You are on page 1of 14

Official Use Only

3/wgLn] 3/ jl/kl/ j[Iff/f]k0f ug{ clgjfo{ 5 .

Sheet List
Sheet
Number Sheet Name

S.0 INDEX SHEET


S.1 Trench Plan
S.2 Beam Column Layout
Plan
S.3 Floor Beam Plan
S.4 Beam Elevation grid
1,2,3
S.5 Beam Elevation grid
A,B,C,D
Project Name: 3 Storey
S.6 Footing Details Commercial
S.7 Slab Detailing(Bottom) Building Design
S.8 Slab Detailing(Top) Location: Dhangadhi-02
S.9 Beam Details
S.10 Sill and Lintel Band Drawn By: Dilli Raj Phulara
Details
Checked Er. Surendra Bam
S.11 Column Details By: NEC 17353 Civil"A"
S.12 Staircase Details
S.13 Septic Tank Details
Client's Name: Batu Devi Khadka

Plot no:7 Plot area:420.50 sq.m

Active & Innovative


Engineering Pvt. Ltd.
Dhangadhi submetro politian city-03
Contact no: 9841080149

Building Purpose: Commercial

INDEX SHEET

Sheet No: S.0

STRUCTURAL DRAWINGS
Scale:
Official Use Only
3/wgLn] 3/ jl/kl/ j[Iff/f]k0f ug{ clgjfo{ 5 .

A B C D E
8' - 0" 10' - 9" 10' - 9" 6' - 0"

6
IF-1 IF-1 IF-1 IF-1 IF-1
12' - 2"

12' - 2"
5
IF-1 IF-2 IF-2 IF-2 IF-1
12' - 5"

12' - 5"
4 IF-1 IF-2 IF-2 IF-2 IF-1 Project Name: 3 Storey
Commercial
7' - 0"

7' - 0"
Building Design

3 IF-1 IF-2 IF-2 IF-1


Location: Dhangadhi-02
IF-2
Drawn By: Dilli Raj Phulara
9' - 2"

9' - 2"
Checked Er. Surendra Bam
By: NEC 17353 Civil"A"
2
IF-1 IF-2 IF-2 IF-2 IF-1

Client's Name: Batu Devi Khadka


11' - 5"

11' - 5"

Plot no:7 Plot area:420.50 sq.m


IF-1 IF-1 IF-1 IF-1 IF-1
1 Active & Innovative
8' - 0" 10' - 9" 10' - 9" 6' - 0" Engineering Pvt. Ltd.
Dhangadhi submetro politian city-03
Structural Foundation Schedule Contact no: 9841080149

Type Mark Count Length Width Building Purpose: Commercial


TRENCH PLAN
1 Trench Plan
1/8" = 1'-0" IF-1 18 5' - 0" 5' - 0"
IF-2 12 6' - 0" 6' - 0"
Sheet No: S.1
Grand total: 30

Scale: 1/8" = 1'-0"


Official Use Only
3/wgLn] 3/ jl/kl/ j[Iff/f]k0f ug{ clgjfo{ 5 .

A 1
B C D E
S.5

8' - 0" 10' - 9" 10' - 9" 6' - 0"

6
C1 C2 C2 C2 C1
12' - 2"

12' - 2"
5
C1 C2 C2 C2 C1
12' - 5"

12' - 5"
4 Project Name: 3 Storey
C1 C2 C2 C2 C1
Commercial
7' - 0"

7' - 0"
Building Design

3 Location: Dhangadhi-02
C1 C2 C2 C2 C1
1 1 COLUMN DETAILS Drawn By: Dilli Raj Phulara
9' - 2"

9' - 2"
S.4 S.4
Ground floor First floor second floor
Checked Er. Surendra Bam
12" 12" 12"
By: NEC 17353 Civil"A"
2 C1 12" 12" 12"
C1 C2 C2 C2 C1
12"X12"

4-16+4-12mm∅
4-16+4-12mm∅ 4-16+4-12mm∅ 4-16+4-12mm∅
Client's Name: Batu Devi Khadka
11' - 5"

11' - 5"

12" 12" 12"

C2 12" 12" 12" Plot no:7 Plot area:420.50 sq.m


12"X12"

