(C220D5 Shunt) PCC1302 Feature code list

Number Description Part Number Parameter Value


1 Current Transformer Setting 0326-7007 Genset Primary CT Current 975
Prime kVA rating (3 phase/ 50Hz) 200
2 KVA Rating A050F068
Standby kVA rating (3 phase/ 50Hz) 220
CODE-DES FEATURE PCC1302
3 0326-7029 Magnetic Pickup Enable Enable
(6C Application)
4 PPR(Flywheel teeth) 0326-7032 Teeth Pulses Per Revolution 138
6 Excitation type 0326-7213 Excitation Source Shunt
7 Phase 0326-6970 Single/3 Phase Connection Three Phase
8 Norminal Voltage 0326-6978 Genset Nominal Voltage 400
9 D/Y 0326-7011 Genset Delta/Wye Connection Wye
10 Application type 0326-6988 Application Rating Select Standby
11 HZ 0326-7038 Alternate Frequency Switch 50 Hz
12 PCC1302-AVR Enable 0326-6984 AVR Enable Enable
CODE-DES FEATURE PCC1302 -
13 ELECTRONIC GOVERNOR Electronic Governor Enable Enable
ENABLED 0326-7027
Fault Input #3 Fault Select Trim Shutdown
14 customer configure input 0326-7014
Configurable Input #3 Function Fault Input
Oil Pressure Sensor Type Sender
15 Oil pressure type 0326-7048
Oil Pressure Sender Type 2-Wire
16 RPM/HZ 0326-7042 Frequency to Speed Gain Select #1
17 Max Over Excitation Duty Cycle A045K270 Max Over Excitation Duty Cycle 56
LOP Shutdown Threshold 173
LOP Warning Threshold 193
HCT Shutdown Threshold 104
HCT Warning Threshold 100
Low Oil Pressure Idle Shutdown Threshold 83
18 Engine Protection No PN
Low Oil Pressure Idle warning Threshold 103
LOP shutdown Delay 10
LOP warning Delay 10
ECM Fault Code 1117 Enabled Disable
Nominal Battery Voltage 24V
Initial Crank Fueling Command 50
Initial Crank Fueling Period 2
Crank Fueling Ramp Rate 25
Maximum Crank Fueling 100
Crank Exit Fueling Command 50
Governor Enable Speed 1300
Governor Preload Offset 200
Governor Ramp Time 3
Dither Factor 15
Maximum Governor Duty Cycle 95
19 PCC1302-start & gain A058C703
Minimum Governor Duty Cycle 10
Starter Disconnect Speed 450
Charging Alternator Functions Disable Enable
24V Charging Alternator Voltage for Starter
26
Disconnect
Governor Gain Adjust 100
Gov K2 Gain Adjust 100
Gov K3 Gain Adjust 100
Gov D Gain Adjust 100
GK1 (50Hz) 1300

Page 1 of 5
GK2 (50Hz) 300
GK3 (50Hz) 28800
Governor Damping Effect (50Hz) 0.85
V/Hz Knee Frequency 1
V/Hz Rolloff Slop 5
Overspeed Shutdown Threshold 50Hz 1875
CODE-CONTROLLER PCC1302 (DIDO
20 PCC1302 calibration A055W189 COMMERCIAL CALIBRATION)
CODE-DES CONTROLLER HMI220(HMI220 OP
PANEL LOCAL W/O CB AND REMOTE-
21 HMI220 A029E523 ENGLISH,CHINESE)

(C175D5) PCC1302 Feature code list


Number Description Part Number Parameter Value

1 Current Transformer Setting 0326-6997 Genset Primary CT Current 400


Prime kVA rating (3 phase/ 50Hz) 160
2 KVA Rating No PN
Standby kVA rating (3 phase/ 50Hz) 175
CODE-DES FEATURE PCC1302 Inbuilt Rated In Auto False
4 A056H128
(6C Application) Magnetic Pickup Enable Enable
5 PPR(Flywheel teeth) 0326-7032 Teeth Pulses Per Revolution 138
6 Excitation type 0326-7213 Excitation Source Shunt
7 Phase 0326-6970 Single/3 Phase Connection Three Phase
8 Norminal Voltage 0326-6978 Genset Nominal Voltage 400
9 D/Y 0326-7011 Genset Delta/Wye Connection Wye
10 Application type 0326-6988 Application Rating Select Standby
11 HZ 0326-7038 Alternate Frequency Switch 50 Hz
12 PCC1302-AVR Enable 0326-6984 AVR Enable Enable
CODE-DES FEATURE PCC1302
13 - ELECTRONIC GOVERNOR Electronic Governor Enable Enable
ENABLED 0326-7027
14 Oil Pressure Sensor Type Sender
Oil pressure type 0326-7048
15 Oil Pressure Sender Type 2-Wire
16 RPM/HZ 0326-7042 Frequency to Speed Gain Select #1
Max Over Excitation Duty
17 A045K270 Max Over Excitation Duty Cycle 56
Cycle
LOP Shutdown Threshold 173
LOP Warning Threshold 193
HCT Shutdown Threshold 104
HCT Warning Threshold 100

