGE MODIFIED

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A01.a

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN TABLE OF CONTENTS : =E02/A00 - =E02/W01 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

PAGE DESCRIPTION REV. X PAGE DESCRIPTION REV. X

=E02/Z01 REFERENCE F87T P643 B =E02+CRP2/X110 Terminal diagram =E02+CRP2-X12 B


A A
=E02/Z02 REFERENCE F87T P643 B =E02+CRP2/X111 Terminal diagram =E02+CRP2-X20 B
=E02/Z03 REFERENCE F67 P143 B =E02+CRP2/X112 Terminal diagram =E02+CRP2-X21 B
=E02/Z04 REFERENCE F67 P143 B =E02+CRP2/X113 Terminal diagram =E02+CRP2-X22 B
=E02/Z05 REFERENCE BCU C264 B =E02+CRP2/X114 Terminal diagram =E02+CRP2-X42 B
=E02/Z06 REFERENCE BCU C264 B =E02+CRP2/X115 Terminal diagram =E02+CRP2-X43 B
=E02/Z07 REFERENCE BCU C264 B =E02+CRP2/X116 Terminal diagram =E02+CRP2-X44 B

B =E02/Z08 REFERENCE F90 (REG-DA) B =E02+CRP2/X117 Terminal diagram =E02+CRP2-X45 B B


=E02/Z09 REFERENCE CONTROL DEVICES B =E02+CRP2/X118 Terminal diagram =E02+CRP2-X51 B
=E02/Z10 REFERENCE CONTROL DEVICES B =E02+CRP2/X119 Terminal diagram =E02+CRP2-X52 B
=E02/Z11 REFERENCE INDICATOR METTER B =E02+CRP2/X120 Terminal diagram =E02+CRP2-X53 B
=E02/Z12 REFERENCE CURRENT AND VOLTAGE TESTBLOCK B =E02+CRP2/X121 Terminal diagram =E02+CRP2-X54 B
=E02/Z13 REFERENCE RELAY F74 B =E02+CRP2/X122 Terminal diagram =E02+CRP2-X91 B
=E02/Z14 REFERENCE RELAY TESTBLOCK B =E02+CRP2/X123 Terminal diagram =E02+CRP2-X410 B
C =E02/Z15 CB REFERENCE (GL312F1/GE) B =E02+CRP2/X124 Terminal diagram =E02+CRP2-X411 B C

=E02/Z16 CB REFERENCE (GL312F1/GE) B =E02+CRP2/X125 Terminal diagram =E02+CRP2-X412 B


=E02/Z17 CB REFERENCE (GL312F1/GE) B =E02+CRP2/X126 Terminal diagram =E02+CRP2-X413 B
=E02/Z18 CB REFERENCE (GL312F1/GE) B =E02+MK/X100 Terminal diagram =E02+MK-XAC B
=E02/Z19 DS REFERENCE B =E02+MK/X101 Terminal diagram =E02+MK-XAC1 B
=E02/Z20 DS REFERENCE B =E02+MK/X102 Terminal diagram =E02+MK-XDC B
=E02/Z21 DS REFERENCE B =E02+MK/X103 Terminal diagram =E02+MK-XDC1 B
D D
=E02/Z22 ES REFERENCE B =E02+MK/X104 Terminal diagram =E02+MK-XDC2 B
=E02/Z23 ES REFERENCE B =E02+MK/X105 Terminal diagram =E02+MK-X3 B
=E02+CRP2/X100 Terminal diagram =E02+CRP2-XAC B =E02+MK/X106 Terminal diagram =E02+MK-X7 B
=E02+CRP2/X101 Terminal diagram =E02+CRP2-XDC1 B =E02+MK/X107 Terminal diagram =E02+MK-X8 B
=E02+CRP2/X102 Terminal diagram =E02+CRP2-XDC2 B =E02+MK/X108 Terminal diagram =E02+MK-X10 B
=E02+CRP2/X103 Terminal diagram =E02+CRP2-XDC3 B =E02+MK/X109 Terminal diagram =E02+MK-X11 B

E =E02+CRP2/X104 Terminal diagram =E02+CRP2-X3 B =E02+MK/X110 Terminal diagram =E02+MK-X20 B E


=E02+CRP2/X105 Terminal diagram =E02+CRP2-X7 B =E02+MK/X111 Terminal diagram =E02+MK-X41 B
=E02+CRP2/X106 Terminal diagram =E02+CRP2-X8 B =E02+MK/X112 Terminal diagram =E02+MK-X42 B
=E02+CRP2/X107 Terminal diagram =E02+CRP2-X9 B =E02+MK/X113 Terminal diagram =E02+MK-X45 B
=E02+CRP2/X108 Terminal diagram =E02+CRP2-X10 B
=E02+CRP2/X109 Terminal diagram =E02+CRP2-X11 B
X: AUTOMATIC PAGE MODIFIED

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A01.a F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN TABLE OF CONTENTS : =E02/Z01 - =E02+MK/X113 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION


A A
M
THREE WINDING TRANSFORMER 3 UNIT POTENTIAL TRANSFORMER A AMMETER MCCB CÓ ĐỘNG CƠ ĐIỀU KHIỂN

TWO WINDING TRANSFORMER 2 UNIT POTENTIAL TRANSFORMER V VOLTMETER MCCB, MCB

AUTO TRANSFORMER SURGE ARRESTOR W WATTMETER RESISTOR


B B

CURRENT TRANSFORMER WYE VAR VAR METER FUSE

REACTOR DELTA ‎cosφ POWER FACTOR METER BATTERY

CAPACITOR OPEN DELTA Hz FREQUENCY METER INVERTER


C C

REACTOR EARTHING Wh WATTHOUR METER DIODE

HIGH VOLTAGE CIRCUIT BREAKER INTERLOCKING VARh VAr METER

MEDIUM CIRCUIT BREAKER LATCHING DEVICE AMPE SWITCH


D D

DAO CẮM HỢP BỘ TRUNG ÁP M CONTROL MOTOR VOLT SWITCH

DISCONECTOR CONTROL KEY RELAY TEST BLOCK

E
EARTH SWITCH ~ ALTERNATIVE CURRENT VOLTAGE/CURRENT TEST BLOCK
E

LOAD DISCONECTOR DIRECT CURENT LAMP

CONTACTOR

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN DEVICE SYMBOL PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

KÝ HIỆU MÔ TẢ KÝ HIỆU MÔ TẢ

21/21N DISTANCE PROTECTION 86 TRIP-LOCKOUT RELAY


A A
25 SYNCHROCHECK 87B BUSBAR DIFFERENTIAL PROTECTION

26 THERMAL PROTECTION 87L LINE DIFFERENTIAL PROTECTION

27 UNDERVOLTAGE PROTECTION 87N RESTRICTED GROUND FAULT PROTECTION

33 POSITION BLOCK RELAY 87S STUB DIFFERENTIAL PROTECTION

49 THERMAL OVERLOAD PROTECTION 87T TRANSFORMER DIFFERENTIAL PROTECTION

50 INSTANTANEOUS OVERCURRENT PROTECTION 90 AUTOMATIC CONTROL VOLTAGE RELAY


B B
50BF CIRCUIT-BREAKER FAILURE PROTECTION 94 TRIPPING RELAY

50G INSTANTANEOUS GROUND OVERCURRENT PROTECTION 96 GAS RELAY

50N INSTANTANEOUS NEUTRAL OVERCURRENT PROTECTION FR FAULT RECORDER

51 TIME OVERCURRENT PROTECTION FL FAULT LOCATOR

51G TIME GROUND OVERCURRENT PROTECTION SOTF SWITCH ON TO FAULT

51N TIME NEUTRAL OVERCURRENT PROTECTION BCU BAY CONTROL UNIT


C C
5IUb UNBALANCE OVERCURRENT PROTECTION A CURRENT MEASUREMENT FUNCTION

51/27 VOLTAGE CONTROLLED OVERCURRENT V VOLTAGE MEASUREMENT FUNCTION

59 OVERVOLTAGE PROTECTION f FREQUENCY MEASUREMENT FUNCTION

59N ZEZO-SEQUENCE OVERVOLTAGE PROTECTION ‎cosφ POWER FACTOR MEASUREMENT FUNCTION

63 PRESSURE RELAY W EFFECTIVE POWER MEASUREMENT FUNCTION

D 64 GROUND DETECTOR RELAY VAR REACTIVE POWER MEASUREMENT FUNCTION D

67 DIRECTIONAL OVERCURRENT RELAY Wh ACTIVE ENERGY MEASUREMENT FUNCTION

67N DIRECTIONAL OVERCURRENT PROTECTION FOR GROUND FAULTS VARh REACTIVE ENERGY MEASUREMENT FUNCTION

67NS DIRECTIONAL SENSITIVE GROUND-FAULT DETECTION

68 POWER-SWING BLOCKING

71 LEVEL OIL RELAY


E E
74 TRIP CIRCUIT SUPERVISION

79 AUTO RECLOSING

81 FREQUENCY PROTECTION

85 COMBINATION OF PROTECTION

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN FUNCTION SYMBOL PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

KÝ HIỆU MÔ TẢ KÝ HIỆU MÔ TẢ KÝ HIỆU MÔ TẢ KÝ HIỆU MÔ TẢ


A A

NORMALY OPEN CONTACT (NO) RELAY TEST BLOCK CONTACT LAMP EARTHING BAR

NORMALY CLOSE CONTACT (NC) CURRENT/VOLTAGE TEST BLOCK CONTACT LIGHTS BELL

CHANGE OVER CONTACT (CO) SOLENOID / COIL SOCKET HOOTER


B B

CONTACTOR NORMALY OPEN CONTACT ON DELAY COIL SURGE ARRESTOR MEARSUREMENT DEVICE

CONTACTOR NORMALY CLOSE CONTACT LATCHED COIL FUSE V VOLMETTER

NORMALLY OPEN ON BUTTON BINARY INPUT RELAY HEATER A AMMETTER


C C

NORMALLY CLOSED OFF BUTTON ANALOG INPUT RELAY RESISTOR

PUSH BUTTON (DETENT) POWER SUPPLY DIODE

SELECTOR SWITCH CONTACT CONVERTER CAPACITOR


D D

~
LIMIT SWITCH CONTACT RECTIFIER REACTOR/CURRENT-VOLTAGE INPUT RELAY

TEMPERATURE CONTROLER CONTACT INVERTER TERMINAL


~

MAKE CONTACT DELAYED WHEN


COUNTER DRAWOUT TERMINAL
E CLOSING E

MAKE CONTACT DELAYED WHEN


MCCB/MCB DIODE TERMINAL
OPENING I>

FUSE TERMINAL

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A05

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN SECONDARY CIRCUIT SYMBOL PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

NO. SYMBOL DESCRIPTION MANUFACTORY CODE QTY. UNIT NOTE CUBICLE

1 F87T TRANSFORMER DIFFERENTIAL PROTECTION RELAY SCHNEIDER P64331QA6M0B68M 01 Pcs 16BI + 16BO + 2LC IEC61850 =E02+CRP2
A A
2 F67 DIRECTIONAL OVER CURRENT RELAY SCHNEIDER P14331QA7M0B58L 01 Pcs 16BI + 14BO + 2LC IEC61850 =E02+CRP2

3 BCU BAY CONTROL UNIT SCHNEIDER C264U11M6A10013302100031111D10 01 Pcs 58BI + 26BO + 2ST IEC61850 =E02+CRP2

REG-DA B0 I0 H0 F1 M1 S0 T0 K1
4 F90 AUTO VOLTAGE REGULATOR RELAY A-EBERLE 01 Pcs 16BI+12BO+1AI+1xRS232+ 1xLC IEC61850 =E02+CRP2
E00 D0 C00 XW93.1 G2 A2

5 PMF MULTIFUNCTION METTER CEWE ELITE 448 01 Pcs =E02+CRP2

6 XF... RELAY TESTBLOCK FUJI TSB-14-11111111111111-V 03 Pcs =E02+CRP2

7 F86... TRIP AND LOCKOUT RELAY ARTECHE BJ-8RP 02 Pcs 8CO =E02+CRP2
B B
8 F74... TRIPPING SUPERVISORY RELAY ARTECHE VDF-10 02 Pcs 2CO =E02+CRP2

9 XTC... CURRENT TESTBLOCK FUJI KTT-AW4 B M 03 Pcs =E02+CRP2

10 XTV... VOLTAGE TESTBLOCK FUJI KTT-VW4 B M 04 Pcs =E02+CRP2

11 SQF01 CONTROL AND DISCREPANCY SWITCH FOR CB FUJI BHL-3B3111-220L1-W-Y-B-L54-Y07E 01 Pcs =E02+CRP2

12 SQL01 CONTROL AND DISCREPANCY SWITCH FOR DS FUJI BHL-3B3111-220L1-W-Y-B-L54-Z07E 01 Pcs =E02+CRP2

13 SQE... SEMAPHORE FOR ES FUJI SPSR-30S-DC220-BB 01 Pcs =E02+CRP2


C C
14 S.B/M "BCU/MIMIC" SELECTOR SWITCH SALZER SA25-FA 6015-61009-M1-I-F-3-BS-0 01 Pcs =E02+CRP2

15 S.25 "SYN./BYPASS" SELECTOR SWITCH SALZER SA25-FA 6037-61638-M1-I-F-3-BS-0 01 Pcs =E02+CRP2

16 S.L/R "LOCAL/REMOTE" SELECTOR SWITCH FOR FAN AND OLTC SALZER SA25-FA 6037-61638-M1-I-F-3-BS-0 01 Pcs =E02+CRP2

17 S.M/S/I "MASTER/SLAVE/INDEPENTDENT" SELECTOR SWITCH SALZER SA25-FA 6027-61669-M1-I-F-3-BS-0 01 Pcs =E02+CRP2

18 S.AM1, S.AM2 "AUTO/MAN" SELECTOR SWITCH SALZER SA25-FA 6037-61638-M1-I-F-3-BS-0 02 Pcs =E02+CRP2

D 19 S.CF1/S.CF2 "ON/OFF" SELECTOR SWITCH SALZER SA25-FA 6037-61638-M1-I-F-3-BS-0 02 Pcs =E02+CRP2 D

20 S.RL "RAISER/OFF/LOWER" SELECTOR SWITCH SALZER SA25-FA 3000-61762-M1-I-F-3-BS-0 01 Pcs =E02+CRP2

21 PW 220VAC/VDC - 24VDC CONVERTER OMRON S8JC-Z05024C 01 Pcs =E02+CRP2

PTO, PTP
22 TRANSFORMER INDICATOR METTER AUTONICS MT4W-DA-18 04 Pcs =E02+CRP2
PTW1, PTW2

23 KT... TRIPPING AUXILARY RELAY FINDER 55.34 01 Lot =E02+CRP2

24 K.... AUXILARY RELAY IDEC RU4S 01 Lot =E02+CRP2

E 25 FQAC MCB AC FOR LIGHTING AND HEATING LEGRAND DX3 01 Pcs 2P-16A-6kA =E02+CRP2
E

26 FQ... MCB DC LEGRAND DX3 DC 01 Lot 2P-10A-16kA =E02+CRP2

27 KQP CONTACTOR ABB ESB25 01 Pcs =E02+CRP2

28 XAC, XDC POWER TERMINALS DEGSON PC6 01 Lot =E02+CRP2

29 X4... CURRENT TERMINALS DEGSON PCTK 01 Lot =E02+CRP2

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A05 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A06

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LIST OF EQUIPMENTS: =E02+CRP2 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

NO. SYMBOL DESCRIPTION MANUFACTORY CODE QTY. UNIT NOTE CUBICLE

30 X... SIGNAL TERMINALS DEGSON PC4 01 Lot =E02+CRP2


A A
31 B0 THERMOSTAT CYMAX =E02+CRP2

32 B1 DOOR LIMIT SWITCH CHINA =E02+CRP2

33 E0 HEATING RESISTER CYMAX =E02+CRP2

34 E1 LIGHTING LAMP CHINA =E02+CRP2

35

36
B B
37

38

39

40

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A06 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A07

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LIST OF EQUIPMENTS: =E02+CRP2 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

NO. SYMBOL DESCRIPTION MANUFACTORY CODE QTY. UNIT NOTE CUBICLE

1 FQAC, FQAC1 MCB AC LEGRAND DX3 02 Pcs 2P-16A-6kA =E02+MK


A A
2 FQCB, FQDS MCB DC LEGRAND DX3 DC 02 Pcs 2P-16A-16kA =E02+MK

3 KQP CONTACTOR ABB ESB25 01 Pcs =E02+MK

4 XAC, XDC POWER TERMINALS DEGSON PC6 01 Lot =E02+MK

5 X4... CURRENT TERMINALS DEGSON PCTK 01 Lot =E02+MK

6 X5... VOLTAGE TERMINALS DEGSON PC6 01 Lot =E02+MK

7 X... SIGNAL TERMINALS DEGSON PC4 01 Lot =E02+MK


B B
8 B0 THERMOSTAT CYMAX =E02+MK

9 B1 DOOR LIMIT SWITCH CHINA =E02+MK

10 E0 HEATING RESISTER CYMAX =E02+MK

11 E1 LIGHTING LAMP CHINA =E02+MK

12

13
C C
14

15

16

17

18

D 19 D

20

21

22

23

24

E 25
E

26

27

28

29

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A07 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LIST OF EQUIPMENTS: =E02+MK PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

P2 E02+CRP2
CL: 5P20
CT TO F87B
CL: 0.5
200-400-600
TO METTERING PANEL
/1/1/1/1/1A CL: 0.2
TO METTERING PANEL XTC1 XTV1
CL: 5P20
TO FR
CL: 5P20 PMF (ELITE 448)
P1
U, I, P, Q, f, pF, ...
E02 QF01
B XTV3 B
110 0.11 0.11
kV QE25 XTC3 BCU
3 3 3 M QL02 XTV4
C11 BCU (C264)

XTC2 XTV2
96B 96P P2 CL: 0.5
CL: 0.5
26W 26Q CL: 5P20
F90 (C264) 90 FR
CL: 3P
CL: 5P20
63 71Q
C P1 C
P2 P1
T2
P2 P1
XF67
F67 (P143)
XF67
P1
CL: 0.5 67/67N 27/59 74 SOTF
CL: 5P20 XF67
TO F67 22KV INCOMING 50/51N 50/51 FR 25
CL: 5P20

P2

XF87T

D D
F87T (P643)
CL: 5P20 CL: 5P20

87T 64 49 50/51
CL: 5P20 CL: 5P20
FR

FROM TU C42
-38
P1
CL: 0.5
CL: 5P20
VOLTAGE CIRCUIT TO METTERING PANEL
1500/2500 CL: 5P20 BJ-8RP VDF-10
CURRENT CIRCUIT
E /1/1/1A E
P2 F86-1, F86-2 F74-1, F74-2

J13 QF01

C41
22 0.11 0.11
kV
3 3 3
CL: 0.5

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE
CONTROL, PROTECTION & MEASUREMENT PRINCIPLE
24/11/2020
APPROVED NGUYEN DINH TUAN PECC2/TT-110KV/E02-132
DIAGRAM
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

CIRCUIT BREAKER =E02+CRP2 +J13 =E05+CRP5 =E02+CRP4 TC-C41


EQUIPMENT
E03-QF01 J01-QF01 -F87T -F861 -F862 -F67 -F87B -F861 -F862 -F861 -F862
PANEL

BLOCK BLOCK SET SET START EXT. START SET SET SET SET
SYMBOL TYPE FUNCTION TC1 TC2 CC TC 94 50BF
CC CC 86 86 50BF TRIP 50BF 86 86 86 86

-F87T P643 87T, 87N, 94,50,51 X X X X X X X X


B B
67/67N, 50/51,
-F67 P143 50/51N, SOTF
X X X X X X X X

=E02+CRP2 -F741 VDF-10 74 TCS X

-F742 VDF-10 74 TCS X

-F861 BJ-8RP 86 X X X X

-F862 BJ-8RP 86 X X X X

C 50BF BAY E02(STAGE 1) X X X X X* C

50BF BAY E02(STAGE 2) X X X X X X

50BF BAY E02(STAGE 2) X X X X


=E05+CRP5 -F87B P746
50BF BAY E03(STAGE 2) X X X X

87B X X X X X* X X X X

81 X X
D -F27 P141
D
59 X X

67/67N, 50/51, 50/51 X X*

50BF X X
+J13 -F67
74 TCS X

86 X X
E INTERNAL PROTECTION E
=T2+LCB
TRANS. T2
X X X X

50BF TC-C41 X X

NOTE:
X*: AUTO START
TCS: TRIP COIL SUPERVISOR

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN TRIPPING MATRIX PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

FRONT VIEW SIDE VIEW REAR VIEW


A A
ENTEC =E02+CRP2
EQUIPMENT
T2 TRANSFORMER BAY

F87T TAG NAME DESCRIPTION


MiCOM P 143

=E01+WR
ALARM ALARM

ALARM ALARM

ALARM

ALARM

c LEAR
READ
c
ALARM

ALARM

ALARM
BCU BAY CONTROL UNIT
ALARM
ENTER
ALARM

ALARM
ALSTOM

F67 DIRECTIONAL OVERCURRENT PROTECTION RELAY


F67
MiCOM

ALARM
P 143

ALARM
F87T TRANSFORMER DIFFERENTIAL PROTECTION RELAY
ALARM ALARM

ALARM ALARM

c ALARM

TRANSFORMER VOLTAGE REGULATOR


ALARM

c LEAR
READ
ENTER
ALARM

ALARM

ALARM

ALARM
F90
ALSTOM

F741, F742 TRIPPING CIRCUIR SUPERVISION RELAY


BCU
MiCOM P 143

ALARM

ALARM
ALARM

ALARM
F861, F862 RƠLE TRIP-LOCKOUT
ALARM ALARM

ALARM
c ALARM

c LEAR ALARM

PMF MULTIFUNCTION METER


READ
ALARM
ENTER
ALARM

ALARM
ALSTOM

B PTW1, PTW2, PTO, PTP INDICATOR WINDING TEMPERATURE, OIL TEMPERATURE AND TAP POSITION B
S.AM1 S.M/S/I S.R/O/L S.L/R S.ES
SQF01 DISCREPANCY CONTROL SWITCH FOR CB
S.AM2 S.FC1 S.FC2 PLF1 PLF2
SQL01; SQE15 DISCREPANCY CONTROL SWITCH FOR DS; ES
PTP PTO PTW1 PTW2 S.B/M
HI

GO

LO
DIGITAL MULTI METER
HI

GO

LO
DIGITAL MULTI METER
HI

GO

LO
DIGITAL MULTI METER
HI

GO

LO
DIGITAL MULTI METER "MIMIC/BCU" SELECTOR SWITCH
MD MD MD MD
2200

MT4W Autonics MT4W Autonics MT4W Autonics MT4W Autonics

S.25 " SYN./BYPASS" SELECTOR SWITCH

PMF S.R/L "LOCAL/REMOTE" SELECTOR SWITCH


S.RE S.LT
-SQL02
S.B/M S.QE25 S.AM1; S.AM2 "AUTO/MANUAL" SELECTOR SWITCH
I U P Q

S.25
P.LC -SQF01 S.R/O/L "RAISE/OFF/LOWER" SELECTOR SWITCH
S.81
T1
S.M/S/I "MASTER/SLAVE/INDEP." SELECTOR SWITCH
S.CF1;S.CF2 "ON/OFF" SELECTOR SWITCH FOR CONTROL FAN
F90
S.RE RESET 86 PUSH BUTTON
C 22KV
C
S.LT LAMP TEST PUSH BUTTON
F861 F862 F741 F742
S.ES EMERGENCY STOP PUSH BUTTON
P.F1; P.F2; P.LC LAMP INDICATOR FOR: FAN1; FAN2; CB CONTROL AT LOCAL
XF87T.1
XF87T.2

XTC.MF XTV.MF XTV.90


XF... RELAY TESTBLOCK
XF67

XTC.BC XTC.90 XTV1.BC XTV2.BC


XC.., XV.. CURRENT TESTBLOCK, VOLTAGE TESTBLOCK

100 800 750 800


800
D D
TOP VIEW BOTTOM VIEW BASE NAME PLATE (SCALE 1:5)
4x∅14
100
C =E02+CRP2

45
750
800
200
800

800
750

C (Scale 1:5) REMARK:


E IP DEGREE: IP41 E
Ø14 APPLICATION STANDARD: IEC60529
25 MATERIAL: STEEL
STEEL THICKNESS: 2mm
4x∅8 PAINT COLOR: RAL7032
800 550 DOOR APPLY AREA: REAR
OPEN DOOR: 180°

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LAYOUT DRAWING PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

864 570 REMOVE FRONT DOOR REMOVE BACK DOOR


A 1500 A

B B

C C
450 800
800
506

A-A
TOP VIEW

D D
450
75 300
470

4x∅14

25 750
760 800
E LEGEND: E
- PROTECTION CLASS: IP55
- STANDARD: IEC60529
- THICKNESS: 2mm
-MATERIAL:SUS 302
- OPEN FROM FRONT DOOR
- ALL DIMENSIONS ARE IN MILLIMETER

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B05

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LAYOUT DRAWING MARSHALLING KIOSK =E03+MK PECC2/TT-110KV/E02-132

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SCADA LEVEL PANEL LEVEL EQUIPMENT LEVEL


A A
OPEN/CLOSE COMMAND DS E03-QL02 FROM SCADA

BCU "LOCAL/REMOTE" ON "LOCAL"

&
OPEN/CLOSE COMMAND DS E02-QL02 FROM BCU
&
HMI "LOCAL/REMOTE" ON "REMOTE"
≥1
≥1 &
HMI "LOCAL/REMOTE" ON "LOCAL"
&
B BCU "LOCAL/REMOTE" ON "REMOTE" B
&
OPEN/CLOSE COMMAND DS E02-QL02 FROM HMI
SOFT INTERLOCKING *
HMI LEVEL
BCU
DS "REM./LOC./MAN." SWITCH ON "REMOTE"

MIMIC

C C
&
MIMIC "BCU/MIMIC" SWITCH ON "BCU"
E02 QF01

QE25
M QL02 MIMIC "BCU/MIMIC" SWITCH ON "MIMIC" &
C12
& ≥1
OPEN/CLOSE COMMAND DS E02-QL02 FROM CONTROL SWITCH
&
D D
OPEN/CLOSE
T2 ≥1 DS E02-QL02
CB E02-QF01 OPEN

ES E02-QE25 FULLY OPEN

&
* SOFT INTERLOCKING
CB E02-QF01 OPEN ES E03-QE24 FULLY OPEN

E E
-38 ES E02-QE25 FULLY OPEN
&
J13 OPEN/CLOSE COMMAND AT LOCAL
&
DS "REM./LOC./MAN." SWITCH ON "LOCAL" &
QF01 ES E03-QE24 FULLY OPEN OPEN/CLOSE BY HANDLE ≥1
C42
DS "REM./LOC./MAN." SWITCH ON "MAN" &

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B05 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B06

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN OPERATION LOGIC DIAGRAM FOR DS E02-QL02 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

EQUIPMENT LEVEL
A A

B B

DS E03-QL02 FULLY OPEN


C C
OPEN/CLOSE

CB J13-QF01 AT TEST POSITION


& ES E02-QE25
E02 QF01

QE25
M QL02
C12

D D
T2

E E
-38

J13

QF01

C42

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B06 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B07

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN OPERATION LOGIC DIAGRAM FOR ES E02-QE25 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SCADA LEVEL PANEL LEVEL EQUIPMENT LEVEL


A A
CLOSE COMMAND CB E02-QF01 FROM SCADA
SF6 LOCKOUT
BCU "LOCAL/REMOTE" ON "LOCAL"

& SPRING CHARGED


CLOSE COMMAND CB E02-QF01 FORM BCU
&
HMI "LOCAL/REMOTE" ON "REMOTE"
≥1 INTERLOCK INSIDE CB IS OK

≥1 &
HMI "LOCAL/REMOTE" ON "LOCAL"
& CB "LOCAL/REMOTE" SWITCH ON "LOCAL"
B BCU "LOCAL/REMOTE" ON "REMOTE" B
&
CLOSE COMMAND CB E02-QF01 FROM HMI CLOSE COMMAND FROM EQUIP.
SOFT INTERLOCKING (*)
DS E02-QL02 OPENED
&
HMI LEVEL
BCU
CB J13-QF01 AT TEST POSITION
MIMIC

BCU "BCU/MIMIC" SWITCH ON "BCU" &


C C
&
E02 QF01
CLOSE
& CB E02-QF01
QE25
M QL02
CB "LOCAL/REMOTE" SWITCH ON "REMOTE"
C12
TRIPPING CIRCUIT IS NOT OK

& ≥1
RƠLE LOCKOUT OPERATED

D D
T2
DS E02-QL02 CLOSED
(*)

CB J13-QF01 AT SERVICE POSITION &


BCU/MIMIC SWITCH ON "MIMIC"

&
E CLOSE COMMAND CB E02-QF01 FROM CONTROL SWITCH E
-38

J13

QF01

C42

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B07 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B08

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CLOSING LOGIC DIAGRAM FOR CB E02-QF01 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

PANEL LEVEL EQUIPMENT LEVEL


A
SCADA LEVEL A

OPEN COMMAND CB FROM SCADA

& &
HMI "LOCAL/REMOTE" ON "REMOTE" BCU "LOCAL/REMOTE" ON "REMOTE" SF6 LOCKOUT

≥1
HMI LEVEL ≥1
B OPEN COMMAND FROM BCU B
OPEN COMMAND CB FROM HMI CB "LOCAL/REMOTE" SWITCH ON "LOCAL"
&
& BCU "LOCAL/REMOTE" ON "LOCAL" &
HMI "LOCAL/REMOTE" ON "LOCAL" OPENING COMMAND FROM EQUIP.

BCU

C OPEN CB QF01 C
& & TRIP CIRCUIT 1
BCU/MIMIC SWITCH ON "BCU" CB "LOCAL/REMOTE" SWITCH ON "REMOTE"

E02 QF01
& ≥1
QE25
M QL02
≥1
C12
BCU/MIMIC SWITCH ON "MIMIC"

&
OPENING COMMAND FROM CONTROL SWITCH
D D

T2

PROTECTION RELAY OPERATED

RELAY F861 OPERATED

RELAY F862 OPERATED

E E
PROTECTION RELAY OPERATED
-38
≥1
RELAY F861 OPERATED OPEN CB QF01
J13 & TRIP CIRCUIT 2
RELAY F862 OPERATED
SF6 LOCKOUT

QF01

C42
MIMIC
POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02
DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B08 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE D01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN OPENING LOGIC DIAGRAM FOR CB E02-QF01 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E01+CRP1 +CRP2 =E03+CRP3

POWER SUPPLY
A FOR HEATING AND LIGHTING A

-W144
ACL1 1 -XAC 1 -XAC 2 ACL1
=E01/D01.7/ / =E03/D01.1

ACL2 2 -XAC 3 -XAC 4 ACL2


=E01/D01.7/ / =E03/D01.1

ACL3 3 -XAC 5 -XAC 6 ACL3


=E01/D01.7/ / =E03/D01.1

ACN 4 -XAC 7 -XAC 8 ACN


=E01/D01.7/ / =E03/D01.1

B B
1 3 12 14 96 98

-FQAC 11 95
2P-16A I> I>

/R07.3

/R07.4
2 4

LIGHTING HEATING SOCKET


C C

1 1
-B1 -B0
6A 2 0÷90°C 2

D D

1 1
1 1

-E0 -E1 -E2 -XSK


8W 60W 2 60W 2 16A
2 2
E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE D01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE D02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN AC POWER SUPPLY FOR CONTROL PANEL PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E04+MK +MK

POWER SUPPLY AC POWER SUPPLY


HEATING & LIGHTING HV EQUIPMENT
A -W169 A
=E04/D02.6/
L1 1 -XAC 1 -XAC 2

=E04/D02.6/
L2 2 -XAC 3 -XAC 4

=E04/D02.6/
L3 3 -XAC 5 -XAC 6

=E04/D02.6/
N 4 -XAC 7 -XAC 8

B B

1 3 12 14 96 98 1 3 12 14 96 98

-FQAC1 11 95 -FQAC2 11 95
2P-16A I> I> 2P-16A I> I>

/R03.2

/R03.4

/R03.2

/R03.4
2 4 2 4
C C

.AC.L
/ D03.3

.AC.N
/ D03.3

LAMP HEAT SOCKET

D D

1
1 1 -B0
-B1 -B2 0÷90°C 2
6A 2 6A 2 1

-XSK
16A

1 1 2
E 1 1 E
-E1 -E2 -E0 -E3
8W 8W 60W 2 60W 2
2 2

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE D02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE D03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN AC POWER SUPPLY FOR MARSHALLING KIOSK PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+MK

A A

AC POWER SUPPLY AC POWER SUPPLY AC POWER SUPPLY


CB E02-QF01 DS E02-QL02 ES E02-QE25

.AC.L
D02.5

220 VAC
B .AC.N B
D02.5

-XAC1 1 3 2 4

-W170 1 2 -W171 1 2 -W172 1 2

+QF01 +QL02 +QE25


C C

TB1 1 2 -X1 20 21 -XT2 20 21


1

3
F1 F1 F1
2

4
D D

IL H IL H IL H
/Z16.6 /Z19.7 /Z22.6

E LAMP HEAT LAMP HEAT LAMP HEAT


E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE D03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE G01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN AC POWER SUPPLY FOR CB, DS, ES PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E01+CRP1 +CRP2 =E03+CRP3

DC2 POWER SUPPLY


A -W145
POWER SUPPLY BCU A
=E01/G01.8
DC1+ 1 -XDC1 1 -XDC1 2 DC1+
/ =E03/G01.1

=E01/G01.8
DC1- 2 -XDC1 3 -XDC1 4 DC1-
/ =E03/G01.1

-W146

=E01/G01.8
DC2+ 1 -XDC2 1 -XDC2 2 DC2+
/ =E03/G01.1

=E01/G01.8
DC2- 2 -XDC2 3 -XDC2 4 DC2-
/ =E03/G01.1

B B

1 3 1 3
12 14 96 98 12 14 96 98

-FQDC2 11 95 -FQDC1 11 95
2P-10A I> I> 2P-10A I> I>

/R07.8

/R07.8

/R07.7

/R07.8
2 4 2 4

1 2 /G01.5
1 7 8 /G01.5
C C
-KQP1 R3 R4 /G01.4
220VDC R5 R6 /G01.4
2

R3 R5 1 7
-KQP1
/G01.6 R4 R6 2 8

DC-
D / G02.1 D
DC+
/ G02.1

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE G01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE G02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN DC POWER SUPPLY FOR CONTROL PANEL PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2
POWER SUPPLY POWER SUPPLY POWER SUPPLY POWER SUPPLY POWER SUPPLY
RELAY F87T BCU INDICATOR METTER INDICATOR FOR METTERING

A A

DC+ DC+
G01.6 /G03.1

DC- DC-
G01.6 /G03.1

-XDC3 1 11 2 12 3 13 4 14 5 15

B 1 3
12 14 96 98
1 3
12 14 96 98
1 3
12 14 96 98
1 3
12 14 96 98
1 3
12 14 96 98 B

-FQ87T 11 95 -FQBCU 11 95 -FQPM 11 95 -FQSI 11 95 -FQMF 11 95


2P-10A I> I> 2P-10A I> I> 2P-10A I> I> 2P-10A I> I> 2P-10A I> I>
/R07.5

/R07.5

/N06.3

/N06.3

/R07.6

/R07.5

/R07.3

/R07.6

/R07.7

/R07.7
2 4 2 4 2 4 2 4 2 4

1 2
C AC AC C
-PW 3 P N
GND

PMF
SI+ /Z12.6
4 5 /Q01.1 -PS
-PE SI-
/Q01.1 ELITE 448

-X7 1 4

-PE
D 87T+ BCU+ D
/ N07.2 /R01.1

87T- BCU-
/ N07.2 /R01.1

X12 1 5 X8 1 7

2 1 23 24 8 9 8 9 8 9 8 9
F87T J BCU A -PTP -PTO -PTW1 -PTW2
/Z01.3 /Z05.2 /Z11.3 /Z11.5 /Z11.3 /Z11.5
-PS -PS
E GND GND GND GND E
P643 C264
MT4W MT4W MT4W MT4W

-PE

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE G02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE G03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN DC POWER SUPPLY FOR CONTROL PANEL PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2

A A
POWER SUPPLY POWER SUPPLY POWER SUPPLY POWER SUPPLY POWER SUPPLY
RELAY F67 RELAY F90 TC2 TC1 CLOSING CIRCUIT

G02.8
DC+

G02.8
DC-

-XDC3 6 16 7 17 8 18 9 19 10 20

B B

1 3 1 3 1 3 1 3 1 3
12 14 96 98 12 14 96 98 12 14 96 98 12 14 96 98 12 14 96 98

-FQ67 11 95 -FQ90 11 95 -FQTC2 11 95 -FQTC1 11 95 -FQCB 11 95


2P-10A I> I> 2P-10A I> I> 2P-10A I> I> 2P-10A I> I> 2P-10A I> I>
/R07.5

/R07.5

/R07.6

/R07.4

/R07.4

/R07.7

/R07.4

/R07.6

/R07.6

/R07.7
2 4 2 4 2 4 2 4 2 4

C C
F67+ F90+ TC2+ TC1+ C+
/ N06.1 /M02.2 /N02.1 /N01.1 /M05.1

F67- F90- TC2- TC1- C-


/ N06.1 /M02.1 /N02.7 /N01.7 /M05.5

X21 1 5 X22 1 6 -X20 1 7 -X10 1 5 X11 1 3

-W164 18 19 -W165 13 14 15 16

+MK
-X20 1 6 -X10 1 4 X11 1 2
D D

+QF01

-TB1 9 10 -TB1 7 8 -TB1 5 6

J2 J1 21 22
F67 J F90 MCB5 MCB4 MCB3
/Z03.3 /Z08
-PS -PS
E E
P143 REG-DA TC2+

TC1+
TC2-

TC1-

CC+

CC-
N02.2 /

N02.2 /

N01.1 /

N01.1 /

M05.1 /

M05.1 /
-PE

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE G03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE G04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN DC POWER SUPPLY FOR CONTROL PANEL PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=N00+DC +MK =E01+MK

DC POWER SUPPLY DC POWER SUPPLY


A FOR CB MOTOR FOR DS, ES MOTOR A
-W173
DC+ 1 -XDC 1 -XDC 2 DC+
=N00+DC/G05.2 / =E01/G04.1

DC- 2 -XDC 3 -XDC 4 DC-


=N00+DC/G05.2 / =E01/G04.1

1 3 1 3
12 14 96 98 12 14 96 98

-FQCB 11 95 -FQDS 11 95
B B
2P-16A I> I> 2P-16A I> I>

/R03.3

/R03.5

/R03.3

/R03.5
2 4 2 4

-XDC2 2 ES+
/ P02.1
-XDC2 4 ES-
/ P02.1

-XDC1 1 2 -XDC2 1 3

-W174 1 2 -W175 1 2

C C

+QF01 +QL02

X1 450 460

-X1 1 2 -X1 5 4

D QM1 D
1

DSQ2+

DSQ2-
Q1
2

3
Q1

M01.2 /

M01.2 /
4
/Z19.3 M
1 5
Q1
/Z16.3 6
M
E E

POWER SUPPLY POWER SUPPLY POWER SUPPLY


FOR CB MOTOR FOR DS MOTOR FOR CONTROL CIRCUIT

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE G04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE M01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN DC POWER SUPPLY FOR HV EQUIPMENT PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2

A CLOSE DS QL02 OPEN DS QL02 CLOSE DS QL02 OPEN DS QL02 A


FROM MIMIC FROM MIMIC FROM BCU FROM BCU

6 8 2 3
1
-SQL02 BCU E
-S.B/M

Push close

Push open
/Z09.1 C3 C4 /Z05.6
/Z09.1 -DO1 -DO2
MIMIC /Z05.6 /Z05.6
2
B 5 7 1 4 B

-X3 1 X3 2 X3 3 X3 4

-W164 1 2 3 4

+MK INT_QL02+ INT_QL02-


C P01.5 P01.5 C
-X3 1 9 11 12
INTERLOCKING CIRCUIT

-W188 1 6 7 8

+QL02
-X1 4A -X1 4B -X1 8 -X1 7 -X1 9A
DSQ2+
G04.5
D D
-X1 6A -X1 6B SB3

SA1 SA1 SA1 SA1 -X1 9

-KA1
-KM1 -KM2 -SB2 -SB1

-KA4

CS1 CS2
E E
KA4 KM2 KM1 /Z20.3
-QM1

CLOSE OPEN
DSQ2- -X1 12
G04.5

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE M01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE M02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CONTROL CIRCUIT DS E02-QL02 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2

RAISE TAP. LOW TAP. RAISE COMMAND & AUTO LOWER COMMAND & AUTO
FROM MIMIC FROM MIMIC FROM F90 FROM F90
A A
F90+ F90+
G03.4/ / R09.3
-X22 2 -X22 3

5 1

-S.M/S/I
/Z10.1
INDEP. MASTER

6 2
B B

1
-S.L/R
/Z10.4
LOCAL
2

LOWER
RAISE
7 45 41
-S.A/M1 -F90
/Z10.1 /Z08
R1 R2
C MAN /Z08.6 /Z08.6 C

8 46 42

LOWER
RAISE

1 3
-S.R/O/L
/Z10.6
RAISE LOWER
D D
2 4

1 5 2 6
-KF90 -KF90
/R10.4 9 /R10.4 10
18 19
-F90
/Z08 5 9 /M03.4 5 9 /M03.3
1 1
E7 E8 13 6 10 /M03.3 13 6 10 /M03.4
E /Z08.3 /Z08.3 2 2 E
KSCR KSCL
7 11 7 11
14 3 14 3
8 12 8 12
20 4 4

-X22 7 -X22 8 -X22 9

G03.4/
F90-

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE M02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE M03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN OLTC CONTROL CIRCUIT PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2

LOWER RAISE EMERGENCY STOP EMERGENCY STOP


A FROM BCU A

LOWER

RAISE
1
1 5 1 5 BCU D -S.ES 3
/Z05.4 /Z09.5
-KSCL -KSCR -DO1
/M02.6 9 /M02.5 9 /Z05.4 4
B B
2

2 6 2 6
-KSCR -KSCL
/M02.5 10 /M02.6 10

X22 10 11 12 13 14

C -W168 2 3 4 5 6 C

=T2+OLTC

-X1 12 -X1 10 -X1 11 -X1 14 -X1 15

-S32 S3

D D

-Q1
/
L1

S4 S5
-K1 -K2

E E
K2 K1

K1 K2 Q1

/
N
LOWER RAISE EMERGENCY STOP

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE M03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE M04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN OLTC CONTROL CIRCUIT PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2
ON/OFF ON/OFF ON/OFF ON/OFF
AUTO MODE MANUAL MODE CONTROL FAN
FAN GROUP 1 FAN GROUP 2 FAN GROUP 1 FAN GROUP 2
AUTOMATIC FROM BCU
FROM BCU FROM BCU
A A
5 9
-S.L/R
/Z10.4
LOCAL LOCAL

6 10

AUTO

MAN.

MAN.
1 3 7 1 1 3 7 9
-S.A/M2 SCF1 SCF2 - BCU D
B /Z10.1 /Z10.4 /Z10.4 /Z05.4 DO2 DO4 DO5
B
AUTO MAN. MAN. /Z05.4 /Z05.4 /Z05.4

2 4 8 2 2 4 8 10

C C
-X3 5 6 7 8

-W162 1 2 3 4

=T2+LCB
-X2 1 X2 2 3 4 5 6

D D
1S2 1S1 C5A
.L1 L1
4.5:E / /

Stop 1 Stop 2
C1 C2 C3 C4
-OTI -WTI1

Start 1 Start 2
E C5A C3 C3 C4 C4 E

C2 C1

C2 C1 C5 C5A C3 C4 MC1 MC2

.N1 N1
4.5:E / /

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE M04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE M05

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN FAN CONTROL CIRCUIT PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2

CLOSE CB QF01 CLOSE cmd. CLOSE CB QF01 CLOSE CB QF01


START SOTF
A FROM BCU WITH SYN. FROM MIMIC WITH SYN. A
C+
G03.8
X11 2 C-
G03.8
X11 4 X11 5 13
-S.B/M
/Z09.1
14 10
F861 10 11 MIMIC
/N03.7 F741 14
1 /Z13.4 6 6
B -SQF01 B

Push close
5 1 15 /Z09.1 5
BCU E F67 D F67 F F67 G
/Z05.6 -DO3 /Z03 BI1 /Z03.6 BI16 /Z04 -DO9
14 10 5
F862 10 11 /Z05.6 /Z03.6 /Z03.6
/N04.7 F742 6 2 16 6
1 /Z13.4 6 1 3
-S.25
SYN. BYPASS
2 4

C C
X11 6 7
-W164 16 17

+MK
X11 9
INT_CB+ INT_CB- INT_CBR- INT_CBR+
P01.1 P01.1 P01.3 P01.3

X11 3 X11 5 X11 7


-W186 13 14 15
D D

+QF01

PBS1 -TB1 14 -TB1 15 TB1 18 TB1 17

G03.8/
CC+
3 4
7 5
43A
6
E E

CLOSING COIL

-52CC
/Z15.2

G03.8/
CC-

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE M05 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CLOSING CIRCUIT CB E02-QF01 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2

A OPEN Cmd. CB OPEN Cmd. CB F87T TRIP F67 TRIP F861 F862 TRIP CIRCUIRT SUPERVISOR 1 A
FROM MIMIC FROM BCU TC1 QF01 TC1 QF01 TRIP TC1 TRIP TC1 CB E03-QF01

TC1+ TC1-
G03.7 G03.7/
X10 2 3 4 -X10 6 7

TC1+
N03.1

15 TC1-
1 1
N03.1
-S.B/M F87T H F67 H
B /Z09.1 MIMIC /Z02 BO1 /Z04 -BO1
B
16 /Z02.6 /Z04.6
1 2
2 2 F861 20 21 F862 20 21 + -
/N03.7 /N04.7 -F741
/Z13.2 K3

8 7 1 9 2 2

-SQF01 BCU E -XF872 -XF67 K1 K2


Push open

K1 K2
/Z09.1 C4 /Z05.6 /Z14.4 /Z14.5
-DO4
/Z05.6
12 4 8
7 8 2 10

C C

T.TC1 /N03.1

-X10 8 X10 9 -X10 11 12


-W164 12 13 14 15

+MK X10 1 2 3 4

-W186 9 10 11 12

D +QF01 TC1+ TB1 16 TB1 11 12 13 D


G03.6

3
PBS2
7 5
4
43A
6

-A3

TRIPPING COIL 1 1 3

E -P1 -P2 E
-S1 -S1
2 4

-A2 -52TC1
/Z15.4

G03.6/
TC1-

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE
TRIPPING CIRCUIT 1
24/11/2020
APPROVED NGUYEN DINH TUAN PECC2/TT-110KV/E02-132
CB E02-QF01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2
F861 F862 TRIP CIRCUIRT SUPERVISOR 2
F87T TRIP F67 TRIP TRIP TC2 TRIP TC2 CB E03-QF01
TC2 QF01 TC QF01
TC2+ TC2+ TC2-
A G03.6 N04.1 G03.6 A
-X20 2

-X20 8 9
3 11
-XF872 -XF67
/Z14.4 /Z14.5

TC2-
N04.1
4 12
B 862 F861 30 31 F862 30 31 1 2 B
/ N04.4 /N03.7 /N04.7
-F742 + -
3 3 3 3
/Z13.2 K3

F87T H F67 H
/Z02 BO2 /Z04 -BO2 K1 K2
K1 K2

/Z02.6 /Z04.6

4 4 12 4 8

T.TC2 /N04.1
C C
X20 10 12 13

-W165 17 18 19

+MK
X20 1 2 3

-W187 12 13 14

+QF01
D TC2+ TB1 26 TB1 23 24 25 D
G03.5

3
PBS2
7 5
4
43A
6

-A4
TRIPPING COIL 2
5

E -P2 E
-S1 -S1
6

-A4 -52TC2
/Z15.7

TC2-
G03.5

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE
TRIPPING CIRCUIT 2
24/11/2020
APPROVED NGUYEN DINH TUAN PECC2/TT-110KV/E02-132
CB E02-QF01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2

A 50BF(E02,E05), F87B INTERNAL LOAD F87T TRIP F67 TRIP RESET A


F87B TRIP
TRIP SEND F861 PROTECTION TRIP SHEDDING LOCKOUT 1 LOCKOUT 1 LOCKOUT F861

N01.7/
TC1+

X10 13 X10 14

K94.TC1+
-W161 8

=E05+CRP5 5 5

E02.TC1+
F87T H F67 H

N09.1 /
B /Z02 BO3 /Z04 BO3
B
/Z02.6 /Z04.6

6 6

=E05/N06.2 /
K81 3 7
/N13.4
9 3
11
BCU E -S.RL
/Z05.6 /Z09.7
-DO5
=E05/N06.2

=E05/N06.3 /Z05.6
C C

N09.1
10 4
5 13
-XF872 -XF67
E02.F861
E02.TC1

/Z14.4 /Z14.5

K94.861
6 14
-W161 7 9

X10 10 X10 15 X10 16


D D
/ N01.4
T.TC1

SET RESET
b d
-F861
a c

N01.8/
TC1-
E E

11 1 /M05.2 51 5 /R06.2
10 50
21 2 /N01.5 61 6 /R11.7
20 60
31 3 /N02.5 70 7
30 71
41 4 /N11.6 80 8
40 81

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN TRIP-LOCKOUT 1 CIRCUIT PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2

A 50BF(E02,E05), F87B 50BF J13 TRIP INTERNAL F67 TRIP LOAD F87T TRIP RESET A
F87B TRIP LOCKOUT 2 LOCKOUT 2
TRIP SEND F862 LOCKOUT 2 PROTECTION TRIP SHEDDING LOCKOUT F862

N02.5/
TC2+
X20 3 X20 4 5 X20 6
-W161 10 -W167 9

K94.TC2+
=E05+CRP5

=C42+J13
E02.TC2+
N02.5/
862
X ...

N09.5 /
B B

=E05/N06.5 /
7 7
F67 H 4 8 F87T H
/Z04 BO4 -K81 /Z02 BO4
/Z04.6 /N13.4 12 /Z02.6

8 8
11 3*
BCU E -S.RL
=E05/N06.5

=E05/N06.6

/Z05.6 /Z09.7
-DO6
/Z05.6
C C

N09.5
12 4*
7
E02.F862
E02.TC2

X ... -XF872
/Z14.4

K94.862
-W161 11 12 -W167 10 8

X20 11 X20 14 15 16
D D
/ N02.4
T.TC2

SET RESET
b d
-F862
a c

N02.8/
TC2-
E E

11 1 /M05.2 51 5 /R06.3
10 50
21 2 /N01.6 61 6 /R11.7
20 60
31 3 /N02.6 70 7
30 71
41 4 /N11.7 80 8
40 81

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N05

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN TRIP-LOCKOUT2 CIRCUIT PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2

F87T TRIP F67 TRIP 50BF BAY E03 F87T TRIP F67 TRIP
MV 22KV MV 22KV SET 86, 50BF 24KV SIDE MV 22KV MV 22KV
A A

MV22+
/ N09.1
X3 9 10

-W161 1

=E05+CRP5

E02.BF+
9 9 11 11
B F87T H F67 H F87T H F67 H B
/Z02 BO5 /Z04 BO5 /Z02 BO6 /Z04 BO6

=E05/N06.7 /
/Z02.6 /Z04.6 /Z02.6 /Z04.6

10 10 12 12

=E05/N06.7
-XF872 11
/Z14.4 -XF872
/Z14.4

C 10 C

E02.BF
12
N09.1/
K94.MV

-W161 2

X3 11 X3 12
X3 13 X3 14

-W167 1 2 3 4
D D

=C42+J13

XC 13
XC 14 XC 11 XC 12

SET 86, 50BF TRIP CB J13


E E
CUIBLE: J13 CUIBLE: J13

PAGE: =MV22+J13/Q03 PAGE: =MV22+J13/Q03

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N05 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N06

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN SEND TRIP CIRCUIT PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2

A A
BCU F87T MCB BCU MCB BCU
SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE
FAILED FAILED OFF TRIP

F67+
G03.2
X21 2 3 4

-W167 11

=C42+J13
B B
XY 23

5 11
-BCU A -
F87T J 12 14 96 98
/Z05.2 /Z01.3 -FQBCU -FQBCU
/Z01.3 /G02.3 11 /G02.3 95
C C
6 12
XY 24

-W167 12

X21 8 9 10 11 12 13 14 15 16 17

D D

4 6 8 10 12 14 16 2 4 6 8 10 12 14
F67 D F
/Z03 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 BI14 BI15
/Z03.6 /Z03.6 /Z03.6 /Z03.6 /Z03.6 /Z03.6 /Z03.6 /Z03.6 /Z03.6 /Z03.6 /Z03.6 /Z03.6 /Z03.6 /Z03.6

3 5 7 9 11 13 15 3 5 7 9 11 13

E E
X21 6 X21 7
F67-
G03.2

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N06 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N07

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT F67 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2
BUCHHOLZ RELAY RAPID PRESSURE RELAY OIL TEMP. 22KV WINDING TEMP.
TRIP OF TRANSFORMER TRIP RELAY TRIP RELAY TRIP

A A
SAFETY VAL OIL FLOW RAPID PRESSURE RELAY 110KV WINDING TEMP.
TRIP RELAY TRIP OF OLTC TRIP RELAY TRIP

87T+ 87T+
G02.2 / N10.1

-X12 2
=T2+LCB -W162 11

B B

X5 9

C C
X5 11 12 13 14 15 16 17 18

-W162 12 13 14 15 16 17 18 19

X12 7 8 9 10 11 12 13 14

KT1 KT2 KT3 KT4 KT5 KT6 KT7 KT8


D / N08.2 / N08.2 / N08.2 / N08.2 / N08.2 / N08.2 / N08.2 / N08.2 D

2 4 6 8 10 12 14 16
F87T D
/Z01
BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8
/Z01.6 /Z01.6 /Z01.6 /Z01.6 /Z01.6 /Z01.6 /Z01.6 /Z01.6

E 1 3 5 7 9 11 13 15 E

87T-
/ N10.1

-X12 6
87T- KT-
G02.2 / N08.2

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N07 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N08

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN INTERNAL PROTECTION TRANSFORMER TRIP PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2

A A

BUCHHOLZ RELAY RAPID PRESSURE RELAY OIL TEMP. 22KV WINDING TEMP.
TRIP OF TRANSFORMER TRIP RELAY TRIP RELAY TRIP
SAFTY VAL OIL FLOW RAPID PRESSURE RELAY 110KV WINDING TEMP.
TRIP RELAY TRIP OF OLTC TRIP RELAY TRIP

N07.6/
KT8
B B

N07.6/
KT7

N07.5/
KT6

N07.4/
KT5

N07.4/
KT4
C C

N07.3/
KT3

N07.3/
KT2

N07.2/
KT1

D D

14 14 14 14 14 14 14 14
-KT1 -KT2 -KT3 -KT4 -KT5 -KT6 -KT7 -KT8
220VDC 13 220VDC 13 220VDC 13 220VDC 13 220VDC 13 220VDC 13 220VDC 13 220VDC 13

E N07.6/
KT- E

5 9 /N09.2 5 9 /N09.2 5 9 /N09.2 5 9 /N09.3 5 9 /N09.3 5 9 /N09.4 5 9 /N09.4 5 9 /N09.4


1 1 1 1 1 1 1 1
6 10 /N09.5 6 10 /N09.6 6 10 /N09.6 6 10 /N09.7 6 10 /N09.7 6 10 /N09.7 6 10 /N09.8 6 10 /N09.8
2 2 2 2 2 2 2 2
7 11 /N09.2 7 11 /N09.2 7 11 /N09.2 7 11 /N09.3 7 11 /N09.3 7 11 /N09.4 7 11 /N09.4 7 11 /N09.4
3 3 3 3 3 3 3 3
8 12 /N09.5 8 12 /N09.6 8 12 /N09.6 8 12 /N09.7 8 12 /N09.7 8 12 /N09.7 8 12 /N09.8 8 12 /N09.8
4 4 4 4 4 4 4 4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N08 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N09

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN INTERNAL PROTECTION TRANSFORMER TRIP PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2

A A

N03.4/
K94.TC1+ N04.4/
K94.TC2+

1 5 1 5 1 5 1 5 1 5 1 5 1 5 1 5 2 6 2 6 2 6 2 6 2 6 2 6 2 6 2 6
B B
-KT1 -KT2 -KT3 -KT4 -KT5 -KT6 -KT7 -KT8 -KT1 -KT2 -KT3 -KT4 -KT5 -KT6 -KT7 -KT8
/N08.2 9 /N08.3 9 /N08.4 9 /N08.4 9 /N08.5 9 /N08.5 9 /N08.6 9 /N08.6 9 /N08.2 10 /N08.3 10 /N08.4 10 /N08.4 10 /N08.5 10 /N08.5 10 /N08.6 10 /N08.6 10

/ N03.4
K94.861 / N04.4
K94.862

C C

N05.4/
MV22+ R11.8/
FR.K94+

D 3 7 3 7 3 7 3 7 3 7 3 7 3 7 3 7 4 8 4 8 4 8 4 8 4 8 4 8 4 8 4 8 D
-KT1 -KT2 -KT3 -KT4 -KT5 -KT6 -KT7 -KT8 -KT1 -KT2 -KT3 -KT4 -KT5 -KT6 -KT7 -KT8
/N08.2 11 /N08.3 11 /N08.4 11 /N08.4 11 /N08.5 11 /N08.5 11 /N08.6 11 /N08.6 11 /N08.2 12 /N08.3 12 /N08.4 12 /N08.4 12 /N08.5 12 /N08.5 12 /N08.6 12 /N08.6 12

/ N05.2
K94.MV / R11.8
FR.K94-

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N09 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N10

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN INTERNAL PROTECTION TRANSFORMER TRIP PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2

A A

BUCHHOLZ RELAY LOW LEVEL OIL HIGH LEVEL OIL LOW LEVEL OIL HIGH LEVEL OIL OIL TEMP. 110KV WINDING TEMP. 22KV WINDING TEMP.
ALARM OF TRANS. ALARM OF TRANS. ALARM OF OLTC ALARM OF OLTC ALARM RELAY ALARM RELAY ALARM RELAY ALARM

87T+
N07.3

X12 3 X12 4
-W163 8

B B

=T2+LCB
-X6 6

C C

-X6 11 12 13 14 15 20 27 34

-W163 9 10 11 12 13 14 15 16

D D

X12 15 X12 16 X12 17 X12 18 X12 19 X12 20 X12 21 X12 22

2 4 6 8 10 12 14 16
F87T F
/Z01.6
E BI9 BI10 BI11 BI12 BI13 BI14 BI15 BI16
E
/Z01.6 /Z01.6 /Z01.6 /Z01.6 /Z01.6 /Z01.6 /Z01.6 /Z01.6

1 3 5 7 9 11 13 15

87T-
N07.7

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N10 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N11

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT F87T PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2

A F87T TRIP F67 TRIP F861 TRIP F862 TRIP A


START 50BF START 50BF START 50BF BAY E03 START 50BF BAY E03

15 1
B F87T H F67 G B
/Z02 BO8 /Z04 BO8
/Z02.6 /Z04.3

16 2 F861 40 41 F862 40 41
/N03.7 /N04.7
4 4

13 15
-XF872 -XF67
C /Z14.4 /Z14.5 C

14 16

-X3 15 16

-W161 3 4

D D
F87B.E02+

=E05+CRP5
E02.50BF
=E05/N12.3 /
=E05/N12.3

E E
F87T, F67 BAY E03
START 50BF

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N11 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N12

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN SIGNAL SEND TO F87B PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+MK

CB E02-QF01 CB E02-QF01 DS E02-QL02 DS E02-QL02


A CLOSED OPENED CLOSED OPENED A

-X3 13 14 15

-W186 2 -W188 9

+QF01 +QL02
B B

TB2 1 TB2 25 -X2 13 -X2 15

S2-1 S2-5 CS1-7 -CS1-8


/Z18.1 /Z18.5 /Z21.5 /Z21.5

C C

-TB2 2 -TB2 26 -X2 14 -X2 16

-W186 3 4 -W188 12 13
D D

-X3 21 23 26 27
-W176 1 2 3 4 5

=E05+CRP5
E02.MK+

E02.DSO
E02.CBO

E02.DSC
E02.CBC

E E
=E05/N09.5 /

=E05/N09.6 /

=E05/N09.6 /

=E05/N09.7 /
=E05/N09.5/

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N12 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N13

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT OF F87B PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E0X+XXX +CRP2 =E04+CRP4

A A

-W160
-X91 1 LOAD SHEDDING LEVEL 1 2 1 LV1.
/ =E04/N05.1

-X91 1 LOAD SHEDDING LEVEL 2 2 2 LV2.