1 8-16mm∅ 4-16+4-12mm∅ 4-16+4-12mm∅

C1 8' - 0"
C2 10' - 9"
C2 10' - 9"
C2 C1
6' - 0"
Active & Innovative
1 Engineering Pvt. Ltd.
S.5
Dhangadhi submetro politian city-03
Contact no: 9841080149

Building Purpose: Commercial

Beam Column Layout Plan Beam Column Layout Plan


1
1/8" = 1'-0"
Sheet No: S.2

Scale: As indicated
Official Use Only
3/wgLn] 3/ jl/kl/ j[Iff/f]k0f ug{ clgjfo{ 5 .

A S.5 B C D E
3' - 0" 8' - 0" 10' - 9" 10' - 9" 6' - 0" 3' - 0"

3' - 0"

3' - 0"
6
Floor Beam
9"X14"

Floor Beam
12' - 2"

12' - 2"
9"X14"

Floor Beam
9"X14"

5
Floor Beam
9"X14"
Floor Beam
9"X14"
12' - 5"

12' - 5"
Floor Beam
9"X14"

Project Name: 3 Storey


4 Commercial
Building Design
7' - 0"

7' - 0"
Location: Dhangadhi-02
3
Drawn By: Dilli Raj Phulara
1 1
Floor Beam
9' - 2"

9' - 2"
9"X14"
S.4 S.4
Checked Er. Surendra Bam
Floor Beam
9"X14"
By: NEC 17353 Civil"A"

2
Client's Name: Batu Devi Khadka
11' - 5"

11' - 5"
Plot no:7 Plot area:420.50 sq.m

1 Active & Innovative


3' - 0" 8' - 0" 10' - 9" 10' - 9" 6' - 0" Engineering Pvt. Ltd.
Dhangadhi submetro politian city-03
Contact no: 9841080149

1 Building Purpose: Commercial


S.5
Floor Beam Plan Floor Beam Plan
1
1/8" = 1'-0"
Sheet No: S.3

Scale: 1/8" = 1'-0"


Official Use Only
3/wgLn] 3/ jl/kl/ j[Iff/f]k0f ug{ clgjfo{ 5 .
3' - 0"
E 6' - 0"
D 10' - 9"
C 10' - 9"
B 8' - 0"
A 3' - 0"
8Ø@5"C/C Spacing 8Ø@5"C/C Spacing
8Ø@5"C/C Spacing 8Ø@5"C/C Spacing 8Ø@5"C/C Spacing
8Ø@5"C/C Spacing 8Ø@5"C/C Spacing
1 1 2 1 1 2 1 1 2 1 1 2 1 1

3rd F
33' - 0" 2-16∅(th)-1-12∅(Th)+1-12∅(ex)
2-16Ø(th)+1-12∅(th)
1 1 1 1 1 1 1 1 1 1
2 2 2 2
8Ø@6" C/C Spacing 8Ø@6" C/C Spacing 8Ø@6" C/C Spacing 8Ø@6" C/C Spacing
8Ø@6" C/C Spacing

5"

5"
10' - 0"

9"

9"
9" 9"
8Ø@5"C/C Spacing
2-16Ø(th)+1-12∅(th) 2-16∅(th)-1-12∅(Th)+1-12∅(ex)
8Ø@5"C/C Spacing 8Ø@5"C/C Spacing 8Ø@5"C/C Spacing
8Ø@5"C/C Spacing
1 1 1 2 1 1 8Ø@5"C/C Spacing 2 2 1 SECTION-2-2
1 1 2 1 1 SECTION-1-1
2
2ndF
23' - 0"
1 1 1 2 1 2 1 2 1 1
1 1 1 2 2
8Ø@6" C/C Spacing 8Ø@6" C/C Spacing 8Ø@6" C/C Spacing 2-16∅(th)-1-12∅(Th)+1-12∅(ex)
2-16Ø(th)+1-12∅(th)

5"

5"
10' - 0"

9"

