AIR CONDITIONING SYSTEMS

MODEL

CMB-P-V-J
CMB-P-V-JA
CMB-P-V-KA
CMB-P-V-KB

Il-2
0000004506.BOOK 1 ページ 2017年12月22日 金曜日 午後1時49分

BC controller Indoor units

CMB-P-V-J, CMB-P-V-JA, CMB-P-V-KA, CMB-P-V-KB


I.BC controller

1. SPECIFICATIONS ........................................................................................................................................... 2
2. EXTERNAL DIMENSIONS ............................................................................................................................ 13
3. ELECTRICAL WIRING DIAGRAMS .............................................................................................................. 19
4. SOUND LEVELS ........................................................................................................................................... 28
4-1. Sound levels in cooling mode ............................................................................................................... 28
4-2. Sound levels in heating mode............................................................................................................... 29
4-3. Sound levels in defrost mode................................................................................................................ 30
5. ELECTRICAL CHARACTERISTICS .............................................................................................................. 31
6. OPTIONAL PARTS........................................................................................................................................ 32
6-1. JOINT and REDUCER.......................................................................................................................... 32
6-2. JOINT KIT "CMY-R160-J1" FOR BC CONTROLLER .......................................................................... 37
7. INSTALLATION ............................................................................................................................................. 38
7-1. Installing BC controllers ........................................................................................................................ 38
8. SYSTEM DESIGN ......................................................................................................................................... 39
8-1. Compatibility ......................................................................................................................................... 39
8-2. System examples.................................................................................................................................. 40

MEES17K069 Il-2 1
0000004506.BOOK 2 ページ 2017年12月22日 金曜日 午後1時49分

1. SPECIFICATIONS Indoor units


I.BC
1. SPECIFICATIONS
controller

Model CMB-P104V-J
Number of branch 4
Power source 1-phase 220-230-240 V
50Hz 60Hz
Power input Cooling kW 0.067/0.076/0.085 0.054/0.061/0.067
Heating kW 0.030/0.034/0.038 0.024/0.027/0.030
Current input Cooling A 0.31/0.34/0.36 0.25/0.27/0.28
Heating A 0.14/0.15/0.16 0.11/0.12/0.13
External finish Galvanized steel plate
(Lower part drain pan: Pre-coated galvanized sheets + powder coating)
Connectable outdoor/heat source unit capacity P200 to P350
Model P80 or smaller
Indoor unit capacity connectable to 1 branch *12
(Use optional joint pipe combing 2 branches when the total unit capacity exceeds P81.)
External dimension H x W x D mm 246 x 596 x 495
in. 9-11/16 x 23-1/2 x 19-1/2
Refrigerant To outdoor/heat source unit Connectable unit capacity High press. pipe Low press. pipe
piping mm (in.) O.D. P200 15.88 (5/8) Brazed 19.05 (3/4) Brazed
diameter mm (in.) O.D. P250/P300 19.05 (3/4) Brazed 22.2 (7/8) Brazed
*13 mm (in.) O.D. P350 19.05 (3/4) Brazed or 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
To indoor unit Liquid pipe Gas pipe
Indoor unit Model 50 or smaller 6.35 (1/4) Brazed Indoor unit Model 50 or smaller 12.7 (1/2) Brazed
mm (in.) O.D. bigger than 50 9.52 (3/8) Brazed bigger than 50 15.88 (5/8) Brazed
(19.05 (3/4), 22.2 (7/8) with optional joint pipe used.)
Field drain pipe size mm (in.) O.D. 32 (1-1/4)
Net weight kg (lbs) 23 (51)
Sound power level
Rated operation dB <A> 56(When P200 Outdoor/Heat source unit connected),57(P250),59(P350)
(measured in anechoic room)
Defrost dB <A> 71
Sound pressure level
Rated operation dB <A> 38(When P200 Outdoor/Heat source unit connected),39(P250),40(P350)
(measured in anechoic room)
Defrost dB <A> 53
Accessories Drain Connection pipe, Washer, Tie band
Remarks

Notes:
1.Installation/foundation work, electrical connection work, insulation work, power source switch, and other items
shall be referred to the Installation Manual.
2.The equipment is for R410A refrigerant.
3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away
from any indoor units.)
4.Sound pressure/power level differs depending on the connected outdoor/heat source unit capacity or operation condition.
The sound pressure/power level at the rated operation is the value of the cooling mode.
5.The sound pressure/power level values were obtained in an anechoic room. Actual sound pressure level is usually
greater than that measured in anechoic room due to ambient noise and deflection sound.
6.The sound pressure level values were obtained at the location below 1.5m from the unit.
7.The solenoid valve switching sound is 56 dB (sound pressure level) regardless of the unit model.
8.Indoor units P100, P125, P140 can be connected to 1 branch. (In this case, cooling capacity decreases a little.)
9.Refrigerant piping diameter for connection of plural indoor units with 1 branch shall be referred to the
Installation Manual.
10.This unit is not designed for outside installations.
11.When blazing the pipes, be sure to blaze, after covering a wet cloth to the insulation pipes of the units in order to prevent
it from burning and shrinking by heat.
12.Indoor unit capacity connectable to 1 branch is changed depending on the indoor unit type and connection
method. Please refer to the Installation Manual for more information.
13.For the refrigerant pipe size, refer to Installation Manual of outdoor units/heat source units.
14.The ambient relative humidity of the BC controller needs to be kept below 80%.
BC controller

MEES17K069 Il-2 2
0000004506.BOOK 3 ページ 2017年12月22日 金曜日 午後1時49分

1. SPECIFICATIONS Indoor units

Model CMB-P106V-J
Number of branch 6
Power source 1-phase 220-230-240 V
50Hz 60Hz
Power input Cooling kW 0.097/0.110/0.123 0.078/0.088/0.097
Heating kW 0.045/0.051/0.057 0.036/0.041/0.045
Current input Cooling A 0.45/0.48/0.52 0.36/0.39/0.41
Heating A 0.21/0.23/0.24 0.17/0.18/0.19
External finish Galvanized steel plate
(Lower part drain pan: Pre-coated galvanized sheets + powder coating)
Connectable outdoor/heat source unit capacity P200 to P350
Model P80 or smaller
Indoor unit capacity connectable to 1 branch *12
(Use optional joint pipe combing 2 branches when the total unit capacity exceeds P81.)
External dimension H x W x D mm 246 x 596 x 495
in. 9-11/16 x 23-1/2 x 19-1/2
Refrigerant To outdoor/heat source unit Connectable unit capacity High press. pipe Low press. pipe
piping mm (in.) O.D. P200 15.88 (5/8) Brazed 19.05 (3/4) Brazed
diameter mm (in.) O.D. P250/P300 19.05 (3/4) Brazed 22.2 (7/8) Brazed
*13 mm (in.) O.D. P350 19.05 (3/4) Brazed or 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
To indoor unit Liquid pipe Gas pipe
Indoor unit Model 50 or smaller 6.35 (1/4) Brazed Indoor unit Model 50 or smaller 12.7 (1/2) Brazed
mm (in.) O.D. bigger than 50 9.52 (3/8) Brazed bigger than 50 15.88 (5/8) Brazed
(19.05 (3/4), 22.2 (7/8) with optional joint pipe used.)
Field drain pipe size mm (in.) O.D. 32 (1-1/4)
Net weight kg (lbs) 27 (60)
Sound power level
Rated operation dB <A> 56(When P200 Outdoor unit connected),57(P250),59(P350)
(measured in anechoic room)
Defrost dB <A> 71
Sound pressure level
Rated operation dB <A> 38(When P200 Outdoor unit connected),39(P250),40(P350)
(measured in anechoic room)
Defrost dB <A> 53
Accessories Drain Connection pipe, Washer, Tie band
Remarks

Notes:
1.Installation/foundation work, electrical connection work, insulation work, power source switch, and other items
shall be referred to the Installation Manual.
2.The equipment is for R410A refrigerant.
3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away
from any indoor units.)
4.Sound pressure/power level differs depending on the connected outdoor/heat source unit capacity or operation condition.
The sound pressure/power level at the rated operation is the value of the cooling mode.
5.The sound pressure/power level values were obtained in an anechoic room. Actual sound pressure level is usually
greater than that measured in anechoic room due to ambient noise and deflection sound.
6.The sound pressure level values were obtained at the location below 1.5m from the unit.
7.The solenoid valve switching sound is 56 dB (sound pressure level) regardless of the unit model.
8.Indoor units P100, P125, P140 can be connected to 1 branch. (In this case, cooling capacity decreases a little.)
9.Refrigerant piping diameter for connection of plural indoor units with 1 branch shall be referred to the
Installation Manual.
10.This unit is not designed for outside installations.
11.When blazing the pipes, be sure to blaze, after covering a wet cloth to the insulation pipes of the units in order to prevent
it from burning and shrinking by heat.
12.Indoor unit capacity connectable to 1 branch is changed depending on the indoor unit type and connection
method. Please refer to the Installation Manual for more information.
13.For the refrigerant pipe size, refer to Installation Manual of outdoor units/heat source units.
14.The ambient relative humidity of the BC controller needs to be kept below 80%.
BC controller

MEES17K069 Il-2 3
0000004506.BOOK 4 ページ 2017年12月22日 金曜日 午後1時49分

1. SPECIFICATIONS Indoor units

Model CMB-P108V-J
Number of branch 8
Power source 1-phase 220-230-240 V
50Hz 60Hz
Power input Cooling kW 0.127/0.144/0.161 0.102/0.115/0.127
Heating kW 0.060/0.068/0.076 0.048/0.054/0.060
Current input Cooling A 0.58/0.63/0.68 0.47/0.50/0.53
Heating A 0.28/0.30/0.32 0.22/0.24/0.25
External finish Galvanized steel plate
(Lower part drain pan: Pre-coated galvanized sheets + powder coating)
Connectable outdoor/heat source unit capacity P200 to P350
Model P80 or smaller
Indoor unit capacity connectable to 1 branch *12
(Use optional joint pipe combing 2 branches when the total unit capacity exceeds P81.)
External dimension H x W x D mm 246 x 596 x 495
in. 9-11/16 x 23-1/2 x 19-1/2
Refrigerant To outdoor/heat source unit Connectable unit capacity High press. pipe Low press. pipe
piping mm (in.) O.D. P200 15.88 (5/8) Brazed 19.05 (3/4) Brazed
diameter mm (in.) O.D. P250/P300 19.05 (3/4) Brazed 22.2 (7/8) Brazed
*13 mm (in.) O.D. P350 19.05 (3/4) Brazed or 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
To indoor unit Liquid pipe Gas pipe
Indoor unit Model 50 or smaller 6.35 (1/4) Brazed Indoor unit Model 50 or smaller 12.7 (1/2) Brazed
mm (in.) O.D. bigger than 50 9.52 (3/8) Brazed bigger than 50 15.88 (5/8) Brazed
(19.05 (3/4), 22.2 (7/8) with optional joint pipe used.)
Field drain pipe size mm (in.) O.D. 32 (1-1/4)
Net weight kg (lbs) 31 (69)
Sound power level
Rated operation dB <A> 56(When P200 Outdoor unit connected),57(P250),59(P350)
(measured in anechoic room)
Defrost dB <A> 71
Sound pressure level
Rated operation dB <A> 38(When P200 Outdoor unit connected),39(P250),40(P350)
(measured in anechoic room)
Defrost dB <A> 53
Accessories Drain Connection pipe, Washer, Tie band
Remarks

Notes:
1.Installation/foundation work, electrical connection work, insulation work, power source switch, and other items
shall be referred to the Installation Manual.
2.The equipment is for R410A refrigerant.
3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away
from any indoor units.)
4.Sound pressure/power level differs depending on the connected outdoor/heat source unit capacity or operation condition.
The sound pressure/power level at the rated operation is the value of the cooling mode.
5.The sound pressure/power level values were obtained in an anechoic room. Actual sound pressure level is usually
greater than that measured in anechoic room due to ambient noise and deflection sound.
6.The sound pressure level values were obtained at the location below 1.5m from the unit.
7.The solenoid valve switching sound is 56 dB (sound pressure level) regardless of the unit model.
8.Indoor units P100, P125, P140 can be connected to 1 branch. (In this case, cooling capacity decreases a little.)
9.Refrigerant piping diameter for connection of plural indoor units with 1 branch shall be referred to the
Installation Manual.
10.This unit is not designed for outside installations.
11.When blazing the pipes, be sure to blaze, after covering a wet cloth to the insulation pipes of the units in order to prevent
it from burning and shrinking by heat.
12.Indoor unit capacity connectable to 1 branch is changed depending on the indoor unit type and connection
method. Please refer to the Installation Manual for more information.
13.For the refrigerant pipe size, refer to Installation Manual of outdoor units/heat source units.
14.The ambient relative humidity of the BC controller needs to be kept below 80%.
BC controller

MEES17K069 Il-2 4
0000004506.BOOK 5 ページ 2017年12月22日 金曜日 午後1時49分

1. SPECIFICATIONS Indoor units

Model CMB-P1012V-J
Number of branch 12
Power source 1-phase 220-230-240 V
50Hz 60Hz
Power input Cooling kW 0.186/0.211/0.236 0.150/0.168/0.186
Heating kW 0.090/0.102/0.114 0.072/0.081/0.090
Current input Cooling A 0.85/0.92/0.99 0.69/0.74/0.78
Heating A 0.42/0.44/0.48 0.33/0.36/0.38
External finish Galvanized steel plate
(Lower part drain pan: Pre-coated galvanized sheets + powder coating)
Connectable outdoor/heat source unit capacity P200 to P350
Model P80 or smaller
Indoor unit capacity connectable to 1 branch *12
(Use optional joint pipe combing 2 branches when the total unit capacity exceeds P81.)
External dimension H x W x D mm 246 x 911 x 639
in. 9-11/16 x 35-7/8 x 25-3/16
Refrigerant To outdoor/heat source unit Connectable unit capacity High press. pipe Low press. pipe
piping mm (in.) O.D. P200 15.88 (5/8) Brazed 19.05 (3/4) Brazed
diameter mm (in.) O.D. P250/P300 19.05 (3/4) Brazed 22.2 (7/8) Brazed
*13 mm (in.) O.D. P350 19.05 (3/4) Brazed or 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
To indoor unit Liquid pipe Gas pipe
Indoor unit Model 50 or smaller 6.35 (1/4) Brazed Indoor unit Model 50 or smaller 12.7 (1/2) Brazed
mm (in.) O.D. bigger than 50 9.52 (3/8) Brazed bigger than 50 15.88 (5/8) Brazed
(19.05 (3/4), 22.2 (7/8) with optional joint pipe used.)
Field drain pipe size mm (in.) O.D. 32 (1-1/4)
Net weight kg (lbs) 46 (102)
Sound power level
Rated operation dB <A> 56(When P200 Outdoor unit connected),57(P250),59(P350)
(measured in anechoic room)
Defrost dB <A> 71
Sound pressure level
Rated operation dB <A> 38(When P200 Outdoor unit connected),39(P250),40(P350)
(measured in anechoic room)
Defrost dB <A> 53
Accessories Drain Connection pipe, Washer, Tie band
Remarks

Notes:
1.Installation/foundation work, electrical connection work, insulation work, power source switch, and other items
shall be referred to the Installation Manual.
2.The equipment is for R410A refrigerant.
3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away
from any indoor units.)
4.Sound pressure/power level differs depending on the connected outdoor/heat source unit capacity or operation condition.
The sound pressure/power level at the rated operation is the value of the cooling mode.
5.The sound pressure/power level values were obtained in an anechoic room. Actual sound pressure level is usually
greater than that measured in anechoic room due to ambient noise and deflection sound.
6.The sound pressure level values were obtained at the location below 1.5m from the unit.
7.The solenoid valve switching sound is 56 dB (sound pressure level) regardless of the unit model.
8.Indoor units P100, P125, P140 can be connected to 1 branch. (In this case, cooling capacity decreases a little.)
9.Refrigerant piping diameter for connection of plural indoor units with 1 branch shall be referred to the
Installation Manual.
10.This unit is not designed for outside installations.
11.When blazing the pipes, be sure to blaze, after covering a wet cloth to the insulation pipes of the units in order to prevent
it from burning and shrinking by heat.
12.Indoor unit capacity connectable to 1 branch is changed depending on the indoor unit type and connection
method. Please refer to the Installation Manual for more information.
13.For the refrigerant pipe size, refer to Installation Manual of outdoor units/heat source units.
14.The ambient relative humidity of the BC controller needs to be kept below 80%.
BC controller

MEES17K069 Il-2 5
0000004506.BOOK 6 ページ 2017年12月22日 金曜日 午後1時49分

1. SPECIFICATIONS Indoor units

Model CMB-P1016V-J
Number of branch 16
Power source 1-phase 220-230-240 V
50Hz 60Hz
Power input Cooling kW 0.246/0.279/0.312 0.198/0.222/0.246
Heating kW 0.119/0.135/0.151 0.096/0.108/0.119
Current input Cooling A 1.12/1.22/1.30 0.90/0.97/1.03
Heating A 0.55/0.59/0.63 0.44/0.47/0.50
External finish Galvanized steel plate
(Lower part drain pan: Pre-coated galvanized sheets + powder coating)
Connectable outdoor/heat source unit capacity P200 to P350
Model P80 or smaller
Indoor unit capacity connectable to 1 branch *12
(Use optional joint pipe combing 2 branches when the total unit capacity exceeds P81.)
External dimension H x W x D mm 246 x 1,135 x 639
in. 9-11/16 x 44-11/16 x 25-3/16
Refrigerant To outdoor/heat source unit Connectable unit capacity High press. pipe Low press. pipe
piping mm (in.) O.D. P200 15.88 (5/8) Brazed 19.05 (3/4) Brazed
diameter mm (in.) O.D. P250/P300 19.05 (3/4) Brazed 22.2 (7/8) Brazed
*13 mm (in.) O.D. P350 19.05 (3/4) Brazed or 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
To indoor unit Liquid pipe Gas pipe
Indoor unit Model 50 or smaller 6.35 (1/4) Brazed Indoor unit Model 50 or smaller 12.7 (1/2) Brazed
mm (in.) O.D. bigger than 50 9.52 (3/8) Brazed bigger than 50 15.88 (5/8) Brazed
(19.05 (3/4), 22.2 (7/8) with optional joint pipe used.)
Field drain pipe size mm (in.) O.D. 32 (1-1/4)
Net weight kg (lbs) 56 (124)
Sound power level
Rated operation dB <A> 56(When P200 Outdoor unit connected),57(P250),59(P350)
(measured in anechoic room)
Defrost dB <A> 71
Sound pressure level
Rated operation dB <A> 38(When P200 Outdoor unit connected),39(P250),40(P350)
(measured in anechoic room)
Defrost dB <A> 53
Accessories Drain Connection pipe, Washer, Tie band
Remarks