/ =E04/N05.1

-X91 1 LOAD SHEDDING LEVEL 3 2 3 LV3.


/ =E04/N05.1

B -X91 1 LOAD SHEDDING LEVEL 4 2 4 LV4. B


/ =E04/N05.1

-X91 1 COM 2 5 COM.


/ =E04/N05.1

LEVEL 1

LEVEL 2

LEVEL 3

LEVEL 4
4 6 8 10
-S.81
C /Z09.1 C

14
-K81
D 220VDC 13 D

5 9
E 1 E
6 10
2
7 11 /N03.4
3
8 12 /N04.5
4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N13 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE P01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LOAD SHEDDING CIRCUIT PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

+MK
INTETLOCKING FOR INTETLOCKING FOR
INTETLOCKING FOR
CLOSE CB QF01 CLOSE CB QF01
A CLOSE/OPEN DS QL02 A
AT LOCAL AT REMOTE

INT_CB+ INT_CBR+ INT_QL02+


M05.2 M05.8 M01.3
-X11 4 -X3 2
-W188 14 -W188 15 -W186 1 -W185 7

=C42+J13
+QL02 -X2 3 +QL02 -X2 1 +QF01 -TB2 27 X... ...

B B

ES J01-QE38 OPENED
DS QL02 OPENED

CB QF01 OPENED
DS QL02 CLOSED
-CS1-2 -CS1-1 S2-6
/Z21.4 /Z21.3 /Z18.5

-X2 4 -X2 2 TB2 28 X... ...


C C
-W188 16 -W188 17 -W186 5 -W185 8

-X11 10 -X11 11 -X3 28 -X3 30


-W184 4

-W185 11 -W185 12 -W190 5

E5.Q24+
=E05+MK
=C42+J13

=C42+J13
-X... ... -X... ... +QE25 -XT2 3

=E05/P02.7 /
ES E05-QE24 OPENED
D D
CB J13 AT SERVICE

ES QE25 OPENED
CB J13 AT TEST

-CS1-2
/Z23.3

=E05/P02.7
E5.Q24-
-X... ... -X... ... -XT2 4
E E
-W185 9 -W185 10 -W190 6

-W184 3
-X11 6 -X11 8 -X3 29

-X3 10

INT_CB- INT_CBR- INT_QL02-


M05.4 M05.6 M01.4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE P01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE P02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN INTERLOCKING FOR CB, DS, ES PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+MK LIÊN ĐỘNG THAO TÁC =E05+MK
DNĐ QE25 -W188 -W184
2 -X3 3 1
E2.Q2+
ES+ / =E05/P04.5
A G04.6 A
-X3 16 +QL02 -X2 35
-W188 10

DS QL02 OPENED
+QL02 -X2 31 -CS1-18
/Z21.7
DS QL02 OPENED

-CS1-16 -X2 36
B /Z21.6 B

3 -X3 4 2
E2.Q2-
/ =E05/P04.6

-X2 32
-W188 11
=C42+J13
-W185
4 -X3 5 1 -X... ...
-X3 19
-W185 5
+QL02 -X2 27

C C
=C42+J13

-X... ...

DS QL02 OPENED
CB J01-QF01 AT TEST

-CS1-14
/Z21.6

-X2 28

-X... ...
5 -X3 6 2 -X... ...
D D
-W185 6

-W190
1 -X3 7 3 -X... ...
ES-
G04.6
-X3 20 -X3 24 +QE25 -XT2 27

-W190 3 4

ES QE25 OPENED
+QE25
-XT2 1 2 -CS1-8
E /Z23.4 E
13
-S4
14
-XT2 28
-KA4
/Z22.4
2 -X3 8 4 -X... ...

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE P02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Q01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN INTERLOCKING FOR CB, DS, ES PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2
S. CONTROL CB QF01 CB QF01 DS E02-QL02 ES E02-QE25

LAMT TEST AT "LOCAL" OPENED CLOSED OPENED CLOSED OPENED CLOSED


A A
G02.6/
SI+
-X7 2 -X7 3
-W164 5

+MK
-X7 1 -X7 2 -X7 3 -X7 4
-W186 6 -W189 1 -W190 7

+QF01 +QL02 +QE25


TB2 31 TB2 5 -X2 19 17 -XT2 19 17

B B

S2 S2 CS1 CS1 CS1 CS1


/Z18.6 /Z18.2 /Z21.5 /Z21.5 /Z23.5 /Z23.4

TB2 32 TB2 6 -X2 20 18 -XT2 20 18

-W186 7 8 -W189 2 3 -W190 8 9

-X7 5 6 7 8 9 10

C -W164 6 7 8 9 10 11 C
-X7 8 9 10 11 12 13
9 11 9 11
-SQF01 -SQL02
/Z09.1 /Z09.1
2 1
SQE25
/Z09.5 3
10 12 10 12

KT+
/ R10.5
D 3 D
1 5 1 5 2 6 3 7
-S.LT -KLCB -KST2 -KST2 -KST2
/Z09.5 /R10.4 /Q01.2 /Q01.2 /Q01.2
9 9 10 11
TEST

4 X1 X1
X1 -SQF01 -SQL02
14 14 PL01 /Z09.1 /Z09.1
-KST2 -KST1 /Z09.5 X2
220VDC 13 220VDC 13 X2 X2

E SI- E
/ R10.5
-X7 5 -X7 6 -X7 7
G02.6/
SI-

5 9 /Q01.4 5 9 /R10.6
1 1
6 10 /Q01.5 6 10 /R10.7
2 2
7 11 /Q01.6 7 11
3 3
8 12 8 12
4 4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Q01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Q02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN INDICATOR CIRCUIT PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2

A TEMPERATURE OF TEMPERATURE OF TEMPERATURE OF A


TAP POSITION SIGNAL
OIL TRANSFORMER 110KV WINDING 22KV WINDING

B B

64
F90
/Z08
-AI1

63

C 5 5 5 5 C
PTP PTO PTW1 PTW2
/Z11.3 /Z11.5 /Z11.3 /Z11.5
-AI -AI -AI -AI

3 3 3 3

-X7 14 15 16 17 18 19 20 21

D D
-W148 1 2 -W162 5 6 7 8 9 10

=T2+OLTC =T2+LCB

(+) (-) (+) (-) (+) (-) (+) (-)


AI04 11 14 X3 1 X3 2 3 4 7 8

E E
4-20mA 4-20mA 4-20mA 4-20mA

ANALOG OUPUT

CUIBLE: LOCAL

PAGE: =D1/10

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Q02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN TAP POSITION AND THERMAL WINDING INDICATOR CIRCUIT PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2

=E02+QF01
=E02+QF01 =E02+QF01 =E02+QF01 =E02+QF01 =E02+QF01 =E02+QF01
CONTROL SPARE
A CB OPENED CB CLOSED SF6 ALARM SF6 LOCKOUT SPRING DISCHARED MCB OFFF A
AT LOCAL

BCU+ BCU+
G02.4 R04.1
-X8 2
-W165 1

+MK BCU+
R02.1
-X8 1
B -W187 4 B

+QF01

TB2 29 3 TB1 40 -TB1 42 44 51 46 30 32 34 36 38

S2 S2 A2 A3 A4-1 LS-1 43A MCB1 MCB2 MCB3 MCB4 MCB5


/Z18.5 /Z18.2 /Z17.4 /Z17.4 /Z17.5 /Z17.6 /Z17.5 /Z17.2 /Z17.3 /Z17.3 /Z17.3 /Z17.4

C C

TB2 20 4 TB1 41 -TB1 43 45 52 47 31 33 35 37 39

-W187 5 6 7 8 9 10 11

X8 4 5 6 7 8 9 10

D D
-W165 2 3 4 5 6 7 8

X8 10 11 12 13 14 15 16 17
CBL
/ R10.1
1 2 4 5 7 8 10 11
- BCU I
/Z06.3
DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8
/Z06.3 /Z06.3 /Z06.3 /Z06.3 /Z06.3 /Z06.3 /Z06.3 /Z06.3
E E

3 6 9 12
BCU-
R02.1

-X8 8
BCU- -X8 9
G02.4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT BCU PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+MK

DS E02-QL02 DS E02-QL02 DS E02-QL02 DS E02-QL02 ES E02-QE25 ES E02-QE25 DS E02-QL02


SPARE
OPENED CLOSED CTR. AT LOCAL MCB OFF OPENED CLOSED MCB OFF
A A
BCU+ BCU+
R01.2 R03.1
-X8 2 -X8 3
-W189 4 -W190 10

+QL02 +QE25

X2 23 -X2 21 -X2 77 -X2 83 -X2 87 -X2 75 -X2 73 XT2 7 -XT2 1 -XT2 87


B B

CS1 CS1 SA1 QF1 QF3 KA1 QM1 CS1 CS1 QF3
/Z21.6 /Z21.5 /Z20.7 /Z20.7 /Z19.8 /Z19.5 /Z19.5 /Z23.3 /Z23.3 /Z22.8

X2 24 -X2 22 -X2 80 -X2 84 -X2 88 -X2 76 -X2 74 XT2 8 -XT2 2 -XT2 88

C C
-W189 5 6 7 8 -W190 11 12 13

-X8 11 12 13 14 15 16 17

+CRP2
-W165 9 10 11 12 -W166 1 2 3

D D
-X8 18 19 20 21 22 23 24 25

13 14 16 17 19 20 22 23
- BCU I
/Z06.3
DI9 DI10 DI11 DI12 DI13 DI14 DI15 DI16
/Z06.3 /Z06.3 /Z06.3 /Z06.3 /Z06.3 /Z06.3 /Z06.3 /Z06.3

E 15 18 21 24 E

BCU- BCU-
R01.8 R03.1

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT BCU PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+MK

=E02+MK =E02+MK =E02+MK


SPARE SPARE SPARE SPARE SPARE
MCB AC OFF MCB DC OFF MCB TRIP
A A
BCU+ BCU+
R02.8

12 14 12 14 12 14 12 14 96 98 96 98 96 98 96 98
-FQAC1 -FQAC2 -FQCB -FQDS -FQAC1 -FQAC2 -FQCB -FQDS
B /D02.3 /D02.5 /G04.3 /G04.4 /D02.3 /D02.5 /G04.3 /G04.4
B
11 11 11 11 95 95 95 95

C C

-X8 18 19 20

+CRP2
-W166 4 5 6

D D
-X8 26 27 28 29 30 31 32 33

1 2 4 5 7 8 10 11
- BCU J
/Z06.4
DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8
/Z06.5 /Z06.5 /Z06.5 /Z06.5 /Z06.5 /Z06.5 /Z06.5 /Z06.5

E 3 6 9 12 E

BCU- BCU-
R02.8 R04.1

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT BCU PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2

=E05+CRP5 =C42+J13 =C42+J13 MCB TUC42 OFF FAN GROUP 1 FAN GROUP 2
A SPARE SPARE A
MCB VT CL:0.5 OFF RELAY FAIL MCB RELAY OFF BLOCK 25 RUNNING RUNNING
BCU+ BCU+
R01.8 /R06.1
-X8 3 -X8 4 -X8 5 -X8 6
-W161 5 -W167 5 -W163

=C42+J13 =T2+LCB
=E05+CRP5

E02.BCU+

-XY 15
B B
BCU+
=E05/R08.6 /

/R05.1
-X0 1 -X0 3

C C
/=E05/R08.7

-XY 90 -XY 16 -X3 22 X0 2 X0 4


MCBVT20.5

D D
-W161 6 -W167 6 7 8 -W163 1 2

-X8 34 35 36 37 38 39 40 41
F1 F2
R10.1 R10.1

13 14 16 17 19 20 21 22
- BCU J
/Z06.4
E DI9 DI10 DI11 DI12 DI13 DI14 DI15 DI16
E
/Z06.4 /Z06.5 /Z06.5 /Z06.5 /Z06.5 /Z06.5 /Z06.5 /Z06.5

15 18 21 23

BCU- BCU-
R03.8 R05.1

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R05

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT BCU PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2

A A

FAN GROUP 1 FAN GROUP 2 FAN FAN =T2+LCB


SPARE
IS OK IS OK AT AUTO AT LOCAL MCB OFF

=T2+LCB

B B

R04.7/
BCU+
X0 5 7 9 11 13 15 17 19 21 24 X6 8

C C

X0 6 8 10 12 14 16 18 20 22 25 X6 28

-W163 3 4 5 6 7
D D

X8 42 43 44 45 46 47

1 2 4 5 7 8
- BCU K
/Z06.6
DI1 DI2 DI3 DI4 DI5 DI6
E /Z06.6 /Z06.6 /Z06.6 /Z06.6 /Z06.6 /Z06.6 E

3 6 9

BCU- BCU-
R04.8 R06.1

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R05 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R06

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT BCU PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2

A A
F861 F862 TCS1 TCS2 S.S. "BCU/MIMIC" S.S. "LOCAL/REMOTE" TRANS. S.S. "AUTO/MAN" TRANS. S.S. "SYN./BYPASS"
OPERATED OPERATED FAIL FAIL AT MIMIC AT REMOTE AT MAN AT SYN.

BCU+ BCU+
R04.7 / R07.1

B B

17 12 12
50 51 50 51 13 9 13 9 1
F861 F862 -S.B/M -S.L/R -S.A/M2
F741 F742 -S.25
/N03.7 /N04.7 /Z09.1 /Z10.4 /Z10.1
5 5 /Z13.3 5 /Z13.3 5
/Z09.4 MIMIC /Z10.6 REMOTE /Z10.3 MAN SYN.
2
18 11 11

C C

D D

10 11 13 14 16 17 19 20
- BCU K
/Z06.6
DI7 DI8 DI9 DI10 DI11 DI12 DI13 DI14
/Z06.6 /Z06.6 /Z06.6 /Z06.6 /Z06.6 /Z06.6 /Z06.6 /Z06.6

12 14 18 21
E E

BCU- BCU-
R05.8 R07.1

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R06 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R07

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT BCU PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2

=E02+CRP2 =E02+CRP2 =E02+CRP2


F67 FAIL F90 FAIL SPARE SPARE SPARE SPARE SPARE
MCB AC OFF MCB DC OFF MCB TRIP
A A

BCU+
R06.8

12 14 12 14 12 14 12 14 12 14 12 14 12 14 12 14 12 14 12 14 12 14
-FQSI -FQTC1 -FQTC2 -FQ67 -FQ87T -FQ90 -FQPM -FQCB -FQMF -FQDC1 -FQDC2
/G02.6 11 /G03.6 11 /G03.5 11 /G03.1 11 /G02.1 11 /G03.3 11 /G02.4 11 /G03.8 11 /G02.7 11 /G01.5 11 /G01.4 11
B B

11
- F67 J -F90 55 12 14
/Z03.3 /Z08
-R13 -FQAC
/Z08.6 54 56 /D01.4 11
12

96 98 96 98 96 98 96 98 96 98 96 98 96 98 96 98 96 98 96 98 96 98 96 98
F90F
/ R10.1 -FQAC -FQ90 -FQ87T -FQ67 -FQPM -FQSI -FQTC1 -FQTC2 -FQCB -FQMF -FQDC1 -FQDC2
C /D01.4 /G03.3 95 /G02.1 /G03.1 /G02.4 /G02.6 /G03.6 /G03.5 /G03.8 /G02.7 /G01.5 /G01.4
C
95 95 95 95 95 95 95 95 95 95 95

D D

X8 48 49 50 51 52

22 23 1 2 4 5 7 8 10 11
BCU K H
/Z06.6
DI15 DI16 DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8
E /Z06.6 /Z06.6 /Z07.3 /Z07.3 /Z07.3 /Z07.3 /Z07.3 /Z07.3 /Z07.3 /Z07.3 E

24 3 6 9 12

BCU- BCU-
R06.7 R10.1

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R07 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R08

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT BCU PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2
OLTC IN SLAVE MODE OLTC IN AUTO MODE
OLTC IN SLAVE MODE OLTC IN AUTO MODE SELECTED FROM BCU SELECTED FROM BCU
A A
OLTC IN MASTER MODE OLTC IN INDE. MODE OLTC IN MANUAL MODE
OLTC IN MASTER MODE OLTC IN INDE. MODE OLTC IN MANUAL MODE SELECTED FROM BCU SELECTED FROM BCU SELECTED FROM BCU

.F90+
R09.5

13 15
-S.L/R
/Z10.4
/Z10.6 LOCAL /Z10.7 LOCAL
B B
14 16

7 9 11 1 3 11 13 15 19 22
-S.M/S/I -S.A/M1 BCU D
/Z10.1 /Z10.1 /Z05.4 -DO6 -DO7 DO8 -DO9 -DO10
/Z10.3 MASTER /Z10.3 SLAVE /Z10.3 INDE /Z10.2 AUTO /Z10.2 MAN /Z05.4 /Z05.4 /Z05.4 /Z05.4 /Z05.4

8 10 12 2 4 12 14 16 21 24

C C

D D

12 13 14 16 17
-F90
/Z08
E E2 E3 E4 E5 E6
E
/Z08.3 /Z08.3 /Z08.3 /Z08.3 /Z08.3

20

.F90- .F90-
R08.5 R08.1

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R08 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R09

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT F90 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2

TAP CHANGER
SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE
A IN OPERATION A

F90+ .F90+
M02.7 R08.2

-X22 4 -X22 5
-W168 1

=T2+OLTC
X1 276
B B

C C
X1 300

-W168 7

-X22 15 16 17 18 19 20 21 22 23

D D

11 23 24 25 26 28 29 30 31
-F90
/Z08

E1 E9 E10 E11 E12 E13 E14 E15 E16


/Z08.3 /Z08.3 /Z08.3 /Z08.3 /Z08.3 /Z08.3 /Z08.3 /Z08.3 /Z08.3
E E

15 27 32

.F90-

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R09 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R10

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT F90 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2

FAN GROUP 1 FAN GROUP 2 F90 CB CONTROL


A RUNNING RUNNING HEALTHY AT LOCAL FAN GROUP1 FAN GROUP2 A
RUNNING RUNNING

R01.6/
CBL Q01.8/
KT+

B B
R07.2/
F90F

R04.7/
F2 1 5 1 5 1 5 2 6
-KSF1 -KST1 -KSF2 -KST1
/R10.2 9 /Q01.2 9 /R10.3 9 /Q01.2 10

C R04.6/
F1 C

D D

14 14 14 14 X1 X1
-KSF1 -KSF2 -KF90 KLCB P.CF1 P.CF2
220VDC 13 220VDC 13 220VDC 13 220VDC 13 /Z09.5 X2 /Z09.5 X2

R07.8/
BCU- Q01.8/
SI-

E E
5 9 /R10.6 5 9 /R10.7 5 9 /M02.4 5 9 /Q01.3
1 1 1 1
6 10 6 10 6 10 /M02.4 6 10
2 2 2 2
7 11 7 11 7 11 7 11
3 3 3 3
8 12 8 12 8 12 8 12
4 4 4 4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R10 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R11

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN MULTIPLED SIGNAL CIRCUIT AND LAMP INDICATOR FOR FAN OPERATORPECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+MK +CRP2
CB E02-QF01 CB E02-QF01
CLOSED OPENED
A A

F87T TRIP F67 TRIP F861 TRIP F862 TRIP INTERNAL TRANS.
SEND TO FR SEND TO FR SEND TO FR SEND TO FR PROTECTION TRIP

-X3 17 18

-W187 1
FR.K94+
/ N09.5
+QF01

B B
TB2 9 TB2 33
14 14
F87T H F67 H 60 61 60 61
/Z02 BO7 /Z04 BO7
F861 F862
/Z02.6 /Z04.6 /N03.7 /N04.7
6 6
15 15
S3-1 S3-5
/Z18.2 /Z18.6

C C

/ N09.5
-TB2 10 -TB2 34

FR.K94-
-W187 2 3

D D
-X3 22 25 -X3 17 -X3 18 -X3 19 -X3 20 -X3 21 -X3 22

=E00+FR

E02.F87T
CBE02.O
CBE02.C

E02.K94
E02.861

E02.862
E02.F67
FR+

FR+
E E
=E00+FR/R02.3 /

=E00+FR/R02.3 /

=E00+FR/R02.4 /

=E00+FR/R02.4 /

=E00+FR/R02.5 /

=E00+FR/R02.5 /

=E00+FR/R02.6 /
=E00+FR/R02.3 /

=E00+FR/R02.4 /

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R11 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R12

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN SEND SIGNAL CIRCUIT PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E03+CRP3 +CRP2 =E01+CRP1

A A

B -W147 B
A+ 1 A+
=E03/R09.8 / / =E01/R12.2

B- 2 B-
=E03/R09.8 / / =E01/R12.2

-X9 1 6 2 7 3 8 4 9 5 10

C C

9 10 9 10 9 10 9 10 2 3
PTO PTW1 PTW2 PTP PMF
/Z11.5 A(+) B(-) /Z11.3 A(+) B(-) /Z11.5 A(+) B(-) /Z11.3 A(+) B(-) /Z12.6 A(+) B(-)
RS485 RS485 RS485 RS485 RS485

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R12 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE S01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN MODBUS RS485 CIRCUIT PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CT =T2+CT =C42+J13
CORE 1 - CL: 3P,200-400- 600 /1A
GE
TYPE: OSKF145
NEUTRAL CT 110KV NEUTRAL CT 22KV
200-400-600/1/1/1/1A
A 5P20/5P20/0.5/0.5/5P20 CORE 2 - CL: 5P20 CORE 2 - CL: 5P20 A
A B C 200-400- 600 /1A 12000- 1600 /1A

CURRENT FOR F87T

CUIBLE: INCOMING

PAGE: =MV22+J01/T03

1S1 1S1 1S1 1S4 1S4 1S4 2S1 2S4 2S1 2S1
B B

+MK =T2+LCB
-W181 -W182
1 -W183
1 1 -W182
2 -W181
2 2

X4 O21 O24 X4 1O21 1O23


-X41 1 2 3 4 5 6 XIC 5 XIC 6 XIC 7 XIC 8

PE
C C

+CRP2
-W150 1 2 3 4 -W149 1 2 -W151 1 2 -W152 1 2 3 4

-X410 1 2 3 4 -X411 1 2 -X412 1 2 -X413 1 2 3 4

D D

1 3 5 7 9 11 13 15 17 19 21 23
-XF871
/Z14.4

2 4 6 8 10 12 14 16 18 20 22 24

24 26 28 16 14 18 20 22
E F87T C E
/Z01.3
IA(1) IB(1) IC(1) IY(HV) IY(LV) IA(2) IB(2) IC(2)

23 25 27 15 13 17 19 21

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE S01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE S02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CURRENT CIRCUIT OF RELAY F87T PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CT
GE
TYPE: OSKF145
200-400-600/1/1/1/1A
A A
5P20/5P20/0.5/0.5/5P20 CORE 2 - CL: 5P20, 200-400- 600 /1A CORE 5 - CL: 5P20, 200-400- 600 /1A
A B C A B C

B B

2S1 2S1 2S1 2S4 2S4 2S4 5S1 5S1 5S1 5S4 5S4 5S4

C C

+MK
-W181 -W182
3 -W183
3 3 -W182
4 -W181
4 4 -W177 -1W178 -1W179 1 -W178
2 -W177
2 2

X42 1 2 3 4 5 6 X45 1 2 3 4 5 6

D D

PE PE
-W180 1 2 3 4

=E00+FR =E05+CRP5
E02.CTN

E02.CTN
E02.CTA

E02.CTC

E02.CTA

E02.CTC
E02.CTB

E02.CTB
E E
=E00+FR/S01.4

=E00+FR/S01.4

=E00+FR/S01.5

=E00+FR/S01.5

=E05/S06.3

=E05/S06.4

=E05/S06.4

=E05/S06.4
CT E02 TO FR CT E02 TO F87B

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE S02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE S03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CURRENT CIRCUIT OF RELAY PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=T2+CT =E04+CRP4 =E00+FR =C42+J13
BUSHING TYPE CT TRANS. 110KV

A A

A B C BUSBAR VOLTAGE C12 - CL: 3P BUSBAR VOLTAGE C12 - CL: 3P BUSBAR VOLTAGE C11-CL: 3P

PHASE B (SYN CHECK)

B B
2S1 2S1 2S1 2S4 2S4 2S4

=E00+FR/S04.4

=E00+FR/S04.4

=E00+FR/S04.4

=E00+FR/S04.5
=E04/S04.7

=E04/S04.7

=E04/S04.8

=E04/S04.8
=T2+LCB

X4 A21 B21 C21 A24 B24 C24


XY 20 XY 22

E02.BVTA

E02.BVTB

E02.BVTC

E02.BVTN
BVT23P.A

BVT23P.B

BVT23P.C

BVT23P.N
PE

C C

+CRP2
-W153 1 2 3 4 -W154 1 2 3 4 -W155 1 2

X52 1 3 5 7 X52 2 4 6 8 X54 1 2

-X42 1 2 3 4

D D

1 3 5 7 21 23 25 27 17 19
-XF67
/Z14.5

2 4 6 8 22 24 26 28 18 20

3 6 8 12 19 20 21 22 23
E F67 C E
/Z03
IA IB IC IN VA VB VC VS

2 5 7 11 24

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE S03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE S04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CURRENT, VOLTAGE CIRCUIT OF RELAY F67 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=T2+CT =C42+J13
BUSHING TYPE CT TRANS. 22KV BUSHING TYPE CT TRANS. 110KV
CORE 2: CL: 5P20 RATIO 2000/1A CORE 3: CL: 5P20 RATIO 600/1A
A A B C A A

VOLTAGE FROM CVT 22KV CLASS 0.5

VOLTAGE 22KV

CUIBLE: INCOMING

PAGE: =MV24+J01/S01

2S1 2S1 2S1 2S4 2S4 2S4 3S1 3S4


B B

=T2+LCB

XY 25 26 27 28
X4 2A21 2B21 2C21 2C23 2B23 2A23 X4 A31 X4 A34

PE
C C

=C42+J13 +CRP2
-W157 1 2 3 4

-W156 1 2

-W020 1 2 3 4
X53 1 2 3 4

XIC 9 10 11 12
-X43 1 2
VB
/ T02.7

VN
D / T02.7 D

TO F67 INCOMING PANEL


1 3 1 3
-XTC2 -XTV2
/Z12.4 /Z12.4

2 4 2 4

E E

F90 1 21
/Z08
I1 U1

3 22

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE S04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE T01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CURRENT, VOLTAGE OF RELAY F90 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=T2+CT =E04+CRP4 =E00+FR
BUSHING TYPE CT TRANS. 110KV
BUSBAR VOLTAGE C12 - CL: 0.5 BUSBAR VOLTAGE C12 - CL: 0.5

A A B C 110 0.11 110 0.11 A


kV kV
3 3 3 3

=E00+FR/S04.6

=E00+FR/S04.6

=E00+FR/S04.6

=E00+FR/S04.7
=E04/T02.7

=E04/T02.8

=E04/T02.8

=E04/T02.8
2S1 2S1 2S1 2S4 2S4 2S4
B B

=T2+LCB

E02.BVTA1

E02.BVTB1

E02.BVTC1

E02.BVTN1
X4 A21 B21 C21 A24 B24 C24

BVT20.5.A

BVT20.5.B

BVT20.5.C

BVT20.5.N
PE

+CRP2
-W159 1 2 3 4

-W158 1 2 3 4

C C
-X51 1 3 5 7 -X51 2 4 6 8

-X44 1 2 3 4

V.A
/ T02.4

V.B
/ T02.5

V.C
D / T02.5 D
V.N
/ T02.5
1 5 7 1 3 5 7
3
-XTC1 -XTV1
/Z12.4 /Z12.4

2 6 8 2 4 6 8
4
V1 V2 V3 22
PMF S1 S1 S1
E /Z12.6 E
I1 I2 I3 V1 V2 V3

S2 S2 S2
N
A

C
B
T02.2

T02.2

T02.2

T02.3

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE T01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE T02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CURRENT, VOLTAGE CIRCUIT FOR BCU PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2

A A

/T01.1

/T01.2

/T01.2

/T01.3

/T01.6

/T01.6

/T01.6

/T01.6

/S04.8

/S04.8
A

V.A

V.B

V.C

V.N

VB

VN
B B

1 5 7 1 3 5 7 1 3
3
-XTC3 -XTV3 -XTV4
/Z12.4 /Z12.4 /Z12.5

C C
2 6 8 2 4 6 8 2 4
4

BCU L 15 11 7 3 21 23 25 27

/Z07.6
IA.1A IB.1A IC.1A IN.1A U V W N

16 12 8 4 22 24 26 28

D D

-X45 1 2 3 4

=E00+FR
E2.CTN
E2.CTA

E2.CTC
E2.CTB

E E
=E00+FR/S02.7

=E00+FR/S02.7

=E00+FR/S02.7

=E00+FR/S02.8

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE T02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE T03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CURRENT, VOLTAGE CIRCUIT FOR BCU PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CT
GE
TYPE: OSKF145
200-400-600/1/1/1/1A
A A
5P20/5P20/0.5/0.5/5P20 CORE 3 - CL: 5P20, 200-400- 600 /1A CORE 4 - CL: 5P20, 200-400- 600 /1A
A B C A B C

B B

3S1 3S1 3S1 3S4 3S4 3S4 4S1 4S1 4S1 4S4 4S4 4S4

C C

=E00+MP2
E02CT0.2.C1

E02CT0.2.A1

E02CT0.5.C1

E02CT0.5.A1
E02CT0.2.B1

E02CT0.5.B1
E02CT0.2.A

E02CT0.2.C

E02CT0.5.A

E02CT0.5.C
E02CT0.2.B

E02CT0.5.B
D D
=E00+MP2/T01.6

=E00+MP2/T01.6

=E00+MP2/T01.7

=E00+MP2/T01.7

=E00+MP2/T01.6

=E00+MP2/T01.6

=E00+MP2/T02.6

=E00+MP2/T02.6

=E00+MP2/T02.7

=E00+MP2/T02.7

=E00+MP2/T02.6

=E00+MP2/T02.6
E E

CT E02 TO PMT CLASS 0.2 CT E02 TO PMT CLASS 0.5

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE T03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE W01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CURRENT CIRCUIT FOR METTERING PANEL PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2 +MK

A A

-X3 23 24 25 26 27 28 29 30 -X3 31 32 33 34 35 36 37 38 39 40

-X7 22 23 24 25 -X7 11 12 13 14 15
B B

-X8 53 54 55 56 57 58 59 60 -X8 21 22 23 24 25 26 27 28 29 30

-X10 17 18 19 20 -X10 7 8 9 10 11 12 13 14 15

-X11 8 9 10 11 12 13 14 15 -X11 12 13 14 15 16 17 18 19 20

-X12 23 24 25 26 27 28 29 30 -X20 6 7 8 9 10 11 12 13 14 15
C C
-X20 17 18 19 20

-X21 18 19 20 21 22 23 24 25

-X22 24 25 26 27 28 29 30

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE W01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN SPARE CIRCUIT PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E02+CRP2

FUNCTION F87T P643 F87T CHỨC NĂNG


A A

C D
24 1
CURRENT INPUT PHASE A 110 kV SIDE /S01.1 IA(1) BI1 /N07.2 SAFETY VAL TRIP
23 2

26 3
CURRENT INPUT PHASE B 110kV SIDE /S01.2 IB(1) BI2 /N07.3 BUCHHOLZ RELAY TRIP
25 4

28 5
CURRENT INPUT PHASE C 110kV SIDE /S01.2 IC(1) BI3 /N07.3 OIL FLOW RELAY TRIP
B 27 6 B
18 7
CURRENT INPUT PHASE A 24KV SIDE /S01.6 IA(2) BI4 /N07.4 RAPID PRESSURE RELAY OF TRANSFORMER TRIP
17 8

20 9
CURRENT INPUT PHASE B 24KV SIDE /S01.7 IB(2) BI5 /N07.4 RAPID PRESSURE RELAY OF OLTC TRIP
19 10

22 11
CURRENT INPUT PHASE C 24KV SIDE /S01.7 IC(2) BI6 /N07.5 OIL TEMP. RELAY TRIP
21 12

F87T E 13
BI7 /N07.5 110KV WINDING TEMP. RELAY TRIP
C 24 14 C
IA(3)
23 15
BI8 /N07.6 22KV WINDING TEMP. RELAY TRIP
26 16
IB(3)
25 F F87T
28 1
IC(3) BI9 /N10.2 BUCHHOLZ RELAY ALARM
27 2

F87T C 3
BI10 /N10.3 LOW LEVEL OIL OF TRANS. ALARM
12 4
IY(TV)
D 11 5 D
BI11 /N10.3 HIGH LEVEL OIL OF TRANS. ALARM
14 6
NEUTRAL CURRENT INPUT 24KV SIDE /S01.4 IY(LV)
13 7
BI12 /N10.4 LOW LEVEL OIL OF OLTC ALARM
16 8
NEUTRAL CURRENT INPUT 110KV SIDE /S01.4 IY(HV)
15 9
BI13 /N10.5 HIGH LEVEL OIL OF OLTC ALARM
F87T J 10

1 11
POWER SUPPLY /G02.2 AUX BI14 /N10.5 OIL TEMP. RELAY ALARM
SUPPLY 12
2
E E
13
BI15 /N10.6 110KV WINDING TEMP. RELAY ALARM
11 14
F87T FAILURE /N06.2 15
12
BI16 /N10.7 22KV WINDING TEMP. RELAY ALARM
13 16

14

P54331RB7M0K18M

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE F87T P643 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E02+CRP2

FUNCTION F87T P543 F87T CHỨC NĂNG


A A

G H
1 1
BO9 BO1 /N01.4 F87T TRIP TC1 QF01
2 2

3 3
BO10 BO2 /N02.3 F87T TRIP TC2 QF01
4 4

5 5
BO11 BO3 /N03.5 F87T TRIP LOCKOUT 1
B 6 6 B
7 7
BO12 BO4 /N04.6 F87T TRIP LOCKOUT 2
8 8

9 9
BO13 BO5 /N05.2 F87T TRIP MV 22KV
10 10

11 11
BO14 BO6 /N05.7 F87T TRIP MV 22KV
12 12

13 13

14 BO15 BO7 14 /R11.5 F87T TRIP SEND TO FR


C C
15 15
16 16

17 BO16 BO8 17 /N11.4 F87T TRIP START 50BF

18 18

D D

E E

P54331RB7M0K18M

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE F87T P643 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2

FUNCTION F67 P143 F67 CHỨC NĂNG


A A

C D
5A
1 1
BI1 /M05.5 START SOTF
1A
CURRENT INPUT PHASE A /S03.1 2 IA 2

3 3
5A BI2 /N06.1 BCU FAILED
4 4
1A
CURRENT INPUT PHASE B /S03.2 5 IB 5
BI3 /N06.2 F87T FAILED
B 6 6 B
5A
7 7
BI4 /N06.3 MCB BCU OFF
1A
CURRENT INPUT PHASE C /S03.2 8 IC 8

9 9
5A BI5 /N06.3 MCB BCU TRIP
10 10
1A
CURRENT INPUT PHASE N /S03.3 11 IN 11
BI6 /N06.4 SPARE
12 12
5A
13 13
BI7 /N06.4 SPARE
1A
C 14 IN_SEN. 14 C
15 15
BI8 /N06.5 SPARE
19 16
VOLTAGE INPUT BVT C11 PHASE A /S03.4 VA
F F67
20 1
VOLTAGE INPUT BVT C11 PHASE B /S03.4 VB BI9 /N06.5 SPARE
2

21 3
VOLTAGE INPUT BVT C11 PHASE C /S03.5 VC BI10 /N06.6 SPARE
22 4
D 5 D
23 BI11 /N06.6 SPARE
6
/S03.7 VS
24
7
BI12 /N06.7 SPARE
8

F67 9
J BI13 /N06.7 SPARE
10
1
AUX
POWER SUPPLY /G03.2 SUPPLY
11
2 BI14 /N06.8 SPARE
12
E E
13
11 BI15 /N06.8 SPARE
F67 FAIL /R07.1 14
12
15
13 BI16 /M05.6 CLOSE cmd. WITH SYN.
16
14

P14331RA7M0B58L

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE F67 P143 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2

FUNCTION F67 P143 F67 CHỨC NĂNG


A A

G H
1 1
F67 TRIP START 50BF /N11.5 BO8 BO1 /N01.5 F67 TRIP TC1 QF01
2 2

3 3
BO9 BO2 /N02.4 F67 TRIP TC QF01
4 4

5 5
BO10 BO3 /N03.6 F67 TRIP LOCKOUT 1
B 6 6 B
7 7
BO11
8 BO4 8 /N04.4 F67 TRIP LOCKOUT 2

9 9

10 10

11 BO5 11 /N05.3 F67 TRIP MV 22KV


BO12
12 12

13 13

14 BO13 BO6 14 /N05.8 F67 TRIP MV 22KV


C C
15 15
16 16

17 BO14 BO7 17 /R11.6 F67 TRIP SEND TO FR


18 18

D D

E E

P14331RA7M0B58L

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z05

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE F67 P143 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2

A A

MODULE BIU241 BCU BCU BCU


FUNCTION MODULE DOU201 FUNCTION FUNCTION
- A D E

O2 1 1
DO1 /M03.5 EMERGENCY STOP FROM BCU /M01.7 CLOSE DS QL02 FROM BCU
2 2
O1 3 3
DO2 /M04.6 CONTROL FAN AUTOMATIC FROM BCU /M01.7 OPEN DS QL02 FROM BCU
4 4
B B
WD 6 /N06.1 BCU FAIL 5
DO3 /M05.4 CLOSE CB QF01 FROM BCU
5 6

VIN
7 7
+ DO4 /M04.7 ON/OFF FAN GROUP 1 FROM BCU /N01.3 OPEN Cmd. CB FROM BCU
DI1 8
- 8
VIN
- 9 9
DI2
+ DO5 /M04.8 ON/OFF FAN GROUP 2 FROM BCU /N03.7 RESET LOCKOUT F861
10 10

11 11
DO6 /R08.5 OLTC IN MASTER MODE SELECTED FROM BCU /N04.7 RESET LOCKOUT F862
RS232/ RXD/TB
RS485 12 12
C SERIAL
C
SG(0V)
LINK 1
13 13
DO7 /R08.6 OLTC IN SLAVE MODE SELECTED FROM BCU
TXD/TA
14 14
SG(0V)
RS232/
RS422/ 15 15
RS485 DO8 /R08.6 OLTC IN INDE. MODE SELECTED FROM BCU
CTS
16 16
RXD/TB
17 17
SERIAL
LINK 2 TXD/TA
18 18
RTS/RB
19 19

D
RA
20 DO9 21 /R08.7 OLTC IN AUTO MODE SELECTED FROM BCU D
RCD
21 20

= + 23 22
GND /G02.3
22 DO10 24 /R08.7 OLTC IN MANUAL MODE SELECTED FROM BCU
_
= 24 23
Power
Supply

E E

C264U11M6A10013302100001111D10

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z05 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z06

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE BCU C264 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2

A A

BCU BCU BCU


MODULE DIU200 FUNCTION FUNCTION FUNCTION
- I - J - K
VIN
+
VIN
+ 1 /R01.2 =E02+QF01 CB OPENED /R03.2 =E02+MK MCB AC OFF /R05.2 FAN GROUP 1 IS OK
DI2 DI1
- - 2 /R01.3 =E02+QF01 CB CLOSED /R03.3 =E02+MK MCB DC OFF /R05.4 FAN GROUP 2 IS OK

3
B VIN
+
VIN
+ 4 /R01.3 =E02+QF01 SF6 ALARM /R03.4 =E02+MK MCB TRIP /R05.6 FAN AT AUTO B
DI4 DI3
- - 5 /R01.4 =E02+QF01 SF6 LOCKOUT /R03.4 SPARE /R05.6 FAN AT LOCAL

6
VIN
+
VIN
+ 7 /R01.5 =E02+QF01 SPRING DISCHARED /R03.5 SPARE /R05.7 =T2+LCB MCB OFF
DI6 DI5
- - 8 /R01.5 =E02+QF01 CONTROL AT LOCAL /R03.6 SPARE /R05.7 SPARE

9
VIN
+
VIN
+ 10 /R01.6 =E02+QF01 MCB OFFF /R03.6 SPARE /R06.2 F861 OPERATED
DI8 DI7
- - 11 /R01.7 SPARE /R03.7 SPARE /R06.3 F862 OPERATED

C 12 C
VIN VIN
13 /R02.2 DS E02-QL02 OPENED /R04.2 =E05+CRP5 MCB VT CL:0.5 OFF /R06.4 TCS1 FAIL
+ +
DI10 DI9
- - 14 /R02.3 DS E02-QL02 CLOSED /R04.2 =C42+J13 RELAY FAIL /R06.4 TCS2 FAIL

15
VIN
+
VIN
+ 16 /R02.3 DS E02-QL02 CTR. AT LOCAL /R04.3 =C42+J13 MCB RELAY OFF /R06.5 S.S. "BCU/MIMIC" AT MIMIC
DI12 DI11
- - 17 /R02.4 DS E02-QL02 MCB OFF /R04.4 SPARE /R06.6 S.S. "LOCAL/REMOTE" TRANS. AT REMOTE

18
VIN
+
VIN
+ 19 /R02.6 ES E02-QE25 OPENED /R04.4 SPARE /R06.7 S.S. "AUTO/MAN" TRANS. AT MAN
D DI14 DI13 D
- - 20 /R02.6 ES E02-QE25 CLOSED /R04.5 MCB TUC42 OFF BLOCK 25 /R06.7 S.S. "SYN./BYPASS" AT SYN.

21
VIN
+
VIN
+ 22 /R02.7 DS E02-QL02 MCB OFF /R04.6 FAN GROUP 1 RUNNING /R07.1 F67 FAIL
DI16 DI15
- - 23 /R02.7 SPARE /R04.7 FAN GROUP 2 RUNNING /R07.2 F90 FAIL

24

E E

C264U11M6A10013302100001111D10

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z06 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z07

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE BCU C264 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E02+CRP2

A A
BCU
MODULE TMU220 FUNCTION
- L
BCU IN.5A
MODULE CCU200 FUNCTION
-H
1 2
VIN
+
VIN
+ 1 /R07.3 =E02+CRP2 MCB AC OFF IN.1A /T02.3 CURRENT CIRCUIT BAY E02-PHASE N
DI2 DI1
- - 2 /R07.3 =E02+CRP2 MCB DC OFF
3 4
3
IC.5A
VIN
+
VIN
+ 4 /R07.4 =E02+CRP2 MCB TRIP
B DI4 DI3 5 6 B
- - 5 /R07.4 SPARE
IC.1A /T02.2 CURRENT CIRCUIT BAY E02-PHASE C
6 7 8
VIN
+
VIN
7 /R07.5 SPARE
DI6 DI5 IB.5A
- - 8 /R07.6 SPARE 9 10
9
IB.1A /T02.2 CURRENT CIRCUIT BAY E02-PHASE B
VIN
+
VIN
+ 10 /R07.6 SPARE 11 12
DI8 DI7
- - 11 /R07.7 SPARE
IA.5A
12 13 14
C C
13
IA.1A /T02.2 CURRENT CIRCUIT BAY E02-PHASE A
CO1 14 15 16
15

16 17 18
CO2
17
X
18 19 20

19
U /T02.4 VOLTAGE CIRCUIT BVT C11 PHASE A
D CO3 20 21 22 D
21
V /T02.5 VOLTAGE CIRCUIT BVT C11 PHASE B
22 23 24
CO4
23
W /T02.5 VOLTAGE CIRCUIT BVT C11 PHASE C
24 25 26

N /T02.7 VOLTAGE CIRCUIT TU4T2 PHASE B


27 28

E E

C264U11M6A10013302100001111D10

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z07 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z08

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE BCU C264 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E02+CRP2

FUNCTION -F90 -F90 FUNCTION


REG-DA
A A
1 56
CURRENT CIRCUIT BUSHING CT-PHASE A /S04.4 I1
3 Life Contact R13 55 /R07.2
54

2 Auto 19
VOLTAGE CIRCUIT TU-C41 PHASE A /S04.6 U1
5 R12 20
Manual 21

21 + R11 47
_ = Power
POWER SUPPLY /G03.3 =
22 Supply R10 48
B R9 49 B
TAP CHANGER IN OPERATION /R09.3 11 E1 TC in op. R8 50
OLTC IN MASTER MODE /R08.2 12 E2 Progr. R7 51
OLTC IN SLAVE MODE /R08.2 13 E3 Progr. R6 52
OLTC IN INDE. MODE /R08.3 14 E4 Progr. 53
15
OLTC IN AUTO MODE /R08.4 16 E5 Auto 46
OLTC IN MANUAL MODE /R08.4 17 E6 Manual 45
Raise R1 /M02.5 RAISE COMMAND & AUTO FROM F90
RAISE TAP. FROM MIMIC /M02.2 18 E7 Progr. 44
LOW TAP. FROM MIMIC /M02.3 19 E8 Progr. 43
20 42
SPARE /R09.3 23 E9 BCD1
Lower
41
R2 /M02.6 LOWER COMMAND & AUTO FROM F90
C SPARE /R09.4 24 E10 BCD2 40 C
/R09.4 25 E11 BCD4 39
/R09.5 26 E12 BCD8 38
Progr. R3
27 37
/R09.5 28 E13 BCD10 36
Progr. R4
/R09.6 29 E14 BCD20 35
/R09.6 30 E15 BCD sgn 34
Progr. R5
/R09.7 31 E16 Progr. 33
32
GND
86
63 + CTS
85
TAP POSITTION SIGNAL /Q02.1 _ AI1 RTS
64 84
D COM2 RS232 RxD D
83
TxD
82
81

Rx-
80
Rx+
79
COM3 RS485 Tx-
78
Tx+
77

E E
100BASE-TX

RJ45

A-EBERLE: REG-DA B0 H0 F1 M1 S0 T0 K1 E00 D0 C00 XW94 G2 A2

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z08 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z09

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE F90 (REG-DA) PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2
SELECTED SWITCH "BCU/MIMIC": SA16-FA 6037-61042/SALZER
PUSH BUTTON 1NO
PUSH BUTTON RESET LOCKOUT 2 NO
A MIMIC X X X X X X X X X A
3 3 3*

1 3 5 7 9 11 13 15 17
MIMIC
BCU

4 4 4*

2 4 6 8 10 12 14 16 18 -S.LT /Q01.2 GREEN -S.RL /N03.8 /N04.8 RED

-S.ES /M03.6 GREEN


S.B/M /M01.4 /M05.7 /N01.2 /R06.5

B B

LAMP FOR CB AT LOCAL, FAN RUNNING

X1
CLOSE X

OPEN X
LED X2
INDICATOR
PUSH CLOSE X X
C /Q01.3 RED C
-PL01 CB E03-QF01 AT "LOCAL"
PUSH OPEN X X

-PL02
Push close

Push close
Push open

Push open

1 3 5 7 9 11 L1
-PL03
close
open

-P.CF1 /R10.6 FAN GROUP1 RUNNING RED

2 4 6 8 10 12 L2 -P.CF2 /R10.7 FAN GROUP1 RUNNING RED

D D
-SQF01 /M05.7 /N01.2 /Q01.4 /Q01.5 /Q01.5
ES SEMAPHORE: SPSR/FUJI
-SQL02 /M01.5 /M01.6 /Q01.6 /Q01.6 /Q01.6

+(~)

ES Semaphore
SELECT SWITCH "OFF/1/2/3/4" : SA25/SALZER
FUJI
2 1 2 1 2
SPSR
1 91-230 VAC/DC -(~) 3 3
OFF
1
2
3
4

E E

2 4 6 8 10 -SQE25 /Q01.7

-S.81 /N13.4 /N13.4 /N13.5 /N13.5

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z09 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z10

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE CONTROL DEVICES PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2

A A

SELECTOR SWITCH "MASTER/SLAVE/INDEP.":


SA25/SALZER
SELECTED SWITCH "LOCAL/REMOTE": SA25/SALZER

MASTER X X LOCAL X X X X X X

SLAVE X X REMOTE X X X X X X

B INDEP. X X
B
1 3 5 7 9 11 13 15 17 19 21 23

REMOTE
LOCAL
1 3 5 7 9 11
MASTER

INDEN.
SLAVE

2 4 6 8 10 12 14 16 18 20 22 24

2 4 6 8 10 12
S.L/R /M02.2 /M04.3 /M04.4 /R06.6 /R08.2 /R08.4

S.M/S/I /M02.3 /M02.2 /R08.2 /R08.2 /R08.3

C C
SELECTED SWITCH ."RAISE/OFF/LOWER" SA25/SALZER
SELECTED SWITCH "AUTO/MANUAL": SA25/SALZER SELECTED SWITCH "ON/OFF": SA25/SALZER

AUTO X X X ON X X X RAISE X X

MANUAL X X X OFF X X X LOWER X X

1 3 5 7 9 11 1 3 5 7 9 11 1 3 5 7
MANUAL

LOWER
RAISE
AUTO

OFF
ON
D D
2 4 6 8 10 12 2 4 6 8 10 12 2 4 6 8

-S.R/O/L /M02.2 /M02.3


S.A/M1 /R08.4 /R08.4 /M02.2 SCF1 /M04.4

S.A/M2 /M04.3 /M04.3 /M04.4 /R06.7 SCF2 /M04.6

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z10 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z11

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE CONTROL DEVICES PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2

A A

Digital Meter -PTP FUNCTION -PTO FUNCTION


MT4W

Com (1÷20)
10
1 - 19 /R12.6 MODBUS PROTOCOL /R12.2 MODBUS PROTOCOL
9

+
= 3
B TEMPERATURE OF OIL TRANSFORMER B
4-20mA /Q02.1 TAP POSITTION SIGNAL /Q02.3
= _ 5

6
Hold Zero
7

~ 8
Power
Supply
24VDC /G02.4 POWER SUPPLY /G02.5 POWER SUPPLY
= 9

C C

Digital Meter -PTW1 FUNCTION -PTW2 FUNCTION


MT4W
Com (1÷20)

10
D 0-150°C /R12.3 MODBUS PROTOCOL /R12.4 MODBUS PROTOCOL D
9

+
= 3
4-20mA /Q02.5 TEMPERATURE OF 110KV WINDING /Q02.7 TEMPERATURE OF 22KV WINDING
= _ 5

6
Hold Zero
7
E E
~ 8
Power
Supply
24VDC /G02.6 POWER SUPPLY /G02.7 POWER SUPPLY
= 9

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z11 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z12

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE INDICATOR METTER PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2

CURRENT TEST BLOCK


Multi-function -PMF CHỨC NĂNG
A A
L1 L2 L3 ELITE
-KTT-AW4
XTC1 XTC2 XTC3
V1 /T01.5
S1 V1 VOLTAGE CIRCUIT PHASE A
1 2
S2

V2 /T01.5
S1 V2 VOLTAGE CIRCUIT PHASE B
3 4

EQUIPMENT
S2
B B
S1 /T01.1 /S04.4 /T02.1 V3 V3 /T01.6 VOLTAGE CIRCUIT PHASE C
5 6
S2

VN VN
7 8
S1
/T01.1
I1 CURRENT CIRCUIT BAY-PHASE A
S2

S1
/T01.2
C I2 CURRENT CIRCUIT BAY-PHASE B
C
S2

S1
VOLTAGE TEST BLOCK /T01.2
I3 CURRENT CIRCUIT BAY-PHASE C
S2
L1 L2 L3
-KTT-VW4
XTV1 XTV2 XTV3 XTV4
1a Tx
1 2 2
1n
RS485 RS232 Rx /R12.7 MODBUS PROTOCOL
D 3 D
1a GND
3 4 5
EQUIPMENT

1n

1a /T01.5 /S04.6 /T02.4 /T02.6


5 6
1n

7 8 + (L)
= P
E Power (~) E
Supply - (N) /G02.7 POWER SUPPLY
= N

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z12 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z13

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE CURRENT AND VOLTAGE TESTBLOCK PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2

A A

TRIP SUPERVISION RELAY

5 6 1

B
VDF-10 B

K1 K2

C C

K3-1 K3-2
K1 K2 K3

D 9 13 10 14 12 4 8 2 D

-F741 TRIP CIRCUIRT SUPERVISOR 1 CB E03-QF01


/R06.3 /M05.3
/N01.7

-F742 /R06.4 TRIP CIRCUIRT SUPERVISOR 2 CB E03-QF01


/M05.3
/N02.7
E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z13 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z14

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE RELAY F74 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP2

RELAY TEST BLOCK


A A

TSB-14 XF871 XF872 XF67

1 2 /S01.1 /N01.4 /S03.1

3 4 /S01.2 /N02.3 /S03.2

B B
5 6 /S01.2 /N03.5 /S03.2

7 8 /S01.2 /N04.6 /S03.3

9 10 /S01.4 /N05.3 /N01.5

11 12 /S01.4 /N05.8 /N02.4


C C

13 14 /S01.4 /N11.4 /N03.6

15 16 /S01.5 /N11.5

17 18 /S01.6 /S03.7

D D
19 20 /S01.7 /S03.8

21 22 /S01.7 /S03.4

23 24 /S01.7 /S03.4

E E
25 26 /S03.5

27 28 /S03.5

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z14 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z15

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE RELAY TESTBLOCK PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

TC1 TC2
LOCAL CLOSE REMOTE AUTO LOCAL REMOTE P.D.
TC1 SF6 PRESSURE LOCAL REMOTE P.D.
TC2 SF6 PRESSURE
A SUPVN. SUPVN. SUPVN. SUPVN. A
INTELOCK CLOSE RECLOSE TRIP 1 TRIP 1 TRIP POST CLOSE ALARM & LOCKOUT TRIP 2 TRIP 2 TRIP POST CLOSE LOCKOUT
PRE CLOSE PRE CLOSE

220VDC1 TB1 15 14 TB1 18 19 TB1 17 220VDC2 TB1 22 TB1 16 TB1 11 12 TB1 13 220VDC3 TB1 27 TB1 26 TB1 23 24 TB1 25

MCB3 MCB4 MCB5


TB1 J1 K71 TB1 J3 K171 TB1 J1 K371
5 7 9
K13A K9 K17 K71
3
PBS1 3 3
4
PBS2 PBS2
4 TB1 20 TB1 21 4 TB1 30
3 1
B L 0 R
DMA DMA
B
K21 K13 K3 K5 K7 K321 K313 K303 K305 K307
43A
1 3 5
2
7 5 7 5
L O R L O R
K11 43A 43A
P1 P2 P2

K17 6 6

2 4 6

21
TB1 23 24 TB1 32
21
94
C 22 C

K701

31 31 21

A3 A3 A4
32
32 22
K703

31
A4
32
K17 K73 K173 K373
K705

D 9 13 1 D
S1 94 S1 11 13
10 2 3 5
14
K707
S1 S1 S1 S1
4 12 6 14
9
K25 K325
LS
10

K709
1 1
1 K79
52CC 52TC1 52TC2
A1 A1 A1 A1
2 2 2
94 A2 A3 A4
K74
A2 A2 A2 A2
E E
MCB3 MCB4 MCB5
TB1 J2 K72 TB1 J2 K172 TB1 J2 K372
6 8 10

TB1 31

=E02 -QF01 /M05.4 /N01.3 /N02.3

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z15 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z16

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CB REFERENCE (GL312F1/GE) PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A MOTOR CIRCUIT HEATING & LIGHTING CIRCUIT A

220VDC 220V AC
TB1
M1 (Ph)
TB1 MCB2
3 1 H1
1 2
MPCB1 1
2
B B
M3

H3
3

MPCB1
4

1
LS
2

1 1
C M5 C
DS TH
2 2
M7

X1 H5 H7
M A1

M TR1 X1 1
A2 IL H
X2
X2 2

M6

D D

LS
3

M4

6
220V AC
MPCB1 (N)
E 5
MCB2 E
TB1 TB1
M2 H2 H4
4
3 4
2

=E02 -QF01 /G04.3 /D03.3

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z16 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z17

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CB REFERENCE (GL312F1/GE) PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

CLOSING AND TRIPPING COIL 1 SUPPLY MCB TRIPPED ALARM


A A

HEATING AND LIGHTING SUPPLY MCB TRIPPED ALARM

TRIPPING COIL 1 SUPPLY MCB TRIPPED ALARM

TRIPPING COIL 2 SUPPLY MCB TRIPPED ALARM


MOTOR SUPPLY MCB TRIPPED ALARM

SF6 GAS 2ND STAGE (P2) LOCKOUT

SF6 GAS 2ND STAGE (P2) LOCKOUT

REMOTE POSITION SIEMENSECTED

SPRING CHARGE FAILURE ALARM


LOCAL POSITION SIEMENSECTED
SF6 GAS 1ST STAGE (P1) ALARM

SPRING CHARGED 1NDI ALARM.