9"
8Ø@5"C/C Spacing 8Ø@5"C/C Spacing 8Ø@5"C/C Spacing
8Ø@5"C/C Spacing 8Ø@5"C/C Spacing 8Ø@5"C/C
1 Spacing
1 1 2 1 1 2 1 1 2 1 2 1 9" 9"
2-16Ø(th)+1-12∅(th) 2-16∅(th)-1-12∅(Th)+1-12∅(ex) Project Name: 3 Storey
1st F
13' - 0" SECTION-1-1
SECTION-2-2 Commercial
1 1 2
1 1 2 1 1 2 1 2 1 1 Building Design
8Ø@6" C/C Spacing
8Ø@6" C/C Spacing 8Ø@6" C/C Spacing

Location: Dhangadhi-02
10' - 0"

2-16∅(th)-1-12∅(Th)+1-12∅(ex)
2-16Ø(th)+1-12∅(th)
Drawn By: Dilli Raj Phulara

Checked Er. Surendra Bam

5"

5"
8Ø@5"C/C Spacing 8Ø@5"C/C Spacing
8Ø@5"C/C Spacing 8Ø@5"C/C Spacing 8Ø@5"C/C Spacing
B B B
8Ø@5"C/C Spacing
B B
8Ø@5"C/C Spacing By: NEC 17353 Civil"A"
B B B B B
B B
Plinth

9"

9"
3' - 0"
3' - 0"

B B B B B B B B B B
B B 9" 9"
8Ø@6" C/C Spacing 8Ø@6" C/C Spacing 2-16Ø(th)+1-12∅(th) 2-16∅(th)-1-12∅(Th)+1-12∅(ex) Client's Name: Batu Devi Khadka
8Ø@6" C/C Spacing
8Ø@6" C/C Spacing Ground Lvl
8Ø@5"C/C Spacing 8Ø@5"C/C Spacing SECTION-2-2
8Ø@5"C/C Spacing 8Ø@5"C/C Spacing 8Ø@5"C/C Spacing
8Ø@5"C/C Spacing
8Ø@5"C/C Spacing
0' - 0" SECTION-1-1
B B B B B B B B B B
B B
Plot no:7 Plot area:420.50 sq.m
5' - 0"

B B B B B B B B B B
B B

8Ø@6" C/C Spacing


8Ø@6" C/C Spacing
8Ø@6" C/C Spacing
8Ø@6" C/C Spacing
Active & Innovative
Footing Lvl Engineering Pvt. Ltd.
-5' - 0"
Dhangadhi submetro politian city-03
Clear cover 25mm (1") from Clear cover 25mm (1") from 7" Contact no: 9841080149
Beam Grid-1,2,3,4,5,6 main reinforcement bar of main reinforcement bar of
1 Beam. Beam. 3-12∅ TH
3/16" = 1'-0" 3-12∅ TH
Building Purpose: Commercial

3"
Beam Elevation grid 1,2,3

9"
12"
12"

3-12∅ TH 3-12∅ TH
Sheet No: S.4
8 mm Ø 2 8 mm Ø 2
legged stirrups legged
@ 4" c/c stirrups @ 4" c/c
DETAIL OF As indicated
9" 9" BEAM STIRRUPS
Scale:
Upper Tie Beam Lower Tie Beam
Official Use Only
3/wgLn] 3/ jl/kl/ j[Iff/f]k0f ug{ clgjfo{ 5 .

6 5 4 3 2 1

4th F
3' - 0" 12' - 2" 12' - 5" 7' - 0" 9' - 2" 11' - 5" 41' - 0"

8mm@5"c/c spacing

8mm@5"c/c spacing 8mm@5"c/c spacing


8mm@5"c/c spacing 1 8mm@5"c/c spacing 8mm@5"c/c spacing
1 1 2 1 1 2 1 1 2 1 2 1

3rd F
33' - 0"
1
1 1 2 8mm@6"c/c spacing 1 1 2 8mm@6"c/c spacing 1 1 2 8mm@6"c/c spacing 1 2 8mm@6"c/c spacing
1 8mm@6"c/c spacing
10' - 0"