Notes:
1.Installation/foundation work, electrical connection work, insulation work, power source switch, and other items
shall be referred to the Installation Manual.
2.The equipment is for R410A refrigerant.
3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away
from any indoor units.)
4.Sound pressure/power level differs depending on the connected outdoor/heat source unit capacity or operation condition.
The sound pressure/power level at the rated operation is the value of the cooling mode.
5.The sound pressure/power level values were obtained in an anechoic room. Actual sound pressure level is usually
greater than that measured in anechoic room due to ambient noise and deflection sound.
6.The sound pressure level values were obtained at the location below 1.5m from the unit.
7.The solenoid valve switching sound is 56 dB (sound pressure level) regardless of the unit model.
8.Indoor units P100, P125, P140 can be connected to 1 branch. (In this case, cooling capacity decreases a little.)
9.Refrigerant piping diameter for connection of plural indoor units with 1 branch shall be referred to the
Installation Manual.
10.This unit is not designed for outside installations.
11.When blazing the pipes, be sure to blaze, after covering a wet cloth to the insulation pipes of the units in order to prevent
it from burning and shrinking by heat.
12.Indoor unit capacity connectable to 1 branch is changed depending on the indoor unit type and connection
method. Please refer to the Installation Manual for more information.
13.For the refrigerant pipe size, refer to Installation Manual of outdoor units/heat source units.
14.The ambient relative humidity of the BC controller needs to be kept below 80%.
BC controller

MEES17K069 Il-2 6
0000004506.BOOK 7 ページ 2017年12月22日 金曜日 午後1時49分

1. SPECIFICATIONS Indoor units

Model CMB-P108V-JA
Number of branch 8
Power source 1-phase 220-230-240 V
50Hz 60Hz
Power input Cooling kW 0.127/0.144/0.161 0.102/0.115/0.127
Heating kW 0.060/0.068/0.076 0.048/0.054/0.060
Current input Cooling A 0.58/0.63/0.68 0.47/0.50/0.53
Heating A 0.28/0.30/0.32 0.22/0.24/0.25
External finish Galvanized steel plate
(Lower part drain pan: Pre-coated galvanized sheets + powder coating)
Connectable outdoor/heat source unit capacity P200 to P900
Model P80 or smaller
Indoor unit capacity connectable to 1 branch *12
(Use optional joint pipe combing 2 branches when the total unit capacity exceeds P81.)
External dimension H x W x D mm 246 x 911 x 639
in. 9-11/16 x 35-7/8 x 25-3/16
Refrigerant To outdoor/heat source unit Connectable unit capacity High press. pipe Low press. pipe
piping mm (in.) O.D. P200 15.88 (5/8) Brazed 19.05 (3/4) Brazed
diameter mm (in.) O.D. P250/P300 19.05 (3/4) Brazed 22.2 (7/8) Brazed
*13 mm (in.) O.D. P350 19.05 (3/4) Brazed or 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P400 to P500 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
22.2 (7/8) Brazed or 28.58 (1-1/8)
*13 mm (in.) O.D. P550 28.58 (1-1/8) Brazed
Brazed
22.2 (7/8) Brazed or 28.58 (1-1/8) 28.58 (1-1/8) Brazed or 34.93 (1-3/8)
*13 mm (in.) O.D. P600
Brazed Brazed
mm (in.) O.D. P650 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P700 to P800 28.58 (1-1/8) Brazed 34.93 (1-3/8) Brazed
mm (in.) O.D. P850/P900 28.58 (1-1/8) Brazed 41.28 (1-5/8) Brazed
To indoor unit Liquid pipe Gas pipe
Indoor unit Model 50 or smaller 6.35 (1/4) Brazed Indoor unit Model 50 or smaller 12.7 (1/2) Brazed
mm (in.) O.D. bigger than 50 9.52 (3/8) Brazed bigger than 50 15.88 (5/8) Brazed
(19.05 (3/4), 22.2 (7/8) with optional joint pipe used.)
Total down-stream Indoor
To other BC controller High press. pipe Liquid pipe Low press. pipe
unit capacity
mm (in.) O.D. to P200 15.88 (5/8) Brazed 9.52 (3/8) Brazed 19.05 (3/4) Brazed
mm (in.) O.D. P201 to P300 19.05 (3/4) Brazed 9.52 (3/8) Brazed 22.2 (7/8) Brazed
mm (in.) O.D. P301 to P350 19.05 (3/4) Brazed 12.7 (1/2) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P351 to P400 22.2 (7/8) Brazed 12.7 (1/2) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P401 to P600 22.2 (7/8) Brazed 15.88 (5/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P601 to P650 28.58 (1-1/8) Brazed 15.88 (5/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P651 to P800 28.58 (1-1/8) Brazed 19.05 (3/4) Brazed 34.93 (1-3/8) Brazed
mm (in.) O.D. P801 to P1000 28.58 (1-1/8) Brazed 19.05 (3/4) Brazed 41.28 (1-5/8) Brazed
mm (in.) O.D. P1001 or above 34.93 (1-3/8) Brazed 19.05 (3/4) Brazed 41.28 (1-5/8) Brazed
Field drain pipe size mm (in.) O.D. 32 (1-1/4)
Net weight kg (lbs) 45 (100)
Sound power level Rated operation
dB <A> 62(When P250 Outdoor/Heat source unit connected),65(P450),68(P700),69(P900)
(measured in anechoic room)
Defrost dB <A> 74
Sound pressure level Rated operation
dB <A> 44(When P250 Outdoor/Heat source unit connected),47(P450),50(P700),51(P900)
(measured in anechoic room)
Defrost dB <A> 56
Accessories Drain Connection pipe, Washer, Tie band
Remarks

Notes:
1.Installation/foundation work, electrical connection work, insulation work, power source switch, and other items
shall be referred to the Installation Manual.
2.The equipment is for R410A refrigerant.
3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away
BC controller

from any indoor units.)


4.Sound pressure/power level differs depending on the connected outdoor/heat source unit capacity or operation condition.
The sound pressure/power level at the rated operation is the value of the cooling mode.
5.The sound pressure/power level values were obtained in an anechoic room. Actual sound pressure level is usually
greater than that measured in anechoic room due to ambient noise and deflection sound.
6.The sound pressure level values were obtained at the location below 1.5m from the unit.
7.The solenoid valve switching sound is 56 dB (sound pressure level) regardless of the unit model.
8.Indoor units P100, P125, P140 can be connected to 1 branch. (In this case, cooling capacity decreases a little.)
9.Refrigerant piping diameter for connection of plural indoor units with 1 branch shall be referred to the
Installation Manual.
10.This unit is not designed for outside installations.
11.When blazing the pipes, be sure to blaze, after covering a wet cloth to the insulation pipes of the units in order to prevent
it from burning and shrinking by heat.
12.Indoor unit capacity connectable to 1 branch is changed depending on the indoor unit type and connection
method. Please refer to the Installation Manual for more information.
13.For the refrigerant pipe size, refer to Installation Manual of outdoor units/heat source units.
14.The ambient relative humidity of the BC controller needs to be kept below 80%.

MEES17K069 Il-2 7
0000004506.BOOK 8 ページ 2017年12月22日 金曜日 午後1時49分

1. SPECIFICATIONS Indoor units

Model CMB-P1012V-JA
Number of branch 12
Power source 1-phase 220-230-240 V
50Hz 60Hz
Power input Cooling kW 0.186/0.211/0.236 0.150/0.168/0.186
Heating kW 0.090/0.102/0.114 0.072/0.081/0.090
Current input Cooling A 0.85/0.92/0.99 0.69/0.74/0.78
Heating A 0.42/0.44/0.48 0.33/0.36/0.38
External finish Galvanized steel plate
(Lower part drain pan: Pre-coated galvanized sheets + powder coating)
Connectable outdoor/heat source unit capacity P200 to P900
Model P80 or smaller
Indoor unit capacity connectable to 1 branch *12
(Use optional joint pipe combing 2 branches when the total unit capacity exceeds P81.)
External dimension H x W x D mm 246 x 1,135 x 639
in. 9-11/16 x 44-11/16 x 25-3/16
Refrigerant To outdoor/heat source unit Connectable unit capacity High press. pipe Low press. pipe
piping mm (in.) O.D. P200 15.88 (5/8) Brazed 19.05 (3/4) Brazed
diameter mm (in.) O.D. P250/P300 19.05 (3/4) Brazed 22.2 (7/8) Brazed
*13 mm (in.) O.D. P350 19.05 (3/4) Brazed or 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P400 to P500 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
22.2 (7/8) Brazed or 28.58 (1-1/8)
*13 mm (in.) O.D. P550 28.58 (1-1/8) Brazed
Brazed
22.2 (7/8) Brazed or 28.58 (1-1/8) 28.58 (1-1/8) Brazed or 34.93 (1-3/8)
*13 mm (in.) O.D. P600
Brazed Brazed
mm (in.) O.D. P650 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P700 to P800 28.58 (1-1/8) Brazed 34.93 (1-3/8) Brazed
mm (in.) O.D. P850/P900 28.58 (1-1/8) Brazed 41.28 (1-5/8) Brazed
To indoor unit Liquid pipe Gas pipe
Indoor unit Model 50 or smaller 6.35 (1/4) Brazed Indoor unit Model 50 or smaller 12.7 (1/2) Brazed
mm (in.) O.D. bigger than 50 9.52 (3/8) Brazed bigger than 50 15.88 (5/8) Brazed
(19.05 (3/4), 22.2 (7/8) with optional joint pipe used.)
Total down-stream Indoor
To other BC controller High press. pipe Liquid pipe Low press. pipe
unit capacity
mm (in.) O.D. to P200 15.88 (5/8) Brazed 9.52 (3/8) Brazed 19.05 (3/4) Brazed
mm (in.) O.D. P201 to P300 19.05 (3/4) Brazed 9.52 (3/8) Brazed 22.2 (7/8) Brazed
mm (in.) O.D. P301 to P350 19.05 (3/4) Brazed 12.7 (1/2) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P351 to P400 22.2 (7/8) Brazed 12.7 (1/2) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P401 to P600 22.2 (7/8) Brazed 15.88 (5/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P601 to P650 28.58 (1-1/8) Brazed 15.88 (5/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P651 to P800 28.58 (1-1/8) Brazed 19.05 (3/4) Brazed 34.93 (1-3/8) Brazed
mm (in.) O.D. P801 to P1000 28.58 (1-1/8) Brazed 19.05 (3/4) Brazed 41.28 (1-5/8) Brazed
mm (in.) O.D. P1001 or above 34.93 (1-3/8) Brazed 19.05 (3/4) Brazed 41.28 (1-5/8) Brazed
Field drain pipe size mm (in.) O.D. 32 (1-1/4)
Net weight kg (lbs) 56 (124)
Sound power level Rated operation
dB <A> 62(When P250 Outdoor/Heat source unit connected),65(P450),68(P700),69(P900)
(measured in anechoic room)
Defrost dB <A> 74
Sound pressure level Rated operation
dB <A> 44(When P250 Outdoor/Heat source unit connected),47(P450),50(P700),51(P900)
(measured in anechoic room)
Defrost dB <A> 56
Accessories Drain Connection pipe, Washer, Tie band
Remarks

Notes:
1.Installation/foundation work, electrical connection work, insulation work, power source switch, and other items
shall be referred to the Installation Manual.
2.The equipment is for R410A refrigerant.
3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away
from any indoor units.)
BC controller

4.Sound pressure/power level differs depending on the connected outdoor/heat source unit capacity or operation condition.
The sound pressure/power level at the rated operation is the value of the cooling mode.
5.The sound pressure/power level values were obtained in an anechoic room. Actual sound pressure level is usually
greater than that measured in anechoic room due to ambient noise and deflection sound.
6.The sound pressure level values were obtained at the location below 1.5m from the unit.
7.The solenoid valve switching sound is 56 dB (sound pressure level) regardless of the unit model.
8.Indoor units P100, P125, P140 can be connected to 1 branch. (In this case, cooling capacity decreases a little.)
9.Refrigerant piping diameter for connection of plural indoor units with 1 branch shall be referred to the
Installation Manual.
10.This unit is not designed for outside installations.
11.When blazing the pipes, be sure to blaze, after covering a wet cloth to the insulation pipes of the units in order to prevent
it from burning and shrinking by heat.
12.Indoor unit capacity connectable to 1 branch is changed depending on the indoor unit type and connection
method. Please refer to the Installation Manual for more information.
13.For the refrigerant pipe size, refer to Installation Manual of outdoor units/heat source units.
14.The ambient relative humidity of the BC controller needs to be kept below 80%.

MEES17K069 Il-2 8
0000004506.BOOK 9 ページ 2017年12月22日 金曜日 午後1時49分

1. SPECIFICATIONS Indoor units

Model CMB-P1016V-JA
Number of branch 16
Power source 1-phase 220-230-240 V
50Hz 60Hz
Power input Cooling kW 0.246/0.279/0.312 0.198/0.222/0.246
Heating kW 0.119/0.135/0.151 0.096/0.108/0.119
Current input Cooling A 1.12/1.22/1.30 0.90/0.97/1.03
Heating A 0.55/0.59/0.63 0.44/0.47/0.50
External finish Galvanized steel plate
(Lower part drain pan: Pre-coated galvanized sheets + powder coating)
Connectable outdoor/heat source unit capacity P200 to P900
Model P80 or smaller
Indoor unit capacity connectable to 1 branch *12
(Use optional joint pipe combing 2 branches when the total unit capacity exceeds P81.)
External dimension H x W x D mm 246 x 1,135 x 639
in. 9-11/16 x 44-11/16 x 25-3/16
Refrigerant To outdoor/heat source unit Connectable unit capacity High press. pipe Low press. pipe
piping mm (in.) O.D. P200 15.88 (5/8) Brazed 19.05 (3/4) Brazed
diameter mm (in.) O.D. P250/P300 19.05 (3/4) Brazed 22.2 (7/8) Brazed
*13 mm (in.) O.D. P350 19.05 (3/4) Brazed or 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P400 to P500 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
22.2 (7/8) Brazed or 28.58 (1-1/8)
*13 mm (in.) O.D. P550 28.58 (1-1/8) Brazed
Brazed
22.2 (7/8) Brazed or 28.58 (1-1/8) 28.58 (1-1/8) Brazed or 34.93 (1-3/8)
*13 mm (in.) O.D. P600
Brazed Brazed
mm (in.) O.D. P650 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P700 to P800 28.58 (1-1/8) Brazed 34.93 (1-3/8) Brazed
mm (in.) O.D. P850/P900 28.58 (1-1/8) Brazed 41.28 (1-5/8) Brazed
To indoor unit Liquid pipe Gas pipe
Indoor unit Model 50 or smaller 6.35 (1/4) Brazed Indoor unit Model 50 or smaller 12.7 (1/2) Brazed
mm (in.) O.D. bigger than 50 9.52 (3/8) Brazed bigger than 50 15.88 (5/8) Brazed
(19.05 (3/4), 22.2 (7/8) with optional joint pipe used.)
Total down-stream Indoor
To other BC controller High press. pipe Liquid pipe Low press. pipe
unit capacity
mm (in.) O.D. to P200 15.88 (5/8) Brazed 9.52 (3/8) Brazed 19.05 (3/4) Brazed
mm (in.) O.D. P201 to P300 19.05 (3/4) Brazed 9.52 (3/8) Brazed 22.2 (7/8) Brazed
mm (in.) O.D. P301 to P350 19.05 (3/4) Brazed 12.7 (1/2) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P351 to P400 22.2 (7/8) Brazed 12.7 (1/2) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P401 to P600 22.2 (7/8) Brazed 15.88 (5/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P601 to P650 28.58 (1-1/8) Brazed 15.88 (5/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P651 to P800 28.58 (1-1/8) Brazed 19.05 (3/4) Brazed 34.93 (1-3/8) Brazed
mm (in.) O.D. P801 to P1000 28.58 (1-1/8) Brazed 19.05 (3/4) Brazed 41.28 (1-5/8) Brazed
mm (in.) O.D. P1001 or above 34.93 (1-3/8) Brazed 19.05 (3/4) Brazed 41.28 (1-5/8) Brazed
Field drain pipe size mm (in.) O.D. 32 (1-1/4)
Net weight kg (lbs) 63 (139)
Sound power level Rated operation
dB <A> 62(When P250 Outdoor/Heat source unit connected),65(P450),68(P700),69(P900)
(measured in anechoic room)
Defrost dB <A> 74
Sound pressure level Rated operation
dB <A> 44(When P250 Outdoor/Heat source unit connected),47(P450),50(P700),51(P900)
(measured in anechoic room)
Defrost dB <A> 56
Accessories Drain Connection pipe, Washer, Tie band
Remarks

Notes:
1.Installation/foundation work, electrical connection work, insulation work, power source switch, and other items
shall be referred to the Installation Manual.
2.The equipment is for R410A refrigerant.
3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away
BC controller

from any indoor units.)


4.Sound pressure/power level differs depending on the connected outdoor/heat source unit capacity or operation condition.
The sound pressure/power level at the rated operation is the value of the cooling mode.
5.The sound pressure/power level values were obtained in an anechoic room. Actual sound pressure level is usually
greater than that measured in anechoic room due to ambient noise and deflection sound.
6.The sound pressure level values were obtained at the location below 1.5m from the unit.
7.The solenoid valve switching sound is 56 dB (sound pressure level) regardless of the unit model.
8.Indoor units P100, P125, P140 can be connected to 1 branch. (In this case, cooling capacity decreases a little.)
9.Refrigerant piping diameter for connection of plural indoor units with 1 branch shall be referred to the
Installation Manual.
10.This unit is not designed for outside installations.
11.When blazing the pipes, be sure to blaze, after covering a wet cloth to the insulation pipes of the units in order to prevent
it from burning and shrinking by heat.
12.Indoor unit capacity connectable to 1 branch is changed depending on the indoor unit type and connection
method. Please refer to the Installation Manual for more information.
13.For the refrigerant pipe size, refer to Installation Manual of outdoor units/heat source units.
14.The ambient relative humidity of the BC controller needs to be kept below 80%.

