You are on page 1of 2

4098 Smoke/Heat Base

Installation Instructions
Cautions and Warnings
DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED. Upon unpacking your Simplex product, inspect the contents of the
carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify Simplex.
ELECTRICAL HAZARD - Disconnect electrical power when making any internal adjustments or repairs. Servicing should be performed by qualified
Simplex Representatives.
STATIC HAZARD - Static electricity can damage components. Therefore, handle as follows:
1. Ground yourself before opening or installing components.
2. Keep uninstalled component wrapped in anti-static material at all times.
Introduction
The 4098 Smoke/Heat Bases are designed to be used with Simplex smoke and heat detectors, as well the QuickConnect2 photo sensor. The different smoke/heat base
configurations include the following:
• 4098-9788 2-Wire Base • 4-Wire Relay Base (4098-9682)
• Heat Base with LED Interface (4098-9684) • 2-Wire Relay Base (4098-9683)

Note: Refer to the 4098 Detectors, Sensors, and Bases Application Manual (574-709) that was shipped with the fire alarm system for compatibility data,
maintenance, and correct application of these Smoke/Heat Bases.

Installation

Cautions: Install the bases in this instruction in accordance with applicable NFPA standards, local codes, and the authorities having jurisdiction.
Failure to follow these instructions may result in failure of the detector or sensor to initiate an alarm condition. Simplex is not responsible for
detectors or sensors that have been improperly installed, tested, or maintained. Smoke detectors or sensors come with dust covers to protect
them from contamination during completion of building construction. Smoke detectors and sensors will not operate with dust covers in place.

Mounting

The bases mount to a 4-inch square, single-gang, or octagonal electrical box. Install the base using Figure 1 as a reference.

Note: The 2- and 4-wire relay bases and the Heat Base with LED Interface require an 1 ½-inch extension ring (not supplied) mounted to the 4-inch square or
octagonal electrical box (relay module(s) cannot be used in single-gang installations) to meet the space requirement of the relay cube and its wires. The relay
cube must be installed in the electrical box directly behind the base.
FLUSH MOUNTED
(BOX TO BE FLUSH OR RECESSED 1/4 " MAX )

SINGLE GANG (2 1/8" DEEP) 4" (10.16cm x 1 1/2" DEEP) 4" (10.16cm x 1 1/2" DEEP)
ELECTRICAL BOX OCTAGONAL SQUARE
(NOT SUPPLIED) ELECTRICAL BOX ELECTRICAL BOX
( NOT SUPPLIED) (NOT SUPPLIED)

DETECTOR
BASE

4098-9832
ADAPTER PLATE KIT
LOCK TAB (REQUIRED FOR 4"
SQUARE OR ANY SURFACE
(SEE NOTE 1) MOUNTED ELECTRICAL BOX)

BASE
# 8-32 x 1 1/2"
PANHEAD MACHINE
SCREW

SLOTTED HOLE
(TIGHTEN UNTIL SNUG,
1-3 in.-lbs.)
(SEE NOTE 3)
# 8-32 x 1 1/4" # 8 x 1" THREAD FORMING
PANHEAD MACHINE PANHEAD SCREW
# 6-32 SCREW
SCREW (TIGHTEN TO 4-6 in.-lbs.)
WITH WASHER
(TIGHTEN TO 4-6 in.-lbs.)
(NOT SUPPLIED)
Notes:

1. Break off plastic lock tab to engage locking mechanism. To lock detector/sensor into
base, turn unit until the locking tab clicks into place. To unlock detector/sensor, insert
the blade of a flat-head screwdriver into the slot located on the base and then pull down DETECTOR/SENSOR
DETECTOR
on handle. This action allows the detector/sensor to be turned and removed. (AS
SEE
(ASREQUIRED)
REQUIRED)
SEENOTES
NOTES11AND
AND22
2. Refer to the 4098 Detectors, Sensors, and Bases Application Manual (574-709) for
detailed information. CLOCKWISE
FOR ATTACHMENT
3. Use the slotted hole indicated for the first screw when mounting the base.

Figure 1. Typical Base Mounting

Wiring

All screw terminals accept 14- to 18-gauge AWG solid or stranded wire. Maximum torque should not exceed 12 inch-pounds. Do not loop wire under
terminals. Recommended strip length is 3/8 inch. Break wire runs to provide supervision. Figures 2, 3 and 4 illustrate the wiring connections for the different
base configurations.