B B

SPRING DISCHARGED ALARM


C C
TB1 30 TB1 32 TB1 34 TB1 36 TB1 38 TB1 40 TB1 42 TB1 44 TB1 47 TB1 48 TB1 49 TB1 51 TB2 49

X1-1 X1-3 X1-5 X1-7 X1-9 X3-11 X3-21 X4-2 X4-3 X5-1 X6-1 X7-1

15 13
L O R 15
11 11 11 11 11 13 13 13 11 5
43A
MPCB1 MCB2 MCB3 MCB4 MCB5 A2 A3 A4 LS TR1 LS
14 16 18
12 12 12 12 12 14 14 14 6
D 12 D
X1-2 X1-4 X1-6 X1-8 X1-10 X3-12 X3-22 X4-1 X5-2 X6-2 X7-2

TB1 31 TB1 33 TB1 35 TB1 37 TB1 39 TB1 41 TB1 43 TB1 45 TB1 46 TB1 50 TB1 52 TB2 50

=E02 -QF01 /R01.6 /R01.6 /R01.7 /R01.7 /R01.8 /R01.3 /R01.4 /R01.4 /R01.5 /R01.5
E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z17 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z18

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CB REFERENCE (GL312F1/GE) PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

B B

AUXILIARY CONTACTS

C MC SPARE AUXILIARY CONTACTS 12NO+12NC C

TB2 1 TB2 3 TB2 5 TB2 7 TB2 9 TB2 11 TB2 13 TB2 15 TB2 21 TB2 23 TB2 25 TB2 27 TB2 29 TB2 31 TB2 33 TB2 35 TB2 37 TB2 39 TB2 41 TB2 43 TB2 45 TB2 47
TB2 17 TB2 19

3 1 3 5 1 3 5 11
1 5 7 7 7 9 11 15 15 9 11 9 13 15
13 15
S2 S2
S3 S3 S3 S3 S4 S4 S4 S4 S4 S4
S2 S2 S2 S2 S1 S2 S3 S3 S3 S4 S4
S3
D 2
4 6 8
2 4 6 8
2 4 6 8 10 12 16 10 12 10 12 14 16
D
16 14 16

U20 U24 U28 U32


U35

TB2 2 TB2 4 TB2 6 TB2 8 TB2 10 TB2 12 TB2 14 TB2 18 TB2 22 TB2 26 TB2 28 TB2 30 TB2 32 TB2 34 TB2 36 TB2 38 TB2 40 TB2 44 TB2 46 TB2 48
TB2 16 TB2 20 TB2 24 TB2 42

=E02 -QF01 /N12.3 /R01.3 /Q01.5 /R11.2 /N12.4 /P01.6 /R01.2 /Q01.4 /R11.3

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z18 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z19

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CB REFERENCE (GL312F1/GE) PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

MOTOR CIRCUIT CMM 400/800 SIGNALLINGS HEATING & LIGHTING CIRCUIT SIGNALLINGS

A A

220VDC
-X1 1 2

1 3 5

-QM1
I> I> I>

2 4 6
B B

1 1 1
KM2 KM1 R3
2 2 2
C C
3 3 -1NC -1NC
KM2 KM1 KM1 KM2
4 4 -2NC -2NC

1
13 5 A1
-M1
M SQ100 KM2 -KA1
300W 14 6 A2
D 2 D

5
KM1
6

E E
=E02 - QL02 /G04.4 /R02.4 /R02.5 /D03.5 /R02.4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z19 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z20

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN DS REFERENCE PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

CONTROL CIRCUIT SIGNALLINGS


A A

220 VDC

B B

C C

D D

=E02 - QL02 /M01.5 /R02.4 /R02.3

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z20 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z21

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN DS REFERENCE PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A AUXILIARY CONTACTS A

DS CLOSED

B B

C C

DS OPENED

D D

=E02 -QL02 /P01.4 /P01.2 /N12.5 /N12.5 /Q01.6 /Q01.6 /R02.3 /R02.2 /P02.5 /P02.2 /P02.5
E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z21 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z22

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN DS REFERENCE PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

INTERLOCKING CIRCUIT HEATING CIRCUIT SIGNALLINGS


A A

B B

C C

D D

E E

- +QE25 /P02.3 /D03.6 /R02.7

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z22 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z23

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN ES REFERENCE PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

AUXILIARY CONTACTS

A A

B B

C C

D D

E E

- +QE25 /R02.6 /P01.6 /R02.6 /P02.5 /Q01.7 /Q01.7

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z23 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE +CRP2/X100

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN ES REFERENCE PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+CRP2-XAC A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +CRP1 -XAC 2 1 +/D01.2
=E03 +CRP3 -XAC 1 2 +/D01.7
=E01 +CRP1 -XAC 4 3 =E02 +CRP2 FQAC 1 +/D01.2

B =E03 +CRP3 -XAC 3 4 +/D01.7 B


=E01 +CRP1 -XAC 6 5 +/D01.2
=E03 +CRP3 -XAC 5 6 +/D01.7
=E01 +CRP1 -XAC 8 7 =E02 +CRP2 FQAC 3 +/D01.2
=E03 +CRP3 -XAC 7 8 +/D01.7

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X100 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X101

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+CRP2-XAC PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+CRP2-XDC1 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +CRP1 -XDC1 2 1 =E02 +CRP2 FQDC1 1 +/G01.2
2 =E03 +CRP3 XDC1 1 +/G01.7
=E01 +CRP1 -XDC1 4 3 =E02 +CRP2 FQDC1 3 +/G01.2

B 4 =E03 +CRP3 XDC1 3 +/G01.7 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X101 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X102

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+CRP2-XDC1 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+CRP2-XDC2 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +CRP1 -XDC2 2 1 =E02 +CRP2 FQDC2 1 +/G01.2
2 =E03 +CRP3 XDC2 1 +/G01.7
=E01 +CRP1 -XDC2 4 3 =E02 +CRP2 FQDC2 3 +/G01.2

B 4 =E03 +CRP3 XDC2 3 +/G01.7 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X102 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X103

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+CRP2-XDC2 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+CRP2-XDC3 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +CRP2 -FQ87T 1 1 =E02 +CRP2 KQP1 2 +/G02.1
=E02 +CRP2 -FQBCU 1 2 +/G02.3
=E02 +CRP2 -FQPM 1 3 +/G02.4

B =E02 +CRP2 -FQSI 1 4 +/G02.6 B


=E02 +CRP2 -FQMF 1 5 +/G02.7
=E02 +CRP2 -FQ67 1 6 +/G03.1
=E02 +CRP2 -FQ90 1 7 +/G03.3
=E02 +CRP2 -FQTC2 1 8 +/G03.5
=E02 +CRP2 -FQTC1 1 9 +/G03.6
=E02 +CRP2 -FQCB 1 10 +/G03.8
=E02 +CRP2 -FQ87T 3 11 =E02 +CRP2 KQP1 8 +/G02.2
=E02 +CRP2 -FQBCU 3 12 +/G02.3
=E02 +CRP2 -FQPM 3 13 +/G02.4
C =E02 +CRP2 -FQSI 3 14 +/G02.6 C
=E02 +CRP2 -FQMF 3 15 +/G02.7
=E02 +CRP2 -FQ67 3 16 +/G03.2
=E02 +CRP2 -FQ90 3 17 +/G03.3
=E02 +CRP2 -FQTC2 3 18 +/G03.5
=E02 +CRP2 -FQTC1 3 19 +/G03.6
=E02 +CRP2 -FQCB 3 20 +/G03.8

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X103 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X104

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+CRP2-XDC3 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+CRP2-X3 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +MK -X3 1 1 =E02 +CRP2 BCU-E-DO1 2 +/M01.2
=E02 +MK 9 2 =E02 +CRP2 S.B/M-C1 2 +/M01.4
=E02 +MK 11 3 =E02 +CRP2 SQL02-C3 5 +/M01.5

B =E02 +MK 12 4 =E02 +CRP2 SQL02-C4 7 +/M01.6 B


=T2 +LCB -X2 1 5 =E02 +CRP2 S.L/R-C3 5 +/M04.2
=T2 +LCB X2 2 6 =E02 +CRP2 S.A/M2-C1 2 +/M04.3
=T2 +LCB 4 7 =E02 +CRP2 SCF1-C1 2 +/M04.4
=T2 +LCB 6 8 =E02 +CRP2 SCF2-C1 2 +/M04.6
=E02 +CRP2 BO5 9 9 =C42 +J13 XC 13 +/N05.2
=E05 +CRP5 23 10 =E02 +CRP2 KT1 7 +/N05.4
=C42 +J13 XC 14 11 =E02 +CRP2 XF872-C5 10 +/N05.3
12 =E05 +CRP5 X3 24 +/N05.4
=C42 +J13 XC 11 13 =E02 +CRP2 F87T-H-BO6 11 +/N05.6
C =C42 +J13 XC 12 14 =E02 +CRP2 F87T-H-BO6 12 +/N05.7 C
=E05 +CRP5 X12 8 15 =E02 +CRP2 F87T-H-BO8 15 +/N11.2
=E05 +CRP5 X12 38 16 =E02 +CRP2 XF872-C7 14 +/N11.4
=E00 +FR -X8 5 17 =E02 +CRP2 F87T-H-BO7 14 +/R11.5
=E00 +FR 31 18 =E02 +CRP2 F87T-H-BO7 15 +/R11.5
=E00 +FR 32 19 =E02 +CRP2 F67-H-BO7 15 +/R11.6
=E00 +FR 33 20 =E02 +CRP2 F861-R 6 +/R11.7
=E00 +FR 34 21 =E02 +CRP2 F862-R 6 +/R11.7
=E00 +FR 35 22 =E02 +CRP2 KT1 12 +/R11.8
D 23 +/W01.1 D
24 +/W01.1
25 +/W01.2
26 +/W01.2
27 +/W01.2
28 +/W01.2
29 +/W01.2
30 +/W01.2

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X104 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X105

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+CRP2-X3 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+CRP2-X7 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
1 =E02 +CRP2 FQSI 2 +/G02.6
=E02 +MK -X7 1 2 =E02 +CRP2 S.LT-C1 3 +/Q01.4
3 +/Q01.5

B 4 =E02 +CRP2 FQSI 4 +/G02.6 B


5 =E02 +CRP2 KST2 13 +/Q01.2
6 =E02 +CRP2 PL01 X2 +/Q01.3
7 +/Q01.8
=E02 +MK -X7 5 8 =E02 +CRP2 SQF01-C5 9 +/Q01.4
=E02 +MK 6 9 =E02 +CRP2 SQF01-C6 11 +/Q01.5
=E02 +MK 7 10 =E02 +CRP2 SQL02-C5 9 +/Q01.6
=E02 +MK 8 11 =E02 +CRP2 SQL02-C6 11 +/Q01.6
=E02 +MK 9 12 =E02 +CRP2 SQE25 2 +/Q01.7
=E02 +MK 10 13 =E02 +CRP2 SQE25 1 +/Q01.7
C =T2 +OLTC AI04 11 14 =E02 +CRP2 PTP-AI 3 +/Q02.1 C
=T2 +OLTC 14 15 =E02 +CRP2 F90-AI1 64 +/Q02.2
=T2 +LCB X3 1 16 =E02 +CRP2 PTO-AI 3 +/Q02.3
=T2 +LCB X3 2 17 =E02 +CRP2 PTO-AI 5 +/Q02.4
=T2 +LCB 3 18 =E02 +CRP2 PTW1-AI 3 +/Q02.5
=T2 +LCB 4 19 =E02 +CRP2 PTW1-AI 5 +/Q02.5
=T2 +LCB 7 20 =E02 +CRP2 PTW2-AI 3 +/Q02.7
=T2 +LCB 8 21 =E02 +CRP2 PTW2-AI 5 +/Q02.7
22 +/W01.1
D 23 +/W01.1 D
24 +/W01.2
25 +/W01.2

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X105 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X106

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+CRP2-X7 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+CRP2-X8 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +CRP2 -PS 23 1 =E02 +CRP2 FQBCU 2 +/G02.3 =T2 +LCB X0 4 41 =E02 +CRP2 BCU-J-DI16 22 +/R04.7
=E02 +MK -X8 1 2 +/R01.2 =T2 +LCB X0 6 42 =E02 +CRP2 BCU-K-DI1 1 +/R05.2
=E05 +CRP5 -X3 49 3 +/R04.2 =T2 +LCB 14 43 =E02 +CRP2 BCU-K-DI2 2 +/R05.4

B =C42 +J13 -XY 15 4 +/R04.2 =T2 +LCB 22 44 =E02 +CRP2 BCU-K-DI3 4 +/R05.6 B
5 +/R04.6 =T2 +LCB 25 45 =E02 +CRP2 BCU-K-DI4 5 +/R05.6
6 =E02 +CRP2 F861-R 51 +/R04.7 =T2 +LCB X6 28 46 =E02 +CRP2 BCU-K-DI5 7 +/R05.7
=E02 +CRP2 -PS 24 7 =E02 +CRP2 FQBCU 4 +/G02.3 47 =E02 +CRP2 BCU-K-DI6 8 +/R05.7
=E02 +CRP2 DI1 3 8 +/R01.2 =E02 +CRP2 DI4 5 48 +/R07.4
9 +/R01.3 =E02 +CRP2 DI5 7 49 +/R07.5
=E02 +MK X8 4 10 =E02 +CRP2 BCU-I-DI1 1 +/R01.2 =E02 +CRP2 DI6 8 50 +/R07.6
=E02 +MK 5 11 =E02 +CRP2 BCU-I-DI2 2 +/R01.3 =E02 +CRP2 DI7 10 51 +/R07.6
=E02 +MK 6 12 =E02 +CRP2 BCU-I-DI3 4 +/R01.3 =E02 +CRP2 DI8 11 52 +/R07.7
=E02 +MK 7 13 =E02 +CRP2 BCU-I-DI4 5 +/R01.4 53 +/W01.1
C =E02 +MK 8 14 =E02 +CRP2 BCU-I-DI5 7 +/R01.5 54 +/W01.1 C
=E02 +MK 9 15 =E02 +CRP2 BCU-I-DI6 8 +/R01.5 55 +/W01.2
=E02 +MK 10 16 =E02 +CRP2 BCU-I-DI7 10 +/R01.6 56 +/W01.2
17 =E02 +CRP2 BCU-I-DI8 11 +/R01.7 57 +/W01.2
=E02 +MK -X8 11 18 =E02 +CRP2 BCU-I-DI9 13 +/R02.2 58 +/W01.2
=E02 +MK 12 19 =E02 +CRP2 BCU-I-DI10 14 +/R02.3 59 +/W01.2
=E02 +MK 13 20 =E02 +CRP2 BCU-I-DI11 16 +/R02.3 60 +/W01.2
=E02 +MK 14 21 =E02 +CRP2 BCU-I-DI12 17 +/R02.4
=E02 +MK 15 22 =E02 +CRP2 BCU-I-DI13 19 +/R02.6
D =E02 +MK 16 23 =E02 +CRP2 BCU-I-DI14 20 +/R02.6 D
=E02 +MK 17 24 =E02 +CRP2 BCU-I-DI15 22 +/R02.7
25 =E02 +CRP2 BCU-I-DI16 23 +/R02.7
=E02 +MK -X8 18 26 =E02 +CRP2 BCU-J-DI1 1 +/R03.2
=E02 +MK 19 27 =E02 +CRP2 BCU-J-DI2 2 +/R03.3
=E02 +MK 20 28 =E02 +CRP2 BCU-J-DI3 4 +/R03.4
29 =E02 +CRP2 BCU-J-DI4 5 +/R03.4
30 =E02 +CRP2 BCU-J-DI5 7 +/R03.5
31 =E02 +CRP2 BCU-J-DI6 8 +/R03.6

E 32 =E02 +CRP2 BCU-J-DI7 10 +/R03.6 E


33 =E02 +CRP2 BCU-J-DI8 11 +/R03.7
=E05 +CRP5 50 34 =E02 +CRP2 BCU-J-DI9 13 +/R04.2
=C42 +J13 -XY 90 35 =E02 +CRP2 BCU-J-DI10 14 +/R04.2
=C42 +J13 -XY 16 36 =E02 +CRP2 BCU-J-DI11 16 +/R04.3
37 =E02 +CRP2 BCU-J-DI12 17 +/R04.4
38 =E02 +CRP2 BCU-J-DI13 19 +/R04.4
=C42 +J13 -X3 22 39 =E02 +CRP2 BCU-J-DI14 20 +/R04.5
=T2 +LCB X0 2 40 =E02 +CRP2 BCU-J-DI15 21 +/R04.6

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X106 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X107

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+CRP2-X8 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+CRP2-X9 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +CRP2 9 1 =E03 +CRP3 X9 2 +/R12.2
=E02 +CRP2 9 2 +/R12.3
=E02 +CRP2 9 3 +/R12.4

B =E02 +CRP2 9 4 +/R12.5 B


=E02 +CRP2 2 5 =E01 +CRP1 X9 1 +/R12.6
=E02 +CRP2 10 6 =E03 +CRP3 X9 4 +/R12.3
=E02 +CRP2 10 7 +/R12.4
=E02 +CRP2 10 8 +/R12.5
=E02 +CRP2 10 9 +/R12.6
=E02 +CRP2 3 10 =E01 +CRP1 X9 6 +/R12.7

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X107 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X108

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+CRP2-X9 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+CRP2-X10 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +MK -X10 1 1 =E02 +CRP2 FQTC1 2 +/G03.6
2 =E02 +CRP2 S.B/M-C8 15 +/N01.2
3 =E02 +CRP2 F87T-H-BO1 1 +/N01.4

B 4 +/N01.5 B
=E02 +MK 4 5 =E02 +CRP2 FQTC1 4 +/G03.6
6 =E02 +CRP2 F741-K 2 +/N01.7
7 +/N01.8
=E02 +MK X10 1 8 =E02 +CRP2 BCU-E-DO4 8 +/N01.3
=E02 +MK -X10 2 9 =E02 +CRP2 XF872-C1 2 +/N01.4
=E05 +CRP5 X3 18 10 +/N03.2
=E02 +MK -X10 3 11 =E02 +CRP2 F741-K 4 +/N01.7
=E02 +MK -X10 4 12 =E02 +CRP2 F741-K 8 +/N01.7
=E02 +CRP2 -K 1 13 =E05 +CRP5 X3 17 +/N03.3
C =E02 +CRP2 -K81 7 14 =E02 +CRP2 KT1 5 +/N03.4 C
=E05 +CRP5 19 15 +/N03.3
=E02 +CRP2 -KT1 9 16 =E02 +CRP2 K81 11 +/N03.4
17 +/W01.1
18 +/W01.1
19 +/W01.2
20 +/W01.2

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X108 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X109

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+CRP2-X10 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+CRP2-X11 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +MK X11 1 1 =E02 +CRP2 FQCB 2 +/G03.8
2 =E02 +CRP2 F861-S 10 +/M05.3
=E02 +MK X11 2 3 =E02 +CRP2 FQCB 4 +/G03.8

B =E02 +CRP2 BI1 1 4 +/M05.5 B


5 +/M05.6
=E02 +MK X11 7 6 =E02 +CRP2 F67-D-BI1 2 +/M05.5
=E02 +MK X11 9 7 =E02 +CRP2 S.25-C2 4 +/M05.7
8 +/W01.1
9 +/W01.1
10 +/W01.2
11 +/W01.2
12 +/W01.2
13 +/W01.2
C 14 +/W01.2 C
15 +/W01.2

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X109 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X110

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+CRP2-X11 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+CRP2-X12 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +CRP2 -PS 2 1 =E02 +CRP2 FQ87T 2 +/G02.1
=T2 +LCB X5 9 2 +/N07.2
3 =T2 +LCB X6 6 +/N10.2

B 4 +/N10.3 B
=E02 +CRP2 -PS 1 5 =E02 +CRP2 FQ87T 4 +/G02.2
=E02 +CRP2 -KT1 13 6 =E02 +CRP2 F87T-D-BI1 1 +/N07.2
=T2 +LCB X5 11 7 =E02 +CRP2 F87T-D-BI1 2 +/N07.2
=T2 +LCB 12 8 =E02 +CRP2 F87T-D-BI2 4 +/N07.3
=T2 +LCB 13 9 =E02 +CRP2 F87T-D-BI3 6 +/N07.3
=T2 +LCB 14 10 =E02 +CRP2 F87T-D-BI4 8 +/N07.4
=T2 +LCB 15 11 =E02 +CRP2 F87T-D-BI5 10 +/N07.4
=T2 +LCB 16 12 =E02 +CRP2 F87T-D-BI6 12 +/N07.5
=T2 +LCB 17 13 =E02 +CRP2 F87T-D-BI7 14 +/N07.5
C =T2 +LCB 18 14 =E02 +CRP2 F87T-D-BI8 16 +/N07.6 C
=T2 +LCB -X6 11 15 =E02 +CRP2 F87T-F-BI9 2 +/N10.2
=T2 +LCB 12 16 =E02 +CRP2 F87T-F-BI10 4 +/N10.3
=T2 +LCB 13 17 =E02 +CRP2 F87T-F-BI11 6 +/N10.3
=T2 +LCB 14 18 =E02 +CRP2 F87T-F-BI12 8 +/N10.4
=T2 +LCB 15 19 =E02 +CRP2 F87T-F-BI13 10 +/N10.5
=T2 +LCB 20 20 =E02 +CRP2 F87T-F-BI14 12 +/N10.5
=T2 +LCB 27 21 =E02 +CRP2 F87T-F-BI15 14 +/N10.6
=T2 +LCB 34 22 =E02 +CRP2 F87T-F-BI16 16 +/N10.7
D 23 +/W01.1 D
24 +/W01.1
25 +/W01.2
26 +/W01.2
27 +/W01.2
28 +/W01.2
29 +/W01.2
30 +/W01.2

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X110 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X111

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+CRP2-X12 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+CRP2-X20 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +MK -X20 1 1 =E02 +CRP2 FQTC2 2 +/G03.5
2 =E02 +CRP2 XF872-C2 3 +/N02.3
=E05 +CRP5 20 3 +/N04.2

B =C42 +J13 X ... 4 +/N04.3 B


5 =E02 +CRP2 KT1 6 +/N04.4
6 =E02 +CRP2 K81 8 +/N04.7
=E02 +MK 6 7 =E02 +CRP2 FQTC2 4 +/G03.5
8 =E02 +CRP2 F742-K 2 +/N02.7
9 +/N02.8
=E02 +MK X20 1 10 =E02 +CRP2 F87T-H-BO2 4 +/N02.3
=E05 +CRP5 21 11 +/N04.2
=E02 +MK 2 12 =E02 +CRP2 F742-K 4 +/N02.7
=E02 +MK 3 13 =E02 +CRP2 F742-K 8 +/N02.7
C =E05 +CRP5 22 14 +/N04.2 C
=C42 +J13 X ... 15 +/N04.3
=E02 +CRP2 -KT1 10 16 =E02 +CRP2 F67-H-BO4 8 +/N04.4
17 +/W01.1
18 +/W01.1
19 +/W01.2
20 +/W01.2

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X111 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X112

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+CRP2-X20 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+CRP2-X21 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +CRP2 -PS J2 1 =E02 +CRP2 FQ67 2 +/G03.1
2 =E02 +CRP2 BCU-A-WD 5 +/N06.1
3 =C42 +J13 XY 23 +/N06.4

B 4 +/N06.4 B
=E02 +CRP2 -PS J1 5 =E02 +CRP2 FQ67 4 +/G03.2
6 =E02 +CRP2 F67-D-BI2 3 +/N06.1
7 +/N06.2
=E02 +CRP2 BI6 12 8 =C42 +J13 XY 24 +/N06.4
=E02 +CRP2 BI7 14 9 +/N06.4
=E02 +CRP2 BI8 16 10 +/N06.5
=E02 +CRP2 BI9 2 11 +/N06.5
=E02 +CRP2 BI10 4 12 +/N06.6
=E02 +CRP2 BI11 6 13 +/N06.6
C =E02 +CRP2 BI12 8 14 +/N06.7 C
=E02 +CRP2 BI13 10 15 +/N06.7
=E02 +CRP2 BI14 12 16 +/N06.8
=E02 +CRP2 BI15 14 17 +/N06.8
18 +/W01.1
19 +/W01.1
20 +/W01.2
21 +/W01.2
22 +/W01.2
D 23 +/W01.2 D
24 +/W01.2
25 +/W01.2

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X112 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X113

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+CRP2-X21 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+CRP2-X22 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +CRP2 -PS 21 1 =E02 +CRP2 FQ90 2 +/G03.3
2 =E02 +CRP2 S.M/S/I-C3 5 +/M02.2
3 =E02 +CRP2 F90-R1 45 +/M02.5

B 4 =T2 +OLTC X1 276 +/R09.3 B


5 =E02 +CRP2 S.L/R-C7 13 +/R09.4
=E02 +CRP2 -PS 22 6 =E02 +CRP2 FQ90 4 +/G03.3
7 =E02 +CRP2 F90-E7 20 +/M02.2
8 =E02 +CRP2 KSCR 14 +/M02.5
9 +/M02.7
=T2 +OLTC -X1 12 10 =E02 +CRP2 KSCL 5 +/M03.2
=T2 +OLTC -X1 10 11 =E02 +CRP2 KSCR 10 +/M03.3
=T2 +OLTC -X1 11 12 =E02 +CRP2 KSCL 10 +/M03.4
=T2 +OLTC -X1 14 13 =E02 +CRP2 BCU-D-DO1 1 +/M03.4
C =T2 +OLTC -X1 15 14 =E02 +CRP2 BCU-D-DO1 2 +/M03.5 C
=E02 +CRP2 E1 11 15 =T2 +OLTC X1 300 +/R09.3
=E02 +CRP2 E9 23 16 +/R09.3
=E02 +CRP2 E10 24 17 +/R09.4
=E02 +CRP2 E11 25 18 +/R09.4
=E02 +CRP2 E12 26 19 +/R09.5
=E02 +CRP2 E13 28 20 +/R09.5
=E02 +CRP2 E14 29 21 +/R09.6
=E02 +CRP2 E15 30 22 +/R09.6
D =E02 +CRP2 E16 31 23 +/R09.7 D
24 +/W01.1
25 +/W01.1
26 +/W01.2
27 +/W01.2
28 +/W01.2
29 +/W01.2
30 +/W01.2

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X113 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X114

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+CRP2-X22 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+CRP2-X42 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=T2 +LCB X4 A21 1 =E02 +CRP2 XF67-C1 1 +/S03.1
=T2 +LCB B21 2 =E02 +CRP2 XF67-C2 3 +/S03.2
=T2 +LCB C21 3 =E02 +CRP2 XF67-C3 5 +/S03.2

B =T2 +LCB A24 4 =E02 +CRP2 XF67-C4 7 +/S03.3 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X114 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X115

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+CRP2-X42 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+CRP2-X43 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=T2 +LCB X4 A31 1 =E02 +CRP2 XTC2 1 +/S04.4
=T2 +LCB X4 A34 2 =E02 +CRP2 XTC2 3 +/S04.5

B B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X115 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X116

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+CRP2-X43 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+CRP2-X44 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=T2 +LCB X4 A21 1 =E02 +CRP2 XTC1 1 +/T01.1
=T2 +LCB B21 2 =E02 +CRP2 XTC1 3 +/T01.2
=T2 +LCB C21 3 =E02 +CRP2 XTC1 5 +/T01.2

B =T2 +LCB A24 4 =E02 +CRP2 XTC1 7 +/T01.3 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X116 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X117

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+CRP2-X44 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+CRP2-X45 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +CRP2 IA.1A 16 1 =E00 +FR X47 1 +/T02.2
=E02 +CRP2 IB.1A 12 2 =E00 +FR X47 2 +/T02.2
=E02 +CRP2 IC.1A 8 3 =E00 +FR X47 3 +/T02.2

B =E02 +CRP2 IN.1A 4 4 =E00 +FR X47 4 +/T02.3 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X117 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X118

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+CRP2-X45 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+CRP2-X51 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +CRP2 1 1 =E04 +CRP4 X54 2 +/T01.5
2 =E00 +FR X57 1 +/T01.7
=E02 +CRP2 3 3 =E04 +CRP4 X54 4 +/T01.5

B 4 =E00 +FR X57 3 +/T01.7 B


=E02 +CRP2 5 5 =E04 +CRP4 X54 6 +/T01.6
6 =E00 +FR X57 5 +/T01.8
=E02 +CRP2 7 7 =E04 +CRP4 X54 8 +/T01.6
8 =E00 +FR X57 7 +/T01.8

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X118 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X119

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+CRP2-X51 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+CRP2-X52 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +CRP2 C11 21 1 =E04 +CRP4 X52 2 +/S03.4
2 =E00 +FR X55 1 +/S03.6
=E02 +CRP2 C12 23 3 =E04 +CRP4 X52 4 +/S03.4

B 4 =E00 +FR X55 2 +/S03.6 B


=E02 +CRP2 C13 25 5 =E04 +CRP4 X52 6 +/S03.5
6 =E00 +FR X55 3 +/S03.6
=E02 +CRP2 C14 27 7 =E04 +CRP4 X52 8 +/S03.5
8 =E00 +FR X55 4 +/S03.7

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X119 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X120

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+CRP2-X52 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+CRP2-X53 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +CRP2 1 1 =C42 +J13 XY 25 +/S04.6
=E02 +CRP2 1 2 =C42 +J13 XY 26 +/S04.6
3 =C42 +J13 XY 27 +/S04.7

B =E02 +CRP2 3 4 =C42 +J13 XY 28 +/S04.7 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X120 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X121

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+CRP2-X53 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+CRP2-X54 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +CRP2 C9 17 1 =C42 +J13 XY 20 +/S03.7
=E02 +CRP2 C10 19 2 =C42 +J13 XY 22 +/S03.8

B B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X121 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X122

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+CRP2-X54 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+CRP2-X91 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +CRP2 C2 4 1 +/N13.2
=E02 +CRP2 C3 6 1 +/N13.2
=E02 +CRP2 C4 8 1 +/N13.2

B =E02 +CRP2 C5 10 1 +/N13.2 B


=E02 +CRP2 -K81 13 1 +/N13.2
=E04 +CRP4 -X91 1 2 +/N13.7
=E04 +CRP4 -X91 3 2 +/N13.7
=E04 +CRP4 -X91 5 2 +/N13.7
=E04 +CRP4 -X91 7 2 +/N13.7
=E04 +CRP4 -X91 9 2 +/N13.7

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X122 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X123

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+CRP2-X91 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+CRP2-X410 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +MK -X41 1 1 =E02 +CRP2 XF871-C1 1 +/S01.1
=E02 +MK 2 2 =E02 +CRP2 XF871-C2 3 +/S01.2
=E02 +MK 3 3 =E02 +CRP2 XF871-C3 5 +/S01.2

B =E02 +MK 4 4 =E02 +CRP2 XF871-C4 7 +/S01.2 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X123 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X124

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+CRP2-X410 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+CRP2-X411 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=T2 +LCB X4 O21 1 =E02 +CRP2 XF871-C5 9 +/S01.4
=T2 +LCB O24 2 =E02 +CRP2 XF871-C6 11 +/S01.4

B B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X124 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X125

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+CRP2-X411 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+CRP2-X412 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=T2 +LCB X4 1O21 1 =E02 +CRP2 XF871-C7 13 +/S01.4
=T2 +LCB 1O23 2 =E02 +CRP2 XF871-C8 15 +/S01.5

B B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X125 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X126

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+CRP2-X412 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+CRP2-X413 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=C42 +J13 XIC 5 1 =E02 +CRP2 XF871-C9 17 +/S01.6
=C42 +J13 XIC 6 2 =E02 +CRP2 XF871-C10 19 +/S01.7
=C42 +J13 XIC 7 3 =E02 +CRP2 XF871-C11 21 +/S01.7

B =C42 +J13 XIC 8 4 =E02 +CRP2 XF871-C12 23 +/S01.7 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X126 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE +MK/X100

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+CRP2-X413 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+MK-XAC A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E04 +MK -XAC 2 1 =E02 +MK FQAC1 1 +/D02.2
2 +/D02.8
3 =E04 +MK XAC 4 +/D02.2

B 4 =E02 +MK FQAC2 1 +/D02.8 B


5 =E04 +MK XAC 6 +/D02.2
6 +/D02.8
=E02 +MK -FQAC1 3 7 =E04 +MK XAC 9 +/D02.2
8 =E02 +MK FQAC2 3 +/D02.8

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X100 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X101

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+MK-XAC PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+MK-XAC1 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +QF01 TB1 1 1 =E02 +MK FQAC2 2 +/D03.3
=E02 +QL02 -X1 20 2 =E02 +QE25 XT2 20 +/D03.4
=E02 +QF01 2 3 =E02 +MK FQAC2 4 +/D03.3

B =E02 +QL02 21 4 =E02 +QE25 XT2 21 +/D03.5 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X101 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X102

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+MK-XAC1 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+MK-XDC A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=N00 +DC -XT1 11 1 =E02 +MK FQCB 1 +/G04.2
=E01 +MK -XDC 1 2 =E02 +MK FQDS 1 +/G04.7
=N00 +DC -XT1 12 3 =E02 +MK FQCB 3 +/G04.2

B =E01 +MK -XDC 3 4 =E02 +MK FQDS 3 +/G04.7 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X102 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X103

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+MK-XDC PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+MK-XDC1 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +QF01 X1 450 1 =E02 +MK FQCB 2 +/G04.3
=E02 +QF01 -X1 460 2 =E02 +MK FQCB 4 +/G04.3

B B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X103 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X104

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+MK-XDC1 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+MK-XDC2 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +QL02 -X1 1 1 =E02 +MK FQDS 2 +/G04.4
=E02 +MK -X3 16 2 +/G04.5
=E02 +QL02 2 3 =E02 +MK FQDS 4 +/G04.4

B =E02 +MK -X3 24 4 +/G04.5 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X104 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X105

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+MK-XDC2 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+MK-X3 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +QL02 -X1 4A 1 =E02 +CRP2 X3 1 +/M01.2
=E02 +QF01 -TB2 27 2 +/P01.6
=E05 +MK -X3 51 3 =E02 +QL02 X2 35 +/P02.6

B =E05 +MK -X3 52 4 =E02 +QL02 X2 36 +/P02.6 B


=C42 +J13 -X... ... 5 =E02 +QL02 X2 27 +/P02.6
=C42 +J13 -X... ... 6 =E02 +QL02 X2 28 +/P02.6
=C42 +J13 -X... ... 7 =E02 +QE25 XT2 27 +/P02.6
=C42 +J13 -X... ... 8 =E02 +QE25 XT2 28 +/P02.6
=E02 +QL02 -X1 4B 9 =E02 +CRP2 X3 2 +/M01.4
10 =E05 +MK X3 33 +/P01.7
=E02 +QL02 -X1 8 11 =E02 +CRP2 X3 3 +/M01.5
=E02 +QL02 -X1 7 12 =E02 +CRP2 X3 4 +/M01.6
=E02 +QF01 TB2 1 13 =E05 +CRP5 X12 3 +/N12.3
C =E02 +QL02 -X2 13 14 +/N12.5 C
15 +/N12.5
=E02 +QL02 -X2 31 16 =E02 +MK XDC2 2 +/P02.2
=E02 +QF01 TB2 9 17 =E00 +FR X8 4 +/R11.2
18 +/R11.3
=C42 +J13 -X... ... 19 =E02 +QL02 X2 32 +/P02.2
=E02 +QE25 -XT2 1 20 =C42 +J13 X... ... +/P02.2
=E05 +CRP5 19 21 =E02 +QF01 TB2 2 +/N12.3
=E00 +FR 30 22 =E02 +QF01 TB2 10 +/R11.2
D =E05 +CRP5 20 23 =E02 +QF01 TB2 26 +/N12.4 D
=E02 +QE25 2 24 =E02 +MK XDC2 4 +/P02.3
=E00 +FR X8 29 25 =E02 +QF01 TB2 34 +/R11.3
=E05 +CRP5 21 26 =E02 +QL02 X2 14 +/N12.5
=E05 +CRP5 22 27 =E02 +QL02 X2 16 +/N12.5
=E02 +QE25 -XT2 3 28 =E02 +QF01 TB2 28 +/P01.6
=C42 +J13 X... ... 29 =E02 +QE25 XT2 4 +/P01.6
=E05 +MK -X3 32 30 =C42 +J13 X... ... +/P01.7
31 +/W01.6

E 32 +/W01.6 E
33 +/W01.6
34 +/W01.6
35 +/W01.6
36 +/W01.6
37 +/W01.7
38 +/W01.7
39 +/W01.7
40 +/W01.7

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X105 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X106

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+MK-X3 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+MK-X7 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +QF01 TB2 31 1 =E02 +CRP2 X7 2 +/Q01.4
=E02 +QL02 -X2 19 2 +/Q01.6
=E02 +QE25 -XT2 19 3 +/Q01.7

B 4 +/Q01.7 B
=E02 +QF01 TB2 32 5 =E02 +CRP2 X7 8 +/Q01.4
=E02 +QF01 TB2 6 6 =E02 +CRP2 X7 9 +/Q01.5
=E02 +QL02 -X2 20 7 =E02 +CRP2 X7 10 +/Q01.6
=E02 +QL02 18 8 =E02 +CRP2 X7 11 +/Q01.6
=E02 +QE25 -XT2 20 9 =E02 +CRP2 X7 12 +/Q01.7
=E02 +QE25 18 10 =E02 +CRP2 X7 13 +/Q01.7
11 +/W01.6
12 +/W01.6
13 +/W01.6
C 14 +/W01.6 C
15 +/W01.6

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X106 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X107

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+MK-X7 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+MK-X8 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +QF01 TB2 29 1 =E02 +CRP2 X8 2 +/R01.2
=E02 +QL02 X2 23 2 +/R02.2
=E02 +QE25 XT2 7 3 =E02 +MK FQAC1 12 +/R02.6

B =E02 +QF01 TB2 20 4 =E02 +CRP2 X8 10 +/R01.2 B


=E02 +QF01 4 5 =E02 +CRP2 X8 11 +/R01.3
=E02 +QF01 TB1 41 6 =E02 +CRP2 X8 12 +/R01.3
=E02 +QF01 -TB1 43 7 =E02 +CRP2 X8 13 +/R01.4
=E02 +QF01 52 8 =E02 +CRP2 X8 14 +/R01.5
=E02 +QF01 47 9 =E02 +CRP2 X8 15 +/R01.5
=E02 +QF01 31 10 =E02 +CRP2 X8 16 +/R01.6
=E02 +QL02 X2 24 11 =E02 +CRP2 X8 18 +/R02.2
=E02 +QL02 -X2 22 12 =E02 +CRP2 X8 19 +/R02.3
=E02 +QL02 -X2 80 13 =E02 +CRP2 X8 20 +/R02.3
C =E02 +QL02 -X2 84 14 =E02 +CRP2 X8 21 +/R02.4 C
=E02 +QE25 XT2 8 15 =E02 +CRP2 X8 22 +/R02.6
=E02 +QE25 -XT2 2 16 =E02 +CRP2 X8 23 +/R02.6
=E02 +QE25 -XT2 88 17 =E02 +CRP2 X8 24 +/R02.7
=E02 +MK -FQAC1 11 18 =E02 +CRP2 X8 26 +/R03.2
=E02 +MK -FQCB 11 19 =E02 +CRP2 X8 27 +/R03.3
=E02 +MK -FQAC1 95 20 =E02 +CRP2 X8 28 +/R03.4
21 +/W01.6
22 +/W01.6
D 23 +/W01.6 D
24 +/W01.6
25 +/W01.6
26 +/W01.6
27 +/W01.7
28 +/W01.7
29 +/W01.7
30 +/W01.7

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X107 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X108

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+MK-X8 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+MK-X10 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +QF01 TB1 16 1 =E02 +CRP2 X10 8 +/N01.3
=E02 +QF01 TB1 11 2 =E02 +CRP2 X10 9 +/N01.4
=E02 +QF01 TB1 12 3 =E02 +CRP2 X10 11 +/N01.7

B =E02 +QF01 TB1 13 4 =E02 +CRP2 X10 12 +/N01.7 B


=E02 +QF01 -TB1 7 1 =E02 +CRP2 X10 1 +/G03.6
=E02 +QF01 -TB1 8 4 =E02 +CRP2 X10 5 +/G03.6
7 +/W01.6
8 +/W01.6
9 +/W01.6
10 +/W01.6
11 +/W01.6
12 +/W01.6
13 +/W01.7
C 14 +/W01.7 C
15 +/W01.7

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X108 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X109

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+MK-X10 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+MK-X11 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +QF01 -TB1 5 1 =E02 +CRP2 X11 1 +/G03.8
=E02 +QF01 -TB1 6 2 =E02 +CRP2 X11 3 +/G03.8
=E02 +QF01 -TB1 14 3 +/M05.2

B =E02 +QL02 -X2 3 4 +/P01.2 B


=E02 +QF01 -TB1 15 5 +/M05.3
6 =C42 +J13 X... ... +/P01.2
=E02 +QF01 TB1 18 7 =E02 +CRP2 X11 6 +/M05.5
8 =C42 +J13 X... ... +/P01.4
=E02 +QL02 -X2 1 9 =E02 +CRP2 X11 7 +/M05.7
=C42 +J13 -X... ... 10 =E02 +QL02 X2 4 +/P01.2
=C42 +J13 -X... ... 11 =E02 +QL02 X2 2 +/P01.4
12 +/W01.6
13 +/W01.6
C 14 +/W01.6 C
15 +/W01.6
16 +/W01.6
17 +/W01.6
18 +/W01.7
19 +/W01.7
20 +/W01.7

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X109 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X110

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+MK-X11 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+MK-X20 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +QF01 -TB1 9 1 =E02 +CRP2 X20 1 +/G03.5
=E02 +QF01 TB1 23 1 =E02 +CRP2 X20 10 +/N02.3
=E02 +QF01 TB1 24 2 =E02 +CRP2 X20 12 +/N02.7

B =E02 +QF01 TB1 25 3 =E02 +CRP2 X20 13 +/N02.7 B


=E02 +QF01 -TB1 10 6 =E02 +CRP2 X20 7 +/G03.5
6 +/W01.6
7 +/W01.6
8 +/W01.6
9 +/W01.6
10 +/W01.6
11 +/W01.6
12 +/W01.7
13 +/W01.7
C 14 +/W01.7 C
15 +/W01.7

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X110 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X111

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+MK-X20 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+MK-X41 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +CT-PA +CT-PA-PA 1S1 1 =E02 +CRP2 X410 1 +/S01.1
=E02 +CT-PB +CT-PB-PB 1S1 2 =E02 +CRP2 X410 2 +/S01.2
=E02 +CT-PC +CT-PC-PC 1S1 3 =E02 +CRP2 X410 3 +/S01.2

B =E02 +CT-PC 1S4 4 =E02 +CRP2 X410 4 +/S01.2 B


5 =E02 +CT-PB PB 1S4 +/S01.2
=E02 +MK PE 6 =E02 +CT-PA PA 1S4 +/S01.3

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X111 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X112

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+MK-X41 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+MK-X42 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +CT-PA +CT-PA-PA 2S1 1 =E00 +FR X42 1 +/S02.2
=E02 +CT-PB +CT-PB-PB 2S1 2 =E00 +FR X42 2 +/S02.2
=E02 +CT-PC +CT-PC-PC 2S1 3 =E00 +FR X42 3 +/S02.3

B =E02 +CT-PC 2S4 4 =E00 +FR X42 4 +/S02.3 B


=E02 +CT-PB +CT-PB-PB 2S4 5 +/S02.3
=E02 +CT-PA +CT-PA-PA 2S4 6 =E02 +MK PE +/S02.3

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X112 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X113

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+MK-X42 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E02+MK-X45 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +CT-PA 5S1 1 =E05 +CRP5 X452 1 +/S02.6
=E02 +CT-PB +CT-PB-PB 5S1 2 =E05 +CRP5 X452 2 +/S02.6
=E02 +CT-PC +CT-PC-PC 5S1 3 =E05 +CRP5 X452 3 +/S02.6

B =E02 +CT-PC 5S4 4 =E05 +CRP5 X452 4 +/S02.6 B


=E02 +CT-PB +CT-PB-PB 5S4 5 +/S02.7
=E02 +CT-PA +CT-PA-PA 5S4 6 =E02 +MK PE +/S02.7

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E02


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X113 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE =E03+/A00

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRANSFORMER BAY T2 - 132 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E02+MK-X45 PECC2/TT-110KV/E02-132
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

B B

B 24/11/2020 2nd FOR APPROVED

A 12/10/2020 1st FOR APPROVED

REV. DATE DESCRIPTION

CUSTOMER

C C
POWER ENGINEERING CONSULTING J.S.C. 2

PROJECT

TAN THUAN OFFSHORE WIND POWER PLANT

D D

LOCATION

TAN THUAN OFFSHORE WIND POWER PLANT

DRAW. NAME STAMP

E =E03+CRP3: WIRING DIAGRAMS FOR 110KV TRANSMISSION LINE E03 BAY E


=E03+MK: MARSHALLING KIOSK FOR TRANSMISSION LINE E03 BAY
=E03+VTB: VT-BOX FOR TRANSMISSION LINE E03 BAY

DRAWING NO. PECC2/TT-110KV/E03-171

STANDARD: IEC PAGE: A00 TOTAL NO. OF PAGE: 84

DESIGNED NGUYEN VAN NHAT CONTRACTOR

CHECKED NGUYEN VAN CHUNG


F F
APPROVED NGUYEN DINH TUAN
ENERGY TECHNOLOGY
JOINT STOCK COMPANNY
DATE 24/11/2020 Rev.: B

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

PAGE DESCRIPTION REV. X PAGE DESCRIPTION REV. X

=E03/A00 WIRING DIAGRAMS FOR 110KV TRANSMISSION LINE BAY B =E03/N04 TRIP-LOCKOUT2 CIRCUIT B
A A
=E03/A01 TABLE OF CONTENTS : =E03/A00 - =E03/Z02 B =E03/N05 LOAD SHEDDING CIRCUIT B
=E03/A01.a TABLE OF CONTENTS : =E03/Z03 - =E03+VTB/X105 B =E03/N06 BINNARY INPUT F87L B
=E03/A02 DEVICE SYMBOL B =E03/N07 BINNARY INPUT F87L B
=E03/A03 FUNCTION SYMBOL B =E03/N08 BINNARY INPUT F21 B
=E03/A04 SECONDARY CIRCUIT SYMBOL B =E03/N09 BINNARY INPUT F85 B
=E03/A05 LIST OF EQUIPMENTS: =E03+CRP3 C =E03/N10 BINNARY INPUT OF F87B B

B =E03/A06 LIST OF EQUIPMENTS: =E03+CRP3 C =E03/N11 SIGNAL SEND TO F87B B B


=E03/A07 LIST OF EQUIPMENTS: =E03+MK C =E03/P01 INTERLOCKING FOR CB, DS, ES B
=E03/B01 CONTROL, PROTECTION & MEASUREMENT PRINCIPLE DIAGRAM B =E03/P02 INTERLOCKING FOR CB, DS, ES B
=E03/B02 TRIPPING MATRIX B =E03/P03 INTERLOCKING FOR CB, DS, ES B
=E03/B03 LAYOUT DRAWING B =E03/P04 INTERLOCKING FOR CB, DS, ES B
=E03/B04 LAYOUT DRAWING MARSHALLING KIOSK =E03+MK B =E03/Q01 INDICATOR CIRCUIT B
=E03/B05 OPERATION LOGIC DIAGRAM FOR DS E03-QL01 B =E03/Q02 INDICATOR CIRCUIT B
C =E03/B06 OPERATION LOGIC DIAGRAM FOR DS E03-QL07 B =E03/R01 BINNARY INPUT BCU B C

=E03/B08 OPERATION LOGIC DIAGRAM FOR ES E03-QE75 B =E03/R02 BINNARY INPUT BCU B
=E03/B09 OPERATION LOGIC DIAGRAM FOR ES E03-QE15 B =E03/R03 BINNARY INPUT BCU B
=E03/B10 OPERATION LOGIC DIAGRAM FOR ES E03-QE76 B =E03/R04 BINNARY INPUT BCU B
=E03/B11 CLOSING LOGIC DIAGRAM FOR CB E03-QF01 B =E03/R05 BINNARY INPUT BCU B
=E03/B12 OPENING LOGIC DIAGRAM FOR CB E03-QF01 B =E03/R06 BINNARY INPUT BCU B
=E03/D01 AC POWER SUPPLY FOR CONTROL PANEL B =E03/R07 BINNARY INPUT BCU B
D D
=E03/D02 AC POWER SUPPLY FOR MARSHALLING KIOSK B =E03/R08 SIGNAL SEND TO FR B
=E03/D03 AC POWER SUPPLY FOR CB, DS, ES B =E03/R09 MODBUS RS485 CIRCUIT B
=E03/G01 DC POWER SUPPLY FOR CONTROL PANEL B =E03/S01 LINE VOLTAGE CIRCUIT B
=E03/G02 DC POWER SUPPLY FOR CONTROL PANEL B =E03/S02 LINE VOLTAGE CIRCUIT B
=E03/G03 DC POWER SUPPLY FOR CONTROL PANEL B =E03/S03 CURRENT CIRCUIT OF RELAY B
=E03/G04 DC POWER SUPPLY FOR HV EQUIPMENT B =E03/S04 VOLTAGE CIRCUIT OF RELAY B

E =E03/M01 CONTROL CIRCUIT DS E03-QL01 B =E03/T01 VOLTAGE CIRCUIT OF MEASUREMENT B E


=E03/M02 CONTROL CIRCUIT DS E03-QL07 B =E03/T02 VOLTAGE CIRCUIT OF MEASUREMENT B
=E03/M04 CLOSING CIRCUIT CB E03-QF01 B =E03/T03 VOLTAGE CIRCUIT OF MEASUREMENT B
=E03/N01 TRIPPING CIRCUIT 1 CB E03-QF01 B =E03/W01 SPARE CIRCUIT B
=E03/N02 TRIPPING CIRCUIT 2 CB E03-QF01 B =E03/Z01 REFERENCE F87L (P543) B
=E03/N03 TRIP-LOCKOUT1 CIRCUIT B =E03/Z02 REFERENCE F87L (P543) B
X: AUTOMATIC PAGE MODIFIED