MEES17K069 Il-2 9
0000004506.BOOK 10 ページ 2017年12月22日 金曜日 午後1時49分

1. SPECIFICATIONS Indoor units

Model CMB-P1016V-KA
Number of branch 16
Power source 1-phase 220-230-240 V
50Hz 60Hz
Power input Cooling kW 0.246/0.279/0.312 0.198/0.222/0.246
Heating kW 0.119/0.135/0.151 0.096/0.108/0.119
Current input Cooling A 1.12/1.22/1.30 0.90/0.97/1.03
Heating A 0.55/0.59/0.63 0.44/0.47/0.50
External finish Galvanized steel plate
(Lower part drain pan: Pre-coated galvanized sheets + powder coating)
Connectable outdoor/heat source unit capacity P200 to P1100
Model P80 or smaller
Indoor unit capacity connectable to 1 branch *12
(Use optional joint pipe combing 2 branches when the total unit capacity exceeds P81.)
External dimension H x W x D mm 246 x 1,135 x 639
in. 9-11/16 x 44-11/16 x 25-3/16
Refrigerant To outdoor/heat source unit Connectable unit capacity High press. pipe Low press. pipe
piping mm (in.) O.D. P200 15.88 (5/8) Brazed 19.05 (3/4) Brazed
diameter mm (in.) O.D. P250/P300 19.05 (3/4) Brazed 22.2 (7/8) Brazed
*13 mm (in.) O.D. P350 19.05 (3/4) Brazed or 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P400 to P500 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
22.2 (7/8) Brazed or 28.58 (1-1/8)
*13 mm (in.) O.D. P550 28.58 (1-1/8) Brazed
Brazed
22.2 (7/8) Brazed or 28.58 (1-1/8) 28.58 (1-1/8) Brazed or 34.93 (1-3/8)
*13 mm (in.) O.D. P600
Brazed Brazed
mm (in.) O.D. P650 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P700 to P800 28.58 (1-1/8) Brazed 34.93 (1-3/8) Brazed
mm (in.) O.D. P850 to P1000 28.58 (1-1/8) Brazed 41.28 (1-5/8) Brazed
mm (in.) O.D. P1050/P1100 34.93 (1-3/8) Brazed 41.28 (1-5/8) Brazed
To indoor unit Liquid pipe Gas pipe
Indoor unit Model 50 or smaller 6.35 (1/4) Brazed Indoor unit Model 50 or smaller 12.7 (1/2) Brazed
mm (in.) O.D. bigger than 50 9.52 (3/8) Brazed bigger than 50 15.88 (5/8) Brazed
(19.05 (3/4), 22.2 (7/8) with optional joint pipe used.)
Total down-stream Indoor
To other BC controller High press. pipe Liquid pipe Low press. pipe
unit capacity
mm (in.) O.D. to P200 15.88 (5/8) Brazed 9.52 (3/8) Brazed 19.05 (3/4) Brazed
mm (in.) O.D. P201 to P300 19.05 (3/4) Brazed 9.52 (3/8) Brazed 22.2 (7/8) Brazed
mm (in.) O.D. P301 to P350 19.05 (3/4) Brazed 12.7 (1/2) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P351 to P400 22.2 (7/8) Brazed 12.7 (1/2) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P401 to P600 22.2 (7/8) Brazed 15.88 (5/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P601 to P650 28.58 (1-1/8) Brazed 15.88 (5/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P651 to P800 28.58 (1-1/8) Brazed 19.05 (3/4) Brazed 34.93 (1-3/8) Brazed
mm (in.) O.D. P801 to P1000 28.58 (1-1/8) Brazed 19.05 (3/4) Brazed 41.28 (1-5/8) Brazed
mm (in.) O.D. P1001 or above 34.93 (1-3/8) Brazed 19.05 (3/4) Brazed 41.28 (1-5/8) Brazed
Field drain pipe size mm (in.) O.D. 32 (1-1/4)
Net weight kg (lbs) 65 (144)
Sound power level Rated operation
dB <A> 56(When P300 Outdoor/Heat source unit connected),61(P550),63(P800),66(P1100)
(measured in anechoic room)
Defrost dB <A> 73
Sound pressure level Rated operation
dB <A> 38(When P300 Outdoor/Heat source unit connected),43(P550),45(P800),48(P1100)
(measured in anechoic room)
Defrost dB <A> 55
Accessories Drain Connection pipe, Washer, Tie band
Remarks

Notes:
1.Installation/foundation work, electrical connection work, insulation work, power source switch, and other items
shall be referred to the Installation Manual.
2.The equipment is for R410A refrigerant.
3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
BC controller

(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away
from any indoor units.)
4.Sound pressure/power level differs depending on the connected outdoor/heat source unit capacity or operation condition.
The sound pressure/power level at the rated operation is the value of the cooling mode.
5.The sound pressure/power level values were obtained in an anechoic room. Actual sound pressure level is usually
greater than that measured in anechoic room due to ambient noise and deflection sound.
6.The sound pressure level values were obtained at the location below 1.5m from the unit.
7.The solenoid valve switching sound is 56 dB (sound pressure level) regardless of the unit model.
8.Indoor units P100, P125, P140 can be connected to 1 branch. (In this case, cooling capacity decreases a little.)
9.Refrigerant piping diameter for connection of plural indoor units with 1 branch shall be referred to the
Installation Manual.
10.This unit is not designed for outside installations.
11.When blazing the pipes, be sure to blaze, after covering a wet cloth to the insulation pipes of the units in order to prevent
it from burning and shrinking by heat.
12.Indoor unit capacity connectable to 1 branch is changed depending on the indoor unit type and connection
method. Please refer to the Installation Manual for more information.
13.For the refrigerant pipe size, refer to Installation Manual of outdoor units/heat source units.
14.The ambient relative humidity of the BC controller needs to be kept below 80%.

MEES17K069 Il-2 10
0000004506.BOOK 11 ページ 2017年12月22日 金曜日 午後1時49分

1. SPECIFICATIONS Indoor units

Model CMB-P104V-KB
Number of branch 4
Power source 1-phase 220-230-240 V
50Hz 60Hz
Power input Cooling kW 0.060/0.068/0.076 0.048/0.054/0.060
Heating kW 0.030/0.034/0.038 0.024/0.027/0.030
Current input Cooling A 0.28/0.30/0.32 0.22/0.24/0.25
Heating A 0.14/0.15/0.16 0.11/0.12/0.13
External finish Galvanized steel plate
(Lower part drain pan: Pre-coated galvanized sheets + powder coating)
Connectable Main BC controller CMB-P108/1012/1016V-JA, CMB-P1016V-KA
The maximum number of connectable Sub BC controllers 11
The maximum connectable capacity of indoor units P350 for each
External dimension H x W x D mm 246 x 596 x 495
in. 9-11/16 x 23-1/2 x 19-1/2
Refrigerant To outdoor/heat source unit Connectable unit capacity High press. pipe Low press. pipe
piping mm (in.) O.D. - - -
diameter To indoor unit Liquid pipe Gas pipe
Indoor unit Model 50 or smaller 6.35 (1/4) Brazed Indoor unit Model 50 or smaller 12.7 (1/2) Brazed
mm (in.) O.D. bigger than 50 9.52 (3/8) Brazed bigger than 50 15.88 (5/8) Brazed
(19.05 (3/4), 22.2 (7/8) with optional joint pipe used.)
Total down-stream Indoor
To other BC controller High press. pipe Liquid pipe Low press. pipe
unit capacity
mm (in.) O.D. to P200 15.88 (5/8) Brazed 9.52 (3/8) Brazed 19.05 (3/4) Brazed
mm (in.) O.D. P201 to P300 19.05 (3/4) Brazed 9.52 (3/8) Brazed 22.2 (7/8) Brazed
mm (in.) O.D. P301 to P350 19.05 (3/4) Brazed 12.7 (1/2) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P351 to P400 22.2 (7/8) Brazed 12.7 (1/2) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P401 to P600 22.2 (7/8) Brazed 15.88 (5/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P601 to P650 28.58 (1-1/8) Brazed 15.88 (5/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P651 to P800 28.58 (1-1/8) Brazed 19.05 (3/4) Brazed 34.93 (1-3/8) Brazed
mm (in.) O.D. P801 to P1000 28.58 (1-1/8) Brazed 19.05 (3/4) Brazed 41.28 (1-5/8) Brazed
mm (in.) O.D. P1001 or above 34.93 (1-3/8) Brazed 19.05 (3/4) Brazed 41.28 (1-5/8) Brazed
Field drain pipe size mm (in.) O.D. 32 (1-1/4)
Net weight kg (lbs) 21 (47)
Sound power level Rated operation
dB <A> 56(When P200 Outdoor/Heat source unit connected),57(P250),59(P350)
(measured in anechoic room)
Defrost dB <A> 71
Sound pressure level Rated operation
dB <A> 38(When P200 Outdoor/Heat source unit connected),39(P250),40(P350)
(measured in anechoic room)
Defrost dB <A> 53
Accessories Drain Connection pipe, Washer, Tie band
Remarks

Notes:
1.Installation/foundation work, electrical connection work, insulation work, power source switch, and other items
shall be referred to the Installation Manual.
2.The equipment is for R410A refrigerant.
3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away
from any indoor units.)
4.Sound pressure/power level differs depending on the connected outdoor/heat source unit capacity or operation condition.
The sound pressure/power level at the rated operation is the value of the cooling mode.
5.The sound pressure/power level values were obtained in an anechoic room. Actual sound pressure level is usually
greater than that measured in anechoic room due to ambient noise and deflection sound.
6.The sound pressure level values were obtained at the location below 1.5m from the unit.
7.The solenoid valve switching sound is 56 dB (sound pressure level) regardless of the unit model.
8.Indoor units P100, P125, P140 can be connected to 1 branch. (In this case, cooling capacity decreases a little.)
9.Refrigerant piping diameter for connection of plural indoor units with 1 branch shall be referred to the
Installation Manual.
10.This unit is not designed for outside installations.
11.When blazing the pipes, be sure to blaze, after covering a wet cloth to the insulation pipes of the units in order to prevent
it from burning and shrinking by heat.
BC controller

12.Can't use singleness. (MAIN BC CONTROLLER is necessary)


13.The ambient relative humidity of the BC controller needs to be kept below 80%.

MEES17K069 Il-2 11
0000004506.BOOK 12 ページ 2017年12月22日 金曜日 午後1時49分

1. SPECIFICATIONS Indoor units

Model CMB-P108V-KB
Number of branch 8
Power source 1-phase 220-230-240 V
50Hz 60Hz
Power input Cooling kW 0.119/0.135/0.151 0.096/0.108/0.119
Heating kW 0.060/0.068/0.076 0.048/0.054/0.060
Current input Cooling A 0.55/0.59/0.63 0.44/0.47/0.50
Heating A 0.28/0.30/0.32 0.22/0.24/0.25
External finish Galvanized steel plate
(Lower part drain pan: Pre-coated galvanized sheets + powder coating)
Connectable Main BC controller CMB-P108/1012/1016V-JA, CMB-P1016V-KA
The maximum number of connectable Sub BC controllers 11
The maximum connectable capacity of indoor units P350 for each
External dimension H x W x D mm 246 x 596 x 495
in. 9-11/16 x 23-1/2 x 19-1/2
Refrigerant To outdoor/heat source unit Connectable unit capacity High press. pipe Low press. pipe
piping mm (in.) O.D. - - -
diameter To indoor unit Liquid pipe Gas pipe
Indoor unit Model 50 or smaller 6.35 (1/4) Brazed Indoor unit Model 50 or smaller 12.7 (1/2) Brazed
mm (in.) O.D. bigger than 50 9.52 (3/8) Brazed bigger than 50 15.88 (5/8) Brazed
(19.05 (3/4), 22.2 (7/8) with optional joint pipe used.)
Total down-stream Indoor
To other BC controller High press. pipe Liquid pipe Low press. pipe
unit capacity
mm (in.) O.D. to P200 15.88 (5/8) Brazed 9.52 (3/8) Brazed 19.05 (3/4) Brazed
mm (in.) O.D. P201 to P300 19.05 (3/4) Brazed 9.52 (3/8) Brazed 22.2 (7/8) Brazed
mm (in.) O.D. P301 to P350 19.05 (3/4) Brazed 12.7 (1/2) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P351 to P400 22.2 (7/8) Brazed 12.7 (1/2) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P401 to P600 22.2 (7/8) Brazed 15.88 (5/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P601 to P650 28.58 (1-1/8) Brazed 15.88 (5/8) Brazed 28.58 (1-1/8) Brazed
mm (in.) O.D. P651 to P800 28.58 (1-1/8) Brazed 19.05 (3/4) Brazed 34.93 (1-3/8) Brazed
mm (in.) O.D. P801 to P1000 28.58 (1-1/8) Brazed 19.05 (3/4) Brazed 41.28 (1-5/8) Brazed
mm (in.) O.D. P1001 or above 34.93 (1-3/8) Brazed 19.05 (3/4) Brazed 41.28 (1-5/8) Brazed
Field drain pipe size mm (in.) O.D. 32 (1-1/4)
Net weight kg (lbs) 28 (62)
Sound power level Rated operation
dB <A> 56(When P200 Outdoor/Heat source unit connected),57(P250),59(P350)
(measured in anechoic room)
Defrost dB <A> 71
Sound pressure level Rated operation
dB <A> 38(When P200 Outdoor/Heat source unit connected),39(P250),40(P350)
(measured in anechoic room)
Defrost dB <A> 53
Accessories Drain Connection pipe, Washer, Tie band
Remarks

Notes:
1.Installation/foundation work, electrical connection work, insulation work, power source switch, and other items
shall be referred to the Installation Manual.
2.The equipment is for R410A refrigerant.
3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away
from any indoor units.)
4.Sound pressure/power level differs depending on the connected outdoor/heat source unit capacity or operation condition.
The sound pressure/power level at the rated operation is the value of the cooling mode.
5.The sound pressure/power level values were obtained in an anechoic room. Actual sound pressure level is usually
greater than that measured in anechoic room due to ambient noise and deflection sound.
6.The sound pressure level values were obtained at the location below 1.5m from the unit.
7.The solenoid valve switching sound is 56 dB (sound pressure level) regardless of the unit model.
8.Indoor units P100, P125, P140 can be connected to 1 branch. (In this case, cooling capacity decreases a little.)
9.Refrigerant piping diameter for connection of plural indoor units with 1 branch shall be referred to the
Installation Manual.
10.This unit is not designed for outside installations.
11.When blazing the pipes, be sure to blaze, after covering a wet cloth to the insulation pipes of the units in order to prevent
it from burning and shrinking by heat.
12.Can't use singleness. (MAIN BC CONTROLLER is necessary)
BC controller

13.The ambient relative humidity of the BC controller needs to be kept below 80%.

MEES17K069 Il-2 12
0000004506.BOOK

2. EXTERNAL DIMENSIONS
Drain hose I.D.32(1-1/4")
(Accessory) Cutting point Cutting point Note 1. Suspension bolt(ø10) and nut(M10) prepare in the field. <Accessories>

MEES17K069
2. Take notice of service space as follows. • Drain hose I.D.32(1-1/4") ················ 1pc.
Note 4 Note 4
(Please give attention not to occupy service space by letting ducts • Tie band ······································ 3pcs.
• Square washer (with cushion) ·········· 4pcs.

30
and pipes through.)

12
3. Install this product in a location where noise (refrigerant noise) • Square washer ····························· 4pcs.
emitted by the unit will not disturb the neighbors.
20 (For use in quiet environments with low background noise,position
60
14 50 the BC CONTROLLER at least 5m away from any indoor units.)
Drain Piping Detail of X section Detail of Y section 4. Refer to the Installation Manual for refrigerant piping diameter size
when connecting plural indoor units with 1 branch.
5. Refer to the Installation Manual for connection pipe of outdoor unit
diameter size.
6.Refer to the Installation Manual for insulation of connection pipe and
CMB-P104, 106, 108V-J

Connection pipe of outdoor unit


13 ページ 2017年12月22日

drain piping.
(High pressure) 7.Refer to the Installation Manual for Installation of drain pan.
Note 5 8.Do not place the BC controller directly on the floor because the
drain pan needs to be installed in a tilted position.
金曜日

2. EXTERNAL DIMENSIONS

119

X 450 200

66
Control box

R1 screw Access
door
午後1時49分

450

304
429
29
(700)

298
(Lifting bolt pitch)

215
132
Service

68
250

space

100
Y
68 23 596
602
219
(Lifting bolt pitch)

Connection pipe of outdoor unit (250)


(Low pressure)
(100)

Note 5

102 60×A=B
60 Connection pipe of
indoor unit (Liquid)

11
120
Note 4

1 2 3 4 5 6 7 8
Service
space

246
Connection pipe of
indoor unit (Gas)

60 Note 4 (Note 2)
A B
CMB-P104V-J 3 180
(200)

60 72 60×A=B

Il-2
CMB-P106V-J 5 300
CMB-P108V-J 7 420
Unit: mm
Indoor units

13
BC controller
BC controller

Note 1. Suspension bolt(ø10) and nut(M10) prepare in the field. <Accessories>


Drain hose I.D.32(1-1/4") 2. Take notice of service space as follows. • Drain hose I.D.32(1-1/4") ················ 1pc.

MEES17K069
(Accessory) Cutting point Cutting point (Please give attention not to occupy service space by letting ducts • Tie band ······································ 3pcs.
0000004506.BOOK

Note 4 Note 4 and pipes through.) • Square washer (with cushion) ·········· 4pcs.
3. Install this product in a location where noise (refrigerant noise) • Square washer······························ 4pcs.
emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise,position

12
30
20 the BC CONTROLLER at least 5m away from any indoor units.)
60
14 50 4. Refer to the Installation Manual for refrigerant piping diameter size
Drain Piping Detail of X section Detail of Y section when connecting plural indoor units with 1 branch.
5. Refer to the Installation Manual for connection pipe of outdoor unit
CMB-P1012, 1016V-J

diameter size.
6.Refer to the Installation Manual for insulation of connection pipe and
Connection pipe of outdoor unit drain piping.
(High pressure) 7.Refer to the Installation Manual for Installation of drain pan.
8.Do not place the BC controller directly on the floor because the
Note 5 drain pan needs to be installed in a tilted position.
2. EXTERNAL DIMENSIONS
14 ページ 2017年12月22日

66
Control box
450 200
金曜日

89
R1 screw Access
door
450

437
573
Service
39 space
(700)
午後1時49分

374
(Lifting bolt pitch)

303

286
250

73
100
Y

68 23 A

219 B
(Lifting bolt pitch)

Connection pipe of outdoor unit (250)


(Low pressure)
Note 5
(100)

180 60×C=D Connection pipe of


120 60 indoor unit (Liquid)

11
Note 4

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

246
Connection pipe of
indoor unit (Gas)
Service
Note 4 space
60
60 150 60×C=D
A B C D (Note 2)
CMB-P1012V-J 911 938 11 660

Il-2
CMB-P1016V-J 1135 1161 15 900
(200)
Unit: mm
Indoor units

14
Note 1. Suspension bolt(ø10) and nut(M10) prepare in the field. <Accessories>
0000004506.BOOK

2. Take notice of service space as follows. • Drain hose I.D.32(1-1/4") ················1pc.


(Please give attention not to occupy service • Tie band ······································3pcs.

MEES17K069
space by letting ducts and pipes through.) • Square washer (with cushion) ··········4pcs.
Drain hose I.D.32(1-1/4")
(Accessory) Cutting point Cutting point 3. Please take service space for connection pipe of SUB BC CONTROLLER. • Square washer······························4pcs.
Note 5 Note 5 4. Install this product in a location where noise (refrigerant noise)
emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position
the BC CONTROLLER at least 5m away from any indoor units.)