8mm@5"c/c spacing

8mm@5"c/c spacing 8mm@5"c/c spacing


1 1 2 1 1 2 1 8mm@5"c/c spacing
1 2 1 1 8mm@5"c/c spacing
2 1 8mm@5"c/c spacing

2ndF
23' - 0" Project Name: 3 Storey
1 1 2 8mm@6"c/c spacing 1 1 2 8mm@6"c/c spacing 1 1 2 1 spacing
8mm@6"c/c 1 2 1
8mm@6"c/c spacing 8mm@6"c/c spacing
Commercial
Building Design
10' - 0"

Location: Dhangadhi-02

8mm@5"c/c spacing Drawn By: Dilli Raj Phulara


8mm@5"c/c spacing 8mm@5"c/c spacing
8mm@5"c/c spacing 8mm@5"c/c spacing 8mm@5"c/c spacing
1 1 2 1 1 2 1 1 2 1 1 2 1
Checked Er. Surendra Bam
1st F
13' - 0" By: NEC 17353 Civil"A"
1 1 2 8mm@6"c/c spacing 1 1 2 8mm@6"c/c spacing 1 1 2 1 spacing
8mm@6"c/c 1 2 8mm@6"c/c spacing
1 8mm@6"c/c spacing

Client's Name: Batu Devi Khadka


10' - 0"

Plot no:7 Plot area:420.50 sq.m


8mm@5"c/c spacing

8mm@5"c/c spacing 8mm@5"c/c spacing

A A A A A A
8mm@5"c/c spacing
A A A A
8mm@5"c/c spacing
A A A A A
8mm@5"c/c spacing
Plinth Active & Innovative
3' - 0"
Engineering Pvt. Ltd.
3' - 0"

A A A A A A A A A A A A A A A
8mm@6"c/c spacing 8mm@6"c/c spacing 8mm@6"c/c spacing 8mm@6"c/c spacing 8mm@6"c/c spacing
8mm@5"c/c spacing
Ground Lvl Dhangadhi submetro politian city-03
8mm@5"c/c spacing 8mm@5"c/c spacing 0' - 0" Contact no: 9841080149
8mm@5"c/c spacing 8mm@5"c/c spacing 8mm@5"c/c spacing
B B B B B B B B B B B B B B B
5' - 0"

Building Purpose: Commercial


B B B B B B B B B B B B B B B
8mm@6"c/c spacing 8mm@6"c/c spacing 8mm@6"c/c spacing 8mm@6"c/c spacing 8mm@6"c/c spacing
Footing Lvl Beam Elevation grid A,B,C,D
-5' - 0"

Sheet No: S.5


Beam Grid-A,B,C,D,E
1
3/16" = 1'-0"
Scale: 3/16" = 1'-0"
Official Use Only
3/wgLn] 3/ jl/kl/ j[Iff/f]k0f ug{ clgjfo{ 5 .
6'-0"

5'-0"

8MM Ø STIRRUPS @ 4" C/C

8MM Ø STIRRUPS @ 4" C/C

4"
A
A

4"
A

6'-0"
A

12"
5'-0"
12"

4"
4"
4" 12" 4"
4" 12" 4"

12 MM Ø @ 6" C/C BOTHWAY

12 MM Ø @ 6" C/C BOTHWAY

FOUNDATION PLAN ( IF2)


SCALE= : 1"=4'-0"
FOUNDATION PLAN ( IF1)
SCALE= : 1"=4'-0"
Project Name: 3 Storey
1'-0"
Commercial
12" Building Design
P.L.
P.L. 6-12 MM Ø THROUGH OUT Location: Dhangadhi-02
6-12 MM Ø THROUGH OUT

2'-0"
2'-0"

8MM Ø STIRRUPS @ 6" C/C 8MM Ø STIRRUPS @ 6" C/C


Drawn By: Dilli Raj Phulara
G.L.
G.L.
Checked Er. Surendra Bam
6-12 MM Ø THROUGH OUT By: NEC 17353 Civil"A"
3'-1"

8MM Ø STIRRUPS @ 4" C/C


6-12 MM Ø THROUGH OUT
3'-1"
5'-0"

4" 4" 12 MM Ø @ 6" C/C BOTHWAY


8MM Ø STIRRUPS @ 4" C/C
Client's Name: Batu Devi Khadka
10"

5'-0"

1'-8" 1'-8" 4" 4" 12 MM Ø @ 6" C/C BOTHWAY


Plot no:7 Plot area:420.50 sq.m
8"
5"

10"

3" THICK P.C.C (1:3:6)


2" THICK ONE LAYER BRICK SOLING 1'-8" 1'-8" Active & Innovative
5'-0"
Engineering Pvt. Ltd.
8"

SECTION OF FOUNDATION &


5"

COLUMN Dhangadhi submetro politian city-03


3" THICK P.C.C (1:3:6)
Contact no: 9841080149
SECTION AT A-A OF
2" THICK ONE LAYER BRICK SOLING
IF2 SCALE= : 1"=2'-0" 6'-0" Building Purpose: Commercial
SECTION OF FOUNDATION &
Footing Details
COLUMN
SECTION AT A-A OF
Sheet No: S.6
IF1
SCALE= : 1"=2'-0"

Scale: 1/8" = 1'-0"


Official Use Only
3/wgLn] 3/ jl/kl/ j[Iff/f]k0f ug{ clgjfo{ 5 .
A B C D E
3' - 0" 8' - 0" 10' - 9" 10' - 9" 6' - 0" 3' - 0"

3' - 0"

3' - 0"
6

12' - 2"

12' - 2"
5
12' - 5"

12' - 5"
10Ø @6"c/c in bothways
4
Project Name: 3 Storey
7' - 0"

7' - 0"
Commercial
Building Design
3
Location: Dhangadhi-02
9' - 2"

9' - 2"
Drawn By: Dilli Raj Phulara

Checked Er. Surendra Bam


2 By: NEC 17353 Civil"A"
11' - 5"

11' - 5"
Client's Name: Batu Devi Khadka

Plot no:7 Plot area:420.50 sq.m


1
3' - 0" 8' - 0" 10' - 9" 10' - 9" 6' - 0" 3' - 0"
Active & Innovative
Engineering Pvt. Ltd.
Dhangadhi submetro politian city-03
Contact no: 9841080149
Slab Detailing Bottom
1
1/8" = 1'-0" Building Purpose: Commercial

Slab Detailing(Bottom)

Sheet No: S.7

Scale: 1/8" = 1'-0"


Official Use Only
3/wgLn] 3/ jl/kl/ j[Iff/f]k0f ug{ clgjfo{ 5 .
A B C D E
3' - 0" 8' - 0" 10' - 9" 10' - 9" 6' - 0" 3' - 0"

3' - 0"

6
12' - 2"

5
12' - 5"

8d @ 6"c/c spacing 8d @ 6"c/c spacing 8d @ 6"c/c spacing

8d @ 6"c/c spacing

4
3 Storey
7' - 0"

Project Name:
Commercial
Building Design
3
8d @ 6"c/c spacing Location: Dhangadhi-02
9' - 2"

Drawn By: Dilli Raj Phulara


8d @ 6"c/c spacing
Checked Er. Surendra Bam
2 By: NEC 17353 Civil"A"
11' - 5"

Client's Name: Batu Devi Khadka

Plot no:7 Plot area:420.50 sq.m


1
3' - 0" 8' - 0" 10' - 9" 10' - 9" 6' - 0" 3' - 0"
Active & Innovative
Slab Detailing Top
Engineering Pvt. Ltd.
1
1/8" = 1'-0" Dhangadhi submetro politian city-03
A B C D E Contact no: 9841080149

8' - 0" 10' - 9" 10' - 9" 6' - 0" Building Purpose: Commercial
8Ø @ 6"c/c Spacing(Top)
3' - 0" 2' - 8" 3' - 7" 3' - 7" 3' - 9" 2' - 0" 2' - 0" Slab Detailing(Top)
2' - 8" 3' - 7"
0' - 5"

0' - 9"

1st F Sheet No: S.8


8Ø @ 6"c/c Spacing(Bot)

0' - 9"
13' - 0"

Section XX Scale: As indicated


2
1/4" = 1'-0"
Official Use Only
3/wgLn] 3/ jl/kl/ j[Iff/f]k0f ug{ clgjfo{ 5 .