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A01.a

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN TABLE OF CONTENTS : =E03/A00 - =E03/Z02 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

PAGE DESCRIPTION REV. X PAGE DESCRIPTION REV. X

=E03/Z03 REFERENCE F21 (P445) B =E03+CRP3/X115 Terminal diagram =E03+CRP3-X51 B


A A
=E03/Z04 REFERENCE F21 (P445) B =E03+CRP3/X116 Terminal diagram =E03+CRP3-X52 B
=E03/Z05 REFERENCE BCU C264 B =E03+CRP3/X117 Terminal diagram =E03+CRP3-X53 B
=E03/Z06 REFERENCE BCU C264 B =E03+CRP3/X118 Terminal diagram =E03+CRP3-X54 B
=E03/Z07 REFERENCE BCU C264 B =E03+CRP3/X119 Terminal diagram =E03+CRP3-X91 B
=E03/Z09 REFERENCE CONTROL DEVICES B =E03+CRP3/X120 Terminal diagram =E03+CRP3-X411 B
=E03/Z10 REFERENCE CURRENT AND VOLTAGE TESTBLOCK B =E03+MK/X100 Terminal diagram =E03+MK-XAC B

B =E03/Z11 REFERENCE RELAY F74 B =E03+MK/X101 Terminal diagram =E03+MK-XAC1 B B


=E03/Z12 REFERENCE RELAY TESTBLOCK B =E03+MK/X102 Terminal diagram =E03+MK-XDC B
=E03/Z13 CB REFERENCE (GL312F1/GE) B =E03+MK/X103 Terminal diagram =E03+MK-XDC1 B
=E03/Z14 CB REFERENCE (GL312F1/GE) B =E03+MK/X104 Terminal diagram =E03+MK-XDC2 B
=E03/Z15 CB REFERENCE (GL312F1/GE) B =E03+MK/X105 Terminal diagram =E03+MK-X3 B
=E03/Z16 CB REFERENCE (GL312F1/GE) B =E03+MK/X106 Terminal diagram =E03+MK-X7 B
=E03/Z17 DS REFERENCE B =E03+MK/X107 Terminal diagram =E03+MK-X8 B
C =E03/Z18 DS REFERENCE B =E03+MK/X108 Terminal diagram =E03+MK-X10 B C

=E03/Z19 DS REFERENCE B =E03+MK/X109 Terminal diagram =E03+MK-X11 B


=E03/Z20 ES REFERENCE B =E03+MK/X110 Terminal diagram =E03+MK-X12 B
=E03/Z21 ES REFERENCE B =E03+MK/X111 Terminal diagram =E03+MK-X20 B
=E03+CRP3/X100 Terminal diagram =E03+CRP3-XAC B =E03+MK/X112 Terminal diagram =E03+MK-X41 B
=E03+CRP3/X101 Terminal diagram =E03+CRP3-XDC1 B =E03+MK/X113 Terminal diagram =E03+MK-X42 B
=E03+CRP3/X102 Terminal diagram =E03+CRP3-XDC2 B =E03+MK/X114 Terminal diagram =E03+MK-X44 B
D D
=E03+CRP3/X103 Terminal diagram =E03+CRP3-XDC3 B =E03+MK/X115 Terminal diagram =E03+MK-X45 B
=E03+CRP3/X104 Terminal diagram =E03+CRP3-X3 B =E03+VTB/X100 Terminal diagram =E03+VTB-XAC B
=E03+CRP3/X105 Terminal diagram =E03+CRP3-X7 B =E03+VTB/X101 Terminal diagram =E03+VTB-X8 B
=E03+CRP3/X106 Terminal diagram =E03+CRP3-X8 B =E03+VTB/X102 Terminal diagram =E03+VTB-X12 B
=E03+CRP3/X107 Terminal diagram =E03+CRP3-X9 B =E03+VTB/X103 Terminal diagram =E03+VTB-X51 B
=E03+CRP3/X108 Terminal diagram =E03+CRP3-X10 B =E03+VTB/X104 Terminal diagram =E03+VTB-X52 B

E =E03+CRP3/X109 Terminal diagram =E03+CRP3-X11 B =E03+VTB/X105 Terminal diagram =E03+VTB-X53 B E


=E03+CRP3/X110 Terminal diagram =E03+CRP3-X12 B
=E03+CRP3/X111 Terminal diagram =E03+CRP3-X20 B
=E03+CRP3/X112 Terminal diagram =E03+CRP3-X21 B
=E03+CRP3/X113 Terminal diagram =E03+CRP3-X41 B
=E03+CRP3/X114 Terminal diagram =E03+CRP3-X44 B
X: AUTOMATIC PAGE MODIFIED

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A01.a F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN TABLE OF CONTENTS : =E03/Z03 - =E03+VTB/X105 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION


A A
M
THREE WINDING TRANSFORMER 3 UNIT POTENTIAL TRANSFORMER A AMMETER MCCB CÓ ĐỘNG CƠ ĐIỀU KHIỂN

TWO WINDING TRANSFORMER 2 UNIT POTENTIAL TRANSFORMER V VOLTMETER MCCB, MCB

AUTO TRANSFORMER SURGE ARRESTOR W WATTMETER RESISTOR


B B

CURRENT TRANSFORMER WYE VAR VAR METER FUSE

REACTOR DELTA ‎cosφ POWER FACTOR METER BATTERY

CAPACITOR OPEN DELTA Hz FREQUENCY METER INVERTER


C C

REACTOR EARTHING Wh WATTHOUR METER DIODE

HIGH VOLTAGE CIRCUIT BREAKER INTERLOCKING VARh VAr METER

MEDIUM CIRCUIT BREAKER LATCHING DEVICE AMPE SWITCH


D D

DAO CẮM HỢP BỘ TRUNG ÁP M CONTROL MOTOR VOLT SWITCH

DISCONECTOR CONTROL KEY RELAY TEST BLOCK

E
EARTH SWITCH ~ ALTERNATIVE CURRENT VOLTAGE/CURRENT TEST BLOCK
E

LOAD DISCONECTOR DIRECT CURENT LAMP

CONTACTOR

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN DEVICE SYMBOL PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

KÝ HIỆU MÔ TẢ KÝ HIỆU MÔ TẢ

21/21N DISTANCE PROTECTION 86 TRIP-LOCKOUT RELAY


A A
25 SYNCHROCHECK 87B BUSBAR DIFFERENTIAL PROTECTION

26 THERMAL PROTECTION 87L LINE DIFFERENTIAL PROTECTION

27 UNDERVOLTAGE PROTECTION 87N RESTRICTED GROUND FAULT PROTECTION

33 POSITION BLOCK RELAY 87S STUB DIFFERENTIAL PROTECTION

49 THERMAL OVERLOAD PROTECTION 87T TRANSFORMER DIFFERENTIAL PROTECTION

50 INSTANTANEOUS OVERCURRENT PROTECTION 90 AUTOMATIC CONTROL VOLTAGE RELAY


B B
50BF CIRCUIT-BREAKER FAILURE PROTECTION 94 TRIPPING RELAY

50G INSTANTANEOUS GROUND OVERCURRENT PROTECTION 96 GAS RELAY

50N INSTANTANEOUS NEUTRAL OVERCURRENT PROTECTION FR FAULT RECORDER

51 TIME OVERCURRENT PROTECTION FL FAULT LOCATOR

51G TIME GROUND OVERCURRENT PROTECTION SOTF SWITCH ON TO FAULT

51N TIME NEUTRAL OVERCURRENT PROTECTION BCU BAY CONTROL UNIT


C C
5IUb UNBALANCE OVERCURRENT PROTECTION A CURRENT MEASUREMENT FUNCTION

51/27 VOLTAGE CONTROLLED OVERCURRENT V VOLTAGE MEASUREMENT FUNCTION

59 OVERVOLTAGE PROTECTION f FREQUENCY MEASUREMENT FUNCTION

59N ZEZO-SEQUENCE OVERVOLTAGE PROTECTION ‎cosφ POWER FACTOR MEASUREMENT FUNCTION

63 PRESSURE RELAY W EFFECTIVE POWER MEASUREMENT FUNCTION

D 64 GROUND DETECTOR RELAY VAR REACTIVE POWER MEASUREMENT FUNCTION D

67 DIRECTIONAL OVERCURRENT RELAY Wh ACTIVE ENERGY MEASUREMENT FUNCTION

67N DIRECTIONAL OVERCURRENT PROTECTION FOR GROUND FAULTS VARh REACTIVE ENERGY MEASUREMENT FUNCTION

67NS DIRECTIONAL SENSITIVE GROUND-FAULT DETECTION

68 POWER-SWING BLOCKING

71 LEVEL OIL RELAY


E E
74 TRIP CIRCUIT SUPERVISION

79 AUTO RECLOSING

81 FREQUENCY PROTECTION

85 COMBINATION OF PROTECTION

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN FUNCTION SYMBOL PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

KÝ HIỆU MÔ TẢ KÝ HIỆU MÔ TẢ KÝ HIỆU MÔ TẢ KÝ HIỆU MÔ TẢ


A A

NORMALY OPEN CONTACT (NO) RELAY TEST BLOCK CONTACT LAMP EARTHING BAR

NORMALY CLOSE CONTACT (NC) CURRENT/VOLTAGE TEST BLOCK CONTACT LIGHTS BELL

CHANGE OVER CONTACT (CO) SOLENOID / COIL SOCKET HOOTER


B B

CONTACTOR NORMALY OPEN CONTACT ON DELAY COIL SURGE ARRESTOR MEARSUREMENT DEVICE

CONTACTOR NORMALY CLOSE CONTACT LATCHED COIL FUSE V VOLMETTER

NORMALLY OPEN ON BUTTON BINARY INPUT RELAY HEATER A AMMETTER


C C

NORMALLY CLOSED OFF BUTTON ANALOG INPUT RELAY RESISTOR

PUSH BUTTON (DETENT) POWER SUPPLY DIODE

SELECTOR SWITCH CONTACT CONVERTER CAPACITOR


D D

~
LIMIT SWITCH CONTACT RECTIFIER REACTOR/CURRENT-VOLTAGE INPUT RELAY

TEMPERATURE CONTROLER CONTACT INVERTER TERMINAL


~

MAKE CONTACT DELAYED WHEN


COUNTER DRAWOUT TERMINAL
E CLOSING E

MAKE CONTACT DELAYED WHEN


MCCB/MCB DIODE TERMINAL
OPENING I>

FUSE TERMINAL

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A05

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN SECONDARY CIRCUIT SYMBOL PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

NO. SYMBOL DESCRIPTION MANUFACTORY CODE QTY. UNIT NOTE CUBICLE

1 F87L LINE DIFFERENTIAL PROTECTION RELAY SCHNEIDER P54331Q77M0K28M 01 Pcs 16BI + 24BO + 2LC IEC61850 =E03+CRP3
A A
2 F67 DISTANCE PROTECTION RELAY SCHNEIDER P44531QE7M0K28L 01 Pcs 8BI + 8BO + 2LC IEC61850 =E03+CRP3

3 BCU BAY CONTROL UNIT SCHNEIDER C264U11M6A10013302100031111D10 01 Pcs 58BI + 26BO + 2ST IEC61850 =E03+CRP3

REG-DA B0 I0 H0 F1 M1 S0 T0 K1
4 F90 AUTO VOLTAGE REGULATOR RELAY A-EBERLE 01 Pcs 16BI+12BO+1AI+1xRS232+ 1xLC IEC61850 =E03+CRP3
E00 D0 C00 XW93.1 G2 A2

5 PMF MULTIFUNCTION METTER CEWE ELITE 448 01 Pcs =E03+CRP3

6 XF... RELAY TESTBLOCK FUJI TSB-14-11111111111111-V 03 Pcs =E03+CRP3

7 F86... TRIP AND LOCKOUT RELAY ARTECHE BJ-8RP 02 Pcs 8CO =E03+CRP3
B B
8 F74... TRIPPING SUPERVISORY RELAY ARTECHE VDF-10 02 Pcs 2CO =E03+CRP3

9 XTC... CURRENT TESTBLOCK FUJI KTT-AW4 B M 03 Pcs =E03+CRP3

10 XTV... VOLTAGE TESTBLOCK FUJI KTT-VW4 B M 04 Pcs =E03+CRP3

11 SQF01 CONTROL AND DISCREPANCY SWITCH FOR CB FUJI BHL-3B3111-220L1-W-Y-B-L54-Y07E 01 Pcs =E03+CRP3

12 SQL01 CONTROL AND DISCREPANCY SWITCH FOR DS FUJI BHL-3B3111-220L1-W-Y-B-L54-Z07E 01


02 Pcs =E03+CRP3

13 SQE... SEMAPHORE FOR ES FUJI SPSR-30S-DC220-BB 03 Pcs =E03+CRP3


C C
14 S.B/M "BCU/MIMIC" SELECTOR SWITCH SALZER SA25-FA 6015-61009-M1-I-F-3-BS-0 01 Pcs =E03+CRP3

15 S.25 "SYN./BYPASS" SELECTOR SWITCH SALZER SA25-FA 6037-61638-M1-I-F-3-BS-0 01 Pcs =E03+CRP3

16 S.79 "ON/OFF" SELECTOR SWITCH FOR 79 SALZER SA25-FA 6037-61638-M1-I-F-3-BS-0 01 Pcs =E03+CRP3

17 S.87L "ON/OFF" SELECTOR SWITCH FOR 87L SALZER SA25-FA 6037-61638-M1-I-F-3-BS-0 01 Pcs =E03+CRP3

18 S.81 LOAD SHEDDING SLECTOR SWITCH SALZER SA25-FA 6029-61071-M1-I-F-3-BS-0 02 Pcs =E03+CRP3

D 19 P.LOCAL LAMP FOR CB CONTROL AT LOCAL IDEC YW1P 01 Pcs =E03+CRP3 D

20 S.R/L RESET LOCKOUT BUTTON IDEC YW1B 01 Pcs =E03+CRP3

21 K.... AUXILARY RELAY IDEC RU4S 01 Lot =E03+CRP3

22 FQAC MCB AC FOR LIGHTING AND HEATING LEGRAND DX3 01 Pcs 2P-16A-6kA =E03+CRP3

23 FQ... MCB DC LEGRAND DX3 DC 01 Lot 2P-10A-16kA =E03+CRP3

24 KQP CONTACTOR ABB ESB25 01 Pcs =E03+CRP3

E 25 XAC, XDC POWER TERMINALS DEGSON PC6 01 Lot =E03+CRP3


E

26 X4... CURRENT TERMINALS DEGSON PCTK 01 Lot =E03+CRP3

27 X... SIGNAL TERMINALS DEGSON PC4 01 Lot =E03+CRP3

28 B0 THERMOSTAT CYMAX =E03+CRP3

29 B1 DOOR LIMIT SWITCH CHINA =E03+CRP3

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A05 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A06

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LIST OF EQUIPMENTS: =E03+CRP3 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

NO. SYMBOL DESCRIPTION MANUFACTORY CODE QTY. UNIT NOTE CUBICLE

30 E0 HEATING RESISTER CYMAX =E03+CRP3


A A
31 E1 LIGHTING LAMP CHINA =E03+CRP3

32

33

34

35

36
B B
37

38

39

40

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A06 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A07

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LIST OF EQUIPMENTS: =E03+CRP3 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

NO. SYMBOL DESCRIPTION MANUFACTORY CODE QTY. UNIT NOTE CUBICLE

1 FQAC, FQAC1 MCB AC LEGRAND DX3 02 Pcs 2P-16A-6kA =E03+MK


A A
2 FQCB, FQDS MCB DC LEGRAND DX3 DC 02 Pcs 2P-16A-16kA =E03+MK

3 KQP CONTACTOR ABB ESB25 01 Pcs =E03+MK

4 XAC, XDC POWER TERMINALS DEGSON PC6 01 Lot =E03+MK

5 X4... CURRENT TERMINALS DEGSON PCTK 01 Lot =E03+MK

6 X5... VOLTAGE TERMINALS DEGSON PC6 01 Lot =E03+MK

7 X... SIGNAL TERMINALS DEGSON PC4 01 Lot =E03+MK


B B
8 B0 THERMOSTAT CYMAX =E03+MK

9 B1 DOOR LIMIT SWITCH CHINA =E03+MK

10 E0 HEATING RESISTER CYMAX =E03+MK

11 E1 LIGHTING LAMP CHINA =E03+MK

12

13
C C
14

15

16

17

18

D 19 D

20

21

22

23

24

E 25
E

26

27

28

29

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A07 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LIST OF EQUIPMENTS: =E03+MK PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

110KV DONG HAI


A A

LVT
110 0.11 0.11
kV
3 3 3

CL: 3P

B CL: 0.5 +CRP3 B


QE76 XTC1 PMF (ELITE 448) XTV1

M QL07 CL: 0.5


TO METTERING PANEL
U I P Q
f pF ...
QE75

XTC2 BCU (C264) XTV2


P2
25 FR
CL: 5P20
TO F87B
XTV3
CT CL: 0.5 BVT C11 CL:0.5
400-800-1200 FROM =E05+CRP5 PANEL
C C
/1/1/1/1A CL: 0.5
TO METTERING PANEL
BVT C11 CL:0.5
F21 (P445)
CL: 5P20 TO =E01+CRP1 PANEL
XF21 67/67N SOTF 27/59 85 XF21
CL: 5P20 50/51 50/51N FR 21/21N

P1
XF87L XF87L
F87L (P543)

E03 F87L 68 27/59 85


XF87L
D QF01 21/21N 67/67N 79/25 D
TO FR BVT C11 CL:3P
50/51 50/51N FL/FR FROM =E05+CRP5 PANEL

BVT C11 CL:3P


F861 (BJ-8RP) F741 (VDF-10) TO =E01+CRP1 PANEL

QE15
M QL01 F862 (BJ-8RP) F742 (VDF-10)

E E

C11
VOLTAGE CIRCUIT

CURRENT CIRCUIT

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171
CONTROL, PROTECTION & MEASUREMENT PRINCIPLE
DATE 24/11/2020
APPROVED NGUYEN DINH TUAN PECC2/TT-110KV/E03-171
DIAGRAM
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

CIRCUIT BREAKER =E03+CRP3 =E05+CRP5 =E01+CRP1


DEVICE OPPOSITE
A E03-QF01 -F87L -F21 -F861 -F862 -F87B -F861 -F862 -F861 -F862 A
PANEL

BLOCK START LOCK LOCK START LOCK LOCK LOCK LOCK


SYMBOL TYPE FUNCTION TC1 TC2 CC PTT PTT OUT PTT DTT
CC 79 OUT OUT 50BF OUT OUT OUT

87L, Z1(21,21N), 67N X X X* X X0

-F87L P543 Z2, Z3(21/21N) 67, 50/51,


X X X X X
SOTF, 79 FINAL

B 79/25 X B

67N, 21/21N X X X X X0

-F21 P445
67, 50/51,50/51N (I>>) X X X X X
=E03+CRP3

-F741 VDF-10 74 TCS X

-F742 VDF-10 74 TCS X


C C
-F861 BJ-8RP 86 X X X X

-F862 BJ-8RP 86 X X X X

50BF BAY E03(STAGE2) X X X X X0

50BF BAY E03(STAGE1) X X X X X*

D D
50BF BAY E05(STAGE2) X X X X
=E05+CRP5 -F87B P746
50BF BAY E01(STAGE2) X X X X

87B X X X X X* X X X X

-F271 P141 27/59, 81 X X

E PTT Z1 (21/21N), 67N X0 X1 E


OPPOSITE
DTT(50BF) X0 X0

X0: COMMUNICATION THROUGH OPTICAL CABLE


X*: AUTO START
X1: COMMUNICATION THROUGH TELEPROTECTION
NOTE: TCS: TRIPPING COIL SUPPERVISOR
PTT: START PROTECTION
DTT: SENT TRIP
POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03
DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN TRIPPING MATRIX PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SIDE VIEW REAR VIEW


A FRONT VIEW A
EQUIPMENT

ENTEC =E03+CRP3
TAG NAME DESCRIPTION
TO 110kV DONG HAI
=E03+WR
SW BCU BAY CONTROL UNIT

MiCOM
F67
P 143
F87B BUSBAR DIFFERENTIAL PROTECTION RELAY
ALARM ALARM

ALARM

F21 DISTANCE PROTECTION RELAY


ALARM

ALARM ALARM

ALARM
c ALARM

c LEAR ALARM
READ
ALARM
ENTER
ALARM

ALARM
ALSTOM

F741, F742 TRIPPING CIRCUIR SUPERVISION RELAY


F21
MiCOM P P142 F861, F862 RƠLE TRIP-LOCKOUT
ALARM ALARM

ALARM ALARM

ALARM ALARM
c
PMV1, PMV2 VOLTAGE METER FOR BUS 1, BUS 2
ALARM ALARM

c LEAR ALARM
READ
ALARM
ENTER
ALARM

ALARM
ALSTOM

SQF01 DISCREPANCY CONTROL SWITCH FOR CB


BCU

SQL01;SQL02;SQE14; SQE15;SQE24; SQE25 DISCREPANCY CONTROL SWITCH FOR DS; ES


B ALARM

ALARM

ALARM

ALARM
c
B
S.B/M "MIMIC/BCU" SELECTOR SWITCH
ALARM

ALARM

ALARM
o I L/R
ALARM

S.25 " SYN./BYPASS" SELECTOR SWITCH

S.87L "ON/OFF" SELECTOR SWITCH FOR 87L


S.50BF "ON/OFF" SELECTOR SWITCH FOR 50BF
S.RE
2200

RESET 86 PUSH BUTTON


S.LT LAMP TEST PUSH BUTTON
SQL01
S.RE S.LT
P.LC LAMP INDICATOR FOR CB CONTROL AT LOCAL
S.B/M -SQE15
-SQF01 XF... RELAY TESTBLOCK
S.25
P.LC
XC.., XV.. CURRENT TESTBLOCK, VOLTAGE TESTBLOCK
S.79 -SQL07
-SQE75
F27 27/59/81 PROTECTION RELAY
S.87L
C C
-SQE76
S.81

F861 F862 F741 F742

XTV.MF
XF87L
XF21

XTC.BC XTC.MF XTV1.BC XTV2.BC

750 800
800 800
D D
TOP VIEW BOTTOM VIEW BASE NAME PLATE (SCALE 1:5)
4x∅14 100

C =E03+CRP3

45
750
800
200
800

800
750

C (Scale 1:5) REMARK:


E IP DEGREE: IP41 E
Ø14 APPLICATION STANDARD: IEC60529
25 MATERIAL: STEEL
STEEL THICKNESS: 2mm
4x∅8 PAINT COLOR: RAL7032
800 550 DOOR APPLY AREA: REAR
OPEN DOOR: 180°

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LAYOUT DRAWING PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

864 570 REMOVE FRONT DOOR REMOVE BACK DOOR


A A

1500

B B

C C
450 800
800
506

A-A
TOP VIEW
D D
450
75 300
470

4x∅14

25 750
760 800
E LEGEND: E
- PROTECTION CLASS: IP55
- STANDARD: IEC60529
- THICKNESS: 2mm
-MATERIAL:SUS 302
- OPEN FROM FRONT DOOR
- ALL DIMENSIONS ARE IN MILLIMETER

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B05

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LAYOUT DRAWING MARSHALLING KIOSK =E03+MK PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SCADA LEVEL PANEL LEVEL EQUIPMENT LEVEL


A A
OPEN/CLOSE COMMAND DS E03-QL01 FROM SCADA

BCU "LOCAL/REMOTE" ON "LOCAL"

&
OPEN/CLOSE COMMAND DS E03-QL01 FROM BCU
&
HMI "LOCAL/REMOTE" ON "REMOTE"
≥1
≥1 &
HMI "LOCAL/REMOTE" ON "LOCAL"
&
B BCU "LOCAL/REMOTE" ON "REMOTE" B
&
OPEN/CLOSE COMMAND DS E03-QL01 FROM HMI
SOFT INTERLOCKING *
HMI LEVEL
BCU
11O KV DONG HAI DS "REM./LOC./MAN." SWITCH ON "REMOTE"

MIMIC

C C
&
MIMIC "BCU/MIMIC" SWITCH ON "BCU"

QE76
MIMIC "BCU/MIMIC" SWITCH ON "MIMIC" &
M QL07
QE75 & ≥1
OPEN/CLOSE COMMAND DS E03-QL01 FROM CONTROL SWITCH
&
D D
OPEN/CLOSE
CT ≥1 DS E03-QL01
CB E03-QF01 OPEN

ES E03-QE15 FULLY OPEN


E03
ES E03-QE75 FULLY OPEN
&
* SOFT INTERLOCKING
CB E03-QF01 OPEN ES E05-QE14 FULLY OPEN
QF01
E E
ES E03-QE15 FULLY OPEN
&
QE15 OPEN/CLOSE COMMAND AT LOCAL
ES E03-QE75 FULLY OPEN &
M QL01
DS "REM./LOC./MAN." SWITCH ON "LOCAL" &
ES E05-QE14 FULLY OPEN OPEN/CLOSE BY HANDLE ≥1
C11
DS "REM./LOC./MAN." SWITCH ON "MANUAL" &

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B05 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B06

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN OPERATION LOGIC DIAGRAM FOR DS E03-QL01 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SCADA LEVEL PANEL LEVEL EQUIPMENT LEVEL


A A
OPEN/CLOSE COMMAND DS E03-QL07 FROM SCADA

BCU "LOCAL/REMOTE" ON "LOCAL"

&
OPEN/CLOSE COMMAND DS E03-QL07 FROM BCU
&
HMI "LOCAL/REMOTE" ON "REMOTE"
≥1
≥1 &
HMI "LOCAL/REMOTE" ON "LOCAL"
&
B BCU "LOCAL/REMOTE" ON "REMOTE" B
&
OPEN/CLOSE COMMAND DS E03-QL07 FROM HMI
SOFT INTERLOCKING *
HMI LEVEL
BCU
11O KV DONG HAI DS "REM./LOC./MAN." SWITCH ON "REMOTE"

MIMIC

C C
&
MIMIC "BCU/MIMIC" SWITCH ON "BCU"

QE76
MIMIC "BCU/MIMIC" SWITCH ON "MIMIC" &
M QL07
QE75 & ≥1
OPEN/CLOSE COMMAND DS E03-QL07 FROM CONTROL SWITCH
&
D D
OPEN/CLOSE
CT ≥1 DS E03-QL07
CB E03-QF01 OPEN

ES E03-QE15 FULLY OPEN


E03
ES E03-QE75 FULLY OPEN
&
* SOFT INTERLOCKING
CB E03-QF01 OPEN ES E03-QE76 FULLY OPEN
QF01
E E
ES E03-QE15 FULLY OPEN
&
QE15 OPEN/CLOSE COMMAND AT LOCAL
ES E03-QE75 FULLY OPEN &
M QL01
DS "REM./LOC./MAN." SWITCH ON "LOCAL" &
ES E03-QE76 FULLY OPEN OPEN/CLOSE BY HANDLE ≥1
C11
DS "REM./LOC./MAN." SWITCH ON "MANUAL" &

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B06 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B08

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN OPERATION LOGIC DIAGRAM FOR DS E03-QL07 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

EQUIPMENT LEVEL
A A

B B

11O KV DONG HAI

DS E03-QL07 FULLY OPEN


C C
OPEN/CLOSE
DS E03-QL01 FULLY OPEN
≥1 ES E03-QE75

QE76
M QL07
QE75

D D
CT

E03

QF01
E E

QE15
M QL01

C11

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B08 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B09

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN OPERATION LOGIC DIAGRAM FOR ES E03-QE75 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

EQUIPMENT LEVEL
A A

B B

11O KV DONG HAI

DS E03-QL07 FULLY OPEN


C C
OPEN/CLOSE
DS E03-QL01 FULLY OPEN
≥1 ES E03-QE15

QE76
M QL07
QE75

D D
CT

E03

QF01
E E

QE15
M QL01

C11

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B09 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B10

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN OPERATION LOGIC DIAGRAM FOR ES E03-QE15 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

EQUIPMENT LEVEL
A A

B B

11O KV DONG HAI


DS E03-QL07 FULLY OPEN

MCB LVT ON
C C
OPEN/CLOSE
NO VOLTAGE IN LINE
≥1 ES E03-QE76

QE76 DS E03-QL09 FULLY OPEN


M QL07
QE75

D D
CT

E03

QF01
E E

QE15
M QL01

C11

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B10 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B11

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN OPERATION LOGIC DIAGRAM FOR ES E03-QE76 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SCADA LEVEL PANEL LEVEL EQUIPMENT LEVEL


A A
CLOSE COMMAND CB E03-QF01 FROM SCADA
SF6 LOCKOUT
BCU "LOCAL/REMOTE" ON "LOCAL"

& SPRING CHARGED


CLOSE COMMAND CB E03-QF01 FORM BCU
&
HMI "LOCAL/REMOTE" ON "REMOTE"
≥1 INTERLOCKING INSIDE CB IS OK

≥1 &
HMI "LOCAL/REMOTE" ON "LOCAL"
& CB "LOCAL/REMOTE" SWITCH ON "LOCAL"
B BCU "LOCAL/REMOTE" ON "REMOTE" B
&
CLOSE COMMAND CB E03-QF01 FROM HMI CLOSE COMMAND FROM EQUIP.
SOFT INTERLOCKING
DS E03-QL01 FULLY OPEN
&
HMI LEVEL
BCU
11O KV DONG HAI DS E03-QL07 FULLY OPEN
MIMIC
BCU "BCU/MIMIC" ON "BCU"

SYNCHRO IS OK &
C "SYN./BYPASS" SELECT SWITCH ON "SYN." & C
≥1 &
"SYN./BYPASS" SELECT SWITCH ON "BYPASS"
CLOSE
& CB E03-QF01
QE76 CB "LOCAL/REMOTE" SWITCH ON "REMOTE"
TRIPPING CIRCUIT IS NOT OK
M QL07
QE75 RELAY LOCKOUT OPERATED &
≥1
BCU/MIMIC ON "MIMIC"
D D
CT
CLOSE COMMAND CB E03-QF01 FROM CONTROL SWITCH

E03 &
SYNCHRO IS OK &
"SYN./BYPASS" SELECT SWITCH ON "SYN." &
≥1
"SYN./BYPASS" SELECT SWITCH ON "BYPASS" DS E03-QL01 CLOSE

QF01 (*)
AUTO RECLOSER OPERATED
E ≥1 DS E03-QL07 CLOSE E

"ON/OFF" 79 SWITCH ON "ON"


QE15
M QL01 &
AUTO RECLOSER IS OK

C11 SYNCHRO IS OK

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B11 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B12

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CLOSING LOGIC DIAGRAM FOR CB E03-QF01 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

PANEL LEVEL EQUIPMENT LEVEL


A
SCADA LEVEL A

OPEN COMMAND E03-QF01 FROM SCADA

& &
HMI "LOCAL/REMOTE" ON "REMOTE" BCU "LOCAL/REMOTE" ON "REMOTE" SF6 LOCKOUT

≥1
HMI LEVEL ≥1
B OPEN COMMAND E03-QF01 FROM BCU B
OPEN COMMAND E03-QF01 FROM HMI CB "LOCAL/REMOTE" SWITCH ON "LOCAL"
&
& BCU "LOCAL/REMOTE" ON "LOCAL" &
HMI "LOCAL/REMOTE" ON "LOCAL" OPENING COMMAND FROM EQUIP.

BCU
11O KV DONG HAI
C OPEN CB QF01 C
& & TRIP CIRCUIT 1
BCU/MIMIC ON "BCU" CB "LOCAL/REMOTE" SWITCH ON "REMOTE"

& ≥1
≥1
QE76 BCU/MIMIC ON "MIMIC"
M QL07
QE75
&
OPENING COMMAND FROM CONTROL SWITCH
D D

CT PROTECTION RELAY OPERATED

RELAY F861 OPERATED


E03
RELAY F862 OPERATED

E QF01 E
PROTECTION RELAY OPERATED
≥1
RELAY F861 OPERATED OPEN CB QF01
QE15 & TRIP CIRCUIT 2
M QL01 RELAY F862 OPERATED
SF6 LOCKOUT

C11 MIMIC
POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03
DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B12 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE D01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN OPENING LOGIC DIAGRAM FOR CB E03-QF01 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E02+CRP2 +CRP3 =E04+CRP4

POWER SUPPLY
A HEATING & LIGHTING A

-W192
ACL1 1 -XAC 1 -XAC 2 ACL1
=E02/D01.7/ / =E04/D01.1

ACL2 2 -XAC 3 -XAC 4 ACL2


=E02/D01.7/ / =E04/D01.1

ACL3 3 -XAC 5 -XAC 6 ACL3


=E02/D01.7/ / =E04/D01.1

ACN 4 -XAC 7 -XAC 8 ACN


=E02/D01.7/ / =E04/D01.1

B B
1 3 12 14 96 98

-FQAC 11 95
2P-16A I> I>

/R06.5

/R06.7
2 4

LAMP HEATER SOCKET


C C

1 1
-B1 -B0
6A 2 0÷90°C 2

D D

1 1
1 1

-E0 -E1 -E2 -XSK


8W 60W 2 60W 2 16A
2 2
E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE D01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE D02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN AC POWER SUPPLY FOR CONTROL PANEL PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E01+MK +MK +VTB

POWER SUPPLY AC POWER SUPPLY


HEATING & LIGHTING HV EQUIPMENT
A -W210 A
=E01/D02.7/
L1 1 -XAC 1 -XAC 2

=E01/D02.7/
L2 2 -XAC 3 -XAC 4

=E01/D02.7/
L3 3 -XAC 5 -XAC 6

=E01/D02.7/
N 4 -XAC 8 -XAC 9

B B

POWER SUPPLY
HEATING & LIGHTING

1 3 12 14 96 98 1 3 12 14 96 98 -W211
-XAC 7 1 -XAC 6 -XAC 6
-FQAC1 11 95 -FQAC2 11 95
-XAC 10 2 -XAC 8 -XAC 8
2P-16A I> I> 2P-16A I> I>

/R04.6

/R05.1

/R04.6

/R05.2
2 4 2 4
C C

.AC.L 1 3 12 14 96 98
/ D03.2

.AC.N
/ D03.2 -FQAC 11 95
2P-16A I> I>

/R05.4

/R05.5
2 4

LAMP HEAT SOCKET LAMP HEAT

D D

1
1 1 -B0 1 1
-B1 -B2 0÷90°C 2 -B1 -B0
6A 2 6A 2 6A 2 0÷90°C 2
1

-XSK
16A

1 1 2 1
E 1 1 1 E
-E1 -E2 -E0 -E3 -E1 -E3
8W 8W 60W 2 60W 2 8W 60W 2
2 2 2

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE D02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE D03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN AC POWER SUPPLY FOR MARSHALLING KIOSK PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+MK

A A

AC POWER SUPPLY AC POWER SUPPLY AC POWER SUPPLY AC POWER SUPPLY AC POWER SUPPLY AC POWER SUPPLY
CB E03-QF01 DS E03-QL01 ES E03-QE15 DS E03-QL07 ES E03-QE75 ES E03-QE76

.AC.L
D02.5

220 VAC
B .AC.N B
D02.5

-XAC1 1 5 2 6 3 7 4 8

-W212 1 2 -W213 1 2 -W214 1 2 -W215 1 2 -W216 1 2 -W217 1 2

+QF01 +QL01 +QE15 +QL07 +QE75 +QE76


C C

TB1 1 2 -X1 20 21 -XT1 20 21 -X1 20 21 -XT1 20 21 -XT1 20 21


1

3
F1 F1 F1 F1 F1 F1
2

4
D D

IL H IL H H IL H H H
/Z14.6 /Z17.7 /Z20.6 /Z17.7 /Z20.6 /Z20.6

E LAMP HEAT LAMP HEAT HEAT LAMP HEAT HEAT HEAT


E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE D03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE G01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN AC POWER SUPPLY FOR CB, DS, ES PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=302+CRP2 +CRP3 =E04+CRP4

DC2 DC1 POWER 1 SUPPLY POWER 2 SUPPLY


A -W193
POWER SUPPLY POWER SUPPLY FOR SWITCH FOR SWITCH A
=E02/G01.8
DC1+ 1 -XDC1 1 -XDC1 2 DC1+
/ =E04/G01.1

=E02/G01.8
DC1- 2 -XDC1 3 -XDC1 4 DC1-
/ =E04/G01.1

-W194

=E02/G01.8
DC2+ 1 -XDC2 1 -XDC2 2 DC2+
/ =E04/G01.1

=E02/G01.8
DC2- 2 -XDC2 3 -XDC2 4 DC2-
/ =E04/G01.1

B B

1 3 1 3 1 3 1 3
12 14 96 98 12 14 96 98 12 14 96 98 12 14 96 98

-FQDC2 11 95 -FQDC1 11 95 -FQSW1 11 95 -FQSW2 11 95


2P-10A I> I> 2P-10A I> I> 2P-10A I> I> 2P-10A I> I>

/R06.6

/R06.7

/R06.6

/R06.7

/N11.7

/N11.8

/N11.7

/N11.8
2 4 2 4 2 4 2 4

1 2 /G01.3
1 7 8 /G01.4
C C
-KQP1 R3 R4 /G01.2
220VDC R5 R6 /G01.2
2

R3 R5 1 7
-KQP1
/G01.4 R4 R6 2 8

L+ L- L+ L-

DC- -SW
D / G02.1 -PS1 -PS2 D
DC+
/ G02.1

-PE

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE G01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE G02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN DC POWER SUPPLY FOR CONTROL PANEL PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP3

A POWER SUPPLY POWER SUPPLY POWER SUPPLY POWER SUPPLY A


RELAY F87l BCU INDICATOR FOR METTERING

DC+ DC+
G01.4 /G03.1

DC- DC-
G01.4 /G03.1

-XDC3 1 9 2 10 3 11 4 12

B 1 3
12 14 96 98
1 3
12 14 96 98
1 3
12 14 96 98
1 3
12 14 96 98 B

-FQ87L 11 95 -FQBCU 11 95 -FQSI 11 95 -FQMF 11 95


2P-10A I> I> 2P-10A I> I> 2P-10A I> I> 2P-10A I> I>
/R06.6

/R06.7

/N08.5

/N08.6

/R06.6

/R06.7

/R06.6

/R06.7
2 4 2 4 2 4 2 4

C C

SI+
/Q01.1

SI-
/Q01.1

-X7 1 4

D 87L+ BCU+ D
/ N06.1 /R01.1

87L- BCU-
/ N06.1 /R01.1

X12 1 8 X8 1 7

2 1 23 24 P N
F87L J BCU A PMF
/Z01.3 /Z05.2 /Z10.6
-PS -PS -PS
E P643 C264 ELITE 448
E

-PE

-PE

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE G02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE G03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN DC POWER SUPPLY FOR CONTROL PANEL PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP3

A A
POWER SUPPLY POWER SUPPLY POWER SUPPLY POWER SUPPLY
RELAY F21 TC2 TC1 CLOSING CIRCUIT

G02.8
DC+

G02.8
DC-

-XDC3 5 13 6 14 7 15 8 16

B B

1 3 1 3 1 3 1 3
12 14 96 98 12 14 96 98 12 14 96 98 12 14 96 98

-FQ21 11 95 -FQTC2 11 95 -FQTC1 11 95 -FQCB 11 95


2P-10A I> I> 2P-10A I> I> 2P-10A I> I> 2P-10A I> I>

/R06.6

/R06.7

/R06.6

/R06.7

/R06.6

/R06.7

/R06.6

/R06.7
2 4 2 4 2 4 2 4

C F21+ TC2+ TC1+ C+ C


/ N08.1 /N02.1 /N01.1 /M04.1

F21- TC2- TC1- C-


/ N08.1 /N02.7 /N01.7 /M04.4

X21 1 5 -X20 1 4 -X10 1 5 X11 1 3

-W205 12 13 -W204 9 10 15 16

+MK
-X20 1 2 -X10 1 5 X11 1 2
D D
-W236 16 17 -W235 8 9 10 13

+QF01

-TB1 9 10 -TB1 7 8 -TB1 5 6

2 1
F21 F MCB5 MCB4 MCB3
/Z04.3 -PS
E E
P445
TC2+

TC1+
TC2-

TC1-

CC+

CC-
N02.2 /

N02.2 /

N01.1 /

N01.1 /

M04.1 /

M04.1 /
-PE

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE G03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE G04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN DC POWER SUPPLY FOR CONTROL PANEL PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E04+MK +MK

DC POWER SUPPLY DC POWER SUPPLY


A FOR CB MOTOR FOR DS, ES MOTOR A
-W218
DC+ 1 -XDC 1 -XDC 2
=E04/G04.7

DC- 2 -XDC 3 -XDC 4


=E04/G04.7

1 3 1 3
12 14 96 98 12 14 96 98

-FQCB 11 95 -FQDS 11 95
2P-16A I> I> 2P-16A I> I>

/R04.7

/R05.2

/R04.7

/R05.3
B B
2 4 2 4

-XDC 5 ES+
/ P03.1
-XDC 6 ES-
/ P03.1

-XDC1 1 2 -XDC2 1 3 -XDC2 2 4

-W219 1 2 -W220 1 2 -W221 1 2

C C

+QF01 +QL01 +QL07

X1 450 460

-X1 1 2 -X1 5 4 -X1 1 2 -X1 5 4

D QM1 QM1 D
1

DSQ1+

DSQ7+
DSQ1-

DSQ7-
Q1
2

3
Q1 M01.2 /

M01.2 /

M02.2 /

M02.2 /
4
/Z17.3 M /Z17.3 M
1 5
Q1
/Z14.3 6
M
E E

POWER SUPPLY POWER SUPPLY POWER SUPPLY POWER SUPPLY POWER SUPPLY
FOR CB MOTOR FOR DS MOTOR FOR CONTROL CIRCUIT FOR DS MOTOR FOR CONTROL CIRCUIT

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE G04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE M01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN DC POWER SUPPLY FOR HV EQUIPMENT PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP3

A CLOSE DS QL01 OPEN DS QL01 CLOSE DS QL01 OPEN DS QL01 A


FROM MIMIC FROM MIMIC FROM BCU FROM BCU

6 8 1 3
1
-SQL01 BCU D
-S.B/M

Push close

Push open
/Z09.1 C3 C4 /Z05.4 -DO1 -DO2
/Z09.1
MIMIC /Z05.4 /Z05.4
2
B 5 7 2 4 B

-X3 1 X3 7 X3 8 X3 9
-W204 1 2 3 4

+MK INT_QL01+ INT_QL01-


C P01.5 P01.5 C
-X3 1 3 5 6
INTERLOCKING CIRCUIT

-W233 1 2 3 4

+QL01
-X1 4A -X1 4B -X1 8 -X1 7 -X1 9A
DSQ1+
G04.4
D D
-X1 6A -X1 6B SB3

SA1 SA1 SA1 SA1 -X1 9

-KA1
-KM1 -KM2 -SB2 -SB1

-KA4

CS1 CS2
E E
KA4 KM2 KM1 /Z18.3
-QM1

CLOSE OPEN
DSQ1- -X1 12
G04.4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE M01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE M02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CONTROL CIRCUIT DS E03-QL01 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP3

A CLOSE DS QL07 OPEN DS QL07 CLOSE DS QL07 OPEN DS QL07 A


FROM MIMIC FROM MIMIC FROM BCU FROM BCU

6 8 5 7
3
-SQL07 BCU D
-S.B/M

Push close

Push open
/Z09.1 C3 C4 /Z05.4 -DO3 -DO4
/Z09.1
MIMIC /Z05.4 /Z05.4
4
B 5 7 6 8 B

-X3 10 X3 11 X3 12 X3 13
-W204 5 6 7 8

+MK INT_QL07+ INT_QL07-


C P02.1 P02.1 C
-X3 7 9 11 12

INTERLOCKING CIRCUIT
-W238 1 2 3 4

+QL07
-X1 4A -X1 4B -X1 8 -X1 7 -X1 9A
DSQ7+
G04.6
D D
-X1 6A -X1 6B SB3

SA1 SA1 SA1 SA1 -X1 9

-KA1
-KM1 -KM2 -SB2 -SB1

-KA4

CS1 CS2
E E
KA4 KM2 KM1 /Z18.3
-QM1

CLOSE OPEN
DSQ7- -X1 12
G04.6

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE M02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE M04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CONTROL CIRCUIT DS E03-QL07 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP3

CLOSE CB QF01 CLOSE CB CLOSE CB QF01 CLOSE CB CLOSED CB


START SOTF
A FROM BCU WITH SYN. FROM MIMIC WITH SYN. AR A
C+
G03.8
X11 2 C-
G03.8 13
X11 4 X11 5 -S.B/M
/Z09.1
MIMIC
14 10
F861 10 11 14
/N03.6 F741
1 /Z11.4 6 6
B -SQF01 B

Push close
13 1 15 /Z09.1 11 17
BCU D F87L D F87L E F87L H
/Z05.4 -DO7 /Z01 BI1 /Z01.6 BI16 /Z02 -BO6 -BO8
14 10 5
F862 10 11 /Z05.4 /Z01.6 /Z01.6 /Z02.6 /Z02.6
/N04.6 F742 14 2 16 12 18
1 /Z11.4 6 1 3
-S.25
/Z09.4
SYN. BYPASS
2 4

C C
X11 6 7 8
-W204 17 18 19

+MK
X11 9
INT_CB+ INT_CB- INT_CBR- INT_CBR+
P01.1 P01.1 P01.3 P01.3

X11 3 X11 5 X11 7 11

-W235 11 12 14 15
D D

+QF01

PBS1 -TB1 14 -TB1 15 TB1 18 TB1 17

G03.7/
CC+
3 4
7 5
43A
6
E E

CLOSING COIL

-52CC
/Z13.2

G03.7/
CC-

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE M04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CLOSING CIRCUIT CB E03-QF01 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP3

A OPEN Cmd. CB OPEN Cmd. CB F87L TRIP F21 TRIP F861 F862 TRIP CIRCUIRT SUPERVISOR 1 A
FROM MIMIC FROM BCU TC1 QF01 TC1 QF01 TRIP TC1 TRIP TC1 CB E03-QF01

TC1+ TC1-
G03.6 G03.6/
X10 2 3 4 -X10 6 7

TC1+
N03.1

15 TC1-
1 1
N03.1
-S.B/M F87L H F21 E
B /Z09.1 MIMIC /Z02 BO1 /Z03 -BO1
B
16 /Z02.6 /Z03.5
1 2
2 2 F861 20 21 F862 20 21 + -
/N03.6 /N04.6 -F741
/Z11.2 K3

8 15 9 9 2 2

-SQF01 BCU D -XF87L -XF21 K1 K2


Push open

K1 K2
/Z09.1 C4 /Z05.4 /Z12.4 /Z12.5
-DO8
/Z05.4
12 4 8
7 16 10 10

C C

T.TC1 /N03.1
-X10 8 X10 9 -X10 11 12

-W204 11 12 13 14

+MK X10 1 2 3 4

-W235 4 5 6 7

D +QF01 TC1+ TB1 16 TB1 11 12 13 D


G03.6

3
PBS2
7 5
4
43A
6

-A3

TRIPPING COIL 1 1 3

E -P1 -P2 E
-S1 -S1
2 4

-A2 -52TC1
/Z13.4

G03.6/
TC1-

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171
TRIPPING CIRCUIT 1
DATE 24/11/2020
APPROVED NGUYEN DINH TUAN PECC2/TT-110KV/E03-171
CB E03-QF01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP3
F87L TRIP F21 TRIP F861 F862 TRIP CIRCUIRT SUPERVISOR 2
TC2 QF01 TC QF01 TRIP TC2 TRIP TC2 CB E03-QF01

TC2+ TC2+
A G03.5 N04.2 A
-X20 2 TC2-
G03.5

-X20 5 6

11 3
-XF87L F21 E
/Z12.4 /Z03 -BO2 TC2-
/Z03.5 N04.2

B 12 4 F861 30 31 F862 30 31 1 2 B
/N03.6 /N04.6
862 -F742 + -
/ N04.5 3 3
3 11 /Z11.2 K3

F87L H -XF21
/Z02 /Z12.5
BO2 K1 K2
K1 K2

/Z02.6

4 12 12 4 8

T.TC2 /N04.2
C C
X20 7 9 10

-W205 14 15 16

+MK
X20 3 4 5

-W236 13 14 15

+QF01
D TC2+ TB1 26 TB1 23 24 25 D
G03.4

3
PBS2
7 5
4
43A
6

-A4
TRIPPING COIL 2
5

E -P2 E
-S1 -S1
6

-A4 -52TC2
/Z13.7

TC2-
G03.5

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171
TRIPPING CIRCUIT 2
DATE 24/11/2020
APPROVED NGUYEN DINH TUAN PECC2/TT-110KV/E03-171
CB E03-QF01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP3

A F87B, 27/59 50BF(E02,E05), F87B LOAD F87T TRIP F21 TRIP RESET A
C11 TRIP TRIP SEND F861 SHEDDING LOCKOUT 1 LOCKOUT 1 LOCKOUT F861

N01.7/
TC1+

X10 13 X10 14
-W203 6

=E05+CRP5
5 5

E03.TC1+
F87L H F21 E
B /Z02 BO3 /Z03 BO3
B
/Z02.6 /Z03.5

6 6

=E05/N07.2 /
K81 3 7
/N05.4
19 3
11
BCU D -S.RL
/Z05.4 /Z09.7
-DO9
=E05/N07.2

=E05/N07.2 /Z05.4
C C
21 4
13 13
-XF87L -XF21
E03.F861
E03.TC1

/Z12.4 /Z12.5

14 14
-W203 5 7

X10 10 X10 15
D D
/ N01.4
T.TC1

SET RESET
b d
-F861
a c

N01.8/
TC1-
E E

11 1 /M04.2 51 5 /R05.7
10 50
21 2 /N01.5 61 6 /R08.7
20 60
31 3 /N02.5 70 7
30 71
41 4 /N11.4 80 8
40 81

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN TRIP-LOCKOUT1 CIRCUIT PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP3

A F87B, 27/59 50BF(E02,E05), F87B LOAD F87L TRIP F21 TRIP RESET A
C11 TRIP TRIP SEND F862 SHEDDING LOCKOUT 2 LOCKOUT 2 LOCKOUT F862

N02.7/
TC2+
X20 3 X20 12
-W203 11

862

=E05+CRP5
N02.4/

E03.TC2+
B B

=E05/N07.3 /
7 7
F87L H F21 E
/Z02 BO4 /Z03 BO4
/Z02.6 /Z03.5
K81 4 8
8 8
/N05.4
22 3*
12
BCU D -S.RL
=E05/N07.3

=E05/N07.4
/Z05.4 /Z09.7
-DO10
/Z05.4
C C
24 4*
15
E03.F862
E03.TC2

-XF21
/Z12.5

16
-W203 12 13

X20 8 X20 11
D D
/ N02.4
T.TC2

SET RESET
b d
-F862
a c

N02.7/
TC2-
E E

11 1 /M04.2 51 5 /R05.8
10 50
21 2 /N01.6 61 6 /R08.7
20 60
31 3 /N02.6 70 7
30 71
41 4 /N11.5 80 8
40 81

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N05

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN TRIP-LOCKOUT2 CIRCUIT PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E01+CRP1 +CRP3 =E05+CRP5

A A

-W203
LV1. -X91 1 LOAD SHEDDING LEVEL 1 2 14 LV1.
=E01/N13.7/ / =E05/N18.2

LV2. -X91 3 LOAD SHEDDING LEVEL 2 4 15 LV2.


=E01/N13.7/ / =E05/N18.2

LV3. -X91 5 LOAD SHEDDING LEVEL 3 6 16 LV3.


=E01/N13.7/ / =E05/N18.2

B LV4. -X91 7 LOAD SHEDDING LEVEL 4 8 17 LV4. B


=E01/N13.7/ / =E05/N18.2

COM. -X91 9 COM 10 18 COM.