12
5. Refer to the Installation Manual for refrigerant piping diameter size

30
20
60 when connecting plural indoor units with 1 branch.
14 50
6. Refer to the Installation Manual for connection pipe of outdoor unit
Drain Piping Detail of X section Detail of Y section
or SUB BC CONTROLLER diameter size.
7. Refer to the Installation Manual for insulation of connection pipe and
Connection pipe of outdoor unit drain piping.
15 ページ 2017年12月22日

(High pressure) 8. Refer to the Installation Manual for Installation of drain pan.
9. Do not place the BC controller directly on the floor because the drain
Note 6
CMB-P108, 1012, 1016V-JA

pan needs to be installed in a tilted position.


Connection pipe of SUB BC CONTROLLER
(High pressure)
金曜日

2. EXTERNAL DIMENSIONS

X Note 6

66
Control box
Connection pipe of SUB BC CONTROLLER
(Liquid)
65
89 Note 6
R1 screw
午後1時49分

450 200 250

437
573
Access
39 73 door

357

374
(Lifting bolt pitch)
278
450

303

286
Service
space
(700)

73
250

100
Y

68 23 A

219 B
(Lifting bolt pitch)
Connection pipe of outdoor unit Connection pipe of
(Low pressure) (300)
indoor unit (Liquid)
Note 6
(100)

Note 5
180 60×C=D 120
166 60

11
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Service space

246
Connection pipe of
indoor unit (Gas)
(Note 2,3)
Note 5
60
A B C D
(200)

60 150 60×C=D
CMB-P108V-JA 911 938 7 420
CMB-P1012V-JA 1135 1161 11 660

Il-2
CMB-P1016V-JA 1135 1161 15 900
Unit: mm
Indoor units

15
BC controller
BC controller

Note 1. Suspension bolt(ø10) and nut(M10) prepare in the field. <Accessories>


2. Take notice of service space as follows. • Drain hose I.D.32(1-1/4") ················1pc.
Drain hose I.D.32(1-1/4") (Please give attention not to occupy service • Tie band ······································3pcs.

MEES17K069
(Accessory) Cutting point Cutting point space by letting ducts and pipes through.) • Square washer (with cushion) ··········4pcs.
0000004506.BOOK

Note 6 Note 6 3. Please take service space for connection pipe of SUB BC CONTROLLER. • Square washer······························4pcs.
4. When using an outdoor unit-38HP(P950) or more, use this product.
5. Install this product in a location where noise (refrigerant noise)
emitted by the unit will not disturb the neighbors.

12
30
20 (For use in quiet environments with low background noise, position
60 the BC CONTROLLER at least 5m away from any indoor units.)
14 50 CMB-P1016V-KA
6. Refer to the Installation Manual for refrigerant piping diameter size
Drain Piping Detail of X section Detail of Y section
when connecting plural indoor units with 1 branch.
7. Refer to the Installation Manual for connection pipe of outdoor unit
or SUB BC CONTROLLER diameter size.
Connection pipe of outdoor unit 8. Refer to the Installation Manual for insulation of connection pipe and
(High pressure) drain piping.
Note 7 9. Refer to the Installation Manual for Installation of drain pan.
10. Do not place the BC controller directly on the floor because the drain Connection pipe of SUB BC CONTROLLER
(High pressure)
2. EXTERNAL DIMENSIONS

pan needs to be installed in a tilted position.


16 ページ 2017年12月22日

X Note 7

66
Control box
金曜日

Connection pipe of SUB BC CONTROLLER


89 (Liquid)
65
R1 screw Note 7

450 200 250

437
573
39 73
Access

357
午後1時49分

door

374
(Lifting bolt pitch)
278

303

286
450

Service
space
(700)

73
250

100
Y
68 23 1135

219 1161
(Lifting bolt pitch)
Connection pipe of outdoor unit
(Low pressure)
Note 7 (300)
(100)

180 60×15=900 120 Connection pipe of


166 60 indoor unit (Liquid)

11
Note 6

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

246
Connection pipe of Service space
indoor unit (Gas)
Note 6
60 (Note 2,3)
60 150 60×15=900
(200)

Il-2
Unit: mm
Indoor units

16
0000004506.BOOK

Note 1. Suspension bolt(ø10) and nut(M10) prepare in the field. <Accessories>


2. Take notice of service space as follows. • Drain hose I.D.32(1-1/4") ················ 1pc.
Drain hose I.D.32(1-1/4")

MEES17K069
(Accessory) (Please give attention not to occupy service space by letting ducts and • Tie band ······································ 3pcs.
Cutting point Cutting point
pipes through.) • Square washer (with cushion) ·········· 4pcs.
Note 5 Note 5
3. Can't use singleness. (MAIN BC CONTROLLER is necessary.) • Square washer ····························· 4pcs.

30
4. Install this product in a location where noise (refrigerant noise)

12
emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position
20
CMB-P104V-KB

60 the BC CONTROLLER at least 5m away from any indoor units.)


14 50
5. Refer to the Installation Manual for refrigerant piping diameter size
Drain Piping Detail of X section Detail of Y section when connecting plural indoor units with 1 branch.
6. Refer to the Installation Manual for connection pipe of MAIN BC CONTROLLER
or outdoor unit diameter size.
7.Refer to the Installation Manual for insulation of connection pipe and drain piping.
17 ページ 2017年12月22日

8.Refer to the Installation Manual for Installation of drain pan.


9.Do not place the BC controller directly on the floor because the drain pan needs
Connection pipe of MAIN BC CONTROLLER
to be installed in a tilted position.
金曜日

2. EXTERNAL DIMENSIONS

(High pressure)
Note 6

119

X 450 200

66
Control box
午後1時49分

R1 screw Access
door
35
450

304
429

298
(700)

(Lifting bolt pitch)

215
197
132
Service

68
250

space

100
Connection pipe of MAIN BC CONTROLLER
(Liquid) Y
29
Note 6 596
68 23
602
219 (Lifting bolt pitch)
Connection pipe of outdoor unit
(Low pressure) (250)
Note 6
(100)

102 60×3=180
120 60 Connection pipe of
indoor unit (Liquid)

11
Note 5

1 2 3 4

Service

246
space

60 Connection pipe of (Note 2)

Il-2
60 72 60×3=180 indoor unit (Gas)
(200)

Note 5
Unit: mm
Indoor units

17
BC controller
BC controller

Note1.Suspension bolt(ø10) and nut(M10) prepare in the field. <Accessories>

MEES17K069
Drain hose I.D.32(1-1/4") 2.Take notice of service space as follows. • Drain hose I.D.32(1-1/4") ··········1pc.
0000004506.BOOK

(Accessory) Cutting point Cutting point (Please give attention not to occupy service space by letting ducts and • Tie band ································3pcs.
pipes through.) • Square washer (with cushion) ····4pcs.
Note 5 Note 5
3.Can't use singleness. (MAIN BC CONTROLLER is necessary.) • Square washer ·······················4pcs.
4.Install this product in a location where noise (refrigerant noise)

30
12
emitted by the unit will not disturb the neighbors.

20
(For use in quiet environments with low background noise, position
the BC CONTROLLER at least 5m away from any indoor units.)
CMB-P108V-KB
60
14 50 5.Refer to the Installation Manual for refrigerant piping diameter size
Drain Piping Detail of X section Detail of Y section when connecting plural indoor units with 1 branch.
6.Refer to the Installation Manual for connection pipe of MAIN BC CONTROLLER
or outdoor unit diameter size.
7.Refer to the Installation Manual for insulation of connection pipe and drain piping.
8.Refer to the Installation Manual for Installation of drain pan.
9.Do not place the BC controller directly on the floor because the drain pan needs
Connection pipe of MAIN BC CONTROLLER
2. EXTERNAL DIMENSIONS
18 ページ 2017年12月22日

to be installed in a tilted position.


(High pressure)
Note 6
金曜日

119
X

66
Control box

R1 screw 450 200

35 Access
午後1時49分

door

304
429
450

298
(Lifting bolt pitch)

215
197
(700)

132
68
Service
space
250

100
Connection pipe of MAIN BC CONTROLLER
(Liquid) 29 Y
Note 6 596
68 23
602
219 (Lifting bolt pitch)
Connection pipe of outdoor unit
(Low pressure) (250)
(100)

Note 6

102 60×7=420
120 60 Connection pipe of
indoor unit (Liquid) Service

11
space
Note 5

1 2 3 4 5 6 7 8
(Note 2)
Connection pipe of
(200)

indoor unit (Gas)

246
Note 5

60

Il-2
60 72 60×7=420
Unit: mm
Indoor units

18
0000004506.BOOK

TR TB02
Indoor/outdoor

3. ELECTRICAL WIRING DIAGRAMS


S(SHIELD)

MEES17K069
20V~22V 220V~240V Transmission Line
M2
M1
3 1
1
2 CNTR
PS1 2 3
1 3 2 1 2 1 (Red)
CMB-P104V-J
3 T5 T1
1 1
CN03 CN02 CN26 1 1
CNP1 (Yellow) 1 2 2 SV1B
2 2
(Black) X02 3 3 3 SV1A
3 3
X01 5 4 4 SV1C
4 4
X30 7
3 T2
1 1 1
2 CN27(Red)
19 ページ 2017年12月22日

PS3 2 CNP3 SV2B


1 1 2 2
3 5 5
X04 3 3 3 SV2A
6 6
X03 5 4 4 SV2C
1 CN13 (Symbol explanation)
金曜日

7 7
2 (Red) X31 7 Symbol Name
1 1 T3 TR Transformer
CN28(Blue)
1 1 2 2 SV3B TH11,12,15,16 Thermister sensor
TH11 8 8
2 X06 SV3A
LEV1,3 Expansion valve
t° 3 3 3
10 1 9 9 PS1,3 Pressure sensor
3 X05 SV3C
5 4 4
TH12 10 10 Circuit
3. ELECTRICAL WIRING DIAGRAMS

4 CN10 X32 CONT.B BC controller


午後1時49分

t° 7 board
5 SW2 SW1 T4 Terminal block
1 1 TB01 (for power source)
CN29(Green)
6 CONT.B 1 2 2 SV4B Terminal block
11 11 TB02 (for Transmission)
7 X08 3 3 3 SV4A
12 12 SV1~4A,B,C Solenoid valve
8 SW4 X07 5 4 4 SV4C
13 13
T1~5 Terminal
X33 7 F01 Fuse AC250V 6.3A F
1 LD1:CPU in
operation Z1 Function setting connector
TH15 CN36(Green)
2
t° CN11 SW5 1
3 14 14
ZNR01 ZNR02 X21 Note 1. TB02 is transmission terminal block.
TH16 3
4 15 15
t° U U Never connect power line to it.
DSA 16 16
1 SW6 F01 2. The initial set values of switch on CONT. B are as follows.
Z1 2
TYP1
250VAC SW1:0
6.3A F
SW2:0
CN07 CN05
(Yellow) (Red)
1 2 3 4 5 6 1 2 3 4 5 6 1 3 5
CN12
TB01 TO NEXT INDOOR UNIT
L
M M N PULL BOX

LEV3 LEV1
FUSE(16A)

BREAKER(16A)

POWER SUPPLY
~220V-240V

Il-2
50Hz/60Hz
Indoor units

19
BC controller
BC controller

TR TB02 Indoor/outdoor
20V~22V 220V~240V S(SHIELD)
M2 Transmission line

M1

MEES17K069
3 1 1
0000004506.BOOK

2 2 CNTR
PS1 3
1 3 2 1 2 1
3 (Red)
T7 1 1 T1
CN03 CN02 CN26 1 1
CNP1 (Yellow) 1 2 2 SV1B
2 2
(Black)

CMB-P106V-J
X02 3 3 3 SV1A
3 3
X01 5 4 4 SV1C
4 4
X30 7
3 1 1 1 T2
2 2 CN27(Red)
PS3 CNP3 1 2 2 SV2B
1 5 5
3
X04 3 3 3 SV2A
6 6
X03 5 4 4 SV2C
1 CN13 7 7
2 (Red) X31 7

1 1 T3
CN28(Blue)
1
20 ページ 2017年12月22日

CONT.B 1 2 2 SV3B
TH11 8 8
2 X06 3 SV3A
t° 3 3
9 9
3 X05 4
5 4 SV3C
TH12 10 10
金曜日

4 X32 7
t° CN10
5 1 1 T4 (Symbol explanation)
CN29(Green)
6 10 1 1 2 2 SV4B Symbol Name
3. ELECTRICAL WIRING DIAGRAMS

11 11
7 X08 3 3 SV4A Transformer
3 TR
12 12
8 X07 4 4 SV4C
SW2 SW1 LD1:CPU in 5 TH11,12,15,16 Thermister sensor
13 13
operation X33 7 LEV1,3 Expansion valve
1
午後1時49分

TH15 1 1 T5 PS1,3 Pressure sensor


2 CN30(Black)
t° CN11 1 2 2 SV5B Circuit
3 SW4 ZNR01 ZNR02 14 14 CONT.B BC controller
TH16 X10 3 3 3 SV5A board
4 U U 15 15 Terminal block
t° X09 5 4 4 SV5C TB01
DSA 16 16 (for power source)
F01 X34 7
1 Terminal block
TYP1 SW5 TB02
Z1 2 (for Transmission)
250VAC 1 1 T6
CN31(Yellow)
6.3A F 1 2 2 SV6B SV1~6A,B,C Solenoid valve
1 1
T8
X12 3 3 3 SV6A
T1~8 Terminal
SW6 2 2
X11 5 4 4 SV6C F01 Fuse AC250V 6.3A F
3 3
X35 1
Z1 Function setting connector
4 4
X21 3
5 5

CN36(Green) 6 6

7 7

CN07 CN05 8 8
(Yellow) (Red)
1 2 3 4 5 6 1 2 3 4 5 6 1 3 5
Note 1. TB02 is transmission terminal block.
CN12 Never connect power line to it.
TB01 2. The initial set values of switch on CONT. B are as follows.
TO NEXT INDOOR UNIT
L SW1:0
M M
N PULL BOX
LEV3 LEV1
SW2:0
FUSE(16A)

BREAKER(16A)

Il-2
POWER SUPPLY
~220V-240V
50Hz/60Hz
Indoor units

20
0000004506.BOOK

MEES17K069
Note 1. TB02 is transmission terminal block. (Symbol explanation)
Never connect power line to it. Symbol Name
2. The initial set values of switch on CONT. B are as follows. TR Transformer
TH11,12,15,16 Thermister sensor
SW1:0
CMB-P108V-J
LEV1,3 Expansion valve
SW2:0
PS1,3 Pressure sensor
TR TB02 Indoor/outdoor
20V~22V 220V~240V S(SHIELD) REL.B Circuit Relay
M2 Transmission line
M1 CONT.B board BC controller
Terminal block
TB01 (for power source)
7 6 5 4 3 2 1
3 1 1
CN50
21 ページ 2017年12月22日

2 CNTR T9 Terminal block


PS1 2 3
1 3 2 1 2 1 1 3 (Red) TB02
3 1 1 T1 (for Transmission)
CN03 CN02 CN38 CN26 1 1
CNP1 (Yellow) 1 2 2 SV1B SV1~8A,B,C Solenoid valve
2 2
(Black) X02 3 3 3 SV1A
3 3
金曜日

X01 4 SV1C
T1~10 Terminal
5 4
4 4
X30 7 F01 Fuse AC250V 6.3A F
3 1 1 1 T2
2 2 CNP3
CN27(Red) Z1 Function setting connector
PS3 1 2 2 SV2B
1 3 5 5
X04 3 3 3 SV2A

SV8C
SV8A
SV8B
SV7C
SV7A
SV7B
6 6
X03 5 4 4 SV2C
1 CN13 7 7
2 (Red) X31 7 T8 T7
1 1 T3 4 3 2 1 4 3 2 1
3. ELECTRICAL WIRING DIAGRAMS

CN28(Blue)
午後1時49分

1 CONT.B 1 2 2 SV3B
TH11 8 8
2 X06 3 3 3 SV3A
t° 9 9
3 X05 5 4 4 SV3C T10 4 3 2 1 4 3 2 1
TH12 LD1:CPU in 1010
4 operation X32 7
t° CN10
5 1 1 T4
CN29(Green) 16 15 14 13 12 11 10 9 8 7 6 5 4
6 10 1 1 2 2 SV4B 16 15 14 13 12 11 10 9 8 7 6 5 4
1111
7 X08 3 3 3 SV4A
1212
8 SW2 SW1 X07 5 4 4 SV4C
1313
X33 7
1
TH15 1 1 T5
2 CN30(Black) 1 3 5 7 1 3 5 7 1 3 5 7 1 3 5 7
t° CN11 1 2 2 SV5B
3 SW4 1414
TH16 X10 3 3 3 SV5A
4 1515
X09
CN32

CN33(Red)

t° 4 4

CN35(Blue)
5 SV5C

X20
X19
X39
X18
X17
X38
X16
X15
X37
X14
X13
X36

CN34(Black)
ZNR01 ZNR02 1616
X34 7
1 SW5
Z1 TYP1 U U
2 1 1 T6
CN31(Yellow)
1 2 2 SV6B CN39
DSA F01 1 1
X12 3 3 3
SW6 3 SV6A REL.B
250VAC 2 2
X11 1
5 4 4 SV6C
6.3A F 3 3
X35 7 7 6 5 4 3 2 1

CN36(Green) CN52
1
X21 3

CN07 CN05
(Yellow) (Red)
1 2 3 4 5 6 1 2 3 4 5 6 1 3 5 TB01 TO NEXT INDOOR UNIT
CN12 L
N PULL BOX
POWER SUPPLY
~220V-240V
M M 50Hz/60Hz
FUSE(16A) BREAKER(16A)
LEV3 LEV1

Il-2
Indoor units

21
BC controller
BC controller

Note 1. TB02 is transmission terminal block.

