You are on page 1of 3

Errata sheet date: 7/2/18

Errata for the 2018 Guidelines for Design and Construction of Hospitals

Content Corrections
PAGE SECTION ERROR CORRECTED TEXT
53 Table 1.2-6 3
In cases where greater speech privacy is 3
This is the performance required
required between patient care rooms 4
In cases where greater speech privacy is
when both room doors.... required between patient rooms when
4
This is the performance required... both patient patient room doors...
67 2.1-1 2.1-1 General 2.1-1 General
... ...
2.1-1.1.4 Outpatient projects located in
hospitals shall meet the requirements of
the FGI Guidelines for Design and
Construction of Outpatient Facilities.
132 Table 2.1-2 Procedure room/Class 2 imaging room Procedure room/Class 2 imaging room
Nurse Call Required stations: Bath, Staff assistance Required stations: Staff assistance,
Devices Optional station: Emergency call Emergency call
Optional station: Nurse master
Operating room/Class 3 imaging room
Required stations: Bath, Staff assistance Operating room/Class 3 imaging room
Required stations: Staff assistance,
Electroconvulsive therapy treatment Emergency call
room/pre-procedure and recovery patient
care stations Electroconvulsive therapy treatment
Required stations: Bath, Staff assistance room/pre-procedure and recovery patient
care stations
Required stations: Staff assistance,
Emergency call
133 Table 2.1-3 Class 1 imaging room Class 1 imaging room
Station 1 oxygen, 1 vacuum, 1 medical air 1 oxygen, 1 vacuum
Outlets
Operating room/Class 3 imaging room Operating room/Class 3 imaging room
2 oxygen, 5 vacuum, 1 medical air, 1 WAGD, 2 oxygen, 5 vacuum, 1 medical air, 1 WAGD
1 instrument air
152 2.2-2.8.2 2.2-2.8.2 NICU Rooms and Areas 2.2-2.8.2 NICU Rooms and Areas
... ...
2.2-2.8.2.6 Reserved
2.2-2.8.2.7 Nurse call system. A nurse call
system shall be provided in accordance with
Section 2.1-8.5.1 (Call Systems).

continued

*The row highlighted in blue indicates changes made since the 6/7/18 version of this errata sheet.
Errata for 2018 Guidelines for Design and Construction of Hospitals, continued 7/2/18

PAGE SECTION ERROR CORRECTED TEXT


171– 72 2.2-3.1.3.6 2.2-3.1.3.6 Treatment room or area... 2.2-3.1.3.6 Treatment room or area...
(4)(c) and *(4) Trauma/resuscitation room.... *(4) Trauma/resuscitation room....
(4)(d)
(c) The trauma/resuscitation room shall contain (c) The trauma/resuscitation room
the following: ... shall contain the following: ...
(iii) A hand-washing station that meets the (iii) A hand-washing station(s)
requirements in Section 2.1-2.8.7 (Hand- that meets the requirements
Washing Station) in Section 2.1-2.8.7 (Hand-
... Washing Station)
(d) Hand scrub facilities. Hand scrub facilities ...
shall be provided for trauma rooms in
accordance with Section 2.1-2.8.6 (Hand
Scrub Facilities).
176 2.2-3.2.2.2 2.2-3.2 Observation Unit 2.2-3.2 Observation Unit
2.2-3.2.2 Patient Care Stations 2.2-3.2.2 Patient Care Stations
... ...
2.2-3.2.2.2 Space requirements *2.2-3.2.2.2 Space requirements. All
*(1) Area. All patient care stations (bays, cubicles, or patient care stations (bays, cubicles, or
single-patient rooms) designed to accommodate single-patient rooms) designed to
observation beds shall be provided in accordance accommodate observation beds shall
with Section 2.1-3.2.2.1 (Single-Patient be provided in accordance with Section
Examination Room—Space requirements) or 2.1-3.2.2.1 (Single-Patient Examination
Section 2.1-3.2.3.1 (Multiple-Patient Examination Room—Space requirements) or Section
Room—Space requirements). 2.1-3.2.3.1 (Multiple-Patient
Examination Room—Space
A2.2-3.2.2.2 (1) Additional space in patient
care stations... requirements).
A2.2-3.2.2.2 Additional space
(2) Clearances
in patient care stations...
(a) A minimum clearance of 5 feet (1.52 meters)
shall be provided between beds in bays in an
open observation area. [Note: Clearances are included in the
cross-referenced sections.]
(b) A minimum clearance of 3 feet (91.44
centimeters) shall be provided between walls
or partitions and the sides of beds in cubicles
in an open observation room and in patient
rooms.
184 2.2- (1) Patient toilet room (1) Patient toilet room
3.3.5.10 (a) Location... (a) Location...
(1)(a)(iii)
*(iii) Where pre- and postoperative patient *(iii) Where pre- and
care stations are single-patient rooms, the postoperative single-room
toilet room shall be directly accessible patient care stations are used
from the patient care station. for airborne infection isolation
A2.2-3.3.5.10 (1)(a)(iii) Pre- and patients, the toilet room shall
postoperative patient care stations that are be directly accessible from the
single-patient rooms are most commonly patient care station.
used for pediatric patients and for patients
requiring an airborne infection isolation
room, who should have their own
dedicated patient toilet room.