=E01/N13.7/ / =E05/N18.2

LEVEL 1

LEVEL 2

LEVEL 3

LEVEL 4
4 6 8 10
-S.81
C /Z09.1 C

14
-K81
D 220VDC 13 D

5 9
E 1 E
6 10
2
7 11 /N03.4
3
8 12 /N04.4
4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N05 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N06

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LOAD SHEDDING CIRCUIT PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP3

A =E03+QF01 =E03+QF01 =E03+QF01 =E03+VTB 50BF DTT =E05+CRP5 =E04+CRP4 =E04+CRP4 =E04+CRP4 A
CB CLOSED SPRING DISCHARGED SF6 LOCKOUT MCB LVT 3P OFF TO END LINE MCB BVT CL:3P OFF SWITCH FAIL MCB SWITCH OFF MCB SWITCH TRIP
87L+ 87L+
G02.2 N07.1

X12 2 3 4 5

-W205 8 -W209 7 -W203 8 -W202 5

F87L.E04+
87L.E05+
+MK +VTB

=E05+CRP5

=E04+CRP4
B B
X12 1 X12 2 X12 3
X12 15
-W235 16

=E04/N11.5 /
=E05/N07.5 /
+QF01
-TB2 1 -TB1 51 -TB1 42

12 14
S2 LS A3 -FQP
C /Z16.1 /Z15.6 /Z15.4 /S02.4 11
C

/=E04/N11.6

/=E04/N11.7

/=E04/N11.8
=E05/N07.5

=E05/N07.6
-TB2 2 -TB1 52 -TB1 43

E04.MCBO

E04.MCBT
50BF.DTT

E05.MCB

E04.SW
-W235 17 18 19

X12 4 X12 5 X12 6 X12 15


D D

-W205 9 10 11 -W209 8 -W203 9 10 -W202 6 7 8

X12 11 12 13 14 15 16 17 18 19

4 6 8 10 12 14 16 2 4
F87L D E
/Z01 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10
E /Z01.6 /Z01.6 /Z01.6 /Z01.6 /Z01.6 /Z01.6 /Z01.6 /Z01.6 /Z01.6
E

3 5 7 9 11 13 15 1 3
87L-
N07.1

X12 9 X12 10
87L-
G02.2

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N06 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N07

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT F87L PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP3

A F21 F21 A
ON 87L ON 79 SPARE
START 79 FAILURE

87L+
N06.8

X12 6 X12 7

B B

7 9
-S.B/M
/Z09.1
MIMIC MIMIC
8 10

ON
ON
C 9 11 1 3 1 1 C
F21 E F21 F BCU E -S.87L -S.79
/Z03 -BO5 /Z04.3 WD1 /Z05.6 /Z09.4 /Z09.4
DO1 DO2
/Z03.5 /Z04.3 /Z05.6 /Z05.6

10 12 2 4 2 2

D D

X12 20

6 8 10 12 16
F87L E
E /Z01.6 BI11 BI12 BI13 BI14 BI15
E
/Z01.6 /Z01.6 /Z01.6 /Z01.6 /Z01.6

5 7 9 11 15

87L-
N06.8

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N07 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N08

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT F87L PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP3

BCU RECEIVE 50BF - DTT RECEIVE 21 - PTT F85 FAIL OR MCB BCU MCB BCU
SPARE SPARE
FAILURE FROM THE END LINE FROM THE END LINE CHANNEL FAIL OFF TRIP
A A

F21+
G03.3
X21 2 X21 3 X21 4

-W208 1

=T00+TELE
X1.2 1 X1.2 3 X1.2 17
B B

5
-BCU A 12 14 96 98
/Z05.2 -FQBCU -FQBCU
/G02.3 11 /G02.3 95
6

C C

X1.2 2 X1.2 4 X1.2 18


X21 11 X21 12

D D
-W208 2 3 4

X21 8 X21 9 X21 10

2 4 6 8 10 12 14 D16
F21 D
/Z04 BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8
/Z04.6 /Z04.6 /Z04.6 /Z04.6 /Z04.6 /Z04.6 /Z04.6 /Z04.6
E E
1 3 5 7 9 11 13 D15

X21 6 X21 7
F21-
G03.3

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N08 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N09

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT F21 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP3

50BF DTT 21 PTT


A TO THE END LINE TO THE END LINE A

X21 14 X21 15

=E05+CRP5

85.E05+
B B

=E05/N07.7 /
11
F21 E
/Z03 -BO6
/Z03.5

12

=E05/N07.7
C C

50BF.85
X21 16
X21 13 X21 18
D X21 17 D

-W208 5 6 7

=T00+TELE
XDC 4 X1.1 1 X1.1 2
E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N09 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N10

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT F85 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+MK

CB E03-QF01 CB E03-QF01 DS E03-QL01 DS E03-QL01


A CLOSED OPENED CLOSED OPENED A

-X3 13 14 15

-W235 1 -W233 5

+QF01 +QL01
B B

TB2 5 TB2 25 -X2 9 -X2 11

S2-3 S2-5 CS1-5 -CS1-6


/Z16.2 /Z16.5 /Z19.4 /Z19.4

C C

-TB2 6 -TB2 26 -X2 10 -X2 12

-W235 2 3 -W233 6 7
D D

-X3 16 17 18 19

-W222 1 2 3 4 5

=E05+CRP5
E03.MK+

E03.DSO
E03.CBO

E03.DSC
E03.CBC

E E
=E05/N10.2 /

=E05/N10.3 /

=E05/N10.3 /

=E05/N10.4 /
=E05/N10.2/

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N10 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N11

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT OF F87B PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP3

F87L START F21 START F861 TRIP F862 TRIP SWITCH MCB SWITCH MCB SWITCH
A 50BF BAY E03 50BF BAY E03 A
START 50BF BAY E03 START 50BF BAY E03 FAILURE OFF TRIP

9 17
H E
B F87L BO5 F21 BO8 B
/Z02 /Z03 NC NO
/Z02.6 /Z03.5
-SW 12 14 12 14 96 98 96 98
10 18
F861 40 41 F862 40 41 -FQSW1 -FQSW2 -FQSW1 -FQSW2
/N03.6 /N04.6 /G01.5 11 /G01.6 11 /G01.5 95 /G01.6 95
4 4
COM

15 17
-XF87L -XF21
/Z12.4 /Z12.5

C C
16 18

-X3 14 15 16 17 18 19

-W203 1 2 -W202 1 2 3 4
F87B.E03+

=E05+CRP5 =E04+CRP4

E03.MCBO

E03.MCBT
E03.50BF

D D

F87L.E03+

E03.SW
=E05/N12.4 /

=E04/N06.6 /

=E04/N06.7 /

=E04/N06.7 /
=E05/N12.4

=E04/N06.6
F87L, F67 BAY E03
START 50BF

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N11 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE P01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN SIGNAL SEND TO F87B PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

+MK
INTETLOCKING FOR INTETLOCKING FOR
INTETLOCKING FOR
CLOSE CB QF01 CLOSE CB QF01
A CLOSE/OPEN DS QL01 A
AT LOCAL AT REMOTE

INT_CB+ INT_CBR+ INT_QL01+


M04.2 M04.7 M01.3
-X11 4 -X11 10 -X3 2
-W233 15 16 -W236 1 -W241 1

+QL01 -X2 3 +QL01 -X2 1 +QF01 -TB2 33 +QE75 -XT2 11

B B
DS QL01 OPENED

CB QF01 OPENED

ES QE75 OPENED
DS QL01 CLOSED
-CS1-2 -CS1-1 -S3-5 -CS1-6
/Z19.4 /Z19.3 /Z16.6 /Z21.4

-X2 4 -X2 2 -TB2 34 -XT2 12


C -W233 17 18 -W236 3 -W241 2 C

-X11 12 -X11 13 -X3 22


-X3 20
-W238 14 15 -W232 2

-W240 1

E5.Q14.+
=E05+MK
+QL07 -X2 3 +QL07 -X2 1 +QE15 -XT2 11

=E05/P02.7 /
ES E05-QE14 OPENED
D D
DS QL07 OPENED

ES QE15 OPENED
DS QL07 CLOSED

-CS1-2 -CS1-1 -CS1-6


/Z19.4 /Z19.3 /Z21.4

=E05/P02.7
E5.Q14.-
-X2 4 -X2 2 -XT2 12
E E
-W238 12 13 -W240 2

-W232 1
-X11 6 -X11 8 -X3 21

-X3 4

INT_CB- INT_CBR- INT_QL01-


M04.3 M04.5 M01.4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE P01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE P02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN INTERLOCKING FOR CB, DS, ES PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+MK

INTETLOCKING FOR
A CLOSE/OPEN DS QL07 A

INT_QL07+
M02.3
-X3 8
-W236 2 -W241 3

+QF01 -TB2 27 +QE75 -XT2 3

B B
CB QF01 OPENED

ES QE75 OPENED
-S2-6 -CS1-2
/Z16.5 /Z21.3

-TB2 28 -XT2 4
C C
-W236 4 -W241 4

-X3 23 -X3 25
-W240 3 -W242 2

+QE15 -XT2 3 +QE76 -XT2 3

D D
ES QE15 OPENED

ES QE76 OPENED

-CS1-2 -CS1-2
/Z21.3 /Z21.3

-XT2 4 -XT2 4
E E
-W240 4 -W242 1

-X3 24 -X3 10

INT_QL07-
M02.4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE P02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE P03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN INTERLOCKING FOR CB, DS, ES PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+MK INTETLOCKING FOR +VTB INTETLOCKING FOR
CLOSE/OPEN ES QE15 -KMV2 -W223 CLOSE/OPEN ES QE76
-FQM2 -KMV1 1 -X8 11 2

A -W223 22 1 9 5 A
ES+ -X3 27 1 -X8 8 21 24 -X8 9 -X8 10 9 5
G04.7
/S01.7 /S01.6
-X3 26 /S01.5 -X3 35
-W233 8 -W231 1
MCB LVT CLOSED AND NO VOLTAGE IN LINE

+QL01 -X2 19

=E04+MK
DS E04-QL09 OPENED

E4.Q9+

=E04/P04.6
DS QL01 OPENED

=E04/P04.7 /
-CS1-10
B /Z19.5 B

E4.Q9-
-X2 20
-W233 9 -W231 2

-X3 28 -X3 36
-W238 5 -W238 7

C C
+QL07 -X2 19 +QL07 -X2 7
DS QL07 OPENED

DS QL07 OPENED
-CS1-10 -CS1-4
/Z19.5 /Z19.4

-X2 20 -X2 8
D D
-W238 6

-W238 8

-X3 29
ES-
G04.7
-X3 30 -X3 32 -X3 31 -X3 33 -X3 37 -X3 34
-W240 5 6 -W241 5 6 -W242 4 3

+QE15 +QE75 +QE76


-XT1 1 2 -XT1 1 2 -XT1 1 2
E E
13 13 13
-S4 -S4 -S4
14 14 14

-KA4 -KA4 -KA4


/Z20.4 /Z20.4 /Z20.4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE P03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE P04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN INTERLOCKING FOR CB, DS, ES PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+MK

A A

INTETLOCKING FOR INTETLOCKING FOR INTETLOCKING FOR


ES E05-QE14 DS E04-QL09 DS E04-QL09

B B

+QL01 +QF01 +QE76


-X2 7 -TB2 31 -XT2 11
DS QL01 OPENED

DS QL01 OPENED

DS QL01 OPENED
-CS1-4 -S2-8 CS1-6
/Z19.4 /Z16.6 /Z21.4
C C

-X2 8 -TB2 32 -XT2 12

-W233 10 11 -W236 5 6 -W242 5 6

D D

-X3 38 39 -X3 40 41 -X3 42 43

-W231 3 5 4 6

=E05+MK =E04+MK

E3.Q76+
E E
E3.Q1+

E3.Q0+

E3.Q76-
E3.Q1-

E3.Q0-
=E05/P04.3 /

=E04/P02.5 /

=E04/P02.8 /
=E05/P04.3/

=E04/P02.5/

=E04/P02.8/
POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03
DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE P04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Q01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN INTERLOCKING FOR CB, DS, ES PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP3
S. CONTROL CB QF01 CB QF01 DS E03-QL01 ES E03-QE15

LAMT TEST AT "LOCAL" OPENED CLOSED OPENED CLOSED OPENED CLOSED


A A
G02.5/
SI+
-X7 2 X7 3
-W205 1

SI+
+MK / Q02.1
-X7 1 2 3
-W236 10 -W233 12 -W240 7

+QF01 +QL01 +QE15


X1 221 X1 233 -X2 15 13 -XT2 15 13
B B

BG1-6 BG1-7 CS1-8 CS1-7 CS1-8 CS1-7


/Z19.5 /Z19.5 /Z21.4 /Z21.4

X1 222 X1 234 -X2 16 14 -XT2 16 14

-W236 11 12 -W233 13 14 -W240 8 9

-X7 9 10 11 13 15 17

C -W205 2 3 4 5 6 7 C
-X7 8 9 10 11 12 13
9 11 9 11
-SQF01 -SQL01
/Z09.1 /Z09.1
2 1
SQE15
/Z09.4 3
10 12 10 12

KT+
/ Q02.1
D 3 D
1 5 1 5 2 6 3 7
-S.LT -KLCB -KST2 -KST2 -KST2
/Z09.7 /R07.7 /Q01.2 /Q01.2 /Q01.2
9 9 10 11
TEST

4 X1 X1
X1 -SQF01 -SQL01
14 14 PL01 /Z09.1 /Z09.1
-KST1 -KST2 /Z09.7 X2
220VDC 13 220VDC 13 X2 X2

E SI- E
/ Q02.1
-X7 5 -X7 6 -X7 7
G02.5/
SI-

5 9 5 9 /Q01.3
1 1
6 10 6 10 /Q01.5
2 2
7 11 7 11 /Q01.6
3 3
8 12 8 12 /Q02.3
4 4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Q01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Q02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN INDICATOR CIRCUIT PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+MK

DS E03-QL07 ES E03-QE75 ES E03-QE76

A OPENED CLOSED OPENED CLOSED OPENED CLOSED A

Q01.7/
SI+ -X7 8

X7 4 -X7 5 6 7

-W238 11 -W241 7 -W242 7

+QL07 +QE75 +QE76


-X2 15 13 -XT2 15 13 -XT2 15 13

B CS1-8 CS1-7 CS1-8 CS1-7 CS1-8 CS1-7 B


/Z19.5 /Z19.5 /Z21.4 /Z21.4 /Z21.4 /Z21.4

-X2 16 14 -XT2 16 14 -XT2 16 14

-W238 9 10 -W241 8 9 -W242 8 9

X7 23 25 X7 19 21 22 24

C C
+CRP3

X7 14 15
9 11
X7 16 17 18 19

-SQL07
/Z09.1
2 1 2 1
SQE75 SQE76
/Z09.4 3 /Z09.4 3
10 12
D D

Q01.8/
KT+

4 8
-KST2
/Q01.2 12

E X1 E
-SQL09
/Z09.1

X2

Q01.8/
SI-

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Q02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN INDICATOR CIRCUIT PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP3

=E03+QF01 =E03+QF01
A =E03+QF01 =E03+QF01 =E03+QF01 =E03+QF01 =E03+QF01 A
SPRING CHARGED CONTROL SPARE
CB OPENED CB CLOSED SF6 ALARM SF6 LOCKOUT MCB OFFF
FAILURE ALARM AT LOCAL
BCU+ BCU+
G02.4 R05.1
-X8 2
-W206 1

+MK BCU+
R02.1
-X8 1
B -W237 1 B

+QF01

TB2 29 3 TB1 40 -TB1 44 51 46 30 32 34 36 38

S2 S2 A2 A4-1 TR1-1 43A MCB1 MCB2 MCB3 MCB4 MCB5


/Z16.5 /Z16.2 /Z15.4 /Z15.5 /Z15.6 /Z15.5 /Z15.2 /Z15.3 /Z15.3 /Z15.3 /Z15.4

C C

TB2 20 4 TB1 41 -TB1 45 52 47 31 33 35 37 39

-W237 2 3 4 5 6 7 8

X8 7 8 9 10 11 12 14

-W206 2 3 4 5 6 7 8
D D

X8 10 11 12 13 14 15 16 17
CBL
/ R07.7
1 2 4 5 7 8 10 11
- BCU I
/Z06.3
DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8
/Z06.3 /Z06.3 /Z06.3 /Z06.3 /Z06.3 /Z06.3 /Z06.3 /Z06.3

E 3 6 9 12 E
BCU-
R02.1

-X8 8

BCU- -X8 9
G02.4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT BCU PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+MK

A DS E03-QL01 DS E03-QL01 DS E03-QL01 DS E03-QL01 DS E03-QL07 DS E03-QL07 DS E03-QL07 DS E03-QL07 A


OPENED CLOSED CTR. AT LOCAL MCB OFF OPENED CLOSED CTR. AT LOCAL MCB OFF
BCU+ BCU+
R01.2 R03.1
-X8 2
-W234 1 -W239 1

+QL01 +QL07

X2 23 -X2 21 -X2 77 -X2 83 -X2 87 -X2 75 -X2 73 X2 23 -X2 21 -X2 77 -X2 83 -X2 87 -X2 75 -X2 73
B B

CS1 CS1 SA1 QF1 QF3 KA1 QM1 CS1 CS1 SA1 QF1 QF3 KA1 QM1
/Z19.6 /Z19.5 /Z18.7 /Z18.7 /Z17.8 /Z17.5 /Z17.5 /Z19.6 /Z19.5 /Z18.7 /Z18.7 /Z17.8 /Z17.5 /Z17.5

X2 24 -X2 22 -X2 80 -X2 84 -X2 88 -X2 76 -X2 74 X2 24 -X2 22 -X2 80 -X2 84 -X2 88 -X2 76 -X2 74

C C
-W234 2 3 4 5 -W239 2 3 4 5

-X8 13 15 16 17 18 19 20 21

+CRP3
-W206 9 10 11 12 13 14 15 16

-X8 18 19 20 21 22 23 24 25
D D

13 14 16 17 19 20 22 23
- BCU I
/Z06.3
DI9 DI10 DI11 DI12 DI13 DI14 DI15 DI16
/Z06.3 /Z06.3 /Z06.3 /Z06.3 /Z06.3 /Z06.3 /Z06.3 /Z06.3

E 15 18 21 24 E

BCU- BCU-
R01.8 R03.1

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT BCU PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+MK

A ES E03-QE15 ES E03-QE15 ES E03-QE15 A


SPARE SPARE SPARE SPARE SPARE
OPENED CLOSED MCB OFF
BCU+ BCU+
R02.8 R04.1
-X8 3
-W240 10

+QE15

XT2 23 -XT2 21 -XT2 87


B B

CS1 CS1 QF3


/Z21.5 /Z21.5 /Z20.8

XT2 24 -XT2 22 -XT2 88

C C
-W240 11 12 13

-X8 22 24 25 26 27 28 29

+CRP3
-W207 1 2 3

-X8 26 27 28 29 30 31 32 33
D D

1 2 4 5 7 8 10 11
- BCU J
/Z06.4
DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8
/Z06.5 /Z06.5 /Z06.5 /Z06.5 /Z06.5 /Z06.5 /Z06.5 /Z06.5

E 3 6 9 12 E

BCU- BCU-
R02.8 R04.2

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT BCU PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+MK

ES E03-QE75 ES E03-QE75 ES E03-QE75 ES E03-QE76 ES E03-QE76 ES E03-QE76 E03+MK E03+MK


OPENED CLOSED MCB OFF OPENED CLOSED MCB OFF MCB AC "OFF" MCB dC "OFF"
A A
BCU+
R03.8
-X8 4 -X8 5 -X8 6
-W241 10 -W242 10

BCU+
+QE75 +QE76 R05.1

XT2 23 -XT2 21 -XT2 87 XT2 23 -XT2 21 -XT2 87


B 12 14 12 14 12 14 12 14 B
-FQAC1 -FQAC2 -FQCB -FQDS
/D02.3 11 /D02.4 11 /G04.2 11 /G04.4 11
CS1 CS1 QF3 CS1 CS1 QF3
/Z21.5 /Z21.5 /Z20.8 /Z21.5 /Z21.5 /Z20.8

XT2 24 -XT2 22 -XT2 88 XT2 24 -XT2 22 -XT2 88

C C
-W241 11 12 13 -W242 11 12 13

-X8 30 31 32 33 34 35 36 37

+CRP3
-W207 4 5 6 7 8 9 10 11

-X8 34 35 36 37 38 39 40 41
D D

13 14 16 17 19 20 22 23
- BCU J
/Z06.4
DI9 DI10 DI11 DI12 DI13 DI14 DI15 DI16
/Z06.4 /Z06.5 /Z06.5 /Z06.5 /Z06.5 /Z06.5 /Z06.5 /Z06.5

E 15 18 21 24 E

BCU- BCU-
R03.8 R05.1

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R05

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT BCU PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP3

=E03+VTB =E03+VTB =E03+VTB


A =E03+MK NO VOLTAGE =E03+VTB MCB VTC11 CL0.5 F861 F862 A
MCB AC MCB VT MCB VT
MCB TRIP IN LINE MCB TRIP OFF BLOCK 25 OPERATED OPERATED
OFF 0.5 OFF 0.5 OFF (BL 25)
BCU+
R01.8
-X8 3 -X8 4 -X8 5 -X8 6
-W209 1 -W203 3

E03.BCU+
+MK +VTB

=E05+CRP5
BCU+
R06.1

-X8 12 -X8 1
B B

=E05/R09.2 /
BCU+
R04.7

2 6
96 98 96 98 96 98 96 98 KMV1
-FQAC1 -FQAC2 -FQCB -FQDS /S01.5 10
/D02.3 95 /D02.4 95 /G04.2 95 /G04.4 95 12 14 12 14 12 14 96 98 96 98 96 98 96 98
-FQAC -FQM1 -FQM2 -FQAC -FQM1 -FQM2 -FQP
/D02.7 11 /S01.3 11 /S01.7 11 /D02.7 95 /S01.3 95 /S01.7 95 /S02.4 95
2 6 F861 50 51 F862 50 51
KMV2 /N03.6 /N04.7
/S01.6 10 5 5
C C

=E05/R09.3
-X8 23 -X8 13 -X8 2 -X8 3 -X8 4 -X8 5

VTC11
-W207 12 -W209 2 3 4 5 6 -W203 4
D D

-X8 42 43 44 45 46 61 47

1 2 4 5 7 8 10 11 10
- BCU K
/Z06.6
DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 DI9
/Z06.6 /Z06.6 /Z06.6 /Z06.6 /Z06.6 /Z06.6 /Z06.6 /Z06.6 /Z06.6

E 3 6 9 12 12 E

BCU- BCU-
R04.8 R06.1

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R05 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R06

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT BCU PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP3

TCS1 TCS2 S.S. "BCU/MIMIC" S.S. "SYN./BYPASS" =E03+CRP3 =E03+CRP3 =E03+CRP3


FAILURE FAILURE AT MIMIC AT SYN. MCB AC OFF MCB DC OFF MCB TRIP
A A

BCU+
R05.8

96
-FQMF 95 98
/G02.6
96
12 -FQAC 95 98
-FQMF 11 14 /D01.4
B /G02.6 96 B
12 -FQDC195 98
-FQDC111 14 /G01.3
/G01.3 96
17 5 12 -FQDC295 98
-S.B/M -S.25 -FQDC211 14 /G01.2
13 9 13 9 12 14
/Z09.1 /Z09.4 /G01.2 96
F741 F742 -FQAC 12 -FQ87L 95 98
/Z11.3 5 /Z11.3 5 /Z09.4 BCU /Z09.6 SYN. /D01.4 11 -FQ87L 11 14 /G02.2
18 6 /G02.2 96
12 -FQ21 95 98
-FQ21 11 14 /G03.2
C /G03.2 96 C
12 -FQCB 95 98
-FQCB 11 14 /G03.7
/G03.7 96
12 -FQSI 95 98
-FQSI 11 14 /G02.4
/G02.4 96
12 -FQTC1 95 98
-FQTC1 11 14 /G03.6
/G03.6 96
12 -FQTC2 95 98
-FQTC2 11 14 /G03.4
D D
/G03.4

14 16 17 19 20 22 23
- BCU K
/Z06.6
DI10 DI11 DI12 DI13 DI14 DI15 DI16
/Z06.6 /Z06.6 /Z06.6 /Z06.6 /Z06.6 /Z06.6 /Z06.6

E 18 21 24 E

BCU- BCU-
R05.8 R07.1

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R06 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R07

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT BCU PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP3

A A
SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE

B B

C CBL C
R01.5

D X8 48 X8 49 50 51 52 53 54 55 D

1 2 4 5 7 8 10 11
BCU H
/Z07.3 14
DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 -KLCB
/Z07.3 /Z07.3 /Z07.3 /Z07.3 /Z07.3 /Z07.3 /Z07.3 /Z07.3 220VDC 13
E E
3 6 9 12
BCU-
R06.8

5 9 /Q01.3
1
6 10
2
7 11
3
8 12
4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R07 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R08

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT BCU PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+MK +CRP3
CB E02-QF01 CB E02-QF01
CLOSED OPENED
A A

F87T TRIP F21 TRIP F861 TRIP F862 TRIP


SEND TO FR SEND TO FR SEND TO FR SEND TO FR

-X3 44 45

-W236 7

+QF01

B B
TB2 9 TB2 35
14 14
F87L H F21 E 60 61 60 61
/Z02 BO7 /Z03 BO7
F861 F862
/Z02.6 /Z03.5 /N03.6 /N04.7
6 6
15 15
S3-1 S3-6
/Z16.2 /Z16.6

C C

-TB2 10 -TB2 36

-W236 8 9

D D
-X3 46 47 -X3 2 -X3 3 -X3 4 -X3 5 -X3 6

=E00+FR

E03.F87L
CBE03.O
CBE03.C

E03.861

E03.862
E03.F21
FR+

FR+
E E
=E00+FR/R03.3 /

=E00+FR/R03.3 /

=E00+FR/R03.4 /

=E00+FR/R03.4 /

=E00+FR/R03.5 /

=E00+FR/R03.5 /
=E00+FR/R03.3 /

=E00+FR/R03.4 /

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R08 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R09

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN SIGNAL SEND TO FR PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E04+CRP4 +CRP3 =E02+CRP2

A A

B -W191 B
A+ -X9 1 2 1 A+
=E04/R09.8 / / =E02/R12.2

B- -X9 3 4 2 B-
=E04/R09.8 / / =E02/R12.2
-X9 5

C C

2 3
PMF
/Z10.6 A(+) B(-)
RS485

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R09 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE S01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN MODBUS RS485 CIRCUIT PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+LVT

A 110 0.11 0.11 0.11 A


kV
3 3 3 3

CLASS 0.5: 10VA


CLASS 0.5: 20VA CUỘN 1 - CL: 0.5 CUỘN 2 - CL: 0.5
CLASS 3P :50VA A B C A B C

* * * * * *
B B
* * * * * *
1a 1n 1a 1n 1a 1n 2a 2n 2a 2n 2a 2n
SEAL-IN POINT

+VTB
-W243 1 2 -W245 1 2 -W247 1 2 -W244 1 2 -W246 1 2 -W248 1 2

X51 1 4 X51 2 5 X51 3 6 X52 1 4 X52 2 5 X52 3 6

PE PE
C C

5 9 /P03.4 5 9 /P03.5
1 3 5 7 1 1 1 3 5 7
12 14 96 98 6 10 /R05.3 6 10 /R05.3 12 14 22 24 96 98
-FQM1 2 2 -FQM2
4P-2A 7 11 7 11 4P-2A
11 95 3 3
11 21 95
I> I> I> I> I> I> I> I>
/R05.4

/R05.5

/R05.4

/P03.4

/R05.6
8 12 8 12
2 4 6 8 4 4 2 4 6 8
D D

13 13
-KMV1 -KMV2
110VAC 14 110VAC 14

SEAL-IN POINT X51 7 8 9 10 X52 7 8 9 10

=E00+MP1 +CRP3
LVT0.5.N

LVT0.5.N
LVT0.5.A

LVT0.5.C

LVT0.5.A

LVT0.5.C
LVT0.5.B

LVT0.5.B
E E
=E00+MP1/T03.2

=E00+MP1/T03.3

=E00+MP1/T03.3

=E00+MP1/T03.3

T01.5

T01.5

T01.5

T01.6
POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03
DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE S01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE S02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LINE VOLTAGE CIRCUIT PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+LVT

A 110 0.11 0.11 0.11 A


kV
3 3 3 3

CLASS 0.5: 10VA


CLASS 0.5: 20VA CUỘN 3 - CL: 3P
CLASS 3P :50VA A B C

* * *
B B
* * *
3a 3n 3a 3n 3a 3n

+VTB
-W244 3 4 -W246 3 4 -W248 3 4

X53 1 4 X53 2 5 X53 3 6

PE

C C

1 3 5 7 12 14 96 98
-FQP
4P-2A 11 95
I> I> I> I>

/N06.4

/R05.6
2 4 6 8

D D

X53 7 8 9 10

+CRP3

LVT3P.N
LVT3P.A

LVT3P.C
LVT3P.B

E E
S04.3

S04.4

S04.4

S04.4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE S02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE S03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LINE VOLTAGE CIRCUIT PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CT CORE 1 - CL: 5P20, 400-800- 1200 /1A CORE 2 - CL: 5P20, 400-800- 1200 /1A CORE 5 - CL: 5P20, 400-800- 1200 /1A
GE
TYPE: OSKF145 A B C A B C A B C
400-800-1200/1/1/1/1/1A
A 5P20/5P20/0.5/0.5/5P20 A

1S1 1S1 1S1 1S5 1S5 1S5 2S1 2S1 2S1 2S5 2S5 2S5 5S1 5S1 5S1 5S5 5S5 5S5

-W225 -W227
1 -W229
1 1 -W227
2 -W225
2 2 -W226 -W228
1 -W230
1 1 -W228
2 -W226
2 2 -W226 -W228
3 -W230
3 3 -W228
4 -W226
4 4
+MK
B B

-X41 1 2 3 4 5 6 -X42 1 2 3 4 5 6 -X45 1 2 3 4 5 6

PE
-W224 1 2 3 4
PE PE

-W198 1 2 3 4 -W199 1 2 3 4
+CRP3 =E05+CRP5

C C

-X41 1 2 3 4 -X42 1 2 3 4

E03.CTN
E03.CTC
E03.CTA

E03.CTB
1 3 5 7 1 3 5 7
-XF87L -XF21
/Z12.4 /Z12.5

=E05/S06.5 /

=E05/S06.6 /

=E05/S06.6 /

=E05/S06.6 /
2 4 6 8 2 4 6 8

D 3 6 9 12 3 6 9 12 D
F87L C F21 C
/Z01 /Z04
IA IB IC IN IA IB IC IN
/Z01.3 /Z01.3 /Z01.3 /Z01.3 /Z04.3 /Z04.3 /Z04.3 /Z04.3 CT E03 SEND
F87B =E05+CRP5
2 5 8 11 2 5 8 11

-X411 1 2 3 4

E E
E03.CTN
E03.CTA

E03.CTC
E03.CTB

=E00+FR
=E00+FR/S01.7

=E00+FR/S01.7

=E00+FR/S01.7

=E00+FR/S01.7

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE S03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE S04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CURRENT CIRCUIT OF RELAY PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E00+FR +VTB =E05+CRP5 =E01+CRP1

LINE VOLTAGE - CL: 3P LINE VOLTAGE - CL: 3P BUSBAR VOLTAGE - CL: 3P BUSBAR VOLTAGE - CL: 3P
A A
110 0.11 110 0.11 110 0.11 110 0.11
kV kV kV kV
3 3 3 3 3 3 3 3

=E00+FR/S03.1

=E00+FR/S03.1

=E00+FR/S03.2

=E00+FR/S03.2

=E01/S03.4

=E01/S03.5

=E01/S03.5

=E01/S03.5
=E05/S07.1

=E05/S07.2

=E05/S07.2

=E05/S07.2
S02.4

S02.4

S02.5

S02.5

BVT13P.N
BVT13P.A

BVT13P.C
BVT13P.B
LVT3P.N
LVT3P.A

LVT3P.C
LVT3P.B

BVT13P.A

BVT13P.B

BVT13P.C

BVT13P.N
E03.LVTA

E03.LVTB

E03.LVTC

E03.LVTN
B B

-W200 1 2 3 4 -W201 1 2 3 4
+CRP3

-X53 1 3 5 7 -X53 2 4 6 8 -X52 1 -X52 3 5 7 -X52 2 -X52 4 6 8

C C

D D
21 23 25 27 21 23 25 27 17 19
-XF21 -XF87L
/Z12.5 /Z12.4

22 24 26 28 22 24 26 28 18 20

19 20 21 22 19 20 21 22
E F21 C F87L C 23 E
/Z04 /Z01
VA VB VC VA VB VC VS
/Z04.3 /Z04.3 /Z04.3 /Z01.3 /Z01.3 /Z01.3 /Z01.3

24

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE S04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE T01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN VOLTAGE CIRCUIT OF RELAY PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CT +VTB
CORE 4 - CL: 0.5, 400-800- 1200 /1A
GE
TYPE: OSKF145
400-800-1200/1/1/1/1/1A A B C LINE VOLTAGE - CL: 0.5
A 5P20/5P20/0.5/0.5/5P20 A
110 0.11
kV
3 3

4S1 4S1 4S1 4S5 4S5 4S5


B B

-W225 -W227
3 -W229
3 3 -W227
4 -W225
4 4
+MK

S01.7

S01.7

S01.7

S01.7
LVT0.5.N
LVT0.5.A

LVT0.5.C
LVT0.5.B
-X44 1 2 3 4 5 6

PE

C C
+CRP3
-W196 1 2 3 4 -W195 1 2 3 4

-X51 1 3 5 7

-X44 1 2 3 4
2 4 6 8

V.A
/ T02.4

V.B
/ T02.4

V.C
D / T02.4 D
V.N
7 / T02.5
1 3 5 1 3 5 7
-XTC1 -XTV1
/Z10.4 /Z10.4

2 6 8 2 4 6 8
4
V1 V2 V3 22
PMF S1 S1 S1
/Z10.6
E I2 E
I1 I3 V1 V2 V3

S2 S2 S2
N
A

C
B
T02.2

T02.2

T02.3

T02.3

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE T01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE T02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN VOLTAGE CIRCUIT OF MEASUREMENT PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP3 =E05+CRP5 =E01+CRP1

A A

BUSBAR VOLTAGE - CL: 0.5 BUSBAR VOLTAGE - CL: 0.5

110 0.11 110 0.11


kV kV
3 3 3 3

=E01/T01.5

=E01/T01.5

=E01/T01.6

=E01/T01.6
=E05/T02.1

=E05/T02.2

=E05/T02.2

=E05/T02.2
B B

BVT10.5.N
BVT10.5.A

BVT10.5.C
BVT10.5.B

BVT10.5.A

BVT10.5.B

BVT10.5.C

BVT10.5.N
-W197 1 2 3 4
/T01.2

/T01.2

/T01.3

/T01.3

/T01.6

/T01.6

/T01.6

/T01.6
-X54 1 3 5 7 -X54 2 4 6 8

C C
A

V.A

V.B

V.C

V.N
1 5 7 1 3 5 7 1 3
3
-XTC2 -XTV2 -XTV3
/Z10.4 /Z10.4 /Z10.5
D D

2 6 8 2 4 6 8 2 4
4

BCU L 15 11 7 3 21 23 25 27

/Z07.6
IA.1A IB.1A IC.1A IN.1A U V W N

E 16 12 8 4 22 24 26 28 E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE T02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE T03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN VOLTAGE CIRCUIT OF MEASUREMENT PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CT
400-800-1200/1/1/1/1A
5P20/5P20/0.5/0.5/5P20
A A
CORE 2 - CL: 5P20, 400-800- 1200 /1A
A B C

B B

3S1 3S1 3S1 3S4 3S4 3S4

C C

=E00+MP1

E03CT0.5.C1

E03CT0.5.A1
E03CT0.5.B1
E03CT0.5.A

E03CT0.5.C
E03CT0.5.B
D D
=E00+MP1/T03.6

=E00+MP1/T03.6

=E00+MP1/T03.7

=E00+MP1/T03.7

=E00+MP1/T03.6

=E00+MP1/T03.6
E E

CT E03 TO PMT CLASS 0.5

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE T03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE W01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN VOLTAGE CIRCUIT OF MEASUREMENT PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP3 +MK

A A

-X3 20 21 22 23 24 25 26 27 28 29 30 -X3 48 49 50 51 52 53 54 55

-X7 20 21 22 23 24 25 -X7 12 14 16 18 20
B B

-X8 56 57 58 59 60 62 63 64 65 -X8 38 39 40 41 42 43 44 45

-X10 16 17 18 19 20 -X10 7 8 9 10 11 12 13 14 15

-X11 9 10 11 12 13 14 15 -X11 14 15 16 17 18 19 20

-X12 21 22 23 24 25 26 27 28 29 30 -X20 6 7 8 9 10 11 12 13 14 15
C C
-X20 13 14 15 16 17 18 19 20

-X21 19 20 21 22 23 24 25

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE W01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN SPARE CIRCUIT PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP3

FUNCTION F87L P543 F87L CHỨC NĂNG


A A

C D
5A
1 1
BI1 /M04.5 START SOTF
1A
CURRENT CIRCUIT E03 - PHASE A /S03.2 2 IA 2

3 3
5A BI2 /N06.2 =E03+QF01 CB CLOSED
4 4
1A
CURRENT CIRCUIT E03 - PHASE B /S03.2 5 IB 5
BI3 /N06.2 =E03+QF01 SPRING DISCHARGED
B 6 6 B
5A
7 7
BI4 /N06.3 =E03+QF01 SF6 LOCKOUT
1A
CURRENT CIRCUIT E03 - PHASE C /S03.2 8 IC 8

9 9
5A BI5 /N06.4 =E03+VTB MCB LVT 3P OFF
10 10
1A
CURRENT CIRCUIT E03 - PHASE N /S03.3 11 IN 11
BI6 /N06.5 50BF DTT TO END LINE
12 12
5A
13 13
BI7 /N06.5 =E05+CRP5 MCB BVT CL:3P OFF
1A
C 14 IN_SEN. 14 C
15 15
BI8 /N06.6 =E04+CRP4 SWITCH FAIL
19 16
VOLTAGE CIRCUIT BAY E03 - PHASE A /S04.3 VA
E F87L
20 1
VOLTAGE CIRCUIT BAY E03 - PHASE B /S04.4 VB BI9 /N06.7 =E04+CRP4 MCB SWITCH OFF
2

21 3
VOLTAGE CIRCUIT BAY E03 - PHASE C /S04.4 VC BI10 /N06.7 =E04+CRP4 MCB SWITCH TRIP
22 4
D 5 D
23 BI11 /N07.2 F21 START 79
6
VOLTAGE CIRCUIT LINE - PHASE B /S04.6 VS
24
7
BI12 /N07.3 F21 FAILURE
8

F87L 9
J BI13 /N07.3 ON 87L
10
1
AUX
POWER SUPPLY /G02.2 SUPPLY
11
2 BI14 /N07.4 ON 79
12
E E
13
11 BI15 /N07.4 SPARE
14
12
15
13 BI16 /M04.5 CLOSE CB WITH SYN.
16
14

P54331RB7M0K18M

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE F87L (P543) PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP3
FUNCTION F87L P543 F87L CHỨC NĂNG

A A
F H
1 1
BO17 BO1 /N01.4 F87L TRIP TC1 QF01
2 2

3 3
BO18 BO2 /N02.3 F87L TRIP TC2 QF01
4 4

5 5
BO19 BO3 /N03.4 F87T TRIP LOCKOUT 1
6 6

B 7 7 B
BO20 BO4 /N04.5 F87L TRIP LOCKOUT 2
8 8
9 9
BO21 BO5 /N11.2 F87L START 50BF BAY E03
10 10

11 11
BO22 BO6 /M04.8 CLOSE CB WITH SYN.
12 12

13 13

14 BO23 BO7 14 /R08.5 F87T TRIP SEND TO FR

C 15 15 C
16 16
17 BO24 BO8 17 /M04.8 CLOSED CB AR
18 18
G F87L
1
BO9
2

3
BO10
D 4 D
5
BO11
6

7
BO12
8

9
BO13
10

11
E BO14 E
12

13
BO15 14

15

16
BO16 17

18

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE F87L (P543) PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP3

P445 F21 CHỨC NĂNG


A A

E
1
BO1 /N01.5 F21 TRIP TC1 QF01
2

3
BO2 /N02.4 F21 TRIP TC QF01
4

5
BO3 /N03.5 F21 TRIP LOCKOUT 1
B 6 B
7
BO4 /N04.6 F21 TRIP LOCKOUT 2
8

9
BO5 /N07.2 F21 TRIP START 79
10

11
BO6 /N09.5 SEND 21 - PTT TO THE END LINE
12

13

C BO7 14 /R08.6 F21 TRIP SEND TO FR C


15
16

BO8 17 /N11.3 F21 START 50BF BAY E03


18

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE F21 (P445) PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP3

FUNCTION F21 P445 F21 CHỨC NĂNG


A A

C D
5A
1 1
BI1 /N08.2 BCU FAILURE
1A
CURRENT CIRCUIT E03 - PHASE A /S03.4 2 IA 2

3 3
5A BI2 /N08.3 RECEIVE 50BF - DTT FROM THE END LINE
4 4
1A
CURRENT CIRCUIT E03 - PHASE B /S03.4 5 IB 5
BI3 /N08.3 RECEIVE 21 - PTT FROM THE END LINE
B 6 6 B
5A
7 7
BI4 /N08.4 F85 FAIL OR CHANNEL FAIL
1A
CURRENT CIRCUIT E03 - PHASE C /S03.4 8 IC 8

9 9
5A BI5 /N08.5 MCB BCU OFF
10 10
1A
CURRENT CIRCUIT E03 - PHASE N /S03.5 11 IN 11
BI6 /N08.6 MCB BCU TRIP
12 12
5A
13 13
BI7 /N08.6 SPARE
1A
C 14 IN_SEN. 14 C
15 15
BI8 /N08.7 SPARE
19 16
VOLTAGE CIRCUIT BAY E03 - PHASE A /S04.1 VA

20
VOLTAGE CIRCUIT BAY E03 - PHASE B /S04.2 VB

21
VOLTAGE CIRCUIT BAY E03 - PHASE C /S04.2 VC
22
D D
23
VS
24

F21
F
1
AUX
POWER SUPPLY /G03.2 SUPPLY
2

E E
11
F21 FAILURE /N07.3
12

13

14

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z05

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE F21 (P445) PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP3

A A

MODULE BIU241 BCU BCU BCU


FUNCTION MODULE DOU201 FUNCTION FUNCTION
- A D E

O2 1 1
DO1 /M01.7 CLOSE DS QL01 FROM BCU /N07.3 BCU ON 87L
2 2
O1 3 3
DO2 /M01.7 OPEN DS QL01 FROM BCU /N07.4 BCU ON 79
4 4
B B
WD 6 /N08.2 BCU FAILURE 5
DO3 /M02.7 CLOSE DS QL07 FROM BCU
5 6

VIN
7 7
+ DO4 /M02.7 OPEN DS QL07 FROM BCU
DI1 8
- 8
VIN
- 9 9
DI2
+ DO5
10 10

11 11
DO6
RS232/ RXD/TB
RS485 12 12
C SERIAL
C
SG(0V)
LINK 1
13 13
DO7 /M04.4 CLOSE CB QF01 FROM BCU
TXD/TA
14 14
SG(0V)
RS232/
RS422/ 15 15
RS485 DO8 /N01.3 OPEN Cmd. CB FROM BCU
CTS
16 16
RXD/TB
17 17
SERIAL
LINK 2 TXD/TA
18 18
RTS/RB
19 19

D
RA
20 DO9 21 /N03.6 RESET LOCKOUT F861 D
RCD
21 20

= + 23 22
GND /G02.3
22 DO10 24 /N04.7 RESET LOCKOUT F862
_
= 24 23
Power
Supply

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z05 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z06

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE BCU C264 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP3

A A

BCU BCU BCU


MODULE DIU200 FUNCTION FUNCTION FUNCTION
- I - J - K
VIN
+
VIN
+ 1 /R01.2 =E03+QF01 CB OPENED /R03.2 SPARE /R05.1 =E03+MK MCB TRIP
DI2 DI1
- - 2 /R01.3 =E03+QF01 CB CLOSED /R03.2 SPARE /R05.3 NO VOLTAGE IN LINE

3
B VIN
+
VIN
+ 4 /R01.3 =E03+QF01 SF6 ALARM /R03.3 SPARE /R05.4 =E03+VTB MCB AC OFF B
DI4 DI3
- - 5 /R01.4 =E03+QF01 SF6 LOCKOUT /R03.3 SPARE /R05.4 =E03+VTB MCB VT 0.5 OFF

6
VIN
+
VIN
+ 7 /R01.4 =E03+QF01 SPRING CHARGED FAILURE ALARM/R03.5 ES E03-QE15 OPENED /R05.4 =E03+VTB MCB VT 0.5 OFF (BL 25)
DI6 DI5
- - 8 /R01.5 =E03+QF01 CONTROL AT LOCAL /R03.6 ES E03-QE15 CLOSED /R05.5 =E03+VTB MCB TRIP

9
VIN
+
VIN
+ 10 /R01.5 =E03+QF01 MCB OFFF /R03.6 ES E03-QE15 MCB OFF /R05.7 MCB VTC11 CL0.5 OFF BLOCK 25
DI8 DI7
- - 11 /R01.6 SPARE /R03.7 SPARE /R05.7 F861 OPERATED

C 12 C
VIN VIN
13 /R02.1 DS E03-QL01 OPENED /R04.2 ES E03-QE75 OPENED /R05.8 F862 OPERATED
+ +
DI10 DI9
- - 14 /R02.2 DS E03-QL01 CLOSED /R04.2 ES E03-QE75 CLOSED /R06.2 TCS1 FAILURE

15
VIN
+
VIN
+ 16 /R02.3 DS E03-QL01 CTR. AT LOCAL /R04.3 ES E03-QE75 MCB OFF /R06.3 TCS2 FAILURE
DI12 DI11
- - 17 /R02.3 DS E03-QL01 MCB OFF /R04.4 ES E03-QE76 OPENED /R06.3 S.S. "BCU/MIMIC" AT MIMIC

18
VIN
+
VIN
+ 19 /R02.5 DS E03-QL07 OPENED /R04.4 ES E03-QE76 CLOSED /R06.4 S.S. "SYN./BYPASS" AT SYN.
D DI14 DI13 D
- - 20 /R02.6 DS E03-QL07 CLOSED /R04.5 ES E03-QE76 MCB OFF /R06.5 =E03+CRP3 MCB AC OFF

21
VIN
+
VIN
+ 22 /R02.6 DS E03-QL07 CTR. AT LOCAL /R04.6 E03+MK MCB AC "OFF" /R06.5 =E03+CRP3 MCB DC OFF
DI16 DI15
- - 23 /R02.7 DS E03-QL07 MCB OFF /R04.7 E03+MK MCB dC "OFF" /R06.8 =E03+CRP3 MCB TRIP

24

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z06 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z07

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE BCU C264 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E03+CRP3

A A
BCU
MODULE TMU220 FUNCTION
- L
BCU IN.5A
MODULE CCU200 FUNCTION
-H
1 2
VIN
+
VIN
+ 1 /R07.2 SPARE IN.1A /T02.3 CURRENT CIRCUIT -PHASE N
DI2 DI1
- - 2 /R07.3 SPARE
3 4
3
IC.5A
VIN
+
VIN
+ 4 /R07.3 SPARE
B DI4 DI3 5 6 B
- - 5 /R07.4 SPARE
IC.1A /T02.3 CURRENT CIRCUIT -PHASE C
6 7 8
VIN
+
VIN
7 /R07.5 SPARE
DI6 DI5 IB.5A
- - 8 /R07.5 SPARE 9 10
9
IB.1A /T02.2 CURRENT CIRCUIT -PHASE B
VIN
+
VIN
+ 10 /R07.6 SPARE 11 12
DI8 DI7
- - 11 /R07.6 SPARE
IA.5A
12 13 14
C C
13
IA.1A /T02.2 CURRENT CIRCUIT -PHASE A
CO1 14 15 16
15

16 17 18
CO2
17
X
18 19 20

19
U /T02.4 VOLTAGE CIRCUIT BVT C11 PHASE A
D CO3 20 21 22 D
21
V /T02.4 VOLTAGE CIRCUIT BVT C11 PHASE B
22 23 24
CO4
23
W /T02.4 VOLTAGE CIRCUIT BVT C11 PHASE C
24 25 26

N /T02.6 VOLTAGE CIRCUIT BVT C12 PHASE B


27 28

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z07 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z09

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE BCU C264 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP3

SELECT SWITCH "BCU/MIMIC": SA25-FA 6015-61009/SALZER SELECT SWITCH "SYN./BYPASS": SA25-FA 6037-61638-M1-I-F-3-BS-0/SALZER PUSH BUTTON 2 NO

A MIMIC X X X X X X X X X SYN. X X X 3 3* A

BYPASS X X X
1 3 5 7 9 11 13 15 17
MIMIC
BCU

4 4*
1 3 5 7 9 11

BYPASS
SYN.
2 4 6 8 10 12 14 16 18
-S.RL /N03.7 /N04.8 RED
2 4 6 8 10 12
S.B/M /M01.4 /M02.4 /N07.5 /N07.6 /M04.7 /N01.2 /R06.3

B B
S.25 /M04.6 /M04.7 /R06.4
Discrepancy control switch for CB, DS, ES: BHL-3B3111-220L1-W-Y-B-L54-Y07E

CLOSE X
SELECT SWITCH "ON/OFF" : SA25-FA 6037-61638-M1-I-F-3-BS-0/SALZER PUSH BUTTON 1NO
OPEN X
LED 3
ON X X X
INDICATOR
PUSH CLOSE X X
OFF X X X
PUSH OPEN X X
4
1 3 5 7 9 11
Push close

Push close
Push open

Push open

C 1 3 5 7 9 11 L1 C

OFF
ON
close
open

-S.LT /Q01.2 GREEN


2 4 6 8 10 12
2 4 6 8 10 12 L2

S.79 /N07.6
-SQF01 /M04.7 /N01.2 /Q01.4 /Q01.5 /Q01.5
S.87L /N07.5
-SQL01 /M01.5 /M01.6 /Q01.6 /Q01.6 /Q01.6

D -SQL07 /M02.5 /M02.6 /Q02.2 /Q02.2 D


ES SEMAPHORE: SPSR/FUJI LAMP FOR CB AT LOCAL
-SQL09 /Q02.2
+(~) X1

ES Semaphore
SELECT SWITCH "OFF/1/2/3/4" : SA25/SALZER FUJI
2 1 2 1 2
SPSR X2

91-230 VAC/DC -(~) 3 3


1 -PL01 /Q01.3 CB E03-QF01 AT "LOCAL"
OFF
1
2
3
4

E E
-SQE15 /Q01.7
2 4 6 8 10
-SQE75 /Q02.4

-S.81 /N05.4 /N05.4 /N05.5 /N05.5 -SQE76 /Q02.6

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z09 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z10

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE CONTROL DEVICES PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP3

CURRENT TEST BLOCK


A Multi-function -PMF CHỨC NĂNG A
L1 L2 L3 ELITE
-KTT-AW4
XTC1 XTC2
V1 /T01.5
S1 V1 VOLTAGE CIRCUIT PHASE A
1 2
S2

V2 /T01.5
S1 V2 VOLTAGE CIRCUIT PHASE B
3 4

EQUIPMENT
S2
B B
S1 /T01.2 /T02.1 V3 V3 /T01.5 VOLTAGE CIRCUIT PHASE C
5 6
S2

VN VN
7 8
S1
/T01.2
I1 CURRENT CIRCUIT BAY-PHASE A
S2

S1
/T01.2
C I2 CURRENT CIRCUIT BAY-PHASE B
C
S2

S1
VOLTAGE TEST BLOCK /T01.3
I3 CURRENT CIRCUIT BAY-PHASE C
S2
L1 L2 L3
-KTT-VW4
XTV1 XTV2 XTV3
1a Tx
1 2 2
1n
RS485 RS232 Rx /R09.4 MODBUS PROTOCOL
D 3 D
1a GND
3 4 5
EQUIPMENT

1n

1a /T01.5 /T02.4 /T02.6


5 6
1n

7 8 + (L)
= P
E Power (~)
POWER SUPPLY E
Supply - (N) /G02.6
= N

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z10 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z11

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE CURRENT AND VOLTAGE TESTBLOCK PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP3

A A

TRIP SUPERVISION RELAY

5 6 1

B
VDF-10 B

K1 K2

C C

K3-1 K3-2
K1 K2 K3

D 9 13 10 14 12 4 8 2 D

-F741 TRIP CIRCUIRT SUPERVISOR 1 CB E03-QF01


/R06.2 /M04.3
/N01.7

-F742 TRIP CIRCUIRT SUPERVISOR 2 CB E03-QF01


/R06.3 /M04.3
/N02.7
E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z11 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z12

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE RELAY F74 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP3

RELAY TESTBLOCK

A A
TSB-14 XF87L XF21

1 2 /S03.2 /S03.4

3 4 /S03.2 /S03.4

B 5 6 /S03.2 /S03.4 B

7 8 /S03.3 /S03.5

9 10 /N01.4 /N01.5

11 12 /N02.3 /N02.4

C C

13 14 /N03.4 /N03.5

15 16 /N11.2 /N04.6

17 18 /S04.6 /N11.3

D D
19 20 /S04.6

21 22 /S04.3 /S04.1

23 24 /S04.4 /S04.2

E 25 26 /S04.4 /S04.2 E

27 28 /S04.4 /S04.2

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z12 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z13

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE RELAY TESTBLOCK PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

TC1 TC2
LOCAL CLOSE REMOTE AUTO LOCAL REMOTE P.D.
TC1 SF6 PRESSURE LOCAL REMOTE P.D.
TC2 SF6 PRESSURE
A SUPVN. SUPVN. SUPVN. SUPVN. A
INTELOCK CLOSE RECLOSE TRIP 1 TRIP 1 TRIP POST CLOSE ALARM & LOCKOUT TRIP 2 TRIP 2 TRIP POST CLOSE LOCKOUT
PRE CLOSE PRE CLOSE

220VDC1 TB1 15 14 TB1 18 19 TB1 17 220VDC2 TB1 22 TB1 16 TB1 11 12 TB1 13 220VDC3 TB1 27 TB1 26 TB1 23 24 TB1 25

MCB3 MCB4 MCB5


TB1 J1 K71 TB1 J3 K171 TB1 J1 K371
5 7 9
K13A K9 K17 K71
3
PBS1 3 3
4
PBS2 PBS2
4 TB1 20 TB1 21 4 TB1 30
3 1
B L 0 R
DMA DMA
B
K21 K13 K3 K5 K7 K321 K313 K303 K305 K307
43A
1 3 5
2
7 5 7 5
L O R L O R
K11 43A 43A
P1 P2 P2

K17 6 6

2 4 6

21
TB1 23 24 TB1 32
21
94
C 22 C

K701

31 31 21

A3 A3 A4
32
32 22
K703

31
A4
32
K17 K73 K173 K373
K705

D 9 13 1 D
S1 94 S1 11 13
10 2 3 5
14
K707
S1 S1 S1 S1
4 12 6 14
9
K25 K325
LS
10

K709
1 1
1 K79
52CC 52TC1 52TC2
A1 A1 A1 A1
2 2 2
94 A2 A3 A4
K74
A2 A2 A2 A2
E E
MCB3 MCB4 MCB5
TB1 J2 K72 TB1 J2 K172 TB1 J2 K372
6 8 10

TB1 31

=E03 -QF01 /M04.4 /N01.3 /N02.3

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z13 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z14

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CB REFERENCE (GL312F1/GE) PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A MOTOR CIRCUIT HEATING & LIGHTING CIRCUIT A

220VDC 220V AC
TB1
M1 (Ph)
TB1 MCB2
3 1 H1
1 2
MPCB1 1
2
B B
M3

H3
3

MPCB1
4

1
LS
2

1 1
C M5 C
DS TH
2 2
M7

X1 H5 H7
M A1

M TR1 X1 1
A2 IL H
X2
X2 2

M6

D D

LS
3

M4

6
220V AC
MPCB1 (N)
E 5
MCB2 E
TB1 TB1
M2 H2 H4
4
3 4
2

=E03 -QF01 /G04.2 /D03.2

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z14 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z15

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CB REFERENCE (GL312F1/GE) PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

CLOSING AND TRIPPING COIL 1 SUPPLY MCB TRIPPED ALARM


A A

HEATING AND LIGHTING SUPPLY MCB TRIPPED ALARM

TRIPPING COIL 1 SUPPLY MCB TRIPPED ALARM

TRIPPING COIL 2 SUPPLY MCB TRIPPED ALARM


MOTOR SUPPLY MCB TRIPPED ALARM

SF6 GAS 2ND STAGE (P2) LOCKOUT

SF6 GAS 2ND STAGE (P2) LOCKOUT

REMOTE POSITION SIEMENSECTED

SPRING CHARGE FAILURE ALARM


LOCAL POSITION SIEMENSECTED
SF6 GAS 1ST STAGE (P1) ALARM

SPRING CHARGED 1NDI ALARM.


