Professional Documents
Culture Documents
Air Cooled Condensing Unit Failure Report
Air Cooled Condensing Unit Failure Report
Objective:
To identify various causes of Failure of Bitzer Compressor installed in Gas Turbine / Steam Turbine
Building & Electrical Building
System Introduction
Gas Turbine and Steam Turbine Buildings each are provided with 6 Nos. of AHU’s (Air Handling Unit),
with Each AHU having its own Air Cooled Condensing Unit (ACCU) (compressor). The AHU draws fresh
Air from outside the building, Filters & cools it and provides it to the Building at a temperature of about
28 Degrees. The Building Consist of opening at the roof top from where Hot air escapes. Hence this
system works as an Open loop.
Normally Five AHU units are running while one Unit is available as a stand by. Also ACCU of the
respective AHU run based on the temperature set point of 28 Degree. Once the Building temperature
reaches the set point, the ACCU stops and starts back again if temperature increases by 1 Degree
HVAC in Electrical Building is divided into two Sections. Each Section Consist of having 2 AHU’s and Each
AHU has Two ACCU’s. The AHU draws Air from the Building as Return Air and from Outside the building
as Fresh Air. Hence this system works are a Close Loop system.
Failures Observed:
1|Page
Failure Analysis Report for ACCU Compressor Failure
On May 2015, 81SAM05AN002 compressor failed during warranty period (WD-869, WO#9054). Stator
winding was found burnt which led to tripping of the MCC feeder of ACCU. Stator rewinding and repair
was done.
2|Page
Failure Analysis Report for ACCU Compressor Failure
On October 2015, abnormal sound was observed from 70SAM03AN002 ACCU. EPC sent the
compressor for servicing and replacement of bearing under warranty (WD-942, WO#13258).
On March 2016, compressor for 05SAB02AN003 got tripped and motor IR was found low
(WO#17439). After checking, it was found that motor got burnt (due to short circuit) and some internal
mechanical damage was found. Servicing, stator rewinding and replacement of damaged components
were done.
On June 2016, 71SAM04AN002 ACCU was tripping frequently (WO#19529). Inspection was
carried out by authorized service center and some mechanical failures were found. Bearings, oil filter
and pressure relief valve were replaced and servicing was done.
On July 2016, 71SAM01AN002 was found tripping on low pressure fault and motor IR was found
low (WO#20593). Compressor was inspected and stator winding was found burnt. Expansion valve for
the AHU was also found damaged giving low pressure alarm for the unit. Stator was sent for rewinding
and repair and expansion valve was replaced.
System Observations:
During Peak Summer GT/ST Building HVAC System are not able to meet the set point and due to
which ACCU compressors are continuously running. Continuous operation of compressor will
lead heat up and mechanical and Electrical Damage. Return gas temp. must be 55 degree.
Temperature Element of Expansion valve not properly touching the return line. All Expansion
valves Temperature element has to be checked and aligned with the return line.
The ACCU compressors were operated as per O&M manual and as per manufacturer’s
recommendations. All the settings were kept as per design. Preventive maintenance is carried out as per
the manual. System has to be reviewed to determine the underlying root causes of such frequent
failures.
Action Plan
Overhauling of Six Compressor Per year to cover total 30 compressors in Five years time
Oil replacement of Compressor Once in two years.
3|Page
Failure Analysis Report for ACCU Compressor Failure
Train Manpower to enable opening of Screw Section of the Compressor which will enable Onsite
Repair works for Bearings.
All Condenser FAN pressure Switch / HP/LP pressure switch calibration to be done.
Discharge Gas Temperature Sensor for All Sensors to be Checked for calibration.
Antifreeze protection to be provided. Option of Outlet temperature sensor installation
Incase the ACCU Shutdown due to Flow Fault which may be due to any fault in the flow switch
or failure of AHU due to any reason, the ACCU is shutdown without pump down.
ACCU is tripping after tripping seconds which may be too long and there are chances of Liquid
entering the compressor and further electrical and mechanical damage.
Strategy For checking healthiness of the compressors during winter.
4|Page