MEES17K069
Never connect power line to it.
0000004506.BOOK

2. The initial set values of switch on CONT. B are as follows.


SW1:0
SW2:0
(Symbol explanation)
TR TB02
Symbol Name
S(SHIELD) Indoor/outdoor
20V~22V 220V~240V Transmission line Transformer
M2 TR
CMB-P1012,1016V-J
M1
TH11,12,15,16 Thermister sensor
T19
LEV1,3 Expansion valve
3 1 1
2 CNTR T17 T18 PS1,3 Pressure sensor
PS1 2 (Red) 3
1 3 2 1 3 2 1 2 1 1 3
3 CN38 1 1 T1
CNVCC1 CN03 CN02 CN26 11 REL.B Circuit Relay
CNP1 (Blue) (Yellow) 1 2 2 SV1B
22
(Black) X02 3 3 3 SV1A CONT.B board BC controller
22 ページ 2017年12月22日

33
X01 5 4 4 SV1C
44 Terminal block
X30 7 TB01
3
(for power source)
1 1 1 T2
PS3 2 2 CN27(Red)
CNP3 CNOUT1 1 2 2 SV2B Terminal block
1 3 55
金曜日

1 X04 3 3 3 SV2A
TB02 (for Transmission)
66
2 X03 5 4 4 SV2C

SV9A
SV9B
SV8A
SV8B
SV7A
SV7B

SV9C
SV8C
SV7C

SV10A
SV10B

SV10C
1 CN13 CONT. B 77 SV1~16A,B,C Solenoid valve
2 (Red) 3 X31 7
4 1 1 T3 T10 T9 T8 T7 T1~20 Terminal
CN28(Blue)
3. ELECTRICAL WIRING DIAGRAMS

1 5 1 2 2 SV3B
TH11 LD1:CPU in 88 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1
2 operation 6 X06 3 3 3 SV3A F01 Fuse AC250V 6.3A F
t° 99
3 7 X05 5 4 4 SV3C
TH12 1010 Z1 Function setting connector
4 8 X32 7
t° CN10 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1
5 1 1 T4
午後1時49分

10 1 1 CN29(Green)
6 1 2 2 SV4B
2 11 11
7 X08 3 3 3 SV4A 16 15 14 13 12 11 10 9 8 7 6 5 4
3 1212 16 15 14 13 12 11 10 9 8 7 6 5 4
8 SW2 SW1 X07 5 4 4 SV4C
4 1313
X33 7
1
TH15 CNOUT3 1 1 T5
2 CN30(Black)
t° CN11 1 2 2 SV5B
3 SW4 1414
X10 1 3 5 7 1 3 5 7 1 3 5 7 1 3 5 7
TH16 3 3 3 SV5A 1 1 T11
4 1515 CN40
t° X09 5 4 4 SV5C (Yellow) 1 2 2 SV11B
1616 1 3 3 2 1 11
X34 7 CNVCC2 X41 SV11A

X20
X19
X39
X18
X17
X38
X16
X15
X37
X14
X13
X36
1 ZNR01 ZNR02 3 3 3

CN39
22

CN32
SW5

CN33(Red)

CN35(Blue)
Z1 2 TYP1 (Blue)

CN34(Black)
1 1 T6 X40 5 4 4 SV11C
U U CN31(Yellow) 33
1 2 2 SV6B X42 7
11 1 1 T12
X12 3 3 3 SV6A CN41(Green)
22 1 2 2 SV12B
SW6 DSA F01 44
X11 5 4 4 SV6C X44
250VAC 33 3 3 3 SV12A
6.3A F X35 55
X43 5 4 4 SV12C
CN36(Green) 66
1 X45 7
X21 1 1 T13 T20
3 CN42
1 2 2 SV13B
77
X47 3 3 3 SV13A
88
X46 5 4 4 SV13C
CN07 CN05 99
(Yellow) X48 7
(Red) TO NEXT 1 1 T14
1 234 5 6 1 234 5 6 1 3 5 TB01 CN43(Red)
INDOOR UNIT POWER SUPPLY 1 2 2 SV14B
CN12 L 1010
N
~220V-240V REL. B X50 3 3 3 SV14A
PULL BOX 50Hz/60Hz 11 11
X49 5 4 4 SV14C
1212
X51 7 1 1 T15
M M FUSE(16A) BREAKER(16A) CN44(Yellow)
1 2 2 SV15B
1 1313
2 X53 3 3 3 SV15A
LEV3 LEV1 3 1414
4 X52 5 4 4 SV15C
CNOUT2 1515
5 X54
6 7 1 1
1616 T16
7 CN45(Green)
1 2 2 SV16B
8 11
X56 3 3 3 SV16A
1 22
2 X55 5 4 4 SV16C
CNOUT4 33
3 X57 7
4 44
55
66
77

Il-2
88 CMB-P1016V-J ONLY
Indoor units

22
TR TB02 Indoor/outdoor (Symbol explanation)
0000004506.BOOK

20V~22V 220V~240V S(SHIELD)


M2 Transmission line Symbol Name
M1

MEES17K069
TR Transformer
7 6 5 4 3 2 1 TH11,12,15,16 Thermister sensor
3 1 1
2 CN50 CNTR
PS1 2 3 T9 LEV1,3,4 Expansion valve
3 2 1 2 1 1 3 (Red)
1 3
1 1 T1
CN03 CN02 CN38 CN26 1 1 PS1,3 Pressure sensor
CNP1 (Yellow) 1 2 2 SV1B
2 2
(Black) X02 3 3 3 SV1A REL.B Circuit Relay
3 3
CMB-P108V-JA
X01 5 4 4 SV1C
4 4 CONT.B board BC controller
X30 7
3 1 1 1 T2 Terminal block
2 2
CN27(Red) TB01 (for power source)
PS3 CNP3 1 2 2 SV2B
1 3 5 5
X04 3 3 3 SV2A Terminal block
6 6
X03 5 4 4 SV2C
TB02
1 CN13 7 7
(for Transmission)
2 (Red) X31 7
23 ページ 2017年12月22日

SV1~8A,B,C Solenoid valve


1 1 T3
CN28(Blue)
1 1 2 2 SV3B SVM1,SVM1b Solenoid valve
TH11 8 8
2 X06 3 3
3 SV3A
t° 9 9 T1~11
3 X05 5 4 4 SV3C
Terminal
金曜日

TH12 10 10
4 X32 7 F01
t° CN10 Fuse AC250V 6.3A F
5 1 1 T4
CN29(Green) Z1 Function setting connector
6 1 2 2 SV4B
11 11
7 X08 3 3 3 SV4A
12 12
8 CONT.B X07 5 4 4 SV4C
13 13
X33 7 T11
1
SV8C
SV8A
SV8B
SV7C
SV7A
SV7B

TH15 LD1:CPU in 1 1
3. ELECTRICAL WIRING DIAGRAMS

T5 T10

SVM1

SVM1b
CN30(Black)
午後1時49分

2 operation
t° CN11 1 2 2 SV5B T8 T7
3 14 14
TH16 X10 3 3 3 SV5A
4 10 1 15 15 4 3 2 1 4 3 2 1 4 3 2 1
t° X09 5 4 4 SV5C
16 16
X34 7
1
Z1 TYP1 SW2 SW1
2 1 1 T6
CN31(Yellow) 4 3 2 1 4 3 2 1 4 3 2 1
1 2 2 SV6B
1 1
X12 3 3 3 SV6A
2 2
SW4 X11 8 7 6 5 4 3 2 1 16 15 14 13 12 11 10 9 8 7 6 5 4
5 4 4 SV6C
3 3 8 7 6 5 4 3 2 1 16 15 14 13 12 11 10 9 8 7 6 5 4
ZNR01 ZNR02 X35 7
U U
SW5
CN36(Green)
1
DSA
1 X21
F01 3
2 250VAC
3 CN08 1 3 5 7 1 3 5 7 1 3 5 7 1 3 5 7
M 6.3A F
4 (Green) SW6
CN46(Yellow)
5 1
LEV4 6 CN39
X60 3
X20
X19
X39
X18
X17
X38
X16
X15
X37
X14
X13
X36

3
CN32

CN33(Red)

CN35(Blue)
CN34(Black)

1 1

X62 3
CN07 CN05 7 6 5 4 3 2 1
(Yellow) X61 5
(Red)
1 2 3 4 5 6 1 2 3 4 5 6 1 3 5 CN52 REL. B
6 TO NEXT INDOOR UNIT
CN12 TB01
CN47
L
N PULL BOX
POWER SUPPLY
M M ~220V-240V
50Hz/60Hz
LEV3 LEV1 FUSE(16A) BREAKER(16A)

Note 1. TB02 is transmission terminal block.


Never connect power line to it.
2. The initial set values of switch on CONT. B are as follows.

Il-2
SW1:0
SW2:0
Indoor units

23
BC controller
BC controller

(Symbol explanation)
TR TB02 Indoor/outdoor Symbol Name

MEES17K069
20V~22V 220V~240V S(SHIELD)
M2 Transmission line
TR Transformer
0000004506.BOOK

M1
TH11,12,15,16 Thermister sensor
T19 LEV1,3,4 Expansion valve
3 1 1
2 CNTR T17 T18 PS1,3 Pressure sensor
PS1 2 (Red) 3
1 3 2 1 3 2 1 2 1 1 3
3 1 1 T1
CNVCC1 CN03 CN02 CN38 CN26 1 1 REL.B
CNP1 (Blue) (Yellow) 1 2 2 SV1B
Circuit Relay
2 2
(Black) CONT. B X02 3 3 3 SV1A board BC controller
10 1
3 3 CONT.B
X01 5 4 4 SV1C
LD1:CPU in 4 4
operation X30 7
Terminal block
3 1 SW2 SW1 1 1 T2 TB01 (for power source)
CMB-P1012,1016V-JA

2 2
CN27(Red)
PS3 CNP3 CNOUT1 1 2 2 SV2B
1 3 5 5 Terminal block

SV9C
SV9A
SV9B
SV8C
SV8A
SV8B
SV7C
SV7A
SV7B

SV10C
SV10A
SV10B
1 X04 3 3 3 SV2A TB02
6 6 (for Transmission)
1 SW4 2 X03 5 4 4 SV2C
CN13 7 7 T10 T9 T8 T7
2 (Red) 3 X31 7 SV1~16A,B,C
4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 Solenoid valve
4 1 1 T3
CN28(Blue)
1 5 1 2 2 SV3B SVM1,SVM1b
TH11 SW5 8 8 Solenoid valve
2 6 X06 3 3 3 SV3A
24 ページ 2017年12月22日

t° 9 9 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1
3 7 X05 5 4 4 SV3C T1~21 Terminal
TH12 10 10
4 8 X32 7
t° CN10 SW6 F01
5 1 1 T4 16 15 14 13 12 11 10 9 8 7 6 5 4 Fuse AC250V 6.3A F
1 CN29(Green) 16 15 14 13 12 11 10 9 8 7 6 5 4
6 1 2 2 SV4B
11 11
金曜日

7 2
Z1 Function setting connector
X08 3 3 3 SV4A
3 12 12
8 X07 5 4 4 SV4C
4 13 13
X33 7
1
TH15 CNOUT3 1 1 T5 1 3 5 7 1 3 5 7 1 3 5 7 1 3 5 7
3. ELECTRICAL WIRING DIAGRAMS

2 CN30(Black)
t° CN11 1 2 2 SV5B
3 14 14 1 3 3 2 1
TH16 X10 3 3 3 SV5A CNVCC2

X20
X19
X39
X18
X17
X38
X16
X15
X37
X14
X13
X36
15 15

CN32
CN39
4

CN33(Red)

CN35(Blue)
CN34(Black)
t° X09 5 4 4 SV5C (Blue)
16 16 CN40 1 1 T11
1 X34 7 (Yellow) SV11B
Z1 TYP1 1 2 2
1 1
午後1時49分

2 1 1 T6
CN31(Yellow) X41 3 3 3 SV11A
1 2 2 SV6B 2 2
1 1 X40 5 4 4 SV11C
X12 3 3 3 SV6A 3 3
1 2 2 X42 7
X11 5 4 4 SV6C 1 1 T12
2 3 3 CN41(Green)
3 ZNR01 ZNR02 1 2 2 SV12B
M CN08 X35 7 4 4
4 (Green) X44 3 SV12A
5 U U 5 5 3 3
LEV4 6 CN36(Green) X43 5 4 4 SV12C
1 6 6 CMB-P1016V-JA ONLY
DSA X45 7
1 F01 X21 3 1 1 T13
250VAC CN42 T20
2 1 2 2 SV13B
3 CN07 6.3A F CN46(Yellow) 7 7
M 4 1 X47 3 3 3 SV13A
(Yellow) 8 8
5 X60 X46 5 4 SV13C
LEV3 6 3 REL. B 9 9 4
X48 7
1 1 1 T14
TO NEXT CN43(Red)
1 2 2 SV14B
X62 3 INDOOR UNIT POWER SUPPLY 10 10
CN05 X50 3 3 3 SV14A
(Red) X61 5 TB01 ~220V-240V 11 11
1 2 3 4 5 6
PULL BOX 50Hz/60Hz X49 5 4 4 SV14C
1 3 5 6 L 12 12
CN12 N X51 7
1 1 T15
CN47 CN44(Yellow)
1 2 2 SV15B
FUSE(16A) BREAKER(16A) 13 13
1 X53 3 3 3 SV15A
2 14 14
M 3 X52 5 4 4 SV15C
15 15
4
LEV1 X54 7
5 CNOUT2 16 16 1 1 T16
6 CN45(Green)
1 2 2 SV16B
7 1 1
8 X56 3 3 3 SV16A
2 2
1 X55 5 4 4 SV16C
3 3
2 X57 7
3 CNOUT4 4 4
4 1 1 T21
5 5
2 2 SVM1
6 6
3 3
7 7
4 4 SVM1b
8 8
Note 1. TB02 is transmission terminal block.
Never connect power line to it.
2. The initial set values of switch on CONT. B are as follows.
SW1:0

Il-2
SW2:0
Indoor units

24
(Symbol explanation)
0000004506.BOOK

TR TB02 Indoor/outdoor Symbol Name


20V~22V 220V~240V S(SHIELD)
Transmission line

MEES17K069
M2 Transformer
M1
TR
TH11,12,15,16 Thermister sensor
3 CNTR(Red) 1 T19 LEV1,3,4 Expansion valve
1
2 CN38 T17 T18
PS1 2 3
1 3 2 1 3 2 1 2 1 3 1
3 1 1 T1 PS1,3 Pressure sensor
CNVCC1 CN03 CN02 CN26 1 1
CNP1 (Blue) (Yellow) 1 2 2 SV1B
2 2 REL.B Circuit Relay
(Black) X02 3 3 3 SV1A
10 1 3 3
X01 4 SV1C
CMB-P1016V-KA

5 4 CONT.B board BC controller


4 4
X30 7
3 1 SW2 SW1 1 1 T2 Terminal block
2 2 CONT. B CN27(Red) TB01
PS3 CNP3 1 2 2 SV2B (for power source)
1 3 5 5
X04 3 3 3 SV2A

SV9C
SV9A
SV9B
SV8C
SV8A
SV8B
SV7C
SV7A
SV7B

SV10C
SV10A
SV10B
6 6 Terminal block
SW4 X03 5 4 4 SV2C
1 CN13 7 7 TB02
2 (Red) X31 7
T10 T9 T8 T7 (for Transmission)
LD1:CPU in
25 ページ 2017年12月22日

1 1 T3 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1
operation CN28(Blue) SV1~16A,B,C Solenoid valve
1 1 2 2 SV3B
TH11 SW5 8 8
2 X06 3 3 3 SV3A SVM1,1b Solenoid valve
t° 9 9
3 CNOUT1 X05 5 4 4 SV3C 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1
TH12 1010
4 T1~21 Terminal
金曜日

1 X32 7
t° CN10 SW6
5 2 1 1 T4
CN29(Green) 16 15 14 13 12 11 10 9 8 7 6 5 4 F01 Fuse AC250V 6.3A F
6 3 1 2 2 SV4B 16 15 14 13 12 11 10 9 8 7 6 5 4
11 11
7 4 X08 3 3 3 SV4A
8
1212 Z1 Function setting connector
5 X07 5 4 4 SV4C
1313
6 X33 7
1
TH15 7 1 1 T5 1 3 5 7 1 3 5 7 1 3 5 7 1 3 5 7
2 CN30(Black)
t° CN11 8 1 2 2 SV5B
3 1414
1 3 3 2 1
3. ELECTRICAL WIRING DIAGRAMS

TH16 X10 3 3 3 SV5A


午後1時49分

X20
X19
X39
X18
X17
X38
X16
X15
X37
X14
X13
X36
4 1 1515 CNVCC2
X09

CN32
CN39
t° 5 4 4 SV5C (Blue)
1616

CN33(Red)

CN35(Blue)
CN34(Black)
2 X34 1 1 T11
1 7 CN40
Z1 TYP1 3 (Yellow) 1 2 2 SV11B
2 1 1 T6 1 1
4 CN31(Yellow) X41
1 2 2 SV6B 3 3 3 SV11A
1 1 2 2
X12 X40 5 4 4 SV11C
1 CNOUT3 3 3 3 SV6A 3 3
2 2 X42
2 X11 5 4 4 SV6C 7
3 3 1 1 T12
3 CN08 CN41(Green)
M 4 X35 7 1 2 2 SV12B
(Green) 4 4
5 X44 3 SV12A
LEV4 6 CN36(Green) 5 5 3 3
1 X43 5 4 4 SV12C
6 6
1 X21 3 X45 7
1 1 T13 T20
2 ZNR01 CN42
3 CN07 ZNR02 CN46(Yellow) 1 2 2 SV13B
M 7 7
4 (Yellow) 1 X47
U U 3 3 3 SV13A
5 X60 8 8
LEV3 6 3 X46 5 4 4 SV13C
9 9
DSA X48 7
F01 CN47 1 1 T14
1 CN43(Red)
250VAC 1 SV14B
CN05 6.3A F X62 REL. B 10 10 2 2
3
(Red) X50 3 3 3 SV14A
X61 5 11 11
1 2 3 4 5 6 1 3 5 X49 5 4 SV14C
12 12 4
6 TO NEXT
CN12 TB01 INDOOR UNIT X51 7
POWER SUPPLY 1 1 T15
L ~220V-240V CN44(Yellow) SV15B
1 2 2
N PULL BOX 50Hz/60Hz 13 13
X53 3 3 3 SV15A
M 14 14
X52 5 4 4 SV15C
15 15
LEV1 X54 7
16 16 1 1 T16
FUSE(16A) BREAKER(16A) CN45(Green)
1 2 2 SV16B
1 1 1
2 X56 3 3 3 SV16A
3 2 2
X55 5 4 4 SV16C
4 3 3
5 CNOUT2 X57 7
6 4 4 T21
1 1
7 5 5
8 2 2 SVM1
6 6
1 3 3
2 7 7
CNOUT4 4 4 SVM1b
3 8 8
4

Note 1. TB02 is transmission terminal block.


Never connect power line to it.
2. The initial set values of switch on CONT. B are as follows.