SHIELD OPTIONAL
(SEE NOTE 2)

+IDNet +IDNet TO OTHER


FROM PANEL -IDNet -IDNet IDNet DEVICES
(SEE NOTE 1)

Notes:
1. Maximum quantity of devices per circuit
is 250 for the 4010 FACP.
2. Shield should be insulated from electrical
box.
4098-9788 4098-9788 3. 4098-9757 is ONLY compatible with
4010 FACP.

Figure 2. 4098-9788 Base for use with 4098-9757 QuickConnect2

 2001 Simplex Time Recorder Co., Westminster, MA 01441-0001 USA


 2001 Simplex International Time Equipment Co., Ltd., Mississauga, Ontario L4V 1H3 Canada 574-706
All specifications and other information shown were current as of publication, and are subject to change without notice.
Suffix “C” following an 8-digit Product ID number denotes ULC listed product.
Rev. E
Suffix “E” following an 8-digit Product ID number denotes Global product. The 2nd suffix identifies the market country, models with this suffix are not UL listed.

firealarmresources.com
PRIMARY 1
SEE NOTE 4

INITIATING BACKUP 2
CIRCUIT SEE NOTE 4
1

SEE NOTE 5

4098-9683 EOL
4098-9684 2-WIRE RESISTOR
SEE 4098-9788 SEE 4098-9788 HEAT DETECTOR RELAY BASE SEE NOTE 3
NOTE BASE NOTE BASE LED BASE SEE NOTE 2
7 7
INITIATING
CIRCUIT
2

LISTED
SIMPLEX
FIRE ALARM
CONTROL
PANEL
2120,
4001, 4002
4020, 4100+
4004, OR 4005

BLK RED

RED BRN REMOTE LED


BLK
4098-9830
BLK REMOTE LED SEE NOTE 1
RED BLK
4098-9830
SEE NOTE 1 VIO
REMOTE LED BLK N/C
RED RED
4098-9830 WHT BLU C
SEE NOTE 1 GRY
N/O AUX. RELAY CONTACTS
BLK YEL EACH RATED 1 AMP AT 28VDC /
N/C 0.5 AMPS AT 125VAC,
ORN RESISTIVE
C
BLK GRN
N/O
EOL
RESISTOR
SEE NOTE 3 RELAY MODULE
SEE NOTE 2

Figure 3. 4098-9788 Base, 4098-9683 2-Wire Relay Base, and 4098-9684 Heat Base with LED Interface

24VDC
EOL RELAY
2098-9735
OR
2098-9739

RED
+
RESETABLE REMOTE LED REMOTE LED BLK
-
POWER 4098-9830 4098-9830
SOURCE YEL
(SEE NOTE 1) (SEE NOTE 1)
24VDC
YEL

RED RED
+
INITIATING
CIRCUIT -

BLK BLK

EOL
RESISTOR
RED RED RED (SEE NOTE 3)

ORG ORG ORG ORG ORG ORG

LISTED GRN GRN GRN GRN GRN GRN


SIMPLEX
FIRE ALARM
CONTROL N/C VIO N/C VIO N/C VIO
SEE SEE SEE
PANEL BLU NOTE BLU NOTE BLU NOTE
N/O N/O N/O
2120, GRY 6 GRY 6 GRY 6
4001, 4002
4020, 4100+,
4004, OR 4005
BLK BLK BLK BLK BLK BLK

RELAY RELAY RELAY

Figure 4. 4098-9682 4-Wire Relay Base

Notes: 1. If used, remote LED (4098-9830) is polarized; observe color-coded wiring.


2. When using 2-wire relay base, wire only one relay base per initiating circuit. No other bases are installed on this circuit.
3. Refer to wiring diagrams provided with the system panel for proper end-of-line (EOL) resistor values.
4. It is recommended that the primary-1 and backup-2 lines be in separate wire runs and in compliance with local requirements.
5. For Style D (formerly Class A), initiating circuit, wire dotted lines and do not use EOL resistor. For Style B (formerly Class B), initiating
circuit, refer to wire diagrams provided with the system panel for proper EOL resistor value.
6. Auxiliary alarm contacts - Form C - each rated 3 amperes at 28VDC/115VAC, resistive.
7. Break wires before connecting to Terminal 4 to maintain supervision. Do not loop wire underneath Terminal 4.

574-706
Rev. E

firealarmresources.com