B B

SPRING DISCHARGED ALARM


C C
TB1 30 TB1 32 TB1 34 TB1 36 TB1 38 TB1 40 TB1 42 TB1 44 TB1 47 TB1 48 TB1 49 TB1 51 TB2 49

X1-1 X1-3 X1-5 X1-7 X1-9 X3-11 X3-21 X4-2 X4-3 X5-1 X6-1 X7-1

15 13
L O R 15
11 11 11 11 11 13 13 13 11 5
43A
MPCB1 MCB2 MCB3 MCB4 MCB5 A2 A3 A4 LS TR1 LS
14 16 18
12 12 12 12 12 14 14 14 6
D 12 D
X1-2 X1-4 X1-6 X1-8 X1-10 X3-12 X3-22 X4-1 X5-2 X6-2 X7-2

TB1 31 TB1 33 TB1 35 TB1 37 TB1 39 TB1 41 TB1 43 TB1 45 TB1 46 TB1 50 TB1 52 TB2 50

=E03 -QF01 /R01.5 /R01.6 /R01.6 /R01.7 /R01.7 /R01.3 /N06.3 /R01.4 /R01.5 /R01.4 /N06.2
E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z15 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z16

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CB REFERENCE (GL312F1/GE) PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

B B

AUXILIARY CONTACTS

C MC SPARE AUXILIARY CONTACTS 12NO+12NC C

TB2 1 TB2 3 TB2 5 TB2 7 TB2 9 TB2 11 TB2 13 TB2 15 TB2 21 TB2 23 TB2 25 TB2 27 TB2 29 TB2 31 TB2 33 TB2 35 TB2 37 TB2 39 TB2 41 TB2 43 TB2 45 TB2 47
TB2 17 TB2 19

3 1 3 5 1 3 5 11
1 5 7 7 7 9 11 15 15 9 11 9 13 15
13 15
S2 S2
S3 S3 S3 S3 S4 S4 S4 S4 S4 S4
S2 S2 S2 S2 S1 S2 S3 S3 S3 S4 S4
S3
D 2
4 6 8
2 4 6 8
2 4 6 8 10 12 16 10 12 10 12 14 16
D
16 14 16

U20 U24 U28 U32


U35

TB2 2 TB2 4 TB2 6 TB2 8 TB2 10 TB2 12 TB2 14 TB2 18 TB2 22 TB2 26 TB2 28 TB2 30 TB2 32 TB2 34 TB2 36 TB2 38 TB2 40 TB2 44 TB2 46 TB2 48
TB2 16 TB2 20 TB2 24 TB2 42

=E03 -QF01 /N06.2 /R01.3 /N10.3 /R08.2 /N10.4 /P02.2 /R01.2 /P04.6 /P01.6 /R08.3

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z16 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z17

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CB REFERENCE (GL312F1/GE) PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

MOTOR CIRCUIT CMM 400/800 SIGNALLINGS HEATING & LIGHTING CIRCUIT SIGNALLINGS

A A

220VDC
-X1 1 2

1 3 5

-QM1
I> I> I>

2 4 6
B B

1 1 1
KM2 KM1 R3
2 2 2
C C
3 3 -1NC -1NC
KM2 KM1 KM1 KM2
4 4 -2NC -2NC

1
13 5 A1
-M1
M SQ100 KM2 -KA1
300W 14 6 A2
D 2 D

5
KM1
6

E E
=E03 - QL01 /G04.3 /R02.4 /R02.4 /D03.3 /R02.4

=E03 - QL07 /G04.5 /R02.7 /R02.8 /D03.6 /R02.7

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z17 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z18

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN DS REFERENCE PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

CONTROL CIRCUIT SIGNALLINGS


A A

220 VDC

B B

C C

D D

=E03 - QL01 /M01.5 /R02.3 /R02.3

E E
=E03 - QL07 /M02.5 /R02.7 /R02.6

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z18 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z19

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN DS REFERENCE PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A AUXILIARY CONTACTS A

DS CLOSED

B B

C C

DS OPENED

D D

=E03 -QL01 /P01.4 /P01.2 /P04.3 /N10.5 /N10.5 /Q01.6 /Q01.6 /P03.2 /R02.2 /R02.1
E E
=E03 -QL07 /P01.4 /P01.2 /P03.6 /Q02.2 /Q02.2 /P03.2 /R02.6 /R02.5

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z19 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z20

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN DS REFERENCE PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

INTERLOCKING CIRCUIT HEATING CIRCUIT SIGNALLINGS


A A

B B

C C

D D

E E

- +QE15 /P03.3 /D03.4 /R03.6

- +QE75 /P03.5 /D03.6 /R04.3

- +QE76 /P03.7 /D03.7 /R04.5

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z20 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z21

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN ES REFERENCE PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

AUXILIARY CONTACTS

A A

B B

C C

D D

E E

- +QE15 /P02.2 /P01.6 /Q01.7 /Q01.7 /R03.6 /R03.5

- +QE75 /P02.3 /P01.7 /Q02.4 /Q02.4 /R04.2 /R04.2

- +QE76 /P02.3 /P04.7 /Q02.6 /Q02.6 /R04.4 /R04.4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z21 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE +CRP3/X100

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN ES REFERENCE PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+CRP3-XAC A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +CRP2 -XAC 2 1 +/D01.2
=E04 +CRP4 -XAC 1 2 +/D01.7
=E02 +CRP2 -XAC 4 3 +/D01.2

B =E04 +CRP4 -XAC 3 4 +/D01.7 B


=E02 +CRP2 -XAC 6 5 =E03 +CRP3 FQAC 1 +/D01.2
=E04 +CRP4 -XAC 5 6 +/D01.7
=E02 +CRP2 -XAC 8 7 =E03 +CRP3 FQAC 3 +/D01.2
=E04 +CRP4 -XAC 7 8 +/D01.7

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X100 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X101

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+CRP3-XAC PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+CRP3-XDC1 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +CRP2 -XDC1 2 1 =E03 +CRP3 FQDC1 1 +/G01.2
=E03 +CRP3 -FQSW1 1 2 =E04 +CRP4 XDC1 1 +/G01.7
=E02 +CRP2 -XDC1 4 3 =E03 +CRP3 FQDC1 3 +/G01.2

B =E03 +CRP3 -FQSW1 3 4 =E04 +CRP4 XDC1 3 +/G01.7 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X101 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X102

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+CRP3-XDC1 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+CRP3-XDC2 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E02 +CRP2 -XDC2 2 1 =E03 +CRP3 FQDC2 1 +/G01.2
=E03 +CRP3 -FQSW2 1 2 =E04 +CRP4 XDC2 1 +/G01.7
=E02 +CRP2 -XDC2 4 3 =E03 +CRP3 FQDC2 3 +/G01.2

B =E03 +CRP3 -FQSW2 3 4 =E04 +CRP4 XDC2 3 +/G01.7 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X102 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X103

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+CRP3-XDC2 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+CRP3-XDC3 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +CRP3 -FQ87L 1 1 =E03 +CRP3 KQP1 2 +/G02.2
=E03 +CRP3 -FQBCU 1 2 +/G02.3
=E03 +CRP3 -FQSI 1 3 +/G02.4

B =E03 +CRP3 -FQMF 1 4 +/G02.6 B


=E03 +CRP3 -FQ21 1 5 +/G03.2
=E03 +CRP3 -FQTC2 1 6 +/G03.4
=E03 +CRP3 -FQTC1 1 7 +/G03.6
=E03 +CRP3 -FQCB 1 8 +/G03.7
=E03 +CRP3 -FQ87L 3 9 =E03 +CRP3 KQP1 8 +/G02.2
=E03 +CRP3 -FQBCU 3 10 +/G02.3
=E03 +CRP3 -FQSI 3 11 +/G02.5
=E03 +CRP3 -FQMF 3 12 +/G02.6
=E03 +CRP3 -FQ21 3 13 +/G03.2
C =E03 +CRP3 -FQTC2 3 14 +/G03.5 C
=E03 +CRP3 -FQTC1 3 15 +/G03.6
=E03 +CRP3 -FQCB 3 16 +/G03.7

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X103 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X104

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+CRP3-XDC3 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+CRP3-X3 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +MK -X3 1 1 =E03 +CRP3 BCU-D-DO1 1 +/M01.2
=E00 +FR -X8 7 2 =E03 +CRP3 F87L-H-BO7 14 +/R08.5
=E00 +FR 39 3 =E03 +CRP3 F87L-H-BO7 15 +/R08.5

B =E00 +FR 40 4 =E03 +CRP3 F21-E-BO7 15 +/R08.6 B


=E00 +FR 41 5 =E03 +CRP3 F861-R 6 +/R08.7
=E00 +FR 42 6 =E03 +CRP3 F862-R 6 +/R08.7
=E03 +MK 3 7 =E03 +CRP3 S.B/M-C1 2 +/M01.4
=E03 +MK 5 8 =E03 +CRP3 SQL01-C3 5 +/M01.5
=E03 +MK 6 9 =E03 +CRP3 SQL01-C4 7 +/M01.6
=E03 +MK -X3 7 10 =E03 +CRP3 BCU-D-DO3 5 +/M02.2
=E03 +MK 9 11 =E03 +CRP3 S.B/M-C2 4 +/M02.4
=E03 +MK 11 12 =E03 +CRP3 SQL07-C3 5 +/M02.5
=E03 +MK 12 13 =E03 +CRP3 SQL07-C4 7 +/M02.6
C =E05 +CRP5 X12 9 14 =E03 +CRP3 F87L-H-BO5 9 +/N11.1 C
=E05 +CRP5 X12 39 15 =E03 +CRP3 XF87L-C8 16 +/N11.2
=E04 +CRP4 5 16 =E03 +CRP3 SW-SWF NC +/N11.5
=E04 +CRP4 17 17 =E03 +CRP3 SW-SWF COM +/N11.6
=E04 +CRP4 18 18 =E03 +CRP3 FQSW1 11 +/N11.7
=E04 +CRP4 19 19 =E03 +CRP3 FQSW1 95 +/N11.8
20 +/W01.1
21 +/W01.1
22 +/W01.2
D 23 +/W01.2 D
24 +/W01.2
25 +/W01.2
26 +/W01.2
27 +/W01.2
28 +/W01.3
29 +/W01.3
30 +/W01.3

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X104 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X105

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+CRP3-X3 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+CRP3-X7 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
1 =E03 +CRP3 FQSI 2 +/G02.4
=E03 +MK -X7 1 2 =E03 +CRP3 S.LT-C1 3 +/Q01.4
3 +/Q01.5

B 4 =E03 +CRP3 FQSI 4 +/G02.5 B


5 =E03 +CRP3 KST1 13 +/Q01.2
6 =E03 +CRP3 PL01 X2 +/Q01.3
7 +/Q01.8
=E03 +MK -X7 9 8 =E03 +CRP3 SQF01-C5 9 +/Q01.4
=E03 +MK 10 9 =E03 +CRP3 SQF01-C6 11 +/Q01.5
=E03 +MK 11 10 =E03 +CRP3 SQL01-C5 9 +/Q01.6
=E03 +MK 13 11 =E03 +CRP3 SQL01-C6 11 +/Q01.6
=E03 +MK 15 12 =E03 +CRP3 SQE15 2 +/Q01.7
=E03 +MK 17 13 =E03 +CRP3 SQE15 1 +/Q01.7
C =E03 +MK X7 23 14 =E03 +CRP3 SQL07-C5 9 +/Q02.2 C
=E03 +MK 25 15 =E03 +CRP3 SQL07-C6 11 +/Q02.2
=E03 +MK X7 19 16 =E03 +CRP3 SQE75 2 +/Q02.4
=E03 +MK 21 17 =E03 +CRP3 SQE75 1 +/Q02.4
=E03 +MK 22 18 =E03 +CRP3 SQE76 2 +/Q02.6
=E03 +MK 24 19 =E03 +CRP3 SQE76 1 +/Q02.6
20 +/W01.1
21 +/W01.1
22 +/W01.2
D 23 +/W01.2 D
24 +/W01.2
25 +/W01.2

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X105 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X106

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+CRP3-X7 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+CRP3-X8 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +CRP3 -PS 23 1 =E03 +CRP3 FQBCU 2 +/G02.3 =E03 +MK 37 41 =E03 +CRP3 BCU-J-DI16 23 +/R04.7
=E03 +MK -X8 1 2 +/R01.2 =E03 +MK -X8 23 42 =E03 +CRP3 BCU-K-DI1 1 +/R05.1
3 =E03 +VTB X8 12 +/R05.3 =E03 +VTB -X8 13 43 =E03 +CRP3 BCU-K-DI2 2 +/R05.3

B 4 =E05 +CRP5 X3 51 +/R05.7 =E03 +VTB -X8 2 44 =E03 +CRP3 BCU-K-DI3 4 +/R05.4 B
5 =E03 +CRP3 F861-R 51 +/R05.7 =E03 +VTB -X8 3 45 =E03 +CRP3 BCU-K-DI4 5 +/R05.4
6 +/R05.8 =E03 +VTB -X8 4 46 =E03 +CRP3 BCU-K-DI5 7 +/R05.4
=E03 +CRP3 -PS 24 7 =E03 +CRP3 FQBCU 4 +/G02.3 =E05 +CRP5 52 47 =E03 +CRP3 BCU-K-DI7 10 +/R05.7
=E03 +CRP3 DI1 3 8 +/R01.2 =E03 +CRP3 DI1 1 48 +/R07.2
9 +/R01.3 =E03 +CRP3 DI2 2 49 +/R07.3
=E03 +MK X8 7 10 =E03 +CRP3 BCU-I-DI1 1 +/R01.2 =E03 +CRP3 DI3 4 50 +/R07.3
=E03 +MK 8 11 =E03 +CRP3 BCU-I-DI2 2 +/R01.3 =E03 +CRP3 DI4 5 51 +/R07.4
=E03 +MK 9 12 =E03 +CRP3 BCU-I-DI3 4 +/R01.3 =E03 +CRP3 DI5 7 52 +/R07.5
=E03 +MK 10 13 =E03 +CRP3 BCU-I-DI4 5 +/R01.4 =E03 +CRP3 DI6 8 53 +/R07.5
C =E03 +MK 11 14 =E03 +CRP3 BCU-I-DI5 7 +/R01.4 =E03 +CRP3 DI7 10 54 +/R07.6 C
=E03 +MK 12 15 =E03 +CRP3 BCU-I-DI6 8 +/R01.5 =E03 +CRP3 DI8 11 55 +/R07.6
=E03 +MK 14 16 =E03 +CRP3 BCU-I-DI7 10 +/R01.5 56 +/W01.1
17 =E03 +CRP3 BCU-I-DI8 11 +/R01.6 57 +/W01.1
=E03 +MK -X8 13 18 =E03 +CRP3 BCU-I-DI9 13 +/R02.1 58 +/W01.2
=E03 +MK 15 19 =E03 +CRP3 BCU-I-DI10 14 +/R02.2 59 +/W01.2
=E03 +MK 16 20 =E03 +CRP3 BCU-I-DI11 16 +/R02.3 60 +/W01.2
=E03 +MK 17 21 =E03 +CRP3 BCU-I-DI12 17 +/R02.3 =E03 +CRP3 DI6 8 61 =E03 +VTB X8 5 +/R05.5
=E03 +MK 18 22 =E03 +CRP3 BCU-I-DI13 19 +/R02.5 62 +/W01.2
D =E03 +MK 19 23 =E03 +CRP3 BCU-I-DI14 20 +/R02.6 63 +/W01.2 D
=E03 +MK 20 24 =E03 +CRP3 BCU-I-DI15 22 +/R02.6 64 +/W01.3
=E03 +MK 21 25 =E03 +CRP3 BCU-I-DI16 23 +/R02.7 65 +/W01.3
26 =E03 +CRP3 BCU-J-DI1 1 +/R03.2
27 =E03 +CRP3 BCU-J-DI2 2 +/R03.2
28 =E03 +CRP3 BCU-J-DI3 4 +/R03.3
29 =E03 +CRP3 BCU-J-DI4 5 +/R03.3
=E03 +MK 27 30 =E03 +CRP3 BCU-J-DI5 7 +/R03.5
=E03 +MK 28 31 =E03 +CRP3 BCU-J-DI6 8 +/R03.6

E =E03 +MK 29 32 =E03 +CRP3 BCU-J-DI7 10 +/R03.6 E


33 =E03 +CRP3 BCU-J-DI8 11 +/R03.7
=E03 +MK -X8 30 34 =E03 +CRP3 BCU-J-DI9 13 +/R04.2
=E03 +MK 31 35 =E03 +CRP3 BCU-J-DI10 14 +/R04.2
=E03 +MK 32 36 =E03 +CRP3 BCU-J-DI11 16 +/R04.3
=E03 +MK 33 37 =E03 +CRP3 BCU-J-DI12 17 +/R04.4
=E03 +MK 34 38 =E03 +CRP3 BCU-J-DI13 19 +/R04.4
=E03 +MK 35 39 =E03 +CRP3 BCU-J-DI14 20 +/R04.5
=E03 +MK 36 40 =E03 +CRP3 BCU-J-DI15 22 +/R04.6

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X106 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X107

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+CRP3-X8 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+CRP3-X9 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +CRP3 2 1 =E04 +CRP4 X9 2 +/R09.2
=E02 +CRP2 -X9 1 2 +/R09.7
=E03 +CRP3 3 3 =E04 +CRP4 X9 4 +/R09.2

B =E02 +CRP2 6 4 +/R09.7 B


5 +/R09.7

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X107 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X108

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+CRP3-X9 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+CRP3-X10 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +MK -X10 1 1 =E03 +CRP3 FQTC1 2 +/G03.6
2 =E03 +CRP3 S.B/M-C8 15 +/N01.2
3 =E03 +CRP3 F87L-H-BO1 1 +/N01.4

B 4 +/N01.5 B
=E03 +MK 5 5 =E03 +CRP3 FQTC1 4 +/G03.6
6 =E03 +CRP3 F741-K 2 +/N01.7
7 +/N01.8
=E03 +MK X10 1 8 =E03 +CRP3 BCU-D-DO8 16 +/N01.3
=E03 +MK -X10 2 9 =E03 +CRP3 XF87L-C5 10 +/N01.4
=E05 +CRP5 X3 26 10 +/N03.2
=E03 +MK -X10 3 11 =E03 +CRP3 F741-K 4 +/N01.7
=E03 +MK -X10 4 12 =E03 +CRP3 F741-K 8 +/N01.7
=E03 +CRP3 -K 1 13 =E05 +CRP5 X3 25 +/N03.3
C =E03 +CRP3 BO3 5 14 =E03 +CRP3 K81 7 +/N03.4 C
=E05 +CRP5 27 15 =E03 +CRP3 K81 11 +/N03.3
16 +/W01.1
17 +/W01.1
18 +/W01.2
19 +/W01.2
20 +/W01.2

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X108 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X109

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+CRP3-X10 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+CRP3-X11 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +MK X11 1 1 =E03 +CRP3 FQCB 2 +/G03.7
2 =E03 +CRP3 F861-S 10 +/M04.2
=E03 +MK X11 2 3 =E03 +CRP3 FQCB 4 +/G03.7

B =E03 +CRP3 BI1 1 4 +/M04.5 B


5 +/M04.5
=E03 +MK X11 7 6 =E03 +CRP3 F87L-D-BI1 2 +/M04.5
=E03 +MK X11 9 7 =E03 +CRP3 S.25-C2 4 +/M04.7
=E03 +MK 11 8 =E03 +CRP3 F87L-H-BO8 18 +/M04.8
9 +/W01.1
10 +/W01.1
11 +/W01.2
12 +/W01.2
13 +/W01.2
C 14 +/W01.2 C
15 +/W01.2

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X109 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X110

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+CRP3-X11 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+CRP3-X12 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +CRP3 -PS 2 1 =E03 +CRP3 FQ87L 2 +/G02.2
=E03 +MK X12 1 2 +/N06.2
=E03 +VTB X12 15 3 +/N06.4

B =E05 +CRP5 31 4 +/N06.5 B


=E04 +CRP4 15 5 =E03 +CRP3 F21-E-BO5 9 +/N06.6
6 +/N07.2
7 +/N07.3
=E03 +CRP3 -PS 1 8 =E03 +CRP3 FQ87L 4 +/G02.2
=E03 +CRP3 BI2 3 9 +/N06.2
10 +/N06.2
=E03 +MK X12 4 11 =E03 +CRP3 F87L-D-BI2 4 +/N06.2
=E03 +MK X12 5 12 =E03 +CRP3 F87L-D-BI3 6 +/N06.2
=E03 +MK X12 6 13 =E03 +CRP3 F87L-D-BI4 8 +/N06.3
C =E03 +VTB X12 15 14 =E03 +CRP3 F87L-D-BI5 10 +/N06.4 C
=E05 +CRP5 32 15 =E03 +CRP3 F87L-D-BI6 12 +/N06.5
=E05 +CRP5 33 16 =E03 +CRP3 F87L-D-BI7 14 +/N06.5
=E04 +CRP4 16 17 =E03 +CRP3 F87L-D-BI8 16 +/N06.6
=E04 +CRP4 17 18 =E03 +CRP3 F87L-E-BI9 2 +/N06.7
=E04 +CRP4 18 19 =E03 +CRP3 F87L-E-BI10 4 +/N06.7
=E03 +CRP3 BI15 16 20 +/N07.4
21 +/W01.1
22 +/W01.1
D 23 +/W01.2 D
24 +/W01.2
25 +/W01.2
26 +/W01.2
27 +/W01.2
28 +/W01.2
29 +/W01.3
30 +/W01.3

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X110 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X111

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+CRP3-X12 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+CRP3-X20 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +MK -X20 1 1 =E03 +CRP3 FQTC2 2 +/G03.4
2 =E03 +CRP3 XF87L-C6 11 +/N02.3
=E05 +CRP5 28 3 =E03 +CRP3 K81 8 +/N04.3

B =E03 +MK 2 4 =E03 +CRP3 FQTC2 4 +/G03.5 B


5 =E03 +CRP3 F742-K 2 +/N02.7
6 +/N02.8
=E03 +MK X20 3 7 =E03 +CRP3 F87L-H-BO2 4 +/N02.3
=E05 +CRP5 29 8 +/N04.2
=E03 +MK 4 9 =E03 +CRP3 F742-K 4 +/N02.7
=E03 +MK 5 10 =E03 +CRP3 F742-K 8 +/N02.7
=E05 +CRP5 30 11 =E03 +CRP3 K81 12 +/N04.3
12 =E03 +CRP3 F21-E-BO4 7 +/N04.7
13 +/W01.1
C 14 +/W01.1 C
15 +/W01.2
16 +/W01.2
17 +/W01.2
18 +/W01.2
19 +/W01.2
20 +/W01.2

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X111 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X112

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+CRP3-X20 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+CRP3-X21 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +CRP3 -PS 2 1 =E03 +CRP3 FQ21 2 +/G03.2
=E03 +CRP3 -WD 5 2 =T00 +TELE X1.2 1 +/N08.3
3 =E03 +CRP3 FQBCU 12 +/N08.5

B 4 +/N08.5 B
=E03 +CRP3 -PS 1 5 =E03 +CRP3 FQ21 4 +/G03.2
6 =E03 +CRP3 F21-D-BI1 1 +/N08.2
7 +/N08.2
=T00 +TELE X1.2 2 8 =E03 +CRP3 F21-D-BI2 4 +/N08.3
=T00 +TELE X1.2 4 9 =E03 +CRP3 F21-D-BI3 6 +/N08.3
=T00 +TELE X1.2 18 10 =E03 +CRP3 F21-D-BI4 8 +/N08.4
11 =E03 +CRP3 F21-D-BI7 14 +/N08.6
12 =E03 +CRP3 F21-D-BI8 D16 +/N08.7
13 =T00 +TELE XDC 4 +/N09.3
C 14 =E05 +CRP5 X3 34 +/N09.4 C
15 =E03 +CRP3 F21-E-BO6 11 +/N09.5
=E05 +CRP5 35 16 +/N09.4
17 =T00 +TELE X1.1 1 +/N09.4
=E03 +CRP3 -BO6 12 18 =T00 +TELE X1.1 2 +/N09.5
19 +/W01.1
20 +/W01.1
21 +/W01.2
22 +/W01.2
D 23 +/W01.2 D
24 +/W01.2
25 +/W01.2

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X112 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X113

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+CRP3-X21 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+CRP3-X41 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +MK -X41 1 1 =E03 +CRP3 XF87L-C1 1 +/S03.2
=E03 +MK 2 2 =E03 +CRP3 XF87L-C2 3 +/S03.2
=E03 +MK 3 3 =E03 +CRP3 XF87L-C3 5 +/S03.2

B =E03 +MK 4 4 =E03 +CRP3 XF87L-C4 7 +/S03.3 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X113 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X114

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+CRP3-X41 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+CRP3-X44 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +MK -X44 1 1 =E03 +CRP3 XTC1 1 +/T01.2
=E03 +MK 2 2 =E03 +CRP3 XTC1 3 +/T01.2
=E03 +MK 3 3 =E03 +CRP3 XTC1 5 +/T01.3

B =E03 +MK 4 4 =E03 +CRP3 XTC1 7 +/T01.3 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X114 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X115

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+CRP3-X44 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+CRP3-X51 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +VTB X52 7 1 =E03 +CRP3 XTV1 1 +/T01.5
2 +/T01.5
=E03 +VTB X52 8 3 =E03 +CRP3 XTV1 3 +/T01.5

B 4 +/T01.5 B
=E03 +VTB X52 9 5 =E03 +CRP3 XTV1 5 +/T01.5
6 +/T01.6
=E03 +VTB X52 10 7 =E03 +CRP3 XTV1 7 +/T01.6
8 +/T01.6

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X115 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X116

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+CRP3-X51 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+CRP3-X52 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E05 +CRP5 -X53 1 1 +/S04.6
=E01 +CRP1 X52 1 2 +/S04.7
=E05 +CRP5 -X52 1 3 =E03 +CRP3 XF87L-C9 17 +/S04.6

B =E01 +CRP1 3 4 +/S04.7 B


=E05 +CRP5 -X52 5 5 +/S04.6
=E01 +CRP1 5 6 +/S04.8
=E05 +CRP5 -X52 9 7 =E03 +CRP3 XF87L-C10 19 +/S04.6
=E01 +CRP1 7 8 +/S04.8

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X116 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X117

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+CRP3-X52 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+CRP3-X53 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E00 +FR -X52 1 1 +/S04.1
=E03 +VTB X53 7 2 =E03 +CRP3 XF87L-C11 21 +/S04.3
=E00 +FR 2 3 +/S04.2

B =E03 +VTB X53 8 4 =E03 +CRP3 XF87L-C12 23 +/S04.4 B


=E00 +FR 3 5 +/S04.2
=E03 +VTB X53 9 6 =E03 +CRP3 XF87L-C13 25 +/S04.4
=E00 +FR 4 7 +/S04.2
=E03 +VTB X53 10 8 =E03 +CRP3 XF87L-C14 27 +/S04.4

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X117 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X118

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+CRP3-X53 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+CRP3-X54 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E05 +CRP5 -X53 3 1 +/T02.6
=E01 +CRP1 -X51 1 2 +/T02.7
=E05 +CRP5 -X52 3 3 =E03 +CRP3 XTV3 1 +/T02.6

B =E01 +CRP1 3 4 +/T02.8 B


=E05 +CRP5 -X52 7 5 +/T02.6
=E01 +CRP1 5 6 +/T02.8
=E05 +CRP5 -X52 11 7 =E03 +CRP3 XTV3 3 +/T02.7
=E01 +CRP1 7 8 +/T02.8

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X118 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X119

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+CRP3-X54 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+CRP3-X91 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +CRP3 C2 4 1 =E01 +CRP1 X91 2 +/N05.2
=E05 +CRP5 -X92 1 2 +/N05.7
=E03 +CRP3 C3 6 3 =E01 +CRP1 X91 4 +/N05.2

B =E05 +CRP5 -X92 3 4 +/N05.7 B


=E03 +CRP3 C4 8 5 =E01 +CRP1 X91 6 +/N05.2
=E05 +CRP5 -X92 5 6 +/N05.7
=E03 +CRP3 C5 10 7 =E01 +CRP1 X91 8 +/N05.2
=E05 +CRP5 -X92 7 8 +/N05.7
=E03 +CRP3 -K81 13 9 =E01 +CRP1 X91 10 +/N05.2
=E05 +CRP5 -X92 9 10 +/N05.7

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X119 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X120

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+CRP3-X91 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+CRP3-X411 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +CRP3 IA 2 1 =E00 +FR X43 1 +/S03.2
=E03 +CRP3 IB 5 2 =E00 +FR X43 2 +/S03.2
=E03 +CRP3 IC 8 3 =E00 +FR X43 3 +/S03.2

B =E03 +CRP3 IN 11 4 =E00 +FR X43 4 +/S03.3 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X120 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE +MK/X100

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+CRP3-X411 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+MK-XAC A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E01 +MK -XAC 2 1 =E03 +MK FQAC1 1 +/D02.2
2 +/D02.6
3 =E01 +MK XAC 4 +/D02.2

B 4 =E03 +MK FQAC2 1 +/D02.6 B


5 =E01 +MK XAC 6 +/D02.2
6 +/D02.6
=E03 +VTB -XAC 6 7 +/D02.6
=E03 +MK -FQAC1 3 8 =E01 +MK XAC 8 +/D02.2
9 =E03 +MK FQAC2 3 +/D02.6
=E03 +VTB -XAC 8 10 +/D02.6

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X100 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X101

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+MK-XAC PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+MK-XAC1 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +QF01 TB1 1 1 =E03 +MK FQAC2 2 +/D03.2
=E03 +QL01 -X1 20 2 =E03 +QE15 XT1 20 +/D03.3
=E03 +QL07 -X1 20 3 =E03 +QE75 XT1 20 +/D03.5

B =E03 +QE76 -XT1 20 4 +/D03.7 B


=E03 +QF01 2 5 =E03 +MK FQAC2 4 +/D03.2
=E03 +QL01 21 6 =E03 +QE15 XT1 21 +/D03.3
=E03 +QL07 21 7 =E03 +QE75 XT1 21 +/D03.5
=E03 +QE76 21 8 +/D03.7

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X101 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X102

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+MK-XAC1 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+MK-XDC A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E04 +MK -XDC 2 1 =E03 +MK FQCB 1 +/G04.2
2 =E03 +MK FQDS 1 +/G04.8
=E04 +MK -XDC 4 3 =E03 +MK FQCB 3 +/G04.2

B 4 =E03 +MK FQDS 3 +/G04.8 B


=E03 +MK -X3 26 5 =E03 +MK XDC2 2 +/G04.7
=E03 +MK -X3 32 6 =E03 +MK XDC2 4 +/G04.7

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X102 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X103

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+MK-XDC PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+MK-XDC1 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +QF01 X1 450 1 =E03 +MK FQCB 2 +/G04.2
=E03 +QF01 -X1 460 2 =E03 +MK FQCB 4 +/G04.3

B B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X103 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X104

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+MK-XDC1 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+MK-XDC2 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +QL01 -X1 1 1 =E03 +MK FQDS 2 +/G04.4
=E03 +QL07 -X1 1 2 =E03 +MK XDC 5 +/G04.5
=E03 +QL01 2 3 =E03 +MK FQDS 4 +/G04.4

B =E03 +QL07 2 4 =E03 +MK XDC 6 +/G04.5 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X104 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X105

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+MK-XDC2 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+MK-X3 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +QL01 -X1 4A 1 =E03 +CRP3 X3 1 +/M01.2 =E04 +MK -X3 15 41 =E03 +QF01 TB2 32 +/P04.6
=E03 +QF01 -TB2 33 2 +/P01.6 =E04 +MK -X3 17 42 =E03 +QE76 XT2 11 +/P04.7
=E03 +QL01 -X1 4B 3 =E03 +CRP3 X3 7 +/M01.4 =E04 +MK -X3 35 43 =E03 +QE76 XT2 12 +/P04.7

B 4 =E05 +MK X3 31 +/P01.7 =E03 +QF01 TB2 9 44 =E00 +FR X8 6 +/R08.2 B


=E03 +QL01 -X1 8 5 =E03 +CRP3 X3 8 +/M01.5 45 +/R08.3
=E03 +QL01 -X1 7 6 =E03 +CRP3 X3 9 +/M01.6 =E00 +FR 38 46 =E03 +QF01 TB2 10 +/R08.2
=E03 +QL07 -X1 4A 7 =E03 +CRP3 X3 10 +/M02.2 =E00 +FR X8 37 47 =E03 +QF01 TB2 36 +/R08.3
=E03 +QF01 -TB2 27 8 +/P02.2 48 +/W01.6
=E03 +QL07 -X1 4B 9 =E03 +CRP3 X3 11 +/M02.4 49 +/W01.6
10 =E03 +QE76 XT2 4 +/P02.3 50 +/W01.6
=E03 +QL07 -X1 8 11 =E03 +CRP3 X3 12 +/M02.5 51 +/W01.6
=E03 +QL07 -X1 7 12 =E03 +CRP3 X3 13 +/M02.6 52 +/W01.6
=E03 +QF01 TB2 5 13 =E05 +CRP5 X12 4 +/N10.3 53 +/W01.6
C =E03 +QL01 -X2 9 14 +/N10.5 54 +/W01.7 C
15 +/N10.5 55 +/W01.7
=E05 +CRP5 X12 23 16 =E03 +QF01 TB2 6 +/N10.3
=E05 +CRP5 24 17 =E03 +QF01 TB2 26 +/N10.4
=E05 +CRP5 25 18 =E03 +QL01 X2 10 +/N10.5
=E05 +CRP5 26 19 =E03 +QL01 X2 12 +/N10.5
=E03 +QE15 -XT2 11 20 =E03 +QF01 TB2 34 +/P01.6
=E03 +QE75 -XT2 11 21 =E03 +QE15 XT2 12 +/P01.6
=E05 +MK -X3 30 22 =E03 +QE75 XT2 12 +/P01.7
D =E03 +QE15 -XT2 3 23 =E03 +QF01 TB2 28 +/P02.2 D
=E03 +QE75 -XT2 3 24 =E03 +QE15 XT2 4 +/P02.2
=E03 +QE76 -XT2 3 25 =E03 +QE75 XT2 4 +/P02.3
=E03 +QL01 -X2 19 26 =E03 +MK XDC 5 +/P03.2
=E03 +VTB -X8 8 27 +/P03.3
=E03 +QL07 -X2 19 28 =E03 +QL01 X2 20 +/P03.2
29 =E03 +QL07 X2 20 +/P03.2
=E03 +QE15 -XT1 1 30 +/P03.2
=E03 +QE75 -XT1 1 31 +/P03.4

E =E03 +QE15 2 32 =E03 +MK XDC 6 +/P03.3 E


=E03 +QE75 2 33 +/P03.5
=E03 +QE76 2 34 +/P03.7
=E04 +MK 51 35 =E03 +VTB X8 11 +/P03.6
=E03 +QL07 -X2 7 36 =E04 +MK X3 50 +/P03.6
=E03 +QE76 -XT1 1 37 =E03 +QL07 X2 8 +/P03.6
=E05 +MK -X3 49 38 =E03 +QL01 X2 7 +/P04.2
=E05 +MK -X3 48 39 =E03 +QL01 X2 8 +/P04.3
=E04 +MK -X3 33 40 =E03 +QF01 TB2 31 +/P04.5

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X105 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X106

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+MK-X3 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+MK-X7 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +QF01 X1 221 1 =E03 +CRP3 X7 2 +/Q01.4
=E03 +QL01 -X2 15 2 +/Q01.6
=E03 +QE15 -XT2 15 3 +/Q01.7

B =E03 +QL07 -X2 15 4 +/Q02.2 B


=E03 +QE75 -XT2 15 5 +/Q02.4
=E03 +QE76 -XT2 15 6 +/Q02.6
7 +/Q02.7
8 +/Q02.8
=E03 +QF01 X1 222 9 =E03 +CRP3 X7 8 +/Q01.4
=E03 +QF01 X1 234 10 =E03 +CRP3 X7 9 +/Q01.5
=E03 +QL01 -X2 16 11 =E03 +CRP3 X7 10 +/Q01.6
12 +/W01.6
=E03 +QL01 14 13 =E03 +CRP3 X7 11 +/Q01.6
C 14 +/W01.6 C
=E03 +QE15 -XT2 16 15 =E03 +CRP3 X7 12 +/Q01.7
16 +/W01.6
=E03 +QE15 14 17 =E03 +CRP3 X7 13 +/Q01.7
18 +/W01.6
=E03 +QE75 -XT2 16 19 =E03 +CRP3 X7 16 +/Q02.4
20 +/W01.6
=E03 +QE75 14 21 =E03 +CRP3 X7 17 +/Q02.4
=E03 +QE76 -XT2 16 22 =E03 +CRP3 X7 18 +/Q02.6
D =E03 +QL07 -X2 16 23 =E03 +CRP3 X7 14 +/Q02.2 D
=E03 +QE76 14 24 =E03 +CRP3 X7 19 +/Q02.6
=E03 +QL07 14 25 =E03 +CRP3 X7 15 +/Q02.2

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X106 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X107

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+MK-X7 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+MK-X8 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +QF01 TB2 29 1 =E03 +CRP3 X8 2 +/R01.2 41 +/W01.6
=E03 +QL01 X2 23 2 =E03 +QL07 X2 23 +/R02.1 42 +/W01.6
3 =E03 +QE15 XT2 23 +/R03.2 43 +/W01.6

B =E03 +QE75 XT2 23 4 =E03 +QE76 XT2 23 +/R04.2 44 +/W01.7 B


=E03 +MK -FQAC1 12 5 +/R04.6 45 +/W01.7
6 +/R04.6
=E03 +QF01 TB2 20 7 =E03 +CRP3 X8 10 +/R01.2
=E03 +QF01 4 8 =E03 +CRP3 X8 11 +/R01.3
=E03 +QF01 TB1 41 9 =E03 +CRP3 X8 12 +/R01.3
=E03 +QF01 -TB1 45 10 =E03 +CRP3 X8 13 +/R01.4
=E03 +QF01 52 11 =E03 +CRP3 X8 14 +/R01.4
=E03 +QF01 47 12 =E03 +CRP3 X8 15 +/R01.5
=E03 +QL01 X2 24 13 =E03 +CRP3 X8 18 +/R02.1
C =E03 +QF01 31 14 =E03 +CRP3 X8 16 +/R01.5 C
=E03 +QL01 -X2 22 15 =E03 +CRP3 X8 19 +/R02.2
=E03 +QL01 -X2 80 16 =E03 +CRP3 X8 20 +/R02.3
=E03 +QL01 -X2 84 17 =E03 +CRP3 X8 21 +/R02.3
=E03 +QL07 X2 24 18 =E03 +CRP3 X8 22 +/R02.5
=E03 +QL07 -X2 22 19 =E03 +CRP3 X8 23 +/R02.6
=E03 +QL07 -X2 80 20 =E03 +CRP3 X8 24 +/R02.6
=E03 +QL07 -X2 84 21 =E03 +CRP3 X8 25 +/R02.7
22 +/R03.2
D =E03 +MK -FQAC1 95 23 =E03 +CRP3 X8 42 +/R05.1 D
24 +/R03.2
25 +/R03.3
26 +/R03.3
=E03 +QE15 XT2 24 27 =E03 +CRP3 X8 30 +/R03.5
=E03 +QE15 -XT2 22 28 =E03 +CRP3 X8 31 +/R03.6
=E03 +QE15 -XT2 88 29 =E03 +CRP3 X8 32 +/R03.6
=E03 +QE75 XT2 24 30 =E03 +CRP3 X8 34 +/R04.2
=E03 +QE75 -XT2 22 31 =E03 +CRP3 X8 35 +/R04.2

E =E03 +QE75 -XT2 88 32 =E03 +CRP3 X8 36 +/R04.3 E


=E03 +QE76 XT2 24 33 =E03 +CRP3 X8 37 +/R04.4
=E03 +QE76 -XT2 22 34 =E03 +CRP3 X8 38 +/R04.4
=E03 +QE76 -XT2 88 35 =E03 +CRP3 X8 39 +/R04.5
=E03 +MK -FQAC2 11 36 =E03 +CRP3 X8 40 +/R04.6
=E03 +MK -FQCB 11 37 =E03 +CRP3 X8 41 +/R04.7
38 +/W01.6
39 +/W01.6
40 +/W01.6

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X107 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X108

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+MK-X8 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+MK-X10 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +QF01 TB1 16 1 =E03 +CRP3 X10 8 +/N01.3
=E03 +QF01 TB1 11 2 =E03 +CRP3 X10 9 +/N01.4
=E03 +QF01 TB1 12 3 =E03 +CRP3 X10 11 +/N01.7

B =E03 +QF01 TB1 13 4 =E03 +CRP3 X10 12 +/N01.7 B


=E03 +QF01 -TB1 7 1 =E03 +CRP3 X10 1 +/G03.6
=E03 +QF01 -TB1 8 5 =E03 +CRP3 X10 5 +/G03.6
7 +/W01.6
8 +/W01.6
9 +/W01.6
10 +/W01.6
11 +/W01.6
12 +/W01.6
13 +/W01.7
C 14 +/W01.7 C
15 +/W01.7

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X108 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X109

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+MK-X10 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+MK-X11 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +QF01 -TB1 5 1 =E03 +CRP3 X11 1 +/G03.7
=E03 +QF01 -TB1 6 2 =E03 +CRP3 X11 3 +/G03.7
=E03 +QF01 -TB1 14 3 +/M04.2

B =E03 +QL01 -X2 3 4 +/P01.2 B


=E03 +QF01 -TB1 15 5 +/M04.3
6 =E03 +QL07 X2 4 +/P01.2
=E03 +QF01 TB1 18 7 =E03 +CRP3 X11 6 +/M04.5
8 =E03 +QL07 X2 2 +/P01.4
9 =E03 +CRP3 X11 7 +/M04.7
=E03 +QL01 -X2 1 10 +/P01.4
=E03 +QF01 TB1 17 11 =E03 +CRP3 X11 8 +/M04.8
=E03 +QL07 -X2 3 12 =E03 +QL01 X2 4 +/P01.2
=E03 +QL07 -X2 1 13 =E03 +QL01 X2 2 +/P01.4
C 14 +/W01.6 C
15 +/W01.6
16 +/W01.6
17 +/W01.6
18 +/W01.6
19 +/W01.6
20 +/W01.7

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X109 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X110

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+MK-X11 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+MK-X12 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +QF01 -TB2 1 1 =E03 +CRP3 X12 2 +/N06.2
2 +/N06.2
3 +/N06.3

B =E03 +CRP3 X12 11 4 =E03 +QF01 TB2 2 +/N06.2 B


=E03 +CRP3 12 5 =E03 +QF01 TB1 52 +/N06.2
=E03 +CRP3 13 6 =E03 +QF01 TB1 43 +/N06.3

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X110 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X111

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+MK-X12 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+MK-X20 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +QF01 -TB1 9 1 =E03 +CRP3 X20 1 +/G03.4
=E03 +QF01 -TB1 10 2 =E03 +CRP3 X20 4 +/G03.5
=E03 +QF01 TB1 23 3 =E03 +CRP3 X20 7 +/N02.3

B =E03 +QF01 TB1 24 4 =E03 +CRP3 X20 9 +/N02.7 B


=E03 +QF01 TB1 25 5 =E03 +CRP3 X20 10 +/N02.7
6 +/W01.6
7 +/W01.6
8 +/W01.6
9 +/W01.6
10 +/W01.6
11 +/W01.6
12 +/W01.7
13 +/W01.7
C 14 +/W01.7 C
15 +/W01.7

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X111 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X112

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+MK-X20 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+MK-X41 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +CT-PA +CT-PA-PA 1S1 1 =E03 +CRP3 X41 1 +/S03.2
=E03 +CT-PB +CT-PB-PB 1S1 2 =E03 +CRP3 X41 2 +/S03.2
=E03 +CT-PC +CT-PC-PC 1S1 3 =E03 +CRP3 X41 3 +/S03.2

B =E03 +CT-PC 1S5 4 =E03 +CRP3 X41 4 +/S03.3 B


=E03 +CT-PB +CT-PB-PB 1S5 5 +/S03.3
=E03 +CT-PA +CT-PA-PA 1S5 6 =E03 +MK PE +/S03.3

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X112 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X113

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+MK-X41 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+MK-X42 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +CT-PA 2S1 1 =E03 +CRP3 X42 1 +/S03.4
=E03 +CT-PB +CT-PB-PB 2S1 2 =E03 +CRP3 X42 2 +/S03.4
=E03 +CT-PC +CT-PC-PC 2S1 3 =E03 +CRP3 X42 3 +/S03.4

B =E03 +CT-PC 2S5 4 =E03 +CRP3 X42 4 +/S03.5 B


=E03 +CT-PB +CT-PB-PB 2S5 5 +/S03.5
=E03 +CT-PA +CT-PA-PA 2S5 6 =E03 +MK PE +/S03.5

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X113 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X114

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+MK-X42 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+MK-X44 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +CT-PA +CT-PA-PA 4S1 1 =E03 +CRP3 X44 1 +/T01.2
=E03 +CT-PB +CT-PB-PB 4S1 2 =E03 +CRP3 X44 2 +/T01.2
=E03 +CT-PC +CT-PC-PC 4S1 3 =E03 +CRP3 X44 3 +/T01.3

B =E03 +CT-PC 4S5 4 =E03 +CRP3 X44 4 +/T01.3 B


=E03 +CT-PB +CT-PB-PB 4S5 5 +/T01.3
=E03 +CT-PA +CT-PA-PA 4S5 6 =E03 +MK PE +/T01.3

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X114 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X115

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+MK-X44 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+MK-X45 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +CT PA 5S1 1 =E05 +CRP5 X453 1 +/S03.7
=E03 +CT PB 5S1 2 =E05 +CRP5 X453 2 +/S03.7
=E03 +CT PC 5S1 3 =E05 +CRP5 X453 3 +/S03.7

B =E03 +CT PC 5S5 4 =E05 +CRP5 X453 4 +/S03.7 B


=E03 +CT PB 5S5 5 +/S03.8
=E03 +CT PA 5S5 6 =E03 +MK PE +/S03.8

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X115 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE +VTB/X100

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+MK-X45 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+VTB-XAC A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +VTB -FQAC 1 6 =E03 +MK XAC 7 +/D02.7
6 +/D02.8
=E03 +VTB -FQAC 3 8 =E03 +MK XAC 10 +/D02.7

B 8 +/D02.8 B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X100 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X101

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+VTB-XAC PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+VTB-X8 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
1 =E03 +VTB FQAC 12 +/R05.4
=E03 +VTB -FQM2 21 8 =E03 +MK X3 27 +/P03.3
9 =E03 +VTB FQM2 24 +/P03.4

B =E03 +VTB -KMV1 9 10 +/P03.4 B


=E03 +MK -X3 35 11 =E03 +VTB KMV2 1 +/P03.5
=E03 +CRP3 -X8 3 12 =E03 +VTB KMV1 2 +/R05.3
=E03 +VTB KMV2 10 13 =E03 +CRP3 X8 43 +/R05.3
=E03 +VTB -FQAC 11 2 =E03 +CRP3 X8 44 +/R05.4
=E03 +VTB -FQM1 11 3 =E03 +CRP3 X8 45 +/R05.4
=E03 +VTB -FQM2 11 4 =E03 +CRP3 X8 46 +/R05.4
=E03 +VTB -FQAC 95 5 =E03 +CRP3 X8 61 +/R05.5

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X101 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X102

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+VTB-X8 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+VTB-X12 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +VTB -FQP 12 15 =E03 +CRP3 X12 3 +/N06.4
=E03 +CRP3 14 15 =E03 +VTB FQP 11 +/N06.4

B B

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X102 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X103

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+VTB-X12 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+VTB-X51 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +BVT-PA +BVT-PA-PA 1a 1 =E03 +VTB FQM1 1 +/S01.2
=E03 +BVT-PB +BVT-PB-PB 1a 2 =E03 +VTB FQM1 3 +/S01.3
=E03 +BVT-PC +BVT-PC-PC 1a 3 =E03 +VTB FQM1 5 +/S01.4

B =E03 +BVT-PA 1n 4 =E03 +VTB PE +/S01.2 B


=E03 +BVT-PB 1n 5 +/S01.3
=E03 +BVT-PC 1n 6 =E03 +VTB FQM1 7 +/S01.4
=E03 +VTB -FQM1 2 7 =E00 +MP1 X53 1 +/S01.3
=E03 +VTB -FQM1 4 8 =E00 +MP1 X53 2 +/S01.3
=E03 +VTB -FQM1 6 9 =E00 +MP1 X53 3 +/S01.3
=E03 +VTB -FQM1 8 10 =E00 +MP1 X53 4 +/S01.3

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X103 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X104

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+VTB-X51 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+VTB-X52 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +BVT-PA +BVT-PA-PA 2a 1 =E03 +VTB FQM2 1 +/S01.6
=E03 +BVT-PB +BVT-PB-PB 2a 2 =E03 +VTB FQM2 3 +/S01.7
=E03 +BVT-PC +BVT-PC-PC 2a 3 =E03 +VTB FQM2 5 +/S01.8

B =E03 +BVT-PA 2n 4 =E03 +VTB PE +/S01.6 B


=E03 +BVT-PB 2n 5 +/S01.7
=E03 +BVT-PC 2n 6 =E03 +VTB FQM2 7 +/S01.8
=E03 +VTB -FQM2 2 7 =E03 +CRP3 X51 1 +/S01.7
=E03 +VTB -FQM2 4 8 =E03 +CRP3 X51 3 +/S01.7
=E03 +VTB -FQM2 6 9 =E03 +CRP3 X51 5 +/S01.7
=E03 +VTB -FQM2 8 10 =E03 +CRP3 X51 7 +/S01.7

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X104 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE X105

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+VTB-X52 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A Terminal diagram =E03+VTB-X53 A

Connection

Connection

Connection

Connection
Terminal

Terminal
Jumper

Jumper
point

point

point

point
Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column Bay Panel Terminal/Equip. Bay Panel Equipment/Ter. Page/column
=E03 +LVT-PA +LVT-PA-PA 3a 1 =E03 +VTB FQP 1 +/S02.4
=E03 +LVT-PB +LVT-PB-PB 3a 2 =E03 +VTB FQP 3 +/S02.4
=E03 +LVT-PC +LVT-PC-PC 3a 3 =E03 +VTB FQP 5 +/S02.5

B =E03 +LVT-PA 3n 4 =E03 +VTB PE +/S02.4 B


=E03 +LVT-PB 3n 5 +/S02.5
=E03 +LVT-PC 3n 6 =E03 +VTB FQP 7 +/S02.5
=E03 +VTB -FQP 2 7 =E03 +CRP3 X53 2 +/S02.4
=E03 +VTB -FQP 4 8 =E03 +CRP3 X53 4 +/S02.4
=E03 +VTB -FQP 6 9 =E03 +CRP3 X53 6 +/S02.5
=E03 +VTB -FQP 8 10 =E03 +CRP3 X53 8 +/S02.5

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E03


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE X105 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE =E04+/A00

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E03-171 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN Terminal diagram =E03+VTB-X53 PECC2/TT-110KV/E03-171
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

B B

B 24/11/2020 2nd FOR APPROVED

A 12/10/2020 1st FOR APPROVED

REV. DATE DESCRIPTION

CUSTOMER

C C
POWER ENGINEERING CONSULTING J.S.C. 2

PROJECT

TAN THUAN OFFSHORE WIND POWER PLANT

D D

LOCATION

TAN THUAN OFFSHORE WIND POWER PLANT

DRAW. NAME STAMP

E =E04+CRP4: WIRING DIAGRAMS FOR 110KV TRANSMISSION LINE E04 BAY E


=E04+MK: MARSHALLING KIOSK FOR TRANSMISSION LINE E04 BAY
=E04+VTB: VT-BOX FOR TRANSMISSION LINE E04 BAY

DRAWING NO. PECC2/TT-110KV/E04-172

STANDARD: IEC PAGE: A00 TOTAL NO. OF PAGE: 86

DESIGNED NGUYEN VAN NHAT CONTRACTOR

CHECKED NGUYEN VAN CHUNG


F F
APPROVED NGUYEN DINH TUAN
ENERGY TECHNOLOGY
JOINT STOCK COMPANNY
DATE 24/11/2020 Rev.: B

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

PAGE DESCRIPTION REV. X PAGE DESCRIPTION REV. X

=E04/A00 WIRING DIAGRAMS FOR 110KV TRANSMISSION LINE BAY B =E04/N02 TRIPPING CIRCUIT 2 CB E04-QF01 B
A A
=E04/A01 TABLE OF CONTENTS : =E04/A00 - =E04/W01 B =E04/N03 TRIP-LOCKOUT1 CIRCUIT B
=E04/A01.a TABLE OF CONTENTS : =E04/Z01 - =E04+VTB/X105 B =E04/N04 TRIP-LOCKOUT2 CIRCUIT B
=E04/A02 DEVICE SYMBOL B =E04/N05 LOAD SHEDDING CIRCUIT B
=E04/A03 FUNCTION SYMBOL B =E04/N06 BINNARY INPUT F87L B
=E04/A04 SECONDARY CIRCUIT SYMBOL B =E04/N07 BINNARY INPUT F87L B
=E04/A05 LIST OF EQUIPMENTS: =E04+CRP4 C =E04/N08 BINNARY INPUT F21 B

B =E04/A06 LIST OF EQUIPMENTS: =E04+CRP4 C =E04/N09 BINNARY INPUT F85 B B


=E04/A07 LIST OF EQUIPMENTS: =E04+MK C =E04/N10 BINNARY INPUT OF F87B B
=E04/B01 CONTROL, PROTECTION & MEASUREMENT PRINCIPLE DIAGRAM B =E04/N11 SIGNAL SEND TO F87B B
=E04/B02 TRIPPING MATRIX B =E04/P01 INTERLOCKING FOR CB, DS, ES B
=E04/B03 LAYOUT DRAWING B =E04/P02 INTERLOCKING FOR CB, DS, ES B
=E04/B04 LAYOUT DRAWING MARSHALLING KIOSK =E04+MK B =E04/P03 INTERLOCKING FOR CB, DS, ES B
=E04/B05 OPERATION LOGIC DIAGRAM FOR DS E04-QL02 B =E04/P04 INTERLOCKING FOR CB, DS, ES B
C =E04/B06 OPERATION LOGIC DIAGRAM FOR DS E04-QL07 B =E04/Q01 INDICATOR CIRCUIT B C

=E04/B07 OPERATION LOGIC DIAGRAM FOR DS E04-QL09 B =E04/Q02 INDICATOR CIRCUIT B


=E04/B08 OPERATION LOGIC DIAGRAM FOR ES E04-QE75 B =E04/R01 BINNARY INPUT BCU B
=E04/B09 OPERATION LOGIC DIAGRAM FOR ES E04-QE25 B =E04/R02 BINNARY INPUT BCU B
=E04/B10 OPERATION LOGIC DIAGRAM FOR ES E04-QE76 B =E04/R03 BINNARY INPUT BCU B
=E04/B11 CLOSING LOGIC DIAGRAM FOR CB E04-QF01 B =E04/R04 BINNARY INPUT BCU B
=E04/B12 OPENING LOGIC DIAGRAM FOR CB E04-QF01 B =E04/R05 BINNARY INPUT BCU B
D D
=E04/D01 AC POWER SUPPLY FOR CONTROL PANEL B =E04/R06 BINNARY INPUT BCU B
=E04/D02 AC POWER SUPPLY FOR MARSHALLING KIOSK B =E04/R07 BINNARY INPUT BCU B
=E04/D03 AC POWER SUPPLY FOR CB, DS, ES B =E04/R08 SIGNAL SEND TO FR B
=E04/G01 DC POWER SUPPLY FOR CONTROL PANEL B =E04/R09 MODBUS RS485 CIRCUIT B
=E04/G02 DC POWER SUPPLY FOR CONTROL PANEL B =E04/S01 LINE VOLTAGE CIRCUIT B
=E04/G03 DC POWER SUPPLY FOR CONTROL PANEL B =E04/S02 LINE VOLTAGE CIRCUIT B

E =E04/G04 DC POWER SUPPLY FOR HV EQUIPMENT B =E04/S03 CURRENT CIRCUIT OF RELAY B E


=E04/M01 CONTROL CIRCUIT DS E04-QL02 B =E04/S04 VOLTAGE CIRCUIT OF RELAY B
=E04/M02 CONTROL CIRCUIT DS E04-QL07 B =E04/T01 VOLTAGE CIRCUIT OF MEASUREMENT B
=E04/M03 CONTROL CIRCUIT DS E04-QL09 B =E04/T02 VOLTAGE CIRCUIT OF MEASUREMENT B
=E04/M04 CLOSING CIRCUIT CB E04-QF01 B =E04/T03 VOLTAGE CIRCUIT OF MEASUREMENT B
=E04/N01 TRIPPING CIRCUIT 1 CB E04-QF01 B =E04/W01 SPARE CIRCUIT B
X: AUTOMATIC PAGE MODIFIED

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A01.a

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN TABLE OF CONTENTS : =E04/A00 - =E04/W01 PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

PAGE DESCRIPTION REV. X PAGE DESCRIPTION REV. X

=E04/Z01 REFERENCE F87L (P543) B =E04+CRP4/X113 Terminal diagram =E04+CRP4-X41 B


A A
=E04/Z02 REFERENCE F87L (P543) B =E04+CRP4/X114 Terminal diagram =E04+CRP4-X42 B
=E04/Z03 REFERENCE F21 (P445) B =E04+CRP4/X115 Terminal diagram =E04+CRP4-X44 B
=E04/Z04 REFERENCE F21 (P445) B =E04+CRP4/X116 Terminal diagram =E04+CRP4-X51 B
=E04/Z05 REFERENCE BCU C264 B =E04+CRP4/X117 Terminal diagram =E04+CRP4-X52 B
=E04/Z06 REFERENCE BCU C264 B =E04+CRP4/X118 Terminal diagram =E04+CRP4-X53 B
=E04/Z07 REFERENCE BCU C264 B =E04+CRP4/X119 Terminal diagram =E04+CRP4-X54 B