Il-2
SW1:0
SW2:0
Indoor units

25
BC controller
BC controller

TR TB02 Indoor/outdoor
20V~22V 220V~240V S(SHIELD)
Transmission line

MEES17K069
M2
0000004506.BOOK

M1

CNTR
3 2 1 2 1 (Red)
CN03 CN02 T5 1 1 T1 CMB-P104V-KB
CN26 1 1
(Yellow) 1 2 2 SV1B
2 2
X02 3 3 3 SV1A
3 3
X01 5 4 4 SV1C
4 4
X30 7
3 1 1 1 T2
2 2 CN27(Red)
PS3 CNP3
1 1 2 2 SV2B
3 5 5
X04 (Symbol explanation)
26 ページ 2017年12月22日

3 3 3 SV2A
6 6
X03 SV2C
Symbol Name
1 5 4 4
CN13 7 7 TR Transformer
2 (Red) X31 7
10 1 TH12,15,16 Thermister sensor
金曜日

1 1 T3
CN28(Blue) LEV3 Expansion valve
1 1 2 2 SV3B
8 8 Circuit
2 X06 CONT.B BC controller
3. ELECTRICAL WIRING DIAGRAMS

SW2 SW1 CONT.B 3 3 3 SV3A board


9 9
3 X05 5 4 4 SV3C Terminal block
TH12 10 10 TB01 (for power source)
4 X32 7
t° CN10 Terminal block
LD1:CPU in TB02
午後1時49分

5 1 1 T4 (for Transmission)
SW4 operation CN29(Green)
6 1 2 2 SV4B SV1~4A,B,C Solenoid valve
11 11
7 X08 3 3 SV4A
T1~5 Terminal
3
12 12 F01
8 X07 4 4 SV4C
Fuse AC250V 6.3A F
5
SW5 13 13 Z1 Function setting connector
X33 7
1 PS3 Pressure sensor
TH15
2
t° CN11
3 SW6 ZNR01 ZNR02 14 14
TH16 Note 1. TB02 is transmission terminal block.
4 U U 15 15
t° Never connect power line to it.
16 16
1 2. The initial set values of switch on CONT. B are as follows.
TYP1 DSA
Z1 2 F01 SW1:0
250VAC
CN07
6.3A F SW2:0
(Yellow)
1 2 3 4 5 6 1 3 5
TO NEXT
CN12 TB01 INDOOR UNIT
L
N PULL BOX
M
FUSE(16A)
LEV3
BREAKER(16A)

POWER SUPPLY
~220V-240V

Il-2
50Hz/60Hz
Indoor units

26
0000004506.BOOK

Note 1.TB02 is transmission terminal block. (Symbol explanation)


Never connect power line to it. Symbol Name

MEES17K069
2. The initial set values of switch on CONT. B are as follows. TR Transformer
SW1:0 TH12,15,16 Thermister sensor
SW2:0 LEV3 Expansion valve
PS3 Pressure sensor
REL.B
CMB-P108V-KB
TR TB02 Circuit Relay
Indoor/outdoor
20V~22V 220V~240V S(SHIELD)
M2 Transmission line CONT.B board BC controller
M1 Terminal block
TB01 (for power source)
7654321 Terminal block
1 TB02
CN50 CNTR T9 (for Transmission)
3
27 ページ 2017年12月22日

3 2 1 2 1 1 3(Red)
1 1 T1 SV1~8A,B,C Solenoid valve
CN03 CN02 CN38 CN26 1 1
(Yellow) 1 2 2 SV1B
2 2 T1~10 Terminal
X02 3 3 3 SV1A
3 3
金曜日

X01 5 4 4 SV1C F01 Fuse AC250V 6.3A F


4 4
X30 7 Z1 Function setting connector
3 1 1 1 T2
2 2
CN27(Red)
PS3 CNP3 1 2 2 SV2B
1 3 5 5
X04 3 3 3 SV2A
SV8C
SV8A
SV8B
SV7C
SV7A
SV7B

6 6
1 X03 5 4 4 SV2C
CN13 7 7
2 (Red) X31 7 T8 T7
3. ELECTRICAL WIRING DIAGRAMS
午後1時49分

1 1 T3 4 3 2 1 4 3 2 1
1
CN28(Blue)
CONT.B 1 2 2 SV3B
8 8
2 X06 3 3 3 SV3A
9 9
3 X05 5 4 4 SV3C T10 4 3 2 1 4 3 2 1
TH12 LD1:CPU in 10 10
4 operation X32 7
t˚ CN10
5 1 1 T4
6 10 1
CN29(Green) 16 15 14 13 12 11 10 9 8 7 6 5 4
1 2 2 SV4B 16 15 14 13 12 11 10 9 8 7 6 5 4
11 11
7 X08 3 3 3 SV4A
12 12
8 SW2 SW1 X07 5 4 4 SV4C
13 13
X33 7
1
TH15 1 1 T5
2 CN30(Black) 1 3 5 7 1 3 5 7 1 3 5 7 1 3 5 7
t˚ CN11 1 2 2 SV5B
3 SW4 14 14
TH16 X10 3 3 3 SV5A
4 15 15
X20
X19
X39
X18
X17
X38
X16
X15
X37
X14
X13
X36

t˚ X09 5 4 4 SV5C
CN32

ZNR01 ZNR02 16 16
CN35(Blue)
CN33(Red)

CN34(Black)

1 SW5 X34 7
Z1 TYP1 U U
2 1 1 T6
CN31(Yellow)
1 2 2 SV6B CN39
DSA F01 1 1
250VAC X12 3 3 3 SV6A 3
SW6 2 2 REL.B
6.3A F X11 4 4 SV6C
1
5
3 3
X35 7 7 6 5 4 3 2 1

CN36(Green) CN52
1
X21 3

CN07
(Yellow)
1 2345 6 1 3 5 TB01 TO NEXT INDOOR UNIT
CN12 L
N PULL BOX
POWER SUPPLY
~220V-240V
M 50Hz/60Hz
FUSE(16A) BREAKER(16A)
LEV3

Il-2
Indoor units

27
BC controller
0000004506.BOOK 28 ページ 2017年12月22日 金曜日 午後1時49分

4. SOUND LEVELS Indoor units

4-1. Sound levels in cooling mode


4. SOUND LEVELS

Measurement condition Sound level of CMB-P1016V-KA


90
25% 50%
75% 100%

80

Octave band sound level (dB)


70
NC -70

60
NC -60

50
NC -50
1.5m

40
NC -40

30
NC -30

20 Approximate minimum
audible limit on NC -20
Measurement location continuous noise
10
63 125 250 500 1k 2k 4k 8k
■Cooling operation Octave band central frequency (Hz)
Total down-stream Indoor capacity 63 125 250 500 1k 2k 4k 8k dB(A)
25% 34.0 31.0 34.5 33.5 29.5 32.5 30.5 22.5 38.0
50% 35.0 36.5 41.0 38.0 36.0 37.5 34.0 26.0 43.0
75% 35.0 38.5 43.5 40.0 38.0 39.5 36.0 27.0 45.0
100% 36.0 42.0 47.0 43.0 41.5 42.5 38.0 29.0 48.0

Sound level of CMB-P104-1016V-J Sound level of CMB-P104,108V-KB


90 90
25% 50% 25% 50%
75% 100% 75% 100%

80 80
Octave band sound level (dB)

Octave band sound level (dB)

70 70
NC -70 NC -70

60 60
NC -60 NC -60

50 50
NC -50 NC -50

40 40
NC -40 NC -40

30 30
NC -30 NC -30

20 Approximate minimum 20 Approximate minimum


audible limit on NC -20 audible limit on NC -20
continuous noise continuous noise
10 10
63 125 250 500 1k 2k 4k 8k 63 125 250 500 1k 2k 4k 8k
■Cooling operation Octave band central frequency (Hz) ■Cooling operation Octave band central frequency (Hz)
Total down-stream Indoor capacity 63 125 250 500 1k 2k 4k 8k dB(A) Total down-stream Indoor capacity 63 125 250 500 1k 2k 4k 8k dB(A)
25% 31.5 24.0 28.5 27.5 28.0 26.0 25.0 19.0 33.0 25% 31.5 24.0 28.5 27.5 28.0 26.0 25.0 19.0 33.0
50% 33.5 29.0 33.0 31.5 32.0 31.0 31.5 25.0 38.0 50% 33.5 29.0 33.0 31.5 32.0 31.0 31.5 25.0 38.0
75% 33.0 29.5 34.0 32.0 32.0 32.5 33.0 26.0 39.0 75% 33.0 29.5 34.0 32.0 32.0 32.5 33.0 26.0 39.0
100% 31.5 30.0 34.0 32.0 32.0 33.5 35.0 27.5 40.0 100% 31.5 30.0 34.0 32.0 32.0 33.5 35.0 27.5 40.0

Sound level of CMB-P108-1016V-JA


90
25% 50%
75% 100%

80
Octave band sound level (dB)

70
NC -70

60
BC controller

NC -60

50
NC -50

40
NC -40

30
NC -30

20 Approximate minimum
audible limit on NC -20
continuous noise
10
63 125 250 500 1k 2k 4k 8k
■Cooling operation Octave band central frequency (Hz)
Total down-stream Indoor capacity 63 125 250 500 1k 2k 4k 8k dB(A)
25% 37.0 37.5 40.5 37.5 35.5 39.5 35.5 29.5 44.0
50% 38.0 40.0 43.5 40.5 39.5 42.5 38.0 32.0 47.0
75% 39.0 43.0 46.0 43.0 43.0 45.5 41.0 34.5 50.0
100% 39.0 44.0 47.0 44.0 44.5 46.0 42.5 35.5 51.0

Depending on the operation conditions, the unit generates noise caused by valve actuation, refrigerant flow, and
pressure changes when operating normally. Please consider to avoid location where quietness is required.

MEES17K069 Il-2 28
0000004506.BOOK 29 ページ 2017年12月22日 金曜日 午後1時49分

4. SOUND LEVELS Indoor units

4-2. Sound levels in heating mode

Measurement condition Sound level of CMB-P1016V-KA


90
25% 50%
75% 100%

80

Octave band sound level (dB)


70
NC -70

60
NC -60

50
NC -50
1.5m

40
NC -40

30
NC -30

20 Approximate minimum
audible limit on NC -20
Measurement location continuous noise
10
63 125 250 500 1k 2k 4k 8k
■Heating operation Octave band central frequency (Hz)
Total down-stream Indoor capacity 63 125 250 500 1k 2k 4k 8k dB(A)
25% 39.0 41.0 42.5 40.5 40.5 41.0 40.5 42.0 48.0
50% 41.0 45.0 46.5 44.5 44.0 45.0 43.0 42.0 51.0
75% 41.5 46.5 48.0 45.5 45.5 46.0 43.5 42.5 52.0
100% 43.0 49.0 51.0 48.0 47.5 48.5 44.5 42.5 54.0

Sound level of CMB-P104-1016V-J Sound level of CMB-P104,108V-KB


90 90
25% 50% 25% 50%
75% 100% 75% 100%

80 80
Octave band sound level (dB)

Octave band sound level (dB)

70 70
NC -70 NC -70

60 60
NC -60 NC -60

50 50
NC -50 NC -50

40 40
NC -40 NC -40

30 30
NC -30 NC -30

20 Approximate minimum 20 Approximate minimum


audible limit on NC -20 audible limit on NC -20
continuous noise continuous noise
10 10
63 125 250 500 1k 2k 4k 8k 63 125 250 500 1k 2k 4k 8k
■Heating operation Octave band central frequency (Hz) ■Heating operation Octave band central frequency (Hz)
Total down-stream Indoor capacity 63 125 250 500 1k 2k 4k 8k dB(A) Total down-stream Indoor capacity 63 125 250 500 1k 2k 4k 8k dB(A)
25% 32.0 30.0 39.0 37.5 41.0 36.0 32.5 32.5 44.0 25% 32.0 30.0 39.0 37.5 41.0 36.0 32.5 32.5 44.0
50% 35.5 32.0 42.0 39.0 43.0 38.0 34.0 34.5 46.0 50% 35.5 32.0 42.0 39.0 43.0 38.0 34.0 34.5 46.0
75% 37.5 33.5 43.5 39.5 44.0 39.5 34.5 35.0 47.0 75% 37.5 33.5 43.5 39.5 44.0 39.5 34.5 35.0 47.0
100% 44.5 37.0 48.5 41.0 47.0 43.0 35.5 36.5 50.0 100% 44.5 37.0 48.5 41.0 47.0 43.0 35.5 36.5 50.0

Sound level of CMB-P108-1016V-JA


90
25% 50%
75% 100%

80
Octave band sound level (dB)

70
NC -70

60
BC controller

NC -60

50
NC -50

40
NC -40

30
NC -30

20 Approximate minimum
audible limit on NC -20
continuous noise
10
63 125 250 500 1k 2k 4k 8k
■Heating operation Octave band central frequency (Hz)
Total down-stream Indoor capacity 63 125 250 500 1k 2k 4k 8k dB(A)
25% 38.5 43.0 47.0 41.5 41.5 42.0 40.5 43.0 49.0
50% 40.5 48.0 51.5 46.0 45.0 45.0 42.0 45.0 52.0
75% 42.0 51.5 54.5 49.0 47.5 47.0 42.5 45.5 54.0
100% 42.5 53.0 56.0 50.5 48.5 47.5 43.0 46.0 55.0

Depending on the operation conditions, the unit generates noise caused by valve actuation, refrigerant flow, and
pressure changes when operating normally. Please consider to avoid location where quietness is required.

MEES17K069 Il-2 29
0000004506.BOOK 30 ページ 2017年12月22日 金曜日 午後1時49分

4. SOUND LEVELS Indoor units

4-3. Sound levels in defrost mode

Measurement condition Sound level of CMB-P1016V-KA


90
(E)P200-(E)P300 (E)P350
(E)P400-(E)P600 (E)P650
(E)P700-(E)P800 (E)P850
80 (E)P900 (E)P950-(E)P1100

Octave band sound level (dB)


70
NC -70

60
NC -60

50
NC -50
1.5m

40
NC -40

30
NC -30

20 Approximate minimum
audible limit on NC -20
Measurement location continuous noise
10
63 125 250 500 1k 2k 4k 8k
■Defrost operation Octave band central frequency (Hz)
Capacity of connected outdoor unit 63 125 250 500 1k 2k 4k 8k dB(A)
(E)P200-(E)P300 31.5 44.5 46.5 39.5 40.5 46.5 49.5 52.0 55.0
(E)P350 34.0 46.5 48.5 41.5 42.0 46.5 50.0 51.0 55.0
(E)P400-(E)P600 36.5 49.0 51.5 44.0 43.5 47.5 50.0 49.0 55.0
(E)P650 37.5 50.0 52.5 44.5 44.0 47.5 50.0 48.0 55.0
(E)P700-(E)P800 38.5 51.0 53.5 45.5 44.5 47.5 50.0 47.0 55.0
(E)P850 39.0 51.5 53.5 46.0 45.0 47.0 50.0 47.0 55.0
(E)P900 39.5 51.5 54.0 46.0 45.0 47.0 50.0 46.5 55.0
(E)P950-(E)P1100 40.0 52.0 54.5 46.5 45.0 47.5 49.5 46.0 55.0

Sound level of CMB-P104-1016V-J Sound level of CMB-P104,108V-KB


90 90
(E)P200-(E)P300 (E)P350 (E)P200-(E)P300 (E)P350

80 80
Octave band sound level (dB)

Octave band sound level (dB)

70 70
NC -70 NC -70

60 60
NC -60 NC -60

50 50
NC -50 NC -50

40 40
NC -40 NC -40

30 30
NC -30 NC -30

20 Approximate minimum 20 Approximate minimum


audible limit on NC -20 audible limit on NC -20
continuous noise continuous noise
10 10
63 125 250 500 1k 2k 4k 8k 63 125 250 500 1k 2k 4k 8k
Octave band central frequency (Hz) Octave band central frequency (Hz)

■Defrost operation ■Defrost operation


Capacity of connected outdoor unit 63 125 250 500 1k 2k 4k 8k dB(A) Capacity of connected outdoor unit 63 125 250 500 1k 2k 4k 8k dB(A)
(E)P200-(E)P300 45.5 47.5 50.5 44.5 43.0 42.0 37.5 26.0 49.0 (E)P200-(E)P300 45.5 47.5 50.5 44.5 43.0 42.0 37.5 26.0 49.0
(E)P350 47.0 47.0 51.0 49.0 48.0 46.5 41.5 30.5 53.0 (E)P350 47.0 47.0 51.0 49.0 48.0 46.5 41.5 30.5 53.0

Sound level of CMB-P108-1016V-JA


90
(E)P200-(E)P300 (E)P350
(E)P400-(E)P600 (E)P650
(E)P700-(E)P800 (E)P850
80 (E)P900
Octave band sound level (dB)

70
NC -70

60
BC controller

NC -60

50
NC -50

40
NC -40

30
NC -30

20 Approximate minimum
audible limit on NC -20
continuous noise
10
63 125 250 500 1k 2k 4k 8k
■Defrost operation Octave band central frequency (Hz)
Capacity of connected outdoor unit 63 125 250 500 1k 2k 4k 8k dB(A)
(E)P200-(E)P300 37.5 49.0 51.0 45.0 43.0 45.0 48.0 45.0 53.0
(E)P350 40.0 50.5 53.5 47.0 45.0 46.5 50.0 47.0 55.0
(E)P400-(E)P600 41.5 51.0 54.5 48.0 46.5 47.0 51.5 47.0 56.0
(E)P650 42.0 51.0 54.5 48.0 47.0 46.5 51.5 47.5 56.0
(E)P700-(E)P800 42.0 50.5 55.0 48.0 47.0 46.5 51.5 47.0 56.0
(E)P850 42.0 50.5 55.0 48.0 47.0 46.5 51.5 47.0 56.0
(E)P900 42.0 50.5 55.0 48.0 47.0 46.0 51.5 47.0 56.0

Depending on the operation conditions, the unit generates noise caused by valve actuation, refrigerant flow, and
pressure changes when operating normally. Please consider to avoid location where quietness is required.

MEES17K069 Il-2 30
0000004506.BOOK 31 ページ 2017年12月22日 金曜日 午後1時49分

5. ELECTRICAL CHARACTERISTICS Indoor units


5. ELECTRICAL CHARACTERISTICS

Symbols: MCA (Max. Circuit Amps), MFA (Max. Fuse Amps), RLA (Rated Load Amps)
Power supply
BC controller RLA(A)
Hz Volts Range+-10% MCA(A) MFA(A)
220 0.31
CMB-P104V-J 230 0.45 0.34
240 0.36
220 0.45
CMB-P106V-J 230 0.65 0.48
240 0.52
220 0.58
CMB-P108V-J 230 0.85 0.63
240 0.68
220 0.85
CMB-P1012V-J 230 1.24 0.92
240 0.99
220 1.12
CMB-P1016V-J 230 1.63 1.22
240 1.30
220 0.58
Max.: 264V
CMB-P108V-JA 50/60 230 0.85 15 0.63
Min.: 198V
240 0.68
220 0.85
CMB-P1012V-JA 230 1.24 0.92
240 0.99
220 1.12
CMB-P1016V-JA 230 1.63 1.22
240 1.30
220 1.12
CMB-P1016V-KA 230 1.63 1.22
240 1.30
220 0.28
CMB-P104V-KB 230 0.40 0.30
240 0.32
220 0.55
CMB-P108V-KB 230 0.79 0.59
240 0.63

BC controller

MEES17K069 Il-2 31
0000004506.BOOK 32 ページ 2017年12月22日 金曜日 午後1時49分

6. OPTIONAL PARTS Indoor units

6-1. JOINT and REDUCER


6. OPTIONAL PARTS

CITY MULTI units can be easily connected by using Joint sets and Reducer sets provided by Mitsubishi Electric. Refer to section
"Piping Design" or the Installation Manual that comes with the Joint set or Reducer set for how to install the Joint set or Reducer set.

