Comm’t
No.
OWNER COMMENTS CONTRACTOR RESPONSE
Inside the commissioning procedure, there is no
Organization chart/flow. The control power &
auxiliary power change over test, function test,
relay setting test can be given in Check list
format like these. Which helps to go through
during commission: