Professional Documents
Culture Documents
PROTECTION OF TRANSFORMERS
FLOPPY NO : TCE.M6-EL-FP-DOC-005
FILE NAME : M6-6508.DOC
REV.NO RO R1 ISSUE
CONTENTS
1.0 SCOPE 1
3.0 DISCUSSIONS 18
TABLES
APPENDIX
ISSUE
R1
ISSUE
R1
1.0 SCOPE
ISSUE
R1
TABLE – 1
ISSUE
R1
TABLE – 1 (cont’d)
ISSUE
R1
TABLE – 1 (cont’d)
ISSUE
R1
TABLE – 1 (cont’d)
SR. DESCRIPTION DEVICE DETAILS SETTING REMARKS
NO. NO. RANGE
1.8 Gas protection ‘63G’ Two stages buchholz For transformers
relay with one alarm protected by fuse, trip
stage and one stage without any
tripping stage. This is switching device
supplied along with cannot be used as
the transformer. tripping device is not
Each stage will available. Only alarm
actuate an auxiliary stage may be used.
relay with four pairs
of self reset contacts
(Alarm) or Hand
reset contacts (Trip)
1.9 Transformer oil ‘OTI’ Oil temperature These are optional
temperature trip indicators are usually items depending on
provided with two transfomer rating and
contacts, one for applications
alarm on “Oil
temperature high”
and other for trip on
“Oil temperature very
high”
1.10 Transformer WTI Winding temp.
winding indicators are - DO -
temperature trip provided with two
stages, one for alarm
on ‘winding temp.
high’ and the other
for trip on ‘winding
temperature very
high’
1.11 Oil pressure trip PRD Pressure relief This will be provided
device supplied with for transformers above
the transformer shall 2500 kVA.
be provided with
auxiliary relay with
four pairs of hand
reset contacts for
tripping
NOTE: 1. Items 1.8, 1.9 & 1.11 are not applicable for dry type transformers.
ISSUE
R1
TABLE – 2
ISSUE
R1
TABLE – 2 (cont’d)
ISSUE
R1
TABLE – 2 (cont’d)
ISSUE
R1
TABLE – 3
(b) Adjustable
percentage bias
for through fault
stability
(c) Auxiliary CT on
both sides for
ratio matching
and
compensation for
line CT mismatch
ISSUE
R1
TABLE – 3 (cont’d)
SR. DESCRIPTION DEVICE DETAILS SETTING REMARKS
NO. NO. RANGE
3.3 Backup ‘51’ Same as item 1.2 Range 50-
overcurrent 200%
protection for
phase faults on
HV side
3.4 Instantaneous ‘50N’ Applicable only when Range 20-
ground fault HV is delta connected 80% for
protection on HV Same as item 1.3 effectively
side earthed
system
and 10-
40% for
system
with
ground
fault
currents
limited to
rated
current/
impedance
earthed
systems
3.5 Backup ground 51N Applicable for star Range 20-
fault protection connected HV 80% for
on HV side winding effectively
Same as item 1.4 earthed
system
and 10-
40% for
systems
with limited
ground
fault
current
3.6 Backup phase ‘51’ Same as item 1.5 Range 50-
overcurrent 200%
protection for
phase faults on
LV side
ISSUE
R1
TABLE – 3 (cont’d)
SR. DESCRIPTION DEVICE DETAILS SETTING REMARKS
NO. NO. RANGE
3.7 Backup ‘51N’ Same as item 2.7 Range 20-
overcurrent 80% for
protection for effectively
ground fault on earthed
LV side system
and 10-
40% for
system
with low
resistance
earthing
3.8 Restricted earth ‘64’ Same as item 2.8 10-40%
fault protection range
of LV side when
LV neutral is
grounded
through low
resistance
3.9 Standby earth ‘51SN’ Same as item 2.9 Relay time setting to
fault protection be co-ordinated with
of LV side when short time rating of
LV neutral is resistor
grounded
through low
resistance
3.10 Gas protection 63G Same as 1.8
3.11 Winding WTI Same as item 1.10
temperature trip
3.12 Transformer oil DTI Same as item 1.9
temperature trip
3.13 Oil pressure trip PRD Same as item 1.11
ISSUE
R1
TABLE – 4
ISSUE
R1
TABLE – 4 (cont’d)
ISSUE
R1
TABLE – 5
PROTECTION OF AUTO-TRANSFORMERS
If tertiary winding is
brought out for
loading, additional
bias from this side
also to be provided
5.2 Restricted E/F Alt:1 7CT method – Single
protection ‘64’ See fig.1 phase
All CT ratios should instantaneo
be identical us current
operated Specify value
relay. of stabilising
Alt-2 9CT method – Range 20- resistor taking
See fig.2 80% RCT into
All CT ratios should account
be equal. One CT is Three phase
required on each instantaneo
phase at neutral end us current
of common winding. operated
This alternative also relay
covers phase faults Range 20-
inside transformers 80%
5.3 Backup overcurrent 67/51- Protection shall be 3 relays –
protection for phase 50 provided on all one per
faults (Directional) phases. phase.
on HV side Directionalisation is Range 50-
required as power 200% for
flow can be both inverse
ways. Additional high current
set instantaneous unit element and
can be provided to 500-2000%
clear internal faults for high set
unit
ISSUE
R1
TABLE – 5 (cont’d)
ISSUE
R1
TABLE – 5 (cont’d)
ISSUE
R1
TABLE – 6
ISSUE
R1
3.0 DISCUSSIONS
3.1 Transformers below 500 kVA are generally used for distribution
systems and are usually protected by fuses. Hence this range of
power rating is not included in the recommendations. Appendix-1
gives such a typical system for general guidance. For particular
applications where H.V. circuit breakers are provided table I may
be followed. LV side of the transformers may have circuit breakers
or fuses. In case of fuses, LV backup overcurrent and ground fault
protections are not applicable.
ISSUE
R1
3.5 When two transformers are operated in parallel, and they are not
provided with differential protection, directional over current phase
and ground fault relaying mentioned in 3.4 should be provided for
selective isolation of faulty transformer (internal fault).
3.7 A common high speed, hand reset trip relay should be used for
simultaneous tripping of both HV and LV breakers whenever the
protections operate.
3.9 Winding temperature, alarm and trip, oil temperature alarm & trip
normally form part of transformer and are covered here for the sake
ISSUE
R1
ISSUE
R1
3.7 (a) Differential & restricted earth fault protection for star connected
windings can be combined for transformer upto 63 MVA or 132
kV. If earthing transformers are provided these can be included
in the REF scheme. Earthing transformer can also be covered
by the differential protection.
ISSUE
R1