CMY-Y102SS-G2 mm
For Gas pipe: <Deformed pipe(Accessory)> For Liquid pipe:
ø15.88 ø12.7
(Outside diameter) <Deformed pipe(Accessory)>

28
ø15.88
ø19.05 ø15.88 ø9.52
ø19.05 (Outside diameter) ø9.52 ø6.35
ø19.05 ø9.52
30

ø9.52 (Outside diameter)

18
30
20
(2 Pcs.) 36
58 (2 Pcs.)
ø19.05 ø12.7
(Outside diameter)

*Pipe diameter is indicated by inside diameter. 37

CMY-Y102LS-G2 <Deformed pipe(Accessory)> mm


ø28.58
For Gas pipe: ø19.05 ø12.7
ø25.4
(Outside diameter)
For Liquid pipe:
(Outside diameter)

<Deformed pipe(Accessory)>
37 54
ø19.05 ø15.88 (2 Pcs.)
ø25.4 ø19.05
(Outside diameter) (Outside diameter) ø9.52
ø6.35
(Outside diameter)
ø19.05
30 ø9.52 20
ø25.4 41
ø25.4 ø19.05 ø22.2 (2 Pcs.) ø12.7
ø12.7
39

20

(Outside diameter) ø25.4 ø15.88 ø12.7 ø9.52


(Outside diameter) (Outside diameter)
40
54
76 23
ø25.4 ø22.2 45
(Outside diameter) (2 Pcs.)

42
*Pipe diameter is indicated by inside diameter. (2 Pcs.)

CMY-R101S-G mm
ø28.6
43

ø28.6
ø28.6
86

ø28.6 ø28.6
(Outside diameter) (Outside diameter)

ø22.2 ø19.05
80 80
(2 Pcs.) (2 Pcs.) <Accessory>
• Cover ··········1 Pcs.
• Band ··········3 Pcs.
Note. Pipe diameter is indicated by inside diameter.

CMY-R102S-G mm
ø41.28
BC controller

58

ø41.28
ø41.28
116
ø41.28 ø34.93
(Outside diameter) (Outside diameter)

ø34.93 ø28.6
92 50
(2 Pcs.)
ø28.6 ø28.6
(Outside diameter) <Accessory>
(Outside diameter) • Cover ··········1 Pcs.
ø19.05 • Band ··········3 Pcs.
ø22.2
80 80 Note. Pipe diameter is indicated by inside diameter.

MEES17K069 Il-2 32
0000004506.BOOK 33 ページ 2017年12月22日 金曜日 午後1時49分

6. OPTIONAL PARTS Indoor units

CMY-R201S-G mm
For High pressure For Low pressure For Liquid line

ø15.88 ø19.05
ø9.52
ø25.4
ø12.7

26
20

16
ø19.05 ø19.05 ø12.7
58 ø25.4 42
66
ø25.4
ø19.05 ø12.7
(Outside diameter)
(Outside diameter) (Outside diameter)
ø15.88 ø19.05 ø9.52
30 41 23
(2 Pcs.) (2 Pcs.) (2 Pcs.)
ø25.4
(Outside diameter)
ø22.2
42
(2 Pcs.)
ø25.4
(Outside diameter)
<Accessory>
ø28.6 • Cover ·················3 Pcs.
54 Note. Pipe diameter is indicated by inside diameter.
(2 Pcs.)

CMY-R202S-G mm
For High pressure For Low pressure For Liquid line
ø19.05 ø19.05
ø12.7
ø25.4 ø25.4
26

26

18
ø15.88 ø15.88
ø25.4 66 ø25.4 66 49
ø25.4 ø25.4 ø15.88
(Outside diameter) (Outside diameter) (Outside diameter)
ø22.2 ø12.7
ø28.6
42 28
54
(2 Pcs.) (2 Pcs.) (2 Pcs.)
ø25.4 ø25.4 ø15.88
(Outside diameter) (Outside diameter) (Outside diameter)
ø19.05 ø9.52
ø19.05
41 41 28
ø25.4 ø25.4 ø12.7
(Outside diameter) (Outside diameter) (Outside diameter)
ø15.88 ø22.2 ø9.52
23
45 42
ø19.05 ø19.05
(Outside diameter) (Outside diameter)
ø15.88 ø22.2 <Accessory>
30 54 • Cover ·················3 Pcs.
Note. Pipe diameter is indicated by inside diameter.

CMY-R203S-G mm
For High pressure For Low pressure For Liquid line
ø19.05 ø25.4
ø12.7
ø25.4 ø31.75
30
26

18

ø15.88
ø25.4 ø31.75 ø15.88
66 49
90
ø25.4 ø31.75 ø15.88
(Outside diameter) (Outside diameter) (Outside diameter)
ø28.6 ø28.6 ø12.7
54 28
(2 Pcs.) 46
ø25.4 (2 Pcs.) ø12.7
ø25.4
(Outside diameter) (Outside diameter) (Outside diameter)
ø9.52
ø19.05 ø19.05 23
41 41
ø25.4 ø25.4
(Outside diameter) (Outside diameter)
ø22.2 ø22.2
42 42
ø19.05 ø25.4
BC controller

(Outside diameter) ø15.88 (Outside diameter) <Accessory>


ø28.6 • Cover ·················3 Pcs.
30 54 Note. Pipe diameter is indicated by inside diameter.

MEES17K069 Il-2 33
0000004506.BOOK 34 ページ 2017年12月22日 金曜日 午後1時49分

6. OPTIONAL PARTS Indoor units

CMY-R204S-G For High pressure For Low pressure For Liquid line mm
ø19.05 ø25.4 ø15.88
ø25.4 ø31.75 ø19.05

30
26

20
ø19.05
ø25.4 66 ø31.75 58
90
ø25.4 ø19.05 ø31.75 ø19.05 ø15.88
(Outside diameter) (Outside diameter) ø25.4
(Outside diameter) (Outside diameter) (Outside diameter) (Outside diameter)
ø28.6 ø15.88 ø28.6 ø15.88 ø12.7
ø19.05 28
54 30 30
46 41
(2 Pcs.)
ø25.4 ø19.05 ø31.75 ø25.4 ø19.05 ø15.88
(Outside diameter) (Outside diameter) (Outside diameter) (Outside diameter) (Outside diameter) (Outside diameter)
ø19.05 ø22.2 ø22.2 ø12.7 ø9.52
ø34.93
54 37 28
41 69 42
(2 Pcs.)
ø31.75 ø25.4
ø25.4
(Outside diameter) (Outside diameter) (Outside diameter)

ø22.2 ø41.28 ø28.6


<Accessory>
42 54
69 • Cover ·················3 Pcs.
(2 Pcs.) Note. Pipe diameter is indicated by inside diameter.

CMY-R205S-G For High pressure For Low pressure For Liquid line mm
ø25.4 ø25.4 ø19.05
ø31.75 ø31.75 ø25.4
30

30

26
ø31.75 ø31.75 ø25.4
90 90 66
ø31.75 ø25.4 ø31.75 ø25.4 ø25.4
(Outside diameter) (Outside diameter) ø19.05
(Outside diameter) (Outside diameter) (Outside diameter) (Outside diameter)
ø19.05 ø41.28 ø22.2 ø19.05 ø12.7
ø34.93
41 42 41 37
69 69
(2 Pcs.) (2 Pcs.)
(3 Pcs.) ø25.4
ø31.75 ø25.4 ø31.75
(Outside diameter) (Outside diameter) (Outside diameter) ø25.4 ø12.7
(Outside diameter)
(Outside diameter) (Outside diameter)
ø22.2
ø28.6 ø28.6 ø28.6 ø15.88 ø9.52
42 46 54 23
46 45
(2 Pcs.)
ø31.75 ø25.4
ø31.75 ø25.4 (Outside diameter)
(Outside diameter) (Outside diameter) ø19.05
(Outside diameter) (Outside diameter)
ø25.4 ø34.93 ø31.75 ø15.88
ø28.6
69 54 30
55 54
(2 Pcs.) (2 Pcs.)
ø25.4 ø25.4
(Outside diameter) (Outside diameter) <Accessory>
ø15.88
ø19.05
• Cover ·················3 Pcs.
45 41
Note. Pipe diameter is indicated by inside diameter.

CMY-R301S-G mm

ø19.05
(Outside diameter)
ø15.88
80

ø28.6 ø22.2
(Outside diameter) (Outside diameter)
ø22.2 ø19.05
80 80
BC controller

Note. Pipe diameter is indicated by inside diameter.

CMY-R302S-G mm

ø41.28
(Outside diameter) ø34.93
(Outside diameter)
ø34.93 ø28.6
92 50
(2 Pcs.)

ø28.6 ø22.2 ø19.05


(Outside diameter) (Outside diameter) (Outside diameter)
ø22.2 ø19.05 ø15.88
80 80 80
(2 Pcs.) (2 Pcs.)

Note. Pipe diameter is indicated by inside diameter.

MEES17K069 Il-2 34
0000004506.BOOK 35 ページ 2017年12月22日 金曜日 午後1時49分

6. OPTIONAL PARTS Indoor units

CMY-R303S-G mm
ø28.6 ø22.2
(Outside diameter) (Outside diameter)
ø22.2 ø19.05
80 80

ø19.05 ø19.05 ø12.7


(Outside diameter) (Outside diameter) (Outside diameter)
ø15.88 ø12.7 ø9.52
80 80 80
(2 Pcs.)

Note. Pipe diameter is indicated by inside diameter.

CMY-R304S-G mm

ø41.28
(Outside diameter) ø34.93
(Outside diameter)
ø34.93 ø28.6
92 50
(2 Pcs.)

ø28.6 ø22.2 ø19.05


(Outside diameter) (Outside diameter) (Outside diameter)
ø22.2 ø19.05 ø15.88
80 80 80
(2 Pcs.) (2 Pcs.)

Note. Pipe diameter is indicated by inside diameter.

CMY-R305S-G mm

ø28.6 ø22.2 ø34.93


(Outside diameter) (Outside diameter) (Outside diameter)

ø22.2 ø19.05 ø28.6


80 80 50

ø19.05 ø19.05 ø12.7


(Outside diameter) (Outside diameter) (Outside diameter)
ø15.88 ø12.7 ø9.52
80 80 80
(2 Pcs.)

Note. Pipe diameter is indicated by inside diameter.

CMY-R306S-G mm

ø19.05 ø28.6
(Outside diameter) (Outside diameter)

ø15.88 ø22.2
BC controller

80 80

ø22.2 ø16 ø15.88


(Outside diameter) (Outside diameter) (Outside diameter)
ø12.7 ø9.52
ø19.05
80 80 80

Note. Pipe diameter is indicated by inside diameter.

MEES17K069 Il-2 35
0000004506.BOOK 36 ページ 2017年12月22日 金曜日 午後1時49分

6. OPTIONAL PARTS Indoor units

How to select Joint and Reducer


Outdoor/Heat source unit

C C

BC controller
(Main)
D D

BC controller BC controller BC controller


(Sub) (Sub) (Sub)
D D D
A A

IU IU IU
IU: Indoor unit

CMY-Y102SS-G2
Between BC and Total down-stream indoor unit capacity: -P200
A Branch joint
indoor units
CMY-Y102LS-G2 Total down-stream indoor unit capacity: P201-P250
Low pressure Between outdoor CMY-R101S-G Outdoor unit capacity: P200-P650
B
pipe joint units and Sub BC CMY-R102S-G Outdoor unit capacity: P700-P1100
CMY-R201S-G Total down-stream indoor unit capacity: -P350
CMY-R202S-G Total down-stream indoor unit capacity: P351-P600
Between Main BC
C Branch joint CMY-R203S-G Total down-stream indoor unit capacity: P601-P650
and Sub BC
CMY-R204S-G Total down-stream indoor unit capacity: P651-P1000
CMY-R205S-G Total down-stream indoor unit capacity: P1001-
CMY-R301S-G For J type (Outdoor unit capacity: P200-P300)
Between outdoor
CMY-R302S-G For JA type (Outdoor unit capacity: P200-P900)
units and BC
CMY-R304S-G For KA type (Outdoor unit capacity: P200-P1000)
D Reducer
CMY-R303S-G For JA type (When using the Sub BC controller)
Between Main BC
CMY-R305S-G For KA type (When using the Sub BC controller)
and Sub BC
CMY-R306S-G For KB type
Main BC controller has two ports for Sub BC controller. Low pressure pipe has to be branched from the outdoor unit.
(“B” in the figure)
Items “B” and “C” are not necessary when J-type BC controller is used.
BC controller

MEES17K069 Il-2 36
0000004506.BOOK 37 ページ 2017年12月22日 金曜日 午後1時49分

6. OPTIONAL PARTS Indoor units

6-2. JOINT KIT "CMY-R160-J1" FOR BC CONTROLLER


Joint kit "CMY-R160-J1" for BC controller is used to combine 2 ports of the BC controller at a PURY/PQRY system so as to
enable down-stream Indoor capacity above P80 as shown in Fig. 1.
The Joint kit include following items:
1 Instruction 2 Joint pipe(Small) 3 Joint pipe(Large) 4 Cover 1 5 Cover 2 6 Cover 3 7 Band 8 Reducer 1 9 Reducer 2
OD19.05-ID22.2 OD19.05-ID15.88

This sheet 1pc 1pc 1pc 2pcs 1pc for gas side 1pc for Iiquid side 8pcs 1pc 1pc
Please prepare the following items in the field. 1 Tape for insulation material sealing 2 Extension pipe for refrigerant circuit

2 Joint pipe (for liquid side) 3 Joint pipe (for gas side) mm (in.)

ø19.05(3/4")
ø9.52(3/8") ø15.88(5/8")
ø9.52(3/8")

60(2-3/8")

60(2-3/8")
ø9.52(3/8")
ø15.88(5/8")

226(8-29/32") 226(8-29/32")

1. Designing CMY-R160-J1 to a PURY/PQRY system


The maximum down-stream Indoor capacity for 1 port of BC Outdoor/Heat source unit
controller is P80. When the down-stream Indoor capacity is
above P80, Joint kit CMY-R160-J1 is needed to combined 2 Joint BC controller
ports of BC controller to enlarge the capacity, like Group 2 and CMY-Y102SS-G2
3 in Fig. 1.
Maximum 3 Indoor units are allowed to connect to 1 port of BC Joint kit
controller or 2 combined ports of BC controller using CMY- CMY-R160-J1
IU IU IU
R160-J1.
Group1
When connecting Indoor units to 1 port of BC controller or 2 Total Indoor Capacity
combined ports of BC controller using CMY-R160-J1 or CMY- <=P80
Y102SS-G2 is applicable, like Group 1 and 2 in Fig. 1

Caution: Mixed cooling and heating mode at the same time for IU IU IU IU
Indoor units connecting to 1 port or 2 combined ports is not
Group2 Group3
available. Total Indoor Capacity Indoor Capacity
P81 to P250 P100 to P250

Fig.1. CMY-R160-J1 applying scheme


2. Piping at the installation site
The connection of CMY-R160-J1 to BC controller and pipe leading to Indoor units is referable to Fig. 2. Non-oxidized brazing is
necessary. All piping must be careful to avoid foreign material getting inside.
After piping and air-tight testing, insulation work to the Joint and pipe should be done. Details is available at the Installation Manual.

Cutting point 50 Cutting point


20
BC controller

2 Joint pipe (for liquid side)

Piping to indoor unit


(Non-oxidized brazing)
3 Joint pipe(for gas side)

Have pipe expansion of indoor unit connecting port by


cutting the piping at the cutting point.
Remove burr after cutting the piping to prevent entering
the piping.
Fig.2. Connecting CMY-R160-J1 Check that there is no crack at the pipe expansion part.

MEES17K069 Il-2 37
0000004506.BOOK 38 ページ 2017年12月22日 金曜日 午後1時49分

7. INSTALLATION Indoor units

7-1. Installing BC controllers


7. INSTALLATION

Installing hanging bolts


Install locally procured hanging bolts (threaded rod) following the procedure given in the figure.
The hanging bolt size is ø10 (M10 screw).
To hang the unit, use a lifting machine to lift and pass it through the hanging bolts.

Nut (not supplied) Washer (with cushion)(supplied) CMB-P104, 106, 108V-J, CMB-P1012, 1016V-J
* Attach the cushion facing down. CMB-P104, 108V-KB CMB-P108, 1012, 1016V-JA
CMB-P1016V-KA

14mm
Double nut
(not supplied)

14mm
30mm
Minimum
30 mm
Hanging bolt ø10 (Top view)
(M10 screw) Washer (without cushion) (supplied) 30mm
(not supplied)

►Be sure to install the BC controller horizontally, using a level. If the controller is installed at an angle, drain water may leak
out. If the controller is slanted, loosen the fixing nuts on the hanging brackets to adjust its position.
►Provide a downward pitch of 1.5º or below to the BC controller.
►Do not place the BC controller directly on the floor because the drain pan needs to be installed in a tilted position.
BC controller

MEES17K069 Il-2 38
0000004506.BOOK 39 ページ 2017年12月22日 金曜日 午後1時49分

8. SYSTEM DESIGN Indoor units

8-1. Compatibility
8. SYSTEM DESIGN

Outdoor/Heat source unit BC controller Compatibility


PURY-(E)P-Y(S)NW
PURY-(E)P-Y(S)LM
PQRY-P-Y(S)LM G1 type Compatible
PURY-RP-Y(S)JM
PURY-(E)P-Y(S)JM
PURY-(E)P-Y(S)NW
PURY-(E)P-Y(S)LM S/W Ver. 7.08 or later
PQRY-P-Y(S)LM S/W Ver. 6.42 or later J type Compatible
PURY-RP-Y(S)JM S/W Ver. 5.58 or later
PURY-(E)P-Y(S)JM S/W Ver. 1.42 or later

BC controller
Outdoor/Heat source unit Compatibility
Main Sub
PURY-(E)P-Y(S)NW JA/KA type GB1/HB1 type GB1/HB1 type Compatible
PURY-(E)P-Y(S)LM S/W Ver. 7.08 or later JA/KA type KB type GB1/HB1 type Not compatible
PQRY-P-Y(S)LM S/W Ver. 6.42 or later JA/KA type GB1/HB1 type Compatible
PURY-RP-Y(S)JM S/W Ver. 5.58 or later GA1/HA1 type KB type KB type Compatible
PURY-(E)P-Y(S)JM S/W Ver. 1.42 or later GA1/HA1 type KB type GB1/HB1 type Not compatible
GA1/HA1 type KB type Compatible

BC controller
Outdoor/Heat source unit Compatibility
Main Sub
PURY-(E)P-Y(S)NW
PURY-(E)P-Y(S)LM S/W Ver. 7.08 or later
PQRY-P-Y(S)LM S/W Ver. 6.42 or later
JA/KA type KB type Compatible(*)
PURY-RP-Y(S)JM S/W Ver. 5.58 or later
PURY-(E)P-Y(S)JM S/W Ver. 1.42 or later

*Up to 11 Sub BC controllers can be connected.