B =E04/Z09 REFERENCE CONTROL DEVICES B =E04+CRP4/X120 Terminal diagram =E04+CRP4-X91 B B


=E04/Z10 REFERENCE CURRENT AND VOLTAGE TESTBLOCK B =E04+CRP4/X121 Terminal diagram =E04+CRP4-X411 B
=E04/Z11 REFERENCE RELAY F74 B =E04+MK/X100 Terminal diagram =E04+MK-XAC B
=E04/Z12 REFERENCE RELAY TESTBLOCK B =E04+MK/X101 Terminal diagram =E04+MK-XAC1 B
=E04/Z13 CB REFERENCE (GL312F1/GE) B =E04+MK/X102 Terminal diagram =E04+MK-XDC B
=E04/Z14 CB REFERENCE (GL312F1/GE) B =E04+MK/X103 Terminal diagram =E04+MK-XDC1 B
=E04/Z15 CB REFERENCE (GL312F1/GE) B =E04+MK/X104 Terminal diagram =E04+MK-XDC2 B
C =E04/Z16 CB REFERENCE (GL312F1/GE) B =E04+MK/X105 Terminal diagram =E04+MK-X3 B C

=E04/Z17 DS REFERENCE B =E04+MK/X106 Terminal diagram =E04+MK-X7 B


=E04/Z18 DS REFERENCE B =E04+MK/X107 Terminal diagram =E04+MK-X8 B
=E04/Z19 DS REFERENCE B =E04+MK/X108 Terminal diagram =E04+MK-X10 B
=E04/Z20 ES REFERENCE B =E04+MK/X109 Terminal diagram =E04+MK-X11 B
=E04/Z21 ES REFERENCE B =E04+MK/X110 Terminal diagram =E04+MK-X12 B
=E04+CRP4/X100 Terminal diagram =E04+CRP4-XAC B =E04+MK/X111 Terminal diagram =E04+MK-X20 B
D D
=E04+CRP4/X101 Terminal diagram =E04+CRP4-XDC1 B =E04+MK/X112 Terminal diagram =E04+MK-X41 B
=E04+CRP4/X102 Terminal diagram =E04+CRP4-XDC2 B =E04+MK/X113 Terminal diagram =E04+MK-X42 B
=E04+CRP4/X103 Terminal diagram =E04+CRP4-XDC3 B =E04+MK/X114 Terminal diagram =E04+MK-X44 B
=E04+CRP4/X104 Terminal diagram =E04+CRP4-X3 B =E04+MK/X115 Terminal diagram =E04+MK-X45 B
=E04+CRP4/X105 Terminal diagram =E04+CRP4-X7 B =E04+VTB/X100 Terminal diagram =E04+VTB-XAC B
=E04+CRP4/X106 Terminal diagram =E04+CRP4-X8 B =E04+VTB/X101 Terminal diagram =E04+VTB-X8 B

E =E04+CRP4/X107 Terminal diagram =E04+CRP4-X9 B =E04+VTB/X102 Terminal diagram =E04+VTB-X12 B E


=E04+CRP4/X108 Terminal diagram =E04+CRP4-X10 B =E04+VTB/X103 Terminal diagram =E04+VTB-X51 B
=E04+CRP4/X109 Terminal diagram =E04+CRP4-X11 B =E04+VTB/X104 Terminal diagram =E04+VTB-X52 B
=E04+CRP4/X110 Terminal diagram =E04+CRP4-X12 B =E04+VTB/X105 Terminal diagram =E04+VTB-X53 B
=E04+CRP4/X111 Terminal diagram =E04+CRP4-X20 B
=E04+CRP4/X112 Terminal diagram =E04+CRP4-X21 B
X: AUTOMATIC PAGE MODIFIED

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A01.a F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN TABLE OF CONTENTS : =E04/Z01 - =E04+VTB/X105 PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION


A A
M
THREE WINDING TRANSFORMER 3 UNIT POTENTIAL TRANSFORMER A AMMETER MCCB CÓ ĐỘNG CƠ ĐIỀU KHIỂN

TWO WINDING TRANSFORMER 2 UNIT POTENTIAL TRANSFORMER V VOLTMETER MCCB, MCB

AUTO TRANSFORMER SURGE ARRESTOR W WATTMETER RESISTOR


B B

CURRENT TRANSFORMER WYE VAR VAR METER FUSE

REACTOR DELTA ‎cosφ POWER FACTOR METER BATTERY

CAPACITOR OPEN DELTA Hz FREQUENCY METER INVERTER


C C

REACTOR EARTHING Wh WATTHOUR METER DIODE

HIGH VOLTAGE CIRCUIT BREAKER INTERLOCKING VARh VAr METER

MEDIUM CIRCUIT BREAKER LATCHING DEVICE AMPE SWITCH


D D

DAO CẮM HỢP BỘ TRUNG ÁP M CONTROL MOTOR VOLT SWITCH

DISCONECTOR CONTROL KEY RELAY TEST BLOCK

E
EARTH SWITCH ~ ALTERNATIVE CURRENT VOLTAGE/CURRENT TEST BLOCK
E

LOAD DISCONECTOR DIRECT CURENT LAMP

CONTACTOR

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN DEVICE SYMBOL PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

KÝ HIỆU MÔ TẢ KÝ HIỆU MÔ TẢ

21/21N DISTANCE PROTECTION 86 TRIP-LOCKOUT RELAY


A A
25 SYNCHROCHECK 87B BUSBAR DIFFERENTIAL PROTECTION

26 THERMAL PROTECTION 87L LINE DIFFERENTIAL PROTECTION

27 UNDERVOLTAGE PROTECTION 87N RESTRICTED GROUND FAULT PROTECTION

33 POSITION BLOCK RELAY 87S STUB DIFFERENTIAL PROTECTION

49 THERMAL OVERLOAD PROTECTION 87T TRANSFORMER DIFFERENTIAL PROTECTION

50 INSTANTANEOUS OVERCURRENT PROTECTION 90 AUTOMATIC CONTROL VOLTAGE RELAY


B B
50BF CIRCUIT-BREAKER FAILURE PROTECTION 94 TRIPPING RELAY

50G INSTANTANEOUS GROUND OVERCURRENT PROTECTION 96 GAS RELAY

50N INSTANTANEOUS NEUTRAL OVERCURRENT PROTECTION FR FAULT RECORDER

51 TIME OVERCURRENT PROTECTION FL FAULT LOCATOR

51G TIME GROUND OVERCURRENT PROTECTION SOTF SWITCH ON TO FAULT

51N TIME NEUTRAL OVERCURRENT PROTECTION BCU BAY CONTROL UNIT


C C
5IUb UNBALANCE OVERCURRENT PROTECTION A CURRENT MEASUREMENT FUNCTION

51/27 VOLTAGE CONTROLLED OVERCURRENT V VOLTAGE MEASUREMENT FUNCTION

59 OVERVOLTAGE PROTECTION f FREQUENCY MEASUREMENT FUNCTION

59N ZEZO-SEQUENCE OVERVOLTAGE PROTECTION ‎cosφ POWER FACTOR MEASUREMENT FUNCTION

63 PRESSURE RELAY W EFFECTIVE POWER MEASUREMENT FUNCTION

D 64 GROUND DETECTOR RELAY VAR REACTIVE POWER MEASUREMENT FUNCTION D

67 DIRECTIONAL OVERCURRENT RELAY Wh ACTIVE ENERGY MEASUREMENT FUNCTION

67N DIRECTIONAL OVERCURRENT PROTECTION FOR GROUND FAULTS VARh REACTIVE ENERGY MEASUREMENT FUNCTION

67NS DIRECTIONAL SENSITIVE GROUND-FAULT DETECTION

68 POWER-SWING BLOCKING

71 LEVEL OIL RELAY


E E
74 TRIP CIRCUIT SUPERVISION

79 AUTO RECLOSING

81 FREQUENCY PROTECTION

85 COMBINATION OF PROTECTION

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN FUNCTION SYMBOL PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

KÝ HIỆU MÔ TẢ KÝ HIỆU MÔ TẢ KÝ HIỆU MÔ TẢ KÝ HIỆU MÔ TẢ


A A

NORMALY OPEN CONTACT (NO) RELAY TEST BLOCK CONTACT LAMP EARTHING BAR

NORMALY CLOSE CONTACT (NC) CURRENT/VOLTAGE TEST BLOCK CONTACT LIGHTS BELL

CHANGE OVER CONTACT (CO) SOLENOID / COIL SOCKET HOOTER


B B

CONTACTOR NORMALY OPEN CONTACT ON DELAY COIL SURGE ARRESTOR MEARSUREMENT DEVICE

CONTACTOR NORMALY CLOSE CONTACT LATCHED COIL FUSE V VOLMETTER

NORMALLY OPEN ON BUTTON BINARY INPUT RELAY HEATER A AMMETTER


C C

NORMALLY CLOSED OFF BUTTON ANALOG INPUT RELAY RESISTOR

PUSH BUTTON (DETENT) POWER SUPPLY DIODE

SELECTOR SWITCH CONTACT CONVERTER CAPACITOR


D D

~
LIMIT SWITCH CONTACT RECTIFIER REACTOR/CURRENT-VOLTAGE INPUT RELAY

TEMPERATURE CONTROLER CONTACT INVERTER TERMINAL


~

MAKE CONTACT DELAYED WHEN


COUNTER DRAWOUT TERMINAL
E CLOSING E

MAKE CONTACT DELAYED WHEN


MCCB/MCB DIODE TERMINAL
OPENING I>

FUSE TERMINAL

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A05

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN SECONDARY CIRCUIT SYMBOL PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

NO. SYMBOL DESCRIPTION MANUFACTORY CODE QTY. UNIT NOTE CUBICLE

1 F87L LINE DIFFERENTIAL PROTECTION RELAY SCHNEIDER P54331Q77M0K28M 01 Pcs 16BI + 24BO + 2LC IEC61850 =E04+CRP4
A A
2 F67 DISTANCE PROTECTION RELAY SCHNEIDER P44531QE7M0K28L 01 Pcs 8BI + 8BO + 2LC IEC61850 =E04+CRP4

3 BCU BAY CONTROL UNIT SCHNEIDER C264U11M6A10013302100031111D10 01 Pcs 58BI + 26BO + 2ST IEC61850 =E04+CRP4

REG-DA B0 I0 H0 F1 M1 S0 T0 K1
4 F90 AUTO VOLTAGE REGULATOR RELAY A-EBERLE 01 Pcs 16BI+12BO+1AI+1xRS232+ 1xLC IEC61850 =E04+CRP4
E00 D0 C00 XW93.1 G2 A2

5 PMF MULTIFUNCTION METTER CEWE ELITE 448 01 Pcs =E04+CRP4

6 XF... RELAY TESTBLOCK FUJI TSB-14-11111111111111-V 03 Pcs =E04+CRP4

7 F86... TRIP AND LOCKOUT RELAY ARTECHE BJ-8RP 02 Pcs 8CO =E04+CRP4
B B
8 F74... TRIPPING SUPERVISORY RELAY ARTECHE VDF-10 02 Pcs 2CO =E04+CRP4

9 XTC... CURRENT TESTBLOCK FUJI KTT-AW4 B M 03 Pcs =E04+CRP4

10 XTV... VOLTAGE TESTBLOCK FUJI KTT-VW4 B M 04 Pcs =E04+CRP4

11 SQF01 CONTROL AND DISCREPANCY SWITCH FOR CB FUJI BHL-3B3111-220L1-W-Y-B-L54-Y07E 01 Pcs =E04+CRP4

12 SQL01 CONTROL AND DISCREPANCY SWITCH FOR DS FUJI BHL-3B3111-220L1-W-Y-B-L54-Z07E 01


02 Pcs =E04+CRP4

13 SQE... SEMAPHORE FOR ES FUJI SPSR-30S-DC220-BB 03 Pcs =E04+CRP4


C C
14 S.B/M "BCU/MIMIC" SELECTOR SWITCH SALZER SA25-FA 6015-61009-M1-I-F-3-BS-0 01 Pcs =E04+CRP4

15 S.25 "SYN./BYPASS" SELECTOR SWITCH SALZER SA25-FA 6037-61638-M1-I-F-3-BS-0 01 Pcs =E04+CRP4

16 S.79 "ON/OFF" SELECTOR SWITCH FOR 79 SALZER SA25-FA 6037-61638-M1-I-F-3-BS-0 01 Pcs =E04+CRP4

17 S.87L "ON/OFF" SELECTOR SWITCH FOR 87L SALZER SA25-FA 6037-61638-M1-I-F-3-BS-0 01 Pcs =E04+CRP4

18 S.81 LOAD SHEDDING SLECTOR SWITCH SALZER SA25-FA 6029-61071-M1-I-F-3-BS-0 02 Pcs =E04+CRP4

D 19 P.LOCAL LAMP FOR CB CONTROL AT LOCAL IDEC YW1P 01 Pcs =E04+CRP4 D

20 S.R/L RESET LOCKOUT BUTTON IDEC YW1B 01 Pcs =E04+CRP4

21 K.... AUXILARY RELAY IDEC RU4S 01 Lot =E04+CRP4

22 FQAC MCB AC FOR LIGHTING AND HEATING LEGRAND DX3 01 Pcs 2P-16A-6kA =E04+CRP4

23 FQ... MCB DC LEGRAND DX3 DC 01 Lot 2P-10A-16kA =E04+CRP4

24 KQP CONTACTOR ABB ESB25 01 Pcs =E04+CRP4

E 25 XAC, XDC POWER TERMINALS DEGSON PC6 01 Lot =E04+CRP4


E

26 X4... CURRENT TERMINALS DEGSON PCTK 01 Lot =E04+CRP4

27 X... SIGNAL TERMINALS DEGSON PC4 01 Lot =E04+CRP4

28 B0 THERMOSTAT CYMAX =E04+CRP4

29 B1 DOOR LIMIT SWITCH CHINA =E04+CRP4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A05 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A06

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LIST OF EQUIPMENTS: =E04+CRP4 PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

NO. SYMBOL DESCRIPTION MANUFACTORY CODE QTY. UNIT NOTE CUBICLE

30 E0 HEATING RESISTER CYMAX =E04+CRP4


A A
31 E1 LIGHTING LAMP CHINA =E04+CRP4

32

33

34

35

36
B B
37

38

39

40

C C

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A06 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE A07

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LIST OF EQUIPMENTS: =E04+CRP4 PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

NO. SYMBOL DESCRIPTION MANUFACTORY CODE QTY. UNIT NOTE CUBICLE

1 FQAC, FQAC1 MCB AC LEGRAND DX3 02 Pcs 2P-16A-6kA =E04+MK


A A
2 FQCB, FQDS MCB DC LEGRAND DX3 DC 02 Pcs 2P-16A-16kA =E04+MK

3 KQP CONTACTOR ABB ESB25 01 Pcs =E04+MK

4 XAC, XDC POWER TERMINALS DEGSON PC6 01 Lot =E04+MK

5 X4... CURRENT TERMINALS DEGSON PCTK 01 Lot =E04+MK

6 X5... VOLTAGE TERMINALS DEGSON PC6 01 Lot =E04+MK

7 X... SIGNAL TERMINALS DEGSON PC4 01 Lot =E04+MK


B B
8 B0 THERMOSTAT CYMAX =E04+MK

9 B1 DOOR LIMIT SWITCH CHINA =E04+MK

10 E0 HEATING RESISTER CYMAX =E04+MK

11 E1 LIGHTING LAMP CHINA =E04+MK

12

13
C C
14

15

16

17

18

D 19 D

20

21

22

23

24

E 25
E

26

27

28

29

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE A07 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LIST OF EQUIPMENTS: =E04+MK PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

220KV DONG HAI


A A

LVT1
110 0.11 0.11
kV
3 3 3

CL: 3P

B CL: 0.5 +CRP4 B


QE76 XTC1 PMF (ELITE 448) XTV1

M QL07 CL: 0.5


TO METTERING PANEL
U I P Q
f pF ...
QE75

XTC2 BCU (C264) XTV2


P2
25 FR
CL: 5P20
TO F87B
XTV3
CT CL: 0.5 BVT C11 CL:0.5
400-800-1200 FROM =E03+WR PANEL
C C
/1/1/1/1A CL: 0.5
TO METTERING PANEL
F21 (P445)
CL: 5P20
XF67 67/67N SOTF 27/59 85 XF67
CL: 5P20 50/51 50/51N FR 21/21N

P1
XF87L
F87L (P543)
XF87L
E05 F87L 68 27/59 85
XF87L
D QF01 21/21N 67/67N 79/25 D
BVT C11 CL:3P
50/51 50/51N FL/FR FROM =E03+WR PANEL

F861 (BJ-8RP) F741 (VDF-10)


QE25
M QL02 F862 (BJ-8RP) F742 (VDF-10)

E E

C11
VOLTAGE CIRCUIT

CURRENT CIRCUIT

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172
CONTROL, PROTECTION & MEASUREMENT PRINCIPLE
DATE 24/11/2020
APPROVED NGUYEN DINH TUAN PECC2/TT-110KV/E04-172
DIAGRAM
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

CIRCUIT BREAKER =E04+CRP4 =E05+CRP5 =E02+CRP2


DEVICE OPPOSITE
A E04-QF01 -F87L -F21 -F861 -F862 -F87B -F861 -F862 -F861 -F862 A
PANEL

BLOCK START LOCK LOCK START LOCK LOCK LOCK LOCK


SYMBOL TYPE FUNCTION TC1 TC2 CC PTT PTT OUT PTT DTT
CC 79 OUT OUT 50BF OUT OUT OUT

87L, Z1(21,21N), 67N X X X* X X0

-F87L P543 Z2, Z3(21/21N) 67, 50/51,


X X X X X
SOTF, 79 FINAL

B 79/25 X B

67N, 21/21N X X X X X0

-F21 P445
67, 50/51,50/51N (I>>) X X X X X
=E05+CRP4

-F741 VDF-10 74 TCS X

-F742 VDF-10 74 TCS X


C C
-F861 BJ-8RP 86 X X X X

-F862 BJ-8RP 86 X X X X

50BF BAY E04 (STAGE2) X X X X

50BF BAY E04 (STAGE1) X X X X X*

D D
50BF BAY E05(STAGE2) X X X X X0
=E05+CRP5 -F87B P746
50BF BAY E03(STAGE2) X X X X

87B X X X X X* X X X X

-F271 P141 27/59 X X

E PTT Z1 (21/21N), 67N X0 X1 E


OPPOSITE
DTT(50BF) X0 X0

X0: COMMUNICATION THROUGH OPTICAL CABLE


X*: AUTO START
X1: COMMUNICATION THROUGH TELEPROTECTION
NOTE: TCS: TRIPPING COIL SUPPERVISOR
PTT: START PROTECTION
DTT: SENT TRIP
POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04
DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN TRIPPING MATRIX PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

FRONT VIEW SIDE VIEW REAR VIEW


A A
ENTEC =E04+CRP4
EQUIPMENT
TO 110kV DAM DOI
SW
TAG NAME DESCRIPTION
F87L =E04+WR
MiCOM

ALARM
P 143

ALARM
BCU BAY CONTROL UNIT
ALARM ALARM

ALARM ALARM

c ALARM

F87L LINE DIFFERENTIAL PROTECTION RELAY


ALARM

c LEAR ALARM
READ
ALARM
ENTER
ALARM

ALARM
ALSTOM

F21 DISTANCE PROTECTION RELAY


F21
MiCOM P P142

ALARM

ALARM
ALARM

ALARM
F741, F742 TRIPPING CIRCUIR SUPERVISION RELAY
ALARM ALARM

ALARM
c ALARM

c LEAR ALARM

F861, F862 RƠLE TRIP-LOCKOUT


READ
ALARM
ENTER
ALARM

ALARM
ALSTOM

BCU PMF MULTIFUNCTION METER

SQF01 DISCREPANCY CONTROL SWITCH FOR CB


B B
ALARM
c
ALARM

ALARM

ALARM

ALARM

ALARM

ALARM

ALARM
o I L/R
SQL02; SQL07; SQE25; SQE75; SQE76 DISCREPANCY CONTROL SWITCH FOR DS; ES

S.B/M "MIMIC/BCU" SELECTOR SWITCH


S.25 " SYN./BYPASS" SELECTOR SWITCH

S.79 "ON/OFF" SELECTOR SWITCH FOR AUTO RECLOSE


2200

S.RE RESET 86 PUSH BUTTON


S.LT LAMP TEST PUSH BUTTON
-SQL02
S.RE S.LT

S.B/M -SQE25 P.LC LAMP INDICATOR FOR CB CONTROL AT LOCAL


-SQF01
S.25 XF... RELAY TESTBLOCK
P.LC

S.79 -SQL07 XC.., XV.. CURRENT TESTBLOCK, VOLTAGE TESTBLOCK


-SQE75
S.87L
C -SQE76
-SQL09
C

F861 F862 F741 F742

XTV.MF
XF87L
XF21

XTC.BC XTC.MF XTV1.BC XTV2.BC

100 800 750 800


D 800 D

TOP VIEW BOTTOM VIEW BASE NAME PLATE (SCALE 1:5)


4x∅14
100
C =E04+CRP4

45
750
800
200
800

800
750

E C (Scale 1:5) REMARK: E


IP DEGREE: IP41
Ø14 APPLICATION STANDARD: IEC60529
25 MATERIAL: STEEL
STEEL THICKNESS: 2mm
4x∅8 PAINT COLOR: RAL7032
800 550 DOOR APPLY AREA: REAR
OPEN DOOR: 180°

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LAYOUT DRAWING PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

864 570 REMOVE FRONT DOOR REMOVE BACK DOOR


A A

1500

B B

C C
450 800
800
506

A-A
TOP VIEW
D D
450
75 300
470

4x∅14

25 750
760 800
E LEGEND: E
- PROTECTION CLASS: IP55
- STANDARD: IEC60529
- THICKNESS: 2mm
-MATERIAL:SUS 302
- OPEN FROM FRONT DOOR
- ALL DIMENSIONS ARE IN MILLIMETER

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B05

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LAYOUT DRAWING MARSHALLING KIOSK =E04+MK PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SCADA LEVEL PANEL LEVEL EQUIPMENT LEVEL


A A
OPEN/CLOSE COMMAND DS E04-QL02 FROM SCADA

BCU "LOCAL/REMOTE" ON "LOCAL"

&
OPEN/CLOSE COMMAND DS E04-QL02 FROM BCU
&
HMI "LOCAL/REMOTE" ON "REMOTE"
≥1
≥1 &
HMI "LOCAL/REMOTE" ON "LOCAL"
&
B BCU "LOCAL/REMOTE" ON "REMOTE" B
&
OPEN/CLOSE COMMAND DS E04-QL02 FROM HMI
SOFT INTERLOCKING *
HMI LEVEL
BCU
11O KV DAM DOI DS "REM./LOC./MAN." SWITCH ON "REMOTE"

QL09 MIMIC
M

C C
&
MIMIC "BCU/MIMIC" SWITCH ON "BCU"

QE76
MIMIC "BCU/MIMIC" SWITCH ON "MIMIC" &
M QL07
QE75 & ≥1
OPEN/CLOSE COMMAND DS E04-QL02 FROM CONTROL SWITCH
&
D D
OPEN/CLOSE
CT ≥1 DS E04-QL02
CB E04-QF01 OPEN

ES E04-QE25 FULLY OPEN


E04
ES E04-QE75 FULLY OPEN
&
* SOFT INTERLOCKING
CB E04-QF01 OPEN ES E05-QE24 FULLY OPEN
QF01
E E
ES E04-QE25 FULLY OPEN
&
QE25 OPEN/CLOSE COMMAND AT LOCAL
ES E04-QE75 FULLY OPEN &
M QL02
DS "REM./LOC./MAN." SWITCH ON "LOCAL" &
ES E05-QE24 FULLY OPEN OPEN/CLOSE BY HANDLE ≥1
C12
DS "REM./LOC./MAN." SWITCH ON "MANUAL" &

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B05 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B06

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN OPERATION LOGIC DIAGRAM FOR DS E04-QL02 PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SCADA LEVEL PANEL LEVEL EQUIPMENT LEVEL


A A
OPEN/CLOSE COMMAND DS E04-QL07 FROM SCADA

BCU "LOCAL/REMOTE" ON "LOCAL"

&
OPEN/CLOSE COMMAND DS E04-QL07 FROM BCU
&
HMI "LOCAL/REMOTE" ON "REMOTE"
≥1
≥1 &
HMI "LOCAL/REMOTE" ON "LOCAL"
&
B BCU "LOCAL/REMOTE" ON "REMOTE" B
&
OPEN/CLOSE COMMAND DS E04-QL07 FROM HMI
SOFT INTERLOCKING *
HMI LEVEL
BCU
11O KV DAM DOI DS "REM./LOC./MAN." SWITCH ON "REMOTE"

QL09 MIMIC
M

C C
&
MIMIC "BCU/MIMIC" SWITCH ON "BCU"

QE76
MIMIC "BCU/MIMIC" SWITCH ON "MIMIC" &
M QL07
QE75 & ≥1
OPEN/CLOSE COMMAND DS E04-QL07 FROM CONTROL SWITCH
&
D D
OPEN/CLOSE
CT ≥1 DS E04-QL07
CB E04-QF01 OPEN

ES E04-QE25 FULLY OPEN


E04
ES E04-QE75 FULLY OPEN
&
* SOFT INTERLOCKING
CB E04-QF01 OPEN ES E04-QE76 FULLY OPEN
QF01
E E
ES E04-QE25 FULLY OPEN
&
QE25 OPEN/CLOSE COMMAND AT LOCAL
ES E04-QE75 FULLY OPEN &
M QL02
DS "REM./LOC./MAN." SWITCH ON "LOCAL" &
ES E04-QE76 FULLY OPEN OPEN/CLOSE BY HANDLE ≥1
C12
DS "REM./LOC./MAN." SWITCH ON "MANUAL" &

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B06 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B07

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN OPERATION LOGIC DIAGRAM FOR DS E04-QL07 PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SCADA LEVEL PANEL LEVEL EQUIPMENT LEVEL


A A
OPEN/CLOSE COMMAND DS E04-QL09 FROM SCADA

BCU "LOCAL/REMOTE" ON "LOCAL"

&
OPEN/CLOSE COMMAND DS E04-QL09 FROM BCU
&
HMI "LOCAL/REMOTE" ON "REMOTE"
≥1
≥1 &
HMI "LOCAL/REMOTE" ON "LOCAL"
&
B BCU "LOCAL/REMOTE" ON "REMOTE" B
&
OPEN/CLOSE COMMAND DS E04-QL09 FROM HMI
SOFT INTERLOCKING *
HMI LEVEL
BCU
11O KV DAM DOI ES "REM./LOC./MAN." SWITCH ON "REMOTE"

QL09 MIMIC
M

C C
&
MIMIC "BCU/MIMIC" SWITCH ON "BCU"

QE76
MIMIC "BCU/MIMIC" SWITCH ON "MIMIC" &
M QL07
QE75 & ≥1
OPEN/CLOSE COMMAND DS E04-QL09 FROM CONTROL SWITCH
&
D D
OPEN/CLOSE
CT ES E04-QE76 FULLY OPEN ≥1 DS E04-QL09

* SOFT INTERLOCKING
ES E04-QE76 FULLY OPEN
E04
ES E04-QE76 FULLY OPEN &
CB E04-QF01 FULLY OPEN
ES E04-QE76 FULLY OPEN
QF01 ≥1
CB E04-QF01 FULLY OPEN
E & E
CB E04-QF01 FULLY OPEN

QE25 OPEN/CLOSE COMMAND AT LOCAL


≥1 &
M QL02 CB E04-QF01 FULLY OPEN
ES "REM./LOC./MAN." SWITCH ON "LOCAL" &
OPEN/CLOSE BY HANDLE ≥1
C12
ES"REM./LOC./MAN." SWITCH ON "MANUAL" &

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B07 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B08

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN OPERATION LOGIC DIAGRAM FOR DS E04-QL09 PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

EQUIPMENT LEVEL
A A

B B

11O KV DAM DOI

QL09
M

DS E04-QL07 FULLY OPEN


C C
OPEN/CLOSE
DS E04-QL02 FULLY OPEN
≥1 ES E04-QE75

QE76
M QL07
QE75

D D
CT

E04

QF01
E E

QE25
M QL02

C12

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B08 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B09

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN OPERATION LOGIC DIAGRAM FOR ES E04-QE75 PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

EQUIPMENT LEVEL
A A

B B

11O KV DAM DOI

QL09
M

DS E04-QL07 FULLY OPEN


C C
OPEN/CLOSE
DS E04-QL02 FULLY OPEN
≥1 ES E04-QE25

QE76
M QL07
QE75

D D
CT

E04

QF01
E E

QE25
M QL02

C12

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B09 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B10

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN OPERATION LOGIC DIAGRAM FOR ES E04-QE25 PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

EQUIPMENT LEVEL
A A

B B

11O KV DAM DOI


DS E04-QL07 FULLY OPEN

QL09
M

MCB LVT ON
C C
OPEN/CLOSE
NO VOLTAGE IN LINE
≥1 ES E04-QE76

QE76 DS E04-QL09 FULLY OPEN


M QL07
QE75

D D
CT

E04

QF01
E E

QE25
M QL02

C12

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B10 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B11

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN OPERATION LOGIC DIAGRAM FOR ES E04-QE76 PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SCADA LEVEL PANEL LEVEL EQUIPMENT LEVEL


A A
CLOSE COMMAND CB E04-QF01 FROM SCADA
SF6 LOCKOUT
BCU "LOCAL/REMOTE" ON "LOCAL"

& SPRING CHARGED


CLOSE COMMAND CB E04-QF01 FORM BCU
&
HMI "LOCAL/REMOTE" ON "REMOTE"
≥1 INTERLOCKING INSIDE CB IS OK

≥1 &
HMI "LOCAL/REMOTE" ON "LOCAL"
& CB "LOCAL/REMOTE" SWITCH ON "LOCAL"
B BCU "LOCAL/REMOTE" ON "REMOTE" B
&
CLOSE COMMAND CB E04-QF01 FROM HMI CLOSE COMMAND FROM EQUIP.
SOFT INTERLOCKING (*)
DS E04-QL02 FULLY OPEN
&
HMI LEVEL
BCU
11O KV DAM DOI DS E04-QL07 FULLY OPEN
MIMIC
BCU "BCU/MIMIC" ON "BCU"
QL09
SYNCHRO IS OK &
M

C "SYN./BYPASS" SELECT SWITCH ON "SYN." & C


≥1 &
"SYN./BYPASS" SELECT SWITCH ON "BYPASS"
CLOSE
& CB E04-QF01
QE76 CB "LOCAL/REMOTE" SWITCH ON "REMOTE"
TRIPPING CIRCUIT IS NOT OK
M QL07
QE75 RELAY LOCKOUT OPERATED &
≥1
BCU/MIMIC ON "MIMIC"
D D
CT
CLOSE COMMAND CB E04-QF01 FROM CONTROL SWITCH

E04 &
SYNCHRO IS OK &
"SYN./BYPASS" SELECT SWITCH ON "SYN." &
≥1
"SYN./BYPASS" SELECT SWITCH ON "BYPASS" DS E04-QL02 CLOSE

QF01 (*)
AUTO RECLOSER OPERATED
E ≥1 DS E04-QL07 CLOSE E

"ON/OFF" 79 SWITCH ON "ON"


QE25
M QL02 &
AUTO RECLOSER IS OK

C12 SYNCHRO IS OK

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B11 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE B12

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CLOSING LOGIC DIAGRAM FOR CB E04-QF01 PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

PANEL LEVEL EQUIPMENT LEVEL


A
SCADA LEVEL A

OPEN COMMAND E04-QF01 FROM SCADA

& &
HMI "LOCAL/REMOTE" ON "REMOTE" BCU "LOCAL/REMOTE" ON "REMOTE" SF6 LOCKOUT

≥1
HMI LEVEL ≥1
B OPEN COMMAND E04-QF01 FROM BCU B
OPEN COMMAND E04-QF01 FROM HMI CB "LOCAL/REMOTE" SWITCH ON "LOCAL"
&
& BCU "LOCAL/REMOTE" ON "LOCAL" &
HMI "LOCAL/REMOTE" ON "LOCAL" OPENING COMMAND FROM EQUIP.

BCU
11O KV DAM DOI
C OPEN CB QF01 C

QL09 & & TRIP CIRCUIT 1


BCU/MIMIC ON "BCU" CB "LOCAL/REMOTE" SWITCH ON "REMOTE"
M

& ≥1
≥1
QE76 BCU/MIMIC ON "MIMIC"
M QL07
QE75 &
OPENING COMMAND FROM CONTROL SWITCH
D D

CT PROTECTION RELAY OPERATED

RELAY F861 OPERATED


E04
RELAY F862 OPERATED

E QF01 E
PROTECTION RELAY OPERATED
≥1
RELAY F861 OPERATED OPEN CB QF01
QE25 & TRIP CIRCUIT 2
M QL02 RELAY F862 OPERATED
SF6 LOCKOUT

C12 MIMIC
POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04
DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE B12 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE D01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN OPENING LOGIC DIAGRAM FOR CB E04-QF01 PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E03+CRP3 +CRP4 =E05+CRP5

POWER SUPPLY
A HEATING & LIGHTING A

-W249
ACL1 1 -XAC 1 -XAC 2 ACL1
=E03/D01.7/ / =E05/D01.1

ACL2 2 -XAC 3 -XAC 4 ACL2


=E03/D01.7/ / =E05/D01.1

ACL3 3 -XAC 5 -XAC 6 ACL3


=E03/D01.7/ / =E05/D01.1

ACN 4 -XAC 7 -XAC 8 ACN


=E03/D01.7/ / =E05/D01.1

B B
1 3 12 14 96 98

-FQAC 11 95
2P-16A I> I>

/R06.5

/R06.7
2 4

LAMP HEATER SOCKET


C C

1 1
-B1 -B0
6A 2 0÷90°C 2

D D

1 1
1 1

-E0 -E1 -E2 -XSK


8W 60W 2 60W 2 16A
2 2
E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE D01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE D02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN AC POWER SUPPLY FOR CONTROL PANEL PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E05+MK +MK =E02+MK

POWER SUPPLY AC POWER SUPPLY


HEATING & LIGHTING HV EQUIPMENT
A -W269 A
L1 1 -XAC 1 -XAC 2 L1
=E05/D02.6/ / =E02/D02.1

L2 2 -XAC 3 -XAC 4 L2
=E05/D02.6/ / =E02/D02.1

L3 3 -XAC 5 -XAC 6 L3
=E05/D02.6/ / =E02/D02.1

N 4 -XAC 8 -XAC 9 N
=E05/D02.6/ / =E02/D02.1

B B

+VTB POWER SUPPLY


HEATING & LIGHTING

1 3 12 14 96 98 1 3 12 14 96 98 -W270
-XAC 7 1 -XAC 6 -XAC 6
-FQAC1 11 95 -FQAC2 11 95
-XAC 10 2 -XAC 8 -XAC 8
2P-16A I> I> 2P-16A I> I>

/R04.6

/R05.1

/R04.6

/R05.2
2 4 2 4
C C

.AC.L 1 3 12 14 96 98
/ D03.1

.AC.N
/ D03.1 -FQAC 11 95
2P-16A I> I>

/R05.4

/R05.5
2 4

LAMP HEAT SOCKET LAMP HEAT

D D

1
1 1 -B0 1 1
-B1 -B2 0÷90°C 2 -B1 -B0
6A 2 6A 2 6A 2 0÷90°C 2
1

-XSK
16A

1 1 2 1
E 1 1 1 E
-E1 -E2 -E0 -E3 -E1 -E3
8W 8W 60W 2 60W 2 8W 60W 2
2 2 2

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE D02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE D03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN AC POWER SUPPLY FOR MARSHALLING KIOSK PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+MK

A A

AC POWER SUPPLY AC POWER SUPPLY AC POWER SUPPLY AC POWER SUPPLY AC POWER SUPPLY AC POWER SUPPLY AC POWER SUPPLY
CB E04-QF01 DS E04-QL02 ES E04-QE25 DS E04-QL07 ES E04-QE75 ES E04-QE76 DS E04-QL09

.AC.L
D02.5

220 VAC
B .AC.N B
D02.5

-XAC1 1 5 2 6 3 7 4 8

-W271 1 2 -W272 1 2 -W273 1 2 -W274 1 2 -W275 1 2 -W276 1 2 -W277 2 1

+QF01 +QL02 +QE25 +QL07 +QE75 +QE76 +QL09


C C

TB1 1 2 -X1 20 21 -XT1 20 21 -X1 20 21 -XT1 20 21 -XT1 20 21 -X1 20 21


1

3
F1 F1 F1 F1 F1 F1 F1
2

4
D D

IL H IL H H IL H H H IL H
/Z14.6 /Z17.7 /Z20.6 /Z17.7 /Z20.6 /Z20.6 /Z17.7

E LAMP HEAT LAMP HEAT HEAT LAMP HEAT HEAT HEAT LAMP HEAT
E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE D03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE G01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN AC POWER SUPPLY FOR CB, DS, ES PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=N00+DC +CRP4 =E05+CRP5

DC2 DC1 POWER 1 SUPPLY POWER 2 SUPPLY


A -W250
POWER SUPPLY POWER SUPPLY FOR SWITCH FOR SWITCH A
=E03/G01.7
DC1+ 1 -XDC1 1 -XDC1 2 DC1+
/ =E05/G01.1

=E03/G01.7
DC1- 2 -XDC1 3 -XDC1 4 DC1-
/ =E05/G01.1

-W251

=E03/G01.7
DC2+ 1 -XDC2 1 -XDC2 2 DC2+
/ =E05/G01.1

=E03/G01.7
DC2- 2 -XDC2 3 -XDC2 4 DC2-
/ =E05/G01.1

B B

1 3 1 3 1 3 1 3
12 14 96 98 12 14 96 98 12 14 96 98 12 14 96 98

-FQDC2 11 95 -FQDC1 11 95 -FQSW1 11 95 -FQSW2 11 95


2P-10A I> I> 2P-10A I> I> 2P-10A I> I> 2P-10A I> I>

/R06.6

/R06.7

/R06.6

/R06.7

/N11.7

/N11.8

/N11.7

/N11.8
2 4 2 4 2 4 2 4

1 2 /G01.3
1 7 8 /G01.4
C C
-KQP1 R3 R4 /G01.2
220VDC R5 R6 /G01.2
2

R3 R5 1 7
-KQP1
/G01.4 R4 R6 2 8

L+ L- L+ L-

DC- -SW
D / G02.1 -PS1 -PS2 D
DC+
/ G02.1

-PE

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE G01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE G02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN DC POWER SUPPLY FOR CONTROL PANEL PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP4

A POWER SUPPLY POWER SUPPLY POWER SUPPLY POWER SUPPLY A


RELAY F87l BCU INDICATOR FOR METTERING

DC+ DC+
G01.4 /G03.1

DC- DC-
G01.4 /G03.1

-XDC3 1 9 2 10 3 11 4 12

B 1 3
12 14 96 98
1 3
12 14 96 98
1 3
12 14 96 98
1 3
12 14 96 98 B

-FQ87L 11 95 -FQBCU 11 95 -FQSI 11 95 -FQMF 11 95


2P-10A I> I> 2P-10A I> I> 2P-10A I> I> 2P-10A I> I>
/R06.6

/R06.7

/N08.5

/N08.6

/R06.6

/R06.7

/R06.6

/R06.7
2 4 2 4 2 4 2 4

C C

SI+
/Q01.1

SI-
/Q01.1

-X7 1 4

D 87L+ BCU+ D
/ N06.1 /R01.1

87L- BCU-
/ N06.1 /R01.1

X12 1 8 X8 1 7

2 1 23 24 P N
F87L J BCU A PMF
/Z01.3 /Z05.2 /Z10.6
-PS -PS -PS
E P643 C264 ELITE 448
E

-PE

-PE

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE G02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE G03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN DC POWER SUPPLY FOR CONTROL PANEL PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP4

A A
POWER SUPPLY POWER SUPPLY POWER SUPPLY POWER SUPPLY
RELAY F21 TC2 TC1 CLOSING CIRCUIT

G02.8
DC+

G02.8
DC-

-XDC3 5 13 6 14 7 15 8 16

B B

1 3 1 3 1 3 1 3
12 14 96 98 12 14 96 98 12 14 96 98 12 14 96 98

-FQ21 11 95 -FQTC2 11 95 -FQTC1 11 95 -FQCB 11 95


2P-10A I> I> 2P-10A I> I> 2P-10A I> I> 2P-10A I> I>

/R06.6

/R06.7

/R06.6

/R06.7

/R06.6

/R06.7

/R06.6

/R06.7
2 4 2 4 2 4 2 4

C C
F21+ TC2+ TC1+ C+
/ N08.1 /N02.1 /N01.1 /M04.1

F21- TC2- TC1- C-


/ N08.1 /N02.6 /N01.7 /M04.4

X21 1 5 -X20 1 5 -X10 1 6 X11 1 3

-W262 13 14 -W261 9 10 15 16

+MK
-X20 1 5 -X10 1 6 X11 1 2
D D
-W296 16 17 -W294 8 9 10 13

+QF01

-TB1 9 10 -TB1 7 8 -TB1 5 6

2 1
F21 F MCB5 MCB4 MCB3
/Z04.3 -PS
E E
P445
TC2+

TC1+
TC2-

TC1-

CC+

CC-
N02.2 /

N02.2 /

N01.1 /

N01.1 /

M04.1 /

M04.1 /
-PE

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE G03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE G04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN DC POWER SUPPLY FOR CONTROL PANEL PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E04+MK +MK =E03+MK

DC POWER SUPPLY DC POWER SUPPLY


A FOR CB MOTOR FOR DS, ES MOTOR A
-W278
DC+ 1 -XDC 1 -XDC 2 DC+
=E05/G04.7 / =E03/G04.1

DC- 2 -XDC 3 -XDC 4 DC-


=E05/G04.7 / =E03/G04.1

1 3 1 3
12 14 96 98 12 14 96 98

-FQCB 11 95 -FQDS 11 95
B B
2P-16A I> I> 2P-16A I> I>

/R04.7

/R05.2

/R04.7

/R05.3
2 4 2 4

ES+
/ P03.1

ES-
/ P03.1

-XDC1 1 2 -XDC2 1 4 -XDC2 2 5 -XDC2 3 6

C -W279 1 2 -W280 1 2 -W281 1 2 -W282 1 2 C

+QF01 +QL02 +QL07 +QL09

X1 450 460

-X1 1 2 -X1 5 4 -X1 1 2 -X1 5 4 -X1 1 2 -X1 5 4

D QM1 QM1 QM1 D


1

DSQ2+

DSQ7+

DSQ9+
DSQ2-

DSQ7-

DSQ9-
Q1
2

3
Q1 M01.2 /

M01.2 /

M02.2 /

M02.2 /

M03.2 /

M03.2 /
4
/Z17.3 M /Z17.3 M /Z17.3 M
1 5
Q1
/Z14.3 6
M
E E

POWER SUPPLY POWER SUPPLY POWER SUPPLY POWER SUPPLY POWER SUPPLY POWER SUPPLY POWER SUPPLY
FOR CB MOTOR FOR DS MOTOR FOR CONTROL CIRCUIT FOR DS MOTOR FOR CONTROL CIRCUIT FOR DS MOTOR FOR CONTROL CIRCUIT

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE G04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE M01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN DC POWER SUPPLY FOR HV EQUIPMENT PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP4

A CLOSE DS QL02 OPEN DS QL02 CLOSE DS QL02 OPEN DS QL02 A


FROM MIMIC FROM MIMIC FROM BCU FROM BCU

6 8 1 3
1
-SQL02 BCU D
-S.B/M

Push close

Push open
/Z09.1 C3 C4 /Z05.4 -DO1 -DO2
/Z09.1
MIMIC /Z05.4 /Z05.4
2
B 5 7 2 4 B

-X3 1 X3 2 X3 3 X3 4
-W261 1 2 3 4

+MK INT_QL02+ INT_QL02-


C P01.5 P01.5 C
-X3 1 3 5 6
INTERLOCKING CIRCUIT

-W293 1 2 3 4

+QL02
-X1 4A -X1 4B -X1 8 -X1 7 -X1 9A
DSQ2+
G04.4
D D
-X1 6A -X1 6B SB3

SA1 SA1 SA1 SA1 -X1 9

-KA1
-KM1 -KM2 -SB2 -SB1

-KA4

CS1 CS2
E E
KA4 KM2 KM1 /Z18.3
-QM1

CLOSE OPEN
DSQ2- -X1 12
G04.4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE M01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE M02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CONTROL CIRCUIT DS E04-QL02 PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP4

A CLOSE DS QL07 OPEN DS QL07 CLOSE DS QL07 OPEN DS QL07 A


FROM MIMIC FROM MIMIC FROM BCU FROM BCU

6 8 5 7
3
-SQL07 BCU D
-S.B/M

Push close

Push open
/Z09.1 C3 C4 /Z05.4 -DO3 -DO4
/Z09.1
MIMIC /Z05.4 /Z05.4
4
B 5 7 6 8 B

-X3 5 X3 6 X3 7 X3 8
-W261 5 6 7 8

+MK INT_QL07+ INT_QL07-


C P02.1 P02.1 C
-X3 7 9 11 12

INTERLOCKING CIRCUIT
-W298 1 2 3 4

+QL07
-X1 4A -X1 4B -X1 8 -X1 7 -X1 9A
DSQ7+
G04.6
D D
-X1 6A -X1 6B SB3

SA1 SA1 SA1 SA1 -X1 9

-KA1
-KM1 -KM2 -SB2 -SB1

-KA4

CS1 CS2
E E
KA4 KM2 KM1 /Z18.3
-QM1

CLOSE OPEN
DSQ7- -X1 12
G04.6

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE M02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE M03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CONTROL CIRCUIT DS E04-QL07 PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP4

A CLOSE DS QL09 OPEN DS QL09 CLOSE ES QL09 OPEN ES QL09 A


FROM MIMIC FROM MIMIC FROM BCU FROM BCU

6 8 9 11
5
-SQL09 BCU D
-S.B/M

Push close

Push open
/Z09.1 C3 C4 /Z05.4 -DO5 -DO6
/Z09.1
MIMIC /Z05.4 /Z05.4
6
B 5 7 10 12 B

-X3 9 X3 10 X3 11 X3 12
-W262 1 2 3 4

+MK INT_QL09+ INT_QL09-


C P02.5 P02.5 C
-X3 13 16 18 19

INTERLOCKING CIRCUIT
-W300 1 2 3 4

+QL09
-X1 4A -X1 4B -X1 8 -X1 7 -X1 9A
DSQ9+
G04.8
D D
-X1 6A -X1 6B SB3

SA1 SA1 SA1 SA1 -X1 9

-KA1
-KM1 -KM2 -SB2 -SB1

-KA4

CS1 CS2
E E
KA4 KM2 KM1 /Z18.3
-QM1

CLOSE OPEN
DSQ9- -X1 12
G04.8

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE M03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE M04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CONTROL CIRCUIT DS E04-QL09 PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP4

CLOSE CB QF01 CLOSE CB CLOSE CB QF01 CLOSE CB CLOSED CB


START SOTF
A FROM BCU WITH SYN. FROM MIMIC WITH SYN. AR A
C+
G03.8
X11 2 C-
G03.8 13
X11 4 X11 5 -S.B/M
/Z09.1
MIMIC
14 10
F861 10 11 14
/N03.6 F741
1 /Z11.4 6 6
B -SQF01 B

Push close
13 1 15 /Z09.1 11 17
BCU D F87L D F87L E F87L H
/Z05.4 -DO7 /Z01 BI1 /Z01.6 BI16 /Z02 -BO6 -BO8
14 10 5
F862 10 11 /Z05.4 /Z01.6 /Z01.6 /Z02.6 /Z02.6
/N04.6 F742 14 2 16 12 18
1 /Z11.4 6 1 3
-S.25
/Z09.4
SYN. BYPASS
2 4

C C
X11 6 7 7
-W261 17 18 19

+MK
X11 9
INT_CB+ INT_CB- INT_CBR- INT_CBR+
P01.1 P01.1 P01.3 P01.3

X11 3 X11 5 X11 7 X11 11


-W294 11 12 14 15
D D

+QF01

PBS1 -TB1 14 -TB1 15 TB1 18 TB1 17

G03.7/
CC+
3 4
7 5
43A
6
E E

CLOSING COIL

-52CC
/Z13.2

G03.7/
CC-

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE M04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CLOSING CIRCUIT CB E04-QF01 PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP4

A OPEN Cmd. CB OPEN Cmd. CB F87L TRIP F21 TRIP LOAD F861 F862 TRIP CIRCUIRT SUPERVISOR 1 A
FROM MIMIC FROM BCU TC1 QF01 TC1 QF01 SHEDDING TRIP TC1 TRIP TC1 CB E03-QF01

TC1+ TC1+ TC1-


G03.6 N03.1 G03.6/
X10 2 3 4 -X10 7 8

15 TC1-
1 1
N03.1
-S.B/M F87L H F21 E
B /Z09.1 MIMIC /Z02 BO1 /Z03 -BO1
B
16 /Z02.6 /Z03.5
1 2
1 5 F861 20 21 F862 20 21
2 2 -F741 + -
-K81 /N03.6 /N04.6
/Z11.2 K3
/N05.4 9 2 2
8 15 9 9
-SQF01 BCU D -XF87L -XF21 K1 K2
Push open

K1 K2
/Z09.1 C4 /Z05.4 /Z12.4 /Z12.5
-DO8
/Z05.4
12 4 8
7 16 10 10

C C

T.TC1 /N03.1

-X10 9 X10 10 -X10 12 13


-W261 11 12 13 14

+MK X10 1 2 3 4

-W294 4 5 6 7

D +QF01 TC1+ TB1 16 TB1 11 12 13 D


G03.6

3
PBS2
7 5
4
43A
6

-A3

TRIPPING COIL 1 1 3

E -P1 -P2 E
-S1 -S1
2 4

-A2 -52TC1
/Z13.4

G03.6/
TC1-

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172
TRIPPING CIRCUIT 1
DATE 24/11/2020
APPROVED NGUYEN DINH TUAN PECC2/TT-110KV/E04-172
CB E04-QF01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP4
F87L TRIP F21 TRIP LOAD F861 F862 TRIP CIRCUIRT SUPERVISOR 2
TC2 QF01 TC QF01 SHEDDING TRIP TC2 TRIP TC2 CB E03-QF01

TC2+ TC2+
A G03.5 N04.2 A
-X20 2 TC2-
G03.5

-X20 6 7

11 3
-XF87L F21 E
/Z12.4 /Z03 -BO2 TC2-
/Z03.5 N04.2
2 6 F861 30 31 F862 30 31
B 12 4 1 2 B
-K81 /N03.6 /N04.6
862 /N05.4 -F742 + -
/ N04.4 10 3 3
3 11 /Z11.2 K3

F87L H -XF21
/Z02 /Z12.5
BO2 K1 K2
K1 K2

/Z02.6

4 12 12 4 8

T.TC2 /N04.2
C C
X20 8 10 11

-W262 15 16 17

+MK
X20 1 2 3

-W296 13 14 15

+QF01
D TC2+ TB1 26 TB1 23 24 25 D
G03.4

3
PBS2
7 5
4
43A
6

-A4
TRIPPING COIL 2
5

E -P2 E
-S1 -S1
6

-A4 -52TC2
/Z13.7

TC2-
G03.5

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172
TRIPPING CIRCUIT 2
DATE 24/11/2020
APPROVED NGUYEN DINH TUAN PECC2/TT-110KV/E04-172
CB E04-QF01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP4

A F87B, 27/59 50BF(E02,E05), F87B F87T TRIP F21 TRIP RESET A


C11 TRIP TRIP SEND F861 LOCKOUT 1 LOCKOUT 1 LOCKOUT F861

N01.5/
TC1+

X10 5
-W259 3

=E05+CRP5
5 5

E04.TC1+
F87L H F21 E
B /Z02 BO3 /Z03 BO3
B
/Z02.6 /Z03.5

6 6

=E05/N08.2 /
19 3
BCU D -S.RL
/Z05.4 /Z09.7
-DO9
=E05/N08.2

=E05/N08.2 /Z05.4
C C
21 4
13 13
-XF87L -XF21
E04.TC1

E04.861

/Z12.4 /Z12.5

14 14
-W259 4 5

X10 11 X10 14
D D
/ N01.4
T.TC1

SET RESET
b d
-F861
a c

N01.8/
TC1-
E E

11 1 /M04.2 51 5 /R05.7
10 50
21 2 /N01.6 61 6 /R08.7
20 60
31 3 /N02.5 70 7
30 71
41 4 /N11.4 80 8
40 81

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN TRIP-LOCKOUT1 CIRCUIT PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP4

A F87B, 27/59 50BF(E02,E05), F87B F87L TRIP F21 TRIP RESET A


C11 TRIP TRIP SEND F862 LOCKOUT 2 LOCKOUT 2 LOCKOUT F862

N02.7/
TC2+
X20 3 X20 4
-W259 9

=E05+CRP5

E04.TC2+
N02.4/
862

B B

=E05/N08.3 /
7 7
F87L H F21 E
/Z02 BO4 /Z03 BO4
/Z02.6 /Z03.5

8 8
22 3*
BCU D -S.RL
=E05/N08.3

=E05/N08.4
/Z05.4 /Z09.7
-DO10
/Z05.4
C C
24 4*
15
E04.TC2

E04.862

-XF21
/Z12.5

16
-W259 10 11

X20 9 X20 12
D D
/ N02.4
T.TC2

SET RESET
b d
-F862
a c

N02.7/
TC2-
E E

11 1 /M04.2 51 5 /R05.8
10 50
21 2 /N01.6 61 6 /R08.7
20 60
31 3 /N02.6 70 7
30 71
41 4 /N11.5 80 8
40 81

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N05

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN TRIP-LOCKOUT2 CIRCUIT PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E02+CRP2 +CRP4 =E05+CRP5

A A

-W259
LV1. -X91 1 LOAD SHEDDING LEVEL 1 2 14 LV1
=E02/N13.7/ / =E05/N17.2

LV2. -X91 3 LOAD SHEDDING LEVEL 2 4 15 LV2


=E02/N13.7/ / =E05/N17.2

LV3. -X91 5 LOAD SHEDDING LEVEL 3 6 16 LV3


=E02/N13.7/ / =E05/N17.2

B LV4. -X91 7 LOAD SHEDDING LEVEL 4 8 17 LV4 B


=E02/N13.7/ / =E05/N17.2

COM. -X91 9 COM 10 18 COM


=E02/N13.7/ / =E05/N17.2

LEVEL 1

LEVEL 2

LEVEL 3

LEVEL 4
4 6 8 10
-S.81
C /Z09.1 C

14
-K81
D 220VDC 13 D

5 9 /N01.5
E 1 E
6 10 /N02.5
2
7 11
3
8 12
4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N05 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N06

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LOAD SHEDDING CIRCUIT PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP4

A =E04+QF01 =E04+QF01 =E04+QF01 =E04+VTB 50BF DTT =E05+CRP5 =E03+CRP3 =E03+CRP3 =E03+CRP3 A
CB CLOSED SPRING DISCHARGED SF6 LOCKOUT MCB LVT 3P OFF TO END LINE MCB BVT CL:3P OFF SWITCH FAIL MCB SWITCH OFF MCB SWITCH TRIP
87L+ 87L+
G02.2 N07.1