www.fgiguidelines.org
Errata for 2018 Guidelines for Design and Construction of Hospitals, continued 7/2/18

PAGE SECTION ERROR CORRECTED TEXT


197 2.2- 2.2-3.4.8 Support Areas for Imaging Services 2.2-3.4.8 Support Areas for Imaging
3.4.8.13 ... Services
2.2-3.4.8.13 Equipment and supply storage ...
(1) Clean linen storage 2.2-3.4.8.13 Equipment and supply
storage
(a) A storage area for clean linen shall be
provided. (1) Clean linen storage. A storage area for
clean linen shall be provided.
(b) A hand-washing station shall be
provided in the clean linen storage
area.
198 – 2.2- *2.2-3.4.8.19 Facilities for processing *2.2-3.4.8.19 Facilities for processing
199 3.4.8.19 ultrasound probes ultrasound probes
A2.2-3.4.8.19 Processing A2.2-3.4.8.19 Processing
ultrasound probes in a soiled ultrasound probes in a soiled
workroom. Some organizations workroom. Some organizations
process ultrasound probes in a process endocavitary ultrasound
soiled workroom; see Section probes in a soiled workroom; see
2.1-3.8.12 (Soiled Workroom or Section 2.1-3.8.12 (Soiled
Soiled Holding Room) for Workroom or Soiled Holding
requirements for a soiled Room) for general requirements
workroom. for a soiled workroom. For soiled
workrooms where ultrasound
probe or other semi-critical
instrument decontamination is
performed, an instrument-
washing sink would be required.
(1) Where an ultrasound probe processing (1) Where an ultrasound probe processing
room is provided, it shall meet the room is provided, it shall meet the
following requirements: ... following requirements: ...
(d) The decontamination area shall be (d) The decontamination area shall be
equipped with the following: ... equipped with the following: ...
(ii) Sink appropriate to the method of (ii) Instrument-washing sSink
decontamination used appropriate to the method of
decontamination used
*(2) Where ultrasound probes are processed *(2) Where ultrasound probes are
at the point of use or in a separate room processed at the point of use or in a
or area using a self-contained, automated separate room or area using a self-
high-level disinfection unit specifically contained, automated high-level
designed for ultrasound probes: ... disinfection unit specifically designed
(b) Access to a soiled workroom shall be for ultrasound probes: ...
provided in the same clinical area to *(b) Access to a soiled workroom with
support probe decontamination when an instrument-washing sink shall be
necessary. provided in the same clinical area to
support probe decontamination
when necessary.

www.fgiguidelines.org