Column
Beam

0.30 L or Ld Ld MAIN BAR 8mm ∅ Bar


whichever spacing of
is greater
stirrups >/ 150
9"


min hich

80 m ho is g
8∅-6"c/c AT MID

(w
im eve
u
or ok r ea
10 le te
STIRRUP 8∅-4"c/c AT END

∅ ng r)

12"
0.30 L or Ld

r
Ld

th
whichever spacing of 2-16∅ +1-12∅TOP / BOT.
is greater stirrups >/ 150
TIE BEAM 9"X12"
END HOOKS OF STIRRUPS ARE
TYPICAL LAP LOCATION FOR BEAM BARS LOCATED ALTERNATELY AT
TOP

Varies as Site
CORNER BAR OF THE SECTION DETAIL A-135°HOOK DETAIL FOR

Condition
STIRRUPS & TIES

m
BRICK

in
m

.1
in. WORK
Beam

0
10



0∅
.1
in
m
0.25L or Ld GROUND
0.25L or Ld whichever is
whichever is greater LVL.
greater ∅

Column
HOOP,U-SHAPED STIRRUPS &
Column CROSS TIES 135° BENT
L

2'
3-12∅TOP . Project Name: 3 Storey
TYPICAL LOCATION FOR BEAM BARS
Commercial

12"
8∅-4"c/c AT END
8∅-6"c/c AT MID
3-12∅B. Building Design

See Detail - A
0.3L or ld
whichever is greater Ld
Location: Dhangadhi-02

3"
spacing of
stirrups >/150
P.C.C.
Brick
Soling

10" Drawn By: Dilli Raj Phulara


EXTRA LATERAL TIES
FOR 8 BARS
0.3L or ld
Ld
whichever is greater
Se TOE WALL SECTION Checked Er. Surendra Bam
e
TYPICAL LAP LOCATION FOR BEAM BARS
D
et
ai
By: NEC 17353 Civil"A"
l-
A
Ld

Ld 25 GAP BETWEEN BARS


Ld
Client's Name: Batu Devi Khadka
Ld
Ld

Ld LATERAL TIES FOR 4 BARS


SHAPE OF LATERAL TIES
FOR COLUMN

(SECTIONAL ELEVATION) (SECTIONAL ELEVATION)


Plot no:7 Plot area:420.50 sq.m
(ALT I)
MIN. 8MM ∅ LATERAL Lateral Tie
40
TYPICAL END DETAILS FOR BEAM REINFORCEMENT
40

2'-2"
Active & Innovative

75 inim len eve r)
m
m u gth r
m m
or h
(w gr

10 ook
hi ea


c h te

Secondary Beam
Engineering Pvt. Ltd.
is

2'-2"

DETAIL A
-135° HOOK DETAIL
Max
Dhangadhi submetro politian city-03
FOR STIRRUPS & Lateral Ties
60°

2"mm Ld Ld Contact no: 9841080149


SPACING 6" SPACING 6"
MAX. MAX.

Acc. Site condition


Building Purpose: Commercial
Ld+10Ø

CONNECTION DETAIL BETWEEN MAIN &


SPECIAL CONFINING

SECONDARY
BEAM Beam Details
LAPPING NOTES FOR
TIES

BEAM
LAP LENGTH SHALL NOT BE LESS THAN BAR DEVELOPMENT LENGTH IN
TENSION
NOT MORE THAN 50% OF THE BARS SHALL BE SPLICED AT ONE
SECTION.
LAP SPLICE SHALL NOT BE
PROVIDED:-
1. WITHIN A
Sheet No: S.9
JOINT
2. WITHIN A DISTANCE OF 2d FROM JOINT
FACE
3. WITHIN A QUARTER LINGTH OF THE
MEMBER

HOOK FOR BEAM BAR 1/8" = 1'-0"


SCALE=NTS
LAPING FOR BEAM BAR Scale:
Official Use Only
3/wgLn] 3/ jl/kl/ j[Iff/f]k0f ug{ clgjfo{ 5 .