GA1/HA1/GB1/HB1 type and JA/KA/KB type can be mixed.
The only combination that is not available is mix of GB1/HB1 type and KB type.
When mixing GA1/HA1/GB1/HB1 type and JA/KA/KB type, specifications and restrictions is according to
GA1/HA1/GB1/HB1type. (piping length, connectable number of Sub BC)

BC controller

MEES17K069 Il-2 39
0000004506.BOOK 40 ページ 2017年12月22日 金曜日 午後1時49分

8. SYSTEM DESIGN Indoor units

8-2. System examples


Refer to “6-1. JOINT and REDUCER” and “Piping Design of Outdoor/Heat source Units” for joint/reducer selection rules, pipe
length restrictions, and pipe diameter.

8-2-1. When G1-type BC controller is used


Note1. No Header usable on PURY system.
Note2. Indoor unit sized P100-P250 should be connected to BC controller via Y shape joint CMY-R160-J1 ; Joint CMY-R160-J1 Liquid side
CMY-R160-J1
(Liquid side) 226
Note3. Indoor unit sized P100-P250 does NOT share BC controller ports with other Indoor units ; (M)ø3/8"(Brazing)
Note4. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better ; M BC controller (N)ø9.52ID
Piping length needs to consider the actual length and equivalent length which bents are counted. (M)ø3/8"(Brazing)
Equivalent piping length (m)=Actual piping length+"M" x Number of bent.
Note5. Set DIP-SW 4-6 to ON of BC controller, in case of connected Indoor unit sized P100-P250 with 2 ports. Joint CMY-R160-J1 Gas side
Note6. It is also possible to connect Indoor unit sized P100-P140 with 1 port (set DIP-SW 4-6 to OFF). N 226
S T
However, the cooling capacity decreases a little. (S)ø5/8"(Brazing)
CMY-R160-J1
Note7. Do not connect multiple indoor units to the same port when operating each of them in different mode (Gas side)
IU (T)ø19.05ID
(cooling, heating, stop, and thermo-off). The indoor units connected to the same port must be set to (S)ø5/8"(Brazing)
operate in the same mode. Set them in the same group to make them run/stop in the same mode all
together. For other options, enable the thermo setting on the remote controller, or set the common
thermostat (optional) to run/stop the units in the same mode based on a representative temperature.
Note8. Indoor capactiy is described as its model size. For example, PEFY-P63VML-E, its capacity is P63.
Note9. Total down-stream Indoor capacity is the summary of the model size of Indoors down-stream.
For example, PEFY-P63VML-E + PEFY-P32VML-E : Total Indoor capacity = P63 + P32 = P95.
Note10. To enable the continuous heating mode, set SW4 (848) to ON.
Outdoor/Heat source unit PURY-(E)P-Y(S)NW
PURY-(E)P-Y(S)LM
PQRY-P-Y(S)LM
PURY-RP-Y(S)JM
Pipe (High pressure)
Pipe (Low pressure)
CMY-R160-J1 (joint)
Possible to remove the total capacity P140 and under P140,
but the capacity should be multiplied by a correction factor 0.97
BC controller (G1 type) (P15-P80)
Refer to the IU
installation manual
for the connection

Pipe (Liquid)

Pipe (Gas)

IU IU IU IU IU IU IU
(P15-P80) (P100-P250) Max. 3 sets for 1 port. Max. 3 sets for 2 port.
Total capacity < = P80 Total capacity > P80
CMY-R160-J1 (joint)
Possible to remove P140 and under P140, but the IU (each) max < = P80
IU: Indoor unit
capacity should be multiplied by a correction factor 0.97

8-2-2. When J-type BC controller is used


Note1. No Header usable on PURY system.
Note2. Indoor unit sized P100-P250 should be connected to BC controller via Y shape joint CMY-R160-J1 ; Joint CMY-R160-J1 Liquid side
CMY-R160-J1
If the system consists only of PEFY-P50, 63, 71, 80, 100VMHS2-E models of indoor units, connect to the (Liquid side) 226

BC controller via Y-shape joint CMY-R160-J1. (M)ø3/8"(Brazing)


M BC controller
(N)ø9.52ID
Note3. Indoor unit sized P100-P250 does NOT share BC controller ports with other Indoor units ; (M)ø3/8"(Brazing)
Note4. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better ;
Piping length needs to consider the actual length and equivalent length which bents are counted.
Equivalent piping length (m)=Actual piping length+"M" x Number of bent. Joint CMY-R160-J1 Gas side
Note5. Set DIP-SW 4-6 to ON of BC controller, in case of connected Indoor unit sized P100-P250 with 2 ports. S T
N 226
If the system consists only of PEFY-P50, 63, 71, 80, 100VMHS2-E models of indoor units, set the dipswitches CMY-R160-J1 (S)ø5/8"(Brazing)
SW4-1 and SW4-6 on the BC controller to ON. (Gas side)
IU (T)ø19.05ID
(S)ø5/8"(Brazing)
Note6. It is also possible to connect Indoor unit sized P100-P140 with 1 port (set DIP-SW 4-1 and 4-6 to OFF).
PEFY-P50, 63, 71, 80, 100VMHS2-E models of indoor units can be connected to the system using a single port.
However, the cooling capacity decreases a little.
Note7. Do not connect multiple indoor units to the same port when operating each of them in different mode (cooling, heating, stop, and thermo-off). The indoor units connected to the same port
must be set to operate in the same mode. Set them in the same group to make them run/stop in the same mode all together. For other options, enable the thermo setting on the remote
controller, or set the common thermostat (optional) to run/stop the units in the same mode based on a representative temperature.
Note8. Indoor capactiy is described as its model size. For example, PEFY-P63VML-E, its capacity is P63.
Note9. Total down-stream Indoor capacity is the summary of the model size of Indoors down-stream. For example, PEFY-P63VML-E + PEFY-P32VML-E: Total Indoor capacity = P63 + P32 = P95.
Note10. To enable the continuous heating mode, set SW4 (848) to ON.
Note11. To connect the BC controller to the main pipe, use the reducer.
Outdoor/Heat source unit
PURY-(E)P-Y(S)NW
PURY-(E)P-Y(S)LM S/W Ver. 7.08 or later
BC controller

PQRY-P-Y(S)LM S/W Ver. 6.42 or later


Pipe (High pressure) PURY-RP-Y(S)JM S/W Ver. 5.58 or later
Pipe (Low pressure)
CMY-R160-J1 (joint)
Possible to remove the total capacity P140 and under P140,
but the capacity should be multiplied by a correction factor 0.97
BC controller (J type) (P15-P80)
Refer to the IU
installation manual
for the connection

Pipe (Liquid)

Pipe (Gas)

IU IU IU IU IU IU IU
(P15-P80) (P100-P250) Max. 3 sets for 1 port. Max. 3 sets for 2 port.
CMY-R160-J1 (joint) Total capacity < = P80 Total capacity > P80
Possible to remove P140 and under P140, but the IU (each) max < = P80
capacity should be multiplied by a correction factor 0.97 IU: Indoor unit

MEES17K069 Il-2 40
0000004506.BOOK 41 ページ 2017年12月22日 金曜日 午後1時49分

8. SYSTEM DESIGN Indoor units

8-2-3. When JA/KA- and GB1/HB1-type BC controllers are used together


Note1. No Header usable on PURY system.
Joint CMY-R160-J1 Liquid side
Note2. Indoor unit sized P100-P250 should be connected to BC controller via Y shape joint CMY-R160-J1 ; CMY-R160-J1
(Liquid side) 226
If the system consists only of PEFY-P50, 63, 71, 80, 100VMHS2-E models of indoor units, connect to the (M)ø3/8"(Brazing)
BC controller via Y-shape joint CMY-R160-J1. M BC controller
(N)ø9.52ID
Note3. Indoor unit sized P100-P250 does NOT share BC controller ports with other Indoor units ; (M)ø3/8"(Brazing)
Note4. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better ;
Piping length needs to consider the actual length and equivalent length which bents are counted. Joint CMY-R160-J1 Gas side
Equivalent piping length (m)=Actual piping length+"M" x Number of bent. N 226
S
Note5. Set DIP-SW 4-6 to ON of BC controller, in case of connected Indoor unit sized P100-P250 with 2 ports. T
(S)ø5/8"(Brazing)
If the system consists only of PEFY-P50, 63, 71, 80, 100VMHS2-E models of indoor units, set the dipswitches CMY-R160-J1
IU (T)ø19.05ID
(Gas side)
SW4-1 and SW4-6 on the BC controller to ON. (S)ø5/8"(Brazing)
Note6. It is also possible to connect Indoor unit sized P100-P140 with 1 port (set DIP-SW 4-1 and 4-6 to OFF).
PEFY-P50, 63, 71, 80, 100VMHS2-E models of indoor units can be connected to the system using a single port.
However, the cooling capacity decreases a little.
Note7. Do not connect multiple indoor units to the same port when operating each of them in different mode (cooling, heating, stop, and thermo-off). The indoor units connected to the same
port must be set to operate in the same mode. Set them in the same group to make them run/stop in the same mode all together. For other options, enable the thermo setting on the
remote controller, or set the common thermostat (optional) to run/stop the units in the same mode based on a representative temperature.
Note8. For sub BC controller CMB-P•V-GB1 the connectable indoor unit capacities may sum to equal that of a P350 unit or less.
However, if two sub controllers are used the TOTAL sum of connectable units connected to BOTH sub controllers must also not exceed that of a P350 unit.
For sub BC controller CMB-P1016V-HB1 the connectable indoor unit capacities may sum to equal that or a P350 unit or less. However, if two sub controllers are used
the TOTAL sum of connectable units connected to BOTH sub controllers must also not exceed that of a P450 unit.
Note9. Indoor capactiy is described as its model size. For example, PEFY-P63VML-E, its capacity is P63.
Note10. Total down-stream Indoor capacity is the summary of the model size of Indoors down-stream. For example,
PEFY-P63VML-E + PEFY-P32VML-E : Total Indoor capacity = P63 + P32 = P95.
Note11. To enable the continuous heating mode, set SW4 (848) to ON.
Note12. To connect the BC controller to the main pipe, use the reducer.
Note13. To connect the sub BC controller to the main BC controller, use the reducer.
Outdoor/Heat source unit PURY-(E)P-Y(S)NW
PURY-(E)P-Y(S)LM S/W Ver. 7.08 or later Pipe (LP Gas)
Pipe (High pressure) PQRY-P-Y(S)LM S/W Ver. 6.42 or later Pipe (Liquid)
PURY-RP-Y(S)JM S/W Ver. 5.58 or later
Pipe (Low pressure) Pipe (HP Gas)

BC controller (JA/KA type)


CMY-R160-J1 (joint)
Possible to remove the total capacity P140 and under P140,
but the capacity should be multiplied by a correction factor 0.97 BC controller (GB1/HB1 type)
BC controller (GB1/HB1 type)

Pipe
(Liquid)

IU IU IU IU IU IU IU IU IU Pipe (Gas) IU
(P15-P80) (P100-P250) Max. 3 sets for 1 port. Max. 3 sets for 2 port. (P15-P80) (P15-P80)
Total capacity < = P80 Total capacity > P80
CMY-R160-J1 (joint) IU (each) max < = P80
Possible to remove P140 and under P140, but the
capacity should be multiplied by a correction factor 0.97 IU: Indoor unit

8-2-4. When GA1/HA1- and KB-type BC controllers are used together


Note1. No Header usable on PURY system.
Joint CMY-R160-J1 Liquid side
Note2. Indoor unit sized P100-P250 should be connected to BC controller via Y shape joint CMY-R160-J1 ; CMY-R160-J1
226
(Liquid side)
Note3. Indoor unit sized P100-P250 does NOT share BC controller ports with other Indoor units ; (M)ø3/8"(Brazing)
Note4. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better ; M BC controller
(N)ø9.52ID
Piping length needs to consider the actual length and equivalent length which bents are counted. (M)ø3/8"(Brazing)
Equivalent piping length (m)=Actual piping length+"M" x Number of bent.
Note5. Set DIP-SW 4-6 to ON of BC controller, in case of connected Indoor unit sized P100-P250 with 2 ports. Joint CMY-R160-J1 Gas side
Note6. It is also possible to connect Indoor unit sized P100-P140 with 1 port (set DIP-SW 4-6 to OFF). S T
N 226
However, the cooling capacity decreases a little. CMY-R160-J1 (S)ø5/8"(Brazing)
Note7. Do not connect multiple indoor units to the same port when operating each of them in different mode (Gas side)
IU (T)ø19.05ID
(S)ø5/8"(Brazing)
(cooling, heating, stop, and thermo-off). The indoor units connected to the same port must be set to operate
in the same mode. Set them in the same group to make them run/stop in the same mode all together. For other
options, enable the thermo setting on the remote controller, or set the common thermostat (optional) to run/stop the units in the same mode based on a representative temperature.
Note8. The maximum total capacity of indoor units that can be connected to each sub BC controller CMB-P•V-KB is 350.
Note9. Indoor capactiy is described as its model size. For example, PEFY-P63VML-E, its capacity is P63.
Note10. Total down-stream Indoor capacity is the summary of the model size of Indoors down-stream.
For example, PEFY-P63VML-E + PEFY-P32VML-E : Total Indoor capacity = P63 + P32 = P95.
Note11. To enable the continuous heating mode, set SW4 (848) to ON.
Note12. To connect the sub BC controller to the main BC controller, use the reducer.
Outdoor/Heat source unit
BC controller

PURY-(E)P-Y(S)NW
PURY-(E)P-Y(S)LM S/W Ver. 7.08 or later
PQRY-P-Y(S)LM S/W Ver. 6.42 or later
IU
PURY-RP-Y(S)JM S/W Ver. 5.58 or later

BC controller (GA1/HA1 type) BC controller (KB type)


CMY-R160-J1 (joint)
Possible to remove the total capacity P140 and under P140,
but the capacity should be multiplied by a correction factor 0.97
BC controller (KB type)

IU
IU IU IU IU IU IU IU IU
(P15-P80) (P100-P250) Max. 3 sets for 1 port. Max. 3 sets for 2 port.
Total capacity < = P80 Total capacity > P80
CMY-R160-J1 (joint) IU (each) max < = P80
Possible to remove P140 and under P140, but the
capacity should be multiplied by a correction factor 0.97 IU: Indoor unit

MEES17K069 Il-2 41
0000004506.BOOK 42 ページ 2017年12月22日 金曜日 午後1時49分

8. SYSTEM DESIGN Indoor units

8-2-5. When JA/KA- and KB-type BC controllers are used together


Note1. No Header usable on PURY system.
Joint CMY-R160-J1 Liquid side
Note2. Indoor unit sized P100-P250 should be connected to BC controller via Y shape joint CMY-R160-J1 ; CMY-R160-J1
(Liquid side) 226
If the system consists only of PEFY-P50, 63, 71, 80, 100VMHS2-E models of indoor units, connect to the (M)ø3/8"(Brazing)
BC controller via Y-shape joint CMY-R160-J1. M BC controller
(N)ø9.52ID
Note3. Indoor unit sized P100-P250 does NOT share BC controller ports with other Indoor units ; (M)ø3/8"(Brazing)
Note4. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better ;
Piping length needs to consider the actual length and equivalent length which bents are counted. Joint CMY-R160-J1 Gas side
Equivalent piping length (m)=Actual piping length+"M" x Number of bent. N 226
S
Note5. Set DIP-SW 4-6 to ON of BC controller, in case of connected Indoor unit sized P100-P250 with 2 ports. T
(S)ø5/8"(Brazing)
If the system consists only of PEFY-P50, 63, 71, 80, 100VMHS2-E models of indoor units, set the dipswitches CMY-R160-J1
IU (T)ø19.05ID
(Gas side)
SW4-1 and SW4-6 on the BC controller to ON. (S)ø5/8"(Brazing)
Note6. It is also possible to connect Indoor unit sized P100-P140 with 1 port (set DIP-SW 4-1 and 4-6 to OFF).
PEFY-P50, 63, 71, 80, 100VMHS2-E models of indoor units can be connected to the system using a single port.
However, the cooling capacity decreases a little.
Note7. Do not connect multiple indoor units to the same port when operating each of them in different mode (cooling, heating, stop, and thermo-off). The indoor units connected to the same
port must be set to operate in the same mode. Set them in the same group to make them run/stop in the same mode all together. For other options, enable the thermo setting on the
remote controller, or set the common thermostat (optional) to run/stop the units in the same mode based on a representative temperature.
Note8. The maximum total capacity of indoor units that can be connected to each sub BC controller CMB-P•V-KB is 350.
Note9. Indoor capactiy is described as its model size. For example, PEFY-P63VML-E, its capacity is P63.
Note10. Total down-stream Indoor capacity is the summary of the model size of Indoors down-stream. For example,
PEFY-P63VML-E + PEFY-P32VML-E : Total Indoor capacity = P63 + P32 = P95.
Note11. To enable the continuous heating mode, set SW4 (848) to ON.
Note12. To connect the BC controller to the main pipe, use the reducer.
Note13. To connect the sub BC controller to the main BC controller, use the reducer.
Outdoor/Heat source unit PURY-(E)P-Y(S)NW
(P15-P80)
PURY-(E)P-Y(S)LM S/W Ver. 7.08 or later Pipe (LP Gas)
IU
Pipe (High pressure) PQRY-P-Y(S)LM S/W Ver. 6.42 or later Pipe (Liquid)
PURY-RP-Y(S)JM S/W Ver. 5.58 or later
Pipe (Low pressure) Pipe (HP Gas)
BC controller (KB type)

BC controller (JA/KA type)


CMY-R160-J1 (joint)
Possible to remove the total capacity P140 and under P140,
but the capacity should be multiplied by a correction factor 0.97 BC controller (KB type) BC controller (KB type)
BC controller (KB type)

Pipe
(Liquid)

IU IU IU IU IU IU IU IU IU Pipe (Gas) IU IU
(P15-P80) (P100-P250) Max. 3 sets for 1 port. Max. 3 sets for 2 port. (P15-P80) (P15-P80) (P15-P80)
Total capacity < = P80 Total capacity > P80
CMY-R160-J1 (joint) IU (each) max < = P80
Possible to remove P140 and under P140, but the
capacity should be multiplied by a correction factor 0.97 IU: Indoor unit
BC controller

MEES17K069 Il-2 42
Warning
■ Do not use refrigerant other than the type indicated in the manuals provided with the unit and on the nameplate.
- Doing so may cause the unit or pipes to burst, or result in explosion or fire during use, repair, or at the time of disposal of the unit.
- It may also be in violation of applicable laws.
- MITSUBISHI ELECTRIC CORPORATION cannot be held responsible for malfunctions or accidents resulting from the use of the wrong
type of refrigerant.
■ Our airconditioning equipment and heat pumps contain a fluorinated greenhouse gas, R410A.

New publication effective Dec. 2017


MEES17K069 Specifications subject to change without notice