Low Oil Pressure Idle Shutdown Threshold 83


18 Engine Protection No PN
Low Oil Pressure Idle warning Threshold 103

LOP shutdown Delay 10


LOP warning Delay 10
ECM Fault Code 1117 Enabled Disable
Nominal Battery Voltage 24V
Initial Crank Fueling Command 50
19 PCC1302-start & gain A058C703
Initial Crank Fueling Period 2
Page 2 of 5
Crank Fueling Ramp Rate 25
Maximum Crank Fueling 100
Crank Exit Fueling Command 50
Governor Enable Speed 1300
Governor Preload Offset 200
Governor Ramp Time 3
Dither Factor 15
Maximum Governor Duty Cycle 95
Minimum Governor Duty Cycle 10
Starter Disconnect Speed 450

Charging Alternator Functions Disable Enable

24V Charging Alternator Voltage for Starter


26
Disconnect
Governor Gain Adjust 100
Gov K2 Gain Adjust 100
Gov K3 Gain Adjust 100
Gov D Gain Adjust 100
GK1 (50Hz) 1300
GK2 (50Hz) 300
GK3 (50Hz) 28800
Governor Damping Effect (50Hz) 0.85
V/Hz Knee Frequency 1
V/Hz Rolloff Slop 5
Overspeed Shutdown Threshold 50Hz 1875
CODE-CONTROLLER PCC1302 (DIDO
20 PCC1302 calibration A055W189 COMMERCIAL CALIBRATION)
CODE-DES CONTROLLER HMI211(SERIES LCD
21 HMI211 0326-6810 CALIBRATION)

(C250D5) PCC1302 Feature code list


Numbe
Description Parameter Value
r Part Number

1 Current Transformer Setting 0326-7007 Genset Primary CT Current 975


Prime kVA rating (3 phase/ 50Hz) 228
Prime kVA rating (3 phase/ 60Hz) 281
2 KVA Rating 0326-7732
Standby kVA rating (3 phase/ 50Hz) 250
Standby kVA rating (3 phase/ 60Hz) 313
CODE-DES FEATURE PCC1302
3 0326-7029 Magnetic Pickup Enable Enable
(6C Application)
4 PPR(Flywheel teeth) 0326-7032 Teeth Pulses Per Revolution 138
6 Excitation type 0326-7213 Excitation Source Shunt
7 Phase 0326-6970 Single/3 Phase Connection Three Phase
8 Norminal Voltage 0326-6978 Genset Nominal Voltage 400
9 D/Y 0326-7011 Genset Delta/Wye Connection Wye
10 Application type 0326-6988 Application Rating Select Standby
11 HZ 0326-7038 Alternate Frequency Switch 50 Hz
12 PCC1302-AVR Enable 0326-6984 AVR Enable Enable
Page 3 of 5
CODE-DES FEATURE PCC1302
13 - ELECTRONIC GOVERNOR Electronic Governor Enable Enable
ENABLED
0326-7027
Fault Input #3 Fault Select Trim Shutdown
14 customer configure input 0326-7014
Configurable Input #3 Function Fault Input
Oil Pressure Sensor Type Sender
15 Oil pressure type 0326-7048
Oil Pressure Sender Type 2-Wire
16 RPM/HZ 0326-7042 Frequency to Speed Gain Select #1
Max Over Excitation Duty
17 A045K270 Max Over Excitation Duty Cycle 56
Cycle
LOP Shutdown Threshold 173
LOP Warning Threshold 193
HCT Shutdown Threshold 104
HCT Warning Threshold 100
Low Oil Pressure Idle Shutdown Threshold 83
18 Engine Protection No PN
Low Oil Pressure Idle warning Threshold 103
LOP shutdown Delay 10
LOP warning Delay 10
ECM Fault Code 1117 Enabled Disable
Nominal Battery Voltage 24V
Initial Crank Fueling Command 50
Initial Crank Fueling Period 2
Crank Fueling Ramp Rate 25
Maximum Crank Fueling 100
Crank Exit Fueling Command 50
Governor Enable Speed 1300
Governor Preload Offset 200
Governor Ramp Time 3
Dither Factor 15
Maximum Governor Duty Cycle 95
Minimum Governor Duty Cycle 10
Starter Disconnect Speed 450
Charging Alternator Functions Disable Enable
19 PCC1302-start & gain A058C703
24V Charging Alternator Voltage for Starter
26
Disconnect
Governor Gain Adjust 100
Gov K2 Gain Adjust 100
Gov K3 Gain Adjust 100
Gov D Gain Adjust 100
GK1 (50Hz) 1300
GK2 (50Hz) 300
GK3 (50Hz) 28800
Governor Damping Effect (50Hz) 0.85
V/Hz Knee Frequency 1
V/Hz Rolloff Slop 5
Overspeed Shutdown Threshold 50Hz 1875
CODE-CONTROLLER PCC1302 (DIDO
20 PCC1302 calibration A055W189 COMMERCIAL CALIBRATION)

Page 4 of 5
CODE-DES CONTROLLER HMI220(HMI220 OP
PANEL LOCAL W/O CB AND REMOTE-
21 HMI220 A029E523 ENGLISH,CHINESE)

Page 5 of 5