FLOOR LINTEL BAND


BEAM
WALL

LINTEL BAND B
B
L

SILL A

WALL A
SILL BAND

FLOOR
BEAM

DETAIL OF NON STRUCTURAL WALL AT D-D DETAIL OF NON STRUCTURAL WALL AT D-D

2- 10 mm Dia. Project Name: 3 Storey


50 2- 10 mm Dia. TOP BAR
50 2- 10 mm Dia. 50 Commercial
Building Design
75

75

75
230 CHAIR Location: Dhangadhi-02
8 Dia. @ 150 mm c/c 230 230 BOTTOM BAR
8 Dia. @ 150 mm c/c 8 Dia. @ 150 mm c/c
X-SECTION OF SILL BAND AT A-A Drawn By: Dilli Raj Phulara
X-SECTION OF LINTEL BAND AT B-B
DETAIL AT L
Checked Er. Surendra Bam
Lintel Band Details CHAIR DETAIL By:
1 SCALE:1"=2'0" NEC 17353 Civil"A"
1/8" = 1'-0"
2"
Client's Name: Batu Devi Khadka

3 1/2"
3.
15
" 3"
3.15"
Plot no:7 Plot area:420.50 sq.m

8
M
M

C
H
A
I
R
R
E
S
T
I
N
G
O
N
S
L
A
B
F
O
R
M
W
O
R
K
Active & Innovative

O
P
T
I
O
N
-
I
I
Engineering Pvt. Ltd.
2"
STIRRUPS FOR COLUMN-C1 Dhangadhi submetro politian city-03

2 1/2"
Contact no: 9841080149
3"

8
M
M

C
H
A
I
R
Building Purpose: Commercial

R
E
S
T
I
N
G
 Clear cover 1.5" from the main
O
N
B
O
T
T
O
M
B
A
R
S
O
P
T
I
O
N
-
I
Sill and Lintel Band Details
reinforcement bar
 Concrete grade: M20 Chair Bar Sheet No: S.10
2
1/8" = 1'-0"
Scale: 1/8" = 1'-0"
Official Use Only
3/wgLn] 3/ jl/kl/ j[Iff/f]k0f ug{ clgjfo{ 5 .

GENERAL NOTES
1. Dimensions are to be read only and not
measured
2. Change in dimension are to be notified
3. The structural drawings shall be read in
conjuction with architectural drawings.
Discrepancies, if any shall be reported to
the site engineer
4. Contractor shall be responsible for
checking field dimensions and site
conditions

STRUCTURAL SPECIFICATION
A. FOUNDATION
 Foundation shall not rest on loose soil. If loose soil is encountered at design
 depth, the consultant shall be informed as soon as possible
Project Name: 3 Storey
B. CONCRETE MIX Commercial
Building Design
 Concrete mix for Columns, beams & Staircase shall be M20 [1:1.5:3]
 Concrete mix for Foundation and Slab shall be at minimum M20 [1:1.5:3] Location: Dhangadhi-02

C. CLEAR COVER Drawn By: Dilli Raj Phulara


 Clear Cover of Concrete is recommended as follows Checked Er. Surendra Bam
6.1 Slab 15mm
By: NEC 17353 Civil"A"
6.2 Staircase / RCC wall 20mm
6.3 Beam 25mm
6.4 Column 40mm
Client's Name: Batu Devi Khadka
6.5 Footing 50-75mm

D. LAP LENGTH./DEVELOPMENT LENGTH TO REINFORCEMENT Plot no:7 Plot area:420.50 sq.m


Dia [mm] Ld [mm - inches]
8 480 19"
10 600 24"
Active & Innovative
12 720 28" Engineering Pvt. Ltd.
16 960 38" Dhangadhi submetro politian city-03
20 1200 48" Contact no: 9841080149
25 1500 60"
E. OTHERS Building Purpose: Commercial
Provide Adequate cover blocks, Chairs, stools to keep reinforcement in
Column Details
position
Sheet No: S.11

Column Details
1 Scale: 1/8" = 1'-0"
1/8" = 1'-0"
Official Use Only
3/wgLn] 3/ jl/kl/ j[Iff/f]k0f ug{ clgjfo{ 5 .
2'-6"
12∅6"c/c
Chairs 2'-6
"
2-12∅

12"
2-10∅
10"
8∅ Vertical stirrups @ 6"
10∅@6"c/c 2'-6
" 7" c/c throughout

LANDING

6.94"
BEAM
5" Thick Slab 2'-6
"
WAST SLAB THICKNESS 5"