X12 2 3 4 5

-W262 9 -W267 6 -W259 6

F87L.E03+
87L.E05+
+MK +VTB

=E05+CRP5

=E03+CRP3
B B
X12 1 X12 2 X12 3
X12 15
-W294 16

=E03/N11.5 /
=E05/N08.5 /
+QF01
-TB2 1 -TB1 51 -TB1 42

12 14
S2 LS A3 -FQP
C /Z16.1 /Z15.6 /Z15.4 /S02.4 11
C

/=E03/N11.6

/=E03/N11.7

/=E03/N11.8
=E05/N08.5

=E05/N08.6
-TB2 2 -TB1 52 -TB1 43

E03.MCBO

E03.MCBT
50BF.DTT

E05.MCB

E03.SW
-W294 17 18 19

X12 4 X12 5 X12 6 X12 15


D D

-W262 10 11 12 -W267 7 -W259 7 8

X12 11 12 13 14 15 16 17 18 19

4 6 8 10 12 14 16 2 4
F87L D E
/Z01 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10
E /Z01.6 /Z01.6 /Z01.6 /Z01.6 /Z01.6 /Z01.6 /Z01.6 /Z01.6 /Z01.6
E

3 5 7 9 11 13 15 1 3
87L-
N07.1

X12 9 X12 10
87L-
G02.2

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N06 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N07

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT F87L PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP4

A F21 F21 A
ON 87L ON 79 SPARE
START 79 FAILURE

87L+
N06.8

X12 6 X12 7

B B

7 9
-S.B/M
/Z09.1
MIMIC MIMIC
8 10

ON
ON
C 9 11 1 3 1 1 C
F21 E F21 F BCU E -S.87L -S.79
/Z03 -BO5 /Z04.3 WD1 /Z05.6 /Z09.4 /Z09.4
DO1 DO2
/Z03.5 /Z04.3 /Z05.6 /Z05.6

10 12 2 4 2 2

D D

X12 20

6 8 10 12 16
F87L E
E /Z01.6 BI11 BI12 BI13 BI14 BI15
E
/Z01.6 /Z01.6 /Z01.6 /Z01.6 /Z01.6

5 7 9 11 15

87L-
N06.8

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N07 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N08

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT F87L PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP4

BCU RECEIVE 50BF - DTT RECEIVE 21 - PTT F85 FAIL OR MCB BCU MCB BCU
SPARE SPARE
FAILURE FROM THE END LINE FROM THE END LINE CHANNEL FAIL OFF TRIP
A A

F21+
G03.3
X21 2 X21 3 X21 4
-W266 1

=T00+TELE
X2.2 1 X2.2 3 X2.2 17
B B

5
-BCU A 12 14 96 98
/Z05.2 -FQBCU -FQBCU
/G02.3 11 /G02.3 95
6

C C

X2.2 2 X2.2 4 X2.2 18


X21 11 X21 12

D D
-W266 2 3 4

X21 8 X21 9 X21 10

2 4 6 8 10 12 14 D16
F21 D
/Z04 BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8
/Z04.6 /Z04.6 /Z04.6 /Z04.6 /Z04.6 /Z04.6 /Z04.6 /Z04.6
E E
1 3 5 7 9 11 13 D15

X21 6 X21 7
F21-
G03.3

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N08 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N09

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT F21 PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP4

50BF DTT 21 PTT


A TO THE END LINE TO THE END LINE A

X21 14 X21 15
-W259 12

=E05+CRP5

85.E05+
B B

=E05/N08.7 /
11
F21 E
/Z03 -BO6
/Z03.5

12

=E05/N08.7
C C

50BF.85
-W259 13

X21 16
X21 13 X21 18
D X21 17 D

-W266 5 6 7

=T00+TELE
XDC 4 X2.1 1 X2.1 2
E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N09 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N10

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT F85 PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+MK

CB E04-QF01 CB E04-QF01 DS E04-QL02 DS E04-QL02


A CLOSED OPENED CLOSED OPENED A

-X3 20 21 22

-W294 1 -W293 5

+QF01 +QL02
B B

TB2 5 TB2 25 -X2 9 -X2 11

S2-3 S2-5 CS1-5 -CS1-6


/Z16.2 /Z16.5 /Z19.4 /Z19.4

C C

-TB2 6 -TB2 26 -X2 10 -X2 12

-W294 2 3 -W293 6 7
D D

-X3 23 24 25 26

-W283 1 2 3 4 5

=E05+CRP5
E04.MK+

E04.DSO
E04.CBO

E04.DSC
E04.CBC

E E
=E05/N10.5 /

=E05/N10.6 /

=E05/N10.6 /

=E05/N10.7 /
=E05/N10.5/

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N10 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE N11

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT OF F87B PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP4

F87L START F21 START F861 TRIP F862 TRIP SWITCH MCB SWITCH MCB SWITCH
A 50BF BAY E04 50BF BAY E04 A
START 50BF BAY E04 START 50BF BAY E04 FAILURE OFF TRIP

9 17
H E
B F87L BO5 F21 BO8 B
/Z02 /Z03 NC NO
/Z02.6 /Z03.5
-SW 12 14 12 14 96 98 96 98
10 18
F861 40 41 F862 40 41 -FQSW1 -FQSW2 -FQSW1 -FQSW2
/N03.6 /N04.6 /G01.5 11 /G01.6 11 /G01.5 95 /G01.6 95
4 4
COM

15 17
-XF87L -XF67
/Z12.4

C C
16 18

-X3 13 14 15 16 17 18

-W259 1 2
F87B.E04+

=E05+CRP5 =E03+CRP3

E04.MCBO

E04.MCBT
E04.50BF

D D

F87L.E04+

E04.SW
=E05/N12.4 /

=E03/N06.6 /

=E03/N06.7 /

=E03/N06.7 /
=E05/N12.4

=E03/N06.6
F87L, F67 BAY E04
START 50BF

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE N11 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE P01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN SIGNAL SEND TO F87B PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

+MK
INTETLOCKING FOR INTETLOCKING FOR
INTETLOCKING FOR
CLOSE CB QF01 CLOSE CB QF01
A CLOSE/OPEN DS QL02 A
AT LOCAL AT REMOTE

INT_CB+ INT_CBR+ INT_QL02+


M04.2 M04.7 M01.3
-X11 4 -X11 10 -X3 2
-W293 15 16 -W296 1 -W302 1

+QL02 -X2 3 +QL02 -X2 1 +QF01 -X1 231 +QE75 -X2 27

B B
DS QL02 OPENED

ES QE75 OPENED
DS QL02 CLOSED

CB 172 OPENED
-CS1-2 -CS1-1 -BG1-8 -CS1-14
/Z19.4 /Z19.3 /Z21.5

-X2 4 -X2 2 -X2 232 -X2 28


C -W293 17 18 -W302 2 C
-W296 4

-X11 12 -X11 13 -X3 29


-X3 27
-W298 14 15 -W292 2

-W301 1

E5.Q24.+
=E05+MK
+QL07 -X2 3 +QL07 -X2 1 +QE25 -XT2 27

=E05/P02.7 /
ES E03-QE24 OPENED
D D
DS QL07 OPENED

ES QE25 OPENED
DS QL07 CLOSED

-CS1-2 -CS1-1 -CS1-14


/Z19.4 /Z19.3 /Z21.5

=E05/P02.7
E5.Q24.-
-X2 4 -X2 2 -XT2 28
E E
-W298 12 13 -W301 2

-W292 1
-X11 6 -X11 8 -X3 28

-X3 4

INT_CB- INT_CBR- INT_QL02-


M04.3 M04.5 M01.4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE P01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE P02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN INTERLOCKING FOR CB, DS, ES PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+MK

INTETLOCKING FOR INTETLOCKING FOR


A CLOSE/OPEN DS QL07 CLOSE/OPEN DS QL09 A

INT_QL07+ INT_QL09+
M02.3 M03.3
-X3 8 -X3 14
-W303 4

-W296 2 -W302 3

+QE76 -X2 31
+QF01 -TB2 27 +QE75 -XT2 3

ES E04-QE76 OPENED
B B
-X3 15
CB QF01 OPENED

ES QE75 OPENED
-W296 3
-CS1-16
-S2-6 -CS1-2 /Z21.6
/Z16.5 /Z21.3

=E03+MK

E3.Q0+
+QF01 -TB2 31

-X2 32

=E03/P04.6 /
CB E03-QF01 OPENED
-TB2 28 -XT2 4

CB E04-QF01 OPENED
-W303 2

C C
-W296 5 -W302 4
-X3 35
S2-8

=E03/P04.5
-X3 30 -X3 32 /Z16.6

E3.Q76+
-W301 3 -W303 3

=E03+MK
+QE25 -XT2 3 +QE76 -XT2 3

E3.Q0-
-TB2 32

=E03/P04.7 /
ES E03-QE76 OPENED
D D
ES QE25 OPENED

ES QE76 OPENED

-W296 6
-CS1-2 -CS1-2

=E03/P04.7
/Z21.3 /Z21.3 -X3 33

E3.Q76-
-XT2 4 -XT2 4
E E
-W301 4 -W303 1

-X3 31 -X3 10 -X3 34


-X3 17

INT_QL07- INT_QL09-
M02.4 M03.4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE P02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE P03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN INTERLOCKING FOR CB, DS, ES PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+MK INTETLOCKING FOR +VTB INTETLOCKING FOR
CLOSE/OPEN ES QE25 -KMV2 -W284 CLOSE/OPEN ES QE75
-FQM2 -KMV1 1 -X8 11 2

A -W284 22 1 9 5 A
ES+ -X3 37 1 -X8 8 21 24 -X8 9 -X8 10 9 5
G04.8
/S01.7 /S01.6
-X3 36 /S01.5 -X3 45
-W293 8 -W300 5
MCB LVT CLOSED AND NO VOLTAGE IN LINE

+QL02 -X2 19 +QL09 -X2 7

DS QL07 OPENED
DS QL02 OPENED

-CS1-10 -CS1-4
B /Z19.5 /Z19.4 B

-X2 20 -X2 8
-W293 9 -W300 6

-X3 38 -X3 46
-W298 5 -W298 7

C C
+QL07 -X2 19 +QL07 -X2 7
CB J01-QF01 AT TEST

DS QL07 OPENED
-CS1-10 -CS1-4
/Z19.5 /Z19.4

-X2 20 -X2 8
D D
-W298 6 -W298 8

-X3 39
ES-
G04.8
-X3 40 -X3 42 -X3 41 -X3 43 -X3 47 -X3 44
-W301 5 6 -W302 5 6 -W303 6 5

+QE25 +QE75 +QE76


-XT1 1 2 -XT1 1 2 -XT1 1 2
E E
13 13 13
-S4 -S4 -S4
14 14 14

-KA4 -KA4 -KA4


/Z20.4 /Z20.4 /Z20.4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE P03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE P04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN INTERLOCKING FOR CB, DS, ES PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+MK

A A

INTETLOCKING FOR INTETLOCKING FOR


ES E05-QE24 ES E03-QE76

B B

+QL02 +QL09
-X2 7 -X2 11

DS QL02 OPENED

DS QL09 OPENED
-CS1-4 -CS1-6
/Z19.4 /Z19.4
C C

-X2 8 -X2 12

-W293 10 11 -W300 7 8

D D

-X3 48 49 -X3 50 51

-W292 3 4

=E05+MK =E03+MK

E E
E4.Q2+

E4.Q9+
E4.Q2-

E4.Q9-
=E05/P04.6 /

=E03/P03.6 /
=E05/P04.6/

=E03/P03.6/
POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04
DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE P04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Q01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN INTERLOCKING FOR CB, DS, ES PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP4
S. CONTROL CB QF01 CB QF01 DS E04-QL02 ES E04-QE25

LAMT TEST AT "LOCAL" OPENED CLOSED OPENED CLOSED OPENED CLOSED


A A
G02.5/
SI+
-X7 2 X7 3
-W263 1

SI+
+MK / Q02.1
-X7 1 2 3
-W296 10 -W293 12 -W301 7

+QF01 +QL02 +QE25


X1 221 X1 233 -X2 15 13 -XT2 15 13
B B

BG1-6 BG1-7 CS1-8 CS1-7 CS1-8 CS1-7


/Z19.5 /Z19.5 /Z21.4 /Z21.4

X1 222 X1 234 -X2 16 14 -XT2 16 14

-W296 11 12 -W293 13 14 -W301 8 9

-X7 9 10 11 12 13 14

-W263 2 3 4 5 6 7

C C
-X7 8 9 10 11 12 13
9 11 9 11
-SQF01 -SQL02
/Z09.1 /Z09.1
2 1
SQE25
/Z09.4 3
10 12 10 12

KT+
/ Q02.1
D 3 D
1 5 1 5 2 6 3 7
-S.LT -KLCB -KST2 -KST2 -KST2
/Z09.7 /R07.7 /Q01.2 /Q01.2 /Q01.2
9 9 10 11
TEST

4 X1 X1
X1 -SQF01 -SQL02
14 14 PL01 /Z09.1 /Z09.1
-KST1 -KST2 /Z09.7 X2
220VDC 13 220VDC 13 X2 X2

E SI- E
/ Q02.1
-X7 5 -X7 6 -X7 7
G02.5/
SI-

5 9 5 9 /Q01.3
1 1
6 10 6 10 /Q01.5
2 2
7 11 7 11 /Q01.6
3 3
8 12 /Q02.8 8 12 /Q02.3
4 4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Q01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Q02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN INDICATOR CIRCUIT PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+MK

DS E04-QL07 ES E04-QE75 ES E04-QE76 DS E04-QL09

A OPENED CLOSED OPENED CLOSED OPENED CLOSED OPENED CLOSED A

Q01.7/
SI+ -X7 8

X7 4 -X7 5 6 7

-W298 11 -W302 7 -W303 7 -W300 9

+QL07 +QE75 +QE76 +QL09


-X2 15 13 -XT2 15 13 -XT2 15 13 -X2 15 13

B CS1-8 CS1-7 CS1-8 CS1-7 CS1-8 CS1-7 CS1-8 CS1-7 B


/Z19.5 /Z19.5 /Z21.4 /Z21.4 /Z21.4 /Z21.4 /Z19.5 /Z19.5

-X2 16 14 -XT2 16 14 -XT2 16 14 -X2 16 14

-W298 9 10 -W302 8 9 -W303 8 9 -W300 10 11

X7 15 16 X7 17 18 19 20 21 22

C -W263 8 9 10 11 12 13 14 15 C
+CRP4

X7 14 15 20 21
9 11
X7 16 17 18 19
9 11
-SQL07 -SQL09
/Z09.1 /Z09.1
2 1 2 1
SQE75 SQE76
/Z09.4 3 /Z09.4 3
10 12 10 12

D D

Q01.8/
KT+

4 8 4 8
-KST2 -KST1
/Q01.2 12 /Q01.2 12

X1 X1

E -SQL09 -SQL09 E
/Z09.1 /Z09.1

X2 X2

Q01.8/
SI-

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Q02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN INDICATOR CIRCUIT PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP4

=E04+QF01 =E04+QF01
A =E04+QF01 =E04+QF01 =E04+QF01 =E04+QF01 =E04+QF01 A
SPRING CHARGED CONTROL SPARE
CB OPENED CB CLOSED SF6 ALARM SF6 LOCKOUT MCB OFFF
FAILURE ALARM AT LOCAL
BCU+ BCU+
G02.4 R05.1
-X8 2
-W264 1

+MK BCU+
R02.1
-X8 1
B -W297 1 B

+QF01

TB2 29 3 TB1 40 -TB1 44 51 46 30 32 34 36 38

S2 S2 A2 A4-1 TR1-1 43A MCB1 MCB2 MCB3 MCB4 MCB5


/Z16.5 /Z16.2 /Z15.4 /Z15.5 /Z15.6 /Z15.5 /Z15.2 /Z15.3 /Z15.3 /Z15.3 /Z15.4

C C

TB2 20 4 TB1 41 -TB1 45 52 47 31 33 35 37 39

-W297 2 3 4 5 6 7 8

X8 7 8 9 10 11 12 13

-W264 2 3 4 5 6 7 8
D D

X8 10 11 12 13 14 15 16 17
CBL
/ R07.7
1 2 4 5 7 8 10 11
- BCU I
/Z06.3
DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8
/Z06.3 /Z06.3 /Z06.3 /Z06.3 /Z06.3 /Z06.3 /Z06.3 /Z06.3

E 3 6 9 12 E
BCU-
R02.1

-X8 8

BCU- -X8 9
G02.4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT BCU PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+MK

A DS E04-QL02 DS E04-QL02 DS E04-QL02 DS E04-QL02 DS E04-QL07 DS E04-QL07 DS E04-QL07 DS E04-QL07 A


OPENED CLOSED CTR. AT LOCAL MCB OFF OPENED CLOSED CTR. AT LOCAL MCB OFF
BCU+ BCU+
R01.2 R03.1
-X8 2
-W295 1 -W299 1

+QL02 +QL07

X2 23 -X2 21 -X2 77 -X2 83 -X2 87 -X2 75 -X2 73 X2 23 -X2 21 -X2 77 -X2 83 -X2 87 -X2 75 -X2 73
B B

CS1 CS1 SA1 QF1 QF3 KA1 QM1 CS1 CS1 SA1 QF1 QF3 KA1 QM1
/Z19.6 /Z19.5 /Z18.7 /Z18.7 /Z17.8 /Z17.5 /Z17.5 /Z19.6 /Z19.5 /Z18.7 /Z18.7 /Z17.8 /Z17.5 /Z17.5

X2 24 -X2 22 -X2 80 -X2 84 -X2 88 -X2 76 -X2 74 X2 24 -X2 22 -X2 80 -X2 84 -X2 88 -X2 76 -X2 74

C C
-W295 2 3 4 5 -W299 2 3 4 5

-X8 14 15 16 17 18 19 20 21

+CRP4
-W264 9 10 11 12 13 14 15 16

-X8 18 19 20 21 22 23 24 25
D D

13 14 16 17 19 20 22 23
- BCU I
/Z06.3
DI9 DI10 DI11 DI12 DI13 DI14 DI15 DI16
/Z06.3 /Z06.3 /Z06.3 /Z06.3 /Z06.3 /Z06.3 /Z06.3 /Z06.3

E 15 18 21 24 E

BCU- BCU-
R01.8 R03.1

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT BCU PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+MK

A DS E04-QL09 DS E04-QL09 DS E04-QL09 DS E04-QL09 ES E04-QE25 ES E04-QE25 ES E04-QE25 A


SPARE
OPENED CLOSED CTR. AT LOCAL MCB OFF OPENED CLOSED MCB OFF
BCU+ BCU+
R02.8 R04.1
-X8 3
-W300 12 -W301 10

+QL09 +QE25

X2 23 -X2 21 -X2 77 -X2 83 -X2 87 -X2 75 -X2 73 XT2 23 -XT2 21 -XT2 87


B B

CS1 CS1 SA1 QF1 QF3 KA1 QM1 CS1 CS1 QF3
/Z19.6 /Z19.5 /Z18.7 /Z18.7 /Z17.8 /Z17.5 /Z17.5 /Z21.5 /Z21.5 /Z20.8

X2 24 -X2 22 -X2 80 -X2 84 -X2 88 -X2 76 -X2 74 XT2 24 -XT2 22 -XT2 88

C C
-W300 13 14 15 16 -W301 11 12 13

-X8 22 23 24 25 26 27 28

+CRP4
-W262 5 6 7 8 -W264 17 18 19

-X8 26 27 28 29 30 31 32 33
D D

1 2 4 5 7 8 10 11
- BCU J
/Z06.4
DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8
/Z06.5 /Z06.5 /Z06.5 /Z06.5 /Z06.5 /Z06.5 /Z06.5 /Z06.5

E 3 6 9 12 E

BCU- BCU-
R02.8 R04.2

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT BCU PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+MK

ES E04-QE75 ES E04-QE75 ES E04-QE75 ES E04-QE76 ES E04-QE76 ES E04-QE76 E04+MK E04+MK


OPENED CLOSED MCB OFF OPENED CLOSED MCB OFF MCB AC "OFF" MCB dC "OFF"
A A
BCU+
R03.8
-X8 4 -X8 5 -X8 6
-W302 10 -W303 10

BCU+
+QE75 +QE76 R05.1

XT2 23 -XT2 21 -XT2 87 XT2 23 -XT2 21 -XT2 87


B 12 14 12 14 12 14 12 14 B
-FQAC1 -FQAC2 -FQCB -FQDS
/D02.3 11 /D02.4 11 /G04.2 11 /G04.4 11
CS1 CS1 QF3 CS1 CS1 QF3
/Z21.5 /Z21.5 /Z20.8 /Z21.5 /Z21.5 /Z20.8

XT2 24 -XT2 22 -XT2 88 XT2 24 -XT2 22 -XT2 88

C C
-W302 11 12 13 -W303 11 12 13

-X8 29 30 31 32 33 34 35 36

+CRP4
-W265 1 2 3 4 5 6 7 8

-X8 34 35 36 37 38 39 40 41
D D

13 14 16 17 19 20 22 23
- BCU J
/Z06.4
DI9 DI10 DI11 DI12 DI13 DI14 DI15 DI16
/Z06.4 /Z06.5 /Z06.5 /Z06.5 /Z06.5 /Z06.5 /Z06.5 /Z06.5

E 15 18 21 24 E

BCU- BCU-
R03.8 R05.1

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R05

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT BCU PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP4

=E04+VTB =E04+VTB =E04+VTB


A =E04+MK NO VOLTAGE =E04+VTB MCB VTC12 CL0.5 F861 F862 A
MCB AC MCB VT MCB VT
MCB TRIP IN LINE MCB TRIP OFF BLOCK 25 OPERATED OPERATED
OFF 0.5 OFF 0.5 OFF (BL 25)
BCU+
R01.8
-X8 3 -X8 4 -X8 5 -X8 6
-W267 1 -W260 1

E04.BCU+
+MK +VTB

=E05+CRP5
BCU+
R06.1

-X8 12 -X8 1
B B

=E05/R09.6 /
BCU+
R04.7

2 6
96 98 96 98 96 98 96 98 KMV1
-FQAC1 -FQAC2 -FQCB -FQDS /S01.5 10
/D02.3 95 /D02.4 95 /G04.2 95 /G04.4 95 12 14 12 14 12 14 96 98 96 98 96 98 96 98
-FQAC -FQM1 -FQM2 -FQAC -FQM1 -FQM2 -FQP
/D02.7 11 /S01.3 11 /S01.7 11 /D02.7 95 /S01.3 95 /S01.7 95 /S02.4 95
2 6 F861 50 51 F862 50 51
KMV2 /N03.6 /N04.6
/S01.6 10 5 5
C C

=E05/R09.7
-X8 37 -X8 13 -X8 2 -X8 3 -X8 4 -X8 5

VTC12
-W265 9 -W267 2 3 4 5 8 -W260 2
D D

-X8 42 43 44 45 46 61 47

1 2 4 5 7 8 10 11 10
- BCU K
/Z06.6
DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 DI9
/Z06.6 /Z06.6 /Z06.6 /Z06.6 /Z06.6 /Z06.6 /Z06.6 /Z06.6 /Z06.6

E 3 6 9 12 12 E

BCU- BCU-
R04.8 R06.1

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R05 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R06

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT BCU PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP4

TCS1 TCS2 S.S. "BCU/MIMIC" S.S. "SYN./BYPASS" =E04+CRP4 =E04+CRP4 =E04+CRP4


FAILURE FAILURE AT MIMIC AT SYN. MCB AC OFF MCB DC OFF MCB TRIP
A A

96
BCU+ -FQ85 95 98
R05.8

96
12 -FQMF 95 98
-FQ85 11 14 /G02.6
96
12 -FQAC 95 98
-FQMF 11 14 /D01.4
B /G02.6 96 B
12 -FQDC195 98
-FQDC111 14 /G01.3
/G01.3 96
17 5 12 -FQDC295 98
-S.B/M -S.25 -FQDC211 14 /G01.2
13 9 13 9 12 14
/Z09.1 /Z09.4 /G01.2 96
F741 F742 -FQAC 12 -FQ87L 95 98
/Z11.3 5 /Z11.3 5 /Z09.4 BCU /Z09.6 SYN. /D01.4 11 -FQ87L 11 14 /G02.2
18 6 /G02.2 96
12 -FQ21 95 98
-FQ21 11 14 /G03.2
C /G03.2 96 C
12 -FQCB 95 98
-FQCB 11 14 /G03.7
/G03.7 96
12 -FQSI 95 98
-FQSI 11 14 /G02.4
/G02.4 96
12 -FQTC1 95 98
-FQTC1 11 14 /G03.6
/G03.6 96
12 -FQTC2 95 98
-FQTC2 11 14 /G03.4
D D
/G03.4

14 16 17 19 20 22 23
- BCU K
/Z06.6
DI10 DI11 DI12 DI13 DI14 DI15 DI16
/Z06.6 /Z06.6 /Z06.6 /Z06.6 /Z06.6 /Z06.6 /Z06.6

E 18 21 24 E

BCU- BCU-
R05.8 R07.1

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R06 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R07

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT BCU PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP4

A A
SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE

B B

C CBL C
R01.5

D X8 48 X8 49 50 51 52 53 54 55 D

1 2 4 5 7 8 10 11
BCU H
/Z07.3 14
DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 -KLCB
/Z07.3 /Z07.3 /Z07.3 /Z07.3 /Z07.3 /Z07.3 /Z07.3 /Z07.3 220VDC 13
E E
3 6 9 12
BCU-
R06.8

5 9 /Q01.3
1
6 10
2
7 11
3
8 12
4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R07 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R08

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN BINNARY INPUT BCU PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+MK +CRP4
CB E02-QF01 CB E02-QF01
CLOSED OPENED
A A

F87T TRIP F21 TRIP F861 TRIP F862 TRIP


SEND TO FR SEND TO FR SEND TO FR SEND TO FR

-X3 52 53

-W296 7

+QF01

B B
TB2 9 TB2 35
14 14
F87L H F21 E 60 61 60 61
/Z02 BO7 /Z03 BO7
F861 F862
/Z02.6 /Z03.5 /N03.6 /N04.6
6 6
15 15
S3-1 S3-6
/Z16.2 /Z16.6

C C

-TB2 10 -TB2 36

-W296 8 9

D D
-X3 54 55 -X3 19 -X3 20 -X3 21 -X3 22 -X3 23

=E00+FR

E04.F87L
CBE04.O
CBE04.C

E04.861

E04.862
E04.F21
FR+

FR+
E E
=E00+FR/R04.3 /

=E00+FR/R04.3 /

=E00+FR/R04.4 /

=E00+FR/R04.4 /

=E00+FR/R04.5 /

=E00+FR/R04.5 /
=E00+FR/R04.3 /

=E00+FR/R04.4 /

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R08 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE R09

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN SIGNAL SEND TO FR PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP4 =E03+CRP3

A A

B -W268 B
-X9 1 2 1 A+
/ =E03/R09.2
-X9 3 4 2 B-
/ =E03/R09.2
-X9 5

C C

2 3
PMF
/Z10.6 A(+) B(-)
RS485

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE R09 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE S01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN MODBUS RS485 CIRCUIT PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+LVT

A 110 0.11 0.11 0.11 A


kV
3 3 3 3

CLASS 0.5: 10VA


CLASS 0.5: 20VA CUỘN 1 - CL: 0.5 CUỘN 2 - CL: 0.5
CLASS 3P :50VA A B C A B C

* * * * * *
B B
* * * * * *
1a 1n 1a 1n 1a 1n 2a 2n 2a 2n 2a 2n
SEAL-IN POINT

+VTB
-W304 1 2 -W305 1 2 -W306 1 2 -W307 1 2 -W308 1 2 -W309 1 2

X51 1 4 X51 2 5 X51 3 6


X52 1 4 X52 2 5 X52 3 6

PE PE
C C

5 9 /P03.4 5 9 /P03.5
1 3 5 7 1 1 1 3 5 7
12 14 96 98 6 10 /R05.3 6 10 /R05.3 12 14 22 24 96 98
-FQM1 2 2 -FQM2
4P-2A 7 11 7 11 4P-2A
11 95 3 3
11 21 95
I> I> I> I> I> I> I> I>
/R05.4

/R05.5

/R05.4

/P03.3

/R05.6
8 12 8 12
2 4 6 8 4 4 2 4 6 8
D D

13 13
-KMV1 -KMV2
110VAC 14 110VAC 14

SEAL-IN POINT X51 7 8 9 10 X52 7 8 9 10


E4LVT0.5.N
E4LVT0.5.A

E4LVT0.5.C
E4LVT0.5.B

=E00+MP1 +CRP4

LVT0.5.N
LVT0.5.A

LVT0.5.C
LVT0.5.B
E E
=E00+MP1/T03.a.2

=E00+MP1/T03.a.3

=E00+MP1/T03.a.3

=E00+MP1/T03.a.3

T01.5

T01.5

T01.5

T01.6
POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04
DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE S01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE S02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LINE VOLTAGE CIRCUIT PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+LVT

A 110 0.11 0.11 0.11 A


kV
3 3 3 3

CLASS 0.5: 10VA


CLASS 0.5: 20VA CUỘN 3 - CL: 3P
CLASS 3P :50VA A B C

* * *
B B
* * *
3a 3n 3a 3n 3a 3n

+VTB
-W307 3 4 -W308 3 4 -W309 3 4

X53 1 4 X53 2 5 X53 3 6

PE

C C

1 3 5 7 12 14 96 98
-FQP
4P-2A 11 95
I> I> I> I>

/N06.4

/R05.6
2 4 6 8

D D

X53 7 8 9 10

+CRP4

LVT3P.N
LVT3P.A

LVT3P.C
LVT3P.B

E E
S04.3

S04.4

S04.4

S04.4

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE S02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE S03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN LINE VOLTAGE CIRCUIT PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CT CORE 1 - CL: 5P20, 400-800- 1200 /1A CORE 2 - CL: 5P20, 400-800- 1200 /1A CORE 5 - CL: 5P20, 400-800- 1200 /1A
GE
TYPE: OSKF145 A B C A B C A B C
400-800-1200/1/1/1/1/1A
A 5P20/5P20/0.5/0.5/5P20 A

1S1 1S1 1S1 1S5 1S5 1S5 2S1 2S1 2S1 2S5 2S5 2S5 5S1 5S1 5S1 5S5 5S5 5S5

-W286 -W288
1 -W290
1 1 -W288
2 -W286
2 2 -W286 -W288
3 -W290
3 3 -W288
4 -W286
4 4 -W287 -W289
3 -W291
3 3 -W289
4 -W287
4 4
+MK
B B

-X41 1 2 3 4 5 6 -X42 1 2 3 4 5 6 -X45 1 2 3 4 5 6

PE
-W285 1 2 3 4
PE PE

-W252 1 2 3 4 -W253 1 2 3 4
+CRP4 =E05+CRP5

C C

-X41 1 2 3 4 -X42 1 2 3 4

E04.CTN
E04.CTC
E04.CTA

E04.CTB
1 3 5 7 1 3 5 7
-XF87L -XF21
/Z12.4 /Z12.5

=E05/S06.7 /

=E05/S06.7 /

=E05/S06.8 /

=E05/S06.8 /
2 4 6 8 2 4 6 8

D 3 6 9 12 3 6 9 12 D
F87L C F21 C
/Z01 /Z04
IA IB IC IN IA IB IC IN
/Z01.3 /Z01.3 /Z01.3 /Z01.3 /Z04.3 /Z04.3 /Z04.3 /Z04.3 CT E04 SEND
F87B =E05+CRP5
2 5 8 11 2 5 8 11

-X411 1 2 3 4

E E
E04.CTN
E04.CTA

E04.CTC
E04.CTB

=E00+FR
=E00+FR/S02.1

=E00+FR/S02.2

=E00+FR/S02.2

=E00+FR/S02.2

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE S03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE S04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN CURRENT CIRCUIT OF RELAY PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E00+FR +VTB =E05+CRP5 =E02+CRP2

LINE VOLTAGE - CL: 3P BUSBAR VOLTAGE - CL: 3P BUSBAR VOLTAGE - CL: 3P


A A
110 0.11 110 0.11 110 0.11
kV kV kV
3 3 3 3 3 3

=E00+FR/S04.2

=E00+FR/S04.2

=E00+FR/S04.2

=E00+FR/S04.2

=E02/S03.4

=E02/S03.4

=E02/S03.5

=E02/S03.5
=E05/S07.7

=E05/S07.7

=E05/S07.8

=E05/S07.8
S02.4

S02.4

S02.5

S02.5

BVT23P.N
BVT23P.A

BVT23P.C
BVT23P.B
LVT3P.N
LVT3P.A

LVT3P.C
LVT3P.B

BVT23P.A

BVT23P.B

BVT23P.C

BVT23P.N
E04.LVTA

E04.LVTB

E04.LVTC

E04.LVTN
B B

-W254 1 2 3 4 -W255 1 2 3 4
+CRP4

-X53 1 3 5 7 -X53 2 4 6 8 -X52 1 -X52 3 5 7 -X52 2 -X52 4 6 8

C C

D D
21 23 25 27 21 23 25 27 17 19
-XF21 -XF87L
/Z12.5 /Z12.4

22 24 26 28 22 24 26 28 18 20

19 20 21 22 19 20 21 22
E F21 C F87L C 23 E
/Z04 /Z01
VA VB VC VA VB VC VS
/Z04.3 /Z04.3 /Z04.3 /Z01.3 /Z01.3 /Z01.3 /Z01.3

24

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE S04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE T01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN VOLTAGE CIRCUIT OF RELAY PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CT +VTB
CORE 4 - CL: 0.5, 400-800- 1200 /1A
GE
TYPE: OSKF145
400-800-1200/1/1/1/1/1A A B C LINE VOLTAGE - CL: 0.5
A 5P20/5P20/0.5/0.5/5P20 A
110 0.11
kV
3 3

1S1 1S1 1S1 2S5 2S5 2S5


B B

-W287 -W289
1 -W291
1 1 -W289
2 -W287
2 2
+MK

S01.7

S01.7

S01.7

S01.7
LVT0.5.N
LVT0.5.A

LVT0.5.C
LVT0.5.B
-X44 1 2 3 4 5 6

PE

C C
+CRP4
-W256 1 2 3 4 -W257 1 2 3 4

-X51 1 3 5 7

-X44 1 2 3 4
2 4 6 8

V.A
/ T02.4

V.B
/ T02.4

V.C
D / T02.4 D
V.N
7 / T02.5
1 3 5 1 3 5 7
-XTC1 -XTV1
/Z10.4 /Z10.4

2 6 8 2 4 6 8
4
V1 V2 V3 22
PMF S1 S1 S1
/Z10.6
E I2 E
I1 I3 V1 V2 V3

S2 S2 S2
N
A

C
B
T02.2

T02.2

T02.3

T02.3

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE T01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE T02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN VOLTAGE CIRCUIT OF MEASUREMENT PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP4 =E05+CRP5 =E02+CRP2

A A

BUSBAR VOLTAGE - CL: 0.5


110 0.11
kV
3 3

=E02/T01.5

=E02/T01.5

=E02/T01.6

=E02/T01.6
=E05/T02.7

=E05/T02.7

=E05/T02.8

=E05/T02.8
B B

BVT20.5.N
BVT20.5.A

BVT20.5.C
BVT20.5.B

BVT20.5.A

BVT20.5.B

BVT20.5.C

BVT20.5.N
-W258 1 2 3 4
/T01.2

/T01.2

/T01.3

/T01.3

/T01.6

/T01.6

/T01.6

/T01.6
-X54 1 3 5 7 -X54 2 4 6 8

C C
A

V.A

V.B

V.C

V.N
1 5 7 1 3 5 7 1 3
3
-XTC2 -XTV2 -XTV3
/Z10.4 /Z10.4 /Z10.5
D D

2 6 8 2 4 6 8 2 4
4

BCU L 15 11 7 3 21 23 25 27

/Z07.6
IA.1A IB.1A IC.1A IN.1A U V W N

E 16 12 8 4 22 24 26 28 E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE T02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE T03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN VOLTAGE CIRCUIT OF MEASUREMENT PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CT
400-800-1200/1/1/1/1A
5P20/5P20/0.5/0.5/5P20
A A
CORE 3 - CL: 5P20, 400-800- 1200 /1A
A B C

B B

3S1 3S1 3S1 3S4 3S4 3S4

C C

=E00+MP1

E04CT0.5.C1

E04CT0.5.A1
E04CT0.5.B1
E04CT0.5.A

E04CT0.5.C
E04CT0.5.B
D D
=E00+MP1/T03.a.6

=E00+MP1/T03.a.6

=E00+MP1/T03.a.7

=E00+MP1/T03.a.7

=E00+MP1/T03.a.6

=E00+MP1/T03.a.6
E E

CT E04 TO PMT CLASS 0.5

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE T03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE W01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN VOLTAGE CIRCUIT OF MEASUREMENT PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP4 +MK

A A

-X3 24 25 26 27 28 29 30 -X3 56 57 58 59 60 61 62 63 64 65

-X7 22 23 24 25 26 27 28 29 30 -X7 23 24 25 26 27 28 29 30
B B

-X8 56 57 58 59 60 62 63 64 65 -X8 38 39 40 41 42 43 44 45

-X10 15 16 17 18 19 20 -X10 7 8 9 10 11 12 13 14 15

-X11 9 10 11 12 13 14 15 -X11 14 15 16 17 18 19 20

-X12 21 22 23 24 25 26 27 28 29 30 -X20 6 7 8 9 10 11 12 13 14 15
C C
-X20 13 14 15 16 17 18 19 20

-X21 19 20 21 22 23 24 25

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE W01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z01

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN SPARE CIRCUIT PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP4

FUNCTION F87L P543 F87L CHỨC NĂNG


A A

C D
5A
1 1
BI1 /M04.5 START SOTF
1A
CURRENT CIRCUIT E04 - PHASE A /S03.2 2 IA 2

3 3
5A BI2 /N06.2 =E04+QF01 CB CLOSED
4 4
1A
CURRENT CIRCUIT E04 - PHASE B /S03.2 5 IB 5
BI3 /N06.2 =E04+QF01 SPRING DISCHARGED
B 6 6 B
5A
7 7
BI4 /N06.3 =E04+QF01 SF6 LOCKOUT
1A
CURRENT CIRCUIT E04 - PHASE C /S03.2 8 IC 8

9 9
5A BI5 /N06.4 =E04+VTB MCB LVT 3P OFF
10 10
1A
CURRENT CIRCUIT E04 - PHASE N /S03.3 11 IN 11
BI6 /N06.5 50BF DTT TO END LINE
12 12
5A
13 13
BI7 /N06.5 =E05+CRP5 MCB BVT CL:3P OFF
1A
C 14 IN_SEN. 14 C
15 15
BI8 /N06.6 =E03+CRP3 SWITCH FAIL
19 16
VOLTAGE CIRCUIT BAY E04 - PHASE A /S04.3 VA
E F87L
20 1
VOLTAGE CIRCUIT BAY E04 - PHASE B /S04.4 VB BI9 /N06.7 =E03+CRP3 MCB SWITCH OFF
2

21 3
VOLTAGE CIRCUIT BAY E04 - PHASE C /S04.4 VC BI10 /N06.7 =E03+CRP3 MCB SWITCH TRIP
22 4
D 5 D
23 BI11 /N07.2 F21 START 79
6
VOLTAGE CIRCUIT LINE - PHASE B /S04.6 VS
24
7
BI12 /N07.3 F21 FAILURE
8

F87L 9
J BI13 /N07.3 ON 87L
10
1
AUX
POWER SUPPLY /G02.2 SUPPLY
11
2 BI14 /N07.4 ON 79
12
E E
13
11 BI15 /N07.4 SPARE
14
12
15
13 BI16 /M04.5 CLOSE CB WITH SYN.
16
14

P54331RB7M0K18M

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z01 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z02

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE F87L (P543) PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP4
FUNCTION F87L P543 F87L CHỨC NĂNG

A A
F H
1 1
BO17 BO1 /N01.4 F87L TRIP TC1 QF01
2 2

3 3
BO18 BO2 /N02.3 F87L TRIP TC2 QF01
4 4

5 5
BO19 BO3 /N03.4 F87T TRIP LOCKOUT 1
6 6

B 7 7 B
BO20 BO4 /N04.4 F87L TRIP LOCKOUT 2
8 8
9 9
BO21 BO5 /N11.2 F87L START 50BF BAY E04
10 10

11 11
BO22 BO6 /M04.8 CLOSE CB WITH SYN.
12 12

13 13

14 BO23 BO7 14 /R08.5 F87T TRIP SEND TO FR

C 15 15 C
16 16
17 BO24 BO8 17 /M04.8 CLOSED CB AR
18 18
G F87L
1
BO9
2

3
BO10
D 4 D
5
BO11
6

7
BO12
8

9
BO13
10

11
E BO14 E
12

13
BO15 14

15

16
BO16 17

18

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z02 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z03

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE F87L (P543) PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP4

P445 F21 CHỨC NĂNG


A A

E
1
BO1 /N01.5 F21 TRIP TC1 QF01
2

3
BO2 /N02.4 F21 TRIP TC QF01
4

5
BO3 /N03.5 F21 TRIP LOCKOUT 1
B 6 B
7
BO4 /N04.6 F21 TRIP LOCKOUT 2
8

9
BO5 /N07.2 F21 TRIP START 79
10

11
BO6 /N09.5 SEND 21 - PTT TO THE END LINE
12

13

C BO7 14 /R08.6 F21 TRIP SEND TO FR C


15
16

BO8 17 /N11.3 F21 START 50BF BAY E04


18

D D

E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z03 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z04

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE F21 (P445) PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP4

FUNCTION F21 P445 F21 CHỨC NĂNG


A A

C D
5A
1 1
BI1 /N08.2 BCU FAILURE
1A
CURRENT CIRCUIT E04 - PHASE A /S03.4 2 IA 2

3 3
5A BI2 /N08.3 RECEIVE 50BF - DTT FROM THE END LINE
4 4
1A
CURRENT CIRCUIT E04 - PHASE B /S03.4 5 IB 5
BI3 /N08.3 RECEIVE 21 - PTT FROM THE END LINE
B 6 6 B
5A
7 7
BI4 /N08.4 F85 FAIL OR CHANNEL FAIL
1A
CURRENT CIRCUIT E04 - PHASE C /S03.4 8 IC 8

9 9
5A BI5 /N08.5 MCB BCU OFF
10 10
1A
CURRENT CIRCUIT E04 - PHASE N /S03.5 11 IN 11
BI6 /N08.6 MCB BCU TRIP
12 12
5A
13 13
BI7 /N08.6 SPARE
1A
C 14 IN_SEN. 14 C
15 15
BI8 /N08.7 SPARE
19 16
VOLTAGE CIRCUIT BAY E04 - PHASE A /S04.1 VA

20
VOLTAGE CIRCUIT BAY E04 - PHASE B /S04.2 VB

21
VOLTAGE CIRCUIT BAY E04 - PHASE C /S04.2 VC
22
D D
23
VS
24

F21
F
1
AUX
POWER SUPPLY /G03.2 SUPPLY
2

E E
11
F21 FAILURE /N07.3
12

13

14

P44531RB7M0K28L

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z04 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z05

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE F21 (P445) PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP4

A A

MODULE BIU241 BCU BCU BCU


FUNCTION MODULE DOU201 FUNCTION FUNCTION
- A D E

O2 1 1
DO1 /M01.7 CLOSE DS QL02 FROM BCU /N07.3 BCU ON 87L
2 2
O1 3 3
DO2 /M01.7 OPEN DS QL02 FROM BCU /N07.4 BCU ON 79
4 4
B B
WD 6 /N08.2 BCU FAILURE 5
DO3 /M02.7 CLOSE DS QL07 FROM BCU
5 6

VIN
7 7
+ DO4 /M02.7 OPEN DS QL07 FROM BCU
DI1 8
- 8
VIN
- 9 9
DI2
+ DO5 /M03.7 CLOSE ES QL09 FROM BCU
10 10

11 11
DO6 /M03.7 OPEN ES QL09 FROM BCU
RS232/ RXD/TB
RS485 12 12
C SERIAL
C
SG(0V)
LINK 1
13 13
DO7 /M04.4 CLOSE CB QF01 FROM BCU
TXD/TA
14 14
SG(0V)
RS232/
RS422/ 15 15
RS485 DO8 /N01.3 OPEN Cmd. CB FROM BCU
CTS
16 16
RXD/TB
17 17
SERIAL
LINK 2 TXD/TA
18 18
RTS/RB
19 19

D
RA
20 DO9 21 /N03.6 RESET LOCKOUT F861 D
RCD
21 20

= + 23 22
GND /G02.3
22 DO10 24 /N04.6 RESET LOCKOUT F862
_
= 24 23
Power
Supply

E E

C264U11M6A10013302100001111D10

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z05 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z06

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE BCU C264 PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP4

A A

BCU BCU BCU


MODULE DIU200 FUNCTION FUNCTION FUNCTION
- I - J - K
VIN
+
VIN
+ 1 /R01.2 =E04+QF01 CB OPENED /R03.2 DS E04-QL09 OPENED /R05.1 =E04+MK MCB TRIP
DI2 DI1
- - 2 /R01.3 =E04+QF01 CB CLOSED /R03.2 DS E04-QL09 CLOSED /R05.3 NO VOLTAGE IN LINE

3
B VIN
+
VIN
+ 4 /R01.3 =E04+QF01 SF6 ALARM /R03.3 DS E04-QL09 CTR. AT LOCAL /R05.4 =E04+VTB MCB AC OFF B
DI4 DI3
- - 5 /R01.4 =E04+QF01 SF6 LOCKOUT /R03.3 DS E04-QL09 MCB OFF /R05.4 =E04+VTB MCB VT 0.5 OFF

6
VIN
+
VIN
+ 7 /R01.4 =E04+QF01 SPRING CHARGED FAILURE ALARM/R03.5 ES E04-QE25 OPENED /R05.4 =E04+VTB MCB VT 0.5 OFF (BL 25)
DI6 DI5
- - 8 /R01.5 =E04+QF01 CONTROL AT LOCAL /R03.6 ES E04-QE25 CLOSED /R05.5 =E04+VTB MCB TRIP

9
VIN
+
VIN
+ 10 /R01.5 =E04+QF01 MCB OFFF /R03.6 ES E04-QE25 MCB OFF /R05.7 MCB VTC12 CL0.5 OFF BLOCK 25
DI8 DI7
- - 11 /R01.6 SPARE /R03.7 SPARE /R05.7 F861 OPERATED

C 12 C
VIN VIN
13 /R02.1 DS E04-QL02 OPENED /R04.2 ES E04-QE75 OPENED /R05.8 F862 OPERATED
+ +
DI10 DI9
- - 14 /R02.2 DS E04-QL02 CLOSED /R04.2 ES E04-QE75 CLOSED /R06.2 TCS1 FAILURE

15
VIN
+
VIN
+ 16 /R02.3 DS E04-QL02 CTR. AT LOCAL /R04.3 ES E04-QE75 MCB OFF /R06.3 TCS2 FAILURE
DI12 DI11
- - 17 /R02.3 DS E04-QL02 MCB OFF /R04.4 ES E04-QE76 OPENED /R06.3 S.S. "BCU/MIMIC" AT MIMIC

18
VIN
+
VIN
+ 19 /R02.5 DS E04-QL07 OPENED /R04.4 ES E04-QE76 CLOSED /R06.4 S.S. "SYN./BYPASS" AT SYN.
D DI14 DI13 D
- - 20 /R02.6 DS E04-QL07 CLOSED /R04.5 ES E04-QE76 MCB OFF /R06.5 =E04+CRP4 MCB AC OFF

21
VIN
+
VIN
+ 22 /R02.6 DS E04-QL07 CTR. AT LOCAL /R04.6 E04+MK MCB AC "OFF" /R06.5 =E04+CRP4 MCB DC OFF
DI16 DI15
- - 23 /R02.7 DS E04-QL07 MCB OFF /R04.7 E04+MK MCB dC "OFF" /R06.8 =E04+CRP4 MCB TRIP

24

E E

C264U11M6A10013302100001111D10

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z06 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z07

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE BCU C264 PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
=E04+CRP4

A A
BCU
MODULE TMU220 FUNCTION
- L
BCU IN.5A
MODULE CCU200 FUNCTION
-H
1 2
VIN
+
VIN
+ 1 /R07.2 SPARE IN.1A /T02.3 CURRENT CIRCUIT BAY E02-PHASE N
DI2 DI1
- - 2 /R07.3 SPARE
3 4
3
IC.5A
VIN
+
VIN
+ 4 /R07.3 SPARE
B DI4 DI3 5 6 B
- - 5 /R07.4 SPARE
IC.1A /T02.3 CURRENT CIRCUIT BAY E02-PHASE C
6 7 8
VIN
+
VIN
7 /R07.5 SPARE
DI6 DI5 IB.5A
- - 8 /R07.5 SPARE 9 10
9
IB.1A /T02.2 CURRENT CIRCUIT BAY E02-PHASE B
VIN
+
VIN
+ 10 /R07.6 SPARE 11 12
DI8 DI7
- - 11 /R07.6 SPARE
IA.5A
12 13 14
C C
13
IA.1A /T02.2 CURRENT CIRCUIT BAY E02-PHASE A
CO1 14 15 16
15

16 17 18
CO2
17
X
18 19 20

19
U /T02.4 VOLTAGE CIRCUIT BVT C11 PHASE A
D CO3 20 21 22 D
21
V /T02.4 VOLTAGE CIRCUIT BVT C11 PHASE B
22 23 24
CO4
23
W /T02.4 VOLTAGE CIRCUIT BVT C11 PHASE C
24 25 26

N /T02.6 VOLTAGE CIRCUIT TU4T2 PHASE B


27 28

E E

C264U11M6A10013302100001111D10

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z07 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z09

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE BCU C264 PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP4

SELECT SWITCH "BCU/MIMIC": SA25-FA 6015-61009/SALZER SELECT SWITCH "SYN./BYPASS": SA25-FA 6037-61638-M1-I-F-3-BS-0/SALZER PUSH BUTTON 2 NO

A MIMIC X X X X X X X X X SYN. X X X 3 3* A

BYPASS X X X
1 3 5 7 9 11 13 15 17
MIMIC
BCU

4 4*
1 3 5 7 9 11

BYPASS
SYN.
2 4 6 8 10 12 14 16 18
-S.RL /N03.7 /N04.7 RED
2 4 6 8 10 12
S.B/M /M01.4 /M02.4 /M03.4 /N07.5 /N07.6 /M04.7 /N01.2 /R06.3

B B
S.25 /M04.6 /M04.7 /R06.4
Discrepancy control switch for CB, DS, ES: BHL-3B3111-220L1-W-Y-B-L54-Y07E

CLOSE X
SELECT SWITCH "ON/OFF" : SA25-FA 6037-61638-M1-I-F-3-BS-0/SALZER PUSH BUTTON 1NO
OPEN X
LED 3
ON X X X
INDICATOR
PUSH CLOSE X X
OFF X X X
PUSH OPEN X X
4
1 3 5 7 9 11
Push close

Push close
Push open

Push open

C 1 3 5 7 9 11 L1 C

OFF
ON
close
open

-S.LT /Q01.2 GREEN


2 4 6 8 10 12
2 4 6 8 10 12 L2

S.79 /N07.6
-SQF01 /M04.7 /N01.2 /Q01.4 /Q01.5 /Q01.5
S.87L /N07.5
-SQL02 /M01.5 /M01.6 /Q01.6 /Q01.6 /Q01.6

D -SQL07 /M02.5 /M02.6 /Q02.2 /Q02.2 D


/Q02.2
-SQL09 /M03.5 /M03.6 /Q02.7 /Q02.7
/Q02.7 ES SEMAPHORE: SPSR/FUJI LAMP FOR CB AT LOCAL

+(~) X1

ES Semaphore
SELECT SWITCH "OFF/1/2/3/4" : SA25/SALZER FUJI
2 1 2 1 2
SPSR X2

91-230 VAC/DC -(~) 3 3


E 1 /Q01.3 E
-PL01 CB E04-QF01 AT "LOCAL"
OFF
1
2
3
4

-SQE25 /Q01.7
2 4 6 8 10
-SQE75 /Q02.4

-S.81 /N05.4 /N05.4 /N05.5 /N05.5 -SQE76 /Q02.6

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z09 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z10

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE CONTROL DEVICES PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP4

CURRENT TEST BLOCK


A Multi-function -PMF CHỨC NĂNG A
L1 L2 L3 ELITE
-KTT-AW4
XTC1 XTC2
V1 /T01.5
S1 V1 VOLTAGE CIRCUIT PHASE A
1 2
S2

V2 /T01.5
S1 V2 VOLTAGE CIRCUIT PHASE B
3 4

EQUIPMENT
S2
B B
S1 /T01.2 /T02.1 V3 V3 /T01.5 VOLTAGE CIRCUIT PHASE C
5 6
S2

VN VN
7 8
S1
/T01.2
I1 CURRENT CIRCUIT BAY-PHASE A
S2

S1
/T01.2
C I2 CURRENT CIRCUIT BAY-PHASE B
C
S2

S1
VOLTAGE TEST BLOCK /T01.3
I3 CURRENT CIRCUIT BAY-PHASE C
S2
L1 L2 L3
-KTT-VW4
XTV1 XTV2 XTV3
1a Tx
1 2 2
1n
RS485 RS232 Rx /R09.4 MODBUS PROTOCOL
D 3 D
1a GND
3 4 5
EQUIPMENT

1n

1a /T01.5 /T02.4 /T02.6


5 6
1n

7 8 + (L)
= P
E Power (~) E
Supply - (N) /G02.6 POWER SUPPLY
= N

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z10 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z11

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE CURRENT AND VOLTAGE TESTBLOCK PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP4

A A

TRIP SUPERVISION RELAY

5 6 1

B
VDF-10 B

K1 K2

C C

K3-1 K3-2
K1 K2 K3

D 9 13 10 14 12 4 8 2 D

-F741
/R06.2 /M04.3 /N01.7

-F742 /R06.3 /M04.3 /N02.7


E E

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z11 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z12

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE RELAY F74 PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+CRP4

RELAY TESTBLOCK

A A
TSB-14 XF87L XF21

1 2 /S03.2 /S03.4

3 4 /S03.2 /S03.4

B 5 6 /S03.2 /S03.4 B

7 8 /S03.3 /S03.5

9 10 /N01.4 /N01.5

11 12 /N02.3 /N02.4

C C

13 14 /N03.4 /N03.5

15 16 /N11.2 /N04.6

17 18 /S04.6

D D
19 20 /S04.6

21 22 /S04.3 /S04.1

23 24 /S04.4 /S04.2

E 25 26 /S04.4 /S04.2 E

27 28 /S04.4 /S04.2

POWER ENGINEERING CONSULTING J.S.C. 2 BAY =E04


DESIGNED NGUYEN VAN NHAT
F CUSTOMER: POWER ENGINEERING CONSULTING J.S.C. 2
TAN THUAN OFFSHORE WIND POWER PLANT PAGE Z12 F
CHECKED NGUYEN VAN CHUNG
ENERGY TECHNOLOGY NEXT PAGE Z13

PROJECT: TAN THUAN OFFSHORE WIND POWER PLANT


JOINT STOCK COMPANY CON. & PRO. PANEL FOR 110KV TRAN. LINE BAY E04-172 DATE 24/11/2020
APPROVED NGUYEN DINH TUAN REFERENCE RELAY TESTBLOCK PECC2/TT-110KV/E04-172
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

TC1 TC2
LOCAL CLOSE REMOTE AUTO LOCAL REMOTE P.D.
TC1 SF6 PRESSURE LOCAL REMOTE P.D.
TC2 SF6 PRESSURE
A SUPVN. SUPVN. SUPVN. SUPVN. A
INTELOCK CLOSE RECLOSE TRIP 1 TRIP 1 TRIP POST CLOSE ALARM & LOCKOUT TRIP 2 TRIP 2 TRIP POST CLOSE LOCKOUT
PRE CLOSE PRE CLOSE

220VDC1 TB1 15 14 TB1 18 19 TB1 17 220VDC2 TB1 22 TB1 16 TB1 11 12 TB1 13 220VDC3 TB1 27 TB1 26 TB1 23 24 TB1 25

MCB3 MCB4 MCB5


TB1 J1 K71 TB1 J3 K171 TB1 J1 K371
5 7 9
K13A K9 K17 K71
3
PBS1 3 3
4
PBS2