10∅@6"c/c 10∅@6"c/c

LANDING BEAM
REST ON WALL ONLY
12∅6"c/c
12mm ∅ nosing bar 10"

6.94"
8mm ∅ stirrups( nosing
stand)@6"c/c

TREAD = 11" TYP.NOSE BAR DETAIL


RISER = 7" FOR NOSING
LANDING WIDTH =3'-6"
12∅6"c/c
" Chairs
2'-6
Project Name: 3 Storey
11" 1
A B 1
Commercial
10∅@6"c/c Building Design
S.4 S.4
1
7"

Location: Dhangadhi-02
5" Thick Slab S.5
"
2'-6
WAST SLAB THICKNESS 5" Drawn By: Dilli Raj Phulara
3' - 6"
10∅@6"c/c 10∅@6"c/c Checked Er. Surendra Bam
LANDING BEAM 2 By: NEC 17353 Civil"A"

0' - 11"
REST ON WALL ONLY
2'-6"
12∅6"c/c
Client's Name: Batu Devi Khadka

Plot no:7 Plot area:420.50 sq.m

11' - 5"
Staircase Details
1 Active & Innovative
3/32" = 1'-0"
Engineering Pvt. Ltd.

3' - 5"
Dhangadhi submetro politian city-03
Contact no: 9841080149

1 Building Purpose: Commercial

Staircase Details
1' - 0" 7' - 0" 1' - 0"

1
Stair Plan Sheet No: S.12
2 S.5
1/4" = 1'-0"

Scale: As indicated
Official Use Only
3/wgLn] 3/ jl/kl/ j[Iff/f]k0f ug{ clgjfo{ 5 .

10'-6"
9'

9"
A A
1'x1'
OPENIN

6'-0"
1'x1'

3'
G
OPENIN IN WALL
G (BELOW TO DRAIN
IN WALL SLAB)
(BELOW EXCESS

9"
SLAB)
B TO
B
SEWER MANHOLE
9" 2' 9" 2'-9" 4" 2'-10" 4" 2'-9" 9"
AGE /DRAIN
2'-9" 10'-6" PIPE
INLET
PLAN OF SEPTIC TANK

HONEY COMB
∅5'-0" BRICK MASONARY
IN 1:6 CEMENT
MORTAR
PLAN OF SOAK PIT
Project Name: 3 Storey
SCALE: 1"=4'-0"
Commercial
Building Design

Location: Dhangadhi-02

Drawn By: Dilli Raj Phulara


REMOVABLE COVER 4" TH. RCC SLAB
4"
THICK Checked Er. Surendra Bam
G.L. G.L.
OUTLET PIPE RCC
WATER LVL. By: NEC 17353 Civil"A"
1'
1'-6"

SLAB
1'-0"

EXCESS
BRICK G.L. TO
MASONARY MANHOLE
EARTH COMPACTION EFFLUENT LVL.
3'-1"

IN 1:6 CEMENT /DRAIN


4" TH. RCC(1:2:4) BAFFLE WALL
6'

ONE LAYER BRICK SOLING


MORTAR Client's Name: Batu Devi Khadka
5'-6"

10'-6" BRICK
BALAST
3"

7'
3"

3mm TH. PUNNING PACKIN


20mm TH. PLASTER
SLOPE 1:40 SLOPE 1:40 G
9"
Plot no:7 Plot area:420.50 sq.m
1'

2"4"

HONEY COMB HONEY COMB

9" 1'-6" 6" 9" 2'-9" 4" 2'-10" 4" 2'-9" 9" 6"
BRICK
MASONARY
BRICK
MASONARY
Active & Innovative
IN 1:6 CEMENT IN 1:6 CEMENT
SECTION AT A-A MORTAR 9" 5' MORTAR Engineering Pvt. Ltd.
SECTION
SCALE: 1"=4'-0" AT B-B Dhangadhi submetro politian city-03
SCALE: 1"= Contact no: 9841080149
4'-0"
Building Purpose: Commercial

Septic Tank Details Septic Tank Details


1
1/8" = 1'-0"
Sheet No: S.13

Scale: 1/8" = 1'-0"